Hospital!ExpansionandMechanical!Upgrades!! Deliver$500...

8
Hospital Expansion and Mechanical Upgrades Deliver $500,000 in Energy Savings 150,000 SQ.FT.BLODGETT HOSPITAL CAMPUS EXPANSION CAMPUS BOILER AND CHILLED WATER PLANT UPGRADES NET DECREASE ION ENERGY CONSUMPTION www.synergyengineers.com 150,000 Sq. Ft. Inpatient Addition

Transcript of Hospital!ExpansionandMechanical!Upgrades!! Deliver$500...

Page 1: Hospital!ExpansionandMechanical!Upgrades!! Deliver$500 ...synergy-engineers.com/wp-content/uploads/2016/03/Blodgett_Healthcare... · Synergy Maximizes Building Performance from Start

   

   

 

 Hospital  Expansion  and  Mechanical  Upgrades    

Deliver  $500,000  in  Energy  Savings    

150,000  SQ.  FT.  BLODGETT  HOSPITAL  CAMPUS  EXPANSION    

CAMPUS  BOILER  AND  CHILLED  WATER  PLANT  UPGRADES  

NET  DECREASE  ION  ENERGY  CONSUMPTION    

       

                             

                                                                                                                                     

www.synergy-­‐engineers.com  

150,000  Sq.  Ft.  Inpatient  Addition  

Page 2: Hospital!ExpansionandMechanical!Upgrades!! Deliver$500 ...synergy-engineers.com/wp-content/uploads/2016/03/Blodgett_Healthcare... · Synergy Maximizes Building Performance from Start

Synergy Maximizes Building Performance from Start to Finish.

LEARN  HOW  WE  CAN  HELP  YOU      [email protected]    

Summary

Spectrum  Health  Blodgett  Hospital,  East  Grand  Rapids,  Michigan  $98  Million  Renovation  and  Expansion  Project             LEED  Silver  Chiller  and  Boiler  Plant  Upgrades  

Project  Background  Spectrum  Health  is  one  of  the  largest  providers  of  health  care  services  in  Michigan,  offering  a  continuum  of  healthcare  services  across  multiple  campuses  throughout  West  Michigan.  Synergy  Consulting  Engineers  was  selected  to  provide  systems  analysis  and  design  of  approved  recommendations  of  the  Spectrum  Health  Blodgett  Hospital’s  Boiler  Plant  and  Chilled  Water  Plant  that  service  the  800,000  Sq.  Ft.  campus.  Synergy  also  provided  commissioning  services  for  the  new  150,000  Sq.  Ft.  five-­‐story  inpatient  addition  with  120  patient  rooms  and  support  spaces,  and  main  campus  renovations  including  new  state-­‐of-­‐the-­‐art  operating  rooms,  164  private  rooms,  and  a  36-­‐bed  post-­‐anesthesia  care  unit,  or  PACU  –  one  of  the  largest  in  the  country.      

ImpactSynergy  delivers  performance-­‐based  engineering  solutions  for  Healthcare  owners  and  operators  interested  in  pursuing  energy  efficiency,  energy  management  and  planned  initiatives  for  capital  improvements.  For  Spectrum  Health,  the  performance  and  efficiency  of  upgrades  made  to  the  Boiler  and  Chilled  Water  Plants  at  Blodgett  Hospital  made  it  possible  to  improve  services  for  the  main  campus  and  the  new  150,000  Sq.  Ft.  inpatient  addition,  with  an  actual  Net  Decrease  in  Energy  Consumption  and  an  Annual  Savings  of  nearly  $500,000.    

Initial  Evaluation/Study  The  purpose  of  the  initial  study  was  to  present  an  evaluation  of  the  existing  plants  and  to  determine  if  each  would  meet  the  immediate  and  future  demands  of  the  hospital.    This  report  also  included  an  energy  analysis  that  compared  the  efficiency,  operating  costs,  and  useful  life  of  the  existing  chillers  and  boilers  with  new  high  performance/efficient  systems  and  design  strategies.  

The  content  of  this  study  is  based  on:  1. Field  observations2. Archive  /  Design  drawings3. Interviews  with  maintenance  personnel  to  ascertain  operational  concerns  and  deficiencies

with  the  existing  chiller  plant4. Test  &  Balance  reports5. Current  utility  rates6. Accepted  Engineering  practice

Scope  of  Study  • The  study  estimated  the  existing  demand  of  the  hospital  by  calculating  the  actual  load.• The  new  addition  estimated  load  is  added  to  the  total  existing  load  to  determine  if  the  existing  plants

have  sufficient  capacity.• The  condition  of  the  equipment  in  each  plant  was  evaluated  to  determine  the  viability  of  continued  use

and  required  improvements.• Multiple  options  were  then  evaluated  on  a  life  cycle  basis  to  determine  the  best  option  for  improvements

that  met  the  needs  of  the  facility  including  the  new  addition  and  maximize  energy  efficiency.

Page 3: Hospital!ExpansionandMechanical!Upgrades!! Deliver$500 ...synergy-engineers.com/wp-content/uploads/2016/03/Blodgett_Healthcare... · Synergy Maximizes Building Performance from Start

As  part  of  the  Energy  Center  renovations,  the  chiller  renovations  involved  removal  and  replacement  of  two  of  the  four  existing  chillers.  Using  the  most  recent  air  and  hydronic  balance  reports,  design  data,  and  by  interviewing  energy  plant  personnel,  the  cooling  load  of  the  hospital  was  determined.    The  results  show  that  in  order  to  meet  this  cooling  demand  on  design  cooling  days,  there  would  need  to  be  2,700  tons  of  nominal  chiller  capacity  in  use.  

E         Existing  Equipment  Data  

CH-­‐1  Absorption  Chiller   Carrier   1,000  tons  

CH-­‐2  Centrifugal  Chiller   Trane   460/3   1,200  tons  

CH-­‐3  Absorption  Chiller   Trane   1,000  tons  

CH-­‐4  Screw  Chiller   Trane   460/3   300  tons  

Winter  Cooler  Heat  Exchanger   Alfa  Laval   -­‐   400  tons  

CT-­‐1  Cooling  Tower   Marley   460/3/74   1,650  gpm  

CT-­‐2  Cooling  Tower   Marley   460/3/50   1,680  gpm  

CT-­‐3  Cooling  Tower   Marley   460/3/50   1,680  gpm  

CT-­‐4  Cooling  Tower   Marley   460/3/50   1,680  gpm  

CT-­‐5  Cooling  Tower   Marley   460/3/50   1,680  gpm  

Condensing  Water  Pump  P-­‐1   Bell  &  Gossett   460/3/104   3,360  gpm  @  80’  hd  

Condensing  Water  Pump  P-­‐2   Bell  &  Gossett   460/3/104   3,360  gpm  @  80’  hd  

Condensing  Water  Pump  P-­‐3   Bell  &  Gossett   460/3/104   3,360  gpm  @  80’  hd  

Chilled  Water  Pump  P-­‐1   Bell  &  Gossett   460/3/74   2,680  gpm  @  70’  hd  

Chilled  Water  Pump  P-­‐2   Bell  &  Gossett   460/3/74   2,680  gpm  @  70’  hd  

Chilled  Water  Pump  P-­‐3   Bell  &  Gossett   460/3/74   2,680  gpm  @  70’  hd  

Any  changes  to  the  chilled  water  plant  had  to  produce  a  minimum  of  2,700  to  2,900  tons  of  cooling.    The  2,700  to  2,900  tons  of  required  capacity  is  based  on  2,000  to  2,250  tons  of  current  load  and  650  tons  of  future  required  load.    With  this  chiller  capacity,  the  existing  facility  load  and  the  new  addition  load  is  sustainable.      

Multiple  options  were  evaluated  to  meet  these  demands  (see  chart  below)  

Summary of Recommended Options Chiller   Option  A   Option  B   Option  C   Option  D  X-­‐CH-­‐1  (Carrier  Absorber)   D   D   D   D  X-­‐CH-­‐2  (Trane  Centrifugal)   B   B   P   B  X-­‐CH-­‐3  (Trane  Absorber)   D   D   B   D  X-­‐CH-­‐4  (Trane  Screw)     P   P   P   P  New  1,200  ton     P   P   NR   NR  New  1,200  ton   P   NR   NR   NR  New  1,500  ton   NR   P   P   P  New  1,500  ton   NR   NR   NR   P  Primary  Tonnage   2,700  tons   3,000  tons   3,000  tons   3,300  tons  Total  Tonnage  w/Backup   3,900  tons   4,200  tons   4,000  tons   4,500  tons  Estimated  Costs     $1,255,000   $1,533,000   $1,163,000   $1,810,000  

P  =  Primary  Chiller        B  =  Backup  Chiller        D  =  Demolition        NR  =  Not  Required  

Synergy Maximizes Building Performance from Start to Finish.

LEARN  HOW  WE  CAN  HELP  YOU      [email protected]    

Page 4: Hospital!ExpansionandMechanical!Upgrades!! Deliver$500 ...synergy-engineers.com/wp-content/uploads/2016/03/Blodgett_Healthcare... · Synergy Maximizes Building Performance from Start

One  1200  ton  and  one  1500  ton  centrifugal  chiller  was  installed.  The  new  chillers  were  needed,  in  part,  for  the  added  capacity  of  the  new  150,000  square  foot  addition  to  Blodgett  hospital  and  were  sized  to  allow  for  addition  capacity  and  redundancies.  

The  following  items  are  additional  improvements  that  further  increased  efficiency  of  the  chilled  water  plant:  

• Increase  Capacity  of  Winter  Cooler• Control  Valve  on  Steam  Lines  for  Cooling  Towers

Basin  Heating• Variable  Primary  Pumping• Variable  Secondary  Pumping• Variable  Primary  Only  Pumping• Temperature  Control  System• Thermal  Storage

• Series  Chillers• Condenser  Heat

Recovery• Decrease  Steam

Boiler  Plant  Capacity• Remote  Condenser

Water  Basin  /  DrainBack  Tank

The  energy  economics  were  simulated  using  the  Trane  Trace  700  simulation  program.  All  costs  were  calculated  over  a  study  life  of  40  years.  Estimate  for  equipment  installation  cost  was  based  on:    Install  cost  ($)=  equipment  cost  ($)*  1.5  

Basis  of  Calculations  Utility  Rates  Electricity   $0.0650/KWH  Gas   $0.975/Therm  

Based  on  the  results  from  the  economic  analysis  (first  cost  ranking  and  economic  ranking),  option  A  actually  ranked  higher  than  option  B.    However,  option  B  was  determined  to  be  the  best  option.    Although  utility  costs  and  life  cycle  costs  are  lower  with  option  A,  when  the  load  exceeds  2,700  tons  the  backup  centrifugal  chiller  will  be  required  to  operate  to  meet  the  demand.    Therefore  if  a  chiller  were  to  fail  under  these  conditions  the  chilled  water  plant  would  be  unable  to  adequately  maintain  the  chilled  water  setpoint.    With  option  B  there  is  an  additional  300  tons  of  capacity  at  relatively  the  same  utility  cost.    The  utility  costs  are  relatively  the  same  because  there  are  more  operating  hours  on  the  more  efficient  centrifugal  chillers.  

Pump  Replacement  Included  as  part  of  the  Energy  Center  Renovations,  the  entire  chilled  water  and  condensing  water  pump  packages  have  been  updated  and  replaced.  These  pumps  are  used  to  supply  the  entire  buildings  cooling  demand  to  the  various  air  handler  units  throughout  the  hospital.  The  pumping  system  change  required  the  hospital  to  change  from  a  primary/secondary  system  with  several  booster  pumps  located  throughout  the  hospital  to  a  primary  pumping  system  utilizing  3  larger  pumps.  The  pumps  were  connected  to  Variable  Frequency  Drives  (VFD's)  which  control  the  speed  of  the  pumps,  allowing  the  flow  of  water  to  match  the  exact  load  that  is  needed.  In  turn,  this  has  reduced  the  over-­‐all  electrical  demand  to  power  the  pumps.  

Synergy Maximizes Building Performance from Start to Finish.

LEARN  HOW  WE  CAN  HELP  YOU      [email protected]    

Page 5: Hospital!ExpansionandMechanical!Upgrades!! Deliver$500 ...synergy-engineers.com/wp-content/uploads/2016/03/Blodgett_Healthcare... · Synergy Maximizes Building Performance from Start

Ice  Storage  Ice  storage,  or  thermal  storage,  is  a  fairly  old  concept  that  involves  the  shifting  of  electrical  loads  from  more  expensive  peak  demand  hours  to  less  expensive  non-­‐peak  demand  hours  through  the  nighttime  production  of  ice.  The  ice  is  then  stored  throughout  the  day  and  used  to  cool  the  buildings  chilled  water  supply,  reducing  the  demand  on  the  chillers  when  cooling  loads  are  at  their  highest.  While  a  direct  energy  efficiency  gain  is  not  realized  from  the  production  of  ice,  the  decreased  demand  on  the  chillers,  which  are  the  number  one  consumer  of  electricity  in  any  major  facility,  is  reduced.  In  less  than  a  year  and  a  half,  the  savings  from  the  ice  storage  system  has  more  than  offset  the  cost  associated  with  the  ice  storage  installation.  The  use  of  ice  storage  can  produce  1944  ton  hours  of  cooling  for  the  facility.    

Plate  Heat  Exchanger  In  conjunction  with  the  chiller  and  cooling  tower  replacement,  the  Energy  Center  plate  heat  exchanger  has  also  been  replaced.  Because  a  building  always  has  a  latent  heat  load  regardless  of  the  time  of  year,  a  heat  exchanger  is  used  as  a  means  of  "free  cooling"  in  the  colder  months  on  internal  heating  loads  from  MRI  units,  data  rooms,  and  machine  rooms.  When  temperatures  are  48  degrees  or  less  outside  we  are  able  to  divert  the  flow  of  water  through  the  plate  heat  exchanger,  reducing  the  over-­‐all  demand  on  the  chillers.  Since  the  Plate  Heat  Exchanger  has  been  operational,  an  additional  300  tons  of  cooling  can  be  diverted,  allowing  the  chillers  to  remain  idle  during  this  time.  

Cooling  Tower  Replacement  Of  the  existing  five  Marley  cooling  towers,  four  were  completely  removed.  Two  new  CCS  cooling  towers  now  perform  the  job  of  the  previous  four.  The  cooling  towers  work  through  evaporative  cooling,  using  the  colder  outside  air  temperatures  to  cool  the  water  flowing  through  the  towers.  The  towers  are  an  updraft  or  counterflow  high  efficiency  style  of  cooling  tower,  that  will  increase  heat  rejection  capacity,  and  also  reduce  the  chemical  and  maintenance  costs  associated  with  cooling  towers.  In  a  year-­‐to-­‐year  comparison,  an  estimated  6.83  million  gallons  of  water  consumption  has  been  reduced  and  we  have  seen  a  3.2  million  gallon  savings  from  blow  down  in  the  towers.  Along  with  water  savings,  82  gallons  of  cooling  water  treatment  was  eliminated,  saving  $2,288  that  year.  

Air  Handler  Replacement  Since  2008,  twelve  of  the  hospitals  existing  air-­‐handling  units  have  been  completely  replaced.  The  new  custom-­‐designed  units  were  brought  into  the  building  in  multiple  sections  or  assembled  completely  on  site.  The  fans  in  each  unit  are  equipped  with  a  VFD  control  module  that  allows  the  fan  to  operate  at  the  exact  air  volume  needed.  Along  with  the  VFD's,  all  AHUs  are  tied  into  our  Building  Automation  System,  or  BAS  for  short  (see  below  for  a  more  detailed  description  of  this  system).  With  all  of  the  new  technology  that  was  put  into  these  units,  our  Facilities  Team  was  able  to  have  a  better  understanding  of  the  buildings’  heating  and  cooling  needs  and  can  respond  to  issues  at  the  click  of  a  button.

Building  Automation  System  (BAS)  In  conjunction  with  the  AHU  replacements,  controls  for  the  units  were  also  updated.  Through  the  use  of  a  Trane  Building  Automation  System,  Spectrum  Health  Facilities  team  members  are  able  to  monitor  the  running  conditions  of  all  AHU's  throughout  the  facility  from  a  centrally  located  

computer.  This  ensures  that  all  of  the  units  are  functioning  to  their  designed  specifications,  in  turn,  increasing  the  over-­‐all  efficiency  and  energy  savings  of  the  unit.  

Synergy Maximizes Building Performance from Start to Finish.

LEARN  HOW  WE  CAN  HELP  YOU      [email protected]    

Page 6: Hospital!ExpansionandMechanical!Upgrades!! Deliver$500 ...synergy-engineers.com/wp-content/uploads/2016/03/Blodgett_Healthcare... · Synergy Maximizes Building Performance from Start

The  Boiler  Plant  The  existing  boiler  plant  consists  of  (5)  existing  water  tube  steam  boilers  (300  HP|16,000  #/hr  each  –  80,000  #/hr  combined)  that  provide  the  steam  to  the  existing  absorption  chillers,  steam  heating  coils,  steam  radiators,  heating  water  heat  exchangers,  humidifiers,  and  domestic  water  heat  exchangers.    The  two  newest  boilers  are  1974  vintage.    The  three  older  boilers  are  1965  vintage.    Based  upon  the  steam  produced  (measured  by  steam  meter)  and  associated  firing  rates  the  efficiency  of  each  boiler  is  approximately  50-­‐60%.  

When  considering  the  existing  steam  demand  (without  the  absorption  chillers)  and  the  future  demand  of  the  addition,  it  is  our  recommendation  to  plan  to  replace  all  (5)  existing  boilers  with  (7)  new  Vertical  Tube,  Fulton,  150  HP,  Steam  Boilers.    The  Fulton  Boilers  are  85%  efficient,  high  performance  boilers  with  a  total  connected  capacity  of  41,400  #/hr.  Due  to  the  lower  capacity  of  each  boiler,  the  steam  supply  will  be  matched  effectively  and  evenly  to  the  steam  demand.  

Table  1  –  Existing  Steam  Demand   Steam

( #/hr)

Heating Water (MBH)

Steam Heating (AHU Heating Coils & Steam Convectors)

Heating Hot Water (via Steam|Hot Water Heat Exchangers)

AHU Heating Coils & Reheat Coils, Radiant Heating

Domestic Hot Water (via Steam|Hot Water Heat Exchangers)

Humidification

Food Service

Sterilization

TOTAL 22,000 #/hr

Table  2  –  Future  Steam  Demand  ( Inc lud ing  New  Add i t ion )  

Steam

( #/hr)

Heating Water (MBH)

Steam Heating (AHU Heating Coils & Steam Convectors)

Heating Hot Water (via Steam|Hot Water Heat Exchangers)

AHU Heating Coils & Reheat Coils, Radiant Heating 8,311 MBH

Domestic Hot Water (via Steam|Hot Water Heat Exchangers) 2,900 #/hr

Humidification

Food Service

Sterilization

TOTAL 34,000 #/hr

Synergy Maximizes Building Performance from Start to Finish.

LEARN  HOW  WE  CAN  HELP  YOU      [email protected]    

Page 7: Hospital!ExpansionandMechanical!Upgrades!! Deliver$500 ...synergy-engineers.com/wp-content/uploads/2016/03/Blodgett_Healthcare... · Synergy Maximizes Building Performance from Start

Table  3  –  Existing  Boiler  Data  

Manufacturer | Model Install Date Capacity

B-1 Cleaver Brooks 1974 16,000 #/hr

B-2 Cleaver Brooks 1974 16,000 #/hr

B-3 Cleaver Brooks 1965 16,000 #/hr

B-4 Cleaver Brooks 1965 16,000 #/hr

B-5 Cleaver Brooks 1965 16,000 #/hr

Connected Capacity 80,000 #/hr

Table  4  –  New  Boi ler  Data  

Manufacturer | Model Capacity

B-1 ( Vertical Fire Tube ) Fulton | VPM 150 5,175 #/hr

B-2 ( Vertical Fire Tube ) Fulton | VPM 150 5,175 #/hr

B-3 ( Vertical Fire Tube ) Fulton | VPM 150 5,175 #/hr

B-4 ( Vertical Fire Tube ) Fulton | VPM 150 5,175 #/hr

B-5 ( Vertical Fire Tube ) Fulton | VPM 150 5,175 #/hr

B-6 ( Vertical Fire Tube ) Fulton | VPM 150 5,175 #/hr

B-7 ( Vertical Fire Tube ) Fulton | VPM 150 5,175 #/hr

B-8 ( Vertical Fire Tube ) Fulton | VPM 150 5,175 #/hr

Connected Capacity 41,400 #/hr

Beyond  the  boilers,  other  systems  included  in  the  study  include:  

• Boiler  Feed  Water  System• Boiler  Blow-­‐down  System• Ventilation|Combustion  Air• Facility  Energy  Management  Control  System• Steam,  Steam  Condensate,  and  Heating  Water  Piping• Steam  |  Hot  Water  Heat  Exchangers• Prioritized  Recommendations

Synergy Maximizes Building Performance from Start to Finish.

LEARN  HOW  WE  CAN  HELP  YOU      [email protected]    

Page 8: Hospital!ExpansionandMechanical!Upgrades!! Deliver$500 ...synergy-engineers.com/wp-content/uploads/2016/03/Blodgett_Healthcare... · Synergy Maximizes Building Performance from Start

Priority  Recommendation  1. Install  (3)  new  modular  steam  boilers  and  remove  B-­‐1,  B-­‐2,  &  B-­‐3.2. Install  new  boiler  feed  water  system.3. Install  (5)  additional  modular  steam  boilers  and  remove  B-­‐4  &  B-­‐5  (A  section  of  the  existing  roofwill  need  to  be  removed  if  this  is  not  complete  in  conjunction  with  the  chiller  plant  improvement).

4. Install  new  boiler  stack  economizer  in  new  boiler  breeching.    Abandon  the  existing  chimneys.5. Take  pipe  samples  of  the  heating  piping  to  assess  their  condition.    Focus  on  mains  and  fittings.6. Replace  existing  piping  as  required.7. Inspect  hot  water  tubing  in  existing  heat  exchangers  (check  tubing  thickness  and  tubing  corrosion)8. Replace  existing  heat  exchangers  as  required.9. Test  the  existing  exhaust  and  intake  airflows10. Add  steam  pressure  gauges  to  each  side  of  the  PRV’s.11. Tear  down  two  existing  Chimneys

Implementation  All  five  existing  Cleaver  Brooks  boilers  were  replaced  with  8  new  Vertical  Tube,  150  HP,  Fulton  steam  boilers.  The  new  Fulton  boilers  are  a  high  efficiency  boiler  with  a  smaller  nominal  capacity  than  the  existing,  allowing  the  steam  capacity  and  demand  to  be  matched  much  more  effectively.  The  Fulton  boilers  are  also  dual  fired  boilers,  allowing  for  operation  on  both  natural  gas  and  fuel  oil.  

LEED  This  project  was  commissioned  in  accordance  with  LEED  NC  v2.2  EA  Prerequisite  1  EA  Cr.  3"  Synergy  also  provided  commissioning  services  for  all  major  systems  in  the  facility.  Synergy  employs  one  of  the  most  comprehensive  Commissioning  process  available  to  ensure  that  the  systems  installed  perform  as  designed  and  met  the  owner’s  project  requirements.    

Looking  at  the  numbers:   Blodgett  2009/2010  Actual  

Blodgett  2009/2010  at  2010/11  Pricing  

Blodgett    2010/2011  Actual  

Square Footage 594,143 594,143 788,533

Cost / KWH $0.0776 $0.0869 $0.0869

Total KWH consumed 22,419,481 22,419,481 24,107,135 Total KWH cost / year $1,739,752 $1,948,253 $2,094,910

Cost / MCF $7.7737 $5.8928 $5.8928

Total MCF consumed 128,612 128,612 141,626 MCF transport cost $130,744 $130,744 $117,968

Total Gas Cost / year $1,130,535 $888,629 $952,542

Total Energy Cost $2,870,287 $2,836,882 $3,047,452

Total Cost per square foot $4.8310 $4.7747 $3.8647 Projected Energy costs before boiler and chiller renovations $2,836,882

Projected Energy costs minus the cost of the Blodgett expansion $2,296,191 Blodgett Renovation Energy Savings $540,691

SILVER

Synergy Maximizes Building Performance from Start to Finish.

LEARN  HOW  WE  CAN  HELP  YOU      [email protected]