Room Controller design and application brochure Greengate

Office

Conference room

Classroom Healthcare

2www.eaton.com/lightingsystems

Table of contentsRoom Controller system 3

Features and benefits 4

Built-in energy savings lighting control strategies 5

Out-of-the-box control strategies 6

Stand-alone architecture 7

Network architecture 9

Ordering options 11

Model installation diagrams 13

APPLICATIONS

Office 14

Open office 15

Conference room 16

Corridor, hall or stairwell 17

Classroom – Suspended fixtures and tree daylight zones 18

Classroom – Recessed fixtures and tree daylight zones 19

System components 21

QuicKits and starter kits 23

TYPICAL WIRING DIAGRAMS

Small office with Daylighting 24

Office with Receptacle and Emergency Control 24

Office with HVAC output 25

Conference room with receptacle and Emergency Control, daylighting and programmable scene wallstations

25

Classroom with emergency and receptacle control 26

Classroom with daylight dimming 26

Demand Response Connections 27

Alternative Voltage Connection 27

Receptacle wiring 28

Wallstation sharing 29

Network wiring 30

3 www.eaton.com/lightingsystems

Room Controller system

The Room Controller System provides energy compliant lighting, plug and emergency control capabilities that allow for out-of-the-box functionality in virtually any space. The system can be ordered based on specific budget or performance requirements.

Simplified compliance with a product designed to meet the latest energy codes Reduce cost of installation with single enclosure and simplified wiring Save time with out-of-the-box controls functionality, no programming needed

4www.eaton.com/lightingsystems

Features and benefitsStand-Alone Architecture

Code compliant automatic lighting, emergency and plug load control.

Delivers occupancy status to HVAC system via contact closure. Receives local Demand Response signal.

Contractor Benefits

Reduce material cost with the Room Controller included wiring compartment with direct conduit connections. No need for additional junction boxes.

Simplified wiring with RJ45 connections for all low voltage devices saves time on the site.

Save time on network projects that require startup, with the Room Controller that works immediately on power up.

Distributor Benefits

Give the electrical contractor what they need to start a project with convenient Room Controller starter kits.

Reduce inventory requirements with sensors that work with Room Controllers or with stand-alone applications.

Out-of-the-box functionality provides immediate verification of wiring and code compliance.

Specifier Benefits

Worry free design with the Room Controller system that was designed to meet the current energy codes. Simplified sequence of operations definition and training with out-of-the-box functionality. Simplify complex user interaction with flexible wallstations that can be customized with zone or scene buttons.

End User Benefits

Reduce training time with simple and consistent user experience in all rooms that have the Room Controller installed. Remove maintenance concerns with RJ45 plug in low voltage devices that work immediately when connected. Save on operating costs with a system that was designed to provide consistent energy savings and drive energy efficiency throughout the building.

Network Architecture Code compliant automatic lighting, emergency and plug load control with enhanced user control and centralized time schedule control.

Integrates with BMS via BACnet IP. Centralized Demand Response via network.

5 www.eaton.com/lightingsystems

STRATEGY DESCRIPTION ESTIMATED SAVINGS

ManualDimmer

Manual/personal dimming control – is one of five alternative methods to meet the Multi-level lighting control requirements.

10-20%

OccupancySensor

Occupancy/vacancy sensing – provides Manual On/Automatic Off or Automatic On/Automatic Off and Partial Off capabilities.

20-60%

DaylightingControl

Daylight dimming – provides three daylight dimming zone that automatically adjust the lighting based on daylight available in the space.

20-45%

ReceptacleControl

Plug load control – automatically turns On receptacles upon occupancy regardless of light status. Ensures receptacles are turned Off when the space is vacant.

15-50% Controlled loads

TuningControl

High-end/Task Tuning – lowers the maximum light level for automatic energy savings.

10-30%

DemandResponse

Demand Response – automatically reduces light level based on signal from OpenADR device or BMS closure.

10-40%

Remote SignalControl

Remote Signal Control – Automatically sends a signal to the HVAC system based on occupancy.

20%

Built-in energy saving lighting control strategies

6www.eaton.com/lightingsystems

The Room Controller system can now be specified and ordered based on project needs. The Room Controller system is available in both a stand-alone and networked architecture.

Individual components – Simple product offering list Room Controller Starter Kits – Basic Electrical Distributor stocking products, everything the electrical contractor will need for installation above the ceiling. Customize for each space with specific wallstations and sensor requirements.

Room Controller QuicKits – Easy to order, designed and packaged for immediate in room installation and provide a complete all-in-one package solution, with pre-defined sequence of operations.

Supported by Eaton a global leader with expertise in power distribution and circuit protection; backup power protection; control and automation; lighting and security; structural solutions and wiring devices; solutions for harsh and hazardous environments; and engineering services. Eaton is positioned through its global solutions to answer today’s most critical electrical power management challenges.

DemandResponse

UL924 (Energy Back-up Circuit) Manually Switched

ON/OFF

OccupancySensor

DaylightingControl

ReceptacleControl

Integration

Out-of-the-box control strategies

7 www.eaton.com/lightingsystems

Stand-alone architectureThe Room Controller system was designed to meet the energy codes requirements of virtually any space. This application illustrates how conference rooms can use daylight dimming in conjunction with natural light entering the space, while providing Scene Control/Automatic Off and receptacle control to achieve energy savings up to 65% and achieve higher quality lighting. Providing optional control of individual lighting zones and HVAC output will allow for even greater energy savings.

Space AssumptionsSpace

100 square feet or larger

Electrical Load

Greater than 0.5 watts per square feet planned

Daylighting

Contains glazing larger than 24 square feet total requiring daylighting for both primary and secondary sidelit zones

Others

The general lighting is not intended for continuous use (24/7, 365). Egress lighting is not part of the general lighting use.

Building

When larger than 10,000 square feet, Demand Response is required (capable of lowering lighting power by 15%)

Room Controller(Mounted in Ceiling)

OAWC Ceiling Sensor

Wallstation

Daylight Sensor(Mounted on Ceiling)

8www.eaton.com/lightingsystems

• Luminaires turned off when vacant

• 120V receptacles only, one within 6 feet of uncontrolled

• Each 5,000 square feet to have shutoff controls

• Luminaire must provide uniform dimming

• Capable of reducing power by at lease one of five control functions

• When a dimming luminaire is present, a manual dimmer is recommended. Other functional options available

• Must be accessible to occupants to operate the lighting

Reference:

T24-2013 130.1(a)

ASHRAE 90.1-2013 9.4.1.1.a

IECC 2015 C405.2.2.3

Reference:

T24-2013 130.1(b)

ASHRAE 90.1-2013 9.4.1.1.d

IECC 2015 C405.2.2.2

Reference:

T24-2013 130.1(c), 130.5(d)

ASHRAE 90.1-2013 9.4.1.1.h, 9.4.1.1.i, 8.4.2

IECC 2015 C405.2.1

Reference:

T24-2013 130.1(d)

ASHRAE 90.1-2013 9.4.1.1.e, 9.4.1.1.f,

IECC 2015 C405.2.3

SPACE LEVEL (AREA CONTROL)

MULTI-LEVEL LIGHTING

SHUTOFF CONTROL

AUTOMATIC DAYLIGHTING CONTROL

(CHOOSE AT LEAST ONE)

(CHOOSE ONE)

• Eliminate energy waste when natural light present

Exceptions when daylighting control not required: • No skylights

• Glazing <24 square feet

• Daylit zone is less than 120W

OccupancySensor

ReceptacleControl

Manual On/Auto Off

Manually SwitchedON/OFF

9 www.eaton.com/lightingsystems

The Room Controller products can be networked together to expand their out of the box capabilities. Perfect for projects that have multiple rooms that have similar requirements. The Room Controllers can be installed and provide control capabilities on day one without requiring network programming. As the project schedule allows network programming can be completed to provide centralized control and user training.

Network architecture

Room Controller(Mounted in Ceiling)

OAWC Ceiling Sensor Wallstation

Daylight Sensor(Mounted on Ceiling)

Room Controller(Mounted in Ceiling)

OAWC Ceiling Sensor

Wallstation

Daylight Sensor(Mounted on Ceiling)

Room Controller(Mounted in Ceiling)

OAWC Ceiling Sensor Wallstation

Daylight Sensor(Mounted on Ceiling)

Room Controller(Mounted in Ceiling)

OAWC Ceiling Sensor

Wallstation

Daylight Sensor(Mounted on Ceiling)

Space AssumptionsSpace

Multiple spaces each less than 2000 square feet

Electrical Load

Greater than 0.5 watts per square feet planned

Daylighting

Contains glazing larger than 24 square feet total requiring daylighting for both primary and secondary sidelit zones

Others

The general lighting is not intended for continuous use (24/7, 365). Egress lighting is not part of the general lighting use.

Building

When larger than 10,000 square feet, Demand Response is required (capable of lowering lighting power by 15%)

10www.eaton.com/lightingsystems

• Luminaires turned off when vacant

• 120V receptacles only, one within 6 feet of uncontrolled

• Each 5,000 square feet to have shutoff controls. Automatic Time Switch remain on for no more than 2 hours.

Exception when shutoff control not required:• Areas designed to serve 24 hour, 365

day continuous use considered egress lighting

• Luminaire must provide uniform dimming

• Capable of reducing power by at lease one of five control functions

• When a dimming luminaire is present, a manual dimmer is recommended. Other functional options available

• Must be accessible to occupants to operate the lighting

Exceptions when space level control not required: • Areas or sections designed to serve

as egress lighting are not accessible to unauthorized personnel

SPACE LEVEL (AREA CONTROL)

MULTI-LEVEL LIGHTING

SHUTOFF CONTROL

AUTOMATIC DAYLIGHTING CONTROL

(CHOOSE AT LEAST ONE)

• Eliminate energy waste when natural light present

Exceptions when daylighting control not required: • No skylights

• Glazing <24 square feet

• Daylit zone is less than 120W

Manually SwitchedON/OFF

OccupancySensor

ReceptacleControl

Manual On/Auto Off

Remote SignalControl

Automatic(Astronomical Time Switch)

(CHOOSE ONE OR MORE

Reference:

T24-2013 130.1(a)

ASHRAE 90.1-2013 9.4.1.1.a

IECC 2015 C405.2.2.3

Reference:

T24-2013 130.1(b)

ASHRAE 90.1-2013 9.4.1.1.d

IECC 2015 C405.2.2.2

Reference:

T24-2013 130.1(c), 130.5(d)

ASHRAE 90.1-2013 9.4.1.1.h, 9.4.1.1.i, 8.4.2

IECC 2015 C405.2.1

Reference:

T24-2013 130.1(d)

ASHRAE 90.1-2013 9.4.1.1.e, 9.4.1.1.f,

IECC 2015 C405.2.3

11 www.eaton.com/lightingsystems

ROOM CONTROLLER SYSTEM COMPONENT

ROOM CONTROLLER STARTER KIT

ROOM CONTROLLER QUICKITS

ROOM CONTROLLER

PLENUM

UL924 (Energy Back-up Circuit)

LuminaireDimming

RC3-PLRC3D-PLRC3DE-PLRC3DEHC-PL

RC3DE-PL-T24RC3D-PL-T24RC3DE-PL-KITRC3D-PL-KIT

RCQK-RC3DE-CONFRCQK-RC3D-OFFICERCQK-RC3DE-CLASSRCQK-RC3DEHC

ROOM CONTROLLER

PLENUM NETWORK

UL924 (Energy Back-up Circuit)

LuminaireDimming

RC3-PL-NRC3D-PL-NRC3DE-PL-NRC3DEHC-PL-N

SCENE

WALLSTATIONS

ManualDimmer

RC-3TLB-P1-*RC-6TSB-P2-*RC-6TSB-P3-*RC-6TSB-P4-*

RCQK-RC3DE-CONF

ZONE WALLSTATIONS

Manually SwitchedON/OFF

RC-*

RCQK-RC3DE-CONFRCQK-RC3D-OFFICERCQK-RC3DE-CLASSRCQK-RC3DEHC

Room Controller Starter KitIdeal for distributor stocking programs to provide Electrical Contractors with components that are required for rough-in installation. The distributor can then finalize the order with off the shelf accessories based on individual product needs.

Room Controller QuicKitsSpecially built to provide all components that are needed for typical room types. QuicKits include all components for specific room types.

Room Controller System ComponentsWhen a QuicKit or Starter Pack does not meet your requirements, individual components should be specified.

Ordering options

12www.eaton.com/lightingsystems

ROOM CONTROLLER SYSTEM COMPONENT

ROOM CONTROLLER STARTER KIT

ROOM CONTROLLER QUICKITS

DIMMING SLIDER

ManualDimmer

RC-SS1-*

OCCUPANCY SENSOR

OccupancySensor

OAC-*OAWC-*

RCQK-RC3DE-CONFRCQK-RC3D-OFFICERCQK-RC3DE-CLASS

INPUT/OUTPUT

DEVICE

OCC-RJ45

RC3DE-PL-T24RC3D-PL-T24RC3DE-PL-KITRC3D-PL-KIT

RCQK-RC3DE-CONFRCQK-RC3D-OFFICERCQK-RC3DE-CLASSRCQK-RC3DEHC

DAYLIGHT SENSOR

DaylightingControl

DSRC-FMOIR

RCQK-RC3DE-CONFRCQK-RC3D-OFFICERCQK-RC3DE-CLASSRCQK-RC3DEHC

RECEPTACLE

SWITCHPACK

ReceptacleControl

SPRC-R-20-120RC3DE-PL-T24RC3D-PL-T24

RCQK-RC3DE-CONFRCQK-RC3D-OFFICERCQK-RC3DE-CLASS

QUICKCONNECT CABLE

Remote SignalControl

GGRJ45-*

RC3DE-PL-T24RC3D-PL-T24RC3DE-PL-KITRC3D-PL-KIT

RCQK-RC3DE-CONFRCQK-RC3D-OFFICERCQK-RC3DE-CLASSRCQK-RC3DEHC

PERSONAL REMOTE

ManualDimmer Room

Controller

Personal Remote

HHPR-RC

Zone Control

R1R2

R3

SETAUX

Open/Close

Shade or

Solatube

S1S2

S3

S4S5

S6

To save scene press

SET and select Scene

HHPR-RC RCQK-RC3DE-CONF

DAYLIGHT SETTING

REMOTE

Lumen MaintenanceControl

HHPRG-RC

13 www.eaton.com/lightingsystems

LED Switching Luminaires

LED 0-10V Dimming Luminaires

LED 0-10V Dimming Luminaires

UL 924 Emergency Control

Wallstation

Wallstation

Wallstation

Wallstation

Wallstation

SliderWallstation

SliderWallstation

Handheld Daylight

Programmer

Handheld Daylight

Programmer

Occupancy Sensor

Occupancy Sensor

Occupancy Sensor

Daylight Sensor

Daylight Sensor

Receptacle Switchpack

Receptacle Switchpack

Receptacle Switchpack

HVAC Output

HVAC Output

LED Luminaire

LED Luminaire

LED Luminaire

LED Luminaire

LED Luminaire

LED Luminaire

LED Luminaire

LED Luminaire

LED Luminaire

LED Luminaire

Model installation diagrams

RC3-PL with receptacle control

RC3D-PL with receptacle control

RC3DE-PL with receptacle and emergency control

14www.eaton.com/lightingsystems

Space AssumptionsSpace

Less than 250 square feet

Electrical Load

Greater than 0.5 watts per square feet planned

Daylighting

Contains glazing larger than 24 square feet total requiring daylighting for both primary and secondary sidelit zones

Building

When larger than 10,000 square feet, Demand Response is required (capable of lowering lighting power by 15%)

Solutions

Room Controller QuicKit RCQK-RC3DE-OFFICE

OR

Room Controller Components

RC3DE-PL Room Controller

RC-3TLB-OS1-W Wallstation

RC-SS1-W Dimming Slider

DSRC-FMOIR Daylight Sensor

OAWC-DT-120W Wall Corner Occupancy Sensor

OCC-RJ45 Input/ Output Device

SPRC-R-20-120 Receptacle Switchpack

GGRJ45-10-G QuickConnect Cable

GGRJ45-25-G QuickConnect Cable

Luminaire Controls

UL924 (Energy Back-up Circuit)

LuminaireDimming

Sequence of Operations

Occupied Unoccupied

Lights Manual ON or Automatic ON – 50% Lights turn Off after sensor time-out

Receptacle ON Receptacle turns off after sensor time-out + 30 sec

HVAC occupancy closed HVAC occupancy opens

Automatic daylight dimming

Occupant uses wallstations to control lighting

Demand Response dims lighting based on settings

Functional Controls

Manually SwitchedON/OFF

ManualDimmer

DaylightingControl

TuningControl

DemandResponse

OccupancySensor

ReceptacleControl

Application: Office

15 www.eaton.com/lightingsystems

Space AssumptionsSpace

250 square feet or larger

Electrical Load

Greater than 0.5 watts per square feet planned

Daylighting

Contains glazing larger than 24 square feet total requiring daylighting for both primary and secondary sidelit zones

Building

When larger than 10,000 square feet, Demand Response is required (capable of lowering lighting power by 15%)

Solutions

Room Controller QuicKit RCQK-RC3DE-CONF

OR

Room Controller Starter Kit RC3DE-PL-T24

OR

Room Controller Components

RC3DE-PL Room Controller

RC-5TSB-OS2-W Wallstation

DSRC-FMOIR Daylight Sensor

OAC-DT-2000 Ceiling Occupancy Sensor

OCC-RJ45 Input/ Output Device

SPRC-R-20-120 Receptacle Switchpack

GGRJ45-10-G QuickConnect Cable

GGRJ45-25-G QuickConnect Cable

Luminaire Controls

UL924 (Energy Back-up Circuit)

LuminaireDimming

Sequence of Operations

Occupied Unoccupied

Lights Manual ON or Automatic ON – 50% Lights turn Off after sensor time-out

Receptacle ON Receptacle turns off after sensor time-out + 30 sec

HVAC occupancy closed HVAC occupancy opens

Three automatic daylight dimming zones

Occupant uses wallstations to control lighting

Demand Response dims lighting based on settings

Functional Controls

Manually SwitchedON/OFF

ManualDimmer

DaylightingControl

TuningControl

DemandResponse

OccupancySensor

ReceptacleControl

Application: Open office

16www.eaton.com/lightingsystems

Solutions

Room Controller QuicKit RCQK-RC3DE-CONF

OR

Room Controller Components

RC3DE-PL Room Controller

RC-6TSB-P3-W Scene Wallstation

RC-6TSB-ZAD-W Wallstation

DSRC-FMOIR Daylight Sensor

OAWC-DT-120W Wall Corner Occupancy Sensor

OCC-RJ45 Input/ Output Device

SPRC-R-20-120 Receptacle Switchpack

GGRJ45-10-G QuickConnect Cable

GGRJ45-25-G QuickConnect Cable

Luminaire Controls

UL924 (Energy Back-up Circuit)

LuminaireDimming

Sequence of Operations

Occupied Unoccupied

Lights Manual ON or Automatic ON – 50% Lights turn Off after sensor time-out

Receptacle ON Receptacle turns off after sensor time-out + 30 sec

HVAC occupancy closed HVAC occupancy opens

Automatic daylight dimming

Occupant uses wallstations to control lighting

Demand Response dims lighting based on settings

Programmable Scene Wallstations

Functional Controls

Manually SwitchedON/OFF

ManualDimmer

DaylightingControl

TuningControl

DemandResponse

OccupancySensor

ReceptacleControl

Application: Conference roomSpace AssumptionsSpace

100 square feet or larger

Electrical Load

Greater than 0.5 watts per square feet planned

Daylighting

Contains glazing larger than 24 square feet total requiring daylighting for both primary and secondary sidelit zones

Others

The general lighting is not intended for continuous use (24/7, 365). Egress lighting is not part of the general lighting use.

Building

When larger than 10,000 square feet, Demand Response is required (capable of lowering lighting power by 15%)

17 www.eaton.com/lightingsystems

Luminaire Controls

UL924 (Energy Back-up Circuit)

LuminaireDimming

Sequence of Operations

Occupied Unoccupied

Lights Automatic ON Lights turn Off or dim after sensor time-out

Occupant uses wallstations to control lighting Timeclock turns lights off

Demand Response dims lighting based on settings

Programmable Scene Wallstations

Functional Controls

ManualDimmer

TuningControl

DemandResponse

OccupancySensor

Application: Corridor, hall or stairwellSpace AssumptionsSpace

Accessible areas

Electrical Load

Greater than 0.5 watts per square feet planned

Daylighting

Contains glazing larger than 24 square feet total requiring daylighting for both primary and secondary sidelit zones

Building

When larger than 10,000 square feet, Demand Response is required (capable of lowering lighting power by 15%)

Solutions

Room Controller QuicKit RC3DE-PL-KIT

OR

Room Controller Components

RC3DE-PL Room Controller

RC-6TSB-P3-W Scene Wallstation

OAWC-DT-120W Wall Corner Occupancy Sensor

OCC-RJ45 Input/ Output Device

GGRJ45-10-G QuickConnect Cable

GGRJ45-25-G QuickConnect Cable

18www.eaton.com/lightingsystems

Solutions

Room Controller QuicKit RCQK-RC3DE-CLASS

OR

Room Controller Starter Kit RC3DE-PL-T24

OR

Room Controller Components

RC3DE-PL Room Controller

RC-2TLB-ES1-W Wallstation

RC-6TSB-P3-W Scene Wallstation

DSRC-FMOIR Daylight Sensor

OAWC-DT-120W Wall Corner Occupancy Sensor

OCC-RJ45 Input/ Output Device

SPRC-R-20-120 Receptacle Switchpack

GGRJ45-10-G QuickConnect Cable

GGRJ45-25-G QuickConnect Cable

Luminaire Controls

UL924 (Energy Back-up Circuit)

LuminaireDimming

Sequence of Operations

Occupied Unoccupied

Lights Manual ON or Automatic ON – 50% Lights turn Off after sensor time-out

Receptacle ON Receptacle turns off after sensor time-out + 30 sec

HVAC occupancy closed HVAC occupancy opens

Three automatic daylight dimming zones

Occupant uses wallstations to control lighting

Demand Response dims lighting based on settings

Programmable Scene Wallstations

Functional Controls

Manually SwitchedON/OFF

ManualDimmer

DaylightingControl

TuningControl

DemandResponse

OccupancySensor

ReceptacleControl

Application: Classroom – Suspended fixtures and three daylight zones

Space AssumptionsSpace

Less than 2000 square feet

Electrical Load

Greater than 0.7 watts per square feet planned

Daylighting

Contains glazing larger than 24 square feet total requiring daylighting for both primary and secondary sidelit zones

Building

When larger than 10,000 square feet, Demand Response is required (capable of lowering lighting power by 15%)

19 www.eaton.com/lightingsystems

Solutions

Room Controller QuicKit RCQK-RC3DE-CLASS

OR

Room Controller Starter Kit RC3DE-PL-T24

OR

Room Controller Components

RC3DE-PL Room Controller

RC-2TLB-ES1-W Wallstation

RC-6TSB-P3-W Scene Wallstation

DSRC-FMOIR Daylight Sensor

OAWC-DT-120W Wall Corner Occupancy Sensor

OCC-RJ45 Input/ Output Device

SPRC-R-20-120 Receptacle Switchpack

GGRJ45-10-G QuickConnect Cable

GGRJ45-25-G QuickConnect Cable

Luminaire Controls

UL924 (Energy Back-up Circuit)

LuminaireDimming

Sequence of Operations

Occupied Unoccupied

Lights Manual ON or Automatic ON – 50% Lights turn Off after sensor time-out

Front and back switching with mixed daylighting Receptacle turns off after sensor time-out + 30 sec

Receptacle ON HVAC occupancy opens

HVAC occupancy closed

Three automatic daylight dimming zones

Occupant uses wallstations to control lighting

Demand Response dims lighting based on settings

Functional Controls

Manually SwitchedON/OFF

ManualDimmer

DaylightingControl

TuningControl

DemandResponse

OccupancySensor

ReceptacleControl

Application: Classroom - Recessed fixtures and three daylight zones

Space AssumptionsSpace

Less than 2000 square feet

Electrical Load

Greater than 0.7 watts per square feet planned

Daylighting

Contains glazing larger than 24 square feet total requiring daylighting for both primary and secondary sidelit zones

Building

When larger than 10,000 square feet, Demand Response is required (capable of lowering lighting power by 15%)

21 www.eaton.com/lightingsystems

System componentsRoom Controller

This is your central relay and dimmer control as well as coordinates all the actions from wallstations, daylight sensor and occupancy sensor.

Wallstation

The intuitive user interface provides for manual override and is pre-engraved buttons describing their respective functionality.

Occupancy sensor

Any Greengate low voltage occupancy sensors can be used with the Room Controller, so select one to meet your applications needs.

Daylight sensor

Dimmable daylighting requirements have increased with the latest version of ASHRAE 90.1. The Room Controller daylight sensor allows up to three dimming zones to be controlled from a single sensor.

Plug load control

Saving additional energy by shutting off plug loads is now part of ASHRAE 90.1, and is easily achieved with the Receptacle Switchpack and the Room Controller.

CATALOG NUMBER DESCRIPTION COLOR

Room Controller System

RC3-PL Room Controller, three relay, plenum, 120/277 VAC, 60 Hz, 20A B

RC3D-PL Room Controller, three relay, three dimmer, plenum, 120/277 VAC, 60 Hz, 20A B

RC3DE-PL Room Controller, three relay, three dimmer, one emergency output, plenum,120/277 VAC, 60 Hz, 20A B

RC3DEHC-PL Healthcare Room Controller for patient rooms, three relay, three dimmer, one emergency output, plenum, 120/277 VAC, 60 Hz, 20A B

RC3-PL-N Room Controller, network, three relay, plenum, 120/277 VAC, 60 Hz, 20A B

RC3D-PL-N Room Controller, network, three relay, three dimmer, plenum, 120/277 VAC, 60 Hz, 20A B

RC3DE-PL-N Room Controller, network, three relay, three dimmer, one emergency output, plenum,120/277 VAC, 60 Hz, 20A B

RC3DEHC-PL-N Healthcare Room Controller for patient rooms, network, three relay, three dimmer, one emergency output, plenum, 120/277 VAC, 60 Hz, 20A B

Room Controller Wallstations

RC-2TLB-ES1-* Room Controller Wallstation, 2 large buttons (Entry, All Off) W, V, G, B

RC-6TSB-TS1-* Room Controller Wallstation, 6 small buttons (General, Whiteboard, Quiet Time, A/V Mode, Raise, Lower) W, V, G, B

RC-6TSB-TS2-* Room Controller Wallstation, 6 small buttons (General, Whiteboard, Quiet Time, Raise, Lower, All Off) W, V, G, B

RC-5TSB-TS3-* Room Controller Wallstation, 5 small buttons (General, Whiteboard, Quiet Time, A/V Mode, All Off) W, V, G, B

RC-6TSB-TS4-* Room Controller Wallstation, 6 small buttons (General, Whiteboard, A/V Mode, Raise, Lower, All Off) W, V, G, B

RC-4TSB-TS5-* Room Controller Wallstation, 4 small buttons (Entry, General, Whiteboard, All Off) W, V, G, B

RC-6TSB-TS6-* Room Controller Wallstation, 6 small buttons (Entry, General, Whiteboard, Raise, Lower, All Off) W, V, G, B

RC-6TSB-TS7-* Room Controller Wallstation, 6 small buttons (Row 1, Row 2, Row 3, Raise, Lower, All Off) W, V, G, B

RC-6TSB-TS8-* Room Controller Wallstation, 6 small buttons (Uplights, Downlights, Accent, Raise, Lower, All Off) W, V, G, B

22www.eaton.com/lightingsystems

CATALOG NUMBER DESCRIPTION COLOR

Room Controller Wallstations - Continued

RC-6TSB-CR1-* Room Controller Wallstation, 6 small buttons (General, Meeting, Whiteboard, Presentation, Raise, Lower) W, V, G, B

RC-5TSB-CR2-* Room Controller Wallstation, 5 small buttons (General, Meeting, Whiteboard, Presentation, All Off) W, V, G, B

RC-4TSB-HC1-* Room Controller Wallstation, 4 small buttons (General, Exam, Reading, All Off) W, V, G, B

RC-6TSB-HC2-* Room Controller Wallstation, 6 small buttons (General, Exam, Reading, Raise, Lower, All Off) W, V, G, B

RC-3TLB-OS1-* Room Controller Wallstation, 3 large buttons (Half Lights, Full Lights, All Off) W, V, G, B

RC-5TSB-OS2-* Room Controller Wallstation, 5 small buttons (Half Lights, Full Lights, Raise, Lower, All Off) W, V, G, B

RC-6TSB-OS3-* Room Controller Wallstation, 6 small buttons (Half Lights, Full Lights, Undercabinet, Raise, Lower, All Off) W, V, G, B

RC-2TLB-OS4-* Room Controller Wallstation, 2 large buttons (All On, All Off) W, V, G, B

RC-6TSB-ZAD-* Room Controller Wallstation, 6 small buttons (Zone 1 UP, Sone 1 DN, Zone 2 UP, Zone 2 DN, Zone 3 UP, Zone 3 DN) W, V, G, B

RC-3TLB-Z1D-* Room Controller Wallstation, 3 large buttons (Zone 1 On/Off, Zone 1 UP, Zone 1 DN) W, V, G, B

RC-3TLB-Z2D-* Room Controller Wallstation, 3 large buttons (Zone 2 On/Off, Zone 2 UP, Zone 2 DN) W, V, G, B

RC-3TLB-Z3D-* Room Controller Wallstation, 3 large buttons (Zone 3 On/Off, Zone 3 UP, Zone 3 DN) W, V, G, B

Room Controller Slider Stations

RC-SS1-* Room Controller Slider Station W, V, G, B

Room Controller Daylight Sensors

DSRC-FMOIR Room Controller Open Loop Daylight Sensor, fixture mount, RJ45 connection W

DSCM-MT Room Controller Open Loop Daylight Sensor mounting bracket W

Handheld Remotes

HHPRG-RC Room Controller Open Loop Daylight Sensor handheld zone remote programmer B

HHPR-RC Room Controller Personal Remote B

Room Controller Switchpacks

SPRC-R-20-120 Room Controller receptacle rated switchpack, 120/2774 VAC, 50/60 Hz, 20A W

SP-R-20-120 Occupancy sensor receptacle rated switchpack w/ Cat5 and flying leads, 120/277 VAC, 50/60 Hz, 20A W

Room Controller Input/Output Devices

OCC-RJ45 Room Controller BMS output W

GGRC-COUPLER Room Controller RJ45 coupler W

GGRC-SPLITTER Room Controller RJ45 splitter W

GGRJ45-006-G Room Controller RJ45 cable, 6 inches Gr

GGRJ45-03-G Room Controller RJ45 cable, 3 feet Gr

GGRJ45-10-G Room Controller RJ45 cable, 10 feet Gr

GGRJ45-25-G Room Controller RJ45 cable, 25 feet Gr

GGRJ45-50-G Room Controller RJ45 cable, 50 feet Gr

GGRJ45-100-G Room Controller RJ45 cable, 100 feet Gr

GGRJ45-10P-G Room Controller RJ45 cable, 10 feet, plenum rated Gr

GGRJ45-25P-G Room Controller RJ45 cable, 25 feet, plenum rated Gr

GGRJ45-50P-G Room Controller RJ45 cable, 50 feet, plenum rated Gr

GGRJ45-100P-G Room Controller RJ45 cable, 100 feet, plenum rated Gr

23 www.eaton.com/lightingsystems

QuicKits and starter kits

Starter KitsIdeal stocking product for the Electrical Distributor.

QuicKitsEasy to order, designed and packaged for immediate in room installation and provide a complete all-in-one package solution.

CATALOG NUMBER INCLUDED COMPONENTS

RC3DE-PL-T24 RC3DE-PL (QTY1)

SPRC-R-20-120 (QTY1)

OCC-RJ45 (QTY1)

GGRJ45-10P-G (QTY1)

GGRJ45-25P-G (QTY3)

RC3D-PL-T24 RC3D-PL (QTY1)

SPRC-R-20-120 (QTY1)

OCC-RJ45 (QTY1)

GGRJ45-10P-G (QTY1)

GGRJ45-25P-G (QTY3)

RC3DE-PL-KIT RC3DE-PL

OCC-RJ45

GGRJ45-10P-G (QTY1)

GGRJ45-25P-G (QTY2)

RC3D-PL-KIT RC3D-PL (QTY1)

OCC-RJ45 (QTY1)

GGRJ45-10P-G (QTY1)

GGRJ45-25P-G (QTY2)

CATALOG NUMBER INCLUDED COMPONENTS

RCQK-RC3DE-CONF RC3DE-PL (QTY1)

SPRC-R-20-120 (QTY1)

DSRC-FMOIR (QTY1)

OAWC-DT-120W (QTY1)

OCC-RJ45 (QTY1)

GGRJ45-10P-G (QTY1)

GGRJ45-006-G (QTY1)

GGRJ45-25P-G (QTY3)

RC-6TSB-P2 (QTY1)

RC-6TSB-ZAD (QTY1)

HHPR-RC (QTY1)

RCQK-RC3D-OFFICE RC3D-PL (QTY1)

SPRC-R-20-120 (QTY1)

OAC-DT-2000-R (QTY1)

DSRC-FMOIR (QTY1)

OCC-RJ45 (QTY1)

GGRJ45-10P-G (QTY1)

GGRJ45-25P-G (QTY3)

RC-5TSB-OS2 (QTY1)

RCQK-RC3DE-CLASS RC3DE-PL (QTY1)

SPRC-R-20-120 (QTY1)

DSRC-FMOIR (QTY1)

OAC-DT-2000 (QTY1)

OCC-RJ45 (QTY1)

GGRJ45-10P-G (QTY1)

GGRJ45-25P-G (QTY4

RC-4TSB-TS5 (QTY1)

RC-6TSB-TS4 (QTY1)

RCQK-RC3DEHC RC3DEHC-PL (QTY1)

OCC-RJ45 (QTY1)

DSRC-FMOIR (QTY1)

GGRJ45-25P-G (QTY4)

GG37P (QTY1)

GPCS-3Z-DIM (QTY1)

RC-6TSB-HC2 (QTY1)

RC-4TSB-HC1 (QTY1)

24www.eaton.com/lightingsystems

Typical wiring diagrams

Wallstation

Occupancy Sensor

Daylight Sensor

Wallstation

Occupancy Sensor

Daylight Sensor

Receptacle Rated

Switchpack

Figure 1: Small Office with Daylighting

Figure 2: Office with Receptacle and Emergency Control

25 www.eaton.com/lightingsystems

Wallstation

Occupancy Sensor

Daylight Sensor

Wallstation

Occupancy Sensor

Daylight Sensor

Receptacle Rated

Switchpack

Figure 3: Office with HVAC output

Figure 4: Conference room with receptacle and Emergency Control, daylighting and programmable scene wallstations

Typical wiring diagrams

26www.eaton.com/lightingsystems

WallstationEntry Station

Occupancy Sensor

Daylight Sensor

Receptacle Rated

Switchpack

WallstationEntry Station

Occupancy Sensor

Daylight Sensor

Figure 5: Classroom with emergency and receptacle control

Figure 6: Classroom with daylight dimming

Typical wiring diagrams

27 www.eaton.com/lightingsystems

Typical wiring diagramsFigure 7: Demand Response Connections

Figure 8: Alternative voltage connection

28www.eaton.com/lightingsystems

Typical wiring diagramsFigure 9: Receptacle wiring

29 www.eaton.com/lightingsystems

Typical wiring diagramsFigure 10: Wallstation Sharing

30www.eaton.com/lightingsystems

Typical wiring diagramsFigure 11: Network Wiring

1

2

3

4

5

6

Inte

grat

ion

Con

trol

sA

djus

tabl

e Sk

ylig

hts

Low

End

Hig

h En

d

Ener

gyO

ptio

ns

Stat

usR

eset

0-10

V G

ain

Adj

ustm

ent

Dimmer 3 Dimmer 2 Dimmer 1

+ - -+ + -0-10V Dimming

0-10V Dimming Outputs-+

Dimmer 3 Dimmer 2 Dimmer 1

-++ -

Blu

e - E

M L

ine

InB

lue

- EM

Loa

ds O

ut

CA

UTI

ON

: Bon

ding

bet

wee

n co

ndui

t con

nect

ions

is n

ot a

utom

atic

and

mus

t be

prov

ided

as

part

of t

he in

stal

latio

n.

Bla

ck -

Line

InW

hite

/Bla

ck -

120V

NW

hite

/Ora

nge

- 277

V N

Blu

e - L

oad

InYe

llow

- Lo

ad 1

Out

Red

- Lo

ad 2

Out

Purp

le -

Load

3 O

ut

Energy Options DIP Switch

Demand Response Occupancy Not Used

1 2 3 4Default 10%

20%30%40%

OccVac (default)

TimeClock

AlertMode

DemandResponse

A/VMode

+- In

tegr

atio

n C

ontr

ols

+-+-+-

Green

Black

Red

White

Adj

usta

ble

Skyl

ight

s

Sensors

ReceptacleBMS/Out

Switchpack

Qui

ckC

onne

ct C

able

s

Sensors

SliderStation

Wallstations

Half Lights

Full Lights

All Off

Model: O

CC

-RJ45

Occupancy Sensor C

oupler

Brown

Black

Red

Blue

120V PowerReceptacle Required

EIM

ControlKeeperTouchScreen

The Ethernet Interface Module (EIM)and Wireless Ethernet Interface Module (WEIM) may be connected toany Lighting Control Panel in the systemusing the RS-232 cable included.(Part #:52-018703-00)

QuickConnect Coupler(GGRC-COUPLER)

Daylight sensor(DSRC-FMOIR)

1

2

3

4

5

6

Inte

grat

ion

Con

trol

sA

djus

tabl

e Sk

ylig

hts

Low

End

Hig

h En

d

Ener

gyO

ptio

ns

Stat

usR

eset

0-10

V G

ain

Adj

ustm

ent

Dimmer 3 Dimmer 2 Dimmer 1

+ - -+ + -0-10V Dimming

0-10V Dimming Outputs-+

Dimmer 3 Dimmer 2 Dimmer 1

-++ -

Blu

e - E

M L

ine

InB

lue

- EM

Loa

ds O

ut

CA

UTI

ON

: Bon

ding

bet

wee

n co

ndui

t con

nect

ions

is n

ot a

utom

atic

and

mus

t be

prov

ided

as

part

of t

he in

stal

latio

n.

Bla

ck -

Line

InW

hite

/Bla

ck -

120V

NW

hite

/Ora

nge

- 277

V N

Blu

e - L

oad

InYe

llow

- Lo

ad 1

Out

Red

- Lo

ad 2

Out

Purp

le -

Load

3 O

ut

Energy Options DIP Switch

Demand Response Occupancy Not Used

1 2 3 4Default 10%

20%30%40%

OccVac (default)

TimeClock

AlertMode

DemandResponse

A/VMode

+- In

tegr

atio

n C

ontr

ols

+-+-+-

Green

Black

Red

White

Adj

usta

ble

Skyl

ight

s

Sensors

ReceptacleBMS/Out

Switchpack

Qui

ckC

onne

ct C

able

s

Sensors

SliderStation

Wallstations

SPRC-R-20-12020A Receptacle Control

Half Lights

Full Lights

Wallstation

All Off

Slider Station

Occupancy/Vacancy Sensor

(OAWC-DT-120W)

OCC-RJ45(Occupancy Coupler)

QuickConnect Coupler(GGRC-COUPLER)

Daylight sensor(DSRC-FMOIR)SPRC-R-20-120

20A Receptacle Control

Wallstation Slider Station

Occupancy/Vacancy Sensor

(OAWC-DT-120W)

OCC-RJ45(Occupancy Coupler)

QuickConnect Coupler(GGRC-COUPLER)

Daylight sensor(DSRC-FMOIR)SPRC-R-20-120

20A Receptacle Control

Wallstation Slider Station

Occupancy/Vacancy Sensor

(OAWC-DT-120W)

OCC-RJ45(Occupancy Coupler)

Model: O

CC

-RJ45

Occupancy Sensor C

oupler

Brown

Black

Red

Blue

1

2

3

4

5

6

Inte

grat

ion

Con

trol

sA

djus

tabl

e Sk

ylig

hts

Low

End

Hig

h En

d

Ener

gyO

ptio

ns

Stat

usR

eset

0-10

V G

ain

Adj

ustm

ent

Dimmer 3 Dimmer 2 Dimmer 1

+ - -+ + -0-10V Dimming

0-10V Dimming Outputs-+

Dimmer 3 Dimmer 2 Dimmer 1

-++ -

Blu

e - E

M L

ine

InB

lue

- EM

Loa

ds O

ut

CA

UTI

ON

: Bon

ding

bet

wee

n co

ndui

t con

nect

ions

is n

ot a

utom

atic

and

mus

t be

prov

ided

as

part

of t

he in

stal

latio

n.

Bla

ck -

Line

InW

hite

/Bla

ck -

120V

NW

hite

/Ora

nge

- 277

V N

Blu

e - L

oad

InYe

llow

- Lo

ad 1

Out

Red

- Lo

ad 2

Out

Purp

le -

Load

3 O

ut

Energy Options DIP Switch

Demand Response Occupancy Not Used

1 2 3 4Default 10%

20%30%40%

OccVac (default)

TimeClock

AlertMode

DemandResponse

A/VMode

+- Inte

grat

ion

Con

trol

s

+-+-+-

Green

Black

Red

White

Adj

usta

ble

Skyl

ight

s

Sensors

ReceptacleBMS/Out

Switchpack

Qui

ckC

onne

ct C

able

s

Sensors

SliderStation

Wallstations

Half Lights

Full Lights

All Off

Model: O

CC

-RJ45

Occupancy Sensor C

oupler

Brown

Black

Red

Blue

Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com

EatonLighting systems203 Cooper CirclePeachtree City, GA 30269www.eaton.com/lightingsystems

© 2015 EatonAll Rights ReservedPublication No. BR503006ENDecember 3, 2015

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

Eaton’s Lighting systems – Controls products203 Cooper CirclePeachtree City, GA 30269P: 800-553-3879F: 800-954-7016www.eaton.com/lightingsystems

International HeadquartersUsk House, LakesideLlantarnam ParkCwmbran, NP44 3HD UKP: +44 1923 495495F: +44 1633 867880

Canada Sales5925 McLaughlin RoadMississauga, Ontario L5R 1B8P: 905-501-3000F: 905-501-3172

Our Controls Product BrandsGreengateiLuminZero 88Fifth Light TechnologyiLight (International Only)

Our Lighting Product BrandsHaloHalo CommercialPortfolioIRiSRSAMetaluxCoreliteNeo-RayFail-SafeMWSAmetrixShaperioLumarkMcGraw-EdisonInvueLumièreStreetworksAtLiteSure-Lites