Heating Technical Data ERLQ-CV3€¦ · • Heating • ERLQ-CV3 5 • Outdoor Unit • ERLQ-CV3 2...

113
Heating Technical Data ERLQ-CV3

Transcript of Heating Technical Data ERLQ-CV3€¦ · • Heating • ERLQ-CV3 5 • Outdoor Unit • ERLQ-CV3 2...

HeatingTechnical Data

ERLQ-CV3

• Heating • ERLQ-CV3 1

• Outdoor Unit • ERLQ-CV3

TABLE OF CONTENTSERLQ-CV3

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

Cooling Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

Heating Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

Certification Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

5 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

6 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

7 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

8 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

Wiring Diagrams - Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

Sound Power Spectrum Quiet Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

Sound Pressure Spectrum - Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

Sound Pressure Spectrum - Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107

Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107

11 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

• Outdoor Unit • ERLQ-CV3

1

2

1 Features

door Uni ting Q-CV3 kin Alth

Out Hea ERL Dai • Outdoor unit extracts heat from the outdoor air, even at -25°C • Inverter controlled swing compressor

Guaranteed operation down

to -25°C

Inverter

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

CONNECTABLE INDOOR UNITS

2-1 Capacity and Power inputEHBH04CB3V/ERLQ004CV3

EHBH08CB9W/ERLQ006CV3

EHBH08CB3V/ERLQ006CV3

EHBH08CB9W/ERLQ008CV3

EHBH08CB3V/ERLQ008CV3

EHBH11CB3V/ERLQ011CV3

Heating capacity Min. kW 1.80 (1) -

Nom. kW 4.40 (1) / 4.03 (2)

6.00 (1) / 5.67 (2) 7.40 (1) / 6.89 (2) 11.2 (1) / 11.0 (2)

Max. kW 5.12 (1) / 4.90 (2)

8.35 (1) / 7.95 (2) 10.0 (1) / 9.53 (2) 8.60 (3) / 8.60 (4)

Power input Heating Nom. kW 0.870 (1) / 1.13 (2)

1.27 (1) / 1.59 (2) 1.66 (1) / 2.01 (2) 2.43 (1) / 3.10 (2)

Max. kW - 3.13 (3) / 4.10 (4)

COP 5.04 (1) / 3.58 (2)

4.74 (1) / 3.56 (2) 4.45 (1) / 3.42 (2) 4.60 (1) / 2.75 (3) / 3.55 (2) /

2.10 (4)

Pump Nominal ESP unit Heating kPa 53.0 (5) / 56.0 (6)

45.0 (5) / 48.0 (6) 33.0 (5) / 38.0 (6) 37.0 (7) / 39.0 (8)

Water side Heat exchanger

Water flow rate Heating Nom. l/min 12.6 (5) / 11.6 (6)

17.2 (5) / 16.3 (6) 21.2 (5) / 19.8 (6) 32.1 (7) / 31.5 (8)

General Supplier/Manufacturer details

Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium

Name or trademark Daikin Europe N.V.

Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater

No

Low-temperature heat pump No

Supplementary heater integrated

Yes

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 40.0 41.0

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 61.0 62.0 64.0

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 2,700 2,820 5,400

Brine/water to water unit

Rated water/brine flow

m³/h 0.00 -

Other Capacity control Inverter

Cdh (Degradation heating) 1.00

Pck (Crankcase heater mode)

kW 0.00 0.055

Poff (Off mode) kW 0.0080 0.055

Psb (Standby mode) kW 0.0080 0.055

Pto (Thermostat off) kW 0.0060 0.0070 0.0080 0.057

Integrated supplementary heater

NOx emission mg/kWh

0.00

Psup kW 3.00 9.00 3.00 9.00 3.00

Type of energy input Electrical

• Heating • ERLQ-CV3 3

• Outdoor Unit • ERLQ-CV3

2

4

2 Specifications

Space heating Average climate water outlet 55°C

General SCOP 3.20 3.22 3.23 3.09

Annual energy consumption

kWh 2,356 3,369 4,064 6,260

Annual energy consumption (GCV)

Gj 8.48 12.1 14.6 22.6

ηs (Seasonal space heating efficiency)

% 125 126 120

Prated at -10°C

kW 3.70 5.30 6.40 9.99

Seasonal space heating eff. class

A++ A+

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.00

COPd 2.03 2.02 1.98 1.99

Pdh kW 3.36 4.50 5.47 8.83

PERd % 81.2 80.8 79.2 79.6

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00

COPd 3.08 3.17 3.24

Pdh kW 2.00 4.43 3.43 5.28

PERd % 123 127 130

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.990 0.950

COPd 4.27 4.20 4.31

Pdh kW 2.77 3.51 3.50 4.47

PERd % 171 168 172

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.990 0.930

COPd 6.33 5.82 6.41

Pdh kW 2.65 3.28 5.37

PERd % 253 233 256

Tol (temperature operating limit)

COPd 1.80 1.74 1.66 1.79

Pdh kW 3.76 4.62 6.18 9.08

PERd % 72.0 69.6 66.4 71.6

TOL °C -10.0

WTOL °C 55.0

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.00 0.680 0.220 0.910

Tbiv (bivalent temperature)

COPd 1.80 1.74 1.66 1.99

Pdh kW 3.76 5.09 6.18 8.83

PERd % 72.0 69.6 66.4 79.6

Tbiv °C -10.0 -9.00 -10.0 -7.00

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 2,133 2,306 3,088 6,740

Annual energy consumption (GCV)

Gj 7.68 8.30 11.1 24.3

ηs (Seasonal space heating efficiency)

% 107 110 95.0

Prated at -22°C

kW 2.39 2.60 3.56 6.99

Warm climate water outlet 55°C

General Annual energy consumption

kWh 1,168 1,491 1,904 2,630

Annual energy consumption (GCV)

Gj 4.20 5.37 6.85 9.47

ηs (Seasonal space heating efficiency)

% 186 182 178 125

Prated at 2°C

kW 4.27 5.30 6.59 7.58

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 5

• Outdoor Unit • ERLQ-CV3

2

6

2 Specifications

Space heating Average climate water outlet 35°C

General SCOP 4.52 4.29 4.34 3.98

Annual energy consumption

kWh 1,980 2,540 3,489 5,380

Annual energy consumption (GCV)

Gj 7.13 9.14 12.6 19.4

ηs (Seasonal space heating efficiency)

% 178 169 171 156

Prated at -10°C

kW 4.40 5.34 7.40 11.2

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

COPd 3.01 2.69 2.63

Pdh kW 4.01 4.72 6.68 8.88

PERd % 120 108 105

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00

COPd 4.41 4.24 4.05

Pdh kW 2.40 3.90 6.03

PERd % 176 170 162

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.980 1.00 0.940

COPd 5.85 5.75 6.77

Pdh kW 1.70 2.59 5.74

PERd % 234 230 271

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.980 0.920

COPd 7.71 7.27 8.97

Pdh kW 2.04 2.61 6.50

PERd % 308 291 359

Tol (temperature operating limit)

COPd 2.61 2.29 2.34

Pdh kW 4.36 4.70 6.81 8.76

PERd % 104 91.6 93.6

TOL °C -10.0

WTOL °C 35.0

G Condition (-15°CDB/-)

COPd 0.00 -

Pdh kW 0.00 -

PERd % 0.00 -

Tbiv (bivalent temperature)

COPd 2.61 2.47 2.82

Pdh kW 4.36 4.93 7.14 9.09

PERd % 104 98.8 113

Tbiv °C -10.0 -8.00 -5.00

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.040 0.640 0.590 2.44

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Cold climate water outlet 35°C

General Annual energy consumption

kWh 1,450 2,040 2,480 6,430

ηs (Seasonal space heating efficiency)

% 151 153 151 148

Prated at -22°C

kW 2.28 3.25 3.89 10.3

Qhe Annual energy consumption (GCV)

Gj 5.20 7.34 8.91 23.1

Warm climate water outlet 35°C

General Annual energy consumption

kWh 905 1,270 1,570 1,950

Annual energy consumption (GCV)

Gj 3.26 4.56 5.67 7.02

ηs (Seasonal space heating efficiency)

% 269 259 251 192

Prated at 2°C

kW 4.81 6.40 7.68 9.06

Domestic hot water heating

General Function to fix water heating during off peak hours

Yes -

Average climate ηwh (water heating efficiency)

% -

Cold climate ηwh (water heating efficiency)

% -

Warm climate ηwh (water heating efficiency)

% -

CONNECTABLE INDOOR UNITS

2-2 Capacity and Power inputEHBH11CB9W/ERLQ011CV3

EHBH16CB3V/ERLQ014CV3

EHBH16CB9W/ERLQ014CV3

EHBH16CB3V/ERLQ016CV3

EHBH16CB9W/ERLQ016CV3

Heating capacity Nom. kW 11.2 / 11.0 14.5 / 13.6 16.0 / 15.2

Max. kW 8.60 / 8.60 10.6 / 10.8 11.4 / 10.9

Power input Heating Nom. kW 2.43 / 3.10 3.37 / 4.10 3.76 / 4.66

Max. kW 3.13 / 4.10 4.00 / 5.19 4.32 / 5.22

COP 4.60 / 2.75 / 3.55 / 2.10

4.30 / 2.65 / 3.32 / 2.08 4.25 / 2.64 / 3.26 / 2.09

Pump Nominal ESP unit Heating kPa 37.0 / 39.0 49.0 / 57.0 33.0 / 42.0

Water side Heat exchanger

Water flow rate Heating Nom. l/min 32.1 / 31.5 41.6 / 39.0 45.9 / 43.6

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 7

• Outdoor Unit • ERLQ-CV3

2

8

2 Specifications

General Supplier/Manufacturer details

Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium

Name or trademark Daikin Europe N.V.

Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater No

Low-temperature heat pump No

Supplementary heater integrated

Yes

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 41.0 44.0

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 64.0 66.0

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 5,400

Other Capacity control Inverter

Cdh (Degradation heating) 1.00

Pck (Crankcase heater mode)

kW 0.055

Poff (Off mode) kW 0.055

Psb (Standby mode) kW 0.055

Pto (Thermostat off) kW 0.057

Integrated supplementary heater

NOx emission mg/kWh 0.00

Psup kW 9.00 3.00 9.00 3.00 9.00

Type of energy input Electrical

Space heating Average climate water outlet 55°C

General SCOP 3.09 3.16 3.06

Annual energy consumption

kWh 6,260 7,900 8,970

Annual energy consumption (GCV)

Gj 22.6 28.4 32.3

ηs (Seasonal space heating efficiency)

% 120 123 119

Prated at -10°C

kW 9.99 12.7 13.9

Seasonal space heating eff. class

A+

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.00

COPd 1.99 1.76 1.78

Pdh kW 8.83 9.97 12.2

PERd % 79.6 70.4 71.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00

COPd 3.24 3.55 3.12

Pdh kW 5.28 6.76 7.61

PERd % 130 142 125

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 55°C

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.950 1.00

COPd 4.31 4.22 4.40

Pdh kW 4.47 4.66 4.83

PERd % 172 169 176

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.930 0.940 0.930

COPd 6.41 5.44 6.36

Pdh kW 5.37 5.26 5.38

PERd % 256 218 254

Tol (temperature operating limit)

COPd 1.79 1.75 1.71

Pdh kW 9.08 12.2 13.3

PERd % 71.6 70.0 68.4

TOL °C -10.0

WTOL °C 55.0

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.910 0.550 0.580

Tbiv (bivalent temperature)

COPd 1.99 1.92 1.78

Pdh kW 8.83 11.0 12.2

PERd % 79.6 76.8 71.2

Tbiv °C -7.00 -6.00 -7.00

Cold climate water outlet 55°C

General Annual energy consumption

kWh 6,740 7,870 8,580

Annual energy consumption (GCV)

Gj 24.3 28.3 30.9

ηs (Seasonal space heating efficiency)

% 95.0 95.5 98.3

Prated at -22°C

kW 6.99 8.15 9.12

Warm climate water outlet 55°C

General Annual energy consumption

kWh 2,630 3,270 3,420

Annual energy consumption (GCV)

Gj 9.47 11.8 12.3

ηs (Seasonal space heating efficiency)

% 125 135 136

Prated at 2°C

kW 7.58 9.84 10.3

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 9

• Outdoor Unit • ERLQ-CV3

2

10

2 Specifications

Space heating Average climate water outlet 35°C

General SCOP 3.98 3.90 3.80

Annual energy consumption

kWh 5,380 7,250 8,270

Annual energy consumption (GCV)

Gj 19.4 26.1 29.8

ηs (Seasonal space heating efficiency)

% 156 153 149

Prated at -10°C

kW 11.2 14.5 16.0

Seasonal space heating eff. class

A++ A+

A Condition (-7°CDB/-8°CWB)

COPd 2.63 2.33

Pdh kW 8.88 10.7 12.4

PERd % 105 93.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00

COPd 4.05 4.07 3.74

Pdh kW 6.03 7.71 8.62

PERd % 162 163 150

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.940 1.00 0.940

COPd 6.77 5.71 6.77

Pdh kW 5.74 5.05 5.74

PERd % 271 228 271

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.920 0.930 0.920

COPd 8.97 6.71 8.97

Pdh kW 6.50 5.16 6.50

PERd % 359 268 359

Tol (temperature operating limit)

COPd 2.34 2.60 2.05

Pdh kW 8.76 12.6 11.7

PERd % 93.6 104 82.0

TOL °C -10.0

WTOL °C 35.0

Tbiv (bivalent temperature)

COPd 2.82 2.83 2.56

Pdh kW 9.09 11.6 12.1

PERd % 113 102

Tbiv °C -5.00 -4.00

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 2.44 1.93 4.35

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Notes

(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)

(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )

(3) Tamb 35°C - LWE 7°C (DT=5°C)

(4) Tamb 35°C - LWE 18°C (DT=5°C)

(5) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)

(6) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)

(7) Contains fluorinated greenhouse gases

(8) Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C

Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C

Space heating Cold climate water outlet 35°C

General Annual energy consumption

kWh 6,430 8,170 9,050

ηs (Seasonal space heating efficiency)

% 148 141 137

Prated at -22°C

kW 10.3 12.3 13.3

Qhe Annual energy consumption (GCV)

Gj 23.1 29.4 32.6

Warm climate water outlet 35°C

General Annual energy consumption

kWh 1,950 2,350 2,480

Annual energy consumption (GCV)

Gj 7.02 8.46 8.92

ηs (Seasonal space heating efficiency)

% 192 199

Prated at 2°C

kW 9.06 10.9 11.4

Domestic hot water heating

Average climate ηwh (water heating efficiency)

% -

Cold climate ηwh (water heating efficiency)

% -

Warm climate ηwh (water heating efficiency)

% -

CONNECTABLE INDOOR UNITS

2-3 Capacity and Power inputEHBX04CB3V/ERLQ004CV3

EHBX08CB3V/ERLQ006CV3

EHBX08CB9W/ERLQ006CV3

EHBX08CB3V/ERLQ008CV3

EHBX08CB9W/ERLQ008CV3

EHBX11CB3V/ERLQ011CV3

Heating capacity Min. kW 1.80 (1) -

Nom. kW 4.40 (1) / 4.03 (2)

6.00 (1) / 5.67 (2) 7.40 (1) / 6.89 (2) 11.2 (1) / 11.0 (2)

Max. kW 5.12 (1) / 4.90 (2)

8.35 (1) / 7.95 (2) 10.0 (1) / 9.53 (2) 8.60 (3) / 8.60 (4)

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 11

• Outdoor Unit • ERLQ-CV3

2

12

2 Specifications

Cooling capacity Min. kW 2.00 (1) / 2.00 (2)

2.50 (1) / 2.50 (2) -

Nom. kW 4.08 (1) / 4.17 (2)

5.88 (1) / 4.84 (2) 6.20 (1) / 5.36 (2) 12.1 (1) / 11.7 (2)

Power input Heating Nom. kW 0.870 (1) / 1.13 (2)

1.27 (1) / 1.59 (2) 1.66 (1) / 2.01 (2) 2.43 (1) / 3.10 (2)

Max. kW - 3.13 (3) / 4.10 (4)

Cooling Nom. kW 0.900 (1) / 1.80 (2)

1.51 (1) / 2.07 (2) 1.64 (1) / 2.34 (2) 3.05 (1) / 4.31 (2)

COP 5.04 (1) / 3.58 (2)

4.74 (1) / 3.56 (2) 4.45 (1) / 3.42 (2) 4.60 (1) / 2.75 (3) / 3.55 (2) /

2.10 (4)

EER 4.55 (1) / 2.32 (2)

3.89 (1) / 2.34 (2) 3.79 (1) / 2.29 (2) 3.98 (1) / 2.72 (2)

Pump Nominal ESP unit Cooling kPa 55.0 (3) / 47.0 (4)

55.0 (3) / 39.0 (4) 50.0 (3) / 38.0 (4) 33.0 (5) / 3.00 (6)

Heating kPa 53.0 (5) / 56.0 (6)

45.0 (5) / 48.0 (6) 33.0 (5) / 38.0 (6) 37.0 (7) / 39.0 (8)

Water side Heat exchanger

Water flow rate Cooling Nom. l/min 12.0 (3) / 14.3 (4)

13.9 (3) / 19.4 (4) 15.4 (3) / 19.7 (4) 33.6 (5) / 43.1 (6)

Heating Nom. l/min 12.6 (5) / 11.6 (6)

17.2 (5) / 16.3 (6) 21.2 (5) / 19.8 (6) 32.1 (7) / 31.5 (8)

General Supplier/Manufacturer details

Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium

Name or trademark Daikin Europe N.V.

Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater No

Low-temperature heat pump No

Supplementary heater integrated

Yes

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 40.0 41.0

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 61.0 62.0 64.0

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 2,700 2,820 5,400

Brine/water to water unit

Rated water/brine flow

m³/h - 0.00 - 0.00 -

Other Capacity control Inverter

Cdh (Degradation heating) 1.00

Pck (Crankcase heater mode)

kW 0.00 0.055

Poff (Off mode) kW 0.0080 0.055

Psb (Standby mode) kW 0.0080 0.055

Pto (Thermostat off) kW 0.0060 0.0070 0.0080 0.057

Integrated supplementary heater

NOx emission mg/kWh 0.00

Psup kW 3.00 9.00 3.00 9.00 3.00

Type of energy input Electrical

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 55°C

General SCOP 3.20 3.22 3.23 3.09

Annual energy consumption

kWh 2,356 3,369 4,064 6,260

Annual energy consumption (GCV)

Gj 8.48 12.1 14.6 22.6

ηs (Seasonal space heating efficiency)

% 125 126 120

Prated at -10°C

kW 3.70 5.30 6.40 9.99

Seasonal space heating eff. class

A++ A+

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.00

COPd 2.03 2.02 1.98 1.99

Pdh kW 3.36 4.50 5.47 8.83

PERd % 81.2 80.8 79.2 79.6

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00

COPd 3.08 3.17 3.24

Pdh kW 2.00 4.43 3.43 5.28

PERd % 123 127 130

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.990 0.950

COPd 4.27 4.20 4.31

Pdh kW 2.77 3.51 3.50 4.47

PERd % 171 168 172

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.990 0.930

COPd 6.33 5.82 6.41

Pdh kW 2.65 3.28 5.37

PERd % 253 233 256

Tol (temperature operating limit)

COPd 1.80 1.74 1.66 1.79

Pdh kW 3.76 4.62 6.18 9.08

PERd % 72.0 69.6 66.4 71.6

TOL °C -10.0

WTOL °C 55.0

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.00 0.680 0.220 0.910

Tbiv (bivalent temperature)

COPd 1.80 1.74 1.66 1.99

Pdh kW 3.76 5.09 6.18 8.83

PERd % 72.0 69.6 66.4 79.6

Tbiv °C -10.0 -9.00 -10.0 -7.00

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 13

• Outdoor Unit • ERLQ-CV3

2

14

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 2,133 2,306 3,088 6,740

Annual energy consumption (GCV)

Gj 7.68 8.30 11.1 24.3

ηs (Seasonal space heating efficiency)

% 107 110 95.0

Prated at -22°C

kW 2.39 2.60 3.56 6.99

Warm climate water outlet 55°C

General Annual energy consumption

kWh 1,168 1,491 1,904 2,630

Annual energy consumption (GCV)

Gj 4.20 5.37 6.85 9.47

ηs (Seasonal space heating efficiency)

% 186 182 178 125

Prated at 2°C

kW 4.27 5.30 6.59 7.58

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 35°C

General SCOP 4.52 4.29 4.34 3.98

Annual energy consumption

kWh 1,980 2,540 3,489 5,380

Annual energy consumption (GCV)

Gj 7.13 9.14 12.6 19.4

ηs (Seasonal space heating efficiency)

% 178 169 171 156

Prated at -10°C

kW 4.40 5.34 7.40 11.2

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

COPd 3.01 2.69 2.63

Pdh kW 4.01 4.72 6.68 8.88

PERd % 120 108 105

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00

COPd 4.41 4.24 4.05

Pdh kW 2.40 3.90 6.03

PERd % 176 170 162

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.980 1.00 0.940

COPd 5.85 5.75 6.77

Pdh kW 1.70 2.59 5.74

PERd % 234 230 271

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.980 0.920

COPd 7.71 7.27 8.97

Pdh kW 39.2 2.61 6.50

PERd % 308 291 359

Tol (temperature operating limit)

COPd 2.61 2.29 2.34

Pdh kW 4.36 4.70 6.81 8.76

PERd % 104 91.6 93.6

TOL °C -10.0

WTOL °C 35.0

G Condition (-15°CDB/-)

COPd 0.00 -

Pdh kW 0.00 -

PERd % 0.00 -

Tbiv (bivalent temperature)

COPd 2.61 2.47 2.82

Pdh kW 4.36 4.93 7.14 9.09

PERd % 104 98.8 113

Tbiv °C -10.0 -8.00 -5.00

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.040 0.640 0.590 2.44

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 15

• Outdoor Unit • ERLQ-CV3

2

16

2 Specifications

Space heating Cold climate water outlet 35°C

General Annual energy consumption

kWh 1,450 2,040 2,480 6,430

ηs (Seasonal space heating efficiency)

% 151 153 151 148

Prated at -22°C

kW 2.28 3.25 3.89 10.3

Qhe Annual energy consumption (GCV)

Gj 5.20 7.34 8.91 23.1

Warm climate water outlet 35°C

General Annual energy consumption

kWh 905 1,270 1,570 1,950

Annual energy consumption (GCV)

Gj 3.26 4.56 5.67 7.02

ηs (Seasonal space heating efficiency)

% 269 259 251 192

Prated at 2°C

kW 4.81 6.40 7.68 9.06

Domestic hot water heating

General Function to fix water heating during off peak hours

Yes -

Average climate ηwh (water heating efficiency)

% -

Cold climate ηwh (water heating efficiency)

% -

Warm climate ηwh (water heating efficiency)

% -

CONNECTABLE INDOOR UNITS

2-4 Capacity and Power inputEHBX11CB9W/ERLQ011CV3

EHBX16CB3V/ERLQ014CV3

EHBX16CB9W/ERLQ014CV3

EHBX16CB9W/ERLQ016CV3

EHBX16CB3V/ERLQ016CV3

Heating capacity Nom. kW 11.2 / 11.0 14.5 / 13.6 16.0 / 15.2

Max. kW 8.60 / 8.60 10.6 / 10.8 11.4 / 10.9

Cooling capacity Nom. kW 12.1 / 11.7 12.7 / 12.6 13.8 / 13.1

Power input Heating Nom. kW 2.43 / 3.10 3.37 / 4.10 3.76 / 4.66

Max. kW 3.13 / 4.10 4.00 / 5.19 4.32 / 5.22

Cooling Nom. kW 3.05 / 4.31 3.21 / 5.08 3.74 / 5.73

COP 4.60 / 2.75 / 3.55 / 2.10

4.30 / 2.65 / 3.32 / 2.08 4.25 / 2.64 / 3.26 / 2.09

EER 3.98 / 2.72 3.96 / 2.47 3.69 / 2.29

Pump Nominal ESP unit Cooling kPa 33.0 / 3.00 64.0 / 32.0 61.0 / 23.0

Heating kPa 37.0 / 39.0 49.0 / 57.0 33.0 / 42.0

Water side Heat exchanger

Water flow rate Cooling Nom. l/min 33.6 / 43.1 36.0 / 46.0 37.6 / 48.0

Heating Nom. l/min 32.1 / 31.5 41.6 / 39.0 45.9 / 43.6

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

General Supplier/Manufacturer details

Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium

Name or trademark Daikin Europe N.V.

Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater No

Low-temperature heat pump No

Supplementary heater integrated

Yes

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 41.0 44.0

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 64.0 66.0

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 5,400

Other Capacity control Inverter

Cdh (Degradation heating) 1.00

Pck (Crankcase heater mode)

kW 0.055

Poff (Off mode) kW 0.055

Psb (Standby mode) kW 0.055

Pto (Thermostat off) kW 0.057

Integrated supplementary heater

NOx emission mg/kWh

0.00

Psup kW 9.00 3.00 9.00 3.00

Type of energy input Electrical

Space heating Average climate water outlet 55°C

General SCOP 3.09 3.16 3.06

Annual energy consumption

kWh 6,260 7,900 8,970

Annual energy consumption (GCV)

Gj 22.6 28.4 32.3

ηs (Seasonal space heating efficiency)

% 120 123 119

Prated at -10°C

kW 9.99 12.7 13.9

Seasonal space heating eff. class

A+

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.00

COPd 1.99 1.76 1.78

Pdh kW 8.83 9.97 12.2

PERd % 79.6 70.4 71.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00

COPd 3.24 3.55 3.12

Pdh kW 5.28 6.76 7.61

PERd % 130 142 125

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 17

• Outdoor Unit • ERLQ-CV3

2

18

2 Specifications

Space heating Average climate water outlet 55°C

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.950 1.00

COPd 4.31 4.22 4.40

Pdh kW 4.47 4.66 4.83

PERd % 172 169 176

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.930 0.940 0.930

COPd 6.41 5.44 6.36

Pdh kW 5.37 5.26 5.38

PERd % 256 218 254

Tol (temperature operating limit)

COPd 1.79 1.75 1.71

Pdh kW 9.08 12.2 13.3

PERd % 71.6 70.0 68.4

TOL °C -10.0

WTOL °C 55.0

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.910 0.550 0.580

Tbiv (bivalent temperature)

COPd 1.99 1.92 1.78

Pdh kW 8.83 11.0 12.2

PERd % 79.6 76.8 71.2

Tbiv °C -7.00 -6.00 -7.00

Cold climate water outlet 55°C

General Annual energy consumption

kWh 6,740 7,870 8,580

Annual energy consumption (GCV)

Gj 24.3 28.3 30.9

ηs (Seasonal space heating efficiency)

% 95.0 95.5 98.3

Prated at -22°C

kW 6.99 8.15 9.12

Warm climate water outlet 55°C

General Annual energy consumption

kWh 2,630 3,270 3,420

Annual energy consumption (GCV)

Gj 9.47 11.8 12.3

ηs (Seasonal space heating efficiency)

% 125 135 136

Prated at 2°C

kW 7.58 9.84 10.3

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 35°C

General SCOP 3.98 3.90 3.80

Annual energy consumption

kWh 5,380 7,250 8,270

Annual energy consumption (GCV)

Gj 19.4 26.1 29.8

ηs (Seasonal space heating efficiency)

% 156 153 149

Prated at -10°C

kW 11.2 14.5 16.0

Seasonal space heating eff. class

A++ A+

A Condition (-7°CDB/-8°CWB)

COPd 2.63 2.33

Pdh kW 8.88 10.7 12.4

PERd % 105 93.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00

COPd 4.05 4.07 3.74

Pdh kW 6.03 7.71 8.62

PERd % 162 163 150

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.940 1.00 0.940

COPd 6.77 5.71 6.77

Pdh kW 5.74 5.05 5.74

PERd % 271 228 271

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.920 0.930 0.920

COPd 8.97 6.71 8.97

Pdh kW 6.50 5.16 6.50

PERd % 359 268 359

Tol (temperature operating limit)

COPd 2.34 2.60 2.05

Pdh kW 8.76 12.6 11.7

PERd % 93.6 104 82.0

TOL °C -10.0

WTOL °C 35.0

Tbiv (bivalent temperature)

COPd 2.82 2.83 2.56

Pdh kW 9.09 11.6 12.1

PERd % 113 102

Tbiv °C -5.00 -4.00

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 2.44 1.93 4.35

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 19

• Outdoor Unit • ERLQ-CV3

2

20

2 Specifications

Notes

(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)

(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )

(3) Tamb 35°C - LWE 7°C (DT=5°C)

(4) Tamb 35°C - LWE 18°C (DT=5°C)

(5) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)

(6) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)

(7) Contains fluorinated greenhouse gases

(8) Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C

Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C

Cold climate water outlet 35°C

General Annual energy consumption

kWh 6,430 8,170 9,050

ηs (Seasonal space heating efficiency)

% 148 141 137

Prated at -22°C

kW 10.3 12.3 13.3

Qhe Annual energy consumption (GCV)

Gj 23.1 29.4 32.6

Warm climate water outlet 35°C

General Annual energy consumption

kWh 1,950 2,350 2,480

Annual energy consumption (GCV)

Gj 7.02 8.46 8.92

ηs (Seasonal space heating efficiency)

% 192 199

Prated at 2°C

kW 9.06 10.9 11.4

Domestic hot water heating

Average climate ηwh (water heating efficiency)

% -

Cold climate ηwh (water heating efficiency)

% -

Warm climate ηwh (water heating efficiency)

% -

CONNECTABLE INDOOR UNITS

2-5 Capacity and Power input

EHVH04S18CB3V/

ERLQ004CV3

EHVH08S26CB9W/

ERLQ006CV3

EHVH08S18CB3V/

ERLQ006CV3

EHVH08S18CB3V/

ERLQ008CV3

EHVH08S26CB9W/

ERLQ008CV3

EHVH11S18CB3V/

ERLQ011CV3

Heating capacity Min. kW 1.80 (1) -

Nom. kW 4.40 (1) / 4.03 (2)

6.00 (1) / 5.67 (2) 7.40 (1) / 6.89 (2) 11.2 (1) / 11.0 (2)

Max. kW 5.12 (1) / 4.90 (2)

8.35 (1) / 7.95 (2) 10.0 (1) / 9.53 (2) 8.60 (3) / 8.60 (4)

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Power input Heating Nom. kW 0.870 (1) / 1.13 (2)

1.27 (1) / 1.59 (2) 1.66 (1) / 2.01 (2) 2.43 (1) / 3.10 (2)

Max. kW - 3.13 (3) / 4.10 (4)

COP 5.04 (1) / 3.58 (2)

4.74 (1) / 3.56 (2) 4.45 (1) / 3.42 (2) 4.60 (1) / 2.75 (3) / 3.55 (2) /

2.10 (4)

Tank Name Stainless steel domestic hot

water tank 180 l

- Stainless steel domestic hot

water tank 180 l

Pump Nominal ESP unit Heating kPa 53.0 (5) / 56.0 (6)

45.0 (5) / 47.0 (6) 33.0 (5) / 37.0 (6) 34.2 (7) / 35.9 (8)

Water side Heat exchanger

Water flow rate Heating Nom. l/min 12.6 (5) / 11.6 (6)

17.2 (5) / 16.3 (6) 21.2 (5) / 19.8 (6) 32.1 (7) / 31.5 (8)

General Supplier/Manufacturer details

Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium

Name or trademark Daikin Europe N.V.

Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated

Yes

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 42.0

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 61.0 62.0 64.0

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 2,700 2,820 5,400

Brine/water to water unit

Rated water/brine flow

m³/h - 0.00 -

Other Capacity control Inverter

Cdh (Degradation heating) 1.00

Pck (Crankcase heater mode)

kW 0.00 0.055

Poff (Off mode) kW 0.0080 0.055

Psb (Standby mode) kW 0.0080 0.055

Pto (Thermostat off) kW 0.0060 0.0070 0.0080 0.057

Integrated supplementary heater

NOx emission mg/kWh 0.00

Psup kW 3.00 9.00 3.00

Type of energy input Electrical

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 21

• Outdoor Unit • ERLQ-CV3

2

22

2 Specifications

Space heating Average climate water outlet 55°C

General SCOP 3.20 3.22 3.23 3.09

Annual energy consumption

kWh 2,356 3,369 4,064 6,260

Annual energy consumption (GCV)

Gj 8.48 12.1 14.6 22.6

ηs (Seasonal space heating efficiency)

% 125 126 120

Prated at -10°C

kW 3.70 5.30 6.40 9.99

Seasonal space heating eff. class

A++ A+

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.00

COPd 2.03 2.02 1.98 1.99

Pdh kW 3.36 4.50 5.47 8.83

PERd % 81.2 80.8 79.2 79.6

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00

COPd 3.08 3.17 3.24

Pdh kW 2.00 4.43 3.43 5.28

PERd % 123 127 130

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.990 0.950

COPd 4.27 4.20 4.31

Pdh kW 2.77 3.51 3.50 4.47

PERd % 171 168 172

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.990 0.930

COPd 6.33 5.82 6.41

Pdh kW 2.65 3.28 5.37

PERd % 253 233 256

Tol (temperature operating limit)

COPd 1.80 1.74 1.66 1.79

Pdh kW 3.76 4.62 6.18 9.08

PERd % 72.0 69.6 66.4 71.6

TOL °C -10.0

WTOL °C 55.0

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.00 0.680 0.220 0.910

Tbiv (bivalent temperature)

COPd 1.80 1.74 1.66 1.99

Pdh kW 3.76 5.09 6.18 8.83

PERd % 72.0 69.6 66.4 79.6

Tbiv °C -10.0 -9.00 -10.0 -7.00

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 2,133 2,306 3,088 6,740

Annual energy consumption (GCV)

Gj 7.68 8.30 11.1 24.3

ηs (Seasonal space heating efficiency)

% 107 110 95.0

Prated at -22°C

kW 2.39 2.60 3.56 6.99

Warm climate water outlet 55°C

General Annual energy consumption

kWh 1,168 1,491 1,904 2,630

Annual energy consumption (GCV)

Gj 4.20 5.37 6.85 9.47

ηs (Seasonal space heating efficiency)

% 186 182 178 125

Prated at 2°C

kW 4.27 5.30 6.59 7.58

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 23

• Outdoor Unit • ERLQ-CV3

2

24

2 Specifications

Space heating Average climate water outlet 35°C

General SCOP 4.52 4.29 4.34 3.98

Annual energy consumption

kWh 1,980 2,540 3,489 5,380

Annual energy consumption (GCV)

Gj 7.13 9.14 12.6 19.4

ηs (Seasonal space heating efficiency)

% 178 169 171 156

Prated at -10°C

kW 4.40 5.34 7.40 11.2

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

COPd 3.01 2.69 2.63

Pdh kW 4.01 4.72 6.68 8.88

PERd % 120 108 105

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00

COPd 4.41 4.24 4.05

Pdh kW 2.40 3.90 6.03

PERd % 176 170 162

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.980 1.00 0.940

COPd 5.85 5.75 6.77

Pdh kW 1.70 2.59 5.74

PERd % 234 230 271

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.980 0.920

COPd 7.71 7.27 8.97

Pdh kW 39.2 2.61 6.50

PERd % 308 291 359

Tol (temperature operating limit)

COPd 2.61 2.29 2.34

Pdh kW 4.36 4.70 6.81 8.76

PERd % 104 91.6 93.6

TOL °C -10.0

WTOL °C 35.0

G Condition (-15°CDB/-)

COPd 0.00 -

Pdh kW 0.00 -

PERd % 0.00 -

Tbiv (bivalent temperature)

COPd 2.61 2.47 2.82

Pdh kW 4.36 4.93 7.14 9.09

PERd % 104 98.8 113

Tbiv °C -10.0 -8.00 -5.00

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.040 0.640 0.590 2.44

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Cold climate water outlet 35°C

General Annual energy consumption

kWh - 6,430

ηs (Seasonal space heating efficiency)

% - 148

Prated at -22°C

kW - 10.3

Qhe Annual energy consumption (GCV)

Gj - 23.1

Warm climate water outlet 35°C

General Annual energy consumption

kWh - 1,950

Annual energy consumption (GCV)

Gj - 7.02

ηs (Seasonal space heating efficiency)

% - 192

Prated at 2°C

kW - 9.06

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 25

• Outdoor Unit • ERLQ-CV3

2

26

2 Specifications

Domestic hot water heating

General Declared load profile L XL L XL L

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 1,084 1,871 1,194 1,871 1,170

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 95.0 90.0 86.4 90.0 87.4

Qelec (Daily electricity consumption)

kWh 4.93 8.50 5.43 8.50 5.32

Qfuel (Daily fuel consumption)

kWh 0.00

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 1,221 2,037 1,332 2,037 1,340

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 84.0 83.0 77.5 83.0 76.6

Qelec (Daily electricity consumption)

kWh 5.55 9.26 6.05 9.26 6.08

Qfuel (Daily fuel consumption)

kWh 0.00

Warm climate AEC (Annual electricity consumption)

kWh 966 1,784 1,123 1,784 1,110

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 106 94.0 91.8 94.0 92.3

Qelec (Daily electricity consumption)

kWh 4.39 8.11 5.10 8.11 5.04

Qfuel (Daily fuel consumption)

kWh - 0.00

CONNECTABLE INDOOR UNITS

2-6 Capacity and Power inputEHVH11S26CB9W/

ERLQ011CV3EHVH16S18CB3V/

ERLQ014CV3EHVH16S26CB9W/

ERLQ014CV3EHVH16S18CB3V/

ERLQ016CV3EHVH16S26CB9W/

ERLQ016CV3

Heating capacity Nom. kW 11.2 / 11.0 14.5 / 13.6 16.0 / 15.2

Max. kW 8.60 / 8.60 10.6 / 10.8 11.4 / 10.9

Power input Heating Nom. kW 2.43 / 3.10 3.37 / 4.10 3.76 / 4.66

Max. kW 3.13 / 4.10 4.00 / 5.19 4.32 / 5.22

COP 4.60 / 2.75 / 3.55 / 2.10

4.30 / 2.65 / 3.32 / 2.08 4.25 / 2.64 / 3.26 / 2.09

Tank Name Stainless steel domestic hot

water tank 260 l

Stainless steel domestic hot

water tank 180 l

Stainless steel domestic hot

water tank 260 l

Stainless steel domestic hot

water tank 180 l

Stainless steel domestic hot

water tank 260 l

Pump Nominal ESP unit Heating kPa 34.2 / 35.9 43.2 / 51.2 26.8 / 36.3

Water side Heat exchanger

Water flow rate Heating Nom. l/min 32.1 / 31.5 41.6 / 39.0 45.9 / 43.6

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

General Supplier/Manufacturer details

Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium

Name or trademark Daikin Europe N.V.

Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated Yes

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 42.0 44.0

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 64.0 66.0

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 5,400

Other Capacity control Inverter

Cdh (Degradation heating) 1.00

Pck (Crankcase heater mode)

kW 0.055

Poff (Off mode) kW 0.055

Psb (Standby mode) kW 0.055

Pto (Thermostat off) kW 0.057

Integrated supplementary heater

NOx emission mg/kWh 0.00

Psup kW 9.00 3.00 9.00 3.00 9.00

Type of energy input Electrical

Space heating Average climate water outlet 55°C

General SCOP 3.09 3.16 3.06

Annual energy consumption

kWh 6,260 7,900 8,970

Annual energy consumption (GCV)

Gj 22.6 28.4 32.3

ηs (Seasonal space heating efficiency)

% 120 123 119

Prated at -10°C

kW 9.99 12.7 13.9

Seasonal space heating eff. class

A+

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.00

COPd 1.99 1.76 1.78

Pdh kW 8.83 9.97 12.2

PERd % 79.6 70.4 71.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00

COPd 3.24 3.55 3.12

Pdh kW 5.28 6.76 7.61

PERd % 130 142 125

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.950 1.00

COPd 4.31 4.22 4.40

Pdh kW 4.47 4.66 4.83

PERd % 172 169 176

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 27

• Outdoor Unit • ERLQ-CV3

2

28

2 Specifications

Space heating Average climate water outlet 55°C

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.930 0.940 0.930

COPd 6.41 5.44 6.36

Pdh kW 5.37 5.26 5.38

PERd % 256 218 254

Tol (temperature operating limit)

COPd 1.79 1.75 1.71

Pdh kW 9.08 12.2 13.3

PERd % 71.6 70.0 68.4

TOL °C -10.0

WTOL °C 55.0

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.910 0.550 0.580

Tbiv (bivalent temperature)

COPd 1.99 1.92 1.78

Pdh kW 8.83 11.0 12.2

PERd % 79.6 76.8 71.2

Tbiv °C -7.00 -6.00 -7.00

Cold climate water outlet 55°C

General Annual energy consumption

kWh 6,740 7,870 8,580

Annual energy consumption (GCV)

Gj 24.3 28.3 30.9

ηs (Seasonal space heating efficiency)

% 95.0 95.5 98.3

Prated at -22°C

kW 6.99 8.15 9.12

Warm climate water outlet 55°C

General Annual energy consumption

kWh 2,630 3,270 3,420

Annual energy consumption (GCV)

Gj 9.47 11.8 12.3

ηs (Seasonal space heating efficiency)

% 125 135 136

Prated at 2°C

kW 7.58 9.84 10.3

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 35°C

General SCOP 3.98 3.90 3.80

Annual energy consumption

kWh 5,380 7,250 8,270

Annual energy consumption (GCV)

Gj 19.4 26.1 29.8

ηs (Seasonal space heating efficiency)

% 156 153 149

Prated at -10°C

kW 11.2 14.5 16.0

Seasonal space heating eff. class

A++ A+

A Condition (-7°CDB/-8°CWB)

COPd 2.63 2.33

Pdh kW 8.88 10.7 12.4

PERd % 105 93.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00

COPd 4.05 4.07 3.74

Pdh kW 6.03 7.71 8.62

PERd % 162 163 150

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.940 1.00 0.940

COPd 6.77 5.71 6.77

Pdh kW 5.74 5.05 5.74

PERd % 271 228 271

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.920 0.930 0.920

COPd 8.97 6.71 8.97

Pdh kW 6.50 5.16 6.50

PERd % 359 268 359

Tol (temperature operating limit)

COPd 2.34 2.60 2.05

Pdh kW 8.76 12.6 11.7

PERd % 93.6 104 82.0

TOL °C -10.0

WTOL °C 35.0

Tbiv (bivalent temperature)

COPd 2.82 2.83 2.56

Pdh kW 9.09 11.6 12.1

PERd % 113 102

Tbiv °C -5.00 -4.00

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 2.44 1.93 4.35

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 29

• Outdoor Unit • ERLQ-CV3

2

30

2 Specifications

Space heating Cold climate water outlet 35°C

General Annual energy consumption

kWh 6,430 8,170 9,050

ηs (Seasonal space heating efficiency)

% 148 141 137

Prated at -22°C

kW 10.3 12.3 13.3

Qhe Annual energy consumption (GCV)

Gj 23.1 29.4 32.6

Warm climate water outlet 35°C

General Annual energy consumption

kWh 1,950 2,350 2,480

Annual energy consumption (GCV)

Gj 7.02 8.46 8.92

ηs (Seasonal space heating efficiency)

% 192 199

Prated at 2°C

kW 9.06 10.9 11.4

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Notes

(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)

(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )

(3) Tamb 35°C - LWE 7°C (DT=5°C)

(4) Tamb 35°C - LWE 18°C (DT=5°C)

(5) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)

(6) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)

(7) Contains fluorinated greenhouse gases

(8) Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C

Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C

Domestic hot water heating

General Declared load profile XL L XL L XL

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 1,720 1,170 1,720 1,170 1,720

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 97.7 87.4 97.7 87.4 97.7

Qelec (Daily electricity consumption)

kWh 7.83 5.32 7.83 5.32 7.83

Qfuel (Daily fuel consumption)

kWh 0.00

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 1,980 1,340 1,980 1,340 1,980

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 85.1 76.6 85.1 76.6 85.1

Qelec (Daily electricity consumption)

kWh 8.99 6.08 8.99 6.08 8.99

Qfuel (Daily fuel consumption)

kWh 0.00

Warm climate AEC (Annual electricity consumption)

kWh 1,630 1,110 1,630 1,110 1,630

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 103 92.3 103 92.3 103

Qelec (Daily electricity consumption)

kWh 7.40 5.04 7.40 5.04 7.40

Qfuel (Daily fuel consumption)

kWh 0.00

CONNECTABLE INDOOR UNITS

2-7 Capacity and Power input EHVH04S18CB3VF/ERLQ004CV3 EHVH08S18CB3VF/ERLQ006CV3 EHVH08S18CB3VF/ERLQ008CV3

Heating capacity Min. kW 1.80 (1)

Nom. kW 4.40 (1) / 4.03 (2) 6.00 (1) / 5.67 (2) 7.40 (1) / 6.89 (2)

Max. kW 5.12 (1) / 4.90 (2) 8.35 (1) / 7.95 (2) 10.0 (1) / 9.53 (2)

Power input Heating Nom. kW 0.870 (1) / 1.13 (2) 1.27 (1) / 1.59 (2) 1.66 (1) / 2.01 (2)

COP 5.04 (1) / 3.58 (2) 4.74 (1) / 3.56 (2) 4.45 (1) / 3.42 (2)

Tank Name Stainless steel domestic hot water tank 180 l

-

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 31

• Outdoor Unit • ERLQ-CV3

2

32

2 Specifications

Pump Nominal ESP unit Heating kPa 53.0 (3) / 56.0 (4) 45.0 (3) / 47.0 (4) 33.0 (3) / 37.0 (4)

Water side Heat exchanger

Water flow rate Heating Nom. l/min 12.6 (3) / 11.6 (4) 17.2 (3) / 16.3 (4) 21.2 (3) / 19.8 (4)

General Supplier/Manufacturer details

Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium

Name or trademark Daikin Europe N.V.

Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated

Yes

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 42.0

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 61.0 62.0

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 2,700 2,820

Brine/water to water unit

Rated water/brine flow m³/h - 0.00

Other Capacity control Inverter

Cdh (Degradation heating) 1.00

Pck (Crankcase heater mode)

kW 0.00

Poff (Off mode) kW 0.0080

Psb (Standby mode) kW 0.0080

Pto (Thermostat off) kW 0.0060 0.0070 0.0080

Integrated supplementary heater

NOx emission mg/kWh

0.00

Psup kW 3.00

Type of energy input Electrical

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 55°C

General SCOP 3.20 3.22 3.23

Annual energy consumption

kWh 2,356 3,369 4,064

Annual energy consumption (GCV)

Gj 8.48 12.1 14.6

ηs (Seasonal space heating efficiency)

% 125 126

Prated at -10°C

kW 3.70 5.30 6.40

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.00

COPd 2.03 2.02 1.98

Pdh kW 3.36 4.50 5.47

PERd % 81.2 80.8 79.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00

COPd 3.08 3.17

Pdh kW 2.00 4.43 3.43

PERd % 123 127

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.990

COPd 4.27 4.20

Pdh kW 2.77 3.51 3.50

PERd % 171 168

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.990

COPd 6.33 5.82

Pdh kW 2.65 3.28

PERd % 253 233

Tol (temperature operating limit)

COPd 1.80 1.74 1.66

Pdh kW 3.76 4.62 6.18

PERd % 72.0 69.6 66.4

TOL °C -10.0

WTOL °C 55.0

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.00 0.680 0.220

Tbiv (bivalent temperature)

COPd 1.80 1.74 1.66

Pdh kW 3.76 5.09 6.18

PERd % 72.0 69.6 66.4

Tbiv °C -10.0 -9.00 -10.0

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 33

• Outdoor Unit • ERLQ-CV3

2

34

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 2,133 2,306 3,088

Annual energy consumption (GCV)

Gj 7.68 8.30 11.1

ηs (Seasonal space heating efficiency)

% 107 110

Prated at -22°C

kW 2.39 2.60 3.56

Warm climate water outlet 55°C

General Annual energy consumption

kWh 1,168 1,491 1,904

Annual energy consumption (GCV)

Gj 4.20 5.37 6.85

ηs (Seasonal space heating efficiency)

% 186 182 178

Prated at 2°C

kW 4.27 5.30 6.59

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 35°C

General SCOP 4.52 4.29 4.34

Annual energy consumption

kWh 1,980 2,540 3,489

Annual energy consumption (GCV)

Gj 7.13 9.14 12.6

ηs (Seasonal space heating efficiency)

% 178 169 171

Prated at -10°C

kW 4.40 5.34 7.40

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

COPd 3.01 2.69

Pdh kW 4.01 4.72 6.68

PERd % 120 108

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00

COPd 4.41 4.24

Pdh kW 2.40 3.90

PERd % 176 170

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.980 1.00

COPd 5.85 5.75

Pdh kW 1.70 2.59

PERd % 234 230

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.980

COPd 7.71 7.27

Pdh kW 39.2 2.61

PERd % 308 291

Tol (temperature operating limit)

COPd 2.61 2.29

Pdh kW 4.36 4.70 6.81

PERd % 104 91.6

TOL °C -10.0

WTOL °C 35.0

G Condition (-15°CDB/-)

COPd 0.00

Pdh kW 0.00

PERd % 0.00

Tbiv (bivalent temperature)

COPd 2.61 2.47

Pdh kW 4.36 4.93 7.14

PERd % 104 98.8

Tbiv °C -10.0 -8.00

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.040 0.640 0.590

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 35

• Outdoor Unit • ERLQ-CV3

2

36

2 Specifications

Notes

(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)

(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )

(3) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)

(4) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)

Tamb 35°C - LWE 7°C (DT=5°C)

Tamb 35°C - LWE 18°C (DT=5°C)

Contains fluorinated greenhouse gases

Space heating Cold climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Qhe Annual energy consumption (GCV)

Gj -

Warm climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Domestic hot water heating

General Declared load profile L

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 1,084 1,194

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 95.0 86.4

Qelec (Daily electricity consumption)

kWh 4.93 5.43

Qfuel (Daily fuel consumption)

kWh 0.00

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 1,221 1,332

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 84.0 77.5

Qelec (Daily electricity consumption)

kWh 5.55 6.05

Qfuel (Daily fuel consumption)

kWh 0.00

Warm climate AEC (Annual electricity consumption)

kWh 966 1,123

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 106 91.8

Qelec (Daily electricity consumption)

kWh 4.39 5.10

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

CONNECTABLE INDOOR UNITS

2-8 Capacity and Power input

EHVX04S18CB3V/

ERLQ004CV3

EHVX08S18CB3V/

ERLQ006CV3

EHVX08S26CB9W/

ERLQ006CV3

EHVX08S18CB3V/

ERLQ008CV3

EHVX08S26CB9W/

ERLQ008CV3

EHVX11S18CB3V/

ERLQ011CV3

Heating capacity Min. kW 1.80 (1) -

Nom. kW 4.40 (1) / 4.03 (2)

6.00 (1) / 5.67 (2) 7.40 (1) / 6.89 (2) 11.2 (1) / 11.0 (2)

Max. kW 5.12 (1) / 4.90 (2)

8.35 (1) / 7.95 (2) 10.0 (1) / 9.53 (2) 8.60 (3) / 8.60 (4)

Cooling capacity Min. kW 2.00 (1) / 2.00 (2)

2.50 (1) / 2.50 (2) -

Nom. kW 4.08 (1) / 4.17 (2)

5.88 (1) / 4.84 (2) 6.20 (1) / 5.36 (2) 12.1 (1) / 11.7 (2)

Power input Heating Nom. kW 0.870 (1) / 1.13 (2)

1.27 (1) / 1.59 (2) 1.66 (1) / 2.01 (2) 2.43 (1) / 3.10 (2)

Max. kW - 3.13 (3) / 4.10 (4)

Cooling Nom. kW 0.900 (1) / 1.80 (2)

1.51 (1) / 2.07 (2) 1.64 (1) / 2.34 (2) 3.05 (1) / 4.31 (2)

COP 5.04 (1) / 3.58 (2)

4.74 (1) / 3.56 (2) 4.45 (1) / 3.42 (2) 4.60 (1) / 2.75 (3) / 3.55 (2) /

2.10 (4)

EER 4.55 (1) / 2.32 (2)

3.89 (1) / 2.34 (2) 3.79 (1) / 2.29 (2) 3.98 (1) / 2.72 (2)

Tank Name - Stainless steel domestic hot

water tank 180 l

Pump Nominal ESP unit Cooling kPa 54.0 (3) / 47.0 (4)

54.0 (3) / 38.0 (4) 50.0 (3) / 37.0 (4) 29.8 (5) / 1.30 (6)

Heating kPa 53.0 (5) / 56.0 (6)

45.0 (5) / 47.0 (6) 33.0 (5) / 37.0 (6) 34.2 (7) / 35.9 (8)

Water side Heat exchanger

Water flow rate Cooling Nom. l/min 12.0 (3) / 14.3 (4)

13.9 (3) / 19.4 (4) 15.4 (3) / 19.7 (4) 33.6 (5) / 43.1 (6)

Heating Nom. l/min 12.6 (5) / 11.6 (6)

17.2 (5) / 16.3 (6) 21.2 (5) / 19.8 (6) 32.1 (7) / 31.5 (8)

General Supplier/Manufacturer details

Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium

Name or trademark Daikin Europe N.V.

Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated

Yes

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 42.0

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 61.0 62.0 64.0

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

• Heating • ERLQ-CV3 37

• Outdoor Unit • ERLQ-CV3

2

38

2 Specifications

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 2,700 2,820 5,400

Brine/water to water unit

Rated water/brine flow

m³/h - 0.00 -

Other Capacity control Inverter

Cdh (Degradation heating) 1.00

Pck (Crankcase heater mode)

kW 0.00 0.055

Poff (Off mode) kW 0.0080 0.055

Psb (Standby mode) kW 0.0080 0.055

Pto (Thermostat off) kW 0.0060 0.0070 0.0080 0.057

Integrated supplementary heater

NOx emission mg/kWh

0.00

Psup kW 3.00 9.00 3.00 9.00 3.00

Type of energy input Electrical

Space heating Average climate water outlet 55°C

General SCOP 3.20 3.22 3.23 3.09

Annual energy consumption

kWh 2,356 3,369 4,064 6,260

Annual energy consumption (GCV)

Gj 8.48 12.1 14.6 22.6

ηs (Seasonal space heating efficiency)

% 125 126 120

Prated at -10°C

kW 3.70 5.30 6.40 9.99

Seasonal space heating eff. class

A++ A+

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.00

COPd 2.03 2.02 1.98 1.99

Pdh kW 3.36 4.50 5.47 8.83

PERd % 81.2 80.8 79.2 79.6

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00

COPd 3.08 3.17 3.24

Pdh kW 2.00 4.43 3.43 5.28

PERd % 123 127 130

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.990 0.950

COPd 4.27 4.20 4.31

Pdh kW 2.77 3.51 3.50 4.47

PERd % 171 168 172

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.990 0.930

COPd 6.33 5.82 6.41

Pdh kW 2.65 3.28 5.37

PERd % 253 233 256

Tol (temperature operating limit)

COPd 1.80 1.74 1.66 1.79

Pdh kW 3.76 4.62 6.18 9.08

PERd % 72.0 69.6 66.4 71.6

TOL °C -10.0

WTOL °C 55.0

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 55°C

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.00 0.680 0.220 0.910

Tbiv (bivalent temperature)

COPd 1.80 1.74 1.66 1.99

Pdh kW 3.76 5.09 6.18 8.83

PERd % 72.0 69.6 66.4 79.6

Tbiv °C -10.0 -9.00 -10.0 -7.00

Cold climate water outlet 55°C

General Annual energy consumption

kWh 2,133 2,306 3,088 6,740

Annual energy consumption (GCV)

Gj 7.68 8.30 11.1 24.3

ηs (Seasonal space heating efficiency)

% 107 110 95.0

Prated at -22°C

kW 2.39 2.60 3.56 6.99

Warm climate water outlet 55°C

General Annual energy consumption

kWh 1,168 1,491 1,904 2,630

Annual energy consumption (GCV)

Gj 4.20 5.37 6.85 9.47

ηs (Seasonal space heating efficiency)

% 186 182 178 125

Prated at 2°C

kW 4.27 5.30 6.59 7.58

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 39

• Outdoor Unit • ERLQ-CV3

2

40

2 Specifications

Space heating Average climate water outlet 35°C

General SCOP 4.52 4.29 4.34 3.98

Annual energy consumption

kWh 1,980 2,540 3,489 5,380

Annual energy consumption (GCV)

Gj 7.13 9.14 12.6 19.4

ηs (Seasonal space heating efficiency)

% 178 169 171 156

Prated at -10°C

kW 4.40 5.34 7.40 11.2

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

COPd 3.01 2.69 2.63

Pdh kW 4.01 4.72 6.68 8.88

PERd % 120 108 105

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00

COPd 4.41 4.24 4.05

Pdh kW 2.40 3.90 6.03

PERd % 176 170 162

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.980 1.00 0.940

COPd 5.85 5.75 6.77

Pdh kW 1.70 2.59 5.74

PERd % 234 230 271

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.980 0.920

COPd 7.71 7.27 8.97

Pdh kW 39.2 2.61 6.50

PERd % 308 291 359

Tol (temperature operating limit)

COPd 2.61 2.29 2.34

Pdh kW 4.36 4.70 6.81 8.76

PERd % 104 91.6 93.6

TOL °C -10.0

WTOL °C 35.0

G Condition (-15°CDB/-)

COPd 0.00 -

Pdh kW 0.00 -

PERd % 0.00 -

Tbiv (bivalent temperature)

COPd 2.61 2.47 2.82

Pdh kW 4.36 4.93 7.14 9.09

PERd % 104 98.8 113

Tbiv °C -10.0 -8.00 -5.00

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.040 0.640 0.590 2.44

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Cold climate water outlet 35°C

General Annual energy consumption

kWh - 6,430

ηs (Seasonal space heating efficiency)

% - 148

Prated at -22°C

kW - 10.3

Qhe Annual energy consumption (GCV)

Gj - 23.1

Warm climate water outlet 35°C

General Annual energy consumption

kWh - 1,950

Annual energy consumption (GCV)

Gj - 7.02

ηs (Seasonal space heating efficiency)

% - 192

Prated at 2°C

kW - 9.06

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 41

• Outdoor Unit • ERLQ-CV3

2

42

2 Specifications

Domestic hot water heating

General Declared load profile L XL L XL L

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 1,084 1,194 1,871 1,194 1,871 1,170

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 95.0 86.4 90.0 86.4 90.0 87.4

Qelec (Daily electricity consumption)

kWh 4.93 5.43 8.50 5.43 8.50 5.32

Qfuel (Daily fuel consumption)

kWh 0.00

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 1,221 1,332 2,037 1,332 2,037 1,340

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 84.0 77.5 83.0 77.5 83.0 76.6

Qelec (Daily electricity consumption)

kWh 5.55 6.05 9.26 6.05 9.26 6.08

Qfuel (Daily fuel consumption)

kWh 0.00

Warm climate AEC (Annual electricity consumption)

kWh 966 1,123 1,784 1,123 1,784 1,110

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 106 91.8 94.0 91.8 94.0 92.3

Qelec (Daily electricity consumption)

kWh 4.39 5.10 8.11 5.10 8.11 5.04

Qfuel (Daily fuel consumption)

kWh - 0.00

CONNECTABLE INDOOR UNITS

2-9 Capacity and Power inputEHVX11S26CB9W/

ERLQ011CV3EHVX16S18CB3V/

ERLQ014CV3EHVX16S26CB9W/

ERLQ014CV3EHVX16S18CB3V/

ERLQ016CV3EHVX16S26CB9W/

ERLQ016CV3

Heating capacity Nom. kW 11.2 / 11.0 14.5 / 13.6 16.0 / 15.2

Max. kW 8.60 / 8.60 10.6 / 10.8 11.4 / 10.9

Cooling capacity Nom. kW 12.1 / 11.7 12.7 / 12.6 13.8 / 13.1

Power input Heating Nom. kW 2.43 / 3.10 3.37 / 4.10 3.76 / 4.66

Max. kW 3.13 / 4.10 4.00 / 5.19 4.32 / 5.22

Cooling Nom. kW 3.05 / 4.31 3.21 / 5.08 3.74 / 5.73

COP 4.60 / 2.75 / 3.55 / 2.10

4.30 / 2.65 / 3.32 / 2.08 4.25 / 2.64 / 3.26 / 2.09

EER 3.98 / 2.72 3.96 / 2.47 3.69 / 2.29

Tank Name Stainless steel domestic hot

water tank 260 l

Stainless steel domestic hot

water tank 180 l

Stainless steel domestic hot

water tank 260 l

Stainless steel domestic hot

water tank 180 l

Stainless steel domestic hot

water tank 260 l

Pump Nominal ESP unit Cooling kPa 29.8 / 1.30 59.2 / 27.2 55.0 / 18.8

Heating kPa 34.2 / 35.9 43.2 / 51.2 26.8 / 36.3

Water side Heat exchanger

Water flow rate Cooling Nom. l/min 33.6 / 43.1 36.0 / 46.0 37.6 / 48.0

Heating Nom. l/min 32.1 / 31.5 41.6 / 39.0 45.9 / 43.6

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

General Supplier/Manufacturer details

Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium

Name or trademark Daikin Europe N.V.

Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated

Yes

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 42.0 44.0

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 64.0 66.0

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 5,400

Other Capacity control Inverter

Cdh (Degradation heating) 1.00

Pck (Crankcase heater mode)

kW 0.055

Poff (Off mode) kW 0.055

Psb (Standby mode) kW 0.055

Pto (Thermostat off) kW 0.057

Integrated supplementary heater

NOx emission mg/kWh 0.00

Psup kW 9.00 3.00 9.00 3.00 9.00

Type of energy input Electrical

Space heating Average climate water outlet 55°C

General SCOP 3.09 3.16 3.06

Annual energy consumption

kWh 6,260 7,900 8,970

Annual energy consumption (GCV)

Gj 22.6 28.4 32.3

ηs (Seasonal space heating efficiency)

% 120 123 119

Prated at -10°C

kW 9.99 12.7 13.9

Seasonal space heating eff. class

A+

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.00

COPd 1.99 1.76 1.78

Pdh kW 8.83 9.97 12.2

PERd % 79.6 70.4 71.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00

COPd 3.24 3.55 3.12

Pdh kW 5.28 6.76 7.61

PERd % 130 142 125

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 43

• Outdoor Unit • ERLQ-CV3

2

44

2 Specifications

Space heating Average climate water outlet 55°C

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.950 1.00

COPd 4.31 4.22 4.40

Pdh kW 4.47 4.66 4.83

PERd % 172 169 176

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.930 0.940 0.930

COPd 6.41 5.44 6.36

Pdh kW 5.37 5.26 5.38

PERd % 256 218 254

Tol (temperature operating limit)

COPd 1.79 1.75 1.71

Pdh kW 9.08 12.2 13.3

PERd % 71.6 70.0 68.4

TOL °C -10.0

WTOL °C 55.0

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.910 0.550 0.580

Tbiv (bivalent temperature)

COPd 1.99 1.92 1.78

Pdh kW 8.83 11.0 12.2

PERd % 79.6 76.8 71.2

Tbiv °C -7.00 -6.00 -7.00

Cold climate water outlet 55°C

General Annual energy consumption

kWh 6,740 7,870 8,580

Annual energy consumption (GCV)

Gj 24.3 28.3 30.9

ηs (Seasonal space heating efficiency)

% 95.0 95.5 98.3

Prated at -22°C

kW 6.99 8.15 9.12

Warm climate water outlet 55°C

General Annual energy consumption

kWh 2,630 3,270 3,420

Annual energy consumption (GCV)

Gj 9.47 11.8 12.3

ηs (Seasonal space heating efficiency)

% 125 135 136

Prated at 2°C

kW 7.58 9.84 10.3

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 35°C

General SCOP 3.98 3.90 3.80

Annual energy consumption

kWh 5,380 7,250 8,270

Annual energy consumption (GCV)

Gj 19.4 26.1 29.8

ηs (Seasonal space heating efficiency)

% 156 153 149

Prated at -10°C

kW 11.2 14.5 16.0

Seasonal space heating eff. class

A++ A+

A Condition (-7°CDB/-8°CWB)

COPd 2.63 2.33

Pdh kW 8.88 10.7 12.4

PERd % 105 93.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00

COPd 4.05 4.07 3.74

Pdh kW 6.03 7.71 8.62

PERd % 162 163 150

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.940 1.00 0.940

COPd 6.77 5.71 6.77

Pdh kW 5.74 5.05 5.74

PERd % 271 228 271

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.920 0.930 0.920

COPd 8.97 6.71 8.97

Pdh kW 6.50 5.16 6.50

PERd % 359 268 359

Tol (temperature operating limit)

COPd 2.34 2.60 2.05

Pdh kW 8.76 12.6 11.7

PERd % 93.6 104 82.0

TOL °C -10.0

WTOL °C 35.0

Tbiv (bivalent temperature)

COPd 2.82 2.83 2.56

Pdh kW 9.09 11.6 12.1

PERd % 113 102

Tbiv °C -5.00 -4.00

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 2.44 1.93 4.35

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 45

• Outdoor Unit • ERLQ-CV3

2

46

2 Specifications

Space heating Cold climate water outlet 35°C

General Annual energy consumption

kWh 6,430 8,170 9,050

ηs (Seasonal space heating efficiency)

% 148 141 137

Prated at -22°C

kW 10.3 12.3 13.3

Qhe Annual energy consumption (GCV)

Gj 23.1 29.4 32.6

Warm climate water outlet 35°C

General Annual energy consumption

kWh 1,950 2,350 2,480

Annual energy consumption (GCV)

Gj 7.02 8.46 8.92

ηs (Seasonal space heating efficiency)

% 192 199

Prated at 2°C

kW 9.06 10.9 11.4

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Notes

(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)

(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )

(3) Tamb 35°C - LWE 7°C (DT=5°C)

(4) Tamb 35°C - LWE 18°C (DT=5°C)

(5) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)

(6) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)

(7) Contains fluorinated greenhouse gases

(8) Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C

Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C

Domestic hot water heating

General Declared load profile XL L XL L XL

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 1,720 1,170 1,720 1,170 1,720

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 97.7 87.4 97.7 87.4 97.7

Qelec (Daily electricity consumption)

kWh 7.83 5.32 7.83 5.32 7.83

Qfuel (Daily fuel consumption)

kWh 0.00

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 1,980 1,340 1,980 1,340 1,980

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 85.1 76.6 85.1 76.6 85.1

Qelec (Daily electricity consumption)

kWh 8.99 6.08 8.99 6.08 8.99

Qfuel (Daily fuel consumption)

kWh 0.00

Warm climate AEC (Annual electricity consumption)

kWh 1,630 1,110 1,630 1,110 1,630

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 103 92.3 103 92.3 103

Qelec (Daily electricity consumption)

kWh 7.40 5.04 7.40 5.04 7.40

Qfuel (Daily fuel consumption)

kWh 0.00

CONNECTABLE INDOOR UNITS

2-10 Capacity and Power inputEHSXB04P30B/ERLQ004CV3

EHSXB08P30B/ERLQ006CV3

EHSXB08P50B/ERLQ006CV3

EHSXB08P30B/ERLQ008CV3

EHSXB08P50B/ERLQ008CV3

EHSXB16P50B/ERLQ011CV3

Indoor unit EHSXB04P30BA

EHSXB08P30BA

EHSXB08P50BA

EHSXB08P30BA

EHSXB08P50BA

EHSXB16P50BA

Outdoor unit ERLQ004CAV3

ERLQ006CAV3 ERLQ008CAV3 ERLQ011CAV3

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 47

• Outdoor Unit • ERLQ-CV3

2

48

2 Specifications

Heating capacity Min. kW 1.80 (1) / 1.81 (2) -

Nom. kW 4.26 (3) / 3.47 (4) / 4.53 (1) /

3.98 (2)

5.14 (3) / 4.60 (4) / 6.06 (1) / 5.78 (2)

5.53 (3) / 5.51 (4) / 7.78 (1) / 7.27 (2)

5.95 (1) / 7.74 (2) / 11.80 (3) /

10.40 (4)

Max. kW 4.90 (1) / 5.12 (2)

8.35 (1) / 7.95 (2) 10.02 (1) / 9.53 (2) 11.38 (3) / 11.00 (4)

Cooling capacity Min. kW 2.0 (5) / 2.1 (6) 2.5 (5) / 2.6 (6)

Nom. kW 4.4 (5) / 4.0 (6) 5.2 (5) / 4.6 (6) 15.1 (5) / 11.7 (6)

Max. kW 5.9 (5) / 4.5 (6) 7.3 (5) / 5.5 (6) 8.4 (5) / 6.4 (6) 15.1 (5) / 11.7 (6)

Power input Heating Nom. kW 0.87 (5) / 1.04 (6) / 1.49 (3) /

0.85 (4)

1.30 (5) / 1.58 (6) / 1.88 (3) / 1.26 (4)

1.69 (5) / 2.04 (6) / 1.98 (3) / 1.56 (4)

2.57 (5) / 3.13 (6) / 2.43 (1) /

2.35 (2)

Max. kW 1.12 (5) / 1.44 (6)

1.99 (5) / 2.32 (6) 2.54 (5) / 2.96 (6) 2.64 (5) / 3.25 (6)

Cooling Nom. kW 1.05 (5) / 1.41 (6)

1.43 (5) / 1.85 (6) 4.55 (5) / 4.30 (6)

Max. kW 1.86 (5) / 2.04 (6)

2.27 (5) / 2.51 (6) 2.89 (5) / 3.20 (6) 4.53 (5) / 4.31 (6)

COP 5.23 (5) / 3.84 (6) / 2.85 (3) /

4.07 (4)

4.65 (5) / 3.66 (6) / 2.73 (3) / 3.64 (4)

4.60 (5) / 3.57 (6) / 2.78 (3) / 3.54 (4)

4.38 (5) / 3.32 (6) / 2.45 (1) /

3.29 (2)

EER 4.21 (5) / 2.85 (6)

3.65 (5) / 2.51 (6) 3.32 (5) / 2.72 (6)

Pump Type Grundfos UPM3 25-75 CHBL

Nominal ESP unit Cooling kPa 45.0 (7) / 48.0 (8)

44.0 (7) / 46.0 (8) -

Heating kPa 46.0 (9) / 48.0 (10)

40.0 (9) / 41.0 (10) 37.0 (9) / 36.0 (10) -

Water side Heat exchanger

Water flow rate Cooling Nom. l/min 12.7 (7) / 11.5 (8)

12.9 (7) / 13.3 (8) 43.3 (7) / 33.5 (8)

Heating Nom. l/min 13.0 (9) / 11.3 (10)

17.4 (9) / 16.6 (10) 22.3 (9) / 20.8 (10) 33.8 (9) / 29.8 (10)

General Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated No

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 39

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 61 62 64

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 2,700 2,820 -

Other Capacity control Inverter

Cdh (Degradation heating) 0.9

Pck (Crankcase heater mode)

kW 0.000

Poff (Off mode) kW 0.011 0.012 0.050

Psb (Standby mode) kW 0.011 0.012 0.050

Pto (Thermostat off) kW 0.043 0.048 0.105

Integrated supplementary heater

Psup kW 9.0

Type of energy input Electrical

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 55°C

General Annual energy consumption

kWh 2,934 3,828 4,725 6,345

ηs (Seasonal space heating efficiency)

% 132 126 128

Prated at -10°C

kW 5 6 8 10

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.03 2.09 2.10 1.94

Pdh kW 4.2 5.3 5.4 9.0

PERd % 81.2 83.6 84.0 77.6

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.31 3.13 3.25 3.30

Pdh kW 2.6 3.1 3.9 5.4

PERd % 132.4 125.2 130.0 132.0

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0 0.9

COPd 4.43 4.09 4.42 4.26

Pdh kW 1.8 2.1 2.6 4.6

PERd % 177.2 163.6 176.8 170.4

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 6.55 5.99 6.30

Pdh kW 2.2 2.0 5.5

PERd % 262.0 239.6 252.0

Tol (temperature operating limit)

COPd 1.64 1.79 1.78

Pdh kW 4.1 5.1 9.1

PERd % 65.6 71.6 71.2

TOL °C -10

WTOL °C 55

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.7 0.9 2.4 1.0

Tbiv (bivalent temperature)

COPd 2.03 2.09 2.36 1.94

Pdh kW 4.2 5.3 5.8 9.0

PERd % 81.2 83.6 94.4 77.6

Tbiv °C -7 -4 -7

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 49

• Outdoor Unit • ERLQ-CV3

2

50

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 3,069 4,008 4,575 8,185

ηs (Seasonal space heating efficiency)

% 110 104 109 101

Prated at -22°C

kW 4 5 9

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.30 2.47 2.41 1.98

Pdh kW 2.2 2.6 3.2 5.2

PERd % 92.0 98.8 96.4 79.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0 0.9 1.0

COPd 3.75 3.26 3.69 3.25

Pdh kW 1.4 2.0 2.4 3.2

PERd % 150.0 130.4 147.6 130.0

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.9

COPd 5.92 4.42 5.58 5.50

Pdh kW 1.6 2.6 3.2 5.2

PERd % 236.8 176.8 223.2 220.0

D Condition (12°CDB/11°CWB)

COPd 8.65 5.54 7.79 7.56

Pdh kW 1.6 3.0 3.6 6.1

PERd % 346.0 221.6 311.6 302.4

Tol (temperature operating limit)

COPd 0.89 1.05 0.98 1.22

Pdh kW 0.8 1.0 1.2 5.7

PERd % 35.6 42.0 39.2 48.8

TOL °C -20

WTOL °C 55

G Condition (-15°CDB/-)

COPd 1.25 1.42 1.33 1.51

Pdh kW 2.9 3.6 4.3 7.1

PERd % 50.0 56.8 53.2 60.4

Tbiv (bivalent temperature)

COPd 1.25 1.42 1.33 1.51

Pdh kW 2.9 3.6 4.3 7.1

PERd % 50.0 56.8 53.2 60.4

Tbiv °C -15

Rated heat output supplementary capacity

Psup (at Tdesign -22°C)

kW 3.5 4.4 5.2 3.4

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Warm climate water outlet 55°C

General Annual energy consumption

kWh 1,174 1,901 1,932 2,637

ηs (Seasonal space heating efficiency)

% 186 149 176 146

Prated at 2°C

kW 4 5 7 8

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 2.11 2.29 2.15 1.82

Pdh kW 4.3 5.5 6.6 7.6

PERd % 84.4 91.6 86.0 72.8

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 3.76 3.41 3.70 3.07

Pdh kW 2.8 3.5 4.2 4.9

PERd % 150.4 136.4 148.0 122.8

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 7.26 4.86 6.52 5.88

Pdh kW 1.6 2.9 3.5 5.4

PERd % 290.4 194.4 260.8 235.2

Tbiv (bivalent temperature)

COPd 2.11 2.29 2.15 1.82

Pdh kW 4.3 5.5 6.6 7.6

PERd % 84.4 91.6 86.0 72.8

Tbiv °C 2

Average climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Cold climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Qhe Annual energy consumption (GCV)

Gj -

Warm climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 51

• Outdoor Unit • ERLQ-CV3

2

52

2 Specifications

Domestic hot water heating

General Declared load profile L XL L XL

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 1,063 1,148 1,654 1,256 1,797 2,158

ηwh (water heating efficiency)

% 103 98 108 90 99 84

Qelec (Daily electricity consumption)

kWh 4.753 5.138 7.453 5.630 8.105 9.681

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 1,221 1,263 1,858 1,387 2,200 2,394

ηwh (water heating efficiency)

% 92 89 95 80 76

Qelec (Daily electricity consumption)

kWh 5.473 5.653 8.379 6.226 10.000 10.755

Warm climate AEC (Annual electricity consumption)

kWh 948 1,068 1,510 1,138 1,696 1,921

ηwh (water heating efficiency)

% 120 107 117 100 106 95

Qelec (Daily electricity consumption)

kWh 4.229 4.763 6.796 5.091 8.000 8.600

CONNECTABLE INDOOR UNITS

2-11 Capacity and Power input EHSXB16P50B/ERLQ014CV3 EHSXB16P50B/ERLQ016CV3

Indoor unit EHSXB16P50BA

Outdoor unit ERLQ014CAV3 ERLQ016CAV3

Heating capacity Nom. kW 14.81 / 13.73 / 8.28 / 9.57 15.34 / 14.86 / 8.04 / 10.05

Max. kW 14.55 / 13.59 16.10 / 15.22

Cooling capacity Min. kW 2.5 / 2.6 -

Nom. kW 16.1 / 12.6 16.8 / 13.1

Max. kW 16.1 / 12.6 16.8 / 13.1

Power input Heating Nom. kW 3.42 / 4.07 / 3.17 / 2.93

Max. kW 3.43 / 4.22 3.83 / 4.71

Cooling Nom. kW 5.44 / 5.10 6.18 / 5.72

Max. kW 5.42 / 5.09 6.15 / 5.74

COP 4.27 / 3.34 / 2.58 / 3.22 4.10 / 3.22 / 2.44 / 3.15

EER 2.96 / 2.47 2.72 / 2.29

Pump Type Grundfos UPM3 25-75 CHBL

Water side Heat exchanger

Water flow rate Cooling Nom. l/min 46.0 / 36.1 48.1 / 37.5

Heating Nom. l/min 42.4 / 39.4 44.0 / 42.6

General Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated No

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 39

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 64 66

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating general Other Capacity control Inverter

Cdh (Degradation heating) 0.9

Pck (Crankcase heater mode)

kW 0.000

Poff (Off mode) kW 0.050

Psb (Standby mode) kW 0.050

Pto (Thermostat off) kW 0.105

Integrated supplementary heater

Psup kW 9.0

Type of energy input Electrical

Space heating Average climate water outlet 55°C

General Annual energy consumption

kWh 7,654 8,978

ηs (Seasonal space heating efficiency)

% 130 127

Prated at -10°C

kW 12 14

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 1.92 1.85

Pdh kW 10.9 12.6

PERd % 76.8 74.0

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.30 3.19

Pdh kW 6.6 7.8

PERd % 132.0 127.6

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 4.34 4.47

Pdh kW 4.6 4.9

PERd % 173.6 178.8

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 6.45 6.52

Pdh kW 5.5 5.4

PERd % 258.0 260.8

Tol (temperature operating limit)

COPd 1.63 1.57

Pdh kW 9.8 11.2

PERd % 65.2 62.8

TOL °C -10

WTOL °C 55

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 2.5 3.0

Tbiv (bivalent temperature)

COPd 1.92 1.84

Pdh kW 10.9 12.6

PERd % 76.8 73.6

Tbiv °C -7

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 53

• Outdoor Unit • ERLQ-CV3

2

54

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 9,676 10,405

ηs (Seasonal space heating efficiency)

% 101

Prated at -22°C

kW 10 11

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.04 2.05

Pdh kW 6.2 6.6

PERd % 81.6 82.0

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.20 3.19

Pdh kW 3.8 4.0

PERd % 128.0 127.6

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.9

COPd 5.50

Pdh kW 5.2

PERd % 220.0

D Condition (12°CDB/11°CWB)

COPd 7.56

Pdh kW 6.1

PERd % 302.4

Tol (temperature operating limit)

COPd 1.13 1.08

Pdh kW 6.4 6.8

PERd % 45.2 43.2

TOL °C -20

WTOL °C 55

G Condition (-15°CDB/-)

COPd 1.50 1.42

Pdh kW 8.4 8.9

PERd % 60.0 56.8

Tbiv (bivalent temperature)

COPd 1.50 1.42

Pdh kW 8.4 8.9

PERd % 60.0 56.8

Tbiv °C -15

Rated heat output supplementary capacity

Psup (at Tdesign -22°C)

kW 4.6 4.9

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Warm climate water outlet 55°C

General Annual energy consumption

kWh 3,282 3,429

ηs (Seasonal space heating efficiency)

% 153 154

Prated at 2°C

kW 10

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 1.90 1.78

Pdh kW 9.8 10.3

PERd % 76.0 71.2

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 3.22 3.25

Pdh kW 6.3 6.6

PERd % 128.8 130.0

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 5.88

Pdh kW 5.4

PERd % 235.2

Tbiv (bivalent temperature)

COPd 1.90 1.78

Pdh kW 9.8 10.3

PERd % 76.0 71.2

Tbiv °C 2

Average climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Cold climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Qhe Annual energy consumption (GCV)

Gj -

Warm climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 55

• Outdoor Unit • ERLQ-CV3

2

56

2 Specifications

Notes

(1) EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB

(2) EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB

(3) EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB

(4) EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB

(5) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)

(6) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )

(7) Tamb 35°C - LWE 18°C (DT=5°C)

(8) Tamb 35°C - LWE 7°C (DT=5°C)

(9) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)

(10) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)

Domestic hot water heating

General Declared load profile XL

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 2,158

ηwh (water heating efficiency)

% 84

Qelec (Daily electricity consumption)

kWh 9.681

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 2,394

ηwh (water heating efficiency)

% 76

Qelec (Daily electricity consumption)

kWh 10.755

Warm climate AEC (Annual electricity consumption)

kWh 1,921

ηwh (water heating efficiency)

% 95

Qelec (Daily electricity consumption)

kWh 8.600

CONNECTABLE INDOOR UNITS

2-12 Capacity and Power inputEHSH04P30B/ERLQ004CV3

EHSH08P30B/ERLQ006CV3

EHSH08P50B/ERLQ006CV3

EHSH08P30B/ERLQ008CV3

EHSH08P50B/ERLQ008CV3

EHSH16P50B/ERLQ011CV3

Indoor unit EHSH04P30BA

EHSH08P30BA

EHSH08P50BA

EHSH08P30BA

EHSH08P50BA

EHSH16P50BA

Outdoor unit ERLQ004CAV3

ERLQ006CAV3 ERLQ008CAV3 ERLQ011CAV3

Heating capacity Min. kW 1.80 (1) / 1.81 (2) -

Nom. kW 4.26 (3) / 3.47 (4) / 4.53 (1) /

3.98 (2)

5.14 (3) / 4.60 (4) / 6.06 (1) / 5.78 (2)

5.53 (3) / 5.51 (4) / 7.78 (1) / 7.27 (2)

5.95 (1) / 7.74 (2) / 11.80 (3) /

10.40 (4)

Max. kW 4.90 (1) / 5.12 (2)

8.35 (1) / 7.95 (2) 10.02 (1) / 9.53 (2) 11.38 (3) / 11.00 (4)

Power input Heating Nom. kW 0.87 (5) / 1.04 (6) / 1.49 (3) /

0.85 (4)

1.30 (5) / 1.58 (6) / 1.88 (3) / 1.26 (4)

1.69 (5) / 2.04 (6) / 1.98 (3) / 1.56 (4)

2.57 (5) / 3.13 (6) / 2.43 (1) /

2.35 (2)

Max. kW 1.12 (5) / 1.44 (6)

1.99 (5) / 2.32 (6) 2.54 (5) / 2.96 (6) 2.64 (5) / 3.25 (6)

COP 5.23 (5) / 3.84 (6) / 2.85 (3) /

4.07 (4)

4.65 (5) / 3.66 (6) / 2.73 (3) / 3.64 (4)

4.60 (5) / 3.57 (6) / 2.78 (3) / 3.54 (4)

4.38 (5) / 3.32 (6) / 2.45 (1) /

3.29 (2)

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Pump Type Grundfos UPM3 25-75 CHBL

Nominal ESP unit Heating kPa 46.0 (7) / 48.0 (8)

40.0 (7) / 41.0 (8) 37.0 (7) / 36.0 (8) -

Water side Heat exchanger

Water flow rate Heating Nom. l/min 13.0 (7) / 11.3 (8)

17.4 (7) / 16.6 (8) 22.3 (7) / 20.8 (8) 33.8 (7) / 29.8 (8)

General Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater

Yes

Low-temperature heat pump No

Supplementary heater integrated

No

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 39

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 61 62 64

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 2,700 2,820 -

Other Capacity control Inverter

Cdh (Degradation heating) 0.9

Pck (Crankcase heater mode)

kW 0.000

Poff (Off mode) kW 0.011 0.012 0.050

Psb (Standby mode)

kW 0.011 0.012 0.050

Pto (Thermostat off) kW 0.043 0.048 0.105

Integrated supplementary heater

Psup kW 9.0

Type of energy input Electrical

Space heating Average climate water outlet 55°C

General Annual energy consumption

kWh 2,934 3,828 4,725 6,345

ηs (Seasonal space heating efficiency)

% 130 125 127 125

Prated at -10°C

kW 5 6 8 10

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.03 2.09 2.10 1.94

Pdh kW 4.2 5.3 5.4 9.0

PERd % 81.2 83.6 84.0 77.6

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.31 3.13 3.25 3.30

Pdh kW 2.6 3.1 3.9 5.4

PERd % 132.4 125.2 130.0 132.0

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 57

• Outdoor Unit • ERLQ-CV3

2

58

2 Specifications

Space heating Average climate water outlet 55°C

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0 0.9

COPd 4.43 4.09 4.42 4.26

Pdh kW 1.8 2.1 2.6 4.6

PERd % 177.2 163.6 176.8 170.4

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 6.55 5.99 6.30

Pdh kW 2.2 2.0 5.5

PERd % 262.0 239.6 252.0

Tol (temperature operating limit)

COPd 1.64 1.79 1.78

Pdh kW 4.1 5.1 9.1

PERd % 65.6 71.6 71.2

TOL °C -10

WTOL °C 55

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.7 0.9 2.4 1.0

Tbiv (bivalent temperature)

COPd 2.03 2.09 2.36 1.94

Pdh kW 4.2 5.3 5.8 9.0

PERd % 81.2 83.6 94.4 77.6

Tbiv °C -7 -4 -7

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 3,069 4,008 4,575 8,185

ηs (Seasonal space heating efficiency)

% 109 103 109 100

Prated at -22°C

kW 4 5 9

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.30 2.47 2.41 1.98

Pdh kW 2.2 2.6 3.2 5.2

PERd % 92.0 98.8 96.4 79.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0 0.9 1.0

COPd 3.75 3.26 3.69 3.25

Pdh kW 1.4 2.0 2.4 3.2

PERd % 150.0 130.4 147.6 130.0

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.9

COPd 5.92 4.42 5.58 5.50

Pdh kW 1.6 2.6 3.2 5.2

PERd % 236.8 176.8 223.2 220.0

D Condition (12°CDB/11°CWB)

COPd 8.65 5.54 7.79 7.56

Pdh kW 1.6 3.0 3.6 6.1

PERd % 346.0 221.6 311.6 302.4

Tol (temperature operating limit)

COPd 0.89 1.05 0.98 1.22

Pdh kW 0.8 1.0 1.2 5.7

PERd % 35.6 42.0 39.2 48.8

TOL °C -20

WTOL °C 55 1 55

G Condition (-15°CDB/-)

COPd 1.25 1.42 1.33 1.51

Pdh kW 2.9 3.6 4.3 7.1

PERd % 50.0 56.8 53.2 60.4

Tbiv (bivalent temperature)

COPd 1.25 1.42 1.33 1.51

Pdh kW 2.9 3.6 4.3 7.1

PERd % 50.0 56.8 53.2 60.4

Tbiv °C -15

Rated heat output supplementary capacity

Psup (at Tdesign -22°C)

kW 3.5 4.4 5.2 3.4

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 59

• Outdoor Unit • ERLQ-CV3

2

60

2 Specifications

Space heating Warm climate water outlet 55°C

General Annual energy consumption

kWh 1,174 1,901 1,932 2,637

ηs (Seasonal space heating efficiency)

% 179 145 171 135

Prated at 2°C

kW 4 5 7 8

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 2.11 2.29 2.15 1.82

Pdh kW 4.3 5.5 6.6 7.6

PERd % 84.4 91.6 86.0 72.8

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 3.76 3.41 3.70 3.07

Pdh kW 2.8 3.5 4.2 4.9

PERd % 150.4 136.4 148.0 122.8

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 7.26 4.86 6.52 5.88

Pdh kW 1.6 2.9 3.5 5.4

PERd % 290.4 194.4 260.8 235.2

Tbiv (bivalent temperature)

COPd 2.11 2.29 2.15 1.82

Pdh kW 4.3 5.5 6.6 7.6

PERd % 84.4 91.6 86.0 72.8

Tbiv °C 2

Average climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Cold climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Qhe Annual energy consumption (GCV)

Gj -

Warm climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Domestic hot water heating

General Declared load profile L XL L XL

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 1,063 1,148 1,747 1,256 1,866 2,187

ηwh (water heating efficiency)

% 103 98 102 90 96 83

Qelec (Daily electricity consumption)

kWh 4.753 5.138 7.866 5.630 8.409 9.811

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 1,221 1,263 1,954 1,387 2,104 2,435

ηwh (water heating efficiency)

% 92 89 91 80 84 74

Qelec (Daily electricity consumption)

kWh 5.473 5.653 9.000 6.226 9.496 10.938

Warm climate AEC (Annual electricity consumption)

kWh 948 1,068 1,559 1,138 1,727 1,956

ηwh (water heating efficiency)

% 120 107 115 100 104 93

Qelec (Daily electricity consumption)

kWh 4.229 4.763 7.014 5.091 8.000 8.760

CONNECTABLE INDOOR UNITS

2-13 Capacity and Power input EHSH16P50B/ERLQ014CV3 EHSH16P50B/ERLQ016CV3

Indoor unit EHSH16P50BA

Outdoor unit ERLQ014CAV3 ERLQ016CAV3

Heating capacity Nom. kW 8.28 / 9.57 / 14.81 / 13.73 15.34 / 14.86 / 8.04 / 10.05

Max. kW 14.55 / 13.59 16.10 / 15.22

Power input Heating Nom. kW 3.42 / 4.07 / 3.17 / 2.93 3.42 / 4.07 / 3.17 / 2.93

Max. kW 3.43 / 4.22 3.83 / 4.71

COP 4.27 / 3.34 / 2.58 / 3.22 4.10 / 3.22 / 2.44 / 3.15

Pump Type Grundfos UPM3 25-75 CHBL

Water side Heat exchanger

Water flow rate Heating Nom. l/min 42.4 / 39.4 44.0 / 42.6

General Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated

No

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 39

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 64 66

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 61

• Outdoor Unit • ERLQ-CV3

2

62

2 Specifications

Space heating general Other Capacity control Inverter

Cdh (Degradation heating) 0.9

Pck (Crankcase heater mode)

kW 0.000

Poff (Off mode) kW 0.050

Psb (Standby mode) kW 0.050

Pto (Thermostat off) kW 0.105

Integrated supplementary heater

Psup kW 9.0

Type of energy input Electrical

Space heating Average climate water outlet 55°C

General Annual energy consumption

kWh 7,654 8,978

ηs (Seasonal space heating efficiency)

% 126 125

Prated at -10°C

kW 12 14

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 1.92 1.85

Pdh kW 10.9 12.6

PERd % 76.8 74.0

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.30 3.19

Pdh kW 6.6 7.8

PERd % 132.0 127.6

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 4.34 4.47

Pdh kW 4.6 4.9

PERd % 173.6 178.8

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 6.45 6.52

Pdh kW 5.5 5.4

PERd % 258.0 260.8

Tol (temperature operating limit)

COPd 1.63 1.57

Pdh kW 9.8 11.2

PERd % 65.2 62.8

TOL °C -10

WTOL °C 55

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 2.5 3.0

Tbiv (bivalent temperature)

COPd 1.92 1.84

Pdh kW 10.9 12.6

PERd % 76.8 73.6

Tbiv °C -7

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 9,676 10,405

ηs (Seasonal space heating efficiency)

% 100

Prated at -22°C

kW 10 11

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.04 2.05

Pdh kW 6.2 6.6

PERd % 81.6 82.0

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.20 3.19

Pdh kW 3.8 4.0

PERd % 128.0 127.6

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.9

COPd 5.50

Pdh kW 5.2

PERd % 220.0

D Condition (12°CDB/11°CWB)

COPd 7.56

Pdh kW 6.1

PERd % 302.4

Tol (temperature operating limit)

COPd 1.13 1.08

Pdh kW 6.4 6.8

PERd % 45.2 43.2

TOL °C -20

WTOL °C 55

G Condition (-15°CDB/-)

COPd 1.50 1.42

Pdh kW 8.4 8.9

PERd % 60.0 56.8

Tbiv (bivalent temperature)

COPd 1.50 1.42

Pdh kW 8.4 8.9

PERd % 60.0 56.8

Tbiv °C -15

Rated heat output supplementary capacity

Psup (at Tdesign -22°C)

kW 4.6 4.9

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 63

• Outdoor Unit • ERLQ-CV3

2

64

2 Specifications

Space heating Warm climate water outlet 55°C

General Annual energy consumption

kWh 3,282 3,429

ηs (Seasonal space heating efficiency)

% 144 145

Prated at 2°C

kW 10

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 1.90 1.78

Pdh kW 9.8 10.3

PERd % 76.0 71.2

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 3.22 3.25

Pdh kW 6.3 6.6

PERd % 128.8 130.0

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 5.88

Pdh kW 5.4

PERd % 235.2

Tbiv (bivalent temperature)

COPd 1.90 1.78

Pdh kW 9.8 10.3

PERd % 76.0 71.2

Tbiv °C 2

Average climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Cold climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Qhe Annual energy consumption (GCV)

Gj -

Warm climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Notes

(1) EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB

(2) EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB

(3) EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB

(4) EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB

(5) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)

(6) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )

(7) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)

(8) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)

Domestic hot water heating

General Declared load profile XL

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 2,187

ηwh (water heating efficiency)

% 83

Qelec (Daily electricity consumption)

kWh 9.811

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 2,435

ηwh (water heating efficiency)

% 74

Qelec (Daily electricity consumption)

kWh 10.938

Warm climate AEC (Annual electricity consumption)

kWh 1,956

ηwh (water heating efficiency)

% 93

Qelec (Daily electricity consumption)

kWh 8.760

CONNECTABLE INDOOR UNITS

2-14 Capacity and Power inputEHSX04P30B/ERLQ004CV3

EHSX08P50B/ERLQ006CV3

EHSX08P30B/ERLQ006CV3

EHSX08P30B/ERLQ008CV3

EHSX08P50B/ERLQ008CV3

EHSX16P50B/ERLQ011CV3

Indoor unit EHSX04P30BA

EHSX08P50BA

EHSX08P30BA EHSX08P50BA

EHSX16P50BA

Outdoor unit ERLQ004CAV3

ERLQ006CAV3 ERLQ008CAV3 ERLQ011CAV3

Heating capacity Min. kW 1.80 (1) / 1.81 (2) -

Nom. kW 4.26 (3) / 3.47 (4) / 4.53 (1) /

3.98 (2)

5.14 (3) / 4.60 (4) / 6.06 (1) / 5.78 (2)

5.53 (3) / 5.51 (4) / 7.78 (1) / 7.27 (2)

5.95 (1) / 7.74 (2) / 11.80 (3) /

10.40 (4)

Max. kW 4.90 (1) / 5.12 (2)

8.35 (1) / 7.95 (2) 10.02 (1) / 9.53 (2) 11.38 (3) / 11.00 (4)

Cooling capacity Min. kW 2.0 (5) / 2.1 (6) 2.5 (5) / 2.6 (6)

Nom. kW 4.4 (5) / 4.0 (6) 5.2 (5) / 4.6 (6) 15.1 (5) / 11.7 (6)

Max. kW 5.9 (5) / 4.5 (6) 7.3 (5) / 5.5 (6) 8.4 (5) / 6.4 (6) 15.1 (5) / 11.7 (6)

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 65

• Outdoor Unit • ERLQ-CV3

2

66

2 Specifications

Power input Heating Nom. kW 0.87 (5) / 1.04 (6) / 1.49 (3) /

0.85 (4)

1.30 (5) / 1.58 (6) / 1.88 (3) / 1.26 (4)

1.69 (5) / 2.04 (6) / 1.98 (3) / 1.56 (4)

2.57 (5) / 3.13 (6) / 2.43 (1) /

2.35 (2)

Max. kW 1.12 (5) / 1.44 (6)

1.99 (5) / 2.32 (6) 2.54 (5) / 2.96 (6) 2.64 (5) / 3.25 (6)

Cooling Nom. kW 1.05 (5) / 1.41 (6)

1.43 (5) / 1.85 (6) 4.55 (5) / 4.30 (6)

Max. kW 1.86 (5) / 2.04 (6)

2.27 (5) / 2.51 (6) 2.89 (5) / 3.20 (6) 4.53 (5) / 4.31 (6)

COP 5.23 (5) / 3.84 (6) / 2.85 (3) /

4.07 (4)

4.65 (5) / 3.66 (6) / 2.73 (3) / 3.64 (4)

4.60 (5) / 3.57 (6) / 2.78 (3) / 3.54 (4)

4.38 (5) / 3.32 (6) / 2.45 (1) /

3.29 (2)

EER 4.21 (5) / 2.85 (6)

3.65 (5) / 2.51 (6) 3.32 (5) / 2.72 (6)

Pump Type Grundfos UPM3 25-75 CHBL

Nominal ESP unit Cooling kPa 45.0 (7) / 48.0 (8)

- 44.0 (7) / 46.0 (8) -

Heating kPa 46.0 (9) / 48.0 (10)

40.0 (7) / 41.0 (8)

40.0 (9) / 41.0 (10)

37.0 (9) / 36.0 (10) -

Water side Heat exchanger

Water flow rate Cooling Nom. l/min 12.7 (7) / 11.5 (8)

- 12.9 (7) / 13.3 (8) 43.3 (7) / 33.5 (8)

Heating Nom. l/min 13.0 (9) / 11.3 (10)

17.4 (7) / 16.6 (8)

17.4 (9) / 16.6 (10)

22.3 (9) / 20.8 (10) 33.8 (9) / 29.8 (10)

General Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated

No

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 39

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 61 62 64

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 2,700 2,820 -

Other Capacity control Inverter

Cdh (Degradation heating) 0.9

Pck (Crankcase heater mode)

kW 0.000

Poff (Off mode) kW 0.011 0.012 0.050

Psb (Standby mode) kW 0.011 0.012 0.050

Pto (Thermostat off) kW 0.043 0.048 0.105

Integrated supplementary heater

Psup kW 9.0

Type of energy input Electrical

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 55°C

General Annual energy consumption

kWh 2,934 3,828 4,725 6,345

ηs (Seasonal space heating efficiency)

% 132 126 128

Prated at -10°C

kW 5 6 8 10

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.03 2.09 2.10 1.94

Pdh kW 4.2 5.3 5.4 9.0

PERd % 81.2 83.6 84.0 77.6

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.31 3.13 3.25 3.30

Pdh kW 2.6 3.1 3.9 5.4

PERd % 132.4 125.2 130.0 132.0

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0 0.9

COPd 4.43 4.09 4.42 4.26

Pdh kW 1.8 2.1 2.6 4.6

PERd % 177.2 163.6 176.8 170.4

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 6.55 5.99 6.30

Pdh kW 2.2 2.0 5.5

PERd % 262.0 239.6 252.0

Tol (temperature operating limit)

COPd 1.64 1.79 1.78

Pdh kW 4.1 5.1 9.1

PERd % 65.6 71.6 71.2

TOL °C -10

WTOL °C 55

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.7 0.9 2.4 1.0

Tbiv (bivalent temperature)

COPd 2.03 2.09 2.36 1.94

Pdh kW 4.2 5.3 5.8 9.0

PERd % 81.2 83.6 94.4 77.6

Tbiv °C -7 -4 -7

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 67

• Outdoor Unit • ERLQ-CV3

2

68

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 3,069 4,008 4,575 8,185

ηs (Seasonal space heating efficiency)

% 110 103 104 109 100

Prated at -22°C

kW 4 5 9

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.30 2.47 2.41 1.98

Pdh kW 2.2 2.6 3.2 5.2

PERd % 92.0 98.8 96.4 79.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0 0.9 1.0

COPd 3.75 3.26 3.69 3.25

Pdh kW 1.4 2.0 2.4 3.2

PERd % 150.0 130.4 147.6 130.0

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.9

COPd 5.92 4.42 5.58 5.50

Pdh kW 1.6 2.6 3.2 5.2

PERd % 236.8 176.8 223.2 220.0

D Condition (12°CDB/11°CWB)

COPd 8.65 5.54 7.79 7.56

Pdh kW 1.6 3.0 3.6 6.1

PERd % 346.0 221.6 311.6 302.4

Tol (temperature operating limit)

COPd 0.89 1.05 0.98 1.22

Pdh kW 0.8 1.0 1.2 5.7

PERd % 35.6 42.0 39.2 48.8

TOL °C -20

WTOL °C 55

G Condition (-15°CDB/-)

COPd 1.25 1.42 1.33 1.51

Pdh kW 2.9 3.6 4.3 7.1

PERd % 50.0 56.8 53.2 60.4

Tbiv (bivalent temperature)

COPd 1.25 1.42 1.33 1.51

Pdh kW 2.9 3.6 4.3 7.1

PERd % 50.0 56.8 53.2 60.4

Tbiv °C -15

Rated heat output supplementary capacity

Psup (at Tdesign -22°C)

kW 3.5 4.4 5.2 3.4

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Warm climate water outlet 55°C

General Annual energy consumption

kWh 1,174 1,901 1,932 2,637

ηs (Seasonal space heating efficiency)

% 186 145 149 176 135

Prated at 2°C

kW 4 5 7 8

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 2.11 2.29 2.15 1.82

Pdh kW 4.3 5.5 6.6 7.6

PERd % 84.4 91.6 86.0 72.8

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 3.76 3.41 3.70 3.07

Pdh kW 2.8 3.5 4.2 4.9

PERd % 150.4 136.4 148.0 122.8

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 7.26 4.86 6.52 5.88

Pdh kW 1.6 2.9 3.5 5.4

PERd % 290.4 194.4 260.8 235.2

Tbiv (bivalent temperature)

COPd 2.11 2.29 2.15 1.82

Pdh kW 4.3 5.5 6.6 7.6

PERd % 84.4 91.6 86.0 72.8

Tbiv °C 2

Average climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Cold climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Qhe Annual energy consumption (GCV)

Gj -

Warm climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 69

• Outdoor Unit • ERLQ-CV3

2

70

2 Specifications

Domestic hot water heating

General Declared load profile L XL L XL

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 1,063 1,747 1,148 1,256 1,866 2,187

ηwh (water heating efficiency)

% 103 102 98 90 96 83

Qelec (Daily electricity consumption)

kWh 4.753 7.866 5.138 5.630 8.409 9.811

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 1,221 1,954 1,263 1,387 2,104 2,435

ηwh (water heating efficiency)

% 92 91 89 80 84 74

Qelec (Daily electricity consumption)

kWh 5.473 9.000 5.653 6.226 9.496 10.938

Warm climate AEC (Annual electricity consumption)

kWh 948 1,559 1,068 1,138 1,727 1,956

ηwh (water heating efficiency)

% 120 115 107 100 104 93

Qelec (Daily electricity consumption)

kWh 4.229 7.014 4.763 5.091 8.000 8.760

CONNECTABLE INDOOR UNITS

2-15 Capacity and Power input EHSX16P50B/ERLQ014CV3 EHSH16P50B/ERLQ016CV3

Indoor unit EHSX16P50BA

Outdoor unit ERLQ014CAV3 ERLQ016CAV3

Heating capacity Nom. kW 14.81 / 13.73 / 8.28 / 9.57 15.34 / 14.86 / 8.04 / 10.05

Max. kW 14.55 / 13.59 16.10 / 15.22

Cooling capacity Min. kW 2.5 / 2.6 -

Nom. kW 16.1 / 12.6 16.8 / 13.1

Max. kW 16.1 / 12.6 16.8 / 13.1

Power input Heating Nom. kW 3.42 / 4.07 / 3.17 / 2.93

Max. kW 3.43 / 4.22 3.83 / 4.71

Cooling Nom. kW 5.44 / 5.10 6.18 / 5.72

Max. kW 5.42 / 5.09 6.15 / 5.74

COP 4.27 / 3.34 / 2.58 / 3.22 4.10 / 3.22 / 2.44 / 3.15

EER 2.96 / 2.47 2.72 / 2.29

Pump Type Grundfos UPM3 25-75 CHBL

Water side Heat exchanger

Water flow rate Cooling Nom. l/min 46.0 / 36.1 48.1 / 37.5

Heating Nom. l/min 42.4 / 39.4 44.0 / 42.6

General Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated No

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 39

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 64 66

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating general Other Capacity control Inverter

Cdh (Degradation heating) 0.9

Pck (Crankcase heater mode)

kW 0.000

Poff (Off mode) kW 0.050

Psb (Standby mode) kW 0.050

Pto (Thermostat off) kW 0.105

Integrated supplementary heater

Psup kW 9.0

Type of energy input Electrical

Space heating Average climate water outlet 55°C

General Annual energy consumption

kWh 7,654 8,978

ηs (Seasonal space heating efficiency)

% 130 127

Prated at -10°C

kW 12 14

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 1.92 1.85

Pdh kW 10.9 12.6

PERd % 76.8 74.0

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.30 3.19

Pdh kW 6.6 7.8

PERd % 132.0 127.6

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 4.34 4.47

Pdh kW 4.6 4.9

PERd % 173.6 178.8

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 6.45 6.52

Pdh kW 5.5 5.4

PERd % 258.0 260.8

Tol (temperature operating limit)

COPd 1.63 1.57

Pdh kW 9.8 11.2

PERd % 65.2 62.8

TOL °C -10

WTOL °C 55

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 2.5 3.0

Tbiv (bivalent temperature)

COPd 1.92 1.84

Pdh kW 10.9 12.6

PERd % 76.8 73.6

Tbiv °C -7

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 71

• Outdoor Unit • ERLQ-CV3

2

72

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 9,676 10,405

ηs (Seasonal space heating efficiency)

% 101

Prated at -22°C

kW 10 11

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.04 2.05

Pdh kW 6.2 6.6

PERd % 81.6 82.0

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.20 3.19

Pdh kW 3.8 4.0

PERd % 128.0 127.6

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.9

COPd 5.50

Pdh kW 5.2

PERd % 220.0

D Condition (12°CDB/11°CWB)

COPd 7.56

Pdh kW 6.1

PERd % 302.4

Tol (temperature operating limit)

COPd 1.13 1.08

Pdh kW 6.4 6.8

PERd % 45.2 43.2

TOL °C -20

WTOL °C 55

G Condition (-15°CDB/-)

COPd 1.50 1.42

Pdh kW 8.4 8.9

PERd % 60.0 56.8

Tbiv (bivalent temperature)

COPd 1.50 1.42

Pdh kW 8.4 8.9

PERd % 60.0 56.8

Tbiv °C -15

Rated heat output supplementary capacity

Psup (at Tdesign -22°C)

kW 4.6 4.9

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Warm climate water outlet 55°C

General Annual energy consumption

kWh 3,282 3,429

ηs (Seasonal space heating efficiency)

% 153 154

Prated at 2°C

kW 10

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 1.90 1.78

Pdh kW 9.8 10.3

PERd % 76.0 71.2

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 3.22 3.25

Pdh kW 6.3 6.6

PERd % 128.8 130.0

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 5.88

Pdh kW 5.4

PERd % 235.2

Tbiv (bivalent temperature)

COPd 1.90 1.78

Pdh kW 9.8 10.3

PERd % 76.0 71.2

Tbiv °C 2

Average climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Cold climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Qhe Annual energy consumption (GCV)

Gj -

Warm climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 73

• Outdoor Unit • ERLQ-CV3

2

74

2 Specifications

Notes

(1) EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB

(2) EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB

(3) EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB

(4) EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB

(5) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)

(6) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )

(7) Tamb 35°C - LWE 18°C (DT=5°C)

(8) Tamb 35°C - LWE 7°C (DT=5°C)

(9) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)

(10) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)

Domestic hot water heating

General Declared load profile XL

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 2,187

ηwh (water heating efficiency)

% 83

Qelec (Daily electricity consumption)

kWh 9.811

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 2,435

ηwh (water heating efficiency)

% 74

Qelec (Daily electricity consumption)

kWh 10.938

Warm climate AEC (Annual electricity consumption)

kWh 1,956

ηwh (water heating efficiency)

% 93

Qelec (Daily electricity consumption)

kWh 8.760

CONNECTABLE INDOOR UNITS

2-16 Capacity and Power inputEHSHB04P30B/ERLQ004CV3

EHSHB08P30B/ERLQ006CV3

EHSHB08P50B/ERLQ006CV3

EHSHB08P30B/ERLQ008CV3

EHSHB08P50B/ERLQ008CV3

EHSHB16P50B/ERLQ011CV3

Indoor unit EHSHB04P30BA

EHSHB08P30BA

EHSHB08P50BA

EHSHB08P30BA

EHSHB08P50BA

EHSHB16P50BA

Outdoor unit ERLQ004CAV3

ERLQ006CAV3 ERLQ008CAV3 ERLQ011CAV3

Heating capacity Min. kW 1.80 (1) / 1.81 (2) -

Nom. kW 4.26 (3) / 3.47 (4) / 4.53 (1) /

3.98 (2)

5.14 (3) / 4.60 (4) / 6.06 (1) / 5.78 (2)

5.53 (3) / 5.51 (4) / 7.78 (1) / 7.27 (2)

5.95 (1) / 7.74 (2) / 11.80 (3) /

10.40 (4)

Max. kW 4.90 (1) / 5.12 (2)

8.35 (1) / 7.95 (2) 10.02 (1) / 9.53 (2) 11.38 (3) / 11.00 (4)

Power input Heating Nom. kW 0.87 (5) / 1.04 (6) / 1.49 (3) /

0.85 (4)

1.30 (5) / 1.58 (6) / 1.88 (3) / 1.26 (4)

1.69 (5) / 2.04 (6) / 1.98 (3) / 1.56 (4)

2.57 (5) / 3.13 (6) / 2.43 (1) /

2.35 (2)

Max. kW 1.12 (5) / 1.44 (6)

1.99 (5) / 2.32 (6) 2.54 (5) / 2.96 (6) 2.64 (5) / 3.25 (6)

COP 5.23 (5) / 3.84 (6) / 2.85 (3) /

4.07 (4)

4.65 (5) / 3.66 (6) / 2.73 (3) / 3.64 (4)

4.60 (5) / 3.57 (6) / 2.78 (3) / 3.54 (4)

4.38 (5) / 3.32 (6) / 2.45 (1) /

3.29 (2)

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Pump Type Grundfos UPM3 25-75 CHBL

Nominal ESP unit Heating kPa 46.0 (7) / 48.0 (8)

40.0 (7) / 41.0 (8) 37.0 (7) / 36.0 (8) -

Water side Heat exchanger

Water flow rate Heating Nom. l/min 13.0 (7) / 11.3 (8)

17.4 (7) / 16.6 (8) 22.3 (7) / 20.8 (8) 33.8 (7) / 29.8 (8)

General Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated No

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 39

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 61 62 64

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor)

m³/h 2,700 2,820 -

Other Capacity control Inverter

Cdh (Degradation heating) 0.9

Pck (Crankcase heater mode)

kW 0.000

Poff (Off mode) kW 0.011 0.012 0.050

Psb (Standby mode) kW 0.011 0.012 0.050

Pto (Thermostat off) kW 0.043 0.048 0.105

Integrated supplementary heater

Psup kW 9.0

Type of energy input Electrical

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 75

• Outdoor Unit • ERLQ-CV3

2

76

2 Specifications

Space heating Average climate water outlet 55°C

General Annual energy consumption

kWh 2,934 3,828 4,725 6,345

ηs (Seasonal space heating efficiency)

% 130 125 127 125

Prated at -10°C

kW 5 6 8 10

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.03 2.09 2.10 1.94

Pdh kW 4.2 5.3 5.4 9.0

PERd % 81.2 83.6 84.0 77.6

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.31 3.13 3.25 3.30

Pdh kW 2.6 3.1 3.9 5.4

PERd % 132.4 125.2 130.0 132.0

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0 0.9

COPd 4.43 4.09 4.42 4.26

Pdh kW 1.8 2.1 2.6 4.6

PERd % 177.2 163.6 176.8 170.4

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 6.55 5.99 6.30

Pdh kW 2.2 2.0 5.5

PERd % 262.0 239.6 252.0

Tol (temperature operating limit)

COPd 1.64 1.79 1.78

Pdh kW 4.1 5.1 9.1

PERd % 65.6 71.6 71.2

TOL °C -10

WTOL °C 55

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.7 0.9 2.4 1.0

Tbiv (bivalent temperature)

COPd 2.03 2.09 2.36 1.94

Pdh kW 4.2 5.3 5.8 9.0

PERd % 81.2 83.6 94.4 77.6

Tbiv °C -7 -4 -7

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 3,069 4,008 4,575 8,185

ηs (Seasonal space heating efficiency)

% 109 103 109 101

Prated at -22°C

kW 4 5 9

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.30 2.47 2.41 1.98

Pdh kW 2.2 2.6 3.2 5.2

PERd % 92.0 98.8 96.4 79.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0 0.9 1.0

COPd 3.75 3.26 3.69 3.25

Pdh kW 1.4 2.0 2.4 3.2

PERd % 150.0 130.4 147.6 130.0

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.9

COPd 5.92 4.42 5.58 5.50

Pdh kW 1.6 2.6 3.2 5.2

PERd % 236.8 176.8 223.2 220.0

D Condition (12°CDB/11°CWB)

COPd 8.65 5.54 7.79 7.56

Pdh kW 1.6 3.0 3.6 6.1

PERd % 346.0 221.6 311.6 302.4

Tol (temperature operating limit)

COPd 0.89 1.05 0.98 1.22

Pdh kW 0.8 1.0 1.2 5.7

PERd % 35.6 42.0 39.2 48.8

TOL °C -20

WTOL °C 55

G Condition (-15°CDB/-)

COPd 1.25 1.42 1.33 1.51

Pdh kW 2.9 3.6 4.3 7.1

PERd % 50.0 56.8 53.2 60.4

Tbiv (bivalent temperature)

COPd 1.25 1.42 1.33 1.51

Pdh kW 2.9 3.6 4.3 7.1

PERd % 50.0 56.8 53.2 60.4

Tbiv °C -15

Rated heat output supplementary capacity

Psup (at Tdesign -22°C)

kW 3.5 4.4 5.2 3.4

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 77

• Outdoor Unit • ERLQ-CV3

2

78

2 Specifications

Space heating Warm climate water outlet 55°C

General Annual energy consumption

kWh 1,174 1,901 1,932 2,637

ηs (Seasonal space heating efficiency)

% 179 145 171 146

Prated at 2°C

kW 4 5 7 8

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 2.11 2.29 2.15 1.82

Pdh kW 4.3 5.5 6.6 7.6

PERd % 84.4 91.6 86.0 72.8

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 3.76 3.41 3.70 3.07

Pdh kW 2.8 3.5 4.2 4.9

PERd % 150.4 136.4 148.0 122.8

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 7.26 4.86 6.52 5.88

Pdh kW 1.6 2.9 3.5 5.4

PERd % 290.4 194.4 260.8 235.2

Tbiv (bivalent temperature)

COPd 2.11 2.29 2.15 1.82

Pdh kW 4.3 5.5 6.6 7.6

PERd % 84.4 91.6 86.0 72.8

Tbiv °C 2

Average climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Cold climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Qhe Annual energy consumption (GCV)

Gj -

Warm climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Domestic hot water heating

General Declared load profile L XL L XL

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 1,063 1,148 1,654 1,256 1,797 2,158

ηwh (water heating efficiency)

% 103 98 108 90 99 84

Qelec (Daily electricity consumption)

kWh 4.753 5.138 7.453 5.630 8.105 9.681

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 1,221 1,263 1,858 1,387 2,200 2,394

ηwh (water heating efficiency)

% 92 89 95 80 76

Qelec (Daily electricity consumption)

kWh 5.473 5.653 8.379 6.226 10.000 10.755

Warm climate AEC (Annual electricity consumption)

kWh 948 1,068 1,510 1,138 1,696 1,921

ηwh (water heating efficiency)

% 120 107 117 100 106 95

Qelec (Daily electricity consumption)

kWh 4.229 4.763 6.796 5.091 8.000 8.600

CONNECTABLE INDOOR UNITS

2-17 Capacity and Power input EHSHB16P50B/ERLQ014CV3 EHSHB16P50B/ERLQ016CV3

Indoor unit EHSHB16P50BA

Outdoor unit ERLQ014CAV3 ERLQ016CAV3

Heating capacity Nom. kW 14.81 / 13.73 / 8.28 / 9.57 15.34 / 14.86 / 8.04 / 10.05

Max. kW 14.55 / 13.59 16.10 / 15.22

Power input Heating Nom. kW 3.42 / 4.07 / 3.17 / 2.93

Max. kW 3.43 / 4.22 3.83 / 4.71

COP 4.27 / 3.34 / 2.58 / 3.22 4.10 / 3.22 / 2.44 / 3.15

Pump Type Grundfos UPM3 25-75 CHBL

Water side Heat exchanger

Water flow rate Heating Nom. l/min 42.4 / 39.4 44.0 / 42.6

General Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated No

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 39

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 64 66

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Other Capacity control Inverter

Cdh (Degradation heating) 0.9

Pck (Crankcase heater mode)

kW 0.000

Poff (Off mode) kW 0.050

Psb (Standby mode) kW 0.050

Pto (Thermostat off) kW 0.105

Integrated supplementary heater

Psup kW 9.0

Type of energy input Electrical

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 79

• Outdoor Unit • ERLQ-CV3

2

80

2 Specifications

Space heating Average climate water outlet 55°C

General Annual energy consumption

kWh 7,654 8,978

ηs (Seasonal space heating efficiency)

% 126 125

Prated at -10°C

kW 12 14

Seasonal space heating eff. class

A++

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 1.92 1.85

Pdh kW 10.9 12.6

PERd % 76.8 74.0

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.30 3.19

Pdh kW 6.6 7.8

PERd % 132.0 127.6

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 4.34 4.47

Pdh kW 4.6 4.9

PERd % 173.6 178.8

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 6.45 6.52

Pdh kW 5.5 5.4

PERd % 258.0 260.8

Tol (temperature operating limit)

COPd 1.63 1.57

Pdh kW 9.8 11.2

PERd % 65.2 62.8

TOL °C -10

WTOL °C 55

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 2.5 3.0

Tbiv (bivalent temperature)

COPd 1.92 1.84

Pdh kW 10.9 12.6

PERd % 76.8 73.6

Tbiv °C -7

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 9,676 10,405

ηs (Seasonal space heating efficiency)

% 100

Prated at -22°C

kW 10 11

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.0

COPd 2.04 2.05

Pdh kW 6.2 6.6

PERd % 81.6 82.0

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 3.20 3.19

Pdh kW 3.8 4.0

PERd % 128.0 127.6

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.9

COPd 5.50

Pdh kW 5.2

PERd % 220.0

D Condition (12°CDB/11°CWB)

COPd 7.56

Pdh kW 6.1

PERd % 302.4

Tol (temperature operating limit)

COPd 1.13 1.08

Pdh kW 6.4 6.8

PERd % 45.2 43.2

TOL °C -20

WTOL °C 55

G Condition (-15°CDB/-)

COPd 1.50 1.42

Pdh kW 8.4 8.9

PERd % 60.0 56.8

Tbiv (bivalent temperature)

COPd 1.50 1.42

Pdh kW 8.4 8.9

PERd % 60.0 56.8

Tbiv °C -15

Rated heat output supplementary capacity

Psup (at Tdesign -22°C)

kW 4.6 4.9

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 81

• Outdoor Unit • ERLQ-CV3

2

82

2 Specifications

Space heating Warm climate water outlet 55°C

General Annual energy consumption

kWh 3,282 3,429

ηs (Seasonal space heating efficiency)

% 144 145

Prated at 2°C

kW 10

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.0

COPd 1.90 1.78

Pdh kW 9.8 10.3

PERd % 76.0 71.2

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

1.0

COPd 3.22 3.25

Pdh kW 6.3 6.6

PERd % 128.8 130.0

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.9

COPd 5.88

Pdh kW 5.4

PERd % 235.2

Tbiv (bivalent temperature)

COPd 1.90 1.78

Pdh kW 9.8 10.3

PERd % 76.0 71.2

Tbiv °C 2

Average climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Cold climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Qhe Annual energy consumption (GCV)

Gj -

Warm climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Notes

(1) EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB

(2) EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB

(3) EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB

(4) EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB

(5) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)

(6) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )

(7) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)

(8) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)

Domestic hot water heating

General Declared load profile XL

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 2,158

ηwh (water heating efficiency)

% 84

Qelec (Daily electricity consumption)

kWh 9.681

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 2,394

ηwh (water heating efficiency)

% 76

Qelec (Daily electricity consumption)

kWh 10.755

Warm climate AEC (Annual electricity consumption)

kWh 1,921

ηwh (water heating efficiency)

% 95

Qelec (Daily electricity consumption)

kWh 8.600

CONNECTABLE INDOOR UNITS

2-18 Capacity and Power input

EHVZ04S18CB3V/

ERLQ004CV3

EHVZ08S18CB3V/

ERLQ006CV3

EHVZ08S18CB3V/

ERLQ008CV3

EHVZ16S18CB3V/

ERLQ011CV3

EHVZ16S18CB3V/

ERLQ014CV3

EHVZ16S18CB3V/

ERLQ016CV3

Heating capacity Min. kW 1.80 (1) -

Nom. kW 4.40 (1) / 4.03 (2)

6.00 (1) / 5.67 (2)

7.40 (1) / 6.89 (2)

11.2 (1) / 11.0 (2)

14.4 (1) / 13.5 (2)

15.9 (1) / 15.1 (2)

Max. kW 5.12 (1) / 4.90 (2)

8.35 (1) / 7.95 (2)

10.0 (1) / 9.53 (2)

8.60 (3) / 8.60 (4)

10.5 (3) / 10.7 (4)

11.3 (3) / 10.8 (4)

Power input Heating Nom. kW 0.870 (1) / 1.13 (2)

1.27 (1) / 1.59 (2)

1.66 (1) / 2.01 (2)

2.43 (1) / 3.10 (2)

3.39 (1) / 4.12 (2)

3.77 (1) / 4.67 (2)

Max. kW - 3.13 (3) / 4.10 (4)

4.02 (3) / 5.21 (4)

4.33 (3) / 5.22 (4)

COP 5.04 (1) / 3.58 (2)

4.74 (1) / 3.56 (2)

4.45 (1) / 3.42 (2)

4.60 (1) / 2.75 (3) / 3.55 (2) /

2.10 (4)

4.24 (1) / 2.61 (3) / 3.28 (2) /

2.05 (4)

4.22 (1) / 2.61 (3) / 3.23 (2) /

2.07 (4)

Tank Name Stainless steel domestic hot water tank 180 l

Water side Heat exchanger

Water flow rate Heating Nom. l/min 12.6 (5) / 11.6 (6)

17.2 (5) / 16.3 (6)

21.2 (5) / 19.8 (6)

32.1 (1) / 31.5 (1)

41.3 (1) / 38.7 (2)

45.6 (1) / 43.3 (2)

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 83

• Outdoor Unit • ERLQ-CV3

2

84

2 Specifications

General Supplier/Manufacturer details

Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium

Name or trademark Daikin Europe N.V.

Product description Air-to-water heat pump Yes

Brine-to-water heat pump No

Heat pump combination heater Yes

Low-temperature heat pump No

Supplementary heater integrated Yes

Water-to-water heat pump No

LW(A) Sound power level (according to EN14825)

Indoor dB(A) 42.0 47.0

LW(A) Sound power level (according to EN14825)

Outdoor dB(A) 61.0 62.0 64.0 66.0

Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825

Space heating general Air to water unit Rated airflow (outdoor) m³/h 2,700 2,820 5,400

Brine/water to water unit

Rated water/brine flow m³/h 0.00

Other Capacity control Inverter

Cdh (Degradation heating) 1.00

Pck (Crankcase heater mode)

kW 0.00 0.055

Poff (Off mode) kW 0.0080 0.055

Psb (Standby mode) kW 0.0080 0.055

Pto (Thermostat off) kW 0.0060 0.0070 0.0080 0.057

Integrated supplementary heater

NOx emission mg/kWh 0.00

Psup kW 3.00

Type of energy input Electrical

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 55°C

General SCOP 3.20 3.22 3.23 3.09 3.16 3.06

Annual energy consumption

kWh 2,360 3,370 4,060 6,260 7,900 8,970

Annual energy consumption (GCV)

Gj 8.48 12.1 14.6 22.6 28.4 32.3

ηs (Seasonal space heating efficiency)

% 125 126 120 123 119

Prated at -10°C

kW 3.70 5.30 6.40 9.99 12.7 13.9

Seasonal space heating eff. class

A++ A+

A Condition (-7°CDB/-8°CWB)

Cdh (Degradation heating)

1.00

COPd 2.03 2.02 1.98 1.99 1.76 1.78

Pdh kW 3.36 4.50 5.47 8.83 9.97 12.2

PERd % 81.2 80.8 79.2 79.6 70.4 71.2

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00

COPd 3.08 3.17 3.24 3.55 3.12

Pdh kW 2.00 4.43 3.43 5.28 6.76 7.61

PERd % 123 127 130 142 125

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.990 0.950 1.00

COPd 4.27 4.20 4.31 4.22 4.40

Pdh kW 2.77 3.51 3.50 4.47 4.66 4.83

PERd % 171 168 172 169 176

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.990 0.930 0.940 0.930

COPd 6.33 5.82 6.41 5.44 6.36

Pdh kW 2.65 3.28 5.37 5.26 5.38

PERd % 253 233 256 218 254

Tol (temperature operating limit)

COPd 1.80 1.74 1.66 1.79 1.75 1.71

Pdh kW 3.76 4.62 6.18 9.08 12.2 13.3

PERd % 72.0 69.6 66.4 71.6 70.0 68.4

TOL °C -10.0

WTOL °C 55.0

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.00 0.680 0.220 0.910 0.550 0.580

Tbiv (bivalent temperature)

COPd 1.80 1.74 1.66 1.99 1.92 1.78

Pdh kW 3.76 5.09 6.18 8.83 11.0 12.2

PERd % 72.0 69.6 66.4 79.6 76.8 71.2

Tbiv °C -10.0 -9.00 -10.0 -7.00 -6.00 -7.00

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 85

• Outdoor Unit • ERLQ-CV3

2

86

2 Specifications

Space heating Cold climate water outlet 55°C

General Annual energy consumption

kWh 2,130 2,310 3,090 6,740 7,870 8,580

Annual energy consumption (GCV)

Gj 7.68 8.30 11.1 24.3 28.3 30.9

ηs (Seasonal space heating efficiency)

% 107 110 95.0 95.5 98.3

Prated at -22°C

kW 2.39 2.60 3.56 6.99 8.15 9.12

Warm climate water outlet 55°C

General Annual energy consumption

kWh 1,170 1,490 1,900 2,630 3,270 3,420

Annual energy consumption (GCV)

Gj 4.20 5.37 6.85 9.47 11.8 12.3

ηs (Seasonal space heating efficiency)

% 186 182 178 125 135 136

Prated at 2°C

kW 4.27 5.30 6.59 7.58 9.84 10.3

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Space heating Average climate water outlet 35°C

General SCOP 4.52 4.29 4.34 -

Annual energy consumption

kWh 1,980 2,540 3,490 -

Annual energy consumption (GCV)

Gj 7.13 9.14 12.6 -

ηs (Seasonal space heating efficiency)

% 178 169 171 -

Prated at -10°C

kW 4.40 5.34 7.40 -

Seasonal space heating eff. class

A++ -

A Condition (-7°CDB/-8°CWB)

COPd 3.01 2.69 -

Pdh kW 4.01 4.72 6.68 -

PERd % 120 108 -

B Condition (2°CDB/1°CWB)

Cdh (Degradation heating)

1.00 0.990 1.00 -

COPd 4.41 4.24 -

Pdh kW 2.40 3.90 -

PERd % 176 170 -

C Condition (7°CDB/6°CWB)

Cdh (Degradation heating)

0.980 1.00 -

COPd 5.85 5.75 -

Pdh kW 1.70 2.59 -

PERd % 234 230 -

D Condition (12°CDB/11°CWB)

Cdh (Degradation heating)

0.980 -

COPd 7.71 7.27 -

Pdh kW 2.04 2.61 -

PERd % 308 291 -

Tol (temperature operating limit)

COPd 2.61 2.29 -

Pdh kW 4.36 4.70 6.81 -

PERd % 104 91.6 -

TOL °C -10.0 -

WTOL °C 35.0 -

Tbiv (bivalent temperature)

COPd 2.61 2.47 -

Pdh kW 4.36 4.93 7.14 -

PERd % 104 98.8 -

Tbiv °C -10.0 -8.00 -

Rated heat output supplementary capacity

Psup (at Tdesign -10°C)

kW 0.040 0.640 0.590 -

Cold climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Qhe Annual energy consumption (GCV)

Gj -

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3 87

• Outdoor Unit • ERLQ-CV3

2

88

2 Specifications

Notes

(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)

(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )

(3) Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C

(4) Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C

(5) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)

(6) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)

(7) Capacity must be split up over the additional and main zone. Refer to ESP-data for more details on available head (kPa).

Space heating Warm climate water outlet 35°C

General ηs (Seasonal space heating efficiency)

% -

Pump Additional Zone Nominal ESP unit (*RLQ*C*)

Heating kPa 52.3 (5) / 55.4 (6)

40.6 (5) / 43.3 (6)

28.3 (5) / 32.7 (6)

26.2 (1) / 28.3 (2)

25.0 (7)

Pump Main Zone Nominal ESP unit (*RLQ*C*)

Heating kPa 48.6 (5) / 51.9 (6)

39.5 (5) / 42.3 (6)

26.4 (5) / 31.2 (6)

18.2 (1) / 20.7 (2)

25.0 (7)

Domestic hot water heating

General Declared load profile L

Function to fix water heating during off peak hours

Yes

Average climate AEC (Annual electricity consumption)

kWh 1,080 1,190 1,170

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 95.0 86.4 87.4

Qelec (Daily electricity consumption)

kWh 4.93 5.43 5.32

Qfuel (Daily fuel consumption)

kWh 0.00

Water heating energy efficiency class

A

Cold climate AEC (Annual electricity consumption)

kWh 1,220 1,330 1,340

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 84.0 77.5 76.6

Qelec (Daily electricity consumption)

kWh 5.55 6.05 6.08

Qfuel (Daily fuel consumption)

kWh 0.00

Warm climate AEC (Annual electricity consumption)

kWh 966 1,120 1,110

AFC (Annual fuel consumption)

Gj 0.00

ηwh (water heating efficiency)

% 106 91.8 92.3

Qelec (Daily electricity consumption)

kWh 4.39 5.10 5.04

Qfuel (Daily fuel consumption)

kWh 0.00

2-19 Technical Specifications ERLQ004CV3 ERLQ006CV3 ERLQ008CV3 ERLQ011CV3 ERLQ014CV3 ERLQ016CV3

Dimensions Unit HeightxWidthxDepth

mm 735x832x307 1,345x900x320

Weight Unit kg 54 56 113

Compressor Quantity 1

Type Hermetically sealed swing compressor Hermetically sealed scroll compressor

CONNECTABLE INDOOR UNITS

• Heating • ERLQ-CV3

3

2

• Outdoor Unit • ERLQ-CV3

2 Specifications

Notes

(1) Operation range domestic hot water (outdoor unit): range increase by support booster heater or backup heater. See separate drawing for operation range.

(2) The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to

sound spectrum drawing for more information.

(3) Daikin Altherma inverter controlled compressor starting current always \<= max. running current

(4) Contains fluorinated greenhouse gases

Operation range heating (outdoor unit): range increase by support back-up heater. See separate drawing for operation range.

Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)

Condition: Ta 35°C - LWE 7°C ( DT = 5°C)

Operation range Cooling Min.~Max. °CDB 10.0~43.0 10.0~46.0

Domestic hot water Min.~Max. °CDB -25 (1)~35 (1) -20 (1)~35 (1)

Refrigerant Type R-410A

GWP 2,087.5

Charge TCO2eq 3.1 3.3 7.1

kg 1.5 1.6 3.4

Control Expansion valve (electronic type)

Sound power level Heating Nom. dBA 61 62 64 (2) 66 (2)

Cooling Nom. dBA 63 64 (3) 66 (3) 69 (3)

Sound pressure level Heating Nom. dBA 48 (2) 49 (2) 51 (4) 52 (4)

Cooling Nom. dBA 48 (2) 49 (2) 50 (2) 50 (4) 52 (4) 54 (4)

2-20 Electrical Specifications ERLQ004CV3 ERLQ006CV3 ERLQ008CV3 ERLQ011CV3 ERLQ014CV3 ERLQ016CV3

Power supply Name/Phase/Frequency/Voltage Hz/V V3/1~/50/230

Current Recommended fuses A 16 20 40

2-19 Technical Specifications ERLQ004CV3 ERLQ006CV3 ERLQ008CV3 ERLQ011CV3 ERLQ014CV3 ERLQ016CV3

• Heating • ERLQ-CV3 89

• Outdoor Unit • ERLQ-CV3

3

90

3 Electrical data3 - 1 Electrical Data

ERLQ004-008CV3Starting current

1 2

1 2

Specifications

Example

Standard On/OFF compressor starting current >> max. running current

Example

Running current [A]

Maximum running current

Time

Daikin Altherma inverter-controlled compressor starting current always max. running current.

Time

Running current [A]

Maximum running current

Example Example

Figure ·A· Starting current

4D094715A

• Heating • ERLQ-CV3

3

4

• Outdoor Unit • ERLQ-CV3

4 Capacity tables4 - 1 Cooling Capacity Tables

• Heating • ERLQ-CV3 91

• Outdoor Unit • ERLQ-CV3

4

92

4 Capacity tables4 - 1 Cooling Capacity Tables

• Heating • ERLQ-CV3

3

4

• Outdoor Unit • ERLQ-CV3

4 Capacity tables4 - 2 Heating Capacity Tables

• Heating • ERLQ-CV3 93

• Outdoor Unit • ERLQ-CV3

4

94

4 Capacity tables4 - 2 Heating Capacity Tables

• Heating • ERLQ-CV3

3

4

• Outdoor Unit • ERLQ-CV3

4 Capacity tables4 - 2 Heating Capacity Tables

ERLQ011-016C

3TW60332-5A

Capacity in function of � eld piping length for inverter

Field piping length (m)

Cooling

Heating

Capacity (%)

NOTE

Capacity drop is at nominal capacity

• Heating • ERLQ-CV3 95

• Outdoor Unit • ERLQ-CV3

4

96

4 Capacity tables4 - 3 Certification Programs

ERLQ004 008CV3

Rated data for certification programmes heating mode

Certification programme Ta [°C] EWC [°C] LWC [°C] HC [kW] COP

Minim

umrequ

iredCO

P

Vivrelec

Minim

umrequ

iredCO

P

NFPA

C

Minim

umrequ

iredCO

P

EHPA

Minim

umrequ

iredCO

P

Ecolab

el

Minim

umrequ

iredCO

P

SEI

Minim

umrequ

iredCO

P

microgene

ratio

n

Minim

umrequ

iredCO

P

SPF(DAB

)

EHPA 10/8 30 35 4,47 5,12Crédit d'impôt, NF PAC 7/6 30 35 4,40 5,04EHPA 2/1 35 3,27 4,02NF PAC, EHPA 7/ 8 35 4,37 2,81SPF 2/1 30 35 3,27 4,02NF PAC 7/6 40 45 4,03 3,58EHPA 7/ 8 45 4,20 2,27NF PAC 7/ 8 45 4,70 2,34EHPA 7/6 47 55 3,71 2,91EHPA 7/ 8 55 3,74 1,80EHPA 10/8 30 35 6,25 5,07Crédit d'impôt, NF PAC 7/6 30 35 6,00 4,74EHPA 2/1 35 4,58 3,66NF PAC, EHPA 7/ 8 35 5,31 2,84SPF 2/1 30 35 4,05 3,88NF PAC 7/6 40 45 5,67 3,56NF PAC 7/ 8 45 5,12 2,22EHPA 7/6 47 55 5,43 2,95EHPA 7/ 8 55 4,47 1,80EHPA 10/8 30 35 7,39 4,75Crédit d'impôt, NF PAC 7/6 30 35 7,40 4,45EHPA 2/1 35 5,80 3,53NF PAC, EHPA 7/ 8 35 5,46 2,71SPF 2/1 30 35 4,56 3,81NF PAC 7/6 40 45 6,89 3,42NF PAC 7/ 8 45 6,13 2,12EHPA 7/6 47 55 6,79 2,87EHPA 7/ 8 55 5,59 1,80

Rated data for certification programmes standby power consumption

Certification programmeNF PAC 7,5WNF PAC 7,5WNF PAC 7,5W

Sound power measurements

Certification programmeRequired setup of unit

for testTa [°C] EW [°C] LW [°C] Mode dBA

Promotelec, Ecolabel, Eurovent Nominal 7/6 30 35 Heating 40

NF PAC, Ecolabel Nominal 7/6 30 35 Heating 42

Symbols

CC= Cooling capacity at maximum operating frequency, measured according to EN 14511.HC= Heating capacity at maximum operating frequency, measured according to EN 14511

COP/EER= Coefficient of Performance/Energy efficiency ratio according to EN 14511.LWE= Leaving water evaporator temperature [°C]LWC= Leaving water condensor temperature [°C]

Ta= Ambient temperature [°C DB/WB]

PI [W]

*RLQ004**RLQ006**RLQ008*

EHVZ04S18CB3V

EHVZ08S18CB3V

1,30Radiator 2,201,60

3,71

Fan coil 2,50 2,701,50

3,002,00 2,10

4,00 3,40 3,20

*RLQ008*

Floor

4,00

3,10

1,30Radiator 2,201,60

3,71

Fan coil 2,50 2,701,50

3,002,00 2,10

4,00 3,40 3,20

*RLQ006*

Floor

4,00

3,10

1,30Radiator 2,201,50 1,60

3,71

Fan coil2,50 2,70

3,10

3,002,00 2,10

4,00 3,40 3,20

*RLQ004*

Floor

4,00

3,10

3D096433

ERLQ004-008CV3

Rated data for certification programmes - heating mode

Certification programme Ta [°C] EWC [°C] LWC [°C] HC [kW] COP

Min

imum

requ

ired

COP

Vivr

elec

Min

imum

requ

ired

COP

NF

PAC

Min

imum

requ

ired

COP

EHPA

Min

imum

requ

ired

COP

Ecol

abel

Min

imum

requ

ired

COP

SEI

Min

imum

requ

ired

COP

mic

roge

nera

tion

Min

imum

requ

ired

COP

SPF

(DAB

)

EHPA 10/8 30 35 4,47 5,12Crédit d'impôt, NF PAC, Microgeneration 7/6 30 35 4,40 5,04EHPA, SEI 2/1 35 3,27 4,02NF PAC, EHPA -7/-8 35 4,37 2,81Ecolabel, SPF 2/1 30 35 3,27 4,02NF PAC 7/6 40 45 4,03 3,58EHPA -7/-8 45 4,20 2,27NF PAC -7/-8 45 4,70 2,34Ecolabel 2/1 40 45 3,97 2,77Danish incentive (< 2013) 2/1 50 55 3,93 2,43Danish incentive (< 2013) -7/-8 50 55 4,20 1,98EHPA 7/6 47 55 3,71 2,91EHPA -7/-8 55 3,74 1,80EHPA 10/8 30 35 6,25 5,07Crédit d'impôt, NF PAC, Microgeneration 7/6 30 35 6,00 4,74EHPA, SEI 2/1 35 4,58 3,66NF PAC, EHPA -7/-8 35 5,31 2,84Ecolabel 2/1 30 35 4,58 3,66SPF 2/1 30 35 4,05 3,88NF PAC 7/6 40 45 5,67 3,56NF PAC -7/-8 45 5,12 2,22Ecolabel 2/1 40 45 5,69 2,81Danish incentive (< 2013) 2/1 50 55 5,27 2,29Danish incentive (< 2013) -7/-8 50 55 4,96 1,86EHPA 7/6 47 55 5,43 2,95EHPA -7/-8 55 4,47 1,80EHPA 10/8 30 35 7,39 4,75Crédit d'impôt, NF PAC, Microgeneration 7/6 30 35 7,40 4,45EHPA, SEI 2/1 35 5,80 3,53NF PAC, EHPA -7/-8 35 5,46 2,71Ecolabel 2/1 30 35 5,80 3,53SPF 2/1 30 35 4,56 3,81NF PAC 7/6 40 45 6,89 3,42NF PAC -7/-8 45 6,13 2,12Ecolabel 2/1 40 45 6,08 2,63Danish incentive (< 2013) 2/1 50 55 5,45 2,27Danish incentive (< 2013) -7/-8 50 55 5,50 1,86EHPA 7/6 47 55 6,79 2,87EHPA -7/-8 55 5,40 1,80

Rated data for certification programmes - cooling mode

Certification programme Ta [°C] EWC [°C] LWC [°C] CC [kW] EER

Min

imum

requ

ired

EER

Vivr

elec

Min

imum

requ

ired

EER

Italy

D1

*RLQ004* Floor Ecolabel, Italy D1 35 23 18 4,08 4,55Fan coil Ecolabel 35 12 7 4,17 2,32

*RLQ006* Floor Ecolabel, Italy D1 35 23 18 5,88 3,89Fan coil Ecolabel 35 12 7 4,84 2,34

*RLQ008* Floor Ecolabel, Italy D1 35 23 18 6,20 3,79Fan coil Ecolabel 35 12 7 5,36 2,29

Rated data for certification programmes - standby power consumption

Certification programmeNF PAC 7,5WNF PAC 7,5WNF PAC 7,5W

Sound power measurements

Certification programmeRequired setup of

unit for testTa [°C] EW [°C] LW [°C] Mode dBA

Promotelec, Ecolabel, Eurovent Nominal 35 12 7 Cooling4042

NF PAC, Ecolabel Nominal 7/6 30 35 Heating4042

SymbolsCC= Cooling capacity at maximum operating frequency, measured according to EN 14511.HC= Heating capacity at maximum operating frequency, measured according to EN 14511

COP/EER= Coefficient of Performance/Energy efficiency ratio according to EN 14511.LWE= Leaving water evaporator temperature [°C]LWC= Leaving water condensor temperature [°C]

Ta= Ambient temperature [°C DB/WB]sCOP = Seasonal coefficient of performance, according to EN14825 and EN14511

EHB(H/X)(04/08)*EHV(H/X)(04/08)*

EHB(H/X)(04/08)*EHV(H/X/Z)(04/08)*

3

*RLQ008*Danish energy agency Average climate - low temperature (35°C) 4,34 3,5

Danish energy agency Average climate - high temperature( 55°C) 3,2 3

*RLQ006**RLQ006*

Danish energy agency Average climate - low temperature (35°C) 4,29 3,5*RLQ008* Danish energy agency Average climate - high temperature( 55°C) 3,22

3,5*RLQ004* Danish energy agency Average climate - high temperature( 55°C) 3,2 3

Rated data for certification programmes - heating mode

Min

imum

requ

ired

COP

DEA

PI [W]Certification programme sCOP

*RLQ004*Danish energy agency Average climate - low temperature (35°C) 4,52

2,20 - - - - -2,20 3,60 - - - -2,20 - - - - -2,20 3,60 - - - -2,20 - - - - -2,20 3,60 - - - -

-- 1,30 - - - - -- 2,20 - - - -

-- - - - - - -

- - -

Radiator

- - - - - -

- -1,50 1,60 - - - - -Fan coil2,50 2,70 - - -

- - 2,60

-- - - - - - 3,71- - - 3,10 - -

3,00 - -2,00 2,10 - - - - -

- - -4,00 3,40 - - - 3,20 -

*RLQ008*

Floor

4,00 - - -

- - 3,10 -

-- 1,30 - - - - -- 2,20 - - - -

-- - - - - - -

-

Radiator

- - - - - -

- -1,50 1,60 - - - - -Fan coil2,50 2,70 - - -

1,50 - 2,60

-- - - - - - 3,71- - - 3,10 - -

3,00 - -2,00 2,10 - - - - -

- - -4,00 3,40 - - - 3,20 -

*RLQ006*

Floor

4,00 - - -

- - 3,10 -

- - -- 1,30 - - - - -

- -- - - - - - -

Radiator

- - - - -

- 2,20 - -

-1,50 - - 2,60 - - -1,50 1,60 - - - -

- - - - - -

3,71

Fan coil

2,50 2,70 - - - - --

- - - 3,10 - -

3,00 - -2,00 2,10 - - - - -

- - -4,00 3,40 - - - 3,20 -

*RLQ004*

Floor

4,00 - - -

- - 3,10 -

3TW60819-3G

• Heating • ERLQ-CV3

3

4

• Outdoor Unit • ERLQ-CV3

4 Capacity tables4 - 3 Certification Programs

ERLQ011 016CV3

Certification programme Ta [°C] EWC [°C] LWC [°C]HC [kW] COP

Minim

umrequ

ired

COP

NFPA

C

Minim

umrequ

ired

COP

EHPA

Minim

umrequ

ired

COP

Ecolab

el

Minim

umrequ

ired

COP

SPF(DAB

)

EHPA 10 35 11,20 4,85NF PAC, EHPA 7/6 30 35 11,20 4,60EHPA 2/1 35 8,56 3,60SPF (DAB) 2/1 30 35 5,71 3,71NF PAC, EHPA 7/ 8 35 8,60 2,75NF PAC 7/6 40 45 11,00 3,55

2/1 45 8,20 2,84NF PAC 7/ 8 45 8,60 2,10EHPA 7/6 47 55 10,76 2,71EHPA 7/ 8 55 8,79 1,74EHPA 10 35 14,30 4,70NF PAC, EHPA 7/6 30 35 14,40 4,24EHPA 2/1 35 10,20 3,35SPF (DAB) 2/1 30 35 5,71 3,71NF PAC, EHPA 7/ 8 35 10,50 2,61NF PAC 7/6 40 45 13,50 3,28

2/1 45 9,90 2,63NF PAC 7/ 8 45 10,70 2,05EHPA 7/6 47 55 13,30 2,71EHPA 7/ 8 55 10,83 1,74EHPA 10 35 15,70 4,50NF PAC, EHPA 7/6 30 35 15,90 4,22EHPA 2/1 35 10,90 3,31SPF (DAB) 2/1 30 35 5,71 3,71NF PAC 7/ 8 35 11,30 2,61NF PAC 7/6 40 45 15,10 3,23

2/1 45 10,80 2,63NF PAC 7/ 8 45 10,80 2,07EHPA 7/6 47 55 15,04 2,80EHPA 7/ 8 55 10,79 1,71

Rated data for certification programmes standby power consumption

Certification programmeNF PAC 22WNF PAC 25WNF PAC 22WNF PAC 25WNF PAC 22WNF PAC 25W

Symbols

CC= Cooling capacity at nominal operating frequency, measured according to EN14511.HC= Heating capacity at nominal operating frequency, measured according to EN14511.

COP/EER= Coefficient of Performance/Energy efficiency ratio according to EN 14511.LWE= Leaving water evaporator temperature [°C]LWC= Leaving water condensor temperature [°C]

Ta= Ambient temperature [°C DB/WB]

*RLQ011C* V3*RLQ011C* W1*RLQ014C* V3*RLQ014C* W1*RLQ016C* V3*RLQ016C* W1

Radiator

2,601,60

2,10

Fan coil2,70

3,103,71

*RLQ016C*

Floor3,40

Radiator

1,60

2,10

Fan coil2,70

3,103,71

*RLQ014C*

Floor3,40

Radiator

2,601,60

2,10

Fan coil2,70

3,103,71

Rated data for certification programmes heating mode

*RLQ011C*

Floor3,40

3D091994

ERLQ011 016CV3

Certification programme Ta [°C] EWC [°C] LWC [°C]HC [kW] COP

Minim

umrequ

iredCO

P

NFPA

C

Minim

umrequ

iredCO

P

EHPA

Minim

umrequ

iredCO

P

Ecolabel

Minim

umrequ

iredCO

P

SPF(DAB

)

EHPA 10 35 11,20 4,85NF PAC, EHPA 7/6 30 35 11,20 4,60EHPA 2/1 35 8,56 3,60Ecolabel 2/1 30 35 8,56 3,60SPF (DAB) 2/1 30 35 5,71 3,71NF PAC, EHPA, Piemonte (Italy) 7/ 8 35 8,60 2,75NF PAC 7/6 40 45 11,00 3,55

2/1 45 8,20 2,84NF PAC 7/ 8 45 8,60 2,10Ecolabel 2/1 40 45 8,20 2,80EHPA 7/6 47 55 10,76 2,71EHPA 7/ 8 55 8,79 1,74EHPA 10 35 14,30 4,70NF PAC, EHPA 7/6 30 35 14,50 4,30EHPA 2/1 35 10,30 3,41Ecolabel 2/1 30 35 10,30 3,41SPF (DAB) 2/1 30 35 5,71 3,71NF PAC, EHPA 7/ 8 35 10,60 2,65Piemonte (Italy) 7/ 8 35 8,60 2,75NF PAC 7/6 40 45 13,60 3,32

2/1 45 10,00 2,67NF PAC 7/ 8 45 10,80 2,08Ecolabel 2/1 40 45 10,00 2,70EHPA 7/6 47 55 13,30 2,71EHPA 7/ 8 55 10,83 1,74EHPA 10 35 15,70 4,50NF PAC, EHPA 7/6 30 35 16,00 4,25EHPA 2/1 35 11,10 3,35Ecolabel 2/1 30 35 11,10 3,35SPF (DAB) 2/1 30 35 5,71 3,71NF PAC 7/ 8 35 11,40 2,64Piemonte (Italy) 7/ 8 35 8,60 2,75NF PAC 7/6 40 45 15,20 3,26

2/1 45 10,90 2,63NF PAC 7/ 8 45 10,90 2,09Ecolabel 2/1 40 45 10,90 2,66EHPA 7/6 47 55 15,04 2,80EHPA 7/ 8 55 10,79 1,71

Certification programme Ta [°C] EWC [°C] LWC [°C] CC [kW] EER

Minim

umrequ

ired

EER

Ecolabel

Minim

umrequ

ired

EER

ItalyD1

Floor Ecolabel, Italy D1 35 23 18 12,13 3,98Fan coil Ecolabel 35 12 7 11,72 2,72

Floor Ecolabel, Italy D1 35 23 18 12,72 3,96Fan coil Ecolabel 35 12 7 12,55 2,47

Floor Ecolabel, Italy D1 35 23 18 13,79 3,69Fan coil Ecolabel 35 12 7 13,12 2,29

Certification programme

NF PAC 22WNF PAC 25WNF PAC 22WNF PAC 25WNF PAC 22WNF PAC 25W

SymbolsCC= Cooling capacity at nominal operating frequency, measured according to EN14511.HC= Heating capacity at nominal operating frequency, measured according to EN14511.

COP/EER= Coefficient of Performance/Energy efficiency ratio according to EN 14511.LWE= Leaving water evaporator temperature [°C]LWC= Leaving water condensor temperature [°C]

Ta= Ambient temperature [°C DB/WB]

*RLQ016C* W1

*RLQ014C* W1*RLQ016C* V3

*RLQ011C* W1*RLQ014C* V3

Rated data for certification programmes standby power consumption

*RLQ011C* V3

*RLQ016C*2,20 3,602,20

*RLQ014C*2,20 3,602,20

Rated data for certification programmes cooling mode

*RLQ011C*2,20 3,602,20

Radiator

Fan coil

2,702,60

1,60

2,10

3,103,71

3,10

*RLQ016C*

Floor

3,40

2,60

Radiator

1,60Fan coil

2,70

3,712,10

3,103,10

*RLQ014C*

Floor

3,40

Radiator

Fan coil

2,702,60

1,60

3,712,10

3,103,10

Rated data for certification programmes heating mode

*RLQ011C*

Floor

3,40

3TW60332 3F

• Heating • ERLQ-CV3 97

• Outdoor Unit • ERLQ-CV3

5

98

5 Dimensional drawings5 - 1 Dimensional Drawings

ERLQ011-016CV3

3TW60334-2

Hole for anchor 1 Gas pipe connection Ø15.9 � are2 Liquid connection pipe Ø9.5 flare3 Service port (in the unit)4 Electronic connection and grounding terminal M5 (in switchbox)5 Refrigerant piping intake6 Power supply wiring intake (knock hole Ø34)7 Control wiring intake (knock hole Ø27)8 Drain outlet

• Heating • ERLQ-CV3

3

6

• Outdoor Unit • ERLQ-CV3

6 Centre of gravity6 - 1 Centre of Gravity

ERLQ011-016CV3

4TW31729-4

• Heating • ERLQ-CV3 99

• Outdoor Unit • ERLQ-CV3

7

100

7 Piping diagrams7 - 1 Piping Diagrams

• Heating • ERLQ-CV3

3

8

• Outdoor Unit • ERLQ-CV3

8 Wiring diagrams8 - 1 Wiring Diagrams - Single Phase

• Heating • ERLQ-CV3 101

• Outdoor Unit • ERLQ-CV3

8

102

8 Wiring diagrams8 - 1 Wiring Diagrams - Single Phase

ERLQ011-016CV3

A1P Printed circuit board (main) K2R Magnetic relay (Y3S) R5T Thermistor (heat exchanger middle)A2P Printed circuit board (service) K3R Magnetic relay (E1H) R6T Thermistor (liquid)A3P Printed circuit board (noise � lter) K4R Magnetic relay (E1HC) RC Signal receiver circuitA4P Printed circuit board (communication) K10R Magnetic relay (upload) R10T Thermistor (fin)BS1~BS4 Push button switch K11R Magnetic relay (main) S1NPH Pressure sensorC1~C4 Capacitor L1R Reactor S1PH Pressure switch (high)DS1 Dip switch M1C Motor (compressor) TC Signal transmission circuitE1H Bottomplate heater M1F Motor (fan) (upper) V1R Power moduleE1HC Crankcase heater M2F Motor (fan) (lower) V2R,V3R Diode module F1U,F3U,F4U Fuse (T 3.6A / 250V) PS Swtiching power supply V1T IGBTF6U Fuse (T 5.0A / 250V) Q1DI Earth leakage circuit breaker X1M Terminal strip (power supply)F7U,F8U Fuse (F 1.0A / 250V) R1 Resistor Y1E Electronic expansion valve (main)

H1P~7P (A2P)

Light emit. diode (serv. monitor-orange)[H2P] Pepare, test ............................ � ickering Malfunction detection ..................light up

R2 Resistor Y3E Electronic expansion valve (inj)R1T Thermistor (air) Y1S Solenoid valve (4 way valve)R2T Thermistor (discharge) Y3S Solenoid valve (hot gas pass)

HAP(A1P)

Light emitting diode(Service monitor green)

R3T Thermistor (suction) Z1C~Z3C Noise filter (ferrity core)R4T Thermistor (heat exchanger) Z1F~Z4F Noise filter

K1R Magnetic relay (Y1S)

NOTES

1. This wiring diagram only applies to the outdoor unit2. L: live, N: neutral, : � eld wiring3. : terminal strip, : connector, : connection, : protective earth (screw), : connector, : noiseless earth, : terminal4. Refer to the option manual, for connecting wiring to X6A.5. Refer to the ‘wiring diagram sticker’ (on back of front plate) on how to use BS1~BS4 and DS1 switch6. Do not operate the unit by short-circuiting protection device S1PH7. Colors: = blue, = brown, = green, = red, = white, = yellow, = orange, = black8. Con� rm the method of setting the selector switches (DS1) by service manual; Factory setting of all switches: “off”9. : option, : wiring dependent on model

2TW60336-2

1N~50Hz230V

Wire entrance

HAP

A1P(Back) (Front)

El. compo. assy.(position of elements)

Position of compressor

terminal

(Note 4)

Indoor

Outdoor

• Heating • ERLQ-CV3

3

9

• Outdoor Unit • ERLQ-CV3

9 Sound data9 - 1 Sound Power Spectrum Quiet Mode

NOTES

1 Data is valid at free field condition (measured in a semi-anachoic room).2 dBA = A-weighted sound pressure level. (A-scale according to IEC)3 Reference acoustic pressure 0dB = 20 Pa.4 If the sound is measured under actual installation conditions, the measured value will be

higher due to environmental noise and sound reflections.5 Data is valid at night quiet mode level 2

Measuring location (discharge side):

Soun

d pre

ssur

e lev

el (d

B)

Soun

d pre

ssur

e lev

el (d

B)

Soun

d pre

ssur

e lev

el (d

B)

Cooling

Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz)

3TW60337-3

NOTES

1 Data is valid at free field condition (measured in a semi-anachoic room).2 dBA = A-weighted sound pressure level. (A-scale according to IEC)3 Reference acoustic pressure 0dB = 20 Pa.4 If the sound is measured under actual installation conditions, the measured value will be

higher due to environmental noise and sound reflections.5 Data is valid at night quiet mode level 2

Measuring location (discharge side):

Soun

d pre

ssur

e lev

el (d

B)

Soun

d pre

ssur

e lev

el (d

B)

Soun

d pre

ssur

e lev

el (d

B)

Heating

Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz)

3TW60337-4

• Heating • ERLQ-CV3 103

• Outdoor Unit • ERLQ-CV3

9

104

9 Sound data9 - 2 Sound Pressure Spectrum - Cooling

• Heating • ERLQ-CV3

3

9

• Outdoor Unit • ERLQ-CV3

9 Sound data9 - 2 Sound Pressure Spectrum - Cooling

NOTES

1 Data is valid at free field condition (measured in a semi-anachoic room).2 dBA = A-weighted sound pressure level. (A-scale according to IEC)3 Reference acoustic pressure 0dB = 20 Pa.4 If the sound is measured under actual installation conditions, the measured value will be

higher due to environmental noise and sound reflections.5 Data is valid at nominal capacity

Measuring location (discharge side):

Soun

d pre

ssur

e lev

el (d

B)

Soun

d pre

ssur

e lev

el (d

B)

Soun

d pre

ssur

e lev

el (d

B)

Cooling

Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz)

3TW60337-1

• Heating • ERLQ-CV3 105

• Outdoor Unit • ERLQ-CV3

9

106

9 Sound data9 - 3 Sound Pressure Spectrum - Heating

NOTES

1 Data is valid at free field condition (measured in a semi-anachoic room).2 dBA = A-weighted sound pressure level. (A-scale according to IEC)3 Reference acoustic pressure 0dB = 20 Pa.4 If the sound is measured under actual installation conditions, the measured value will be

higher due to environmental noise and sound reflections.5 Data is valid at nominal capacity

Measuring location (discharge side):

Soun

d pre

ssur

e lev

el (d

B)

Soun

d pre

ssur

e lev

el (d

B)

Soun

d pre

ssur

e lev

el (d

B)

Heating

Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz)

3TW60337-2

ERLQ004-008CV3Heating

Notes1. Data is valid at free field condition.

Measured in a semi-anechoic chamber2. Data is valid at nominal operation condition.3. dBA = A-weighted sound pressure level (A scale according to IEC).4. Reference acoustic pressure 0 dB = 20 μPa5. If the sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and

sound reflections.

NR0 NR5 NR10 NR15NR20

NR25

NR30

NR35NR40

NR45

NR50

NR55

NR60

NR65

NR70

NR75

10

20

30

40

50

60

70

10

15

20

25

30

35

40

45

50

55

60

65

70

63 125 250 500 1000 2000 4000 8000 dBA

ERLQ008CA*

NR0 NR5 NR10 NR15NR20

NR25

NR30

NR35NR40

NR45

NR50

NR55

NR60

NR65

NR70

NR75

10

20

30

40

50

60

70

10

15

20

25

30

35

40

45

50

55

60

65

70

63 125 250 500 1000 2000 4000 8000 dBA

ERLQ006CA*

NR0 NR5 NR10 NR15NR20

NR25

NR30

NR35NR40

NR45

NR50

NR55

NR60

NR65

NR70

NR75

10

20

30

40

50

60

70

10

15

20

25

30

35

40

45

50

55

60

65

70

63 125 250 500 1000 2000 4000 8000 dBA

ERLQ004CA*

Octave band centre frequency [Hz]Octave band centre frequency [Hz]Octave band centre frequency [Hz]

Soun

d pr

essu

re le

vel [

dB]

Soun

d pr

essu

re le

vel [

dB]

Soun

d pr

essu

re le

vel [

dB]

3,28Ft(1m)

4,92Ft

(1,5m)

3TW60817-2B

• Heating • ERLQ-CV3

3

10

• Outdoor Unit • ERLQ-CV3

10 Installation10 - 1 Installation Method

ERLQ011-016C

3TW60339-1

Installation servicing space

A B1 B2 C D1 D2 E L1/L2200

200 200 200200 500 1000

300 300 300 500 1000 1500

500 500 1000L1<L2 200 500L2<L1 200 500

L1<L2 L1 H 350 500 750 1000 0<L1 1/2H

21000 0<L1 1/2H

H<L1 L1 H

L2<L1 L2 H 200 1000 500 1000 0<L2 1/2H300 1/2H<L2 H

H<L2 L2 H

NOTES

Legend (Unit: mm)Suction side obstacleDischarge side obstacleLeft side obstacleRight side obstacleTop side obstacleObstacle is present

This situation is not allowed

1 Recommended installation set-up for the ERLQ011~016*(to prevent exposure to wind or that the heat exchanger coil is affected by snow)

2 In these cases, close bottom of the installation frame to prevent discharged air from being bypassed

• Heating • ERLQ-CV3 107

• Outdoor Unit • ERLQ-CV3

10

108

10 Installation10 - 1 Installation Method

ERLQ011-016C

4TW60339-2

Installation guidelines / precautions Daikin AlthermaOutdoor unitInstallation location (general)

Select an installation site that meets the following requirements:• The foundation must be strong enough to support the weight of the unit. The floor is flat to prevent vibrations and noise

generation and to have sufficient stability.• The space around the unit is adequate for maintenance/servicing and allows for sufficient air circulation.(Refer to “Installation

and service space” information sheet}• There is no danger of fire due to leakage of inflammable gas.• The equipment is not intended for use in a potentially explosive atmosphere.• Select the location of the unit in such a way that the sound and discharged cold/hot air generated by the unit does not disturb

anyone, and the location is selected according the applicable legislation.• All piping lengths and distances have been taken into consideration (refer to “Technical specification” information sheet).• Take care that in the event of a water leak, water cannot cause any damage to the installation space and surroundings.• Install units, power cords and inter-unit cables at least 3 m away from television and radio sets. This is to prevent

interference to images and sounds.• Depending on radio wave conditions, electromagnetic interference may still occur even if installed more than 3 m away.

Do not install in the following locations:• Locations where sulphurous acids and other corrosive gases may be present in the atmosphere.• Locations where a mineral oil mist, spray or vapour may be present in the atmosphere.• Locations where flammable gases may leak, where thinner, gasoline and other volatile substances are handled, or where

carbon dust and other incendiary substances are found in the atmosphere.• In areas where the air contains high levels of salt such as that near the ocean.• To prevent exposure to wind, install the outdoor unit with its suction side facing the wall.• Never install the outdoor unit at a site where the suction side (left and back) may be exposed directly to wind, snow. (See

“Installation and Service space” information sheet and figure 1)

Installation location (in cold climates)• To prevent exposure to wind, install a baffle plate on the air discharge side of the outdoor unit.• Unit should be installed in a way that a minimum of 10 cm free space is assured below the unit’s bottom plate at all

conditions (prevent burying in snow), e.g.: heavy snowfall (if necessary construct a pedestal).• In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit. Make sure that

the heat exchanger coil (left and back side) is not affected by the snow (if necessary construct a lateral canopy and baffle plate on the air side).

• Recommended installation set-up. (See “Installation and Service space” information sheet and figure 2)

Figure 1: construction to prevent exposure to wind and

snow

Figure 2: construction to prevent affect of snow to the

unit

• Heating • ERLQ-CV3

3

11

• Outdoor Unit • ERLQ-CV3

11 Operation range11 - 1 Operation Range

���

��

��

��

��

��

��

��

��

�� �� ��

��

�� ��

����

���

��

��

��

��

��

��

��

� ��

��

�� ��

��

��

����

��

��

�� �� ��

�� �����

��

��

��

��

�� ��

����

��

��

���

��

��

��

��

��

��

��

���� �

��

��

��

��

�� �� ���

��

������

��

��

��

����

��

��

��� ��

��

��

��

�� ��

• Heating • ERLQ-CV3 109

Daikin Europe N.V. Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR OostendeDaikin Europe N.V. participates in the Eurovent Certifica-tion programme for Liquid Chilling Packages (LCP), Airhandling units (AHU), Fan coil units (FCU) and variablerefrigerant flow systems (VRF) Check ongoing validity ofcertificate online: www.eurovent-certification.com or us-ing: www.certiflash.com

EEDEN 09/16

The present leaflet is drawn up by way of information only and does not constitute an offer bindingupon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of itsknowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fit-ness for particular purpose of its content and the products and services presented therein. Specifica-tions are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability forany direct or indirect damage, in the broadest sense, arising from or related to the use and/or inter-pretation of this leaflet. All content is copyrighted by Daikin Europe N.V.