Horizontal Distribution of Forces to Individual Shear Wallssite.iugaza.edu.ps › sshihada › files...

19
124 Horizontal Distribution of Forces to Individual Shear Walls Interaction of Shear Walls with Each Other In the shown figure the slabs act as horizontal diaphragms extending between cantilever walls and they are expected to ensure that the positions of the walls, relative to each other, don't change during lateral displacement of the floors. The flexural resistance of rectangular walls with respect to their weak axes may be neglected in lateral load analysis. The distribution of the total seismic load, x F or y F among all cantilever walls may be approximated by the following expressions. ix ix ix F F F iy iy iy F F F where: ix F = load induced in wall by inter-story translation only, in x-direction iy F = load induced in wall by inter-story translation only, in y-direction ix F " = load induced in wall by inter-story torsion only, in x-direction iy F " = load induced in wall by inter-story torsion only, in y-direction ix F = total external load to be resisted by a wall, in x-direction iy F = total external load to be resisted by a wall, in y-direction To obtain ix F and iy F ' , the forces x F and y F are distributed to the individual shear walls in proportion to their rigidities.

Transcript of Horizontal Distribution of Forces to Individual Shear Wallssite.iugaza.edu.ps › sshihada › files...

  • 124

    Horizontal Distribution of Forces to Individual Shear Walls

    Interaction of Shear Walls with Each Other

    In the shown figure the slabs act as horizontal diaphragms extending between

    cantilever walls and they are expected to ensure that the positions of the walls,

    relative to each other, don't change during lateral displacement of the floors.

    The flexural resistance of rectangular walls with respect to their weak axes

    may be neglected in lateral load analysis.

    The distribution of the total seismic load, xF or yF among all cantilever walls

    may be approximated by the following expressions.

    ixixix FFF

    iyiyiy FFF

    wwhheerree::

    ixF == load induced in wall by inter-story translation only, in x-direction

    iyF = load induced in wall by inter-story translation only, in y-direction

    ixF" = load induced in wall by inter-story torsion only, in x-direction

    iyF" = load induced in wall by inter-story torsion only, in y-direction

    ixF = total external load to be resisted by a wall, in x-direction

    iyF = total external load to be resisted by a wall, in y-direction

    To obtain ixF and iyF ' , the forces xF and yF are distributed to the individual

    shear walls in proportion to their rigidities.

  • 125

    The force resisted by wall i due to inter-story translation, in x-direction, is

    given by

    iy

    iyx

    ixI

    IFF

    The force resisted by wall i due to inter-story translation, in y-direction, is

    given by

    ix

    ixy

    iyI

    IFF

    where:

    xF = total external load to be resisted by all walls, in x-direction

    yF = total external load to be resisted by all walls, in y-direction

    ixI = second moment of area of a wall section about x axis

    iyI = second moment of areas of a wall section about y axis

    ixI = total second moment of areas of all walls in x-direction

    iyI = total second moment of area of all walls in y-direction

    The force resisted by wall i due to inter-story torsion, in x-direction, is given

    by

    iyiixi

    iyiyx

    ixIyIx

    IytorsionaccidentaleFF

    22

    The force resisted by wall i due to inter-story torsion, in y-direction, is given

    by

    iyiixi

    ixixy

    iyIyIx

    IxtorsionaccidentaleFF

    22

    where:

    ix = x-coordinate of a wall with respect to the center of rigidity C.R of the

    lateral load resisting system

    iy = y-coordinate of a wall with respect to the center of rigidity C.R of the

    lateral load resisting system

    xe = eccentricity resulting from non-coincidence of center of gravity C.G and

    center of rigidity C.R, in x-direction

    ye = eccentricity resulting from non-coincidence of center of gravity C.G and

    center of rigidity C.R, in y-direction

  • 126

    7x

    3 =

    21

    m

    Example (4):

    A seven-story building frame system with shear walls has the dimensions

    shown in the Figure. Eight shear walls, each 3 m long and 0.2 m thick, are

    used as a lateral force resisting system. Determine the forces acting on shear

    wall G.

    Building layout

    Solution:

    Neglecting moments of inertia about weak axes, second moments of area of

    each of the shear walls about y-axis are given by

    43

    45.012

    32.0mIIII HyGyByAy

    A B

    D

    F

    H G

    E

    C

    6m

    6m

    6m

    4.5

    m

    4.5

    m

    4.5

    m

    4.5

    m

  • 127

    Total second moments of area about y-axis are given by

    44

    1

    8.1445.0 mIi

    iy

    Second moments of area of each of the shear walls about x-axis are given by

    43

    45.012

    32.0mIIII FxExDxCx

    Total second moments of area about x-axis are given by

    44

    1

    8.1445.0 mIi

    ix

    To locate the center of rigidity C.R, the distance from the origin to the C.R

    y in the y-direction is given by

    m

    I

    yI

    y

    i

    iy

    i

    iiy

    25.118.1

    5.445.0218245.04

    1

    4

    1

    The distance from the origin to the C.R in the x-direction x is given by

  • 128

    m

    I

    xI

    x

    i

    ix

    i

    iix

    0.98.1

    1845.024

    1

    4

    1

    Thus, the eccentricity in y-direction mey 25.20.925.11

    The eccentricity in x-direction mex 0.00.90.9

    Torsion caused by eccentricity ye , 1T xF25.2

    Torsion caused by accidental eccentricity , 2T xx FF 9.01805.0

    Total torsion, 21 TT xx FF 9.025.2

    iy

    iyx

    ixI

    IFF

    xx

    HxGxBxAx FF

    FFFF 25.08.1

    45.0

    iyiixi

    iyi

    ixIyIx

    IyTTF

    22

    21

    xx

    xxHxGxBxAx

    FF

    FFFFFF

    9.025.20133.0

    945.02945.0275.645.0275.645.02

    45.075.69.025.22222

    xF018.0 (For walls A and B as shown in the figure below)

    xF042.0 (For walls G and H as shown in the figure below)

    So, the forces acting on shear wall G are given by the following expression:

    x

    xx

    F

    FF

    292.0

    042.025.0

  • 129

    Example (5):

    For the building shown in Example (3), evaluate the seismic force acting on shear

    wall "A".

    Solution:

    43 45.012/32.0 mIDx

    43 067.112/42.0 mIEx

    m

    I

    xI

    x

    i

    ix

    i

    iix

    55.10067.145.0

    15067.102

    1

    2

    1

    mex 05.35.755.10

    43 45.012/32.0 mIII CyByAy

    m

    I

    yI

    y

    i

    iy

    i

    iiy

    33.845.03

    1545.01045.003

    1

    3

    1

    mey 83.05.733.8

  • 130

    Horizontal distribution of forces for wall A:

    AxAxAx FFF

    xxAx FFF 333.0)45.0(3

    45.0

    2222222 67.645.067.145.033.845.045.4067.155.1045.045.067.6

    T

    IyIx

    IyTF

    iyiixi

    Ayi

    Ax

    TFAx 02426.0

    Maximum eccentricity= 0.83 + 0.05 (15) = 1.58 m

    Minimum eccentricity= 0.83 - 0.05 (15) = 0.08 m xxAx FFF 00194.008.002426.0.min,

    xAx FF 00194.0333.0

    or,

    xAx FF 33.0

  • 131

    Classification of Structural Walls According To Seismic Risk

    According to Chapter 2 and of ACI 318-14, structural walls are defined as being

    walls proportioned to resist combinations of shears, moments, and axial forces in the

    plane of the wall; a shear wall is a structural wall.

    Reinforced concrete structural walls are categorized as follows:

    1- Ordinary reinforced concrete structural walls: They are walls complying with the requirements of Chapter 11.

    2- Special reinforced concrete structural walls: They are walls complying with the requirements of 18.2.3 through 18.2.8 and 18.10.

    Special Provisions for Earthquake Resistance

    Design requirements for earthquake-resistant structures in ACI 318 are determined by the SDC to which the structure is assigned.

    According to Clause 5.2.2 of ACI 318-14, Seismic Design Categories (SDCs) shall be in accordance with the general building code.

    Table R5.2.2 correlates SDC to seismic risk terminology used in ACI 318.

  • 132

    Design of Ordinary Shear Walls

    The shear wall is designed as a cantilever beam fixed at the base, to transfer load to

    the foundation. Shear forces, bending moments and axial loads are maximums at the

    base of the wall.

    Types of Reinforcement:

    To control cracking, shear reinforcement is required in the transverse and

    longitudinal directions, to resist in-plane shear forces.

    The vertical reinforcement in the wall serves as flexural reinforcement. If large

    moment capacity is required, additional reinforcement can be placed at the ends of

    the wall within the section itself, or within enlargements at the ends. The heavily

    reinforced or enlarged sections are called boundary elements.

    ACI Table R18.2 summarizes the applicability of provisions of chapter 18 in terms of

    various seismic design categories.

  • 133

    In-Plane Shear Strength:

    According to ACI 11.5.1.1, design of cross sections subjected to shear are based on

    un VV (1)

    where uV is the factored force at the section considered and nV is the nominal shear

    strength computed from ACI 11.5.4.4,or

    scn VVV (2)

    where cV is nominal shear strength provided by concrete and sV is nominal shear

    strength provided by shear reinforcement.

    Based on ACI 11.5.4.3, max,nV at any horizontal section for shear in plane of the wall

    is not to be taken greater than

  • 134

    dhfV cn 65.2max, (3)

    where h is thickness of wall, and d is the effective depth in the direction of

    bending, may be taken as wl8.0 , where wl is length of wall considered in direction of

    shear force, as stated in ACI 11.5.4.2. A larger value of d , equal to the distance from

    extreme compression fiber to center of force of all reinforcement in tension, be

    permitted if the center of tension is calculated by a strain compatibility analysis.

    Based on ACI 11.5.4.6, the shear strength provided by concrete cV is given by any of

    the following equations, as applicable.

    For axial compression, Eqn. (4) is applicable

    dhfV cc 53.0 (4)

    For axial tension, Eqn. (5) is applicable

    dhfA

    NV c

    g

    uc

    35153.0

    (5)

    where gA is the gross area of wall section and uN is the factored axial tension force

    in Eqn. (5).

    ACI 11.9.6 specifies that a more detailed analysis is permitted to evaluate cV as

    follows, where cV is the lesser of the two values shown in Eqns. (6) and (7).

    w

    ucc

    l

    dNdhfV

    4'88.0 (6)

    hdl

    V

    M

    hl

    Nfl

    fVw

    u

    u

    w

    ucw

    cc

    2

    2.0'33.0

    '16.0 (7)

    Where uN is positive for compression and negative for tension. If 2// wuu lVM is negative, Eqn. (7) is not applicable.

  • 135

    Shear Reinforcement:

    A- If in-plane shear force uV is less than 2/cV , minimum wall longitudinal and

    transverse shear reinforcement shall be in accordance with ACI Table 11.6.1.

    B- If in-plane shear force uV is more than or equal to 2/cV , minimum shear

    reinforcement in the longitudinal direction, l shall be provided, based on ACI

    11.6.2.

    0025.00025.05.250.00025.0

    t

    w

    wl

    l

    h (8)

    The above value need not exceed t given in Table 11.6.1.

    Minimum shear reinforcement in the transverse direction, t shall be at least 0.0025.

    C- According to ACI 11.5.4.8 when the factored shear force uV exceeds cV ,

    transverse shear reinforcement must be provided according to the following equation.

    S

    dfAV

    ytv

    s

    (9)

    Where v

    A is area of transverse shear reinforcement within a distance S . Longitudinal

    shear reinforcement, l is provided as in case (B), shown above.

    Spacing of Transverse Reinforcement:

    Based on ACI 11.7.3.1, spacing of transverse reinforcement is not to exceed the

    smallest of cmhlw 45,3,5/ .

  • 136

    Spacing of Longitudinal Reinforcement:

    Based on ACI 11.7.2.1, spacing of transverse reinforcement is not to exceed the

    smallest of cmhlw 45,3,3/ .

    Critical Section for Shear:

    The critical section for shear is taken at a distance equal to half the wall length 2/wl ,

    or half the wall height 2/wh , whichever is less. Sections between the base of the wall

    and the critical section are to be designed for the shear at the critical section, as

    specified in ACI 11.5.4.7.

    Shear wall Reinforcement

  • 137

    Design for Flexure:

    The wall must be designed to resist the bending moment at the base and the axial

    force produced by the wall weight or the vertical loads it carries. Thus, it is

    considered as a beam-column.

    For rectangular shear walls containing uniformly distributed vertical reinforcement

    and subjected to an axial load smaller than that producing balanced failure, the

    following equation, developed by Cardenas and Magura in ACI SP-36 in 1973, can

    be used to determine the approximate moment capacity of the wall.

    wys

    uwysu

    l

    C

    fA

    PlfAM 115.0

    Where:

    185.02

    wl

    C

    cw

    ys

    fhl

    fA

    and

    cw

    u

    fhl

    P

    C distance from the extreme compression fiber to the neutral axis

    sA = total area of vertical reinforcement

    wl = horizontal length of wall

    uP = factored axial compressive load

    yf = yield strength of reinforcement

    = strength reduction factor for bending

    Additional Reinforcement around Openings:

    In addition to the required transverse and longitudinal reinforcement explained

    earlier, ACI 11.7.5.1 states that not less than mm162 bars are provided around

    all window and door openings in both directions in walls having two layers of

    reinforcement. In walls having a single layer of reinforcement in both

    directions,

    mm161 is to be provided. Such bars are to be extended to develop

    yf in tension at the corners of the openings.

    Additional reinforcement around wall openings

  • 138

    Example (6):

    For shear wall 'A' in example (5), design the reinforcement required for shear and

    flexure using ACI 318-14 for reinforced concrete design (ordinary shear wall).

    Use 22 /4200 and /300 cmkgfcmkgf yc .

    Solution:

    From example 5, xAx FF 33.0

    Critical section for shear is located at a distance not more than the smaller

    of 2/

    2/

    w

    w

    h

    l, i.e., at 1.5 m from the base of the wall.

    1- Design for shear:

    Check for maximum nominal shear force

  • 139

    dh'f65.2V cmax,n

    tons32.2201000/3008.02030065.2 KOtonstonsVu .16.1524.16532.22075.0max,

    dh'f53.0V cc tons06.441000/3008.02030053.0Vc

    tons045.3306.4475.0Vc tons523.162/045.332/Vc

    In zones 1 through 8, 2/VV cu

    1-1 Transverse shear reinforcement:

    0020.0t

    ofsmaller the2 S

    cm

    cmh

    cmlw

    45

    603

    605/

    or cmS 45max,2

    cmcmS

    Ah

    S

    A tt /04.0 and 200020.00020.0 2

    22

    For two curtains of reinforcement and trying 10 mm bars

    max,22

    2

    25.39 , 04.0785.02

    ScmSS

    O.K

    Use 10 mm bars @ 30cm.

    1-2 Longitudinal shear reinforcement:

    0012.0l

    ofsmaller the1 S

    cm

    cmh

    cmlw

    45

    603

    1003/

    or cmS 45max,1

    For two curtains of reinforcement, and trying 10 mm bars

    11

    0.7852 200012.00012.0

    Sh

    S

    Al

    And max,11 42.65 ScmS

    Use 10mm bars @ 30cm.

    Note that flexural reinforcement is expected to control.

  • 140

    2- Design for flexure and axial loads:

    wys

    uwysu

    l

    c1

    fA

    P1lfA5.0M

    Where:

    1w 85.02l

    c

    ,

    'fhl

    fA

    cw

    ys and

    'fhl

    p

    cw

    u

    For the vertical shear reinforcement of 10 mm @ 30cm, 2s cm28.17A ,

    836.028030070

    05.085.0 ,

    04032.030020300

    420028.17

    'fhl

    fA

    cw

    ys

    , u

    u

    cw

    u P00055.030020300

    1000P

    'fhl

    P ,

    79124.0P00055.004032.0

    836.085.004032.02

    P00055.004032.0

    l

    c uu

    w

    For zone 1:

    Neglecting dead load supported by the shear wall and considering own weight of the

    wall only, the load combination to be considered is

    EDS QDS 2.09.0 , or

    Vertical load= (0.90 – (0.2)(0.107) ) D = 0.88 D

    tonsPu 68.315.22432.088.0

    072346.079124.0

    68.3100055.004032.0

    wl

    c

    mtmtMu .47.265.55.130 , i.e. boundary elements are required at wall ends

    mtM u .92.13455.13047.265'

    2, 99.14785.02

    26642009.0

    10000092.134cmA additionals

    Use 8 16 mm bars in each of the two boundary elements.

    For zone 2:

    tonsPu 72.275.22132.088.0

    069685.079124.0

    72.2700055.004032.0

    wl

    c

  • 141

    mtmtMu .99.219.96.125 , i.e. boundary elements are required at wall ends

    mtM u .03.9496.12599.219'

    2, 92.10785.02

    26642009.0

    10000003.94cmA additionals

    Use 8 14 mm bars in each of the two boundary elements.

    For zone 3: tonsPu 76.235.21832.088.0

    066933.0

    79124.0

    76.2300055.004032.0

    wl

    c

    mtmtMu .41.175.35.121 , i.e. boundary elements are required at wall ends

    mtM u .06.5435.12141.175'

    2, 95.6785.02

    26642009.0

    10000006.54cmA additionals

    Use 6 14 mm bars in each of the two boundary elements.

    For zone 4:

    tonsPu 80.195.21532.088.0

    064182.079124.0

    80.1900055.004032.0

    wl

    c

    mtmtMu .90.132.70.116 , i.e. boundary elements are required at wall ends

    mtM u .20.1670.1169.132'

    2, 18.3785.02

    26642009.0

    1000002.16cmA additionals

    Use 3 14 mm bars in each of the two boundary elements.

  • 142

    For Zone 5

    tonsPu 84.155.21232.088.0

    061431.079124.0

    84.1500055.004032.0

    wl

    c

    mtmtMu .78.93.03.112 , i.e. no boundary elements are required at wall ends

    For Zone 6 tonsPu 88.115.2932.088.0

    058679.0

    79124.0

    88.1100055.004032.0

    wl

    c

    mtmtMu .43.59.33.107 , i.e. no boundary elements are required at wall ends

    For Zone 7 tonsPu 92.75.2632.088.0

    055928.0

    79124.0

    92.700055.004032.0

    wl

    c

    mtmtMu .32.31.59.102 , i.e. no boundary elements are required at wall ends

    For Zone 8 tonsPu 96.35.2332.088.0

    053177.0

    79124.0

    96.300055.004032.0

    wl

    c

    mtmtMu .98.10.83.97 , i.e. no boundary elements are required at wall ends