Los NATIONAL LABORATORY Alamos 20.268 14.025 0.0899* 1s* Hydrogen 1.0079 1 H 1 Hydrogen Gas Safety Self-Study

Transcript of Hydrogen Gas Safety · (EIV), which provides an automatic or manual means for stopping the hydrogen...

LosN A T I O N A L L A B O R A T O R Y

Alamos

20.26814.0250.0899*

1s* Hydrogen

1.00791

H1

HydrogenGas SafetySelf-Study

This training course is presented with the understanding that the information and materialsprovided were developed based on specific circumstances present at the Los Alamos NationalLaboratory at the time of publication. Those circumstances may or may not be similar toconditions present at other locations represented by participants in this course. Thecourse materials and information will need to be adapted accordingly. The University ofCalifornia/Los Alamos National Laboratory will not be liable for direct or indirect damagesresulting from use of this material.

Instructional DesignersScott Robbins and George Glass

Technical AdvisorJeff Hollander

EditorsSusan Basquin and Karen Smith

Cover DesignerRosalie Ott

Course Number: 8724 August 2000

Document Number: ESH13-401-sb-8/00

Introduction

Hydrogen Gas Safety 1

About This Course

Course Purpose

This self-study course is intended to provide hydrogen gas userswith the fundamental awareness necessary to minimize the risk ofaccident or injury due to human error.

Course Objectives

When you have completed this course you will be able to

• identify the physical properties associated with hydrogen gas,

• recognize the physical hazards associated with hydrogen gas,

• recognize the health hazards associated with hydrogen gas,

• list the components of a hydrogen gas supply system,

• identify appropriate precautions for preventing electrical ignitionof hydrogen gas,

• identify safe-handling guidelines appropriate for hydrogen gassystems,

• identify the safety considerations for moving gas cylinders,

• identify the safety considerations for storing hydrogen gascylinders,

• identify the airborne concentrations at which alarm systems willbe activated,

• list the four steps required in case a hydrogen alarm isactivated,

• list the four steps appropriate for responding in case of ahydrogen fire, and

• list the points of contact for assistance in safely installing ahydrogen gas supply system.

Introduction

Hydrogen Gas Safety 2

About This Self-Study Guide

What Is Self-Study?

Self-study is a method of instructional delivery that allows you towork independently rather than under the direction of a classroominstructor.

In This Guide

This self-study contains two learning units, followed by lessonslearned and references.

At the end of this study guide is a cumulative quiz to review theinformation in all the units. Instructions for accessing and taking thequiz follow this guide. A score of 80% on the quiz is required forcourse credit.

Hazards and Precautions

Hydrogen Gas Safety 3

Properties of Hydrogen

What Is Hydrogen?

Hydrogen is a colorless, odorless, tasteless, flammable nontoxicgas. It is the lightest of all gases, with a specific gravity of 0.0695.The hydrogen content of atmospheric air at sea level is 0.5 ppm.

Hydrogen has two isomers (forms): ortho-hydrogen, in which thetwo atomic nuclei spin in the same direction; and para-hydrogen, inwhich they spin in opposite directions. There is no difference in thechemical properties of the two forms of hydrogen, but there areslight differences in physical properties. Gaseous hydrogen is amixture of 75% ortho-hydrogen and 25% para-hydrogen at roomtemperature; this mixture is called normal hydrogen (CGA G51991).

Hydrogen Has Unique Properties

Several unique properties contribute to the hazards associated withgaseous and liquid hydrogen systems:

• Hydrogen is flammable over a wide range of concentrations.

• The ignition energy for hydrogen is very low.

• A single volume of liquid hydrogen expands to about 850volumes of gas at standard temperature and pressure whenvaporized. At 7,000 ft elevation, this expansion rate is increasedto approximately 1,000 volumes of gas at standard temperature.

• Hydrogen is able to reduce the performance of somecontainment and piping materials, such as carbon steel.

Hazards and Precautions

Hydrogen Gas Safety 4

Properties of HydrogenÑcontinued

Flammability

Hydrogen burns with a nearly invisible bluish flame, unless it iscontaminated with impurities, in which case a pale-yellow flame iseasily visible in the dark. The temperature of burning hydrogen inair is high (3,713¡ F, as compared with 2,276o F for gasoline), andwarm hydrogen gas rises rapidly because of its buoyancy.Hydrogen forms a flammable mixture over a wide range ofconcentrations in air and requires a minimum ignition source, onlyone-tenth of the energy required for gasoline vapors. It is thecombination of these factors that contributes to the flammabilityhazard associated with hydrogen gas. (See the table below for asummary of the physical properties of hydrogen.)

Embrittlement

Because of its small molecular size, hydrogen can easily passthrough porous materials and is capable of being absorbed bysome containment materials, which can result in loss of ductility orembrittlement. At elevated temperatures, this process isaccelerated. Because of the possibility of hydrogen embrittlementof some materials, piping and component materials that are notsubject to this form of degradation should be selected.Recommended materials include 300-series stainless steels,copper, and brass.

Hazards and Precautions

Hydrogen Gas Safety 5

Properties of HydrogenÑcontinued

Physical Properties and Characteristics of Hydrogen

The following table lists the physical properties and characteristicsof hydrogen and their values.

Physical Properties and Characteristics of Hydrogen

Property/Characteristic Values (approximate)

Color None

Odor None

Toxicity Nontoxic

Density, liquid (boiling point) 4.4 lb/ft3 (0.07 g/cm3)

Boiling point (1 atm) -423.2 F (-252.9° C)

Critical temperature (188.2 psia) -400.4 F (-240.2° C)

Stoichiometric mixture in air 29 vol %

Flammability limits in air 4–75 vol %

Detonation limits in air 18–60 vol %

Minimum ignition energy in air 20 µJ

Autoignition temperature 1,085° F (585° C)

Volume expansion:

liquid (-252.9° C) to gas (-252.9° C) 1:53

gas (from -252.9° C to 20° C) 1:16

liquid (-252.9° C) to gas (20° C) 1:848

Hazards and Precautions

Hydrogen Gas Safety 6

Hazards of Hydrogen

Flammability and Explosivity Are Primary Hazards

The primary physical hazards associated with hydrogen gas are itsflammability and explosivity. This is because hydrogen can form aflammable mixture with air over a wide range of concentrations(4%Ð75%), and very low energy is needed to ignite hydrogen-airmixtures. Once hydrogen is ignited, the reaction can proceed eitherby deflagration (subsonic propagation) or detonation (supersonicpropagation). Deflagration in a closed volume can cause a pressureincrease of almost eight times the initial pressure. Detonation froma low-energy ignition source is possible in hydrogen-air mixtures of18Ð60% vol that are well mixed and confined. Although hydrogen-air mixtures have the same calorific value per pound as TNT, therate of energy release is much slower for hydrogen-air mixtures.Hydrogen detonations, although rare, are characterized bypressure increases so rapid that pressure-relief devices are usuallyineffective. When using hydrogen in enclosed areas, consultNational Fire Protection Association documents 68 and 69.

Effects on Health

Hydrogen is nontoxic and has even been used as a filler for oxygensources for underwater diving. The primary health effect associatedwith hydrogen is the possibility that it could displace air in a poorlyventilated or confined space, resulting in asphyxiation. However,because it is flammable at only 4% in air, the most significantconcern should be the physical hazard of flammability and thepossibility of burns resulting from fires and explosions. Whenworking with liquid hydrogen, there is an additional health hazard ofcryogenic burns.

Hazards and Precautions

Hydrogen Gas Safety 7

Components of the Supply Systems

Pressure-Relief Devices

In any pressurized system, each component of the system musthave a pressure rating that equals or exceeds the maximumallowable working pressure (MAWP). The MAWP is the maximumpressure at which a system is safe to operate. This is the maximumsetting for the primary pressure relief device.

Hydrogen cylinders must be equipped with pressure-relief devicesto release the gas at or below the MAWP. The relieving capacity ofthe pressure relief device must be sufficient to prevent the systempressure from increasing more than 10% above the MAWP. Thetype of pressure relief device used consists of a frangible diskcombined with a backing of low melting point fusible metaldesigned to burst under a combination of high temperature andexcessive pressure.

Pressure-relief devices are also necessary on all volumes whereliquid hydrogen or cold hydrogen gas can be trapped, and onvacuum insulation spaces surrounding liquid hydrogen. It isimportant that the discharge of pressure-relief devices is ventedoutdoors in a way that avoids impingement of escaping gas onadjacent equipment, structures, or personnel. Vents shall notdischarge where hydrogen can accumulate, such as below eavesof buildings.

Valves

To allow for maintenance activities and emergency response,isolation valves are required. An isolation valve shall be installed atan accessible location in a hydrogen pipeline so that hydrogen flowcan be shut off when necessary.

A special type of isolation valve is the emergency isolation valve(EIV), which provides an automatic or manual means for stoppingthe hydrogen flow in an emergency. EIVs are used on systemswhere branch or multiple distribution lines feed different facilities,and are located outside each building to permit emergency isolationof the system.

In some systems, excess flow valves may be necessary to ensurethat the flow rate of the hydrogen gas does not exceedspecifications. Check valves prevent reverse flow, which couldresult in contamination of the hydrogen gas system. All of thevalves described in this section must be gas tight and made ofmaterials suitable for use with hydrogen.

Hazards and Precautions

Hydrogen Gas Safety 8

Components of the Supply SystemsÑcontinued

Regulators

Shutoff valves that come with gas cylinders cannot be used tocontrol the discharge rate of the gas in use. Additional equipmentthat is required for hydrogen gas delivery systems includesregulators with pressure gauges. As with valves and pipingmaterials, these instruments must be intended for use withhydrogen gas.

The following precautions should be observed when using anyregulator:

• Provide mechanical shielding for regulators to protect them frommechanical damage.

• Make sure that the regulator that is to be used is intended to beused with hydrogen gas.

• Select a regulator with a delivery gauge range approximately 2times the operating pressure and at least 1.2 times the MAWP.Gauges are more accurate in midrange, and regulators aredesigned to operate at about half of the delivery gauge range.

• Never attempt to repair a regulator.

• Never change the delivery gauge on a regulator. Regulatorshave internal safety devices to protect the delivery gauges, andchanging the gauge defeats that protection.

• Never use an adapter.

All component volumes containing hydrogen, including transferlines, should be evacuated or purged with nitrogen or an inert gasbefore and after use. The effectiveness of the purge should beverified.

Electrical Equipment

Because of the extremely low energy required to ignite flammablemixtures of hydrogen gas, you must exercise caution when usinghydrogen around electrical equipment. All flexible hoses and pipingsystems must be electrically grounded. The National Fire ProtectionAssociation has established standards for the specifications ofelectrical equipment intended to be used around hydrogen gas. TheOccupational Safety and Health Administration has alsoestablished specifications for electrical equipment used aroundindoor hydrogen gas systems with a gas volume capacity greaterthan 400 cubic feet. Contact your area safety engineer forassistance in ensuring that these standards are followed.

Hazards and Precautions

Hydrogen Gas Safety 9

Hydrogen Gas Cylinders

Using Hydrogen Gas Cylinders

The following are some safe-handling guidelines that have beenestablished by the Compressed Gas Association for usinghydrogen gas cylinders. By following these guidelines you can helpassure the safety of your hydrogen gas operations.

• It is very important to secure all compressed gas cylinders in anupright position so that they cannot be knocked over.

• Hydrogen gas cylinders should never be used if pressure hasnot been reduced by a suitable regulator at the cylinder, or atthe outlet of the header valve of a cylinder manifold. Use onlyregulators intended to be used with hydrogen and never forceconnections that do not readily fit together.

• Never crack a hydrogen cylinder valve to remove dust or dirtfrom fittings prior to attaching a regulator. While this practicemay be acceptable for other gases, with hydrogen there is a riskof self-ignition.

• Once the regulator is attached, be sure that the regulatoradjusting screw is in the closed position before opening thecylinder valve. When opening the valve, turn the hand wheelslowly so that the hydrogen does not enter the regulatorsuddenly. Never use a wrench, hammer, or other tool to open orclose the hand wheel.

• When opening the cylinder valve to extract content, turn thehand wheel all the way open and then back toward the closedposition one quarter turn. When the work is finished, turn thecylinder valve off and be sure to bleed off all remaininghydrogen from the regulator before removing it from thecylinder.

Hazards and Precautions

Hydrogen Gas Safety 10

Hydrogen Gas CylindersÑcontinued

Moving Hydrogen Gas Cylinders

When moving cylinders, the following general precautions shouldbe observed:

• Replace cylinder valve cap before moving a cylinder from itssecured, in-use position.

• Move cylinders on cylinder carts or with other approvedcylinder-transporting devices.

• Never roll or drop cylinders. Severe foot injury or damage to thecylinder could result.

• Before moving cylinders, remove regulator and secureprotective valve cap, unless cylinder is part of a mobile system(such as a cart-mounted set). If cylinder is part of a mobilesystem, close the cylinder valves and bleed the pressure fromregulators and hoses.

• Never lift cylinders by their protective caps.

• Wear safety shoes or toe protection.

Storing Hydrogen Gas Cylinders

The following points are important to follow for storing hydrogengas cylinders that are awaiting removal or are anticipated for use.

• Hydrogen gas cylinders should be stored outside and away fromdoors, windows, and building air intakes. Indoor storage ofhydrogen requires specially designed facilities. Consult theIndustrial Hygiene and Safety Group (ESH-5) and the FacilityRisk Management Group (ESH-3) before setting up indoorstorage locations for hydrogen cylinders not in use.

• Cylinders must be protected against heat, corrosiveatmospheres, rain, snow accumulation, and direct sunlight. Thestorage area should be paved and easily accessible to deliverytrucks and users with cylinder carts. Cylinder storage areasshould drain readily, which may require that cylinders be placedon pallets or otherwise raised above surrounding surfaces.

• Prevent cylinders from toppling by securing them with chains,cylinder racks, or other devices approved by Operational Safetyat ESH-5.

• Hydrogen must be separated from oxidizing gases when stored.Acceptable separation is a 5-ft-high fire barrier with a half-hourfire rating or a distance of at least 20 ft.

Hazards and Precautions

Hydrogen Gas Safety 11

Ventilation and Alarms

Because of its small molecular size, hydrogen can leak fromapertures through which other gases cannot pass. Ventilation withlarge quantities of air is vital to dilute small leaks of hydrogen tobelow the lower flammable limit of 4% in air. Whenever possible,hydrogen should be stored and used outside, with naturalventilation, or under a shed with a nonpeaked roof and no walls.Indoor locations must have ventilation adequate to handle thelargest anticipated hydrogen leak or spill. Exhaust fans must beexplosion-proof.

Wherever hydrogen is used indoors, flammable gas detectionsystems must be set to go off when the hydrogen concentrationreaches 30% of the lower flammable limit. Sensors should beplaced on or at the height of the ceiling immediately above the pointof anticipated leakage. The alarm should be calibrated annually (ormore often, depending on risk) with a known hydrogen gas mixture.

Emergency Procedures

Hydrogen Gas Safety 12

In an Emergency

Cold Burns

Exposure to cryogenic materials may result in serious injury to bodytissues similar to heat burns. If a worker comes in contact withliquid or cold gaseous hydrogen, he/she should be transported tothe Occupational Medicine Group (ESH-2) or the Los AlamosMedical Center for treatment. If transportation for medical treatmentis not available, the affected area can be thawed with tepid water;however, the area should not be rubbed.

If a Leak Is Detected

When a hydrogen leak is discovered or when an alarm sounds,take the following steps:

1. Evacuate the immediate area of all nonessential personnel.

2. Shut off the hydrogen source immediately and vent allhydrogen to a safe outside location.

3. Increase indoor ventilation with emergency explosion-proofexhaust fans, if possible.

4. Initiate the emergency plan and make the required emergencycontacts. Call 911 and 667-6211 [Emergency Management andResponse (EM&R)].

Emergency Procedures

Hydrogen Gas Safety 13

In an EmergencyÑcontinued

In Case of Fire

To detect a small, local hydrogen fire (the flame is nearly invisible),use a piece of tissue paper on a stick; the paper will readily ignitewhen it contacts a flame. If fire is present, perform the following:

1. Shut off the hydrogen source.

2. Let the fire burn itself out. (If the flame is snuffed out, it mayreignite and cause greater damage.)

3. If you have received hands-on training in the proper operationof a water fire extinguisher then you may use water spray tothermally protect people and equipment if the fire is hot enoughto warrant it. However, a venting hydrogen flame cannotnormally be extinguished with water.

4. Initiate the emergency plan (which should include calling thefire department) and make the required emergency contacts.Call 911 and 667-6211 (EM&R).

Ultraviolet/infrared detectors and alarms should be installed onsystems with the potential for large leaks.

For Nonemergency Assistance

The following are Laboratory points of contact that may be ofassistance in your hydrogen gas system design, set-up, andmaintenance needs.

Organization Service Contact

Area IndustrialHygienists

identifies the industrial hygienistassigned to your operating group

5-4427

Gas Plant provides services to meetcompressed gas procurement andcylinder disposal requirements

7-4406

EM&R coordinates response to emergencysituations at the Laboratory

7-6211

OperationalSafety, ESH-5

provides consultation andassistance to Laboratory pressuresystem users.

7-4644

Cryogenic andLiquified GasSafetyCommittee

Jim Hoffer, Chairman 7-4049

(

Lessons Learned

Hydrogen Gas Safety 14

Lessons Learned

The Rover project (1961), which was never completed, used largeamounts of hydrogen as the rocket propellant in a nuclear rocketengine. Back in those days a serious accident occurred whenhydrogen gas leaked into a large enclosed space and resulted in anexplosion. Ten people inside the space sustained injuries includingbruises, ruptured eardrums, and fractured bones.

The space was covered by a removable sheet metal shed, whichwas completely destroyed by the explosion. Hydrogen had leakedthrough a valve into 500 ft of piping, and when the valve wasopened, the low-pressure hydrogen in the pipe was forced to flowrapidly through a nozzle. It was conjectured that the rapidly movingparticles generated sufficient friction upon exiting the nozzle toignite the hydrogen-air mixture. The ignition energy of a hydrogen-air mixture can be as low as 20 microjoules, an amountapproximately equal to the energy in a small (1 mm3) particle ofsand traveling at 4 m/s (9 mph). The valve was found to bedefective and definitely leaking.

The lesson learned from this accident was that more stringentcontrols needed to be instituted. Administrative controls wereimplemented by appointing managers for day-in-day-out control,and by setting up a status board to schedule operations on dayspreceding major experiments. Physical controls were implementedby adding double-block and bleed-valve configurations between thehydrogen source, a tank farm, and the experimental apparatus. Inthis way, the piping outside the tank farm was guaranteed to befree of gas when none was meant to be flowing.

References

Hydrogen Gas Safety 15

Los Alamos National Laboratory. Laboratory ImplementationRequirement (LIR) 402-1200-01.0, Pressure, Vacuum, andCryogenic Systems, October 1, 1999. Los Alamos NationalLaboratory.

Los Alamos National Laboratory. Technical Bulletin 1403, Gaseousand Liquid Hydrogen. Environment, Safety, and Health Manual,Chapter 1 May 24, 1991. Los Alamos National Laboratory.

Los Alamos National Laboratory. Technical Bulletin 1402,Compressed Gases Environment, Safety, and Health Manual,Chapter 1 May 24, 1991. Los Alamos National Laboratory.

Compressed Gas Association. CGA G-5, Hydrogen. 1991.Compressed Gas Association, Inc., 1235 Jefferson Davis Highway,Arlington, VA 22202.

Compressed Gas Association. CGA G-5.4, Standard for HydrogenPiping Systems at Consumer Locations. 1992. Compressed GasAssociation, Inc., 1235 Jefferson Davis Highway, Arlington, VA22202

Final Quiz

To receive credit for this self-study, you must complete the final quiz. The final quiz is located inthe Training Validation System (TVS).

Caution

• You need a SecureID or Crypto Card that is assigned to you and Administrative Access tothe Lab’s Integrated Computing Network (ICN) to complete the final quiz.

If you do not have a SecureID or Crypto Card that is assigned to you and ICNAdministrative Access, you must complete the final quiz at the ES&H Training Center inWhite Rock.

To schedule a time to complete the final quiz, contact the ESH-13 Registrar either by phoneat 7-0059 between 8:00 am and 12:00 pm or by e-mail at [email protected].

• Do not complete the final quiz using another person’s SecureID or Crypto Card. You canonly receive credit for the final quiz using a SecureID or Crypto Card that is assigned to you.

Starting the Quiz

To start the final quiz, click the Start Quiz button below:

Troubleshooting

• Acrobat Reader for Windows displays error “A Web browser has not been specified. Do youwant to configure the Weblink preferences?”

• Acrobat Reader for Macintosh displays “Select Web Browser” dialog box.

• Clicking Start Quiz button doesn’t bring up Netscape Navigator and/or get error message“The Web browser has not responded to your request for one minute: Terminating request.”.

• You get an error message after submitting the TVS quiz.

• Other problems: Contact CIC-6 Customer Server at 5-4444.

Acrobat Reader for Windows displays error “A Web browser has not beenspecified. Do you want to configure the Weblink preferences?”

If you are using a Windows PC, you may see the error message below when you click the Start Quizbutton:

This message appears when a Web browser has not been selected in the Acrobat Reader WeblinkPreferences. To select a Web browser, follow the instructions below:

1. Click the Yes button on the Acrobat Weblink error dialog box.Acrobat Reader displays the Weblink Preferences window.

2. Click the Browse… button.Acrobat Reader displays the Locate the Web Browser dialog box.

3. Use the dialog box to find your Web browser program, highlight the program name, and click theOpen button.Acrobat Reader puts the path to the Web browser program you selected into the WWW BrowserApplication text box on the Weblink Preferences window.

4. Click the OK button on the Weblink Preferences window.Acrobat Reader closes the Weblink Preferences window, starts the Web browser you selected, andlinks to TVS.

Note: If you need assistance configuring Adobe Acrobat Reader, contact CIC-6 Customer Service at 5-4444.

Return to Starting the Quiz

Acrobat Reader for Macintosh displ ays “Select Web Br owser” dialo g box

If you are using a Macintosh, you may see the dialog box below when you click the Start Quiz button:

This message appears when a Web browser has not been selected in the Acrobat Reader WeblinkPreferences. To select a Web browser, follow the instructions below:

1. Use the dialog box to find your Web browser program, highlight the program name, and click theOpen button.Acrobat Reader puts the name of the Web browser program you selected into the WWW BrowserApplication text box on the Weblink Preferences window.

2 Click the OK button on the Weblink Preferences window.Acrobat Reader closes the Weblink Preferences window, starts the Web browser you selected, andlinks to TVS.

Note: If you need assistance configuring Adobe Acrobat Reader, contact CIC-6 Customer Service at 5-4444.

Return to Starting the Quiz

The Web browser has not responded to your request for one minute:Terminating request.

If you are using a Macintosh, Adobe Acrobat Reader 3.x, and Netscape Navigator 4.x, you may see thefollowing problems when you click on the Start Quiz button:

• Netscape Navigator will fail to appear and• You see the following error message dialog box:

There is a bug in Adobe Acrobat Reader 3.x that creates these problems. In fact, a Netscape Navigatorwindow is open behind the Acrobat Reader window. You can work around the problem by following theinstructions below:

1. Click the OK button on the error message dialog box.Adobe Acrobat closes the error message dialog box and returns to the document window.

2. Click the Application Menu icon on the Mac OS menu bar.The Mac OS displays the Application Menu.

3 Click Netscape Navigator in the Application Menu.The Mac OS displays the Netscape Navigator window.

Note: If you need further assistance, contact CIC-6 Customer Service at 5-4444.

Return to Starting the Quiz

TVS Error Message After Submitting Quiz

If you receive an error message from TVS after you submit your quiz, please contact JohnConlon at 5-8248 or [email protected] with the following information:

• Your z-number• Your name• Your e-mail address• The approximate time you submitted your quiz• Your IP address (if available)

John will check TVS to see if your quiz was graded and contact you with the results.

Return to Starting the Quiz