Harmonics Signals
-
Upload
paulmacartney -
Category
Documents
-
view
236 -
download
1
Transcript of Harmonics Signals
-
7/29/2019 Harmonics Signals
1/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
IntroductionIntroductiontotoHarmonicsHarmonics
BACKFORWARD
-
7/29/2019 Harmonics Signals
2/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic IssuesHarmonic Issues What are Harmonics?
Where do they come from?
What are the effects of Harmonics? What are the current standards?
How do you measure Harmonics?
How do you know if theres a harmonic problem?
How can they be controlled or eliminated? Common myths and misconceptions
References
FORWARD BACK
-
7/29/2019 Harmonics Signals
3/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Definition of HarmonicsDefinition of Harmonics They are AC currents or voltages at integer multiples
of the fundamental frequency
The fundamental is the lowest frequency in thewaveform, generally the repetition frequency
They cannot transfer power on the average
Harmonics are present in any non-sinusoidalwaveform
More rapid changes in the waveform require thepresence of higher order harmonics
FORWARD BACK
-
7/29/2019 Harmonics Signals
4/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Square Wave Harmonic ContentSquare Wave Harmonic Content
Fund
3
3,5
3,5,7
3,5,7,9
3,5,7,9,11
3,5,7,9,11,13
FORWARD BACK
-
7/29/2019 Harmonics Signals
5/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Sources of HarmonicsSources of Harmonics They arise from non-linear loads in which current is
not strictly proportional to voltage
Linear loads like resistors, capacitors and inductorsdo not produce harmonics
Since diodes and SCRs are non-linear, those circuitsgenerate harmonic currents
Other equipment which causes harmonics:
UPS, rectifiers, transformers, ballasts, welders, arc furnaces, andpersonal computers
FORWARD BACK
-
7/29/2019 Harmonics Signals
6/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
CSI Current WaveformCSI Current Waveform
FORWARD BACK
-
7/29/2019 Harmonics Signals
7/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
PWM Current WaveformPWM Current Waveform
FORWARD BACK
-
7/29/2019 Harmonics Signals
8/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Effects of HarmonicsEffects of Harmonics Reduction of power system efficiency
Increased heating of transformers (K-factor)
Excitation of power system resonances Increased acoustical noise in motors
RFI generation
Interference with sensitive equipment
There are no good effects!
FORWARD BACK
-
7/29/2019 Harmonics Signals
9/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Examples of Sensitive EquipmentExamples of Sensitive Equipment Carrier synchronized clocks
Audio/video recording equipment
Generator regulators and synchronizers Telephone equipment
Fluorescent lights
AM radio receivers
Medical equipment PLCs
FORWARD BACK
-
7/29/2019 Harmonics Signals
10/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic StandardsHarmonic Standards
IEEE-519 1992
Definitions: Voltage total harmonic distortion (VTHD)
Current total harmonic distortion (CTHD) K-Factor
Point of Common Coupling
VTHD Limits, Table 10.2
CTHD Limits, Table 10.3 Dilution by linear loads
There are no Susceptibility Limits!
FORWARD BACK
-
7/29/2019 Harmonics Signals
11/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
THD Definitions from IEEE-519THD Definitions from IEEE-519Voltage Total Harmonic Distortion VTHD
Current Total Harmonic Distortion CTHD
Sum of squares of amplitudes of all voltage harmonics
Sum of squares of amplitudes of all current harmonics
Amplitude of fundamental voltage
Amplitude of fundamental Current
FORWARD BACK
-
7/29/2019 Harmonics Signals
12/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Point of Common CouplingPoint of Common Coupling The point of common coupling is the location in the
power distribution system where harmonic distortionis to be measured, usually where harmonic currents
flow into a bus which feeds other equipment. Itslocation must be specified!
In the absence of a specified location, the POCC forcurrent harmonics is the plant-utility interface
FORWARD BACK
-
7/29/2019 Harmonics Signals
13/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Definition of K-FactorDefinition of K-Factor
K Factor =
S (Square of P.U. Harmonic Current)*(Square of Harmonic Number)
K-Factor theoretically represents the increase in stray losses(conductor eddy currents) in a magnetic component
DITs need to have a K-Factor specification
CSI VFDs typically have a K-Factor of 13 PWM VFDs typically have a K-Factor of 6
FORWARD BACK
BACK
-
7/29/2019 Harmonics Signals
14/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
IEEE 519 Table 10.2IEEE 519 Table 10.2Low Voltage System Classification and Distortion Limits
Special
Applications
General
Systems
Dedicated
Systems
Notch Depth 10% 20% 50%
VTHD 3% 5% 10%
Notch Area 16400 22800 36500
FORWARD BACK
FORWARD BACK
-
7/29/2019 Harmonics Signals
15/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
IEEE 519 Table 10.3IEEE 519 Table 10.3
Current Distortion Limits for General Distribution Systems
Isc/Il < 11(5, 7)11
-
7/29/2019 Harmonics Signals
16/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic AnalysisHarmonic Analysis
Tools and TechniquesTools and Techniques For simple cases, use Short-Circuit Ratio and look up
VTHD on a curve for that product Short Circuit Ratio is the short circuit current at the POCC divided
by the drive rated current
For simple cases, use TURBOSIM to make a moreprecise calculation of VTHD
There is no simple way of getting CTHD short of aspecific calculation
For complex multi-VFD cases, use VFDNET
Watch out for underlying assumptions in thecalculations!
FORWARD BACK
FORWARD BACK
-
7/29/2019 Harmonics Signals
17/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
CSI Voltage Distortion ChartCSI Voltage Distortion Chart
FORWARD BACK
FORWARD BACK
-
7/29/2019 Harmonics Signals
18/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
PWM Voltage Distortion ChartPWM Voltage Distortion Chart
FORWARD BACK
FORWARD BACK
-
7/29/2019 Harmonics Signals
19/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Current Distortion System ExampleCurrent Distortion System Example
FORWARD BACK
FORWARD BACK
-
7/29/2019 Harmonics Signals
20/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Example CalculationExample CalculationVTHD CTHD 5 th 7 th 1 1 th 1 3 th 1 7 th 1 9 th 2 3r d 2 5 th 2 9 th 3 1 s t 3 5 th 3 7 th
DRIVE T YPE
PWM 2.5% LR 2.7 1 5 .4 1 4 .2 4. 88 2 .7 4 1 .2 4 1 .1 6 0 .7 1 0. 6 0. 49 0. 34 0 .3 4 0 .2 3 0 .23
PWM 5% LR 2 1 2 .2 1 1 .5 3 .1 1 2 .2 9 1 .2 4 0 .8 3 0 .6 8 0 .3 8 0 .3 8 0 .2 6 0 .2 3 0 .1 9 0 .1 5
CS I 2.5% LR 4 1 0 .8 7 .88 4 .8 3. 3 2 .5 5 1 .9 9 1 .6 9 1.39 1.2 0 .98 0 .86 0 .71 0 .64
CS I 5% LR 3.1 10.3 7.8 4 .6 9 3 .1 1 2 .3 6 1 .7 6 1 .4 3 1.05 0. 86 0. 64 0 .5 3 0 .3 4 0. 3
CS I 12-Puls e 2.2 4.39 0 0 3.15 2.59 0 0 1.13 0.98 0 0 0.41 0.34
PWM 12-Puls e 1 2.78 0 0 2.4 1.24 0 0 0.41 0.41 0 0 0.19 0.15
Cle a np o we r 0.35 1.35 0.98 0.38 0.38 0.45 0.38 0.26 0.15 0.08 0 0 0.04 0
P e rfe c t Ha rmony 9 0.56 1.3 0 0 0 0 1.03 0.72 0 0 0 0 0.2 0.17
P e rfe c t Ha rmony 15 0.31 0.45 0 0 0 0 0 0 0 0 0.32 0.3 0 0
FORWARD BACK
FORWARD BACK
-
7/29/2019 Harmonics Signals
21/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Current Harmonics of Various DrivesCurrent Harmonics of Various DrivesCTHD5th 7th 11th 13th 17th 19th 23rd 25th 29th 31st 35th 37th
DRIVE TYPE
6-P PWM 2.5% LR 41 37.8 13 7.3 3.3 3.1 1.9 1.6 1.3 0.9 0.9 0.6 0.6
6-P PWM 5% LR 32.6 30.6 8.3 6.1 3.3 2.2 1.8 1 1 0.7 0.6 0.5 0.4
6-P CSI 2.5% LR 28.8 21 12.8 8.8 6.8 5.3 4.5 3.7 3.2 2.6 2.3 1.9 1.7
6-P CSI 5% LR 27.5 20.8 12.5 8.3 6.3 4.7 3.8 2.8 2.3 1.7 1.4 0.9 0.8
CSI 12-Pulse 11.7 0 0 8.4 6.9 0 0 3 2.6 0 0 1.1 0.9
PWM 12-Pulse 7.4 0 0 6.4 3.3 0 0 1.1 1.1 0 0 0.5 0.4
Cleanpower 3.6 2.6 1 1 1.2 1 0.7 0.4 0.2 0 0 0.1 0
Perfect Harmony 9 3.47 0.01 0 0 0 2.75 1.93 0 0 0 0 0.53 0.46
Perfect Harmony 15 1.21 0.01 0 0 0 0 0 0 0 0.85 0.81 0 0
FORWARD BACK
FORWARD BACK
-
7/29/2019 Harmonics Signals
22/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic Analysis GotchasHarmonic Analysis Gotchas Analysis assumes perfect phase and amplitude
balance in the power source!
Cable reactance is neglected unless specified -- it canhave a significant effect on the results
Transformers are assumed to have 5.75% impedanceunless otherwise specified
Pre-existing distortion is neglected -- this can be very
severe on generator sources Power factor correction capacitors are presumed not
to be present unless otherwise specified
FORWARD BACK
FORWARD BACK
-
7/29/2019 Harmonics Signals
23/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic Mitigation TechniquesHarmonic Mitigation Techniques Load segregation
Input Line Reactance
Harmonic Filters Higher Pulse Numbers
Perfect Harmony
Lowest Harmonics are Pulse Number +/- 1
Poor Mans Twelve Pulse
Input Switching Converter Cleanpower VFD
FORWARD BACK
FORWARD BACK
-
7/29/2019 Harmonics Signals
24/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Load SegregationLoad Segregation Load Segregation seeks to connect VFDs and other
harmonic producing loads to the power distributionsystem at the lowest impedance point rather thanconnecting to a higher impedance local bus.
It is frequently accomplished by using a DIT toconnect the drive directly to a medium voltage bus.
It can also include using a UPS to isolate sensitiveequipment.
O
FORWARD BACK
-
7/29/2019 Harmonics Signals
25/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Load SegregationLoad Segregation
FORWARD BACK
-
7/29/2019 Harmonics Signals
26/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Input Line ReactanceInput Line Reactance Input reactance reduces the level of VTHD
It can be added with a DIT or line reactor
It has only a small effect on CTHD It is mandatory on our PWM drives as it is a vital part
of the device protection scheme
If a DIT is used for this purpose it needs to have anappropriate K-Factor
FORWARD BACK
-
7/29/2019 Harmonics Signals
27/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic FiltersHarmonic Filters A filter consisting of L-C-R components can be
designed to meet an harmonic requirement
Filter are specific to the power system characteristicsand must be re-designed for every application
Filters are large, expensive, wasteful of power andtime-consuming to design
They are especially hard to design when an
emergency generator is the source, or when multipleutility feeds are involved
FORWARD BACK
-
7/29/2019 Harmonics Signals
28/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic FilterHarmonic Filter
FORWARD BACK
-
7/29/2019 Harmonics Signals
29/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Higher Pulse NumbersHigher Pulse Numbers Using Higher Pulse Numbers is an effective way to
reduce harmonics.
It reduces the CTHD substantially
Magnetic components are required to provide phase-shifted sources
Additional input conversion devices (thyristors ordiodes are required)
This technique is not affected by power systemimpedance changes.
The Perfect Harmony uses this technique
FORWARD BACK
-
7/29/2019 Harmonics Signals
30/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
2300 VAC
INDUCTION
MOTOR
C3
A1
B1
C1
A2
B2
C2
A3
B3
POWER
CELL
POWER
CELLPOWER
CELL
POWER
CELL
POWER
CELL
POWER
CELL
POWER
CELL
POWER
CELLPOWER
CELL
INPUT POWER
Perfect Harmony CircuitPerfect Harmony Circuit
FORWARD BACK
-
7/29/2019 Harmonics Signals
31/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Perfect Harmony InputPerfect Harmony Input
FORWARD BACK
-
7/29/2019 Harmonics Signals
32/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Poor Mans Twelve-PulsePoor Mans Twelve-Pulse This technique is applicable only where there are a
number of similarly sized VFDs on a bus
About Half of the VFDs are connected through delta-wye DITs, while the other half are connected throughline reactors or delta-delta DITs
The phase shifting effects of the transformers resultsin significant harmonic cancellation of the fifth andseventh harmonic on the primary side
It is more effective for PWM drives than CSIs
FORWARD BACK
-
7/29/2019 Harmonics Signals
33/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Poor Mans 12-PulsePoor Mans 12-Pulse
FORWARD BACK
-
7/29/2019 Harmonics Signals
34/72
Power Quality Drives
ROBICONThe Sine of Quality
Robicon 1997
Input Switching ConvertersInput Switching Converters By using transistor switches on the input, the current
harmonics can be shifted to much higher frequency--typically above 35th harmonic.
They may then be removed by a very small filterintegral to the drive.
This technique results in unity power factor and theability to regenerate power back to the line.
The Cleanpower drive utilizes this technique.
FORWARD BACK
-
7/29/2019 Harmonics Signals
35/72
Power Quality Drives
ROBICONThe Sine of Quality
Robicon 1997
Clean Power CircuitClean Power Circuit
FORWARD BACK
-
7/29/2019 Harmonics Signals
36/72
Power Quality Drives
ROBICONThe Sine of Quality
Robicon 1997
Clean Power Input WaveformClean Power Input Waveform
FORWARD BACK
-
7/29/2019 Harmonics Signals
37/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Clean Power Input WaveformClean Power Input Waveform
2V 10mV 2ms SAVE
FORWARD BACK
-
7/29/2019 Harmonics Signals
38/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Comparison of CTHDsComparison of CTHDs 6-Pulse PWM with 2.5% LR 40%
6-Pulse CSI with 2.5% LR 30%
12-Pulse CSI with %5 DIT 15% 12 Pulse PWM with 5% LR 9%
Cleanpower VFD
-
7/29/2019 Harmonics Signals
39/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic MythsHarmonic Myths
and Misconceptionsand Misconceptions Diode Input circuits cause no harmonics
DITs Prevent Harmonics from Flowing into the powersystem
Higher Order Harmonics (>23) need not beconsidered
FORWARD BACK
-
7/29/2019 Harmonics Signals
40/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
ConclusionsConclusions Harmonic Control is a major issuewith consultants
and customers.
HRG has the Knowledge, Experience, and Productsto deal with any VFD harmonic issue.
We can exploit this advantage because many of ourcompetitors are not so well equipped.
The competition must not be permitted to get away
with avoiding or ignoring the harmonic issues onprojects.
FORWARD BACK
-
7/29/2019 Harmonics Signals
41/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Square Wave HarmonicSquare Wave Harmonic
ContentContentFund
3
3,5
3,5,7
3,5,7,9
3,5,7,9,11
3,5,7,9,11,13
FORWARD BACK
-
7/29/2019 Harmonics Signals
42/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Practical Motor Drive CircuitsPractical Motor Drive Circuits
Almost all motor drive circuits consist of three parts:
A input converter to change the AC to DC;
A DC link to store and filter the DC;
An output inverter to change the DC into AC. Both output voltage and frequency must be controlled together
for motor load.
AC-DCConversion
DC-ACConversion
DC Link
AC Input;
fixed Frequency,
fixed Voltage
AC Output;
variable Frequency,
variable Voltage
MotorCapacitor
or
Inductor
FORWARD BACK
-
7/29/2019 Harmonics Signals
43/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Basic VFD TopologiesBasic VFD Topologies
The line-side converter determines the input
harmonic current and power factor; there is
almost no influence from the inverter, as it is
isolated by the DC line.
There are only two choices of topologies:
Current-Fed
Voltage-Fed circuits. Then, the line-side converter circuit is
determined.
FORWARD BACK
-
7/29/2019 Harmonics Signals
44/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
The Basic AC-DC RectifierThe Basic AC-DC Rectifier
The bridge rectifier is the
workhorse of power
electronics. It is used in 1
phase and 3 phase versions
most commonly.
The output voltage is a DC
voltage equal to 3/ * Vllpk
This is also used as the input
power conversion for PWM
AC drives.
FORWARD BACK
-
7/29/2019 Harmonics Signals
45/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Properties of the Bridge RectifierProperties of the Bridge Rectifier
The positive bus is at the potential of the most positive line voltage,
while the negative bus is at the potential of the most negative line
voltage. (Its like an auction--the highest potential line wins)
The input current is quite distorted, with large fifth and seventh current
harmonics. But since the rate of change of current is low, there are fewhigher order harmonics.
This circuit is used as the building block for multi-phase arrangements
to reduce the current distortion.
The input displacement power factor is uniformly high.
This circuit cannot return energy to the line.
AC and DC side inductors are frequently used to reduce the input
harmonic current.
This is arguably the most basic and inexpensive power conversion unit.
FORWARD BACK
-
7/29/2019 Harmonics Signals
46/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
CommutationCommutation
Ls: Source
inductance
Line Commutation
IaIb
Va
Vb
0 0
Vba
Load
Commutation is the process of transferring current from one switching
element to another.
There are various ways that this is accomplished.
Line commutation: the AC line voltage causes the current to transfer
Forced commutation: Another circuit element acts to transfer the current.
Self commutation: the switching device turns off by itself.
FORWARD BACK
-
7/29/2019 Harmonics Signals
47/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
3-Phase Rectifier Input Current3-Phase Rectifier Input Current
Line-side Reactance OnlyLine-side Reactance Only
FORWARD BACK
-
7/29/2019 Harmonics Signals
48/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
6-Pulse Thyristor Converter6-Pulse Thyristor Converter
Input Current WaveformInput Current Waveform
FORWARD BACK
-
7/29/2019 Harmonics Signals
49/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Current HarmonicsCurrent Harmonics
of Various Drivesof Various DrivesCTHD5th 7th 11th 13th 17th 19th 23rd 25th 29th 31st 35th 37th
DRIVE TYPE
6-P PWM 2.5% LR 41 37.8 13 7.3 3.3 3.1 1.9 1.6 1.3 0.9 0.9 0.6 0.6
6-P PWM 5% LR 32.6 30.6 8.3 6.1 3.3 2.2 1.8 1 1 0.7 0.6 0.5 0.4
6-P CSI 2.5% LR 28.8 21 12.8 8.8 6.8 5.3 4.5 3.7 3.2 2.6 2.3 1.9 1.7
6-P CSI 5% LR 27.5 20.8 12.5 8.3 6.3 4.7 3.8 2.8 2.3 1.7 1.4 0.9 0.8
CSI 12-Pulse 11.7 0 0 8.4 6.9 0 0 3 2.6 0 0 1.1 0.9
PWM 12-Pulse 7.4 0 0 6.4 3.3 0 0 1.1 1.1 0 0 0.5 0.4
Cleanpower 3.6 2.6 1 1 1.2 1 0.7 0.4 0.2 0 0 0.1 0
Perfect Harmony 9 3.47 0.01 0 0 0 2.75 1.93 0 0 0 0 0.53 0.46
Perfect Harmony 15 1.21 0.01 0 0 0 0 0 0 0 0.85 0.81 0 0
FORWARD BACK
-
7/29/2019 Harmonics Signals
50/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Input Switching ConverterInput Switching Converter
FORWARD BACK
-
7/29/2019 Harmonics Signals
51/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Input Switching ConvertersInput Switching Converters
By using transistor switches on the input, the current
harmonics can be shifted to much higher frequency--
typically above 35th harmonic. This is the same
technique used on the output. They may then be removed by a very small filter
integral to the drive.
This technique results in unity power factor (or any
power factor you want) and the ability to regenerate
power back to the line.
FORWARD BACK
-
7/29/2019 Harmonics Signals
52/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Comparison of CurrentComparison of Current
Total Harmonic DistortionTotal Harmonic Distortion 6-Pulse PWM with 2.5% line reactor 40%
6-Pulse CSI with 2.5% line reactor 30%
12-Pulse CSI with %5 DIT 15% 12 Pulse PWM with 5% line reactor 9%
Switching Converter
-
7/29/2019 Harmonics Signals
53/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Twelve-Pulse Bridge RectifierTwelve-Pulse Bridge Rectifier
3-PHASE MV INPUT
INPUT FILTER FORHARMONIC CORRECTION
12 Pulse Rectifier
To Inverter
12recnv
To Inverter
FORWARD BACK
-
7/29/2019 Harmonics Signals
54/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonics of RectifiersHarmonics of Rectifiers
0
5
10
15
20
25
30
35
5 7 11 1 3 17 1 9 2 3 2 5 2 9 3 1 3 5 3 7
P ercent Harm onic Current
6-pu lse: All b a rs
12-pu lse: Black ba rs on ly
FORWARD BACK
-
7/29/2019 Harmonics Signals
55/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
The Controlled RectifierThe Controlled Rectifier
By substituting thyristors for
diodes, we can control the DC
voltage of the rectifier.
In this form, it is usable as a
regulated DC supply like a DCmotor drive.
It also is widely used as the
input stage for variable
frequency AC drives of the
current-fed type.
The output voltage is a functionof the input and the phase delay
of the turn on pulse to the
SCRs.
FORWARD BACK
-
7/29/2019 Harmonics Signals
56/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
12-Pulse Thyristor Converter12-Pulse Thyristor Converter
3-PHASE MV INPUT
INPUT FILTER FOR
POWER FACTOR ANDHARMONIC CORRECTION
12 Pulse Thyristor Converter
To Inverter
12scrcnv
To Inverter
FORWARD BACK
-
7/29/2019 Harmonics Signals
57/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
12-Pulse Thyristor Converter12-Pulse Thyristor Converter
WaveformsWaveforms
FORWARD BACK
-
7/29/2019 Harmonics Signals
58/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonics of ThyristorHarmonics of Thyristor
ConvertersConverters
0
5
10
15
20
25
5 7 11 13 17 19 23 25 29 31 35 37
Percent Harmonic Current
6-pulse: All b ars
12-pulse : Blac k bars only
FORWARD BACK
-
7/29/2019 Harmonics Signals
59/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Voltage-Fed and Current-FedVoltage-Fed and Current-Fed
TopologiesTopologies Voltage-fed and current-fed refer to the two basic VFD
strategies of applying power to the motor. In Europe, these are
called voltage-impressed and current-impressed, which is a
clearer description.
In voltage-fed circuits, the output of the inverter is a voltage,
usually the DC link voltage. The motor and its load determines
the current that flows. The inverter doesnt care what the current
is. (within limits)
In current-fed circuits, the output of the inverter is a current,
usually the DC link current. The motor and its load determinesthe voltage. The inverter doesnt care what the voltage is.
FORWARD BACK
-
7/29/2019 Harmonics Signals
60/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Comparison of Voltage-fed andComparison of Voltage-fed and
Current-fed circuitsCurrent-fed circuits Today, voltage-fed VFDs use a rectifier bridge. This gives them consistently
high P.F. and minimum high-order harmonics. The reactive power needs of the
motor come from the capacitor, and are not reflected to the line. The DC link
electrolytic capacitors can be a reliability and lifetime issue. Energy stored in the
link is very high compared to the CSIs, and a fault in the inverter can lead to
very high currents. The motors inherent inductance can be conveniently used tofilter a PWM voltage wave. On the other hand, very fast wavefronts have
become a concern to motor designers and users.
The preferred approach in current-fed inverters is to use a thyristor converter to
control the current. Thus the power factor is the load power factor times the PU
speed. The reactive power demand of the motor is passed back to the line. High
order harmonics are present due to the high di/dt. Link energy storage is
relatively low, and the DC link reactor provides immunity to faults and grounds.Since the current is regulated, inverter faults do not cause high currents. One
cannot change the motor current instantaneously, so all the CSI circuits require
a capacitive filter on the motor to absorb the high di/dt of the inverter.
FORWARD BACK
-
7/29/2019 Harmonics Signals
61/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
CF versus VF VFDsCF versus VF VFDs
Current-fed Type
Lower Cost at High HP
Four- Quadrant
P.F. = P.U. Speed*Load P.F.96.5% Efficiency
Immune to short circuits
Low-Cost Components
Large Magnetics
Lower motor noise
Non-Critical layout
30% Harmonic Current
Low dV/dt at output
Voltage-fed Type
Lower Cost at Low HP
Two-Quadrant
95% displacement P.F.96-97.5% Efficiency
Requires protection
Higher-cost Components
Small or no Magnetics
Higher Motor Noise
Critical Layout
40% Harmonic current
High dV/dt at output
FORWARD BACK
-
7/29/2019 Harmonics Signals
62/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic StandardsHarmonic Standards
IEEE-519 1992
Definitions:
Voltage total harmonic distortion (VTHD)
Current total harmonic distortion (CTHD) K-Factor
Point of Common Coupling
VTHD Limits, Table 10.2
CTHD Limits, Table 10.3
Dilution by linear loads There are no Susceptibility Limits!
FORWARD BACK
-
7/29/2019 Harmonics Signals
63/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
THD Definitions from IEEE-519THD Definitions from IEEE-519
Voltage Total Harmonic Distortion VTHD
Current Total Harmonic Distortion CTHD
Sum of squares of amplitudes of all voltage harmonics
Sum of squares of amplitudes of all current harmonics
Amplitude of fundamental voltage
Amplitude of fundamental Current
FORWARD BACK
-
7/29/2019 Harmonics Signals
64/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Point of Common CouplingPoint of Common Coupling
The point of common coupling is the location in the
power distribution system where harmonic distortion
is to be measured, usually where harmonic currents
flow into a bus which feeds other equipment. Itslocation must be specified!
In the absence of a specified location, the POCC for
current harmonics is the plant-utility interface
FORWARD BACK
-
7/29/2019 Harmonics Signals
65/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Current DistortionCurrent Distortion
System ExampleSystem Example
FORWARD BACK
-
7/29/2019 Harmonics Signals
66/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Example CalculationExample Calculation
VTHD CTHD 5 th 7 th 1 1 th 1 3 th 1 7 th 1 9 th 2 3r d 2 5 th 2 9 th 3 1 s t 3 5 th 3 7 th
DRIVE T YPE
PWM 2.5% LR 2.7 1 5 .4 1 4 .2 4. 88 2 .7 4 1 .2 4 1 .1 6 0 .7 1 0. 6 0. 49 0. 34 0 .3 4 0 .2 3 0 .23
PWM 5% LR 2 1 2 .2 1 1 .5 3 .1 1 2 .2 9 1 .2 4 0 .8 3 0 .6 8 0 .3 8 0 .3 8 0 .2 6 0 .2 3 0 .1 9 0 .1 5
CS I 2.5% LR 4 1 0 .8 7 .88 4 .8 3. 3 2 .5 5 1 .9 9 1 .6 9 1.39 1.2 0 .98 0 .86 0 .71 0 .64
CS I 5% LR 3.1 10.3 7.8 4 .6 9 3 .1 1 2 .3 6 1 .7 6 1 .4 3 1.05 0. 86 0. 64 0 .5 3 0 .3 4 0. 3
CS I 12-Puls e 2.2 4.39 0 0 3.15 2.59 0 0 1.13 0.98 0 0 0.41 0.34
PWM 12-Puls e 1 2.78 0 0 2.4 1.24 0 0 0.41 0.41 0 0 0.19 0.15
Cle a np o we r 0.35 1.35 0.98 0.38 0.38 0.45 0.38 0.26 0.15 0.08 0 0 0.04 0
P e rfe c t Ha rmony 9 0.56 1.3 0 0 0 0 1.03 0.72 0 0 0 0 0.2 0.17
P e rfe c t Ha rmony 15 0.31 0.45 0 0 0 0 0 0 0 0 0.32 0.3 0 0
FORWARD BACK
-
7/29/2019 Harmonics Signals
67/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Current HarmonicsCurrent Harmonics
of Various Drivesof Various DrivesCTHD5th 7th 11th 13th 17th 19th 23rd 25th 29th 31st 35th 37th
DRIVE TYPE
6-P PWM 2.5% LR 41 37.8 13 7.3 3.3 3.1 1.9 1.6 1.3 0.9 0.9 0.6 0.6
6-P PWM 5% LR 32.6 30.6 8.3 6.1 3.3 2.2 1.8 1 1 0.7 0.6 0.5 0.4
6-P CSI 2.5% LR 28.8 21 12.8 8.8 6.8 5.3 4.5 3.7 3.2 2.6 2.3 1.9 1.7
6-P CSI 5% LR 27.5 20.8 12.5 8.3 6.3 4.7 3.8 2.8 2.3 1.7 1.4 0.9 0.8
CSI 12-Pulse 11.7 0 0 8.4 6.9 0 0 3 2.6 0 0 1.1 0.9
PWM 12-Pulse 7.4 0 0 6.4 3.3 0 0 1.1 1.1 0 0 0.5 0.4
Cleanpower 3.6 2.6 1 1 1.2 1 0.7 0.4 0.2 0 0 0.1 0
Perfect Harmony 9 3.47 0.01 0 0 0 2.75 1.93 0 0 0 0 0.53 0.46
Perfect Harmony 15 1.21 0.01 0 0 0 0 0 0 0 0.85 0.81 0 0
FORWARD BACK
-
7/29/2019 Harmonics Signals
68/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic Analysis GotchasHarmonic Analysis Gotchas
Analysis assumes perfect phase and amplitude balance in the
power source!
Cable reactance is neglected unless specified -- it can have a
significant effect on the results
Transformers are assumed to have 5.75% impedance unless
otherwise specified
Pre-existing distortion is neglected -- this can be very severe on
generator sources
Power factor correction capacitors are presumed not to be
present unless otherwise specified
FORWARD BACK
-
7/29/2019 Harmonics Signals
69/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic FiltersHarmonic Filters
A filter consisting of L-C-R components can be
designed to meet an harmonic requirement
Filter are specific to the power system characteristics
and must be re-designed for every application Filters are large, expensive, wasteful of power and
time-consuming to design
They are especially hard to design when an
emergency generator is the source, or when multiple
utility feeds are involved
FORWARD BACK
-
7/29/2019 Harmonics Signals
70/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Higher Pulse NumbersHigher Pulse Numbers
Using Higher Pulse Numbers is an effective way to
reduce harmonics.
It reduces the CTHD substantially
Magnetic components are required to provide phase-shifted sources
Additional input conversion devices (thyristors or
diodes are required)
This technique is not affected by power systemimpedance changes.
The Perfect Harmony uses this technique
FORWARD BACK
-
7/29/2019 Harmonics Signals
71/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
Harmonic Myths andHarmonic Myths and
MisconceptionsMisconceptions Diode Input circuits cause no harmonics
DITs Prevent Harmonics from Flowing into the power
system
Higher Order Harmonics (>23) need not beconsidered
BACK
-
7/29/2019 Harmonics Signals
72/72
Power Quality Drives
ROBICON The Sine of Quality Robicon 1997
ConclusionsConclusions
Occasionally, VFDs can have an adverse effect on power
quality, severe enough to cause problems with other equipment.
But, there are a number of simple ways to minimize the effect of
a non-linear load.
Beginning in 1992, drive manufacturers have introduced new
technology to overcome these problems.
Today, one can obtain even the largest VFD of a design (Perfect
Harmony and 18-pulse Clean Power) which presents virtually a
linear, unity power factor load to the line.