  • MODEL 1001B TYPE Y OR ZPRESSURIZATION SYSTEM

    PROCESS AUTOMATION

    INSTALLATION AND OPERATION MANUAL

  • Model 1001B Installation and Operation Manual

    2

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Table of Contents

    Page 2 System Purpose and Description Purpose,Systemdescription,Importantnotes

    Page 3 Identifying Your System Definesspecificfeaturesofthesystem

    Page 3 General Information System&materialspecifications,System

    accessories,Spareparts,tools&testequipment,Maintenanceprocedures

    Page 4 Enclosure and Device Design Designrequirements,Adjacentenclosures,Deviceventilation,Temperaturelimitations

    Page 5 Installation Overview Installationdiagram

    Page 6 Getting Started Establishingconnectionsizes,Determiningenclosure

    inlet&outletconnectionlocations

    Page 7 System Mounting LH,RH,TM,BM&WMconfigurations,

    FM&PMconfigurations

    Page 8 Hardware Mounting Optionalenclosureprotectionvent,Warning

    nameplates

    Page 9 Mounting Plate Dimensions Mountingplatedimensiondiagrams

    Page 11 Pneumatic Tubing Requirements Protectivegassupplyrequirements,Pneumatic

    connectionrequirements

    Page 12 Tubing Installation LH,RH,TM,BM,WM,FM&PMtubing

    configurations

    Page 13 Tubing Connection Diagrams LH,RH,TM,BM,WM,FM,&PMconfiguration

    connectionpoints,Pneumaticdiagram

    Page 14 Electrical Supply Requirements Wiringrequirements,Enclosurepower&alarmsignal,

    Enclosurewiringmethods&connections

    Page 15 Conduit Installation Electrical&WPSstyleconduitandconnectionparts

    Page 16 Set-Up & Operating Procedures ClassIIset-upandoperation

    Page 17 Troubleshooting Procedures Troubleshootingchart

    Page 18 Warranty and Liability Statement Warrantynotes,Generalterms,Limitations

    Page 19 Customer Notes

    Page 22 System Maintenance Regularmaintenance,Long-termmaintenance,

    Maintenanceschedule

    Page 23 Systems identification & application information

    Purpose and Description

    PurposePepperl+Fuchs'BebcoEPSSystemallowstheuseofgeneral-purposeornonratedelectricalorelectronicdevices,withexceptiontodevicesthatproduceexcessiveheat,utilizecombustiblegas,orexposearcingcontactstothehazardousatmosphere,inNEMA(NationalElectricalManufacturersAssociation)4or12enclosuresintheplaceofexplosionproofNEMA7enclosures.Otherpurposesincludeheat,moistureanddustcontaminationprevention.

    DescriptionModel1001Bisanenclosurepressurizationsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosurestopreventcombustibledustaccumulation.InClassIIareas,thesystemmaintainsasafe(1.0")pressure.Thisprocessreducesthehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4

    Important NotesOne(1)permanentfilecopyandone(1)operationscopyofthismanualmustbestudiedandretainedbytheoperatorofthissystem.Usersagentsareresponsiblefortransferringthismanualtotheuser,priortostart-up.

    Thecontentsofthismanualhavebeenarrangedtoallowtheuseofthisproductasastand-alonedeviceonequipmentandenclosuressuppliedbytheuseroritsagents.ThemanualsparametersencompassacombinationofbothNationalFireProtectionAssociation(NFPA)requirementsandPepperl+Fuchs,Inc.requirements.Pepperl+FuchsthereforeacknowledgestheuseofNFPA496asaguideline,thatwehaveenhancedcertainNFPArequirementsandthatadditionalinformationhasbeencompiledtocompletethisdocument.Themanualisintendedasacompleteguideandmustbeconsidered,unlessspecificallystatedotherwise,thatalldirectivescontainedhereinarerequirementsforsafe,practicalandefficientuseofthisproduct.

    Thissystemisnotintendedforusetoprotectenclosuresordevicesthatcontainignitableconcentrationsofgasesorvapors.Thisexclusiongenerallyappliestoprocessorproductanalyzingsystemsequipment.

    All specifications are subject to change without notice.

  • Model 1001B Installation and Operation Manual

    3

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Identifying Your System

    Thisenclosureprotectionsystemisofferedinvariousstyles.Forproperinstallationandoperation,examinethesystemmodelnumbernameplatetoidentifythesystemstyle,areaclassification,andtype,asnotedbelow.

    General Information

    System SpecificationsSystemdimensions: Seepages9&10Shippingweight(lbs.): LPS-7,WPS-12Operatingtemp.range: -20Fto+120FSupplypressurerange: *5-120psimax.

    Whenusingtheoptionalinlinefilter,max.supplypressureis80psiSupplyrequirements: CleanairorinertgasSafepressuresetpoint: 1.0"Safepressureflowrate: **0.1-3.5SCFHSystemsupplyfitting: 3/8"tubefittingEnclosuresupplyfitting: 3/8"tubefittingEnclosurereferencefitting: 1/4"tubefittingSwitchsetting(decr,) 0.5"+.02"Switchconduitportsize: 1/2"FPTSwitchcontactrating: 120VAC,15Amps

    * WithEPV-3Vent-120psimax.to5psiminimum.SystemsinstalledwithoutEPV-3mustbeequippedwithredundantregulatorsetto5psimaximum

    **Enclosureintegritydeterminesactualflowrate

    Material SpecificationsRegulatorbody: Zincw/enamelfinishRegulatorhandle: PolycarbonateEnclosurepressuregauge: Aluminumw/enamelfinishTubefittings: 316SSforgedbodyTubing: 316SS1/4".035weldedSystemnameplates: SilkscreenedLexan&SSFastenerhardware: Aluminum&stainlesssteelMountingplate: 31614ga#3brushSSEXPpressureswitchbody: Anodizedcastalum.Enclosurewarningnameplate: SilkscreenedSS

    LexanisaregisteredtrademarkoftheGeneralElectricCorporation

    Model 1001B System AccessoriesOptional Enclosure Protection VentsEPV-3-SA-00 Straightw/sparkarrestorEPV-3-SA-90 Rtanglew/sparkarrestor

    Additional ItemsSMK-1,-4or-6 SystemmountingkitEPSK-2 ClassII,explosionproofswitchkitGPSK-2 ClassII,generalpurposeswitchkitRAH Div.1remotealarmhornRAB-1 Div.1remotealarmbeaconRAB-2 Div.2remotealarmbeaconLCK LfittingconduitkitTCK TfittingconduitkitTR-10G Tamper-proofregulatorw/gaugeEFC-4 1/4"flushconnectorEFC-6 3/8"flushconnectorEBC-6 3/8"bulkheadconnectorEPC-13 1"pipeconnectorILF-6 3/8"filterw/clearbowlETW Enclosuretemperaturewarning

    Recommended Spare PartsQty Description Part#(supercedes)1 Enclosurepressureindicator-CII 513235(001027)1 Enclosurepressurecontrolregulator 513236(002050)1 Installation&operationmanual 129-02011 EXPenclpressurelossalarmswitch-CII 513242(001082)1 Enclosurewarningnameplate-CII 513009(EWN-2)

    Pleasecallandreferencetheabovepartnumberforcurrentsparepartspricing.Immediatepricingisavailabletoallconfirmedcustomers.

    Installation Tools & Testing Equipment1/2"chuckdrill

    Completesetofdrillbits

    1.25"conduitknockoutpunchor1.75"holesaw

    Completesetoftubing,conduitbending,instrumentfittingandelectricalcraftsmanhandtools

    0-250scfhflowmeter(connectedupstreamoftheprotectionsystemtodetermineairconsumptionandflowduringset-upprocedure)

    1001B - LPS - CII - YZ - LH - ##

    Series Model NumberSystem Style

    LPS - less pressure switchWPS- with pressure switch

    Area ClassificationCII - Class II Area

    System TypeYZ - Div. 1 to Div. 2, Div. 2 to Nonhazardous

    Mounting ConfigurationLH - left hand left side of enclosureRH - right hand right side of enclosureTM - top mount top of enclosureBM - bottom mount bottom of enclosureWM - wall mount wall surfaceFM - frame mount external frame or rackPM - panel mount enclosure surface cutout

    (Not available in WPS Style)## - Additional factory installed accessories

    APPROVED BY FM APPROVALS AS ASSOCIATED TYPE Y & Z PRESSURIZATION CONTROL

    EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA

    OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER 1001B-IOM.

    REDUCES INTERNAL AREA CLASSIFICATION AS FOLLOWS:TYPE Y: CL. II, DIV. 1, GR. E, F & G TO CL. II DIV. 2

    TYPE Z: CL. II, DIV. 2, GR. E, TO NONHAZARDOUSF & G

    Model 1001B-WPS-CII Type Y or ZC

    LASSIFIED

    PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS IN ACCORDANCE WITH THE NATIONAL FIRE

    PROTECTION ASSOCIATION STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL

    EQUIPMENT NFPA 496-1996 4S11

    50 CUBIC FEET MAXIMUM ENCLOSURE VOLUME

  • Model 1001B Installation and Operation Manual

    4

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Maintenance ProceduresRegular Maintenance Procedure

    Draintheprotectionsystemfilterfrequently(ifequippedwithaModelILFKin-linefilterkit)andcleansystemwithnonsolventcleaningagentsonly,suchassoapandwater.

    Long-Term Maintenance Procedures

    Calibratetheenclosurepressureindicatorto0inchesbyventingthepurgepressurereferenceportandtheprotectedenclosuretoatmosphereandadjustingthecalibrationscrewinthelowercenterportionoftheindicatorsface.

    Ifventisutilized,fullyopentheenclosurepressurecontrolregulator,toblowoutanydepositsaroundthetipoftheregulatorandtoensurethattheenclosureprotectionventisoperatingproperly,thencarefullyreadjustsystemaccordingtotheset-upandoperatingproceduresonpage16.Replaceortightenstempackingnutasrequiredtoprohibitstempackingleakage.

    Carefullydisassembletheenclosureprotectionventbylooseningthetwobottomhexnutsthatholdtheunittogether.

    (DO NOT REMOVE CAP NUTS ON TOP OF VENT BODY)

    Carefullycleantheflappervalveandventbodyseatswithwarmsoapandwater,beingcarefulnottoextendtheventvalvebeyonditsnormalopeningpoint,andbeingcarefulnottoexertanystressonthevalvehinge.

    Examinetheentireprotectionsystemandtheprotectedenclosure(s),andreplaceanydefectivepartsduringroutineshutdownoftheprotectedenclosure(s).PartsareavailablefromPepperl+Fuchsonimmediatenoticeasrequired.

    Enclosure & Device Design

    Enclosure Design Requirements1. Allwindowsmustbeshatterproofandsizedassmallas

    possible.

    2. AllNFPA496requiredmarkingsmustbeplacedonornearallenclosuredoorsandcovers.

    3. Theenclosuremustwithstandaninternalpressureoften(10)inchesofwaterwithoutsustainingpermanentdeformationandresistallcorrosiveelementsinthesurroundingatmosphere.

    4. Alllightweightobjectsintheenclosure,suchaspaperorinsulation,mustbefirmlysecured.

    5. TheenclosureshouldbeconstructedfrommaterialssuchasmetalornonstaticpolycarbonatetomeetorexceedNEMA4or12performancerequirements,butdoesnotrequirethirdpartyapproval.

    6. Theinstallationofobstructionsorotherbarriersthatblockorimpedetheflowofprotectivegasmustbeavoided.

    7. Thecreationofairpocketsorotherareasthattrapflammablegaseswithintheenclosureordevicesmustbeavoided.

    8. Theenclosureshouldbelocatedinanareawhereimpacthazardsareminimal.

    9. Iftheenclosureisnonmetallicandcontainsequipmentthatutilizesorswitchespowerloadsgreaterthan2500VA,itmustbeconstructedfromsubstantiallynoncombustiblematerials,suchasmaterialsdesignedtomeetorexceedANSI/UL94ratingsof94V-0or945V.

    Adjacent Enclosures1. Adjacentenclosuresmustbeprotectedbyoneofthe

    followingmeans:

    a) purgedorpressurizedinserieswiththeprotectedenclosure

    b) purgedorpressurizedseparatelyor

    c) protectedbyothermeans;e.g.,explosionproofenclosures,hermeticallysealeddevicesorintrinsicsafecircuits

    2. Adjacentpurgedorpressurizedenclosuresmustbedesignedtomeetallconstructionrequirementsabove.

    Total Volume Calculation1. Thetotalvolumeofallpressurizedenclosures,devicesand

    wirewaysmustbeconsidered.

    2. Allenclosure,device,andwirewayvolumesmustbecalculatedwithoutconsiderationofinternallyconsumedspace.

    Device Ventilation1. Encloseddeviceswithintheprotectedenclosurewhichdo

    notexceed1.22in3offreevolumedonotrequireventilationtotheprotectedenclosure.

    2. Ifthefreevolumeofaninternaldeviceexceeds1.22in3itmustbeprotectedbyoneofthefollowingmeans:

    a) ventilatedonthetopandbottomsideswith1in2ofopeningforeach400in3ofvolumewithintheinternalprotectedenclosure,ataminimumdiameterof1/4"

    b) purgedinserieswiththeprotectedenclosureorbepurgedseparatelyor

    c) protectedbyothermeans;e.g.,explosionproofenclosures,hermeticallysealeddevices,orintrinsicsafecircuits.

    Temperature Limitations1. Theenclosuremusthavenosurfaceareathatexceeds80

    percentoftheflammableorignitablesubstancesauto-ignitiontemperature.

    2. Internaldevicesthatexceedthistemperaturemustbeprotectedbyoneofthefollowingmanners:

    a) ThedeviceisenclosedinachamberthatisCULUSorFMlistedasahermeticallysealeddevicethatprohibitstheentranceofaflammableorignitablesubstance,andmaintainsasurfacetemperaturebelowtemperaturelimits.

    b) Itcanbeprovenbytestingthatthedeviceswillnotignitethesubstanceinvolved.

    c) ThedeviceispurgedinaseparateenclosurethatbearsanETW(enclosuretemperaturewarningnameplate).Devicesmaybeaccessedonlyafterpowerhasbeenremovedandthedevicehasbeenallowedtocooltosafetemperature,ortheareaispositivelyknowntobenonhazardous.

  • Model 1001B Installation and Operation Manual

    5

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Model 1002-WPS-LH Shown

    PROTECTIVE GAS SUPPLY

    SYSTEM SUPPLY TUBING

    ELECTRICAL ALARM WIRING CONDUIT & SEAL

    SERVICE VALVE

    SYSTEM SUPPLY FITTING

    ENCLOSURE PROTECTION

    SYSTEM

    SYSTEM MOUNTING

    BOLT

    ENCLOSURE SUPPLY TUBING

    ENCLOSURE PROTECTION

    VENT

    PROTECTED ENCLOSURE

    ENCLOSURE CONNECTION

    FITTINGS

    ENCLOSURE REFERENCE

    TUBING

    ENCLOSURE WARNING

    NAMEPLATE

    Installation Overview

  • Model 1001B Installation and Operation Manual

    6

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Getting Started

    Typical Single Protected Enclosure Connections

    HELPFUL HINTSToensureadequateprotectivegasflowtotheprotectedenclosure(s),allpipingandtubingmustbefullyreamed.

    Precautionsmustbetakentopreventcrimpingandotherdamagetoprotectivegaspipingandtubing.

    Whenprotectingmultipleenclosureswithasingleenclosureprotectionsystem,theenclosuresmustbeconnectedinseriesfromthesmallesttothelargesttoensureadequateprotectivegasflow.

    PROTECTED ENCLOSURE

    C

    B

    ENCLOSURE PROTECTION VENT(Optional)

    E

    SUPPLY

    REFERENCE

    1/2" PROTECTIVE GAS SUPPLY

    HEADER

    ENCLOSURE PROTECTION

    SYSTEM

    Maximum tubing / pipe length and maximum number of bends / elbows

    3/8"O.D.tubingfullyreamed

    20feet10bends

    3/8"O.D.tubingfullyreamed

    Description

    *Tubing or pipe diameter

    Enclosure supply

    System supply tubing

    Enclosure reference

    1/4"O.D.tubingfullyreamed

    5feet5bends

    20feet10bends

    Multi - enclosure connections

    1"I.D.pipefullyreamed

    10feet5elbows

    Optional remote venting

    1"I.D.pipefullyreamed

    30feet5elbows

    A B EDC

    ENCLOSURE PROTECTION

    SYSTEM

    PROTECTED ENCLOSURE

    PROTECTED ENCLOSURE

    D

    SUPPLY

    REFERENCE

    B

    TYPICAL MULTIPLE PROTECTED ENCLOSURE CONNECTIONS

    1/2" PROTECTIVE GAS SUPPLY

    HEADER

    A

    A

    D

    C

    PROTECTED ENCLOSURE

    *NOTE: Tube and pipe sizes are trade sizes and are not equal in inside diameter. DO NOT substitute tube for pipe with same trade size.

  • Model 1001B Installation and Operation Manual

    7

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    System Mounting

    IMPORTANT NOTESThe system should be mounted at EYE LEVEL.

    Care must be taken to ensure the system and all protruding components are clear of all enclosure accesses (doors and covers) and conduit, pipe, tubing or cable entries.

    LH, RH, TM, BM and WM configurations are intended for mounting adjacent to the protected enclosure.

    LH, RH, TM & BM configurations are also suitable for 2" schedule 40 pipe mounting.

    Determine the mounting configuration of your system using the diagrams on pages 9 and 10.

    Remove and save the manila envelope (containing the enclosure warning nameplate) which may be taped to the outer surface of the mounting flange.

    Although all purge systems are factory tested and calibrated, we strongly suggest a bench test of basic functions prior to installation.

    Mounting LH, RH, TM, BM & WM ConfigurationsSurface mounting Systems

    1.Transferholepatternofsystemmountingplatetointendedsurface.

    2. Checkforobstructionshinderingboltfastening,drillandreamthemountingholesbeforemountingthesystem.

    3. Securethesystemtotheenclosure,orothermountingsurface,usingone(1)SMK-1mountingkitorequivalent-four(4)1/4"x3/4"stainlesssteelbolts,nutsandlockwashers.

    Pipe mounting Systems

    1. Locate2"schedule40pipe,(verticalforLH&RH,horizontalforTM&BM)withinfive(5)feetofprotectedenclosure.

    2. Ensuresystemismountedinatrueverticalposition,securethesystemtopipe,usingone(1)PMK-1mountingkitorequivalent-two(2)1/4"x2"stainlesssteelUbolts,nutsandlockwashers.

    Mounting FM & PM Configurations

    1. Transferpanelcutoutpatterntotheintendedsurface.

    2. Checkforobstructionsthatcouldprohibitboltfasteningorsystempneumaticconnections.

    3. Cutpanelcutoutpatternontheintendedsurface.

    4. Deburrallcutoutsurfaces.

    5. SecuresystemtoenclosureusingSMK-4orSMK-6mountingkit,orequivalent1/4"x3/4"stainlesssteelnuts,bolts,mountingclipsandlockwashers.

    HELPFUL HINTSFMandPMconfigurationsaredesignedtomountthroughapanelcutoutone(1)inchsmallerthantheoverallheightandwidthofthesystemmountingplate,usingclipsandfastenersprovidedwithSMK-4orSMK-6mountingkits.Thisdesignfeatureeliminatestheneedtodrillthesystemmountingboltholesintheprotectedenclosure.

    FMconfigurationsareintendedformountingadjacenttotheprotectedenclosure.

    PMconfigurationsareintendedformountingthroughacutoutintheprotectedenclosuresurface.

    Typical Examples of Surface, Pipe, Panel & Frame Mounted Systems

    Typical surface mounted system(Model 1002-LPS-CI-Z-LH shown)

    Typical pipe mounted system(Model 1002-LPS-CI-Z-LH shown)

    Typical panel/frame mounted system(Model 1002-LPS-CI-Z-PM shown)

  • Model 1001B Installation and Operation Manual

    8

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Hardware Mounting

    Optional Enclosure Protection VentAllconfigurationsmustbemountedinatrueverticalposition.

    Theventmustbelocatedtoprovideaccessforroutinetestingoftheventsflapperassembly.Aminimum8"clearanceisrequiredbelowtheventopening.

    1. Determinetheventsmountingconfiguration,i.e.,-00verticalmountor-90sidemount.Seephotosbelow.

    2.Determineventlocationandlayoutventmountingholeontheprotectedenclosure(asdeterminedonpage6,GettingStarted).

    3. Usinga1.75"holesawor1.25"conduitpunch,drillanddeburrtheenclosureprotectionventmountinghole.

    4. Removethehubmountingnutfromtheventhubandplacethehub,withO-ringintact,throughthemountinghole.TheO-ringmustbeontheoutsideoftheprotectedenclosure.

    5. Reinstallthehubmountingnuttothemountinghubfrominsidetheprotectedenclosureandtighten.

    Warning Nameplate(s)AnEWN(EnclosureWarningNameplate)mustbelocatedinaprominentpositiononornearallenclosureaccesses(doorsandcovers).

    One(1)EWNisprovidedwitheachsystem,locatedinthemanilaenvelopetapedtothemountingflangeofthesystem.AdditionalEWNsareavailablefromPepperl+Fuchs.

    AllEWNsprovidelabeledspacesallowingthecustomertomarktheprotectedenclosurewith:1)aTCode(temperatureidentificationnumber),2)Class,GroupandDivisionofsurroundingarea,and3)NFPApressurizationTypeX,YorZ,asmayberequiredbyplantandlocalcodesandisrequiredbyNFPA496.

    AnETW(EnclosureTemperatureWarningnameplate)mustbelocatedinaprominentpositiononornearallenclosureaccesses(doorsandcovers)whenthetemperatureofaninternalcomponentexceeds80percentoftheignitiontemperatureoftheflammablevapor,gasordustinvolved.

    AnETWwarnstheoperatortodeenergizeallequipmentforaspecifiedlengthoftime,allowingtheprotectedequipmenttocoolbeforeopeningtheprotectedenclosure.Thelengthoftimerequiredisdeterminedbythecustomerandcanbefactoryorfieldengraved.

    AllEWNsandETWsarefurnishedwithanadhesiveback,butshouldalsoberivetedorscrewedtotheprotectedenclosure.

    Enclosure temperature warning nameplate

    Enclosure warning nameplate - Class II

    Enclosure warning nameplate - Class I

    EPV - 3 - SA - 00Vertical Mount

    EPV - 3 - SA - 90Side Mount

  • Model 1001B Installation and Operation Manual

    9

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Mounting Plate Dimensions

    1001B-LPS-LH(Left hand configuration)

    1001B-WPS-LH(Left hand configuration)

    1001B-WPS-RH(Right hand configuration)

    1001B-LPS-RH(Right hand configuration)

    1001B-LPS-TM(Top mount configuration)

    1001B-WPS-TM(Top mount configuration)

    4"6"

    .625"3.375"

    7"

    8.875"

    6.375"

    .25" O.D.TYP. 4

    4"7.25"

    .625"3.375"

    12"

    8.875"

    11.375"

    .25" O.D.TYP. 4

    4"7.25"

    .625"3.375"

    11.375"

    .25" O.D.TYP. 4

    8.875"

    12"

    4"6"

    .625"3.375"

    6.375"

    .25" O.D.TYP. 4

    8.875"

    7"

    4"6"

    .62

    5"

    8.125"

    3.3

    75

    "

    7"

    8.75"

    .25" O.D.TYP. 4

    4"

    7.25"

    13.625"

    .62

    5"

    3.3

    75

    "

    14.25"

    8"

    .25" O.D.TYP. 4

  • Model 1001B Installation and Operation Manual

    10

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Mounting Plate Dimensions (continued)

    1001B-WPS-WM(Wall mount configuration)

    1001B-LPS-FM & 1001B-LPS-PM(Frame & panel mount configuration)

    1001B-WPS-FM(Frame mount configuration)

    1001B-LPS-BM(Bottom mount configuration)

    1001B-WPS-BM(Bottom mount configuration)

    1001B-LPS-WM(Wall mount configuration)

    4"

    7.25"

    13.625"

    .62

    5"

    3.3

    75

    "

    14.25"

    8"

    .25" O.D.TYP. 4 .

    62

    5"

    3.3

    75

    "

    4"

    6"

    8.125"

    7"

    8.75"

    .25" O.D.TYP. 4

    11"

    6"

    9.25"

    12"

    8.875"

    14"

    10.875"

    9.875"Panel Cutout

    Panel Cutout13"

    3.25"3.25".25" O.D.TYP. 6

    9"

    10.875"

    9.875"Panel Cutout

    Panel Cutout8"

    2.75" 2".25" O.D.TYP. 4

    7.875"

    1" .5"

    .25" O.D.TYP. 4

    6"

    6"

    7.5"

    7"

    8.875"

    TYPICAL -WMMOUNTING FLANGE

  • Model 1001B Installation and Operation Manual

    11

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Pneumatic Tubing Requirements

    Protective Gas Supply RequirementsTheprotectivegassupplytotheprotectionsystemmustbeaclean,instrumentqualitycompressedairornitrogenandmustcontainnomorethantraceamountsofflammablegas,vaporordust.

    Theprotectivegassupplycompressorintakemustoriginateinanonhazardouslocation.Suctionductpassingthroughahazardouslocationandtheprotectionsystemtubingandpipingmustbefabricatedfromnoncombustiblematerialssuitableforprevailinghazardsandenvironmentalconditions.

    Theprotectivegassupplymustoriginatefromadedicatedinstrumentqualitycompressedairheader(1/2"pipeorlarger),nofartherthantwenty(20)feetfromtheprotectionsystem.LocalcompressorsandgascylindersshouldnotbeusedbeforeconsultingwithPepperl+Fuchs.

    Theprotectivegassupplytotheprotectionsystemmustbeequippedwithatamper-proofregulatorsetat5psimaximum.

    Exception:Iftheprotectedenclosure(s)isequippedwithanEPV-3EnclosureProtectionVent,theprotectivegassupplytotheprotectionsystemmustnotexceed120psimaximum,5psiminimum.

    Pneumatic Connection RequirementsALLFITTINGSMAYBECUSTOMERORFACTORYFURNISHED

    1. Forsystemsupply,one(1)SC-63/8"malestraightconnectororone(1)NC-63/8"maleelbowconnectororequivalentfittingpersystem.

    NOTE: Above fitting is required only if protection system is furnished with an optional in-line filter kit (model ILFK) accessory.

    One(1)similarfittingwhichwillconnecttheinertgassupplytubingtotheinertgassupplyheaderconnectionpointandone(1)lotof3/8"O.D.,.035"wallthickness,weldedorseamlessstainlesssteeltubing.

    2. Forenclosuresupply,one(1)EFC-63/8"flushconnector,orone(1)EBC-63/8"feed-throughconnectororequivalentfittingpersystem.

    3.Forenclosurereference,one(1)EFC-41/4"flushConnector,orone(1)EBC-41/4"feed-throughconnectororequivalentfittingpersystem.

    4.One(1)lotof1/4"&3/8O.D.,.035"wallthickness,weldedorseamlessstainlesssteeltubing.

    5.Formultipleenclosureconnections,two(2)EPC-131.25"pipemountinghubsorequivalentand1.25"150#ratedpipecouplings&unionsperinterconnection.

    One(1)lot150#rating1.25"galvanizedoraluminumpipeandfittings,fullyreamedandunrestricted.

    PM Pneumatic Connection RequirementsInadditiontoitemnumbers1,4and5above,thefollowingfittingsarerequiredforallPMconfigurations.

    1. ForsystemsupplyonPMconfigurations,one(1)additionalEBC-6orequivalent3/8"throughbulkheadfittingpersystemisrequired.

    2. Foratmosphericreference,one(1)PRB-4orequivalent1/4"femalebulkheadfittingandstainlesssteelsinteredelementisrequired.

    SYSTEM SUPPLY FITTINGSSC-6 NC-6

    ENCLOSURE SUPPLY & REFERENCE FITTINGS

    EBC-4 & EBC-6EFC-4 & EFC-6

    EPC-13

    SYSTEM ATMOSPHERIC REFERENCE FITTINGPRB-4

    MULTIPLE ENCLOSURE CONNECTION FITTING

  • Model 1001B Installation and Operation Manual

    12

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    HELPFUL HINTSAllworkmustbeperformedbytechniciansqualifiedinpneumatictubingandelectricalconduitinstallation.

    Pepperl+Fuchsrecommendstheuseof.035"wallthickness,weldedorseamlessstainlesssteeltubing.

    Ifflexibletubingisused,itmustbeinstalledinamannerwhichwillprotectitfromdamageandcorrosion.

    Tubing Installation

    Tubing LH, RH, TM, BM, WM & FM ConfigurationsSystem Supply Connections

    1. Selectorinstallaprotectivegassupplyheadertap,fittedwiththepropertubesizefittingandlocatedwithintwenty(20)feetoftheenclosureprotectionsystem.

    2. Ifaservicevalveisplacedbetweentheprotectivegassupplyheaderandtheenclosureprotectionsystem,itmustbeinstalledincloseproximityoftheprotectedenclosureandbelabeledinaccordancewithNFPA496.

    3. Selecttheappropriatefittingsrequiredtoconnecttheprotectivegassupplytotheprotectionsystemregulatorasdeterminedonpage11,PneumaticConnectionRequirements.

    4. Determineappropriatetubingroutefromtheprotectivegassupplyheadertotheprotectionsystemregulator.

    5. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.

    6. Installtubingandtightenallfittingstofittingmanufacturersspecifications.Securetubingtoappropriatestructuralsupportsasrequired.

    Enclosure Supply & Reference Connections

    1.Chooselocationfortheenclosuresupplyconnection(s)basedontherequirementsonpage6,GettingStarted.

    2. Placetheenclosurereferenceconnectionfittingdirectlybehindtheenclosureprotectionsystemwheneverpossible.Forsystemsprotectingmultipleenclosuresinseries,theenclosurereferenceconnectionfittingmustbeplacedonthelastenclosureintheseries.Seepage6,GettingStarted.

    3. Drillanddeburrenclosuresupplyandreferencefittingholesontheprotectedenclosure.Mountthefittings.

    4. Determineappropriateroutefortheenclosuresupplyandreferencetubing.

    5. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.

    6. Installtubingandtightenallfittingstofittingmanufacturersspecifications.Securetubingtoappropriatestructuralsupportsasrequired.

    Tubing PM ConfigurationsEnclosure Bulkhead Fittings

    1. Selectthefittingsrequiredtoinstallthesystemsupply,systemsupplybulkheadfittingandatmosphericreferencebulkheadfitting.Seepage11,PneumaticTubingRequirements.

    2.Chooselocationforthesystemsupplybulkheadfitting.Thisfittingallowstheprotectivegassupplytopassthroughthewallofaprotectedenclosuretotheprotectionsystemsregulatorsupplyinletconnection.

    3. Chooselocationfortheatmosphericreferencebulkheadfitting.Thisfittingallowstheenclosurepressuregaugetoreferenceatmosphericpressure.

    4. Drillanddeburrsystemsupplyandreferencebulkheadfittingholesintheprotectedenclosure.Mountthefittings.

    System Supply & Reference Connections

    1. Selectorinstallaprotectivegassupplyheadertap,fittedwiththepropertubesizefittingandlocatedwithintwenty(20)feetoftheenclosureprotectionsystem.

    2. Ifaservicevalveisplacedbetweentheprotectivegassupplyheaderandtheprotectionsystem,itmustbeincloseproximityoftheprotectedenclosureandlabeledinaccordancewiththeNFPA496.

    3. Determineappropriatetubingroutefromtheprotectivegassupplyheadertothesystemsupplybulkheadfitting.

    4. Determineappropriatetubingroutefromthesystemsupplybulkheadfittingtotheprotectionsystemregulator.

    5. Determineappropriatetubingroutefromtheatmosphericreferencebulkheadfittingtotheenclosurepressuregaugesreferenceinletconnection.

    6. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.

    7. Installtubingandtightenallfittingstofittingmanufacturersspecifications.Securetubingasrequired.

  • Model 1001B Installation and Operation Manual

    13

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    HELPFUL HINTPneumaticconnectionsarebolded.

    Tubing Connection Diagrams

    LH, RH, TM, BM, WM, & FM Configuration Connection Points & Pneumatic DiagramSystem supply inlet

    Enclosurepressurecontrol

    regulator

    Enclosure supply outlet

    Enclosurepressuregauge

    Enclosurereference

    inlet

    Venturiorifice

    Mountingplate

    LPS Style

    Protectedenclosure

    Optionalenclosureprotectionvent

    WPS Style

    Systemsupply

    OptionalEXPpressureswitch

    Venturiorifice

    Inlet

    Sinteredvent

    Enclosurepressuregauge

    Regulator

    Sinteredvent Reference

    Supply

    Enclosurereferencebulkheadfitting

    Enclosuresupplybulkheadfitting

    PM Configuration Connection Points & Pneumatic Diagram

    Enclosurepressuregauge

    Atmospheric reference

    inlet

    Mountingplate

    Optionalenclosureprotectionvent

    Protectedenclosure

    System supply inlet

    Enclosurepressurecontrol

    regulator

    Enclosure supply outlet

    Systemsupply

    InletSystemsupply

    bulkhead

    Atmosphericreferencebulkhead

    Supply

    Reference

    Regulator

    Enclosurepressuregauge

    Sinteredvent

  • Model 1001B Installation and Operation Manual

    14

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Electrical Supply Requirements

    General Wiring RequirementsWARNING!This device contains electrical parts that can cause shock or injury.

    Allelectricalconnections,conduitandfittingsontheprotectedenclosuremustbesuitableforthehazardouslocationinwhichtheyareinstalled.Inaddition,allconduitandwiremustbeinstalledinaccordancewithNECasrequiredandallrelevantplantandlocalcodes.

    Note:Donotusesealsonconduitusedasaprotectedwirewaytosupplyprotectivegastoadjacentprotectedenclosures.Thesameconduitcanbeutilizedforbothelectricalandpneumaticservicetoanadjacentprotectedenclosure(s),providedtheconduitisoversizedtoallowaminimumfreeclearanceequaltoorlargerthanthepipesizerequiredbetweenmultipleenclosuresasstatedonpage6,GettingStarted.

    Enclosure Power RequirementsTheprotectedenclosure(s)electricalpowersourcemustoriginatefromacircuitbreakerorfuseddisconnectsuitableforthehazardouslocationinwhichitisinstalled.Theswitchmustbelocatedwithinfifty(50)feetoftheprotectedenclosure(s)andtheprotectionsystemandbeproperlymarked.

    Alarm Signal RequirementsForTypeYandZpurgesystems,audiblealarmsorvisualindicatorsmustbeusedtonotifyoperatorsthatpressureinsidetheenclosureisbelowtheNFPAminimum.

    Alarmsareconnecteddirectlytotheenclosureandmonitorthedifferentialairpressurebetweentheenclosureandtheenvironmentoutsideit.Thesealarmsareactivatedbythereductioninfloworpressurewithintheprotectiveenclosureandhaveadirectconnectiontotheenclosure,eliminatingtheneedforanalarmontheprotectivegassupply.

    Thealarmmustbelocatedwheretheoperatorcanseeiteasily.

    Thealarmmusttakeitsmeasurementfromtheenclosureonly.

    Alarmslocatedinthehazardousareamustberatedforthearea.

    Valvescannotbeconnectedbetweenthealarmandtheenclosure.

    IMPORTANT NOTE: NFPA 496 requires the use of an alarm or an indicator to detect the loss of safe enclosure pressure. In addition, the NFPA 496 requires that if an indicator alone is utilized, a protective gas supply alarm must also be installed between the last valve in the protective gas supply and the protected enclosure. Therefore, the protective gas supply to all LPS Style systems must be equipped with the above mentioned protective gas supply alarm. Exception: Systems utilizing an EPSK or GPSK enclosure pressure loss alarm switch accessory will satisfy the above mentioned NFPA requirement.

    Typical Enclosure Wiring MethodsInageneralsense,protectedenclosuresshouldbewiredsimilartoexplosionproofenclosures,inaccordancewithArticle500oftheNationalElectricCode-NFPA70.

    Singleconductorwiringshouldbeplacedinrigidmetalconduit,seal-flexconduitorothermediumsapprovedforuseinthehazardouslocationsurroundingtheprotectedenclosure.Additionally,NFPA496requirestheuseofapprovedsealsonallpressurizedenclosureconduitwiringentries,inaccordancewithNFPA70.Furthermore,theuseofanapprovedsealissimplythemostpracticalwaytopreventexcessiveleakagethroughconduitconnections.

    However,whileexplosionproofenclosuresrequireconduitsealsonallcableentries,inaccordancewithNFPA70.Othermethodsofsealedcableentriesthataresuitableforhazardouslocationscanbeused,suchascompressionglands.

    Inconclusion,therearetwoprimarygoals.First,theinstallershouldensurethatallassociatedwiringandcableisprotectedbypressurizationorothermeans,suchasexplosionproofconduitorintrinsicsafetybarriers.Secondly,theinstallershouldensurethatallassociatedconduitandwirewaysaresealedtoconserveprotectivegas,unlesstheyareusedtosupplyprotectivegastootherenclosuresordevices.

    Typical Enclosure Wiring Connections

    Explosionproofdevice

    Seal

    Intrinsicallysafeorfiberopticdevice

    Adjacentpressurized

    device

    Independentlypressurized

    device

    Intrinsicallysafeorfiberopticdevice

    Seal

    Conduit

    Conduit

    Conduit

    Glandfitting

    Cable

    Seal

    Pressurizedraceway

    Protectedenclosureordevice

  • Model 1001B Installation and Operation Manual

    15

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Conduit Installation

    Electrical Conduit1.Choosethelocationfortheenclosureselectricalconduit

    connection(s)basedontherequirementsonpage14,ElectricalSupplyRequirements.

    2. Drillanddeburrenclosureconduitfittingholesintheprotectedenclosure.Mountthefittings.

    3. Determineappropriateroutefortheenclosureelectricalandpoweralarmsignalconduit.

    4. Measure,cutandthreadconduit,checkconduitfittoinsureproperseating.Fullyreamallconduit.

    5. Installconduitandtightenallfittingstofittingmanufacturersspecifications.Secureconduittoappropriatestructuralsupportsasrequired.

    6. Sealallconduitwithanapprovedcompoundpriortooperationoftheprotectionsystem.

    WPS Style ConduitWPSstylesystemsprovideelectricalcontactsforaudibleorvisualalarmdevicesthatsignalalossofprotectedenclosurepressure.WPSstylesystemsarecalibratedtoalarmat0.50"forClassIIapplications.Theswitchesaresuitableforhazardous(classified)outdoorlocations.Wiringmustbeinstalledwithasealandconduitfittingssuitableforthearea.Alarmcircuitpowermaybederivedfromtheprotectedenclosurepowersourceoranintrinsicallysafealarmsignalsource.Allassociatedalarmdevicesmustbeprotectedbysuitablemeans(explosion-proof,purged,orintrinsicallysafe).

    WPS Style Conduit Connection PartsFittingKitsCanBeFactoryFurnished

    1. ForWPSstyleEXPpressurelossalarmswitchconnectedtoanenclosuremountedalarm,one(1)LCK(Lfittingconduitkit)orequivalentconduitelbow,couplingandsealfittings.

    2. ForWPSstyleEXPpressurelossalarmswitchconnectedtoaremotemountedalarm,one(1)TCK(Tfittingconduitkit)orequivalentconduittee,couplingandsealfittings.

    3. One(1)lot150#rating1/2galvanizedoraluminumpipe.

    HELPFUL HINTItmaybeimpracticaltopourallelectricalconduitsealspriortoinstallationinthefield.However,allconduitconnectionsmustbesealedforpropertestingandoperationoftheenclosureprotectionsystem.Therefore,theuseoftemporarysealssuchasductsealormaskingtapeforbenchorshoptesting,priortofinalfieldinstallationmaybeused.

    LCK L Fitting Conduit Kit

    TCK T Fitting Conduit Kit

    WPS Style EXP Pressure SwitchWith Cover Removed

    Switchbody

    Setpointcalibration

    screw

    Groundingscrew

    1/2"conduitport

    Electricalswitch

    contacts

    Lowportsintered

    vent

    Highporttubefitting

  • Model 1001B Installation and Operation Manual

    16

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    HELPFUL HINTSThetermSafepressureforpurposesofthismanualisdefinedas1.0inchofwatercolumnpressure.

    Regulatormaybeinthelockedpositionuponarrival.Toadjustregulator,pullhandletooutwardposition.

    Totesttheventsoperation,gentlyprodtheventflapperopenwithasoft-pointedobject,(example:eraserendofapencil)ensuringthattheventvalveworksfreely.Onverticallyconfiguredvents,thiscanbeaccomplishedfromwithintheprotectedenclosure.Sidemounted-90configuredventscanbetestedbyremovingtheconduitplugatthebottomofthemountingtee.Multipleoperationsrequireonlyonetestperdayifenclosureisnotopenedorleftunattended.

    Set-up1.Closetheenclosurepressurecontrolregulatorfully,by

    turningitcounterclockwise(CCW).

    2. Removeallcombustibledustfromprotectedenclosure.

    3.Checkoperationofenclosureprotectionvent(ifutilized).

    4.Sealenclosure(s)andadjustenclosurepressurecontrolregulatorbyopeningslowlyclockwise(CW)tosetasafepressureontheenclosurepressureindicator.

    NOTE:Ifpressuresettingisdifficulttostabilizeorset,seepage17,TroubleshootingProcedures.

    5. Installandtightenallboltsonthepressurelossalarmswitch(ifutilized).Energizepowertoswitch(ifutilized)andtestthefunctionofthealarmsystem.

    WARNING! Do not exceed a safe pressure with the enclosure pressure control regulator. Operators must

    follow step-by-step sequence of the start-up instructions nameplate on the protection system.

    OperationWiththeinertgassupplyconnected,enclosurepowerdeenergizedandalarmsystemenergized(ifutilized).

    1.Carefullyreadstart-upinstructionnameplateonsystem.

    2.Checkoperationoftheenclosureprotectionvent(EPV-3,ifutilized),openingitmanuallyseveraltimes.SeeHelpfulHintonthispage.

    3.Removealltracesofcombustibledust.

    4.Sealprotectedenclosure(s).

    5.OpenenclosurepressurecontrolregulatorbyturningCWtosetenclosurepressureIndicatoratsafepressure,thepressurelossalarmswitchshouldthenactivatetosilencethealarmsystem(ifutilized).

    6.EnsuretheprotectionsystemenclosurepressureIndicatormaintainsasafepressureforone(1)minute.

    7. Energizetheprotectedenclosurepower.

    8.Ensuretheenclosurepressureindicatormaintainsasafepressurebeforeleavingsystemunattended.

    Enclosure pressure

    gauge

    Model identification

    nameplate

    Model 1001B-LPS Front View

    Model 1001B-WPS Front View

    Enclosurepressurecontrol

    regulator

    Enclosurepressurecontrol

    regulator

    Start - up instruction nameplate

    EXP pressure loss alarm

    switch

    Enclosure pressure

    gaugeModel

    identification nameplate

    Set-up & Operating Procedures

  • Model 1001B Installation and Operation Manual

    17

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Troubleshooting Procedures

    Problem or Fault Possible Causes Corrective Action

    Enclosurepressurecontrolregulatorwillnotholdasafe1.0inchpressure.

    Leakagearoundgasketing,covers,seams,pipingandtubingconnections,conduitconnectionsandelectricalconduitsealsoftheenclosure.

    Tightenenclosurelatches:Wheretighteningisnotfeasible,andgasketingmaterialsarenotpractical,holesorgapscanbeclosedwithsiliconesealantappliedfrominsidetheprotectedenclosure.

    Enclosurepressureindicatorreadingisdifficulttostabilize.

    Insufficientenclosureleakageoropeningoftheventuriorificeiscrimpedtosmall.

    Removetheorifice,cutoffthecrimpedendandreamthetube,thenrecrimpandreinstallthetubetonoteeffect.Astubeisshortened,reamed,andrecrimped,sensitivitydecreases,allowingeasieradjustmentofsetpointontheenclosure.

    Enclosurepressurelossalarmswitchdoesnotappeartobeoperating.

    Pressureswitchisoutofcalibration Calibratebyslowlyadjustingcounterclockwisetodecreasethesetpoint,andclockwisetoraisethesetpoint.

    (Donotattempttocalibratetheswitchuntilalleffortstomaketheswitchrespondproperlyhavefailed)

    Problemspersists,orifthesystemdoesnotappeartobeoperatingproperly.

    Persistingproblems ContactPepper+Fuchsapplications/customerservicedepartmentat330-486-0002

    Thissectioncoversthemostcommonproblemsdocumentedwiththissystem.Anyproblemsnotcoveredinthissectionshouldbeaddresseddirectlytoourfactory.Pleaseaddressallserviceneedsto:

    Pepperl+Fuchs, Inc. Customer Service Department

  • Model 1001B Installation and Operation Manual

    18

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    PEPPERL+FUCHS STANDARD 24-MONTH WARRANTY1. LimitedWarranty.Pepperl+Fuchs,Inc.(P+F")warrantsPurgeUnitsandcomponentsforPurgeUnitsmanufacturedbyP+F

    (Product"orProducts")tobefreefromdefectsinmaterialandworkmanshipunderNormalUseforaperiodoftwenty-four(24)monthsfromthedateofshipmentofsuchProductsfromP+Fswarehouseorplaceofmanufacture(orfromP+Fsauthorizedrepresentativeordistributor).OnlytheoriginalpurchaserofsuchProducts(theCustomer")shallbeentitledtothebenefitoftheforegoingLimitedWarranty.Norepresentative,agentorsalesmanofP+FisauthorizedtogiveorprovideanywarrantyormakeanyrepresentationcontrarytoorinadditiontotheforegoingLimitedWarranty.

    2. InspectionandClaims.CustomermustinspectandtestallProductsuponreceipt.AllclaimsundertheLimitedWarrantyprovidedhereinmustbemadewithinthirty(30)daysofthediscoveryofthedefect.CustomermustobtainshippinginstructionsfromP+FpriortoreturninganyProduct,whichProductmustbereturnedatCustomersexpenseinaccordancewithP+Fsinstructions.

    3. LimitationsandExclusions.NormalUse"shallmeanuseandoperationwithinratedcapacities,atthecorrectvoltage,andwithanyrequiredmaintenanceasprovidedintheapplicableP+FOperatingManuals.TheLimitedWarrantyprovidedhereindoesnotapplyto(i)anyProductswhichhavebeenalteredormodifiedinanywayordisassembledbytheCustomeroranyoneelse,(ii)anyProductswhichhavebeensubjecttomisuse,negligenceoraccident,orimproperlyinstalled,changed,substitutedorreplaced,(iii)anypartorcomponentnotmanufacturedbyP+F,or(iv)anypartorcomponentthatissubjecttowearorconsumption.ForpartsorcomponentsnotmanufacturedbyP+F,theCustomeroranyotheruserorownershallhaveonlythewarrantyprovidedbythemanufacturerofsuchpartorcomponent.TheLimitedWarrantysetforthhereinisalsosubjecttothefollowing:

    (1) TheLimitedWarrantyislimitedtoelectronicandmechanicalperformanceonly,asexpresslydetailedintheproductspecifications,anddoesnotapplytocosmeticappearance;

    (2) TheLimitedWarrantyshallnotapplytoanycablesattachedto,orintegratedwith,anyProducts.

    (3) TheLimitedWarrantyshallnotapplytoanyProductswhicharestored,orutilized,inharshenvironmentalorelectricalconditionsoutsideP+Fswrittenspecifications.

    THELIMITEDWARRANTYSETFORTHHEREINISTHEONLYWARRANTYMADEBYP+FWITHRESPECTTOTHEPRODUCTS.ITISEXPRESSLYAGREEDANDUNDERSTOODTHATP+FMAKESNOWARRANTYOFMERCHANTABILITYORFITNESSFORAPARTICULARPURPOSE.EXCEPTFORTHELIMITEDWARRANTYSETFORTHHEREIN,THEREISNOOTHERWARRANTY,EXPRESS,IMPLIEDORSTATUTORY;ANDTHEREISNOAFFIRMATIONOFFACTORPROMISEBYP+FWITHREFERENCETOTHEPRODUCTS.INNOEVENTSHALLP+FBELIABLEFORACTUALORANTICIPATEDLOSTPROFITSORFORINCIDENTALORCONSEQUENTIALORPUNITIVEDAMAGESORFORDAMAGESRESULTINGFROMBUSINESSINTERRUPTION,ORINJURYORDEATHOFPERSONS,ORINJURYTOPROPERTY.P+FSLIABILITYONANYCLAIMOFANYKINDARISINGOUTOF,CONNECTEDWITHORRESULTINGFROMTHEDESIGN,MANUFACTURE,SALE,REPAIROROPERATIONOFAPRODUCT,SHALLNOTEXCEEDTHEPRICEALLOCABLETOTHATPRODUCTORTHEPARTTHEREOFWHICHGIVESRISETOTHECLAIM.THEREMEDYSETFORTHINTHISLIMITEDWARRANTYCONSTITUTESTHESOLEANDEXCLUSIVEREMEDYOFTHECUSTOMER.P+FSHALLNOTBELIABLEFORPENALTIESOFANYDESCRIPTION.

    4. LimitationofRemedies.IntheeventofP+Fsliability,whetheronthisLimitedWarrantyorbasedoncontract,tort(including,butnotlimitedto,negligenceandstrictliability)orotherwise,Customerssoleandexclusiveremedywillbelimitedto,atP+Fsoption,therepairorreplacement(f/o/bP+Fsplaceofmanufacture)byP+Fofanynon-conformingitemsforwhichclaimismadebyCustomerinaccordancewithparagraph2,ortherepaymentoftheportionofthepurchasepricepaidbyCustomerattributabletothenon-conformingitem.

    5. ResponsibilityofCustomer:SafetyandProtectionPrecautions.P+FtakesgreatcaretodesignandbuildreliableanddependableProducts;however,someProductscanfaileventually.Customermusttakeprecautionstodesignitsequipmenttopreventpropertydamageandpersonalinjuryintheunlikelyeventofafailure.ASAMATTEROFPOLICY,P+FDOESNOTRECOMMENDTHEINSTALLATIONOFPRODUCTSASTHESOLEDEVICEFORTHEPROTECTIONOFPERSONNELORPROPERTYAND,THEREFORE,THECUSTOMERSHOULDBUILDINREDUNDANCYORDUALCONTROLUSINGAPPROVEDSAFETYDEVICESFORTHESEAPPLICATIONS.

    6. Conflicts.IntheeventthereisanyconflictbetweentheprovisionsofthisLimitedWarrantyandanyprovisionscontainedinanyorders,offers,acceptancesorotherwritingsorstatementsprovidedormadebyCustomertoP+F,theprovisionsofthisLimitedWarrantyshallprevail,andthecontractbetweenP+FandtheCustomershallbedeemedformedonlyupontheprovisionssetforthinthisLimitedWarranty,andanyadditionalorconflictingprovisioninsertedbyCustomershallbeofnoforceoreffect.

    Warranty Terms and Conditions

  • Model 1001B Installation and Operation Manual

    19

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Notes

  • Model 1001B Installation and Operation Manual

    20

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Notes

  • Model 1001B Installation and Operation Manual

    21

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Notes

  • Model 1001B Installation and Operation Manual

    22

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    System Maintenance

    Regular MaintenanceDraintheprotectionsystemregulatorfrequentlyandcleansystemwithnonsolventcleaningagentsonly.

    Long-Term MaintenanceCalibratetheenclosurepressureindicatorto0inchesbyventingthepurgepressurereferenceportandtheprotectedenclosuretoatmosphereandadjustingthecalibrationscrewinthelowercenterportionoftheindicatorsface.

    Fullyopentheenclosurepressurecontrolregulator,toblowoutanydepositsaroundthetipofthevalveandtoensurethattheenclosureprotectionventisoperatingproperly,thencarefullyreadjustsystemaccordingtotheset-upandoperatingproceduresonpage16.Replaceortightenstempackingnutasrequiredtoprohibitstempackingleakage.

    Carefullydisassembletheenclosureprotectionventbylooseningthetwobottomhexnutsthatholdtheunittogether.

    (DO NOT REMOVE CAP NUTS ON TOP OF VENT BODY)

    Carefullycleantheflappervalveandventbodyseatswithwarmsoapandwater,beingcarefulnottoextendtheventvalvebeyonditsnormalopeningpoint,andbeingcarefulnottoexertanystressonthevalvehinge.

    Examinetheentireprotectionsystemandtheprotectedenclosure(s),andreplaceanydefectivepartsduringroutineshutdownoftheprotectedenclosure(s).PartsareavailablefromPepperl+Fuchsonimmediatenoticeasrequired.

    MAINTENANCE SCHEDULEDate Work Performed Performed by

  • Model 1001B Installation and Operation Manual

    23

    Par

    t No.

    511

    872

    Dra

    win

    g N

    o. 1

    29-0

    201a

    03/

    09

    Subject to modifications without notice

    Pepperl+Fuchs Groupwww.pepperl-fuchs.com

    USA: +1 330 486 [email protected] [email protected]

    Singapore: +65 6779 [email protected]

    Copyright Pepperl+Fuchs

    Germany: +49 621 776 2222

    Systems Identification & Application Information

    Date of installation _____________________________________________________

    Unit serial #____________________________________________________________

    Item ___________________________________________________________________

    Customer P.O.# ________________________________________________________

    Customer project# _____________________________________________________

    Service ________________________________________________________________

    Type __________________________________________________________________

    Features ______________________________________________________________

    Application ____________________________________________________________

    Notes: _______________________________________________________________________________________________

    _____________________________________________________________________________________

    _____________________________________________________________________________________

    _____________________________________________________________________________________

    _____________________________________________________________________________________

    _____________________________________________________________________________________

    _____________________________________________________________________________________

    _____________________________________________________________________________________

    _____________________________________________________________________________________

    _____________________________________________________________________________________

  • 5 1

    8

    4

    2

    6

    7

    3

    PROCESS AUTOMATION PROTECTINg YOUR PROCESS

    Northern Europe HeadquartersPepperl+Fuchs GB Ltd. Oldham EnglandTel. +44 161 6336431E-Mail: [email protected]

    6

    Southern/Eastern Europe HeadquartersPepperl+Fuchs Elcon srl Sulbiate ItalyTel. +39 039 62921E-Mail: [email protected]

    7

    South America HeadquartersPepperl+Fuchs Ltda. So Bernado do Campo SP BrazilTel. +55 11 4339 9935E-Mail: [email protected]

    8

    For over a half century, Pepperl+Fuchs has provided new concepts for the world of process automation. Our company sets standards in quality and innovative technology. We develop, produce, and distribute electronic interface modules, Human-Machine Interfaces and hazardous location protection equipment on a global scale, meeting the most demanding needs of industry. Resulting from our world-wide presence and our high flexibility in production and customer service, we are able to offer complete individual solutions wherever and whenever you need us. We are the recognized experts in our technologies Pepperl+Fuchs has earned a strong reputation by supplying the worlds largest process industry companies with the broadest line of proven components for a diverse range of applications.

    www.pepperl-fuchs.com

    Worldwide/german Headquarters Pepperl+Fuchs GmbH Mannheim GermanyTel. +49 621 776 2222E-Mail: [email protected]

    1

    Asia Pacific HeadquartersPepperl+Fuchs PTE Ltd. SingaporeCompany Registration No. 199003130ETel. +65 6779 9091E-Mail: [email protected]

    2

    Central/Western Europe & Africa HeadquartersPepperl+Fuchs N.V. Schoten/Antwerp BelgiumTel. +32 3 6442500E-Mail: [email protected]

    3

    Middle East HeadquartersPepperl+Fuchs M.E (FZE) Dubai UAETel. +971 4 883 8378E-Mail: [email protected]

    4

    North/Central America Headquarters Pepperl+Fuchs Inc. Twinsburg Ohio USATel. +1 330 486 0002E-Mail: [email protected]

    5

    Subject to modifications 2009 PEPPERL+FUCHS, INC. Printed in USA Part No. 511872 Drawing No. 129-0201a (TDOCT-1353_ENG) 03/09