H3C S3100 Series Ethernet Switches Installation Manual (For Soliton) Hangzhou H3C Technologies Co., Ltd. http://www.h3c.com Manual Version: 20080410-C-1.00

Transcript of H3C S3100 Series Ethernet Switches Installation Manual...

Page 1: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton)

Hangzhou H3C Technologies Co., Ltd.

http://www.h3c.com

Manual Version: 20080410-C-1.00

Page 2: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Copyright © 2008, Hangzhou H3C Technologies Co., Ltd. and its licensors

All Rights Reserved

No part of this manual may be reproduced or transmitted in any form or by any means without prior written consent of Hangzhou H3C Technologies Co., Ltd.

Trademarks

H3C, , Aolynk, , H3Care,

, TOP G, , IRF, NetPilot, Neocean, NeoVTL, SecPro, SecPoint, SecEngine, SecPath, Comware, Secware, Storware, NQA, VVG, V2G, VnG, PSPT, XGbus, N-Bus, TiGem, InnoVision and HUASAN are trademarks of Hangzhou H3C Technologies Co., Ltd.

All other trademarks that may be mentioned in this manual are the property of their respective owners.

Notice

The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute the warranty of any kind, express or implied.

To obtain the latest information, please access:

http://www.h3c.com

Technical Support

[email protected]

http://www.h3c.com

Page 3: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

About This Manual

Related Documentation

In addition to this manual, each H3C S3100 Series Ethernet Switches documentation set includes the following:

Manual Description

H3C S3100 Series Ethernet Switches Operation Manual (For Soliton)

It is used for assisting the users in data configurations and typical applications.

H3C S3100 Series Ethernet Switches Command Manual (For Soliton)

It is used for assisting the users in using various commands.

Organization

H3C S3100 Series Ethernet Switches Installation Manual (For Soliton) is organized as follows:

Chapter Contents

1 Product Introduction Introduces the characteristics and technical specifications of S3100 Series Ethernet Switches.

2 Installation Preparation Introduces the installation preparation and precaution of S3100 Series Ethernet Switches.

3 Installation

Introduces the procedures to install an S3100 Series Ethernet Switch, including the setup of the mainframe, cards and cables.

4 First Power-on

Introduces the booting process of an S3100 Series Ethernet Switch, including the power-on booting of the switch and the system initialization.

5 Boot ROM and Host Software LoadingIntroduces how to load Boot ROM and host software for an S3100 Series Ethernet Switch.

6 Maintenance and Troubleshooting

Introduces the problems that might occur during the installation and the booting of an S3100 Series Ethernet Switch and the related solution.

Page 4: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Chapter Contents

7 Appendix A Lightning Protection of the Switch

Introduces lightning protection of S3100 Series Ethernet Switches.

Conventions

The manual uses the following conventions:

I. GUI conventions

Convention Description

< > Button names are inside angle brackets. For example, click <OK>.

[ ] Window names, menu items, data table and field names are inside square brackets. For example, pop up the [New User] window.

/ Multi-level menus are separated by forward slashes. For example, [File/Create/Folder].

II. Symbols

Convention Description

Warning Means reader be extremely careful. Improper operation may cause bodily injury.

Caution Means reader be careful. Improper operation may cause data loss or damage to equipment.

Note Means a complementary description.

Environmental Protection

This product has been designed to comply with the requirements on environmental protection. For the proper storage, use and disposal of this product, national laws and regulations must be observed.

Page 5: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Table of Contents

i

Table of Contents

Chapter 1 Product Introduction ................................................................................................... 1-1 1.1 Overview ............................................................................................................................ 1-1 1.2 Introduction to S3100 Series Ethernet Switches ............................................................... 1-1

1.2.1 S3100-26TP-EI-W................................................................................................... 1-1 1.2.2 S3100-16TP-EI-W................................................................................................... 1-3 1.2.3 S3100-8TP-EI-W..................................................................................................... 1-5

1.3 Introduction to Front Panel LEDs....................................................................................... 1-6 1.3.1 Power LED .............................................................................................................. 1-6 1.3.2 Auto-Sensing 10/100BASE-TX Ethernet Port Status LED ..................................... 1-7 1.3.3 1000 Mbps Uplink Port Status LED......................................................................... 1-8

1.4 Technical Specifications .................................................................................................... 1-8 1.5 SFP Modules Supported by S3100 Series Ethernet Switches.......................................... 1-9

Chapter 2 Installation Preparation............................................................................................... 2-1 2.1 Precautions ........................................................................................................................ 2-1 2.2 Requirements on Environment .......................................................................................... 2-1

2.2.1 Temperature/Humidity Requirements ..................................................................... 2-1 2.2.2 Cleanness Requirements........................................................................................ 2-2 2.2.3 Anti-interference Requirements .............................................................................. 2-3 2.2.4 Laser Usage Security.............................................................................................. 2-3

2.3 Installation Tools ................................................................................................................ 2-3

Chapter 3 Installation.................................................................................................................... 3-1 3.1 Installing a Switch .............................................................................................................. 3-1

3.1.1 Cabinet Mounting .................................................................................................... 3-1 3.1.2 Desk Mounting ........................................................................................................ 3-6 3.1.3 Wall Mounting.......................................................................................................... 3-6 3.1.4 Magnet Mounting..................................................................................................... 3-8

3.2 Connection of Power Cable and Grounding Cable.......................................................... 3-11 3.2.1 Connecting AC Power Cable ................................................................................ 3-11 3.2.2 Connecting DC Power Cable ................................................................................ 3-12 3.2.3 Connecting Grounding Cable................................................................................ 3-13

3.3 Connecting Optical Fiber ................................................................................................. 3-16 3.4 Connection of Console Cable .......................................................................................... 3-16

3.4.1 Console Cable....................................................................................................... 3-16 3.4.2 Connecting Console Cable ................................................................................... 3-17

3.5 Installation Verification..................................................................................................... 3-17

Chapter 4 First Power-on.............................................................................................................. 4-1 4.1 Establishing Configuration Environment............................................................................ 4-1

Page 6: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Table of Contents

ii

4.2 Connecting the Console Cable .......................................................................................... 4-1 4.3 Setting Terminal Parameters ............................................................................................. 4-1 4.4 Booting Switch ................................................................................................................... 4-4

4.4.1 Checking Before Powering on the Switch............................................................... 4-4 4.4.2 Powering on the Switch........................................................................................... 4-4 4.4.3 Changing the Startup Mode .................................................................................... 4-6

Chapter 5 Boot ROM and Host Software Loading ..................................................................... 5-1 5.1 Introduction to Loading Approaches.................................................................................. 5-1 5.2 Local Software Loading ..................................................................................................... 5-1

5.2.1 Boot Menu............................................................................................................... 5-2 5.2.2 Loading Software Using XModem Through Console Port ...................................... 5-3 5.2.3 Loading Software Using TFTP Through Ethernet Port ........................................... 5-8 5.2.4 Loading Software Using FTP Through Ethernet Port ............................................. 5-9

5.3 Remote Software Loading ............................................................................................... 5-11 5.3.1 Remote Loading Using FTP.................................................................................. 5-11 5.3.2 Remote Loading Using TFTP................................................................................ 5-13

Chapter 6 Maintenance and Troubleshooting ............................................................................ 6-1 6.1 Software Loading Failure................................................................................................... 6-1 6.2 Missing Password.............................................................................................................. 6-1

6.2.1 Missing user password............................................................................................ 6-1 6.2.2 Missing Boot ROM Password ................................................................................. 6-2

6.3 Power System Failure........................................................................................................ 6-2 6.4 Configuration System Failure ............................................................................................ 6-2

Page 7: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 1 Product Introduction

1-1

Chapter 1 Product Introduction

1.1 Overview

H3C S3100 Series Ethernet Switches are high-performance, high-density, easy-to-install, NMS-manageable intelligent Ethernet switches which support wire-speed Layer 2 switching.

Table 1-1 lists the models of H3C S3100 Series Ethernet Switches.

Table 1-1 Models of H3C S3100 Series Ethernet Switches

Model Power supply

Number of 10/100 Mbps

electrical ports

1000 Mbps uplink ports

Number of console

ports

S3100-26TP-EI-W AC and +12V RPS DC 24 2 Combo

ports 1

S3100-16TP-EI-W 16 2 Combo ports 1

S3100-8TP-EI-W AC

8 1 Combo port 1

1.2 Introduction to S3100 Series Ethernet Switches

1.2.1 S3100-26TP-EI-W

I. Front panel

S3100-26TP-EI-W Ethernet switches each provide twenty-four auto-sensing 10/100/1000Base-TX Ethernet ports, two 10/100/1000BASE-T Ethernet ports, two 100/1000Base-X SFP ports, and one console port. Each SFP port and the corresponding 10/100/1000BASE-T Ethernet port form a Combo port. For each Combo port, either the SFP port or the corresponding 10/100/1000BASE-T Ethernet port can be used at a time.

Figure 1-1 shows the front panel of an S3100-26TP-EI-W Ethernet switch.

Page 8: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 1 Product Introduction

1-2

(1) (2) (3) (4) (5)

(6)(7)(8)(9)

(1) Auto-sensing 10/100Base-TX Ethernet port status LED (2) Link LED for Combo port (3) Console port (4) Power LED (PWR) (5) RPS DC power LED (6) A/L LED (7) D/S LED (8) Mode button (9) Active LED for Combo port

Figure 1-1 Front panel of an S3100-26TP-EI-W Ethernet switch

Note:

For details about LEDs on the front panel, refer to section 1.3 “Introduction to Front Panel LEDs”.

II. Rear panel

Figure 1-2 shows the rear panel of an S3100-26TP-EI-W Ethernet switch.

(1) (2) (3)

(1) AC power socket (2) RPS DC power socket (3) Grounding screw

Figure 1-2 Rear panel of an S3100-26TP-EI-W Ethernet switch

III. Power system

S3100-26TP-EI-W Ethernet switches can adopt AC input, or RPS 12 VDC input, or both to provide backup. Only the recommended RPS can be used.

AC input:

Rated voltage range: 100 VAC to 240 VAC, 50 Hz/60 Hz Input voltage range: 90 VAC to 264 VAC, 47 Hz to 63 Hz

Page 9: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 1 Product Introduction

1-3

RPS DC input:

Rate voltage range: 10.8 VDC to 13.2 VDC

IV. Cooling system

S3100-26TP-EI-W Ethernet switches cool off naturally.

1.2.2 S3100-16TP-EI-W

I. Front panel

S3100-16TP-EI-W Ethernet switches each provide sixteen auto-sensing 10/100Base-TX Ethernet ports, two 10/100/1000Base-T Ethernet ports, two 100/1000Base-X SFP ports, and one console port. Each SFP port and the corresponding 10/100/1000BASE-T Ethernet port form a Combo port. For each Combo port, either the SFP port or the corresponding 10/100/1000BASE-T Ethernet port can be used at a time.

Figure 1-3 shows the front panel of an S3100-16TP-EI-W Ethernet switch.

(1) (2) (3) (4)

(5)(6)(7)(8)

(1) Auto-sensing 10/100Base-TX Ethernet port status LED (2) Link LED for Combo port (3) Console port (4) Power LED (PWR) (5) A/L LED (6) D/S LED (7) Mode button (8) Active LED for Combo port

Figure 1-3 Front panel of an S3100-16TP-EI-W Ethernet switch

Note:

For details about LEDs on the front panel, refer to section 1.3 “Introduction to Front Panel LEDs”.

II. Rear panel

Figure 1-4 shows the rear panel of an S3100-16TP-EI-W Ethernet switch.

Page 10: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 1 Product Introduction

1-4

(1) (2)

(1) AC power socket (2) Grounding screw

Figure 1-4 Rear panel of an S3100-16TP-EI-W Ethernet switch

III. Side panel

Each S3100-16TP-EI-W Ethernet switch provides a security slot, through which you can lock the device together with an irremovable object to prevent theft.

The security slot is located at the rear end of the left side panel, as shown in Figure 1-5.

(1)

(1) Security slot

Figure 1-5 Security slot on left side panel of an S3100-16TP-EI-W Ethernet switch

Note:

If the left screw hole above the security slot is used, the security slot cannot be used.

IV. Power system

S3100-16TP-EI-W Ethernet switches:

Rated voltage range: 100 VAC to 240 VAC, 50/60Hz Input voltage range: 90 VAC to 264 VAC, 47Hz to 63Hz

Page 11: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 1 Product Introduction

1-5

V. Cooling system

S3100-16TP-EI-W Ethernet switches cool off naturally.

1.2.3 S3100-8TP-EI-W

I. Front panel

S3100-8TP-EI-W Ethernet switches each provide eight auto-sensing 10/100Base-TX Ethernet ports, one 10/100/1000Base-T Ethernet port, one 100/1000Base-X SFP port, and one console port. The SFP port and the 10/100/1000BASE-T Ethernet port form a Combo port. Either the SFP port or the 10/100/1000BASE-T Ethernet port can be used at a time.

Figure 1-6 shows the front panel of an S3100-8TP-EI-W Ethernet switch.

(1) (2) (3) (4)

(5)(6)(7)(8)

(1) Auto-sensing 10/100Base-TX Ethernet port status LED (2) Link LED for Combo port (3) Console port (4) Power LED (PWR) (5) A/L LED (6) D/S LED (7) Mode button (8) Active LED for Combo port

Figure 1-6 Front panel of an S3100-8TP-EI-W Ethernet switch

Note:

For details about LEDs on the front panel, refer to section 1.3 “Introduction to Front Panel LEDs”.

II. Rear panel

Figure 1-7 shows the rear panel of an S3100-8TP-EI-W Ethernet switch.

Page 12: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 1 Product Introduction

1-6

(1) (2)

(1) AC power socket (2) Grounding screw

Figure 1-7 Rear panel of an S3100-8TP-EI-W Ethernet switch

III. Side panel

Each S3100-8TP-EI-W Ethernet switch provides a security slot, through which you can lock the device together with an irremovable object to prevent theft.

The security slot is located at the rear end of the left side panel, as shown in Figure 1-5.

Note:

If the left screw hole above the security slot is used, the security slot cannot be used.

IV. Power system

S3100-8TP-EI-W Ethernet switches:

Rated voltage range: 100 VAC to 240 VAC, 50/60Hz Input voltage range: 90 VAC to 264 VAC, 47Hz to 63Hz

V. Cooling system

S3100-8TP-EI-W Ethernet switches cool off naturally.

1.3 Introduction to Front Panel LEDs

1.3.1 Power LED

Table 1-2 Description of the power LED on S3100 series

LED Mark on the panel Status Description

ON The switch is powered on. Power LED PWR

OFF The switch is powered off.

ON DC input is normal. RPS DC power LED RPS

OFF There is no DC input.

Page 13: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 1 Product Introduction

1-7

Note:

Only S3100-26TP-EI-W Ethernet switches have an RPS DC power LED.

1.3.2 Auto-Sensing 10/100BASE-TX Ethernet Port Status LED

There are two port status LEDs on both sides (yellow LED on the left and green LED on the right) of each 10/100BASE-TX Ethernet port of S3100 series. They indicate the active, link, duplex, and speed statuses of the port.

In addition, there are an A/L LED and a D/S LED on each model of S3100 series. These two LEDs indicate the mode of the port status LEDs. When the A/L LED is on, the port status LEDs respectively indicate the active status and link status of ports. When the D/S LED is on, the port status LEDs respectively indicate the duplex status and speed status of ports. Either the A/L LED or the D/S LED is on at a specific time. For details, see Table 1-3.

Table 1-3 Description of port status LEDs on S3100 series

Port status mode LED Port status LED Description

BLINKING

The port is in the active state and there is traffic on the port. Yellow LED

(left) OFF The port is in the active state but there is

no traffic on the port.

ON The port is connected properly.

The A/L LED is on

Green LED (right) OFF The port is not connected or is incorrectly

connected.

ON The port operates in the full duplex mode.Yellow LED (left) OFF The port operates in the half duplex mode.

ON The port rate is 100 Mbps. The D/S LED is on

Green LED (right) OFF The port rate is 10 Mbps.

You can switch the mode of the port status LEDs by pressing the Mode button. After a switch is powered on, the A/L LED is on initially. If you press the Mode button, the D/S LED will be on. After that, if you press the Mode button again within 45 seconds, the A/L LED will be on again. Otherwise, the A/L LED will automatically be on 45 seconds later.

Page 14: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 1 Product Introduction

1-8

1.3.3 1000 Mbps Uplink Port Status LED

Table 1-4 Description of 1000 Mbps uplink port status LED on S3100 series

LED Mark on the panel Status Description

ON The port is connected properly. 1000 Mbps uplink port link LED LINK

OFF The port is not connected or is incorrectly connected.

BLINKING The port is in the active state and there is traffic on the port. 1000 Mbps uplink

port active LED ACT OFF The port is in the active state but

there is no traffic on the port.

1.4 Technical Specifications

Table 1-5 Technical specifications for S3100 Series Ethernet switches

Model S3100-26TP-EI-W S3100-16TP-EI-W S3100-8TP-EI-W

Physical dimensions (H x W x D)

43.6 x 440 x 260 mm (1.7 x 17.2 x 10.2 in)

43.6 x 300 x 220 mm (1.7 x 11.8 x 8.7 in)

43.6 x 230 x 200 mm (1.7 x 9.1 x 7.9 in)

Weight <3.5 kg (7.7 lb) <2.5 kg (5.5 lb) <1.8 kg (4 lb)

Number of fixed ports

24 x auto-sensing 10/100BASE-TX Ethernet port 2 x 1000 Mbps Combo port

16 x auto-sensing 10/100BASE-TX Ethernet port 2 x 1000 Mbps Combo port

8 x auto-sensing 10/100BASE-TX Ethernet port 1 x 1000 Mbps Combo port

Number of management port

1 x console port

Power system

S3100-16TP-EI-W/S3100-8TP-EI-W Ethernet switches support only AC input. S3100-26TP-EI-W AC-powered switches support AC input and RPS DC input. AC input:

Rated voltage range: 100 VAC to 240 VAC, 50/60 Hz Maximum voltage range: 90 VAC to 264 VAC, 47 Hz to 63Hz

RPS DC input: Rated voltage range: 10.8 VDC to 13.2 VDC

PoE (as powered device)

Not supported Not supported Not supported

Page 15: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 1 Product Introduction

1-9

Model S3100-26TP-EI-W S3100-16TP-EI-W S3100-8TP-EI-W

System power consumption (full load)

22 W 17 W 14 W

Fan None None None

Operating temperature 0°C to 45°C (30°F to 113°F)

Relative humidity (non- condensing)

10% to 90%

1.5 SFP Modules Supported by S3100 Series Ethernet Switches

The front panel of S3100 Ethernet switches provides one or two 1000 Mbps SFP ports in which you can select the required small form-factor pluggable (SFP) modules to insert. For the models of SFP modules, see Table 1-6.

Table 1-6 SFP modules supported by S3100 Series Ethernet switches

Type Model

100 Mbps SFP module SFP-FE-SX-MM1310-A SFP-FE-LX-SM1310-A

1000 Mbps SFP module SFP-GE-SX-MM850-A SFP-GE-LX-SM1310-A

SFP stack module SFP-STACK-Kit

100 Mbps bidirectional (BIDI) module

SFP-FE-LX-SM1310-BIDI SFP-FE-LX-SM1550-BIDI

SFP module

1000 Mbps BIDI module SFP-GE-LX-SM1310-BIDI SFP-GE-LX-SM1490-BIDI

Note:

The types of SFP modules may vary over time. Consult H3C marketing personnel or technical support personnel to obtain the latest information about SFP modules.

For specifications of SFP modules, refer to H3C Low End Series Ethernet Switches Pluggable Module Manual.

Page 16: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 2 Installation Preparation

2-1

Chapter 2 Installation Preparation

2.1 Precautions

To avoid any device impairment and body injury resulting from improper use, please take the following precautions:

Before cleaning the switch, disconnect the power. Do not clean the switch with wet cloth or liquid.

Keep the switch away from water or dampness. Prevent water or moisture from entering the switch chassis.

Do not place the switch on an unstable case or desk, because the switch might be damaged severely in case of a fall.

Keep the switch room drafty and the switch ventilation hole free of obstruction. The switch can operate normally only under correct voltage input. Make sure that

the operating voltage is consistent with that labeled on the switch. To prevent electric shock, do not open the chassis while the switch is operating,

and do not open the chassis arbitrarily even when the switch is powered off. Before changing interface cards, wear an ESD-preventive wrist strap to prevent

the cards from being damaged by electrostatic discharge.

2.2 Requirements on Environment

S3100 Series Ethernet Switches must be used indoors. When you install your switch in a cabinet or on a desk, you must ensure:

Enough space is reserved near the air-intake hole and the ventilation hole of the switch for heat dissipation of the switch chassis.

The cabinet or the workbench takes good ventilation and heat dissipation system. The cabinet or the desk is solid enough to bear the weight of the switch and the

accessories. The cabinet or the desk is well grounded.

To ensure normal operation and to prolong the life span of the switch, the following requirements on the installation site must also be satisfied.

2.2.1 Temperature/Humidity Requirements

You should keep your equipment room within the proper temperature and humidity ranges to ensure the normal operation and working life of your switch. If the humidity in the equipment room is too high for a long time, it may decrease the insulation attribute of insulating material or even cause electric leakage of insulating material, and, sometimes, may change the mechanical performance of material and cause the

Page 17: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 2 Installation Preparation

2-2

rustiness and corrosion of metal parts. If the relative humidity is too low, the captive screws may become loose due to the shrinking of insulation washers; in addition, electrostatic is more likely to be produced in a dry environment, which may damage the circuit of the switch. High temperature may cause even greater damage to the switch. High temperature for a long time will speed up the aging of insulation material, greatly lower the reliability of the switch and greatly reduce the life span of the switch.

For the temperature and humidity requirements of different models, refer to section 1.4 “Technical Specifications”.

2.2.2 Cleanness Requirements

Dust is a potential hazard to the safe operation of the switch. Falling on the equipment, it may cause electrostatic adsorption, and hence result in poor contact of the metal connectors or connection points. This is more likely to happen when the indoor relative humidity is low; in this case, it may not only shorten the device’s working life, but also incur communication failure. The requirements on dust content and particle diameter in the equipment room are shown in the following table:

Table 2-1 Requirements on dust content in the equipment room

Physical active substance Unit Content

Dust particle particle/m³ ≤ 3 x 104 (No visible dust on desk in three days)

Note: Dust particle diameter ≥ 5µm

Besides the requirements on dust, rigorous requirements are also set on the content of chloride, acid, and sulfide in the air of the equipment room. These kinds of harmful gas will accelerate metal corrosion and aging of certain parts. The equipment room should be protected from the intrusion of harmful gases such as SO2, H2S, NH3 and Cl2. The limits of these kinds of harmful gas are shown in the following table.

Table 2-2 Limits on harmful gas in the equipment room

Gas Max content (mg/m³)

SO2 0.2

H2S 0.006

NH3 0.05

Cl2 0.01

Page 18: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 2 Installation Preparation

2-3

2.2.3 Anti-interference Requirements

A switch in use may be affected by the interference from outside the system by way of capacitance coupling, inductance coupling, electromagnetic radiation, public impedance (including the grounding system) coupling or conducting line (power line, signaling line, and transmission line). Therefore, you should pay attention to the following:

If AC supply system is TN system, AC power socket should be a single-phase three-line power socket with Protection Earth (PE) so that the filter circuit on the equipment can effectively filter out the interference coming from the power supply system.

Keep the switch far away from high-power radio transmitters, radars, and high-frequency heavy-current devices.

Adopt electromagnetic shielding measure if necessary. For example, you can adopt shielded interface cable.

Wire interface cables indoors. Do not wire cables outdoors in case that over-voltage and over-current damage the device.

2.2.4 Laser Usage Security

S3100 Series Ethernet Switches are category-1 laser equipment.

Caution:

When an optional interface card of the S3100 Series Ethernet Switches is operating, avoid staring into the optical interface because the high-energy laser beam emitted from the optical fiber may hurt your eyes.

2.3 Installation Tools

Phillips screwdriver Flat-blade screwdriver ESD-preventive wrist strap

Page 19: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 2 Installation Preparation

2-4

Caution:

These installation tools are not shipped with S3100 Series Ethernet Switches. You will have to prepare them beforehand.

Page 20: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-1

Chapter 3 Installation

Caution:

On a mounting screw of the chassis of H3C S3100 Series Ethernet Switches, there is a seal labeled with H3C. You must keep it intact before asking the agent to maintain the switch. You must get the permission of the local agent before you can open the chassis. Otherwise, you will be responsible for irreversible damages caused by your operations.

3.1 Installing a Switch

3.1.1 Cabinet Mounting

You can install a switch into a 19-inch standard cabinet in one of the following ways:

Use front mounting ears Use front mounting ears and a tray Use front mounting ears and guide rails

The installation methods of a switch depend on the depth and width of the switch. For the specific installation methods, see Table 3-1.

Table 3-1 Installation methods for S3100 switches

Model Use front mounting ears

Use front mounting ears and

a tray

Use front mounting ears and guide rails

S3100-26TP-EI-W √ √ √

S3100-16TP-EI-W √ √ —

S3100-8TP-EI-W √ √ —

Note:

When the depth of a switch is greater than 300 mm (11.8 in), the front mounting ears only secure the switch rather than bear its weight.

Page 21: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-2

I. Introduction to mounting ear

Figure 3-1 shows the appearance of a front mounting ear.

(1)

(2)

L1L2

(1) Screw hole used to fix the mounting ear to the cabinet (Use one M6 screw) (2) Screw hole used to fix the switch to the mounting ear

Figure 3-1 Appearance of a standard front mounting ear

When you install S3100 Series Ethernet Switches into 19-inch standard cabinets, you should select front mounting ears with a proper length (L1 as shown in Figure 3-1) according to the physical dimensions of switches. For the selection of front mounting ears, see Table 3-2.

Table 3-2 Selection of mounting ear for S3100 Series Ethernet Switches

Model Physical dimensions (H x W x D) Configuration type of front mounting ear

S3100-26TP-EI-W 43.6 x 440 x 260 mm (1.7 x 17.3 x 10.2 in)

Standard

S3100-16TP-EI-W 43.6 x 300 x 220 mm (1.7 x 11.8 x 8.7 in)

Optional

S3100-8TP-EI-W 43.6 x 230 x 200 mm (1.7 x 9.1 x 7.9 in)

Optional

II. Use front mounting ears to install a switch

Follow these steps to mount a switch into a 19-inch standard cabinet:

1) Wear an ESD-preventive wrist strap to check the grounding and stability of the cabinet.

2) Take out the screws which are packed together with the front mounting ears, and fix one end of mounting ears to the switch, as shown in Figure 3-2.

Page 22: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-3

Figure 3-2 Fix front mounting ears (1)

3) Place the switch horizontally in a proper position, and fix the other end of mounting ears to the front brackets with screws and captive nuts, as shown in Figure 3-3.

Front square-holed bracket

Front mounting ear

Front mounting ear

Front panel

Figure 3-3 Fix front mounting ears (2)

III. Use front mounting ears and a tray

Follow these steps to install a switch into a 19-inch standard cabinet:

1) Wear an ESD-preventive wrist strap to check the grounding and stability of the cabinet.

2) Fix the delivered tray horizontally in a proper position. 3) Take out the screws which are packed together with the front mounting ears, and

fix one end of mounting ears to the switch, as shown in Figure 3-2. 4) Place the switch on the tray horizontally, slide the tray into the cabinet, and fix the

other end of mounting ears to the front brackets with crews and captive nuts, as shown in Figure 3-3.

Page 23: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-4

IV. Use front mounting ears and guide rails

Introduction to guide rail

Figure 3-4 shows the appearance of a guide rail.

Slotted hole 1: Used to fix the guide rail to the rear bracket. You can adjust the screw hole position according to the position of the switch. Cooling hole: Used for heat dissipation between switch and cabinet Slotted hole 2: Used to fix the guide rail to the front bracket

Figure 3-4 Appearance of a guide rail

Note:

Guide rails purchased from H3C apply only to standard cabinets 1,000 mm (39.4 in) deep. Use other supports to substitute for guide rails in the case of other cabinet depths.

Installation procedure

Follow these steps to install a switch into a 19-inch standard cabinet:

Wear an ESD-preventive wrist strap to check the grounding and stability of the cabinet.

1) Take out the screws packed together with the front mounting ears and fix one end of the front mounting ears to the switch, as shown in Figure 3-2.

2) Install guide rails on the brackets on both sides of the cabinet with M5 self-tapping screws. Figure 3-5 is for reference only.

Page 24: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-5

Figure 3-5 Install guide rails

3) Hold the two sides of the switch and slide it gently along the guide rails into the cabinet until it is located in a proper position, as shown in Figure 3-6. Ensure that the bottom side of the guide rails and the switch are in close contact.

Figure 3-6 Install front mounting ears and guide rails

4) Fix the other end of front mounting ears to the front brackets of the cabinet with M6 screws and captive nuts and ensure that the front mounting ears and guide rails have fixed the switch in the cabinet securely, as shown in Figure 3-7.

Page 25: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-6

Rear panel Guide rail

Figure 3-7 Effect diagram of front mounting ear and guide rail installation

Note:

No guide rails are delivered with the device. Ensure a clearance of 1U (44.45 mm, namely, 1.75 inches) between devices for the

purpose of heat dissipation.

3.1.2 Desk Mounting

When a 19-inch standard cabinet is not available, you can simply place the switch on a clean desk. When doing so, you should ensure that:

The desk is stable and well grounded. A clearance about 10 cm (3.9 in) is reserved around the switch for heat

dissipation. No heavy object is placed on the switch. S3100 Series Ethernet Switches are designed with no fan. Therefore, you should

install them in a drafty environment, and keep at least a vertical distance of 1.5 cm (0.6 in) between devices if you need to stack switches one upon another.

3.1.3 Wall Mounting

You can mount some models of S3100 Series Ethernet Switches on concrete walls or wood walls. Table 3-3 lists the models that support wall mounting.

Page 26: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-7

Table 3-3 Models supporting wall mounting

Subseries Models supporting wall mounting Hole distance (mm)

S3100-8TP-EI-W S3100 Ethernet switches S3100-16TP-EI-W

170 mm (6.69 in.)

I. Introduction to screw and anchor kit

Figure 3-8 and Figure 3-9 show the recommended sizes (in mm) of screws and anchor kits used for mounting:

Figure 3-8 Screw

(1)(1)

(1) Outside edge of anchor kit

Figure 3-9 Anchor kit

II. Installation procedure

The wall-mounting procedure is as follows:

As shown in Figure 3-10, drill two holes 5 mm across in the wall on the same horizontal line, with a distance of X=170 mm (6.69 in.).

Page 27: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-8

Note:

Drill two holes according to the sizes of anchor kits and screws so that anchor kits could go into the holes, only the edges could remain outside the wall, and the screws could be fixed on the wall tightly.

1) Insert anchor kits into the holes and keep only the edges outside the wall. 2) Drive screws into the anchor kits, keeping the inside of screw head at least 1.5 mm

(0.06 in) away from the edge of the anchor kit so that the switch could hang on the screws securely.

1.5 mm(Min)X mm

Figure 3-10 Wall mounting

3) Align the two installation holes at the bottom of the switch with these two screws to hang the switch.

Caution:

When mounting the switch, keep the Ethernet ports of the switch facing downwards and the two sides with ventilation holes vertical to the ground.

3.1.4 Magnet Mounting

The following four models support magnet mounting:

S3100-8TP-EI-W S3100-16TP-EI-W

Page 28: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-9

I. Introduction to magnetic accessories

A set of magnetic mounting accessories consists of one permanent magnets and one M3*6 countersunk head screws, as shown in Figure 3-11. Four sets of magnetic mounting accessories are needed for each S3100 switch.

(1)

(2)

(1) Permanent magnet (2) M3*6 countersunk head screw

Figure 3-11 Magnets and countersunk head screws

II. Installation procedure

Follow these steps to complete magnet mounting:

1) As shown in Figure 3-12, use a Phillips screwdriver to pass the countersunk head screw through the round hole at the center of the permanent magnet, fasten it to a blind nut in the dent of the switch bottom, and ensure that the permanent magnet and the switch are fastened reliably.

Note:

Remove the cushion, if any, from the dent before installation. To ensure the firmness of installation, be sure to use four permanent magnets to

secure each S3100 switch.

2) Attach the magnet-mounted device to the specified location. Take care not to get your fingers stuck between because the magnetism is very huge.

Page 29: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-10

(1)

(2)(3)

(1) Blind nut in the dent of the switch bottom (2) Permanent magnet (3) M3*6 countersunk head screw

Figure 3-12 Magnet mounting

Caution:

Apply magnet mounting to only the above four models. Otherwise, a falloff or mis-operation may occur.

Select the installation location carefully. In the case of poor surface, magnet mounting may not be reliable.

Put the device at a stable place free from vibrations or shocks. Otherwise, personal injuries or equipment damage may occur.

Avoid installing the device at a high place because personal injuries or equipment damage may occur in case of a falloff.

Avoid frequently moving the desk-mounted device because such movements may damage the surface coating.

Keep the front panel of the device facing downwards and the two sides with ventilation holes vertical to the ground, if you want to install the device vertically.

Pay attention that the weight of external cables should not bring about a falloff, which may result in personal injuries or equipment damage.

Keep floppy disks and magnetic cards away from magnets to avoid erasure of any information.

Keep computers and monitors that are easily influenced by magnetic fields away from magnets. Otherwise, faults may occur to these electronic devices.

Page 30: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-11

3.2 Connection of Power Cable and Grounding Cable

3.2.1 Connecting AC Power Cable

I. AC power socket (recommended)

You are recommended to use a mono-phase three-core power socket with a neutral point or a multi-function power socket for computers. The neutral point of the power in your building must be well grounded. Normally, the neutral point of the power supply system in your building has already been grounded during the construction and wiring; but you should make sure this is the fact.

Figure 3-13 Recommended AC power socket

II. Connecting AC power cable

1) Connect one end of the grounding cable (delivered with the switch) to the grounding screw on the rear of the chassis and the other end to the ground nearby.

2) Connect one end of the power cable to the power socket on the rear panel of the chassis and the other end to an outside AC power socket.

3) Check whether the PWR LED on the front panel of the switch is ON. If yes, the power is properly connected.

Caution:

Before powering on the switch, you should properly connect the grounding cable.

Page 31: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-12

3.2.2 Connecting DC Power Cable

I. 12V-RPS DC power cable connection for S3100-26TP-EI-W Ethernet switch

Pin Number Designation Pin Number Designation 1 GND 8 GND 2 — 9 — 3 12V 10 RPS_pres 4 12V 11 — 5 12V 12 — 6 12V 13 Control Pin 7 GND 14 GND

Figure 3-14 12V-RPS DC power socket

Connect one end of the grounding cable (delivered with the switch) to the grounding screw and the other end to the ground nearby.

1) Connect the 12V-RPS DC power supply as follows: As shown in Figure 3-15, loosen the fastening screws and remove the air filter

from the 12V-RPS DC power socket. (In the case of no 12V-RPS DC power supply, re-install the air filter.)

(2)(1)

(1) Air filter (2) Fastening screw

Figure 3-15 12V-RPS power socket for an S3100-26TP-EI-W Ethernet switch

Connect one connector (in A direction) of the 12V-RPS DC power cable (Figure 3-16 shows a recommended 12V-RPS DC power cable) to the RPS DC power socket of the switch, and the other connector (in B direction) to the corresponding 12 V power output socket of the RPS power module.

Page 32: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-13

1

7

8

14

14

8

7

1

Direction A Direction B

Figure 3-16 12V-RPS DC power cable

Connect one end of the delivered AC power cable to the power socket of the RPS power module and the other end to the socket of an external AC power supply.

2) Check whether the PWR LED on the front panel of the switch is ON. If yes, the power is properly connected.

Caution:

Before powering on the switch, you should properly connect the grounding cable. The DC power cable should be less than 3 meters long. Only the recommended 12V-RPS DC power supply and power cables can be used.

3.2.3 Connecting Grounding Cable

Caution:

You should properly connect the switch grounding cable since it is crucial to the lightning protection and electromagnetic shield (EMS) of your switch.

The power input end of the switch is connected with a noise filter, whose central ground is directly connected to the chassis, forming the so-called chassis ground (commonly known as PGND). This chassis ground must be securely connected to the earth so that the faradism and leakage electricity can be safely released to the earth, enhancing the EMS capability of the switch.

Ground the switch as follows:

When a grounding strip is available at the installation site, attach one end of the yellow-green grounding cable of the switch to the grounding screw on the grounding strip and fasten the captive nut. (Note that the fire main and lightning rod of your building are not suitable for grounding the switch. The grounding cable

Page 33: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-14

of the switch should be connected to the construction engineering ground of the equipment room.)

(1) Power input (2) Grounding screw (3) Protection grounding cable (4) Grounding strip

Figure 3-17 Ground the switch through a grounding strip

When there is no grounding strip but there is cement floor nearby where a grounding body is allowed to be buried, hammer an angle steel/steel pipe no shorter than 0.5 m (19.7 in.) into the earth, with the yellow-green grounding cable of the switch welded onto the angle steel/steel pipe and the jointing point being processed against erosion.

(1)

(2)

(3)

(4)

(5)

(1) Power input (2) Grounding screw (3) Protection grounding cable (4) Earth (5) Angle steel

Figure 3-18 Ground the switch by burying the grounding body into the earth

For an AC-powered switch, if none of the above two conditions is available, ground it through the PE cable of the AC power supply. In this case, make sure this PE cable is well connected to the ground at the power distribution room or AC transformer.

Page 34: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-15

(1) AC power socket (2) Grounding screw (3) Power transformer (4) PE cable (5) 3-core cable for AC power input (6) Ethernet switch

Figure 3-19 Ground the switch through AC PE cable

For a DC-powered switch (–48 VDC), if none of the first two conditions is available, ground it through the return cable (RTN) of the DC power supply. In this case, make sure this RTN cable is well connected to the ground at the DC output of the DC power cabinet.

(9)(10)(11)(3)

(5)

(2)

(4)

(6)

(7)

(8)

(1)

(1) AC/DC power cabinet (2) –48V strip (3) –48V (4) RTN strip (5) RTN (6) PGND strip (7) Grounding to the earth (8) Grounding cable (9) Screw (10) Ethernet switch (11) DC power input

Figure 3-20 Ground the switch through the PGND of the power cabinet

Page 35: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-16

3.3 Connecting Optical Fiber

Caution:

After a switch starts, the optical port may emit invisible radial when there is no optical connector connected to it and the protective cap is removed from it. Therefore, do not stare into the optical interface.

Be sure to cover the protective cap within 10 seconds if an optical connector is not in use to keep the optical connector clean.

Be sure to cover the protective cap if an optical port has no optical connector attached.

Place the protective caps in a safe place when an optical port has fiber connected to prepare for the cases the fiber is pulled out.

3.4 Connection of Console Cable

3.4.1 Console Cable

The console cable is an 8-core shielded cable. At one end of the cable is a crimped RJ-45 connector to be connected to the console port of the switch; at the other end of the cable is a DB-9 (female) connector to be connected to the 9-core (pin) serial port on the console terminal. See the following figure.

Figure 3-21 Console cable

Table 3-4 Console cable connector pinouts and mapping relation

RJ-45 Signal Direction DB-9

1 RTS ← 7

2 DTR ← 4

3 TXD ← 3

Page 36: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 3 Installation

3-17

RJ-45 Signal Direction DB-9

4 CD → 1

5 GND — 5

6 RXD → 2

7 DSR → 6

8 CTS → 8

3.4.2 Connecting Console Cable

Follow these steps to connect a terminal device, a PC for example, to the switch:

Step 1: Connect the DB-9 female connector of the console cable to the serial port of the PC or the terminal device used to configure the switch.

Step 2: Connect the RJ-45 connector of the console cable to the console port of the switch.

Caution:

Identify the label of the port before connecting a connector.

Note:

When connecting a PC to a powered-on switch, you are recommended to connect the DB-9 connector of the console cable to the PC before connecting the RJ-45 connector to the switch. When disconnecting a PC from a powered-on switch, you are recommended to disconnect the DB-9 connector of the console cable from the PC after disconnecting the RJ-45 connector from the switch.

3.5 Installation Verification

After completing the installation, check that:

The correct power is used. The grounding cable is connected. Both console cable and power cable are properly connected. All the interface cables are wired indoors. If there is any cable wired outdoors,

verify that socket strip with lightning protection and lightning arresters for network ports have been properly connected.

Page 37: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 4 First Power-on

4-1

Chapter 4 First Power-on

4.1 Establishing Configuration Environment

The following figure shows the configuration environment you will establish:

In this environment, a terminal (a PC in this example) is connected to the console port of the switch through the console cable.

Figure 4-1 Network diagram for the configuration of the switch when it is first powered on

4.2 Connecting the Console Cable

Step 1: Connect the DB-9 female connector of the console cable to the serial port of the PC used to configure the switch.

Step 2: Connect the RJ-45 connector of console cable to the console port of the switch.

4.3 Setting Terminal Parameters

Step 1: Start the PC and run the terminal emulation program such as the Terminal of Windows3.1 or the HyperTerminal of Windows95/98/NT/2000/XP.

Step 2: Set terminal parameters (take the HyperTerminal of Windows2000 as an example).

Parameter requirements: Set bits per second to 9600, data bits to 8, parity check to none, stop bits to 1 and flow control to none. Select VT100 as terminal emulation. The following is the specific procedure:

Page 38: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 4 First Power-on

4-2

1) Select [Start/Program/Accessories/Communications/HyperTerminal] to enter the

HyperTerminal window, where click the icon to establish a new connection. The system displays the Connection Description interface, as shown in the following figure.

Figure 4-2 Connection description interface of HyperTerminal

2) Type in the name of the new connection in the connection description interface and click <OK>. The system pops up the following interface. Select the serial port to be used from [Connect using].

Figure 4-3 Setting the serial port used by the HyperTerminal connection

Page 39: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 4 First Power-on

4-3

3) Click <OK> after selecting a serial port and the system pops up the following interface. In the interface, set the bits per second to 9600, data bits to 8, parity check to none, stop bits to 1, and flow control to none.

Figure 4-4 Setting serial port parameters

4) Click <OK> after setting the serial port parameters, and the system enters the following interface.

Figure 4-5 HyperTerminal

Choose [Properties] in the HyperTerminal dialog box to enter the properties window. Click [Settings] to enter the following properties setting window, and select VT100 as the terminal emulation. Click <OK> when the selection is done.

Page 40: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 4 First Power-on

4-4

Figure 4-6 Set terminal emulation in H3C Properties window

4.4 Booting Switch

4.4.1 Checking Before Powering on the Switch

Before powering on the switch, verify that:

The power cable and grounding wire are properly connected. The supply voltage is consistent with that required by the switch. The console cable is properly connected; the terminal (which can be a PC) used

for configuration has been started; and the configuration parameters have been set.

4.4.2 Powering on the Switch

All the S3100 series Ethernet switches have the same BOOTROM display style. This document takes the BOOTROM display of the S3100-26TP-EI-W switch as example:

Starting......

***********************************************************

* *

* H3C S3100-26TP-EI-W BOOTROM, Version 517 *

* *

***********************************************************

Page 41: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 4 First Power-on

4-5

Copyright(c) 2004-2007 Hangzhou H3C Technologies Co., Ltd.

Creation date : Dec 8 2007, 13:47:55

CPU Clock Speed : 200MHz

BUS Clock Speed : 33MHz

Memory Size : 64MB

Mac Address : 00e0fc003100

Press Ctrl-B to enter Boot Menu... 2

The last line prompts you to enter the Boot Menu and waits two seconds for your response.

Note:

The system has two startup modes: normal and fast. The normal startup mode spends a little more time than the fast startup mode because the former takes more self-test operations.

By default, the system starts up in fast mode and the waiting time here is two seconds. While, if you set the startup mode to normal, this waiting time is five seconds. For the setting of the startup mode, refer to the next section.

If you press <Ctrl+B> within 2 seconds, the Boot Menu is displayed: BOOT MENU

1. Download application file to flash

2. Select application file to boot

3. Display all files in flash

4. Delete file from flash

5. Modify bootrom password

6. Enter bootrom upgrade menu

7. Skip current configuration file

8. Set bootrom password recovery

9. Set switch startup mode

0. Reboot

Enter your choice(0-9):

If you perform no operation or press a key other than <Ctrl+B> within two seconds, once the waiting time becomes zero, the system begins to automatically start up and the following information is displayed:

Auto-booting...

Decompress Image...................................................

...................................................................

Page 42: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 4 First Power-on

4-6

...................................................................

...................................................................

...................................................................

...............................................OK!

Starting at 0x80100000...

User interface aux0 is available.

Press ENTER to get started.

4.4.3 Changing the Startup Mode

By default, the system starts up in fast mode. If you want to change the startup mode to normal, press <Ctrl+B> within two seconds to enter the Boot Menu showed below:

BOOT MENU

1. Download application file to flash

2. Select application file to boot

3. Display all files in flash

4. Delete file from flash

5. Modify bootrom password

6. Enter bootrom upgrade menu

7. Skip current configuration file

8. Set bootrom password recovery

9. Set switch startup mode

0. Reboot

Enter your choice(0-9):

Enter 9, and the system prompts you to change the startup mode:

The current mode is fast startup mode!

Are you sure to change it to full startup mode? Yes or No(Y/N)

Enter Y, and the system gives the following prompts:

Setting startup mode...done!

BOOT MENU

1. Download application file to flash

2. Select application file to boot

3. Display all files in flash

4. Delete file from flash

5. Modify bootrom password

6. Enter bootrom upgrade menu

7. Skip current configuration file

8. Set bootrom password recovery

9. Set switch startup mode

Page 43: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 4 First Power-on

4-7

0. Reboot

Enter your choice(0-9):

Enter 0, the system reboots in normal mode and displays the following information:

Starting......

***********************************************************

* *

* H3C S3100-26TP-EI-W BOOTROM, Version 517 *

* *

***********************************************************

Copyright(c) 2004-2007 Hangzhou H3C Technologies Co., Ltd.

Creation date : Dec 8 2007, 13:47:55

CPU Clock Speed : 200MHz

BUS Clock Speed : 33MHz

Memory Size : 64MB

Mac Address : 00e0fc003100

Press Ctrl-B to enter Boot Menu... 5

In normal startup mode, the waiting time here is five seconds. If you press <Ctrl+B> within five seconds, the Boot Menu is displayed. If you perform no operation or press a key other than <Ctrl+B> within five seconds, the system begins to automatically starts up and the following information is displayed:

Auto-booting...

Decompress Image...................................................

...................................................................

...................................................................

...................................................................

...................................................................

...............................................OK!

Starting at 0x80100000...

Board checking...................... LSN1LTSG0

SDRAM fast selftest........................OK!

Flash fast selftest........................OK!

Switch chip selftest.......................OK!

Slot 1/1/1 has FIX_COMBO_PORT module

Page 44: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 4 First Power-on

4-8

Slot 1/2/1 has FIX_COMBO_PORT module

PHY selftest...............................OK!

Please check port leds...............FINISHED!

User interface aux0 is available.

Press ENTER to get started.

The appearance of "Press ENTER to get started" indicates that the switch finishes the auto-startup.

Press <Enter>, and the following prompt is displayed:

<H3C>

You can configure the switch now.

Note:

The H3C S3100 Series Switches provides abundant command views. For detailed descriptions about the configuration commands and CLI, refer to H3C S3100 Series Ethernet Switches Operation Manual (For Soliton) and H3C S3100 Series Ethernet Switches Command Manual (For Soliton).

Page 45: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-1

Chapter 5 Boot ROM and Host Software Loading

Traditionally, the loading of switch software is accomplished through the serial port. This approach is slow, inconvenient, and cannot be used for remote real-time loading. To resolve these problems, the TFTP and FTP modules are introduced into the switch. With these modules, the software and files can be loaded through Ethernet port conveniently.

This chapter introduces how to load Boot ROM and host software into a switch locally and how to do this remotely.

5.1 Introduction to Loading Approaches

You can load the software locally by using:

XModem via console port TFTP via Ethernet port FTP via Ethernet port

You can load the software remotely by using:

FTP TFTP

Note:

Boot ROM software version should be compatible with the host software version when you load the Boot ROM and host software.

5.2 Local Software Loading

If your terminal is directly connected to the switch, you can load Boot ROM and host software locally.

Before loading the software, make sure that your terminal is correctly connected to the switch to ensure the successful loading.

Page 46: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-2

Note:

The loading process of the Boot ROM software is the same as that of the host software, except that during the Boot ROM loading process, you should press <Ctrl+U> and <Enter> after entering the Boot Menu and the system gives somewhat different prompts. The following text mainly describes the Boot ROM loading process.

5.2.1 Boot Menu

Take S3100-26TP-EI-W switch as example. After the switch is powered on, the system displays:

Starting......

***********************************************************

* *

* H3C S3100-26TP-EI-W BOOTROM, Version 517 *

* *

***********************************************************

Copyright(c) 2004-2007 Hangzhou H3C Technologies Co., Ltd.

Creation date : Dec 8 2007, 13:47:55

CPU Clock Speed : 200MHz

BUS Clock Speed : 33MHz

Memory Size : 64MB

Mac Address : 00e0fc003100

Press Ctrl-B to enter Boot Menu... 5

Press <Ctrl+B>. The system displays:

Password :

Page 47: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-3

Note:

To enter the Boot Menu, you should press <Ctrl+B> within five seconds after the information “Press Ctrl-B to enter Boot Menu...” appears. Otherwise, the system starts to decompress the program; and if you want to enter the Boot Menu at this time, you will have to restart the switch.

Input the correct Boot ROM password (by default, no password is set on the switch). The system enters the Boot Menu:

BOOT MENU

1. Download application file to flash

2. Select application file to boot

3. Display all files in flash

4. Delete file from flash

5. Modify bootrom password

6. Enter bootrom upgrade menu

7. Skip current configuration file

8. Set bootrom password recovery

9. Set switch startup mode

0. Reboot

Enter your choice(0-9):

5.2.2 Loading Software Using XModem Through Console Port

I. Introduction to XModem

XModem is a file transfer protocol that is widely used due to its simplicity and good performance. XModem transfers files via console port. It supports two types of data packets (128 bytes and 1 KB), two check methods (checksum and CRC), and error packet retransmission mechanism (generally the maximum number of retransmission attempts is ten).

The XModem transmission procedure is completed by the cooperation of a receiving program and a sending program: The receiving program sends a negotiation packet to negotiate a packet check method. After the negotiation, the sending program starts to transmit data packets. When receiving a complete packet, the receiving program checks the packet using the agreed method. If the check succeeds, the receiving program sends an acknowledgement packet and the sending program proceeds to send another packet; otherwise, the receiving program sends a negative acknowledgement packet and the sending program retransmits the packet.

Page 48: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-4

II. Loading Boot ROM software

Follow these steps to load the Boot ROM software:

Step 1: At the prompt "Enter your choice (0-9):" in the Boot Menu, press <6> or <Ctrl+U>, and then press <Enter> to enter the Boot ROM update menu shown below:

Bootrom update menu:

1. Set TFTP protocol parameter

2. Set FTP protocol parameter

3. Set XMODEM protocol parameter

0. Return to boot menu

Enter your choice(0-3):

Step 2: Enter 3 in the above menu to load the Boot ROM software using XModem. The system displays the following download bits per second setting menu:

Please select your download baudrate:

1.* 9600

2. 19200

3. 38400

4. 57600

5. 115200

0. Return

Enter your choice (0-5):

Step 3: Choose an appropriate download bits per second. For example, if you enter 5, the 115200 bps rate is chosen, and the system displays the following information:

Download baudrate is 115200 bps

Please change the terminal's baudrate to 115200 bps and select XMODEM protocol

Press enter key when ready

Now, press <Enter>.

Note:

If you have chosen 9600 bps, you do not need to modify the HyperTerminal’s bits per second, and therefore you can skip Step 4 and 5 below and proceed to Step 6 directly. In this case, the system will not display the above information.

Step 4: Select [File/Properties] in HyperTerminal, click <Configuration> in the popup dialog box, and select the bits per second of 115200bps in the appeared console port configuration dialog box.

Page 49: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-5

Figure 5-1 Properties dialog box

Figure 5-2 Console port configuration dialog box

Step 5: Click the <Disconnect> button to disconnect the HyperTerminal from the switch and then click the <Call> button to reconnect the HyperTerminal to the switch.

Page 50: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-6

Figure 5-3 Call and disconnect buttons

Note:

The new bits per second takes effect only after you disconnect and reconnect the terminal emulation program.

Step 6: Press <Enter> to start downloading the program. The system displays the following information:

Now please start transfer file with XMODEM protocol.

If you want to exit, Press <Ctrl+X>.

Loading ...CCCCCCCCCC

Step 7: Choose [Transfer/Send File] in the HyperTerminal’s window, and in the following popup dialog box click <Browse>, select the software you need to download, and set the protocol to XModem.

Figure 5-4 Send file dialog box

Step 8: Click <Send>. The system displays the following page.

Page 51: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-7

Figure 5-5 Sending file page

After the download completes, the system displays the following information:

Loading ...CCCCCCCCCC done!

Note:

You do not need to reset the HyperTerminal’s bits per second and can skip the last step if you have chosen 9600 bps. In this case, the system displays the prompt “Bootrom is updating now.....................................done!” instead of the prompt "Your baudrate should be set to 9600 bps again! Press enter key when ready".

Step 9: Reset HyperTerminal’s bits per second to 9600 bps (refer to Step 4 and 5). Then, press any key as prompted. The system will display the following information when it completes the loading.

Bootrom is updating now.....................................done!

III. Loading host software

Follow these steps to load the host software:

Step 1: Select <1> in Boot Menu. The system displays the following information:

1. Set TFTP protocol parameter

2. Set FTP protocol parameter

3. Set XMODEM protocol parameter

0. Return to boot menu

Enter your choice(0-3):3

Page 52: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-8

The subsequent steps are the same as those for loading the Boot ROM software, except that the system gives the prompt for host software loading instead of Boot ROM loading.

5.2.3 Loading Software Using TFTP Through Ethernet Port

I. Introduction to TFTP

TFTP, one protocol in TCP/IP protocol suite, is used for trivial file transfer between client and server. It uses UDP to provide unreliable data stream transfer service.

II. Loading Boot ROM software

PC TFTP Client TFTP Server

Switch

Console port Ethernet port

Figure 5-6 Local loading using TFTP

Step 1: As shown in Figure 5-6, connect the switch through an Ethernet port to the TFTP server, and connect the switch through the console port to the configuration PC.

Note:

You can use one PC as both configuration device and TFTP server.

Step 2: Run the TFTP server program on the TFTP server, and specify the path of the program to be loaded.

Caution:

TFTP server program is not provided with the H3C Series Switches.

Step 3: Run the terminal emulation program on the configuration PC. Start the switch. Then enter the Boot Menu.

At the prompt "Enter your choice (0-9):" in the Boot Menu, press <6> or <Ctrl+U>, and then press <Enter> to enter the Boot ROM update menu shown below:

Bootrom update menu:

1. Set TFTP protocol parameter

Page 53: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-9

2. Set FTP protocol parameter

3. Set XMODEM protocol parameter

0. Return to boot menu

Enter your choice(0-3):

Step 4: Enter 1 to download the Boot ROM software using TFTP. Then set the following TFTP-related parameters as required:

Load File name :S3100-EI.btm

Switch IP address :1.1.1.2

Server IP address :1.1.1.1

Step 5: Press <Enter>. The system displays the following information:

Are you sure to update your bootrom?Yes or No(Y/N)

Step 6: Enter Y to start file downloading or N to return to the Boot ROM update menu. If you enter Y, the system begins to download and update the Boot ROM software. Upon completion, the system displays the following information:

Loading........................................done

Bootrom updating..........done!

III. Loading host software

Follow these steps to load the host software of the switch.

Step 1: Select <1> in Boot Menu. The system displays the following information:

1. Set TFTP protocol parameter

2. Set FTP protocol parameter

3. Set XMODEM protocol parameter

0. Return to boot menu

Enter your choice(0-3):1

The subsequent steps are the same as those for loading the Boot ROM software, except that the system gives the prompt for host software loading instead of Boot ROM loading.

5.2.4 Loading Software Using FTP Through Ethernet Port

I. Introduction to FTP

FTP is an application-layer protocol in the TCP/IP protocol suite. It is used for transferring files between server and client. FTP runs over UDP to provide unreliable data transmission.

You can use FTP to load software to the switch through an Ethernet port. In this case, the switch can act as an FTP server or an FTP client. In the following example, the switch acts as an FTP client.

Page 54: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-10

II. Loading Boot ROM software

PC FTP Client FTP Server

Switch

Console port Ethernet port

Figure 5-7 Local loading using FTP

Step 1: As shown in Figure 5-7, connect the switch through an Ethernet port to the FTP server, and connect the switch through the console port to the configuration PC.

Note:

You can use one computer as both configuration device and FTP server.

Step 2: Run the FTP server program on the FTP server, configure an FTP user name and password, and specify the path of the program to be downloaded.

Step 3: Run the terminal emulation program on the configuration PC. Start the switch. Then enter the Boot Menu.

At the prompt "Enter your choice (0-9):" in the Boot Menu, press <6> or <Ctrl+U>, and then press <Enter> to enter the Boot ROM update menu shown below:

Bootrom update menu:

1. Set TFTP protocol parameter

2. Set FTP protocol parameter

3. Set XMODEM protocol parameter

0. Return to boot menu

Enter your choice(0-3):

Step 4: Enter 2 in the above menu to download the Boot ROM software using FTP. Then set the following FTP-related parameters as required:

Load File name :S3100-EI.btm

Switch IP address :10.1.1.2

Server IP address : 10.1.1.1

FTP User Name :3100-SI

FTP User Password :abc

Step 5: Press <Enter>. The system displays the following information:

Are you sure to update your bootrom?Yes or No(Y/N)

Page 55: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-11

Step 6: Enter Y to start file downloading or N to return to the Boot ROM update menu. If you enter Y, the system begins to download and update the program. Upon completion, the system displays the following information:

Loading........................................done

Bootrom updating..........done!

III. Loading host software

Follow these steps to load the host software:

Step 1: Select <1> in Boot Menu. The system displays the following information:

1. Set TFTP protocol parameter

2. Set FTP protocol parameter

3. Set XMODEM protocol parameter

0. Return to boot menu

Enter your choice(0-3):2

The subsequent steps are the same as those for loading the Boot ROM software, except for that the system gives the prompt for host software loading instead of Boot ROM loading.

5.3 Remote Software Loading

If your terminal is indirectly connected to the switch through Internet, you can telnet to the switch, and use FTP or TFTP to load Boot ROM and host software remotely.

5.3.1 Remote Loading Using FTP

As shown in Figure 5-8, a PC is used as both configuration device and FTP server. You can telnet to the switch, and then execute the FTP commands to download the host program s3100-EI.bin and the Boot ROM program s3100-EI.btm from the remote FTP server (with IP address 202.10.10.53) to the switch.

Figure 5-8 Remote loading using FTP

Step 1: Download the software to the switch using FTP commands.

<H3C> ftp 202.10.10.53

Trying ...

Press CTRL+K to abort

Connected.

Page 56: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-12

220 WFTPD 2.0 service (by Texas Imperial Software) ready for new user

User(none):abc

331 Give me your password, please

Password:

230 Logged in successfully

[ftp] get s3100-EI.bin

[ftp] get s3100-EI.btm

[ftp] bye

Step 2: Update the Boot ROM program on the switch.

<H3C> boot bootrom s3100-EI.btm

please wait ...

Bootrom is updated!

Step 3: Update the host program on the switch.

<H3C> boot boot-loader s3100-EI.bin

<H3C> display boot-loader

Unit 1:

The current boot app is: s3100-EI.bin

The main boot app is: s3100-EI.bin

The backup boot app is:

Step 4: Restart the switch.

<H3C> reboot

Note:

Before restarting the switch, make sure other configurations are all saved to avoid the loss of configuration information.

After the above operations, the Boot ROM and host software loading is completed.

Pay attention to the following:

Host software loading takes effect only after you restart the switch with the reboot command.

If the space of the flash memory is not enough, you can delete the useless files in the flash memory before software downloading.

No power-breaking is permitted during software loading.

Page 57: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 5 Boot ROM and Host Software Loading

5-13

5.3.2 Remote Loading Using TFTP

The remote loading by using TFTP is similar to the remote loading by using FTP. The only difference is that it is TFTP that you use when loading software to the switch. In this case, the switch can only be used as a TFTP client.

Page 58: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 6 Maintenance and Troubleshooting

6-1

Chapter 6 Maintenance and Troubleshooting

6.1 Software Loading Failure

If software loading fails, the system keeps running in original version.

In this case, check if the physical ports are properly connected:

If not, reconnect them correctly and restart the loading procedure. If so, check the loading procedure information displayed on the HyperTerminal for

input errors. If there is any input error, restart the loading procedure with correct input. For example:

1) When using XModem, verify that you have reset the bits per second of the HyperTerminal to 9600 bps after loading the software with a bits per second other than 9600 bps;

2) When using TFTP, verify that you have provided: Correct server and switch IP addresses, Correct name of the software to be loaded, Correct working path of TFTP server;

3) When using FTP, verify that you have provided: Correct server and switch IP addresses, Correct name of the software to be loaded, Correct username and password.

If software loading fails but there are neither physical connection problems nor input errors, please contact your agent for help.

6.2 Missing Password

6.2.1 Missing user password

If you forget your user password, you can:

Access the Boot Menu:

BOOT MENU

1. Download application file to flash

2. Select application file to boot

3. Display all files in flash

4. Delete file from flash

5. Modify bootrom password

6. Enter bootrom upgrade menu

7. Skip current configuration file

8. Set bootrom password recovery

Page 59: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 6 Maintenance and Troubleshooting

6-2

9. Set switch startup mode

0. Reboot

Enter your choice(0-9):

Select <7> and restart the switch. After that, the system will skip the configuration file.

6.2.2 Missing Boot ROM Password

Please contact your agent.

6.3 Power System Failure

You can check whether the power system of the switch fails by viewing the POWER indicator on the front panel. If it is in normal operation, the POWER indicator should stay on. Otherwise, please check that:

The switch power cable is correctly connected. The power input to the switch matches the requirement as labeled on the switch.

6.4 Configuration System Failure

After the switch is powered on and the system is normal, the booting information will be displayed on the configuration terminal. If the configuration system has any faults, there will not be any screen display at the configuration terminal or the displayed characters will be totally illegible.

I. Troubleshooting when there is no terminal display

If there is no output information after the configuration is powered on, please check that:

The power supply is normal The console cable is properly connected

If no problems are found after the above-mentioned items have been checked, the cause may lie in the console cable or the settings of the terminal (such as HyperTerminal) parameters. Please perform the corresponding check.

II. Troubleshooting when the terminal display is illegible

If there is illegible display at the configuration terminal, the cause might lie in the parameter setting error at the terminal (such as HyperTerminal). Please confirm the following terminal parameter (such as HyperTerminal) settings:

Bits per second: 9600 Data bits: 8 Parity check: None Stop bits: 1

Page 60: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Chapter 6 Maintenance and Troubleshooting

6-3

Flow control: None Terminal emulation: VT100.

Page 61: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Table of Contents

i

Table of Contents

Appendix A Lightning Protection of the Switch.........................................................................A-1 A.1 Installation of Lightning Arrester for AC Power (Socket Strip with Lightning Protection)............A-1 A.2 Installation of Lightning Arrester for Network Port.............................................................A-2

Page 62: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Appendix A Lightning Protection of the Switch

A-1

Appendix A Lightning Protection of the Switch

A.1 Installation of Lightning Arrester for AC Power (Socket Strip with Lightning Protection)

Caution:

Lightning arrester will not be shipped with the switch. You should purchase it by yourself if needed.

If an outdoor AC power cord should be directly led to the switch, please serially connect the lightning arrester for AC power (Socket Strip with Lightning Protection) before you plug AC power cord into the switch, thus to prevent the possible damage to the switch due to lightning strike. You can use cable clips and screws to fasten the lightning arrester for AC power on the cabinet, workbench or the wall of equipment room.

Mainboard

Grounding and polarity indicator (red) :On means that the lines are wrongly connected(either the ground wire is not well connected, or the live and zero lines are wrongly connected).Please check the power supply circuit.

Power switchNormal operation indicator (green): On means that the arrester works normally. Otherwise, it means that the protection circuit has been damaged.

Multipurpose power socket, connected to the deviceprotected by the arrester

Power socket (complied with IEC standard), connected to the power supply of the equipment roomthrough power cord

Overload auto protector,which can be manually reset.

Figure A-1 Diagram of lightning arrester

Page 63: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Appendix A Lightning Protection of the Switch

A-2

Caution:

Make sure that the arrester is well grounded before using the lightning arrester for power.

After inserting AC power cord plug of switch into the socket of lightning arrester, if the green LED is on and the red LED does not alarm, it means that the lightning arrester of power is running and the function of lightning protection has taken effect.

Pay adequate attention if the red LED is on. You should correctly locate the problem, whether it is caused because the ground wire of the arrester is not well grounded or because the live and zero wires are connected in reverse direction. You may check that in the following way. When the red LED is on, use a multimeter to examine polarity at the power socket of the arrester. If it is same to that of the power socket in the equipment room, it means that arrester is not well grounded. If it is adverse to that of the power socket in the equipment room, it means that the power socket of the arrester is set to the reverse polarity. In this case, you should open the power socket of arrester to correct polarity. After that, if the red LED still alarms, it means that the arrester is not well grounded yet.

A.2 Installation of Lightning Arrester for Network Port

Note:

Lightning arrester for network port is specially designed for the Ethernet port of 10/100M electrical interface (RJ-45 connector is adopted in this case).

Caution:

Lightning arrester for network port will not be provided along with the switch, and you should purchase it by yourself if needed.

�If an outdoor network cable should be led to the switch, please serially connect the lightning arrester for network port before you plug this cable into the interface on the switch, in case of the possibility that the switch may be damaged due to lightning strike.

I. Required tools

Phillips screwdriver or Flat-blade screwdriver

Page 64: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Appendix A Lightning Protection of the Switch

A-3

Multimeter Tilted wire cutter

II. Installation procedure

Step 1: Tear the protection paper at one side of the double faced adhesive tape apart from the tape, and stick the tape on the surface of the arrester. Tear the protection paper at another side apart from the tape, and stick the arrester onto the chassis of the switch. The arrester should be attached on the chassis as close to the grounding screw as possible.

Step 2: According to the distance to the grounding screw of the switch, cut the ground wire of the arrester, and securely tightening its ground wire to the grounding screw of the switch.

Step 3: Use the multimeter to measure whether the ground wire of the arrester contacts well with the grounding screw of chassis.

Step 4: According to the instruction of arrester for network port, connect the arrester with switch by the cables (be carefully with the cable direction. Outdoor network cable should be inserted into the arrester‘s IN end, and the cable connected to the switch should be inserted into the arrester’s OUT end). When you do that, observe whether the arrester indicators normally display.

Note:

The instruction of lightning arrester for network port contains the technical specifications, installation and maintenance guide of the arrester. Please carefully read it before installing the arrester.

Step 5: Use the nylon ties to bundle the cables neatly.

Switch

Network cable indoors

Power input

Network cable led into from outdoor

Lightning arrester for network port(attached onto the chassis)

Ground wire of lightning arrester

Grounding screw of switch

Metal cabinet that contains the switch

Figure A-2 Installation diagram of lightning arrester for network port

Page 65: H3C S3100 Series Ethernet Switches Installation Manual ...tlt83.narod.ru/olderfiles/1/H3C_Switches_Manual.pdf · Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches

Installation Manual (For Soliton) H3C S3100 Series Ethernet Switches Appendix A Lightning Protection of the Switch

A-4

III. Installation precautions

Fully consider the following items in the installation process, otherwise, the performance of the lightning arrester for network port will be affected:

Lightning arrester for network port is installed in reverse direction. In practice, the “IN” end should be connected to the outdoor network cable and the “OUT” end to the network port on the switch.

Lightning arrester for the network port is not well grounded. The ground wire for the arrester should be as short as possible, so to ensure its good contact with the grounding screw of the switch. After the connection, use the multimeter to confirm that.

The lightning arrester for the network port is not installed completely. If the switch has more than one network ports to interconnect with other devices via cables outdoor, you should install lightning arresters for all these network ports for protection.