The HVB range is an “ATEX certified” enclosure / termination solution fullycompliant with the impact, thermal and ingress requirements of EN50014, andis available in a comprehensive range of three different sizes in 3 or 4 poleoptions for a multitude of high voltage termination applications such as highvoltage down-hole pumps & motors. Using the highest quality materials, unique design benefits and precisionmanufacturing the HVB range is the benchmark in standard gauge steelenclosures of its class.
316L Stainless Steel (1.4404 to EN 10088) Superior electro chemically polished. Sheet Steel - Polyester powder coated to RAL 7032. High integrity closed cell chloroprene. Detachable, hinged door with 4 or 6 x M6 captive hex screws & padlock hasp. Complete with transparent IP20 terminal safety cover with nylon fixings. 4 x external welded lugs, 11mm Ø holes / slots. 3mm thick top / bottom gland plates drilled as required. 3 or 4 pole assemblies suitable for up to 30mm wide cable lugs and M12 lug fixings. 6.6kV at 50Hz. AC, 3 phase (earthed or unearthed supply systems) M10 internal / external brass earth stud assembly & M14 for150mm² phase conductor. IP66 to IEC 529. -20°C (-4°F) to +40°C (104°F) ambient. 7 J (Nm) to EN 50014. ATEX ll 2 G EExe ll T4. – 200A / T5 – 180A / T6 – 160A. (BASEEFA03ATEX0052X) ATEX Category 2 (Zone 1) & Industrial IP66.
Material / Finish Options Gasket Material Lid Fixing Box Mounting Gland Plate / Entries Terminations Voltage Ratings Enclosure Earthing Ingress protection Temperature Range Impact Resistance Certification Applications Enclosure / terminal as
semblies configured to meet clients specification within certification parameters.Refer to our website: www.enclosures-crouse-hinds.uk.com for further company & product information.
HVB ENCLOSURE TECHNICAL DATA REV 0305
DIMENSIONS IN MM 458 x 382 762 x 508 914 x 610 914 x 610(HEIGHT X WIDTH X DEPTH) x 200 x 200 x 200 x 200
FIXING CENTRES (Vert. x Horiz.) 305 x 407 508 x 534 559 x 636 559 x 636
CCH PART REFERENCE HVB463820 HVB765120 HVB916120 HVB916120(3-pole) (3-pole) (3-pole) (4-pole)
WEIDMULLER CROSS REFERENCE I II III - 3 pole III - 4 pole
MATERIAL THICKNESS BODY 1.5 2.0 2.0 2.0
LID 1.5 2.0 2.0 2.0
WEIGHT (EMPTY ENCLOSURE) kg 23.75 37.00 45.00 47.00
MAXIMUM RATINGSVOLTAGE (kV) 6.6 6.6 6.6 6.6
CURRENT (A) T4 200 200 200 200T5 180 180 180 180T6 160 160 160 160
Ratings based on an ambient temp temperature of 40 Degrees Centigrade.
MAXIMUM CABLE SIZEMaximum lug width mm 30 30 30 30Maximum cable size sq.mm 150 150 150 150
kcmil (MCM) 300 300 300 300
MAXIMUM WIRING SPACE(Distance between entries) mm 180 335 410 410
AVAILABLE GLANDING AREA TOP & BOTTOM 337 x 108 464 x 108 566 x 108 566 x 108
MAXIMUM No. of ENTRIESTOP & BOTTOM M40 6 8 8 8
M50 4 6 7 7M63 3 4 5 5M75 3 4 4 4
CURRENT RATINGSCable Size
(sq.mm)
16 47 68 7525 62 89 9835 75 110 12250 89 133 14770 160 180 200
Cable Size(AWG)
6 42 59 654 55 80 883 64 92 1022 73 107 1181 81 121 134
1/0 101 141 1562/0 150 173 1923/0 160 180 200
The ratings below relate to all four HVB sizes
T6 T5 T4
Current (A)
T6 T5 T4
Current (A)
HVB ENCLOSURE TECHNICAL DATA(Imperial)
Rev. 0305
DIMENSIONS, inches 18.03" x 15.04" 30" x 20" 35.98" x 24.02" 35.98" x 24.02"
(HEIGHT X WIDTH X DEPTH) x 7.87" x 7.87" x 7.87" x 7.87"
FIXING CENTRES, inches (vert. x horiz.) 12.01" x 16.02" 20" x 21.02" 22.01" x 25.04" 22.01" x 25.04"
CCH PART REFERENCE HVB463820 HVB765120 HVB916120 HVB916120
(3-pole) (3-pole) (3-pole) (4-pole)
WEIDMULLER CROSS REFERENCE I II III - 3 pole III - 4 pole
MATERIAL THICKNESS, mmBODY 1.5 (16 swg) 2.0 (14 swg) 2.0 (14 swg) 2.0 (14 swg)
LID 1.5 (16 swg) 2.0 (14 swg) 2.0 (14 swg) 2.0 (14 swg)
WEIGHT (EMPTY ENCLOSURE) Lbs 52.25 81.40 99.00 103.40
MAXIMUM RATINGSVOLTAGE (kV) 6.6 6.6 6.6 6.6
CURRENT (A) T4 200 200 200 200
T5 180 180 180 180
T6 160 160 160 160Ratings based on an ambient temp temperature of 40 Degrees Centigrade.
MAXIMUM CABLE SIZEMaximum lug width inches 1.18" 1.18" 1.18" 1.18"
Maximum cable size sq.mm 150 150 150 150
kcmil (MCM) 300 300 300 300
MAXIMUM WIRING SPACE(Distance between entries) mm 7.09" 13.19" 16.14" 16.14"
AVAILABLE GLANDING AREA TOP & BOTTOM 13.27" x 4.25" 18.27" x 4.25" 22.28" x 4.25" 22.28" x 4.25"
MAXIMUM No. of ENTRIES gland / hub gland / hub gland / hub gland / hub
TOP & BOTTOM 1 1/2" NPT 5 / 4 7 / 6 8 / 7 8 / 7
2" NPT 4 / 3 6 / 5 7 / 6 7 / 6
2 1/2" NPT 3 / 3 4 / 4 5 / 5 5 / 5
CURRENT RATINGSCable Size
(sq.mm)
16 47 68 7525 62 89 9835 75 110 12250 89 133 14770 160 180 200
Cable Size(AWG)
6 42 59 654 55 80 883 64 92 1022 73 107 1181 81 121 134
1/0 101 141 1562/0 150 173 1923/0 160 180 200
The ratings below relate to all four HVB sizes
Current (A)
T6 T5 T4
Current (A)
T6 T5 T4
XX
Section X-X
Width
Hei
gh
t
Fixing Centres (horizontal)
Fix
ing
Cen
tres
(ve
rtic
al)
Depth
Cover removed for clarity
3-POLE VERSION SHOWN(Refer to data sheet for actual)
3rd angle projection
HVB Range Assembly - General Arrangement
HVB Rev. 0804