HYDROGEN / WATER - COOLED TURBOGENERATORS: A MATURE ...
Transcript of HYDROGEN / WATER - COOLED TURBOGENERATORS: A MATURE ...
21, rue d’Artois, F-75008 PARIS A1-117 CIGRE 2008http : //www.cigre.org
HYDROGEN / WATER - COOLED TURBOGENERATORS:
A MATURE TECHNOLOGY ON THE MOVE
R. JOHO* Y. SABATER H. FERRETTO D. ABRAHAM W. FERENS
ALSTOM
Switzerland France France Germany Poland
SUMMARY
The decades from 1960 to 1980 brought a tremendous growth of hydrogen/water-cooled
turbogenerators, resulting in some 1200 MVA for full-speed two-pole units and 1600 MVA for half-
speed four-pole units. This development was mainly driven by the nuclear power generation programs.
With the merger of two European manufacturers in 1999, it was decided to continue with the large
two-pole line of the one partner and the nuclear four-pole line of the other partner. Possible synergies
of the two generator lines were thoroughly examined with the primary goal of increasing reliability
and availability. In addition, both series have always been submitted to continuous improvement.
Selected examples of related technology improvements will be described. Using the synergies and the
continuous improvement the availability of the fleet of large units could be brought up to exceptional
high numbers.
Both generator lines are currently in uprating of output for power plants beginning operation around
2011-2012. Coal power plants with low-emission technologies are making use of large full-speed
turbines, requiring generators up to the 1400 MVA range. Nuclear reactors of the third generation will
use half-speed turbine sets requiring generators up to the 2000 MVA range. It is shown how this will
be achieved by increase in utilization and by moderate increase in dimensions. Efficiency in power
generation has become of utmost importance for caring of the primary energy resources. For the newly
developed 2000 MVA generator it will be demonstrated how highest efficiencies can be achieved.
The technologies available will also in future allow a potential for uprating. Both generator lines might
get further aligned by components, in order to bring their ratings up. Four-pole units will be structured
into generator families around different kind of nuclear reactors, for both 50 Hz and 60 Hz, and
involving the experienced static excitation, as an option to the well-referenced brushless exciters. By
the modular build-up around experienced components the manufacturer will be able to satisfy future
customer requirements with a premium performance of the generator.
KEYWORDS
Turbogenerator, Hydrogen-cooling, Water-cooling, Two-pole generator, Four-pole generator, Design,
Development
1. INTRODUCTION
The years 1960 to 1980 brought a tremendous growth of hydrogen/water-cooled turbogenerators up to
1200 MVA full-speed (two-pole) and 1600 MVA half-speed (four-pole). The main driver was the fast
developing nuclear power generation technology. In the mid 80'ies a complete new series of two-pole
generators was introduced by a Swiss manufacturer [1]. In parallel an unsurpassed construction boom
of nuclear power plants in France was served with four-pole generator solutions by a French
manufacturer [2]. The two manufacturers were joining their turbomachinery program in a 1999 joint
venture and a subsequent takeover in 2000. The company now cares for a fleet of more than 600 two-
pole generators and more than 80 four-pole generators. Soon after the merger, the generator program
was clearly allocated in the new organisation. Design responsibility is in Switzerland for two-pole and
in France for four-pole generators. The manufacturing lead center is in Poland for two-pole generators,
in France for four-pole generators, and in Switzerland for rotors. The paper deals with the generator
designs from 1985 up, which basically represent the actual main design features.
2. THE HYDROGEN/WATER-COOLED GENERATOR FLEET
Hydrogen/water-cooled generators are driven by steam turbines (Fig. 1,2). They are designed for table
mounting. Today, the applied power range is from 600 MW up to the highest ratings. Table 1 shows
the MW-classes built for two-pole units, as far as they originate of the new series, started in mid
80'ies. A total of 18 units are in operation for 50 Hz and 60 Hz. They total an EOH (Equivalent
Operating Hours) of more than 1 million and an excellent FOR (Forced Outage Rate) of 0.05%.
Table 1: Two-pole generators (Class 600 MW up, commissioning since 1985)
Plant class MW-class Units 50 Hz 60 Hz Plant references
Nuclear 1200 1 x Leibstadt
Coal 900 2 x Lippendorf
Coal 800 1 x Zimmer
Coal 700 5 x Manjung,Amer 9,Hemweg 8
Coal 600 9
6
x
x
x Shidongkou,Staudinger,Rutenberg,..
China (Commiss. 2008/9)
Steam data of modern PWR reactors make it advantageous for turbine performance to run at the next
lower synchronous speed, which is at 1500 rpm for 50 Hz, using a four-pole generator. The four-pole
generator fleet is listed from 1985 up in Table 2. It consists mainly of second series of P4 types and
N4 types of the French nuclear program. The 28 units in operation have accumulated an EOH of more
than 1.5 million and have an excellent availability. The present references are mainly 50 Hz, but there
is 60 Hz experience from units commissioned before 1985.
Fig. 2: 1722 MVA four-pole generator of the N4
series of the French nuclear power program Fig. 1: 950 MVA two-pole generator in thermal
power station Manjung, MY
1
Table 2: Four-pole generators (Class 1000 MW up, commissioning since 1985)
Plant class MW-class Units 50 Hz 60 Hz Plant references
Nuclear 1500 5 x N4, Oskarshamn 3
Nuclear 1300 18 x Continuation of P4/P'4
Nuclear 1200 2
4
x
x
Ling Ao II (Commiss. 2010/11)
Hong Yan He (Commiss. 2012/14)
Nuclear 1000 6 x x Ulchin,Koeberg,Chinon
3. DESIGN FEATURES OF HYDROGEN/WATER-COOLED GENERATORS
Hydrogen/water-cooled generators have highest utilization number. The definition is given by
C Esson = Sn / (Dr2 ∗ lfe ∗ n)
where Sn: Apparent power, Dr: Rotor diameter, lfe: Core length, n: Rotational speed
Both 2-pole and 4-pole generator types are achieving numbers of close to 40 kVAmin/m3. It is evident
that such high utilization goes along with high specific loss densities in the generator components, be
it in the windings, in the core and in the end regions. The hydrogen serves primarily for heat removal
from the rotor winding and the stator core, but is also indispensable for removal of stray field losses in
end regions. The water cooling of the stator winding bars is a prerequisite for achieving the high
utilization inside the given housing dimensions, which themselves are subject to limits of
transportation, especially the Schnabel car railway transportation (Fig. 3).
Fig. 3: A two-pole generator stator being unloaded from Schnabel car to ship
Two-pole generators are characterized by (Fig. 4):
- Modular housing, center-flanged vertical coolers (Fig. 1)
- Range covered by three standardized rotor diameters and stepped core length
- Pedestal bearings for isolating shaft from frame vibrations
- Rotor winding two-path axial cooling, supported by a high-efficient radial fan on NDE
allowing rotor withdrawal without fan removal
- Static excitation: Simple technology, fast reacting
2
Fig. 4: Two-pole hydrogen/water-cooled generator
The proven key technologies applied:
- Stator end winding: Clamped between rings, axial movable, support re-tightenable
- Stainless steel stator bar water tubes
- Laminated conical core press plate
- Single- and triple-circuit shaft seal system
he water tubing in the stator bars in stainless steel technology is in operation for over 30 years [3]. It
since more than 20 years the standard solution, with an excellent operation record worldwide.
ustomers recognize the robustness of the system, which is characterized by a functional separation of
lectrical connection and water box (Fig. 5).
m ed successfully for over 35 years in more than 100
works with a supply of air-saturated oil and a supply of
an injection of vacuum oil (Fig. 6). A leakage rate of less than
bar(g) and a high hydrogen purity inside the generator, which
far outweigh the higher investment. The system is
ystem auxiliary. It is applied depending on generator
pressure.
T
is
C
e
Fig. 5: Stainless steel water tubing and functional
separation of bar connection and water box Fig. 6: Triple-circuit shaft seal: Floating
rings (FR), separating the oil flows
The triple-circuit shaft seal is a unique syste
hydrogen/water-cooled generators. It
hydrogen-saturated oil, separated by
5 Nm3/day at highest unit pressures of 6
reduces the gas friction loss in the generator, by
fully modularized, including the shaft seal oil s
type, shaft diameter and rated hydrogen
, us
3
Typical data of a large two-pole generator are shown in Table 3.
able 3: Typical data of a large two-pole
enerator [4]
T
g
Model GIGATOP 2-pole
Class 934 MW
MVA 1167 MVA
pf 0.8
UN 27 kV
Speed 3000 rpm
SCR 0.51
pH2 (gauge) 5 bar
Efficiency 98.88 %
Excitation Static Fig. 7: Housing structure of a four-pole generator
Four-pole generators are characterized by (Fig. 8):
- Modular housing, flanged channels for hydrogen ducting, vertical coolers in end covers (Fig. 7)
NDE and DE
r diameters (each frequency) and stepped core length
arings
gle-circuit sh riple circuit)
tor radial-tra w also multi-path axial), axial fans on both ends
- Terminal box on NDE, if needed on
- Range covered by two standardized roto
- End shield be
- Sin
o
aft seal (now also t
oling (no- R nsversal co
Fig. 8: Four-pole hydrogen/water-cooled generator
The proven key technologies applied:
- A cantilevered brushless exciter (Fig. 9). The armature
and the diode arrangement of this unique type of exciter
are housed in a steel ring of bell shape, which is flanged
to the rotor end. The dc field is inserted coaxially in the
armature bore. The short design eliminates the usual
third bearing. This results in a short overall length and
an excellent shaft dynamic behaviour.
4
Fig. 9: Cantilevered brushless exciter
Fig. 10: Stator end winding support
- A reinforced stator end winding support (Fig. 10), that has pr
generators. It is characterized by a solid outer glass-fiber ring and th
outer ring. This gives excellent radial and circum
allows the axial thermal cycling of the end winding.
oven its sustainability in many
e winding ends bolted to the
ferential stiffness. A flexible support system
Table 4: Typical data of a large 4-pole generator
Model GIGATOP 4-pole
Class 1550 MW
MVA 1722 MVA
pf 0.9
UN 20 kV
Speed 1500 rpm
SCR 0.38
pH2 (gauge) 3.8 bar
Efficiency 98.93 %
Excitation Brushless, cantilevered
Terminal Double terminal box
Typical data of a large four-pole generator are
shown in Table 4.
Running tests for:
-Confirmation, -Verification, -Extrapolation
The verification of the performance of
hydrogen/water-cooled generators is done in the
acknowledged way of factory running tests
(Fig. 11). As an established practice, these are
routinely done on first units of a generator type,
and are in accordance to the relevant international
standards. The challenge for largest units is to
provide the driving motor up to 15 MW, for both
frequencies, for the electrical test runs according to
the segregated loss method, and the rigid mounting
on the factory hall floor. The culmination is the
routinely performed sudden short-circuit test from
up to 70 % rated voltage. In addition to
performance confirmation for the customer, by
additional special tests, the manufacturer gets
valuable information to verify the design tools,
which is also essential as a base for designing
higher ratings.
As part of the manufacturing process, all rotors are
routinely passing test runs in the overspin test bed,
such as excited heat runs, balancing runs, and an
overspeed test at 120 % rated speed. Fig. 11: Factory running tests on a
800 MVA two-pole generator
5
4. EXAMPLES OF CONTINUOUS IMPROVEMENT
The continuous product improvement system involves component improvements, learnings from
operation experience, technology alignments. The continuous product improvement system is strictly
subject to the same stringent product development quality rules as applied for new developments. In
the following, the scope is explained by way of examples.
4.1 Laminated conical press plate
A critical issue of the largest two-pole generators is the core end heating in underexcited operation. As
a longstanding practice, large two-pole generators with hydrogen/water cooling are equipped with
laminated press plates on the ends of the core. They consist of stacked laminations, which are
compacted to a ring by vacuum pressure resin impregnation. By its one-side conical shape such a press
art of the magnetic stray flux of the end winding at lowest losses.
two-pole generators, a special investigation was done in a
performance enhancement of the press plate. Supported by electro-magnetic and thermal numerical
nts.
in large generators having water-cooled winding
Roebel bars in the end
solution is the concept of
us field neutralization inside
such bars end in one
lification in the stator bar end
Fig. 13: Twin Roebel bar
plate receives and internally guides p
Facing a continuous uprating of
calculations a couple of design improvements were found. The main improvement consists in an
enlargement of the lateral clearance of adjacent laminations, and the insertion of radial slits extending
from the slot bottom into the yoke (Fig. 12). Both measures serve to sustainably reduce eddy currents
produced by axial flux components. The improvements were integrated into the manufacturing process
f press plates. The solution is also available for replacemeo
4.2 Cross-transposed four-stack Roebel bars
The use of twin Roebel bars is an established solution
bars (Fig. 13). However they need an individual coi
winding, and an additional cross-change per coil. An
a cross-transposed four-stack Roebel bar (Fig. 14), w
each bar while keeping a simple manufacturing of th
large solid lug on both sides, this contributes to a
connections.
Fig. 12: Laminated conical press
plate with enlarged
clearances and radial slits
l connection of the two
alternative, much easier
hich gives a continuo
e Roebel bar [5]. Since all
considerable simp
Fig. 14: Principle of cross-transposed Roebel bar
6
4.3 Rotor cooling of four-pole generators
As a long-standing practice, four-pole generators are equipped with a radial-transversal cooling of the
al direction with a highly efficient use of
ooling gas, and was found an optimum solution for highest ratings (Fig. 15). Because the conductors
wn gas flow applies to one half cooling of the copper stack. The
nding
(2 slot half indicated by gas outlets)
.4 Technology alignments of four-pole generators
rom a manufacturer's standpoint, after merger with another manufacturer, it is obvious to compare
e two existing technology lines, and to check for alignment. A detailed analysis has led to the
llowing technology alignments of four-pole with two-pole technology:
- The stainless steel tubing for the cooling water in the stator bars. This unique and robust
technology is widely approved and, with the stainless steel water box gives highest availability.
m Pressure Impregnation) system, used for the stator bar main
This results in a unique insulation system up to the experienced
epares for the 30 kV range.
- The triple-circuit shaft seal will be applied for the new EPR generator series, which has a
hydrogen pressure equal to experienced levels of two-pole units. The hydrogen loss thus can be
kept at a low 5 Nm3/day.
enerators with ratings up to 2000 MVA (Table 5).
Model GIGATOP 4-pole
rotor winding [2]. Although a proven solution it is rather complex and not suited for supporting a
further increase in unit output. Facing this situation, a cooling concept of a small air-cooled type was
checked and found to have potential for largest sizes. This multi-path forward flow cooling system
gives uniform temperature distribution in axial and radi
c
have two parallel gas ducts: The sho
second half cooling (symbolized by gas outlets) is arranged with a half-pitch shift, and thus contributes
to an even more uniform temperature distribution.
Fig. 15: Principle of multi-path forward flow cooling in rotor wind
4
F
th
fo
- The Micadur® VPI (Vacuu
insulation, is generally applied.
27 kV of two-pole units, and pr
5. TRENDS TOWARDS HIGHER OUTPUTS
A new area of large power plants brings along a need for larger steam turbines and thus for generators.
There is a revival of coal plants using low-emission technologies. This goes along with a need for two-
pole generators beyond 1000 MW. Current projects in Germany require generator ratings up to
1400 MVA. For the new nuclear power plants of the third generation, projects require four-pole
g
Class 1750 MW
MVA 1944 MVA
pf 0.9
Table 5: Typical data of a large four-pole
generator for EPR (Project Flamanville 3)
UN 23 kV* / 27 kV
Speed 1500 rpm
SCR 0.42
pH2 (gauge) 6.0 bar
Efficiency 99.00 %
Excitation Brushless, cantilevered
* requiring terminal box
on NDE and DE
7
8
enerator manufacturer for the current and future uprate The following shows the approach of the g
requirements of the market.
Manufacturer's approach Achieved by
lti-path forward flow cooling
• Increase rated voltage • Based on existing insulation system, limits current
loading in stator bars and bushings
• Uprate brushless exciter • Refine cooling in cantilevered exciter
This means that also the future requirements can be accomplished by using hydrogen cooling
technology for the rotor winding and water cooling technology for the stator winding. These
technologies and all related designs are based on mature and highly reliable solutions and allow a
predictable availability and a reliable maintenance scheduling [6].
enerator families around the
60 Hz, and taking into account differing electrical
bining static excitation with four-
generator line were clearly allocated. Despite the maturity of the
roduct there is always room for continuous improvement of the components and technologies, for
sing synergies, and for further alignment of the technologies.
utputs. The investigations show that even these
gns, hence
enerators”, ABB Review 1/1989
] J.M. Guillard, R. Damiron, J.C. Marino, “1710MVA Generators for the French N4 Nuclear
6
[3] ho, N. Krick, A. Huber, “Ge ding Design –
E Tran s on Energy Conversion, Vol.16, No.1,
March 2001
[4] L. Busse, K.-H. Soyk, “World's Highest Cap Steam Turbos nite-fired
Lippendorf Power Plant”, ABB Review 6/1997
[5] J. Haldemann, “Transpositions in Stator Bars of Large Turbogenerators”, IEEE Transactions on
Energy Con ptember 200
[6] M. Verrier, y, G. Martinet, “N ent in
for Nuclear Power Plants with Reliability Target”, CIGRE Session 200
• Increase hydrogen pressure • Enabled by triple-circuit shaft seal
• Moderate increase in length • Checked by shaft dynamic calculation
• Moderate increase in rotor diameter • Mechanical optimization by finite element analysis
• Reduced temperatures in end zone • Low-loss laminated conical press plate (two-pole)
• Improved cooling of copper shield (four-pole)
• High-efficient rotor cooling • Mu
Future work of the manufacturer will also involve structuring of g
ifferent kinds of plant types, for 50 Hz andd
performance requirements. A flexible modularization will allow com
pole generators. Although short circuit ratios of 0.4...0.5 in this large power range are widely accepted,
special SCR requirements may be considered by an optional air gap (by increasing the stator bore
diameter), while keeping all other dimensions. Of course such a special option will result in a derating
on other generator performances. A plant layout option for the large sizes will be the single terminal
box on NDE for a high rated voltage, and a double terminal box for a low rated voltage.
6. CONCLUSIONS
A large hydrogen/water-cooled generator fleet and the shared experience of the two merged generator
engineering communities results in a broad design and operational know how. The responsibilities for
the two-pole and the four-pole
p
u
The market will require considerable higher generator o
rger units will be based on robust, proven and accepted generator technologies and desila
remain in fields of known high performance reliability.
BIBLIOGRAPHY
[1] K. Weigelt, “Design Features of Large Turbog
[2
Stage”, CIGRE Session 1988, Paper 11-0
J. Oliver, J. Michalec, B. Zimmerli, R. Jo
Amos 3 with 25 Years Experience”, IEE
nerator Win
saction
acity ets for the Lig
version, Vol.19, No.3, Se
M. Thiery, P. Cha
4
pmew Develo the Design of Generators
4, Paper A1-105