Identification of Fault Condition and Switching Event for … · magnitude of this current depends...
Transcript of Identification of Fault Condition and Switching Event for … · magnitude of this current depends...
![Page 1: Identification of Fault Condition and Switching Event for … · magnitude of this current depends on the applied voltage magnitude at the instant of switching, supply impedance,](https://reader035.fdocuments.in/reader035/viewer/2022070821/5f216d793b2bf170706bd1e7/html5/thumbnails/1.jpg)
International Journal of Electrical Electronics & Computer Science Engineering
Volume 1, Issue 6 (December 2014), ISSN : 2348 2273
Available Online at www.ijeecse.com
31
Identification of Fault Condition and Switching Event for Improvement of
Overcurrent using Symmetrical Components
Dhanashree Kotkar1, Nandkumar Wagh
2
1M.TechResearch Scholar, SDCOE, Selukate, Wardha 2Associate Prof. Electrical Engg. Deptt. DESCOET, Dhamangaon
Abstract: In power system, the transient current, inrush
current and overcurrent is quite common and sometimes it
can be represented as fault. As the overcurrent is for very
short period of time, it can be cleared automatically within
1minute and does not damage the system. But the transient
current during switching is treated as a fault current and
system gets disturbed, due to tripping of the relays. To
analyze such conditions, the method of criterion function ‘R’
is proposed in this paper based on symmetrical components.
Which is further implemented in MATLAB as a simulation
for 13 bus bar distribution system and output waveform for
particular value of criterion function ‘R’ is shown and
explained for different fault conditions on power system
equipments such as transformer and Induction Motor.
Keywords: identification, fault condition, overcurrent
Protection, switching event, symmetrical components.
I. INTRODUCTION
A fault is abnormal system condition, which is in most cases is short circuit, and occurs as a random event. The
purpose of protection system is to prevent harm to people,
to limit further damage to power system by removing
faulted equipment [2]. A power is not static but its
parameters changes during operation (switching on or off
of generators, three phase transformers, capacitor banks,
circuit breakers, shunt capacitors and transmission lines)
and during planning (addition of generators and
transmission lines). Faults usually occur in a power
system due to insulation failure, flashover, physical damage or human error. These faults may either be three
phases in nature involving all three phases in a
symmetrical manner, or may be asymmetrical where
usually only one or two phases may be involved. Power
system switching, such as motor starting and transformer
energizing, is the most important source of undesirable
operation of the relay protection.
Traditional methods of over current protection have been
based mainly on phase currents. Inrush currents
associated with motor starting and transformer energizing
can cause interaction problems with other loads in a facility or on the power system. Protection devices can
misinterpret these events as fault currents and may cause
protection devices to trip. Energizing a transformer has
the additional issue of harmonics in the inrush current,
which can excite system resonances and cause dynamic
overvoltage. Here, the high currents occur to energize the transformer core. The steady-state magnetizing current for
a transformer is very low, but the momentary current
when it is first energized can be quite high.
II. OBJECTIVE
The development of deregulation in power systems leads
to a higher requirement on power quality. In the area of relay protection this means that a faster protection is
needed, while undesirable operation of the protection
system is almost unacceptable. A faster protection can
guarantee that an abnormal operation mode somewhere in
a system, such as voltage sag caused by faults, can be
quarantined quickly, so as not to propagate to the rest of
the system and cause instability. In the area of relay
protection employed in distribution system network,
transients caused due to non fault switching events such
as motor starting and transformer energizing are source of
undesirable operation of the protection system. Therefore identification of those factors that produces this
undesirable operation of the relay and introducing
procedures for their discrimination from the real fault
cases are very important. To do this, a relay protection
should be sensitive. Unfortunately, high sensitivity
sometimes causes undesirable operation of relay
protection when there is no fault in the system. In a
deregulated power market this directly leads to penalty
compensation to the users that suffer from the blackout.
Therefore, identification of those factors that produce this
undesirable operation of the relay and introducing
procedures for their discrimination from the real fault cases are very important.
III. METHODOLOGY
An algorithm based on symmetrical components is
proposed to detect and identify the balance condition of
the power system during the fault. An expert system is
presented here that is able to classify different types of
power system events to the underlying causes (i.e., events) and offer useful information in terms of power
quality using MATLAB/SIMULINK software that are
used to analyze real time distribution system. A
MATLAB/GUI based simulation tool has been developed
to analyze power system operation [1]. The criterion
function „R‟ based on concept of symmetrical
![Page 2: Identification of Fault Condition and Switching Event for … · magnitude of this current depends on the applied voltage magnitude at the instant of switching, supply impedance,](https://reader035.fdocuments.in/reader035/viewer/2022070821/5f216d793b2bf170706bd1e7/html5/thumbnails/2.jpg)
International Journal of Electrical Electronics & Computer Science Engineering
Volume 1, Issue 6 (December 2014), ISSN : 2348 2273
Available Online at www.ijeecse.com
32
components presents method for preventing the
undesirable relay operation due to over currents following
switching. It will give a method for improving over current relay operation. It formulates an algorithm based
on different behavior of current components during fault
and non-fault conditions. Based on these differences, a
criterion function „R‟ is introduced, considering
undesirable operations of over current relays due to
switching is presented in [4].
𝑉𝑎𝑏𝑐 = 𝑉𝑎𝑉𝐵
𝑉𝐶
1)
Therefore, the three symmetrical components phasors
arranged into a vector are as follows:
𝑉012 = 𝑉0
𝑉1
𝑉2
2)
Where the subscripts 0, 1, and 2 respectively refer to the
zero, positive, and negative sequence components. A phase rotation operator 'a' is defined to rotate a phasor
vector forward by 120 degrees. Matrix A can be defined
using this operator to transform the phase vector into
symmetrical components:
𝐴 = 1 1 11 𝑎2 𝑎1 𝑎 𝑎2
3)
The phase voltages are generated by the sequence equation.
𝑉𝑎𝑏𝑐 = 𝐴𝑉012 4)
Conversely, the sequence components are generated from
the analysis equations.
𝑉012 = 𝐴−1𝑉𝑎𝑏𝑐 5)
Where 𝐴−1 =1
2 1 1 11 𝑎 𝑎2
1 𝑎2 𝑎
6)
When transformer is switched, inrush current will happen.
This current has some features, which it is enough to
identify itself. In this paper, to extract these features, a
new criterion is proposed to discriminate inrush currents
from internal faults in power transformers. The point is the value of negative sequence is different from positive
sequence in faulty conditions. Helping this rule, the
criterion is introduced:
𝐼0
𝐼1
𝐼2
=1
3 1 1 11 ∝ ∝2
1 ∝2 ∝ 7)
∝=∝⦟120⟹I_a=1⦟0,I_b=1⦟+120,I_c=1⦟-120 8)
In faulty condition, it is obvious that the value of I2 (negative current) is larger than I1 (positive current) in
normal condition. Using this feature, define new below
criterion:
R = 𝐼1 − 𝐼2
𝐼1 + 𝐼2 9)
IV. EFFECT OF SWITCHING ON RELAY
a. Transformer Energizing: When the primary winding
of an unloaded transformer is switched on to normal voltage supply, it acts as a nonlinear inductor. In this
situation there is a transient inrush current that is required
to establish the magnetic field of the transformer. The
magnitude of this current depends on the applied voltage
magnitude at the instant of switching, supply impedance,
transformer size and design. Residual flux in the core can
aggravate the condition. The initial inrush current could
reach values several times full load current and will decay
with time until a normal exciting current value is reached
[3]. The decay of the inrush current may vary from as
short as 20 cycles to as long as minutes for highly
inductive circuits. The inrush current contains both odd and even order harmonics. Although digital relay‟s filter
is used to extract the fundamental component of the
current, the magnitude of the signal may lead to
undesirable operation of the relay. Another concern about
transformer energizing is transient propagation. This
causes considerable amount of even harmonics and dc
component in the voltage. These disturbances may
propagate through transformers to the rest of the system,
and be magnified due to resonance effect.
b. Motor switching: Starting the medium voltage (MV)
and low voltage (LV) induction motors is another subject to be considered. The starting current of a large induction
motor is typically five to six times the rated current. In
fact, the starting current has a very high initial peak. That
value is damped out after a few cycles, normally no more
than two cycles depending on the circuit time-constant
[3]. Then, it drops rapidly to a multiple value of its
nominal level, and is maintained during most of the
acceleration process. The current is then smoothly
reduced to the nominal value that depends on the
mechanical load of the motor. This trend that corresponds
to the direct starting of a three-phase motor connected to
the supply at the worst switching angle.
V. CONCEPT OF CRITERION FUNCTION
The criterion function „R‟ for discriminating fault
from non fault switching is defined as follows:
R = (I1 - I2) / (I1 + I2)
![Page 3: Identification of Fault Condition and Switching Event for … · magnitude of this current depends on the applied voltage magnitude at the instant of switching, supply impedance,](https://reader035.fdocuments.in/reader035/viewer/2022070821/5f216d793b2bf170706bd1e7/html5/thumbnails/3.jpg)
International Journal of Electrical Electronics & Computer Science Engineering
Volume 1, Issue 6 (December 2014), ISSN : 2348 2273
Available Online at www.ijeecse.com
33
Since there is a considerable negative component in
the asymmetrical fault case, according to criterion
function the value of „R‟ is close to zero. In the switching case, the negative component is very small
and „R‟ is close to 1.
The suggested criterion is independent of the amplitude of the current which is advantageous. The
reason is that it operates based on the relative
difference between the negative and positive
component of the current [5].
Another advantage of the suggested criterion function
is that its proper operation is independent of the
power system balancing it also operates properly.
The reason is that during the asymmetrical fault, the negative component of current increases and the
value is much smaller than that before fault event.
R<0.35 indicates the fault; otherwise, overcurrent is the result of switching. It can be mathematically proved as
follows:
a. Analytical model:
Example 1: The single line diagram of power system
considered is shown in figure 1, where negative and
positive sequence reactances are also given. The neutral
of generator and -Y transformers are solidly grounded.
The motor neutral is grounded through reactance Xn = 0.005 per unit on motor base. Pre fault voltage is VF =
1.0500 per unit. Pre fault load current and -Y transformers phase shifts are neglected [6].
Fig. 1: Single Line Diagram for Example 1
Solution: The sequence network of zero, negative and positive for above power system is below
Fig. 2: Zero Sequence Network for Example 1
Fig. 3: Positive Sequence Network for Example 1
Fig. 4: Negative Sequence Network for Example 1
Fig. 5: Thevenin Equivalent of Zero Sequence Network for Example 1
Fig. 6: Thevenin Equivalent of Positive Sequence Network for Example 1
![Page 4: Identification of Fault Condition and Switching Event for … · magnitude of this current depends on the applied voltage magnitude at the instant of switching, supply impedance,](https://reader035.fdocuments.in/reader035/viewer/2022070821/5f216d793b2bf170706bd1e7/html5/thumbnails/4.jpg)
International Journal of Electrical Electronics & Computer Science Engineering
Volume 1, Issue 6 (December 2014), ISSN : 2348 2273
Available Online at www.ijeecse.com
34
Fig. 7: Thevenin Equivalent of Negative Sequence Network for Example 1
CASE 1: When single phase line to ground fault
occurs, the zero, negative and positive sequence
networks are connected in series.
Fig. 8: Interconnected Sequence Network for Single Line to Ground Fault
I0 = I1 = I2 = 1.0500
j (0.25+0.13893+0.14562)
= 1.0500
j (0.5345)
= -j 1.96427 per unit
Criterion function „R‟
R = (I1 - I2)
(I1 + I2)
R = 0.
CASE 2: When line to line fault occurs, the negative
and positive sequence networks are connected in parallel at fault terminals as follows.
Fig. 9: Interconnected Sequence Network for Line to Line Fault
I2 = - I1 = 1.0500
j (0.13893+0.14562)
= 1.0500
j (0.28455)
= 3.690-900 per unit
Criterion function „R‟
R = (I1 - I2)
(I1 + I2)
R = 0.
CASE 3: When double line to ground fault occurs, the
zero, negative and positive sequence networks are connected in parallel at fault terminals as follows.
Fig. 10: Interconnected Sequence Network for Double
Line to Ground Fault
Equivalent Impedance = (Z0 // Z2) + Z1
= (j0.25 // j0.14562) + j0.13893
= j0.23095
I1 = 1.0500
j0.23095
= j 4.5464 per unit
By current division rule
I2 = - (-j 4.5464) x j0.25
j0.25+ j0.14562
= j 2.873 per unit
Criterion function „R‟
R = (I1 - I2)
(I1 + I2)
R = 4.5464 - 2.873
4.5464 + 2.873
= 0.23
By solving above power system problem for criterion
function „R‟, the value of „R‟ is below 0.35. Hence
this value can be used for overcurrent protection.
![Page 5: Identification of Fault Condition and Switching Event for … · magnitude of this current depends on the applied voltage magnitude at the instant of switching, supply impedance,](https://reader035.fdocuments.in/reader035/viewer/2022070821/5f216d793b2bf170706bd1e7/html5/thumbnails/5.jpg)
International Journal of Electrical Electronics & Computer Science Engineering
Volume 1, Issue 6 (December 2014), ISSN : 2348 2273
Available Online at www.ijeecse.com
35
Example 2: A star connected generator has sequence
reactor X0 = 0.09 per unit, X1 = 0.22 per unit, and X2 =
0.36 per unit. The neutral point of machine is grounded through a reactance of 0.09 per unit. The
machine is running on load with rated terminal voltage
when it suffers an unbalance fault. The fault currents
out of machine armature are Ia = 0, Ib = 3.751500 per
unit, and Ic = 3.75300 with respect to phase „a‟ line to neutral voltage.
Solution:
Where a=11200
I1 = 1 (Ia+aIb+a2Ic)
3
=1(0+(11200)x(3.751500)+(11200)2x(3.75300))
3
= - j 2.5 per unit
I2 = 1 (Ia+a2Ib+aIc)
3
=1(0+(11200)2x(3.751500)+(11200)
x(3.75300))
3
= j 1.25 per unit
Criterion function „R‟
R = (I1 - I2)
(I1 + I2)
R = 2.5 – 1.25
2.5 + 1.25
= 0.33
By solving above power system problem for criterion
function „R‟, the value of „R‟ is less than 0.35. Hence
this value can be used for overcurrent protection.
b. Analytical Model: To show the advantage of the criterion function „R‟ for overcurrent protection, a part
of a distribution system 34.5 kV 13 bus is shown in
Fig. 11, is modeled using the MATLAB/Simulink,
also the network parameter of the 13-bus distribution
system is shown. Several non-fault events are applied
to this system along with unsymmetrical faults i.e.,
single line to ground, line to line and double line to ground events at different times. The simulation
results show, how the proposed algorithm could help
the overcurrent relay to discriminate fault from non-
fault events [1].
Fig. 11: 13 Bus (34.5 kV Simulated Distribution System)
VI. SIMULATION RESULT ON 13 BUS SYSTEM
Fig. 12: MATLAB Model of 13 Bus bar system without fault
![Page 6: Identification of Fault Condition and Switching Event for … · magnitude of this current depends on the applied voltage magnitude at the instant of switching, supply impedance,](https://reader035.fdocuments.in/reader035/viewer/2022070821/5f216d793b2bf170706bd1e7/html5/thumbnails/6.jpg)
International Journal of Electrical Electronics & Computer Science Engineering
Volume 1, Issue 6 (December 2014), ISSN : 2348 2273
Available Online at www.ijeecse.com
36
Fig. 13: Voltage & Current Waveform13 Bus bar system without fault
Fig. 14: MATLAB Model of 13 Bus bar system with fault
Fig. 15: Voltage & Current Waveform13 Bus bar system with fault
Fig. 16: Subsystem for Criterion Function
Fig. 17: Subsystem for subsystem 4
Fig. 18: Subsystem for subsystem 4 (gate 2)
Fig. 19: Transformer Energizing on bus 9
Fig. 20: Value of Criterion Function with transformer switching on Bus 9
![Page 7: Identification of Fault Condition and Switching Event for … · magnitude of this current depends on the applied voltage magnitude at the instant of switching, supply impedance,](https://reader035.fdocuments.in/reader035/viewer/2022070821/5f216d793b2bf170706bd1e7/html5/thumbnails/7.jpg)
International Journal of Electrical Electronics & Computer Science Engineering
Volume 1, Issue 6 (December 2014), ISSN : 2348 2273
Available Online at www.ijeecse.com
37
Case-I: By considering asymmetrical different faults:
Fig. 21: LG Fault on bus 9
Fig. 22: Value of „R‟ versus Time due to LG on Bus 9
Fig. 23: LLG Fault on bus 9
Fig. 24: Value of R by LLG Fault on bus 9
Fig. 25: LL Fault on bus 9
Fig. 26: Value of R by LL Fault on bus 9
Fig. 27: Motor switching on bus 9
Fig. 28: Value of Criterion Function R on bus 9
![Page 8: Identification of Fault Condition and Switching Event for … · magnitude of this current depends on the applied voltage magnitude at the instant of switching, supply impedance,](https://reader035.fdocuments.in/reader035/viewer/2022070821/5f216d793b2bf170706bd1e7/html5/thumbnails/8.jpg)
International Journal of Electrical Electronics & Computer Science Engineering
Volume 1, Issue 6 (December 2014), ISSN : 2348 2273
Available Online at www.ijeecse.com
38
Case-II: Fault through low resistance:
Fig. 29: LG Fault without Overcurrent Relay on Bus 9
Fig. 30: Value of „R‟ versus Time due to LG Fault without Overcurrent Relay on Bus 9
Fig. 31: LG Fault with Overcurrent Relay on Bus 9
Fig. 32: Value of „R‟ versus Time due to LG Fault with Overcurrent Relay on Bus 9
VII. DISCUSSION
The nature of plots for value of „R‟ versus time and three phase currents due to three phase short circuit
without overcurrent relay are shown in fig. 29 and fig.
30 and with relay in fig. 31 and fig. 32respectively.
The three phase current waveforms of LG, LL, LLG,
and simultaneous LL and transformer energizing are
same for ground fault and fault through low resistance
as due to overcurrent relay the faulty phases are disconnected on occurrence of fault.
The criterion function „R‟ effectively works with the use of negative sequence component which arises due
to unbalance of unsymmetrical fault conditions. It
provides accurate discrimination between fault and
non fault cases. It operates effectively in power
distribution network when power system is
unbalanced. The mathematical value of criterion
function „R‟ is used as 0.35 and it is proved with
different power system examples. The value of
criterion function „R‟ varies for fault and non fault
cases. The value of criterion function „R‟ for motor switching is near about same for transformer switching
non fault event.
VIII. CONCLUSION
The criterion function „R‟ as a decision making box can
be implemented in relay and gives the signal to the circuit
breaker for exact operation of the system, while switching and fault conditions. Maloperation can be avoided and
continuous power supply will be easily available without
any disturbance.
The focus of this study is on the application of power system disturbance data for the testing of power system
protection equipment. Towards such a goal, study is
carried out not on particular case study, but on seeking a
general procedure for processing any possible disturbance
before it is applied in protection testing. In other words,
the main concern in this work is how to implement such
an application of disturbance data on testing.
IX. APPLICATION
The criterion function „R‟ with overcurrent protection can be used for overhead distribution lines. The above
work is useful to the researchers working on this topic
and it is also useful to one who wants to check the
results with distribution, and transmission lines. The
work is useful to get reliable results with other power system software like EMTDC / PSCAD software [1].
This work is useful to improve distribution system
overcurrent protection and will provide development
in deregulation with reliable power quality.
![Page 9: Identification of Fault Condition and Switching Event for … · magnitude of this current depends on the applied voltage magnitude at the instant of switching, supply impedance,](https://reader035.fdocuments.in/reader035/viewer/2022070821/5f216d793b2bf170706bd1e7/html5/thumbnails/9.jpg)
International Journal of Electrical Electronics & Computer Science Engineering
Volume 1, Issue 6 (December 2014), ISSN : 2348 2273
Available Online at www.ijeecse.com
39
X. REFERENCES
[1] Saeed Lotfi-fard, Jawad Faiz, Reza Iravani, “Improved Overcurrent Protection Using
Symmetrical Components”, IEEE TRANSACTION
ON POWER DELIVERY, Vol. 22. No. 2 April 2007.
[2] R. V. Katre, D. S. Chavan, S. S. Sardey,
“Discrimination Of Fault From Non-Fault Event In
Transformer Using Concept Of Symmetrical
Components”, INTERNATIONAL JOURNAL OF COMPUTATIONAL ENGINEERING RESEARCH, ,
ISSN 2250-3005, Vol. 3. Issue 3, March 2013.
[3] H. Abniki, A. Majzoobi, H. Monsef, et. al., “Identifying Inrush Currents from Internal Faults
Using Symmetrical Components In Power
Transformers”, MODERN ELECTRIC POWER
SYSTEM 2010.
[4] Suchita Sardey, K. D. Thakur, Sunil Sardey,
“Concept of Symmetrical Component As A
Technique For Analysis Of Fault And Improvement
Of Overcurrent Protection Scheme”,
INTERNATIONAL JOURNAL OF ELECTRICAL AND ELECTRONICS ENGINEERING. ISSN: 2231-
5284, Vol.-I, Issue-II, 2011.
[5] M. A. Rahman, B. Jeyasurya, “A State-of-the-art Review of Transformer Protection Algorithms”,
IEEE Trans. Power Del., Vol. 3, No. 2, pp. 534–544,
Apr – 1988 .
[6] T. S. Siddhu, et al., “Design, Implementation and
Testing of a Micro-processor-based high-speed Relay
for Detecting Transformer Winding Faults”, IEEE
Trans. Power Del., Vol. 7, No. 1, pp. 108–117 Jan –
1992.
[7] J. D. Glover and M. Sharma, “Power System Analysis and Design”, Boston, MA: PWS-Kent, pp.
355-504, 1989.
[8] W. A. Elmore, C. A. Kramer, and S. E. Zocholl, “Effects of Waveform Distortion on Protective
Relays”, IEEE Trans. Ind. Appl., Vol. 29, No. 2, pp.
404–411, Apr – 1993.
[9] J. J. Grainger, W. D. Stevenson, Jr., “Power System
Analysis”, McGraw-Hill, pp. 380 – 527 Inc, 1994.
[10] J. F. Witte, F. P. Decesaro, S. R. Mendis, “Damaging
Long-Term Overvoltages on Industrial Capacitor
Banks due to Transformer Energization Inrush Currents”, IEEE Trans. Ind. Appl., Vol. 30, No. 4,
pp. 1107–1115, Aug – 1994.
[11] A. T. Johns and S. K. Salman, “Digital Protection for
Power Systems”, Stevenage, U.K.: Peregrinus, pp. 1
– 5, 1995.
[12]K. Inagaki and M. Higaki, “Digital Protection Method for Power Transformers based on an
Equivalent Circuit composed of Inverse Inductance”,
IEEE Trans. Power Del., Vol. 4, No. 3, pp. 1501–
1510, Jul – 1998.
[13]J. H. Brunke and H. J. Frohlich, “Elimination of
Transformer Inrush Currents by Controlled
Switching-Part II: Application and Performance
Considerations”, IEEE Trans. Power Del., Vol. 16,
No. 2, pp. 281–285, Apr – 2001.
[14]G. C. Gomez and M. M. Morcos, “A Simple Methodology for Estimating the Effect of Voltage
Sags Produced by Induction Motor Starting Cycles
on Sensitive Equipment”, Proc. IEEE 36th Annual
Meeting Conf., Vol. 2, pp. 1196–1199, Oct – 2001.
[15]L. A. Kojovic and J. F. Witte, “Improved Protection Systems using Symmetrical Components”, IEEE, pp.
47 – 57, 2001.
[16]A. Guzman, S. Zocholl, G. Benmouryal, and H. J.
Altuve, “A Current based Solution for Transformer
Differential Protection-Part I: Problem Statement”,
IEEE Trans. Power Del., Vol. 16, No. 4, pp. 485–491, Oct – 2001.
[17]M. C. Shin, C. W. Park, and J. H. Kim, “Fuzzy Logic-based for Large Power Transformer Protection”,
IEEE Trans. Power Del., Vol. 18, No. 3, pp. 718–
724, Jul – 2003.