GB B1092 - Choose NORD constant speed reducers, gear ... · PDF fileFor vertical installation...

52
Intelligent Drivesystems, Worldwide Services B1092 Operating and Assembly Instructions for 1 MA-7 Three-phase Motors for operation with Frequency Inverters BG 63 - 160 GB

Transcript of GB B1092 - Choose NORD constant speed reducers, gear ... · PDF fileFor vertical installation...

Intelligent Drivesystems, Worldwide Services

B1092 Operating and Assembly Instructions for 1 MA-7 Three-phase Motors for operation with Frequency Inverters BG 63 - 160

GB

-2- B1092-GB www.nord.com

Contents

1. General Information ................................................................................................................3

2. Description ..............................................................................................................................3

2.1 Field of application ....................................................................................................................3

2.2 Cooling .....................................................................................................................................3

3. Information on the correct handling of electric motors .....................................................3

3.1 Transport and storage...............................................................................................................3

3.2 Installation .................................................................................................................................4

3.3 Terminal box .............................................................................................................................4

3.4 Balancing, driving elements ......................................................................................................4

3.5 Elekctrical connection ...............................................................................................................4

3.6 Checking the insulation resistance ...........................................................................................5

3.7 ICommissioning.........................................................................................................................5

4. Maintenance ............................................................................................................................6

5. Motors with increased ignition protection, type “e” Ex e 1MA ..........................................8

5.1 Additional information for operation with a frequency inverter..................................................9

6. Drawing and list of replacement parts................................................................................11

6.1 Drawing and list of replacement parts.....................................................................................11

6.2 Tightening torques ..................................................................................................................15

6.3 Cross sections which may be connected................................................................................16

6.4 Changing the bearings ............................................................................................................16

7. Data Sheets............................................................................................................................17

7.1 BG 63 M ..................................................................................................................................17

7.2 BG 71 M ..................................................................................................................................20

7.3 BG 80 M ..................................................................................................................................23

7.4 BG 90 L ...................................................................................................................................26

7.5 BG 100 L .................................................................................................................................29

7.6 BG 100 L (increased performance).........................................................................................32

7.7 BG 112M .................................................................................................................................35

7.8 BG 132 M ................................................................................................................................38

7.9 BG 160 M ................................................................................................................................41

7.10 BG 160 L .................................................................................................................................44

8. Type Plates ............................................................................................................................47

9. Declaration of Conformity ....................................................................................................48

10. Addresses ..............................................................................................................................49

Safety and information symbols

Please always observe the following safety and information symbols!

Danger Danger of death or injury to persons

Attention! Damage to the machine possible

Danger Important information regarding explosion protection

Note!

www.nord.com B1092-GB -3-

1. General information

2. Description

1. General information

The applicable national, local and plant-specific regulations and requirements must be observed.

Technical details may vary for special designs and constructions. In case of doubt it is urgently recommended that the manufacturer is contacted, giving details of the type and serial number (No. …. see rating plate), or have the maintenance work carried out by a service centre.

2.1 Field of Application

Intended use of the motors: The motors are constructed in protection class IP55 (protection class: see rating plate). They may be installed in dusty or damp environments. For use outdoors an additional covering is recommended to avoid the tong-term influence of direct intense sunlight, rain, snow, ice or dust. If necessary, consultation/technical coordination is advisable. Ambient temperature: ......... -20°C to +40°C

Installation altitude: ............. ≤ 1000 m In case of differing ambient conditions, these must be indicated on the rating plate. The details on the rating plate then apply.

2.2 Cooling

1MA motors are self-cooling (with fan).

3. Information on the correct handling of electric motors

3.1 Transport and storage

When transporting the motor, all available lifting lugs must be used. When transporting sets of machinery (e.g. gearbox, fan, pumps etc.) only use the attached lifting lugs. Sets of machinery must not be lifted by hanging on the motor lifting lugs. With long periods of storage the period of use of the bearing grease is reduced. For storage of longer than 12 months the condition of the grease must be checked. If the check reveals contamination of the grease (ingress of condensation causes a change in consistency of the grease) the grease must be replaced. The roller bearings should be replaced if the time from delivery to commissioning of the motor exceeds 4 years. The probable life-span of the bearing system reduces with increasing storage time. Machined surfaces (flange surfaces, shaft ends, etc.) should be protected with corrosion protection agents. If necessary, the insulating resistance of the windings must be checked, see Section 3.6.

All work must be carried out only when the system is in an electrically voltage-free state.

-4- B1092-GB www.nord.com

3. Notes

3.2 Installation

For vertical configuration, all available lifting lugs and if necessary lifting straps (DIN EN 1492-1:2000) and/or tie-down straps (DIN EN 12195-2:2001) must be used to stabilise the position. Attachments must not be used as lifting aids. After installation, screwed-on lifting lugs must be tightened or removed. For vertical installation with the shaft end pointing downwards, a protective cover for the fan cover is recommended, to prevent the entry of foreign bodies. On the other hand, in the case of shaft ends pointing upwards, the ingress of liquids along the shaft must be prevented. Smooth running: Precise alignment of the clutch and a well-balanced drive element (clutch, pulleys, fan …) are prerequisites for smooth vibration-free running. Complete balancing of the motor and the drive elements may be necessary.

3.3 Terminal box

Tightening torques for the screws of the terminal box: See Fig. 4.2.

3.4 Balancing, drive elements

The fitting and removal of drive elements (clutch, pulley, gear wheel,…) must be performed with suitable equipment (see Fig.7). As standard, the rotor is balanced with half parallel key. When fitting the drive element, pay attention to the type of balancing! The balancing condition is stated on the end face of the shaft or the type plate (H = half, F = full parallel key balancing, N = balancing without parallel key). The drive elements must be balanced according to ISO 1940:2003.

For balancing with half parallel key, the protruding visible portion of the parallel key Tp must be machined off (see Fig. 8).

The generally necessary measures for protection against touching the drive elements must be observed.

3.5 Electrical connection

All work must only be carried out by qualified technicians on stationary low-voltage machines which have been switched off and secured against switching on again. This also applies to the auxiliary power circuits. The terminal box must be sealed against dust and water. The mains voltage and frequency must conform to the data on the rating plate. A voltage deviation of ± 5% and/or a frequency deviation of ± 2% are permissible. The connection and configuration of the jumpers must be performed according to the circuit diagram in the terminal box. Connect the bonding conductor to this terminal

. For connection terminals with terminal bridges (e.g. according to DIN 46282) the conductors must be arranged so that approximately the same terminal heights result on both sides of the bar. This type of connection therefore requires that individual conductors are bent to a U-shape or a fork terminal must be connected (see Fig. 5) This also applies to the bonding connector and the external green/yellow earthing conductor.

www.nord.com B1092-GB -5-

3. Notes For tightening torques of screw connections of the electrical connections and terminal board connections (except for the terminal bar) see Fig. 4.

3.6 Checking the insulation resistance

Prior to the initial commissioning of the motor after a long period of storage or standstill (approx. 6 months) the insulation resistance of the windings must be checked. During and immediately after the measurements, the terminals have voltages which can be dangerous, and must not be touched. Insulation resistance The minimum insulation resistance of new, cleaned or repaired windings against earth

is 10 MΩ. Initially, the critical insulation resistance Rkrit is calculated. The calculation is made by

multiplying the measured voltage UN, e.g. 0.69 kV AC, with the constant factor (0.5 MΩ /kV): Rkrit = 0.69 kV x 0.5 MΩ /kV =0.345 MΩ Measurement: The minimum insulation resistance of the winding against earth is measured with 500 V DC. The temperature of the windings should be 25°C ± 15°C. The critical insulation resistance must be measured with the windings at operating temperature using 500 V DC. Testing: If for new or cleaned windings or repaired motors, which have been stored or not used for long periods, the minimum insulation resistance of the winding against earth is less than 10 MΩ, this may be caused by moisture. The windings must then be dried. After long periods of operation the minimum insulation resistance may fall to the critical insulation resistance. As long as the measured value does not fall below the calculated value for the critical insulation resistance, operation of the motor may continue. If this value is fallen below, the motor must be switched off immediately. The cause of this must be established and if necessary the windings or parts of the windings must be repaired, cleaned or dried.

3.7 Commissioning

NOTE: Electromagnetic compatibility Production of interference: Great differences of torque (e.g. when driving a piston compressor) induce a non-sine wave motor current, whose harmonics can cause an impermissible effect on the mains and therefore impermissible production of interference. With supply by frequency inverters, various strengths of interference are produced according to the design of the frequency inverter (type, interference suppression, manufacturer). The EMC information of the inverter manufacturer must be observed. If a shielded motor supply cable is recommended, the shielding is most effective if a large area is electrically connected to the metal terminal box of the motor (with metal screw connectors). With motors with integrated sensors (e.g. thermistors) interference voltages due to the inverter may be produced in the sensor cables. Interference immunity: For motors with integrated sensors (e.g. thermistors) the operator must ensure adequate immunity to interference by the selection of a suitable sensor cable (possibly with screening, with connection as for the motor supply cable) and evaluation device. When operating motors with inverters at higher speeds than the nominal speed, the mechanical limiting speed (Safe operating speed IEC 60034-1) must be observed (max. 3000 1/min).

-6- B1092-GB www.nord.com

4. Maintenance

Safety measures Before starting any work on the motor or the device, but especially before opening the covers of active components, the motor must be isolated according to regulations. In addition to the main power circuits, any additional or auxiliary circuits must be taken into account.

The usual "5 Safety Rules" e.g. according to EN 50110-1 (DIN VDE 0105) are:

• Isolate, • Secure against switching on, • Check for no voltage, • Earth and short circuit, • Cover or fence off neighbouring live components.

These measures may only be removed when the maintenance work is complete and the motor has been completely assembled. NOTE: If the motors are designed with closed condensation outlets, these must be opened occasionally in order to allow any accumulated condensation to drain off. Condensation outlets must always be located at the lowest point of the motor. Changing bearings, grease packing Bearing replacement period [h] under normal operating conditions, with horizontal installation of the motor, cooling medium temperature or motor speed:

40°C

up to 1800 min-1 approx. 40000 h

up to 3000 min-1 approx. 20000 h

NOTE: The permissible axial and transverse forces must not be exceeded. Independent of the hours of operation of a motor which is in use, the roller bearing should be replaced approximately every 3 years due to the reduction of lubrication. Under special operating conditions, e.g. vertical motor installation, heavy loads due to vibration and shock, or operation with frequent reversing, the operating hours stated above are significantly reduced. The motors have groove ball bearings with cover plates (2ZC3 design). The material of the plates should be temperature resistant from -30°C to +150°C, e.g. polyacrylic rubber (ACM). Grease types for standard machines: UNIREX N3 (ESSO); Substitute greases must comply with DIN 51825-K3N:2004. Special greases are indicated on the rating plate or on an additional plate. Dismantle the motor to the necessary extent. Remove the roller bearing using suitable equipment (see Fig. 6). Clean any contamination from the bearing seats. Uniformly heat the roller bearings to approx. 80-100°C and fit. Hard blows (e.g. with a hammer) must be avoided. Any warn sealing elements (e.g. shaft seals) must also be renewed. If shaft sealing rings without springs are installed, the replacement component must also be installed without springs. Centring edge seal When assembling the motor, the bright fitting surfaces between the motor housing and the bearing covers must be sealed with a suitable non-hardening sealing compound, e.g. Fluid-D. Tightening torques for the screws on the bearing covers: see Fig. 4.2. Regreasing device For motors with regreasing devices, the details on the lubrication plate or the rating plate must be observed. Regreasing should be performed with the motor running.

www.nord.com B1092-GB -7-

4. Maintenance General overhaul A general overhaul of the motor must be carried out every 5 years. For this the motor must be dismantled. The following work must be carried out:

• All components of the motor must be cleaned • All components of the motor must be examined for damage • All damaged components must be replaced • All roller bearings must be replaced • All seals and shaft sealing rings must be replaced • Measure the insulation resistance • Check the stationary voltage according to EN 60034-1

The general overhaul must be carried out by qualified personnel in a specialist workshop with appropriate equipment. We strongly recommend that the general overhaul is carried out by NORD-Service.

-8- B1092-GB www.nord.com

5. Motors with increased ignition protection, type "e" Ex e

5. Motors with increased ignition protection, type "e" Ex e 1MA

Identification: CE 0102 II G Ex e lI T3 Attention Repairs must be carried out in or by authorised workshops. Repairs must be documented on the motor (e.g. additional plate).

The increased hazard in areas endangered by explosions or fire damp requires particularly careful observation of the general safety and start-up information. Replacement parts - Only original replacement parts (see replacement parts list) may be used: this particularly applies to seals and connection components. Exceptions are standard equivalent commercially available components (e.g. roller bearings).

Explosion-protected electrical machines comply with standards: EN 60034-1:2004 and all relevant parts, as well as EN 60079-0:2004, EN60079-7:2003. They may only be used in explosion hazard areas according to the conditions stipulated by the responsible supervisory authorities. They are responsible for the determination of the explosion hazard (allocation of zones). If the certification is supplemented with an "X" the special conditions in the EU prototype certification must be observed. The cable entries must be approved for explosion hazard areas and secured against spontaneous loosening. Unused openings must be closed with approved stoppers. For the assembly of the cable entries the instructions in the instruction manual of the cable entry manufacturer must be observed. The number of threaded holes, the thread sizes and the type of thread are given in Table 1. Special entries are indicated. For vertical installation of the motor with the end of the shaft facing upwards or downwards, e.g. types IMV3, IMV6, IMV19, for 1MA motors a cover must be arranged so that foreign bodies cannot enter into the motor fan cover. Cooling of the motor must not be obstructed by the cover. If nothing is stated to the contrary in the EU prototype certification or on the rating plate with regard to type of operation and tolerances, electrical machines are designed for continuous operation and normal infrequent starts, in which there is not significant start-up warming. The motors may only be used for the type of operation stated on the rating plate. Range A in EN 60034-1:2004 - voltage ± 5%, frequency ± 2%, curve shape, symmetrical mains - must be complied with in order that warming remains within the permissible limits. Larger deviations from the rated values can cause a permissible warming of the electrical machine and must be stated on the rating plate. The temperature class of the motor stated on the rating plate must conform with the temperature class of any escaping inflammable gases. In addition, the safety device must be adjusted to the rated current. A triggering device certified according to RL94/9/EU must be used. Thermal protection of the machine by means of direct temperature monitoring of the windings is permissible, if this is certified and stated on the rating plate. An earthing tab is cast onto the housing for the connection of the external bonding cable. The thread sizes for the screws of this external bonding cable are stated in Table 2.

www.nord.com B1092-GB -9-

5. Motors with increased ignition protection, type "e" Ex e

In the case of external sources of heat or cold, no additional measures are necessary if the temperatures of the attached components do not exceed the permissible temperatures listed in Table 3. The values in Table 3 apply for an ambient temperature of -20°C to +40°C with self-ventilation. Special applications with external sources of heat and cold must be examined by means of type testing with regard to the effect on the maximum surface and operating temperatures and suitable measures taken if necessary. For the installation of electrical equipment in explosion hazard areas in Germany, attention is drawn to DIN EN 60079-14:2003 and the "Betriebssicherheitverordnung" [Operating Safety Regulations]! In foreign countries the appropriate national regulations must be observed. Operation with an inverter must be explicitly certified. The separate manufacturer's information must be observed.

5.1 Additional information for operation with a frequency inverter

In addition to this information, the operating instructions of the frequency inverter and if necessary the operating instructions of the gear unit and any other operating instructions must be observed. Failure to observe these can cause material damage and personal injury. Series 1 MA7 motors are produced in the ignition protection type "Increased Safety" and are suitable for operation with a frequency inverter. The suitability can be identified by the statement of the maximum frequency (e.g. f max 100 Hz) on the type plate. Individual acceptance by a designated testing facility is not necessary. It is essential that the supplied data sheet for the EU prototype certification (see Section 7.) is complied with. This includes important information for operation and commissioning. Ex e motors suitable for use with frequency inverters are equipped with a triple PTC. This must be evaluated by a certified triggering device with protection type labelling Ex II (2) G. The joint operation of several motors on one frequency inverter is not permissible. Connecting cables must be dimensioned for a continuous thermal load of at least 80°C. In addition, the frequency inverter used must be equipped with a speed-dependent current limitation (Precision of measurement of effective current: 5%). The current limitation is set to the maximum permissible nominal current of the frequency inverter. A limitation of the output current of the frequency inverter to double the rated current of the motor must be ensured. Observation of the rev/f characteristic and the permissible torque depending on the frequency is essential. Voltage drops due to the use of long supply cables and/or sine wave filters between the motor and the frequency inverter must be taken into account. The maximum permissible length of cable is 30m. The frequency inverter also causes a drop in voltage. The motor terminal voltage can be influenced by increasing the input voltage of the frequency inverter. Voltages in excess of 1556 V (peak values) must not occur at the motor terminals. Unfavourable cable lengths and short switching times of the frequency inverter can cause impermissible overvoltages. The occurrence of such overvoltages must be ruled out before starting up.

-10- B1092-GB www.nord.com

5. Motors with increased ignition protection, type "e" Ex e

Shaft height Thread size Number

63 – 90 M16x1.5

M25x1.5

1

1

100 – 132 M32x1.5 4

160 M40x1.5 4

Table 1: Thread sizes in terminal box

Shaft height Thread of screw for bonding cable

63 – 90 M4

100 – 112 M5

132 – 160 M6

Table 2: Bonding cable screw threads

Number of pairs of poles 4-pole

Maximum shaft temperature 75°C

Maximum flange temperature 75°C

Table 3: Maximum permissible heat and cold sources

www.nord.com B1092-GB -11-

6. Drawing and list of

replacement parts 6.1 List and drawings of replacement parts

Replacement parts which can be supplied ex works Item no. Designation

1.00 AS bearing

.40 Bearing cover

.43 Shaft seal

.58 Spring washer

.60 Roller bearing

.61 Spring strip for bearing cover hub (not always present)

3.00 Rotor, complete

.88 Parallel key for fan

4.00 Stator, complete

.07 Housing foot, right

.08 Housing foot, left

.18 Rating plate

.19 Screw

.20 Cover

.30 Contact bracket

.31 Earthing bracket

5.00 Terminal box, complete

.03 Seal

.04 Seal

.10 Terminal board, complete

.11 Terminal bar

.44 Terminal box, upper section

.70 Retaining clip

.71 Retaining clip

.83 Seal

.84 Terminal box cover

.85 Seal

.90 Terminal box upper section, rotatable 4x90 degrees, complete (for retrofitting)

.92 Terminal box cover

.93 Seal

.95 Terminal box, upper section

.98 Seal

.99 Adapter plate

6.00 BS bearing

.10 Roller bearing

.11 Spring strip for bearing cover hub (not always present)

.20 Bearing cover

.23 Shaft sealing ring

7.00 Ventilation, complete

.04 Fan

.40 Fan hood

Fitting and removal tools for roller bearings, fan and drive elements can not be supplied!

-12- B1092-GB www.nord.com

6. Drawing and list of replacement parts

Standard components to be obtained commercially according to dimensions, materials and surfaces.

4.05 (see Fig. 3) DIN EN ISO 70897090

(DIN 125)

4.10

4.39

5.78

DIN 128

7.12 DIN 471

6.02 DIN 472

4.04 (see Fig. 3) DIN 580

1.49

4.11

4.39

5.19

5.49

5.79

5.89

5.91

5.94

6.29

7.49

DIN EN ISO 4762

(DIN 912)

DIN EN ISO 4017

(DIN 933)

DIN EN ISO 4014

(DIN 931)

DIN EN ISO 7045

(DIN 7985)

3.38 DIN 6885

5.52

5.53

5.96

DIN EN 50262

1.60

6.10

DIN 625 Bearing type

Replacement parts are to be ordered via the Sales departments of the particular producers.

www.nord.com B1092-GB -13-

6. Drawing and list of

replacement parts

Fig. 2 BG63…90L

cert

ified

scr

ew c

onne

ctio

n (5

.1)

For

alu

min

ium

bea

ring

cove

rs (

1.40

AH

90)

a s

prin

g st

rip (

1.61

) is

ins

erte

d in

the

hub

(h

ook

the

bea

d in

to th

e gr

oov

e).

-14- B1092-GB www.nord.com

6. Drawing and list of replacement parts

Fig. 2 BG 100…160L

cert

ified

scr

ew c

onne

ctio

n (5

.1)

For

alu

min

ium

bea

ring

cove

rs (

1.40

/6.2

0) a

sp

ring

strip

(1.

61/6

.11

) is

inse

rted

in t

he h

ub

(hoo

k th

e be

ad

into

the

gro

ove)

.

www.nord.com B1092-GB -15-

6. Drawing and list of

replacement parts

Fig. 3, BD 100…160L, version with lateral configuration of upper section of terminal box (rotatable 4x90 degrees)

6.2 Tightening torques

Tightening torques for terminal board connections

Thread diameter M4 M5 M6 M8 M10 M12 M16

Tightening torque (Nm) min. 0.8 1.8 2.7 5.5 9.0 14.0 27.0

Tightening torque (Nm) max. 1.2 2.5 4.0 8.0 13.0 20.0 40.0

Fig. 4, Tightening torques of screw connections of the electrical connections and terminal board connections (except for the terminal bar)

(*) (**)

Nm min. Nm max. Nm min. Nm max.

O-ring thickness

mm

M12x1.5 4 5

M16x1.5 5 7.5

M25x1.5 6 9

2

3

M32x1.5

M40x1.5 8 12 4 6

2

Fig 4.1, Tightening torques for cable connectors made from metal (*) and plastic 9**) for direct attachment to motor. For other connectors (e.g. reducers) the corresponding torques according to the table should be used.

Tightening torques on terminal box

Thread diameter M4 M5 M6 M8 M10 M12 M16 M20

Tightening torque (Nm) min. 2 3.5 6 16 28 46 110 225

Tightening torque (Nm) max. 3 5 9 24 42 70 165 340

Fig. 4.2, tightening torques for screws on the electrical terminal box, on bearing covers and on screw connectors for bonding cables

The above values apply unless other values are stated.

e.g. outlet for cables and wires - at bottom

-16- B1092-GB www.nord.com

6. Drawing and list of replacement parts

6.3 Cross sections which may be connected

…25 mm2 …10 mm2 …25 mm2 …10 mm2 …25 mm2

For connection with a DIN fork terminal, the fork terminal must be angled downwards.

Connection of a single conductor with retaining clip.

Connection of two conductors of approximately the same diameter with retaining clip.

Connection of a single conductor under the external earthing bracket.

For connection with DIN fork terminal under the external earthing bracket.

Fig. 5, cross sections which may be connected according to the size of terminal (may be reduced due to the size of the cable entries)

6.4 Changing the bearings

Fig. 6, Intermediate plate (protection of centring in the end of the shaft)

Fig. 7, fitting and removal of drive elements (intermediate plate to protect the centring at the end of the shaft)

When fitting drive elements (clutch, gear wheel, pulley etc.) use the thread in the end of the shaft and as far as possible heat the drive elements as necessary. Use suitable equipment for removal. When fitting or removing, no blows (e.g. with a hammer or similar) or radial or axial forces in excess of those permissible according to the catalogue may be transferred to the motor bearing via the end of the shaft.

Fig. 8, balancing with half parallel key

www.nord.com B1092-GB -17-

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3046 X

for the three-phase motor, type 1MA7 063-4…

Rated values and data This certificate applies for the following versions on condition that motors of this type only vary to an insignificant extent from the tested sample with regard to the electrical and thermal load:

Star connection

Torque: 0.3 0.8 1.1 0.36 Nm

Power: 0.008 0.053 0.158 0.108 kW

Voltage: *) 80 200 400 400 V

Current: 0.33 0.48 0.58 0.34 A

Frequency: 10 25 50 100 Hz

Speed of rotation: 244 632 1370 2835 min-1

Operating mode: S1

Heat class F

Delta connection

Torque: 0.3 0.8 1.1 1.1 Nm

Power: 0.008 0.053 0.295 0.334 kW

Voltage: *) 46 115 400 400 V

Current: 0.57 0.83 1.1 1,0 A

Frequency: 10 25 87 100 Hz

Speed of rotation: 244 632 2485 2829 min-1

Operating mode: S1

Heat class F

*) Basic oscillation, measured at the motor terminals.

The voltage depends on the input voltage of the frequency inverter, the voltage drop at the filter and over the motor supply cable and may not fall below the rated value by more than 5% according to IEC 60034 - 1 Range "A", even with minimum input voltage of the frequency inverter. This must be taken into account for the design of the motor, the parameterisation of the inverter (e.g. rev/f adaptation) and for the minimum input voltage of the inverter.

The maximum input voltage of the inverter is 500V.

Adaptation of the rated voltage of the motor by means of the number of windings is permissible. The rated current changes in inverse proportion to the rated voltage.

Sheet 1/3

-18- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3046 X

for the three-phase motor, type 1MA7 063-4…

Monitoring devices To prevent impermissible heating due to overload, the motors are monitored by connection to a device for direct temperature monitoring in combination with defined setting data of the inverter. Due to the special characteristics of motors supplied by inverters and the adapted monitoring device, details of the relationship IA/IN and the heating time tE are not required for motors operated by inverters.

The type of device for direct temperature monitoring has been tested by the Physikalish-Technische Bundesanstalt and consists of three DIN 44082 type M 110 PTCs installed in the windings and a function-tested triggering device according to Guideline 94/9/EU.

With a line current of 1.7 A and a blocked shaft, the PTC must trigger after 31.4 s (± 20 %) assuming a cold condition (20 °C).

By means of the temperature monitoring device, temperature class T3 as per EN 60079-7 is complied with.

Inverter setting data

In combination with the aforementioned monitoring device, the following inverter data must be set and maintained during operation:

Minimum pulse frequency: 3 kHz

Short-term current limit: 1.5*IN

Maximum overload time: 60 s

Minimum frequency fmin: 10 Hz

Maximum frequency fmax: 100 Y / 100 Δ Hz

Permissible duration of operation at fmin:

60 s

The maximum overload time and the permissible duration of operation at fmin refer to a time period of 10 min.

The relationship of the torque to the frequency results from the permissible continuous current limit.

Sheet 2/3

www.nord.com B1092-GB -19-

7. Data Sheets

Translated extract from Data Sheet 01

of the EU Prototype Test Certificate PTB 07 ATEX 3046 X

for the three-phase motor, type 1MA7 063-4…

The continuous current limit of the frequency inverter must be set dependent on the frequency according to the following diagram:

0,4 0,5 0,6 0,7 0,8 0,9

1 1,1 1,2

5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 f / Hz

I /

In

Star connection

Delta connection

Permissible region

Prohibited region

Setting parameters for the continuous current limit of the frequency inverter between 10 Hz and 100 Hz

All other setting data should be selected according to the requirements of the drive unit.

Special conditions Group operation of the motors is not permissible. Motors of this type may only be operated with inverters which fulfil the requirements stated above under "Inverter setting data". The maximum rated current of the frequency inverter may correspond to double the rated current of the motor. The current monitoring of the frequency inverter must record the effective value of the machine current with a tolerance of ± 5 % in relation to the rated current of the motor. Before start-up it must be ensured that no overvoltages due to the inverter with a peak value in excess of

1556 V (2* 2 *550V) occur at the terminals of the electrical machine.

Test report PTB Ex 07-37118

Certification Facility for Explosion Protection Braunschweig, 4 October 2007

pp

L.S.

Dr.-Ing. F. Lienesch

Senior Government Official Sheet 3/3

-20- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 01

of the EU Prototype Test Certificate PTB 07 ATEX 3047 X

for the three-phase motor, type 1MA7 073-4…

Design values and data This certificate applies for the following versions on condition that motors of this type only vary to an insignificant extent from the tested sample with regard to the electrical and thermal load:

Star connection

Torque: 0.5 2.0 2.6 0.8 Nm

Power: 0.005 0.128 0.356 0.224 kW

Voltage: *) 40 200 400 400 V

Current: 0.5 0.92 1.11 0.67 A

Frequency: 5 25 50 100 Hz

Speed of rotation: 102 610 1273 2586 min-1

Operating mode: S1

Heat class F

Delta connection

Torque: 0.5 2.0 2.6 2.6 Nm

Power: 0.005 0.128 0.640 0.764 kW

Voltage: *) 23 115 400 400 V

Current: 0.86 1.59 1.97 1.98 A

Frequency: 5 25 87 100 Hz

Speed of rotation: 102 610 2280 2796 min-1

Operating mode: S1

Heat class F

*) Basic oscillation, measured at the motor terminals.

The voltage depends on the input voltage of the frequency inverter, the voltage drop at the filter and over the motor supply cable and may not fall below the design value by more than 5% according to IEC 60034 - 1 Range "A", even with minimum input voltage of the frequency inverter. This must be taken into account for the design of the motor, the parameterisation of the inverter (e.g. rev/f adaptation) and for the minimum input voltage of the inverter.

The maximum input voltage of the inverter is 500V.

Adaptation of the design voltage of the motor by means of the number of windings is permissible. The rated current changes in inverse proportion to the rated voltage.

Sheet 1/3

www.nord.com B1092-GB -21-

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3047 X

for the three-phase motor, type 1MA7 073-4…

Monitoring devices To prevent impermissible heating due to overload, the motors are monitored by connection to a device for direct temperature monitoring in combination with defined setting data of the inverter. Due to the special characteristics of motors supplied by inverters and the adapted monitoring device, details of the relationship IA/IN and the heating time tE are not required for motors operated by inverters.

The type of device for direct temperature monitoring has been tested by the Physikalish-Technische Bundesanstalt and consists of three DIN 44082 type M 110 PTCs installed in the windings and a function-tested triggering device according to Guideline 94/9/EU.

With a line current of 4.1 A and a blocked shaft, the PTC must trigger after 35 s (± 20 %) assuming a cold condition (20 °C).

By means of the temperature monitoring device, temperature class T3 as per EN 60079-7 is complied with.

Inverter setting data

In combination with the aforementioned monitoring device, the following inverter data must be set and maintained during operation:

Minimum pulse frequency: 3 kHz

Short-term current limit: 1.5*IN

Maximum overload time: 60 s

Minimum frequency fmin: 5 Hz

Maximum frequency fmax: 100 Y / 100 Δ Hz

Permissible duration of operation at fmin:

60 s

The maximum overload time and the permissible duration of operation at fmin refer to a time period of 10 min.

The relationship of the torque to the frequency results from the permissible continuous current limit.

Sheet 2/3

-22- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 01

of the EU Prototype Test Certificate PTB 07 ATEX 3047 X

for the three-phase motor, type 1MA7 073-4…

The continuous current limit of the frequency inverter must be set dependent on the frequency according to the following diagram:

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105

f / Hz

I / In

Star Connection

Delta Connection

Unacceptable Region

Acceptable Region

Setting parameters for the continuous current limit of the frequency inverter between 5 Hz and 100 Hz

All other setting data should be selected according to the requirements of the drive unit.

Special conditions Group operation of the motors is not permissible. Motors of this type may only be operated with inverters which fulfil the requirements stated above under "Inverter setting data". The maximum rated current of the frequency inverter may correspond to double the rated current of the motor. The current monitoring of the frequency inverter must record the effective value of the machine current with a tolerance of ± 5 % in relation to the rated current of the motor. Before start-up it must be ensured that no overvoltages due to the inverter with a peak value in excess of

1556 V (2* 2 *550V) occur at the terminals of the electrical machine.

Test report PTB Ex 07-37119 Certification Facility for Explosion Protection Braunschweig, 4 October 2007 pp L.S. Dr.-Ing. F. Lienesch Senior Government Official Sheet 3/3

www.nord.com B1092-GB -23-

7. Data Sheets

Translated extract from Data Sheet 01

of the EU Prototype Test Certificate PTB 07 ATEX 3048 X

for the three-phase motor, type 1MA7 083-4…

Rated values and data This certificate applies for the following versions on condition that motors of this type only vary to an insignificant extent from the tested sample with regard to the electrical and thermal load:

Star connection

Torque: 1.4 4.5 5.2 1.8 Nm

Power: 0.015 0.295 0.75 0.531 kW

Voltage: *) 40 200 400 400 V

Current: 1.0 1.8 2.0 1.4 A

Frequency: 5 25 50 100 Hz

Speed of rotation: 101 627 1378 2819 min-1

Operating mode: S1

Heat class F

Delta connection

Torque: 1.4 4.5 5.2 5.2 Nm

Power: 0.015 0.295 1.37 1.526 kW

Voltage: *) 23 115 400 400 V

Current: 1.7 3.1 3.6 3.5 A

Frequency: 5 25 87 100 Hz

Speed of rotation: 101 627 2492 2836 min-1

Operating mode: S1

Heat class F

*) Basic oscillation, measured at the motor terminals.

The voltage depends on the input voltage of the frequency inverter, the voltage drop at the filter and over the motor supply cable and may not fall below the design value by more than 5% according to IEC 60034 - 1 Range "A", even with minimum input voltage of the frequency inverter. This must be taken into account for the design of the motor, the parameterisation of the inverter (e.g. rev/f adaptation) and for the minimum input voltage of the inverter.

The maximum input voltage of the inverter is 500V.

Adaptation of the design voltage of the motor by means of the number of windings is permissible. The rated current changes in inverse proportion to the rated voltage.

Sheet 1/3

-24- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 01

of the EU Prototype Test Certificate PTB 07 ATEX 3048 X

for the three-phase motor, type 1MA7 083-4…

Monitoring devices To prevent impermissible heating due to overload, the motors are monitored by connection to a device for direct temperature monitoring in combination with defined setting data of the inverter. Due to the special characteristics of motors supplied by inverters and the adapted monitoring device, details of the relationship IA/IN and the heating time tE are not required for motors operated by inverters.

The type of device for direct temperature monitoring has been tested by the Physikalish-Technische Bundesanstalt and consists of three DIN 44082 type M 110 PTCs installed in the windings and a function-tested triggering device according to Guideline 94/9/EU.

With a line current of 9.8 A and a blocked shaft, the PTC must trigger after 21 s (± 20 %) assuming a cold condition (20 °C).

By means of the temperature monitoring device, temperature class T3 as per EN 60079-7 is complied with.

Inverter setting data

In combination with the aforementioned monitoring device, the following inverter data must be set and maintained during operation:

Minimum pulse frequency: 3 kHz

Short-term current limit: 1.5*IN

Maximum overload time: 60 s

Minimum frequency fmin: 5 Hz

Maximum frequency fmax: 100 Y / 100 Δ Hz

Permissible duration of operation at fmin:

60 s

The maximum overload time and the permissible duration of operation at fmin refer to a time period of 10 min.

The relationship of the torque to the frequency results from the permissible continuous current limit.

Sheet 2/3

www.nord.com B1092-GB -25-

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3048 X

for the three-phase motor, type 1MA7 083-4…

The continuous current limit of the frequency inverter must be set dependent on the frequency according to the following diagram:

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 f / Hz

I /

In

Star connection

Delta connection

Permissible region

Prohibited region

Setting parameters for the continuous current limit of the frequency inverter between 5 Hz and 100 Hz

All other setting data should be selected according to the requirements of the drive unit.

Special conditions Group operation of the motors is not permissible. Motors of this type may only be operated with inverters which fulfil the requirements stated above under "Inverter setting data". The maximum rated current of the frequency inverter may correspond to double the rated current of the motor. The current monitoring of the frequency inverter must record the effective value of the machine current with a tolerance of ± 5 % in relation to the rated current of the motor. Before start-up it must be ensured that no overvoltages due to the inverter with a peak value in excess of

1556 V (2* 2 *550V) occur at the terminals of the electrical machine.

Test report PTB Ex 07-37120

Certification Facility for Explosion Protection Braunschweig, 4 October 2007

pp

L.S.

Dr.-Ing. F. Lienesch

Senior Government Official Sheet 3/3

-26- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3049 X

for the three-phase motor, type 1MA7 096-4…

Rated values and data This certificate applies for the following versions on condition that motors of this type only vary to an insignificant extent from the tested sample with regard to the electrical and thermal load:

Star connection

Torque: 3.0 9.1 9.1 3.6 Nm

Power: 0.034 0.604 1.34 1.08 kW

Voltage: *) 40 200 400 400 V

Current: 1.6 3.1 3.1 2.3 A

Frequency: 5 25 50 100 Hz

Speed of rotation: 108 630 1407 2854 min-1

Operating mode: S1

Heat class F

Delta connection

Torque: 3 9.1 9.1 9.1 Nm

Power: 0.034 0.604 2.41 2.73 kW

Voltage: *) 23 115 400 400 V

Current: 2.8 5.4 5.4 5.7 A

Frequency: 5 25 87 100 Hz

Speed of rotation: 108 630 2518 2870 min-1

Operating mode: S1

Heat class F

*) Basic oscillation, measured at the motor terminals.

The voltage depends on the input voltage of the frequency inverter, the voltage drop at the filter and over the motor supply cable and may not fall below the design value by more than 5% according to IEC 60034 - 1 Range "A", even with minimum input voltage of the frequency inverter. This must be taken into account for the design of the motor, the parameterisation of the inverter (e.g. rev/f adaptation) and for the minimum input voltage of the inverter.

The maximum input voltage of the inverter is 500V.

Adaptation of the design voltage of the motor by means of the number of windings is permissible. The rated current changes in inverse proportion to the rated voltage.

Sheet 1/3

www.nord.com B1092-GB -27-

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3049 X

for the three-phase motor, type 1MA7 096-4…

Monitoring devices To prevent impermissible heating due to overload, the motors are monitored by connection to a device for direct temperature monitoring in combination with defined setting data of the inverter. Due to the special characteristics of motors supplied by inverters and the adapted monitoring device, details of the relationship IA/IN and the heating time tE are not required for motors operated by inverters.

The type of device for direct temperature monitoring has been tested by the Physikalish-Technische Bundesanstalt and consists of three DIN 44082 type M 110 PTCs installed in the windings and a function-tested triggering device according to Guideline 94/9/EU.

With a line current of 17.4 A and a blocked shaft, the PTC must trigger after 17.5 s (± 20 %) assuming a cold condition (20 °C).

By means of the temperature monitoring device, temperature class T3 as per EN 60079-7 is complied with.

Inverter setting data

In combination with the aforementioned monitoring device, the following inverter data must be set and maintained during operation:

Minimum pulse frequency: 3 kHz

Short-term current limit: 1.5*IN

Maximum overload time: 60 s

Minimum frequency fmin: 5 Hz

Maximum frequency fmax: 100 Y / 100 Δ Hz

Permissible duration of operation at fmin:

60 s

The maximum overload time and the permissible duration of operation at fmin refer to a time period of 10 min.

The relationship of the torque to the frequency results from the permissible continuous current limit.

Sheet 2/3

-28- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3049 X

for the three-phase motor, type 1MA7 096-4…

The continuous current limit of the frequency inverter must be set dependent on the frequency according to the following diagram:

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

1,2

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 f / Hz

I / In

Star connection

Delta connection

Permissible region

Prohibited region

Setting parameters for the continuous current limit of the frequency inverter between 5 Hz and 100 Hz

All other setting data should be selected according to the requirements of the drive unit.

Special conditions Group operation of the motors is not permissible. Motors of this type may only be operated with inverters which fulfil the requirements stated above under "Inverter setting data". The maximum rated current of the frequency inverter may correspond to double the rated current of the motor. The current monitoring of the frequency inverter must record the effective value of the machine current with a tolerance of ± 5 % in relation to the rated current of the motor. Before start-up it must be ensured that no overvoltages due to the inverter with a peak value in excess of

1556 V (2* 2 *550V) occur at the terminals of the electrical machine.

Test report PTB Ex 07-37121 Certification Facility for Explosion Protection Braunschweig, 4 October 2007

pp

L.S.

Dr.-Ing. F. Lienesch

Senior Government Official Sheet 3/3

www.nord.com B1092-GB -29-

7. Data Sheets

Translated extract from Data Sheet 01

of the EU Prototype Test Certificate PTB 07 ATEX 3050 X

for the three-phase motor, type 1MA7 106-4…

Rated values and data This certificate applies for the following versions on condition that motors of this type only vary to an insignificant extent from the tested sample with regard to the electrical and thermal load:

Star connection

Torque: 5 13.5 13.5 5.5 Nm

Power: 0.061 0.937 2.0 1.67 kW

Voltage: *) 40 200 400 400 V

Current: 2.4 4.4 4.4 3.4 A

Frequency: 5 25 50 100 Hz

Speed of rotation: 114.2 662 1424 2872 min-1

Operating mode: S1

Heat class F

Delta connection

Torque: 5 13.5 12.7 12.7 Nm

Power: 0.061 0.937 3.38 3.86 kW

Voltage: *) 23 115 400 400 V

Current: 4.15 7.6 7.6 7.8 A

Frequency: 5 25 87 100 Hz

Speed of rotation: 114.2 662 2541 2896 min-1

Operating mode: S1

Heat class F

*) Basic oscillation, measured at the motor terminals.

The voltage depends on the input voltage of the frequency inverter, the voltage drop at the filter and over the motor supply cable and may not fall below the design value by more than 5% according to IEC 60034 - 1 Range "A", even with minimum input voltage of the frequency inverter. This must be taken into account for the design of the motor, the parameterisation of the inverter (e.g. rev/f adaptation) and for the minimum input voltage of the inverter.

The maximum input voltage of the inverter is 500V.

Adaptation of the design voltage of the motor by means of the number of windings is permissible. The rated current changes in inverse proportion to the rated voltage.

Sheet 1/3

-30- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3050 X

for the three-phase motor, type 1MA7 106-4…

Monitoring devices To prevent impermissible heating due to overload, the motors are monitored by connection to a device for direct temperature monitoring in combination with defined setting data of the inverter. Due to the special characteristics of motors supplied by inverters and the adapted monitoring device, details of the relationship IA/IN and the heating time tE are not required for motors operated by inverters.

The type of device for direct temperature monitoring has been tested by the Physikalish-Technische Bundesanstalt and consists of three DIN 44082 type M 120 PTCs installed in the windings and a function-tested triggering device according to Guideline 94/9/EU.

With a line current of 28.8 A and a blocked shaft, the PTC must trigger after 15 s (± 20 %) assuming a cold condition (20 °C).

By means of the temperature monitoring device, temperature class T3 as per EN 60079-7 is complied with.

Inverter setting data

In combination with the aforementioned monitoring device, the following inverter data must be set and maintained during operation:

Minimum pulse frequency: 3 kHz

Short-term current limit: 1.5*IN

Maximum overload time: 60 s

Minimum frequency fmin: 5 Hz

Maximum frequency fmax: 100 Y / 100 Δ Hz

Permissible duration of operation at fmin:

60 s

The maximum overload time and the permissible duration of operation at fmin refer to a time period of 10 min.

The relationship of the torque to the frequency results from the permissible continuous current limit.

Sheet 2/3

www.nord.com B1092-GB -31-

7. Data Sheets

Translated extract from Data Sheet 01

of the EU Prototype Test Certificate PTB 07 ATEX 3050 X

for the three-phase motor, type 1MA7 106-4…

The continuous current limit of the frequency inverter must be set dependent on the frequency according to the following diagram:

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

1,2

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 f / Hz

I / In

Star connection

Delta connection

Permissible region

Prohibited region

Setting parameters for the continuous current limit of the

frequency inverter between 5 Hz and 100 Hz

All other setting data should be selected according to the requirements of the drive unit.

Special conditions Group operation of the motors is not permissible. Motors of this type may only be operated with inverters which fulfil the requirements stated above under "Inverter setting data". The maximum rated current of the frequency inverter may correspond to double the rated current of the motor. The current monitoring of the frequency inverter must record the effective value of the machine current with a tolerance of ± 5 % in relation to the rated current of the motor. Before start-up it must be ensured that no overvoltages due to the inverter with a peak value in excess of

1556 V (2* 2 *550V) occur at the terminals of the electrical machine.

Test report PTB Ex 07-37122

Certification Facility for Explosion Protection Braunschweig, 4 October 2007

pp

L.S.

Dr.-Ing. F. Lienesch

Senior Government Official Sheet 3/3

-32- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 02 of the EU Prototype Test Certificate PTB 07 ATEX 3050 X

for the three-phase motor, type 1MA7 107-4…

Rated values and data This certificate applies for the following versions on condition that motors of this type only vary to an insignificant extent from the tested sample with regard to the electrical and thermal load:

Star connection

Torque: 5 14 16.8 7.5 Nm

Power: 0.065 0.99 2.5 2.2 kW

Voltage: *) 40 200 400 400 V

Current: 2.5 4.6 5.4 4.6 A

Frequency: 5 25 50 100 Hz

Speed of rotation: 124 679 1415 2831 min-1

Operating mode: S1

Heat class F

Delta connection

Torque: 5 14 16.8 16 Nm

Power: 0.065 0.99 4.4 4.8 kW

Voltage: *) 23 115 400 400 V

Current: 4.3 8.0 9.4 9.6 A

Frequency: 5 25 87 100 Hz

Speed of rotation: 124 679 2523 2885 min-1

Operating mode: S1

Heat class F

*) Basic oscillation, measured at the motor terminals.

The voltage depends on the input voltage of the frequency inverter, the voltage drop at the filter and over the motor supply cable and may not fall below the design value by more than 5% according to IEC 60034 - 1 Range "A", even with minimum input voltage of the frequency inverter. This must be taken into account for the design of the motor, the parameterisation of the inverter (e.g. rev/f adaptation) and for the minimum input voltage of the inverter. The maximum input voltage of the inverter is 500V.

Adaptation of the design voltage of the motor by means of the number of windings is permissible. The rated current changes in inverse proportion to the rated voltage.

Sheet 1/3

www.nord.com B1092-GB -33-

7. Data Sheets

Translated extract from Data Sheet 02 of the EU Prototype Test Certificate PTB 07 ATEX 3050 X

for the three-phase motor, type 1MA7 107-4…

Monitoring devices To prevent impermissible heating due to overload, the motors are monitored by connection to a device for direct temperature monitoring in combination with defined setting data of the inverter. Due to the special characteristics of motors supplied by inverters and the adapted monitoring device, details of the relationship IA/IN and the heating time tE are not required for motors operated by inverters.

The type of device for direct temperature monitoring has been tested by the Physikalish-Technische Bundesanstalt and consists of three DIN 44082 type M 120 PTCs installed in the windings and a function-tested triggering device according to Guideline 94/9/EU.

With a line current of 35.2 A and a blocked shaft, the PTC must trigger after 16 s (± 20 %) assuming a cold condition (20 °C).

By means of the temperature monitoring device, temperature class T3 as per EN 60079-7 is complied with.

Inverter setting data

In combination with the aforementioned monitoring device, the following inverter data must be set and maintained during operation:

Minimum pulse frequency: 3 kHz

Short-term current limit: 1.5*IN

Maximum overload time: 60 s

Minimum frequency fmin: 5 Hz

Maximum frequency fmax: 100 Y / 100 Δ Hz

Permissible duration of operation at fmin:

60 s

The maximum overload time and the permissible duration of operation at fmin refer to a time period of 10 min.

The relationship of the torque to the frequency results from the permissible continuous current limit.

Sheet 2/3

-34- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 02

of the EU Prototype Test Certificate PTB 07 ATEX 3050 X

for the three-phase motor, type 1MA7 107-4…

The continuous current limit of the frequency inverter must be set dependent on the frequency according to the following diagram:

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

1,2

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105

f / Hz

I /

In

Star connection

Delta connection

Permisible region

Prohibited region

Setting parameters for the continuous current limit of the frequency inverter between 5 Hz and 100 Hz

All other setting data should be selected according to the requirements of the drive unit.

Special conditions Group operation of the motors is not permissible. Motors of this type may only be operated with inverters which fulfil the requirements stated above under "Inverter setting data". The maximum rated current of the frequency inverter may correspond to double the rated current of the motor. The current monitoring of the frequency inverter must record the effective value of the machine current with a tolerance of ± 5 % in relation to the rated current of the motor. Before start-up it must be ensured that no overvoltages due to the inverter with a peak value in excess of

1556 V (2* 2 *550V) occur at the terminals of the electrical machine.

Test report PTB Ex 07-37427

Certification Facility for Explosion Protection Braunschweig, 4 October 2007

pp

L.S.

Dr.-Ing. F. Lienesch

Senior Government Official Sheet 3/3

www.nord.com B1092-GB -35-

7. Data Sheets

Translated extract from Data Sheet 01

of the EU Prototype Test Certificate PTB 07 ATEX 3051 X

for the three-phase motor, type 1MA7 113-4…

Rated values and data This certificate applies for the following versions on condition that motors of this type only vary to an insignificant extent from the tested sample with regard to the electrical and thermal load:

Star connection

Torque: 10.1 19 23.9 11 Nm

Power: 0.123 1.38 3.57 3.23 kW

Voltage: *) 40 200 400 400 V

Current: 4.4 6.3 7.6 7.8 A

Frequency: 5 25 50 100 Hz

Speed of rotation: 116 699 1422 2788 min-1

Operating mode: S1

Heat class F

Delta connection

Torque: 10.1 19 23.9 20.1 Nm

Power: 0.123 1.38 6.35 6.14 kW

Voltage: *) 23 115 400 400 V

Current: 7.6 10.9 13.4 12.8 A

Frequency: 5 25 87 100 Hz

Speed of rotation: 116 699 2533 2910 min-1

Operating mode: S1

Heat class F

*) Basic oscillation, measured at the motor terminals.

The voltage depends on the input voltage of the frequency inverter, the voltage drop at the filter and over the motor supply cable and may not fall below the design value by more than 5% according to IEC 60034 - 1 Range "A", even with minimum input voltage of the frequency inverter. This must be taken into account for the design of the motor, the parameterisation of the inverter (e.g. rev/f adaptation) and for the minimum input voltage of the inverter.

The maximum input voltage of the inverter is 500V.

Adaptation of the design voltage of the motor by means of the number of windings is permissible. The rated current changes in inverse proportion to the rated voltage.

Sheet 1/3

-36- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3051 X

for the three-phase motor, type 1MA7 113-4…

Monitoring devices To prevent impermissible heating due to overload, the motors are monitored by connection to a device for direct temperature monitoring in combination with defined setting data of the inverter. Due to the special characteristics of motors supplied by inverters and the adapted monitoring device, details of the relationship IA/IN and the heating time tE are not required for motors operated by inverters.

The type of device for direct temperature monitoring has been tested by the Physikalish-Technische Bundesanstalt and consists of three DIN 44082 type M 120 PTCs installed in the windings and a function-tested triggering device according to Guideline 94/9/EU.

With a line current of 54 A and a blocked shaft, the PTC must trigger after 15 s (± 20 %) assuming a cold condition (20 °C).

By means of the temperature monitoring device, temperature class T3 as per EN 60079-7 is complied with.

Inverter setting data

In combination with the aforementioned monitoring device, the following inverter data must be set and maintained during operation:

Minimum pulse frequency: 3 kHz

Short-term current limit: 1.5*IN

Maximum overload time: 60 s

Minimum frequency fmin: 5 Hz

Maximum frequency fmax: 100 Y / 100 Δ Hz

Permissible duration of operation at fmin:

60 s

The maximum overload time and the permissible duration of operation at fmin refer to a time period of 10 min.

The relationship of the torque to the frequency results from the permissible continuous current limit.

Sheet 2/3

www.nord.com B1092-GB -37-

7. Data Sheets

Translated extract from Data Sheet 01

of the EU Prototype Test Certificate PTB 07 ATEX 3051 X

for the three-phase motor, type 1MA7 113-4…

The continuous current limit of the frequency inverter must be set dependent on the frequency according to the following diagram:

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

1,2

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 f / Hz

I / In

Star connection

Delta connection

Permissible region

Prohibited region

Setting parameters for the continuous current limit of the frequency inverter between 5 Hz and 100 Hz

All other setting data should be selected according to the requirements of the drive unit.

Special conditions Group operation of the motors is not permissible. Motors of this type may only be operated with inverters which fulfil the requirements stated above under "Inverter setting data". The maximum rated current of the frequency inverter may correspond to double the rated current of the motor. The current monitoring of the frequency inverter must record the effective value of the machine current with a tolerance of ± 5 % in relation to the rated current of the motor. Before start-up it must be ensured that no overvoltages due to the inverter with a peak value in excess of

1556 V (2* 2 *550V) occur at the terminals of the electrical machine.

Test report PTB Ex 07-37123

Certification Facility for Explosion Protection Braunschweig, 4 October 2007

pp

L.S.

Dr.-Ing. F. Lienesch

Senior Government Official Sheet 3/3

-38- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3052 X

for the three-phase motor, type 1MA7 133-4…

Rated values and data This certificate applies for the following versions on condition that motors of this type only vary to an insignificant extent from the tested sample with regard to the electrical and thermal load:

Star connection

Torque: 15 44 44 20.2 Nm

Power: 0.218 3.28 6.83 6.18 kW

Voltage: *) 40 200 400 400 V

Current: 7.4 13.8 13.9 12.5 A

Frequency: 5 25 50 100 Hz

Speed of rotation: 139 711 1477 2926 min-1

Operating mode: S1

Heat class F

Delta connection

Torque: 15 44 35 35 Nm

Power: 0.218 3.28 9.49 10.88 kW

Voltage: *) 23 115 400 400 V

Current: 12.8 23.9 21.3 21.9 A

Frequency: 5 25 87 100 Hz

Speed of rotation: 139 711 2582 2956 min-1

Operating mode: S1

Heat class F

*) Basic oscillation, measured at the motor terminals.

The voltage depends on the input voltage of the frequency inverter, the voltage drop at the filter and over the motor supply cable and may not fall below the design value by more than 5% according to IEC 60034 - 1 Range "A", even with minimum input voltage of the frequency inverter. This must be taken into account for the design of the motor, the parameterisation of the inverter (e.g. rev/f adaptation) and for the minimum input voltage of the inverter.

The maximum input voltage of the inverter is 500V.

Adaptation of the design voltage of the motor by means of the number of windings is permissible. The rated current changes in inverse proportion to the rated voltage.

Sheet 1/3

www.nord.com B1092-GB -39-

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3052 X

for the three-phase motor, type 1MA7 133-4…

Monitoring devices To prevent impermissible heating due to overload, the motors are monitored by connection to a device for direct temperature monitoring in combination with defined setting data of the inverter. Due to the special characteristics of motors supplied by inverters and the adapted monitoring device, details of the relationship IA/IN and the heating time tE are not required for motors operated by inverters.

The type of device for direct temperature monitoring has been tested by the Physikalish-Technische Bundesanstalt and consists of three DIN 44082 type M 110 PTCs installed in the windings and a function-tested triggering device according to Guideline 94/9/EU.

With a line current of 108 A and a blocked shaft, the PTC must trigger after 13 s (± 20 %) assuming a cold condition (20 °C).

By means of the temperature monitoring device, temperature class T3 as per EN 60079-7 is complied with.

Inverter setting data

In combination with the aforementioned monitoring device, the following inverter data must be set and maintained during operation:

Minimum pulse frequency: 3 kHz

Short-term current limit: 1.5*IN

Maximum overload time: 60 s

Minimum frequency fmin: 5 Hz

Maximum frequency fmax: 100 Y / 100 Δ Hz

Permissible duration of operation at fmin:

60 s

The maximum overload time and the permissible duration of operation at fmin refer to a time period of 10 min.

The relationship of the torque to the frequency results from the permissible continuous current limit.

Sheet 2/3

-40- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3052 X

for the three-phase motor, type 1MA7 133-4…

The continuous current limit of the frequency inverter must be set dependent on the frequency according to the following diagram:

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 f / Hz

I / In

Star connection

Delta connection

Permissible region

Prohibited region

Setting parameters for the continuous current limit of the frequency inverter between 5 Hz and 100 Hz

All other setting data should be selected according to the requirements of the drive unit.

Special conditions Group operation of the motors is not permissible. Motors of this type may only be operated with inverters which fulfil the requirements stated above under "Inverter setting data". The maximum rated current of the frequency inverter may correspond to double the rated current of the motor. The current monitoring of the frequency inverter must record the effective value of the machine current with a tolerance of ± 5 % in relation to the rated current of the motor. Before start-up it must be ensured that no overvoltages due to the inverter with a peak value in excess of

1556 V (2* 2 *550V) occur at the terminals of the electrical machine.

Test report PTB Ex 07-37124

Certification Facility for Explosion Protection Braunschweig, 4 October 2007

pp

L.S.

Dr.-Ing. F. Lienesch

Senior Government Official Sheet 3/3

www.nord.com B1092-GB -41-

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3053 X

for the three-phase motor, type 1MA7 163-4…

Rated values and data This certificate applies for the following versions on condition that motors of this type only vary to an insignificant extent from the tested sample with regard to the electrical and thermal load:

Star connection

Torque: 50 60 65.7 27 Nm

Power: 0.672 4.48 10 8.244 kW

Voltage: *) 53 200 400 400 V

Current: 14 17.6 18.9 17.6 A

Frequency: 5 25 50 100 Hz

Speed of rotation: 128 710 1455 2907 min-1

Operating mode: S1

Heat class F

Delta connection

Torque: 50 60 65.7 56 Nm

Power: 0.672 4.48 17.663 17.3 kW

Voltage: *) 31 115 400 400 V

Current: 24.2 30.5 33.3 32.8 A

Frequency: 5 25 87 100 Hz

Speed of rotation: 128 710 2563 2946 min-1

Operating mode: S1

Heat class F

*) Basic oscillation, measured at the motor terminals.

The voltage depends on the input voltage of the frequency inverter, the voltage drop at the filter and over the motor supply cable and may not fall below the design value by more than 5% according to IEC 60034 - 1 Range "A", even with minimum input voltage of the frequency inverter. This must be taken into account for the design of the motor, the parameterisation of the inverter (e.g. rev/f adaptation) and for the minimum input voltage of the inverter.

The maximum input voltage of the inverter is 500V.

Adaptation of the design voltage of the motor by means of the number of windings is permissible.

The rated current changes in inverse proportion to the rated voltage.

Sheet 1/3

-42- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3053 X

for the three-phase motor, type 1MA7 163-4…

Monitoring devices To prevent impermissible heating due to overload, the motors are monitored by connection to a device for direct temperature monitoring in combination with defined setting data of the inverter. Due to the special characteristics of motors supplied by inverters and the adapted monitoring device, details of the relationship IA/IN and the heating time tE are not required for motors operated by inverters.

The type of device for direct temperature monitoring has been tested by the Physikalish-Technische Bundesanstalt and consists of three DIN 44082 type M 120 PTCs installed in the windings and a function-tested triggering device according to Guideline 94/9/EU.

With a line current of 128 A and a blocked shaft, the PTC must trigger after 23 s (± 20 %) assuming a cold condition (20 °C).

By means of the temperature monitoring device, temperature class T3 as per EN 60079-7 is complied with.

Inverter setting data

In combination with the aforementioned monitoring device, the following inverter data must be set and maintained during operation:

Minimum pulse frequency: 3 kHz

Short-term current limit: 1.5*IN

Maximum overload time: 60 s

Minimum frequency fmin: 5 Hz

Maximum frequency fmax: 100 Y / 100 Δ Hz

Permissible duration of operation at fmin:

60 s

The maximum overload time and the permissible duration of operation at fmin refer to a time period of 10 min.

The relationship of the torque to the frequency results from the permissible continuous current limit.

Sheet 2/3

www.nord.com B1092-GB -43-

7. Data Sheets

Translated extract from Data Sheet 01 of the EU Prototype Test Certificate PTB 07 ATEX 3053 X

for the three-phase motor, type 1MA7 163-4…

The continuous current limit of the frequency inverter must be set dependent on the frequency according to the following diagram:

0,7

0,75

0,8

0,85

0,9

0,95

1

1,05

1,1

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 f / Hz

I / In

Star connection

Delta connection

Permissible region

Prohibited region

Setting parameters for the continuous current limit of the frequency inverter between 5 Hz and 100 Hz

All other setting data should be selected according to the requirements of the drive unit.

Special conditions Group operation of the motors is not permissible. Motors of this type may only be operated with inverters which fulfil the requirements stated above under "Inverter setting data". The maximum rated current of the frequency inverter may correspond to double the rated current of the motor. The current monitoring of the frequency inverter must record the effective value of the machine current with a tolerance of ± 5 % in relation to the rated current of the motor. Before start-up it must be ensured that no overvoltages due to the inverter with a peak value in excess of

1556 V (2* 2 *550V) occur at the terminals of the electrical machine.

Test report PTB Ex 07-37125

Certification Facility for Explosion Protection Braunschweig, 4 October 2007

pp

L.S.

Dr.-Ing. F. Lienesch

Senior Government Official Sheet 3/3

-44- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 02 of the EU Prototype Test Certificate PTB 07 ATEX 3053 X

for the three-phase motor, type 1MA7 166-4…

Rated values and data This certificate applies for the following versions on condition that motors of this type only vary to an insignificant extent from the tested sample with regard to the electrical and thermal load:

Star connection

Torque: 62 88 88 35.5 Nm

Power: 0.774 6.6 13.531 10.901 kW

Voltage: *) 40 200 400 400 V

Current: 21 26 26 23.4 A

Frequency: 5 25 50 100 Hz

Speed of rotation: 119 716 1468 2932 min-1

Operating mode: S1

Heat class F

Delta connection

Torque: 62 88 88 75 Nm

Power: 0.774 6.602 23.757 23.235 kW

Voltage: *) 23 115 400 400 V

Current: 36.4 45 46 44.9 A

Frequency: 5 25 87 100 Hz

Speed of rotation: 119 716 2576 2958 min-1

Operating mode: S1

Heat class F

*) Basic oscillation, measured at the motor terminals.

The voltage depends on the input voltage of the frequency inverter, the voltage drop at the filter and over the motor supply cable and may not fall below the design value by more than 5% according to IEC 60034 - 1 Range "A", even with minimum input voltage of the frequency inverter. This must be taken into account for the design of the motor, the parameterisation of the inverter (e.g. rev/f adaptation) and for the minimum input voltage of the inverter. The maximum input voltage of the inverter is 500V.

Adaptation of the design voltage of the motor by means of the number of windings is permissible. The rated current changes in inverse proportion to the rated voltage.

Sheet 1/3

www.nord.com B1092-GB -45-

7. Data Sheets

Translated extract from Data Sheet 02

of the EU Prototype Test Certificate PTB 07 ATEX 3053 X

for the three-phase motor, type 1MA7 166-4…

Monitoring devices To prevent impermissible heating due to overload, the motors are monitored by connection to a device for direct temperature monitoring in combination with defined setting data of the inverter. Due to the special characteristics of motors supplied by inverters and the adapted monitoring device, details of the relationship IA/IN and the heating time tE are not required for motors operated by inverters.

The type of device for direct temperature monitoring has been tested by the Physikalish-Technische Bundesanstalt and consists of three DIN 44082 type M 120 PTCs installed in the windings and a function-tested triggering device according to Guideline 94/9/EU.

With a line current of 186.7 A and a blocked shaft, the PTC must trigger after 22 s (± 20 %) assuming a cold condition (20 °C).

By means of the temperature monitoring device, temperature class T3 as per EN 60079-7 is complied with.

Inverter setting data

In combination with the aforementioned monitoring device, the following inverter data must be set and maintained during operation:

Minimum pulse frequency: 3 kHz

Short-term current limit: 1.5*IN

Maximum overload time: 60 s

Minimum frequency fmin: 5 Hz

Maximum frequency fmax: 100 Y / 100 Δ Hz

Permissible duration of operation at fmin:

60 s

The maximum overload time and the permissible duration of operation at fmin refer to a time period of 10 min.

The relationship of the torque to the frequency results from the permissible continuous current limit.

Sheet 2/3

-46- B1092-GB www.nord.com

7. Data Sheets

Translated extract from Data Sheet 02

of the EU Prototype Test Certificate PTB 07 ATEX 3053 X

for the three-phase motor, type 1MA7 166-4…

The continuous current limit of the frequency inverter must be set dependent on the frequency according to the following diagram:

0,7

0,75

0,8

0,85

0,9

0,95

1

1,05

1,1

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 f / Hz

I /

In

Star connection

Delta connection

Permissible region

Prohibited region

Setting parameters for the continuous current limit of the frequency inverter between 5 Hz and 100 Hz

All other setting data should be selected according to the requirements of the drive unit.

Special conditions

Group operation of the motors is not permissible. Motors of this type may only be operated with inverters which fulfil the requirements stated above under "Inverter setting data". The maximum rated current of the frequency inverter may correspond to double the rated current of the motor. The current monitoring of the frequency inverter must record the effective value of the machine current with a tolerance of ± 5 % in relation to the rated current of the motor. Before start-up it must be ensured that no overvoltages due to the inverter with a peak value in excess of

1556 V (2* 2 *550V) occur at the terminals of the electrical machine.

Test report PTB Ex 07-37125

Certification Facility for Explosion Protection Braunschweig, 4 October 2007

pp

L.S.

Dr.-Ing. F. Lienesch

Senior Government Official Sheet 3/3

www.nord.com B1092-GB -47-

8. Type Plates

-48- B1092-GB www.nord.com

9. Declaration of Conformity

www.nord.com B1092-GB -49-

10. Addresses

Getriebebau NORD national:

North branch Getriebebau NORD GmbH & Co. KG Tel.: +49(0) 4532 / 401-0 Hamburg / Schleswig-Holstein / Postfach 12 62 · 22943 Bargteheide Fax: +49(0) 4532 / 401-253 Niedersachsen Rudolf-Diesel-Straße 1 · 22941 Bargteheide E-mail: [email protected] Sales office Bremen Getriebebau NORD GmbH & Co. KG Tel.: +49(0) 4249 / 9616-75 westliches Niedersachsen / Vertriebsbüro Bremen Fax: +49(0) 4249 / 9616-76 Bremen Wohlers Feld 16 E-mail: [email protected] 27211 Bassum

West branch Getriebebau NORD GmbH & Co. KG Tel.: +49(0) 211 / 99555-0 Köln / Koblenz / Niederlassung West Fax: +49(0) 211 / 99555-45 südl. Nordrhein-Westfalen / Großenbaumer Weg 10 E-mail: [email protected] Ruhrgebiet / Düsseldorf 40472 Düsseldorf Sales Office Butzbach Getriebebau NORD GmbH & Co. KG Tel.: +49(0) 6033 / 9623-0 Hessen / Frankfurt / Vertriebsbüro Butzbach Fax: +49(0) 6033 / 9623-30 Wiesbaden / Darmstadt Marie-Curie-Straße 2 E-mail: [email protected] 35510 Butzbach

East branch Getriebebau NORD GmbH & Co. KG Tel.: +49(0) 371 / 33407-0 Sachsen / südl. Sachsen-Anhalt / Niederlassung Ost Fax: +49(0) 371 / 33407-20 Thüringen Leipziger Straße 58 E-mail: [email protected] 09113 Chemnitz / Sachsen Sales Office Berlin Getriebebau NORD GmbH & Co. KG Tel.: +49(0) 30 / 639794-13 Berlin / Brandenburg Vertriebsbüro Berlin Fax: +49(0) 30 / 639794-14 Mecklenb.-Vorpommern / Roedernstr. 8 E-mail: [email protected] nördl. Sachsen-Anhalt 12459 Berlin

South branch Getriebebau NORD GmbH & Co. KG Tel.: +49(0) 7158 / 95608-0 Stuttgart / Baden-Würtemberg / Niederlassung Süd Fax: +49(0) 7158 / 95608-20 Saarland / südl. Rheinland-Pfalz Katharinenstr. 2-6 E-mail: [email protected] 70797 Filderstadt – Sielmingen Sales Office Nuremberg Getriebebau NORD GmbH & Co. KG Tel.: +49(0) 911 / 67 23 11 Nuremberg / Northern Bavaria Sales Office Nuremberg Fax: +49(0) 911 / 67 24 71 Schillerstraße 3 E-mail: [email protected] 90547 Stein

-50- B1092-GB www.nord.com

10. Addresses

Getriebebau NORD International:

AT Getriebebau NORD GmbH Deggendorfstraße 8, A-4030 Linz Tel.: +43-732-31 89 20 Fax: +43-732-31 89 20-85 [email protected]

AUS NORD Drivesystems 18 Stoney Way 3030 Derrimut Vic, Australia Tel: +61 (0) 488 588 200 [email protected]

BE NORD Aandrijvingen Belgie N.V. Boutersem Dreef 24, B-2240 Zandhoven Tel.: +32-3-484 59 21 Fax: 32-3-484 59 24 [email protected]

BR Nord Motoredutores do Brasil Ltda. Rua Dr. Moacyr Antonio de Morais 700 CEP: 07140-285 São Paulo Tel.: +55-11-64 02 88 55 Fax: +55-11-64 02 88 30 [email protected]

CA Nord Gear Limited 41 West Drive, CDN - Brampton, Ontario L6T 4A1 Tel.: +1-905-796-36 06 Fax: +1-905-796-81 30 [email protected]

CN NORD Drivesystems No. 510 Chang Yang Street, Suzhou Industrial Park, 215021 P.R. China, Jiangsu Province Tel.: +86-512-85180277-191 Fax: +86-512-85180278 [email protected]

HR NORD-Pogoni d.o.o. Obrtnicka 9, HR-48260 Krizevci Tel.: +385-48-71 19 00 Fax: +385-48-27 04 94 [email protected]

CZ NORD-Poháněcí technika, s. r. o. Bečovská 1398/11, CZ 104 00 Praha 10 - Uhříněves Tel.: +420 222 287 222 Fax: +420 222 287 228 [email protected]

DK NORD-Gear Danmark A/S Kliplev Erhvervspark 28 – Kliplev, DK - 6200 Aabenraa Tel.: +45-73 68 78 00 Fax: +45-73 68 78 10 [email protected]

FI NORD Gear Oy Aunankorvenkatu 7, FIN - 33840 Tampere Tel.: +358-3 25 41 800 Fax: +358-3 25 41 820 [email protected]

FR NORD Réducteurs sarl. 17-19 Av. G. Clémenceau, F-93421 Villepinte Cedex Tel.: +33-1 49 63 01 89 Fax: +33-1 49 63 08 11 [email protected]

HU NORD Hajtastechnika Kft. Törökkö u. 5-7, H-1037 Budapest Tel.: +36-1 437 01 27 Fax: +36-1 250 55 49 [email protected]

IN Nord Drivesystem Pvt. LTD 282/2, 283/2, Village Mann, Tal. Mulshi, IN – Pune – 411 057 Tel.: +91-(0)20-39801-200 Fax: +91-(0)20-39801-216 [email protected]

ID PT. NORD Indonesia Jln. Raya Serpong KM7 Kompleks Rumah Multi Guna Blok D-No. 1 Pakulonan, Serpong 15310 – Tangerang - West Java Tel.: +62-21-53 12 22 22 Fax: +62-21-53 12 22 88 [email protected]

IT NORD-Motoriduttori s.r.l. Via Newton 22, IT-40017 San Giovanni In Persiceto (BO) Tel.: +39-051-68 70 711 Fax: +39-051-68 70 793 [email protected]

MX NORD Gear corporation Av. Lázaro Cárdenas 1007 Pte, San Pedro Garza Caría, N.L. MX – 66266 Mexico, C.P. Tel.: +52-81-82 20 91 65 Fax: +52-81-82 20 90 44 [email protected]

NL NORD Aandrijvingen Nederland B.V. Voltstraat 12, NL-2181 HA Hillegom Tel.: +31-252-52 95 44 Fax: +31-252-52 22 22 [email protected]

NO NORD Gear Norge AS Hestehagen 5, PB 1043, N – 1442 Drøbak Tel.: +47-64 90 55 80 Fax: +47-64 90 55 85 [email protected]

PL NORD Napêdy sp. z o.o. Ul. Grottgera 30, PL-32-020 Wieliczka Tel.: +48-012-28 89 900 Fax: +48-012-28 89 911 [email protected]

RU OOO NORD Privody Ul.A. Nevsky 9, RU-191167 St. Petersburg Tel.: +7-812-327 0192 Fax: +7-812-327 0192 [email protected]

SG NORD GEAR Pte. Ltd. 33 Kian Teck Drive, 628850 Jurong - Singapore Tel.: +65-62 65 91 18 Fax: +65-62 65 68 41 [email protected]

SK NORD Pohony, s.r.o. Stromová 13, SK - 831 01 Bratislava Tel.: +421-2-54 79 13 17 Fax: +421-2-54791402 [email protected]

ES NORD Motorreductores S.A. Aptdo. de Correos 166, ES - 08200 Sabadell Tel.: +34 93 72 35 322 Fax: +34 93 72 33 147 [email protected]

SE NORD Drivsystem AB Ryttargatan 277 / Box 2097, SE-19402 Upplands Väsby Tel.: +46-8-59 41 14 00 Fax: +46-8-59 41 14 14 [email protected]

CH Getriebebau NORD AG Bächigenstr.18, CH-9212 Arnegg Tel.: +41-71-38 89 911 Fax: +41-71-38 89 915 [email protected]

TR NORD-Drivesystems Güç Aktarma Sýstemlerý San. Ve. Ltd. Ptý Ticaret Ltd. Sti., TR-34959 - Tuzla - Istanbul Tel.: +90-216-30 41 360 Fax: +90-216-30 41 369 [email protected]

UKR Getriebebau NORD GmbH Vasilkovskaja 1, Office 100/3, Ukr-03040 Kyiv Tel.: +380-44-53 70 615 Fax: +380-44-53 70 615 [email protected]

UK Nord Gear Limited (UK) 11 Barton Lane, Abingdon Science Park, GB-Abingdon, Oxfordshire OX14 3NB Tel.: +44-1235-53 44 04 Fax: +44-1235-53 44 14 [email protected]

US NORD Gear Corporation 800 Nord Drive, P.O. 367, USA-Waunakee, WI 53597 Tel.: +1-608-84 97 300, +1-888-314-6673 Fax: +1-800-373-6673 [email protected]

VN NORD Gear Pte. Ltd Unit 401, 4F, An Dinh Building, 18 Nam Quoc Cang Street Pham Ngu Lao Ward District 1, Ho Chi Minh City, Vietnam Tel: +84- 8 925 7270 Fax: +84 8 925 7271 [email protected]

Intelligent Drivesystems, Worldwide Services

Getriebebau NORD GmbH & Co. KGRudolf-Diesel-Str. 1D - 22941 BargteheideFon +49 (0) 4532 / 401 - 0 Fax +49 (0) 4532 / 401 - [email protected] M

at.-N

r. 60

5270

2/29

10

DRIVESYSTEMS