The HVB range is an “ATEX certified” enclosure / termination solution fully compliant with the impact, thermal and ingress requirements of EN50014, and is available in a comprehensive range of three different sizes in 3 or 4 pole options for a multitude of high voltage termination applications such as high voltage down-hole pumps & motors. Using the highest quality materials, unique design benefits and precision manufacturing the HVB range is the benchmark in standard gauge steel enclosures of its class. Material / Finish Options Gasket Material Lid Fixing Box Mounting Gland Plate / Entries Terminations Voltage Ratings Enclosure Earthing Ingress protection Temperature Range Impact Resistance Certification Applications Enclosure / terminal assemblies configured to meet clients specification within certification parameters. Refer to our website: www.enclosures-crouse-hinds.uk.com for further company & product information. 316L Stainless Steel (1.4404 to EN 10088) Superior electro chemically polished. Sheet Steel - Polyester powder coated to RAL 7032. High integrity closed cell chloroprene. Detachable, hinged door with 4 or 6 x M6 captive hex screws & padlock hasp. Complete with transparent IP20 terminal safety cover with nylon fixings. 4 x external welded lugs, 11mm Ø holes / slots. 3mm thick top / bottom gland plates drilled as required. 3 or 4 pole assemblies suitable for up to 30mm wide cable lugs and M12 lug fixings. 6.6kV at 50Hz. AC, 3 phase (earthed or unearthed supply systems) M10 internal / external brass earth stud assembly & M14 for150mm² phase conductor. IP66 to IEC 529. -20°C (-4°F) to +40°C (104°F) ambient. 7 J (Nm) to EN 50014. ATEX ll 2 G EExe ll T4. – 200A / T5 – 180A / T6 – 160A. (BASEEFA03ATEX0052X) ATEX Category 2 (Zone 1) & Industrial IP66.

Transcript of HVB “ATEX certified” HVB - Enclosures Cooper Crouse Hinds Datasheet 0405.pdf · The HVB range...

Page 1: HVB “ATEX certified” HVB - Enclosures Cooper Crouse Hinds Datasheet 0405.pdf · The HVB range is an “ATEX certified ... 3mm thick top / bottom gland plates drilled as required.

The HVB range is an “ATEX certified” enclosure / termination solution fullycompliant with the impact, thermal and ingress requirements of EN50014, andis available in a comprehensive range of three different sizes in 3 or 4 poleoptions for a multitude of high voltage termination applications such as highvoltage down-hole pumps & motors. Using the highest quality materials, unique design benefits and precisionmanufacturing the HVB range is the benchmark in standard gauge steelenclosures of its class.

316L Stainless Steel (1.4404 to EN 10088) Superior electro chemically polished. Sheet Steel - Polyester powder coated to RAL 7032. High integrity closed cell chloroprene. Detachable, hinged door with 4 or 6 x M6 captive hex screws & padlock hasp. Complete with transparent IP20 terminal safety cover with nylon fixings. 4 x external welded lugs, 11mm Ø holes / slots. 3mm thick top / bottom gland plates drilled as required. 3 or 4 pole assemblies suitable for up to 30mm wide cable lugs and M12 lug fixings. 6.6kV at 50Hz. AC, 3 phase (earthed or unearthed supply systems) M10 internal / external brass earth stud assembly & M14 for150mm² phase conductor. IP66 to IEC 529. -20°C (-4°F) to +40°C (104°F) ambient. 7 J (Nm) to EN 50014. ATEX ll 2 G EExe ll T4. – 200A / T5 – 180A / T6 – 160A. (BASEEFA03ATEX0052X) ATEX Category 2 (Zone 1) & Industrial IP66.

Material / Finish Options Gasket Material Lid Fixing Box Mounting Gland Plate / Entries Terminations Voltage Ratings Enclosure Earthing Ingress protection Temperature Range Impact Resistance Certification Applications Enclosure / terminal as

semblies configured to meet clients specification within certification parameters.

Refer to our website: www.enclosures-crouse-hinds.uk.com for further company & product information.

Page 2: HVB “ATEX certified” HVB - Enclosures Cooper Crouse Hinds Datasheet 0405.pdf · The HVB range is an “ATEX certified ... 3mm thick top / bottom gland plates drilled as required.

HVB ENCLOSURE TECHNICAL DATA REV 0305

DIMENSIONS IN MM 458 x 382 762 x 508 914 x 610 914 x 610(HEIGHT X WIDTH X DEPTH) x 200 x 200 x 200 x 200

FIXING CENTRES (Vert. x Horiz.) 305 x 407 508 x 534 559 x 636 559 x 636

CCH PART REFERENCE HVB463820 HVB765120 HVB916120 HVB916120(3-pole) (3-pole) (3-pole) (4-pole)

WEIDMULLER CROSS REFERENCE I II III - 3 pole III - 4 pole

MATERIAL THICKNESS BODY 1.5 2.0 2.0 2.0

LID 1.5 2.0 2.0 2.0

WEIGHT (EMPTY ENCLOSURE) kg 23.75 37.00 45.00 47.00

MAXIMUM RATINGSVOLTAGE (kV) 6.6 6.6 6.6 6.6

CURRENT (A) T4 200 200 200 200T5 180 180 180 180T6 160 160 160 160

Ratings based on an ambient temp temperature of 40 Degrees Centigrade.

MAXIMUM CABLE SIZEMaximum lug width mm 30 30 30 30Maximum cable size sq.mm 150 150 150 150

kcmil (MCM) 300 300 300 300

MAXIMUM WIRING SPACE(Distance between entries) mm 180 335 410 410

AVAILABLE GLANDING AREA TOP & BOTTOM 337 x 108 464 x 108 566 x 108 566 x 108

MAXIMUM No. of ENTRIESTOP & BOTTOM M40 6 8 8 8

M50 4 6 7 7M63 3 4 5 5M75 3 4 4 4

CURRENT RATINGSCable Size

(sq.mm)

16 47 68 7525 62 89 9835 75 110 12250 89 133 14770 160 180 200

Cable Size(AWG)

6 42 59 654 55 80 883 64 92 1022 73 107 1181 81 121 134

1/0 101 141 1562/0 150 173 1923/0 160 180 200

The ratings below relate to all four HVB sizes

T6 T5 T4

Current (A)

T6 T5 T4

Current (A)

Page 3: HVB “ATEX certified” HVB - Enclosures Cooper Crouse Hinds Datasheet 0405.pdf · The HVB range is an “ATEX certified ... 3mm thick top / bottom gland plates drilled as required.

HVB ENCLOSURE TECHNICAL DATA(Imperial)

Rev. 0305

DIMENSIONS, inches 18.03" x 15.04" 30" x 20" 35.98" x 24.02" 35.98" x 24.02"

(HEIGHT X WIDTH X DEPTH) x 7.87" x 7.87" x 7.87" x 7.87"

FIXING CENTRES, inches (vert. x horiz.) 12.01" x 16.02" 20" x 21.02" 22.01" x 25.04" 22.01" x 25.04"

CCH PART REFERENCE HVB463820 HVB765120 HVB916120 HVB916120

(3-pole) (3-pole) (3-pole) (4-pole)

WEIDMULLER CROSS REFERENCE I II III - 3 pole III - 4 pole

MATERIAL THICKNESS, mmBODY 1.5 (16 swg) 2.0 (14 swg) 2.0 (14 swg) 2.0 (14 swg)

LID 1.5 (16 swg) 2.0 (14 swg) 2.0 (14 swg) 2.0 (14 swg)

WEIGHT (EMPTY ENCLOSURE) Lbs 52.25 81.40 99.00 103.40

MAXIMUM RATINGSVOLTAGE (kV) 6.6 6.6 6.6 6.6

CURRENT (A) T4 200 200 200 200

T5 180 180 180 180

T6 160 160 160 160Ratings based on an ambient temp temperature of 40 Degrees Centigrade.

MAXIMUM CABLE SIZEMaximum lug width inches 1.18" 1.18" 1.18" 1.18"

Maximum cable size sq.mm 150 150 150 150

kcmil (MCM) 300 300 300 300

MAXIMUM WIRING SPACE(Distance between entries) mm 7.09" 13.19" 16.14" 16.14"

AVAILABLE GLANDING AREA TOP & BOTTOM 13.27" x 4.25" 18.27" x 4.25" 22.28" x 4.25" 22.28" x 4.25"

MAXIMUM No. of ENTRIES gland / hub gland / hub gland / hub gland / hub

TOP & BOTTOM 1 1/2" NPT 5 / 4 7 / 6 8 / 7 8 / 7

2" NPT 4 / 3 6 / 5 7 / 6 7 / 6

2 1/2" NPT 3 / 3 4 / 4 5 / 5 5 / 5

CURRENT RATINGSCable Size

(sq.mm)

16 47 68 7525 62 89 9835 75 110 12250 89 133 14770 160 180 200

Cable Size(AWG)

6 42 59 654 55 80 883 64 92 1022 73 107 1181 81 121 134

1/0 101 141 1562/0 150 173 1923/0 160 180 200

The ratings below relate to all four HVB sizes

Current (A)

T6 T5 T4

Current (A)

T6 T5 T4

Page 4: HVB “ATEX certified” HVB - Enclosures Cooper Crouse Hinds Datasheet 0405.pdf · The HVB range is an “ATEX certified ... 3mm thick top / bottom gland plates drilled as required.

XX

Section X-X

Width

Hei

gh

t

Fixing Centres (horizontal)

Fix

ing

Cen

tres

(ve

rtic

al)

Depth

Cover removed for clarity

3-POLE VERSION SHOWN(Refer to data sheet for actual)

3rd angle projection

HVB Range Assembly - General Arrangement

HVB Rev. 0804