    Requirement of Hydraulic System

    To fulfill the water requirement of the Under Ground Stations To discharge the Seepage & Sewage of the Under Ground

    Stations

    To fulfill the water requirement of Stations Utilities

    For Fire Suppression System

    INTRODUCTION OF HYDRAULIC SYSTEM IN UNDERGROUND STATIONS

    HydraulicSystemComponents

    PTM Supply System

    Raw Water Pumps and Treated Water Pumps

    Seepage System

    Sewage System

    Service Pumps

  • 8/10/2019 Hydraulic System 2

    2/12

    PTM SUPPLY SYSTEM

    BORE WELL PUMPS

    Installed at Shastri Park Depot at different locations.

    Ratings from 7.5 KW to 10 KW

    Supply ground water to PTM Tanks

    BOOSTER PUMPSInstalled at PTM Room

    Ratings from ..

    Supply Water from PTM Tanks to Different U/G Stations

    VALVES AND PIPES

    Requires to divert the Water supply if there is any

    problem in long distance pipe

  • 8/10/2019 Hydraulic System 2

    3/12

    PTM SUPPLY ARRANGEMENT

  • 8/10/2019 Hydraulic System 2

    4/12

    Raw Water Pumps and

    Treated Water Pumps Raw Water Pump transfer the water from Raw

    Water Tank (RWT) to Treated Water Tank (TWT)

    through Water Treatment Plant

    Water Treatment plant is nothing but is thecombination of Dual Media Filter, Iron Remover

    Filter and Softener

  • 8/10/2019 Hydraulic System 2

    5/12

    Water Treatment Plant withRWP & TWP

  • 8/10/2019 Hydraulic System 2

    6/12

    STATION BORE WELL

    Some Stations are provided with Bore wellSupply that fulfills the Water Requirement ofStation during Emergency Period.

    Normally due to the high level of Hardness oflocal water it is recommended that keep the

    Stations Bore well OFF.

  • 8/10/2019 Hydraulic System 2

    7/12

    SEEPAGE SYSTEM

    It is combination of two or more pumps installed atevery underground station to discharge theseepage water from Seepage Pit to MunicipalStorm Water.

    Their operation based on the level sensors signalsinstalled in the seepage pits

    Their Master/Slave operation decided on the basisof their run-hour recorded by the BMS

    Some of the Seepage Pumps are also installed inbetween the tunnels to extract accumulated waterinside the tunnel (i.e. between NDI & RCK; RCK &

    PCK; BRKR & MDHS etc.)

  • 8/10/2019 Hydraulic System 2

    8/12

    SEEPAGE SYSTEM

    To Municipal Storm

    Water Main

    SEEPAGE

    PIT

    UHL

    VHL

    HL

    LL SEEPAGE PUMP

  • 8/10/2019 Hydraulic System 2

    9/12

    SERVICE PUMPS

    It is combination of two or more pumps installed atevery underground station to discharge theSewage/Toilet water from Sewage Pit to MunicipalSewers/Gutters.

    Their operation based on the level sensors signalsinstalled in the sewage pits.

    Their Master/Slave operation decided on the basisof their run-hour recorded by the BMS

  • 8/10/2019 Hydraulic System 2

    10/12

    SEWAGE SYSTEM

    To Municipal Storm

    Water Main

    SEWAGE

    PIT

    HL

    LL SEWAGE PUMP

  • 8/10/2019 Hydraulic System 2

    11/12

    SEWAGE SYSTEM

    These Pumps are installed at few stations (at thistime only at RCK)

    They supply the soft water to the station service

    tanks to fulfill the stations requirements

    Other stations soft water requirements are fulfilled

    by gravitational flow of soft water

  • 8/10/2019 Hydraulic System 2

    12/12

    SERVICE PUMPS

    To Municipal Storm

    Water Main

    TREATED

    WATER

    TANK

    HL

    LLSEWAGE PUMP

    ONE SIDE

    SERVICE

    TANK

    OTHER SIDE