Hazardous Area Classification of Low Pressure Natural Gas ...
Transcript of Hazardous Area Classification of Low Pressure Natural Gas ...
![Page 1: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/1.jpg)
Hazardous Area Classification of
Low Pressure Natural Gas Systems
using CFD Predictions
HSL
Simon Gant
Mat Ivings
Roger Santon
Allyn Jones HIDS13D, HSE -
![Page 2: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/2.jpg)
CONTENTS
• Background: DSEAR
• BS EN 60079-10:2003
• Computational Modelling
• Results
• Discussion & Conclusions
![Page 3: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/3.jpg)
BACKGROUND: DSEAR
• Dangerous Substances and Explosives
Regulations, 2002.
![Page 4: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/4.jpg)
BACKGROUND: DSEAR
• Dangerous Substances and Explosives
Regulations, 2002.
• Responsibility of employers to control or
eliminate risks from explosive atmospheres in
the workplace.
• Puts into effect EU Directive 99/92/EC (ATEX)
• http://www.hse.gov.uk/fireandexplosion/dsear.htm
![Page 5: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/5.jpg)
DSEAR ZONING
• Classification of hazardous areas
according to zones.
• Control & mitigation
measures: appropriate
equipment and/or
ventilation for zoned
areas.
![Page 6: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/6.jpg)
APPLICATION OF DSEAR
• To whom does it apply?
- All workplaces where dangerous
substances are present, used, or
produced.
- Excluding domestic premises
(provided people are not working
there).
![Page 7: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/7.jpg)
TIMESCALES OF DSEAR
• When do the regulations come into
force?
- July 2003 for new premises
- July 2006 for all premises (both old
and new)
![Page 8: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/8.jpg)
DSEAR: NATURAL GAS SYSTEMS
• Estimated ~600,000 businesses
potentially affected.
• Required to carry out risk
assessment, classify areas into
zones and adopt appropriate
control/mitigation measures.
![Page 9: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/9.jpg)
ZONING: BS EN 60079-10:2003
• To provide guidance on zoning,
DSEAR suggests that BS EN
60079 is used.
• BS EN introduces concept of a ‘Vz’
gas cloud volume to quantify the
hazardous zones.
![Page 10: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/10.jpg)
Vz DEFINITION
• Volume of gas in which mean gas
concentration is 25 or 50% of the
Lower Explosive Limit (LEL).
• If Vz < 0.1 m3, ventilation can be
described as ‘high’, and the gas
cloud is of ‘Negligible Extent’
![Page 11: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/11.jpg)
BS EN 60079-10:2003
• Calculation method:
• Origin of method unknown
293.
/ max
min
T
LELk
dtdG
dt
dV
m
03.0
/min
dtdVfVz
• Overly conservative?
![Page 12: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/12.jpg)
AIMS
• To compare predictions of Vz
using:
- BS EN 60079-10:2003
- Computational Fluid Dynamics
(CFD)
![Page 13: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/13.jpg)
CASES CONSIDERED
• Outdoor unobstructed release
• Pressures: 0.5 – 5.0 barg
• Hole Sizes: 0.25 – 5.0 mm2
• Methane, propane, butane and
natural gas
![Page 14: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/14.jpg)
COMPUTATIONAL FLUID
DYNAMICS (CFD)
• Numerical solution of conservation
equations governing transport of
mass, momentum and energy.
• Values of velocity, pressure,
temperature and gas concentration
found at mesh points.
![Page 15: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/15.jpg)
Open end
COMPUTATIONAL FLUID
DYNAMICS (CFD)
Open sides
Coflow
(0.5 m/s)
Jet
![Page 16: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/16.jpg)
COMPUTATIONAL FLUID
DYNAMICS (CFD)
2.2% Methane
50% LEL
![Page 17: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/17.jpg)
COMPUTATIONAL FLUID
DYNAMICS (CFD)
2.2% Methane
50% LEL
Vz volume
(Mean
concentration
50% LEL)
![Page 18: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/18.jpg)
Leak Conditions 50% LEL Vz Volumes (m3)
Pressure
(barg)
Area
(mm2)
CFD BS EN 60079
5.0 2.5 0.0326 6.17 – 30.8
2.5 2.5 0.0148 3.60 – 18.0
0.5 2.5 0.0054 1.73 – 8.63
RESULTS: METHANE
BS EN is 2 – 3 orders
of magnitude larger
![Page 19: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/19.jpg)
RESULTS: METHANE
0
10
20
30
40
50
60
70
0 1 2 3 4 5 6
Mass Flow Rate (g/s)
Vz V
olu
me (
m3)
CFD BS EN 60079 (f=1) BS EN 60079 (f=5)
![Page 20: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/20.jpg)
RESULTS SUMMARY
• Over the range of cases considered,
BS EN estimates Vz to be 2 – 3 orders
of magnitude larger than the CFD.
• Predictions for propane, butane and
natural gas show similar trends to
methane.
![Page 21: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/21.jpg)
CONCLUSIONS
• There is a high level of conservatism in
BS EN 60079 for low-pressure
releases.
• Present CFD results may help to
prepare risk assessments and area
classification.
• Need to study obstructed spaces.
![Page 22: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/22.jpg)
JOINT-INDUSTRY PROJECT ON
AREA CLASSIFICATION
• To experimentally validate the concept of
Vz and ‘negligible extent’.
• To examine gas dispersion and ventilation
in indoor plant areas
• To define area classification rules for low-
pressure secondary leaks of natural gas
for indoor plant areas based on provision
of ventilation.
• http://www.hsl.gov.uk/news/index.htm#gas
![Page 23: Hazardous Area Classification of Low Pressure Natural Gas ...](https://reader035.fdocuments.in/reader035/viewer/2022071613/61570b49a097e25c76508176/html5/thumbnails/23.jpg)
THANK YOU
Any questions?