HARDUAGANJ THERMAL POWER PLANT BY GEETESH SHARMA

66
1 ABOUT UTTAR PRADESH RAJYA VIDYUT UTPADAN NIGAM LTD. UP Rajya Vidyut Utpadan Nigam Ltd. was constituted on 25.08.1980 under the companies act 1956 for construction of new thermal power projects in the state sector. On 14.1.2000, in accordance to up state electricity reforms acts 1999, up state electricity board, till then responsible for generation, transmission and distribution of power within the state of Uttar Pradesh, was unbundled and operations of the state sector thermal power stations was handed over to UPRVUNL. At present 54.09% or 93918.38 MW (Data Source CEA, as on 31/03/2011) of total electricity production in India is from Coal Based Thermal Power Station. A coal based thermal power plant converts the chemical energy of the coal into electrical energy. This is achieved by raising the steam in the boilers, expanding it through the turbine and coupling the turbines to the generators . Today it is looking after operations of five number thermal power plants located in different parts of UP, with a total installed generation capacity of 4683 MW with planting facility as follows. NAMEOFTPS INSTALLED DERATED TOTAL ANPARA TPS 3X210 MW 3X210 MW = 630 MW 1630 MW 2X500 MW 2X500 MW = 1000 MW OBRA TPS 2X50 MW 2X50 MW = 100 MW 1288 MW 2X100 MW 2X94 MW = 18 MW 5X200 MW 5X200 MW = 1000 MW PANKI TPS 2X110 MW 2XI05 MW = 210 MW 210MW PARlCHHA TPS 2X110 MW 2X110 MW = 220 MW 1140 MW HARDUAGANJ 1X60 MW 1X40 MW = 40 MW 415 MW 2X105 MW 2X55MW=110MW 2X250 MW 2X60 MW = 120 MW 1X110 MW 1XI05 MW = 105 MW TOTAL 4683 MW

description

THIS REPORT IS COMPLETED BY GEETESH SHARMA....CONT. NO. 8800980200

Transcript of HARDUAGANJ THERMAL POWER PLANT BY GEETESH SHARMA

  • 1

    ABOUT

    UTTAR PRADESH RAJYA VIDYUT UTPADAN NIGAM LTD.

    UP Rajya Vidyut Utpadan Nigam Ltd. was constituted on 25.08.1980

    under the companies act 1956 for construction of new thermal power

    projects in the state sector. On 14.1.2000, in accordance to up state

    electricity reforms acts 1999, up state electricity board, till then

    responsible for generation, transmission and distribution of power within

    the state of Uttar Pradesh, was unbundled and operations of the state

    sector thermal power stations was handed over to UPRVUNL.

    At present 54.09% or 93918.38 MW (Data Source CEA, as on 31/03/2011) of total electricity production in India is from Coal Based Thermal Power Station. A coal based thermal power plant converts the chemical energy of the coal into electrical energy. This is achieved by raising the steam in the boilers, expanding it through the turbine and coupling the turbines to the generators .

    Today it is looking after operations of five number thermal power plants located in different parts of UP, with a total installed generation capacity of 4683 MW with planting facility as follows.

    NAMEOFTPS INSTALLED

    CAPACITY

    DERATED

    CAPACITY

    TOTAL

    CAPACITY ANPARA TPS 3X210 MW 3X210 MW = 630 MW 1630 MW

    2X500 MW 2X500 MW = 1000 MW

    OBRA TPS 2X50 MW 2X50 MW = 100 MW 1288 MW

    2X100 MW 2X94 MW = 18 MW 5X200 MW 5X200 MW = 1000 MW

    PANKI TPS 2X110 MW 2XI05 MW = 210 MW 210MW

    PARlCHHA TPS 2X110 MW 2X110 MW = 220 MW 1140 MW

    HARDUAGANJ

    TPS

    1X60 MW 1X40 MW = 40 MW 415 MW

    2X105 MW 2X55MW=110MW

    2X250 MW 2X60 MW = 120 MW 1X110 MW 1XI05 MW = 105 MW

    TOTAL

    UPRVUNL

    4683 MW

  • 2

    HARDUAGANJ THERMAL POWER STATION

    PLANT LOCATION

    it is in district ALIGARH about 18 KM from ALIGARH railway station. ALIGARH is on DELHI-KANPUR road/rail rout.

    ABOUT GENERATING UNITS AT HARDUAGANJ THERMAL POWER STATION

    All units of this power station are coal fired thermal power plants,

    having a total generating capacity of 415 mw. The power station

    consists of following units -

    STAGE UNITS INSTALLED DERATED DATE OF ORIGINAL

    NO. CAPACITY CAPACITY COMMISSIONING EQUIPMENT

    MANUFACTURER

    i.

    50 MW Deleted

    ATPS ii. 50 MW Deleted

    iii. 50 MW Deleted

    01 50 MW Deleted 21.04.1968 USSR

    02 50 MW Deleted 23.01.1969 USSR

    BTPS 03 55 MW Deleted Mar.1972 M/S BHARAT HEAVY

    ELECTRICALS LTD.

    04 55 MW Deleted 18.09.1972

    05 60 MW 60 MW 14.05.1977

    CTPS 06 60 MW Deleted 26.10.1977

    07 110 MW 105 MW Aug.1978

    HTPS Extn.

    08 250 MW 250 MW 01.02.2012

    09 250 MW 250 MW 01.02.2012

  • 3

    POWER PLANT DESCRIPTION

    Rankine cycle

    The Rankine cycle is a cycle that converts heat into work. The heat is

    supplied externally to a closed loop, which usually uses water. This

    cycle generates about 90% of all electric power used throughout the

    world, including virtually all solar thermal, biomass, coal and

    nuclearpower plants. It is named after William John MacquornRankine,

    a Scottish polymath and Glasgow University professor. The Rankine

    cycle is the fundamental thermodynamic underpinning of the steam

    engine.

    The four processes in the Rankine cycle

    T-s diagram of a typical Rankine cycle operating between pressures of 0.06bar and

    50bar.

    There are four processes in the Rankine cycle. These states are identified by

    numbers (in brown) in the above Ts diagram.

  • 4

    Process 1-2: The working fluid is pumped from low to high pressure. As the

    fluid is a liquid at this stage the pump requires little input energy.

    Process 2-3: The high pressure liquid enters a boiler where it is heated at

    constant pressure by an external heat source to become a dry saturated

    vapour. The input energy required can be easily calculated using mollier

    diagram or h-s chart or enthalpy-entropy chart also known as steam tables.

    Process 3-4: The dry saturated vapour expands through a turbine, generating

    power. This decreases the temperature and pressure of the vapour, and some

    condensation may occur. Theoutput in this process can be easily calculated

    using the Enthalpy-entropy chart or the steam tables.

    Process 4-1: The wet vapour then enters a condenser where it is condensed

    at a constant temperature to become a saturated liquid.

    In an ideal Rankine cycle the pump and turbine would be isentropic, i.e., the pump

    and turbine would generate no entropy and hence maximize the net work output.

    Processes 1-2 and 3-4 would be represented by vertical lines on the T-S diagram

    and more closely resemble that of the Carnot cycle. The Rankine cycle shown here

    prevents the vapor ending up in the superheat region after the expansion in the

    turbine, [1]

    which reduces the energy removed by the condensers.

    Rankine cycle with reheat

    In this variation, two turbines work in series. The first accepts vapour from the

    boiler at high pressure. After the vapour has passed through the first turbine, it re-

    enters the boiler and is reheated before passing through a second, lower pressure

    turbine. Among other advantages, this prevents the vapour from condensing during

    its expansion which can seriously damage the turbine blades, and improves the

    efficiency of the cycle, as more of the heat flow into the cycle occurs at higher

    temperature.

    Regenerative Rankine cycle

    The regenerative Rankine cycle is so named because after emerging from the

    condenser (possibly as a subcooled liquid) the working fluid is heated by steam

    tapped from the hot portion of the cycle. On the diagram shown, the fluid at 2 is

    mixed with the fluid at 4 (both at the same pressure) to end up with the saturated

    liquid at 7. This is called "direct contact heating". The Regenerative Rankine cycle

    (with minor variants) is commonly used in real power stations.

    Another variation is where bleed steam from between turbine stages is sent to feed

    water heaters to preheat the water on its way from the condenser to the boiler.

  • 5

    These heaters do not mix the input steam and condensate, function as an ordinary

    tubular heat exchanger, and are named "closed feed water heaters".

    The regenerative features here effectively raise the nominal cycle heat input

    temperature, by reducing the addition of heat from the boiler/fuel source at the

    relatively low feed water temperatures that would exist without regenerative feed

    water heating. This improves the efficiency of the cycle, as more of the heat flow

    into the cycle occurs at higher temperature.

  • 6

    POWER PLANT DESCRIPTION-(OVERVIEW)

  • 7

    First of all we send DM water from hotwell to low pressure heater with the help of

    condensate extraction pump. On the suction of L.P. heater the temp of water is

    400C and on the exhaust the temperature of water we got 160

    0C-170

    0C. We take

    steam for heating water in L.P. heater from different stages of turbine.After L.P.

    heater this water goes into deaerator where dissolved gases available in water are

    removed by steam. Now this water goes to high pressure heater through Boiler

    feed pump. B.F.P. send the water into the H.P. heater.We use H.P. heater to

    increase the temperature of water. At the exhaust of H.P. heater water temperature

    becomes 2400C.After this, mixture of water and steam goes through economiser

    where we use flue gases heat to increase the temperature of water. This water is

    send into boiler drum.Boiler drum separates steam from water. From Boiler drum

    water goes into the water wall. In this water wall water converts into saturated

    steam. This saturated steam is send into super heater for becoming superheated

    steam. The temperature of superheated steam raises upto and pressure. After this

    superheated steam goes to turbine and strikes the turbine blades at a very high

    speed. After rotating the turbine, steam temperature and pressure got down. This

    low temperature steam send into the condenser for condensing. After condensing,

    steam changed into water. We collect this water in hotwell and again we use this

    water for making steam through above written process.

    COAL TO ELECTRICITY

    First of all we send pulverised coal in furnace where it burns and its chemical

    energy converts into heat energy. By using this heat energy, water change into

    steam form. This steam have high temperature and pressure. We send this steam

    into turbine through steam line, where steams heat energy convert into turbine

    mechanical energy. Turbine and generator are mounted on the shaft. Due to steam,

    turbines are moving after that generator rotor also got rotary poles are available

    and flux is cut by the rotor due to this electricity form.

    Fuel:- fuel may be defined as a substance which contains hydrogen and carbon

    which on burning with oxygen in atmospheric air produces a large amount of heat.

    The amount of heat generated is known as calorific value of fuel.

  • 8

    Coal Handling And Preparation

    In a coal based power plant coal is transported from coal mines to the power plant by railway in wagons or in a merry-go-round system. Here 4 wagon tipplers are present, 3 in service and 1 in standby. Coal is unloaded from the wagons to a moving underground conveyor belt. This coal from the mines is of no uniform size. So it is taken to the Crusher house and crushed to a size of 20mm. From the crusher house the coal is either stored in dead storage( generally 40 days coal supply) which serves as coal supply in case of coal supply bottleneck or to the live storage(8 hours coal supply) in the raw coal bunker in the boiler house. Raw coal from the raw coal bunker is supplied to the Coal Mills by a Raw Coal Feeder. The Coal Mills or pulverizer pulverizes the coal to 200 mesh size. The powdered coal from the coal mills is carried to the boiler in coal pipes by high pressure hot air. The pulverized coal air mixture is burnt in the boiler in thecombustionzones.Generally in modern boilers tangential firing system is used i.e. the coal nozzles/ guns form tangent to a circle. The temperature in fire ball is of the order of 1300 deg.C. The boiler is a water tube boiler hanging from the top. Water is converted to steam in the boiler and steam is separated from water in the boiler Drum. The saturated steam from the boiler drum is taken to the Low Temperature Superheater, Platen Superheater and Final Superheater respectively for superheating. The superheated steam from the final superheater is taken to the High Pressure Steam Turbine (HPT). In the HPT the steam pressure is utilized to rotate the turbine and the resultant is rotational energy. From the HPT the out coming steam is taken to the Reheater in the boiler to increase its temperature as the steam becomes wet at the HPT outlet. After reheating this steam is taken to the Intermediate Pressure Turbine (IPT) and then to the Low Pressure Turbine (LPT). The outlet of the LPT is sent to the condenser for condensing back to water by a cooling water system. This condensed water is collected in the Hotwell and is again sent to the boiler in a closed cycle. The rotational energy imparted to the turbine by high pressure steam is converted to electrical energy in the Generator.

  • 9

  • 10

    Principal

    Coal based thermal power plant works on the principal of Modified Rankine Cycle.

    i)Fuel preparation system: In coal-fired power stations, the raw feed coal from the coal storage area is first crushed into small pieces and then conveyed to the coal feed hoppers at the boilers. The coal is next pulverized into a very fine powder, so the coal will undergo complete combustion during combustion process.

    ** Pulverizer is a mechanical device for the grinding of

    many different types of materials. For example, they are used to pulverize coal for

    combustion in the steam-generating furnaces of fossil fuel power plants.

    Types of Pulverisers: Ball and Tube mills; Ring and Ball mills; MPS; Ball mill;

    Demolition.

  • 11

    ii)Dryers: they are used in order to remove the excess moisture from coal mainly

    wetted during transport. As the presence of moisture will result in fall in efficiency

    due to incomplete combustion and also result in CO emission.

    iii)Magnetic separators: coal which is brought may contain iron particles. These iron particles may result in wear and tear. The iron particles may include

    bolts, nuts wire fish plates etc. so these are unwanted and so are removed with the

    help of magnetic separators.

    The coal we finally get after these above process are transferred to the storage site.

    Purpose of fuel storage is two

    Fuel storage is insurance from failure of normal operating supplies to arrive.

    Storage permits some choice of the date of purchase, allowing the purchaser

    to take advantage of seasonal market conditions. Storage of coal is primarily

    a matter of protection against the coal strikes, failure of the transportation

    system & general coal shortages.

    WATER TREATEMENT PLANT

  • 12

    Water used in power plant is taken from River. This water is passed

    through gates where screens are placed which remove the floating and

    heavy bodies from the water like wood and fishes.This water is stored in

    pump house from where water is served for different purposes.Then Alum

    is mixed with this water which precipitates the impurity in it and this water is

    then send to clarifier which collect water in a pool.Then this water is passed

    through 1 portable filter and 9 pressure filter.After that water is send to

    Cation exchanger , where positive charged particles are neutralised from

    water by adding Acidic solution to it from Acid storage tank. acid storage

    tanks are present in WTP.Then this water is send to Anion exchanger to

    neutralise negative charged particles from water by adding basic solution to

    it from Alkali storage tank. Alkali storage tank are present in WTP.If then

    also any charge particles left in the water it is neutralised in the mixed

    beds.This water is send to degasifier tower for removing the CO2 generated

    during the process of Anion and Cation removal.

    After these processes DM water is send to the plant.

    Quality of DM water:

    Hardness: Nill

    Ph value: 6.8 to 7.2

    Silica SiO2: less than 0.08 ppm

    Conductivity: 0.5 u mho/cm2

  • 13

    I.D. FAN (Induced Draft Fan).

    Each 250 MW boiler is provided with two 1.0. Fans o, axial KKK BHEL

    make. Each fan is capable of delivering flue gases from the furnace for

    subsequent evacuation through chimney. IG vane is used to shut the damper

    of ID fan so flue gas will not pass through it. It is generally used during

    maintainence.

    Each fan consists:

    1. Suction chamber

    2. Inlet vane control

    3. Impeller supported on two bearing

    4. Outer guide vanes

    5. Diffuser

    6. Flexible coupling

    7. Bearing self aligning roller type

    8. Outlet damper

    F.D. FAN (Forced Draft Fan)

    Each 250 MW boiler is provided with two F.D. Fans,axial KKK BHEL

    make. F.D. fans supplies air for combustion

    process by taking directly atmospheric air. The secondary air after

    pre heating in air heater mixes with the primary air and coal dust

    in the manner to shape the flame and promote rapid mixing for

    proper combustion.

    Each fan consists:

    1. Suction chamber

    2. Inlet vane control

    3. Impeller supported on two bearing

    4. Outer guide vanes

    5. Diffuser

  • 14

    6. Flexible coupling

    7. Bearing self aligning roller type

    8. Outlet damper

    P.A. FAN (Primary Air Fan)

    Each 250 MW boiler is provided with two P.A. Fans of type NDF

    22b, redial KKK BHEL make. This fan handles clean atmospheric air

    which is then created in Ljungstrom Air Preheater the hot primary

    air which comes out of the air preheater scavenges the bowl mill

    and carries the coal particles to the burners. The bowl mills are

    under pressure. A part of the primary cold air is used for regulating

    temperature of hot air entering the bowl mill. A part of the primary

    cold air is used for sealing R.C. Feeder, coal dust lines at the

    discharge end of bowl mills and seal air ring header of mill.

    Each fan consists:

    1. Suction nozzle

    2. Inlet guide vane unit, D-144

    3. Intermediate piece

    4. Impeller

    5. Box-section scroll

    6. Rotor

    7. Bearing

    8. Soft labyrinth seal

    9. Coupling 10. Outlet damper

  • 15

    Condenser

    The condenser condenses the steam from the exhaust of the turbine into liquid to

    allow it to be pumped. If the condenser can be made cooler, the pressure of the

    exhaust steam is reduced and efficiency of the cycle increases. The functions of a

    condenser are:-

    1) To provide lowest economic heat rejection temperature for steam.

    2) To convert exhaust steam to water for reserve thus saving on feed water

    requirement.

    3) To introduce make up water.

    We normally use surface condenser although there is one direct contact condenser

    as well. In direct contact type exhaust steam is mixed with directly with D.M

    cooling water.

    Low pressure heater & high pressure heater

    From hotwell water is send to L.P. heater . Heat of steam ejected by turbine is

    utilised to heat the water before sending it to boiler, so less fuel will be needed to

    make superheated steam . After passing through L.P. heater temperature of

    water becomes 160-1700 C at 135kg/cm2 pressure at exhaust. From L.P. heater

    water is sent to dearetor then boiler feed pump.

    After that, high pressure heaters are used to increase the temperature of water .

    H.P. heaters are used since high pressure will be needed to supply water to the

    boiler at the height of 52m. The mixture of water & steam is then send to

    economiser which further increases its temperature. Water is not converted into

    steam at such a high temperature because of the pressure which is maintained

    from starting otherwise it will be difficult to increase the pressure of steam.

  • 16

    Gland Steam Cooler

    Steam which leak off from glands H.P.T. and I.P.T. is collected in GSC. If quantity

    of steam is less, then it is send to condenser and if more then send to drip pump.

    Deaerator

    A constant pressure deaerator pegged at 7kg/cm2 abs is

    envisaged in turbine cycle installed at 27m level in boiler side to

    provide properly deaerator feed water for boiler, limiting gases

    (mainly oxygen) to O.005ppm. It is a direct contact type heater

    combined with feed storage tank of adequate capacity (87.9m3

    2/3rd

    height storage). The heating steam is normally supplied from

    turbine extractors but during starting and low load operation from

    auxiliary steam station.

    Boiler Feed Pump

    Boiler feed pump takes suction from deaerator and delivers to H.P. heaters.

    Boiler feed pump is a multi stage pump provided for pumping feed water to

    economiser. BFP is the biggest auxiliary equipment after Boiler and Turbine. It

    consumes about 4 to 5 % of total electricity generation.

    Boiler Fill Pump When boiler has to be checked or used for any other use, Boiler Fill Pump is used

    to supply water as it consumes few kilo watts instead of running big auxiliaries like

    Boiler Feed Pump which consume 4 Mega Watt.

  • 17

    Turbine

    The steam turbine is acondensingtendem compound, three

    cylender (H.P., I.P., L.P.) horizontal, disc and diaphragm type with

    nozzle governing and regenerative feed water heating. The L.P.

    turbine is a double flow which incorporates a multi exhaust in

    each flow.

    The high pressure turbine (HPT) comprises of 12 stages, the first stage

    being governing stage the steam flow in HPT being in

    reverse direction, the blade are designed for anti-clock wise

    rotation, when viewed in the direction of steam flow.

  • 18

  • 19

    HP and IP rotors are connected by rigid coupling and have a

    common bearing. The low pressure turbine (LPT) is a double flow

    consisting 4 stages in each.Baumann stage is and present before LPT, It

    dumps majority of steam and majority steam goes to low pressure

    turbine. Steam becomes moist after passing through stages of HPT and

    IPT, so around 400 tonnes of steam is dumped out at Baumann stage.

    Fig.LPT.

    FOR 250MW UNIT LOAD CLASSIFICATION:-

    I.P.T=49%=122.5MW

    H.P.T=31%=77.5MW

    L.P.T=20%=50MW

    EFFICIENCY OF 250MW TURBINE=32.9%

  • 20

    Principle of operation and design

    An ideal steam turbine is considered to be an isentropic process, or constant

    entropy process, in which the entropy of the steam entering the turbine is equal to

    the entropy of the steam leaving the turbine. No steam turbine is truly isentropic,

    however, with typical isentropic efficiencies ranging from 2090% based on the application of the turbine. The interior of a turbine comprises several sets of

    blades, or buckets as they are more commonly referred to. One set of stationary

    blades is connected to the casing and one set of rotating blades is connected to the

    shaft. The sets intermesh with certain minimum clearances, with the size and

    configuration of sets varying to efficiently exploit the expansion of steaTo

    maximize turbine efficiency the steam is expanded, doing work, in a number of

    stages. These stages are characterized by how the energy is extracted from them

    and are known as either impulse or reaction turbines. Most steam turbines use a

    mixture of the reaction and impulse designs: each stage behaves as either one or

    the other, but the overall turbine uses both. Typically, higher pressure sections are impulse type and lower pressure stages are reaction type.

    Impulse turbines

    An impulse turbine has fixed nozzles that orient the steam flow into high speed jets.

    These jets contain significant kinetic energy, which is converted into shaft rotation

    by the bucket-like shaped rotor blades, as the steam jet changes direction. A

    pressure drop occurs across only the stationary blades, with a net increase in

    steam velocity across the stage. As the steamflows through the nozzle its pressure

    falls from inlet pressure to the exit pressure (atmospheric pressure, or more

    usually, the condenser vacuum). Due to this high ratio of expansion of steam, the

    steam leaves the nozzle with a very high velocity. The steam leaving the moving

    blades has a large portion of the maximum velocity of the steam when leaving the

    nozzle. The loss of energy due to this higher exit velocity is commonly called the

    carry over velocity or leaving loss.

  • 21

    Reaction turbines

    In the reaction turbine, the rotor blades themselves are arranged to form

    convergent nozzles. This type of turbine makes use of the reaction force produced

    as the steam accelerates through the nozzles formed by the rotor. Steam is directed

    onto the rotor by the fixed vanes of the stator. It leaves the stator as a jet that fills

    the entire circumference of the rotor. The steam then changes direction and

    increases its speed relative to the speed of the blades. A pressure drop occurs

    across both the stator and the rotor, with steam accelerating through the stator

    and decelerating through the rotor, with no net change in steam velocity across the

    stage but with a decrease in both pressure and temperature, reflecting the work

    performed in the driving of the rotor.

    Operation and maintenance

    When warming up a steam turbine for use, the main steam stop valves (after the

    boiler) have a bypass line to allow superheated steam to slowly bypass the valve

    and proceed to heat up the lines in the system along with the steam turbine. Also, a

    turning gear is engaged when there is no steam to the turbine to slowly rotate the

    turbine to ensure even heating to prevent uneven expansion. After first rotating the

    turbine by the turning gear, allowing time for the rotor to assume a straight plane

    (no bowing), then the turning gear is disengaged and steam is admitted to the

  • 22

    turbine, first to the astern blades then to the ahead blades slowly rotating the turbine at 1015 RPM (0.170.25 Hz) to slowly warm the turbine.

    A modern steam turbine generator installation

    Any imbalance of the rotor can lead to vibration, which in extreme cases can

    lead to a blade breaking away from the rotor at high velocity and being ejected

    directly through the casing. To minimize risk it is essential that the turbine be

    very well balanced and turned with dry steam - that is, superheated steam with a

    minimal liquid water content. If water gets into the steam and is blasted onto the

    blades (moisture carry over), rapid impingement and erosion of the blades can

    occur leading to imbalance and catastrophic failure. Also, water entering the

    blades will result in the destruction of the thrust bearing for the turbine shaft. To

    prevent this, along with controls and baffles in the boilers to ensure high quality

    steam, condensate drains are installed in the steam piping leading to the turbine.

    Turbine should not be run at critical speed.

    4 critical speeds are specified b/w 1200 to 2400 rpm in these generators.

    Speed is increased immediately if rotar rotates at these speeds.

  • 23

    GOVERNING SYSTEM

    Governing system is an important control system in the power plant as it regulates

    the turbine speed, power and participates in the grid frequency regulation.

    Need for governing system The control of a turbine with a governor is essential, as turbines need to be run up

    slowly, to prevent damage while some applications (such as the generation of

    alternating current electricity) require precise speed control. Uncontrolled

    acceleration of the turbine rotor can lead to an over speed trip, which causes the

    nozzle valves that control the flow of steam to the turbine to close. If this fails then

    the turbine may continue accelerating until it breaks apart, often spectacularly.

    Turbines are expensive to make, requiring precision manufacture and special

    quality materials.

    Basic scheme

    Governing system controls the steam flow to the turbine in response to the control

    signals like speed error, power error. It can also be configured to respond to

    pressure error. It is a closed loop control system in which control action

    goes on till the power mismatch is reduced to zero. As shown in the basic

    scheme given in Fig. 1, the inlet steam flow is controlled by the control valve or the

    governor valve. It is a regulating valve. The stop valve shown in the figure a head

    of control valve is used for protection. It is either closed or open. In emergencies

    steam flow is stopped by closing this valve by the protective devices. The electronic

    part output is a voltage or current signal and is converted into a hydraulic

    pressure or a piston position signal by the electro- hydraulic converter (EHC).

    Some designs use high pressure servo valves. The control valves are finally

    operated by hydraulic control valve servo motors.

  • 24

    The steam flow through the control valve is proportional to the valve opening in

    the operating range. So when valve position changes, turbine steam flow changes

    and turbine power output also changes proportionally. Thus governing

    system changes the turbine mechanical power output. In no load

    unsynchronized condition, all the power is used to accelerate the rotor

    only (after meeting rotational losses) and hence the speed changes. When the

    turb ine genera tor uni t i s being s tar ted , governing sys tem

    con trol s the speed precisely by regulating the steam flow. Once the

    unit is synchronized to the power system grid, same control system is used to

    load the machine. As the connected system has very large iner t ia( in f in i te

    bus ) , one machine cannot change the f requency o f the g r id . But i t

    can participate in the power system frequency regulation as part of a group of

    generators that are used for automatic load frequency control. (ALFC).As shown

    in the block diagram, the valve opening changes either by changing the

    reference setting or by the change in speed (or frequency). This is called

    Primary regulation.

    . T h e reference setting can also be changed remotely by power system load

    frequency control. This is called Secondary regulation.

    . Only some generating units in a power system may be used for secondary

    regulation.

  • 25

    3 TYPES OF GOVERNING

    1. Nozzle governing

    2. By pass governing

    3. Throttle governing

    WE are using throttle governing in HADUAGANJ power plant, because in

    this method there are less losses than others.

    Ejectors

    Ejectors are used to create vaccum in turbine condensor. First starting

    ejector sucks air faster but create less vaccum of 500 mmHgcl. Then main

    ejector is used, it sucks slowly but creates more vaccumupto 700 mmHgcl.

    Vaccum is created because steam will not change its phase into water even

    at 450C.

    Also work done P1-P2 becomes more since in vaccum this formula become

    additive,

    i.e. P1-(-P2) = P1+P2

    Another important factor is Latent heat of steam is less in vaccum to change

    from steam to water.

    Gland water cooler valves are filled with water so air would not pass

    through it. GWC is used to supply air when vaccum is not needed in

    condenser.

    EMERGENCY STOP VALVE

    Two emergency stop valve are used with turbine. ESV(Left) and

    ESV(Right)are placed before turbine. When the turbine is in shut down

    condition these valves are closed. Steam will be passed to turbine only after

    opening both ESV(L) and ESV(R).

  • 26

    Turbine Efficiency

    HE = Sensible heat + latent heat + super heat

    EfficiencyRankine = Output/Input = ( HE-HF )/(HE-Ha)

    Ha is the sensible heat of condensate water at point A.

    HE= enthalpy of superheated steam at point E in kCal/kg of steam.

    HF = enthalpy of exhaust steam from L.P. turbine in kCal/kg.

    Mollier chart

    HE = hc + L + Cp(TE-TD)

    Boiler heat rate:- Heat rate is a parameter which monitors the

    performance of boiler/turbine/generator.

    LOSSES:-Lickages, Drain, P.R.D.S. drain, surface losses(not proper insulation),

    condenser, Regenerative system.

    From above it reveals that heat rate of boiler increased performance of turbine

    detoriates.

    Auxiliary P.R.D.S System

    This system is situated in boiler side . A part of the main steam is taken to

    auxiliary steam station and after reducing pressure and temperature. The steam

    is utilised in the following auxiliaries. Initially when unit is lighted up the auxiliary

    P.R.D.S steam is taken from the other running unit by opening the interconnecting

    valve of auxiliary P.R.D.S.

  • 27

    Utilization of auxiliary P.R.D.S. system:-

    (i) Feed water heating in feed water storage tank.

    (ii) Deaerator heating and pressurisation.

    (iii) Main ejectors and starting ejectors.

    (iv) Gland steam cooler.

    (v) Turbine seals.

    (vi) Soot blower.

    (vii) F.O. atomisation at burner level.

    (viii) Steam fracing lines of F.O. lines.

    (ix) Fuel oil heating.

    (x) Steam coiled air pre heater.

    STEAM COIL AIR PREHEATER

    The steam coil air heaters on each at the outlet of F.D. fans are

    used to control the air preheaters cold and temperature of

    corrosion control. Steam coil air heater must be brought into service after

    starting of F.D. fan but before light up of boiler. This can be out only after

    cutting off oil burners from boilers. Air temperature is to be maintained

    below 60-65cby regulating steam inlet to SCAPH.

    BOWL MILL

    The pulverised fuel system adopted for 250MW boilers employs a

    bowl mill by the direct firing system utilizing hot air as dring cum

    transporting medium. A tangential fire system admits the

    pulverised cool together with the air required to combustion

    (secondary air) to the furnace.

    Crushed coal is fed to each pulveriser by its feeder at a rate to suit

    the local dense and primary air is supplied from the primary air

    fans. A portion of the primary air preheated in the air heater. The

  • 28

    hot and cold primary air is proportionally mixed to admission to

    the pulveriser to provide the required drying as indicated by the

    pressure outlet temperature. The total primary air flow may

    constitute from approximately to the total unit combustionair and

    controlled such as to maintain the velocities required to

    transport the coal through the pulveriser and coal piping. Pyrite Hopper

    excretes out the coal which is left unpulverised.

    FUEL

    1. Coal Bituminous Coal

    2. Fixed carbon 36.5%

    3. Volatile matter 25.5%

    4. Moisture 10%

    5. Ash 28%

    6. Hydrogen 34%

    7. Grindability 50 Hard Groove Index (HGI)

    8. High heating valve 4750 kcal/kg

    Bituminous Coal 36.5%

    FURNACE

    Furnace of boiler forms the enclosure for combustion of fuel.This is where the latent heat of vaporisation of water is added.

  • 29

    BOILER

    Boiler is a steam generator which generates the steam at the desired

    rate, pressure and temperature to run prime mover such as Steam

    Turbine in power stations, by burning fuel in the furnace and

    converting chemical energy into thermal energy.Boiler operation is a

    balance between heat flow from combustion of fuel and steam

    generation, in the furnace. It is the most expensive equipment and has

    complicated design, requiring great skill to install and operate.Boiler

    Tube Failure is the main cause of forced outage in electric utility

    steam generating boilers in the whole world.

    The sub critical boiler designed for HARDUAGANJ 250 MW units are of conventional, single drum, natural circulation,radiantdry bottom, balanced draft, reheat type.

    Classification of Boiler

    1) CIRCULATION TYPE:

    a) Natural Circulation Boiler:-Boilers operating below the critical pressure. The natural circulation is based on thermo-siphon

    principle.

    In this system, the flow of water and the water/steam mixture through

    the boiler circuit is produced naturally by the force of gravity due to

    density difference. The water density in the down comers provides the

    driving force that pushes up the less dense water/steam mixture in the

    risers.

    As the pressure increases, the difference in density between water

    and steam reduces thus the hydrostatic head available will not be

  • 30

    able to overcome the frictional resistance for a flow corresponding to

    the minimum requirement of cooling of water wall tubes, Therefore

    natural circulation is limited to boiler with drum operating pressure .

    Circulation Number: - It is the ratio of quantity of water-steam mixture

    flowing through the circuit to the quantity of steam produced in the

    circuit. In other words, if 10 kg of water is circulated for each kg of

    steam generated, the circulation number is 10.Higher circulation

    number reduces the chance of scale formation in evaporating

    surface. At lower operating pressure, circulation ratio increases

    mainly because of the increased difference in density between water

    and steam.

    The general practice adopted for circulation number in various boilers

    is-

    1. Natural circulation industrial boiler 10-15

    2. Natural circulation Utility boiler 7-9

    3. Assisted circulation boiler 2-4

    4. Forced circulation/once through boiler 1

    b) Assisted circulation:-Beyond 175 kg/cm2 this circulation is also termed as Positive circulation in this system circulating water pumps are employed for force movement of water through different circuit of boiler. Generally

    positive circulation is adopted above 182.7 kg/cm2.

    In this type of boilers, since the pressure is high the circulation head caused

    by density difference is too low to cause effective circulation.

    c)Forced Circulation Boiler:- Boilers Operating above critical pressure are

    called super critical Boilers. Above critical pressure, phase transformation is

    absent and hence a once through system is adopted. These boilers are also

    known as once through boilers. A typical operating pressure for such a

    system is 260 kg/cm2. This type of forced circulation requires no boiler drum.

  • 31

    OPERATING PRESSURE

    a) Sub Critical Boiler:-Boilers operating below the critical pressure.

    b) Super Critical Boiler:-Boilers Operating above critical pressure. These

    boilers are necessarily once through type.

    2) FUEL USED:-

    a) Stoker Fired Boiler. b) Pulverised Fuel Fired Boiler. c) Fluidised Bed Combustion Boiler.

    3) DRAUGHT SYSTEM:-

    a) Natural Draught:- The draught required to flow air and gas inside the

    boiler is created by chimney.

    b) Mechanised Draught

    4) Boiler Setting:-

    a) Single Pass Boilers:-All the pressure parts such as super heater, re-heater

    and economiser are arranged as horizontal coils in a single pass of flue gas

    which is the vertical extension of the furnace. These boilers are also known

    as TOWER TYPE BOILERS.

    b) Multi Pass Boilers:-In these boilers, the flue gas passes through more than

    one pass and the pressure parts are distributed in all the passes. Many of the

    electric utility boilers are of two pass.

    Boiler Pressure Parts

    In a steam generator, the parts through which the feed water and steam flows

    above atmospheric pressure are termed as BOILER PRESSURE PARTS. Most

    of the heat released by the fuel in the Boiler is transferred to pressure parts.

  • 32

    The following parts of the Boiler are listed under the category of Boiler pressure

    parts-

    1- Economiser

    2- Boiler Drum

    3- Water wall system

    4- Super-heater

    5- Re-heater

    1- Economiser:--It is situated in 2nd pass of Boiler. Economiser is provided in the Boiler to improve the efficiency of the Boiler by extracting heat from flue

    gases. Before water entering into the evaporating surface of the Boiler, heat

    is added, either in the form of sensible heat or in the form of sensible as

    well as latent heat by the economiser.

    2- Drum and Drum Internals :-Boiler drum is situated on the top of the boiler. The main function of boiler drum is to separate steam from steam-

    water mixture and store the water for evaporator.

    3- Water wall system:-The water walls are tube panels. In water walls, water circulates for steam generation. In the water wall, heat is added to

    evaporate the feed water in the form of saturated steam. The furnace is built

    up of water wall panels for burning the fuel. The water wall panels cover all

    the four sides as well as floor with a opening on only one side for the gases

    to go out of the furnace.

    4- Super Heater:-It is situated in IInd pass of boiler. Super heaters are provided in the boiler to raise the steam temperature above the saturation

    temperature by absorbing heat from flue gases.

    Temperature Control Methods of Super heater

    I. Desuperheating spray control.

    II. Burner tilting. III. Gas bypass dampers. IV. Gas recirculation.

    5. Reheater:- Development of large capacity steam turbines with more number of stages posed a problem of retaining the steam within vapour

    phase till the last stage. In Reheater, the temperature of steam is raised

    after a part of energy is extracted by the steam turbine. This is called as

    reheating of the steam which increases the cycle efficiency.

  • 33

  • 34

    Differences Super Critical Boiler (SBC) & Sub Critical Boiler :-

    Super Critical Boiler (SBC) Sub Critical Boiler

    1. Boiler operates above critical

    pressure.

    Boiler operates below critical

    pressure.

    2. Drum is not provided in this type

    of boilers only separator is used.

    Drum is essential this type of

    boiler for steam separation and

    recirculation Water through

    evaporator.

    3. There is no provision of CBD. Heat is lost through CBD.

    4. MS Temp. around 600 0C. MS Temp. around 540 0C.

    5. Single phase Boiler. Two phase Boiler (water in water

    wall & steam in superheater).

    6. Once through Boiler. Natural circulation Boiler.

    7. Water wall tube temperature rises

    during operation.

    Water wall tube temperature

    constant during whole operation.

    8. Water wall is used to raise the

    temperature of steam. Thermal

    Water wall is used to evaporate

    the water.

    9. Thermal stress is developed in

    water wall tube due to high

    temperature difference.

    Boiler operates at saturation

    temperature in water wall tubes,

    all the circuit is at the same fluid

    temperature.

    10. Spiral wall is used to increase the

    mass flow per tube by reducing

    the number of tubes required to

    envelop the furnace.

    Spiral wall is not used. Vertical

    water wall is used only.

    11. Every water wall tube is the part

    of all four walls.

    Every water wall tube is not the

    part of all four walls.

  • 35

    12. Riffle tube is used in water wall. Plan tube is used in water wall.

    13. Its BFP requires more power

    rating due to restrict flow inside

    riffle tubes.

    Lesser power of BFP is required.

    14. Boiler efficiency is more (around

    93%).

    Boiler efficiency is lower (around

    86%).

    15. Heat rate is lesser. Heat rate is more in comprised to

    SCB.

    16. Boiler is costly. Boiler costs lesser than SCB.

    Boiler Efficiency

    Boiler efficiency is defined as the heat added to the working fluid expressed as a

    percentage of heat in the fuel being burnt. The theoretical limit to boiler efficiency

    is 100%.

    Boiler efficiency depends solely on the boilers ability to burn the fuel and transfer the resulting heat to the water and steam.

    Method of Boiler Efficiency Calculation

    A. Direct Method. B. Indirect Method or Loss Method.

    A. Direct Method :- In this method, the heat supplied to boiler and heat added to the steam in the boiler in given time.

    Boiler Efficiency = (Enthalpy of stm-Enthalpy of feed water)xstm flow

    Qty of coal x C.V.

    = Ws[Cp(T-To)+L+(To-t)

    Mf x C.V.

  • 36

    Where, Ws = Steam flow rate.

    Cp = Specific heat of steam.

    T = S.H. steam temperature.

    To = Saturated temperature of steam.

    L = Latent heat of conversion

    t = Feed water inlet temperature.

    Mf = Fuel burning rate.

    C.V. = Calorific value of fuel.

    The trouble with this method is that several of these quantities are difficult to

    measure particularly coal quantity, the steam quantity and C.V. of coal.

    B. Indirect Method or Loss Method :- The Boiler efficiency is calculated by Heat loss method as -

    BOILER EFFICIENCY = 100 VARIOUS HEAT LOSS

    Boiler Losses :-

    1. Dry flue gas loss.

    2. Wet flue gas loss (moisture in fuel & H2 in fuel).

    3. Moisture in combustion air (in vapour form).

    4. Un-burnt carbon loss (carbon in ash).

    5. Un-burnt gas loss (incomplete combustion of carbon).

    6. Radiation and unaccounted losses.

    High Speed Diesel (Light Oil)

    Light oil required for use with eddy plate oil side ignitors and warm-up oil guns.

    Warming up guns are used during star up the boiler from cold condition when

    steam is not available for heating heavy fuel oil. Worm up oil guns are in service

    till the pressure is raised sufficiently to charge the auxiliary PRDS (Pressure

    Reducing & De-superheating Station), when steam will be available for fuel oil

    heating, tracing and fuel oil atomization.

    Light oil has the advantage of being low viscous at ambient temperatures,

    requires no heating and with low sulphur content. It has negligible carbon reside

    so leaves no soot deposits on the colder heat transfer surfaces.

  • 37

    Ignitors

    Application Star up and coal flame stabilisation.

    No. Of 8 (4 per elevation)

    Capacity 1.5 million cal/hr (6 million BTU/hr)

    Oil firing rate 150 Kg/hr/ignitor.

    Oil pressure at the control

    cabinet

    12.5 to 14 Kg/Cm2g.

    Atomizing air quality L.O.

    (light oil)

    Service air, water free.

    Heavy Fuel Oil System

    In coal fired boiler oil firing is adopted for the purpose of warming up of the

    boiler, imparting stability to the coal flame and low load operation. Efficient or

    complete combustion of fuel oil is best achieved by finer atomizing of oil and

    proper turbulent mixing with combustion air, supplying oil at appropriate

    pressure and temperature are essential requirements for better atomization and

    pumps and heaters are the main auxiliaries for the oil system.

    Heavy fuel oil from storage tank enters the H.O. preheater where it is heated to

    about 115 0C corresponding to an atomizing viscosity. The temperature of H.O.

    from heatingunit is maintained at constant temperature by the automatic

    temperature regulating valve, mounted on auxiliary steam supply line to heaters.

    From the oil preheater oil is left to the boiler through oil delivery line and then

    to each burner. Fuel oil from the oil preheater can be recirculated to return oil

    line from near the boiler front oil heats up the oil lines. At the end of oil supply

    line to burners, a recirculation line with valve for recirculation of fuel oil to the

    return oil line is provided. Fuel oil of 115 0C temperature at boiler front and

    burners can be obtained by recirculation valve. When oil is admitted to each oil

    burner then the recirculation valve is closed. The recirculation valve after last

    burner can be kept slightly open to circulate a small quantity of hot fuel oil to

    prevent solidification of fuel oil at dead ends and to ensure uniform temperature

    of fuel oil in piping. All heavy oil lines are steam traced with steam line to

  • 38

    prevent loss of heat and eventual solidification of heavy oil and to maintain the

    temperature of heavy oil at the required value.

    Technical Data

    Heay Fuel Oil -

    Used for Stabilising coal flame stabilisation

    and low load carrying

    Relevant standard I.S. 1593, 1960.

    Flash point 66 0C.

    Kinematic viscosity at 50 0C

    max.

    120 centistokes.

    Sulphur, total by weight max. 4%

    API gravity 12, SP gravity, 0.986 at 15 0C

    Gross heating value 10270 Kcal/Kg.

    Heay Fuel Oil Guns -

    Application Stabilising coal flame at low load carrying

    hot start up.

    Type Tilting tangential steam atomized, internal

    mixing

    Capacity 25% of boiler MCR per elevation max. 25%

    boiler MCR total in one or two elevations.

    Oil firing rate 33380 kg/hr/gun

    Oil pressure at the gun 8.5 Kg/Cm2g

    Oil viscosity at the atomizing steam

    gun quantity

    16 to 18 centistokessuper heated by 10 15 0C

    Steam consumption 310 kg/hr/gun during normal operation and

    490 kg/hr/gun during scavenging.

    Steam pressure at the gun 9.5 kg/cm(guage).

    Differential pressure between oil

    and steam

    15 psi (1 kg/cm2) steam pressure to be more

    than oil pressure.

    Atomizer nozzle assembly designation mixing plate NB SH spray plate 60 NB.

  • 39

    Ignito Air Fan

    The ignitor air system provides required air to the ignitors at all boiler

    loads. Ignitors require approximately 350scfm of air per ignitor and

    this air is ensured by keeping a 3 differential across the ignitor horn.

    During the boiler start up condition this pressure will not be available

    from the FD fan. For this purpose, system has been provided with

    booster fans called ignitor fan. The ignitor air system is provided with

    two fans in which one is working and the other is standby.

    Air Preheater

    Air preheater is an important boiler auxiliary, which primarily preheats the

    combustion air for rapid and efficient combustion in the furnace. The air heater

    recovers the waste heat from the outgoing flue gases of the boiler and transfers

    the same to the combustion air. The flue gas temperature is 380 0C after leaving

    the economizer, every 20 0C drop in flue gas temperature improves the boiler

    efficiency about 1%.

    Advantage ofAir Preheater:-

    1. Boiler efficiency is increased. 2. More stable combustion in furnace. 3. The combustion is intensified with the use of hot air. 4. Lower grade coal can be burnt efficiently with hot air. 5. The use of hot air improves heat transfer rate and so less heat transfer area is

    required.

    6. Faster load variations are possible. 7. The coal is dried effectively for easy pulverisation and combustion.

  • 40

    Cooling Tower

    Service water is cooled in cooling tower which is used to cool bearings of

    motor/generator etc.

    3 cooling tower pumps are present.

    2 in service and 1 in reserve

    The cooling tower is a semi-enclosed device for evaporative cooling of water by

    contact with air. The hot water coming out from the condenser is fed to the tower

    on the top and allowed to tickle in form of thin sheets or drops. The air flows

    from bottom of the tower or perpendicular to the direction of water flow and then

    exhausts to the atmosphere after effective cooling.

    Cooling tower fan- maintain temperature of water upto 180C. No of fans varies

    with season, maynot needed to run in winter.

    Electrostatic precipitator

    From air preheater this flue gases (mixed with ash) goes to ESP. The precipitator

    has plate banks (A-F) which are insulated from each other between which the flue

    gases are made to pass. ESP has 4 paths and each path contain 6 field i.e. total of

    24 fields. The dust particles are ionized and attracted by charged electrodes. The

    electrodes are maintained at 30KV.Hammering is done to the plates so that fly ash

    comes down and collect at the bottom which is then forwarded through pipe with the help of compressed air. The fly ash is dry form is used in cement manufacture.

  • 41

    Ash slurry pump

    ASP drags fly ash with pipes to the other side of mountain by the force of

    compressed air where ash is collected in bunkers. These are then supplied to the

    Jaypee Cement Factory.

    If ash precipitates in the pipe, water is supplied in the pipes which flows the ash

    with them.

    We use 3 ASP in series of slurry tube. So according to slurry load and pressure

    suitable number of ASP is used.

  • 42

    CHIMNEY

    A chimney is a structure for venting hot flue gases or smoke from a boiler, stove,

    furnace or fireplace to the outside atmosphere. Chimneys are typically vertical, or

    as near as possible to vertical, to ensure that the gases flow smoothly, drawing air

    into the combustion in what is known as the stack, or chimney, effect. The space inside a chimney is called a flue.

    The height of chimneys plays a role in their ability to transfer flue gases using

    stack effect, the dispersion of pollutants at higher altitude helps to ease down its

    influence on surroundings. In the case of chemically aggressive output, the tall

    chimney allows partial or complete self-neutralization of chemicals in the air

    before they reach the ground. The dispersion of pollutants over greater area reduces their concentrations in compliance with regulatory limits.

    Height of chimney is made according to the flue gases venting by it. If the gases are more harmful then the height of chimney is kept more.

  • 43

    250 MW TURBO GENERATOR:-

    DESIGN AND CONSTRUCTIONAL FEATURES OF 250MW TURBO

    GENERATOR

    2.1General-The 250MW Turbo-generator incorporates the modern features of

    direct cooling water and H2 and fast acting excitation system.

    2.2Stator-The stator body is totally enclosed gas tight fabricated structure.

    Hydrogen gas coolers are housed longitudinally inside the stator body. Stator core

    is made up of segmental varnish insulated punching of cold rolled grain oriented

    silicon steel assembled in an inter-leaved manner on core bars. The core consists

    of several packets separated by steel spacers for radial cooling of the core by

    hydrogen and is held in pressed condition by means of heavy non magnetic steel

    press rings bolted to the ends of cold bars. The core bars are designed to provide

  • 44

    elastic suspension of the core in the stator body to isolate the magnetic vibrations

    of stator core from foundation of generator.

    Stator has a three phase double layer short chordate type windings having two

    parallel paths. Each coil side consist of glass insulated soiled and hollow

    conductors with cooling water passing through the later. The elementary

    conductors are rebel transposed in the slot portion of winding to minimise eddy

    losses. The overhang portion of the coils is securely lashed with glass chord to

    bandage rings and special brackets of non magnetic steel which are fixed to core

    press rings.

    Ring type distillate headers of copper supported on insulators are provided

    separately for distillate inlet and outlet in the stator on turbine side .The winding

    ends are solidly soldered into the lugs. The three phase terminals and six neutral

    terminals are brought out to facilitate external connections .

    2.3Rotor-The cylindrical type rotor is forged in one piece (shaft and body) from

    chromium nickel molybdenum steel. The rotor(field) windings is made from hard

    drawn silver bearing copper and is held in position against centrifugal forces by

    duralumin wedges in slot portion and by non magnetic steel regaining rings in the

    over hangs portion.

    The cantering rings are mounted at the end of retaining rings support and prevent

    movement of rotor winding in axial direction due to thermal stresses.

    2.4Hydrogen gas coolers-Four numbers gas coolers are mounted longitudinally

    inside the generator stator body . The gas coolers consists of longitudinally placed

    cooling tubes made out of admiralty brass with coiled copper wire wound outside

    for increasing the cooling surface area. The cooling water flows through the tube

    while the hydrogen comes into contact with external surface of cooling tubes.

    Vent pipes are provided on the slip ring side to remove air from gas coolers while

    filling them with water.

    2.5 Ferquency variation The generator can be operated continuously at rated

    output with a frequency variation (+_) 5% over the rated value. However the

  • 45

    performance of the generator with frequency variation is limited by the turbine

    capability.

    2.6 Temperature of the coolants Not more than 580c and not less than 200c

    temperature of cold gas.

    2.7 Overloading

    2.8 Operation under unbalanced load

    2.9 A-synchronous operation

    3.0 Motoring action Motoring of the turbo-generator is allowed withih the limit

    a ions turbine.

    3.1Operation at reduced hydrogen pressure Continuous operation of the

    generator with hydrogen pressure inside the stator body lower than the rated

    value is not permitted.

    4. STATIC EXCITATION SYSTEM OF 250 MW:-

    Static excitation system has been used in 250 MW unit in order to furnish a

    significant improvement in the overall system stability .This system controls the

    generator voltage by direct variation of the excitation current. Instead of

    conventional rotating converters,the system utilizes static silicon converters

    (thermistors) which are highly efficient and can operate in wide temperature

    range. Due to following advantages .this system has replaced the older ones and is

    being widely used these days.

    (i) Faster response time. (ii) Higher reliability. (iii) Main free performance.

    (iv) no influence due to short circuit in the system.

  • 46

    Hydrogen cooling system:-

    A hydrogen-cooled turbo generator is a turbo generator with gaseous hydrogen

    as a coolant. Hydrogen-cooled turbo generators are designed to provide a low-

    drag atmosphere and cooling for single-shaft and combined-cycle applications in

    combination with steam turbines. Because of the high thermal conductivity and

    other favourable properties of hydrogen gas this is the most common type in its field today.

    The use of gaseous hydrogen as a coolant is based on its properties, namely low

    density, high specific heat, and highest thermal conductivity at 0.168 W/(m.K) of

    all gases; it is 7-10 times better coolant than air. Another advantage of hydrogen is

    its easy detection by hydrogen sensors. A hydrogen-cooled generator can be

    significantly smaller, and therefore less expensive, than an air-cooled one. For stator cooling, water can be used.

    ALTERNATING CURRENT MOTORS

    SERIES AC MOTOR A series ac motor is the same electrically as a dc series motor. Refer to figure 4-1

    and use the left hand rule for the polarity of coils. You can see that the

    instantaneous magnetic polarities of the armature and field oppose each other and

    motor action results. Now, reverse the current by reversing the polarity of the

    input. Note that the field magnetic polarity still opposes the armature magnetic

    polarity. This is because the reversal effects of both the armature and the field. The

    ac input causes these reversals to take place continuously. The construction of the

    ac series motor differs slightly from the dc series motor. Special metals,

    laminations, and windings are used. They reduce losses caused by eddy currents,

    hysteresis, and high reactance. Dc power can be used to drive an ac series motor

    efficiently, but the opposite is not true. The characteristics of a series ac motor are

    similar to those of a series dc motor. It is a varying-speed machine. It has low

    speeds for large loads and high speeds for light loads. The starting torque is very

    high. Series motors are used for driving fans, electric drills, and other small

    appliances. Since the series ac motor has the same general characteristics as the

    series dc motor, a series motor has been designed that can operate both on ac and

    dc. This ac/dc motor is called a universal motor. It finds wide use in small electric

  • 47

    appliances. Universal motors operate at lower efficiency than either the ac or dc

    series motor.

    They are built in small sizes only. Universal motors do not operate on poly phase

    ac power.

    SYNCHRONOUS MOTORS The construction of the synchronous motors is essentially the same as the

    construction of the salient pole alternator. In fact, such an alternator may be run as

    an ac motor. It is similar to the drawing in figure.Synchronous motors have the

    characteristic of constant speed between no load and full load. They are capable of

    correcting the low power factor of an inductive load when they are operated under

    certain conditions. They are often used to drive dc generators. Synchronous motors

    are designed in sizes up to thousands of horsepower. They may be designed as

    either single-phase or multiphase machines. The discussion that follows is based

    on a three-phase design.

    Figure 4-6.Revolving-field synchronous motor.

    Figure 4-7.Self-starting synchronous ac motor.

  • 48

    To start a practical synchronous motor, the stator is energized, but the dc supply to

    the rotor field is not energized. The squirrel-cage windings bring the rotor to near

    synchronous speed. At that point, the dc field is energized. This locks the rotor in

    step with the rotating stator field. Full torque is developed, and the load is driven.

    A mechanical switching device that operates on centrifugal force is often used to

    apply dc to the rotor as synchronous speed is reached.

    The practical synchronous motor has the disadvantage of requiring a dc exciter

    voltage for the rotor. This voltage may be obtained either externally or internally,

    depending on the design of the motor.

    SYNCHRONOUS SPEED is the speed of stator field rotation. It is determined by

    the number of poles and the frequency of the input voltage. Thus, for a given

    motor, synchronous speed is constant.

    SLIP is the difference between actual rotor speed and the synchronous speed in

    induction motors. Slip must exist for there to be torque at the rotor shaft.

    INDUCTION MOTORS

    The induction motor is the most commonly used type of ac motor. Its simple,

    rugged construction costs relatively little to manufacture. The induction motor has

    a rotor that is not connected to an external source of voltage. The induction motor

    derives its name from the fact that ac voltages are induced in the rotor circuit by

    the rotating magnetic field of the stator. The stator construction of the three-phase

    induction motor and the three-phase synchronous motor are almost identical.

    However, their rotors are completely different (see fig. 4-8). The induction rotor is

    made of a laminated cylinder with slots in its surface. The windings in these slots

    are one of two types (shown in fig. 4-9). The most common is the squirrel-cage

    winding. This entire winding is made up of heavy copper bars connected together

    at each end by a metal ring made of copper or brass. No insulation is required

    between the core and the bars. This is because of the very low voltages generated

    in the rotor bars. The other type of winding contains actual coils placed in the rotor

    slots. The rotor is then called a wound rotor.

  • 49

    Figure 4-8.Induction motor.

    Figure 4-9.Types of ac induction motor rotors.

    The rotating magnetic field generated in the stator induces a magnetic field in the

    rotor. The two fields interact and cause the rotor to turn. To obtain maximum

    interaction between the fields, the air gap between the rotor and stator is very

    small.Lenzs law states that any induced emf tries to oppose the changing field that induces it.

    In the case of an induction motor, the changing field is the motion of the resultant

    stator field. A force is exerted on the rotor by the induced emf and the resultant

    magnetic field. This force tends to cancel the relative motion between the rotor and

    the stator field. The rotor, as a result, moves in the same direction as the rotating

    stator field.

  • 50

    It is impossible for the rotor of an induction motor to turn at the same speed as the

    rotating magnetic field. If the speeds were the same, there would be no relative

    motion between the stator and rotor fields; without relative motion there would be

    no induced voltage in the rotor. In order for relative motion to exist between the

    two, the rotor must rotate at a speed slower than that of the rotating magnetic field.

    The difference between the speed of the rotating stator field and the rotor speed is

    called slip. The smaller the slip, the closer the rotor speed approaches the stator

    field speed.

    TRANSFORMER

    A transformer is a static device that transfers electrical energy from one circuit to

    another through inductively coupled conductorsthe transformer's coils without changing its frequency and power on the principle of induction. A varying current

    in the first or primary winding creates a varying magnetic flux in the transformer's

    core and thus a varying magnetic field through the secondary winding. This

    varying magnetic field induces a varying electromotive force (EMF), or "voltage",

    in the secondary winding. This effect is called inductive coupling.

    If a load is connected to the secondary, current will flow in the secondary winding,

    and electrical energy will be transferred from the primary circuit through the

    transformer to the load. In an ideal transformer, the induced voltage in the

    secondary winding (Vs) is in proportion to the primary voltage (Vp) and is given by

    the ratio of the number of turns in the secondary (Ns) to the number of turns in the

    primary (Np) as follows:

    By appropriate selection of the ratio of turns, a transformer thus enables an

    alternating current (AC) voltage to be "stepped up" by making Ns greater than Np,

    or "stepped down" by making Ns less than Np. The windings are coils wound

    around a ferromagnetic core, air-core transformers being a notable

    exception.Transformers are essential for high-voltage electric power transmission,

    which makes long-distance transmission economically practical.

  • 51

    Basic principles

    An ideal transformer. The secondary current arises from the action of the

    secondary EMF on the (not shown) load impedance. The transformer is based on

    two principles: first, that an electric current can produce a magnetic field

    (electromagnetism) and second that a changing magnetic field within a coil of wire

    induces a voltage across the ends of the coil (electromagnetic induction). Changing

    the current in the primary coil changes the magnetic flux that is developed. The

    changing magnetic flux induces a voltage in the secondary coil.

    Autotransformer

    In an autotransformer portions of the same winding act as both the primary and

    secondary. The winding has at least three taps where electrical connections are

    made. An autotransformer can be smaller, lighter and cheaper than a standard dual-

    winding transformer however the autotransformer does not provide electrical

    isolation.

    Autotransformers are often used to step up or down between voltages in the 110-

    117-120 volt range and voltages in the 220-230-240 volt range, e.g., to output

    either 110 or 120V (with taps) from 230V input, allowing equipment from a 100 or

    120V region to be used in a 230V region.

  • 52

    A variable autotransformer is made by exposing part of the winding coils and

    making the secondary connection through a sliding brush, giving a variable turns

    ratio. Such a device is often referred to by the trademark name Variac.

    Instrument transformers

    Instrument transformers are used for measuring voltage and current in electrical

    power systems, and for power system protection and control. Where a voltage or

    current is too large to be conveniently used by an instrument, it can be scaled down

    to a standardized low value. Instrument transformers isolate measurement,

    protection and control circuitry from the high currents or voltages present on the

    circuits being measured or controlled.

    Current transformers, designed for placing around conductors

    A current transformer is a transformer designed to provide a current in its

    secondary coil proportional to the current flowing in its primary coil.

    Voltage transformers (VTs), also referred to as "potential transformers" (PTs), are

    designed to have an accurately known transformation ratio in both magnitude and

    phase, over a range of measuring circuit impedances. A voltage transformer is

    intended to present a negligible load to the supply being measured. The low

    secondary voltage allows protective relay equipment and measuring instruments to

    be operated at a lower voltages.

  • 53

    Different Transformers in Power Station

    Generating Transformer

    Generating Transformer:

    This is the main transformer of generating unit used for stepping up the

    voltage from generating station for the transmission

    In a generating plant for every generating unit one generating transformer is

    required

    Rated voltage on LV side corresponds to the rated generating voltage

    Rated voltage on the HV side corresponds to rated voltage of the HV bus

    Usually these transformers are outdoor type

    LV terminals are connected to the generating terminals via isolated phase

    bus systems

    HV terminals are connected to the outdoor busbars by flexible ACSR

    conductors via overhead flexible bus

    Generator produces electricity which is stepped up to 400 kv before transmission.

    Generating transformer steps up the voltage and decrease the current to reduce i2r

    losses while transmitting supply over a large distance. Also along with losses

    heavy conductors will be needed tocarry heavy current and to support these heavy

    cables heavy towers will beneeded which will increase the overall cost.

    So to minimise the losses and cost during transmission of supply GT is used.

  • 54

    Lightning Arrester: Used for protection of transformer, if lightning falls from sky it will ground the flashover to earth.

    PRV: If internal sparking caused inside GT, gases will expand and increase the pressure inside the transformer. The Pressure Regulating Valvewill operate and

    reduces the pressure.

    Unit auxiliary Transformer

    The Purpose of Unit auxiliary Transformer is to feed power to generator

    auxiliaries of that unit

    These transformers are connected to generators and are used as stepping

    down transformers. The HV side transformer voltage corresponds to the

    voltage of the generating unit and the LV side voltage is stepped down

    Rated KVA of Unit Auxiliary Transformers is approximately 15% of the

    generating rating

    Usually these transformers are outdoor transformers

    One Unit auxiliary transformer is present for every generating unit.

    Station Service Transformer

    In general station service transformer is used for supplying power to

    auxiliary equipment in the power plant when the plant is not generating any

    power.

    Rated HV voltage corresponds to the rated voltage of the outer busbars

    Rated LV voltage corresponds to the auxiliary bus voltage

    Rated KVA corresponds to the load of common auxiliaries of the station.

    This corresponds to the 10% to 15% of the rating of the generating power.

    These transformers are Outdoor type.

  • 55

    Auxiliary Transformers

    These transformers are located in power plant to step down voltage from

    6.6KV to 415V.

    The rating for this transformer corresponds to the rating of the auxiliary load

    it should be bearing.

    These transformers are indoor type and usually dry type transformers are

    used.

    INTERCONNECTING TRANSFORMER

    ICT interconnect ATPS and BTPS switchyard. 220v supply bus from

    ATPS is merged with 440v supply bus from BTPS. And another 6.6kv

    line is taken from ICT to feed auxiliaries. If ATPS generator stop

    working then also some emergency auxiliaries will be working. To feed

    them, supply is taken from BTPS.Both terminals act as input. Power can

    be transmitted from anyside.

    i.e. ATPS to BTPS

    or BTPS to ATPS

  • 56

    Transformer Cooling Methods

    Losses in the transformer are of the order of 1% of its full load kW rating. These

    losses get converted in the heat thereby the temperature of the windings, core, oil

    and the tank rises. The heat is dissipated from the transformer tank and the radiator

    in to the atmosphere. Transformer cooling helps in maintaining the temperature

    rise of various parts within permissible limits. In case of Transformer, Cooling is

    provided by the circulation of the oil. Transformer Oil acts as both insulating

    material and also cooling medium in the transformer. For small rating transformers

    heat is removed from the transformer by natural thermal convection. For large

    rating transformers this type of cooling is not sufficient, for such applications

    forced cooling is used.

    As size and rating of the transformer increases, the losses increase at a faster rate.

    So oil is circulated in the transformer by means of oil pumps. Within the tank the

    oil is made to flow through the space between the coils of the windings.

    Several different combination of natural, forced, air, oil transformer cooling

    methods are available. The choice of picking the right type of transformer cooling

    method for particular appilcatiion depends on the factors such as rating, size, and

    location.

    Transformer Cooling Methods

    Different Transformer Cooling methods are:

    Air Cooling For Dry Type Transformers:

    Air natural Type (A.N.)

    Air Forced type (A.F.)

    Cooling For Oil Immersed Transformers:

    Oil Natural Air Natural Type (O.N.A.N.)

    Oil Natural Air Forced Type (O.N.A.F.)

    Oil Forced Air Natural Type (O.F.A.N.)

    Oil Forced Air Forced Type (O.F.A.F.)

  • 57

    Oil immersed Water Cooling:

    Oil Natural Water Forced (O.N.W.F.)

    Oil Forced Water Forced (O.F.W.F.)

    Oil natural Air Forced Transformer Cooling:

    In this method, air fans are mounted near the Transformer and the forced air is

    directed on to the cooling tubes to increase the rate of cooling. The fans are

    provided with automatic starting. When the temperature of the oil and windings

    increases above a permissible value the thermostats switch on cooling fans. This

    happens during heavy load condition and during higher ambient temperatures.

    In higher rating transformers where the heat dissipation is difficult this type of

    cooling is used. Fans are used to forced and air blast on radiators. Forced air

    cooling increases the heat dissipation rate. In this type of cooling oil circulates by

    natural convection and the blast of air is directed towards the better heat dissipation

    rate.

    Oil Natural and Air Forced Transformer Cooling

  • 58

    Oil Forced Air Forced Transformer Cooling:

    Transformers above 60 MVA employ a combination of Forced Oil and Forced Air

    Cooling. Oil Natural Air Forced type of cooling is not adequate to remove the heat

    caused by the losses which is approximately equal to 1% of the transformer rating

    (0.6MW). In case of Forced Oil and Forced air cooling system a separate cooler is

    mounted away from the transformer tank. This cooler is connected to the

    transformer with pipes at the bottom and the top. The oil is circulated from the

    transformer to the cooler through the pump. The cooler is provided with the fans

    which blast air on the cooling tubes. This type of cooling is provided for the higher

    rating transformers available at the Substations and Power Stations.

    Oil Forced Air Forced Transformer Cooling

    Electrical Interview Questions With Answers

    Site Contains Electrical Interview Questions With Answers.

    Completer portal for Electrical Interviews

  • 59

    SWITCHYARD & ITS EQUIPMENT

    INTRODUCTION:-

    The switchyard is a junction connecting the transmission &

    Distribution system to the power plant.

    Switchyard consist the air insulated aluminium bus type and of the

    high voltage SF6 insulated dead tank circuit breakers arranged in a

    ring bus configuration.

    Each circuit breaker are equipped with a no load breaker, air insulated,

    disconnect switch on each side.

    An isolating disconnect switch are installed in each generator

    transformer connection to the bus.

    In switchyard a power transformer is used to step up or step down the

    voltage.

    Current and voltage transformer are located at points within the

    switchyard to provide for the metering and relaying.

    Control protection and monitoring for the switchyard will be located

    in the switchyard relay room of the electrical building.

    All protection and circuit breaker control will be powered from the

    station battery tn 220v D.C system.

    A grounding grid is provided to control step and touch potentials.

    Lightning protection are provide by shield wires for any overhead

    lines lightning arrestors.

    Interface with SCADA system are provided the communication

    between the facility switchyard and the control building is facilitated.

    Revenue metering are provided on the outgoing lines recording net

    power to or from the switchyard.

    EQUIPMENTS USED IN SWITCHYARD

    (1) BUS BAR

    (2) INSULATOR

    (3) LIGHTNING ARRESTOR

    (4) EARTHING SYSTEM

  • 60

    (5) CONTROL SYSTEM

    (6) TRANSFORMER

    (7) CIRCUIT BREAKRER

    (8) ARCHING HORNS

    (9) SCADA NODES

    (10) ROW

    TYPES OF BUS BAR

    Rigid bus bars:-used for low,md,and high voltage.

    Strain bus bar:-used for high voltages.

    Insulated phase bus bars:-used for medium voltage.

    Sulphuloride bus bar:-used for medium and high voltage system.

    INSULATOR

    Supported the poles and towers in such a way that currents from conductors do not

    flow to earth through these supports.

    CONTROL PANEL

    Control S mostly consists of meters and protective relays. The meters include

    ammeter, voltmeter, wattmeter, energy meter, etc. The relay include fuse failure

    relay, auto reclose relay, check synchronising relay, auxiliary relay and transformer

    relays like OLTC out of step winding temperature alarm, oil temperature alarm.

    The trip indicators included are CB SF6 gas density low, CB Air pressure low, VT

    fuse fail alarm, CB pole disc trip, carrier signal received back up protection, auto

    reclose lock out control DC supply fails distance protection imperative carriers out

    of service, distance protection trip etc.

  • 61

    Circuit Breaker

    A circuit breaker is an automatically operated electric switch designed to protect an

    electrical circuit from damage cause by overload or short circuit. Its function is to

    interrupt continuity to immediately discontinue electrical flaw.

    SULPHUR HEXAFLUORIDE CIRCUIT BREAKERS

    The SF6 is an electro-negative gas and has a strong tendency to absorb free

    electrons .The contacts of the breakers are opened in a high pressure flow of SF6

    gas and an arc is struck between them.The conducting free electrons in the arc are

    rapidly captured by the gas to form relatively immobile ions.

    The advantage of using SF6 circuit breakers :-

    (i) Very short arcing time.

    (ii) Can interrupt much larger currents.

    (iii) Noiseless operation due to its closed gas circuit.

    (iv) No moisture problem.

    (v) Low maintenance cost.

    (vi) No carbon deposits so that tracking and insulating problems are

    eliminated.

  • 62

    Air Blast Circuit Breaker Working

    In the air blast circuit breakers the arc interruption takes place to direct a blast of

    air, at high pressure and velocity, to the arc. Dry and fresh air of the air blast will

    replace the ionized hot gases within the arc zone and the arc length is considerably

    increased. Consequently the arc may be interrupted at the first natural current zero.

    In air blast circuit breakers, the contacts are surrounded by compressed air. When

    the contacts are opened the compressed air is released in forced blast through the

    arc to the atmosphere extinguishing the arc in the process. A compressor plant is

    necessary to maintain high air pressure in the receiver.

  • 63

    In air blast circuit breaker high pressure air is forced on the arc through a nozzle at

    the instant of contact separation. The ionized medium between the contacts is

    blown away by the blast of the air. After the arc extinction the chamber is filled

    with high pressure air, which prevents restrike. In some low capacity circuit

    breakers, the isolator is an integral part of the circuit breaker. The circuit breaker

    opens and immediately after that the isolator opens, to provide addition gap.

    Advantages: How air blast circuit breaker is better than oil circuit breaker:-

    1. The growth of dielectric strength is so rapid that final contact gap needed for arc

    extinction is very small. this reduces the size of device.

    2. The risk of fire is eliminated.

    3. Due to lesser arc energy, air blast circuit breakers are very suitable for

    conditions where frequent operation is required.

    4. The arcing products are completely removed by the blast whereas the oil

    deteriorates with successive operations; the expense of regular oil is replacement is

    avoided.

    5. The energy supplied for arc extinction is obtained from high pressure air and is

    independent of the current to be interrupted.

    6. The arcing time is very small due to the rapid build up of dielectric strength

    between contacts. Therefore, the arc energy is only a fraction that in oil circuit

    breakers, thus resulting in less burning of contacts.

    Disadvantages: 1. Considerable maintenance is required for the compressor plant which supplies

    the air blast.

    2. Air blast circuit breakers are very sensitive to the variations in the rate of

    restriking voltage.

    3. Air blast circuit breakers are finding wide applications in high voltage

    installations. Majority of circuit breakers for voltages beyond 110 kV are of this

    type.

    Aim of electric power supply

    Supply of required amount of power to all consumers overthe entire geographical

    area at all the time continuously.

    Supply energy at lowest cost .

    Maximum possible coverage of geographical area .

  • 64

    Maximum security of supply and minimum fault duration.

    Supply of the power with in the targeted limit of frequency(in case of ac supply).

    Supply with in specified limits of voltages.

    Why DC OVER A.C ?

    Power transfer through an AC Transmission link is given by:-

    Reactive power comes in play.

    Power transfer through the A.C line cant be controlled easily, quickly and

    accurately.

    Losses are high as the reactive power is high .

    Voltage drop will be more.

    HVDC High voltage direct current(HVDC) bulk transmission of electrical power.

    For long distance distribution HVDC system are less expensive and suffer lower

    electrical losses.

    For shorter distances, the higher cost of DC conversion equipment compared to an

    AC system may be warranted where other benifits of direct current links are useful.

    Economic consideration +ve to HVDC Lesser conductors are used as compare to AC

    Lesser losser so better quality.

    Long distance covered.

    Simpler design of towers.

    HV so more security.

  • 65

    Advantages of coal based thermal Power Plant

    They can respond to rapidly changing loads without difficulty A portion of the steam generated can be used as a process steam in

    different industries Steam engines and turbines can work under 25 % of overload continuously Fuel used is cheaper Cheaper in production cost in comparison with that of diesel power stations

    Disadvantages of coal based thermal Power Plant

    Maintenance and operating costs are high Long time required for erection and putting into action A large quantity of water is required Great difficulty experienced in coal handling Presence of troubles due to smoke and heat in the plant Unavailability of good quality coal Maximum of heat energy lost Problem of ash removing

    CONCLUSION

    The electric power plant most importance role in daily life of common

    people and industrial development of nation. Nations progress &

    development is measured by per capita consumption of electricity. It

    changes life style of the people. Thermal power plants supply around

    75% of total power requirement of our country. Considering technical

    feasibility and economical viability the higher capacity thermal power

    plants are now being constructed with sophisticated and complex control

    system.

  • 66

    REFERENCE

    Er. S.K.RANJAN (EE)

    (EED-I, 2*250MW)

    Er. PRADEEP KUMAR (AE)

    (EED-I, 2*250MW)