GUARDIAN DIFFERENTIAL PRESSURE
The standard ranges cover differential pressure applications for settings from 2 mBar to 12 Bar. Dual microswitch and adjustable deadband options are available as detailed overleaf.
DP1500 GUARDIAN INDUSTRIAL & ATEX CERTIFIED Exia DIFFERENTIAL PRESSURE SWITCH
FEATURES
IP66/IP67 certified housing.a
Internal adjustment scale.a
DIFFERENTIAL PRESSURE
SIL2 - IEC61508 proven reliability.a
Differential pressure settings from 2 mBar to 12 Bar.
a316 stainless steel or black anodised aluminium switchcase.
a
Single or dual microswitch option. Adjustable deadband option.
a
This design comprises orifice plate, differential pressure sensitive element and switching mechanism in a compact assembly which enables easy installation between pipe flanges.
Wetted parts NACE MR-01-75 compliant.a
Manual reset pushbutton option.a
ATEX Certified OptionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
SPECIFICATION
ADJUSTMENTRANGE
(BAR) *MBAR
6 - 12
5 - 7
3 - 5
2 - 4
0.2 - 2.4
0.1 - 1.1
*30 - 330
*5 - 55
*2 - 42
ADJUSTMENTRANGE
(PSI) *”WG
90 - 170
75 - 100
45 - 75
30 - 60
5 - 35
2 - 16
*12 - 132
*2 - 20
*1 - 16
14
14
14
14
14
7
7
0.35
0.35
28
28
28
28
28
10
10
0.5 ∆
0.5 ∆
MAX WORKING PRESS. (BAR)
ONE SIDED EQUAL
DEADBAND(BAR) *MBAR
<1.2
<0.7
<0.5
<0.4
<0.25
<0.15
<*35
<*6
<*3
DIAPHRAGMCODE
01SB
01SB
01SB
01SB
01SB
02SB
03SB
08SB
08SB
SPRINGCODE
3
B
G
R
1
2
1
2
1
STANDARD VITONDIAPHRAGM
Dual microswitches may increase the deadband by a factor of two. 3.5 Bar option available.
Temperature limitationsDiaphragm code : 01SBViton : -20 to + 150˚CNitrile : -30 to +90˚CDiaphragm code : 02SB 03SB & 08SBViton : -10 to + 150˚CNitrile : -25 to +95˚CWetted parts : 316 Stainless steel
Process connections : Diaphragm Code 01SB, 02SB and 03SB 1/4” BSP.P or NPT FemaleCode 08SB compression fittings or threaded connections as shown overleaf.Electrical connectionsM20 x 1.5 ISO female standardSuffix “F” for M25 x 1.5 ISO femaleor “C” for 1/2” NPT female
3
cc0C* = MANUAL (RESET RISING)0D* = MANUAL (RESET FALLING)0E* = DUAL HIGH CURRENT DC0M* = SINGLE HIGH DC CURRENT*Change 0 to E for Exia certification
( S ) D P 1 5 0 1 / A 1 N 0 1 S B 1 / S S X
SPRING CODE
SEE RANGE TABLE
DIAPHRAGM CODE
SEERANGE TABLE
PART NUMBER BREAKDOWN
MICROSWITCH OPTIONS01 = SINGLE SWITCH02 = DUAL SWITCHES03 = USE 0104 = USE 0205 = SINGLE FOR Exia06 = DUAL FOR Exia
ADJUSTABLE DEADBAND07 = SINGLE SWITCH - STANDARD08 = SINGLE SWITCH - USE FOR Exia
09* = MANUAL AND AUTO (RESET RISING)0A* = MANUAL AND AUTO (RESET FALLING)
N = STANDARD ADJUSTERA = SECONDARY ADJUSTER (FOR DUAL SETTING OR ADJUSTABLE DIFFERENTIAL MECHANISM)
DIAPHRAGMA = NITRILEB = VITON
DP15 = DIFFERENTIAL PRESSUREPREFIX WITH ‘S’ FOR STAINLESS STEEL SWITCHCASE
MOUNTING DETAILSX = 01SB CASE MOUNTINGN = 02SB & 03SB BRACKETX = 08SB BRACKETE = 2” PIPE BRACKET
PROCESS CONNECTION FORDIAPHRAGM CODES01SB AND 03SB1 = 1/4” BSP.P FEMALE (DP)2 = 1/4” NPT FEMALE (DP)
PROCESS CONNECTIONS FOR DIAPHRAGM CODE 08SB
PLEASE REFER TO MICROSWITCH RATINGS ON PAGE 11.
J = 1/4” BSP.P FEMALE STRAIGHT DPL = 1/4” BSP.T FEMALE STRAIGHT DPN = 1/4” BSP.P MALE STRAIGHT DPQ = 1/4” NPT FEMALE STRAIGHT DPS = 1/4” NPT MALE STRAIGHT DPU = 1/2” NPT FEMALE STRAIGHT DP
1 = 1/4” O/D TUBE POSI. ELBOW DP2 = 1/4” O/D TUBE TEE DPA = 6mm O/D TUBE DPC = 8mm O/D TUBE DPE = 10mm O/D TUBE DPG = 12mm O/D TUBE DP
MAXIMUM DEADBANDAT TOP OF
RANGE(BAR) *MBAR
3.8
2.8
2.1
1.8
0.8
*180
*180
*17
*17
MINIMUM DEADBANDAT TOP OF
RANGE(BAR) *MBAR
0.8
0.6
0.5
0.4
0.2
*40
*40
*3
*3
MAXIMUM DEADBANDAT BOTTOM OF RANGE
(BAR) *MBAR
3.5
2.5
2
1.5
0.55
*120
*120
*12
*12
MINIMUM DEADBANDAT BOTTOM OF RANGE
(BAR) *MBAR
0.65
1.45
0.35
0.25
0.15
*30
*30
*3
*3
ADJUSTMENT RANGE (BAR) (FALLING SET POINTS ONLY)
SWITCH 1 6 - 12
5 - 7
3 - 5
2 - 4
0.2 - 2.4
0.1 - 1.1
30 - 330
5 - 55
2 - 42
SWITCH 2RELATIVE TO
SWITCH 1MIN - (BAR) - MAX(SECONDARY ADJUSTER)
ADJUSTABLE DEADBANDSWITCHING LIMITS
DUAL MICROSWITCHADJUSTMENT LIMITS
0.45
0.35
0.3
0.25
0.2
0.1
0.05
0.01
0.005
1.45
1.35
1.25
1.25
1.2
0.55
0.30
0.15
0.030
TYPE
DP1
500
GU
ARD
IAN
DIF
FERE
NTI
AL P
RESS
URE
SW
ITCH
(DIA
PHRA
GM
CO
DE
01SB
)
3
cc
TYPE
DP1
500
GU
ARD
IAN
DIF
FERE
NTI
AL
PRES
SURE
SW
ITCH
(DIA
PHRA
GM
CO
DE
03SB
)
TYPE
DP1
500
GU
ARD
IAN
DIF
FERE
NTI
AL P
RESS
URE
SW
ITCH
(DIA
PHRA
GM
CO
DE
08SB
)
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1019 | issue 1
3
cc
GUARDIAN VACUUM/COMPOUND
The range is suitable for applications between 10 mBar and 950 mBar of vacuum. Dual microswitch and adjustable deadband options are available. A compound version is also available adjustable between -1 and +2 Bar, though it cannot be set within 150 mBar either side of the zero point or have an adjustable deadband.
V1100 GUARDIAN INDUSTRIAL & ATEX Exia CERTIFIED VACUUM SWITCH
FEATURES
IP66/IP67 certified housing.a Single or dual microswitch option. Adjustable deadband option.
a
SIL2 - IEC61508 proven reliability.a
ANC4B 316 stainless steel or black anodised aluminium switchcase.
a
Wetted parts NACE MR-01-75 compliant.a
VACUUM ANDCOMPOUND
Vacuum Settings from 10 to 950 mBar.a
Internal adjustment scalea
ATEX Certified OptionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
Manual reset pushbutton option.a
Wetted parts : 316 St. SteelDiaphragm : VitonProcess connections :1/4” BSP.P or NPT female.1/2” BSP.P or NPT female or male.
Electrical connection :M20 x 1.5 ISO female standardSuffix “F” for M25 x 1.5 ISO femaleor “C” for 1/2” NPT female
SPECIFICATION
PART NUMBERPREFIX WITH “S” FOR
STAINLESS STEEL SWITCHCASE
(S) V110_/B5_N30/SS5X
(S) V110_/B5_N07/SS5X
(S) V110_/B5_N14/SS5X
PROCESS CONNECTION71 = 1/4” BSP.P FEMALE72 = 1/4” NPT FEMALE10 = 1/2” BSP.P FEMALE74 = 1/2” NPT FEMALE82 = 1/2” BSP.P MALE84 = 1/2” NPT MALE
MICROSWITCH : 01 = SINGLE SWITCH02 = DUAL SWITCHES05 = SINGLE FOR EXIA06 = DUAL FOR EXIA
THE FITTING OF MEDIUM DIFFERENTIAL OR DUAL MICROSWITCHES MAY INCREASE THE DEADBAND BY A FACTOR OF TWO. DUAL MICROSWITCH ADJUSTMENT LIMITS ARE AVAILABLE FROM OUR SALES OFFICE
VACUUM PRESSURE VERSION
ADJUSTMENTRANGE (MBAR)
VACUUM
-950 to -150
-550 to -50
-130 to -10
MAX WORKING PRESS. (BAR)
13
5.5
1.4
DEADBAND (MBAR)
<70
<35
<10
SETTING SWITCH 2 (FROM SWITCH 1) MIN (MBAR) MAX
80 800
70 240
15 85
DRAWING
FIG. 7
FIG. 8
FIG. 9
-1 to +2 Bar 13 <100 CONTACT SALES (S) P110_/B5_N30/SS5X FIG. 6 PAGE 23
3
ccFIG
. 7 T
YPE
V100
0 G
UA
RDIA
N V
ACU
UM
SW
ITCH
67
36.5
65
92
76 36.5
157
26
52
40
Ø10.5
M8
MIC
RO
SWIT
CH
TER
MIN
ALS
INTE
RN
AL E
ARTH
TER
MIN
AL
ENTR
Y TH
REA
D S
IZE
1/4"
BSP
AD
APTO
R
1/4"
NPT
AD
APTO
R
1/2"
BSP
STA
ND
ARD
1/2"
NPT
AD
APTO
R
SEC
ON
D M
ICR
OSW
ITC
H2n
d. M
ICR
OSW
ITC
H A
DJU
STER
SC
REW
(HIG
HES
T PR
ESSU
RE
SETP
OIN
T)
1st.
MIC
RO
SWIT
CH
AD
JUST
ER R
ING
(LO
WES
T PR
ESSU
RE
SETP
OIN
T)A
DJU
STM
EN
T V
IA Ø
3mm
PIN
ADJU
STM
ENT
VIA
2mm
A/F
HEX
PRES
SUR
E AD
JUST
ER L
OC
KIN
G S
CR
EWAD
JUST
MEN
T VI
A 2m
m A
/F H
EX
WAR
NIN
GFA
CTO
RY
PRES
ETC
ALIB
RAT
ION
SC
REW
S
111
76.5
30
OPT
ION
AL 3
04 S
T. S
TL.
ANG
LED
MO
UN
TIN
G B
RAC
KET
110
130
MO
UN
TIN
G H
OLE
S Ø
8.5
THR
O
ELEC
TRIC
AL C
ON
DU
ITEN
TRY
M20
x 1
.5
1/2"
BSP
OR
1/2
" NPT
STE
M H
EAD
OF
SEC
ON
DAR
Y AD
JUST
ER M
ECH
ANIS
MPA
RT
VIEW
SH
OW
ING
ASS
EMBL
Y
HYS
TER
ESIS
AD
JUST
ING
CO
LLAR
AD
JUS
TME
NT
VIA
Ø3m
m P
IN
ADJU
STER
LO
CKI
NG
CO
LLAR
AD
JUS
TME
NT
VIA
Ø3m
m P
IN
10
PRES
SUR
E EN
TRY
(SEE
CH
ART)
TYPI
CAL
AR
RAN
GEM
ENT
DR
AWIN
GFO
R R
EFER
ENC
E O
NLY
27.5
7.5
35.5
162
+ 7.
5 =
169.
5
162
162
+ 27
.5 =
189
.5
162
+ 7.
5 =
169.
5
OVE
RAL
L D
IMEN
SIO
N
GU
ARD
V
FIG
. 8 T
YPE
V100
0 - 7
0 G
UA
RDIA
N V
ACU
UM
SW
ITCH
500
50275
RAB
65
92
MIC
RO
SWIT
CH
TER
MIN
ALS
SEC
ON
D M
ICR
OSW
ITC
H
INTE
RN
AL E
ARTH
TER
MIN
AL
2nd.
MIC
RO
SWIT
CH
AD
JUST
ABLE
SC
REW
(HIG
HES
T VA
CU
UM
SET
POIN
T)AD
JUST
ABLE
VIA
2m
m A
/F H
EX
1st.
MIC
RO
SWIT
CH
AD
JUST
ABLE
SC
REW
(LO
WES
T VA
CU
UM
SET
POIN
T)A
DJU
STA
BLE
VIA
Ø3m
m P
IN
VAC
UU
M A
DJU
STM
ENT
LOC
KIN
G S
CR
EWAD
JUST
ABLE
VIA
2m
m A
/F H
EX
WAR
NIN
GFA
CTO
RY
PRES
ETC
ALIB
RAT
ION
SC
REW
S
ELEC
TRIC
AL C
ON
DU
ITEN
TRY
M20
x 1
.5
52
2685
10
105
40
27.5
40
MO
UN
TIN
G H
OLE
S Ø
8.5
THR
O
110 65.5 7.5
M8
10.5
36.5
34.5
ENTR
Y TH
REA
D S
IZE
1/4"
NPT
AD
APTO
R
1/2"
BSP
STA
ND
ARD
1/2"
NPT
AD
APTO
R
1/4"
BSP
AD
APTO
R
PRES
SUR
E EN
TRY
(SEE
CH
ART)
186.0
50
60
67
76
m
34.5
TYPI
CAL
AR
RAN
GEM
ENT
DR
AWIN
GFO
R R
EFER
ENC
E O
NLY
190.
5 +
7.5
= 19
8
190.
5 +
7.5
= 19
8
190.
5
190.
5 +
27.5
= 2
18
OVE
RAL
L D
IMEN
SIO
N
GU
ARD
V70
3
cc
130
1070
RABm
FIG
. 9 T
YPE
V100
0 - 1
40 G
UA
RDIA
N V
ACU
UM
SW
ITCH
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
3
cc
GUARDIAN LOW - MEDIUM - HIGHTEMPERATURE
The standard range represents the basic models to cover temperature applications spanning -10 to +250°C. The T1100 is supplied fitted with a threaded thermowell, the T1200 has no thermowell but is supplied with a threaded stem. Dual microswitch options are available for alarm and shutdown applications.
T1100 & T1200 GUARDIANINDUSTRIAL & ATEX CERTIFIED Exia TEMPERATURE SWITCH
FEATURES
IP66/IP67 certified housing.a
Single or dual microswitch option.a
SIL2 - IEC61508 proven reliability.a
316 stainless steel or black anodised aluminium switchcase.
a
Wetted parts NACE MR-01-75 option.a
TEMPERATURE
Temperature Settings from -10 to +240°C.a
Internal adjustment scale.a
ATEX Certified OptionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
Temperature Limitations :Ambient : -10 to +80ºC standardProcess : -10 to max on table**Storage : -10 to +80ºC**** -50ºC is available as an option
Repeatibility : +/-1.5% of range (at operating temperature up to 40ºC)Calibration rate : 2ºC per minute rate of charge.
ADJUSTMENTRANGE
(°C)
-10 TO +40
0 TO +50
25 TO 75
50 TO 100
75 TO 125
100 TO 150
125 TO 175
150 TO 200
175 TO 225
200 TO 250
MAXIMUMTEMPERATURE
(ºC)
100
100
125
150
175
200
200
250
280
280
DEADBAND(ºC)
<10
<10
<10
<10
<10
<10
<10
<10
<10
<10
TEMPERATURECODE
L1
L2
M1
M2
M3
M4
M5
H1
H2
H3
THERMOWELL“U” DIMENSIONSIN MM
38, 45, 50, 60*, 75*, 100, 125, 150, 175, 200, 225, 250, 300, 350, 400, 600,660, 800, 1000 & 1200
*STANDARD LENGTHS
(S) T 1 1 0 1 / 0 6 0 M 2 / P A 1 X
P = WITH THERMOWELLS = WITHOUT THERMOWELL
PART NUMBER BREAKDOWN
MICROSWITCH OPTIONS01 = SINGLE SWITCH02 = DUAL SWITCHES03 = USE 0104 = USE 0205 = SINGLE - FOR Exia06 = DUAL FOR Exia09* = MANUAL AND AUTO (RESET RISING)0A* = MANUAL AND AUTO (RESET FALLING)0C* = MANUAL (RESET RISING)0D* = MANUAL (RESET FALLING)
TEMPERATUREELEMENT CODEREFER TO TABLE ON OPPOSITE PAGE
“U” DIMENSION WITHTHERMOWELL
T11 - WITH THERMOWELLT12 - WITHOUT THERMOWELL
PREFIX WITH ‘S’ FORSTAINLESS STEEL CASE
THERMOWELL /STEM1 = 316 ST. ST.4 = HIGH PRESS.0 = FLANGE OR SPECIAL THERMOWELL8 = SLIDING GLAND
THERMOWELL / STEM THREADA = 1/2” BSP.P F = 1” BSP.PB = 1/2” NPT G = 1” NPTC = 3/8” BSP.P K = 1/2” BSP.TD = 3/4” BSP.PE = 3/4” NPT0 = FLANGE OR SPECIAL THERMOWELL
*Change 0 to E for Exia certification
Thermowell and stem material :316 Stainless steelMax working pressure :35 Bar - standard420 Bar - high pressure
Thermowells can be provided flangedor screwed to suit the application. Allexotic metals can be catered for. Materialcertificates and wake frequency vibrationanalysis calculations can be provided.
Electrical connectionM20 x 1.5 ISO female standardSuffix “F” for M25 x 1.5 ISO female or “C” for 1/2” NPT female
SPECIFICATION
800
9
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1056 | issue 1
3
cc
GUARDIAN LOW - MEDIUM - HIGHTEMPERATURE
The standard range represents the basic models to cover temperature applications spanning -40 to +230°C. The T1700 is supplied fitted with a threaded thermowell, the T1800 has no thermowell but is supplied with a sliding gland. Capillary is 316 stainless steel armoured and is available from 2 to 10 metres in length. Dual microswitch options are available for simultaneous operation.
Deadband figures shown in the table below refer to single set points only, if dual microswitches are specified deadband may increase up to a factor of 2.
T1700 & T1800 INDUSTRIAL& ATEX Exia CAPILLARYTEMPERATURE SWITCH
FEATURES
IP66/IP67 certified housing.a Single or dual microswitch option.a
Internal adjustment scale.a
316 stainless steel or black anodised aluminium switchcase.
a
Wetted parts NACE MR-01-75 option.a
CAPILLARY TEMPERATURE
316 stainless steel armoured capillary from 2 to 10 metres
a
SIL2 - IEC61508 proven reliability.a ATEX Certified OptionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
Thermowell and stem material :316 stainless steelMax working pressure :35 Bar - standard420 Bar - high pressureElectrical connectionsM20 x 1.5 ISO female standard
Thermowells can be provided flangedor screwed to suit the application. Allexotic metals can be catered for. Materialcertificates and wake frequency vibrationanalysis calculations can be provided.
Suffix “F” for M25 X 1.5 ISO Femaleor “C” for 1/2” NPT female
ADJUSTMENTRANGE
(°C)
-40 TO -10
-15 TO +15
0 TO 30
20 TO 50
40 TO 70
60 TO 90
80 TO 110
100 TO 130
125 TO 155
150 TO 180
175 TO 205
200 TO 230
MAXIMUMTEMPERATURE
(ºC)
40
70
80
120
145
145
145
180
180
200
280
280
DEADBAND (ºC)
<10
<10
<10
<15
<15
<15
<15
<15
<15
<15
<15
<15
CAPILLARY CODE
40
41
42
45
43
43
43
44
44
44
46
46
Min bulb length according to capillary length 2m - 4m 5m - 7m 8m - 10m
100
100
100
100
100
100
100
100
100
100
100
100
100
150
150
150
100
100
100
100
100
100
100
100
100
200
200
200
100
100
100
100
100
100
100
100
Repeatibility : +/-1.5% of range (atoperating temperature up to 40ºC)Calibration rate : without thermowell, at2°C per minute rate of change.
Temperature Limitations :Ambient : -30 to +80ºC standardProcess : -40 to max on tableStorage : -40 to +80ºC
(S) T 1 7 0 1 / 4 3 - 3 - 1 - 6 / P A 1 0 0
STEM LENGTH1 = 150MM STANDARD2 = 250MM, 4 = 400MM6 = 600MM. (150MM NOT AVAILABLE WITH 150M OR 200MM BULB LENGTH)
PART NUMBER BREAKDOWN
MICROSWITCH OPTIONS01 = SINGLE SWITCH - STANDARD02 = DUAL SWITCHES03 = USE 0104 = USE 0205 = SINGLE FOR Exia06 = DUAL FOR Exia09* = MANUAL AND AUTO (RESET RISING)0A* = MANUAL AND AUTO (RESET FALLING)0C* = MANUAL (RESET RISING)0D* = MANUAL (RESET FALLING)
CAPILLARY LENGTH2 METRES MINIMUM10 METRES MAXIMUM
SLIDING GLAND THREAD3 = 1/2” BSP.P6 = 1/2” NPT
CAPILLARY CODEREFER TO TABLE ON OPPOSITE PAGE
T17 - WITH THERMOWELLT18 - WITHOUT THERMOWELL
PREFIX WITH ‘S’ FORSTAINLESS STEEL SWITCHCASE
THERMOWELL LENGTH100 = 100MM STANDARDIF NOT REQUIRED LEAVE BLANK (OTHER LENGTHS, THREADS AND FLANGES ARE AVAILABLE.PLEASE CONTACT OUR SALES OFFICE).
THERMOWELL CONN. (STANDARD)PA = 1/2” BSP.P PB = 1/2” NPTPC = 3/8” BSP.P PD = 3/4” BSP.PPE = 3/4” NPT PF = 1” BSP.PPG = 1” NPT
*Change 0 to E for Exia certification
THERMOWELL CONN. (HIGH PRESSURE)HA = 1/2” BSP.P HB = 1/2” NPT HC = 3/8” BSP.P HD = 3/4” BSP.PHE = 3/4” NPT HF = 1” BSP.PHG = 1” NPT
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1055 | issue 1
3
cc
GUARDIAN ULTRA LOW PRESSURE / VACUUM
The standard ranges cover differential pressure applications for settings from 2 mBar to 55 mBar. Dual microswitch and adjustable deadband options are available as detailed overleaf.
DP1500 GUARDIAN INDUSTRIAL & ATEX CERTIFIED Exia ULTRA LOW PRESSURE SWITCH
FEATURES
IP66/IP67 certified housing.a
Single or dual microswitch option. Adjustable deadband option.
a
SIL2 - IEC61508 proven reliability.a
316 stainless steel or black anodised aluminium switchcase.
a
Wetted parts NACE MR-01-75 compliant.a
ULTRA LOWPRESSURE / VACUUM
Differential pressure settings from 2 mBar to 55 mBar.
a
Internal adjustment scale.a
Manual reset pushbutton option.a
ATEX Certified OptionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
ADJUSTMENTRANGEMBAR
5 - 55
2 - 42
ADJUSTMENTRANGE
”WG
2 - 20
1 - 16
0.35
0.35
0.5 ∆
0.5 ∆
MAX WORKING PRESS. (BAR)
DEADBANDMBAR
<6
<3
DIAPHRAGMCODE
08SB
08SB
SPRINGCODE
2
1
STANDARD VITONDIAPHRAGM
Dual microswitches may increase the deadband by a factor of two.
MAXIMUM DEADBANDAT TOP OF
RANGE(BAR) *MBAR
*17
*17
MINIMUM DEADBANDAT TOP OF
RANGE(BAR) *MBAR
*3
*3
ADJUSTMENT RANGE (BAR) (FALLING SET POINTS ONLY)
SWITCH 1
5 - 55
2 - 42
MAXIMUM DEADBANDAT BOTTOM OF RANGE
(BAR) *MBAR
*12
*12
MINIMUM DEADBANDAT BOTTOM OF RANGE
(BAR) *MBAR
*3
*3
SWITCH 2RELATIVE TO
SWITCH 1MIN - (BAR) - MAX(SECONDARY ADJUSTER)
ADJUSTABLE DEADBANDSWITCHING LIMITS
DUAL MICROSWITCHADJUSTMENT LIMITS
0.01
0.005
0.15
0.030
SPECIFICATIONTemperature limitationsDiaphragm code : 08SBViton : -10 to + 150˚CNitrile : -25 to +95˚C
Wetted parts : 316 Stainless steel
Process connections : Code 08SB compression fittings or threaded connections as shown overleaf.
Electrical connections : M20 x 1.5 ISO female standard. Suffix “F” for M25 x 1.5 ISO femaleor “C” for 1/2” NPT female
3
cc0C* = MANUAL (RESET RISING)0D* = MANUAL (RESET FALLING)0E* = DUAL HIGH CURRENT DC0M* = SINGLE HIGH DC CURRENT*Change 0 to E for Exia certification
(S) P 1 5 0 1 / A 1 N 0 8 S B 4 / S S X
SPRING CODE
SEE RANGE TABLE
DIAPHRAGM CODE
SEERANGE TABLE
PART NUMBER BREAKDOWN
MICROSWITCH OPTIONS01 = SINGLE SWITCH02 = DUAL SWITCHES03 = USE 0104 = USE 0205 = SINGLE FOR Exia06 = DUAL FOR Exia
ADJUSTABLE DEADBAND07 = SINGLE SWITCH - STANDARD08 = SINGLE SWITCH - USE FOR Exia
09* = MANUAL AND AUTO (RESET RISING)0A* = MANUAL AND AUTO (RESET FALLING)
N = STANDARD ADJUSTERA = SECONDARY ADJUSTER (FOR DUAL SETTING OR ADJUSTABLE DIFFERENTIAL MECHANISM)
DIAPHRAGMA = NITRILEB = VITON
P15 = PRESSUREV15 = VACUUMPREFIX WITH ‘S’ FOR STAINLESS STEEL SWITCHCASE
MOUNTING DETAILSX = 01SB CASE MOUNTINGN = 02SB & 03SB BRACKETX = 08SB BRACKETE = 2” PIPE BRACKET
PROCESS CONNECTIONS FOR DIAPHRAGM CODE 08SB
K = 1/4” BSP.P FEMALE STRAIGHT PR VACM = 1/4” BSP.T FEMALE STRAIGHT PR VACP = 1/4” BSP.P MALE STRAIGHT PR VACR = 1/4” NPT FEMALE STRAIGHT PR VACT = 1/4” NPT MALE STRAIGHT PR VACV = 1/2” NPT FEMALE STRAIGHT PR VAC
4 = 1/4” O/D TUBE POSI. ELBOW PR5 = 1/4” O/D TUBE POSI. ELBOW VACB = 6mm O/D TUBE PR/VACD = 8mm O/D TUBE PR/VACF = 10mm O/D TUBE PR/VACH = 12mm O/D TUBE PR/VAC
FIG
. 12
TYPE
DP1
500
GU
ARD
IAN
DIF
FERE
NTI
AL P
RESS
URE
SW
ITCH
(DIA
PHRA
GM
CO
DE
08SB
)
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1054 | issue 1
3
cc
GUARDIAN MEDIUM PRESSURE
The standard range represents the basic models to cover pressure applications for settings of between 0.2 and 19 bar (3 to 270 PSI). Dual microswitch and adjustable differential options are available as detailed overleaf.
P1100 & P1200 GUARDIAN INDUSTRIAL & ATEX Exia CERTIFIED PRESSURE SWITCH
FEATURES
IP66/IP67 certified housing.a
Single or dual microswitch option. Adjustable deadband option.
a
SIL2 - IEC61508 proven reliability.a
316 stainless steel or black anodised aluminium switchcase.
a
Wetted parts NACE MR-01-75 compliant.a
PRESSURE
Pressure Settings from 200 mBar to 19 Bar.a
Internal adjustment scale.a
Manual reset pushbutton option.a
ATEX Certified OptionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
ADJUSTMENTRANGE(BAR)
9 - 19
4 - 12
2 - 6
1 - 3
0.2 - 1.4
0.3 - 2.5
0.6 - 6.2
1.2 - 12.4
ADJUSTMENTRANGE
(PSI)
130 - 270
60 - 80
30 - 90
15 - 45
3 - 20
5 - 35
10 - 90
20 -180
24
24
16
12
12
12
16
24
50
50
40
12
12
12
40
50
MAX WORKING PRESS. (BAR)
NITRILE VITON
DEADBAND(BAR)
<1.9
<1.2
<0.6
<0.3
<0.2
<0.3
<0.6
<1.3
DIAPHRAGMCODE
15
15
21
30
30
30
21
15
SPRINGCODE
R
0
0
0
1
2
2
2
STANDARD NITRILEDIAPHRAGM
The fitting of a Viton diaphragm or dual microswitches mayincrease the deadband by a factor of two. Microswitchesother than shown below may also increase the deadband.
SPECIFICATIONWetted parts : 316 St. steel or Monel
Diaphragm : Nitrile or Viton
Pressure Limitations : See table below. All switches can be subjected to a full vacuum.
Process connections : 1/4” or 1/2”BSP.P or NPT female (bottom)1/4” BSP.P or NPT female (side)1/2” BSP.P or NPT male (bottom)
Electrical connections :M20 x 1.5 ISO female standardSuffix “F” for M25 x 1.5 ISO female or “C” for 1/2” NPT female
3
cc 3
c c
(S) P 1 1 0 1 / A 0 1 0 N 3 0 / S S 1 X
P11 : CASE MOUNTED - STANDARDFEMALE PROCESS CONNECTIONP12 : STEM MOUNTINGMALE PROCESS CONNECTION
DIAPHRAGMA = NITRILEB = VITON - STD
SPRING CODE
SEE RANGE TABLE
DIAPHRAGM CODE
SEE RANGE TABLE
PART NUMBER BREAKDOWNPROCESS ENTRY ORIENTATIONS = STRAIGHT ENTRY - BOTTOMA = ANGLED ENTRY - SIDE
WETTED PARTSS = 316 ST. ST.M = MONEL
ANODISED ALUMINIUM CASE AS STANDARD IF ST. STEEL REQUIRED PREFIX “S”
MICROSWITCH OPTIONS01 = SINGLE SWITCH02 = DUAL SWITCHES03 = USE 0104 = USE 0205 = SINGLE FOR Exia06 = DUAL FOR Exia
ADJUSTABLE DEADBAND07 = SINGLE SWITCH - STANDARD08 = SINGLE SWITCH - USE FOR Exia
09* = MANUAL AND AUTO (RESET RISING)0A* = MANUAL AND AUTO (RESET FALLING)
E = 2”STANDPIPEBRACKET
X = STD
N = OPTIONAL MOUNTING BRACKET
0C* = MANUAL (RESET RISING)0D* = MANUAL (RESET FALLING)0E* = DUAL HIGH CURRENT DC0M* = SINGLE HIGH CURRENT DC SWITCHING
*Change 0 to E for Exia approval
PROCESS CONNECTION TYPEP11: 10 - STANDARD FEMALEP12: 22 = 1/2” BSP.P MALE 24 = 1/2” NPT MALE 61 = 1” BSP.P MALEFLUSH DIAPHRAGM ONLY AVAILABLE ON 1.2 - 12.4 BARWITH MAX OF 16 BAR
N = STANDARD ADJUSTERA = SECONDARY ADJUSTER(FOR ADJUSTABLE DEADBAND)
PROCESS ENTRY SIZE FOR P11001 = 1/4” BSP.P FEMALE2 = 1/4” NPT. FEMALE5 = 1/2” BSP.P FEMALE6 = 1/2” NPT. FEMALEFOR P12 (MALE) USE = 1
EXAMPLE. Dual microswitches - if switch 1 is set at 10 Bar on a 4 - 12 Bar range switch 2 can be set at the same pressure or between 10.2 and 12.0 Bar with standard adjuster and between 10.7 and 14.5 bar with secondary adjuster. With the second-ary adjuster fitted microswitches cannot be set together.Note: 1) Lowest set point is always switch 1 on dual set point switches. 2) Adjustable deadband mechanism actuates on falling settings, therefore reset on rising pressure.
ADJUSTABLE DEADBANDSWITCHING LIMITS
DUAL MICROSWITCHADJUSTMENT LIMITS
MAXIMUM DIFF
AT TOP OF RANGE(BAR)
6.5
3.7
3.5
2
0.75
0.6
2.5
4
MINIMUM DIFF
AT TOP OF RANGE(BAR)
2.5
1.6
0.7
0.45
0.25
0.25
0.4
1.5
ADJUSTMENT RANGE (BAR) (FALLING SET POINTS ONLY)
SWITCH 1
MAXIMUM DIFF
AT BOTTOM OF RANGE
(BAR)
6.0
3.5
2.5
1.7
0.55
0.45
1.45
3.25
MINIMUM DIFF
AT BOTTOM OF RANGE
(BAR)
2.0
1.1
0.5
0.3
0.15
0.15
0.25
0.6
SWITCH 2RELATIVE TO
SWITCH 1MIN - (BAR) - MAX(SECONDARY ADJUSTER)
0.1 7.5
0.7 4.5
0.3 2.8
0.17 1.2
0.08 1.1
0.3 2.0
0.3 2.6
1.0 7.5
SWITCH 2RELATIVE TO
SWITCH 1MIN - (BAR) - MAX(STANDARD ADJUSTER)
0.3 3.0
0.2 2.0
0.08 1.0
0.05 0.35
NOT
AVAILABLE
9 - 19
4 - 12
2 - 6
1 - 3
0.2 - 1.4
0.3 - 2.5
0.6 - 6.2
1.2 - 12.4
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1053 | issue 1
3
cc
GUARDIAN LOW PRESSURE
This range of switches employs a non-reinforced elastomer sensing element for settings between 8 and 250 mBar. A special feature of the Guardian switch is the wide selection of microswitches that can be fitted eg. single, dual, adjustable dead band, high current DC switching options etc. Reliable and proven design concepts from our established range of switches have also been incorporated. This provides a very competitively priced, lightweight and durable sensor.
P1100 GUARDIAN ATEX Exia CERTIFIED & INDUSTRIAL LOWPRESSURE SWITCH
FEATURES
IP66/IP67 certified housing.a
SPECIFICATION
Internal adjustment scale.a
316 stainless steel or black anodised aluminium switchcase.
aSingle or dual microswitch option. Adjustable deadband option.
a
Wetted parts : 316 St. steel
Diaphragm : Nitrile or Viton
Process connection : 1/4” BSP.P orNPT female
Process temperature limitations :Nitrile: -25 to +95˚CViton: -10 to +150˚C
LOW PRESSURE
Settings from 8 to 250 mBar.a
SIL2 - IEC 61508 proven reliability.a
ATEX intrinsically safe versionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
P 1 1 0 1 / 8 1 N S 3 1 / N X
P11 : STANDARD DIAPHRAGM MATERIAL8 = NITRILE9 = VITON - STD
SPRING CODEPLEASE REFER TO
RANGE TABLE
DIAPHRAGM CODEPLEASE REFER TO
RANGE TABLE
MOUNTINGBRACKET
PART NUMBER BREAKDOWN
MICROSWITCH OPTIONS01 = SINGLE SWITCH02 = DUAL SWITCHES03 = USE 0104 = USE 0205 = SINGLE FOR ATEX Exia06 = DUAL FOR ATEX Exia
ADJUSTABLE DEADBAND07 = SINGLE SWITCH - STANDARD08 = SINGLE SWITCH - FOR ATEX Exia
09* = MANUAL AND AUTO (RESET RISING)0A* = MANUAL AND AUTO (RESET FALLING)0C* = MANUAL RESET (RISING)0D* = MANUAL RESET (FALLING)
0E* = DUAL HIGH CURRENT DC0K* = DPDT MICROSWITCH0M* = SINGLE HIGH CURRENT DC*Change 0 to E for Exia approval
PROCESS CONNECTION TYPE1 = 1/4” BSP.P FEMALE2 = 1/4” NPT FEMALE
ELECTRICALCONNECTION X = M20 STANDARDC = 1/2” NPT FEMALEF = M25 FEMALE
ADJUSTERN = STANDARD ADJUSTERA = SECONDARY ADJUSTERFOR DUAL SETTING OR ADJUSTABLE DEADBAND
FOR STAINLESS STEEL SWITCHCASE PREFIX PART NUMBER WITH “S”
ADJUSTMENTRANGE(mBAR)
50 - 250
8 - 128
ADJUSTMENTRANGE
“WG
20 - 100
5 - 50
7.0
5.0
MAX WORKING PRESSURE
(BAR)
DEADBAND(MBAR)
10 - 30
5 - 15
DIAPHRAGMCODE
S3
S4
SPRINGCODE
1
1
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1052 | issue 1
3
cc
GUARDIAN HIGH PRESSURE
The range incorporates a 316 stainless steel piston with ‘O’ ring seal to cover settings from 1.5 to 640 Bar (20 to 9300 PSI) with a maximum pressure of 700 Bar (10000 PSI). Dual microswitch and adjustable deadband options are available.
P1300 & P1400 GUARDIANINDUSTRIAL & ATEX Exia CERTIFIED PRESSURE SWITCH
FEATURES
IP66/IP67 certified housing.a
Single or dual microswitch option. Adjustable deadband option.
a
SIL2 - IEC61508 proven reliability.a
316 stainless steel or black anodised aluminium switchcase.
a
Wetted parts NACE MR-01-75 compliant.a
HIGH PRESSURE
Pressure Settings from 1.5 Bar to 640 Bar.a
Calibrated adjustment scale.a
Manual reset pushbutton option.a
ATEX Certified OptionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
ADJUSTMENTRANGE(BAR)
440 - 640
290 - 490
160 - 360
115 - 160
80 - 125
45 - 90
30 - 75
15 - 40
5 - 23
1.5 - 17.5
ADJUSTMENTRANGE
(PSI)
6400 - 9300
4200 - 7100
2300 - 5300
1700 - 2300
1200 - 1800
650 - 1250
450 - 1050
220 - 520
70 - 340
20 - 250
MAX WORKING PRESS. (BAR)
700
700
700
700
700
700
700
700
700
700
DEADBAND(BAR)
<32
<25
<16
<8
<6.5
<4.5
<4.0
<2.0
<3.0
<1.25
PISTONCODE
1
1
1
3
3
3
3
4
4
6
SPRINGCODE
B
G
R
B
G
R
0
0
1
2
HIGH PRESSURE PISTON ACTUATED - P1300 & P1400
The fitting of dual microswitches may increase the deadband by a factor of two.The fitting of PTFE or EPDM ‘O’ rings may increase the deadband by a factor of 3.
0C* = MANUAL (RESET RISING)0D* = MANUAL (RESET FALLING)0E* = DUAL HIGH CURRENT DC SWITCHING0M* = SINGLE HIGH CURRENT DC SWITCHING
(S) P 1 3 0 1 / B B 3 4 N 2 2 / S S 3 X
PART NUMBER BREAKDOWN
MICROSWITCH OPTIONS01 = SINGLE MICROSWITCH02 = DUAL MICROSWITCH03 = USE 0104 = USE 0205 = SINGLE FOR Exia USE06 = DUAL FOR Exia USE
ADJUSTABLE DEADBAND07 = SINGLE SWITCH - STANDARD08 = SINGLE SWITCH - USE FOR Exia
09* = MANUAL AND AUTO (RESET RISING)0A* = MANUAL AND AUTO (RESET FALLING)
PROCESS CONNECTIONP13 -1/4” BSP.F = 31_22(FEMALE) -1/4” NPT.F = 32_22STANDARD -1/2” BSP.F = 33_22 -1/2” NPT.F = 34_22P14 -1/2” BSP.M = 41_22(MALE) -1/2” NPT.M = 42_22
PISTON CODESEE TABLE
MOUNTINGP13 : CASE MOUNTED - STANDARDP14 : STEM MOUNTED
SEAL MATERIALA = NITRILE B = VITON (STANDARD)D = PTFE - FOR SETTING ABOVE 10 BAR100 BAR MAX. FEMALE CONN. ONLYE = EPDM - NOT AVAILABLE ON “7”PISTON CODE. FEMALE CONN. ONLYH = HMBR HYDROGENATED NITRILE
S = STANDARD
WETTED PARTSS = 316 STAINLESS
SWITCHCASES = STAINLESS STEELIF ALUMINIUM CASE REQUIRED LEAVE BLANK
BRACKETX = CASE MOUNTEDN = OPTIONAL MOUNTING BRACKET
N = STANDARD ADJUSTERA = SECONDARY ADJUSTER(FOR ADJUSTABLE DEADBAND)
SPRING CODE
SEE RANGE TABLE
*Change 0 to E for Exia certification
3
cc
MAXIMUM DIFF
AT TOP OF RANGE(BAR)
90
90
85
25
21
21
23.5
12.5
10.5
6.5
MINIMUM DIFF
AT TOP OF RANGE(BAR)
45
40
35
11
11
8
7.5
3.5
6.0
1.5
MAXIMUM DIFF
AT BOTTOM OF RANGE
(BAR)
90
90
80
25
20
21
18.3
12.5
9.5
4.5
MINIMUM DIFF
AT BOTTOM OF RANGE
(BAR)
40
30
25
11
8
6
5.8
3.5
3.5
1
SWITCH 2RELATIVE TO
SWITCH 1MIN - (BAR) - MAX(SECONDARY ADJUSTER)
25 - 140
25 - 140
25 - 140
5 - 27
5 - 27
5 - 27
5 - 27
4 - 22
4 - 22
2 -10
SWITCH 2RELATIVE TO
SWITCH 1MIN - (BAR) - MAX(STANDARD ADJUSTER)
4.5 - 31.5
4.5 - 31.5
4.5 - 31.5
1.1 - 7.9
1.1 - 7.9
1.1 - 7.9
1.1 - 7.9
0.7 - 5.0
0.7 - 5.0
0.4 - 2.6
ADJUSTABLE DEADBANDSWITCHING LIMITS
DUAL MICROSWITCHADJUSTMENT LIMITS
ADJUSTMENT RANGE (BAR) (FALLING SET POINTS ONLY)
SWITCH 1
440 - 640
290 - 490
160 - 360
115 - 160
80 - 125
45 - 90
30 - 75
15 - 40
5 - 23
1.5 - 17.5
SPECIFICATIONWetted parts : 316 Stainless steel
Seal : Nitrile or Viton, PTFE or EPDM
Pressure Limitations : See table below. All switches can be subjected to a full vacuum.
Process connections : 1/4” or 1/2”BSP.P or NPT female (bottom) or1/2” BSP.P or NPT male (bottom).
Electrical connectionsM20 x 1.5 ISO female standardSuffix “F” for M25 x 1.5 ISO femaleor “C” for 1/2” NPT female
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1051 | issue 1
3
cc
GUARDIAN FLUSH DIAPHRAGM
The range incorporates a flush diaphragm for settings of between 0.1 and 34 bar (2 to 500 PSI). Dual microswitch and adjustable deadband options are available.
P1100 GUARDIAN INDUSTRIAL & ATEX Exia CERTIFIED FLANGE MOUNTED PRESSURE SWITCH
FEATURES
IP66/IP67 certified housing.a
SPECIFICATION
Single or dual microswitch option. Adjustable deadband option.
a
SIL2 - IEC61508 proven reliability.a
316 stainless steel or black anodised aluminium switchcase.
a
Wetted parts NACE MR-01-75 compliant.a
Wetted parts : 316 St. Steel
Diaphragm : Viton
Pressure Limitations : Please refer to range table. All switches can be subjected to a full vacuum.
Process connections : See part no. breakdown overleaf.
FLUSH DIAPHRAGM
Pressure Settings from 100 mBar to 34 Bar.a
Internal adjustment scale.a
Manual reset pushbutton option.a
ATEX Certified OptionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
ADJUSTMENTRANGE(BAR)
24 - 34
14 - 24
8.0 - 18
4.0 - 13
0.5 - 6.0
0.1 - 1.7
ADJUSTMENTRANGE
(PSI)
350 - 500
200 - 350
120 - 260
60 - 185
10 - 90
2 -24
40
40
40
40
40
12
DEADBAND(BAR)
<3.4
<2.4
<1.8
<1.3
<0.6
<0.2
DIAPHRAGMCODE
15
15
15
15
15
32
SPRINGCODE
B
G
R
0
1
1
FLUSH DIAPHRAGM FLANGE MOUNTED
The fitting of dual microswitches may increase the deadband by a factor of two.
MAX WORKING PRESS. (BAR)
0C* = MANUAL RISING0D* = MANUAL FALLING0E* = DUAL HIGH CURRENT DC SWITCHING0M* = SINGLE HIGH CURRENT DC SWITCHING
*Change 0 to E for Exia certification
( S ) P 1 1 0 1 / V 0 1 0 N 1 5 / F S 2 X
DIAPHRAGMV = VITONSTANDARD
N = NITRILE
10 = STD
SPRING CODE
SEE RANGE TABLE
DIAPHRAGM CODE
SEE RANGETABLE
PART NUMBER BREAKDOWN
SWITCHCASES = STAINLESS STEEL
IF ALUMINIUM CASE REQUIRED LEAVE BLANK
MICROSWITCH OPTIONS01 = SINGLE SWITCH02 = DUAL SWITCHES03 = USE 0104 = USE 0205 = SINGLE FOR Exia USE06 = DUAL FOR Exia USE
ADJUSTABLE DEADBAND07 = SINGLE SWITCH - STANDARD08 = SINGLE SWITCH - USE FOR Exia
09* = MANUAL AND AUTO (RESET RISING)0A* = MANUAL AND AUTO ( RESET FALLING)
BS EN1092-1 FLANGE(REPLACES BS4504)2 = DN50 PN40 FLANGE3 = 2” ANSI FLANGE 150 #4 = 2” ANSI FLANGE 300 #DEPTH OF FLANGE INCREASED TO ALLOW FOR HIGHER PRESSURE & TEMPERATURE RATING
N = STANDARD ADJUSTERA = SECONDARY ADJUSTER (FOR DUAL SETTINGS OR ADJ. DEADBAND)F = FIXED ADJUSTER - REFER TO SALES
F = FLUSH DIAPHRAGM FLANGE MOUNTED
FLANGE MATERIALS = 316 ST. STEEL
Electrical connectionsM20 x 1.5 ISO female standardSuffix “F” for M25 x 1.5 ISO female or “C” for 1/2” NPT female
3
cc
0.5
31.75
52
ELEC
TRIC
AL C
ON
DU
ITEN
TRY
M20
x 1
.5
INTE
RN
AL E
ARTH
TER
MIN
AL
SEC
ON
D M
ICR
OSW
ITC
H
MIC
RO
SWIT
CH
TER
MIN
ALS
65
9267
CAL
IBR
ATIO
N S
CR
EWS
FAC
TOR
Y PR
ESET
WAR
NIN
G
ADJU
STM
ENT
VIA
2mm
A/F
HEX
PRES
SUR
E AD
JUST
ER L
OC
KIN
G S
CR
EW
ADJU
STM
ENT
VIA
2mm
A/F
HEX
1st.
MIC
RO
SWIT
CH
AD
JUST
ER R
ING
(HIG
HES
T PR
ESSU
RE
SETP
OIN
T)2n
d. M
ICR
OSW
ITC
H A
DJU
STER
SC
REW
AD
JUS
TME
NT
VIA
Ø3m
m P
IN(L
OW
EST
PRES
SUR
E SE
TPO
INT)
PAR
T VI
EW S
HO
WIN
G A
SSEM
BLY
OF
SEC
ON
DAR
Y AD
JUST
ER M
ECH
ANIS
M
S80 90
I
7060P
AD
JUS
TME
NT
VIA
Ø3m
m P
INH
YSTE
RIS
IS A
DJU
STIN
G C
OLL
ARA
DJU
STM
EN
T V
IA Ø
3mm
PIN
ADJU
STER
LO
CKI
NG
CO
LLAR
MAX
MIN
H SY
TYPI
CAL
AR
RAN
GEM
ENT
DR
AWIN
GFO
R R
EFER
ENC
E O
NLY
GU
ARD
FLU
Ø10
2
Ø16
5
87
PN40
FLA
NG
EPN
40 F
LAN
GE
174
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1050 | issue 1
3
cc
GUARDIAN VERTICAL MOUNTING
These liquid level switches are designed to give indication or pump control of levels in tanks, vessels or sumps. The float travels unrestricted up or down the rod in response to level change between limits set by the upper and lower adjustable collars which are fixed in position at preselected points. This action operates an SPCO/SPDT microswitch dependant on application.
L1200 GUARDIAN INDUSTRIAL & ATEX Exia CERTIFIED VERTICAL LEVEL SWITCH
FEATURES
IP66/IP67 certified housing.a Manual reset pushbutton option.a
Single or dual microswitch option.a
316 stainless steel or black anodised aluminium switchcase.
a
ATEX Certified OptionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
VERTICAL LEVEL
SIL2 - IEC61508 proven reliabilitya
SPECIFICATIONProcess limitations : For use on non-pressurised systems.
Max. temperature : 100ºC
SG : Minimum 0.8
Switching action :1) High or low level alarms2) High and low level alarms3) Pump control
Float and Rod : 316 Stainless steelwith nitrile bonded seal.
Mounting : 3/4” BSP.P thread suitable for 27mm OD hole supplied with a bonded seal and backing nut.
Electrical connectionM20 x 1.5 ISO female standardSuffix “F” for M25 x 1.5 ISO femaleor “C” for 1/2” NPT female
*Please note : Rod length to be stated upon ordering. Min. 500mm - Max. 2000mm
PART NUMBERPREFIX WITH ‘S’ FOR STAINLESS STEEL SWITCHCASE
(S) L 1 2 _ / A F S 0 0 1 S / X
MICROSWITCH OPTIONS01 = SINGLE SWITCH02 = DUAL SWITCHES03 = USE 0104 = USE 0205 = SINGLE - FOR Exia USE06 = DUAL - FOR Exia USE
0B = PUMP CONTROL0F = PUMP CONTROL - FOR EXIA USEREFER TO RATINGS ON PAGE 11
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1048 | issue 1
3
cc(Horizontal version available)a
GUARDIAN VERTICAL MOUNTING
This range of magnet operated reed switches are equipped with hermetically sealed reed contacts. The float is fitted with an annular magnet which moves freely between two collars to open or close the reed contacts. As standard all wetted parts are 316 stainless steel, however they can be manufactured from different materials to suit a vast range of applications.
L120 GUARDIAN INDUSTRIAL & ATEX Exia VERTICAL REED LEVEL SWITCH
FEATURES
IP66/IP67 certified housing.a
Custom lengths from 50 to 2000mm.a
Single or dual microswitch option.a
ANC4B 316 stainless steel or black anodised aluminium switchcase.
a
ATEX Certified OptionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
L120 GUARDIAN INDUSTRIAL & ATEX EXIA VERTICAL REED LEVEL SWITCH
SIL2 - IEC61508 proven reliabilitya
L 1 2 1 / 1 B 2 5 0 C R / 4 1 0 C R
SWITCHCASE : PREFIX “S” FOR 316 STAINLESS STEEL, LEAVE BLANK IF ALUMINIUM REQUIRED
THREAD 1B = 1” BSP.P1N = 1” NPT
PART NUMBER BREAKDOWNSWINGING ACTIONCR = CLOSE RISING, OR = OPEN RISINGCF = CLOSE FALLING, OR = OPEN FALLINGD = SPDT CHANGEOVER
NUMBER OF FLOATS1 = SINGLE LEVEL2 = DUAL LEVELFOR Exia APPLICATIONS5 = SINGLE LEVEL6 = DUAL LEVEL
FIRST LEVEL FROM HEX.SWITCHING LEVEL : IN MM, MEASURED UNDERNEATH HEX. SWIVEL ADAPTORACCURACY + / - 5MM
SECOND LEVEL FROM HEX.SWITCHING LEVEL : IN MM, MEASURED UNDERNEATH HEX. SWIVEL ADAPTORACCURACY + / - 5MM
SPECIFICATIONHousing : 316 St St or black anodised aluminium
Wetted parts : 316 St St with nitrile seal
Float Diameter : 28mm
Process connection : 1” BSP.P or NPT thread with swivel connection
Electrical connection : Clamp type terminal block for cable sizes up to 2.5mm2
Switching : SPST standard, SPDT option
Max. working pressure : 10 bar
Max. working temperature : 100ºC
Max. voltage : 240 VAC/30 VDC
Max. Amps : 0.5 Resistive
Max. power : 10W
Electrical connectionM20 x 1.5 ISO female standard Suffix “F” for M25 x 1.5 ISO female or “C” for 1/2” NPT female
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1047 | issue 1
3
cc
GUARDIAN HORIZONTAL MOUNTING
These liquid level switches are designed to give indication of high or low level alarms in tanks or vessels. They are fitted with a round or cylindrical float, the movement of which operates an SPCO microswitch via an offset pivot and push rod. A second microswitch can be fitted to give an additional signal.
The switch can be installed either via a 27mm clearance hole, utilising the joint washer and back nut supplied, and the float re-attached to the rod. Where there is no access to the tank interior, the cylindrical float with 2”/50mm flange version enables installation without removing and re-attaching the float.
L1100 GUARDIAN INDUSTRIAL & ATEX Exia CERTIFIED HORIZONTAL LEVEL SWITCH
FEATURES
IP66/IP67 certified housing.a
SIL 2 - IEC 61508 proven reliability.a
Single or dual microswitch option.a
316 stainless steel or black anodised aluminium switchcase.
a
ATEX Certified OptionCE II1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
HORIZONTAL LEVEL
PART NUMBERPREFIX WITH ‘S’ FOR STAINLESS STEEL SWITCHCASE
(S) L 1 1 _ / F S 0 5 _ S / X
MICROSWITCH OPTIONS01 = SINGLE SWITCH02 = DUAL SWITCHES03 = USE 0104 = USE 0205 = SINGLE - FOR Exia USE06 = DUAL - FOR Exia USE
FLOATFS050 = ROUND 4” RODFS051 = CYLINDRICAL 4” RODFS052 = CYLINDRICAL 8” RODFS053 = CYLINDRICAL 2” ROD
MOUNTINGX = NO FLANGE OR BRACKETA = 2” ANSI 150#B = DN50 BSEN1092-1 FLANGE PN16
FLOAT MATERIALS = 316 STAINLESS STEEL - STANDARDP = POLYPROPYLENE
SPECIFICATIONProcess limitations : Full vacuum.Max. pressure : 3.5 Bar (spherical float only).Max. temperature : 100˚C
Switching action : High or Low level alarm (exact re-quirement to be stated upon ordering).
Electrical connectionM20 x 1.5 ISO female standardSuffix “F” for M25 x 1.5 ISO femaleor “C” for 1/2” NPT female
Float and Rod : 316 Stainless steelwith nitrile bonded seal.
Mounting : 3/4” BSP.P thread suitable for 27mm OD hole supplied with a bonded seal and backing nut. Alternatively a suitably sized flange can be provided to enable insertion complete with float.
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1046 | issue 1
3
cc
GUARDIAN
FLOW F1100
This design comprises orifice plate, differential pressure sensitive element and switching mechanism in a compact assembly which enables easy installation between pipe flanges.
F1100 GUARDIAN INDUSTRIAL& ATEX Exia CERTIFIED LIQUID FLOW SWITCH
FEATURES
Pipe sizes from 0.5” to 10” (15 to 250mm).a
IP66/IP67 certified housing.a
FLOW F1100
SIL 2 - IEC 61508 proven reliability.a
Single or dual microswitch option.a
ANC4B 316 stainless steel or black anodised aluminium switchcase.
a
SPECIFICATIONFlange casting: Gunmetal - std316 stainless steel, Monel or Tufnol(Tufnol option on industrial version only)Orifice plate: 316 Stainless steel - std or acetal 66 (for Tufnol flanges)Pressure parametersMetallic flanges: 8 bar / 12 bar testTufnol flanges: 12 bar / 18 bar testTemperature parametersNitrile : -40 to +90ºCViton : -20 to +100ºC
ATEX Certified OptionCE EX I1G Ex ia IICT6 Tamb -50 to +78˚CT5 Tamb -50 to +93˚CT4 Tamb -50 to +128˚C
a
Electrical connectionM20 x 1.5 ISO female standardSuffix “F” for M25 x 1.5 ISO femaleor “C” for 1/2” NPT femaleDiaphragm : Nitrile - with Tufnol flanges Viton - with Metallic flanges
PART NUMBER BREAKDOWN
( S ) F 1 1 0 1 / A 1 0 1 0 0 1 0 / 1 1 XMICROSWITCH OPTIONS01 = SINGLE SWITCH02 = DUAL SWITCHES03 = USE 0104 = USE 0205 = SINGLE FOR Exia06 = DUAL FOR Exia
NB / PLATE SIZE CODES010005 = 1/2” NB PLATES010007 = 3/4” NB PLATES010010 = 1” NB PLATES015015 = 11/2” NB PLATES020020 = 2” NB PLATES020025 = 21/2” NB PLATES030025 = 21/2” NB PLATES030030 = 3” NB PLATES040040 = 4” NB PLATES
SWITCHCASE PREFIX ‘S’ FOR 316 ST ST.IF ALUMINIUM REQUIRED LEAVE BLANK
FLOW INDICATOR1 = NO INDICATOR2 = WITH INDICATOR
FLANGE MATERIAL1 = GUNMETAL - STANDARD2 = STAINLESS STEEL3 = MONEL4 = TUFNOL EPOXIDE
060060 = 6” NB PLATES080080 = 8” NB PLATES100100 = 10” NB PLATES
DIAPHRAGM MATERIALA = NITRILEB = VITON SPRING CODE (PLEASE USE 1)
FIG. 17 TYPE F1000 GUARDIAN FLOW SWITCH
GUARDIAN INDUSTRIAL & ATEX SWITCHES
The Guardian pressure, differential pressure, temperature, level and flow switches are a part of our extensive range of specialist process sensors. They utilise the expertise gained from over 50 years experience of designing and manufacturing control devices for industrial, marine and hazardous area applications.
These switches are constructed with either a robust aluminium or stainless steel enclosure. The aluminium casting is black anodised and supplied with 316 stainless steel covers. The stainless steel case is a natural finish. Covers are gasketted and sealed to achieve an environmental seal to IP66 & IP67 standards. The internals utilise a unique mechanism designed by the engineers at PYROPRESS to produce a wide range, low switching differential and excellent repeatability. This combined with a variety of microswitches, mountings and sensor options has produced a switch range suitable for all weatherproof and intrinsically safe applications.
INTRODUCTION
The design features a simple form of calibration adjustment against a scale plate. This allows users to either order units with a specific setting, or stock a mid range setting and then calibrate to suit the application. Calibration is performed on the opposite side of the switch to the electrical connections, and can be set safely with the switch supply live. On removal of the adjustment cover a small grub screw can be loosened allowing the adjusting ring to be turned with a small Tommy bar or Allen key. The setting is read from the centre of the red indicating ring against the calibrated scale plate.
Calibration procedures for dual microswitches and adjustable switching differential switches are detailed on the operating and maintenance instructions supplied with each switch.
CALIBRATION
Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation
and control. Pyropress control sensors provide safe and
reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential
pressure,vacuum, fluid, flow and level conditions.
ABOUTPYROPRESS QUALITY
To support the design of state of the art products the company has invested heavily in the latest CNC technology.
We are able to produce our own components to a high degree of aaccuracy assuring a reliable and
consistent quality product.
T: +44 (0)1752 333933 | [email protected] www.pyropress.com
Switchcase and covers: 316 stainless steel switchcase with 316 stainless steel covers or black anodised aluminium switchcase and 316 stainless steel covers. Optional 304 stainless steel mounting bracket.
Microswitch: SPCO/SPDT. Options include single or twin switch assemblies for simultaneous or separately adjustable set points, adjustable switching differential, manual reset and noble metal contacts for use on intrinsically safe circuits.
Microswitch ratingStandard microswitch and high : 6 Amps @ 480 V.ACCurrent DC switching : 10 Amps @ 250 V.AC & 125 V.AC : 5 Amps @ 30 V.DC & 0.05 Amps @ 125 V.DCAdjustable deadband : 1.5 Amps @ 250 V.AC & DC : 7.5 Amps @ 125 V.AC & DC
Electrical Connections: Screwed terminals direct onto microswitch, suitable for cable up to 2.5 mm2. (Manual reset microswitch is supplied with 6BA solder tags).
Electrical Conduit Entry: M20 x 1.5 straight entry. Adaptors are available.
Environmental Protection: Switches have been tested and certified by an external test house to IP66 in accordance with BS EN 60529 : 1992. In addition further internal tests confirm that the switchcase meets the requirements of IP67.
Vibration and shock parameters: Switches were subjected to Lloyds Register Type Approval System Test Specification No.1 Clause 12 or 13 Vibration Test 1 or 2 (refer to sales for exact specifications) and shock tested to BS EN 60068-2-27 : 1987.
Temperature Limitations: Pressure, Vacuum and Differential Pressure.
Process: Diaphragm actuated (unless otherwise stated) -30 to +110˚C (Nitrile) or -20 to +150˚C (Viton). Piston actuated -30 to +120˚C (Nitrile), or -20 to +150˚C (Viton) or -50 to +150˚C (PTFE) -30 to 125˚C (EPDM)
Ambient: -25 to +80 Deg.C.
Storage: -25 to +80˚C. (For temp, level and flow refer to specific pages).
Certification: All switches are CE certified and marked in accordance with the following EU directives. Industrial : 2006/95/EC (Low Voltage Directive).
Exia: 94/9/EC ATEX coded CE Ex II1G Exia IIC. CAT 1 (Zone 0) areas. Special conditions for safe use. (Category 1, Zone 0) Aluminium may only be used when the ignition hazardous assessment shows that there is not risk of ignition from incendive, impact or abrasion sparks.
TECHNICAL SPECIFICATION
PPSSC1020 | issue 1