IEEE-IAS 2012.02.18 Presentation - Sprinkler Systems and Fire Pump Applications
IEEE-IAS 2012.02.18 Presentation - Fire Pump Engines
-
Upload
james-s-nasby -
Category
Technology
-
view
1.268 -
download
1
description
Transcript of IEEE-IAS 2012.02.18 Presentation - Fire Pump Engines
Diesel Fire Pump Engines
- for -
F.M. Approvals- by -
James S. Nasby
Columbia Engineering
C.E. IEEE-IAS 2
Topics to be Covered Constant (Variable) Speed Engines PLD Variable Speed Engines Electronic ECM (ECU) Engines Electrical Components Operating Environment Design Parameters Testing & Evaluation Installation Considerations
C.E. IEEE-IAS 3
U.L. Listed Fire Pump Engines
Caterpillar (Energize to Stop)
Clarke Cummins Also U.L. Listed - A/O 2012.02.07: Deutz Kirloskar Oil Engines Ltd National Fire Fighting Mfg Fz Co
Although designed to run at a Fixed Speed, NFPA-20 considers all engines to be variable speed devices by nature of the speed governor and also for overspeed (overpressure) considerations. E.g.: Main Pressure Relief Valve always required.
C.E. IEEE-IAS 4
F.M. Approved Fire Pump Engines
Caterpillar (Energize to Stop)
Clarke Cummins Also F. M. Approved - A/O 2012.02.07
Kirloskar Oil Engines Ltd Deutz Corp Olympiaweg AGCO SISU POWER
C.E. IEEE-IAS 5
Cummins NT & VT Series, Historic
C.E. IEEE-IAS 6
Caterpillar External Diagram
C.E. IEEE-IAS 7
Cummins ECM (ECU) Engine
C.E. IEEE-IAS 8
Clarke Engine w/ Dual Starters
C.E. IEEE-IAS 9
PLD Variable Speed Engines
Clarke PLD Pressure Limiting Driver.
Original design was a hydraulic closed loop (feedback) system which compares the pump output pressure to a spring force by was of a hydraulic cylinder. The cylinder operates to vary the speed governor set point. This mechanical system will become obsolete when mechanical governors become obsolete. This had only a few factory set pressure set points.
Their newer design is based on an electronic PD or PID loop coupled to the engine speed governor ECM (ECU).
C.E. IEEE-IAS 10
Clarke PLD Engine
C.E. IEEE-IAS 11
Electrical Components Batteries Gages Contactors (Two) Valves – Not all are Manual Operable
Single Coil Dual Coil (Energized During Cranking)
Speed Control Governor (Mechanical slowly being phased out due to EPA
Tier 3) Electronic – ECM (ECU); Not all have means for simulating
an Overspeed Condition Speed Switch – Critical ItemOil, Water, Low Temp. (new) Switch Contacts for Controller Starter Motor (One or Two)*
Note: *The dual starter motor Clarke engines do not have manually (mechanically) operable contactors.
C.E. IEEE-IAS 12
Electronic ECM (ECU) Engines
Cummins (U.L. & F.M.) Clarke (U.L. & F.M.) (Had a high current draw in the Alternate ECM position)
Notes:1) Some designs keep the ECM powered up continuously,
others only when needed.2) The 2010 Edition of NFPA-20 adds requirement for
Automatic Switchover between the primary and secondary (back-up) ECM with Manual Over-ride Switch.
C.E. IEEE-IAS 13
Diesel Driver & Fuel Switch & Engine Gage Panel
Caterpillar Fire Pump Engine
MCS 4817 Low Fuel Switch
Typical Engine Gage Panel
C.E. IEEE-IAS 14
Operating Environment
Environmental Conditions: Indoor, Outdoor, Temperature (High & Low) Cooling Heating Combustion Air Horsepower Derated for: Altitude Higher Ambient Temperature
C.E. IEEE-IAS 15
Dual Battery Operation
Diesel Battery Requirements
- Two banks of batteries are required.- Each must have capacity to crank the engine for 180 Seconds (Two times Six 15 Sec. Cranks).
-Typically: - the batteries are SAE 4D or 8D types; - Two 12 Vdc Batteries on 12 Volt Engines - Four 12 Vdc Batteries on 24 Volt Engines - Eight 12 Vdc Batteries on Large Engines*
12 V
24 V
* Requires 20 Amp chargers to meet the 24 Hour Re-Charge time requirement.
C.E. IEEE-IAS 16
Engine Drive
CombustionAir
-and-
RoomCooling
Most EnginesWater Cooled
C.E. IEEE-IAS 17
Design ParametersBattery Voltage Variation
The Engine and Controller must function reliably over a 250% voltage range. E.g.: 6 Vdc Breakaway, 9 Vdc Cranking (undulating voltage & current), 14+ Vdc High Rate Charging.
Battery Banks Sized for 12 @ 15 Sec Cranks (180 Seconds per bank) at 40°F.
New Hold-up Time Requirement (No A.C. Power): 72 Hours Stand-by and still provide three 15 Second cranks.
Engine Wiring & Components Must Accommodate: Cranking Currents (500 Adc or more) Breakaway Currents (1,200 Adc or more) Continuous Charging Current with a typical RMS ratio of
1.8 times the rated D.C. Current.** E.G.: 18 Arms current flow for a 10 amp charger due to ripple current.
C.E. IEEE-IAS 18
Engine Installation Considerations
Environmental Sprinklered Pump Room Outdoor Hazardous Locations, Explosion Proof:
Motor, Controller, Wiring
Air Filter Protection from Getting Wet Other
Salt Air Wind Blown Sand or Dust Temperatures Altitude
C.E. IEEE-IAS 19
Questions ?