Installation & Power Connections - Homepage | WEG & Power Connections Typical Control Connection...

2
Installation & Power Connections Typical Control Connection Refer to user guide chapter 3. PROG DEF User Description P0220 2 1 Local/Remote = always remote P0222 1 1 Remote reference = Al1 P0226 4 4 FWD/REV = DIx P0227 1 1 Start/Stop remote = DIx P0231 0 0 AI1 = speed reference P0233 0 0 AI1 = 0 - 10 V P0263 1 1 DI1 = run/stop P0264 8 8 DI2 = FWD/REV Example 1: 2 - Wire Start/Stop, Speed Potentiometer CFW500-IOS (standard) Digital input 1 DI 1 1 3 5 7 9 2 4 6 8 START/STOP OFF ON Speed potentiometer FWD/REV DI 2 DI 3 DI 4 +24 V dc AO1 GND AI 1 +10 V dc Digital input 2 Digital input 3 Digital input 4 24 V dc power supply (150 mA) Analog output 1 Reference 0 V Reference + 10 V dc potentiometer Analog input 1 Top connection Bottom connection OFF ON DIP SWITCH 1 V mA AI1 Example 2: 3 - Wire Start/Stop, 4 - 20 mA Reference PROG DEF User Description P0220 2 1 Local/Remote = always remote P0222 1 1 Remote reference = Al1 P0227 1 1 Run/Stop remote = DIx P0231 0 0 AI1 = speed reference P0233 0 1 AI1 = 4 - 20 mA P0263 1 6 DI1 = start P0264 8 7 DI2 = stop Digital input 1 DI 1 1 3 5 7 9 2 4 6 8 DI 2 DI 3 DI 4 +24 V dc AO1 GND AI 1 +10 V dc START STOP 4 - 20 mA Reference Digital input 2 Digital input 3 Digital input 4 24 V dc power supply (150 mA) Analog output 1 Reference 0 V Reference + 10 V dc potentiometer Analog input 1 CFW500-IOS (standard) Top connection Bottom connection DIP SWITCH 1 V mA AI1 Example 3: 2 - Wire Start/Stop, Multispeed (4 Speeds) Digital input 1 Top connection Bottom connection DI 1 1 3 5 7 9 2 4 6 8 DIP SWITCHES (Not applicable) START/STOP SPEED SPEED DI 2 DI 3 DI 4 +24 V dc AO1 GND AI 1 +10 V dc Digital input 2 Digital input 3 Digital input 4 24 V dc power supply (150 mA) Analog output 1 Reference 0 V Reference + 10 V dc potentiometer Analog input 1 CFW500-IOS (standard) OFF ON OFF ON OFF ON PROG DEF User Description P0220 0 1 Local/Remote = always remote P0222 2 8 Remote reference = multispeed P0227 3 1 Start/Stop remote = DIx P0263 1 1 DI1 = start/stop P0265 0 13 DI3 = multispeed P0266 0 13 DI4 = multispeed P0124 3 Speed = (DI3 = open and DI4 = open) P0125 10 Speed = (DI3 = open and DI4 = closed) P0126 20 Speed = (DI3 = closed and DI4 = open) P0127 30 Speed = (DI3 = closed and DI4 = closed) Note: Speed setting depends on application. Relay Output PROG DEF User Description P0275 13 11 Run 12 Ready 13 No fault 26 With fault 11 DO1-RL-NO Normally open Top connection Normally closed Common DO1-RL-C DO1-RL-NC 13 15 NO NC Note: for more advance functions, please refer to the the programming manual. Programming CFW500 Keypad Menu/Enter button: - Enter programming mode - Use to Select/Save Run button: - Run in local mode Stop button: - Stop in local mode - Reset Up/Down buttons: - Adjust speed in local mode - Navigate through parameters Back/ESC button: - Return to monitoring mode - Return to previous programming level PROG User Description P0156 1.1xP0401 Overload current at 100% speed P0157 1.0xP0401 Overload current at 50% speed P0158 0.8xP0401 Overload current at 5% speed Motor Overload Settings - MOTOR Group PROG DEF Description P0100 10s Acceleration time (s) P0101 10s Deceleration time (s) P0133 3 Hz Minimum speed (Hz) P0134 66 Hz Maximum speed (Hz) Basic Application - BASIC Group Oriented Start Up - STARTUP Group (Scalar - V/F Mode) Note: set P0202 = 5 during oriented start-up for improved speed control and higher torque capacity at low speed (especially < 5 Hz). Set as per motor nameplate data. PROG DEF User Description P0202 0 0 Control type V/F P0401 - Motor FLC (A) P0402 1710 Motor speed (RPM) P0403 60 Motor frequency PROG DEF User Description P0204 0 5 Load factory defaults (60 Hz) Loading Factory Default Setting Note: for more advance functions, please refer to the programming manual (chapter 5.3). Main display P0205 Secondary display P0206 PROG DEF User Description P0205 P0206 P0205 = 2 P0206 = 1 1 Speed reference (RPM) 2 Output speed (RPM) 3 Motor current (A) 5 Output frequency (Hz) 7 Output voltage (V) 9 Motor torque (%) Changing Monitor Display Parameter

Transcript of Installation & Power Connections - Homepage | WEG & Power Connections Typical Control Connection...

Page 1: Installation & Power Connections - Homepage | WEG & Power Connections Typical Control Connection Refer to user guide chapter 3. PROG DEF UserDescription P0220 2 1 Local/Remote = always

Installation & Power Connections

Typical Control Connection

Refer to user guide chapter 3.

PROG DEF User Description

P0220 2 1 Local/Remote = always remote

P0222 1 1 Remote reference = Al1

P0226 4 4 FWD/REV = DIx

P0227 1 1 Start/Stop remote = DIx

P0231 0 0 AI1 = speed reference

P0233 0 0 AI1 = 0 - 10 V

P0263 1 1 DI1 = run/stop

P0264 8 8 DI2 = FWD/REV

Example 1: 2 - Wire Start/Stop, Speed Potentiometer

CFW

500-IOS

(standard)

Digital input 1DI 11

3

5

7

9

2

4

6

8

START/STOPOFF ON

Speedpotentiometer

FWD/REV DI 2

DI 3

DI 4

+24 V dc

AO1

GND

AI 1

+10 V dc

Digital input 2

Digital input 3

Digital input 4

24 V dc power supply (150 mA)

Analog output 1

Reference 0 V

Reference + 10 V dc potentiometer

Analog input 1

Topconnection

Bottom

connection

OFF ON

DIP SWITCH 1

V mAAI1

Example 2: 3 - Wire Start/Stop, 4 - 20 mA Reference

PROG DEF User Description

P0220 2 1 Local/Remote = always remote

P0222 1 1 Remote reference = Al1

P0227 1 1 Run/Stop remote = DIx

P0231 0 0 AI1 = speed reference

P0233 0 1 AI1 = 4 - 20 mA

P0263 1 6 DI1 = start

P0264 8 7 DI2 = stop

Digital input 1DI 11

3

5

7

9

2

4

6

8

DI 2

DI 3

DI 4

+24 V dc

AO1

GND

AI 1

+10 V dc

START

STOP

4 - 20 mAReference

Digital input 2

Digital input 3

Digital input 4

24 V dc power supply (150 mA)

Analog output 1

Reference 0 V

Reference + 10 V dc potentiometer

Analog input 1

CFW

500-IOS

(standard)

Topconnection

Bottom

connection

DIP SWITCH 1

V mAAI1

Example 3: 2 - Wire Start/Stop, Multispeed (4 Speeds)

Digital input 1

Topconnection

Bottom

connection

DI 11

3

5

7

9

2

4

6

8

DIP SWITCHES(Not applicable)

START/STOP

SPEED

SPEED

DI 2

DI 3

DI 4

+24 V dc

AO1

GND

AI 1

+10 V dc

Digital input 2

Digital input 3

Digital input 4

24 V dc power supply (150 mA)

Analog output 1

Reference 0 V

Reference + 10 V dc potentiometer

Analog input 1

CFW

500-IOS

(standard)

OFF ON

OFF ON

OFF ON

PROG DEF User Description

P0220 0 1 Local/Remote = always remote

P0222 2 8 Remote reference = multispeed

P0227 3 1 Start/Stop remote = DIx

P0263 1 1 DI1 = start/stop

P0265 0 13 DI3 = multispeed

P0266 0 13 DI4 = multispeed

P0124 3 ▲ Speed = ▲ (DI3 = open and DI4 = open)

P0125 10 ▲ Speed = ▲ (DI3 = open and DI4 = closed)

P0126 20 ▲ Speed = ▲ (DI3 = closed and DI4 = open)

P0127 30 ▲ Speed = ▲ (DI3 = closed and DI4 = closed)

Note: ▲ Speed setting depends on application.

Relay OutputPROG DEF User Description

P0275 13

11 Run

12 Ready13 No fault26 With fault

11 DO1-RL-NO Normally open

Top connectionNormally closed

CommonDO1-RL-C

DO1-RL-NC

13

15

NO

NC

Note: for more advance functions, please refer to the the programming manual.

Programming

CFW500 Keypad

Menu/Enter button: - Enter programming mode - Use to Select/Save

Run button: - Run in local mode

Stop button: - Stop in local mode - Reset

Up/Down buttons: - Adjust speed in local mode - Navigate through parameters

Back/ESC button: - Return to monitoring mode - Return to previous programming level

PROG User Description

P0156 1.1xP0401 Overload current at 100% speed

P0157 1.0xP0401 Overload current at 50% speedP0158 0.8xP0401 Overload current at 5% speed

Motor Overload Settings - MOTOR Group

PROG DEF Description

P0100 10s Acceleration time (s)P0101 10s Deceleration time (s)P0133 3 Hz Minimum speed (Hz)P0134 66 Hz Maximum speed (Hz)

Basic Application - BASIC Group

Oriented Start Up - STARTUP Group (Scalar - V/F Mode)

Note: set P0202 = 5 during oriented start-up for improved speed control and higher torque capacity at low speed (especially < 5 Hz). ■ Set as per motor nameplate data.

PROG DEF User Description

P0202 0 0 Control type V/FP0401 - ■ Motor FLC (A)P0402 1710 ■ Motor speed (RPM)P0403 60 ■ Motor frequency

PROG DEF User Description

P0204 0 5 Load factory defaults (60 Hz)

Loading Factory Default Setting

Note: for more advance functions, please refer to the programming manual (chapter 5.3).

Main display P0205

Secondarydisplay P0206

PROG DEF User Description

P0205P0206

P0205 = 2P0206 = 1

1 Speed reference (RPM)

2 Output speed (RPM)

3 Motor current (A)

5 Output frequency (Hz)

7 Output voltage (V)

9 Motor torque (%)

Changing Monitor Display Parameter

Page 2: Installation & Power Connections - Homepage | WEG & Power Connections Typical Control Connection Refer to user guide chapter 3. PROG DEF UserDescription P0220 2 1 Local/Remote = always

Quick Setup Guide

CFW500Machinery Drives

Motors | Automation | Energy | Transmission & Distribution | Coatings

J Centrifugal pumps J Process dosing pumps J Fans/ventilators J Blenders/mixers J Compressors

Cod

: xxx

x | R

ev: 0

0 | D

ate

(m/y

): 06

/201

4Th

e va

lues

sho

wn

are

sub

ject

to c

hang

e w

ithou

t prio

r no

tice.