ILBP-Module_1298-9940-8_RevB

download ILBP-Module_1298-9940-8_RevB

of 32

description

NATIONAL FOAM

Transcript of ILBP-Module_1298-9940-8_RevB

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    1/32

    OPERATING & MAINTENANCE MANUAL

    3/07 MANUAL P/N: 1298-9940-8(B)

    IN-LINE BALANCED PRESSURE

    PROPORTIONING MODULE

    NATIONAL FOAM

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    2/32

    - i - 12/98

    TABLE OF CONTENTS

    Text Page

    Table of Contents........................................................................................................................... i - ii

    Warning-Failure to Read Manual ...................................................................................................... ii i

    Safety Information ............................................................................................................................. iii

    NF Red Alert Fire Emergency Service ............................................................................................. ii i

    CHAPTER 1 - INTRODUCTIONCHAPTER 1 - INTRODUCTIONCHAPTER 1 - INTRODUCTIONCHAPTER 1 - INTRODUCTIONCHAPTER 1 - INTRODUCTION

    General Description ........................................................................................................................ 1-1

    CHAPTER 2 - INSTALLATIONCHAPTER 2 - INSTALLATIONCHAPTER 2 - INSTALLATIONCHAPTER 2 - INSTALLATIONCHAPTER 2 - INSTALLATION

    Cautions and Notes for In-Line Balanced Pressure Proportioning System ................................ 2-1

    2-1. Recommended Materials of Construction ..................................................................................... 2-2

    A. With Synthetic Based Polar Solvent/AFFF & Conventional AFFF Foam Concentrates ..... 2-2

    B. Protein Based Foam Concentrates ......................................................................................... 2-2

    Figure 2-1 In-Line Balanced Pressure Proportioner Module

    3" to 8" Wafer Style with Manual Override ...................................................................... 2-3

    Figure 2-2 In-Line Balanced Pressure Proportioner Module

    3" to 8" Wafer Style without Manual Override ................................................................. 2-4

    Figure 2-3 In-Line Balanced Pressure Proportioner Module2" to 8" Flanged Style ........................................................................................................ 2-5

    2-2. Installation and Start-Up: ILBP Module ......................................................................................... 2-6

    A. Off Loading ............................................................................................................................... 2-6

    B. Installation ................................................................................................................................. 2-6

    C. Operating Requirements .......................................................................................................... 2-7

    CHAPTER 3 - OPERATING PROCEDURESCHAPTER 3 - OPERATING PROCEDURESCHAPTER 3 - OPERATING PROCEDURESCHAPTER 3 - OPERATING PROCEDURESCHAPTER 3 - OPERATING PROCEDURES

    3-1. Minimum Inlet Pressure Requirements ......................................................................................... 3-1

    Figure 3-1 NF Ratio Controller Minimum Inlet Pressure vs. Solution Flow Chart ............... 3-1

    Figure 3-2 Operating Schematic Drawing -

    RCW Style ILBP Module With Manual Override ............................................................. 3-2

    Figure 3-3 Operating Schematic Drawing -

    RCW Style ILBP Module Without Manual Override ........................................................ 3-3

    Figure 3-4 Operating Schematic Drawing -

    RCF Style ILBP Module With Manual Override............................................................... 3-4

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    3/32

    12/98 -

    3-2. ILBP Module Operation .................................................................................................................. 3-5

    3-3. ILBP Module Manual Override (Manual Regulation) .................................................................... 3-5

    3-4. Shutdown ......................................................................................................................................... 3-6

    CHAPTER 4 - INSPECTION AND MAINTENANCECHAPTER 4 - INSPECTION AND MAINTENANCECHAPTER 4 - INSPECTION AND MAINTENANCECHAPTER 4 - INSPECTION AND MAINTENANCECHAPTER 4 - INSPECTION AND MAINTENANCE

    4-1. Inspection and Maintenance .......................................................................................................... 4-1

    4-2. Testing After System Maintenance ................................................................................................ 4-1

    4-3. Annual Testing ................................................................................................................................ 4-1

    Table 4-1 Recommended Inspection & Maintenance Schedule ........................................... 4-24-4. General ............................................................................................................................................ 4-2

    4-5. Water Powered Ball Valves ........................................................................................................... 4-2

    4-6. Electrically Actuated Valves .......................................................................................................... 4-3

    4-7. Control System................................................................................................................................ 4-3

    4-8. Flushing - ILBP Module .................................................................................................................. 4-4

    A. ILBP Module With Diaphragm Valve Manual Override Capabili ty ....................................... 4-4

    B. ILBP Module Without Diaphragm Valve Manual Override Capability .................................. 4-4

    CHAPTER 5 - TROUBLESHOOTINGCHAPTER 5 - TROUBLESHOOTINGCHAPTER 5 - TROUBLESHOOTINGCHAPTER 5 - TROUBLESHOOTINGCHAPTER 5 - TROUBLESHOOTING

    5-1. Troubleshooting .............................................................................................................................. 5-1

    Table 5-1 Troubleshooting ....................................................................................................... 5-1

    5-2. No Proportioning ............................................................................................................................. 5-1

    5-3. Low Percent of Proportioning ......................................................................................................... 5-2

    5-4. High Percent of Proportioning ........................................................................................................ 5-3

    5-5. No Flow at Discharge Device(s) .................................................................................................... 5-4

    5-6. Low Flow at Discharge Device(s) .................................................................................................. 5-4

    5-7. No Operation ................................................................................................................................... 5-4

    APPENDIX - FACTORY MUTUAL APPROVALSAPPENDIX - FACTORY MUTUAL APPROVALSAPPENDIX - FACTORY MUTUAL APPROVALSAPPENDIX - FACTORY MUTUAL APPROVALSAPPENDIX - FACTORY MUTUAL APPROVALS

    A-1. Universal Gold 3% .......................................................................................................................... A-1

    A-2. Aer-O-Lite 3% ................................................................................................................................. A-1

    A-3. Aer-O-Water 3EM ........................................................................................................................... A-2

    Text Page

    TABLE OF CONTEN

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    4/32

    WARNING:This manual has been prepared as an aid and guide for personnel involved in the installation, operation and

    maintenance of a National Foam In-Line Balanced Pressure Proportioning Module and must be kept with the

    module. All instructions must be read and understood thoroughly before attempting any installation, operation

    or maintenance to this module. Failure to follow any instructions can result in personal injury and/or damage

    to this equipment.

    SAFETY INFORMATION

    The International Safety Alert Symbol - - is used with one of the following signal words to alert operating

    personnel to the potential for death, personal injury or damage to equipment or property.

    DANGER: indicates an extremely hazardous situation which, if not avoided, willresult

    in death or serious injury to the operator or major property damage.

    WARNING: indicates a potentially hazardous situation which, if not avoided,canresult

    in serious injury, or death to the operator or major property damage.

    CAUTION: indicates a potentially hazardous situation which, if not avoided,canresult

    in personal injury or property damage.

    NOTE: indicates special instructions which are very important and must be followed.

    It is the responsibility and duty of all personnel involved in the operating and maintenance of this equipment to fully

    understand the DANGER, WARNING, CAUTION and NOTEprocedures by which hazards are to be reduced or

    eliminated. Personnel must become thoroughly familiar with all aspects of safety and equipment prior to operation

    or maintenance of the equipment.

    Operating and Maintenance Instructions and layouts shall be posted at control equipment with a second copy on file.

    All persons who may be expected to inspect, test, maintain or operate foam-generating apparatus shall be thoroughly

    trained and kept thoroughly trained in the functions they are expected to perform.

    - iii - 6/00

    SAFETY INFORMATION

    National Foam

    Red Alert Fire Emergency Service

    National Foams Red Alert Emergency Service is a system set up to respond to an emergencysituation requiring foam, equipment or service and is available 24 hours a day, 365 days a year.

    CALL LIONVILLE, PA 610-363-1400

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    5/32

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    6/32

    1-1 12/98

    controller to the diaphragm valve.

    NFdiaphragm valves, as previously mentioned, are

    available in two versions. One version does not havemanual override capability. This version does not allow

    manual regulation of foam concentrate inlet presssure in

    the event of a diaphragm valve failure. The other version

    does have manual override capability, which allows

    manual regulation of the foam concentrate inlet pressure.

    Pressure is adjusted by the operator by manually opening

    the diaphragm valve (thru use of the Manual Override

    Knob) and regulating the foam concentrate supply valve

    (Valve "V") while watching the duplex gauge for system

    balance. The duplex gauge monitors balancing of foam

    concentrate and water pressures on a single gauge. Foam

    concentrate pressure is indicated by the red pointer andwater pressure is indicated by the black pointer. When

    the red pointer is directly aligned with the black pointer,

    both pointing in the same direction, the system is balanc-

    ing. Diaphragm valves that do not have manual override

    capability also do not have a duplex gauge to monitor

    pressure balance.

    A National Foam ILBP Module is just one compo-

    nent of an In-Line Balanced Pressure Proportioning

    System. This type of foam proportioning system consists

    of one or more ILBP Modules, a foam concentrate pump,

    a pressure sustaining valve and a foam concentratestorage tank. An ILBP System requires a fire water

    supply system for the module(s).

    The ILBP Module is a complete, self-contained unit,

    assembled and tested at the factory. The unit is supplied

    with no finish and is suitable for either horizontal or

    vertical mounting.

    The principle of operation of the ILBP Module is

    based on the use of a modified venturi proportioner

    called a ratio controller. With this type of proportioner,

    water passes thru a jet (venturi) at the inlet of the ratio

    controller, creating a reduced pressure area on the dis-

    charge side of the jet. This reduction in pressure creates

    a pressure differential across the foam concentrate ori-

    fice and causes injection of foam concentrate into the

    water stream at this reduced pressure area.

    As the water flow thru the ratio controller increases, thepressure reduction on the discharge side of the jet in-

    creases, thereby increasing the pressure differential across

    the foam concentrate orifice. A proportionate increase in

    foam concentrate injection will occur with an increase in

    the water flow thru the ratio controller due to the in-

    creased pressure differential. As both the water and foam

    concentrate flow into the common reduced pressure area,

    it is necessary only to maintain identical water and foam

    concentrate pressures at the inlets of the ratio controller.

    A diaphragm valve (pressure control valve) automati-

    cally adjusts the foam concentrate inlet pressure tocorrespond to the water inlet pressure. Pressure sensing

    lines lead from the foam concentrate line upstream of the

    ratio controller and from the water inlet to the ratio

    A National Foam ILBP Module consists of the following major components:

    Ratio Controller

    Diaphragm Valve - with foam concentrate and water sensing lines

    Two Versions

    1. With Manual Override and Duplex Gauge

    2. Without Manual Override and Duplex Gauge

    Foam Concentrate Supply Pressure Gauge

    Foam Concentrate Supply Valve

    The appropriate lengths of pipe and fittings to join these components into a single

    package called an In-Line Balanced Pressure Proportioning Module.

    CHAPTER 1 - INTRODUCTIONCHAPTER 1 - INTRODUCTIONCHAPTER 1 - INTRODUCTIONCHAPTER 1 - INTRODUCTIONCHAPTER 1 - INTRODUCTION

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    7/32

    CHAPTER 2 - INSTCHAPTER 2 - INSTCHAPTER 2 - INSTCHAPTER 2 - INSTCHAPTER 2 - INSTALLALLALLALLALLAAAAATIONTIONTIONTIONTION

    CAUTION:

    Install the In-Line Balanced Pressure Proportioning Module in accordance with instructions in this manVariations may affect performance or cause system failure.

    Customer modification or alteration of this equipment, or the use of replacement parts other than th

    specified by NF, may affect the performance of this equipment and may void the warranty.

    NOTE: National Foam recommends that those individuals charged with designing, installing, operating, testing

    maintaining a foam fire protection system, or the replacement of equipment and/or components of an exist

    system, refer to the appropriate authority having jurisdiction for compliance with applicable standard(s), cod

    and regulation(s) for that particular type of system and its components.

    NOTE: The design requirements for the foam equipment provided may or may not be based on specific des

    requirements provided to National Foam. Any changes to the area(s) of coverage or additions of other produ

    could exceed the design parameters of the foam equipment. Contact NF Engineering Dept. for questions regard

    changes to design.

    NOTE: READ ALL OPERATING INSTRUCTIONS BEFORE USING EQUIPMENT.

    It is the responsibility and duty of all personnel involved in the installation, operation, inspection

    maintenance, and refilling of this system to read and understand this entire manual before using

    equipment.

    NOTE: COMPONENTS FOR AN IN-LINE BALANCED PRESSURE PROPORTIONING SYSTEM

    Products manufactured by NF are warranted free of defects in materials and workmanship for twe

    months from the date of purchase. NF will pass on to the system owner, as far as it is able to do, the ben

    of the manufacturer's warranty for those parts and components not manufactured by NF.

    National Foam may supply components such as an ILBP Module, ratio controller, diaphragm va

    pump(s), gauges, controls etc. for use in new or refurbished in-l ine balanced pressure systems. NF ma

    no warranty, either expressed or implied and assumes no responsibility on the engineering and design

    such systems.

    12/98

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    8/32

    2-1. RECOMMENDED MATERIALS OF CONSTRUCTION

    NOTE:

    1. The following recommenations are for materials which will be in contact with the foam concentrates.

    2. Type 304 and 316 stainless steel includes "L" grades.

    CAUTION:

    Galvanized steel storage tanks or piping must never be used to contain any foam concentrates.

    2-2 12/98

    A. With Synthetic Based Polar Solvent/AFFF and

    Conventional AFFF Foam Concentrates

    1. Piping:

    Brass or Bronze (Note:All foam concen-

    trate lines on NF skid paks are Brass)

    Stainless Steel 304L or 316 grades High Density Polyethylene

    PVC

    Fiberglass with isophthalic based polyester

    and an internal layer (50-100 mils minimum)

    of vinyl ester resin in contact with foam

    concentrate

    2. Valves:

    Brass or Bronze. Cast brass valves fitted

    with stainless steel (304L or 316 grades) orbrass trim are acceptable. Teflon seats and

    packing are preferable for foam concentrate

    service. EPT (EPDM), Buna-N or Viton are

    also acceptable seal materials for use with

    NF foam concentrates.

    Stainless Steel 304L or 316 grades

    3. Storage Tanks:

    Stainless Steel 304L or 316 grades

    High Density Cross Linked Polyethylene

    Fiberglass with isophthalic based polyesterand an internal layer (50-100 mils minimum)

    of vinyl ester resin in contact with foam

    concentrate

    B. With Protein-Based Foam Concentrates

    1. Piping:

    Same materials as Synthetic Based Polar

    Solvent/AFFF and Conventional AFFF Foam

    Concentratewith the exception of stainless

    steel

    Black steel pipe and malleable iron fittings

    2. Valves:

    Brass or Bronze. Cast brass valves fitted

    with stainless steel (304L or 316 grades) or

    brass trim are acceptable. Teflon seats and

    packing are preferable for foam concentrate

    service. EPT (EPDM), Buna-N or Viton are

    also acceptable seal materials for use with

    NF foam concentrates.

    3. Storage Tanks:

    Steel

    Same materials as Synthetic Based Polar

    Solvent/AFFF and Conventional AFFF Foam

    Concentratewith the exception of stainless

    steel.

    INSTALLATION

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    9/32

    12/98

    ControllerPipeSize

    ManualOverride

    MaterialofConstruction-"B"Brass

    FoamConcentrate

    -P-Protein

    RatioControllerStyle-"W"WaferStyle

    -U-Universal

    -UG-UniversalGold

    "C"ContractorModel

    -A-AFFF

    P/

    A/U

    3%&6%

    1%,

    3%&6%

    1%&3%

    6%

    1%&3%

    6%

    19-9/16(497)

    19-1/4(489)

    18-7/8(479)

    21-7/8(556)

    22(559)

    23-3/8(594)

    9-3/4(248)

    10-1/8(257)

    11-1/8(283)

    11-9/16(294)

    12-1/4(311)

    12-9/16(319)

    1-1/2(38)

    1-1/2(38)

    1-1/2(38)

    2(51)

    2(51)

    2(51)

    1-3/16(30)

    1-7/32(31)

    1-5/8(41)

    1-5/8(41)

    1-3/4(44)

    1-3/4(44)

    1-11/16(43)

    1-31/32(50)

    2-3/8(60)

    2-3/8(60)

    2-1/2(64)

    2-1/2(64)

    4-13/16(122)

    8-1/32(204

    )

    10-3/8(264

    )

    10-3/8(264

    )

    11(279)

    11(279)

    19-3/4(502)

    20-1/8(511)

    21-1/8(537)

    21-15/16(557)

    22-11/16(576)

    22-11/16(576)

    3 4 6 6 *8 *8

    SPECIFICATIONS

    TABLEOFDIMENSIONS

    INCHES(MILLIMETERS)

    NOMINAL

    PIPE

    SIZE

    74(34)

    84(38)

    94(43)

    109(49)

    164(74)

    164(74)

    APPROX.

    WEIGHT

    LBS(KGS)

    A

    B

    C

    D

    G

    F

    E

    10.5

    (.72)

    19.5

    (1.3

    4)

    19.5

    (1.3

    4)

    19.5

    (1.3

    4)

    20(1.3

    7)

    20(1.3

    7)

    0.3

    (.02)

    0.3

    (.02)

    0.3

    (.02)

    0.3

    (.02)

    0.3

    (.02)

    0.3

    (.02)

    PRESSURELOSS**

    PSI(BAR)

    MIN.

    FLOW

    MAX.

    FLOW

    450(1703)

    1200(4542)

    2500(9463)

    2500(9463)

    5000(18927)

    *4000(15141)

    70(265)

    150(568)

    300(1136)

    300(1136)

    850(3218)

    850(3218)

    3%

    SY

    STEM

    SOLUTIONCAPACITIES**

    GPM

    (LPM)

    MINIMUM

    MAXIMUM

    FIGURE2-1

    IN-LINEBALANCEDPRESSUREPROPORTIONERMODULE

    MODELNUMBERIDENTIFICATION

    3

    B

    W

    C

    3

    *-8INCHPROPORTIONERRESTRICTEDTO4000GPM(15141LPM)FOR6%

    PROPORTIONING.

    **-ALLDATABASEDON3%

    PROPOR

    TIONING,

    FOR6%

    MULTIPLYBY1.1

    9.

    PERCENTAGE

    MOR

    MATERIALSOF

    CONSTRUCTION

    ComponentDescription

    Material

    DiaphragmValve

    Brass&StainlessSteel

    RatioController

    Brass

    BallValve

    Brass&StainlessSteel

    withTeflonSeals

    PipeandFittings

    Brass

    Hose

    BraidedStainlessSteel

    overTeflonTube

    "D"

    "A"

    "F"

    SOLUTION

    FLOW

    WATER

    FLOW

    "B"

    "C"

    FOAMCONCENTRATE

    INLETCONNECTION

    FOAMCONCENT

    RATE

    SUPPLYVALVE"V"

    (NORMALLYCLO

    SED)

    DIAPHRAGM

    BALANCING

    VALVE

    PRESSUREGAUGE

    BODY

    DRAINPLUG

    BUSHING

    CHECKVALVE

    150#ANSIBOLTED

    FLANGESBY

    OTHERS

    (SAMENOMINA

    LPIPESIZE

    ASRATIOCON

    TROLLER)

    SCH.

    40PIPINGBYOTHERS

    (SAMENOMINALSIZE

    ASRATIOCONTROLLER)

    WATERFLUSH-OUT

    VALVE"P"

    FOAM

    CONCENTRATE

    FLUSH-OUT

    VALVE"R"

    "G"

    (Ref.)

    "E"

    MAN

    UALOVERRIDEKNOB

    (N

    ORMALLYINFULLY

    OPENPOSITION)

    DUPLEXGAUG

    E

    DUPL

    EXGAUGE

    WATER

    FLUSH-OUT

    VA

    LVE"M"

    DU

    PLEXGAUGE

    FOAM

    CONCENTRATE

    FLUSH-OUTVALVE"N"

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    10/32

    "D"

    "A"

    "F"

    SOLUTION

    FLOW

    WATER

    FLOW

    "B"

    "C"

    FOAMCONCENTRATE

    INLETCONNECTION

    FO

    AMCONCENTRATESUPPLYVALVE"V"

    (NORMALLYCLOSED)

    DIAPHRAGMBALANCINGVALVE

    PRESSUREGAUGE

    BODY

    DRAINPLUG

    BUSHINGCHECKVALVE

    150#ANSIBOLTED

    FLANGESBYOTHERS

    (SA

    MENOMINALPIPESIZE

    ASRATIOCONTROLLER)

    SCH.40PIPINGBYOT

    HERS

    (SAMENOMINALSIZE

    ASRATIOCONTROLLER)

    WATERFLUSH-OUT

    VALVE"P"

    FOAM

    CONCENTRATE

    FLUSH-OUT

    VALVE"R"

    "G"

    (Ref.)

    "E"

    2-4 12/98

    ControllerPipeSize

    MaterialofConstruction-"B"

    Brass

    FoamConcentrate

    -P-Protein

    RatioControllerStyle-"W"W

    aferStyle

    -U-Universal

    -UG-UniversalGold

    "C"ContractorModel

    -A-AFFF

    PercentProportioning

    P/A/U

    3%

    &6%

    1%,3%&6%

    1%

    &3%

    6%

    1%

    &3%

    6%

    19-9/16(497)

    19-1/4(489)

    18-7/8(479)

    21-7/8(556)

    22(559)

    23-3/8(594)

    9-3/4(248)

    10-1/8(257)

    11-1/8(283)

    11-9/16(294)

    12-1/4(311)

    12-9/16(319)

    1-1/2(38)

    1-1/2(38)

    1-1/2(38)

    2(51)

    2(51)

    2(51)

    1-3/16(30)

    1-7/32(31)

    1-5/8(41)

    1-5/8(41)

    1-3/4(44)

    1-3/4(44)

    1-11/16(43)

    1-31/32(50)

    2-3/8(60)

    2-3/8(60)

    2-1/2(64)

    2-1/2(64)

    4-13/16(122)

    8-

    1/32(204)

    10

    -3/8(264)

    10

    -3/8(264)

    11(279)

    11(279)

    15-3/8(391)

    15-3/4(400)

    16-3/4(425)

    17-5/8(448)

    18-5/16(465)

    18-5/16(465)

    3466*8*8

    SPECIFICATIONS

    TABLEOFDIMENSIONS

    INCHES(MILLIMETERS)

    NOMINAL

    PIPE

    SIZE

    74(34)

    84(38)

    94(43)

    109(49)

    164(74)

    164(74)

    WEIGHT

    LBS(KGS)

    A

    B

    C

    D

    G

    F

    E

    10.5(.72)

    19.5(1.34)

    19.5(1.34)

    19.5(1.34)

    20(1.37)

    20(1.37)

    0.3(.02)

    0.3(.02)

    0.3(.02)

    0.3(.02)

    0.3(.02)

    0.3(.02)

    PRESSURELO

    SS**

    PSI(BAR)

    MIN.FLOW

    MAX

    .FLOW

    450(1703)

    1200(4542)

    2500(9463)

    2500(9463)

    5000(18927)

    *4000(15141)

    70(265)

    150

    (568)

    300(1136)

    300(1136)

    850(3218)

    850(3218)

    3%SYSTEM

    SOLUTIONCAPACITIES**

    GPM(LPM)

    MINIMUM

    MAXIMUM

    PERCENTAGE

    FIGURE2-2

    IN-LINEBALANCEDPRESSU

    REPROPORTIONERMODULE

    3"-8"WAFERSTYLEWIT

    HOUTMANUALOVERRIDE

    *-8INCHPROPORTIONERRESTRICTEDTO4000GPM(151

    41LPM)FOR6%

    PROPORTIONING.

    **-ALLDATABASEDON3%

    PROPORTIONING,FOR6%

    MUL

    TIPLYBY1.19.

    MATERIALSOFCONSTRUCTION

    ComponentDescription

    Material

    DiaphragmValve

    Brass&StainlessSteel

    RatioController

    Brass

    BallValve

    Brass&StainlessSteel

    withTeflonSeals

    PipeandFitting

    s

    Brass

    Hose

    BraidedStainlessSteel

    overTeflonTube

    MODELNUMBERIDENTIFICATION

    3

    B

    W

    C

    3

    2-1_2-2.P65(2/98

    )

    ILBP2-2.DSF

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    11/32

    12/98

    2-9/16(65)

    2(51)

    3(76)

    3-1/16(78)

    3-1/2(89)

    14(.97)

    10.5

    (.72)

    19.5

    (1.3

    4)

    19.5

    (1.3

    4)

    20(1.3

    7)

    2 3 4 6 8*

    SPECIFICATIONS

    *

    MINIMUM

    PRESSURELOSS**

    PSI(BAR)

    0.5.0

    3)

    0.3

    (.02)

    0.3

    (.02)

    0.3

    (.02)

    0.3

    (.02)

    TAB

    LEOFDIMENSIONS

    INCHES(MILLIMETERS)

    NOMINAL

    PIPE

    SIZE

    30(114)

    70(265)

    150(568)

    300(1136)

    850(3218)

    180(681)

    450(1703)

    1200(4542)

    2500(9463)

    *5000(18927)

    SOLUTIONCAPACITIES

    PSI(BAR)

    MINIMUM

    MAXIMUM

    75(34)

    90(41)

    110(50)

    145(66)

    220(100)

    MAXIMUM

    15-11/16(39

    8)

    16-1/4(413

    )

    15-1/4(387

    )

    18-11/16(47

    5)

    18-1/4(464

    )

    A

    B

    9-5/8(244)

    6-1/2(165)

    10(254)

    12-3/4(324)

    13-1/2(343)

    C

    D

    WEIGHT

    LBS(KGS)

    1-1/2NPT

    1-1/2NPT

    1-1/2NPT

    2NPT

    2NPT

    H

    G

    12(305)

    12(305)

    12(305)

    12-3/4(32

    4)

    12-3/4(32

    4)

    7-1/2(191)

    8(203)

    9-1/2(241)

    11(279)

    12-3/4(324)

    F

    19-3/4(502)

    20-1/2(521)

    22(559)

    23-3/4(603)

    26-1/4(667)

    E

    6"150#

    FLATFACE

    *-8INCHPROPORTIONERRESTRICTED

    TO4000GPM(15141LPM)FOR6%PROPORTIONING.

    **-ALLDATABASEDON3%INJECTION,

    FORPRESSURELOSSESFOR6%INJECTION

    ,MULTIPLYBY1.1

    9.

    FIGURE2-3

    I N L I N E B A L A N C E D P R E S S U R E P R O P O R T I O N E R M O D U L E

    RCF2-3.D

    SF

    RCF2-3.P

    65

    MATERIALSOFCONSTRUCTION

    ComponentDescription

    Material

    Diaphragm

    Valve

    Brass&StainlessSteel

    BallValve

    Brass&Teflon

    RatioController

    Brass

    Pipe

    Brass

    Pittings(Pipe)

    Brass

    Hose

    BraidedStainlessSteel

    3"150#

    FLATFACE

    4"150#

    FLATFACE

    8"150#

    FLATFACE

    2"150#

    FLATFACE

    DIAPHRAGMBALANCINGVALVE

    FOAMCONCENTRATE

    SUPPLY

    "H"

    F1/4

    WATER

    FLOW

    "D"FLANGE

    PERANSIB16.5

    SOLUTION

    FLOW

    E1/4

    DRAIN/FLUSH-OUT

    VALVES-TYPICAL

    5PLACES

    -DUPLEXGAUGE-

    REDNEEDLE-FOAM

    BLACKNEEDLE-WATER

    DUALSCALEENGLISH

    ANDMETRIC

    MANUALOVERRIDEHANDWHEEL

    (NORMALLYINFULLOPENPOS

    ITION)

    FOAMCONCENTRATESUPPLY

    VALVE"V"

    (NORMALLYCLOSED

    )

    PRESSUREGAUGE

    G1/4

    B

    C

    A1/4

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    12/32

    2-6 12/98

    2-2. INSTALLATION AND START-UP: ILBP MODULE

    CAUTION:

    For proper piping sizes contact NF Engineering Department.

    WARNING:

    In accordance with NFPA requirements for supervision of an Automated Foam Fire Protection System -

    manually operated valve(s) in the foam solution line from the proportioner to the discharge device(s) must be

    chained or locked in the open position or equipped with tamper alarm switch(es) which are monitored by a

    supervisory panel alarm.

    The major concern is the possibility that any manually operated valve(s) in the foam solution line to the

    hazard(s) could inadvertently be left in the closed position during a fire condition, which would prevent the foam

    solution from reaching the hazard(s) in the event of an automatic trip sequence.

    A. Off Loading:

    WARNING:

    Be sure the module is properly secured and balanced

    during any lifting or moving procedure. If the module

    is not properly secured in the lifting device, damage to

    the module or injury to personnel could result.

    1. To avoid damage, the module should be left in its

    shipping carton or crate until time of installation into

    foam system.

    2. Use a nylon lifting strap, secured around the ratio

    controller body, to move or mount the module.

    B. Installation:

    NOTE: Refer to Operating Schematic Drawing Fig. 3-1, 3-2 or 3-3.

    1. Mount the module on the water piping main and

    connect the foam concentrate supply piping to

    the module. ILBP modules can be mounted in

    either a horizontal or vertical orientation.

    2. All interconnecting piping to and from the ILBP

    Module (that is - foam concentrate supply pip-

    ing, watermain piping and foam solution piping)

    must be self-supporting so as to eliminate anyload on the module itself.

    3. To facilitate future service/removal of the ratio

    controller, the installer should provide a spool

    piece upstream of the ratio controller. See Chart

    below for minimum spool piece lengths.

    Ratio Controller Minimum Spool Length

    3" .......................................... 8" (203)

    4" ........................................ 10" (254)

    6" ........................................ 12" (305)

    8" ........................................ 14" (356)

    4. Each proportioner module requires 5 diameters of

    straight unobstructed upstream and downstream

    watermain piping to obtain proper flow through theratio controller.

    CAUTION:

    The ILBP Module requires a stable, uniform

    water flow at the inlet to the ratio controller to

    insure proper proportion ing during all rated

    flow conditions.

    INSTALLATION

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    13/32

    5. Regarding onlyRCF style ILBP modules:

    A check valve mustbe placed in the foam con-

    centrate line directly upstream of each

    proportioner module.

    6. Regarding only ILBP Module(s) that have adiaphragm valve with manual override capabil-

    ity: If the module is used with an Automatic

    Zone Foam Concentrate Supply Valve, the

    Manual Foam Concentrate Supply Valve "V" is

    still required for manual override pressure regu-

    lation. Refer to Operating Schematic Dwg. Fig.

    3-1 or Fig. 3-3 for valve locations and normal

    stand-by position.

    7. Cycle all valves to insure freedom of movement

    and that they open and close properly.

    8. For NF recommended components - valves,

    strainers, gauges and connections, and their lo-

    cation in the system, refer to the Operating

    Schematic Drawing Fig. 3-1, 3-2 or 3-3.

    12/98

    9. Check that the system is properly installed accord

    to design with all necessary valves, correct p

    sizes, discharge devices and discharge device lo

    tions, and is installed in compliance with local cod

    10. Hydrostatically test piping in accordance with pcedures outlined in the latest edition of the applica

    section of NFPA.

    11. Flush the foam concentrate piping before introd

    ing foam concentrate into the foam system.

    12. Follow the procedures outlined in Section 2-2.

    Installation, Item Nos. 7 and 8. Refer to Syst

    Flushing procedures outlined in Sect. 4-15.

    13. Place all valves to their normal stand-by positSee Normal Stand-By Valve Position Chart on O

    erating Schematic Dwg. Fig. 3-1, 3-2 or 3-3.

    14. Perform the applicable testing after installation p

    cedures as recommended by the latest edition

    NFPA 11.

    INSTALLAT

    C. Operating Requirements:

    1. Foam concentrate pressure to the ILBP Moduleinlet mustexceed water pressure inlet by at least

    30 psi (2.0 Bar) unless otherwise approved by

    NF Engineering Department.

    2. ILBP Module maximum working pressure - 200

    psi(13.7 Bar).

    3. Regarding only ILBP Module(s) that have a

    diaphragm valve with manual override capabil-

    ity:

    The Manual Override Handwheel on the

    diaphragm valve must be in the normal stand-

    by position for automatic balancing. To placthe normal stand-by position: rotate

    manual override handle in the counter-clo

    wise direction until fully open.

    Check the appropriate sensing line valv

    (Valves "J", "L" or "K") to insure that it is in

    proper stand-by position (Normally Open).

    4. Insure that all valves are in their normal stand

    posit ion before operating the proportioning syst

    See Normal Stand-By Valve Position Chart on O

    erating Schematic Dwg. Fig. 3-1, 3-2 or 3-3.

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    14/32

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    15/32

    12/98

    CHAPTER 3 - OPERACHAPTER 3 - OPERACHAPTER 3 - OPERACHAPTER 3 - OPERACHAPTER 3 - OPERATING PROCEDURESTING PROCEDURESTING PROCEDURESTING PROCEDURESTING PROCEDURES

    3-1. MINIMUM INLET PRESSURE REQUIREMENTS

    Since it is not uncommon for water inlet pressures to be quite low in some system applications, it is

    necessary to determine that the minimum proportioning system inlet pressure is adequate to allow

    proper system operation. The curves in Fig. 3-1 indicate the minimum inlet pressure required relative

    to the anticipated flow rate of the system. These curves apply to all proportioning systems which

    utilize National Foam Model RCT, RCF or RCW ratio controllers.

    FIGURE 3-1

    RATIO CONTROLLER MINIMUM INLET PRESSURE VS. SOLUTION FLOW CHART

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    16/32

    WATERSUPPLY

    WATER PUMP

    (IF REQUIRED)

    MAIN WATERSUPPLY VALVE

    SEE NOTE NO. 3

    FOAMSOLUTION

    V

    SEE NOTE NO. 2

    M

    N

    L

    R P

    P

    D

    ILBP MODULE

    SCHEMATIC

    - TYPICAL -

    SEE NOTE NO. 1

    MANUAL OVERRIDEHANDWHEEL

    BODYDRAIN

    PLUG

    FOAM

    CONCENTRATESUPPLY

    3-2 12/98

    NOTES:

    The schematics show n are typical installations andmay not reflect actual equipment furnished.

    1. Valve "V" - NormallyCLOSED for systems usingno automatic foam concentrate valve(s).

    - Normally OPENfor systems using an

    automatic foam concentrate valve(s).

    2. Position of Zone Foam Concentrate Valve.

    Automatic valve optional.

    3. Position of Zone Water Supply Valve.

    Automatic valve optional.Manual valve required if automatic valve not supplied.

    FIG. 3-2 OPERATING SCHEMATIC DRAWING

    MOD3-1.DSF

    LGND3-1.DSF

    LEGEND

    POSITION

    VALVE DESCRIPTION DESIGNATION MANUAL AUTO.WATER SENSING LINE SHUT-OFF VALVE L OPEN OPEN

    TO DIAPHRAGM VALVE

    DUPLEX GAUGE WATER FLUSH-OUT M CLOSED CLOSED

    DUPLEX GAUGE FOAM CONC. FLUSH-OUT N CLOSED CLOSED

    DIAPHRAGM VALVE WATER FLUSH-OUT P CLOSED CLOSED

    DIAPHRAGM VALVE CONC. FLUSH-OUT R CLOSED OPEN

    FOAM CONCENTRATE SUPPLY VALVE V CLOSED OPEN

    BODY DRAIN PLUG CLOSED CLOSED

    NORMAL STAND-BY VALVE POSITION CHARTRCW IN-LINE BALANCED PRESSURE PROPORTIONING MODULE W/MOR

    FIG. 3-2 OPERATING SCHEMATIC DRAWING

    RCW ILBP MODULE WITH MANUAL OVERRIDE

    P

    D

    FOAM CONCENTRATE LINE

    SENSING LINE

    WATER LINE

    RCW RATIO CONTROLLER

    BALL VALVE (N.O.)

    BALL VALVE (N.C.)

    AUTOMATED VALVE W/MANUALOVERRIDE

    DUPLEX GAUGE

    PRESSURE GAUGE

    DIAPHRAGM VALVE

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    17/32

    WATERSUPPLY

    WATER PUMP(IF REQUIRED)

    MAIN WATERSUPPLY VALVE

    SEE NOTE NO. 3

    FOAMSOLUTION

    V

    SEE NOTE NO. 2

    R P

    P

    ILBP MODULE

    SCHEMATIC

    - TYPICAL -

    SEE NOTE NO. 1

    BODYDRAINPLUG

    FOAM

    CONCENTRATESUPPLY

    12/98

    FIG. 3-3 OPERATING SCHEMATIC DRAW

    MOD3-2.DSF

    LGND3-2.DSF

    NOTES:

    The schematics show n are typical installations and

    may not reflect actual equipment furnished.

    1. Valve "V" - Normally CLOSEDfor systems using

    no automatic foam concentrate valve(s).- Normally OPENfor systems using an

    automatic foam concentrate valve(s).

    2. Position of Zone Foam Concentrate Valve.Automatic valve optional.

    3. Position of Zone Water Supply Valve.

    Automatic valve optional.

    Manual valve required if automatic valve not supplied.

    POSITION

    VALVE DESCRIPTION DESIGNATION MANUAL AUTO.DIAPHRAGM VALVE WATER FLUSH-OUT P CLOSED CLOSED

    DIAPHRAGM VALVE CONC. FLUSH-OUT R CLOSED OPEN

    FOAM CONCENTRATE SUPPLY VALVE V CLOSED OPEN

    BODY DRAIN PLUG CLOSED CLOSED

    NORMAL STAND-BY VALVE POSITION CHARTRCW IN-LINE BALANCED PRESSURE PROPORTIONING MODULE WITHOUT/MORLEGEND

    FIG. 3-3 OPERATING SCHEMATIC DRAWING

    RCW ILBP MODULE WITHOUT MANUAL OVERRIDE

    P

    FOAM CONCENTRATE LINE

    SENSING LINE

    WATER LINE

    RCW RATIO CONTROLLER

    BALL VALVE (N.O.)

    BALL VALVE (N.C.)

    AUTOMATED VALVE W/MANUALOVERRIDE

    PRESSURE GAUGE

    DIAPHRAGM VALVE

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    18/32

    WATERSUPPLY

    WATER PUMP(IF REQUIRED)

    MAIN WATERSUPPLY VALVE

    SEE NOTE NO. 3

    FOAMSOLUTION J

    V

    SEE NOTE NO. 2

    W

    K

    M

    N

    L

    R P

    P

    D

    ILBP MODULE

    SCHEMATIC

    - TYPICAL -

    SEE NOTE NO. 4

    SEE NOTE NO. 1

    MANUAL OVERRIDEHANDWHEEL

    FOAM

    CONCENTRATESUPPLY

    3-4 12/98

    FIG. 3-4 OPERATING SCHEMATIC DRAWING

    RCF ILBP MODULE WITH MANUAL OVERRIDE

    FIG. 3-4 OPERATING SCHEMATIC DRAWING

    MOD3-3.DSF

    LGND3-3.DSF

    NOTES:

    The schematics sho wn are typical installations andmay not reflect actual equipment furnished.

    1. Valve "V" - Normally CLOSEDfor systems usingno automatic foam concentrate valve(s).

    - Normally OPENfor systems using an

    automatic foam concentrate valve(s).

    2. Position of Zone Foam Concentrate Valve.

    Automatic valve optional.

    3. Position of Zone Water Supply Valve.

    Automatic valve optional.Manual valve required if automatic valve not supplied.

    4. A check valve must be installed in the foam concentrateline directly upstream of each proportioner module.

    POSITION

    VALVE DESCRIPTION DESIGNATION MANUAL AUTO.WATER SENSING LINE SUPPLY VALVE J OPEN OPEN

    WATER SENSING LINE SHUT-OFF VALVE L OPEN OPEN

    TO DIAPHRAGM VALVE

    FOAM CONCENTRATE SENSING LINE K OPEN OPEN

    SHUT-OFF VALVE TO DIAPHRAGM VALVE

    DUPLEX GAUGE WATER FLUSH-OUT M CLOSED CLOSED

    DUPLEX GAUGE FOAM CONC. FLUSH-OUT N CLOSED CLOSED

    DIAPHRAGM VALVE WATER FLUSH-OUT P CLOSED CLOSED

    DIAPHRAGM VALVE CONC. FLUSH-OUT R CLOSED OPEN

    FOAM CONCENTRATE SUPPLY VALVE V CLOSED OPEN

    LOWER PETCOCK ON DIAPHRAGM VALVE W CLOSED CLOSED

    NORMAL STAND-BY VALVE POSITION CHARTRCF IN-LINE BALANCED PRESSURE PROPORTIONING MODULE W/MORLEGEND

    P

    D

    FOAM CONCENTRATE LINE

    SENSING LINE

    WATER LINE

    RCF RATIO CONTROLLER

    BALL VALVE (N.O.)

    BALL VALVE (N.C.)

    AUTOMATED VALVE W/MANUALOVERRIDE

    CHECK VALVE

    DUPLEX GAUGE

    PRESSURE GAUGE

    DIAPHRAGM VALVE

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    19/32

    12/98

    3-2. ILBP MODULE OPERATION

    NOTE: Refer to Operating Schematic Drawing Fig. 3-

    2, 3-3 or 3-4 for valve location, designation

    and normal stand-by position.

    1. Verify that all valves on the proportioning system

    are in their normal stand-by position.

    2. Start water pump (if required).

    3. Start foam concentrate pump.

    4. If applicable - Set the desired percentage on the

    metering valve(s) at the appropriate ILBP Module(s).

    NOTE: The metering valve is for regulating the

    foam concentrate injection (percentage) into the sys-

    tem only, and does not have shut-off capability. For

    posit ive foam concentrate shut-off, a separate valve

    must be used along with the metering valve.

    5. Open water supply valve to the desired ILBP

    module(s).

    6. Open foam concentrate supply Valve "V" to

    desired ILBP module(s).

    7. Open any required zone valves downstream of

    desired ILBP module(s).

    8 . Regarding only ILBP Module(s) that have a d

    phragm valve with manual override capability:

    Verify that pointers on the duplex gauge

    balancing; if not, follow procedures in Sect.3

    ILBP Module Manual Override (Manual Re

    lation).

    9. Observe the discharge pressure gauge at the fo

    concentrate pump discharge to insure that the sys

    is operating at design pressure. If system is

    operating at design pressure, refer to the sys

    manual regulation section of the foam concent

    pump system operating and maintenance manua

    the foam concentrate pump system is provided

    NF, refer O. & M. Manual part number 1298-99

    2, Sect. 3-3.B., Pump and Pressure Sustaining Va

    Module.

    3-3. ILBP MODULE MANUAL OVERRRIDE (MANUAL REGULATION)

    NOTE: The instructions below, apply only to ILBP Module Diaphragm Valves with manual

    override capability. These instructions donotapply to Diaphragm Valves which do not

    have manual overrride capability.

    NOTE: Used onlywhen system will not balance automatically.

    4. Turn manual override knob clockwise until it c

    tacts a stop and will not travel further.

    5. Slowly open foam concentrate supply Valve

    until duplex gauge indicates system balance. K

    adjusting valve as required to maintain system b

    ance.

    1. Close foam concentrate supply Valve "V".

    2. Close water sensing shutoff Valve "L".

    3. Verify adequate foam concentrate pressure on foam

    concentrate supply pressure gauge.

    OPERATING PROCEDUR

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    20/32

    3-6 12/98

    3-4. SHUTDOWN

    1. Shut down the foam concentrate pump.

    2. Close the foam concentrate supply Valve "V" at the

    ILBP module(s) being operated.

    WARNING:

    Only after the fire is out and the danger of reignition

    has passed, shall consideration be given to flushing

    and draining the system. Follow the appropriate

    Flushing Instructions which follow in this manual

    after it is determined that it would be safe to flush

    and drain the system.

    3. Flush the foam solution system.

    NOTE: If the system has a water powered foam

    concentrate supply Valve "V", the cylinder water

    pressure supply valve in the water line supplying

    pressure to the water powered ball valve operating

    cylinder mustbe closed before any flushing opera-

    tion.

    a. Make sure Valve "V" at the ILBP module(s)

    being operated is closed.

    b. Flow water through the system and allow water

    to run until clean clear water issues from the

    output devices that were operated.

    c. Close the water supply valve(s). Shut off water

    supply.

    4. Return all valves to their normal stand-by position.

    See Normal Stand-by Valve Position Chart on

    Operating Schematic Dwg. Fig. 3-2, 3-3 or 3-4.

    5. Replenish supply of foam concentrate. If the tank is

    empty, it shall be inspected to determine if cleaning

    is warranted before refilling. If cleaning is judged

    necessary, refer to manufacturer's instructions. If

    storage tank is provided by NF - refer to NF Storage

    Tank Installation, Cleaning & Filling Instruction

    Manual P/N: 1298-9933-7 for recommendations.

    CAUTION:

    Only foam concentrate of the type listed on the

    tank nameplate shall be used to replenish the tank.

    Mixing of different types or brands of foam

    concentrate could cause failure of the system.

    6. Replace all frangible components such as glass dia-

    phragms, rupture discs, etc. , in foam lines or foam

    making devices.

    OPERATING PROCEDURES

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    21/32

    CHAPTER 4 - INSPECTION AND MAINTENANCECHAPTER 4 - INSPECTION AND MAINTENANCECHAPTER 4 - INSPECTION AND MAINTENANCECHAPTER 4 - INSPECTION AND MAINTENANCECHAPTER 4 - INSPECTION AND MAINTENANCE

    4-1. INSPECTION AND MAINTENANCE

    See Table 4-1 for recommended inspection and maintenance procedures. These procedures and

    recommended intervals are based on normal operating conditions and may have to be modified to meet

    the existing conditions.

    WARNING:

    The intervals in this chapter are a general recommendation; some environmental conditions

    may dictate such inspections and maintenance be performed at more frequent intervals.

    For various proportioning system components (diaphragm valve, foam concentrate pump, valves,

    actuators etc.) refer to that particular component's operating and maintenance manual or instruction

    sheet for inspection and maintenance procedures.

    4-2. TESTING AFTER SYSTEM MAINTENANCE

    If during the course of normal system maintenance it becomes necessary to replace, repair or modify

    system components, component parts, operating devices or equipment, the system must be tested to

    insure proper operation before being placed back into service.

    4-3. ANNUAL TESTING

    At least annually, all foam systems shall be thoroughly inspected and checked for proper operation.

    This shall include performance evaluation of the foam concentrate or premix solution quality or both.Deviation of results exceeding 10 percent from those recorded in acceptance testing shall be discussed

    immediately with the manufacturer. Regular service contracts are recommended. The goal of this

    inspection and testing shall be to ensure that the system is in full operating condition, and that it will

    remain in that condition until the next inspection. The inspection report, with recommendations, shall

    be filed with the owner. Between the regular service contract inspections or tests, the system shall

    be inspected by competent personnel following an approved schedule.

    6/00

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    22/32

    TABLE 4-1 - RECOMMENDED INSPECTION & MAINTENANCE SCHEDULE

    WARNING:

    The following recommendations are based on normal operating conditions. Due to environmental or

    other conditions unique to your system, the frequency of some inspecton and maintenance procedures

    may need to be adjusted. Additional inspection and maintenance procedures may also be required.

    NOTE: When performing inspection and maintence procedures which:

    a. require operation of the system or parts of the system,

    b. cause the system to be non-operational during the procedure,

    c. cause a trouble indication,

    the system should be taken out of service and the proper authorities should be notified.

    DESCRIPTION OTHERSEMI-

    ANNUALMONTHLYWEEKLY

    AFTER

    OPERATION

    START

    UP

    AFTER

    ALL

    MAINT.

    PROCEDURES

    ANNUAL

    4-2 12/98

    INSPECTION & MAINTENANCE

    4-4. GENERAL

    1. Check all valves to insure that they are in the

    normal stand-byposition. See Operating

    Schematic Dwg. Fig. 3-2, 3-3 or 3-4.

    2. Check that Manual Override Handwheel is in the

    normal stand-by position for automatic

    balancing. Refer to Sect. 2-2.C., item 3.

    3. Inspect system for physical damage and repair.

    4. Check the complete module, all valves, fittings

    & connections for leakage.

    5. Cycle manual valves where practical.

    6. Check flange bolts for tightness.

    7. Perform system testing after installation as

    described in the latest edition of NFPA 11.

    8. Check module for any external damage to the

    paint surfaces.

    4-5. WATER POWERED BALL VALVES

    1. Cycle the valve(s) either manually or thru control

    panel. If applicable,cycle the valve(s) using the

    solenoid release.

    WARNING:

    When water powered ball valves are cycled,

    Valve "V" must be closed.

    2. Check supervision of circuit if solenoid release

    is provided.

    3. Make sure that the quick release pin is securely

    positioned thru the clevis.

    4. Make sure the drain/vent valve is fully closed.

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    23/32

    INSPECTION & MAINTENAN

    TABLE 4-1 - RECOMMENDED INSPECTION & MAINTENANCE SCHEDULE

    DESCRIPTION OTHESEMI-

    ANNUALMONTHLYWEEKLYAFTER

    OPERATION

    START

    UP ANNUAL

    12/98

    4-6. ELECTRICALLY ACTUATED VALVES

    1. Cycle valve(s) - Valve(s) may be cycled from

    control panel or by manual override at valve.

    WARNING:

    When automated foam concentrate valves

    are cycled, Valve "V" must be closed.

    When automated valves are cycled, the

    main water supply valve must be closed.

    2. Cycle valve(s) from the control panel to insure

    proper operation from control.

    3. Check supervision of control circuit.

    4. Check for leakage past valve seat.

    4-7. CONTROL SYSTEM

    1. Check that proper indicators are present. See

    control panel data.

    2. Check supervision of all circuits.

    3. Check alarm operation.

    4. Check system operation. See control panel data.

    5. Check that all indicators illuminate.

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    24/32

    INSPECTION & MAINTENANCE - FLUSHING

    4-4 12/98

    4-8. FLUSHING - ILBP MODULE

    NOTE: Flushing of the ILBP Module is to be done at Module installation into the system, prior to

    refilling a depleted tank, changing type of foam concentrate, or if the foam concentrate piping has to

    be broken for repairs. Flushing is nota normal shutdown procedure and is not necessary after ILBP

    Module operation.

    A. ILBP Module with

    Diaphragm Valve Manual Override Capability:

    1. Open all ILBP Module sensing line drains and

    flush-out points (Valves M, N, P, R and W).

    2. Turn manual override knob down (clockwise)

    until it contacts stop.

    3. Close Foam Concentrate Supply Valve "V" on

    the ILBP Module.

    4. The ILBP Module will be flushed thru the foam

    solution piping. Flushing must be done thru zone

    discharge devices or thru foam solution piping

    drains (with zone foam solution discharge valves

    closed).

    5. Establish a water flow thru the foam concentrate

    system until the water flows clear at all flush

    points and drains.

    NOTE: Flushing of the ILBP Module can be

    performed at system shutdown when flowing

    water thru the system. Refer to Sect. 3-4., Shut-

    down, for correct procedures.

    6. After the water runs clear, shut off water supply

    then drain the ILBP Module and zone piping.

    NOTE: Remove diaphragm valve body drain

    plug.

    7. Turn manual override knob up (counter-clock-

    wise) until it contacts stop for normal automatic

    balancing operation.

    8. Return all valves to their normal stand-by posi-

    tion (reinstall diaphragm valve body drain plug).

    Refer to Normal Stand-By Valve Position Chart

    on Operating Schematic Dwg. Fig. 3-2 or 3-4.

    B. ILBP Module without

    Diaphragm Valve Manual Override Capability:

    1. Open all ILBP Module drains, flush-out points

    (Valves P and R).

    2. Close Foam Concentrate Supply Valve "V" on

    the ILBP Module.

    3. The ILBP Module will be flushed thru the foamsolution piping. Flushing must be done thru zone

    discharge devices or thru foam solution piping

    drains (with zone foam solution discharge valves

    closed).

    4. Establish a water flow thru the foam concentrate

    system until the water flows clear at all flush

    points and drains.

    NOTE: Flushing of the ILBP Module can be

    performed at system shutdown when flowingwater thru the system. Refer to Sect. 3-4., Shut-

    down, for correct procedures.

    5. After the water runs clear, shut off water supply

    then drain the ILBP Module and zone piping.

    NOTE: Remove diaphragm valve body drain

    plug.

    6. Return all valves to their normal stand-by posi-

    tion (reinstall body drain plug). Refer to NormalStand-By Valve Position Chart on Operating

    Schematic Dwg. Fig. 3-3.

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    25/32

    5-2. No Automatic Foam Concentrate Zone Valve Check that wiring is installed to actuator.

    Proportioning Closed.(Electrically actuated)

    Check that signal from control system isavailable at valve actuator. If voltage is not

    present, check control system.

    If signal is present at actuator, use manual

    override to cycle valve. If valve cycles manu

    ally, then valve actuator is probably bad.

    Remove actuator, check operation, if bad,

    repair or replace. If valve does not open,

    using manual override on actuator, then the

    valve is jammed. Remove valve, determine

    and correct reason for jam. See actuator dat

    Automatic valve actuator does not function See manufacturers troubleshooting data.

    properly.(Electric or hydraulic actuation)

    Automatic Foam Concentrate Zone Valve Check that cylinder water pressure supply

    Closed.(Water Powered Ball Valve) valve is fully open.

    Check that quick release pull pin is not

    removed from clevis. Reinsert pin thru

    clevis and valve handle.

    12/98

    PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION

    TABLE 5-1 TROUBLESHOOTING

    CHAPTER 5 - TROUBLESHOOTINGCHAPTER 5 - TROUBLESHOOTINGCHAPTER 5 - TROUBLESHOOTINGCHAPTER 5 - TROUBLESHOOTINGCHAPTER 5 - TROUBLESHOOTING

    5-1. TROUBLESHOOTING

    See Table 5-1 for Troubleshooting Problems, Possible Causes and Corrective Actions. These procedu

    cover problems that may be experienced during normal operations. Although these recommendations co

    most problems that are experienced there are some situations that may occur which are not covered in th

    instructions. Please contact National Foam's Engineering Department for problems that cannot be resol

    thru the use of this manual.

    NOTE: Refer to individual instruction manuals or sheets for additional information on system compone

    and discharge devices.

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    26/32

    No Proportioning Check Drain/Vent valve on strainer for clog-continued ging which shuts off water supply to cylinder.

    Open Drain/Vent valve on strainer, vent andflush any debris blocking water supply.

    Diaphragm Valve Foam Concentrate Flush- If provided, duplex gauge will show foamOut Valve "R" open or partially open. concentrate pressure lower than water

    pressure. Check to insure all flush valvesare closed.

    Drain valve(s) or connection(s) in foam If provided, duplex gauge will show foamconcentrate piping open or partially open. concentrate pressure lower than water

    pressure. Check to insure all drain valvesare closed.

    Control system not functioning properly. Check wiring for correct interconnection andproper connections. See control systemmanual.

    Concentrate not compatible with the system. Use correct concentrate. Drain and cleantank before filling with new concentrate.

    Ratio controller operating below minimum Increase water pressure. Contact NFinlet pressure. Engineering Dept. for recommendations.

    Refer to Fig. 3-1, Minimum Inlet Pres. Req.

    Foam concentrate storage tank empty. Fill tank. Refer to NF Storage Tank Instruc-tion Manual, P/N: 1298-9933-7.

    5-3. Low Foam Concentrate Discharge Valve "D" and/ Fully open valve(s). If more than one ILBPPercent of or Foam Concentrate Supply Valve "V" Module is supplied by the foam concentrateProportioning partially closed. main, be sure Valve(s) "V" or zone valve(s)

    of ILBP Module(s) not required, are closed.

    Foam Concentrate Zone Valve(s) not fully Fully open valve. Determine cause andopen. correct.

    Automatic Foam Concentrate Zone Valve Cylinder water pressure supply valveopens slowly.(Water powered ball valve) partially open. Fully open valve.

    Tighten Drain/Vent valve on cylinder strainer.Snug with wrench to insure closure to ratedpressure.

    Drain/Vent valve clogged, obstructing watersupply to cylinder. Open Drain/Vent valve onstrainer and vent. Flush any debris blocking

    water supply.

    5-2 12/98

    PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION

    TABLE 5-1 TROUBLESHOOTING

    TROUBLESHOOTING

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    27/32

    Low Percent of Water pressure exceeds the design limits of Adjust pressure to proportioner to be within

    Proportioning the system. System requires more capacity the flow and pressure limits of the system.continued than pump is capable of producing.

    Drain valves in foam concentrate piping Check to insure all drain valves are closed.

    open or partially open. If provided, duplexgauge will show foam concentrate pressure

    lower than water pressure.

    Control system not functioning properly. See control system manual. Check wiring focorrect interconnection.

    Check wiring for proper connections.

    Diaphragm valve not functioning properly. Check water sensing lines for blockage.

    If provided, duplex gauge will not show Make sure that there are no air pockets inbalance. water sensing lines.

    Diaphragm Valve Water Flush-Out "P" open. Fully close flush-out valve.

    Foam concentrate incompatible with system Use only foam concentrates the system was

    design. designed for. Contact NF Engineering Deptif you desire to change foam concentrates.

    Incorrect orifice diameter or adjustment. Contact NF Engineering Dept. for instructio

    on checking orifice and adjustment settings.

    Water flow too high. Exceeds capability Too many discharge devices in operation orof foam concentrate pump. pressure too high. Check design and correct

    to stay within limits of system.

    Ratio controller operating below minimum Increase water pressure. Contact NFinlet pressure. Engineering Dept. for recommendations.

    Refer to Fig. 3-5, Minimum Inlet Pres. Req.

    5-4. High Diaphragm valve not functioning properly. Check foam concentrate sensing lines for

    Percent of If provided, duplex gauge will not show blockage. Make sure that there are no air

    Proportioning balance. pockets in foam concentrate sensing lines.

    Foam concentrate sensing line blocked. Remove line and clear blockage.

    Diaphragm Valve Foam Concentrate Fully close flush-out valve.

    Flush-Out Valve "R" open.

    Foam concentrate incompatible with system Use only foam concentrate the system wasdesign. designed for. Contact NF Engineering Dept

    if you desire to change foam concentrates.

    12/98

    PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION

    TABLE 5-1 TROUBLESHOOTING

    TROUBLESHOOT

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    28/32

    High Percent of Incorrect orifice diameter or adjustment. Contact NF Engineering Dept. for instructions

    Proportioning on checking orifice and adjustment settings.continued

    Water flow too low for ratio controller. Check system pressure. If low, find and

    correct problem.

    Blockage in solution line or valves not

    completely open. Check solution line and

    correct.

    Discharge device blocked. Check devices

    and correct problem.

    5-5. No Flow Water supply valve closed. Open valve. If automated, find reason and

    at Discharge correct.

    Device(s)

    Fire pump did not start. Determine the cause and correct the problem.

    Blockage in the water supply or foam Find the cause of the blockage and correct.

    solution discharge line.

    Manual valves in solution piping shut or Check line for blockage or open manual

    blockage in line. valves.

    5-6. Low Flow System pressure too low. Check inlet pressure and correct for proper

    atDischarge operation.

    Device(S)

    Fire pumps did not start. Determine reason and correct.

    Partial blockage in water or foam solution line. Find blockage and remove.

    Zone valve did not open completely. Valve jammed, determine reason and correct.

    5-7. No Power failure. Check power source and correct problem.

    Operation

    Control system not functioning properly. Check wiring for correct interconnection and

    proper connections. See control system

    manual.

    Foam concentrate storage tank empty. Fill tank.

    Failure of water supply system. Check water supply and correct problem.

    5-4 12/98

    PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION

    TABLE 5-1 TROUBLESHOOTING

    TROUBLESHOOTING

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    29/32

    APPENDIX - FAPPENDIX - FAPPENDIX - FAPPENDIX - FAPPENDIX - FACTORACTORACTORACTORACTORY MUTUY MUTUY MUTUY MUTUY MUTUAL APPROAL APPROAL APPROAL APPROAL APPROVVVVVALSALSALSALSALS

    A-1. Universal Gold - 3% Alcohol Resistent AFFF

    A. In-Line Balanced Pressure Proportioning Systems:

    1. ILBP Proportioner Models - for flow ranges seeFactory Mutual Approval Guide:

    4" BWC3 - UG

    4" BWC3 - UG-MOR

    6" BWC3 - UG

    6" BWC3 - UG-MOR

    B. Foam Discharge Devices:

    1. Sprinklers - listed by the fuel group for whichthey are approved (for application rates seeFactory Mutual Approval Guide):

    a. Alcohols

    Viking Model M17/32" Upright

    Viking Model M1/2" Upright

    Grinnell Model F9501/2" Upright and Pendent

    b. Ketones

    Viking Model M17/32" Upright

    Viking Model M

    1/2" Upright Grinnell Model F950

    1/2" Upright and Pendent

    c. Esters

    Viking Model M17/32" Upright

    Viking Model M

    1/2" Upright

    Grinnell Model F950

    1/2" Upright and Pendent

    d. Ethers

    Viking Model M17/32" Upright and Pendent

    Viking Model M1/2" Upright

    Grinnell Model F9501/2" Upright and Pendent

    e. Hydrocarbons

    Viking Model M17/32" Large Orifice Upright

    Viking Model M1/2" Upright

    Grinnell Model F9501/2" Upright and Pendent

    Grinnell Model B-1

    Foam/Water3/8" Orifice Pendent

    2. Nozzles

    Model JS-10

    Model JS-10B

    Model PC-31A

    3. Foam Chambers

    MCS-9 Type A

    MCS-17 Type A

    MCS-33 Type A

    MCS-55 Type A

    A-2. Aer-O-Lite - 3% AFFF

    A. In-Line Balanced Pressure Proportioning Systems

    1. ILBP Proportioner Models - for flow ranges seFactory Mutual Approval Guide:

    4" BWC3 - A 4" BWC3 - A-MOR 6" BWC3 - A 6" BWC3 - A-MOR

    Factory Mutual Research and Engineering is a non-profit independent research and testing organization. FM testsand approves a wide variety of equipment, materials and services related to fire safety.

    Each year FM publishes an Approval Guide listing all approved equipment, materials and services. This guide givesdetailed information on the approved products, as well as the operational parameters of the approval. In the case offoam proportioning systems, the parameters are the minimum and maximum foam solution flows and the foamconcentrates for which the proportioner is approved.

    The following foam concentrates, along with the particular In-Line Balanced Pressure (ILBP) Proportioning Systemcomponents and discharge device(s) listed under the foam concentrate, constitute an FM Approved foam system. Anapproved system must consist of a foam concentrate, ILBP Proportioning system and discharge device(s).

    12/98

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    30/32

    APPENDIX - FACTORY MUTUAL APPROVALS CONTINUEDAPPENDIX - FACTORY MUTUAL APPROVALS CONTINUEDAPPENDIX - FACTORY MUTUAL APPROVALS CONTINUEDAPPENDIX - FACTORY MUTUAL APPROVALS CONTINUEDAPPENDIX - FACTORY MUTUAL APPROVALS CONTINUED

    B. Foam Discharge Devices:

    1. Water Powered Oscillating Monitors:

    Model HOM-2B-NA 100

    Model HOM-2B-NA 200

    Model HOM-2B-NA 300

    Model HOM-2B-NA 400

    Model HOM-2B-NA 500

    Model HOM-4A-NA 1000

    2. Sprinklers - for hydrocarbons only:

    Viking Model M17/32" Upright

    Viking Model M

    1/2" Upright

    Grinnell Model F9501/2" Upright and Pendent

    A-3. Aer-O-Water 3EM -3% AFFF

    A. In-Line Balanced Pressure Proportioning Systems:

    1. ILBP Proportioner Models - for flow ranges seeFactory Mutual Approval Guide:

    4" BWC3 - A

    4" BWC3 - A-MOR

    6" BWC3 - A

    6" BWC3 - A-MOR

    B. Foam Discharge Devices:

    1. Water Powered Oscillating Monitor:

    Model HOM-2B-NA 100

    Model HOM-2B-NA 200

    Model HOM-2B-NA 300

    Model HOM-2B-NA 400

    Model HOM-2B-NA 500

    Model HOM-4A-NA 1000

    2. Nozzles:

    Model JS-10

    Model JS-10B

    3. Sprinklers:

    Central Model A1/2" Upright and Pendent

    Grinnell F9501/2" Upright and Pendent

    A-2 12/98

    APPENDIX - FACTORY MUTUAL APPROVALS

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    31/32

    NOTES

  • 5/23/2018 ILBP-Module_1298-9940-8_RevB

    32/32

    FOAM SOLUTION PROFESSIONALS

    180 Sheree Bou levard , Suite 3900 P.O. Box 695 Exton , PA 19341-0695 USA

    Telephone: 610-363-1400 Fax: 610-524-9073

    www.Kidde-Fire.com

    NaNaNaNaNational Ftional Ftional Ftional Ftional Foamoamoamoamoam