CONTENTINTRODUCTION ________________________________________________2
PVC INSULATED CABLES 450/750 V, BS 6004 OR MS 136 ____________________________________3
PVC INSULATED, PVC SHEATHED UNARMOURED CABLE 300/500 V, BS 6346 OR MS 274 ____________________________________4
PVC INSULATED, PVC SHEATHED ARMOURED CABLE 600/1000 V, BS 6346 OR MS 274 ___________________________________7
PVC INSULATED, PVC SHEATHED ARMOURED AUXILIARY CABLE 600/100 V, BS 6346 OR MS 274 ___________________________________10
PVC INSULATED, PVC SHEATHED UNARMOURED WITH REDUCED NEUTRAL CABLE 600/1000 V, BS 6346 OR MS 274 __________________________________12
PVC INSULATED, PVC SHEATHED ARMOURED WITH REDUCED NEUTRAL CABLE 600/1000 V, BS 6346 OR MS 274 __________________________________13
CURRENT RATING
RATING FACTOR ______________________________________________14
CURRENT RATING _____________________________________________16
APPENDIX: TECHNICAL DATA
STRANDED ANNEALED COPPER AND ALUMINIUM CONDUCTORS FORMULA FOR ELECTRICAL CALCULATION ______________________21
WIRE GAUGES ________________________________________________23
COMMON CONVERSION FACTOR ________________________________24
PUBLICATIONS REFERRED TO __________________________________24
2
INTRODUCTIONLeader Cable Industry Berhad, incorporated in 1976, has grown steadily to become the country’s single largest cable manufacturer today since its 1990 merger with Universal Cable (M) Berhad under the flagship of its parents, Leader Universal Holdings Berhad (LEADER).
Through its far sighted planning and unceasing product and service innovation, LCIB has successfully cultivated a manufacturing profile of an extensive range of cable and wire products. From households, XLPE cables, telecommunication cables for both domestic and export markets. LCIB has achieved a distinguished reputation as a leading supplier of power and telecommunication cable to major corporations, both local and foreign.
Today, as a subsidiary of the LEADER group of companies, LCIB has one of the most advanced facilities for manufacturing PVC insulated cables in the Asia-Pacific region. The PVC insulated cables manufactured today by LCIB are internationally renowned for its world class quality standards.
PVC has been in use as an insulating and outersheathing material for a long time. Since PVC has some degree of flame retardance, and resistance to oils and chemicals, it has found many suitable applications including low power and control uses. Generally, there are two types of PVC, general purpose and heat resistant PVCs with maximum conductor temperatures of 70°C and 90°C respectively. PVC insulated cables are used in power distribution, building wire, appliance wiring, flexible cord and machine tool wiring. Communication applications use polyvinyl chloride coverings on a limited basis. Insulation and jackets made from polyvinyl chloride have a number of desirable properties that make them the insulation and jacketing material of choice for many common applications. These properties include flexibility, resistance to temperature, resistance to adverse environmental situations and low cost .
This catalogue serves as a guide to LCIB’s manufacturing processes and standards in the production of PVC insulated cables, both armoured and unarmoured, including one with reduced neutral conductor and a maximum phase-to-phase voltage of 1000 volt. The conductor used is mainly plain annealed copper. Other conductors, such as tinned copper and aluminium are also available and may be supplied upon request.
3
CU / PVC INSULATED CABLEConductor Plain annealed copper
Insulation PVC Compound
Colour of cores Red, Yellow, Blue, Black, White and Green or Green/Yellow
Conductor Thicknessof Insulation
Approx. overall diameter Approx net weight
Area Shapemm² mm mm Kg / Km
MS 136, BS 6004 & IEC 60227, 450/750 V1.51.52.5
2.546
101625
355070
95120150
185240300
400500630
s.c.r.m.s.c.
r.m.r.m.r.m.
r.m.r.m.c.c.
c.c.c.c.c.c.
c.c.c.c.c.c.
c.c.c.c.c.c.
c.c.c.c.c.c.
0.70.70.8
0.80.80.8
1.01.01.2
1.21.41.4
1.61.61.8
2.02.22.4
2.62.82.8
2.93.03.5
3.64.24.7
6.16.88.4
9.611.212.9
15.016.618.4
20.623.426.1
29.332.736.4
212333
355172
120175280
370500710
98012201490
187024503070
392049406280
Note : s.c. - solid circular, r.m. - circular stranded, c.c. - compacted circular stranded
4
PVC INSULATED, PVC SHEATHED UNARMOURED CABLE ConductorsPlain annealed copper or aluminium
InsulationGeneral purpose PVC compound
Colour of coresSingle core - red and black 2 cores - red and black 3 cores - red, yellow and blue 4 cores - red, yellow, blue and black
Formation (i) Single core(ii) 2, 3, or 4 cores - stranded together and the interstices may be filled with the sheathing compound or textile. A non-
hygroscopic binder tape may be applied over the laid-up cores.
SheathBlack general purpose PVC compound
PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (1-CORE)
ConductorThickness of
Insulation Thickness of sheath Approx. overall diameter Approx. net weightNominal
sectio nal area Shape
mm2 No./mm mm mm mm kg/km
BS 6004, 300/500V
1.52.54610162535
r.m.r.m.r.m.r.m.r.m.r.m.c.c.c.c.
0.70.80.80.81.01.01.21.2
0.80.80.90.90.91.01.11.1
4.75.36.36.88.29.411.312.6
37517699
150220340440
BS 6346 & MS 274, 600/1000V
5070951201501852403004005006308001000
c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.r.m.
1.41.41.61.61.82.02.22.42.62.82.82.83.0
1.41.41.51.51.61.71.81.92.02.12.22.32.5
14.916.919.220.823
25.528.831.835.439.143.347.853.1
6108301130138016902100274034104310538068208590
10760
Note : r.m. - circular stranded, c.c. - compacted circular stranded
5
PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (2-CORE)
ConductorThickness of
InsulationThickness of
sheathApprox. overall
diameter Approx. net weightNominal sectional area Shape
mm2 No./mm mm mm mm kg/km
BS 6004, 300/500V
1.51.52.52.546
s.c.r.m.s.c.r.m.r.m.r.m.
0.70.70.80.80.80.8
1.21.21.21.21.21.2
8.58.99.7
10.111.212.3
100110140150200260
BS 6346 & MS 274, 600/ 1000V
10162535507095120150185240300400
r.m.r.m.c.c.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.
1.01.01.21.21.41.41.61.61.82.02.22.42.6
1.81.81.81.81.81.92.02.12.22.42.52.72.9
16.218.321.019.922.725.529.231.835.039.143.948.653.9
450620880920
122016702270280034104270556069308770
PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (3-CORE)
ConductorThickness of
InsulationThickness of
sheathApprox. overall
diameter Approx. net weightNominal sectional area Shape
mm2 No./mm mm mm mm kg/km
BS 6004, 300/500V
1.51.52.52.546
s.c.r.m.s.c.r.m.r.m.r.m.
0.70.70.80.80.80.8
1.21.21.21.21.21.4
8.99.4
10.210.711.913.5
120130170180240320
BS 6346 & MS 274, 600/ 1000V
10162535507095120150185240300400
r.m.r.m.c.c.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.
1.01.01.21.21.41.41.61.61.82.02.22.42.6
1.81.81.81.81.81.92.12.22.32.52.62.83.1
17.219.422.322.826.129.534.137.140.945.751.457
63.6
530750
109013601810248033904180511064108360
1042013210
Note : s.c. - solid circular, r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded
6
PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (4-CORE)
ConductorThickness of
InsulationThickness of
sheathApprox. overall
diameter Approx. net weightNominal sectional area Shape
mm2 No./mm mm mm mm kg/km
BS 6004, 300/500V
1.51.52.52.546
s.c.r.m.s.c.r.m.r.m.r.m.
0.70.70.80.80.80.8
1.21.21.21.21.41.4
9.710.211.111.713.414.7
150160210220310410
BS 6346 & MS 274, 600/ 1000V
10162535507095120150185240300400
r.m.r.m.c.c
s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.
1.01.01.21.21.41.41.61.61.82.02.22.42.6
1.81.81.81.81.92.02.22.32.52.62.83.13.3
18.721.324.525.629.633.538.742.146.651.958.665.372.6
700960
14001820245033504580563069208640112901411017860
Note : s.c. - solid circular, r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded
7
PVC INSULATED, PVC SHEATHED ARMOURED CABLEConductor Plain annealed copper or aluminium
Insulation General purpose PVC compound
Colour of cores Single core - red and black2 cores - red and black3 cores - red, yellow and blue4 cores - red, yellow, blue and black Formation(i) Single core(ii) 2,3, or 4 cores - stranded together and the interstices may be filled with the sheathing compound or textile. A non-
hygroscopic binder tape may be applied over the laid-up cores.
Bedding Black general purpose PVC compound
Armour Single core - Aluminium wire2,3, or 4 cores - Galvanised steel wire
Sheath Black general purpose PVC compound
PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (1-CORE)
ConductorThickness of
InsulationThickness of
beddingDiameter of armour wire
Thickness of sheath
Approx. overall
diameter
Approx. net weightNominal
sectional area Shape
mm2 No./mm mm mm mm mm mm kg/km
BS 6346 & MS 274, 600/ 1000V
507095120
150185240300
4005006308001000
c.c.c.c.c.c.c.c.
c.c.c.c.c.c.c.c.
c.c.c.c.c.c.c.c.r.m.
1.41.41.61.6
1.82.02.22.4
2.62.82.82.83.0
0.80.80.81.0
1.01.01.01.0
1.21.21.21.41.4
1.251.251.251.6
1.61.61.61.6
2.02.02.02.52.5
1.51.61.61.7
1.71.81.91.9
2.12.12.22.42.5
19.421.423.726.6
28.631.134.437.2
42.245.749.955.961.1
840109014101790
2120258032703970
5110523077609890
12180
Note : r.m. - circular stranded, c.c. - compacted circular stranded
8
PVC INSULATED, PVC SHEATHED ARMOURED CABLE (2-CORE)
ConductorThickness of
InsulationThickness of
beddingDiameter of armour wire
Thickness of sheath
Approx. overall
diameter
Approx. net weight
Nominal sectional
areaShape
mm2 No./mm mm mm mm mm mm kg/km
BS 6346 & MS 274, 600/ 1000V
1.51.52.52.5
461016
25355070
95120150185
240300400
s.c.r.m.s.c.r.m.
r.m.r.m.r.m.r.m.
c.c.s.m.s.m.s.m.
s.m.s.m.s.m.s.m.
s.m.s.m.s.m.
0.60.60.70.7
0.80.81.01.0
1.21.21.41.4
1.61.61.82.0
2.22.42.6
0.80.80.80.8
0.80.80.80.8
1.01.01.01.0
1.21.21.21.4
1.41.61.6
0.90.90.90.9
0.91.9
1.251.25
1.61.61.61.6
2.02.02.02.5
2.52.52.5
1.31.41.41.4
1.41.51.61.6
1.71.81.91.9
2.12.22.32.4
2.52.72.9
11.912.513.313.7
15.216.520.122.2
26.225.328.330.9
36.038.641.847.1
51.957.062.3
290310360380
460550870
1090
1610169021002640
3680431050606570
8110979011940
PVC IINSULATED, PVC SHEATHED ARMOURED CABLE (3-CORE)
ConductorThickness of
InsulationThickness of
beddingDiameter of armour wire
Thickness of sheath
Approx. overall
diameter
Approx. net weight
Nominal sectional
areaShape
mm2 No./mm mm mm mm mm mm kg/km
BS 6346 & MS 274, 600/ 1000V
1.51.52.52.5
461016
25355070
95120150185
240300400
s.c.r.m.s.c.r.m.
r.m.r.m.r.m.r.m.
c.c.s.m.s.m.s.m.
s.m.s.m.s.m.s.m.
s.m.s.m.s.m.
0.60.60.70.7
0.80.81.01.0
1.21.21.41.4
1.61.61.82.0
2.22.42.6
0.80.80.80.8
0.80.80.80.8
1.01.01.01.2
1.21.21.41.4
1.61.61.6
0.90.90.90.9
0.91.251.251.25
1.61.61.62.0
2.02.02.52.5
2.52.52.5
1.41.41.41.4
1.41.51.61.6
1.71.81.92.0
2.12.22.42.5
2.62.83.0
12.312.913.814.3
15.918.021.123.3
27.528.231.736.3
40.743.749.153.7
59.865.471.8
320340390410
530750
10201300
1930223028203900
4990591075309060
114101378016860
Note : s.c. - solid circular, r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded
9
PVC INSULATED , PVC SHEATHED ARMOURED CABLE (4-CORE)
ConductorThickness of
InsulationThickness of
beddingDiameter of armour wire
Thickness of sheath
Approx. overall
diameter
Approx. net weight
Nominal sectional
areaShape
mm2 No./mm mm mm mm mm mm kg/km
BS 6346 & MS 274, 600/ 1000V
1.51.52.52.5
461016
25355070
95120150185
240300400
s.c.r.m.s.c.r.m.
r.m.r.m.r.m.r.m.
c.c.s.m.s.m.s.m.
s.m.s.m.s.m.s.m.
s.m.s.m.s.m.
0.60.60.70.7
0.80.81.01.0
1.21.21.41.4
1.61.61.82.0
2.22.42.6
0.80.80.80.8
0.80.80.81.0
1.01.01.21.2
1.21.41.41.6
1.61.61.8
0.90.90.90.9
1.251.251.251.6
1.61.62.02.0
2.02.52.52.5
2.52.5
3.15
1.41.41.41.4
1.51.51.61.7
1.81.92.02.1
2.22.42.52.6
2.83.03.3
13.013.714.615.2
17.919.222.626.5
29.931.236.440.3
45.350.354.660.3
67.073.582.7
360380450470
730870
12001770
2340281038804960
64008110963011700
147501786023110
Note : s.c. - solid circular, r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded
10
PVC INSULATED, PVC SHEATHED ARMOURED CABLEConductor Plain annealed copper
Insulation General purpose PVC compound
Colour of cores White with black numbering
Formation Stranded together and the interstices may be filled with the sheathing compound. A non-hygroscopic binder tape may be applied over the laid-up cores
Bedding Black general purpose PVC compound
Armour Galvanised steel wire
Sheath Black general purpose PVC compound
PVC INSULATED, PVC SHEATHED ARMOURED AUXILIARY CABLE (1.5 mm2)
Number of core
Nominal sectional
area
Construction, Number/ Wire
diameter
Thickness of
Insulation
Thickness of bedding
Diameter of armour
wire
Thickness of sheath
Approx. overall
diameter
Approx. net weight
mm2 No./mm mm mm mm mm mm kg/km
BS 6346 & MS 274, 600/ 1000 V
571012
19273748
1.51.51.51.5
1.51.51.51.5
7/0.537/0.537/0.537/0.53
7/0.537/0.537/0.537/0.53
0.60.60.60.6
0.60.60.60.6
0.80.80.80.8
0.81.01.01.0
0.90.9
1.251.25
1.251.61.61.6
1.41.41.51.5
1.61.71.81.9
14.515.419.219.6
22.326.929.533.1
430500780830
1090160019402360
11
PVC INSULATED, PVC SHEATHED ARMOURED AUXILIARY CABLE (2.5mm2)
Number of core
Nominal sectional
area
Construction, Number/ Wire
diameter
Thickness of
Insulation
Thickness of bedding
Diameter of armour
wire
Thickness of sheath
Approx. overall
diameter
Approx. net weight
mm2 No./mm mm mm mm mm mm kg/km
BS 6346 & MS 274, 600/ 1000 V
571012
19273748
2.52.52.52.5
2.52.52.52.5
7/0.677/0.677/0.677/0.67
7/0.677/0.677/0.677/0.67
0.70.70.70.7
0.70.70.70.7
0.80.80.80.8
111
1.2
0.91.251.251.25
1.61.61.62.0
1.51.51.61.6
1.71.81.92.1
16.418.121.822.4
26.730.934.139.8
55075010001080
1640211026003520
PVC INSULATED, PVC SHEATHED ARMOURED AUXILIARY CABLE (4 mm2)
Number of core
Nominal sectional
area
Construction, Number/ Wire
diameter
Thickness of
Insulation
Thickness of bedding
Diameter of armour
wire
Thickness of sheath
Approx. overall
diameter
Approx. net weight
mm2 No./mm mm mm mm mm mm kg/km
BS 6346 & MS 274, 600/ 1000 V
571012
19273748
4444
4444
7/0.857/0.857/0.857/0.85
7/0.857/0.857/0.857/0.85
0.80.80.80.8
0.80.80.80.8
0.80.81.01.0
1.01.21.21.2
1.251.251.61.6
1.62.02.02.0
1.51.61.71.7
1.82.02.12.2
19.120.626.126.8
30.637.241.046.1
82097015001630
2170317039104790
12
PVC INSULATED, PVC SHEATHED UNARMOURED WITH REDUCED NEUTRAL CABLE (3C + E)ConductorPlain annealed copper
InsulationGeneral purpose PVC compound
Colour of coresRed, yellow, blue and black (neutral)
FormationStranded together and the interstices may be filled with the sheathing compound or textile. A non-hygroscopic binder tape may be applied over the laid-up cores
SheathBlack general purpose PVC compound
PVC INSULATED, PVC SHEATHED UNARMOURED WITH REDUCED NEUTRAL CABLE
Phase Conductor Neutral ConductorThickness of sheath
Approx. overall
diameter
Approx. net weight
Nominal sectional
areaShape Thickness of
Insulation
Nominal sectional
areaShape
Thickness of
Insulation
mm2 No./mm mm mm2 No./mm mm mm mm kg/km
BS 6346 & MS 274, 600/ 1000 V
25355070
95120150185
240300300400
c.c.s.m.s.m.s.m.
s.m.s.m.s.m.s.m.
s.m.s.m.s.m.s.m.
1.21.21.41.4
1.61.61.82.0
2.22.42.42.6
16162535
50707095
120150185185
r.m.r.m.c.c.c.c.
c.c.c.c.c.c.c.c.
c.c.c.c.c.c.c.c.
1.01.01.21.2
1.41.41.41.6
1.61.82.02.0
1.81.81.92.0
2.12.22.42.5
2.72.92.93.2
24.525.629.633.5
38.541.946.451.7
58.464.864.872.4
1,2901,6502,2503,060
4,1505,1606,2307,850
10,19012,67012,94016,050
Note : r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded
13
PVC INSULATED, PVC SHEATHED ARMOURED WITH REDUCED NEUTRAL CABLE (3C + E)ConductorPlain annealed copper
InsulationGeneral purpose PVC compound
Colour of coresRed, yellow, blue and black (neutral)
FormationStranded together and the interstices may be filled with the sheathing compound or textile. A non-hygroscopic binder tape may be applied over the laid-up cores.
BeddingBlack general purpose PVC compound
ArmourGalvanised steel wire
SheathBlack general purpose PVC compound
PVC INSULATED, PVC SHEATHED UNARMOURED WITH REDUCED NEUTRAL CABLE
Phase Conductor Neutral Conductor Thickness of
bedding
Diameter of armour
wire
Thickness of sheath
Approx. overall
diameter
Approx. net
weightNominal sectional
areaShape
Thickness of
Insulation
Nominal sectional
areaShape
Thickness of
Insulation
mm2 No./mm mm mm2 No./mm mm mm mm mm mm kg/km
BS 6346 & MS 274, 600/ 1000 V
25355070
95120150185
240300300400
c.c.s.m.s.m.s.m.
s.m.s.m.s.m.s.m.
s.m.s.m.s.m.s.m.
1.21.21.41.4
1.61.61.82.0
2.22.42.42.6
16162535
50707095
120150185185
r.m.r.m.c.c.c.c.
c.c.c.c.c.c.c.c.
c.c.c.c.c.c.c.c.
1.01.01.21.2
1.41.41.41.6
1.61.82.02.0
1.01.01.01.2
1.21.41.41.4
1.61.61.61.8
1.61.61.62.0
2.02.52.52.5
2.52.52.5
3.15
1.81.81.92.0
2.22.32.42.5
2.72.92.93.1
29.931.035.040.1
45.350.154.459.7
66.873.273.282.3
2,2202,6303,3704,560
5,9807,6307,93010,840
16,64016,44016,71021,260
Note : r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded
14
RATING FACTORS FOR GROUPS OF MORE THAN ONE CIRCUIT OF SINGLE - CORE CABLES, OR MORE THAN ONE MULTICORE CABLES
Methof of installation
Rating factor
Number of circuits or multicore cables
2 3 4 5 6 7 8 9 10 12 14 16 18 20
Enclosed, or bunched and clipped direct to a non-metallic surface 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38
Single layer clipped to a non-metallic surface
Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 - - - - - -
Spaced* 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 -
Single layer multicore on a perforated metal cable tray, vertical or horizontal
Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72 0.71 0.70 - - - -
Spaced* 0.91 0.89 0.88 0.87 0.87 - - - - - - - - -
Single layer single-core on a perforated metal cable tray, touching
Horizontal 0.90 0.85 - - - - - - - - - - - -
Vertical 0.85 - - - - - - - - - - - - -
Single layer multicore touching on ladder support 0.86 0.82 0.80 0.79 0.78 0.78 0.78 0.77 - - - - - -
* NOTE : Spaced by a clearance between adjacent surfaces of at least one cable diameter. Where the horizontal clearances between adjacent cables exceeds twice cable diameter no correction factor needs to be applied.
15
RATING FACTORS FOR CABLES INSTALLED IN ENCLOSED TRENCHES
Conductor cross
sectional area
Rating Factor
Trench size 450mm wide x 300 mm deep
Trench size 450mm wide x 600mm deep
Trench size 600mm wide x 760mm deep
2 single core
cables, or 1 three-or four core cables
3 single core
cables, or 2 two-core
cables
4 single core
cables, or 2 three-
or four-core cables
6 single core
cables, 4 two-core cables or 3 three-or four-core cables
6 single core
cables, 4 two-core cables or 3 three-or four-core cables
8 single core
cables, 4 three- or four-core
cable
12 single core
cables, 8 two- or 6 three-core or
four-core cables
12 single core
cables, 8 two- or 6 three-core or
four-core cables
18 single core
cables, 12 two-
core cables or 9 three- or four-core cables
24 single core
cables, 16 two-core cables or 12
three- or four-core cables
mm²
461016
2535507095
120150185240300
400500630
0.930.920.910.91
0.900.890.880.870.86
0.850.840.830.820.81
0.800.780.77
0.900.890.880.87
0.860.850.840.820.81
0.800.780.770.760.74
0.730.720.71
0.870.860.850.84
0.820.810.790.780.76
0.750.740.730.710.69
0.670.660.65
0.820.810.800.78
0.760.750.740.720.70
0.690.670.650.630.62
0.590.580.56
0.860.860.850.85
0.810.800.780.770.75
0.730.720.700.690.68
0.660.640.63
0.830.820.800.78
0.760.740.730.720.70
0.680.670.650.630.62
0.600.580.57
0.760.750.740.71
0.690.680.660.640.63
0.610.590.580.560.54
0.520.510.49
0.810.8
0.780.76
0.740.720.710.7
0.68
0.660.640.630.610.59
0.570.560.54
0.740.730.720.70
0.670.660.640.620.60
0.580.570.550.530.52
0.500.480.47
0.690.680.660.64
0.620.600.590.570.55
0.530.510.490.480.46
0.440.430.41
*NOTE: When cables having different conductor operating temperatures are grouped together the current rating shall be based on the lowest operating temperature of any cable in the group.
Type of protection
Rating Factor
Ambient temperature (oC)
25 30 35 40 45 50 55 60 65
Protective device is intended to provide short-circuit protection only*
1.03 1.0 0.94 0.87 0.79 0.71 0.61 0.50 0.35
Protective device is a semi-enclosed fuse to BS 3036 1.03 1.0 0.97 0.94 0.91 0.87 0.84 0.69 0.48
* NOTE: Except where the device is a semi-enclosed fuse to BS 3036, the factor also applies where the device is intended to provide overload protection.
16
CURRENT-CARRYING CAPACITY FOR SINGLE-CORE, NON-ARMOURED WITH OR WITHOUT SHEATH TO BS 6004 AND BS 6346
Conductor cross
sectional area
Current-carrying capacity
Method of installation
Enclosed in conduit in thermally insulated wall etc.
Enclosed in conduit on a wall or in trunking etc.
Clipped directOn a perforated
cable tray horizontal or vertical
In free air
Horizontal flat
spaced
Vertical flat
spacedTrefoil
2 cables, single-phase a.c. or
d.c.
3 or 4 cables three-phase a.c.
2 cables, single-phase a.c. or
d.c.
3 or 4 cables three-phase a.c.
2 cables, single-phase a.c. or d.c. flat
and touching
3 or 4 cables three-phase a.c. flat
and touching of trefoil
2 cables, single-phase a.c. or d.c. flat
and touching
3 or 4 cables three-phase a.c. flat
and touching of trefoil
2 cables, single-
phase a.c. or d.c. or 3 cables
three-phase a.c.
2 cables, single-phase a.c. or
d.c. or 3 cables three-phase
a.c.
3 cables, trefoil, three phase
a.c.
mm2 A A A A A A A A A A A
1.5
2.5461016
2535507095
120150185240300
4005006308001000
14.5
19.526344661
8099119151182
210240273320367
-----
13.5
1824314256
7389
108136164
188216245286328
-----
17.5
2432415776
101125151192232
269300341400458
546626720
--
15.5
2128365068
89110134171207
239262296346394
467533611
--
20
2737476587
114141182234284
330381436515594
694792904
10301151
18
2533435979
104129167214261
303349400472545
634723826943
1058
-
-----
126156191246300
349404463549635
732835953
10861216
-
-----
112141172223273
318369424504584
679778892
10201149
-
-----
146181219281341
396456521615709
852982113812651420
-
-----
130162197254311
362419480569659
795920
107011881337
-
-----
110137167216264
308356409485561
656749855971
1,079
17
VOLTAGE DROP FOR SINGLE-CORE, NON-ARMOURED WITH OR WITHOUT SHEATH TO BS 6004 AND BS 6346
Conductorcross
sectionalarea
2cabled.c.
2 cables, single-phase a.c. 3 or 4 cables, three-phase a.c.
Enclosed in conduit etc.
in or on a wall
Clipped direct
or on traystouching
In free air(spaced*)
Enclosed in conduit etc.
inor on a wall
Clipped direct,
on trays orin free air(in trefoil)
Clipped direct
or on trays (flat andtouching)
In free air(flat spaced*)
mm2 mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m1.52.54
61016
253550
7095120
150185240
300400500
6308001000
291811
7.34.42.8
1.751.250.93
0.630.460.36
0.290.230.180
0.1450.1050.086
0.0680.0530.042
291811
7.34.42.8
1.801.301.00
0.720.560.47
0.410.370.33
0.310.290.28
0.27--
291811
7.34.42.8
1.751.250.95
0.660.500.41
0.340.290.25
0.220.20
0.185
0.1750.1650.160
291811
7.34.42.8
1.801.300.97
0.690.540.45
0.390.350.31
0.290.270.26
0.250.250.24
25159.5
6.43.82.4
1.551.100.85
0.610.480.41
0.360.320.29
0.270.250.25
0.24--
25159.5
6.43.82.4
1.501.100.82
0.570.430.36
0.300.260.22
0.1900.1750.160
0.1500.1450.140
25159.5
6.43.82.4
1.551.100.84
0.600.470.40
0.340.310.27
0.250.240.23
0.220.220.21
25159.5
6.43.82.4
1.551.150.86
0.630.510.44
0.400.360.34
0.320.310.30
0.290.290.28
NOTE : * Spacings larger than those specified in free air will result in larger voltage drop.
18
CURRENT-CARRYING CAPACITY FOR MULTICORE, NON-ARMOURED TO BS 6004 AND BS 6346
Conductor cross
sectional area
Current-carrying capacity
Method of installation
Enclosed in conduit in thermally insulated wall etc.
Enclosed in conduit on a wall or in trunking etc. Clipped direct On a perforated cable tray
OR in free air
1 two-core cable, single-phase a.c. or
d.c.
1 three-core cable or 1 four-core
cable, three phase a.c.
1 two-core cable, single-
phase a.c. or d.c.
1 three-core cable or 1 four-core
cable, three phase a.c.
1 two-core cable, single
phase a.c. or d.c.
1 three-core cable or 1 four-
core, three phase a.c.
1 two-core cable, single-
phase a.c. or d.c.
1 three-core cable or 1 four-
core cable, three phase
a.c.
mm² A A A A A A A A
1.5
2.5461016
2535507095
120150185240300
400
14
18.525324357
7592110139167
192219248291334
-
13
17.523293952
688399
125150
172196223261298
-
16.5
2330385269
90111133168201
232258294344394
470
15
2027344662
8099118149179
206225255297339
402
19.5
2736466385
112138168213258
299344392461530
634
17.5
2432415776
96119144184223
259299341403464
557
22
3040517094
119148180232282
328378434514593
715
18.5
2534436080
101126153196238
276319364430497
597
VOLTAGE DROP FOR MULTICORE, NON-ARMOURED TO BS 6004 AND BS 6346
Conductor cross-section area Two-core cable, d.c. Two-core cable, single-phase a.c.
Three-or four-core cable, three-phase a.c.
mm2 mV / A/m mV / A/m mV / A/m1.52.54
61016
253550
7095120
150185240
300400
291811
7.34.42.8
1.751.250.93
0.630.460.36
0.290.23
0.180
0.1450.105
291811
7.34.42.8
1.751.250.94
0.650.500.41
0.340.290.24
0.210.185
25159.5
6.43.82.4
1.501.100.81
0.570.430.35
0.290.250.21
0.1850.160
19
CURRENT-CARRYING CAPACITY FOR SINGLE-CORE ARMOURED TO BS 6346
Ambient temperature : 30°C
Conductorcross
sectionalarea
Current-carrying capacityMethod of installation
Clipped direct On a perforatedcable tray
In free air2 cables,
single-phase a.c. 2 cables, d.c. 3 or 4 cables, three-phase a.c.
2 cables,single-phasea.c. or d.c.
flat andtouching
3 or 4 cablesthree-phasea.c. flat
and touching
2 cables,single-phasea.c. or
d.c.flat andtouching
3 or 4 cablesthree-phasea.c. flat
and touching
Horizontalflat
spaced
Verticalflat
spaced
Horizontalspaced
Verticalspaced
Horizontalflat
spaced
Verticalflat
spaced
3 cablestrefoil
mm2 A A A A A A A A A A A507095
120150185
240300400
5006308001000
193245296
342395447
525594687
763843919975
179225269
309354399
465515575
622669710737
205259313
360415469
550624723
805891976
1041
189238285
327375422
492547618
673728777808
229287349
401456511
593668737
810893943
1008
217272332
383436489
568640707
777856905967
229294357
415482548
648748885
1035121814411685
216279340
396460525
622719851
997117413901627
230286338
385436490
566616674
721771824872
212263313
357407456
528578632
676723772816
181231280
324373425
501567657
731809886945
VOLTAGE DROP FOR SINGLE-CORE ARMOURED TO BS 6346
Conductorcross sectional
area
2 cablesd.c.
2 cables, single-phase a.c. 3 or 4 cables, three-phase a.c.
Clipped direct or on trays(touching)
In free air(spaced*)
Clipped direct, ontrays or in free air
(in trefoil touching)
Clipped director on trays(flat and touching)
In free air(flat spaced*)
mm2 mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m507095
120150185
240300400
5006308001000
0.930.630.46
0.360.290.23
0.1800.1450.105
0.0860.0680.0530.042
0.950.680.52
0.430.370.32
0.270.240.22
0.210.1950.1850.180
0.970.720.58
0.500.440.39
0.350.320.30
0.290.270.250.24
0.820.580.45
0.370.320.27
0.230.21
0.195
0.1800.1700.1600.155
0.840.620.50
0.430.380.34
0.300.280.26
0.250.230.220.21
0.860.680.57
0.500.450.41
0.370.340.32
0.300.280.260.24
NOTE : * Spacings larger than those specified in free air will result in larger voltage drop.
20
CURRENT-CARRYING CAPACITY FOR MULTICORE, ARMOURED TO BS 6346
Conductorcross
sectionalarea
Current-carrying capacityMethod of installation
Clipped direct On a perforated cable tray horizontal or verticalOr in free air
1 two-core cable,single-phasea.c. or d.c.
1 three- or four-corecable,
three-phase a.c.
1 two-core cable,single-phasea.c. or d.c.
1 three- or four-corecable,
three-phase a.c.mm2 A A A A1.52.54
61016
253550
7095120
150185240
300400
212838
496789
118145175
222269310
356405476
547621
182533
425877
102125151
192231267
306348409
469540
223141
537297
128157190
241291336
386439516
592683
192635
456283
110135163
207251290
332378445
410590
VOLTAGE DROP FOR MULTICORE, ARMOURED TO BS 6346
Conductor cross-sectional area Two-core cable,d.c. Two-core cable, single-phase a.c.
Three-or four-core cablethree-phase a.c.
(mm2) (mV / A/m) (mV / A/m) (mV / A/m)1.52.54
61016
253550
7095120
150185240
300400
291811
7.34.42.8
1.751.250.93
0.630.460.36
0.290.23
0.180
0.1450.105
291811
7.34.42.8
1.751.250.94
0.650.500.41
0.340.290.24
0.210.185
25159.5
6.43.82.4
1.501.100.81
0.570.430.35
0.290.250.21
0.1850.160
21
APPENDIX - TECHNICAL DATA STRANDED ANNEALED COPPER AND ALUMINIUM CONDUCTORS
Nominal cross
sectional area
Minimum number of wired in the conductor Maximum resistance of conductor at 20°C
Circular conductor Circular compacted conductor Shaped conductor Annealed copper
conductor Plain aluminium conductorCu Al Cu Al Cu Al Plain Wires
Metal-coated wires
mm² ohm/ km ohm/ km ohm/ km
1.52.54610162535507095
1201501852403004005006308001000
77777777191919
37373761616161616161
--777777
191919
37373761616161616161
666666666
1215
18183034345353535353
-----6666
1215
15153030305353535353
------666
1215
1818303434535353--
------666
1215
1515303030535353--
12.17.414.613.081.831.15
0.7270.5240.3870.2680.193
0.1530.124
0.09910.07540.06010.04700.03660.02830.02210.0176
12.27.564.703.111.841.16
0.7340.5290.3910.2700.195
0.1540.1260.100
0.07620.06070.04750.03690.02860.02240.0177
--
7.414.613.081.911.200.8680.6410.4430.320
0.2530.2060.1640.1250.1000.07780.06050.04690.03670.0291
FORMULA FOR ELECTRIC CALCULATION
To calculate Given D.C. A.C. Single Phase A.C. 3 phase
Current (A) kW A = 1000 x kWV A = 1000 x kW
V x pf A = 1000 x kW1.73 x V x pf
Current (A) kVA - A = 1000 x kVAV A = 1000 x kVA
1.73 x V
Current (A) hp A = 746 x hpV x eff A = 746 x hp
V x eff x pf A = 1000 x kW1.73 x V x eff x pf
Power (kW) VA kW = A x V1000 kW = A x V x pf
1000 kW = 1.73 x A x V x pf1000
Apparent Power (kVA) VA - kVA = A x V1000 kW = 1.73 x A x V
1000
pf - Power factor of equipment or system under considerationeff - Efficiency of motor of machineryV - Line voltage
22
APPENDIX - TECHNICAL DATA WIRE GAUGES
Gauge system Diameter Cross sectional area Weight of copper
Weight of Aluminium
A.W.G. S.W.G. mm mil mm² sq. mil CM kg/ km kg/ km
6/05/0--
4/0
-3/0--
2/0
-0--1
-2--3
-4-5-
6-7-8
--9-
10
-1112--
-1314-
15
16-
1718 -
-19-
2021
--
7/06/0-
5/0-
4/03/0-
2/0-01-
2-34-
5-6-7
-8-9-
1011-
12-
13--
1415
--
16-
17
-18--
19
20-
21--
14.73213.11912.70011.78611.684
10.97310.40410.1609.4499.266
8.8398.2528.2307.6207.348
7.0116.5446.4015.8935.827
5.3855.1894.8774.6214.470
4.1154.0643.6653.6583.264
3.2512.9462.9062.6422.588
2.3372.3052.0532.0321.829
1.8281.6281.6261.4501.422
1.2911.2191.1501.0241.016
0.91440.91170.81280.81160.7230
580516.5500464460
432409.6400372
364.8
348324.9324300
289.3
276257.6252232
229.4
212204.3192
181.9176
162160
144.3144
128.5
128116
114.4104
101.9
9290.7480.81
8072
71.9664.08
6457.07
56
50.8248
45.2640.340
3635.89
3231.9528.46
170.5135.2126.7109.1107.2
94.5685.0181.0770.1267.43
61.3653.4953.1945.6042.41
38.6033.6332.1827.2726.66
22.7721.1518.6816.7715.69
13.3012.9710.5510.518.367
8.3026.8186.6335.4815.261
4.2894.1723.3093.2432.627
2.6242.0812.0751.6501.589
1.3091.167
1.03800.82270.8107
0.65670.65290.51890.51740.4105
264,200209,500196,400169,100166,200
146,600131,800125,700108,700104,500
95,10082,91082,45070,69065,730
59,83052,12049,88042,27041,330
35,30032,78028,95026,00024,320
20,62020,11016,35016,29012,970
12,87010,57010,2808,4958,155
6,6486,4675,1295,0274,072
4,0673,2253,2172,5582,463
2,0291,8101,6091,2751,257
1,0181,012804.2802.9636.3
336,400266,800250,000215,300211,600
186,600167,800160,000138,400133,100
121,100105,600105,00090,00083,690
76,18066,37063,50053,82052,620
44,94041,73036,86033,10030,970
26,25025,60020,82020,74016,510
16,38013,46013,09010,82010,380
8,4658,2346,5316,4005,185
5,1784,1074,0963,2573,136
2,5832,3042,0481,6241,600
1,2961,2881,0241,021810.1
151512021126969.9953.2
840.6755.8720.7623.4599.5
545.5475.5472.9405.4377.0
343.2299.0286.1242.4237.0
202.4188.0166.1149.1139.5
118.3115.393.7893.4174.39
73.8060.6158.9648.7246.77
38.1337.0929.4228.8323.35
23.3318.5018.4514.6714.13
11.6310.389.2267.3147.207
5.8385.8044.6134.6003.649
460.2365.0342.0294.6289.5
255.3229.5218.9189.3182.1
165.7144.4143.6123.1114.5
104.290.8086.8873.6371.99
61.4957.1050.4345.2842.37
35.9235.0228.4828.3722.59
22.4218.4117.9114.8014.21
11.5811.268.9358.7567.093
7.0855.6185.6044.4564.290
3.5343.5122.8022.2212.189
1.7731.7631.4011.3971.108
23
APPENDIX - TECHNICAL DATA WIRE GAUGES - continued
Gauge system Diameter Cross sectional area Weight of copper
Weight of Aluminium
A.W.G. S.W.G. mm mil mm² sq. mil CM kg/ km kg/ km
-22-
23-
24--
25-
26-
27-
28
--
29-
30
--
31-
32
-33-
34-
35-
36-
37
--
38-
39
-404142-
43-
4445-
464748-
49
-50
22-
23-
24
-2526-
27
-28-
29-
3031-
32-
3334-
35-
36-
37-
38
-39-
40-
4142-
43-
44-
45-
46
-47--
48
---
49-
50-
0.71120.64390.60960.57330.5588
0.51060.50800.45720.45460.4166
0.40490.37590.36060.34540.3211
0.31500.29470.28600.27430.2548
0.25400.23370.22680.21340.2019
0.19300.17980.17270.16020.1524
0.14260.13210.12700.12190.1131
0.11180.10160.10070.09140.0897
0.081280.079880.071130.063340.06096
0.056410.050800.050230.044740.04064
0.039840.035480.031590.030480.02813
0.025400.02505
2825.35
2422.57
22
20.12018
17.916.4
15.9414.814.213.6
12.64
12.411.6
11.2610.8
10.03
109.2
8.9288.4
7.95
7.67.086.8
6.3056
5.6155.25
4.84.453
4.44
3.9653.6
3.531
3.23.1452.8
2.4942.4
2.2212
1.9781.7611.6
1.5681.3971.2441.2
1.108
10.9863
0.39730.32560.29190.25810.2452
0.20470.20270.16420.16230.1363
0.12880.11100.1021
0.093720.08097
0.077910.068190.064220.059080.05097
0.050670.042890.040390.035750.03203
0.029270.025400.023430.020140.01824
0.015970.013700.012670.011670.01005
0.009810.0081070.0079680.0065670.006319
0.0051890.0050120.0039730.0031510.002919
0.0024990.0020270.0019820.0015720.001297
0.0012460.00098840.00078380.00072970.0006216
0.00050670.0004929
615.8504.7452.4400.1380.1
317.3314.2254.5251.6211.3
199.6172.0158.3145.3125.5
120.8105.799.5491.5879.01
78.5466.4862.6055.4249.64
45.3639.3736.3231.2228.27
24.7621.2419.6318.1015.57
15.2112.5712.3510.189.794
8.0427.7686.1594.8844.524
3.8733.1423.0722.4362.011
1.9321.5321.2151.131
0.9635
0.78540.7641
784.0642.6576.0509.4484.0
404.0400.0324.0320.4269.0
254.1219.0201.5185.0159.8
153.8134.6126.7116.6100.6
100.084.6479.7170.5663.20
57.7650.1346.2439.7536.00
31.5327.0125.0023.0419.83
19.3616.0015.7212.9612.47
10.249.8917.8426.2195.760
4.9324.0003.9113.1022.560
2.4601.9511.5471.4401.227
1.0000.9728
3.5322.8952.5952.2952.180
1.8201.8021.4601.4431.212
1.1450.98670.90770.83320.7198
0.69260.60620.57090.52520.4531
0.45050.38130.359
0.31780.2847
0.26020.22580.20830.17910.1622
0.1420.12180.11260.1038
0.08931
0.087210.072070.070840.058380.05616
0.046130.044560.035320.028010.02595
0.022220.018020.017620.013970.01153
0.011080.0087870.0069680.0064870.005526
0.0045050.004382
1.0730.87920.78800.69700.6622
0.55280.54720.44330.43830.368
0.34770.29970.27570.25300.2186
0.21040.18410.17340.15950.1376
0.13680.11580.1090
0.096530.08647
0.079020.068580.063260.054390.04925
0.043130.037000.034200.031520.02173
0.026490.021890.021510.017730.01706
0.014010.013530.01073
0.0085080.007880
0.0067470.0054720.0053510.0042440.003502
0.0033650.0026690.0021160.0019700.001678
0.0013680.001331
24
APPENDIX - TECHNICAL DATA COMMON CONVERSION FACTOR
Equivalent ReciprocalMass
1 cwt 1 oz 1 lb1 lb
1 ton (long)
=====
50.80228.3494536
0.004541.016
kggmkg
tonne ( metric)tonne ( metric)
0.01970.03522.2046220.26
0.09842Length
1 in1 ft1 yd
1 mile
====
25.40.30480.91441.6093
mmmmkm
0.039373.28081.09360.6214
Area1 in²1 ft²1 yd²
===
645.160.09290.8361
mm²m²m²
0.0015510.7642
1.196Volume
1 in³1 ft³1 ft³1 ft³1 yd³
1 fal (USA)
======
16.3870.02836.229
28.3280.76450.8327
cm3 (ml or cc)m3
gal (lmp)l
m3
gal (lmp)
0.06135.33350.16050.03531.30791.2009
Force1 lbf1 kgf
1 ton (long) f
===
0.45359.80659.964
kgfNkN
2.20460.1019
0.10036Pressure and Stress
1 atm1 atm
1 lbf/in² (psi)1 bar
====
0.10131.01336.894
1.0197
Mpabar
kN/mm2 (kPa)kgf/ cm2
9.8690.98690.145
0.09806Energy (Work and Heal)
1 HP.h1 Btu1 Btu1 Btu1 cal
=====
2544.50.000293
1.0551107.594.187
BtukW.h
kJkgf.m
J
0.003933413
0.94780.00929
0.239
1 mil = 0.001 in = 0.0254 mm
1 CM (circular mil) = 0.7854 x 10-6 in² = 0.5067 x 10-3 mm2
BS 6004 PVC - Insulated Cables (Non-Armoured) for Electrical Power and Lighting
BS 6346 PVC - Insulated Cables for Electric Supply
BS 6360 Conductors in Insulated Cables and Cords
BS 7671 Requirements for Electrical Installations
IEE Wiring Regulations, Sixteenth Edition
MS 136 PVC - Insulated Cables (Non-Armoured) for Electrical Power and Lighting
MS 274 PVC - Insulated Cables for Electric Supply
PUBLICATIONS REFERRED TO
Leader Cable Industry Berhad (26936-P)
Lot 1385, Tikam Batu Industrial Estate 08600 Sungai Petani, Kedah, MalaysiaTel: 604-438 9988 Fax: 604-438 8497 www.leadercable.com.my
Selangor Sales OfficeUnit 8.2, Level 8, Building A, Peremba Square Saujana Resort, Seksyen U2 40150 Shah Alam, Selangor, Malaysia.Tel: 603-7845 7788/6699 Fax: 603-7845 2258/8323