Greengate Psg Fwb

216
Version 3.0 Greengate Product Selection Guide Lighting Control for Energy Management

Transcript of Greengate Psg Fwb

Version 3.0

Greengate Product Selection GuideLighting Control for Energy Management

T

he purpose of this guide is to provide you the detailed information required to specify Greengate energy management products on your project.

This guide has been divided into the following sections for ease of use: Lighting Control Panels, Occupancy Sensors, Daylighting Controls, Glossary and Catalog Number Index. We are committed to offering the most reliable, easy-to-install, energyefficient lighting control solutions on the market. Our high product standards and exceptional customer service will return impressive energy and time-saving rewards on your project. Thank you for your business, Cooper Controls

Cooper Controls Presents GreengateCooper Controls, a business unit of Cooper Lighting, has combined the energy management expertise of PCI Lighting Control Systems, with innovative sensor technology from Novitas, expertise in addressable ballast and digital control technologies of ALC Lighting Controls, and the global reach and resources of Cooper Industries to create Greengate lighting control solutions. These lighting control products unite energy-saving and maintenance free technology, the longest warranty in the industry, and a simplified five (5) step specification process. Greengate lighting controls are cost-effective energy management solutions for commercial, industrial and institutional projects.

Greengate lighting controls make energy management easy.

Why Greengate Energy Code Compliance Lighting Control Strategies Lighting Control Panels Occupancy Sensors Daylighting Controls Patient Room Controls Venergy Advanced Metering Systems International 230 V Market Catalog Number Index

p. 2, 3 p. 4 p. 6 p. 8 p. 84 p. 164 p. 180 p. 188 p. 208 p. 212

Why Greengate Lighting Controls?

Lighting can account for over 40% of the total energy consumed daily by commercial, industrial, or institutional buildings. When trying to improve the energy efficiency of a project, lighting control is an ideal place to start. Lighting control can offer more than energy savings. Combine energy savings with simplified specification and easy installation, low cost of ownership, the best value, and exceptional customer service. That is a solution - a Greengate solution.

Easy to SpecifyIncorporate energy saving lighting control or metering systems into buildings quickly, easily, and accurately. Greengate lighting control solutions are comprised of a full line of occupancy sensors, lighting control panels sized from 2 to 48 circuits that operate with digital or analog controls and interface with building automation systems, as well as, daylighting controls, power metering, and emergency load control. This versatile product line ensures that there is a Greengate solution for any size and type of project. It is easy to create Greengate lighting control systems. All Greengate lighting control panels, sensors, and wallstations are designed to work together, without interfaces or compatibility issues. Simply select the individual products needed by the space from this guide to create the desired lighting control system. Greengate solutions make specification for energy management simple and straightforward. All lighting control panels and sensors work together without interfaces Use the Automation Interface Module (AIM) to communicate to any building system protocol Real-time power metering per relay (CKM/CKMB models) Short Circuit Rating (SCCR) of 25,000 at 277 VAC (CKM/CKMB models)

Low Cost of OwnershipSelect lighting controls that are easy and cost-effective to own year after year after year. Greengate energy management products are installed using common wiring practices, built to last and backed by the industry-leading 10 year relay card warranty. This minimizes labor, maintenance, and replacement costs throughout the life of the building. Beyond product reliability, Greengate solutions ensure that the space operates as efficiently as possible. Industry-exclusive learning sensors automatically adapt to the needs of the space, eliminating the need to manually correct the sensitivity. Relay panels automatically sense new or replaced relay cards and reprogram the panel accordingly. These technologies save time, money, and energy often spent making system adjustments needed both initially and as the space evolves. Industry-leading 10 year relay card warranty Learning sensors automatically adjust sensitivity, without reducing coverage Easy keypad or touchscreen programming navigation Fast and convenient upgrade options

Best ValueSpecify lighting control systems that provide the best value on a project. Equipping a building with Greengate solutions adds over 200 years of energy management expertise and patented technology, assembled by a world-class manufacturing organization into the building systems infrastructure. With over 300 manufacturing and distribution facilities around the world, Cooper Controls uses the latest technologies, products, and manufacturing capabilities and delivers the savings and quality to the customer. Greengate lighting control systems offer more expertise, more support, and more technology at a very competitive price. 200 years of combined energy management experience 300 manufacturing and distribution facilities 50+ factory-trained commissioning experts A member of Cooper Industries

Exceptional Customer ServicePartner with a company dedicated to customer satisfaction and support. From the design team, to the distributor, the building owner, or end user, Cooper Controls is committed to meeting the needs and expectations of each of its customers. Greengate energy management systems are supported from specification through the life of the building with webbased specification tools, free lifetime technical support, web-based and phone diagnostics, and an industry-leading 10 year relay card warranty. Web-based specification tools Free lifetime technical support Internet/phone remote diagnostics Industry-leading 10 year relay card warranty

Why Greengate3

Energy Code Compliance

Energy costs and consumption continue to rise in the United States. As a result, reducing energy waste with lighting control is now required by many federal, state, and local energy codes. While each state may adopt its own energy code regulations, they must each be at least as stringent as the ASHRAE 90.1-2004 guidelines summarized on the next page. Minimally, the lighting control in the building must comply with the energy codes regulating each project. The first step in compliance is to identify the applicable energy code. The map below illustrates the energy codes adopted by each state.

Meets 2009 IECC/ASHRAE 90.1-2007

Meets or exceeds 2006 IECC/ASHRAE 90.1-2004

Meets 2003 IECC/ASHRAE 90.1-2001

Meets 2001 IECC/ASHRAE 90.1-1999

Meets ASHRAE 90.1-2004 with Amendments

No Statewide Code

Signicant adoptions in jurisdiction or mandatory for state owned buildings

Here are the minimal requirements for lighting control as regulated by ASHRAE 90.1- 2004.

Every building over 5,000 square feet must be able to automatically turn lights OFF. Specific building spaces such as college classrooms, conference/meeting rooms, and employee lunch/breakrooms must use occupancy sensor control. Every enclosed area must have independent control over the general lighting. The local control cannot override the automatic shut-off for more than four hours. Exterior lighting must be controlled by a photosensor or an astronomic timeclock.

Is the space an interior or exterior space?

Interior

Is the space a college classroom, a conference/meeting room or an employee lunch/break room? Exterior No Yes

Is building greater than 5,000 sq.ft.?Requires Occupancy Sensor Control 30 minute max. time delay Yes No

Select Automatic Shut-off method

Select Control Method Areas that are slated as dusk/dawn lighting control may use a photosensor or astronomic clock for control Areas without a dusk/dawn designation should use astronomic clock for control.

Time Schedule Independent schedule for each 25,000 sq.ft. area or each floor

Occupancy Sensor 30 minute maximum time delay

Other System Signal Alarm system or other signal indicating facility is not occupied

Provide Space Control Device For each ceiling height partitioned space Maximum controlled area is: - 2,500 sq.ft. if space is < 10,000 sq.ft. - 10,000 sq.ft. if space is > 10,000 sq.ft. Must be able to override automatic shut-off control, but not for more than four hours (not applicable to occupancy sensors) Must be accessible and located so controlled lighting is visible to the occupant

Comply with all other provisions of ASHRAE 90.1 - 2004 item 9

Energy Code Compliance5

Evaluate the Space

The lighting control provisions required by energy codes reduce energy waste. Lighting controls can easily eliminate energy waste by improving the fit between the light provided by the building and the light needed by the employees or occupants. Significantly improve the energy efficiency of the building by identifying the different rooms in the building and the different lighting control needs of each.

Occupancy Sensing Fits areas that are not constantly occupied. Use wall, fixture, or ceiling-mounted sensors to detect occupancy in a space. When the room is unoccupied, the lights are turned OFF or dimmed to a predetermined level, saving energy while the room is empty. This lighting control strategy can return energy savings of up to 60% in restrooms, 45% in private offices, 35% in corridors, 40% in classrooms, and 75% in warehouses, depending upon how often the room is vacant.

Daylighting Employ daylighting in areas that receive daylight exposure. In daylighting, exterior and interior sensors balance the electric light and daylight present in a space by either switching pre-selected lights OFF or dimming. When daylighting is paired with dimming, electric light levels are lowered when daylight is available and raised as daylight wanes. This lighting control strategy minimizes the electric light consumed during the day and has been credited with energy savings of up to 40% in the spaces that receive natural light. Load Shedding This lighting control strategy reduces the energy consumption of a building during peak usage times to better manage both energy use and energy costs. Load shedding can be accomplished without negatively impacting the functionality of the space or the comfort of the workers by dimming or switching lighting levels over a specific time or in areas of lesser priority.

Programmable Timing A typical building has known occupied and unoccupied times. These times can be programmed into the lighting control system to ensure that lighting is not energized during unoccupied times. Daily, weekly, or special time events could control a single lighting event or an entire building. Time schedule sweeps are an effective means to ensure lighting is not turned On and left On after hours.

Demand Response Demand Response is the lighting control strategy that automatically reduces the lighting power consumption of a building in response to an electronic signal sent from the local utility company requesting that their customers reduce their electricity consumption for a certain period of time. The lighting control system receives the signal then automatically dims or turns OFF pre-determined lights throughout the building to reduce its electrical demand. Thereby reducing the overall energy load on the grid and avoiding high power demand utility pricing. Personal Control Personal Control is the lighting control strategy that enables individuals to modify the light levels of the fixtures above their workspace to meet their unique needs or preferences. This strategy can be used to comply with the IECC codes and towards earning LEED certification points. Personal Control can be incorporated into any building by specifying building occupant control software into the lighting control system. This software provides PC-based control that allows individuals to control their overhead lights and change overhead lighting levels from their desktop.

Bi-Level Switching The Bi-Level Switching strategy enables building occupants to have one more option that simply ON or OFF in an area and is required by many local and national codes including Ashrae 90.1, IECC, and Title 24. Bi-Level Switching can be accomplished either automatically or manually and provides a simple method of reducing the lighting load by approximately 50% either by dimming or actually switching lighting loads. This lighting control strategy has been proven to provide energy savings of between 10-15% Power Metering Power Metering is rapidly becoming essential in the daily operation of a successful energy efficient building. Not only is it an effective means to monitor energy usage to support Demand Response times, but it can be used to help drive building occupant and management behaviors. Real-time power metering data per relay/circuit or in aggregate, can be presented on a dashboard to educate and drive behavior energy savings changes. Real-time knowledge of how energy is used in a building space can help a building manager identify key areas of energy usage improvement.

Overview of Greengate Technologies CategoriesLighting Control Panels Greengate lighting control panels offer stand-alone, centralized, and distributed solutions to control lighting levels in any project type. Control schemes can incorporate any combination of sensor-based, automatic, manual, or scheduled inputs to meet the most complex functional requirements.

Occupany Sensors Greengate offers a variety of occupancy sensors to best meet the needs of a project. If the project requires a stand-alone solution for a small space, or a networked solution for whole building control, sensors provide the minor motion detection to ensure efficiency is maximized. Greengate sensors automatically adjust to the building environment, eliminating the needs for constant re-calibration and reducing overall maintenance costs.

Daylighting Sensors Coordinate the daylight and electric light in a space to save energy and balance the light levels of the interior environment. Greengate offers a range of daylighting solutions to match every project budget and control need. Combine available daylight with switching or dimming in a single space, or design an entire building to respond to the presence of natural light.

Software Greengate provides a variety of accessory software to provide building managers and occupants ultimate control of their building and personal lighting. The Keeper Enterprise programming software provides the building manager total lighting control panel, occupancy sensor and daylighting sensor programming, status, and override capabilities. VisionTouch and VisionSwitch softwares provides room, floor, building, or personal lighting control and status via the building LAN. Event Manager software provides the building manager with complete time schedule flexibility including temporary, permanent, and special time event programming. Our Venergy Dashboards provide real-time power metering usage data including kW usage, dollars, and carbon footprint of the facilities energy control strategy.

Lighting Control Strategies7

Control Panels Overview Lighting Control Panel Quick Reference Guide How to Specify

p.8-9 p.10-11 p.12 p.13-19 p.21 p.23 p.27 p.29 p.31 p.33 p.35 p.37 p.39 p.41 p.43 p.45 p.47 p.51 p.53 p.55 p.57 p.59 p.60 p.61 p.62 p.63 p.65 p.67 p.69 p.71 p.73

Lighting Control PanelsGreengate lighting control panels offer stand-alone, centralized, and distributed solutions for projects of varying sizes, control requirements, and load types. The energy saving capabilities of these cost-effective panels allow design teams to attain code compliance effectively. Reasons to use Lighting Control Panels: Power Metering Automatic time of day scheduling Switch multiple loads/circuits, on/off together Centralized Control Load Shedding Code Compliance Maximize the use of available natural light Multiple input devices (Occupancy Sensors, manual switches,)

Product Matrix Network Panels ControlKeeper M ControlKeeper MB ControlKeeper 4A ControlKeeper 4 ControlKeeper 2 SXRC Serial Relay Cards Stand-Alone Panels LiteKeeper 16 & 32 LiteKeeper 8 LiteKeeper 4 XRC Parallel Relay Cards Current Limiting Panel TracKeeper Low Voltage Switches Digital Switch Digita Momentary Toggle Key Switches Three-wire Momentary Two-wire Momentary Line Voltage Switches Automatic Turn-Off Software Keeper Enterprise VisionTouch VisionSwitch Event Manager Accessories Lighting Relay Module Emergency Power Control Relay Interface Module Lighted Switch Card Ethernet Interface Module

ControlKeeper TouchScreen p.25

Momentary Decorator Switch p.49

Automation Interface Module p.75 Telephone Interface Module p.77 Gateway DMX Gateway Modem Communication Cable Network Repeater p.78 p.79 p.80 p.81 p.83

Lighting Control Panels9

Greengate Lighting Control Panel FamiliesGreengate provides energy management solutions for a variety of commercial, institutional, and industrial projects. The size, scope, control needs, and energy management goals of these projects are very diverse. In order to meet the unique needs and objectives of each design, Greengate has developed two families of lighting control panels: ControlKeeper and LiteKeeper.

CKM/CKMB 18, 36, 48 Panel FeaturesNetworkable TouchScreen Interface Keypad and LCD Interface Ethernet Onboard Flash Upgradable Locked Door NEMA 1 Enclosures System Logging (Default) Programming Software (Keeper Enterprise) Floor Plan Software (VisionTouch) Event Software (Event Manager) Open/Closed Loop Dimming Daylighting

ControlKeeperThe ControlKeeper lighting control panel family is designed to provide superior energy management solutions to projects that require individually addressable relays on a networked lighting control system. Use these panels to schedule the lighting throughout the building or campus of buildings with the astronomic clock. Incorporate occupancy sensors or daylighting sensors with these panels to maximize the energy savings in each space.

User InterfacesDigital Switches Low Voltage Switches

LiteKeeperThe LiteKeeper lighting control panels are stand-alone systems for designers looking to create energy savings in spaces through scheduling, occupancy sensing, daylighting, or perhaps just simplified lighting control.

Contact Input Photosensors Analog Photosensors Automatic Turn-off Switches Occupancy Sensors

Relays25K SCCR 10K SCCR option Power Metering Variable Relay Timing Technology Serial Relay Cards Parallel Relay Cards Individual Relay Cards

Communications AccessoriesEthernet BMS Interface DMX Gateway Telephone Interface Module

Emergency Control (UL 924)Total Panel Solution Single Circuit Solution

Lighting Control Panel Quick Reference GuideCKT 16, 32 & 48 CK4A CK4 CK2 LK16 & 32 LK8 LK4

Lighting Control Panels - Quick Reference Guide11

Specify a Lighting Control Panel SystemPrerequisites Complete lighting design and layout. Determine zones and circuiting. Complete branch circuit panel schedule. Identify lighting control strategies.

Greengate lighting control panels are easy to specify, because each panel family is manufactured with robust relay solutions, designed to operate with any type of digital or low voltage control, and built to interact seamlessly with all Greengate products. Sized to accommodate 2-48 relays and available as a stand-alone, centralized, or distributed system, Greengate lighting control panels can support any project. Determine which panel is the best fit and take a project from simple switching to energy saving in 5 steps. Energy management is easy, with Greengate.

Greengate interfaces are available in a variety of styles and offer a wide range of functionalities. low voltage switches (refer to pages 48-57) digital switches (refer to pages 44-47) occupancy sensors (refer to pages 84-163) photosensors (refer to pages 172-177)

5 Steps to Specifying the Right Lighting Control Panel SystemStep 1 Does your project require stand-alone, centralized, or distributed lighting control system? Greengate lighting panels are available as stand-alone, centralized, or distributed. Refer to pages 10-11 within this guide to learn about the specifics of each panel type. Step 2 What size of panel does the project require? Panels ranging from 2-48 relays are available. Refer to pages 10-11 to select the panel family best suited for the project. Step 3 Will daylighting with dimming occur in the space? Refer to page 26 for more details on the ControlKeeper 4A. Step 4 Does the project require special relay types or power metering gathering? Greengate manufactures a variety of relay types including Normally Open, Latching, Two Pole relay cards. Greengate provides a variety of power metering methods, including integral relays with power metering or CT solutions, refer to page 189 for more information. Step 5 What type of user interfaces and software should be installed? Digital or standard low voltage switches, occupancy sensors, photosensors can all be provided. Basic programming software, graphical floor plan control, personal user control or event scheduling software are all available with Greengate, refer to pages 60-63 for details. Complete the Specification Complete the panel schedule for the individual lighting control panels and note their locations on the drawings. Complete the switch input schedule(s) and note their locations on the drawings. Draw the single line wiring diagram for the project. Complete the written specification.

Lighting Control PanelProduct MatrixGreengate Catalog # Max. # of Relays Relay Type Power Use Rating Size (height x width x depth)

CONTROLKEEPERControlKeeper - ControlKeeper M and ControlKeeper MB CKM18* 18 120/347 VAC normally open, normally closed or Latching 120/347 VAC normally open, normally closed or Latching 120/347 VAC normally open, normally closed or Latching 120/347 VAC normally open, normally closed, or Latching with integral Breakers 120/347 VAC normally open, normally closed, or Latching with integral Breakers 120/347 VAC normally open, normally closed or Latching with integral Breakers 90 Watts 31 x 24 x 6

CKM36*

36

90 Watts

40 x 24 x 6

CKM48*

48

90 Watts

48.25 x 24 x 6

CKMB18*

18

90 Watts

54 x 24 x 6

CKMB36*

36

90 Watts

76 x 24 x 6

CKMB48*

48

90 Watts

90 x 24 x 6

* Reference Specication Sheet for complete Catalog Number. ControlKeeper TouchScreen CKT16* CKT32* CKT48* 16 32 48 Serial Relay Cards - options available, order separately Serial Relay Cards - options available, order separately Serial Relay Cards - options available, order separately 75 Watts 75 Watts 75 Watts 18 x 15 x 6.25 30 x 15 x 6.25 41 x 15 x 6.25

* Reference Specication Sheet for complete Catalog Number.

ControlKeeper 4A CK4A-SSRCNO CK4A-SLRC CK4A-STPRCNO 4 4 2 120/277 VAC normally open 120/277/347 VAC mechanically latched 208/240/480 VAC, two pole, normally open 20 Watts 20 Watts 20 Watts 10 x 14 x 3.5 10 x 14 x 3.5 10 x 14 x 3.5

ControlKeeper 4 CK4-120NO CK4-277NO 4 4 120/277 VAC normally open 120/277 VAC normally open 20 Watts 20 Watts 10 x 14 x 3.5 10 x 14 x 3.5

ControlKeeper 2 CK2-120NO CK2-277NO 2 2 120/277 VAC normally open 120/277 VAC normally open 20 Watts 20 Watts 7.5 x 11 x 5 7.5 x 11 x 5

Lighting Control Panels - Product Matrix13

Greengate Catalog #

Max. # of Relays

Relay Type

Power Use Rating

Size (height x width x depth)

LITEKEEPERLK16* LK32* LK LB LK8 LK8-LRC LK8-MRC LK8-TPRC LK4-120NO LK4-277NO 8 8 0 0 4 4 16 32 Parallel Relay Cards - options available, order separately Parallel Relay Cards - options available, order separately LiteKeeper Logic Board Required for LK16 & LK32 120/277 VAC standard, normally open 120/277 VAC Latching 120/277 VAC order relays separately 120/277 VAC order relays separately 120/277VAC normally open 120/277VAC normally open 40 Watts 40 Watts 40 Watts 40 Watts 20 Watts 20 Watts 14 x 9.5 x 5 14 x 9.5 x 5 14 x 9.5 x 5 14 x 9.5 x 5 9.5 x 14 x 3.5 9.5 x 14 x 3.5 75 Watts 75 Watts 18 x 15 x 6.25 30 x 15 x 6.25

* Reference Specication Sheet for complete Catalog Number. Greengate Catalog # Voltage # of Breakers Mounting Option Size (height x width x depth)

TRACKEEPERTK16* TK32* 120 or 277 120 or 277 1 to 16 1 to 32 S = Surface F = Flush S = Surface F = Flush 10 X 14 X 3 3/8 16 X 14 X 3 3/8

* Reference Specication Sheet for complete Catalog Number. Greengate Catalog # Relay Type Voltage

RELAY CARDSSerial Relay Cards - for ControlKeeper Panels SSRCNO SLRC STPRCNO Parallel Relay Cards - for LiteKeeper Panels SRC LRC MRC Relay Card Options for LK8, LK16, and LK32 MRC SRM NO LRM TPRM NO Modular Relay Card - included with LK8-w/MRC 20 Amp 120/277 VAC single pole normally open relay (1 relay space) 20 Amp 120/277/347 VAC latching relay (1 relay space) 20 Amp 208/240/480 VAC two pole normally open (2 relay space) N/A. Refer to specific relays below 20A, 120/277 VAC 20A, 120/277/347 VAC 20A, 208/240/480 VAC Standard Relay Card with 8 relays Latching Relay Card with 8 relays 20A, 120/277 VAC 20A, 120/277/347 VAC Serial Standard Relay Card normally open Serial Latching Relay Card Serial Two Pole Relay Card normally open 20A, 120/277 VAC 20A, 120/277/347 VAC 20A, 208/240/480 VAC

Lighting Control PanelProduct MatrixGreengate Catalog # Relay Type Voltage

RELAY CARDSParallel Relay Cards - for LiteKeeper TPRC Relay Card Options for LK8, LK16, and LK32 TPRC SPR347 TPR208 TPR480 Two Pole Relay Card - included with LK8-TPRC 20 Amp, 120/277/347 VAC single pole relay (1 relay space) 20 Amp, 208/240 VAC two pole relay (1 relay space) 20 Amp, 480 VAC two pole relay (2 relay space) N/A. Refer to specific relays below 20A, 120/277/347 VAC 20A, 208/240 VAC 20A, 208/240/480 VAC

DIGITAL SWITCH - Custom engraving available. Refer to Specication Sheet for more information.Greengate Catalog # GDS-1TLB-* GDS-2TLB-* GDS-3TLB-*GDS-3TLB

Description One button with LED relay status indicator Two button with LED relay status indicators Three button with LED relay status indicators Two button with LED relay status indicators Four button with LED relay status indicators Five button with LED relay status indicators Six button with LED relay status indicators

Communications Canbus Canbus Canbus Canbus Canbus Canbus Canbus

GDS-2TSB-* GDS-4TSB-* GDS-5TSB-* GDS-6TSB-*GDS-6TSB

* Available Colors: W-White, B-Black, V-Ivory

DIGITA SWITCH - Custom engraving available. Refer to Specication Sheet for more information.Digita1 Digita5-1B* Digita5-2B* Digita5-3B* Digita5-4B* Digita5-5B* DG2 Greengate Catalog # One button decorator style rocker One button with LED relay status indicators Two button with LED relay status indicators Three button with LED relay status indicators Four button with LED relay status indicators Five button with LED relay status indicators One Gateway required per digital switch network Canbus (requires DG2) Canbus (requires DG2)

Canbus (requires DG2) Canbus (requires DG2) Canbus (requires DG2) Canbus (requires DG2)

Color

Description

Rating

MOMENTARY DECORATOR SWITCHGMDS-W GMDS-V White Ivory Momentary Decorator Switch Momentary Decorator Switch 3 Amps, 24 VAC/VDC 3 Amps, 24 VAC/VDC

Lighting Control Panels - Product Matrix15

Canbus (requires DG2)

Greengate Catalog #

Color

Description

Type/Rating

LOW VOLTAGE SWITCHES - Variety of wallplates available. Refer to Specication Sheet for more information.RS232 RS232K RS232P** RS232PK**RS237

Ivory Ivory Ivory Ivory Ivory White White White White White Gray Gray Gray Gray White White White

Momentary Switch Momentary Key Switch Momentary Pilot Switch Momentary Pilot Key Switch Switch Blank Momentary Switch Momentary Key Switch Momentary Pilot Switch Momentary Pilot Key Switch Switch Blank Momentary Switch Momentary Key Switch Momentary Pilot Switch Switch Blank 3A, 24 V AC/DC 3A, 24 V AC/DC 3A, 24 V AC/DC

SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPDT, Momentary Contact 3A, 24 VAC/DC SPST, Momentary Contact 3A, 24 VAC/DC SPST, Momentary Contact 3A, 24 VAC/DC SPST, Momentary Contact 3A, 2 VAC/DC

RA232 RS237 RS237K RS237P** RS237PK** RA237

RS237P

RS239 RS232K RS239P** RA239 AML

AMLG

AMLR** switch w/Red LED AMLG switch w/Green LED

** Must order Lighted Switch Card with LK16 & LK32.

Greengate Catalog # Momentary Toggle Switches GMT-* (White-W, V-Ivory, G-Gray) GMTL-N (Satin Nickel)GMTL-N

Relay Type

Voltage

GMT-G

3 position Momentary Switch, up or down closed, center open 3 position Momentary Locking Switch, up or down closed, center open

3A, 24 VAC/DC

3A, 24 VAC/DC

Greengate Catalog #

Relay Type

Voltage

Key Switches MOM-Key MAIN-KeyMOM-Key

Momentary Contact Key Switch Maintained Contact Key Switch

4A, 28V DC 4A, 28V DC

Lighting Control PanelProduct MatrixGreengate Catalog # Relay Type Description

LINE VOLTAGE SWITCHESLine Voltage Automatic Turn-Off Switch G5 G5-D-* G5TG5

5A, 120/240/277V 5A, 120/240/277V 5A, 120/240/277V 5A, 120/240/277V 20A, 120/240/277V 20A, 120/240/277V 20A, 120/240/277V 20A, 120/240/277V

Single Pole, Clear Toggle Single Pole, Decorator Three Way, Clear Toggle Three Way, Decorator Single Pole, Clear Toggle Single Pole, Decorator Three Way, Clear Toggle Three Way, Decorator

G5T-D-* G20 G20-D-*G5-5-D-V

G20T G20T-D-*G5-D-W

* Available Colors: W-White, V-Ivory Greengate Catalog # Description

SOFTWAREKEEPER NW KEEPER SA SOFT VT SOFT VT Screens SOFT VS SOFT EM-10 SOFT EM-25 SOFT EM-50 SOFT EM-UN Keeper Enterprise Network Keeper Enterprise Stand Alone VisionTouch IV; requires Soft VT Screens VisionTouch Graphic Layout Screens VisionSwitch Event Manager 10 Panels Event Manager 25 Panels Event Manager 50 Panels Event Manager Unlimited Panels

Lighting Control Panels - Product Matrix17

Greengate Catalog #

Description

AIM, AUTOMATION INTERFACE MODULE - Add NW for ControlKeeper or SA for LiteKeeperAIM-B-* AIM-N-* AIM-L-* AIM-M-* AIM OEMPRTL Provides BACnet interface (1200 points of control or status) Provides N2 interface (256 points of control or status) Provides Lon interface (1200 points of control or status) Provides Modbus interface (1200 points of control or status) AIM Logic Board (required for each unit)

* NW=Network (ControlKeeper) SA=Stand Alone (LK16 & LK32)

Greengate Catalog #

Input Option

ETHERNET INTERFACE MODULEEIM WEIM Ethernet Interface Module Wireless Ethernet Interface Module

Greengate Catalog #

Electrical

Power Consumption

Size

Modem

TELEPHONE INTERFACE MODULETIM Greengate Catalog # 120 VAC wall transformer included Input 27 Watts 9.5 x 7.25 x 1.5 Bell 103 and 212 A compatible Size

Output

GATEWAYSGATEWAY DMX GATEWAY Greengate Catalog # RS-232 serial connection, 25 pin DMX 512, twisted shielded pair RS-485, twisted shielded pair RS-485, twisted shielded pair 9.5 x 7.25 x 1.5 9.5 x 7.25 x 1.5

Description

MODEMSerial Modem USB Modem 2400 Baud Connection on the Panel Side Permits Connections to the Serial Modem or Telephone Interface Module

RPTR, NETWORK REPEATERRPTR Greengate Catalog # Repeater with power wiring whip for connection to a 24V DC power source

Color

Size

Description

COMMUNICATION CABLELCCP LCCNP Natural Black 0.205 0.250 Cooper Controls communication cable; plenum rated Cooper Controls communication cable; non plenum rated

Lighting Control PanelProduct MatrixGreengate Catalog # Description Rating

EMERGENCY POWER CONTROLCEPC-120 CEPC-277 CEPC-D-F-S-120 CEPC-D-F-S-277 Greengate Catalog # Emergency Power Control 120V Emergency Power Control 277V 0-10V Load Emergency Power Control 120V 0-10V Load Emergency Power Control 277V Voltage Compatibility 120V 277V 120V 277V

CEPC-120

CEPC-D-F-S-120

LIGHTING RELAY MODULELRM120 LRM277 LRM347 120 VAC 277 VAC 347 VAC ControlKeeper M and ControlKeeper MB ControlKeeper M and ControlKeeper MB ControlKeeper M and ControlKeeper MB

RELAY INTERFACE MODULERIM120 RIM277 RIM347 Greengate Catalog # 120 VAC 277 VAC 347 VAC ControlKeeper TouchScreen and LiteKeeper 16 & 32 ControlKeeper TouchScreen and LiteKeeper 16 & 32 ControlKeeper TouchScreen and LiteKeeper 16 & 32

Input Voltage

Description

CONTACT INPUT PHOTOSENSORS (Refer to Specication Sheet in the Daylighting Section)PPS-5 24 VDC Outdoor Contact Input Photosensor

Greengate Catalog #

Orientation

Standard FC Range

Lens

PC-I (indoor) PC-O (outdoor) PC-A (atrium) PC-S (skylight) PC-I-OL (open loop)

Downward Horizontal Horizontal Upward 45

0-100 FC* 0-200 FC* 2-1000 FC* 10-2000 FC* 30-3000 FC*

Clear Fresnel Clear Flat Opaque Dome Dark Dome Opaque Flat

Note: Other FC ranges available by special order. Please contact Customer Service for more informaion.

Greengate Catalog #

Description

LIGHTED SWITCH CARD - An option for the LiteKeeper 16 & 32LSC Provides relay output status indication when used in conjunction with pilot type low voltage switches.

Lighting Control Panels - Product Matrix19

ANALOG PHOTOSENSOR (Refer to Specication Sheet in the Daylighting Section)

Catalog # Project Comments

Type

CKM18, CKM36, CKM48 ControlKeeper M

Prepared by

Date

True real-time power metering relay panel Large, intuitive color touchscreen interface Individually replaceable relays with arc suppression technology Programming stored in non-volatile memory Capable of mixed load voltages (120/277/347 VAC) as well as mixed sources (ie. normal and emergency power) 30 Amp relays are used on all 20A relay cards to extend relay life Specifications:Enclosure: NEMA 1 surface mount, lockable Size: CKM18: 31H X 24W X 6D (up to 18 relays) CKM36: 40H X 24W X 6D (up to 36 relays) CKM48: 48.25H X 24W X 6D (up to 48 relays) Transformer Ratings: Wide input voltage power supply, 120-347 VAC Power Use Ratings: Fully loaded panel 90 watts Operating Temp. Ratings: 32F to 122F (0C to 50C) Master Override: ON/AUTO/OFF or Individual relay control with status LED Programming: Onboard TouchScreen Interface One panel or entire network Optional PC Software Standard Relay Ratings: Normally open 20A, incandescent 120 VAC, ballast 277 VAC Maximum wire size: 8 AWG 1HP @ 120 VAC, 2HP @ 277 VAC Latching Relay Ratings: Normally open, normally closed Latching 20A, incandescent 120 VAC, ballast 347 VAC Maximum wire size: 8 AWG 1HP @ 120 VAC, 2HP @ 277 VAC Two Pole Relay Ratings: Normally open or normally closed Maximum wire size: 8 AWG 1HP @ 120 VAC, 2HP @ 277 VAC Relays have a minimum 25K SCCR @ 277 VAC System warranty: Three year Relay warranty: Ten year UL Approval UL 508 Listed UL 924 with LRM

Overview ControlKeeper M network lighting control panels are scalable to any size application. The large view color touchscreen permits entire network programming and monitoring for complete system control and integration. Control up to 48 relays per panel with discrete inputs for occupancy sensors, low voltage switches and other input devices. ControlKeeper M network panels are designed for intuitive programming, and monitoring of the relays. The relays automatically sense the optimal time to switch lighting loads. Venergy Power Metering software in conjunction with our relays provide a complete Energy Management Solution. System Includes NEMA 1 enclosure Low Voltage input connections Digital Switch interface 0-10V inputs Time schedules with astronomic clock Color Touchscreen Accessories Automation Interface Module Ethernet Interface Module Telephone Interface Module Digital Switch Occupancy & Daylighting Sensors Keeper Enterprise Software Venergy Power Metering Software DMX Interface Dry Contact Switches Prioritization and masking of switch inputs, time schedules, and remotes Timed inputs Occupant warn-off and overrides Power Metering Onboard Ethernet port UL Listed - UL 924 with LRM

Ordering This is a network-ready lighting control system. It can be combined with other ControlKeeper series panels to create a scalable networked lighting control scheme. It can be ordered with any suitable system option or accessory. See next/back page for Ordering details.

Wiring DiagramsEnclosureCKM 18: 31H X 24W X 6D (up to 18 relays) CKM 36: 40H X 24W X 6D (up to 36 relays) CKM 48: 48.25H X 24W X 6D (up to 48 relays)

ControlKeeper M 18/36/4824 in. (609.6 mm) 24 in. (609.6 mm) 6 in. (152.4 mm) 6 in. (152.4 mm)

Ordering

31 in. (787.4 mm)

CKM

-

18

-

6

-

5

40 in. (1016 mm)

-

2

-

S

-

T - CCM1 - AN1

Product CKM ControlKeeper M Panel Size 18 (18 size) 36 (36 size) 48 (48 size) Number of Latching Relays (Single Space) 0-18 (0-18 for 18 size panel) 0-36 (0-36 for 36 size panel) 0-48 (0-48 for 48 size panel) Number of Electrically Held Relays (Single Space) 0-18 (0-18 for 18 size panel) 0-36 (0-36 for 36 size panel) 0-48 (0-48 for 48 size panel)

Analogs 0, AN1, AN2 (18 size) 0, AN1, AN2, AN3, AN4 (36 size) 0, AN1, AN2, AN3, AN4, AN5, AN6 (48 size) (Dependent upon # of CCMs, two ANs for each CCM. Each AN supplies four analog 0-10V inputs) Inputs (Each CCM supplies 18 contact inputs) 0, CCM1 (18 size) 0, CCM1, CCM2 (36 size) 0, CCM1, CCM2, CCM3 (48 size) Display NT No TouchScreen T TouchScreen Enclosure S Surface Number of Two Pole Relays (Double Space) 0-18 (0-18 for 18 size panel) 0-36 (0-36 for 36 size panel) 0-48 (0-48 for 48 size panel)

Additional OptionsCatalog # iBarrier Description Individual Relay Barrier, Voltage and Power Source Separation

Sample One-Line

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

ControlKeeper M Relay Panel Power Metering

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

ControlKeeper M Relay Panel Power Metering

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

ControlKeeper T Relay Panel

ControlKeeper 4A Distributed 0-10V Dimming panel Ethernet link: Programming access or Power Metering data access

Q1

NETWORK

LED1

C1

PCI 2005

CAN-RXLED4

CAN-TXLED5 C5

Q2

K1

C

50-022110-01

U4 U2

SW2

MOV2

TB2

LED3

U6

K2

SWIN PIC RS-232-SP

RSC PIC

C14

0 OHM OPT-47K

LED9

Gnd

STATUS

LED7

SWIN STAT1LED8

U4

U3

POWER

REMOTE

J7

J8

TB2

ANALOG INPUTS

LOCAL

TB3

TB4

DIMMING OUTPUTS

TB5

SWITCH INPUTS

TB6

LSO TEST

ANALOG INPUTS+24 GND

DIMMING OUTPUTSDO RTN DO RTN DO RTN 3 3 2 2 1 1

SWITCH INPUTS AND LIGHTED SWITCH OUTSDO RTN IN +24 4 4 1 IN LS 2 1 IN +24 IN LS 4 2 3TP1

AN AN AN AN 2 3 4 1

ANALOG GND

IN +24 IN LS IN 5 6 3 7

+24

IN 8

LS 4

To other lighting control panels Cable type: Belden 9841 or equal Maximum distance 4000 feet per network

K4

LOAD

RESET PICS

SD1

SW4

LINE

www.coopercontrol.com

800-553-3879

Q4

Ethernet link: Programming access or Power Metering data access

MOV3

TB3

Q3

SW3

K3

RSC STATL1

LED5

U2

PCI-NET TERM

1

PE-52627 PE-52647 or Talema SWV-0-90-330

MOV4

TB4

LOAD

LINE

LOAD

1

U1

LINE

LOAD

LINE

1

2

3

4

5

6

7

8

SW1

SW2

X4 SRC

ALL OFF

ALL ON

TB1

LED2

LED3

54-022510-

MOV1

LED1

ADDRESS

50-022510-00

To other lighting control panels

Lighting Control Panels - Network21

GDS Cable type: Cooper LCCNP or Cooper LCCP or Belden 1502, maximum distance 1000 feet per GDS network

48.25 in. (1225.55 mm)

24 in. (609.6 mm)

6 in. (152.4 mm)

RS-232 DIGITA PCI-NET PCI-NET +NET -NET

Catalog # Project Comments

Type

CKMB18, CKMB36, CKMB48 ControlKeeper M with Circuit Breakers Integrated breakers and relays in a single, space saving enclosure True real-time power metering relay panel Large, intuitive color touchscreen interface Individually replaceable relays with arc suppression technology Programming stored in non-volatile memory 30 Amp relays are used on all 20A relay cards to extend relay life Specifications:Enclosure: NEMA 1 surface mount, lockable Size: CKMB18: 54H X 24W X 6D (up to 18 relays) CKMB36: 76H X 24W X 6D (up to 36 relays) CKMB48: 90H X 24W X 6D (up to 48 relays) Transformer Ratings: Wide input voltage power supply, 120-347 VAC Power Use Ratings: Fully loaded panel 90 watts Operating Temp. Ratings: 32F to 122F (0C to 50C) Master Override: ON/AUTO/OFF or Individual relay control with status LED Programming: Onboard TouchScreen Interface One panel or entire network Optional PC Software Standard Relay Ratings: Normally open 20A, incandescent 120 VAC, ballast 277 VAC Maximum wire size: 8 AWG 1HP @ 120 VAC, 2HP @ 277 VAC Latching Relay Ratings: Normally open, normally closed or Latching 20A, incandescent 120 VAC, ballast 347 VAC Maximum wire size: 8 AWG 1HP @ 120 VAC, 2HP @ 277 VAC Two Pole Relay Ratings: Normally open or normally closed Maximum wire size: 8 AWG 1HP @ 120 VAC, 2HP @ 277 VAC Relays have a minimum 25K SCCR @ 277 VAC System warranty: Three year Relay warranty: Ten year UL Approval UL 508 Listed UL 924 with LRM

Prepared by

Date

Overview ControlKeeper M with Breakers network lighting control panels are scalable to any size application. The large view color touchscreen permits entire network programming and monitoring for complete system control and integration. Control up to 48 relays per panel with integral circuit breakers as well as discrete inputs for occupancy sensors, low voltage switches and other input devices. ControlKeeper M with Breakers network panels are designed for intuitive programming, and monitoring of the relays. The relays automatically sense the optimal time to switch lighting loads. Venergy Power Metering software in conjunction with our relays provide a complete Energy Management Solution. System Includes NEMA 1 enclosure Integral 20A breakers Low Voltage input connections Digital Switch Interface 0-10V inputs Time schedules with astronomic clock Color Touchscreen Accessories Automation Interface Module Ethernet Interface Module Telephone Interface Module Digital Switch Occupancy & Daylighting Sensors Prioritization and masking of switch inputs, time schedules, and remotes Timed inputs Occupant warn-off and overrides RS-232 port Power Metering Onboard Ethernet port UL Listed - UL 924 with LRM Keeper Enterprise Software Venergy Power Metering Softwar DMX Interface Dry Contact Switches

Ordering This is a network-ready lighting control system. It can be combined with other ControlKeeper series panels to create a scalable networked lighting control scheme. It can be ordered with any suitable system option or accessory. See next/back page for Ordering details.

Wiring DiagramsEnclosureCKMB 18: 54H X 24W X 6D (up to 18 relays) CKMB 36: 76H X 24W X 6D (up to 36 relays) CKMB 48: 90H X 24W X 6D (up to 48 relays)

ControlKeeper MB 18/36/4824 in. (609.6 mm) 24 in. (609.6 mm) 6 in. (152.4 mm) 6 in. (152.4 mm)

24 in. (609.6 mm)

6 in. (152.4 mm) 90 in. (2286 mm)5 2 S T - CCM1 - AN1

54 in. (1371.6 mm)

Ordering

CKMB - 120V1P - S

-

18

-

6

Product CKMB ControlKeeper MB Voltage and Phase 120V1P 120V Single Phase 120V3P 120V Three Phase 277V1P 277V Single Phase 277V3P 277V Three Phase 347V3P 347V Three Phase Types of Circuit Breakers S Siemens C Eaton G GE Panel Size 18 (18 size) 36 (36 size) 48 (48 size) Number of Latching Relays (Single Space) 0-18 (0-18 for 18 size panel) 0-36 (0-36 for 36 size panel) 0-48 (0-48 for 48 size panel)

76 in. (1930.4 mm)-

Analogs 0, AN1, AN2 (18 size) 0, AN1, AN2, AN3, AN4 (36 size) 0, AN1, AN2, AN3, AN4, AN5, AN6 (48 size) (Dependent upon # of CCMs, two ANs for each CCM. Each AN supplies four analog 0-10V inputs) Inputs (Each CCM supplies 18 contact inputs) 0, CCM1 (18 size) 0, CCM1, CCM2 (36 size) 0, CCM1, CCM2, CCM3 (48 size) Display NT No TouchScreen T TouchScreen Enclosure S Surface Number of Two Pole Relays (Double space) 0-18 (0-18 for 18 size panel) 0-36 (0-36 for 36 size panel) 0-48 (0-48 for 48 size panel) Number of Electrically Held Relays (Single Space) 0-18 (0-18 for 18 size panel) 0-36 (0-36 for 36 size panel) 0-48 (0-48 for 48 size panel)

Additional OptionsCatalog # iBarrier

Description Individual Relay Barrier, Voltage and Power Source Separation

Sample One-Line

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

ControlKeeper M Relay Panel Power Metering

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

ControlKeeper M Relay Panel Power Metering

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

ControlKeeper T Relay Panel

ControlKeeper 4A Distributed 0-10V Dimming panel Ethernet link: Programming access or Power Metering data access

Q1

NETWORK

LED1

C1

PCI 2005

CAN-RXLED4

CAN-TXLED5 C5

Q2

K1

C

50-022110-01

U4 U2

SW2

MOV2

TB2

LED3

U6

K2

SWIN PIC RS-232-SP

RSC PIC

C14

0 OHM OPT-47K

LED9

Gnd

STATUS

LED7

SWIN STAT1LED8

U4

U3

POWER

REMOTE

J7

J8

TB2

ANALOG INPUTS

LOCAL

TB3

TB4

DIMMING OUTPUTS

TB5

SWITCH INPUTS

TB6

LSO TEST

ANALOG INPUTS+24 GND

DIMMING OUTPUTSDO RTN DO RTN DO RTN 3 3 2 2 1 1

SWITCH INPUTS AND LIGHTED SWITCH OUTSDO RTN IN +24 4 4 1 IN LS 1 2 IN +24 IN LS 4 2 3TP1

AN AN AN AN 2 3 4 1

ANALOG GND

IN +24 IN LS IN 5 6 3 7

+24

IN 8

LS 4

To other lighting control panels Cable type: Belden 9841 or equal Maximum distance 4000 feet per network

K4

LOAD

RESET PICS

SD1

SW4

LINE

www.coopercontrol.com

800-553-3879

Q4

Ethernet link: Programming access or Power Metering data access

MOV3

TB3

Q3

SW3

K3

RSC STATL1

LED5

U2

PCI-NET TERM

1

PE-52627 PE-52647 or Talema SWV-0-90-330

MOV4

TB4

LOAD

LINE

LOAD

1

U1

LINE

LOAD

LINE

1

2

3

4

5

6

7

8

SW1

SW2

X4 SRC

ALL OFF

ALL ON

TB1

LED2

LED3

54-022510-

MOV1

LED1

ADDRESS

50-022510-00

To other lighting control panels

Lighting Control Panels - Network23

GDS Cable type: Cooper LCCNP or Cooper LCCP or Belden 1502, maximum distance 1000 feet per GDS network

RS-232 DIGITA PCI-NET PCI-NET +NET -NET

Catalog # Project Comments

Type

CKT16, CKT32, CKT48 ControlKeeper TouchScreen

Prepared by

Date

Capable of mixed load voltages (120/277/347 VAC) as well as mixed sources (ie. normal and emergency power) Manual and programmable control of each relay via a simple TouchScreen interface Normally open latched and two pole serial relays available 30 Amp relays one used on all 20A relay cards to extend relay life.Overview The ControlKeeper TouchScreen network lighting control panel is a costeffective specication grade lighting control system. Control up to 48 relays per panel. Network up to 254 ControlKeeper panels for a state of the art lighting control system. System Includes UL listed UL 916 standard NEMA 1 enclosure 32 low voltage input connections Digita Switch interface Time schedules with astronomic clock Prioritization and masking of switch inputs, time schedules, and remotes Accessories Keeper Enterprise Software Ethernet Interface Module Telephone Interface Module Flush Mount Kit Available Timed inputs Occupant warn-off and overrides TouchScreen RS-232 port standard RS-485 network standard 4 analog inputs UL Listed - UL 924 with RIM

Specifications:Enclosure: NEMA 1 surface mount, lockable Size: CKT16: 18H X 15W X 6.25D (up to 16 relays) CKT32: 30H X 15W X 6.25D (up to 32 relays) CKT48: 41H X 15W X 6.25D (up to 48 relays) Transformer Ratings: Multi-tapped 120/277 VAC internally fused standard Optional 347 VAC internally fused Power Use Ratings: Fully loaded panel 75 watts Operating Temp. Ratings: 32F to 122F (0C to 50C) Master Override: ON/AUTO/OFF Programming: Onboard TouchScreen Interface Optional PC Software Standard Relay Ratings: 20A, 120/277 VAC Normally open Maximum wire size: 10 AWG Mechanical operations: 10 million Latching Relay Ratings: 20A, 120/277/347 VAC Maximum wire size: 6 AWG Mechanical operations: 10 million Provides a system SCCR rating of 10,000A Two Pole Relay Ratings: 20A, 208/240/480 VAC Normally open Maximum wire size: 6 AWG Mechanical operations: 10 million System warranty: Three year Relay warranty: Ten year UL Approval UL 916 Listed UL 924 with RIM

Digita Switch Low Voltage Switches High Voltage Barrier Available High Voltage Divider Available

Ordering All ControlKeeper TouchScreen lighting control panels require a Logic Board (CKT LB). The logic board is shipped separately from the enclosure and is listed as a separate line item. When ordering any of the below models, you must also order the CKT LB. See next/back page for Ordering details.

Wiring DiagramsEnclosure

ControlKeeper TouchScreen 16/32/48CKT48

CKT32

High Voltage Barrier and Dividers

CKT16

High Voltage Separation Barrier

High Voltage Wiring Compartment System Power SuppyCKT 16 - 120/277 SS1 SL1 STO SHVB1 - SHVD1

Ordering

Product Size CKT ControlKeeper TouchScreen 16 (16 size) 32 (32 size) Voltage 48 (48 size) 120/277 120/277 V 220/230 220/230 V 120/347 120/347 V # of SSRCs (See SXRC cut sheet) 0-4 cards (16 size) 0-8 cards (32 size) 0-12 cards (48 size) # of SLRCs (See SXRC cut sheet) 0-4 cards (16 size) 0-8 cards (32 size) 0-12 cards (48 size)

# of High Voltage Dividers 0-1 (0-1 for 16 size panel) 0-4 (0-4 for 32 size panel) 0-6 (0-6 for 48 size panel) Factory installed in the lowest location of the panel # of High Voltage Barriers 0-1 (0-1 for 16 size panel) 0-3 (0-3 for 32 size panel) 0-5 (0-5 for 48 size panel) Factory installed in the lowest location of the panel # of STPRCs (See SXRC cut sheet) 0-4 cards (16 size) 0-8 cards (32 size) 0-12 cards (48 size)

Additional OptionsCatalog # CKT LB CKT16 FK CKT32 FK CKT48 FK Description ControlKeeper TouchScreen ControlKeeper TouchScreen ControlKeeper TouchScreen ControlKeeper TouchScreen Logic Board (required per enclosure) 16 size Flushmount Kit (option) 32 size Flushmount Kit (option) 48 size Flushmount Kit (option)

Sample One-Line

.

www.coopercontrol.com

800-553-3879

Lighting Control Panels - Network25

Catalog # Project Comments Prepared by

Type

Date

CK4A, ControlKeeper 4A

Support for up to four 0-10V dimming ballast outputs Electrically held normally open as well as mechanically latched and two pole relays available Capable of mixed load voltages (120/277/347 VAC) as well as mixed sources (ie. normal and emergency power) 4 single pole or 2 two pole serial relays Open or closed loop control algorithmsOverview The ControlKeeper 4A network lighting control panel is a cost-effective specication grade lighting control system. Control up to 4 relays per panel with optional support for up to four 0-10V dimming ballast control outputs. Network up to 254 ControlKeeper panels for a state of the art lighting control system. System Includes UL listed UL 916 standard NEMA 1 enclosure 4 relays Support for 4 three-wire or 8 two-wire low voltage inputs 4 analog inputs Digita Switch interface Time schedules with astronomic clock Accessories Keeper Enterprise Network Software Ethernet Interface Module Automation Interface Module Telephone Interface Module Gateway/DMX Gateway Prioritization and masking of switch inputs, time schedules, and remotes Timed inputs Occupant warn-off and overrides RS-232 port standard RS-485 network standard

Specifications:Enclosure: NEMA 1 surface mount enclosure Size: 10H x 14W x 3.5D Transformer Ratings: Multi-tapped 120/277 VAC internally fused standard Optional 347 VAC internally fused Power Use Ratings: Fully loaded panel 20 watts Operating Temp. Ratings: 32F to 104F (0C to 40C) Master Override: ON/AUTO/OFF Programming: Optional PC Software Standard Relay Ratings: 20A, 120/277 VAC Normally open Maximum wire size: 10 AWG Mechanical operations: 10 million Latching Relay Ratings: 20A, 120/277/347 VAC Maximum wire size: 6 AWG Mechanical operations: 10 million Provides a system SCCR rating of 10,000A Two Pole Relay Ratings: 20A, 208/240/480 VAC Normally open Maximum wire size: 6 AWG Mechanical operations: 10 million System warranty: Three year Relay warranty: Ten year

CEPC Digita Switch Dry Contact Switches Contact Input or Analog Photocell Occupancy Sensor

Ordering This is a network-ready lighting control system. It can be combined with other ControlKeeper series panels to create a scalable networked lighting control scheme. It can be ordered with any suitable system option or accessory.CK4A - SLRC -

Product CK4A ControlKeeper 4A

Transformer Voltage Blank 120/277 VAC 347 120/347 VAC Type of Relay Card SSRCNO SLRC SPTRMNO

UL Approval UL 916 listed

Wiring DiagramsEnclosure

ControlKeeper 4A

U5

Reflective Ceiling Plan

Sample Circuiting

Recessed General Lighting Luminaires

Circuit/Zone 1 Circuit/Zone 2 Outboard Lamps OFF Center Lamp Remains Circuit/Zone 3 ON (Full Output) Whiteboard Shuts OFF

Sample Switch Control1. ON/OFF (General) 2. A/V Mode

Daylight Zone 1

Daylight Zone 2

Daylight Zone 3

Sample One-Line

(indoor photosensor) Up to four photosensors connect to ControlKeeper 4A

switches, occupancy sensors, and photosensors)

www.coopercontrol.com

800-553-3879

Lighting Control Panels - Network27

Catalog # Project Comments Prepared by

Type

Date

CK4, ControlKeeper 4

Capable of mixed load voltages (120/277 VAC) as well as mixed sources (ie. normal and emergency power) Normally open Relays are integral to control boardOverview The ControlKeeper 4 network lighting control panel is a cost-effective specication grade lighting control system that can control 4 relays per panel. Network up to 254 ControlKeeper panels for a state of the art lighting control system. System Includes UL listed UL 916 standard NEMA 1 enclosure 4 relays 4 low voltage input connections Digita Switch interface Time schedules with astronomic clock Accessories Keeper Enterprise Network Software Ethernet Interface Module Automation Interface Module Telephone Interface Module Gateway/DMX Gateway

Specifications:Enclosure: NEMA 1 surface mount Size: 10H x 14W x 3.5D Transformer Ratings: 120 VAC or 277 VAC Power Use Ratings: Fully loaded panel 20 watts Operating Temp. Ratings: 32F to 122F (0C to 50C) Master Override: ON/AUTO/OFF Programming: PC Software Standard Relay Ratings: 20A, 120/277 VAC Normally open Maximum wire size: 10 AWG Mechanical operations: 10 million Warranty: Three year

Prioritization and masking of switch inputs, time schedules, and remotes Timed inputs Occupant warn-off and overrides RS-232 port standard RS-485 network standard CEPC Digita Switch Dry Contact Switch Contact Input Photosensor Occupancy Sensor

Ordering This is a network-ready lighting control system. It can be combined with other ControlKeeper series panels to create a scalable networked lighting control scheme.CK4 - 120NO

Product CK4 ControlKeeper 4

Transformer Voltage 120NO 120 VAC Normally Open 277NO 277 VAC Normally Open

UL Approval UL 916 listed

Wiring DiagramsEnclosure

ControlKeeper 414"

10"

3.5"

Reflective Ceiling Plan

Sample Circuiting

Recessed General Lighting Luminaires

Circuit/Zone 1 Circuit/Zone 2 Outboard Lamps OFF Center Lamp Remains Circuit/Zone 3 ON (Full Output) Whiteboard Shuts OFF

Sample Switch Control1. ON/OFF (General) 2. A/V Mode

Daylight Zone 1

Daylight Zone 2

Daylight Zone 3

Classroom or Office Solution with Whiteboard and AV Mode Option

Sample One-Line

switches, occupancy sensors, and photosensors)

.

www.coopercontrol.com

800-553-3879

Lighting Control Panels - Network29

Catalog # Project Comments Prepared by

Type

Date

CK2, ControlKeeper 2

Capable of mixed load voltages (120/277 VAC) as well as mixed sources (ie. normal and emergency power) Normally open relays Relays are built onto control boardOverview The ControlKeeper 2 network lighting control panel is a cost-effective specication grade lighting control system. Control 2 relays per panel. Network up to 254 ControlKeeper panels for a state of the art lighting control system. System Includes UL listed UL 916 standard NEMA 4X enclosure 2 relays 2 low voltage input connections Digita Switch interface Time schedules with astronomic clock Accessories Keeper Enterprise Network Software Ethernet Interface Module Automation Interface Module Telephone Interface Module Gateway/DMX Gateway

Specifications:Enclosure: NEMA 4X surface mount Size: 7.5H x 11W x 5D Transformer Ratings: 120 VAC or 277 VAC Power Use Ratings: Fully loaded panel 20 watts Operating Temp. Ratings: 32F to 122F (0C to 50C) Master Override: ON/AUTO/OFF Programming: Optional PC Software Standard Relay Ratings: 20A, 120/277 VAC Normally open Maximum wire size: 10 AWG Mechanical operations: 10 million System warranty: Three year

Prioritization and masking of switch inputs, time schedules, and remotes Timed inputs Occupant warn-off and overrides RS-232 port standard RS-485 network standard CEPC Digita Switch Dry Contact Switch Contact Input Photosensor Occupancy Sensor

Ordering This is a network-ready lighting control system. It can be ordered with the ControlKeeper TouchScreen, ControlKeeper 4, ControlKeeper 4A, or additional ControlKeeper 2. It can also be ordered with any suitable system option or accessory.

CK2

- 120NO

Product CK2 Control Keeper 2

Voltage 120NO 120 VAC Normally Open 277NO 277 VAC Normally Open

UL Approval UL 916 listed

Wiring DiagramsEnclosure

ControlKeeper 2

Reflective Ceiling PlanTIRC SCAL BARIA PEDS SCAL E E

CK2PORTABLE X-RAY MTR. MTR. MTR. MTR. MTR. MTR. MTR. TV ICE MACHINE TV MTR. STRETCHER LINEN RECPT. HAMPER TRASH EXAM STOOL TV TV TV TV TV TV TV PROC. CART DEFIB. INSTRUMENTPEDS. CC TABLE PROC. CART PROC. CART PROC. CART PROC. CART PROC. CART PROC. CART PROC. CART

PEDS. CC

IV CART

EQUIPMENT CART

IV CART

CRASH CART

KICK BUCKET COPIER FAX SCAN PRINTER UNDER COUNTER REFRIG COFFEE UNDER COUNTER REFRIG COFFEE SUTURE CART

PROC. CART

MAYO

PYXIS

ICE MACHINE

ICE MACHINE

PYXIS

VIEWBOX CARDIAC MTR. PROC. CART

CK2LINEN RECPT. HAMPER TRASH EXAM STOOL DEFIB. INSTRUMENT TABLE CRASH CART KICK BUCKET PROC. CART MAYO

ICE INE MACH

SUTURE CART TV

TRASH

SOILED LINEN

CRASH CART EXAM STOOL

BLANKET WARMER

LINEN CART EXAM STOOL

CASTING CART

TV

TV

TV

TV

TV

MTR.

MTR.

MTR.

MTR.

MTR.

WHITEBOARD

MTR.

The ControlKeeper 2 is the ideal solutionfor A/B switching of lighting loads for small offices or corridors.

Sample One-Line

switches, occupancy sensors, and photosensors)

panel

31 www.coopercontrol.com 800-553-3879

Lighting Control Panels - Network

MTR. MTR. CORKBOARD TV

PROC. CART WIRE RACK PROC. CART PROC. CART PROC. CART PROC. CART TV LD APRN RACK MTR. TV TV

DEFIB. INSTRUMENT TABLE CRASH CART

PROC. CART

TV

CK2TV

MTR.

MTR. LINEN RECPT. HAMPER TRASH MTR. PROC. CART PROC. CART MTR. PORTABLE X-RAY KICK BUCKET PROC. CART MAYO TV TV UNDER COUNTER

Catalog # Project Comments Prepared by

Type

Date

SXRC, Serial Relay Cards (CKT & CK4A Relay Panels)

Surge/Arc suppression for each relay

UL and cUL listed system Rated for 10 million mechanical operations Relay override for each relay LED status indication of relay state Communication LED for system diagnostics 4 single pole or 2 two pole relaysModular design (plugs into the IntelliRelay bus communication system)

Specifications:Serial Standard Relay Card (SSRC) Ratings: 20A, 120/277 VAC Normally open Maximum wire size: 10 AWG Mechanical operations: 10 million Serial Latching Relay Card (SLRC) Ratings: 20A, 120/277/347 VAC Maximum wire size: 6 AWG Mechanical operations: 10 million Provides a system SCCR rating of 10,000A Serial Two Pole Relay Card (STPRC) Ratings: 20A, 208/240/480 VAC Normally open Maximum wire size: 6 AWG Mechanical operations: 10 million Relay warranty: Ten year

Overview The Serial Relay Card is a paradigm shift in the industry. A new serial communication approach greatly enhances system function allowing the controller to talk to the intelligent relays. The Serial Relay Card (SxRC) is a standard feature in ControlKeeper TouchScreen and ControlKeeper 4A lighting control systems. It provides up to four relays per card, depending on type. Description The IntelliRelay design provides a communication protocol between the controller board and the relays. The controller polls the relays to ascertain their configuration and their location. The controller then builds them into the system automatically. The installer or end user does not need to spend time configuring the relays in the controller. OrderingCatalog # SSRC NO SLRC STPRC NO Relay Type Serial Standard Relay Card normally open Serial Latching Relay Card Serial Two Pole Relay Card normally open

UL Approval UL 916 listed system

Wiring Diagrams

Serial Relay Cards

Serial Standard Relay Card

Serial Latching Relay Card

Serial Two Pole Relay Card

www.coopercontrol.com

800-553-3879

Lighting Control Panels - Network Relay Cards33

Catalog # Project Comments Prepared by

Type

Date

LK16, LK32 LiteKeeper 16 and 32

Capable of mixed load voltages (120/277/347 VAC) as well as mixed sources (ie. normal and emergency power) Manual and programmable control of each relay via a simple keypad and 4 line LCD display Normally open, latched, and two pole parallel relays available Flush mount kit and voltage separation barrier available Specifications:Enclosure: NEMA 1 surface mount, lockable Size: LK16: 18H x 15W x 6.25D (up to 16 relays) LK32: 30H x 15W x 6.25D (up to 32 relays) Transformer Ratings: Multi-tapped 120/277 VAC internally fused standard Optional 347 VAC internally fused Power Use Ratings: Fully loaded panel 75 watts Operating Temp. Ratings: 32F to 122F (0C to 50C) Master Override: ON/AUTO/OFF Programming: Onboard keypad and LCD display Optional PC Software Standard Relay Ratings: 20A, 120/277 VAC Normally open Maximum wire size: 10 AWG Mechanical operations: 10 million Latching Relay Ratings: 20A, 120/277/347 VAC Maximum wire size: 6 AWG Mechanical operations: 10 million Provides a system SCCR rating of 10,000A Two Pole Relay Ratings: 20A, 208/240/480 VAC Normally open Maximum wire size: 6 AWG Mechanical operations: 10 million System warranty: Three year Relay warranty: Ten year

Overview The LiteKeeper stand-alone lighting control panel is an all-inclusive premium grade system for applications that would traditionally use a timeclock in conjunction with contactors. Control up to 32 relays per panel. Several relay options and more standard features than any other stand-alone panel on the market combine to create a state of the art stand-alone lighting control system. System Includes UL listed UL 916 standard NEMA 1 enclosure 32 low voltage input connections Digita Switch interface Time schedules with astronomic clock Prioritization and masking of switch inputs, time schedules, and remotes Accessories Keeper Enterprise Software Ethernet Interface Module Automation Interface Module Telephone Interface Module Digita Switch Dry Contact Switches

Timed inputs Occupant warn-off and overrides Keypad and 4 line LCD display RS-232 port standard UL Listed - UL 924 with RIM

Contact Input Photosensor Occupancy Sensor Voltage Separation Barrier Flush Mount Kit CEPC RIM

Ordering All LiteKeeper lighting control panels require a Logic Board (LK LB). The logic board is shipped separately from the enclosure and is listed as a separate line item. When ordering any of the below models, you must also order the LK LB. See next/back page for Ordering details.

UL Approval UL 916 listed UL 924 with RIM

Wiring DiagramsEnclosure

LiteKeeper 16 and 32LK32

High Voltage Barrier and Dividers

LK16

High Voltage Separation Barrier

High Voltage Wiring Compartment System Power Suppy

OrderingProduct Size LK16 LiteKeeper 16 LK32 LiteKeeper 32 Voltage 120/277 220/230 120/347

LK16

-

120/277

- S1

-

L1

-

MO

-

TO

-

HVB1

# of High Voltage Barriers 0-1 (16 size) 0-2 (32 size) Factory installed in the lowest location of the panel

# of SRCs 0-2 cards (16 size) 0-4 cards (32 size) (See XRC cut sheet)

# of TPRCs 0-2 cards (16 size) 0-4 cards (32 size) (See XRC cut sheet)

Additional OptionsCatalog # LK LB LK 16 FK LK 32 FK

# of LRCs 0-2 cards (16 size) 0-4 cards (32 size) (See XRC cut sheet)

LiteKeeper Logic Board (required per enclosure) LiteKeeper 16 size Flushmount Kit (option) LiteKeeper 32 size Flushmount Kit (option)

# of MRCs 0-2 cards (16 size) 0-4 cards (32 size) (See XRC cut sheet)

Sample One-Linelogic board are removed for clarity.

Logic BoardQty 8 - 20 amp 120/277 VAC single pole relays per card

120/277 VAC double tap transformer standard 120/347 VAC double tap transformer is available for Canada

switches, occupancy sensors and photosensors)

120 VAC wall transformer included

www.coopercontrol.com

800-553-3879

Lighting Control Panels - Stand-Alone35

Catalog # Project Comments Prepared by

Type

Date

LK8, LiteKeeper 8

Manual and programmable control of each relay via a simple keypad and 2 line LCD display Normally open, latched, and two pole relays available Uses parallel relay cards Flush mount kit available

Keypad and LCD for simplified programming

Specifications:Enclosure: NEMA 1 surface mount, lockable Size: 14H x 9.5W x 5D or 7D Transformer Ratings: Multi-tapped 120/277 VAC internally fused standard Optional 347 VAC internally fused Power Use Ratings: Fully loaded panel 40 watts Operating Temp. Ratings: 32F to 122F (0C to 50C) Mater Override: ON/AUTO/OFF Programming: Onboard keypad and LCD display Optional PC Software Standard Relay Ratings: 20A, 120/277 VAC Normally open Maximum wire size: 10 AWG Mechanical operations: 10 million Latching Relay Ratings: 20A, 120/277/347 VAC Maximum wire size: 6 AW Mechanical operations: 10 million Provides a system SCCR rating of 10,000A Two Pole Relay Ratings: 20A, 208/240/480 VAC Normally open Maximum wire size: 6 AWG Mechanical operations: 10 million System warranty: Three year Relay warranty: Ten year

Overview The LiteKeeper 8 stand-alone lighting control panel is an all-inclusive premium grade system for applications that would traditionally use a timeclock in conjunction with contactors. Control up to 8 relays per panel. Several relay options and more standard features than any other stand-alone panel on the market combine to create a state of the art stand-alone lighting control system. System Includes UL Listed UL 916 standard NEMA 1 enclosure 8 relays 8 low voltage input connections Time schedules with astronomic clock Accessories Keeper Enterprise Software Ethernet Interface Module Telephone Interface Module Flush Mount Kit Digita Switch Ordering See next/back page for Ordering details.

Prioritization and masking of switch inputs, time schedules, and remotes Timed inputs Occupant warn-off and overrides Keypad and 2 line LCD display RS-232 port standard

Dry Contact Switches Contact Input Photosensor Occupancy Sensor CEPC

UL Approval UL 916 listed

Wiring DiagramsEnclosure

LiteKeeper 8LK8 9.5 LK8-LRC, MRC, TPRC 9.5

5 14 14

7

Ordering

LK8 - LRC

Product LK8 LiteKeeper 8

Options LRC MRC TPRC 347

Latching Relay Card (see Spec Cut Sheet) Modular Relay Card (see Spec Cut Sheet) Two Pole Relay Card (see Spec Cut Sheet) (Canada 347VAC transformer with LRC)

Additional OptionsCatalog # LK 8 FK Description LiteKeeper 8 size Flushmount Kit (option)

Sample One-Line

www.coopercontrol.com

800-553-3879

Lighting Control Panels - Stand-Alone37

Catalog # Project Comments Prepared by

Type

Date

LK4, LiteKeeper 4

Manual and programmable control of each relay via a simple keypad and 2 line LCD display Normally open relays Relays are built onto control board

Specifications:Enclosure: NEMA 1 surface mount, lockable Size: 9.5H x 14W x 3.25D Transformer Ratings: 120 VAC or 277 VAC Power Use Ratings: Fully loaded panel 20 watts Operating Temp. Ratings: 32F to 122F (0C to 50C) Master Override: ON/AUTO/OFF Programming: Onboard keypad and LCD display Optional PC Software Standard Relay Ratings: 20A, 120/277 VAC Normally open Maximum wire size: 10 AWG Mechanical operations: 10 million Warranty: Three year

Overview The LiteKeeper 4 stand-alone lighting control panel is an all-inclusive premium grade system for applications that would traditionally use a timeclock in conjunction with contactors. Each panel allows control of up to four 20A circuits. The LiteKeeper 4 has more standard features than any other standalone panel on the market to create a state of the art stand-alone lighting control system. System Includes UL Listed UL 916 standard NEMA 1 enclosure 4 20A relays 4 low voltage input connections Time schedules with astronomic clock Accessories Keeper Enterprise Software Ethernet Interface Module Telephone Interface Module Dry Contact Switch OrderingCatalog # LK4-120NO LK4-277NO # of Relays 4 4 Input Voltage 120 VAC 277 VAC Relay Type 120/277 VAC standard, normally open 120/277 VAC standard, normally open

Prioritization and masking of switch inputs, time schedules, and remotes Timed inputs Occupant warn-off and overrides Keypad and 2 line LCD display RS-232 port standard

Contact Input Photosensor Occupancy Sensor CEPC

UL Approval UL 916 Listed

Wiring DiagramsEnclosure

LiteKeeper 4

Sample One-Line

Lighting control panel power supply: Voltage specific transformer. Specify 120 VAC or 277 VAC for the transformer voltage. Typical Occupancy Sensor for On/Off control Typical Photosensor for On/Off control+24 ON

PCI LITEKEEPER 12:OO O1/O1/95

1 4 7 *

2 5 8 0

3 6 9 #

A B C D

4 low voltage inputs (Momentary, Maintained, Alternate Action switches, occupancy sensors and photosensors) Each input is software programmable to . control any relay or group of relays

The Ethernet Interface Module (EIM) and Wireless Ethernet Interface Module (WEIM) may be connected to any lighting control pane in the system using the RS-232 cable included

120 VAC wall transformer included

End user computers can program any lighting control panel via the Wireless Ethernet Interface Module (WEIM) using the Keeper Enterprise software.

www.coopercontrol.com

800-553-3879

Lighting Control Panels - Stand-Alone39

Line Load A Line Load B Line Load C Line Load D

Typical relay wiring:

Standard relay information Qty 4 - 20 amp 120/277 VAC single pole relays Available normally open or normally closed Individual status LED manual overrides 10 AWG maximum wire size 10 million operations 3 year warranty

OFF

OFF

OFF

+24

OFF

+24

+24

ON

ON

ON

+24VDC

DC GND

Catalog # Project Comments Prepared by

Type

Date

XRC, Parallel Relay Cards (LiteKeeper Relay Panels)

Standard Relay Card

UL and CUL listed system Modular design 8 single pole or 4 two pole parallel relays per cardOverview The Parallel Relay Card (xRC) is a standard feature in the LiteKeeper lighting control systems. Each Parallel Relay Card contains 8, 20 amp relays. Specify up to 4 total relay cards per enclosure. Description Electronic arc suppression is incorporated into the relay design, prolonging contact life. Self aligning connectors on the Parallel Relay Card allows easy eld expansion. You can add another standard or any of the optional relay cards to a system at any time (enclosure size allowing). Installation No additional installation required. The Parallel Relay Card(s) (xRCs) attach directly to your specied enclosure. Ordering This is a standard feature in the LiteKeeper lighting control systems. When specifying one of these systems, specify enclosure size, and types of relay cards. Mix and match any combination of standard and optional relay cards to create a custom system tailored to meet your needs.Catalog # SRC LRC Relay Type Standard Relay Card with 8 20A 120/277 VAC normally open relays Latching Relay Card with 8 20A 120/277/347 VAC latching relays

Specifications:Standard Relay Card (SRC) Ratings: 20A, 120/277 VAC Normally open Maximum wire size: 10 AWG Mechanical operations: 10 million Latching Relay Card (LRC) Ratings: 20A, 120/277/347 VAC Maximum wire size: 6 AWG Mechanical operations: 10 million Provides a system SCCR rating of 10,000A Modular Relay Card (MRC) Ratings: 20A, 120/277 VAC normally open 20A, 120/277/347 VAC (LRM) 20A, 208/240/480 VAC normally open Maximum wire size: 10 AWG (SRM) or 6 AWG (LRM, TPRM) Mechanical operations: 10 million Two Pole Relay Card (TPRC) Ratings: 20A, 120/277/347/208/240/480 VAC Maximum wire size: 12 AWG Mechanical operations: 60,000 Warranty: Ten year

MRC Relay Card Options for LK8, LK16, LK32 MRC SRM NO TPRM NO Modular Relay Card (Included in LK8 w/MRC) Standard Relay Module Card 20 amp 120/277 VAC single pole normally open relay (1 relay space) Two Pole Module 20 amp 208/240/480 VAC two pole normally open relay (2 relay spaces)

TPRC Relay Card Options for LK8, LK16, LK32 TPRC SPR347 TPR208 Two pole relay card (Included with LK8 w/TPRC) Single pole relay card 20 amp 120/277/347 VAC single pole relay (1 relay space) Two pole relay card 20 amp 208/240 VAC two pole relay (1 relay space) Two pole relay card 20 amp 480 VAC two pole relay (2 relay spaces)

UL Approval UL 916 Listed system

TPR480

Wiring Diagram

Parallel Relay Cards

Latching Relay Card

Modular Relay Card

Two Pole Relay Card

41 www.coopercontrol.com 800-553-3879

Lighting Control Panels - Stand-Alone Relay Cards

Catalog # Project Comments Prepared by

Type

Date

TK16, TK32 TracKeeper

Track light current limiting panel Helps your design meet energy codes Allows track lighting installations to be based on volt-ampere rating of load instead of track length Available in 16 or 32 circuit panels Circuit breaker sizes range from 0.5 to 60A Surface or flush mount options Factory assembled and ready to installOverview The TracKeeper current limiting panel for track lighting allows designers to easily meet energy codes. Limiting the branch circuit volt-ampere rating with the TracKeeper provides you with a xed power consumption limit for your installation as opposed to calculated values based on watts per linear foot of track. Designers can now specify as many linear feet of track as desired without paying a penalty. Additionally, the use of high efciency luminaires will often yield a lower watts/linear foot number than is specied in the code. Keep your track lighting installation options open with the TracKeeper. System Includes NEMA 1 enclosure Hinged locking door As many as 16 or 32 circuit breakers Ordering Specify enclosure size, mounting option, voltage and number of circuit breakers desired. See next/back page for Ordering details.

Specifications:Enclosure: NEMA 1, 14 gauge steel, hinged locking door Surface or ush mount Surface Size: 16 circuit: 10H X 14W X 3 3/8D 32 circuit: 16H X 14W X 3 3/8D Flush Size: 16 circuit: 11 1/2H X 15 1/2W X 3 3/8D 32 circuit: 17 1/2H X 15 1/2W X 3 3/8D AIC rating: 10,000A, 120 VAC; 6,000A, 277 VAC Available circuit breaker ratings (A): 0.5, 1, 2, 3, 4, 5, 6, 7, 8, 10, 13, 15, 16, 20, 25, 30, 32, 40, 50, 60 Circuit breaker wire size range: 14 to 6 AWG Operating Temp. Ratings: 23 to 140F (-5C to 60C) Relative Humidity: 0 - 95% non-condensing System warranty: Three year

TK16

-

120

-

5

-

F

Product TK16 (16 size) TK32 (32 size) Voltage 120 VAC 277 VAC

Mounting Option S Surface F Flush

# of Breakers 0-16 cards (16 size) 0-32 cards (32 size)

UL Approval UL 508A Listed

Example: TK16-120-14-F species a 16 circuit ush mount enclosure with 15 120V circuit breakers.

Panel Schedule

TracKeeper 16 & 32

Trackeeper Track Light Current Limiting Panel Specication Sheet Project: Prepared by: Catalog #: Comments: Step 1 - Selected panel operating voltage: Step 2 - Select enclosure mounting option: Step 3 - Select panel circuit size: Step 4 - Specify number of installed circuit breakers: (120V or 277V) (Surface or Flush Mount) (TK16 or TK32) (1) Date:

Step 5 - Specify each circuit breaker rating: Circuit Breaker 1 Rating (A) Circuit Breaker 2 Rating (A) Circuit Breaker 3 Rating (A) Circuit Breaker 4 Rating (A) Circuit Breaker 5 Rating (A) Circuit Breaker 6 Rating (A) Circuit Breaker 7 Rating (A) Circuit Breaker 8 Rating (A) Circuit Breaker 9 Rating (A) Circuit Breaker 10 Rating (A) Circuit Breaker 11 Rating (A) Circuit Breaker 12 Rating (A) Circuit Breaker 13 Rating (A) Circuit Breaker 14 Rating (A) Circuit Breaker 15 Rating (A) Circuit Breaker 16 Rating (A) Circuit Breaker 17 Rating (A) Circuit Breaker 18 Rating (A) Circuit Breaker 19 Rating (A) Circuit Breaker 20 Rating (A) Circuit Breaker 21 Rating (A) Circuit Breaker 22 Rating (A) Circuit Breaker 23 Rating (A) Circuit Breaker 24 Rating (A) Circuit Breaker 25 Rating (A) Circuit Breaker 26 Rating (A)

Circuit Breaker 28 Rating (A) Circuit Breaker 29 Rating (A) Circuit Breaker 30 Rating (A) Circuit Breaker 31 Rating (A) Circuit Breaker 32 Rating (A)

Provide Panel schedule indicating circuit breaker ratings for each location. Visit www.coopercontrol.com for the form. Once completed print and fax your completed form with your purchase order to 800-954-7016, or email a PDF to [email protected]

www.coopercontrol.com

800-553-3879

Lighting Control Panels - Current Limiting43

Circuit Breaker 27 Rating (A)

Catalog # Project Comments Prepared by

Type

Date

GDS, Greengate Digital Switch 24 VDC supply voltage via the network Capable of controlling loads over entire lighting network Integrates with Keeper Enterprise Software or On-Board programming display Create custom lighting configurations for each button Class 2 low voltage wiring All plastic construction with a separate decorator style snap-on surround Suitable for standard single and multigang NEMA wall box with decorator style wallplate Choice of large or small buttons A range of seven standard wall station templates can be selected Tested to withstand 12kV electrostatic discharge without damage of memory loss Includes single gang screwless wallplateGDS-3TLB GDS-6TSB

Overview The Digital Switch is available for the ControlKeeper M series of lighting control panels. It is a decorator style switch with up to six buttons offers ON/OFF control of any relay or group of relays in the lighting control network. Description The Digital Switch permits multiple control stations to be connected to the lighting control panels. The control stations provide override and status feedback. Advanced system features such as masking and priorities are standard on all lighting control panels and can be applied to these switches to make your application both contractor and user friendly. Installation The Digital Switch ts in a single or multi-gang NEMA wall box and has a standard decorator style opening to permit single or multi-gang congurations. The Digital Switches are networked together using the LCCNP or LCCP wire (provided by Cooper Controls) and can connect to the ControlKeeper M lighting control panel. Up to 32 Digital Switch stations may be wired to a single lighting control panel. Ordering This is an accessory for ControlKeeper M lighting control systems. When ordering, specify the Digital Switch as a separate system accessory. See next/back page for custom and preset engraving options.GDS - 1 - TLB - W -

Specifications:Communications: Canbus (requires Digita Gateway) Warranty: Three year

Product GDS Greengate Digital Switch Number of Buttons 1-3 (Large Button) 2, 4, 5, 6 (Small Button) Button size TLB Large Buttons TSB Small Buttons

Blank Zone1, Zone 2, Zone 3, etc. CE - Custom Engraved (Requires Custom Engraving Form) T1 Preset Engraving Based on Conguration (see back page)

Insert Color W White B Black V Ivory

Engraving Options

Digital Switch

Custom Engraving (Option CE) Guidelines Small button custom engraving, maximum 1 line, 11 characters. Large button cusom engraving, maximum 2 lines, 11 characters per line. Visit our website at www.coopercontrol.com to download the custom engraving form. Custom engraving form must be included when ordering. Allow 4 weeks for delivery. Preset Engraving Based on Conguration Preset engraving options to simplify ordering. Preset engraving options vary based on button congurations, see chart below. Allow 4 weeks for delivery.

Catalog GDS-1TLB-* GDS-2TLB-* GDS-3TLB-*

Button # 1 1 2 1 2 3 1 2 1 2 3 4 1 2 3 4 5 1 2 3 4 5 6

T1 Engraving On/Off On Off On/Off AV Auto On/Off On/Off Row 1 Row 2 Row 3 Row 4 On/Off Whiteboard General AV Auto On/Off Whiteboard Window General AV Auto

GDS-2TSB-*

GDS-4TSB-*

GDS-5TSB-*

GDS-6TSB-*

System SchematicGDS Cable type: Cooper LCCNP or Cooper LCCP or Belden 1502, maximum distance 1000 feet per GDS network

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

ControlKeeper M Relay Panel Power Metering

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

ControlKeeper T Relay Panel

ControlKeeper 4A Distributed 0-10V Dimming panel Ethernet link: Programming access or Power Metering data access

Q1

NETWORK

LED1

C1

PCI 2005

CAN-RXLED4

CAN-TXLED5 C5

Q2

K1

C

50-022110-01

U4 U2

SW2

MOV2

TB2

LED3

U6

K2

SWIN PIC RS-232-SP

RSC PIC

C14

0 OHM OPT-47K

LED9

Gnd

STATUS

LED7

SWIN STAT1LED8

U4

U3

POWER

REMOTE

J7

J8

TB2

ANALOG INPUTS

LOCAL

TB3

TB4

DIMMING OUTPUTS

TB5

SWITCH INPUTS

TB6

LSO TEST

ANALOG INPUTS+24 GND

DIMMING OUTPUTSDO RTN DO RTN DO RTN 3 3 2 2 1 1

SWITCH INPUTS AND LIGHTED SWITCH OUTSDO RTN IN +24 4 4 1 IN LS 1 2 IN +24 IN LS 4 2 3TP1

AN AN AN AN 2 3 4 1

ANALOG GND

IN +24 IN LS IN 5 6 3 7

+24

IN 8

LS 4

To other lighting control panels Cable type: Belden 9841 or equal Maximum distance 4000 feet per network

K4

LOAD

RESET PICS

SD1

SW4

LINE

www.coopercontrol.com

800-553-3879

Q4

Ethernet link: Programming access or Power Metering data access

MOV3

TB3

Q3

SW3

K3

RSC STATL1

LED5

U2

PCI-NET TERM

1

PE-52627 PE-52647 or Talema SWV-0-90-330

MOV4

TB4

LOAD

LINE

LOAD

1

U1

LINE

LOAD

LINE

1

2

3

4

5

6

7

8

SW1

SW2

X4 SRC

ALL OFF

ALL ON

TB1

LED2

LED3

54-022510-

MOV1

LED1

ADDRESS

50-022510-00

To other lighting control panels

Lighting Control Panels - Switches45

ControlKeeper M Relay Panel Power Metering

RS-232 DIGITA PCI-NET PCI-NET +NET -NET

Catalog # Project Comments Prepared by

Type

Date

Digita Switch (Standard)

Digita 5-5B Digita 1

Capable of controlling loads over multiple panels Integrates with Keeper Enterprise Software to simplify programming Create custom lighting configurations for each button Class 2 low voltage

Overview The Digita Switch is an optional feature available for Greengate lighting control panels. A decorator style switch with up to ve buttons offers ON/OFF control of relay groups with the touch of a button. The Digita Switch also provides scene control and raise/lower control of lighting loads when used in conjunction with the ControlKeeper 4A lighting control panel. Description The Digita Switch permits multiple control stations to be connected to the lighting control panels. The control stations provide local overrides and status feedback. Advanced system features such as masking and prioritization can be applied to these switches to make your application both contractor and end user friendly. Installation The Digita Switch ts into a standard decorator style opening and can be networked together using Cooper LCCP Cable, Cooper LCCNP Cable, or Belden 1502 Cable. Set the address on the back of the switch and control up to 99,999 relay groups. Ordering This is an accessory for Greengate lighting control systems (except LK4). When ordering, specify the Digita Switch as a separate system accessory. When ordering switch stations with custom engraving submit a drawing documenting the labeling requirements.Catalog # Digita 1 Digita 5 DG2 Description One button decorator style rocker See next/back page for Ordering information Digita Switch Gateway required per digital switch network connection

Specifications:Communications: Canbus (Requires Digita Gateway) Warranty: Three year

* For Custom Labeling see next/back page for more information.

Ordering

Digita SwitchDigita 5 - 5B - D2

5 = 5 LED pushbuttons

1B 2B 3B 4B 5B

= 1 LED pushbutton = 2 LED pushbutton = 3 LED pushbutton = 4 LED pushbutton = 5 LED pushbutton

Blank = Zone 1 - Zone 5 S1 ON/OFF, A/V Mode S2 ON/OFF, A/V Mode, Whiteboard S3 ON/OFF, A/V Mode, Quiet S4 ON/OFF, A/V Mode, Whiteboard, Quiet D1 ON/OFF, A/V Mode, Raise, Lower D2 ON/OFF, A/V Mode, Raise, Lower, Whiteboard DX Raise, Lower DM ON/OFF, Preset, Raise, Lower CE Customer dened requires custom engraved form at placement of order

The Digita Switch is available in multiple standard engraved options. Simply append the Controller Model to the appropriate Digita Switch. (Example: Digita5-3B52 or Digita5-5BD2)

1. ON/OFF (General) 2. A/V MODE

1. 2. 3. 4.S4

ON/OFF (General) A/V MODE QUIET TIME WHITEBOARDDX

1. RAISE 2. LOWER

S1

1. ON/OFF (General) 2. A/V MO