1. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL ELECTRICAL DRAWINGS. 2. ALL WORK IS NEW UNLESS OTHERWISE NOTED. 3. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK. FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OF OTHER TRADES TO VERIFY SPACE CONDITIONS. MAINTAIN HEADROOM AND SPACE CONDITIONS. 4. SECURE ALL SUPPORTS TO BUILDING STRUCTURE UTILIZING TOGGLE BOLTS (HOLLOW MASONRY), EXPANSION SHIELDS OR INSERTS (CONCRETE AND BRICK), MACHINE SCREWS (METAL), BEAM CLAMPS (FRAMEWORK), WOOD SCREWS (WOOD) OR PAN THRU STRAPS (METAL DECK). NAILS, RAWL PLUGS AND WOOD PLUGS ARE NOT PERMITTED. WHERE REQUIRED BY STRUCTURE, PROVIDE THRU BOLTS AND FISH PLATES. SUPPORT HORIZONTAL RUNS OF METALLIC RACEWAYS NOT MORE THAN 10 FT APART. SUPPORT RACEWAY RISERS AT EACH FLOOR LEVEL. RUN EXPOSED RACEWAYS PARALLEL WITH OR AT RIGHT ANGLES TO WALLS. 5. PASS RACEWAYS OVER WATER, STEAM OR OTHER PIPING WHEN PULL BOXES ARE NOT REQUIRED. NO RACEWAY WITHIN 3 INCHES OF STEAM OR HOT WATER PIPES OR APPLIANCES (EXCEPT PIPE CROSSINGS WHERE RACEWAY SHALL BE AT LEAST 1 INCH FROM PIPE COVERS). 6. CUT CONDUIT ENDS SQUARE. REAM SMOOTH. PAINT MALE THREAD OF FIELD THREADED RACEWAYS WITH GRAPHITE BASE PIPE COMPOUND. DRAW UP TIGHT WITH RACEWAY COUPLING. 7. HORIZONTAL OR CROSS RUNS IN PARTITIONS AND WALLS ARE NOT PERMITTED. DO NOT RUN CONDUIT IN PRECAST ROOF SLABS, IN 2 INCH SLABS OR IN TERRAZZO FLOOR FINISH. 8. LEAVE WIRES WITH SUFFICIENT SLACK TO PERMIT MAKING FINAL CONNECTIONS. RACEWAYS OVER 10 FT LONG IN WHICH WIRING IS NOT INSTALLED: FURNISH FISH WIRE. 9. SET BOXES SQUARE AND TRUE WITH BUILDING FINISH. ERECT WALL AND SWITCH OUTLETS IN ADVANCE OFFURRING AND FIREPROOFING. SECURE TO BUILDING STRUCTURE BY ADJUSTABLE STRAP IRONS. 10. VERIFY LOCATIONS OF OUTLETS AND SWITCHES IN FINISHED ROOMS WITH ARCHITECTURAL DRAWINGS OFINTERIOR DETAILS AND FINISH. IN CENTERING OUTLETS AND LOCATING BOXES AND OUTLETS, ALLOW FOROVERHEAD PIPES, DUCTS AND MECHANICAL EQUIPMENT, VARIATIONS IN FIREPROOFING AND PLASTERING, WINDOW AND DOOR TRIM, PANELING, HUNG CEILINGS AND THE LIKE. CORRECT ANY INACCURACY RESULTING FROM FAILURE TO DO SO WITHOUT EXPENSE TO OWNER. 11. LOCATIONS INDICATED FOR LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS AT OR NEAR DOORS. COORDINATE WITH ARCHITECT AND INSTALL SWITCH ON SIDE OPPOSITE HINGE. VERIFY FINAL HINGELOCATIONS IN FIELD PRIOR TO SWITCH OUTLET INSTALLATION. 12. COVERS OF JUNCTION AND PULLBOXES SHALL BE READILY ACCESSIBLE. 13. PROVIDE PULLBOXES WHERE REQUIRED BY CODE AND WHEREVER NECESSARY TO FACILITATE PULLING OF WIRE. COORDINATE PULLBOX LOCATIONS WITH OTHER TRADES. 14. EMPTY RACEWAY RUNS: PROVIDE PULLBOXES EVERY 100 FT AND AS INDICATED. COORDINATE LOCATIONSWITH OTHER TRADES. 15. JUNCTION AND PULLBOXES: LOCATE GENERALLY NOT EXPOSED IN FINISHED SPACES. WHERE NECESSARY, REROUTE RACEWAYS OR MAKE OTHER ARRANGEMENTS FOR CONCEALMENT. 16. SUPPORT PANEL, JUNCTION AND PULLBOXES INDEPENDENTLY TO BUILDING STRUCTURE WITH NO WEIGHT BEARING ON RACEWAYS. 17. ALL ACCESS DOOR LOCATIONS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL NOTIFY GENERAL CONTRACTOR OF ANY LOCATIONS THAT REQUIRE AN ACCESS PANEL. 18. CONNECT CONDUIT TO MOTOR CONDUIT TERMINAL BOXES WITH FLEXIBLE CONDUIT (MINIMUM 18 IN. LENGTH AND 50% SLACK). DO NOT TERMINATE IN OR FASTEN RACEWAYS TO MOTOR FOUNDATION. 19. PROVIDE 2#14 INDICATING PILOT LIGHT WIRES FROM PILOT LIGHT IN CONTROLLER TO LOAD SIDE OF DISCONNECT SWITCH. RUN WIRES IN BRANCH CIRCUIT CONDUIT AND INCREASE CONDUIT SIZE AS REQUIRED. 20. PULL NO THERMOPLASTIC WIRES AT TEMPERATURES LOWER THAN 32°F (0C). PROVIDE CABLE SUPPORTS FOR WIRE IN RISER CONDUITS AS REQUIRED BY CODE. 21. PROVIDE SEPARATE RACEWAYS FOR CONDUCTORS OF NORMAL AND EMERGENCY CIRCUITS. COMMON BOXES: PROVIDE BARRIERS BETWEEN EMERGENCY AND NORMAL WIRING. 22. HEIGHTS OF OUTLETS FROM FINISHED FLOOR TO CENTERLINE OF OUTLET: RECEPTACLES AND TELEPHONES: GENERALLY 1'-6" OVER WORK BENCHES 3'-6" WALL SWITCHES 4'-0" WALL FIXTURES 7'-0" MOTOR CONTROLLERS 5'-0" GONGS AND HORNS 7'-6" FIRE ALARM STATIONS 4'-0" CLOCKS 7'-6" STROBE LIGHTS 6'-8" TO BOTTOM EXCEPTIONS: AT JUNCTION OF DIFFERENT WALL FINISH MATERIALS, ON MOLDING OR BREAK IN WALL SURFACE, IN VIOLATION OF CODE REQUIREMENTS, AS NOTED OR DIRECTED. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND CONFIRMING ALL MOUNTING HEIGHTS WITH ARCHITECT AND ARCHITECTURAL DRAWINGS. 23. WIRE COLOR CODING: AS PER CODE. WHERE COLOR-CODED CABLE IS NOT AVAILABLE, CERTIFY IN WRITING AND REQUEST PERMISSION FOR OVERLAP COLOR TAPING OF CONDUCTORS (MINIMUM LENGTH 6") INACCESSIBLE LOCATIONS. COLOR CODING, ONCE SELECTED, MUST BE USED CONSISTENTLY FOR THE ENTIREPROJECT. 24. INSTALL NEW WORK AND CONNECT TO EXISTING WORK WITH MINIMUM. INTERFERENCE TO EXISTING FACILITIES. TEMPORARY SHUTDOWNS: ONLY WITH WRITTEN CONSENT OF OWNER. MAINTAIN CONTINUOUS OPERATION OF EXISTING FACILITIES. ALARM AND EMERGENCY SYSTEMS ARE NOT TO BE INTERRUPTED. 25. FIRESTOPPING SHALL BE INSTALLED WHENEVER WIRING OR RACEWAYS CROSS FIRE RATED CONSTRUCTION. 26. REPAIR AND PATCH ANY PENETRATIONS CREATED AS PART OF THIS SCOPE OF WORK. MATCH NEW FINISHES WITH ARCHITECTURAL PLANS. 27. COORDINATE INSTALLATION OF CONDUIT, CABLES, WIRES, AND FIXTURES WITH ALL OTHER TRADES. 28. ANY REQUIRED EXCAVATION AND BACKFILL REQUIRED FOR THIS PROJECT SHALL BE BY THE CONTRACTOR OF EACH TRADES WORK. COORDINATE WITH EACH OTHER TRADE. ELECTRICAL GENERAL NOTES XX XX AIM R RTS H C CD C CD XX CONTROL UNITS (PANELS) SYMBOLS SIGNAL INITIATING DEVICES & ACTIVATION SWITCHES SYMBOLS NOTIFICATION APPLIANCES SYMBOLS FIRE ALARM CONTROL PANEL FIRE ALARM DATA GATHERING PANEL FIRE ALARM ANNUNCIATOR UNINTERRUPTIBLE POWER SUPPLY ELEVATOR STATUS/RECAL NOTIFICATION APPLIANCE SUBSCRIPTS ('XX') WP = WEATHERPROOF WG = WIRE GUARD H = HIGH AUDIBLE SETTING L = LOW AUDIBLE SETTING C = CEILING MOUNT nW = WATTAGE SETTING (n = SPEAKER TAP) P = PENDENT SL = SIGNAL LIGHT RI = REMOTE INDICATOR HORN ONLY C = CEILING MOUNT SPEAKER ONLY C = CEILING MOUNT BELL - SINGLE STROKE BELL - TROUBLE GONG VISIBLE ONLY (STROBE) - WALL MOUNT CD = CANDELA RATING/SETTING VISIBLE ONLY (STROBE) - CEILING MOUNT CD = CANDELA RATING/SETTING COMBINATION HORN/VISIBLE CD = CANDELA RATING/SETTING C = CEILING MOUNT COMBINATION SPEAKER/VISIBLE CD = CANDELA RATING/SETTING C = CEILING MOUNT REMOTE INDICATOR - WALL MOUNT REMOTE ALARM INDICATING AND TEST SWITCH REMOTE INDICATOR - CEILING MOUNT FACP DGP FAA UPS ESR MANUAL STATION - PULL STATION/FIRE ALARM BOX, 'XX' DENOTES TYPE: CO2 = CARBON DIOXIDE DC = DRY CHEMICAL HL = HALON F = FIRE ALARM FO = FOAM WC = WET CHEMICAL CA = CLEAN AGENT WM = WATER MIST DL = DELUGE FIRE SPRINKLER PRE = PREACTION HEAT DETECTOR/SENSOR (THERMAL DETECTION) ORIENTATION NOT TO BE CHANGED HEAT DETECTOR/SENSOR, 'XX' DENOTES TYPE: R/F = COMBINATION RATE OF RISE/FIXED TEMPERATURE R/C = RATE COMPENSATION F = FIXED TEMPERATURE R = RATE OF RISE ONLY SMOKE DETECTOR/SENSOR, 'XX' DENOTES TYPE: AS = AIR SAMPLING P = PHOTOELECTRIC I = IONIZATION R = RELAY BASE SS = SINGLE STATION SB = SOUNDER BASE ID = IN DUCT SMOKE/HEAT DETECTOR/SENSOR COMBINATION SMOKE DETECTION/SENSOR FOR DUCT FLOW DETECTOR/SWITCH TAMPER DETECTOR/SWITCH ADDRESSABLE INPUT MODULE ADDRESSABLE OUTPUT MODULE ADDRESSABLE INPUT/OUTPUT MODULE # DENOTES NUMBER OF INPUTS AND OUTPUTS NON-ADDRESSABLE OUTPUT RELAY XX XX FS TS AOM AIO # RELATED EQUIPMENT DOOR HOLDER DOOR CLOSER END OF LINE RESISTOR ISOLATOR MODULE (STYLE 6 OR 7 FAULT PROTECTION) JUNCTION BOX DH J DCL ISO S C SS T G CD C CD RI RI ELECTRICAL SYMBOLS LIST LIGHTING SYMBOLS POWER SYMBOLS SINGLE LINE DIAGRAM SYMBOLS VOICE/DATA/P.A. SYMBOLS m CB S S 'A' a 'A' NS NS 'A' a 'A' 'A' a 'A' a a a a 'A' NS 'A' a EM a 'A' a 'A' 'A' a 'X' 'X1' 'A' 'A' 'A' 3 a 450 A 100/90/3 1 3, 5, 1 30/3 100/3 100/60/3 90/3 A 1 HA WALL MOUNTED PUBLIC ADDRESS SPEAKER D = DUAL HORN CEILING MOUNTED PUBLIC ADDRESS SPEAKER D = DUAL HORN VOICE & DATA OUTLET LOCATION WITH 3/4" CONDUIT TERMINATED IN A 90 DEG. BEND 6" INTO NEAREST ACCESSIBLE CEILING #/# = # OF VOICE JACKS / # OF DATA JACKS VOICE OUTLET LOCATION WITH 3/4" CONDUIT TERMINATED IN A 90 DEG. BEND 6" INTO NEAREST ACCESSIBLE CEILING P = PUBLIC F = FAX W = WALL MOUNTED 48"AFF # = NUMBER OF JACKS DATA OUTLET LOCATION WITH 3/4" CONDUIT TERMINATED IN A 90 DEG. BEND 6" INTO NEAREST ACCESSIBLE CEILING # = NUMBER OF JACKS TELEVISION OUTLET LOCATION WITH 3/4" CONDUIT TERMINATED IN A 90 DEG. BEND 6" INTO NEAREST ACCESSIBLE CEILING 2'x4'/2'x2' RECESSED FLUORESCENT CEILING MOUNTED FIXTURE 'A' = FIXTURE TYPE 'a' = CONTROLLED BY SWITCH 'a' NS = NOT SWITCHED NL = NIGHT LIGHT SIMILAR TO ABOVE WITH EMERGENCY BACKUP 'A' = FIXTURE TYPE 'a' = CONTROLLED BY SWITCH 'a' RECESSED FLUORESCENT LIGHT FIXTURE ON EMERGENCY LIFE SAFETY CIRCUIT 'A' = FIXTURE TYPE 'a' = CONTROLLED BY SWITCH 'a' WALL MOUNTED FLUORESCENT LIGHT FIXTURE 'A' = FIXTURE TYPE 'a' = CONTROLLED BY SWITCH 'a' NS = NOT SWITCHED NL = NIGHT LIGHT FLUORESCENT STRIP FIXTURE - TYPE AS NOTED 'A' = FIXTURE TYPE 'a' = CONTROLLED BY SWITCH 'a' EM = EMERGENCY BACKUP UNDERCABINET LIGHT FIXTURE 'A' = FIXTURE TYPE RECESSED CEILING MOUNTED FIXTURE 'A' = FIXTURE TYPE 'a' = CONTROLLED BY SWITCH 'a' EM = EMERGENCY BACKUP WALL MOUNTED LIGHT FIXTURE 'A' = FIXTURE TYPE 'a' = CONTROLLED BY SWITCH 'a' EM = EMERGENCY BACKUP ACCENT LIGHT OR WALL WASHER 'A' = FIXTURE TYPE 'a' = CONTROLLED BY SWITCH 'a' EM = EMERGENCY BACKUP CEILING MOUNTED EXIT LIGHT; TYPE 'X' - DIRECTIONAL ARROWS WHERE INDICATED - SHADED AREAS INDICATE ILLUMINATED FACE/FACES WALL MOUNTED EXIT LIGHT; TYPE 'X' - DIRECTIONAL ARROWS WHERE INDICATED - SHADED AREAS INDICATE ILLUMINATED FACE/FACES EMERGENCY BATTERY LIGHT UNIT 'A' = FIXTURE TYPE REMOTE LIGHT HEADS FOR EMERGENCY BATTERY LIGHT UNIT TYPE AS NOTED SINGLE POLE SWITCH a = CONTROLLING OUTLET 'a' 2 = DOUBLE POLE 3 = THREE-WAY 4 = FOUR-WAY D = DOOR K = KEY OPERATED MO = MOMENTARY CONTACT T = TIME SWITCH P = PILOT LIGHT DISCONNECT SWITCH - TOGGLE TYPE WITH THERMAL OVERLOAD DISCONNECT SWITCH - TOGGLE TYPE MOTOR RATED, 20A, 1P, U.O.N. WALL DIMMER - TYPE 'A' NUMBER INDICATES WATTAGE RATING OCCUPANCY SENSOR, CEILING MOUNTED OCCUPANCY SENSOR, WALL MOUNTED PHOTO CONTROL SWITCH SPEAKER BACKBOX 20A, 125V DUPLEX RECEPTACLE - FLUSH WALL MOUNTED CONTROLLED FROM WALL SWITCH 'a' 20A, 125V QUADRUPLEX RECEPTACLE - ABOVE COUNTER - REFER TO ARCH FOR MOUNTING HEIGHT 20A, 125V QUADRUPLEX RECEPTACLE - FLUSH WALL MOUNTED 20A, 125V DUPLEX RECEPTACLE FLUSH WALL MOUNTED. GFI TYPE. 20A, 125V WEATHER RATED DUPLEX RECEPTACLE FLUSH WALL MOUNTED WITH EXTERIOR COVER SINGLE RECEPTACLE - FLUSH WALL MOUNTED FM = FLOOR MACHINE WC = WATER COOLER XR = X-RAY 20A, 125V DUPLEX RECEPTACLE SURFACE MOUNTED 20A, 125V SURGE SUPPRESSION DUPLEX RECEPTACLE. FLUSH WALL MOUNTED FLUSH FLOOR MOUNTED JUNCTION BOX OR POKE-THRU FOR ELECTRIFIED FURNITURE POWER FEED C = VOICE/DATA FEED 20A, 125V DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED 20A, 125V QUADRUPLEX RECEPTACLE FLUSH FLOOR MOUNTED SPECIAL PURPOSE RECEPTACLE - FLUSH WALL MOUNTED A = TYPE SPECIAL PURPOSE RECEPTACLE - FLUSH FLOOR MOUNTED A = INDICATES TYPE PLUG-IN SURFACE METAL RACEWAY - LETTER INDICATES TYPE - WITH SPECIAL PURPOSE RECEPTACLES WHERE INDICATED HOMERUN-NUMERAL WHERE USED INDICATES CIRCUIT NUMBER FOR REFERENCE ONLY. 2#12+1#12G-3/4"C FOR ONE CKT. HOMERUN, U.O.N. 3#12+1#12G-3/4"C FOR TWO CKT. HOMERUN, U.O.N. 4#12+1#12G-3/4"C FOR THREE CKT. HOMERUN, U.O.N. HOMERUN - NUMERAL WHERE USED INDICATES CIRCUIT NUMBER FOR REFERENCE ONLY DIMMER ZONE HOMERUN MOTOR CONTROLLER COMBINATION MOTOR CONTROLLER AND DISCONNECT SWITCH SWITCH AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED UNFUSED DISCONNECT SWITCH SWITCH AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED FUSED DISCONNECT SWITCH; SWITCH AMPS/FUSE AMPS/ # OF POLES, VOLTAGE RATING AS REQUIRED ENCLOSED CIRCUIT BREAKER TRIP AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED NA = NON-AUTOMATIC SURFACE MOUNTED LIGHTING PANELBOARD FLUSH MOUNTED LIGHTING PANELBOARD SURFACE MOUNTED POWER PANELBOARD FLUSH MOUNTED POWER PANELBOARD SURFACE MOUNTED POWER DISTRIBUTION PANELBOARD CEILING MOUNTED JUNCTION BOX WITH FINAL EQUIPMENT CONNECTION FLUSH WALL MOUNTED JUNCTION BOX WITH FINAL EQUIPMENT CONNECTION FLUSH FLOOR MOUNTED JUNCTION BOX a FM C A A B D A OS PC S OS J J J POWER TRANSFORMER VOLTAGES, WINDINGS AND SIZE AS INDICATED AUTOMATIC TRANSFER SWITCH ATS = AUTOMATIC TRANSFER MTS = MANUAL TRANSFER POLES AND RATING AS NOTED MOTOR GENERATOR GROUND CONNECTION FUSED SWITCH 100 AMP SWITCH / 90 AMP/ 3 POLE UNFUSED SWITCH 100 AMP SWITCH / 3 POLE CIRCUIT BREAKER - DRAW OUT TYPE 100 AMP FRAME / 90 AMP TRIP CIRCUIT BREAKER - MOLDED CASE TYPE 90 AMP TRIP / # OF POLES LT = LONG TIME SETTING ST = SHORT TIME SETTING I = INSTANTANEOUS SETTING NETWORK PROTECTOR 2000 AMP FRAME / 1600 AMP TRIP DIGITAL MULTIMETER MEDIUM VOLTAGE CIRCUIT BREAKER 200A CAPACITY MEDIUM VOLTAGE CIRCUIT BREAKER DRAW OUT TYPE - 200A CAPACITY CURRENT TRANSFORMER NUMBER AND RATIO AS INDICATED FUSED SWITCH 100 AMP SWITCH / 90 AMP HOOKSWITCH FUSE - 125A EXPULSION FUSE CURRENT LIMITER LIGHTNING ARRESTOR WITH GROUND CONNECTION CAPACITOR REACTOR COMBINATION MOTOR CONTROLLER AND FUSED DISCONNECT SWITCH; SWITCH AMPS / FUSE AMPS / # OF POLES. VOLTAGE RATING & STARTER SIZE AS REQUIRED COMBINATION MOTOR CONTROLLER AND CIRCUIT BREAKER TRIP AMPS / # OF POLES, VOLTAGE RATING & STARTER SIZE AS REQUIRED 460V 500kVA 120/208V N E L ATS-1 200A 4P M G 100/3 100/90 90/3 2000/1600 M 52 200A 52 200A 3 400/5 100/90 125A 100/90/3 90/3 D S TV S D ## # # K EM EM NL NL EM EM EM PULLBOX EXISTING CONDUIT TO BE REMOVED EXISTING CONDUIT/EQUIPMENT TO REMAIN NEW CONCEALED CONDUIT NEW EXPOSED CONDUIT NEW UNDERGROUND/IN SLAB CONDUIT NEW EMERGENCY CONDUIT CONDUIT TURNING UP CONDUIT TURNING DOWN CONDUIT STUB-UP WITH FLEXIBLE EQUIPMENT CONNECTION FLEXIBLE EQUIPMENT CONNECTION CAPPED CONDUIT PUSH BUTTON K = KEY OPERATED H = HOLD UP P = PANIC SECTION A-A FEEDER DESIGNATION H = 480V L = 208V A = SWITCHBOARD 'A' 1 = FEEDER NUMBER ONE WP + 0 2' 4' 6' 0 8' 16' 24' 0 6" 9" 3" 0 1' 6" 1-6" 0 1/2' 1' 2' 0 1' 2' 3' 0 1' 2' 4' 0 2' 4' 8' 4' 0 8' 16' 0 8' 16' 32' SHEET NUMBER SFA PROJECT NUMBER FULL SHEET SIZE: 30" x 42" REGISTRATION CURRENT ISSUE DRAWING HISTORY SCALE: 1/16" = 1'-0" SCALE: 1/8" = 1'-0" SCALE: 1/4" = 1'-0" SCALE: 1/2" = 1'-0" SCALE: 3/4" = 1'-0" SCALE: 1" = 1'-0" SCALE: 1 1/2" = 1'-0" SCALE: 3" = 1'-0" 1 A CIVIL ENGINEER STRUCTURAL ENGINEER MECHANICAL / ELECTRICAL / PLUMBING FIRE PROTECTION ENGINEER LANDSCAPE ARCHITECT ACOUSTICAL ENGINEER NOTES: DO NOT SCALE DRAWINGS. CONTRACTORS SHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION COPYRIGHT 2016 SFA AUDIO VISUAL ENGINEER 2 3 4 5 6 7 8 9 10 11 12 B C D E F G H I J SECURITY ENGINEER SCALE: 3/32" = 1'-0" SCALE: 3/8" = 1'-0" PROJECT No: MI-1105 C:\Revit Local Files\G150004-000 - Millersville - MEP15_Central_tblancha.rvt E-000 G150004-000 ELECTRICAL COVER SHEET Millersville University LOMBARDO WELCOME CENTER P.O. Box 1002 Millersville, PA 17551-0302 P.O. Box 1002 Millersville, PA 17551-0302 09/28/2016 Derck & Edson 33 South Broad Street Lititz, PA 17543 717-626-2054 Providence Engineering Corporation 10 Eisenhower Blvd. Lancaster, PA 17603 717-509-7000 InPosse 1500 Walnut Street, Suite 1414 Philadelphia, PA 19102 215-282-6800 InPosse 1500 Walnut Street, Suite 1414 Philadelphia, PA 19102 215-282-6800 Derck & Edson 33 South Broad Street Lititz, PA 17543 717-626-2054 N/A N/A N/A ELECTRICAL ABBREVIATIONS KVA KILOVOLT AMPERE KW KILOWATT KWH KILOWATT HOUR LCP LOCAL CONTROL PANEL LIM LINE ISOLATION MONITOR LTG LIGHTING MAP MECHANICAL ALARM PANEL MAX MAXIMUM MCA MINIMUM CIRCUIT AMPERES MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MDP MAIN DISTRIBUTION PANEL MECH MECHANICAL MER MECHANICAL EQUIPMENT ROOM MFS MAIN FUSED SWITCH MH MANHOLE MIC MICROPHONE MIN MINIMUM MLO MAIN LUG ONLY MOPD,MOCP MAXIMUM OVERCURRENT PROTECTION MTD MOUNTED MTG MOUNTING MTS MANUAL TRANSFER SWITCH MUFS MAIN UNFUSED SWITCH N NEUTRAL NIC NOT IN CONTRACT NO NORMALLY CLOSED NO NORMALLY OPEN NP NETWORK PROTECTOR NTS NOT TO SCALE OC ON CENTER OCB OIL CIRCUIT BREAKER OD OUTSIDE DIAMETER P POLE PA PUBLIC ADDRESS PAP PLUMBING ALARM PANEL PB PULL BOX PBS PUSH BUTTON SWITCH PHC PIPE HEATING CABLE PNL PANEL PR PRINTER PS PRESSURE SWITCH PT POTENTIAL TRANSFORMER PWR POWER ø PHASE (RE) RELOCATED EXISTING (RRO) EXISTING TO BE REMOVED AND RETURN TO OWNER RCS REMOTE CONTROL SWITCH RDCP REMOTE DATA COLLECTION PANEL RECEPT,REC RECEPTACLE REF REFRIGERATOR REQ REQUIRED RFL RAISED FLOOR RG ROOM GROUND POINT RM ROOM RO RACEWAY ONLY RP REFERENCE GROUND POINT SAP SPRINKLER ALARM PANEL SBST SUBSTATION SCHED,SCH SCHEDULE SD SMOKE DETECTOR SDP SMOKE DETECTION PANEL SE SINGLE ENDED SUBSTATION SECT SECTION SIG SIGNAL SN SOLID NEUTRAL SP SINGLE POLE SPEC SPECIFICATION SPKLR SPRINKLER SPKR SPEAKER SV SOLENOID VALVE SW SWITCH SWBD SWITCHBOARD SWGR SWITCHGEAR SYM SYMMETRICAL SYS SYSTEMS TB TROUBLE BELL TBD TO BE DETERMINED TEL TELEPHONE TEMP TEMPERATURE THERM THERMOSTAT TLBD TERMINAL BOARD TP TAMPER PROOF TRANSF,XFMR TRANSFORMER TS TAMPER SWITCH TV TELEVISION TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION TYP TYPICAL UFD UNDERFLOOR DUCT UH UNIT HEATER UNF UNFUSED UON UNLESS OTHERWISE NOTED V VOLT OR VOLTAGE VA VOLT AMPERE VP VAPORPROOF WFD VARIABLE FREQUENCY DRIVE WM VOLTMETER W WATT WFS WATERFLOW SWITCH WHM WATT HOUR METER WP WEATHERPROOF WT WATERTIGHT XP EXPLOSION PROOF + SPECIAL MOUNTING HEIGHT. COORDINATE LOCATION WITH ARCHITECTURAL ELEVATIONS 1P SINGLE POLE 2P TWO POLE 3P THREE POLE A AMPERE AC ABOVE COUNTER ACB AIR CIRCUIT BREAKER AFF ABOVE FINISHED FLOOR AIC AMPERE INTERRUPTING CAPACITY AL ALUMINUM ALM ALARM AMM AMMETER AQST AQUASTAT ARF ABOVE RAISED FLOOR ASYM ASYMMETRICAL ATS AUTOMATIC TRANSFER SWITCH AUTO AUTOMATIC AV AUDIO VISUAL AWG AMERICAN WIRE GAUGE BG BREAK GLASS SWITCH BIL BASIC IMPULSE LEVEL BLDG BUILDING C CONDUIT CAB CABINET CAT CATALOG CB CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CKT CIRCUIT CL CENTER LINE CLG CEILING CLOS CLOSET CO CONDUIT ONLY COMM COMMUNICATION CONN CONNECTED CONT CONTINUATION CT CURRENT TRANSFORMER CTL CONTROL CU COPPER CUH CABINET UNIT HEATER DB DECIBEL DE DOUBLE ENDED SUBSTATION DEG DEGREE DF DRINKING FOUNTAIN DIA DIAMETER DISC DISCONNECT DIV DIVISION DN DOWN DP DISTRIBUTION PANEL BOARD DT DUST TIGHT DWG DRAWING °C DEGREE CELSIUS °F DEGREE FAHRENHEIT (E) EXISTING TO REMAIN (ER) EXISTING TO BE REMOVED (ERR) EXISTING TO BE REMOVED AND RELOCATED E.C. EMPTY CONDUIT EA EACH EC ELECTRICAL CONTRACTOR EL ELEVATION ELEC ELECTRICAL ELEV ELEVATOR EMER,EM EMERGENCY EQUIP EQUIPMENT ERC ELECTRIC REHEAT COIL EWC ELECTRIC WATER COOLER EXIST,EX EXISTING EXT EXTERIOR FA FIRE ALARM FACP FIRE ALARM CONTROL PANEL FAP FIRE ALARM ANNUNCIATOR PANEL FBO FURNISHED BY OTHER DIVISION OF WORK FCU FAN COIL UNIT FDR FEEDER FDS FUSED DISCONNECT SWITCH FIXT FIXTURE FL FL FLA FULL LOAD AMPERES FLEX FLEXIBLE FLUOR FLUORESCENT FM FLOOR MACHINE FRZ FREEZER FSP FAN SHUTDOWN PANE; FT FEET OR FOOT G GROUND GEN GENERATOR GFI GROUND FAULT INTERRUPTER HC HUNG CEILING HH HAND HOLE HID HIGH INTENSITY DISCHARGE HN HALF NEUTRAL HP HORSE POWER HV HIGH VOLTAGE HZ HERTZ IC INTERRUPTING CAPACITY ID INSIDE DIAMETER IG ISOLATED GROUND INCAND INCANDESCENT INST INSTRUMENT IPC ISOLATED POWER CENTER IPX ISOLATED POWER CENTER X-RAY JB JUNCTION BOX KCMIL THOUSAND CIRCULAR MILS KV KILOVOLT NO. ISSUE DATE: DESCRIPTION

Transcript of G150004-000 F L R C P E M E-000

Page 1: G150004-000 F L R C P E M E-000

1. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL ELECTRICAL DRAWINGS.

2. ALL WORK IS NEW UNLESS OTHERWISE NOTED.

3. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK. FOLLOWDRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OF OTHER TRADES TO VERIFY SPACE CONDITIONS.MAINTAIN HEADROOM AND SPACE CONDITIONS.

4. SECURE ALL SUPPORTS TO BUILDING STRUCTURE UTILIZING TOGGLE BOLTS (HOLLOW MASONRY), EXPANSIONSHIELDS OR INSERTS (CONCRETE AND BRICK), MACHINE SCREWS (METAL), BEAM CLAMPS (FRAMEWORK), WOODSCREWS (WOOD) OR PAN THRU STRAPS (METAL DECK). NAILS, RAWL PLUGS AND WOOD PLUGS ARE NOTPERMITTED. WHERE REQUIRED BY STRUCTURE, PROVIDE THRU BOLTS AND FISH PLATES. SUPPORT HORIZONTALRUNS OF METALLIC RACEWAYS NOT MORE THAN 10 FT APART. SUPPORT RACEWAY RISERS AT EACH FLOORLEVEL. RUN EXPOSED RACEWAYS PARALLEL WITH OR AT RIGHT ANGLES TO WALLS.

5. PASS RACEWAYS OVER WATER, STEAM OR OTHER PIPING WHEN PULL BOXES ARE NOT REQUIRED. NORACEWAY WITHIN 3 INCHES OF STEAM OR HOT WATER PIPES OR APPLIANCES (EXCEPT PIPE CROSSINGS WHERERACEWAY SHALL BE AT LEAST 1 INCH FROM PIPE COVERS).

6. CUT CONDUIT ENDS SQUARE. REAM SMOOTH. PAINT MALE THREAD OF FIELD THREADED RACEWAYS WITHGRAPHITE BASE PIPE COMPOUND. DRAW UP TIGHT WITH RACEWAY COUPLING.

7. HORIZONTAL OR CROSS RUNS IN PARTITIONS AND WALLS ARE NOT PERMITTED. DO NOT RUN CONDUIT IN PRECASTROOF SLABS, IN 2 INCH SLABS OR IN TERRAZZO FLOOR FINISH.

8. LEAVE WIRES WITH SUFFICIENT SLACK TO PERMIT MAKING FINAL CONNECTIONS. RACEWAYS OVER 10 FT LONG INWHICH WIRING IS NOT INSTALLED: FURNISH FISH WIRE.

9. SET BOXES SQUARE AND TRUE WITH BUILDING FINISH. ERECT WALL AND SWITCH OUTLETS IN ADVANCE OFFURRINGAND FIREPROOFING. SECURE TO BUILDING STRUCTURE BY ADJUSTABLE STRAP IRONS.

10. VERIFY LOCATIONS OF OUTLETS AND SWITCHES IN FINISHED ROOMS WITH ARCHITECTURAL DRAWINGS OFINTERIORDETAILS AND FINISH. IN CENTERING OUTLETS AND LOCATING BOXES AND OUTLETS, ALLOW FOROVERHEAD PIPES,DUCTS AND MECHANICAL EQUIPMENT, VARIATIONS IN FIREPROOFING AND PLASTERING, WINDOW AND DOORTRIM, PANELING, HUNG CEILINGS AND THE LIKE. CORRECT ANY INACCURACY RESULTING FROM FAILURE TODO SO WITHOUT EXPENSE TO OWNER.

11. LOCATIONS INDICATED FOR LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS AT OR NEAR DOORS.COORDINATE WITH ARCHITECT AND INSTALL SWITCH ON SIDE OPPOSITE HINGE. VERIFY FINAL HINGELOCATIONS INFIELD PRIOR TO SWITCH OUTLET INSTALLATION.

12. COVERS OF JUNCTION AND PULLBOXES SHALL BE READILY ACCESSIBLE.

13. PROVIDE PULLBOXES WHERE REQUIRED BY CODE AND WHEREVER NECESSARY TO FACILITATE PULLING OF WIRE.COORDINATE PULLBOX LOCATIONS WITH OTHER TRADES.

14. EMPTY RACEWAY RUNS: PROVIDE PULLBOXES EVERY 100 FT AND AS INDICATED. COORDINATE LOCATIONS WITHOTHER TRADES.

15. JUNCTION AND PULLBOXES: LOCATE GENERALLY NOT EXPOSED IN FINISHED SPACES. WHERE NECESSARY,REROUTE RACEWAYS OR MAKE OTHER ARRANGEMENTS FOR CONCEALMENT.

16. SUPPORT PANEL, JUNCTION AND PULLBOXES INDEPENDENTLY TO BUILDING STRUCTURE WITH NO WEIGHT BEARINGON RACEWAYS.

17. ALL ACCESS DOOR LOCATIONS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR. ELECTRICAL CONTRACTORSHALL NOTIFY GENERAL CONTRACTOR OF ANY LOCATIONS THAT REQUIRE AN ACCESS PANEL.

18. CONNECT CONDUIT TO MOTOR CONDUIT TERMINAL BOXES WITH FLEXIBLE CONDUIT (MINIMUM 18 IN. LENGTHAND 50%SLACK). DO NOT TERMINATE IN OR FASTEN RACEWAYS TO MOTOR FOUNDATION.

19. PROVIDE 2#14 INDICATING PILOT LIGHT WIRES FROM PILOT LIGHT IN CONTROLLER TO LOAD SIDE OF DISCONNECTSWITCH. RUN WIRES IN BRANCH CIRCUIT CONDUIT AND INCREASE CONDUIT SIZE AS REQUIRED.

20. PULL NO THERMOPLASTIC WIRES AT TEMPERATURES LOWER THAN 32°F (0C). PROVIDE CABLE SUPPORTS FORWIRE IN RISER CONDUITS AS REQUIRED BY CODE.

21. PROVIDE SEPARATE RACEWAYS FOR CONDUCTORS OF NORMAL AND EMERGENCY CIRCUITS. COMMON BOXES:PROVIDE BARRIERS BETWEEN EMERGENCY AND NORMAL WIRING.

22. HEIGHTS OF OUTLETS FROM FINISHED FLOOR TO CENTERLINE OF OUTLET:

RECEPTACLES AND TELEPHONES:GENERALLY 1'-6"OVER WORK BENCHES 3'-6"WALL SWITCHES 4'-0"WALL FIXTURES 7'-0"MOTOR CONTROLLERS 5'-0"GONGS AND HORNS 7'-6"FIRE ALARM STATIONS 4'-0"CLOCKS 7'-6"STROBE LIGHTS 6'-8" TO BOTTOM

EXCEPTIONS: AT JUNCTION OF DIFFERENT WALL FINISH MATERIALS, ON MOLDING OR BREAK IN WALL SURFACE, INVIOLATION OF CODE REQUIREMENTS, AS NOTED OR DIRECTED.

CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND CONFIRMING ALL MOUNTING HEIGHTS WITHARCHITECT AND ARCHITECTURAL DRAWINGS.

23. WIRE COLOR CODING: AS PER CODE. WHERE COLOR-CODED CABLE IS NOT AVAILABLE, CERTIFY IN WRITINGANDREQUEST PERMISSION FOR OVERLAP COLOR TAPING OF CONDUCTORS (MINIMUM LENGTH 6") IN ACCESSIBLELOCATIONS. COLOR CODING, ONCE SELECTED, MUST BE USED CONSISTENTLY FOR THE ENTIREPROJECT.

24. INSTALL NEW WORK AND CONNECT TO EXISTING WORK WITH MINIMUM. INTERFERENCE TO EXISTING FACILITIES.TEMPORARY SHUTDOWNS: ONLY WITH WRITTEN CONSENT OF OWNER. MAINTAIN CONTINUOUS OPERATION OFEXISTING FACILITIES. ALARM AND EMERGENCY SYSTEMS ARE NOT TO BE INTERRUPTED.

25. FIRESTOPPING SHALL BE INSTALLED WHENEVER WIRING OR RACEWAYS CROSS FIRE RATED CONSTRUCTION.

26. REPAIR AND PATCH ANY PENETRATIONS CREATED AS PART OF THIS SCOPE OF WORK. MATCH NEW FINISHESWITH ARCHITECTURAL PLANS.

27. COORDINATE INSTALLATION OF CONDUIT, CABLES, WIRES, AND FIXTURES WITH ALL OTHER TRADES.

28. ANY REQUIRED EXCAVATION AND BACKFILL REQUIRED FOR THIS PROJECT SHALL BE BY THE CONTRACTOR OFEACH TRADES WORK. COORDINATE WITH EACH OTHER TRADE.

ELECTRICAL GENERAL NOTES

XX

XX

AIM

R

RTS

HC

CD

CCD

XX

CONTROL UNITS (PANELS) SYMBOLS

SIGNAL INITIATING DEVICES & ACTIVATIONSWITCHES SYMBOLS

NOTIFICATION APPLIANCES SYMBOLS

FIRE ALARM CONTROL PANEL

FIRE ALARM DATA GATHERING PANEL

FIRE ALARM ANNUNCIATOR

UNINTERRUPTIBLE POWER SUPPLY

ELEVATOR STATUS/RECAL

NOTIFICATION APPLIANCE SUBSCRIPTS ('XX')WP = WEATHERPROOFWG = WIRE GUARDH = HIGH AUDIBLE SETTINGL = LOW AUDIBLE SETTINGC = CEILING MOUNTnW = WATTAGE SETTING (n = SPEAKER TAP)P = PENDENTSL = SIGNAL LIGHTRI = REMOTE INDICATOR

HORN ONLYC = CEILING MOUNT

SPEAKER ONLYC = CEILING MOUNT

BELL - SINGLE STROKE

BELL - TROUBLE

GONG

VISIBLE ONLY (STROBE) - WALL MOUNTCD = CANDELA RATING/SETTING

VISIBLE ONLY (STROBE) - CEILING MOUNTCD = CANDELA RATING/SETTING

COMBINATION HORN/VISIBLECD = CANDELA RATING/SETTINGC = CEILING MOUNT

COMBINATION SPEAKER/VISIBLECD = CANDELA RATING/SETTINGC = CEILING MOUNT

REMOTE INDICATOR - WALL MOUNT

REMOTE ALARM INDICATING AND TEST SWITCH

REMOTE INDICATOR - CEILING MOUNT

FACP

DGP

FAA

UPS

ESR

MANUAL STATION - PULL STATION/FIRE ALARM BOX,'XX' DENOTES TYPE:

CO2 = CARBON DIOXIDEDC = DRY CHEMICALHL = HALONF = FIRE ALARMFO = FOAMWC = WET CHEMICALCA = CLEAN AGENTWM = WATER MISTDL = DELUGE FIRE SPRINKLERPRE = PREACTION

HEAT DETECTOR/SENSOR (THERMAL DETECTION) ORIENTATIONNOT TO BE CHANGED

HEAT DETECTOR/SENSOR, 'XX' DENOTES TYPE:R/F = COMBINATION RATE OF RISE/FIXED TEMPERATURER/C = RATE COMPENSATIONF = FIXED TEMPERATURER = RATE OF RISE ONLY

SMOKE DETECTOR/SENSOR, 'XX' DENOTES TYPE:AS = AIR SAMPLINGP = PHOTOELECTRICI = IONIZATIONR = RELAY BASESS = SINGLE STATIONSB = SOUNDER BASEID = IN DUCT

SMOKE/HEAT DETECTOR/SENSOR COMBINATION

SMOKE DETECTION/SENSOR FOR DUCT

FLOW DETECTOR/SWITCH

TAMPER DETECTOR/SWITCH

ADDRESSABLE INPUT MODULE

ADDRESSABLE OUTPUT MODULE

ADDRESSABLE INPUT/OUTPUT MODULE# DENOTES NUMBER OF INPUTS AND OUTPUTS

NON-ADDRESSABLE OUTPUT RELAY

XX

XX

FS

TS

AOM

AIO#

RELATED EQUIPMENTDOOR HOLDER

DOOR CLOSER

END OF LINE RESISTOR

ISOLATOR MODULE(STYLE 6 OR 7 FAULT PROTECTION)

JUNCTION BOX

DH

J

DCL

ISO

SC

SS

T

G

CD

CCD

RI

RI

ELECTRICAL SYMBOLS LISTLIGHTING SYMBOLS

POWER SYMBOLS

SINGLE LINE DIAGRAM SYMBOLS

VOICE/DATA/P.A. SYMBOLS

m

CB

S

S

'A'a

'A'

NSNS 'A'a

'A'

'A'a

'A'a

a a

a'A'NS

'A'a

EM

a'A'

a'A'

'A'a

'X'

'X1'

'A'

'A'

'A'

3a

450

A

100/90/3

13,5,

1

30/3

100/3

100/60/3

90/3

A

1HA

WALL MOUNTED PUBLIC ADDRESS SPEAKERD = DUAL HORN

CEILING MOUNTED PUBLIC ADDRESS SPEAKERD = DUAL HORN

VOICE & DATA OUTLET LOCATION WITH 3/4" CONDUITTERMINATED IN A 90 DEG. BEND 6" INTO NEAREST ACCESSIBLECEILING

#/# = # OF VOICE JACKS / # OF DATA JACKS

VOICE OUTLET LOCATION WITH 3/4" CONDUIT TERMINATED IN A90 DEG. BEND 6" INTO NEAREST ACCESSIBLE CEILING

P = PUBLICF = FAXW = WALL MOUNTED 48"AFF# = NUMBER OF JACKS

DATA OUTLET LOCATION WITH 3/4" CONDUIT TERMINATED IN A90 DEG. BEND 6" INTO NEAREST ACCESSIBLE CEILING

# = NUMBER OF JACKS

TELEVISION OUTLET LOCATION WITH 3/4" CONDUIT TERMINATEDIN A 90 DEG. BEND 6" INTO NEAREST ACCESSIBLE CEILING

2'x4'/2'x2' RECESSED FLUORESCENT CEILING MOUNTEDFIXTURE

'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'NS = NOT SWITCHEDNL = NIGHT LIGHT

SIMILAR TO ABOVE WITH EMERGENCY BACKUP'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'

RECESSED FLUORESCENT LIGHT FIXTURE ON EMERGENCYLIFE SAFETY CIRCUIT

'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'

WALL MOUNTED FLUORESCENT LIGHT FIXTURE'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'NS = NOT SWITCHEDNL = NIGHT LIGHT

FLUORESCENT STRIP FIXTURE - TYPE AS NOTED'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'EM = EMERGENCY BACKUP

UNDERCABINET LIGHT FIXTURE'A' = FIXTURE TYPE

RECESSED CEILING MOUNTED FIXTURE'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'EM = EMERGENCY BACKUP

WALL MOUNTED LIGHT FIXTURE'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'EM = EMERGENCY BACKUP

ACCENT LIGHT OR WALL WASHER'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'EM = EMERGENCY BACKUP

CEILING MOUNTED EXIT LIGHT; TYPE 'X' - DIRECTIONALARROWS WHERE INDICATED - SHADED AREAS INDICATEILLUMINATED FACE/FACES

WALL MOUNTED EXIT LIGHT; TYPE 'X' - DIRECTIONALARROWS WHERE INDICATED - SHADED AREAS INDICATEILLUMINATED FACE/FACES

EMERGENCY BATTERY LIGHT UNIT'A' = FIXTURE TYPE

REMOTE LIGHT HEADS FOR EMERGENCY BATTERY LIGHTUNIT TYPE AS NOTED

SINGLE POLE SWITCHa = CONTROLLING OUTLET 'a'2 = DOUBLE POLE3 = THREE-WAY4 = FOUR-WAYD = DOORK = KEY OPERATEDMO = MOMENTARY CONTACTT = TIME SWITCHP = PILOT LIGHT

DISCONNECT SWITCH - TOGGLE TYPE WITH THERMALOVERLOAD

DISCONNECT SWITCH - TOGGLE TYPE MOTOR RATED, 20A,1P, U.O.N.

WALL DIMMER - TYPE 'A' NUMBER INDICATES WATTAGERATING

OCCUPANCY SENSOR, CEILING MOUNTED

OCCUPANCY SENSOR, WALL MOUNTED

PHOTO CONTROL SWITCH

SPEAKER BACKBOX

20A, 125V DUPLEX RECEPTACLE - FLUSH WALL MOUNTEDCONTROLLED FROM WALL SWITCH 'a'

20A, 125V QUADRUPLEX RECEPTACLE - ABOVE COUNTER -REFER TO ARCH FOR MOUNTING HEIGHT

20A, 125V QUADRUPLEX RECEPTACLE - FLUSH WALLMOUNTED

20A, 125V DUPLEX RECEPTACLE FLUSH WALL MOUNTED.GFI TYPE.

20A, 125V WEATHER RATED DUPLEX RECEPTACLEFLUSH WALL MOUNTED WITH EXTERIOR COVER

SINGLE RECEPTACLE - FLUSH WALL MOUNTEDFM = FLOOR MACHINEWC = WATER COOLERXR = X-RAY

20A, 125V DUPLEX RECEPTACLE SURFACE MOUNTED

20A, 125V SURGE SUPPRESSION DUPLEX RECEPTACLE.FLUSH WALL MOUNTED

FLUSH FLOOR MOUNTED JUNCTION BOX OR POKE-THRUFOR ELECTRIFIED FURNITURE POWER FEED

C = VOICE/DATA FEED

20A, 125V DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED

20A, 125V QUADRUPLEX RECEPTACLE FLUSH FLOORMOUNTED

SPECIAL PURPOSE RECEPTACLE - FLUSH WALL MOUNTEDA = TYPE

SPECIAL PURPOSE RECEPTACLE - FLUSH FLOOR MOUNTEDA = INDICATES TYPE

PLUG-IN SURFACE METAL RACEWAY - LETTER INDICATESTYPE - WITH SPECIAL PURPOSE RECEPTACLES WHEREINDICATED

HOMERUN-NUMERAL WHERE USED INDICATES CIRCUITNUMBER FOR REFERENCE ONLY.

2#12+1#12G-3/4"C FOR ONE CKT. HOMERUN, U.O.N.3#12+1#12G-3/4"C FOR TWO CKT. HOMERUN, U.O.N.4#12+1#12G-3/4"C FOR THREE CKT. HOMERUN, U.O.N.

HOMERUN - NUMERAL WHERE USED INDICATES CIRCUITNUMBER FOR REFERENCE ONLY

DIMMER ZONE HOMERUN

MOTOR CONTROLLER

COMBINATION MOTOR CONTROLLER AND DISCONNECTSWITCH SWITCH AMPS/# OF POLES, VOLTAGE RATING ASREQUIRED

UNFUSED DISCONNECT SWITCHSWITCH AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED

FUSED DISCONNECT SWITCH; SWITCH AMPS/FUSE AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED

ENCLOSED CIRCUIT BREAKERTRIP AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED

NA = NON-AUTOMATIC

SURFACE MOUNTED LIGHTING PANELBOARD

FLUSH MOUNTED LIGHTING PANELBOARD

SURFACE MOUNTED POWER PANELBOARD

FLUSH MOUNTED POWER PANELBOARD

SURFACE MOUNTED POWER DISTRIBUTION PANELBOARD

CEILING MOUNTED JUNCTION BOX WITH FINAL EQUIPMENTCONNECTION

FLUSH WALL MOUNTED JUNCTION BOX WITH FINALEQUIPMENT CONNECTION

FLUSH FLOOR MOUNTED JUNCTION BOX

a

FM

C

A

A

B

D A

OS

PC

S

OS

J

J

J

POWER TRANSFORMERVOLTAGES, WINDINGS AND SIZE AS INDICATED

AUTOMATIC TRANSFER SWITCHATS = AUTOMATIC TRANSFERMTS = MANUAL TRANSFER POLES

AND RATING AS NOTED

MOTOR

GENERATOR

GROUND CONNECTION

FUSED SWITCH100 AMP SWITCH / 90 AMP/ 3 POLE

UNFUSED SWITCH100 AMP SWITCH / 3 POLE

CIRCUIT BREAKER - DRAW OUT TYPE100 AMP FRAME / 90 AMP TRIP

CIRCUIT BREAKER - MOLDED CASE TYPE90 AMP TRIP / # OF POLES

LT = LONG TIME SETTINGST = SHORT TIME SETTINGI = INSTANTANEOUS SETTING

NETWORK PROTECTOR2000 AMP FRAME / 1600 AMP TRIP

DIGITAL MULTIMETER

MEDIUM VOLTAGE CIRCUIT BREAKER200A CAPACITY

MEDIUM VOLTAGE CIRCUIT BREAKERDRAW OUT TYPE - 200A CAPACITY

CURRENT TRANSFORMERNUMBER AND RATIO AS INDICATED

FUSED SWITCH100 AMP SWITCH / 90 AMP

HOOKSWITCH FUSE - 125A EXPULSION FUSE

CURRENT LIMITER

LIGHTNING ARRESTOR WITH GROUND CONNECTION

CAPACITOR

REACTOR

COMBINATION MOTOR CONTROLLER AND FUSEDDISCONNECT SWITCH; SWITCH AMPS / FUSE AMPS / # OFPOLES. VOLTAGE RATING & STARTER SIZE AS REQUIRED

COMBINATION MOTOR CONTROLLER AND CIRCUITBREAKER TRIP AMPS / # OF POLES, VOLTAGE RATING &STARTER SIZE AS REQUIRED

460V500kVA120/208V

NEL

ATS-1200A4P

M

G

100/3

100/90

90/3

2000/1600

M

52 200A

52200A

3400/5

100/90

125A

100/90/3

90/3

DS

TV

S D

##

#

#

K

EM EM

NLNL

EM

EM

EM

PULLBOX

EXISTING CONDUIT TO BE REMOVED

EXISTING CONDUIT/EQUIPMENT TO REMAIN

NEW CONCEALED CONDUIT

NEW EXPOSED CONDUIT

NEW UNDERGROUND/IN SLAB CONDUIT

NEW EMERGENCY CONDUIT

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT STUB-UP WITH FLEXIBLE EQUIPMENTCONNECTION

FLEXIBLE EQUIPMENT CONNECTION

CAPPED CONDUIT

PUSH BUTTONK = KEY OPERATEDH = HOLD UPP = PANIC

SECTION A-A

FEEDER DESIGNATIONH = 480VL = 208VA = SWITCHBOARD 'A'1 = FEEDER NUMBER ONE

WP

+

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

E-000G150004-000

ELECTRICAL COVER SHEET

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

ELECTRICAL ABBREVIATIONSKVA KILOVOLT AMPEREKW KILOWATTKWH KILOWATT HOUR

LCP LOCAL CONTROL PANELLIM LINE ISOLATION MONITORLTG LIGHTING

MAP MECHANICAL ALARM PANELMAX MAXIMUMMCA MINIMUM CIRCUIT AMPERESMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMDP MAIN DISTRIBUTION PANELMECH MECHANICALMER MECHANICAL EQUIPMENT ROOMMFS MAIN FUSED SWITCHMH MANHOLEMIC MICROPHONEMIN MINIMUMMLO MAIN LUG ONLYMOPD,MOCP MAXIMUM OVERCURRENT PROTECTIONMTD MOUNTEDMTG MOUNTINGMTS MANUAL TRANSFER SWITCHMUFS MAIN UNFUSED SWITCH

N NEUTRALNIC NOT IN CONTRACTNO NORMALLY CLOSEDNO NORMALLY OPENNP NETWORK PROTECTORNTS NOT TO SCALE

OC ON CENTEROCB OIL CIRCUIT BREAKEROD OUTSIDE DIAMETER

P POLEPA PUBLIC ADDRESSPAP PLUMBING ALARM PANELPB PULL BOXPBS PUSH BUTTON SWITCHPHC PIPE HEATING CABLEPNL PANELPR PRINTERPS PRESSURE SWITCHPT POTENTIAL TRANSFORMERPWR POWERø PHASE

(RE) RELOCATED EXISTING(RRO) EXISTING TO BE REMOVED AND RETURN TO OWNERRCS REMOTE CONTROL SWITCHRDCP REMOTE DATA COLLECTION PANELRECEPT,REC RECEPTACLEREF REFRIGERATORREQ REQUIREDRFL RAISED FLOORRG ROOM GROUND POINTRM ROOMRO RACEWAY ONLYRP REFERENCE GROUND POINT

SAP SPRINKLER ALARM PANELSBST SUBSTATIONSCHED,SCH SCHEDULESD SMOKE DETECTORSDP SMOKE DETECTION PANELSE SINGLE ENDED SUBSTATIONSECT SECTIONSIG SIGNALSN SOLID NEUTRALSP SINGLE POLESPEC SPECIFICATIONSPKLR SPRINKLERSPKR SPEAKERSV SOLENOID VALVESW SWITCHSWBD SWITCHBOARDSWGR SWITCHGEARSYM SYMMETRICALSYS SYSTEMS

TB TROUBLE BELLTBD TO BE DETERMINEDTEL TELEPHONETEMP TEMPERATURETHERM THERMOSTATTLBD TERMINAL BOARDTP TAMPER PROOFTRANSF,XFMR TRANSFORMERTS TAMPER SWITCHTV TELEVISIONTVSS TRANSIENT VOLTAGE SURGE SUPPRESSIONTYP TYPICAL

UFD UNDERFLOOR DUCTUH UNIT HEATERUNF UNFUSEDUON UNLESS OTHERWISE NOTED

V VOLT OR VOLTAGEVA VOLT AMPEREVP VAPORPROOFWFD VARIABLE FREQUENCY DRIVEWM VOLTMETER

W WATTWFS WATERFLOW SWITCHWHM WATT HOUR METERWP WEATHERPROOFWT WATERTIGHT

XP EXPLOSION PROOF

+ SPECIAL MOUNTING HEIGHT. COORDINATE LOCATION WITHARCHITECTURAL ELEVATIONS

1P SINGLE POLE2P TWO POLE3P THREE POLE

A AMPEREAC ABOVE COUNTERACB AIR CIRCUIT BREAKERAFF ABOVE FINISHED FLOORAIC AMPERE INTERRUPTING CAPACITYAL ALUMINUMALM ALARMAMM AMMETERAQST AQUASTATARF ABOVE RAISED FLOORASYM ASYMMETRICALATS AUTOMATIC TRANSFER SWITCHAUTO AUTOMATICAV AUDIO VISUALAWG AMERICAN WIRE GAUGE

BG BREAK GLASS SWITCHBIL BASIC IMPULSE LEVELBLDG BUILDING

C CONDUITCAB CABINETCAT CATALOGCB CIRCUIT BREAKERCCTV CLOSED CIRCUIT TELEVISIONCKT CIRCUITCL CENTER LINECLG CEILINGCLOS CLOSETCO CONDUIT ONLYCOMM COMMUNICATIONCONN CONNECTEDCONT CONTINUATIONCT CURRENT TRANSFORMERCTL CONTROLCU COPPERCUH CABINET UNIT HEATER

DB DECIBELDE DOUBLE ENDED SUBSTATIONDEG DEGREEDF DRINKING FOUNTAINDIA DIAMETERDISC DISCONNECTDIV DIVISIONDN DOWNDP DISTRIBUTION PANEL BOARDDT DUST TIGHTDWG DRAWING°C DEGREE CELSIUS°F DEGREE FAHRENHEIT

(E) EXISTING TO REMAIN(ER) EXISTING TO BE REMOVED(ERR) EXISTING TO BE REMOVED AND RELOCATEDE.C. EMPTY CONDUITEA EACHEC ELECTRICAL CONTRACTOREL ELEVATIONELEC ELECTRICALELEV ELEVATOREMER,EM EMERGENCYEQUIP EQUIPMENTERC ELECTRIC REHEAT COILEWC ELECTRIC WATER COOLEREXIST,EX EXISTINGEXT EXTERIOR

FA FIRE ALARMFACP FIRE ALARM CONTROL PANELFAP FIRE ALARM ANNUNCIATOR PANELFBO FURNISHED BY OTHER DIVISION OF WORKFCU FAN COIL UNITFDR FEEDERFDS FUSED DISCONNECT SWITCHFIXT FIXTUREFL FLFLA FULL LOAD AMPERESFLEX FLEXIBLEFLUOR FLUORESCENTFM FLOOR MACHINEFRZ FREEZERFSP FAN SHUTDOWN PANE;FT FEET OR FOOT

G GROUNDGEN GENERATORGFI GROUND FAULT INTERRUPTER

HC HUNG CEILINGHH HAND HOLEHID HIGH INTENSITY DISCHARGEHN HALF NEUTRALHP HORSE POWERHV HIGH VOLTAGEHZ HERTZ

IC INTERRUPTING CAPACITYID INSIDE DIAMETERIG ISOLATED GROUNDINCAND INCANDESCENTINST INSTRUMENTIPC ISOLATED POWER CENTERIPX ISOLATED POWER CENTER X-RAY

JB JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILSKV KILOVOLT

NO. ISSUE DATE: DESCRIPTION

Page 2: G150004-000 F L R C P E M E-000

CO

CO

GC

MC

EC

PC/FPC

WV

MH

MH

MH

MH

WV

WV

WV

MH

WV

WV

MH

WV

MH

WV

MH

MH

WV

MH

WV

WV

BENCHMARK

MAG NAIL SET IN

SIDEWALK SEAM

ELEVATION=317.62

EX. BUILDING

GORDINIER HALL

EX. BUILDING

EX. BUILDING

STUDENT MEMORIAL

CENTER

EX.

BUILDING

EX.

BUILDING

EX.

BUILDING

FFE=320.17

FFE=320.21

FFE=320.22

FFE=304.93

C.O.

C.O.

C.O.

C.O.

C.O.

JAMES STREET

( MILLERSVILLE UNIVERSITY)

LOMBARDO WELCOMECENTER

WVWV

UT UT

UT

UT

INSTALL (N)15KV CABLE IN(E)ELECTRICAL DUCTBANK

INTERCEPT (E)ELECTRICALDUCTBANK AT THIS LOCATION

DEDUCT ALTERNATE -TRANSFORMER LOCATION

Z1

TYPICAL MU STANDARDPEDESTRIAN FIXTURE. FIXTUREAND POLE BY OWNER.

(N)DUCTBANK E-1 - REFER TO DETAIL 1/E-002

TO GORDINIER

TO GORDINIER(N) TELECOM DUCTBANKT-1 - SEE DET. 3/E-002

IT ROOM #123 - SEE FLOOR PLAN

(N)GROUNDINGCOUNTERPOISE -REFER TO DET. 8/E-002

(N)DUCTBANK - REFERTO DETAIL 2/E-002

(ER)ABANDONEDDUCTBANK

2

3

12A

2A

4

2A

(N)PAD MOUNTEDTRANSFORMER AND HVL SWITCH -REFER TO DETAIL 5/E-002. PROVIDEHOUSEKEEPING PAD.

PV TRACKER (NOT INCLUDEDIN BASE BID #3). CONNECT TOINVERTER "G1".

Z1

Z1Z1

Z1

Z1

Z1

Z1

Z1

Z1

Z1

Z1

Z1

Z1

Z1Z1Z1

Z1 Z1Z1

Z1

Z1

L2

L2

L2

L2

5

5

5

5

INVERTER "G1" MOUNTEDTO TRACKER SUPPORTG1-1

G1-3

G1-4

G1-2

(E)LOOP FEED SWITCH #7

(E)COMM MANHOLE

(E)COMMMANHOLE MH-10

(E)COMM DUCTBANK

(E)COMM DUCTBANK

(E)COMM DUCTBANK

02

'4

'6

'0

8'

16

'2

4'

06

"9

"3

"0

1'

6"

1-6

"0

1/

2'

1'

2'

01

'2

'3

'0

1'

2'

4'

02

'4

'8

'4

'0

8'

16

'0

8'

16

'3

2'

SHEET NUMBER

SFA PROJECT NUMBER

FULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SC

ALE

: 1/

16

" =

1'-0

"S

CA

LE: 1

/8

" =

1'-0

"S

CA

LE: 1

/4

" =

1'-0

"S

CA

LE: 1

/2

" =

1'-0

"S

CA

LE: 3

/4

" =

1'-0

"S

CA

LE: 1

" =

1'-0

"S

CA

LE: 1

1/

2"

= 1

'-0"

SC

ALE

: 3"

= 1

'-0"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SC

ALE

: 3/

32

" =

1'-0

"S

CA

LE: 3

/8

" =

1'-0

"

PROJECT No: MI-1105

C:\

Revi

t Lo

cal F

iles\

G1

50

00

4-0

00

- M

ille

rsvi

lle -

MEP

15

_C

entr

al_

jbut

z.rv

t

E-001G150004-000

ELECTRICAL SITE PLAN

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1" = 30'-0"1

SITE PLAN

DRAWING NOTES:1. REFER TO E-300 FOR THE SINGLE LINE DIAGRAM. 2. ALL EXCAVTION AND BACKFILL NEEDED FOR ELECTRICAL WORK SHALL BE PERFORMED

BY THE ELECTRICAL CONTRACTOR. REFER TO SITE SPECIFICATION FOR MOREINFORMATION ON EXCAVATION AND BACKFILL REQUIREMENTS.

3. ALL TEMPORARY POWER SHALL BE FED FROM LOOP SWITCH FOR PHASE 2 DORMS.ELECTRICAL CONTRACTOR SHALL CONNECT TO THIS LOOP SWITCH AND PROVIDE POWERFOR A TEMPORARY TRANSFORMER AND TEMPORARY SERVICE FOR THE PROJECT SITEAND ALL TRADES.

4. ALL MAIN ELECTRICAL SERVICE EQUIPMENT SHALL BE PURCHASED BY ELECTRICALCONTRACTOR.

5. ALL EXTERIOR POLE MOUNTED LIGHTING AND BOLLARDS SHALL BE CIRCUITED BACK TO480/277V LIGHTING PANEL AT GORDINIER LOCATED ON FIRST FLOOR.

6. ELECTRICAL CONTRACTOR SHALL INTERCEPT AND REROUTE EXISTING DUCT BANK.CONTRACTOR SHALL PULL 15KV PRIMARY WIRES FROM LOOP FEED SWITCH#7.

7. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL TRADES TO ENSURE THERE IS12 INCH CLEARANCE BETWEEN OTHER TRADES PIPING, ETC...

8. PROVIDE AN ADD ALTERNATE SCOPE ITEM FOR A COMPLETE UL MASTER LABELLIGHTNING PROETECTION SYSTEM LOCATED ON ROOF. REFER TO THE ELECTRICALCONSTRUCTION BID FORM.

9. COORDINATE DUCTBANK DETAILS WITH SINGLE LINE DIAGRAMS FOR CONDUIT ANDFEEDER SIZES. ALL CONDUITS SHALL BE ENCASED IN MIN. 5" CONCRETE ENVELOPEWHERE SHOWN.

10. DUCTBANK/CONDUIT DEPTHS SHALL BE 24" MINIMUM TO 30" MAXIMUM FROM TOP OFDUCTBANK/CONDUIT TO GRADE, UNLESS OTHERWISE INDICATED ON DRAWINGS ORREQUIRED TO PASS OTHER UTILITIES. UNLESS OTHERWISE NOTED, THE MINIMUMDUCTBANK CLEARANCES FROM OTHER UNDERGROUND FACILITIES SHALL BE ASFOLLOWS:

18. BEFORE EXCAVATING, THE ELECTRICAL CONTRACTOR SHALL TAKE ALL POSSIBLEPRECAUTIONS TO LOCATE AND COORDINATE ALL EXISTING UNDERGROUND FACILITIES.

19. LOCATION OF UNDERGROUND CONDUIT RUNS IS DIAGRAMMATIC ONLY. NEW PIPINGSHALL BE INSTALLED AS NECESSARY TO AVOID INTERFERENCE WITH EXISTINGFACILITIES. COORDINATE INSTALLATION OF ALL UNDERGROUND DUCTBANKS, CONDUITSAND MANHOLES WITH CIVIL ENGINEERING DRAWINGS. CIVIL ENGINEERING DRAWINGSSHALL TAKE PRECEDENCE FOR DUCTBANK LOCATIONS.

20. ALL EXISTING WORK, DAMAGED BY ELECTRICAL CONSTRUCTION OPERATIONS, SHALL BEREPAIRED AND RESTORED TO ORIGINAL CONDITION.

21. COORDINATE WITH OWNER ALL EXISTING LANDSCAPE FEATURES (TREES, SHRUBS, ETC.)NOT WISHED TO BE DISTURBED. TAKE PRECAUTIONS TO AVOID DAMAGES.

22. THE CONTRACTOR MUST COORDINATE ALL ELECTRICAL SITEWORK WITH THE SITEWORKCONSULTANT. REFER TO SITE IMPROVEMENT CIVIL ENGINEERING DRAWINGS FORACTUAL DUCTBANK AND CONDUIT LOCATIONS. COORDINATE ALL UNDERGROUND WORKWITH UTILITY COMPANIES.

23. ELECTRICAL CONTRACTOR SHALL PROVIDE HOUSE KEEPING PAD FOR EXTERIORTRANSFORMER. HOUSE KEEPING PAD SHALL BE IN ADDITION TO CONCRETE FLOOR OFGENERAL CONTRACTOR PROVIDED EXCAVATED TRANSFORMER AREA.

24. ELECTRICAL CONTRACTOR SHALL MAINTAIN AND ENSURE ALL EXISTING LIGHTING ISFUNCTIONAL IN PROJECT BOUNDARY DURING THE CONSTRUCTION PROCESS.

25. REFER TO DRAWING E-202 FOR NOTES REGARDING THE PV ARRAY. ALL PV SYSTEMNOTES ON E-202 APPLY TO THE DUAL AXIS TRACKER SHOWN ON THIS PLAN. REFER TO E-002FOR THE DUAL AXIS TRACKER FOUNDATION DETAIL.

A. A DUCTBANK PARALLELING OTHER UNDERGROUND FACILITIES - 24 INCHES.B. A DUCTBANK CROSSES OVER OR UNDER THE TELEPHONE - 3 INCHES OF CONCRETE OR

12 INCHES OF EARTH.C. A DUCTBANK CROSSES OVER OR UNDER GAS AND WATER MAINS OR SEWERS - 12

INCHES OF EARTH.D. THE MULTIPLE CONDUIT RACKS MUST HAVE BASE AND INTERMEDIATE SPACERS

PLACED APPROXIMATELY EVERY 5 FEET.E. ALL 90 DEGREES BENDS MUST BE RIGID GALVANIZED STEEL CONDUIT.F. ALL RIGID STEEL CONDUITS INSTALLED IN DUCTBANK SHALL HAVE BOTH INSIDE AND

OUTSIDE SURFACES PROTECTED AGAINST CORROSION BY A COATING OF ZINC ORENAMEL.

11. WHERE POSSIBLE, CONDUITS SHALL SLOPE 1/8" PER FOOT FROM EXTERIOR EQUIPMENTTO MANHOLE, OR FROM MANHOLE TO MANHOLE AS DETERMINED BY LANDSCAPEFEATURES.

12. ALL CONDUIT AND CABLES ENTERING INTO AND/OR PASSING THROUGH MANHOLESSHALL BE LABELED WITH THEIR CONDUIT NUMBER, SOURCE AND DESTINATION.

13. PROVIDE A PULLWIRE IN ALL SPARE CONDUITS.14. CONDUIT DUCTBANKS EXTERIOR TO THE BUILDING SHALL BE CONCRETE ENCASED

WITH REBAR AS REQUIRED IN DETAILS.15. CONDUIT DUCTBANKS IN THE INTERIOR OF THE BUILDING BELOW THE FLOOR SLAB

SHALL BE DIRECT BURIAL.16. ALL EXISTING DIMENSIONS AND CONDITIONS MUST BE VERIFIED BY CONTRACTOR AT

THE SITE.17. WHERE EQUIPMENT AND CONDUIT ARE TO BE INSTALLED WITHIN LIMITING CONDITIONS,

IT SHALL BE THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO MODIFY DETAILSOR PROVIDE SPECIAL FITTINGS TO SUIT.

KEY NOTES:

TERMINATE TELECOM DUCTBANK INTO EXISTING COMM MANHOLE MH-10. VERIFYEXISTING MANHOLE LOCATION AND ORIENTATION IN FIELD. PENETRATE MANHOLEUSING EXISTING DUCTBANK WINDOW. COORDINATE ALL WORK IN FIELD WITH OWNER.

STUB-UP TELECOM CONDUITS MINIMUM OF 2" ABOVE FINISHED FLOOR SLAB ANDTERMINATE WITH GROUNDING BUSHING. CAP SPARE CONDUIT.

PROVIDE AN ADD ALTERNATE SCOPE ITEM FOR LIGHTNING PROTECTION SYSTEM ONNEW BUILDING THAT IS INSTALLED IN A CONCEALED FASHION.

DISCONNECT AND REMOVE EXISTING ABANDONED COMMUNICATIONS DUCTBANKBACK TO COMM MANHOLE MH-10. COORDINATE EXACT LOCATION IN FIELD WITHEXISTING CONDITIONS AND OWNER. MAINTAIN MANHOLE OPENING FOR NEWDUCTBANK ENTRANCE.

ELECTRICAL CONTRACTOR TO PROVIDE CONCRETE POLE BASE AND INSTALL THEOWNER SUPPLIED LIGHTS.

1

2

3

4

5

NO. ISSUE DATE: DESCRIPTION

PV STRING HOMERUN LEGEND

G1-3

INVERTER NAME

STRING NUMBER

Page 3: G150004-000 F L R C P E M E-000

SCALE: SCALE: SCALE: SCALE: SCALE:

SCALE: SCALE: SCALE: SCALE:

SCALE:

SCALE:

CONDUIT SPACERSSEE SPECIFICATIONS

TOP 1" SHALL BESPRINKLED ANDTHROUGHLYMIXED WITH REDDYE.

7-1/2"MIN.

22"

5"

5" 15-1

/2"

DEPTH ASSPECIFIED

4000PSI CONCRETE

(2) 4" SCH. 40PVC TYPICAL

UNDISTURBED EARTHSEE SPECIFICATIONS

CONDUIT SCHEDULE1- ACTIVE - PRIMARY FEEDER2- SPARE - PULLWIRE ONLY

1 2

5"

5"

FINISHED GRADE

YELLOW LINE MARKER AS SPECIFIED18" BELOW GRADE, ENTIRE WIDTH,OF DUCT BANK - SEE DET. 4/E-002

1

3 4

2

5"M

IN.

7-1/

2"

22"

5"

5"22"

MIN.7-1/2"

5"UNDISTURBED EARTHSEE SPECIFICATIONS

4000PSI CONCRETE

DEPTHASSPECIFIED

FINISHED GRADE

YELLOW LINE MARKER AS SPECIFIED18" BELOW GRADE, ENTIRE WIDTH,OF DUCT BANK - SEE DET. 4/E-002

TOP 1" SHALL BE SPRINKLED ANDTHROUGHLY MIXED WITH RED DYE

CONDUIT SPACERSSEE SPECIFICATIONS

(4) 4" SCH. 40PVC TYPICAL

CONDUIT SCHEDULE1- SPARE, PULLWIRE ONLY2- SPARE, PULLWIRE ONLY

3- ACTIVE - SECONDARY FEEDER4- ACTIVE - SECONDARY FEEDER

CONDUIT SPACERSSEE SPECIFICATIONS

TOP 1" SHALL BESPRINKLED ANDTHROUGHLYMIXED WITH REDDYE.

7-1/2"MIN.

22"

5"

5" 15-1

/2"

DEPTH ASSPECIFIED

4000PSI CONCRETE

(2) 4" SCH. 40PVC TYPICAL

UNDISTURBED EARTHSEE SPECIFICATIONS

CONDUIT SCHEDULE1- ACTIVE - OSP OPTICAL FIBER2- SPARE - PULLWIRE ONLY3- 1"C. - ACTIVE - #6 AWG. INSULATED COPPER FOR DETECTION

1 2

5"

5"

FINISHED GRADE

YELLOW LINE MARKER AS SPECIFIED18" BELOW GRADE, ENTIRE WIDTH,OF DUCT BANK - SEE DET. 4/E-002

3

ZIG-

ZAG

5'-0"

MAX

.

SEE DUCTBANK DETAIL FORACTUAL DEPTH AND WIDTH

ZIG-ZAG YELLOW WARNINGTAPE OVER CONDUITDUCTBANK FOR IT'S ENTIRELENGTHREFER TO SITE PLAN

SIDES OF TRENCH

1. PROVIDE A MINIMUM OF 36" OF CRUSHED GRAVEL AROUND ENTIRE PAD AT 8" IN DEPTH. REFER TO MANUFACTURER FOR OIL CAPACITY TO DETERMINE VOLUME OF GRAVEL BED.

2. DEPTH WILL VARY FOR CONDUIT PENETRATION. MINIMUM DEPTH SHALL BE 36". INCREASE DEPTH FOR CONDUIT PENETRATIONS.

3. REFER TO DETAILS 6 AND 7 ON THIS SHEET.

NOTES:

LOWEST CONDUIT

CRUSHEDGRAVEL

#4 AT 12 EA. WAYEA. FACE

#4 AT 12 TOP & BOT.EA. WAY

4000 P.S.I. CONCRETE

ANCHOR BOLTS PER MANUFACTURER'SREQUIREMENTS.

EDGE OF TRANSFORMER

6"M

IN.

2"10"

CLR3"

10"

GRADE6"M

IN

EXTENDBELOW FROSTLINE OR 36"MIN.

4"

6" X 6" - #8/#8 W.W.F.

A

C

6" WIDE CURBWITH 1" DIAMETER PVC WEEPS

OPENING TOSTRUCTURAL PAD

SECONDARYCONDUITS/DUCTBANKFRONT ELEVATION

PLAN

1#4 CONT. IN CURB

WEEPS (TYP.)

SECTION

SEE NOTE 8

WEEPS (TYP.)PRIMARYCONDUITS/DUCTBANK

STRUCTURAL PADSEE DETAIL X/E6.X

NOTE 2

MIN

.6" 1"

CLR

9 NOTE 1

3

REINFORCING BARS3" CLEAR

NOTES:

SIDE ELEVATIONB

5

6

4

7

5 USE 4000 PSI MINIMUM CONCRETE STRENGTH.

3 SECONDARY CONDUITS SHALL TERMINATE NO LESS THAN 1" ABOVE HOUSEKEEPING PAD.

2. SIZE OF HOUSEKEEPING DRAINAGE PAD TO BE PER MANUFACTURER'S RECOMMENDATIONS.

1. SEE EXTERIOR OIL FILLED TRANSFORMER PAD DETAIL. OTHERWISE USE 6" MIN. (TYP.)

8 PROVIDE 4" LONG, 2 X 2 MIN. ZEE SHAPE OF #10 GAUGE GALVANIZED SHEET STEEL FOR EACH WEEP AND FASTEN TO STRUCTURAL PAD WITH 1/2" STAINLESS STEEL HILTI QUICK BOLTS.

7 FASTEN TRANSFORMER TO PAD PER MANUFACTURER'S RECOMMENDATIONS.

6 STRUCTURAL PAD SHALL BE CONSTRUCTED

WITH NO OPENINGS, EXCEPT F0R CDTS,

GROUND ROD ACCESSWELL (TYP. FOR 3) SEEDETAIL X

3/4" X 10'-0" LONG COPPERGROUND ROD. (TYP. FOR 3)

#2/0 BARE, STRANDEDCOPPER CABLE

10'- 0" ALL SIDES

LL

L

(4) 1/2" x 15" HOT DIP GALVANIZEDSTEEL ANCHOR BOLTS ON A Ø8.91"BOLT CIRCLE AT 90°

N.T.S.1 PRIMARY ELECTRICAL DUCTBANK E-1N.T.S.2 SECONDARY ELECTRICAL DUCTBANK E-2

N.T.S.3 TELECOM DUCTBANK T-1N.T.S.5 EXTERIOR OIL FILLED TRANSFORMER PAD

N.T.S.6 PADMOUNT DRAINAGE PADN.T.S.7 PADMOUNT DRAINAGE PAD

N.T.S.8 EXTERIOR GROUND ROD CONFIGURATIONN.T.S.9 CONDUIT SERVICE ENTRANCE

N.T.S.11 BOLT DIAGRAM FOR Z1 FIXTURE

N.T.S.12 HANOVER LANTERN POLE BASE

N.T.S.10 PV TRACKER FOUNDATION

4 UNDERGROUND DUCTBANK MARKERNTS

4" [RIGID STEEL][SCHEDULE 80PVC] CONDUIT. 48"RADIUS MINIMUM.

REFER TO MFR. SHOPDRAWINGS FOREXACT LOCATION.

CONDUIT COUPLING ORTRANSITION FITTING AS REQUIRED

CRUSHED STONE

FINISHEDFLOOR SLAB

CONCRETEPAD SEEDETAIL

FINISHED INSTALLATIONOF CONDUIT STUB UPINCLUDING BUSHINGSHALL NOT EXCEED 3"ABOVE FINISHEDCONCRETE

[SWITCHGEAR][SUBSTATION] ENCLOSURE, SEE FLOOR PLANS AND DETAILS

4 PROVIDE EPOXY BONDING COMPOUND WHERE HOUSEKEEPING PAD BEARS ON STRUCTURAL PAD.

HOUSEKEEPINGDRAINAGE PADSEE PLAN C

FRONT OFFIXTURE

BOLT CIRCLE � 8.91"

.8"

2.50" OPENFOR CONDUIT

PLATE 11"

15"

2" EXPOSEDTHREAD

APROX. 3/4" GAP:FILL WITH GROUT

LEVELINGWASHERSAND NUTS

CONDUIT(BY OTHERS)

MOUNTING DETAIL

HANOVER LANTERN POLEBY OWNER

ANCHOR BOLTS, NO. AND SIZEAS REQUIRED BY POLE MANUF.

16" X 16" SQUARE FIELDFORMED CONCRETE BASETO 6" BELOW GRADE.REMAINDER OF BASE TOBE 18" DIAMETER

PROVIDE ANCHORBOLTS AS REQUIRED BYPOLE MANUFACTURER

FINISHED GRADE OR PAVING

#4 HOOP @ 12"O.C. SPACING

SCH. 40 PVC CONDUIT WITHCIRCUIT WIRING (SIZE ANDQUANTITY PER PLAN). TRANSITIONTO RIGID GALVANIZED STEELCONDUIT 5'-0" BEFORE POLEAND FOR STUB UP INTO POLE

3000# CONCRETE

3" MIN. CLEARALL SIDES

3'0"

24"M

IN.

1" X 45°CHAMFERALL SIDES

6"

ANCHOR POLE TOCONCRETE BASE ASREQUIRED BY POLEMANUFACTURER

6 #5 VERTICALREINFORCINGBARS

SCALE:

9 PRIMARY CONDUITS SHALL TERMINATE NO MORE THAN 1" ABOVE STRUCTURAL PAD.

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

E-002G150004-000

ELECTRICAL SITE DETAILS

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION

Page 4: G150004-000 F L R C P E M E-000

ST

B115

B1INV#2

B1INV#5

B115

B115

B115

B115

B1INV#2

B115

B1INV#5

B115

B115

B115

B1INV#5

B115

B115

W4INV#3

X1

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

B115

B115

B115

EMNL

EMNL

EM

EM

EM

B115

EM

ECU INV#5 ECU INV#3

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

E-100G150004-000

ELECTRICAL LOWER LEVELPLAN - LIGHTING

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN

DRAWING NOTES:

1. REFER TO E-400 FOR THE LIGHTING FIXTURE SCHEDULE AND LIGHTING CONTROLS SCHEDULE.2. ALL LIGHTS SHALL BE CIRCUITED TO PANEL LP UNLESS OTHERWISE NOTED.3. ALL SWITCHES SHALL BE GRAY WITH STAINLESS STEEL FACE PLATES UNLESS OTHERWISE

NOTED.4. ALL EMERGENCY FIXTURES SHALL BE CONNECTED TO CENTRAL BATTERY INVERTER.5. PROVIDE EMERGENCY CONTROL UNITS SUCH AS WATTSTOPPER ELCU-200 OR BODINE BLCD-20B

ON ALL FIXTURES ON EMERGENCY POWER. THESE FIXUTRES SHALL BE WIRED SO THAT THEYARE CONTROLLED WITH ADJACENT FIXTURES WITHOUT SWITCHING TO THE INVERTER. UPONLOSS OF POWER ALL EMERENCY LIGHT FIXTURES SHALL COME TO FULL ON REGARDLESS OFLIGHTING CONTROL SWITCH POSITION.

6. ALL EXIT SIGNS AND NIGHT LIGHTS SHALL BE CIRCUITED AS UNSWITCHED.

NO. ISSUE DATE: DESCRIPTION

Page 5: G150004-000 F L R C P E M E-000

SD

ST ST ST

VS VS VS

VS

VSVS

VS VS

VS

VS

VS

VS

VS VS

OS

OS

S OS

S OS

OSOS

OS

OS

OS

OS OS OS OS

OS

OS

OS OS OS OS OS OS

OS

OS OS OS OS OS OS

OS

OS

SDSD

SDSD

SD

SD SDSDSD

SD SD SD

SD

SD

STST

S T

SD

SD

SDaSDb

SDa SDb

OS

OSOS

OS OS

OS

OS

OS

OS

SOR

SD

SD

SOR

SDS

KP

SDa

SDa SDb

SDb

OS

OS

VSPC PC PC

PC

PC PCPC

PCPC

PC PCPC PC

PC

PC

PC

PC

VS PC

OSVS

SKP

SDc

SDc

S D

VS

S DSD

DRAWING NOTES:

1. REFER TO E-400 FOR THE LIGHTING FIXTURE SCHEDULE AND LIGHTING CONTROLS SCHEDULE.2. ALL SWITCHES SHALL BE GRAY WITH STAINLESS STEEL FACE PLATES UNLESS OTHERWISE NOTED.3. ALL CONDUIT RUNS IN EXPOSED CEILING AREAS SHALL BE MINIMAL AND SHALL RUN IN CLEAN LINES

AND WILL BE OF HIGH WORKMANSHIP QUALITY. CONCEAL CONDUIT RUNS WHERE POSSIBLE.CONDUIT ALONG THE WALLS/CEILING WHERE APPROPRIATE. FINISH OF SURFACE MOUNTEDCONDUIT SHALL MATCH WALL OR CEILING COLOR OF SPACE.

4. ALL LIGHTS SHALL BE CIRCUITED TO PANEL LP UNLESS OTHERWISE NOTED.5. ALL WIRING DONE IN LOBBY AREA SHALL BE CONCEALED BEHIND CURTAIN WALL FRAMING.6. ALL LOBBY PENDANTS, P1, SHALL BE MOUNTED AT 15'-0'' AFF.7. ALL EMERGENCY FIXTURES SHALL BE CONNECTED TO CENTRAL BATTERY INVERTER8. PROVIDE EMERGENCY CONTROL UNITS SUCH AS WATTSTOPPER ELCU-200 OR BODINE BLCD -20B ON

ALL FIXTURES ON EMERGENCY POWER. THESE FIXUTRES SHALL BE WIRED SO THAT THEY ARECONTROLLED WITH ADJACENT FIXTURES WITHOUT SWITCHING TO THE INVERTER. UPON LOSS OFPOWER ALL EMERENCY LIGHT FIXTURES SHALL COME TO FULL ON REGARDLESS OF LIGHTINGCONTROL SWITCH POSITION.

9. ALL EXIT SIGNS AND NIGHT LIGHTS SHALL BE CIRCUITED AS UNSWITCHED.

KEY NOTES:

PROVIDE AND INSTALL ROOM CONTROLLERS LMRC-211 AND LMBC-300 ABOVE CEILINGS.REFER TO WIRING DIAGRAM ON E-400 FOR MORE INFORMATION.

PROVIDE AND INSTALL ROOM CONTROLLERS LMRC-211, LMRC-213, AND LMBC-300 ABOVECEILIGNS. REFER TO WIRING DIAGRAM ON E-400 FOR MORE INFORMATION.

PROVIDE AND INSTALL ROOM CONTROLLERS LMRC-212 AND LMBC-300 ABOVE CEILINGS. REFERTO WIRING DIAGRAM ON E-400 FOR MORE INFORMATION.

PROVIDE 2 GANG BOX FOR SWICHES AT THIS LOCATION.

PROVIDE 3 GANG BOX FOR SWITCHES AT THIS LOCATION. ALIGN SWITCHES UNDERNEATHOCCUPANCY SENSOR.

FIXTURE SHALL CONTINUE THE WHOLE LENGTH OF THE MULLION AND MOUNTED AT 16'-0'' AFF.

LOCATE ALL P1 REMOTE DRIVERS ABOVE EPIC DECK CEILING.

MOUNT EXIT SIGNS ABOVE GLASS TRANSOM AT 10'-0'' ON WALL.

MOUNT EXIT SIGN ABOVE DOOR, 11'-0'' AFF.

MOUNT EXIT SIGNS ABOVE GLASS TRANSOM AT 9'-0'' ON WALL.

MOUNT EXIT SIGN BETWEEN WOOD SLOT CEILING AT 9'-0''. COORDINATION WITH WOOD SLOTCEILING SHALL BE DONE IN FIELD.

OVERRIDE SWITCHES SHALL CONTROL CORRIDOR LIGHTING ONLY.

PROVIDE 4 FOOT EMERGENCY SECTION IN LIGHTING FIXTURE.

PROVIDE AND INSTALL ROOM CONTROLLERS LRMC-213 AND LMBC-300, ABOVE CEILING, FORALL CORRIDOR LIGHTING CIRCUITS. REFER TO WIRING DIAGRAM ON E-400 FOR MORE

INFORMATION.

PROVIDE AND INSTALL ROOM CONTROLLERS LMRC-212 AND LMBC-300FOR ALL EXTERIORLIGHTING CIRCUITS. REFER TO WIRING DIAGRAM ON E-400 FOR MORE INFORMATION.

PROVIDE AND INSTALL A WATTSTOPPER SEGMENT MANAGER LMSM-3E LOCATED INENCLOSURE LMSM-ENC1. PROVIDE AND INSTALL LMSM-CONNECT ON SEGMENT MANAGER.

PROVIDE AND INSTALL TWO (2) ROOM CONTROLLERS LMRC-213 AND LMBC-300, ABOVE EPICDECK, FOR ALL LOBBY LIGHTING CIRCUITS . REFER TO WIRING DIAGRAM ON E-400 FOR MOREINFORMATION.

BOXED IN AREA SHALL BE CONTROLLED BY PHOTOCELLS, OCCUPANCY SENSORS, ANDDIMMING SWITCHES LOCATED IN AREA.

A1INV#5

B1INV#5

B1INV#5

B111

A14

A14 A1

4

A16

A16

A16

A16

A16

A11

A11

A13

A13

A11

A13

A13

A13

A13

A13

A11

A1A5

A1A5

A1A2

A1A2

A1A2

A1A2

A1A2

A1A2

A18

A1INV#2

A18

D1INV#2

D1INV#2

D18

D1INV#5

D1INV#2

D1INV#2D1

INV#2

D16

D16

D16

A16A1

11

A111

P112

P112

P112

A1A5

D1INV#5

D1INV#2

D113

A211

A211

A2INV#5

X1

X1B

X1B

X1A

X1

X1

D113

D113

A14

A14

A1A5

A17

A1A2

A1INV#1

A1A2

A16

A1A5

A1A5

A18

A1A5

A1INV#1

A1A5

A18D1

8D1INV#1

D18

D1INV#2

D1INV#1

D18

D18

D1INV#1

D18

D1INV#2

A17

A17

W116

W119

W114

W114

A17

A17

D12

D110

P110

P1INV#2

P117

P117

P117

P117

P117

P117

P117

P1INV#2

P2INV#7

P212P2

INV#7

P2INV#7

P212P2

INV#7

D113

A16

A1INV#1

A1INV#1

A16

EM NL

EM NL EM NL

EM NL

EM NL

EM NL

EM NL

EM NL

a

a

a b

aa

a

aa

a

bc

c A18

A18

A16

A18

A16

A18

1

1

1

1

11

111

1 11 1

11 1

1 1

1

1

3

A16

A16

NL

EMNL

NL

INV#6EM

EM NL

EM NL

18

18 18

2

5

5

4

4

W3INV#3

A311

A311

W119

W119

6

6

LV

LV

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

VEST.V-1

ALCOVEL101-5

WOMEN'S143

PASSAGE104

MEN'S142

ALCOVEL101-6JANITOR

141

MECHANICAL141.1

FAMILYTOILET

144

STORAGE140.1

PASSAGEL101-7

VEST.V-2

CLASSROOM/PRESENTATIONROOM

140

V.P. OFFICE112A

SMALL CONF.105

STORAGE103.1

OFFICE112

PASSAGEL101-1

OFFICE118

OFFICE114

OFFICE116

OFFICE110

OFFICE108

OFFICE104

CORRIDORC 1-1

CORRIDORC 1-2

BREAK ROOM107

STORAGE119

ELEC. RM.121

COFFEESTATIONL101-3

STORAGE103.2

ADMISSIONSOPEN OFFICE

106

HOUSINGOPEN OFFICE

130

OFFICE128

OFFICE126

OFFICE124

OFFICE122

MARKETINGOPEN OFFICE

120

SMALL CONF.115

CONFERENCE117

I.T. ROOM123

CALL CENTER109

CORRIDORC 1-3

OFFICE102

WORK ROOM111

RESOURCEROOM

103

RECEPT.L101-2

STUDENTWORK SPACE

113

LOBBYL101

8

8

9

X1A9

10

11

11

6

6

W2INV#3

W2INV#4

W116

12

12

A111

LP

LCP

aP212

P212a

EM

EM

EM

EM EM EM

EMEMEMEM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

INV#7EM

EM

17

17

17INV#6EM13

13

INV#7EM

INV#7EM

13

14

15

15

ECU INV#4

ECU INV#7

ECU INV#5

ECU INV#1

ECU INV#7

1

1

P2A8

P2A8

P2A8

P2A8

P2A8

1

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

E-101G150004-000

ELECTRICAL GROUNDFLOOR PLAN - LIGHTING

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

NO. ISSUE DATE: DESCRIPTION

18

Page 6: G150004-000 F L R C P E M E-000

WP

J

W

WP

TS

TS

TS

TS

TS

TS

FS

F

MDP

RP2#4

PVP

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

HP2#2,4

HP2#10,12HP2#6,8

HP2#1,3

GYLOCL SKID

HP2#5

MDP

MDP

HP2#20,22

ACCU-1

EF-1HP2#7

HP2#17EF-2

400APV UTILITYDISCONNECT

TVSS FOR PVP

PV NET METER

P-1

P-2

1

1

1

RP2#23

RP2#23

RP2#23 RP2#23

RP2#4

UTILITY METER

MEP SHAFT

PROVIDE J-BOXFOR FLOODCONTROLVALVE HP2#21

HP2#23HP2#28

BAS CONTROL PANELS

HP2#30,32

P-4HP2#9

P-3HP2#16

GROUND BUS BAR

HP-19

HP-20 HP-21

HP-22 HP-23

HP-23MDP

HP2

2 - 2 INCH CONDUITSTO ELECTRICALROOM

2 - 2 INCH CONDUITSTO ELECTRICALROOM

FEEDER METERS

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

E-200G150004-000

ELECTRICAL LOWER LEVELPLAN - POWER

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN

DRAWING NOTES:

1. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OFRECEPTACLES, DISPLAYS, AND FIRE ALARM DEVICES IN ALL SPECIALITY AREAS.

2. REFER TO E-000 FOR COMPLETE SYMBOLS LIST AND GENERAL NOTES.3. REFER TO E-300 FOR SINGLE LINE DIAGRAM.4. REFER TO E-401 FOR ELECTRICAL PANEL SCHEDULES.5. ALL RECEPTACLES SHALL BE GRAY WITH STAINLESS STEEL FACE PLATES UNLESS OTHERWISE

NOTED.6. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER CONNECTIONS TO ALL

MECHANICAL EQUIPMENT. REFER TO MECHANICAL DRAWINGS FOR ADDITONAL MECHANICALEQUIPMENT INFORMATION.

7. PROVIDE COMPLETE FIRE ALARM SYSTEM WITH BATTERY BACKUP FOR EMERGENCY POWER.

1

KEY NOTES:

PROVIDE DISCONNECT IN WATERPROOF ENCLOSURE.

NO. ISSUE DATE: DESCRIPTION

Page 7: G150004-000 F L R C P E M E-000

15cd

15cd

15cd

30cd 30cd 30cd 30cd

15cd

15cd

60cd60cd30cd

15cd30cd

60cd

60cd

15cd

30cd

15cd

135cd

F

J J

J

J

JJ

J

J

F

15cd

30cd

30cd30cd 15cd

WP

WP

WP

J

J

J

J

J

J

S

SS

S

S

S

S

S

S

S

S

S

S

S

S SS

SS

J

J

J

J

15cd

15cd

30cd

F

J

J

J

J

J

J

J

J

J

W

W

J

J

15cd

15cd

15cd

15cd

J

J

JJ

JJJ

J

J

J

J

J

J

J

J

J

J

15cd

HH

H

H

H

H

HHHH

15cd

15cd

HH

DRAWING NOTES:

1. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OFRECEPTACLES, DISPLAYS, AND FIRE ALARM DEVICES IN ALL SPECIALITY AREAS.

2. REFER TO E-000 FOR COMPLETE SYMBOLS LIST AND GENERAL NOTES.3. REFER TO E-300 FOR SINGLE LINE DIAGRAM.4. REFER TO E-401 FOR ELECTRICAL PANEL SCHEDULES.5. ALL RECEPTACLES SHALL BE GRAY WITH STAINLESS STEEL FACE PLATES UNLESS OTHERWISE

NOTED.6. ALL CONDUIT RUNS IN EXPOSED CEILING AREAS SHALL BE MINIMAL AND SHALL RUN IN CLEAN LINES

AND WILL BE OF HIGH WORKMANSHIP QUALITY. CONCEAL CONDUIT RUNS WHERE POSSIBLE.CONDUIT ALONG THE WALLS/CEILING WHERE APPROPRIATE. FINISH OF SURFACE MOUNTEDCONDUIT SHALL MATCH WALL OR CEILING COLOR OF SPACE.

7. ALL CABLING SHALL SHALL BE DONE IN CORRDIOR ON J-HOOKS ALONG THE INTERIOR WALL OFTHE OPEN OFFICE AREA, ABOVE THE CEILING.

8. ALL WIRING DONE IN LOBBY AREA SHALL BE CONCEALED BEHIND CURTAIN WALL FRAMING.9. PROVIDE BRANCH CIRCUIT METERING FOR ALL BRANCH CIRCUITS IN PANELS MDP, RP1, RP2, LP,

HP1, AND HP2. PROVIDE NETWORK CONNECTION FROM BRANCH CIRCUIT METERS TO CAMPUSMETERING COMPUTER FOR REMOTE MONITORING OF LOADS. ALL METERING SHALL BEMILLERSVILLE CAMPUS STANDARD SMART METERING FROM E-MON D-MON.

10. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER CONNECTIONS TO ALLMECHANICAL EQUIPMENT. REFER TO MECHANICAL DRAWINGS FOR ADDITONAL MECHANICALEQUIPMENT INFORMATION.

11. PROVIDE COMPLETE FIRE ALARM SYSTEM WITH BATTERY BACKUP FOR EMERGENCY POWER.12. PROVIDE DEDICATED 1" CONDUIT BETWEEN FIRE ALARM SYSTEM CONTROL PANEL AND THE IDF

ROOM FOR NETWORK CONNECTIVITY TO THE CAMPUS FIRE ALARM SYSTEM.13. ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT TO ANY SPEAKERS INDICATED ON THE

DRAWINGS AND TERMINATE AT STORAGE ROOM 140.1. CONFIRM WITH OWNER FINAL TERMINATIONOF CONDUIT AND SPECIFIC POWER REQUIREMENTS.

14. ELECTRICAL CONTRACTOR SHALL PROVIDE POWER TO ALL PROJECTORS AND BACKBOXES FORANY IT/AV NEEDED.

15. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER AND CONTROL WIRINGASSOCIATED WITH MECHANICAL SHADES.

16. ALL CONDUIT ABOVE WOOD SLAT CEILING SHALL BE PAINTED WHITE. COORDINATE FINAL PAINTINGDETAILS WITH ARCHITECT.

17. ELECTRICAL CONTRACTOR SHALL PURCHASE TV MOUNT BACK BOX, PAC525, AND INSTALL ALLNECESSARY POWER CONNECTIONS TO TELEVISION.

18. POWER AND DATA DEVICES SHOWN ON OFFICE FURNITURE ARE DIAGRAMMATIC. FINAL LOCATIONSAND REQUIREMENTS SHALL BE PROVIDED BY FURNITURE VENDOR. COORDINATE WITH FURNITUREVENDOR EXACT DATA AND POWER REQUIREMENTS REQUIRED FOR OFFICE FURNITURE.ELECTRICAL CONTRACTOR SHALL CONNECT TO FURNITURE WHIP TO OWNER PROVIDED PRE-WIRED FURNITURE.

19. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL BACK BOXES, FLOOR BOXES, AND CONDUITSTO DATA DEVICES. CABLING WILL BE PROVIDED BY OTHERS.

20. ALL DISCONNECTS FOR HEATPUMPS AND VAV UNITS SHALL BE MOUNETED ON OR ADJACENT TOUNITS AND SHALL BE CONCEALED ABOVE CEILING.

KEY NOTES:

WIREWAY SHALL BE SIMILAR TO LEGRAND AL2400. WIREWAY SHALL BE INSTALLED AT BASEOF CURTAIN WALL. SEE ARCHITECTURAL DRAWINGS FOR MOUNTING DETAILS. CONFIRMFINISH OR WIREWAY WITH ARCHITECT.

UNDERSLAB CONDUIT PATHWAY TO OPEN OFFICE FURNITURE. PROVIDE THREE (3) 3/4 INCHCONUDITS.

PROVIDE CAT 6 PATH FROM DEVICE BACK TO MDF ROOM. PROVIDE PULL WIRES IN ALL OFTHESE CONDUITS.

LOCATE DEVICES WITHIN RECEPTION DESK. REFER TO ARCHITECTURAL DRAWINGS FOREXACT LOCATION.

PROVIDE HAND DRYER XLERATOR FROM EXCEL, MODEL NUMBER XL-*-ECO. CONFIRM COLOROF HAND DRYER WITH ARCHITECT.

RP1

LPHP1

+

+

+

+

+

FOR TV

FOR TVLCP

FLOOR BOX FOR FURNITURE WHIP

FLOOR BOXFOR FURNITURE WHIP

FOR FURNITURE WHIP

FACP

FAP

FOR FURNITUREWHIP

FLOOR BOX -POWER ANDDATA

FLOOR BOX -POWER ANDDATA

RP2

RP1#28

RP1#28RP1#28

RP1#17

RP1#17

RP1#17

RP1#33

RP1#33

RP1#33

RP1#16

RP1#16

RP1#31

RP1#36

RP1#36

RP1#36

RP1#36

RP1#19 RP1#19 RP1#38 RP1#38

RP1#39

RP1#8

RP1#8

RP1#8

RP1#15

RP1#15RP1#15

RP2#13

RP2#18

RP1#23

RP1#40 RP1#39

RP2#31

RP2#31

RP1#27

RP1#27

RP1#27

RP1#1

RP1#1

RP1#1

RP1#5

RP1#5

RP1#5

RP1#24

RP1#24 RP1#24

RP1#14 RP1#14RP1#14

RP1#26RP1#25

RP1#31

RP1#16

RP1#22

RP1#22

RP1#6

RP1#6

RP1#11

RP2#18

RP2#22

RP2#18

RP2#18

RP2#15

RP1#14

RP2#8

RP1#35

RP1#35

RP1#27

RP1#34

RP1#30

RP1#18

RP1#7

RP1#7RP1#9

RP1#10 RP1#10

RP1#12 RP1#13RP1#10RP1#9

RP1#12

RP1#12 RP1#13RP1#7

RP1#21 RP1#21

RP1#9

RP2#25

RP2#7

RP2#7

RP2#13

RP2#18

RP2#20

RP2#20

RP2#20

RP1#35

RP1#18

RP1#18

RP1#38

RP1#25

RP1#27

RP1#26

RP1#24

RP1#40

RP1#23

RP1#21

RP1#28RP1#3

RP1#2

RP1#11RP1#4

RP1#32

RP2#28

RP2#34

RP2#21

RP1#29

RP1#20

RP2#1

RP2#2

RP2#3

FOR REF.

FOR DISHWASHER

FOR REF.

BOTTLEFILLER

+

EWH-1-2

EWH-1-1

RP2#15RP1#16

+

RP1#31

RP1#31

RP1#31

RP1#31

RP1#37

RP1#37

RP1#37

RP1#37

RP1#37

RP1#37

RP2#36

RP1#39 RP1#22

RP1#40RP1#23

RP2#6

RP2#10

RP2#10

RP2#12+

+

HP-5

HP-4

HP-3

HP-2

HP-1

HP-8

HP-7HP-6

HP-10

HP-11

HP-9

HP-12

HP-14

HP-13

HP-15

HP-16

HP-17

HP-18

RP1#19

HP1#30,32

HP1#37,39

HP1#38,40

HP1#34,36

HP1#33,35

HP1#17,19

HP1#10,12

HP1#9,11HP1#6,8

HP1#5,7

HP1#13,15

HP1#2,4HP1#1,3

HP1#14,16

HP1#21,23

HP1#22,24

HP1#25,27

HP1#18,20

HP1#26

HP1#28

RP2#22

HP2#14 HP2#14

HP2#14

HP2#14

HP2#14

HP2#14

HP2#14

HP1#29

HP1#29

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

VEST.V-1

ALCOVEL101-5

WOMEN'S143

PASSAGE104

MEN'S142

ALCOVEL101-6JANITOR

141

MECHANICAL141.1

FAMILYTOILET144

STORAGE140.1

PASSAGEL101-7

VEST.V-2

CLASSROOM/PRESENTATIONROOM140

V.P. OFFICE112A

SMALL CONF.105

STORAGE103.1

OFFICE112

PASSAGEL101-1

OFFICE118

OFFICE114

OFFICE116

OFFICE110

OFFICE108

OFFICE104

CORRIDORC 1-1

CORRIDORC 1-2

BREAK ROOM107

STORAGE119

ELEC. RM.121

COFFEESTATIONL101-3

STORAGE103.2

ADMISSIONSOPEN OFFICE

106

HOUSINGOPEN OFFICE

130

OFFICE128

OFFICE126

OFFICE124

OFFICE122

MARKETINGOPEN OFFICE

120

SMALL CONF.115

CONFERENCE117

I.T. ROOM123

CALL CENTER109

CORRIDORC 1-3

OFFICE102

WORK ROOM111

RESOURCEROOM103

RECEPT.L101-2

STUDENTWORK SPACE

113

LOBBYL101

RP2#22

RP2#10

RP2#10

1

1

STACKDEVICESON WALL

ADA DOOROPERATOR

ADA DOOROPERATOR

VAVB-7

VAVB-8

VAVB-9

VAVB-10

VAVB-11

VAVB-6

VAVB-5

VAVB-3

VAVB-2VAVB-1

POWER FORADA DOOROPERATOR

POWER FORADA DOOROPERATOR

POWER FOR OWNER PROVIDEDSIGN. TERMINATE CIRCUIT ATFOUNDATION WALL. REFER TODETAIL 2/A1.02 FORTERMINATION DETAIL.

LP#18

RP2#16

RP2#11

HAND DRYERS

HANDDRYER

RP2#12+

+

FORDASHBOARD

VAVB-4

HP1#29HP1#29

TF-1

HP1#31

HP2#15BR-1

HP2#15BR-1

HP2#18BR-1

HP2#18BR-1

AC-1

HP2#11,13

CEILINGMOUNTEDPROJECTOR

CEILING MOUNTPROJECTOR

RP2#20

FLOOR BOX -POWER ANDDATA

RP2#24

RP2#24

FORMOTORIZEDSHADES

FORMOTORIZEDSHADES HP2#19

HP2#26

MOTORIZEDSHADESCONTROLLER

2 2

RP2#22

RP2#22

RP2#24

RP2#24

VAV-1

HP1#29

RP2#27

RP2#26

RP2#29

+

+FORMONITOR

RP2#30

3

3

3

INV

+

FORMICROWAVE

+RP2#19

+

RP2#32RP2#14

RP2#9

HP2#25,27

BACK BOX FORCARD READER

BACK BOX FORCARD READER

BACK BOX FORCARD READER

BACK BOX FORCARD READER

BACK BOX FORCARD READER

AC-2

BACK BOXFOR CARDREADER

HAND DRYERS

RP1#35

RP2#33

KNOX BOXFIRE ALARMCONNECTION.

+

+

RP2#12

RP2#12

+

+

BACK BOX FORCARD READER

BACK BOX FORCARD READER

FLOOR BOXFOR FURNITURE WHIP

FLOOR BOXFOR FURNITURE WHIP

FLOOR BOXFOR FURNITURE WHIP

FLOOR BOXFOR FURNITURE WHIP

POWER FORFAUCETS

POWER FORFAUCETS

RP2#17

POWER FORFAUCETS

RP2#25

TV

4

5

5

DOOR POWER

DOOR POWER

DOOR POWER

DOOR POWER

HP2#29

HP2#29

HP2#31

HP2#31

HP2#29

HP2#29

HP2#29

HP2#31

HP2#31

DOOR POWER

DOOR POWER

DOOR POWER

TV

+

+RP1#22

INCOMING 4"CONDUIT

02'

4'

6'

08'

16'

24'

06"

9"

3"

01'

6"

1-6"

01/2'

1'

2'

01'

2'

3'

01'

2'

4'

02'

4'

8'

4'

08'

16'

08'

16'

32'

SHEET NUMBER

SFA PROJECT NUMBER

FULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCALE: 1/16" = 1'-0"

SCALE: 1/8" = 1'-0"

SCALE: 1/4" = 1'-0"

SCALE: 1/2" = 1'-0"

SCALE: 3/4" = 1'-0"

SCALE: 1" = 1'-0"

SCALE: 1 1/2" = 1'-0"

SCALE: 3" = 1'-0"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCALE: 3/32" = 1'-0"

SCALE: 3/8" = 1'-0"

PROJECT No: MI-1105

C:\Revit Local Files\G150004-000 - M

illersville -

MEP15_Central_skaplan.rvt

E-201G150004-000

ELECTRICAL GROUNDFLOOR PLAN - POWER

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1

GROUND FLOOR PLAN

1

2

3

NO. ISSUE DATE: DESCRIPTION

4

5

Page 8: G150004-000 F L R C P E M E-000

ALL PV PANELS ON THIS ROOF SHALL BE BASIS OF DESIGN TYPE SPR-E20-327 SUNPOWER CORP. PANELS MOUNTED ON BASIS OF DESIGNRACKING SYSTEM TYPE HELIX DT - EAST/WEST 10 DEGREE TILT BYSUNPOWER COPR. PANELS SHALL BE STRUNG AS INDICATED BYCIRCUITING AND HOME RUNS.

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

INV.E7

E4-6E7-1

E5-2E1-2

ALL PV PANELS ON THIS ROOF SHALL BE BASIS OF DESIGN TYPESPR-E20-327 SUNPOWER CORP. PANELS MOUNTED ON BASIS OFDESIGN RACKING SYSTEM TYPE HELIX DT - EAST/WEST 10 DEGREETILT BY SUNPOWER COPR. PANELS SHALL BE STRUNG ASINDICATED BY CIRCUITING AND HOME RUNS.

ALL PV PANELS ON THE ROOF SHALL BE BASIS OF DESIGN TYPESPR-X21-345 SUNPOWER CORP. PANELS MOUNTED ON BASIS OFDESIGN STANDING METAL SEAM ROOF CLAMP SYSTEM. PANELSSHALL BE STRUNG AS INDICATED BY CIRCUITING AND HOME RUNS.

FACADE MOUNTED BIPV: GLASS PANELS AT TOP AND BOTTOM OFCUTRAIN WALL SHALL HAVE GLASS INTEGRATED SOLAR CELLS. BASISOF DESIGN SYSTEM BY ONYX GLASS. MOUNTING SHALL BE ASINDICATED ON ARCHITECTURAL PLANS. PANELS SHALL BE STRUNG ASINDICATED BY CIRCUITING AND HOME RUNS. PANELS SHALL CONNECTTO DESIGNATED COMBINER BOX OR OTHER SIMILAR FUSED DC POWERCOMINATION METHOD. REFER TO 3/E202 FOR ELEVATION. (NOTINCLUDED IN BASE BID #3)

FACADE MOUNTED BIPV: GLASS PANELS AT TOP AND BOTTOM OFCUTRAIN WALL SHALL HAVE GLASS INTEGRATED SOLAR CELLS. BASISOF DESIGN SYSTEM BY ONYX GLASS. MOUNTING SHALL BE ASINDICATED ON ARCHITECTURAL PLANS. PANELS SHALL BE STRUNG ASINDICATED BY CIRCUITING AND HOME RUNS. PANELS SHALL CONNECTTO DESIGNATED COMBINER BOX OR OTHER SIMILAR FUSED DC POWERCOMINATION METHOD. REFER TO 3/E202 FOR ELEVATION. (NOTINCLUDED IN BASE BID #3)

E7-2 E4-5

E7-4 E4-2

INV.E3

INV.E4

E8-1

E3-6 E8-2

E3-1

ACCB1

E3-5

E3-2

INV.C3

INV.C1

ACCB2

INV.W1

INV.W2

ACCB4

W2-3

W2-1

W1-5

W2-2

W2-6

W1-1W1-2

W1-3

W2-4

W1-4

ACCB3

INV.E6

INV.E5

INV.E1

C4-2

C4-4 C4-5C4-3

C2-3

C1-6

MAINTAIN A MINIMUM OF 3'-6"BETWEEN THE PANELS AND THEROOF EDGE.

EW

INV.E2

INV.F2

1

1

1

1

1

INV.C2

W2-5

MAINTAIN A MINIMUM OF 2'-6"BETWEEN THE PANELS AND THEROOF EDGE.

MAINTAIN A MINIMUM OF 2'-6"BETWEEN THE PANELS AND THEROOF EDGE.

PROVIDE A MINIMUM 1'-6" WIDEMAINTENCE ACCESS AISLE.

MAINTAIN A MINIMUM OF 3'-6"BETWEEN THE PANELS AND THEROOF EDGE.

MAINTAIN A MINIMUM OF 2'-6"BETWEEN THE PANELS AND THEROOF EDGE.

PROVIDE A MINIMUM 1'-0" WIDEMAINTENCE ACCESS AISLE.

MAINTAIN A MINIMUM OF 2'-6"BETWEEN THE PANELS AND THEROOF EDGE.

C3-1 C3-2C4-1

C3-4 C3-3C2-5

C3-5 C3-6C2-4

C2-6

C2-2

C2-1

INV.C4

C1-5

C1-1C1-2

C1-4

C1-3

INV.F1

INV.E8

E4-3

E7-3

E7-5

E8-3

E8-4

E8-5

E5-1E1-1

E5-3E1-3

E5-4E1-4

E5-5E1-5

E5-6E1-6

E6-2E2-2

E6-1E2-1

E4-4

E4-1

E3-4E3-3

E7-6

E6-3E2-3

E6-4E2-4

E6-5

E6-6

E2-5

E2-6

L PNM Q RJH

9

12

6

14

4

15U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8L PNM Q RJHE FGLJL PNM Q RJHE FG

BUILDING INTEGRATED PV GLASS TO BE INSTALLED BYGC IN THESE LOCATIONS. EC SHALL WIRE BIPV TOINVERTER F1. (SCOPE OF WORK NOT INCLUDED INBASE BID #3)

INV F2 INV F1

BUILDING INTEGRATED PV GLASS TO BE INSTALLEDBY GC IN THESE LOCATIONS. EC SHALL WIRE BIPV TOINVERTER F2. (SCOPE OF WORK NOT INCLUDED INBASE BID #3)

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

E-202G150004-000

ELECTRICAL ROOF PLAN -POWER

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 ROOF BASE PHOTOVOLTAIC SYSTEM LAYOUT

DRAWING NOTES:

1. REFER TO E-300 FOR THE SINGLE LINE DIAGRAM AND INVERTER SCHEDULE.2. REFER TO SPECIFICATION SECTION 263100 FOR ADDITIONAL SYSTEM INFORMATION INCLUDING RACKING

SYSTEM TYPES AND PV PANEL MANUFACTURER INFORMATION.3. FINAL LAYOUT OF THE PV ARRAY SHALL BE DOCUMENTED BY THE PV CONTRACTOR. CONTRACTOR SHALL

PROVIDE COMPLETE DOCUMENTATION INCLUDING LAYOUT, STRINGING, EQUIPMENT, AND PREDICTEDENERGY GENERATION CALCULATIONS.

4. THIS PROJECT IS PURSUING NET ZERO ENERGY. THE FINAL INSTALLED SYSTEM SHALL PROVIDE ACALCULATED MINIMUM OF 201,000 KWH ANNUALLY THAT INCLUDES A DERATING FACTOR FOR POTENTIALSNOW LOAD.

5. NOT ALL PV ARRAYS INDICATED ARE INCLUDED IN BASE BID #3. IF ROOF TOP ARRAY CAN NOT GENERATETHE CALCULATED MINIMUM ENERGY FOR NET ZERO ENERGY THEN THIS SHOULD BE NOTED INDOCUMENTATION FOR BASE BID #3. THE FINAL SYSTEM MUST CALCULATE OUT TO PROVIDE THE MINIMUMENERGY NEEDED FOR NET ZERO ENERGY.

6. CONTRACTOR SHALL PROVIDE A COMPLETE PV SYSTEM, INCLUDING PANELS, RACKING, WIRING,DISCONNECTS, INVERTERS, ETC. THE CONTRACTOR SHALL PROVIDE DC COMBINER BOXES IF THEY AREREQUIRED FOR THE CONTRACTOR SELECTED INVERTER. THE CONTRACTOR SHALL ALSO PROVIDE ALLDATA CABLE WIRING REQUIRED TO NETWORK CONNECT THE INVERTERS TO THE BUILDING MANAGEMENTSYSTEM AND FOR ANY ENERGY DATA REQUIRED FOR THE BUILDING DASHBOARD SYSTEM.

7. REFER TO E-001 FOR THE LOCATION OF THE DUAL AXIS TRACKER PV SUB-ARRAY.

SCALE: 1/16" = 1'-0"2 ROOF ALTERNATE PV PANEL LAYOUT FOR OTHER APR. MANUFACTURER

SCALE: 1/16" = 1'-0"3 SOUTH FACADE

STRING HOMERUN LEGEND

E1-3

INVERTER NAME

STRING NUMBER

NO. ISSUE DATE: DESCRIPTION

KEY NOTES:

WIRING FROM CENTER HIGH ROOF PV SHALL BE RUN CONCEALED DOWN TO LOWER ROOF. RUNALL WIRING DOWN THE FACADE CONCEALED IN ENLARGED MULLIONS INDICATED.

1

Page 9: G150004-000 F L R C P E M E-000

Y

(AWG/KCMIL)WIRE SIZE

CONDUCTOR PHASEAND NEUTRAL GROUND 1PH, 2W+G

A

No. OF WIRES AND CONDUIT SIZE

B3PH, 3W+G 3PH, 4W+G

C

(IN INCHES)TAGSAMPS

HP-WOAU-1 M M

100A/3P 175A/3P 175A/3P 40A/2P225A/3P

700A/3P

40A/2P 30A/2P

LP30 POLE 208/120V

100A MCB

RP1 42 POLE 208/120V

125A MCB

HP142 POLE 208/120V

125AMCB

HP242 POLE 208/120V

125AMCB

RP2 42 POLE 208/120V

100A MCB

M M

MMMM

HVL SWITCH

30A/3P

M M M MM M M

WIRE & CONDUIT SIZING SCHEDULE

= = =

= == == = == = == ===

800A/3P

'MDP' 208/120V, 3 , 4W, 1200A, 65,000 AIC

12.48KV PRIMARY

GF

1 2

700A/3P

100A/3P

24C

225A/3P

3

10C

208/120V SECONDARY

125A/3P

11C

24B

4

100A/3P

5 6

225KVA

LIGHTINGPANELPANEL

MECH

15C

7 8 129 11

100A/3SPACE

100/3SPACE

UTILITY METER LOCATED AT BUILDING

125A/3P

PANELMECH

11C

TO INCOMINGMILLERSVILLE CAMPUSLOOP FEED SWITCH #7

10

700ADISCONNECT

60A/3P 40A/3P 60A/3P40A/3P

6B

6B

4B

4B

4B

4B

6B

6B

10C

NET METER FOR PV SYSTEM - LOCATED IN BUILDING

EASTERN ROOF PV ARRAYCENTER ROOF PV ARRAY

PVPANEL

PVPANEL

PVPANEL

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

PVPANEL

PVPANEL

STR4

STR5

PVPANEL

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR5

STR4

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

WESTERN ROOF PV ARRAY

10B 13B 13B 15B

PVP 208V, 3P, 800A

AC CB2 AC CB1 AC CB3

AC CB4

12KW

P-1 P-2

Voc MAX DCCOLDEST

MAX DCCURRENT

MINIMUM WIRE & CONDUIT SIZEFOR PV STRING

PV INVERTER INFORMATION

C18 AWG CONDUCTORS &

GROUND PV WIRE IN WEATHERTIGHT INSULATION

12KW 480V3 INVERTER

FRONIUS SYMO20.1" x 28.5" x 8.9"

NUMBER OFMPPT

2

2

2

C2

C3

E1

E2

E3

E4

E5

E6

12KW 480V3 INVERTER

3 INVERTER

8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER

TIGHT INSULATION8 AWG CONDUCTORS &

GROUND PV WIRE IN WEATHERTIGHT INSULATION

8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER

TIGHT INSULATION8 AWG CONDUCTORS &

GROUND PV WIRE IN WEATHERTIGHT INSULATION

8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER

TIGHT INSULATION8 AWG CONDUCTORS &

GROUND PV WIRE IN WEATHERTIGHT INSULATION

8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER

TIGHT INSULATION8 AWG CONDUCTORS &

GROUND PV WIRE IN WEATHERTIGHT INSULATION

INVERTERLETTER

MODELNUMBER

DIMENSIONSWxDxH

NOTE:1. THE ABOVE SCHEDULE IS BASED ON 600 VOLT WIRE TYPE THWN/XHHW AND EMT/RGS CONDUIT

700

800

600

500

200

450

400

300

250

275

225

175

125

150

70

100

90

80

30

50

60

40

20

15

24

25

23

22

14

21

20

19

18

16

17

15

13

11

12

10

9

7

8

3

5

6

4

1

2

3/0

500

350

250

300

.

4/0

1/0

2/0

1

1

2

4

3

10

6

4

8

12

14

6

3

3

4

4

4

4

.

6

6

6

8

8

8

8

10

10

10

10

14

12

350 500

(2)500

(2)500

(2)350

(2)250

(2)4/0

(2)1/0

(2)1/0

(2)1

(2)2

(2)2

(2)4 (2)4

NUMBER INDICATES FEEDER SIZE IN AMPS AND WIRELETTER INDICATES CONDUIT SIZE AND NUMBER OF WIRES2B

2

1 1/4

1 1/4

1

1

3/4

3/4

1

3/4

3/4

3/4

1 1/4

1 1/4

2

1 1/4

3/4

1

1 1/4

3/4

3/4

3/4

2 1/2

3

11/4

1 1/4

1 1/4

3/4

3/4

3/4

3/4

1

1 1/4 1 1/2

1 1/2

1 1/2 2

2

221 1/2

1 1/2 2 2 1/2

2 1/22

2

2 1/2

3

2 1/2

4 4

3

3 3

32 1/2

2 1/2

3 4 4

(2)4 (2)4

(2)2 1/2(2)2 1/2

(2)2 1/2

(2)3

(2)3

(2)4

SPACE

F1

AC

INV G1

1 1 1 1

26.2"x25.6"x10.4"8 AWG CONDUCTORS &

GROUND PV WIRE IN WEATHERTIGHT INSULATION

7.5KW 208V1 INVERTER 600V 30A 1

NOT INCLUDEDIN BASE BID #3

TO BIPV GLASS PANELS

SPACE

MAX ACCURRENT

32A

4A

20.1" x 28.5" x 8.9"

20.1" x 28.5" x 8.9"12KW 208V

41.5A 33.3A

FRONIUS SYMO

FRONIUS SYMO

FRONIUS IG PLUS ADV.

DCDC

INV F1

AC

NOT INCLUDEDIN BASE BID #3

DCDC

TO BIPV GLASS PANELS

INV F2

AC

NOT INCLUDEDIN BASE BID #3

DCDC

AC

INV W1

DC

DCMPPT1 MPPT2

15KW

AC

INV W2

DC

DC

PVPANEL

STR6

PVPANEL

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR5

STR4

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

INV C3

PVPANEL

STR6

PVPANEL

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR5

STR4

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

AC

INV C2

DC

DC

PVPANEL

STR6

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR4

STR3

STR2

STR1

TO ADDITIONAL SOLARTRACKER PV PANELS.

PVPANEL

PVPANEL

PVPANEL

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

AC

INV C4

DC

DC

12KW

MPPT1 MPPT2

12KW 12KW

MPPT1 MPPT2

PVPANEL

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR5

STR4

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

INV C1

PVPANEL

STR6

12KW

AC

DC

DCMPPT1 MPPT2

AC

DC

DCMPPT1 MPPT2

PVPANEL

PVPANEL

STR4

STR5

PVPANEL

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR5

STR4

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

INV E7

PVPANEL

STR6

TO ADDITIONAL PV PANELS.

AC

INV E4

DC

DC

TO ADDITIONAL PV PANELS.

INV E812KW

MPPT1 MPPT2

12KW 12KW

PVPANEL

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR5

STR4

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

INV E3

PVPANEL

STR6

12KW

AC

DC

DCMPPT1 MPPT2

AC

DC

DCMPPT1 MPPT2

PVPANEL

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR5

STR4

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

INV E5

PVPANEL

STR6

PVPANEL

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR5

STR4

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

INV E2

DC

PVPANEL

STR6

AC

INV E6

DC

DC

15KW 15KW 15KW

PVPANEL

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR5

STR4

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

INV E1

PVPANEL

STR6

15KW

AC

DC DC

W1

W2

12KW 208V3 INVERTER

15KW 208V3 INVERTER

600V 41.5A 2

1

8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER

TIGHT INSULATION8 AWG CONDUCTORS &

GROUND PV WIRE IN WEATHERTIGHT INSULATION

F2

G1

26.2"x25.6"x10.4"8 AWG CONDUCTORS &

GROUND PV WIRE IN WEATHERTIGHT INSULATION

7.5KW 208V1 INVERTER 21.1" x 28.5" x 7.8" 600V 35.1A 1

8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER

TIGHT INSULATION

3.8KW 208V1 INVERTER

FRONIUS IG PLUS ADV.600V 17.8A 1

33.3A

41.6A

32A

18.3A

20.1" x 28.5" x 8.9"

20.1" x 28.5" x 8.9"

FRONIUS SYMO

FRONIUS SYMO50A

FRONIUS IG PLUS ADV.

E7

E8

8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER

TIGHT INSULATION8 AWG CONDUCTORS &

GROUND PV WIRE IN WEATHERTIGHT INSULATION

2C4 3 INVERTER8 AWG CONDUCTORS &

GROUND PV WIRE IN WEATHERTIGHT INSULATION

20.1" x 28.5" x 8.9"12KW 208V

41.5A 33.3AFRONIUS SYMO

41.5A 33.3A

41.5A 33.3A

SPACE SPACE

4A 2A

AC

DC

DCMPPT1 MPPT2

PVPANEL

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR5

STR4

STR3

STR2

STR1

TO ADDITIONAL PV PANELS.

PVPANEL

STR6

AC

DC

AC

DC

AC

DC

15KW 208V3 INVERTER 141.6A20.1" x 28.5" x 8.9"

FRONIUS SYMO50A

15KW 208V3 INVERTER 141.6A20.1" x 28.5" x 8.9"

FRONIUS SYMO50A

15KW 208V3 INVERTER 141.6A20.1" x 28.5" x 8.9"

FRONIUS SYMO50A

15KW 208V3 INVERTER 141.6A20.1" x 28.5" x 8.9"

FRONIUS SYMO50A

23 INVERTER 20.1" x 28.5" x 8.9"12KW 208V

41.5A 33.3AFRONIUS SYMO

23 INVERTER 20.1" x 28.5" x 8.9"12KW 208V

41.5A 33.3AFRONIUS SYMO

23 INVERTER 20.1" x 28.5" x 8.9"12KW 208V

41.5A 33.3AFRONIUS SYMO

23 INVERTER 20.1" x 28.5" x 8.9"12KW 208V

41.5A 33.3AFRONIUS SYMO

1000V

1000V

1000V

1000V

1000V

600V

600V

600V

600V

600V

600V

600V

600V

PVPANEL

PVPANEL

PVPANEL

STR3

STR2

STR1

PVPANEL

PVPANEL

STR4

STR5

PVPANEL

PVPANEL

PVPANEL

PVPANEL

PVPANEL

STR5

STR4

STR3

STR2

STR1

PVPANEL

STR6

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

E-300G150004-000

ELECTRICAL SINGLE LINEDIAGRAM

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

DRAWING NOTES:

1. PROVIDE BRANCH CIRCUIT METERING FOR ALL BRANCH CIRCUITS IN PANELS RP1, RP2, LP, HP1, AND HP2. PROVIDE NETWORK CONNECTION FROMBRANCH CIRCUIT METERS TO CAMPUS METERING COMPUTER FOR REMOTE MONITORING OF LOADS. ALL METERING SHALL BE MILLERSVILLE CAMPUSSTANDARD TYPE CLASS 5000 SMART METERING FROM E-MON D-MON.

KEY NOTES:

METERS SHALL BE LOCATED IN BASEMENT. REFER TO E-200 FOR LOCATION.1

NO. ISSUE DATE: DESCRIPTION

Page 10: G150004-000 F L R C P E M E-000

RJ45(Typical)

NTSSCALE:

DIGITAL LIGHTING MANAGEMENT NETWORK DIAGRAM - TYPICAL ROOM CONTROLLERNONESCALE:

FIXTURE W1 - TYPICAL MULLION MOUNTING DETAILNONESCALE:

SCALE:LMSM-3E - TYPICAL WIRING DETAIL

NONE

D

MM

T W PS

MM MM

D

LIGHTING FIXTURE SCHEDULE LIGHTING CONTROL DEVICE SCHEDULE

RECESSED 6" WIDE LINEAR LED WITH SATIN LENS WITH 0-10V DIMMABLEDRIVER AND COMPATIBLE WITH TECH ZONE CEILINGS. CONFIRM LENGTHS

OF FIXTURES WITH DRAWINGS.

MOUNTINGVOLTSTYPENO.CATALOG NUMBERMANUFACTURERDESCRIPTIONTYPE

LAMPS

REMARKS

LED 5.1W/FT UNV

A1

A1A -

FIXTUREWATTS

PENDANT

LED 7.5W/FT UNVGAMMALUXPINNACLE RECESSED-GB56RC2-1SOLED35-UNV-DVR-*N-REC/

*-ASLMD-*-*

GB66B2-1/1CPOLED35-UNV-DIM-*-C*-APL/ASLMD-*

6" WIDE LINEAR LED INDIRECT/DIRECT PENDANT WITH SATINLENS WITH 0-10V DIMMABLE DRIVER. CONFIRM LENGTHS OF

FIXTURES WITH DRAWINGS.

LED 7.2W/FT UNVA2 - RECESSEDRECESSED PERIMETER LED WITH 6" OPENING AND ASYMMETRIC AMBIENTILLUMINATION.

LED UNVA3 - RECESSED

LED 18W UNVD1 - RECESSEDRECESSED 6" DIAMETER LED DOWNLIGHT WITH 1500 LUMEN PACKAGE AND0-10V DIMMABLE DRIVER.

B1 LED 38W UNVLIGHT EMITTING DES.HE WILLIAMS - PENDANTINDUSTRIAL STYLE LED PENDANT

7.4W/FTMULLION MOUNTED LINEAR LED, WET LOCATION RATED WITH REMOTE

DRIVERS,100 DEGREE OPTICS, AND 0-10V DIMMABLE DRIVER. PROVIDE ALLCOMPONENTS FOR A COMPLETE INSTALLATION. CONFIRM LENGTHS OF

FIXTURES WITH DRAWINGS.

C6L15NUVBZ10V-C6L1520DL35KMCCL

SML150-40ND-TBH

PHILIPSHE WILLIAMS

INSIGHT

4WWALL MOUNT EDGE LIT LED EXIT SIGN WITH GREEN LETTERS. SIGNTEXHE WILLIAMS

*CONFIRM MOUNTINGDETAILS AND FINISHES

WITH ARCHITECT

*CONFIRM MOUNTINGDETAILS AND FINISHES

WITH ARCHITECT. CPO =30% OF HIGH OUTPUT

DRIVER.

MXI-6-35K-100-U-CES-*RPS/96/PWR/WET-DIM-*

*CONFIRM NUMBER OFFACES AND CHEVRON

DIRECTION WITH DRAWING.CONFIRM FINISH WITH

ARCHITECT.

LED 6.3W/FT 120P1 - PENDANTSQUARE PROFILE 1.14" X 1.14" LED DIRECT PENDANT WITH REMOTE 0-10VDIMMABLE DRIVER AND DIFFUSE LENS. CONFIRM LENGHTS OF FIXTURES

WITH DRAWINGS.VODE 107-BX 01 * * CC * 2R AE 1 0 Z SO 35 1 0 * 0

*CONFIRM MOUNTINGDETAILS AND FINISHES

WITH ARCHITECT

LIGHTING FIXTURE SCHEDULE NOTES:

1. CATALOG NUMBER IS BASED ON FIRST MANUFACTURER LISTED.

2. ELECTRICAL CONTRACTOR TO VERIFY MOUNTING TYPE AND VOLTAGE (IF MVOLT IS NOT AVAILABLE) PRIOR TO ORDERING FIXTURES.

3. ELECTRICAL CONTRACTOR TO COORDINATE DIMMING BALLAST TYPE WITH THE SPECIFIED LIGHTING CONTROL SYSTEM. DIMMERS SHALL BE COMPATIBLE WITH THE DRIVERS IN THELIGHTING FIXTURE.

4. ELECTRICAL CONTRACTOR TO COORDINATE ALL PRODUCTS SUCH THAT ALL NECESSARY PARTS, ACCESSORIES, ETC ARE INSTALLED FOR A COMPLETE FUNCTIONING SYSTEM AS PERDESIGN INTENT.

VOLTS MOUNTING REMARKSMANUFACTURERTYPE DESCRIPTION CATALOG NUMBER

OS LOW VOLT WALL MOUNTEDPASSIVE INFRARED LOW VOLTAGE WALL SENSOR THAT CONTROLSLIGHTS ON AND OFF WITH OCCUPANCY WITH HIGH DENSITY LENS. LMPX-100

ST WALL SWITCHLINE VOLTAGE DIGITAL TIMER SWITCH TS-400-W-U 120V

LOW VOLT CEILINGVSPASSIVE INFRARED LOW VOLTAGE CEILING SENSOR THAT CONTROLSOFF WITH OCCUPANCY BUT REQUIRES A MANUAL WALL SWITCH TO

TURN LIGHTS ON.LMPC-100

LIGHTING CONTROL DEVICE SCHEDULE NOTES:

1. CATALOG NUMBER IS BASED ON FIRST MANUFACTURER LISTED.

2. TIME CLOCK CONTROL IS BY AREA. REFER TO REFLECTED CEILING PLANS AND SEQUENCE OF OPERATION FOR MORE INFORMATION.

LIGHTING CONTROL SEQUENCE OF OPERATION:

1. ALL EMERGENCY LIGHTING SHALL BE CONTROLLED BY EMERGENCY BATTERY BACKUP IN THE EVENT OF A POWER LOSS. NIGHT LIGHTING AND EXIT SIGNS SHALL ALWAYS BE ON.

2. THE LOBBY, OPEN OFFICE CORRIDOR, AND EXTERIOR LIGHTING SHALL BE CONTROLLED BY TIME CLOCK. THE LOBBY LIGHTS SHALL TURN ON 30 MINUTES BEFORE OPENING AND TURN OFF AT 10:00 PM. AT OFF HOURS LIGHTS IN LOBBY SHALL BECONTROLLED BY OVERRIDE SWITCHES AND OCCUPANCY SENSORS ONLY. THE CORRIDOR LIGHTS SHALL TURN ON 30 MINUTES BEFORE OPENING AND TURN OFF 30 MINUTES AFTER CLOSING. AT OFF HOURS LIGHTS IN THE CORRIDOR SHALL BECONTROLLED BY OVERRIDE SWITCHES AND OCCUPANCY SENSORS. ALL OTHER SPACES SHALL BE CONTROLLED BY LOCAL CONTROLS (SWITCHES, VACANCY SENSORS, AND OCCUPANCY SENSORS AS INDICATED). CONFIRM SCHEDULE WITH OWNERBEFORE PROGRAMMING OF TIME CLOCK. ALL PROGRAMMING SHALL BE DONE BY USING WATTSTOPPER DLM SYSTEM.

3. LOCAL CONTROLS AND OCCUPANCY/VACNACY SENSORS SHALL BE USED IN AREAS NOT CONTROLLED BY TIME CLOCK. ANY OCCUPANCY SENSORS SHALL AUTOMATICALLY TURN ON LIGHTS AFTER ACTIVATION OF SENSOR. THE VACANCY SENSOR SHALLONLY TURN THE LIGHTS OFF AND THE LIGHTS SHALL ONLY TURN ON WITH ACTIVATION OF THE WALL SWITCH.

OS LOW VOLT CEILINGDUAL TECHNOLOGY LOW VOLTAGE CEILING SENSOR THAT CONTROLSLIGHTS ON AND OFF WITH OCCUPANCY. LMDC-100

WATTSTOPPER

WATTSTOPPER

WATTSTOPPER

WATTSTOPPER

SD

SOR

ONE BUTTON DIMMING WALL SWITCH WITH LED DIMMING INDICATOR LMDM-101

OVERRIDE WALL SWITCH

LOW VOLTWATTSTOPPER

LOW VOLTWATTSTOPPER

LOW VOLTWATTSTOPPER

LMSW-100

SOR ONE BUTTON DIMMING WALL SWITCH LOW VOLTWATTSTOPPER

120VWATTSTOPPER

LMSW-100

SKP5 BUTTON SCENE SWITCH WITH RAISE/LOWER AND 4 SCENE PRESETS

AND CUSTOM ENGRAVED BUTTONS. LMSW-105

PC LOW VOLT CEILINGWATTSTOPPER

SOS ONE BUTTON PASSIVE INFRARED WALL SWITCH OCCUPANCY SENSOR DSW-100

0-10V Dimming Wiring DiagramLMRC-211 Single Relay

DEVICES ARE PRESET FOR PLUG n' GO ™ OPERATION,ADJUSTMENT IS OPTIONAL. Sequence of Operation: In this configuration theLMRC-211 defaults to manual-on/automatic-off operation. Enhanced roomcontrollers support up to 64 loads and 48 devices per DLM localnetwork. At system startup, default dimming parameters are established including:levels for presets 1-4; fade times; and fade and ramp rates. Dimming and systemparameters may be customized. For full operational details, adjustmentsand more features of the product, see the DLM SystemInstallation Guide at www.wattstopper.com

Red

Neutral Wht

LightingLoad

LMRC-211Single Relay

On/Off/0-10V DimmingRoom Controller

Vio

Gry

VioGry

LMRJ Series Pre-TerminatedCables or CAT5e. Free Topology& Splitter Acceptable

Class 2 0-10 VoltControl Wiring

0-10VDC DimmingBallast required.

(As Needed)LMDM-101 Digital

Dimming Wall Switch

UnswitchedHot Blk120/277

*DLM OccupancySensor

*NOTE:Corner mount Sensorshown with pigtail &supplied coupler. Ceilingmount Sensor has twoRJ45 ports.

LMRJ-C8Coupler

EarthGround

Grn

LMBC-300Digital Network

Bridge

FromPrevious

DeviceTo NextDevice

SegmentNetwork MS/TP

R - +

(+) White

(R) Green/White (-) Black

Twist & WrapShield TogetherWrap Shield with

Tape for strain relief

FromPreviousDevice

To NextDevice

DLM Terminalblock for MS/TP

SegmentNetwork MS/TP

R - +

SegmentNetwork MS/TP

LMLS-400Photosensor

LMLS-400SINGLE-ZONE ON/OFF AND DIMMING CLOSED LOOP PHOTOSENSOR

*NOTE:TYPICAL WIRING DIAGRAMSHOWN. REFER TO E-101FOR CONTROLS, SWITCHES,AND ROOM CONTROLLERSTHAT ARE NEEDED FORAREA.

WALL SWITCH

WALL SWITCH

WALL SWITCH

WALL SWITCH

WALL SWITCH

LED 18W UNVP2 - PENDANT7" DIAMETER LED CYLINDER WITH 1500 LUMEN WITH WIDE OPTICSPACKAGE WITH 0-10V DIMMABLE DRIVER.

PHILIPSPRESCOLITE C4L10C*35KCCLUVB-C4CC*X5

*CONFIRM MOUNTINGDETAILS AND FINISHES

WITH ARCHITECT

10WWALL MOUNTED MULLION MOUNT EXTERIOR LED FIXTURE.

*CONFIRM MOUNTINGDETAILS AND FINISHES

WITH ARCHITECT

*CONFIRM MOUNTINGDETAILS AND FINISHES

WITH ARCHITECT

10WWALL MOUNTED EXTERIOR LED FIXTURE. SIGNTEX MAEAC10*W*CONFIRM MOUNTINGDETAILS AND FINISHES

WITH ARCHITECT

LED UNV-

LED UNV-

LED UNV-

UNV

SURFACE

WALL

WALL

W1

W2

W3

X1 LED- WALL

GPCAR6N-1SOLED35T-UNV-DVR-*N-RECW*-**CONFIRM MOUNTINGDETAILS AND FINISHES

WITH ARCHITECT

*CONFIRM MOUNTINGDETAILS AND FINISHES

WITH ARCHITECT7.2W/FTRECESSED PERIMETER LED WITH 6" OPENING. GPRG6B-1SOLED35T-UNV-DVR-*-

OS 120V CEILINGDUAL TECHNOLOGY LINE VOLTAGE CEILING SENSOR THAT CONTROLSLIGHTS ON AND OFF WITH OCCUPANCY. DT-355WATTSTOPPER

LV PROVIDE POWER PACKS AS NEEDED.

4WMULLION MOUNT EDGE LIT LED EXIT SIGN WITH GREEN LETTERS. CRS-BB-*G**-*-MMSIGNTEXHE WILLIAMS

*CONFIRM NUMBER OFFACES AND CHEVRON

DIRECTION WITH DRAWING.CONFIRM FINISH WITH

ARCHITECT.

UNVX1A LED- SURFACE

4WPENDANT MOUNT EDGE LIT LED EXIT SIGN WITH GREEN LETTERS. CRS-BB-*G**-*-TWSIGNTEXHE WILLIAMS

*CONFIRM NUMBER OFFACES AND CHEVRON

DIRECTION WITH DRAWING.CONFIRM FINISH WITH

ARCHITECT.

UNVX1B LED- PENDANT

W4

CRS-BB-*G**-*-WM

SIGNTEX

SIGNTEX

MUEAC10*W

MOEAC10*WALL MOUNTED EXTERIOR LED FIXTURE. 10WLED UNV- WALL*CONFIRM MOUNTINGDETAILS AND FINISHES

WITH ARCHITECT

REFER TO E-101 FOR ROOMCONTROLLERS NEEDED

120V CIRCUIT

FIRE ALARMANNUNCIATOR

PANEL(FAP)(W/GRAPHIC DISPLAY)

LOCATED INLOBBY

FIRE ALARMCONTROL PANEL

(FACP)LOCATED IN

ELECTRIC ROOM-121

F

TO OTHER INITIATINGDEVICES

TO OTHER INITIATINGDEVICES

TO OTHER SIGNALINGDEVICES

F

TO OTHER INITIATINGDEVICES

TO OTHER INITIATINGDEVICES

TO OTHER SIGNALINGDEVICES

FIRE ALARM RISER NOTES:

1. SEE ELECTRICAL FLOOR PLANS FOR QUANTITY OF DEVICES.2. INSTALLER SHALL COORDINATE WITH OWNER TO ESTABLISH A FACILITY FIRE

ALARM ADDRESS SCHEDULE FOR ZONING OF AREA DETECTION DEVICES.INSTALLER SHALL INCLUDE WITHIN HIS BID AN ADEQUATE NUMBER OFADDRESSABLE LOOPS & NOTIFICATION APPLIANCE DEVICE OUTPUT CIRCUITSTO ACCOMMODATE THE ESTABLISHED FACILITY ZONING NEEDS, INCLUDINGTWENTY PERCENT SPARE CAPACITY, FOR FUTURE DEVICES, ON ADDRESSZONE AND NOTIFICATION APPLIANCE DEVICE LOOPS.

3. ALL WIRING SHALL BE METAL-CLAD FIRE ALARM/CONTROL CABLE TYPE FPL ASMANUFACTURED BY "AFC" WITH RED FLEXIBLE OUTER METAL JACKET.

4. PROVIDE CONTROL AND MONITOR MODULES AS REQUIRED.5. REFER TO MECHANICAL AND FIRE PROTECTION DRAWINGS FOR QUANTITIES

AND LOCATIONS OF ALL FIRE ALARM DEVICES ASSOCIATED WITH MECHANICALSYSTEMS.

6. PROVIDE POWER SUPPLY(S) AS REQUIRED FOR DOOR CLOSURES, SMOKEDAMPER CONTROL AND VISUAL ANNUCIATORS (STROBES).

7. NO SUBSTITUTIONS. SIEMENS AS BASIS OF DESIGN.8. FIRE ALARM VENDOR SHALL PROVIDE ALL GRAPHICS AND SIGNAGE REQUIRED.9. FIBER CONNECTION TO IT ROOM 123 FOR CONNECTION TO CAMPUS

MONITORING SYSTEM.

KEY NOTES:

PROVIDE (2)UNIVERSAL DIGITAL ALARM - PROTECTED FIBER CONNECTION TO ITROOM 123. CONNECT FIRE ALARM SYSTEM FROM MDF ROOM TO GORDINIERAND THE CAMPUS COMMAND CENTER AT STUDENT MEMORIAL CENTER.PROVIDE BUILDING GRAPHICS FOR DISPLAY AT THE CAMPUS COMMANDCENTER.

GAMMALUXPINNACLE

GAMMALUXPINNACLE

GAMMALUXPINNACLE

RJ45ETHERNET

LAN

LM-MSTPDATALINE

THE LMBC-300'S ARE CONNECTED TOGETHER USINGLM-MSTP DATALINE. THE DATALINE MUST BE RUN IN ALINEAR FASHION.

Segment #1LMBC-300

AS PER PLANSLMBC-300

11LMSM-3E

120 VAC

LMSM-ENC1

BOTTOM OF FIXTURE SHALLBE MOUNTED AT 9'-0'' AFF.

Z1 15WLED EXTERIOR BOLLARD. FLINDT/15W LED/4000K/120-277VPOULSEN UNVLED- IN GRADE

LED 15W UNVP2A - PENDANT4" DIAMETER LED CYLINDER WITH 1000 LUMEN WITH MEDIUM OPTICSPACKAGE WITH 0-10V DIMMABLE DRIVER.

PHILIPSPRESCOLITE C7L20C*35KWCCLUVB-C7CC*X5

*CONFIRM MOUNTINGDETAILS AND FINISHES

WITH ARCHITECT

1

1

4 FIRE ALARM RISER

3

1

2

GROUND FLOOR

LOMBARDO WELCOME CENTERLOWER LEVEL

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

E-400G150004-000

ELECTRICAL LIGHTINGSCHEDULE & FA RISER

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION

Page 11: G150004-000 F L R C P E M E-000

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

E-401G150004-000

ELECTRICAL PANELSCHEDULES

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NOTES:PROVIDE BRANCH CIRCUITING METERING FOR PANEL HP1

TOTAL EST. DEMAND: 127TOTAL CONN.: 127

TOTAL EST. DEMAND: 45734 VAPower 39234 VA 100.00% 39234 VA TOTAL CONN. LOAD: 45734 VAHeating 6500 VA 100.00% 6500 VALOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 148 A 144 A 101 ATOTAL LOAD: 17086 VA 16539 VA 12109 VA

41 SPARE 20 1 0 0 1 20 SPARE 4239 2683 1061 4037

HP-5 50 22683 1061

2 20 HP-438

35 2132 1061 3633

HP-2 40 22132 1061

2 20 HP-334

31 TF-1 20 1 1500 1154 3229 VAVB 20 1 1500 1154

2 20 HP-130

27 1498 1500 1 20 EWH-1-1 2825

HP-18 30 21498 2000 1 30 EWH-1-2 26

23 385 385 2421

HP-16 20 2385 385

2 20 HP-1722

19 1154 730 2017

HP-14 20 21154 730

2 20 HP-1518

15 1154 1498 1613

HP-12 20 21154 1498

2 30 HP-1314

11 1154 914 129

HP-10 20 21154 914

2 20 HP-1110

7 1154 385 85

HP-8 20 21154 385

2 20 HP-96

3 385 730 41

HP-6 20 2385 730

2 20 HP-72

CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT

ENCLOSURE: Type 1 MOUNTING: SURFACE MCB RATING / POLES: 225A / 3P FEED (TOP/ BOTTOM):FEEDER SIZE: WIRES: 4 MAINS RATING: 225 A GROUND BUS: Yes

FED FROM:: PHASES: 3 MAINS TYPE: MAIN CIRCUIT BREAKER BUSSING (CU/AL): CULOCATION: ELEC. RM. 121 VOLTS (V): 120/208 Wye A.I.C. RATING: 22,000 NEUTRAL: 100%

BRANCH PANEL: HP1

NOTES:PROVIDE BRANCH CIRCUITING METERING FOR PANEL HP2

Power 11678 VA 100.00% 11678 VA TOTAL EST. DEMAND: 60Other 4000 VA 100.00% 4000 VA TOTAL CONN.: 60Motor 120 VA 125.00% 150 VA TOTAL EST. DEMAND: 21643 VAHeating 5780 VA 100.00% 5780 VA TOTAL CONN. LOAD: 21613 VAHVAC 35 VA 100.00% 35 VALOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 63 A 41 A 82 ATOTAL LOAD: 7234 VA 4940 VA 9439 VA

41 SPACE -- -- 0 0 -- -- SPACE 4239 SPACE -- -- 0 0 -- -- SPACE 4037 SPACE -- -- 0 0 -- -- SPACE 3835 SPARE 20 1 0 0 -- -- SPACE 3633 SPARE 20 1 0 0 1 20 SPARE 3431 POWER 20 1 2000 2080 3229 POWER 20 1 2500 2080

2 30 ACCU-130

27 104 0 1 20 BAS CONTROL PANEL 2825

POWER ELEC. RM. 121 20 2104 500 1 20 POWER 26

23 BAS CONTROL PANEL 20 1 0 120 1 20 P-3 2421 FLOOD CONTROL VALVE 20 1 250 385 2219 MOTORIZED SHADES 20 1 500 385

2 20 HP-2320

17 EF-2 20 1 35 2640 1 30 BR-1 1815 BR-1 30 1 2640 0 1 20 P-3 1613 104 0 1 20 VAVB 1411

AC-1 20 2104 730 12

9 P-4 20 1 0 7302 20 HP-20

107 EF-1 20 1 0 730 85 GYLOCL SKID 20 1 500 730

2 20 HP-216

3 385 447 41

HP-22 20 2385 447

2 20 HP-192

CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT

ENCLOSURE: Type 1 MOUNTING: SURFACE MCB RATING / POLES: 125A / 3P FEED (TOP/ BOTTOM):FEEDER SIZE: WIRES: 4 MAINS RATING: 225 A GROUND BUS: Yes

FED FROM:: PHASES: 3 MAINS TYPE: MAIN CIRCUIT BREAKER BUSSING (CU/AL): CULOCATION: MECHANICAL 002 VOLTS (V): 120/208 Wye A.I.C. RATING: 22,000 NEUTRAL: 100%

BRANCH PANEL: HP2

NOTES:PROVIDE BRANCH CIRCUITING METERING FOR PANEL LP

TOTAL EST. DEMAND: 34TOTAL CONN.: 27

TOTAL EST. DEMAND: 12210 VAOther 0 VA 0.00% 0 VA TOTAL CONN. LOAD: 9768 VALighting 9768 VA 125.00% 12210 VALOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 26 A 23 A 31 ATOTAL LOAD: 3058 VA 2743 VA 3669 VA

29 SPACE -- -- 0 0 -- -- SPACE 3027 SPACE -- -- 0 0 -- -- SPACE 2825 SPARE 20 1 0 0 -- -- SPACE 2623 SPARE 20 1 0 0 1 20 SPARE 2421 SPARE 20 1 0 0 1 20 SPARE 2219 LIGHTING 20 1 848 0 1 20 SPARE 2017 LIGHTING 20 1 882 0 1 20 MAIN LIGHTING SIGN 1815 LIGHTING 20 1 570 864 1 20 LIGHTING 1613 LIGHTING 20 1 72 350 1 20 LIGHTING 1411 LIGHTING 20 1 521 762 1 20 LIGHTING 129 INVERTER 30 1 461 127 1 20 LIGHTING 107 LIGHTING 20 1 150 383 1 20 LIGHTING 85 LIGHTING 20 1 513 918 1 20 LIGHTING 63 LIGHTING 20 1 420 300 1 20 LIGHTING 41 LIGHTING 20 1 240 736 1 20 LIGHTING 2

CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT

ENCLOSURE: Type 1 MOUNTING: SURFACE MCB RATING / POLES: 100A / 3P FEED (TOP/ BOTTOM):FEEDER SIZE: WIRES: 4 MAINS RATING: 100 A GROUND BUS: Yes

FED FROM:: PHASES: 3 MAINS TYPE: MAIN CIRCUIT BREAKER BUSSING (CU/AL): CULOCATION: ELEC. RM. 121 VOLTS (V): 120/208 Wye A.I.C. RATING: 22,000 NEUTRAL: 100%

BRANCH PANEL: LP

NOTES:PROVIDE BRANCH CIRCUITING METERING FOR PANEL RP1

TOTAL EST. DEMAND: 42TOTAL CONN.: 56

TOTAL EST. DEMAND: 15170 VATOTAL CONN. LOAD: 20340 VA

Receptacle 20340 VA 74.58% 15170 VALOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 62 A 63 A 48 ATOTAL LOAD: 7200 VA 7380 VA 5760 VA

41 SPARE 20 1 0 0 1 20 SPARE 4239 RECEPTACLE OFFICE 124 20 1 540 540 1 20 RECEPTACLE OFFICE 128 4037 RECEPTACLE STUDENT WORK SPACE... 20 1 1080 540 1 20 RECEPTACLE OFFICE 118 3835 RECEPTACLE RESOURCE ROOM 120 20 1 540 720 1 20 RECEPTACLE CONFERENCE 133 3633 RECEPTACLE OFFICE 112 20 1 540 180 1 20 RECEPTACLE RESOURCE ROOM 120 3431 RECEPTACLE STUDENT WORK SPACE... 20 1 1080 180 1 20 IT RACK REC. 3229 RECEPTACLE WORK ROOM 129 20 1 180 180 1 20 RECEPTACLE V.P. OFFICE 112A 3027 RECEPTACLE ROOM 121, 122, 123 20 1 900 720 1 20 RECEPTACLE ROOM 131, 132 2825 RECEPTACLE HOUSING OPEN OFFICE... 20 1 360 360 1 20 RECEPTACLE HOUSING OPEN OFFICE... 2623 RECEPTACLE ROOM 116, 117 20 1 540 720 1 20 RECEPTACLE ROOM 119, 128 2421 RECEPTACLE MARKETING OPEN... 20 1 540 720 1 20 RECEPTACLE ROOM 115, 114 2219 RECEPTACLE MARKETING OPEN... 20 1 540 180 1 20 RECEPTACLE WORK ROOM 129 2017 RECEPTACLE ROOM 110, 109 20 1 540 540 1 20 RECEPTACLE OFFICE 111 1815 RECEPTACLE ROOM 107, 106 20 1 540 720 1 20 RECEPTACLE OFFICE (V.P. O... 1613 RECEPTACLE ADMISSIONS OPEN... 20 1 360 720 1 20 RECEPTACLE ROOM 104, 105 1411 RECEPTACLE ROOM 127, 126 20 1 360 540 1 20 RECEPTACLE ADMISSIONS OPEN... 129 RECEPTACLE ADMISSIONS OPEN... 20 1 540 540 1 20 RECEPTACLE ADMISSIONS OPEN... 107 RECEPTACLE ADMISSIONS OPEN... 20 1 540 540 1 20 RECEPTACLE OFFICE 110 85 RECEPTACLE ROOM 103, 102 20 1 540 360 1 20 RECEPTACLE ADMISSIONS OPEN... 63 IT RACK REC. 20 1 180 180 1 20 IT RACK REC. 41 RECEPTACLE OFFICE 104 20 1 540 180 1 20 IT RACK REC. 2

CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT

ENCLOSURE: Type 1 MOUNTING: SURFACE MCB RATING / POLES: 125A / 3P FEED (TOP/ BOTTOM):FEEDER SIZE: WIRES: 4 MAINS RATING: 225 A GROUND BUS: Yes

FED FROM:: PHASES: 3 MAINS TYPE: MAIN CIRCUIT BREAKER BUSSING (CU/AL): CULOCATION: ELEC. RM. 121 VOLTS (V): 120/208 Wye A.I.C. RATING: 22,000 NEUTRAL: 100%

BRANCH PANEL: RP1

NOTES:PROVIDE BRANCH CIRCUITING METERING FOR PANEL RP2

TOTAL EST. DEMAND: 44TOTAL CONN.: 47

Receptacle 12260 VA 90.78% 11130 VA TOTAL EST. DEMAND: 15950 VAPower 4820 VA 100.00% 4820 VA TOTAL CONN. LOAD: 17080 VAOther 0 VA 0.00% 0 VALOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 37 A 37 A 69 ATOTAL LOAD: 4420 VA 4420 VA 8240 VA

41 SPARE 20 1 0 0 1 20 SPARE 4239 SPARE 20 1 0 0 1 20 SPARE 4037 SPARE 20 1 0 0 1 20 SPARE 3835 SPARE 20 1 0 180 1 20 RECEPTACLE 3633 SPARE 20 1 0 180 1 20 RECEPTACLE 3431 RECEPTACLE BREAK ROOM 124 20 1 360 180 1 20 RECEPTACLE 3229 OTHER RESOURCE ROOM 103 20 1 0 180 1 20 RECEPTACLE RECEPT. L101-2 3027 OTHER CLASSROOM/PRESENTATION... 20 1 0 180 1 20 RECEPTACLE 2825 LAV FAUCETS 20 1 720 0 1 20 OTHER CLASSROOM/PRESENTATION... 2623 RECEPTACLE 20 1 720 4820 1 30 HAND DRYERS 2421 RECEPTACLE 20 1 180 1260 1 20 RECEPTACLE ROOM 137, 136, 135 2219 RECEPTACLE 20 1 180 720 1 20 RECEPTACLE PRESENTATION ROOM... 2017 LAV FAUCETS 20 1 540 900 1 20 RECEPTACLE ROOM 142, 143, 141, 135 1815 RECEPTACLE PRESENTATION ROOM... 20 1 360 0 1 20 DOOR OPERATOR 1613 RECEPTACLE ROOM 145, 146, 144 20 1 360 1000 1 20 COPIER 1411 DOOR OPERATOR 20 1 0 720 1 20 RECEPTACLE 129 COPIER 20 1 1000 720 1 20 RECEPTACLE 107 RECEPTACLE LOBBY 135 20 1 360 180 1 20 RECEPTACLE ALCOVE 147 85 FACP 20 1 0 180 1 20 RECEPTACLE COFFEE STATION L101-3 63 RECEPTACLE 20 1 180 360 1 20 RECEPTACLE 41 RECEPTACLE 20 1 180 180 1 20 RECEPTACLE 2

CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT

ENCLOSURE: Type 1 MOUNTING: SURFACE MCB RATING / POLES: 100A / 3P FEED (TOP/ BOTTOM):FEEDER SIZE: WIRES: 4 MAINS RATING: 100 A GROUND BUS: Yes

FED FROM:: PHASES: 3 MAINS TYPE: MAIN CIRCUIT BREAKER BUSSING (CU/AL): CULOCATION: ELEC. RM. 121 VOLTS (V): 120/208 Wye A.I.C. RATING: 22,000 NEUTRAL: 100%

BRANCH PANEL: RP2

NO. ISSUE DATE: DESCRIPTION

Page 12: G150004-000 F L R C P E M E-000

T

FIRE PROTECTION SYMBOL LISTBASIC

FIRE STANDPIPE PIPING (STANDALONE)

SPRINKLER PIPING

DRY SPRINKLER PIPING

PRE-ACTION SPRINKLER PIPING

DRAIN PIPING

PIPING BELOW SLAB

EXISTING PIPING

EXISTING WORK TO BE REMOVED

HEAT TRACE / FREEZE PROTECTION CABLE & INSULATION

SLOPED CHANGE IN PIPE ELEVATION

BOTTOM PIPE CONNECTION

TOP PIPE CONNECTION

SIDE CONNECTION

PIPE DOWN/DROP

PIPE RISE/UP

PIPE SLOPE

VALVE IN VERTICAL

UNION

REDUCER

WATER PROOF SLEEVE

SLEEVE

FIRE EXTINGUISHERA - WATERB - DRY CHEMICALC - GASEOUS (CO2 OR HALON 1211 - SEE SPEC.)

FIRE EXTINGUISHER IN CABINET

FIRE HOSE VALVE

FIRE HOSE VALVE IN CABINET

FIRE HOSE VALVE w/HOSE IN CABINET

FIRE HOSE VALVE w/FIRE EXTINGUISHER

ROOF MANIFOLD (3-WAY)

SPRINKLER CONTROL VALVE ASSEMBLY

VALVE ASSEMBLYAC - ALARM CHECKDR - DRY PIPEPA - PRE ACTION

CONNECT TO EXISTING

DISCONNECT FROM EXISTING

FIRE DEPARTMENT SIAMESE CONNECTION (WALL MOUNTED)

EXISTING FIRE HYDRANT

NEW FIRE HYDRANT

TEMPERATURE AND PRESSURE RELIEF VALVE

PLUG VALVE

MIXING VALVE

RELIEF VALVE

BALL VALVE

GATE VALVE

GLOBE VALVE

OUTSIDE SCREW & YOKE (OS & Y) VALVE

CHECK VALVE

PRESSURE REDUCING VALVE (PRV)

SOLENOID VALVE

FLOAT VALVE

Y STRAINER w/BLOW-OFF VALVE

REDUCED PRESSURE DETECTOR ASSEMBLY

DOUBLE CHECK DETECTOR ASSEMBLY

HYDRAULIC REF. POINTS # = ELEMENT, # = NODE

TAMPER SWITCH

WATERFLOW SWITCH

PRESSURE GAUGE w/GAUGE COCK

RISER DESIGNATION:X = RISER SERVICE; # = RISER NUMBER

EXTEND EXISTING SPRINKLER PIPING TO NEW SPRINKLER HEAD

DSP

RPDA

DCDA

X#

#

F

PA

DR

S

S

#

FE-X

FE-X

X

FE-X

FP-2-3

XXX-XX-XX

SECOND FLOOR

(REFER TO SPECIFIC TRADE LIST)

EQUIPMENT TAG NUMBERFLOOR DESIGNATIONEQUIPMENT DESIGNATION

FIRE PUMP(REFER TO LIST)

UNIT NUMBER 3

FP EQUIPMENT DESIGNATIONS

1. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL FIRE PROTECTION DRAWINGS.

2. ALL WORK IS NEW UNLESS OTHERWISE NOTED.

3. ALL FIRE PROTECTION WORK SHALL BE IN ACCORDANCE WITH THE CURRENT FIRE PROTECTION CODEAND ALL APPLICABLE LOCAL CODES AND DRAWINGS.

4. PROVIDE WET-PIPE SPRINKLERS IN ALL AREAS.

5. SECURE WATER FLOW TEST DATA TAKEN FROM FIRE HYDRANTS NEAREST SITE. IF RECENT FLOW TESTDATA IS NOT AVAILABLE FROM CITY RECORDS, MAKE NECESSARY TESTS AS REQUIRED BY NFPASTANDARDS TO DETERMINE CHARACTER OF WATER SUPPLY. MINIMUM OF 20 PSI DROP IN PRESSUREBETWEEN STATIC AND RESIDUAL PRESSURE SHALL BE REQUIRED IN ORDER TO OBTAIN ACCURATEDATA.

6. SPRINKLER SYSTEM SHALL BE HYDRAULICALLY CALCULATED.

7. ADD 10% CONTINGENCY FACTOR TO HYDRAULIC CALCULATIONS.

8. EXACT LOCATION OF SPRINKLER HEADS IN FINISHED AREAS WITH SUSPENDED CEILING SHALL BE ASINDICATED ON REFLECTED CEILING PLANS.

9. MINIMUM PRESSURE AT END SPRINKLER HEAD 7 PSI.

10. EQUIVALENT FITTING LENGTHS USED IN HYDRAULIC CALCULATIONS SHALL BE IN ACCORDANCE WITHNFPA STANDARD NO. 13 AND FACTORY MUTUAL 0.5 2-8N.

11. MAXIMUM FLOW VELOCITY SHALL NOT EXCEED 20 F.P.S.

12. ALL AUTOMATIC SPRINKLER HEADS, PIPE FITTINGS, PIPE HANGERS, AUTOMATIC CONTROL VALVES ANDMANUAL CONTROL VALVES SHALL BE UL LISTED AND BEAR FACTORY MUTUAL APPROVAL AND SHALL BEAPPROVED BY THE ENGINEER PRIOR TO INSTALLATION.

13. ALL EXPOSED PIPE, FITTINGS, HANGERS AND SUPPLEMENTARY STEEL SHALL BE PAINTED.

14. ENDS OF ALL CROSS MAINS SHALL BE PROVIDED WITH THREADED FLUSHING CONNECTION NO MORETHAN 2 INCHES IN DIAMETER.

15. PROVIDE AUXILIARY DRAINS FOR ALL PIPING BELOW DUCT SPRINKLERS AND OPEN TRAPPED SECTIONS.PIPING TO ONE SINGLE SPRINKLER IS EXCLUDED.

16. PROVIDE FLUSHING CONNECTIONS WHERE REQUIRED BY NFPA AND F.M.

17. COORDINATE WITH OWNER FOR ALL SHUTDOWNS.

18. PROVIDE TEST CONNECTIONS AT HIGHEST POINT OF MAIN PORTION OF EACH SPRINKLER SYSTEM, WITH1" PIPE AND VALVE. TEST PIPE SHALL BE CONNECTED TO SPRINKLER PIPE AT LEAST 1-1/4" IN SIZE ANDSHALL DISCHARGE OUTSIDE BUILDING OR THROUGH 1/2" SMOOTH BORE BRASS OUTLET, WHERE IT CANBE EASILY SEEN.

19. PROVIDE ADDITIONAL HEADS UNDER DUCTWORK LARGER THAN 48" WIDE.

20. THE REUSE OF EXISTING SPRINKLER HEADS SHALL BE PROHIBITED.

21. NEW SPRINKLER HEAD TYPE AND TEMPERATURE RATING SHALL BE IN ACCORDANCE WITH SCHEDULEUNLESS NOTED OTHERWISE AND/OR REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION.

22. COORDINATE ALL PIPE PENETRATIONS AND CORING WITH STRUCTURAL ENGINEER AND INACCORDANCE WITH DIVISION 01.

23. REFER TO ARCHITECTURAL DRAWINGS FOR ALL CEILING RELATED WORK.

24. COORDINATE ALL NEW FIRE PROTECTION WORK WITH ALL NEW DUCTWORK, PIPING AND UTILITIES OFANY SYSTEMS. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE INTENT OF THE DESIGN. REROUTE ANYPIPING AROUND EXISTING AND/OR NEW SYSTEMS INCLUDING ALL REQUIRED FITTINGS AND SUPPORTSTO MAKE THE INSTALLATION OF THE PIPING AND SPRINKLER HEADS POSSIBLE. RESEAL ANY FIREAND/OR SMOKE RATED PENETRATIONS THAT HAVE BEEN AFFECTED AS A RESULT OF THEMODIFICATION.

25. ALL COMPONENTS USED IN FIRE PROTECTION SYSTEMS SHALL BE IN ACCORDANCE WITH THE OWNER'SGUIDELINES, STANDARDS AND SPECIFICATIONS.

26. WATER SUPPLY INFORMATION TO BE VERIFIED BY FLOW TEST.

27. REPAIR AND PATCH ANY PENETRATIONS CREATED AS PART OF THIS SCOPE OF WORK. MATCH NEWFINISHES WITH ARCHITECTURAL PLANS.

28. COORDINATE INSTALLATION OF PIPING AND SPRINKLER HEADS WITH ALL OTHER TRADES.

29. ALL EXCAVATION AND BACKFILL REQUIRED FOR FIRE PROTECTION WORK SHALL BE BY THE FIREPROTECTION CONTRACTOR. REFER TO SITE SPECIFICATIONS FOR MORE INFORMATION ONEXCAVATION AND BACKFILL REQUIREMENTS.

30. PAINTING OF ALL ARCHITECTURALLY EXPOSED PIPING WORK SHALL BE BY THE GENERAL CONTRACTOR.PAINTING OF ANY NON-ARCHITECTURALLY EXPOSED PIPING SHALL BE BY THIS TRADES CONTRACTOR.REFER TO DIVISION 9 PAINTING.

31. FIRESTOPPING FOR THE WORK INCLUDED IN THESE DOCUMENTS, SHALL BE FURNISHED AND INSTALLEDBY THE FIRE PROTECTION CONTRACTOR. REFER TO DIVISION 7 FIRESTOPPING.

32. SLEEVES THAT ARE REQUIRED FOR THIS PROJECTS SHALL BE FURNISHED BY THE FIRE PROTECTIONCONTRACTOR AND INSTALLED BY THE GENERAL CONTRACTOR. COORDINATE THE LOCATION OF THESLEEVES WITH THE GENERAL CONTRACTOR.

FIRE PROTECTION GENERAL NOTES SPRINKLER HEAD SCHEDULE

MODEL NUMBER

MANUFACTURER

STAR

TYPE

EXIST

SPRI

NKLE

RHD

FLUS

HPE

NDEN

T

REMO

VED/

RELO

CATE

DEX

ISTSP

RHO

TOBE

EXTE

NDED

COVE

RAGE

QUIC

KRES

PONS

E

INTE

RMED

IATES

HIEL

D

(CHR

OMEF

INISH

)SID

EWAL

L

FLUS

HCO

NCEA

LED

PLAT

ESPK

R.

DESIG

NATIO

N

SEMI

-REC

ESSE

D

UPRI

GHT

PEND

ENT

DRY

CENT

RAL

RELIA

BLE

GRIN

NELL

VIKIN

G

REMARKS

A

NOTES:

2. PROVIDE ESCUTCHEONS WHEN PENETRATING EXPOSED WALL.

1. EXPOSED UPRIGHT HEADS IN OCCUPIED SPACES SHALL BE CHROME FINISH.

3. PROVIDE SPRINKLER GUARDS AT ALL HEADS 7'-0" AND LOWER.

4. COORDINATE COLOR SELECTION WITH ARCHITECT.A. SPRINKLER AND ESCUTCHEON TO BE WHITEB. SPRINKLER HEAD TO BE WHITEC. COVER PLATE TO BE WHITED. SPRINKLER AND SHIELD IN EXPOSED IN COORIDORS TO BE WHITEE. SPRINKLER AND SHIELD IN WOOD SLOT CEILING TO BE BLACK

F1FR56 INTERMEDIATE LEVELW/ SHIELD

F1FR56

F1FR56

G4A

DH56 DRY

K=5.6, 1/2" ORIFICE

K=5.6, 1/2" ORIFICE

K=5.6, 1/2" ORIFICE165°F RATING

155°F RATING

155°F RATING

K=5.6, 1/2" ORIFICE155°F RATING

F1FR56 K=5.6, 1/2" ORIFICE155°F RATING

K=5.6, 1/2" ORIFICE155°F RATING

SEE NOTE 4C.

SEE NOTE 4B.

SEE NOTE 4D AND 4E

SEE NOTE 4A.

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

F-000G150004-000

FIRE PROTECTION COVERSHEET

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

FIRE PROTECTION ABBREVIATIONSABD AUTOMATIC BALL DRIPAD AREA DRAINAFF ABOVE FINISHED FLOORATS AUTOMATIC TRANSFER SWITCH

BOP BOTTOM OF PIPE

CFM CUBIC FEET PER MINUTECV CHECK VALVE

DIA DIAMETERDN DOWN (PENETRATES FLOOR SLAB)DR DRAIN

(E) EXISTING(ER) EXISTING TO BE REMOVED(ERR) EXISTING TO BE REMOVED & RELOCATED

FD FLOOR DRAINFHC FIRE HOSE CABINETFHR FIRE HOSE RACKFHV FIRE HOSE VALVEFHVC FIRE HOSE VALVE CABINETFL FLOORFP FIRE PUMPFSP FIRE STANDPIPEFT FEET

GAL GALLONSGC GENERAL CONTRACTORGPM GALLONS PER MINUTEGV GATE VALVE

HD HEAT DETECTOR

ID INSIDE DIAMETERIN INCH

JP JOCKEY PUMP

MAX MAXIMUMMIN MINIMUM

NC NORMALLY CLOSENIC NOT IN THIS CONTRACTNO NORMALLY OPENNTS NOT TO SCALE

OD OUTSIDE DIAMETEROS&Y OUTSIDE SCREW & YOKE GATE VALVE

PRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCH (GAUGE)PSIA POUNDS PER SQUARE INCH (ABSOLUTE)

(RE) RELOCATED EXISTING(RRO) EXISTING TO REMOVED AND RETURN TO OWNER

SD SMOKE DETECTORSPKR SPRINKLER

TOP TOP OF PIPETS TAMPER SWITCH

UON UNLESS OTHERWISE NOTEDUP UP (PENETRATES FLOOR SLAB)

WFS WATER FLOW SWITCH

Z ZONE

NO. ISSUE DATE: DESCRIPTION

Page 13: G150004-000 F L R C P E M E-000

4"SP

DCDA

ALARM CHECKVALVE ASSEMBLY

6" TRANSITION TO 4" SPRINKLER SERVICE.REFER TO PLUMBING DRAWINGS FORCONTINUATION.

F14" RISER UP

4" TO 5" STORZ FDCREFER TO SITE CIVILPLANS FOR CONTINUATION

CHECK VALVE

CAP FOR FUTURE

RISER VALVE

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

3"SP 3"SP

4"SP

4"SP

1"SP

1"SP

1"SP

1"SP

1"SP

1"SP

11/4"

SP

11/4"

SP

4"SP

1"SP

1"SP

1"SP

1"SP

11/4"

SP

1

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

F-100G150004-000

FIRE PROTECTION LOWERLEVEL PLAN

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN

DRAWING KEY NOTES:

COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.1

NO. ISSUE DATE: DESCRIPTION

Page 14: G150004-000 F L R C P E M E-000

F1 4" RISER DN

(2) 2 1/2"FDC

4"DN

4"SP 4"SP 4"SP4"SPRUN SPRINKLER PIPE HIGHAND TIGHT TO STEEL BEAM

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

VEST.V-1

ALCOVEL101-5

WOMEN'S143

PASSAGE104

MEN'S142

ALCOVEL101-6JANITOR

141

MECHANICAL141.1

FAMILYTOILET

144

STORAGE140.1

PASSAGEL101-7

VEST.V-2

CLASSROOM/PRESENTATIONROOM

140

V.P. OFFICE112A

SMALL CONF.105

STORAGE103.1

OFFICE112

PASSAGEL101-1

OFFICE118

OFFICE114

OFFICE116

OFFICE110

OFFICE108

OFFICE104

CORRIDORC 1-1

CORRIDORC 1-2

BREAK ROOM107

STORAGE119

ELEC. RM.121

COFFEESTATIONL101-3

STORAGE103.2

ADMISSIONSOPEN OFFICE

106

HOUSINGOPEN OFFICE

130

OFFICE128

OFFICE126

OFFICE124

OFFICE122

MARKETINGOPEN OFFICE

120

SMALL CONF.115

CONFERENCE117

I.T. ROOM123

CALL CENTER109

CORRIDORC 1-3

OFFICE102

WORK ROOM111

RESOURCEROOM

103

RECEPT.L101-2

STUDENTWORK SPACE

113

LOBBYL101

11/4"

SP

11/4"

SP1"S

P

1"SP

1"SP

1"SP

1"SP

1"SP

1"SP

11/4"

SP

11/4"

SP1"S

P1"SP

1"SP

1"SP

11/2"

SP

11/2"

SP3"SP

3"SP

3"SP 3"SP 3"SP

1 1/2"SP1 1/4"SP

1"SP 1 1/4"SP

1 1/4"SP

1 1/4"SP

1"SP1"SP

1"SP1"SP

1 1/2"SP

1 1/2"SP

1"SP

1 1/2"SP

1 1/2"SP

1 1/2"SP

1 1/2"SP

1 1/2"SP

1 1/4"SP1"SP

1"SP

1"SP

11/2"

SP2"S

P11

/2"SP

1"SP1"SP1"SP

11/2"

SP

1"SP

1"SP

1"SP 1"SP

11/4"

SP2"S

P2"S

P 1"SP

1"SP

1 1/4"SP

1"SP 1"SP

11/2"

SP2"S

P

1"SP1"SP

1"SP 1"SP

2"SP

11/4"

SP11

/2"SP

1"SP

1"SP

1"SP

1"SP

1"SP 1 1/4"SP

11/4"

SP11

/4"SP

1"SP1"SP 1"SP 1"SP

1"SP 11/2"

SP11

/4"SP

1"SP

1"SP

11/4"

SP11

/2"SP

11/4"

SP1"S

P

1"SP

2"SP

1 1/2"SP

11/2"

SP

1"SP

1"SP

1"SP

2"SP

1"SP 1"SPA A

AA

A A

AA

A A

AA

A A A

1

1

11

11

11

1

1

1

INPECTORS TEST DRAIN

2

3 4

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

F-101G150004-000

FIRE PROTECTION GROUNDFLOOR PLAN

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN

DRAWING KEY NOTES:

PROVIDE SPRINKLER COVERAGE ABOVE AND BELOW COMBUSTIBLE WOOD CEILING.REFER TO DETAIL ON DRAWING F-200.

COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.

BASE: PROVIDE CONCEALED SPRINKLER PIPING AND SPRINKLER HEADS IN EPIC DECK CEILING STRUCTURE.COORDINATE WITH ARCHITECTURAL CEILING DETAILS AND DRAWINGS IN THIS AREA.

1

2

3

NO. ISSUE DATE: DESCRIPTION

Page 15: G150004-000 F L R C P E M E-000

DCDA

WITHOUT INSULATIONPIPE PENETRATION

PIPE TO BE CENTERED IN SLEEVE - DONOT SUPPORT PIPE FROM SLEEVE

TERMINAL SLEEVE FLUSH WITHFINISHED WALL SURFACES

SEALANT (SEE SPEC.)

PIPE SLEEVE

ESCUTCHEON PLATE FLUSH AGAINSTWALL AND OF SIZE TO COMPLETELYCOVER OPENING (TYPICAL BOTHSIDES OF WALL)

FINISHED WALL SURFACE

PIPE SLEEVE THRU FLOOR SLAB

SEALENT

FLOOR SLAB

RISER CLAP

PLAN VIEW

UPRIGHT SPRINKLERHEAD CONNECTION

UPRIGHT SPRINKLER HEAD

BRANCH LINE

1%%188" BRANCH TEE

1%%188" NIPPLE

1"x 1/2" REDUCER

SLAB ABOVE

SPRINKLER HEAD CONNECTION

& DWG FOR TYPE)(SEE SPECIFICATIONSPRINKLER HEAD

SUSPENDED CEILING

(IF REQUIRED)1" x 1/2" COUPLING

1" DROP NIPPLE

BRANCH PIPE

WET SYSTEMINSPECTOR'S TEST CONNECTION

WALLEXTERIOR

SPRINKLERFLOW EQUIVALENT TO ONERESISTANT OUTLET GIVINGSMOOTH BORE CORROSION

ABOVE FLOORNOT OVER 7 FT.1 IN. GLOBE VALVE

1 IN.

1 IN. BRANCH LINE 1 IN. PLUG

PITCH

SLEEVE ANDSEALANT

INSTALLATION SCHEMATICTYPICAL ALARM CHECK VALVE

PS

PG

PG

TS

TO SYSTEM

TO WMG

ORIFICE DRAIN

PROVIDE FUNNEL ANDEXTEND PIPE TO DRAIN

EXTEND PIPE TO DRAINBY-PASS WITHCHECK VALVE

FROM SUPPLY

FIRE ALARM TEST PIPEWITH VALVE (N.C.)

ALARM CHECK VALVE

TO ALARM PANEL(BY OTHERS)

TO ALARM PANEL(BY OTHERS)

SCALE:

FOR SPACES WITH CONCEALED COMBUSTILE CONSTRUCTIONTYPICAL SPRINKLER HEAD (W/ COVER PLATE) INSTALLATIONS

BRANCH TEE

ESCUTCHEON

1"x

NIPPLE

BRANCH LINE

CONSTRUCTIONTO PROTECT COMBUSTIBLEUPRIGHT SPRINKLER HEAD

HUNG CEILING

1/2" REDUCER

SPRINKLER HEAD(COLOR AS PER SCHEDULE)

T

T T T

T

T

1 SPRINKLER RISER DIAGRAMNONE

TYPICAL SPRINKLER HEAD IN EPIC DECK DETAIL

AC

ROOF

GROUND FLOOR

LOWER LEVEL

ROOF

GROUND FLOOR

LOWER LEVEL

(2) 2 1/2" FDC

6" COMBINED DOMESTIC AND SPRINKLERWATER SERVICE. 5'-0" FROM BUILDING.FOR CONTINUATION REFER TO SITE/CIVILDRAWINGS.

4"CHECK VALVE

4"

ALARM CHECK VALVE

4"

4"

3" TO SPRINKLERS

2 1/2" DOMESTIC WATER SERVICE.FOR CONTINUATION REFER TOPLUMBING DRAWINGS.

BY FC BY PC

4"

2 1/2"

6"

F1

RISER VALVE

4"TO SPRINKLERS

4"

EPIC DECKSPRINKLER HEAD(COLOR TO BEWHITE)

SPRINKLER PIPEW/EPIC DECK FASTNER ROOF DECK

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

F-200G150004-000

FIRE PROTECTION RISERDIAGRAMS & DETAILS

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION

Page 16: G150004-000 F L R C P E M E-000

SECURITY SYMBOL LISTSECURITY SYMBOLS

SECURITY CAMERA FIXEDX = FLOORY = TYPEXX = NUMBER

SECURITY CAMERA PTZX = FLOORY = TYPEXX = NUMBER

CARD READERB = BIOMETRICC = PROXIMITY/KEYPADM = MAGNETICP = PROXIMITY

DOOR CONTACT

WINDOW CONTACT

DURESS ALARM

INTERCOMM = MASTER STATIONS = SUB STATION

VIDEO INTERCOMM = MASTER STATIONS = SUB STATION

GUEST LOCKS = STAND ALONEIR = INFRA REDRF = RADIO FREQUENCY

REQUEST TO EXITM = MOTIONPB = PUSH BUTTON

DELAYED EGRESS

DOOR RELEASE

LCD SECURITY MONITOR

DIGITAL VIDEO RECORDER

NETWORK VIDEO RECORDER

GLASS BREAK SENSOR

LOCAL ALARM SOUNDER

ELECTRIC DOOR STRIKE

ELECTRIC LOCKSET WITH REX SWITCHFL = FAIL SECURE (DEFAULT)FS = FAIL SAFE

TRANSFER HINGE (POWER & RX)

ELECTROMAGNETIC LOCKS = SINGLED = DOUBLE

PANIC BUTTON

MOTION DETECTOR

FIRE RELAY (CLASS "E" FIRE ALARM)

FIBER OPTIC TRANSMITTER

FIBER OPTIC RECEIVER

IP CONVERTER

JUNCTION BOX - 4"Lx4"Wx4"D

JUNCTION BOX - 6"Lx6"Wx4"D

POWER SUPPLY

ANNUNCIATOR

EMERGENCY TELEPHONE

ACCESS CONTROL SERVER

PATCH PANEL

CLOSED CIRCUIT TELEVISION POWER SUPPLY

UNINTERUPTIBLE POWER SUPPLY

POWER SYMBOLSTRANSFORMER

20A, 125V DUPLEX RECEPTACLE - FLUSH WALL MOUNTED

20A, 125V QUADRUPLEX RECEPTACLE - FLUSH WALLMOUNTED

20A, 125V ISOLATED GROUND, DUPLEX RECEPTACLE, FLUSHFLOOR MOUNTED.

20A, 125V DUPLEX RECEPTACLE FLUSH WALL MOUNTED.GFI TYPE.

20A, 125V EMERGENCY DUPLEX RECEPTACLE.FLUSH WALL MOUNTED

20A, 125V DUPLEX RECEPTACLE SURFACE MOUNTED

20A, 125V SURGE SUPPRESSION DUPLEX RECEPTACLE.FLUSH WALL MOUNTED

FLUSH FLOOR MOUNTED JUNCTION BOX OR POKE-THRUFOR ELECTRIFIED FURNITURE POWER FEED

C = VOICE/DATA FEED

20A, 125V DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED

20A, 125V QUADRUPLEX RECEPTACLE FLUSH FLOORMOUNTED

SPECIAL PURPOSE RECEPTACLE - FLUSH WALL MOUNTEDA = TYPE

SPECIAL PURPOSE RECEPTACLE - FLUSH FLOOR MOUNTEDA = INDICATES TYPE

FLUSH FLOOR MOUNTED 20A, 125V DUPLEX RECEPTACLE

FLUSH FLOOR MOUNTED 20A, 125V QUADRUPLEXRECEPTACLE

FLUSH FLOOR MOUNTED JUNCTION BOX OR POKE-THRUFOR ELECTRIFIED FURNITURE POWER FEED.

PEDESTAL MOUNTED SPECIAL PURPOSE RECEPTACLELETTER INDICATES TYPE

PEDESTAL MOUNTED COMBINATION VOICE/DATA & POWEROUTLET

CEILING MOUNTED JUNCTION BOX WITH FINAL EQUIPMENTCONNECTION

FLUSH WALL MOUNTED JUNCTION BOX WITH FINALEQUIPMENT CONNECTION

FLUSH FLOOR MOUNTED JUNCTION BOX

PULLBOX

POWER POLE

EXISTING CONDUIT TO BE REMOVED

EXISTING CONDUIT/EQUIPMENT TO REMAIN

NEW CONCEALED CONDUIT

NEW EXPOSED CONDUIT

NEW UNDERGROUND/IN SLAB CONDUIT

NEW EMERGENCY CONDUIT

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT STUB-UP WITH FLEXIBLE EQUIPMENTCONNECTION

FLEXIBLE EQUIPMENT CONNECTION

CAPPED CONDUIT

HOMERUN - NUMERAL WHERE USED INDICATES CIRCUITNUMBER FOR REFERENCE ONLY.

HOMERUN - NUMERAL WHERE USED INDICATES CIRCUITNUMBER FOR REFERENCE ONLY

UNDERFLOOR DUCT WITH COMPARTMENT JUNCTION BOXT = TELEPHONEP = POWERS = SIGNAL

CABLE TRAY

SECTION A# = DRAWING NUMBER

a

C

A

A

T

13,5,

1

A

J

J

J

P

S

TP

FIX

PTZ

CR

DC

WC

DA

IC

VI

GL

RX

DE

DR

MON

DVR

NVR

GB

LA

DS

EL

TH

ML

PB

MD

K

FOT

FOR

IPC

J1

PS

AN

ET

ACS

CCTVPS

PP

UPSPS

J2

X-Y-XX

X-Y-XX

X

X

X

X

X

X

X

A

#

SECURITY DEVICE DESIGNATIONS

X = FLOOR NUMBERY = DEVICE TYPE:

A = ACCESSC = CAMERAL = LOCKM = MONITORING

## = SEQUENTIAL NUMBER

X-Y-##

1. ALL WORK SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, NFPA,UL, ADA AND ALL OTHER GOVERNING AGENCIES HAVING JURISDICTION.

2. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK. FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OF OTHER TRADES TO VERIFY SPACECONDITIONS.MAINTAIN HEADROOM AND SPACE CONDITIONS.

3. VERIFY LOCATIONS OF VIDEO CAMERAS IN FINISHED SPACES WITH ARCHITECTURAL DRAWINGS OF INTERIORDETAILS AND FINISH. PROVIDE BACK BOXES AND CONDUIT RUNS TO THE NEAREST ACCESSIBLE

CEILING ON THE SIDE OF THE BUILDING WITH THE IDF ROOM FOR ALL CAMERAS. CAMERAS ANDASSOCIATED WIRING SHALL BE INSTALLED BY A SEPERATE CONTRACTOR.

4. FIRESTOPPING SHALL BE INSTALLED WHENEVER WIRING OR RACEWAYS CROSS FIRE RATED CONSTRUCTION.

5. ANY DAMAGE TO PARTITIONS, FLOORS, CEILINGS OR ANY PART OF THE BUILDING OR EQUIPMENTCAUSED BY THE WORK OF THE CONTRACTOR SHALL BE MADE GOOD AT NO ADDITIONAL EXPENSE TO THEOWNER.

6. ALL CUTTING AND PATHING SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR.

7. CONTRACTOR, BEFORE INSTALLING ANY OF THE WORK, SHALL SEE THAT IT DOES NOT INTERFERE WITHCLEARANCES REQUIRED FOR FINISHED COLUMNS, HUNG CEILINGS, PLASTER, PARTITIONS, WALLS, ETC., ASSHOWN IN THE ARCHITECTURAL DRAWINGS AND DETAILS. IF ANY WORK IS SO INSTALLED AND IT LATERDEVELOPS THAT SUCH DETAILS OR DESIGN CANNOT BE FOLLOWED, CONTRACTOR AT HIS OWN EXPENSESHALL MAKE SUCH CHANGES IN THE WORK AS DIRECTED BY THE ARCHITECT, AS WELL AS TO PERMIT THEINSTALLATION OF THE ARCHITECTURAL WORK AS SHOWN ON THE PLANS AND DETAILS.

8. FINAL ACCEPTANCE IS TO BE MADE AFTER THE CONTRACTOR HAS DEMONSTRATED THAT THE WORKFULLFILLS THE REQUIREMENTS OF THE PLANS AND SPECIFICATIONS.

9. CONTRACTOR SHALL PROVIDE COMPLETE AS-BUILT DOCUMENTATION AND ACAD DRAWINGS.

10. MECHANICAL DOOR LOCK HARDWARE BY OTHERS. COORDINATE WITH ARCHITECT AND GENERAL CONTRACTOR.

11. COORDINATE MOUNTING OF CARD READERS WITH GENERAL CONTRACTOR AT LOCATIONS WHERE THECARD READERS ARE LOCATED ON MULLIONS.

12. COORDINATE EXACT LOCATIONS AND FINISHES OF DEVICES WITH ARCHITECT.

SECURITY GENERAL NOTES0

2'

4'

6'

08

'1

6'

24

'0

6"

9"

3"

01

'6

"1

-6"

01

/2

'1

'2

'0

1'

2'

3'

01

'2

'4

'0

2'

4'

8'

4'

08

'1

6'

08

'1

6'

32

'

SHEET NUMBER

SFA PROJECT NUMBER

FULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SC

ALE

: 1/

16

" =

1'-0

"S

CA

LE: 1

/8

" =

1'-0

"S

CA

LE: 1

/4

" =

1'-0

"S

CA

LE: 1

/2

" =

1'-0

"S

CA

LE: 3

/4

" =

1'-0

"S

CA

LE: 1

" =

1'-0

"S

CA

LE: 1

1/

2"

= 1

'-0"

SC

ALE

: 3"

= 1

'-0"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SC

ALE

: 3/

32

" =

1'-0

"S

CA

LE: 3

/8

" =

1'-0

"

PROJECT No: MI-1105

C:\

Revi

t Lo

cal F

iles\

G1

50

00

4-0

00

- M

ille

rsvi

lle -

MEP

15

_C

entr

al_

ska

pla

n.rv

t

SC-000G150004-000

SECURITY COVER SHEET

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SECURITY ABBREVIATIONS

N NEUTRAL

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NP NETWORK PROTECTOR

NTS NOT TO SCALE

OC ON CENTER

OCB OIL CIRCUIT BREAKER

OD OUTSIDE DIAMETER

P POLE

PA PUBLIC ADDRESS

PAP PLUMBING ALARM PANEL

PB PULL BOX

PBS PUSH BUTTON SWITCH

PHC PIPE HEATING CABLE

PNL PANEL

PR PRINTER

PS PRESSURE SWITCH

PT POTENTIAL TRANSFORMER

PWR POWER

ø PHASE

(RE) RELOCATED EXISTING

(RRO) EXISTING TO BE REMOVED AND RETURN TO OWNER

RCS REMOTE CONTROL SWITCH

RDCP REMOTE DATA COLLECTION PANEL

RECEPT, REC RECEPTACLE

REF REFRIGERATOR

REQ REQUIRED

RFL RAISED FLOOR

RG ROOM GROUND POINT

RM ROOM

RO RACEWAY ONLY

RP REFERENCE GROUND POINT

SAP SPRINKLER ALARM PANEL

SBST SUBSTATION

SCH SCHEDULE

SD SMOKE DETECTOR

SDP SMOKE DETECTION PANEL

SE SINGLE ENDED SUBSTATION

SECT SECTION

SIG SIGNAL

SN SOLID NEUTRAL

SP SINGLE POLE

SPEC SPECIFICATION

SPKLR SPRINKLER

SPKR SPEAKER

SV SOLENOID VALVE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYM SYMMETRICAL

SYS SYSTEMS

TB TROUBLE BELL

TBD TO BE DETERMINED

TEL TELEPHONE

TEMP TEMPERATURE

THERM THERMOSTAT

TLBD TERMINAL BOARD

TP TAMPER PROOF

TRANSF, XFMR TRANSFORMER

TS TAMPER SWITCH

TV TELEVISION

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UH UNIT HEATER

UNF UNFUSED

UON UNLESS OTHERWISE NOTED

V VOLT OR VOLTAGE

VA VOLT AMPERE

VFD VARIABLE FREQUENCY DRIVE

VM VOLTMETER

VP VAPORPROOF

W WATT

WFS WATER FLOW SWITCH

WHM WATT HOUR METER

WP WEATHERPROOF

WT WATERTIGHT

XP EXPLOSION PROOF

+ SPECIAL MOUNTING HEIGHT. COORDINATE LOCATION WITH ARCHITECTURALELEVATIONS

1P SINGLE POLE

2P TWO POLE

3P THREE POLE

A AMPERE

AC ABOVE COUNTER

ACB AIR CIRCUIT BREAKER

AFF ABOVE FINSIHED FLOOR

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALM ALARM

AMM AMMETER

AQST AQUASTAT

ARF ABOVE RAISED FLOOR

ASYM ASYMMETRICAL

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BG BREAK GLASS SWITCH

BIL BASIC IMPULSE LEVEL

BLDG BUILDING

C CONDUIT

CAB CABINET

CAT CATALOG

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CL CENTER LINE

CLG CEILING

CLOS CLOSET

CNTL CONTROL

CO CONDUIT ONLY

COMM COMMUNICATION

CONN CONNECTED

CONT CONTINUATION

CT CURRENT TRANSFORMER

CU COPPER

CUH CABINET UNIT HEATER

DB DECIBEL

DE DOUBLE ENDED SUBSTATION

DEG DEGREE

DF DRINKING FOUNTAIN

DIA DIAMETER

DISC DISCONNECT

DIV DIVISION

DN DOWN

DP DISTRIBUTION PANEL BOARD

DT DUST TIGHT

DWG DRAWING

°C DEGREE CELSIUS

°F DEGREE FAHRENHEIT

(E) EXISTING TO REMAIN

(ER) EXISTING TO BE REMOVED

(ERR) EXISTING TO BE REMOVED & RELOCATED

EA EACH

EC ELECTRICAL CONTRACTOR

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EMER, EM EMERGENCY

EQUIP EQUIPMENT

ERC ELECTRIC REHEAT COIL

EWC ELECTRIC WATER COOLER

EXIST, EX EXISTING

EXT EXTERIOR

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FAP FIRE ALARM ANNUNCIATOR PANEL

FBO FURNISHED BY OTHER DIVISION OF WORK

FCU FAN COIL UNIT

FDR FEEDER

FDS FUSED DISCONNECT SWITCH

FIXT FIXTURE

FL FLOOR

FLA FULL LOAD AMPERES

FLEX FLEXIBLE

FLUOR FLUORESCENT

FM FLOOR MACHINE

FRZ FREEZER

FSP FAN SHUTDOWN PANEL

FT FEET OR FOOT

G GROUND

GEN GENERATOR

GFI GROUND FAULT INTERRUPTER

HC HUNG CEILING

HH HAND HOLE

HID HIGH INTENSITY DISCHARGE

HN HALF NEUTRAL

HP HORSE POWER

HV HIGH VOLTAGE

HZ HERTZ

IC INTERRUPTING CAPACITY

ID INSIDE DIAMETER

INCAND INCANDESCENT

INST INSTRUMENT

IPC ISOLATED POWER CENTER

IPX ISOLATED POWER CENTER-X-RAY

JB JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILS

KV KILOVOLT

KVA KILOVOLT AMPERE

KW KILOWATT

KWH KILOWATT HOUR

LCP LOCAL CONTROL PANEL

LIM LINE ISOLATION MONITOR

LTG LIGHTING

MAP MECHANICAL ALARM PANEL

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPERES

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MER MECHANICAL EQUIPMENT ROOM

MFS MAIN FUSED SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MLO MAIN LUG ONLY

MOPD,MOCP MAXIMUM OVERCURRENT PROTECTION

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MUFS MAIN UNFUSED SWITCH

NO. ISSUE DATE: DESCRIPTION

Page 17: G150004-000 F L R C P E M E-000

CR

CR

CRCR

CR

CR

LA

LA

LACR

LA

LA

LA

CR

CR

PB

PB

PB

HW#1

4/SC-300

HW#1

4/SC-300

HW#7

8/SC-300

HW#16

10/SC-300

HW#7

8/SC-300

HW#2

5/SC-300

SEE TELECOM

DRAWINGS FOR

MORE

INFORMATION

ACCESS CONTROL PANEL

AND POWER SUPPLY -SEE

ELEV. DETAIL 1/SC-300 1

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

VEST.

V-1

ALCOVE

L101-5

WOMEN'S

143

PASSAGE

104

MEN'S

142

ALCOVE

L101-6JANITOR

141

MECHANICAL

141.1

FAMILY

TOILET

144

STORAGE

140.1

PASSAGE

L101-7

VEST.

V-2

CLASSROOM/PRESENTATION

ROOM

140

V.P. OFFICE

112A

SMALL CONF.

105

STORAGE

103.1

OFFICE

112

PASSAGE

L101-1

OFFICE

118

OFFICE

114

OFFICE

116

OFFICE

110

OFFICE

108

OFFICE

104

CORRIDOR

C 1-1

CORRIDOR

C 1-2BREAK ROOM

107

STORAGE

119

ELEC. RM.

121

COFFEE

STATION

L101-3

STORAGE

103.2

ADMISSIONS

OPEN OFFICE

106

HOUSING

OPEN OFFICE

130

OFFICE

128

OFFICE

126

OFFICE

124

OFFICE

122

MARKETING

OPEN OFFICE

120

SMALL CONF.

115

CONFERENCE

117

I.T. ROOM

123

CALL CENTER

109

CORRIDOR

C 1-3

OFFICE

102

WORK ROOM

111

RESOURCE

ROOM

103

RECEPT.

L101-2

STUDENT

WORK SPACE

113

LOBBY

L101

HW#13

9/SC-300

HW#5

6/SC-300

HW#6

7/SC-300

5

HW#3

4/SC-300

3

ARCHITECTURAL BOLLARD

BY OTHERS

2

4

TO DOOR JUNCTION BOX -

SEE DOOR DETAIL 4/SC-300

4

5

HW#3

4/SC-300

TO DOOR JUNCTION BOX -

SEE DOOR DETAIL 4/SC-300

3

ARCHITECTURAL BOLLARD

BY OTHERS

2

02'

4'

6'

08'

16'

24'

06"

9"

3"

01'

6"

1-6"

01/2'

1'

2'

01'

2'

3'

01'

2'

4'

02'

4'

8'

4'

08'

16'

08'

16'

32'

SHEET NUMBER

SFA PROJECT NUMBER

FULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCALE: 1/16" = 1'-0"

SCALE: 1/8" = 1'-0"

SCALE: 1/4" = 1'-0"

SCALE: 1/2" = 1'-0"

SCALE: 3/4" = 1'-0"

SCALE: 1" = 1'-0"

SCALE: 1 1/2" = 1'-0"

SCALE: 3" = 1'-0"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCALE: 3/32" = 1'-0"

SCALE: 3/8" = 1'-0"

PROJECT No: MI-1105

C:\Revit Local Files\G150004-000 - M

illersville -

MEP15_Central_skaplan.rvt

SC-100G150004-000

SECURITY GROUND FLOORPLAN

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1

GROUND FLOOR PLAN

DRAWING NOTES:

1. FOR SECURITY SYMBOLS, ABBREVIATIONS, AND OVERALL GENERAL NOTES, REFER TO

DRAWING SC-000.

2. REFER TO POWER PLANS FOR LOCATION AND QUANTITIES OF POWER DEVICES.

3. ALL CCTV CAMERAS AND ASSOCIATED WIRING SHALL BE PROVIDED BY AND INSTALLED BY A

SEPERATE CONTRACTOR.

5. LOCATIONS OF CONDUIT SYSTEM ROUTING IS DIAGRAMMATIC ONLY. CONDUIT SHALL BE

INSTALLED AS NECESSARY TO AVOID OTHER FACILITIES. COORDINATE INSTALLATION WITH ALL

TRADES TO PROVIDE A COORDINATED LAYOUT.

6. REFER TO SECURE DOOR ELEVATIONS, LOCATED ON DETAIL DRAWINGS.

7. COORDINATE MOUNTING HEIGHTS AND DEVICE LOCATIONS WITH ARCHITECTURAL DRAWINGS.

PROVIDE BACK BOX FLUSH WITH CEILING FOR CCTV CAMERA TO BE INSTALLED BY OTHERS.

COORDINATE EXACT LOCATION IN FIELD WITH OWNER. REFER TO DETAIL 2/SC-300.

SURFACE MOUNT CARD READER TO ARCHITECTURAL BOLLARD. COORDINATE EXACT MOUNTING

REQUIREMENTS IN FIELD WITH OWNER AND ARCHITECTURAL DETAILS.

DIRECT-BURIED 1" CONDUIT, PROVIDED BY ELECTRICAL CONTRACTOR, FOR SECURITY AND DOOR

CONTROL WIRING TERMINATED TO JUNCTION BOX SERVING SECURE DOOR. COORDINATE ALL

WORK WITH ELECTRICAL CONTRACTOR.

COORDINATE LOCATION OF PUSH BUTTON WITH ARCHITECTURAL DETAILS, OWNER, AND GENERAL

CONTRACTOR.

PROVIDE SURFACE MOUNT BACK BOX ON FACE OF STRUCTURAL BEAM FOR CCTV CAMERA TO BE

INSTALLED BY OTHERS. PROVIDE CONCEALED CONDUIT TO ACCESSABLE CEILING ON THE IDF

ROOM SIDE OF THE BUILDING FOR CAMERA INSTALLED TO RUN WIRE. COORDINATE LOCATION IN

FIELD WITH OWNER AND ARCHITECTURAL DETAILS. REFER TO DETAIL 3/SC-300.

1

KEY NOTES:

NO. ISSUE DATE: DESCRIPTION

2

3

4

5

Page 18: G150004-000 F L R C P E M E-000

CR

TH

DA

DR

SCALE:

CR DCCR TH CR CR DCCR TH

DC

ML RX RX CR ML RX RX CR ML RX CR ML RX ML RX CR ML RX ML RX

ML

PB PB PB PB PB PB PB

1ACCESS CONTROL RISER DIAGRAM

NTS

EL

TS

J1

J2

J1

EL

J1 J1 J1 J1

LA

J1

EL

LALAJ1 J1 J1 J1 J1

LA

LA

2WPWP

M M 2WP M M 2 M M M M M 2

ACCESS CONTROL KEY NOTES:

PROVIDE TAMPER SWITCH WITHIN DATA GATHERING

PANEL ENCLOSURE TO ALARM WHEN CABINET IS OPENED.

ACCESS CONTROL PANEL SHALL HAVE CAPACITY TO

SERVE QUANTITY OF CARD READERS INDICATED PLUS

10% SPARE FOR FUTURE GROWTH.

1

2

ACCESS CONTROL SYSTEM NOTES:

1. ACCESS CONTROL SYSTEM COMPONENTS INCLUDING BUT

NOT LIMITED TO CARD READERS, REQUEST TO EXIT

DEVICES, DOOR CONTACTS, DOOR CONTROLLERS, DATA

GATHERING PANELS AND SIMILAR ACTIVE DEVICES SHALL

BE PROVIDED BY DIVISION 26 SECURITY CONTRACTOR.

2. ACCESS CONTROL SYSTEM CABLING SHALL BE

FURNISHED AND INSTALLED BY DIVISION 26 SECURITY

CONTRACTOR AND TERMINATED ONTO ACCESS CONTROL

DEVICES.

3. UNSHIELDED TWISTED PAIR (UTP) FOR ETHERNET AND

FIBER-OPTIC CABLING SHALL BE FURNISHED AND

INSTALLED BY DIVISION 27 TELECOMMUNICATIONS

CONTRACTOR.

4. COORDINATE ALL CABLE TYPES, AND QUANTITIES WITH

EQUIPMENT MANUFACTURER.

5. COORDINATE ALL DEVICE LOCATIONS, OUTLET BOX

DIMENSIONS, CONDUIT SIZES AND SIMILAR

INFRASTRUCTURE REQUIREMENTS IN FIELD WITH OWNER

AND EQUIPMENT VENDOR PRIOR TO COMMENCEMENT OF

ANY WORK.

ACCESS CONTROL DRAWING NOTES:

1. FOR SYMBOLS AND ABBREVIATIONS REFER TO DRAWING

SC-000.

2. FOR IT CLOSET ROOM DETAILS REFER TO

TELECOMMUNICATION DRAWINGS.

3. THIS RISER DIAGRAM INDICATES POSSIBLE TYPICAL

ARRANGEMENTS ONLY; FOR EXACT LOCATIONS AND NUMBER

OF DEVICES REFER TO FLOOR PLANS, DOOR ELEVATION

DETAILS AND DOOR HARDWARE SPECIFICATIONS.

4. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR

EQUIPMENT PANEL, CONDUIT, WIRE SIZES, WIRE TYPES AND

ACTUAL ROUTING OF RACEWAYS.

5. COORDINATE ALL WORK WITH OWNER STANDARDS AND

SPECIFICATIONS.

6. REFER TO DOOR ELEVATION DETAILS ON DRAWING

SC-300 FOR SPECIFIC DOOR CABLING REQUIREMENTS.

ACCESS CONTROL WIRING SCHEDULE:

A PROVIDE 6#18 AWG COPPER CONDUCTORS SHIELDED IN

PLENUM RATED SHEATHING FOR CARD READER

CONNECTION TO DATA GATHERING PANEL (DGP). REFER

TO SECURE DOOR ELEVATION FOR ADDITIONAL CABLING

REQUIREMENTS.

B PROVIDE 2#18 AWG COPPER CONDUCTORS

NON-SHIELDED IN PLENUM RATED SHEATHING FOR LOCAL

AUDIBLE ALARM CONNECTION TO DATA GATHERING

PANEL (DGP).

C PROVIDE 2#22 AWG COPPER CONDUCTORS

NON-SHIELDED IN PLENUM RATED SHEATHING FOR

DURESS ALARM, DOOR CONTACT, DOOR RELEASE AND

PUSH BUTTON CONNECTION TO DATA GATHERING PANEL

(DGP).

E UNSHIELDED TWISTED PAIR (UTP) CATEGORY 6A CABLE

PROVIDED BY DIVISION 27 COMMUNICATIONS

CONTRACTOR; PROVIDE JUMPER (PATCH CABLE) FROM

LAN OUTLET TO EQUIPMENT.

DIAGRAM SYMBOLS:

CARD READER

WP - WEATHERPROOF

MAGNETIC LOCK

TRANSFER HINGE

ELECTRIC LATCH

JUNCTION BOXES

DURESS ALARM

DOOR RELEASE

TAMPER SWITCH

/

ACCESSIBLE CEILINGSYSTEM (TYP.)

CABLE TRAY (TYP.)

A

VESTIBULE V1-1A HOUSINGCORRIDOR #103

A

RESOURCE ROOM#103

A

PASSAGE#L101-1

A

MARKETING OPENOFFICE #120

A

ACCESSCONTROL PANEL

21

LOCAL AUDIBLE ALARM

A

RESOURCE ROOM#103A

DOOR CONTACT

REQUEST TO EXIT - MOTION TYPEM

C

VESTIBULE V1-1

A

VESTIBULE V1-2A

C

VESTIBULE V1-2

A

PRESENTATIONL101-7

A

PRESENTATIONL101-4

LOBBYL101

ITROOM #123

MECHROOM #002

UNEXCAVATED

LOWERLEVEL

GROUNDLEVEL

ROOF

LOMBARDO WELCOME CENTER

02

'4

'6

'0

8'

16

'2

4'

06

"9

"3

"0

1'

6"

1-6

"0

1/

2'

1'

2'

01

'2

'3

'0

1'

2'

4'

02

'4

'8

'4

'0

8'

16

'0

8'

16

'3

2'

SHEET NUMBER

SFA PROJECT NUMBER

FULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SC

ALE

: 1/

16

" =

1'-0

"S

CA

LE: 1

/8

" =

1'-0

"S

CA

LE: 1

/4

" =

1'-0

"S

CA

LE: 1

/2

" =

1'-0

"S

CA

LE: 3

/4

" =

1'-0

"S

CA

LE: 1

" =

1'-0

"S

CA

LE: 1

1/

2"

= 1

'-0"

SC

ALE

: 3"

= 1

'-0"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SC

ALE

: 3/

32

" =

1'-0

"S

CA

LE: 3

/8

" =

1'-0

"

PROJECT No: MI-1105

C:\

Revi

t Lo

cal F

iles\

G1

50

00

4-0

00

- M

ille

rsvi

lle -

MEP

15

_C

entr

al_

ska

pla

n.rv

t

SC-200G150004-000

SECURITY SINGLE LINEDIAGRAM

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION

Page 19: G150004-000 F L R C P E M E-000

SCALE:

SCALE: SCALE:

SCALE: SCALE: SCALE: SCALE:

SCALE:

SCALE: SCALE:

S

TS

FA

4SECURE DOOR ELEVATION HARDWARE SETS #1 AND #3

NONE

5SECURE DOOR ELEVATION HARDWARE SET #2

NONE 6SECURE DOOR ELEVATION HARDWARE SET #5

NONE

7SECURE DOOR ELEVATION HARDWARE SET #6

NONE 8SECURE DOOR ELEVATION HARDWARE SET #7

NONE 9SECURE DOOR ELEVATION HARDWARE SET #13

NONE 10SECURE DOOR ELEVATION HARDWARE SET #16

NONE

1DATA GATEHRING PANEL ELEVATION DETAIL

NONE

2CCTV MINI-DOME IP CAMERA INTERIOR CEILING MOUNT

NONE3

CEILING SURFACE MOUNTED MOUNTED CCTV MINI-DOME CAMERANONE

J1 TO CONTROL PANEL

3

2

RECESSED DOOR OPERATOR IN SLAB

STUB 3/4" CONDUIT WITH DRAG LINE

PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH

COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.

KEY NOTES:

2

3

1

1

CEILING SLAB

FINISHED FLOOR

FINISHED CEILING

4 CARD READER (UNPROTECTED SIDE)

6 6

5 5

7

3' 6"

4

5 EXIT DEVICE BAR

6 MAGNETIC LOCK

7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)

J1

DOOR OPERATION:

-DOOR NORMALLY CLOSED AND LOCKED

-ENTRY BY VALID CARD READ; EITHER POWER OPERATED

OR MANUAL PULL

-FREE EGRESS AT ALL TIMES VIA PANIC DEVICE; REQUEST

TO EXIT MOTION SENSOR WILL SIGNAL VALID EGRESS

-LOCK IS FAIL-SECURE UPON POWER LOSS

-ACTIVATION OF INTERIOR VESTIBULE DOOR

PUSHBUTTON WILL OPEN DOOR UNDER TIME DELAY

-DOOR WILL FAIL-SAFE UNDER FIRE ALARM CONDITION

ARCHITECTURAL BOLLARD

PS

8

8 POWER SUPPLY

TO 120 VAC

J1 TO CONTROL PANEL

3

2

RECESSED DOOR OPERATOR IN SLAB

STUB 3/4" CONDUIT WITH DRAG LINE

PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH

COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.

KEY NOTES:

2

3

1

1

CEILING SLAB

FINISHED FLOOR

FINISHED CEILING

4 PUSH BUTTON (UNPROTECTED SIDE)

5 5

7

3' 6"

4

5 EXIT DEVICE BAR

6 (NOT USED)

7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)

J1

PS

8

8 POWER SUPPLY

TO 120 VAC

DOOR OPERATION:

-DOOR NORMALLY CLOSED AND UNLOCKED

-ENTRY BY VALID CARD READ WILL ACTIVE POWER

OPERATOR OR MANUAL PULL ALWAYS AVAILABLE

-FREE EGRESS AT ALL TIMES VIA PANIC DEVICE; REQUEST

TO EXIT MOTION SENSOR WILL SIGNAL VALID EGRESS

-ACTIVATION OF INTERIOR VESTIBULE DOOR

PUSHBUTTON WILL OPEN DOOR

J1 TO CONTROL PANEL

3

RECESSED DOOR OPERATOR IN SLAB

STUB 3/4" CONDUIT WITH DRAG LINE

PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH

COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.

KEY NOTES:

2

3

1

1

CEILING SLAB

FINISHED FLOOR

FINISHED CEILING

4 CARD READER (UNPROTECTED SIDE)

6

5

7

3' 6"

4

5 EXIT DEVICE BAR

6 MAGNETIC LOCK

7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)

J1

DOOR OPERATION:

-DOOR NORMALLY CLOSED AND LOCKED

-ENTRY BY VALID CARD READ; EITHER POWER OPERATED

OR MANUAL PULL

-FREE EGRESS AT ALL TIMES VIA PANIC DEVICE; REQUEST

TO EXIT MOTION SENSOR WILL SIGNAL VALID EGRESS

-LOCK IS FAIL-SECURE UPON POWER LOSS

-AUDIBLE CHIME WILL RING EACH TIME DOOR IS OPENED

PS

8

8 POWER SUPPLY

TO 120 VAC

3' 6"

9

2

10

9 PUSH BUTTON (UNPROTECTED SIDE)

10 LOCAL AUDIBLE CHIME

J1 TO CONTROL PANEL

3

2

PUSH BUTTON (UNPROTECTED SIDE)

STUB 3/4" CONDUIT WITH DRAG LINE

PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH

COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.

KEY NOTES:

2

3

1

CEILING SLAB

FINISHED FLOOR

FINISHED CEILING

4 CARD READER (UNPROTECTED SIDE)

6 6

5 5

7

5 EXIT DEVICE BAR

6 MAGNETIC LOCK

7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)

J1

DOOR OPERATION:

-DOOR NORMALLY CLOSED AND LOCKED

-ENTRY BY VALID CARD READ

-PUSH BUTTON WILL RELEASE MAGNETIC LOC FOR

EGRESS; REQUEST TO EXIT MOTION SENSOR WILL

SIGNAL VALID EGRESS

-LOCK IS FAIL-SECURE UPON POWER LOSS

-DOOR WILL FAIL-SAFE UNDER FIRE ALARM CONDITION

PS

8

8 POWER SUPPLY

TO 120 VAC

3' 6"

4

3' 6"

1

J1 TO CONTROL PANEL

3

2

PUSH BUTTON (UNPROTECTED SIDE)

STUB 3/4" CONDUIT WITH DRAG LINE

PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH

COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.

KEY NOTES:

2

3

1

CEILING SLAB

FINISHED FLOOR

FINISHED CEILING

4 CARD READER (UNPROTECTED SIDE)

6

5

7

5 EXIT DEVICE BAR

6 MAGNETIC LOCK

7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)

J1

DOOR OPERATION:

-DOOR NORMALLY CLOSED AND LOCKED

-ENTRY BY VALID CARD READ

-PUSH BUTTON WILL RELEASE MAGNETIC LOCK FOR

EGRESS; REQUEST TO EXIT MOTION SENSOR WILL

SIGNAL VALID EGRESS

-LOCK IS FAIL-SECURE UPON POWER LOSS

-DOOR WILL FAIL-SAFE UNDER FIRE ALARM CONDITION

PS

8

8 POWER SUPPLY

TO 120 VAC

3' 6"

4

3' 6"

1

J1 TO CONTROL PANEL

3

2

PUSH BUTTON (UNPROTECTED SIDE)

STUB 3/4" CONDUIT WITH DRAG LINE

PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH

COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.

KEY NOTES:

2

3

1

CEILING SLAB

FINISHED FLOOR

FINISHED CEILING

4 CARD READER (UNPROTECTED SIDE)

6

5

7

5 EXIT DEVICE BAR

6 MAGNETIC LOCK

7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)

J1

DOOR OPERATION:

-DOOR NORMALLY CLOSED AND LOCKED

-ENTRY BY VALID CARD READ

-PUSH BUTTON WILL RELEASE MAGNETIC LOCK FOR

EGRESS; REQUEST TO EXIT MOTION SENSOR WILL

SIGNAL VALID EGRESS

-LOCK IS FAIL-SECURE UPON POWER LOSS

-AUDIBLE CHIME WILL RING EACH TIME DOOR IS OPENED

-DOOR WILL FAIL-SAFE UNDER FIRE ALARM CONDITION

PS

8

8 POWER SUPPLY

TO 120 VAC

3' 6"

4

3' 6"

1

9

9 LOCAL AUDIBLE CHIME

FINISHED FLOOR

CEILING SLAB

FINISHED CEILING

J1

STUB 3/4" CONDUIT WITH DRAG LINE (TYPICAL)

PROVIDE 4" x 4" x 2" DEEP JUNCTION BOX WITH

COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.

CARD READER (BOTH SIDES)

LOCKING DEVICE: ELECTRIFIED MORTISE WITH INTEGRAL RX SWITCH

POWER TRANSFER HINGE AND MORTAR JUNCTION BOX

STUB 3/4" CONDUIT DOWN DOOR FRAME ONTHE HINGE SIDE OF THE DOOR BACK BOX, TO JUNCTION BOXLOCATED ABOVE ACCESSIBLE CEILING

NOTES:

TO CONTROL PANEL

J1

J1

TH

EL

CR

6

5

4

2

3

1

56

1

4

2

3

WIRE HARNESS BY HARDWARE INSTALLER7

3' 6"

7

DOOR OPERATION:

-DOOR NORMALLY CLOSED AND LOCKED; DOOR SWITCH

RELAYS POSITION

-ENTRY BY VALID CARD READ BOTH DIRECTIONS

-FREE EGRESS AT ALL TIMES VIA HANDLE; INTEGRAL RX

SWITCH WILL SIGNAL VALID EGRESS

-LOCK IS FAIL-SECURE UPON POWER LOSS - CORRIDOR

INTO ROOM

-DOOR WILL FAIL-SAFE UNDER FIRE CONDITION

-AUDIBLE CHIME WILL RING WITH EACH DOOR OPEN

4

9 8

DOOR CONTACT8 DC

LOCAL AUDIBLE CHIME9 LA

PS

10

POWER SUPPLY10 PS

TO 120 VAC

FINISHED FLOOR

CEILING SLAB

FINISHED CEILING

J1

STUB 3/4" CONDUIT WITH DRAG LINE (TYPICAL)

PROVIDE 4" x 4" x 2" DEEP JUNCTION BOX WITH

COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.

CARD READER (BOTH SIDES)

LOCKING DEVICE: ELECTRIFIED MORTISE WITH INTEGRAL RX SWITCH

POWER TRANSFER HINGE AND MORTAR JUNCTION BOX

STUB 3/4" CONDUIT DOWN DOOR FRAME ONTHE HINGE SIDE OF THE DOOR BACK BOX, TO JUNCTION BOXLOCATED ABOVE ACCESSIBLE CEILING

NOTES:

TO CONTROL PANEL

J1

J1

TH

EL

CR

6

5

4

2

3

1

56

1

4

2

3

WIRE HARNESS BY HARDWARE INSTALLER7

3' 6"

7

9 8

PS

10

TO 120 VAC

DOOR OPERATION:

-DOOR NORMALLY CLOSED AND LOCKED; SWITCH RELAYS

DOOR POSITION

-ENTRY BY VALID CARD READ

-FREE EGRESS AT ALL TIMES VIA HANDLE; INTEGRAL RX

SWITCH WILL SIGNAL VALID EGRESS

-LOCK IS FAIL-SECURE UPON POWER LOSS - CORRIDOR

INTO ROOM

-DOOR WILL FAIL-SAFE UNDER FIRE CONDITION

-AUDIBLE CHIME WILL RING WITH EACH DOOR OPEN

DOOR CONTACT8 DC

LOCAL AUDIBLE CHIME9 LA

POWER SUPPLY10 PS

CAT-6A CABLE AND OUTLET JACK BY

CONTRACTOR, TO DATA CLOSETTO FIRE ALARM CONTROL PANEL. SEE

FIRE PROTECTION DRAWING

FIRE ALARM INTERFACE RELAY.

COORDINATE WITH FIRE ALARM SYSTEM

INSTALLATION

3/4" FIRE SAFE PLYWOOD MOUTNING

BACKBOARD WITHIN ENCLOSURE

120V, 20 AMP DEDICATED DUPLEX RECEPTACLE TO

ELECTRICAL PANEL -

REFER TO ELECTRICAL DRAWING(TYP)

NETWORK

CONNECTOR -

REFER TO TELECOM

DRAWINGS

ACCESS

CONTROL

PANEL

LOCKPOWER

LOCK

POWER

FAIL

SAFE

LOCK

POWER

AUX

POWER

CABLE TROUGH

6'-6" CA

BLE

TR

OU

GH 4

5

1

(TYP.)

2

(TYP.)

(TYP.)

KEY NOTES:

1

2

3

4

5

I-STAR

7

8

6

TWO (2) SPST LOCAL TOGGLE TYPE

DISCONNECT SWITCHES

PROVIDE QUANTITY OF CARD READER MODULES, INPUT RELAYS AND OUTPUT RELAYS WITHIN ACCESS CONTROL PANEL ENCLOSURE AS REQUIRED TO SUPPORT THE QUANTITY AND TYPES

OF DEVICES SHOWN ON THE RISER DIAGRAM AND DOOR ELEVATION DETAILS.

PROVIDE QUANTITY OF POWER SUPPLY MODULES AS REQUIRED TO PROVIDE POWER TO ALL DEVICES AND MODULES REQUIRED TO SUPPORT THE DEVICES SHOWN ON THE RISER DIAGRAMS

AND DOOR ELEVATION DETAILS.

PROVIDE 60"H X 60"W X 10"D STEEL NEMA 1 ENCLOSURE WITH HINGED, LOCKING FRONT DOOR, VENTILATED BOTTOM, AND VENTILATION FAN FOR MOUNTING OF ACCESS CONTROL

EQUIPMENT. PANELS SHALL BE MANUFACTURED BY HOFFMAN OR APPROVED EQUAL.

COORDINATE FIRE ALARM INTERFACE CONNECTIONS WITH ELECTRICAL DRAWINGS AND CONTRACTOR.

PROVIDE VERTICAL AND HORIZONTAL CABLE TROUGHS IN LOCATIONS AS SHOWN WITH MINIMUM CROSS-SECTION DIMENSIONS OF 8" X 8" IN LENGTHS AS REQUIRED.

BOTTOM VENTALATION LOUVER WITH FILTER MATERIAL SIZE AS RECOMENDED BY ENCLOSURE VENDOR.

VENTILATION FAN WITH CORD/ENDPLUG RATED FOR 120VAC SIZED AS RECOMMENDED BY ENCLOSURE VENDOR.

TAMPER SWITCH MOUNTED WITHIN ENCLOSURE TO ALARM WHEN DOOR IS OPENED.

6

7

8

MINI-DOME CAMERA BY OTHER CONTRACTOR

CEILING - REFER TO

PROVIDE MINIMUM 3/4" CONDUIT RUN CONCEALED

TO ABOVE ACCESSIBLE CEILING

PROVIDE BACKBOX - 4" X 4" X 2 1/8"D

NOTES:

1. DETAIL REPRESENTS TYPICAL SECURITY REQUIREMENTS. SEE THE FLOOR PLANS FOR

DEVICE LOCATIONS.

ARCHITECTURAL PLANSPROVIDE BACK-BOX

MINI-DOME CAMERA BY

CEILING DECK

NOTES:

4"x4"x1.5" (D)

OTHER CONTRACTOR

PROVIDE MINIMUM 3/4" CONDUIT

RUN CONCEALED TO ABOVEACCESSIBLE CEILING

1. DETAIL REPRESENTS TYPICAL SECURITY REQUIREMENTS. SEE THE FLOOR PLANS FOR

DEVICE LOCATIONS.

02

'4

'6

'0

8'

16

'2

4'

06

"9

"3

"0

1'

6"

1-6

"0

1/

2'

1'

2'

01

'2

'3

'0

1'

2'

4'

02

'4

'8

'4

'0

8'

16

'0

8'

16

'3

2'

SHEET NUMBER

SFA PROJECT NUMBER

FULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SC

ALE

: 1/

16

" =

1'-0

"S

CA

LE: 1

/8

" =

1'-0

"S

CA

LE: 1

/4

" =

1'-0

"S

CA

LE: 1

/2

" =

1'-0

"S

CA

LE: 3

/4

" =

1'-0

"S

CA

LE: 1

" =

1'-0

"S

CA

LE: 1

1/

2"

= 1

'-0"

SC

ALE

: 3"

= 1

'-0"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SC

ALE

: 3/

32

" =

1'-0

"S

CA

LE: 3

/8

" =

1'-0

"

PROJECT No: MI-1105

C:\

Revi

t Lo

cal F

iles\

G1

50

00

4-0

00

- M

ille

rsvi

lle -

MEP

15

_C

entr

al_

ska

pla

n.rv

t

SC-300G150004-000

SECURITY DETAILS

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION

Page 20: G150004-000 F L R C P E M E-000

T

FIRE PROTECTION SYMBOL LISTBASIC

FIRE STANDPIPE PIPING (STANDALONE)

SPRINKLER PIPING

DRY SPRINKLER PIPING

PRE-ACTION SPRINKLER PIPING

DRAIN PIPING

PIPING BELOW SLAB

EXISTING PIPING

EXISTING WORK TO BE REMOVED

HEAT TRACE / FREEZE PROTECTION CABLE & INSULATION

SLOPED CHANGE IN PIPE ELEVATION

BOTTOM PIPE CONNECTION

TOP PIPE CONNECTION

SIDE CONNECTION

PIPE DOWN/DROP

PIPE RISE/UP

PIPE SLOPE

VALVE IN VERTICAL

UNION

REDUCER

WATER PROOF SLEEVE

SLEEVE

FIRE EXTINGUISHERA - WATERB - DRY CHEMICALC - GASEOUS (CO2 OR HALON 1211 - SEE SPEC.)

FIRE EXTINGUISHER IN CABINET

FIRE HOSE VALVE

FIRE HOSE VALVE IN CABINET

FIRE HOSE VALVE w/HOSE IN CABINET

FIRE HOSE VALVE w/FIRE EXTINGUISHER

ROOF MANIFOLD (3-WAY)

SPRINKLER CONTROL VALVE ASSEMBLY

VALVE ASSEMBLYAC - ALARM CHECKDR - DRY PIPEPA - PRE ACTION

CONNECT TO EXISTING

DISCONNECT FROM EXISTING

FIRE DEPARTMENT SIAMESE CONNECTION (WALL MOUNTED)

EXISTING FIRE HYDRANT

NEW FIRE HYDRANT

TEMPERATURE AND PRESSURE RELIEF VALVE

PLUG VALVE

MIXING VALVE

RELIEF VALVE

BALL VALVE

GATE VALVE

GLOBE VALVE

OUTSIDE SCREW & YOKE (OS & Y) VALVE

CHECK VALVE

PRESSURE REDUCING VALVE (PRV)

SOLENOID VALVE

FLOAT VALVE

Y STRAINER w/BLOW-OFF VALVE

REDUCED PRESSURE DETECTOR ASSEMBLY

DOUBLE CHECK DETECTOR ASSEMBLY

HYDRAULIC REF. POINTS # = ELEMENT, # = NODE

TAMPER SWITCH

WATERFLOW SWITCH

PRESSURE GAUGE w/GAUGE COCK

RISER DESIGNATION:X = RISER SERVICE; # = RISER NUMBER

EXTEND EXISTING SPRINKLER PIPING TO NEW SPRINKLER HEAD

DSP

RPDA

DCDA

X#

#

F

PA

DR

S

S

#

FE-X

FE-X

X

FE-X

FP-2-3

XXX-XX-XX

SECOND FLOOR

(REFER TO SPECIFIC TRADE LIST)

EQUIPMENT TAG NUMBERFLOOR DESIGNATIONEQUIPMENT DESIGNATION

FIRE PUMP(REFER TO LIST)

UNIT NUMBER 3

FP EQUIPMENT DESIGNATIONS

1. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL FIRE PROTECTION DRAWINGS.

2. ALL WORK IS NEW UNLESS OTHERWISE NOTED.

3. ALL FIRE PROTECTION WORK SHALL BE IN ACCORDANCE WITH THE CURRENT FIRE PROTECTION CODEAND ALL APPLICABLE LOCAL CODES AND DRAWINGS.

4. PROVIDE WET-PIPE SPRINKLERS IN ALL AREAS.

5. SECURE WATER FLOW TEST DATA TAKEN FROM FIRE HYDRANTS NEAREST SITE. IF RECENT FLOW TESTDATA IS NOT AVAILABLE FROM CITY RECORDS, MAKE NECESSARY TESTS AS REQUIRED BY NFPASTANDARDS TO DETERMINE CHARACTER OF WATER SUPPLY. MINIMUM OF 20 PSI DROP IN PRESSUREBETWEEN STATIC AND RESIDUAL PRESSURE SHALL BE REQUIRED IN ORDER TO OBTAIN ACCURATEDATA.

6. SPRINKLER SYSTEM SHALL BE HYDRAULICALLY CALCULATED.

7. ADD 10% CONTINGENCY FACTOR TO HYDRAULIC CALCULATIONS.

8. EXACT LOCATION OF SPRINKLER HEADS IN FINISHED AREAS WITH SUSPENDED CEILING SHALL BE ASINDICATED ON REFLECTED CEILING PLANS.

9. MINIMUM PRESSURE AT END SPRINKLER HEAD 7 PSI.

10. EQUIVALENT FITTING LENGTHS USED IN HYDRAULIC CALCULATIONS SHALL BE IN ACCORDANCE WITHNFPA STANDARD NO. 13 AND FACTORY MUTUAL 0.5 2-8N.

11. MAXIMUM FLOW VELOCITY SHALL NOT EXCEED 20 F.P.S.

12. ALL AUTOMATIC SPRINKLER HEADS, PIPE FITTINGS, PIPE HANGERS, AUTOMATIC CONTROL VALVES ANDMANUAL CONTROL VALVES SHALL BE UL LISTED AND BEAR FACTORY MUTUAL APPROVAL AND SHALL BEAPPROVED BY THE ENGINEER PRIOR TO INSTALLATION.

13. ALL EXPOSED PIPE, FITTINGS, HANGERS AND SUPPLEMENTARY STEEL SHALL BE PAINTED.

14. ENDS OF ALL CROSS MAINS SHALL BE PROVIDED WITH THREADED FLUSHING CONNECTION NO MORETHAN 2 INCHES IN DIAMETER.

15. PROVIDE AUXILIARY DRAINS FOR ALL PIPING BELOW DUCT SPRINKLERS AND OPEN TRAPPED SECTIONS.PIPING TO ONE SINGLE SPRINKLER IS EXCLUDED.

16. PROVIDE FLUSHING CONNECTIONS WHERE REQUIRED BY NFPA AND F.M.

17. COORDINATE WITH OWNER FOR ALL SHUTDOWNS.

18. PROVIDE TEST CONNECTIONS AT HIGHEST POINT OF MAIN PORTION OF EACH SPRINKLER SYSTEM, WITH1" PIPE AND VALVE. TEST PIPE SHALL BE CONNECTED TO SPRINKLER PIPE AT LEAST 1-1/4" IN SIZE ANDSHALL DISCHARGE OUTSIDE BUILDING OR THROUGH 1/2" SMOOTH BORE BRASS OUTLET, WHERE IT CANBE EASILY SEEN.

19. PROVIDE ADDITIONAL HEADS UNDER DUCTWORK LARGER THAN 48" WIDE.

20. THE REUSE OF EXISTING SPRINKLER HEADS SHALL BE PROHIBITED.

21. NEW SPRINKLER HEAD TYPE AND TEMPERATURE RATING SHALL BE IN ACCORDANCE WITH SCHEDULEUNLESS NOTED OTHERWISE AND/OR REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION.

22. COORDINATE ALL PIPE PENETRATIONS AND CORING WITH STRUCTURAL ENGINEER AND INACCORDANCE WITH DIVISION 01.

23. REFER TO ARCHITECTURAL DRAWINGS FOR ALL CEILING RELATED WORK.

24. COORDINATE ALL NEW FIRE PROTECTION WORK WITH ALL NEW DUCTWORK, PIPING AND UTILITIES OFANY SYSTEMS. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE INTENT OF THE DESIGN. REROUTE ANYPIPING AROUND EXISTING AND/OR NEW SYSTEMS INCLUDING ALL REQUIRED FITTINGS AND SUPPORTSTO MAKE THE INSTALLATION OF THE PIPING AND SPRINKLER HEADS POSSIBLE. RESEAL ANY FIREAND/OR SMOKE RATED PENETRATIONS THAT HAVE BEEN AFFECTED AS A RESULT OF THEMODIFICATION.

25. ALL COMPONENTS USED IN FIRE PROTECTION SYSTEMS SHALL BE IN ACCORDANCE WITH THE OWNER'SGUIDELINES, STANDARDS AND SPECIFICATIONS.

26. WATER SUPPLY INFORMATION TO BE VERIFIED BY FLOW TEST.

27. REPAIR AND PATCH ANY PENETRATIONS CREATED AS PART OF THIS SCOPE OF WORK. MATCH NEWFINISHES WITH ARCHITECTURAL PLANS.

28. COORDINATE INSTALLATION OF PIPING AND SPRINKLER HEADS WITH ALL OTHER TRADES.

29. ALL EXCAVATION AND BACKFILL REQUIRED FOR FIRE PROTECTION WORK SHALL BE BY THE FIREPROTECTION CONTRACTOR. REFER TO SITE SPECIFICATIONS FOR MORE INFORMATION ONEXCAVATION AND BACKFILL REQUIREMENTS.

30. PAINTING OF ALL ARCHITECTURALLY EXPOSED PIPING WORK SHALL BE BY THE GENERAL CONTRACTOR.PAINTING OF ANY NON-ARCHITECTURALLY EXPOSED PIPING SHALL BE BY THIS TRADES CONTRACTOR.REFER TO DIVISION 9 PAINTING.

31. FIRESTOPPING FOR THE WORK INCLUDED IN THESE DOCUMENTS, SHALL BE FURNISHED AND INSTALLEDBY THE FIRE PROTECTION CONTRACTOR. REFER TO DIVISION 7 FIRESTOPPING.

32. SLEEVES THAT ARE REQUIRED FOR THIS PROJECTS SHALL BE FURNISHED BY THE FIRE PROTECTIONCONTRACTOR AND INSTALLED BY THE GENERAL CONTRACTOR. COORDINATE THE LOCATION OF THESLEEVES WITH THE GENERAL CONTRACTOR.

FIRE PROTECTION GENERAL NOTES SPRINKLER HEAD SCHEDULE

MODEL NUMBER

MANUFACTURER

STAR

TYPE

EXIST

SPRI

NKLE

RHD

FLUS

HPE

NDEN

T

REMO

VED/

RELO

CATE

DEX

ISTSP

RHO

TOBE

EXTE

NDED

COVE

RAGE

QUIC

KRES

PONS

E

INTE

RMED

IATES

HIEL

D

(CHR

OMEF

INISH

)SID

EWAL

L

FLUS

HCO

NCEA

LED

PLAT

ESPK

R.

DESIG

NATIO

N

SEMI

-REC

ESSE

D

UPRI

GHT

PEND

ENT

DRY

CENT

RAL

RELIA

BLE

GRIN

NELL

VIKIN

G

REMARKS

A

NOTES:

2. PROVIDE ESCUTCHEONS WHEN PENETRATING EXPOSED WALL.

1. EXPOSED UPRIGHT HEADS IN OCCUPIED SPACES SHALL BE CHROME FINISH.

3. PROVIDE SPRINKLER GUARDS AT ALL HEADS 7'-0" AND LOWER.

4. COORDINATE COLOR SELECTION WITH ARCHITECT.A. SPRINKLER AND ESCUTCHEON TO BE WHITEB. SPRINKLER HEAD TO BE WHITEC. COVER PLATE TO BE WHITED. SPRINKLER AND SHIELD IN EXPOSED IN COORIDORS TO BE WHITEE. SPRINKLER AND SHIELD IN WOOD SLOT CEILING TO BE BLACK

F1FR56 INTERMEDIATE LEVELW/ SHIELD

F1FR56

F1FR56

G4A

DH56 DRY

K=5.6, 1/2" ORIFICE

K=5.6, 1/2" ORIFICE

K=5.6, 1/2" ORIFICE165°F RATING

155°F RATING

155°F RATING

K=5.6, 1/2" ORIFICE155°F RATING

F1FR56 K=5.6, 1/2" ORIFICE155°F RATING

K=5.6, 1/2" ORIFICE155°F RATING

SEE NOTE 4C.

SEE NOTE 4B.

SEE NOTE 4D AND 4E

SEE NOTE 4A.

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

F-000G150004-000

FIRE PROTECTION COVERSHEET

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

FIRE PROTECTION ABBREVIATIONSABD AUTOMATIC BALL DRIPAD AREA DRAINAFF ABOVE FINISHED FLOORATS AUTOMATIC TRANSFER SWITCH

BOP BOTTOM OF PIPE

CFM CUBIC FEET PER MINUTECV CHECK VALVE

DIA DIAMETERDN DOWN (PENETRATES FLOOR SLAB)DR DRAIN

(E) EXISTING(ER) EXISTING TO BE REMOVED(ERR) EXISTING TO BE REMOVED & RELOCATED

FD FLOOR DRAINFHC FIRE HOSE CABINETFHR FIRE HOSE RACKFHV FIRE HOSE VALVEFHVC FIRE HOSE VALVE CABINETFL FLOORFP FIRE PUMPFSP FIRE STANDPIPEFT FEET

GAL GALLONSGC GENERAL CONTRACTORGPM GALLONS PER MINUTEGV GATE VALVE

HD HEAT DETECTOR

ID INSIDE DIAMETERIN INCH

JP JOCKEY PUMP

MAX MAXIMUMMIN MINIMUM

NC NORMALLY CLOSENIC NOT IN THIS CONTRACTNO NORMALLY OPENNTS NOT TO SCALE

OD OUTSIDE DIAMETEROS&Y OUTSIDE SCREW & YOKE GATE VALVE

PRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCH (GAUGE)PSIA POUNDS PER SQUARE INCH (ABSOLUTE)

(RE) RELOCATED EXISTING(RRO) EXISTING TO REMOVED AND RETURN TO OWNER

SD SMOKE DETECTORSPKR SPRINKLER

TOP TOP OF PIPETS TAMPER SWITCH

UON UNLESS OTHERWISE NOTEDUP UP (PENETRATES FLOOR SLAB)

WFS WATER FLOW SWITCH

Z ZONE

NO. ISSUE DATE: DESCRIPTION

Page 21: G150004-000 F L R C P E M E-000

4"SP

DCDA

ALARM CHECKVALVE ASSEMBLY

6" TRANSITION TO 4" SPRINKLER SERVICE.REFER TO PLUMBING DRAWINGS FORCONTINUATION.

F14" RISER UP

4" TO 5" STORZ FDCREFER TO SITE CIVILPLANS FOR CONTINUATION

CHECK VALVE

CAP FOR FUTURE

RISER VALVE

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

3"SP 3"SP

4"SP

4"SP

1"SP

1"SP

1"SP

1"SP

1"SP

1"SP

11/4"

SP

11/4"

SP

4"SP

1"SP

1"SP

1"SP

1"SP

11/4"

SP

1

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

F-100G150004-000

FIRE PROTECTION LOWERLEVEL PLAN

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN

DRAWING KEY NOTES:

COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.1

NO. ISSUE DATE: DESCRIPTION

Page 22: G150004-000 F L R C P E M E-000

F1 4" RISER DN

(2) 2 1/2"FDC

4"DN

4"SP 4"SP 4"SP4"SPRUN SPRINKLER PIPE HIGHAND TIGHT TO STEEL BEAM

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

VEST.V-1

ALCOVEL101-5

WOMEN'S143

PASSAGE104

MEN'S142

ALCOVEL101-6JANITOR

141

MECHANICAL141.1

FAMILYTOILET

144

STORAGE140.1

PASSAGEL101-7

VEST.V-2

CLASSROOM/PRESENTATIONROOM

140

V.P. OFFICE112A

SMALL CONF.105

STORAGE103.1

OFFICE112

PASSAGEL101-1

OFFICE118

OFFICE114

OFFICE116

OFFICE110

OFFICE108

OFFICE104

CORRIDORC 1-1

CORRIDORC 1-2

BREAK ROOM107

STORAGE119

ELEC. RM.121

COFFEESTATIONL101-3

STORAGE103.2

ADMISSIONSOPEN OFFICE

106

HOUSINGOPEN OFFICE

130

OFFICE128

OFFICE126

OFFICE124

OFFICE122

MARKETINGOPEN OFFICE

120

SMALL CONF.115

CONFERENCE117

I.T. ROOM123

CALL CENTER109

CORRIDORC 1-3

OFFICE102

WORK ROOM111

RESOURCEROOM

103

RECEPT.L101-2

STUDENTWORK SPACE

113

LOBBYL101

11/4"

SP

11/4"

SP1"S

P

1"SP

1"SP

1"SP

1"SP

1"SP

1"SP

11/4"

SP

11/4"

SP1"S

P1"SP

1"SP

1"SP

11/2"

SP

11/2"

SP3"SP

3"SP

3"SP 3"SP 3"SP

1 1/2"SP1 1/4"SP

1"SP 1 1/4"SP

1 1/4"SP

1 1/4"SP

1"SP1"SP

1"SP1"SP

1 1/2"SP

1 1/2"SP

1"SP

1 1/2"SP

1 1/2"SP

1 1/2"SP

1 1/2"SP

1 1/2"SP

1 1/4"SP1"SP

1"SP

1"SP

11/2"

SP2"S

P11

/2"SP

1"SP1"SP1"SP

11/2"

SP

1"SP

1"SP

1"SP 1"SP

11/4"

SP2"S

P2"S

P 1"SP

1"SP

1 1/4"SP

1"SP 1"SP

11/2"

SP2"S

P

1"SP1"SP

1"SP 1"SP

2"SP

11/4"

SP11

/2"SP

1"SP

1"SP

1"SP

1"SP

1"SP 1 1/4"SP

11/4"

SP11

/4"SP

1"SP1"SP 1"SP 1"SP

1"SP 11/2"

SP11

/4"SP

1"SP

1"SP

11/4"

SP11

/2"SP

11/4"

SP1"S

P

1"SP

2"SP

1 1/2"SP

11/2"

SP

1"SP

1"SP

1"SP

2"SP

1"SP 1"SPA A

AA

A A

AA

A A

AA

A A A

1

1

11

11

11

1

1

1

INPECTORS TEST DRAIN

2

3 4

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

F-101G150004-000

FIRE PROTECTION GROUNDFLOOR PLAN

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN

DRAWING KEY NOTES:

PROVIDE SPRINKLER COVERAGE ABOVE AND BELOW COMBUSTIBLE WOOD CEILING.REFER TO DETAIL ON DRAWING F-200.

COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.

BASE: PROVIDE CONCEALED SPRINKLER PIPING AND SPRINKLER HEADS IN EPIC DECK CEILING STRUCTURE.COORDINATE WITH ARCHITECTURAL CEILING DETAILS AND DRAWINGS IN THIS AREA.

1

2

3

NO. ISSUE DATE: DESCRIPTION

Page 23: G150004-000 F L R C P E M E-000

DCDA

WITHOUT INSULATIONPIPE PENETRATION

PIPE TO BE CENTERED IN SLEEVE - DONOT SUPPORT PIPE FROM SLEEVE

TERMINAL SLEEVE FLUSH WITHFINISHED WALL SURFACES

SEALANT (SEE SPEC.)

PIPE SLEEVE

ESCUTCHEON PLATE FLUSH AGAINSTWALL AND OF SIZE TO COMPLETELYCOVER OPENING (TYPICAL BOTHSIDES OF WALL)

FINISHED WALL SURFACE

PIPE SLEEVE THRU FLOOR SLAB

SEALENT

FLOOR SLAB

RISER CLAP

PLAN VIEW

UPRIGHT SPRINKLERHEAD CONNECTION

UPRIGHT SPRINKLER HEAD

BRANCH LINE

1%%188" BRANCH TEE

1%%188" NIPPLE

1"x 1/2" REDUCER

SLAB ABOVE

SPRINKLER HEAD CONNECTION

& DWG FOR TYPE)(SEE SPECIFICATIONSPRINKLER HEAD

SUSPENDED CEILING

(IF REQUIRED)1" x 1/2" COUPLING

1" DROP NIPPLE

BRANCH PIPE

WET SYSTEMINSPECTOR'S TEST CONNECTION

WALLEXTERIOR

SPRINKLERFLOW EQUIVALENT TO ONERESISTANT OUTLET GIVINGSMOOTH BORE CORROSION

ABOVE FLOORNOT OVER 7 FT.1 IN. GLOBE VALVE

1 IN.

1 IN. BRANCH LINE 1 IN. PLUG

PITCH

SLEEVE ANDSEALANT

INSTALLATION SCHEMATICTYPICAL ALARM CHECK VALVE

PS

PG

PG

TS

TO SYSTEM

TO WMG

ORIFICE DRAIN

PROVIDE FUNNEL ANDEXTEND PIPE TO DRAIN

EXTEND PIPE TO DRAINBY-PASS WITHCHECK VALVE

FROM SUPPLY

FIRE ALARM TEST PIPEWITH VALVE (N.C.)

ALARM CHECK VALVE

TO ALARM PANEL(BY OTHERS)

TO ALARM PANEL(BY OTHERS)

SCALE:

FOR SPACES WITH CONCEALED COMBUSTILE CONSTRUCTIONTYPICAL SPRINKLER HEAD (W/ COVER PLATE) INSTALLATIONS

BRANCH TEE

ESCUTCHEON

1"x

NIPPLE

BRANCH LINE

CONSTRUCTIONTO PROTECT COMBUSTIBLEUPRIGHT SPRINKLER HEAD

HUNG CEILING

1/2" REDUCER

SPRINKLER HEAD(COLOR AS PER SCHEDULE)

SINGLE ARM BRACE

ANGLE CLIP

UNISTRUT TO CLIPBOLTS CONNECTINGTWO 3/8" DIAMETER

BRACESINGLE ARM

PIPE

CLEVISPIPE

CLEVIS

SUPPORT ROD

45

PIPE

PLAN VIEW OF BRACE

HUNG PIPESINGLE ARM BRACE FOR CLEVIS

PLAN VIEW OF BRACE

PIPECLEVISPIPE

TRANSVERSE CABLE BRACECLEVIS

CABLE CONNECTION

CABLESEISMIC

SUPPORT ROD

45°

PIPE

LONGITUDINAL CABLE BRACE

BRACE FOR CLEVIS HUNG PIPETRAVERSE AND LONGITUDINAL CABLE

T

T T T

T

T

1 SPRINKLER RISER DIAGRAMNONE

TYPICAL SPRINKLER HEAD IN EPIC DECK DETAIL

AC

ROOF

GROUND FLOOR

LOWER LEVEL

ROOF

GROUND FLOOR

LOWER LEVEL

(2) 2 1/2" FDC

6" COMBINED DOMESTIC AND SPRINKLERWATER SERVICE. 5'-0" FROM BUILDING.FOR CONTINUATION REFER TO SITE/CIVILDRAWINGS.

4"CHECK VALVE

4"

ALARM CHECK VALVE

4"

4"

3" TO SPRINKLERS

2 1/2" DOMESTIC WATER SERVICE.FOR CONTINUATION REFER TOPLUMBING DRAWINGS.

BY FC BY PC

4"

2 1/2"

6"

F1

RISER VALVE

4"TO SPRINKLERS

4"

EPIC DECKSPRINKLER HEAD(COLOR TO BEWHITE)

SPRINKLER PIPEW/EPIC DECK FASTNER ROOF DECK

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

blim

.rvt

F-200G150004-000

FIRE PROTECTION RISERDIAGRAMS & DETAILS

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION

Page 24: G150004-000 F L R C P E M E-000

1. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL HVAC/MECHANICAL DRAWINGS.2. ALL WORK IS NEW UNLESS OTHERWISE NOTED.3. DRAWINGS ARE DIAGRAMMATIC. DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD.4. COORDINATE THIS WORK WITH THAT OF OTHER TRADES.5. DIMENSIONS SHOWN ON PLAN ARE HORIZONTAL. DIMENSIONS SHOWN IN ELEVATION ARE VERTICAL.6. NEITHER ACCURACY NOR COMPLETION OF SERVICES AND UTILITY LOCATIONS SHOWN ON DRAWINGS IS

GUARANTEED. DETERMINE EXACT LOCATIONS OF EXISTING SERVICES AND UTILITIES IN FIELD, WHETHER OR NOTSHOWN ON DRAWINGS. EXERCISE CAUTION AND IDENTIFY LOCATIONS OF UNMARKED UTILITY LINES ASNECESSARY TO PERFORM WORK OF THIS SECTION.

7. MANUFACTURERS MODEL NUMBERS ARE SPECIFIED AS BASIS OF DESIGN. REFER TO SPECIFICATIONS FOROTHER APPROVED MANUFACTURERS.

8. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURERS RECOMMENDATIONS.9. ALL ACCESS PANELS SHALL BE PROVIDED BY AND INSTALLED BY GC. CONTRACTOR SHALL BE RESPONSIBLE FOR

NOTIFYING GC WHERE ACCESS PANELS ARE REQUIRED.10. PROVIDE HANGERS, INSERTS, ANCHORS, SUPPLEMENTAL STEEL & SUPPORTS AS REQUIRED TO SUPPORT

DUCTWORK, PIPING AND EQUIPMENT FROM STRUCTURE.11. RUN DUCTS AND PIPING CONCEALED, UNLESS OTHERWISE SPECIFIED AND CLEAR OF CEILING INSERTS.12. INSTALL THERMOSTATS AT ADA COMPLIANT HEIGHTS OR AS DIRECTED OTHERWISE BY ARCHITECT.13. STRUCTURAL WELDING SHALL BE CONTINUOUS 1/4" FILLET UNLESS REQUIRED OTHERWISE.14. ALL SLEEVES AND PENETRATIONS THROUGH CONCRETE FLOORS AND ALL CORE DRILLING OR CUTTING OF

CONCRETE FLOORS AND WALLS SHALL BE BY THIS CONTRACTOR.15. ALL PAINTING SHALL BE DONE ACCORDING TO THE SPECIFICATIONS. MECHANICAL CONTRACTOR SHALL BE

RESPONSIBLE FOR ANY DAMAGE TO FINISHED SURFACES CAUSED BY HIS WORK.16. REQUIRED EXCAVATION AND BACKFILL REQUIRED FOR THIS PROJECT SHALL BE BY THIS CONTRACTOR UNLESS

OTHERWISE INDICATED. COORDINATE WITH OTHER TRADES.

AIR SYSTEMS

1. AIR SYSTEMS: REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF AIR DEVICES.2. INTERNAL AIRFLOW DIMENSIONS ARE SHOWN FOR DUCTS. INCREASE DUCT SIZE AS NECESSARY TO MAINTAIN

FREE FLOW AREA INDICATED.3. NO INTERNAL DUCT SOUND LINING OR INSULATION TO BE EXPOSED TO AIR STREAM.4. WHERE REQUIRED, ALL INTERNAL SOUND LINING SHALL BE CONTAINED WITHIN INTERSTITIAL SPACE OF DOUBLE

WALL DUCTWORK.5. ALL VISUALLY EXPOSED DUCTWORK IN FINISHED SPACES REQUIRES INSULATION TO BE DOUBLE WALL WITH

INTERSTITIAL INSULATION.6. USE FLAT TRANSVERSE SEAM FOR DUCTWORK WHERE SPACE AVAILABLE DICTATES.7. DIFFUSER SIZES SHOWN ARE NECK SIZES. REGISTERS AND GRILLE SIZES ARE NOMINAL.8. PROVIDE VOLUME DAMPERS OR OTHER APPROVED BALANCING DEVICES AT DUCT BRANCHES AND RUN OUTS,

AND AT REGISTER GRILLE AND DIFFUSER NECKS IN SUPPLY, RETURN AND EXHAUST DUCTWORK WHETHERSHOWN OR NOT.

9. DUCTWORK DOWNSTREAM OF ALL VAV BOXES SHALL BE DOUBLE WALL WITH INTERSTITIAL INSULATION FOR AMINIMUM OF 15 FEET.

10. PROVIDE 36" CLEARANCE IN FRONT OF ALL ELECTRIC CONTROL PANELS PER N.E.C. AND MFG. REQUIREMENTS.11. PROVIDE DUCT TRANSITIONS FROM VAV BOX INLET/OUTLET DUCT WORK AT SIZES INDICATED TO VAV BOX

INLET/OUTLET UNIT CONNECTIONS.12. VAV DUCT INLET SIZE SHALL BE AS SCHEDULED OR AS INDICATED ON THE FLOOR PLANS. PROVIDE TRANSITION

FROM DUCT SIZE INDICATED ON THE FLOOR PLANS TO SCHEDULED SIZE MINIMUM 2'-0" FROM VAV BOX INLETS.

PIPING SYSTEMS

1. PITCH PIPING 1" IN 20' IN DIRECTION OF FLOW.2. PROVIDE TRAPS IN CONDENSATE LINES THAT EXTEND OVER 2".3. COORDINATE HANGING METHODS WITH STRUCTURAL ENGINEER.

MECHANICAL GENERAL NOTES

SINGLE LINE DUCTWORK OR EQUIPMENT - EXISTING

EXISTING DUCTWORK TO BE REMOVED

DUCTWORK WITH ACOUSTIC LINING

VOLUME DAMPER

FIRE DAMPER AND ACCESS DOOR

BACKDRAFT DAMPER

AUTOMATIC DAMPER

HVAC DUCTWORKSINGLE LINE DUCTWORK OR EQUIPMENT - NEW

DUCTWORK POSITIVE PRESSURE(SUPPLY AIR OR FAN DISCHARGE)

DUCTWORK NEGATIVE PRESSURE(RETURN, EXHAUST OR OUTSIDE AIR)

VD

FD

BDD

M

COMBINATION SMOKE AND FIRE DAMPERWITH ACCESS DOOR

RISE IN DUCTWORK (IN DIRECTION OF AIR FLOW)R

DROP IN DUCTWORK (IN DIRECTION OF AIR FLOW)D

CENTERLINE

CUBIC FEET PER MINUTEOR CFM

DIAMETERØ

SQUARE FEET

OVAL DUCTWORK

TYPE A CEILING DIFFUSER400 CFM SUPPLY AIR

RECTANGULAR CEILING DIFFUSER WITH 12"x12" NECK400 CFM SUPPLY AIR

12x12 CD400

10" BY 8" CEILING REGISTER (CEILING GRILLE)300 CFM RETURN AIR

10x8 CR(CG)300

RECTANGULAR DIFFUSER WITH BLANKING PLATE

10" BY 6" TOP REGISTER, 150 CFM SUPPLY AIR10x8 TR150

10x8 TR(TG)150

10" BY 6" TOP REGISTER (TOP GRILLE)150 CFM RETURN AIR

10x8 BR(BG)150

10" BY 6" BOTTOM REGISTER (BOTTOM GRILLE)150 CFM RETURN AIR

VANED ELBOW (SEE DETAIL)

VANED ELBOW (SEE DETAIL) OR RADIUS ELBOW

FLEXIBLE DUCT

SLOTTED LINEAR DIFFUSER WITH PLENUM

DUCT FLEXIBLE CONNECTION

VERTICAL DUCT DROP(IN DIRECTION OF AIR FLOW)

VERTICAL DUCT RISE(IN DIRECTION OF AIR FLOW)

VARIABLE AIR VOLUME BOXTYPE AVARIABLE AIR VOLUME BOX, TYPE A,WITH REHEAT COILVARIABLE AIR VOLUME BOX, TYPE A, WITHSOUND ATTENUATOR AND REHEAT COIL

THERMOSTAT

H HUMIDISTAT

SMOKE DETECTORSD

HUMIDIFIERH

NEW PIPE WITH DIRECTION OF FLOW

PIPE DROP

PIPE RISE

HVAC PIPING

EXISTING PIPING

EXISTING PIPING TO BE REMOVED

EXISTING PIPING TO BE ABANDONED

PITCH UP IN DIRECTION OF FLOW

PITCH DOWN IN DIRECTION OF FLOW

UNION

CONCENTRIC REDUCER

ECCENTRIC REDUCER - FLAT BOTTOM

ECCENTRIC REDUCER - FLAT TOP

FLANGED CONNECTION

U

D

FLANGED END - BLIND FLANGE

EXPANSION LOOP

PIPE EXPANSION JOINT

PIPE ALIGNMENT GUIDE

PIPE ANCHOR

GATE VALVE

ANGLE GATE VALVE

GLOBE VALVE

ANGLE GLOBE VALVE

NEEDLE VALVE COCK

DRAIN VALVE

LOCK SHIELD VALVE

CHECK VALVE, SWING OR LIFT

SILENT CHECK (NON-SLAM) VALVE

FLEXIBLE CONNECTOR

BUTTERFLY VALVE

SQUARE HEAD COCK

BALANCING VALVE

PLUG VALVE (TYPE AS NOTED)

AUTOMATIC CONTROL VALVE

THREE-WAY AUTOMATIC CONTROL VALVE

BALL VALVE

"Y" TYPE STRAINER WITH BLOWOFF VALVE AND CAP

THERMOMETER AND WELL

PRESSURE GAUGE WITH SYPHON

PUMP

MECHANICAL SYMBOL LIST

AUTOMATIC SMOKE DAMPER

RISE IN DUCTWORK (IN DIRECTION OF AIR FLOW)UC

CONDENSER WATER SUPPLY

CHILLED WATER RETURN

CONDENSER WATER RETURN

CHILLED WATER SUPPLY

DOMESTIC WATER

DRAIN

HOT WATER RETURN

HOT WATER SUPPLY

CWR

CWS

CHWR

CHWS

DW

D

HWR

HWS

HVAC GENERALPOINT OF CONNECTION

POINT OF DISCONNECTION

NEW STEEL CUT

EXISTING STEEL CUT

DIRECT DIGITAL CONTROL PANEL

SECTION DESIGNATION

SHEET No. WHERE SECTION IS SHOWN

EQUIPMENT TAG NUMBERXXX-XX-XX

FLOOR DESIGNATIONEQUIPMENT DESIGNATION

UNIT NUMBER 3

ACU-2-3

SECOND FLOORAIR CONDITIONING UNIT

DDCP

HVAC EQUIPMENT DESIGNATIONS

SD M

FSD M

T

S

BALL JOINT

VAV-A

VAV-A

VAV-A

SECTION DESIGNATION

SHEET No. WHERE SECTION IS SHOWN

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-000G150004-000

MECHANICAL COVER SHEET

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

MECHANICAL ABBREVIATIONSHR HOURHRC HEAT RECOVERY COILHT HEIGHTHTWP HIGH TEMPERATURE WATER PUMPHV HEATING AND VENTILATINGHWP HOT WATER PUMPHX HEAT EXCHANGERHZ FREQUENCE

IN INCH OR INCHESIPS IRON PIPE SIZE

KW KILOWATTKX KITCHEN RANGE HOOD EXHAUST

L LENGTHLAT LEAVING AIRE TEMPERATURELBS POUNDSLCP LOCAL CONTROL PANELLD LINEAR DIFFUSERLDB LEAVING DRY BULB TEMPERATURELF, LIN.FT. LINEAR FEETLR LINEAR RETURNLRA LOCKED ROTOR AMPSLV LOW VELOCITYLWB LEAVING WET BULB TEMPERATURELWT LEAVING WATER TEMPERATURE

MAV MANUAL AIR VENTMAX MAXIMUMMBH THOUSAND BTU PER HOURMCC MOTOR CONTROL CENTERMD MOTORIZED DAMPERMER MECHANICAL EQUIPMENT ROOMMHP MOTOR HORSEPOWERMIN MINIMUMMM MILLIMETERMOT MOTORMOV MOTOR OPERATED VALVEMX MECHANICAL ROOM EXHAUST

N.O. NORMALLY OPENNC NORMALLY CLOSEDNIC NOT IN CONTRACTNO. NUMBERNPSH NET POSITIVE SUCTION HEADNTS NOT TO SCALE

OA OUTSIDE AIROAI OUTSIDE AIR INTAKEOD OUTSIDE DIAMETEROED OPEN END DUCTOV OUTLET VELOCITY

P PUMPPCC PRE-COOLING COILPD PRESSURE DROPPF PRE-FILTERPHC PREHEAT COILPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCHPSIA PSI ABSOLUTEPSIG PSI GAUGE

(RE) RELOCATED EXISTING(RRO) EXISTING TO REMOVED AND RETURN TO OWNERR RISERA RETURN AIRRAD RADIATIONRCC RECOOLING COILREFR REFRIGERANTRF RETURN FANRH RELATIVE HUMIDITYRHC REHEAT COILRHWP REHEAT WATER PUMPRLA RUNNING LOAD AMPSRM ROOMROT ROTATIONRPM REVOLUTIONS PER MINUTE

SA SUPPLY AIRSAU SOUND ATTENUATION UNITSCHWP SECONDARY CHILLED WATER PUMPSD SMOKE DETECTORSF SUPPLY FANSHWP SECONDARY HOT WATER PUMPSLD STRIPLINE DIFFUSERSMK.CTL. SMOKE CONTROL OPERATIONSP STATIC PRESSURESPEC SPECIFICATIONSQ.FT. SQUARE FEETSS STAINLESS STEELSX SMOKE EXHAUST

T THROATTAD TOP ANGULAR DISCHARGETDH TOTAL DYNAMIC HEADTEMP TEMPERATURETF TERMINAL FILTERTG TOP GRILLETHD TOP HORIZONTAL DISCHARGETR TOP REGISTERTRD TRANSFER DUCTTRF TRANSFER FANTRG TRANSFER GRILLETS TIP SPEEDTT TOP THROATTV TURNING VANESTX TOILET EXHAUSTTYP TYPICAL

UBD UPBLAST DISCHARGEUH UNIT HEATERUON UNLESS OTHERWISE NOTED

V VOLTSVA VENTILATION AIRVAC VACUUMVAV VARIABLE AIR VOLUME UNITVF VENTILATION FANVFD VARIABLE FREQUENCY DRIVEVIV VARIABLE INLET VANESVP VACUUM PUMP

W WIDTHW/ WITHW/O WITHOUTWB WET BULBWC WATER COLUMNWG WATER GAUGEWMS WIRE MESH SCREENWP WORKING PRESSUREWSP WORKING STEAM PRESSURE

A AMPERESAAV AUTOMATIC AIR VENTAC AIR CONDITIONINGACCU AIR COOLED CONDENSING UNITACS AUTOMATIC CONTROL SYSTEMACU AIR CONDITIONING UNITAD ACCESS DOORAF AFTER FILTERAFDW AIR FOIL DOUBLE WIDTHAFF ABOVE FINISHED FLOORAFMS AIR FLOW MONITORING STATIONAFSW AIR FOIL SINGLE WIDTHAHU AIR HANDLING UNITAL ALUMINUMAMCS AUTOMATED MONITORING AND CONTROL SYSTEMAP ACCESS PANEL

BAD BOTTOM ANGULAR DISCHARGEBD BLOW DOWNBF BOOSTER FANBFP BOTTOM GRILLEBG BOILER FEED PUMPBHD BOTTOM HORIZONTAL DISCHARGEBHP BRAKE HORSEPOWERBIDW BACKWARD INCLINE DOUBLE WIDTHBISW BACKWARD INCLUDE SINGLE WIDTHBMS BUILDING MANAGEMENT SYSTEMBR BOTTOM REGISTERBT BOTTOM THROATBTU BRITISH THERMAL UNITBTUH BTU PER HOUR

C CONVERTORCAR CONSTANT AIRFLOW REGULATORCC COOLING COILCCP CENTRAL CONTROL PANELCCW COUNTER CLOCKWISECD CEILING DIFFUSERCFFC CAP FOR FUTURE CONNECTIONCFM CUBIC FEET PER MINUTECFP CHEMICAL FEED PUMPCG CEILING GRILLECH CHILLERCHWP CHILLED WATER PUMPCLG CEILINGCOD CLEAN-OUT DOORCOMPR COMPRESSORCOND CONDENSATECOV CHAIR OPERATED VALVECP CONDENSATE PUMPCPA CONTROL POINT ADJUSTMENTCPU CONDENSATE PUMP UNITCR CEILING REGISTERCT COOLING TOWERCU FT CUBIC FEETCU IN CUBIC INCHESCUH CABINET UNIT HEATERCV CONSTANT VOLUMECW CLOCKWISECWP CONDENSER WATER PUMP°C DEGREES CENTIGRADE (CELSIUS)

D DROPDB DRY BULBDBD DOWN BLAST DISCHARGEDF DUCT FURNACE UNITDFWP DEARATOR FEED WATER PUMPDG DIESEL GENERATORDHW DOMESTIC HOTER WATERDMPR DAMPERDN DOWNDOP DIESEL OIL PUMPDWG DRAWINGDX DIRECT EXPANSIONø,DIAM DIAMETER

(E) EXISTING TO REMAIN(ER) EXISTING TO BE REMOVED(ERR) EXISTING TO BE REMOVED & RELOCATEDEA EACHEAT ENTERING AIR TEMPERATUREEDB ENTERING DRY BULB TEMPERATUREEDH ELECTRIC DUCT HEATEREDR EQUIVALENT DIRECT RADIATIONEF EXHAUST FANEL ELEVATIONELEC ELECTRICELEV ELEVATOREQ EQUALET EXPANSION TANKEUH ELECTRIC UNIT HEATEREWB ENTERING WET BULBEWT ENTERING WATER TEMPERATUREEXH EXHAUSTEXIST EXISTINGEXP EXPANSION

F FILTERF&T FLOAT AND THERMOSTATICFA FREE AREA (SQ.FT.)FC FLEXIBLE CONNECTIONFCDW FORWARD CURVED DOUBLE WIDTHFCSW FORWARD CURVED SINGLE WIDTHFCU FAN COIL UNITFD FIRE DAMPERFF FINAL FILTERFG FINISHED GRADEFIN FL FINISHED FLOORFLA FULL LOAD AMPERESFOP FUEL OIL PUMPFOT FUEL COIL TANKFPI FINS PER INCHFPM FEET PER MINUTEFPS FEET PER SECONDFR FLOOR REGISTERFT FEETFTR FINNED TUBE RADIATIONFV FACE VELOCITYFX FUME HOOD EXHAUST°F DEGREES FAHRENHEIT

G GAUGEGAL GALLONGPH GALLONS PER HOURGPM GALLONS PER MINUTEGX GENERAL EXHUAST

H HUMIDIFIERHALX HALON EXHAUSTHC HEATING COILHD HEAD

NO. ISSUE DATE: DESCRIPTION

Page 25: G150004-000 F L R C P E M E-000

CO

CO

GC

MC

EC

PC/FPC

WV

MH

MH

MH

MH

WV

WV

WV

MH

WV

WV

MH

WV

MH

WV

MH

MH

WV

MH

WV

WV

BENCHMARK

MAG NAIL SET IN

SIDEWALK SEAM

ELEVATION=317.62

EX. BUILDING

GORDINIER HALLEX. BUILDING

EX. BUILDING

STUDENT MEMORIAL

CENTER

EX.

BUILDING

EX.

BUILDING

EX.

BUILDING

FFE=320.17

FFE=320.21

FFE=320.22

FFE=304.93

C.O.

C.O.

C.O.

C.O.

C.O.

JAMES STREET

( MILLERSVILLE UNIVERSITY)

LOMBARDO WELCOMECENTER

WVWV

A

B

C

D

E

CLOSED LOOP VERTICAL BOREFIELDGEOTHERMAL HEAT EXCHANGERS.DEPRESS HEAD HEIGHT ANDHORIZONTALPIPING AS REQUIRED TO COORDINATEWITH OTHER UTILITIES. COORDINATEWITH CIVIL SITE PLAN FOR EXACT BORELOCATIONS AND PIPE ROUTING.

WHERE DESIGNATED BORES ARE NOT ABLETO BE DRILLED TO 400 FT, PROVIDEADDITIONAL BORES AND EXTEND PIPING LOOPTO MAKE UP LOST DEPTH AT GHOSTEDLOCATIONS INDICATED. INFORM ENGINEERIMMEDIATELY.

GEOTHERMAL BRANCHESTO BE 18" APART

(5) SETS OF 2" GEO SUPPLY/RETURN LINES(TO/FROM FIELD). SEE M-200 FORCONTINUATION. SEE STRUCTURALFOR COORDINATION.

PUMP ROOM. SEE M-200 FORCONTINUATION.

ACCU-1

BASE BID #2- ACCU-1 LOCATION.

CIRCUIT AS INDICATED. PROVIDE REVERSE RETURN TOEACH SET OF WELLS.

PIPE SIZES SHALL BE AS FOLLOWS:1 BORE: 1.5" (6.25 GPM)2 BORES: 1.5" (12.5 GPM)3 BORES: 2" (18.75 GPM)4 BORES: 2" (25.0 GPM)

REVERSE RETURN PIPING DIAGRAM (NTS)

GLYCOL SUPPLY/RETURN

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-001G150004-000

MECHANICAL SITE PLAN

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1" = 30'-0"1 LOWER LEVEL PLAN

DRAWING NOTES

GROUND LOOP INSTALLATION NOTES:

GENERAL: INSTALLATION SHALL BE IN ACCORDANCE WITH PROJECT SPECIFICATION SECTION 235743 AND CLOSED-LOOP/GEOTHERMAL HEATPUMP SYSTEMS DESIGN AND INSTALLATION STANDARDS 2014 EDITION PUBLISHED BY IGSHPA.

1. THE GROUND LOOP DESIGN FOR THIS PROJECT IS BASED UPON THE FOLLOWING PROPERTIES AS DRAWN FROM THE IN SITU THERMALCONDUCTIVITY TEST PREPARED BY GRTI / ALLIED WELL DRILLING, DATED OCTOBER 13, 2015.A. FORMATION THERMAL CONDUCTIVITY: 1.72 BTU/HR-FT-DEG FB. SOIL VOL. HEAT CAPACITY: 35.8 BTU/DEG F-FT^3C. GROUND TEMPERATURE: 55.7 DEG F

2. THE GROUND LOOP DESIGN FOR THIS PROJECT IS BASED UPON THE FOLLOWING PROPERTIES AS DETERMINED BY THE PROJECTSPECIFICATION:A. BOREHOLE SPACING: 20' O.C. MINIMUMB. GROUT THERMAL CONDUCTIVITY 1.1 BTU/HR-FT-DEG F, MINIMUMC. VERTICAL PIPE CHARACTERISTICS: PE4710, SDR 9, 1.5" NOMINAL DIAMETERD. BOREHOLE CONFIGURATION: SINGLE U-BEND (2-PIPES PER BORE)E. FLUID: 20% PROPYLENE GLYCOL

3. THE BOREFIELD IS BASED ON THE FOLLOWING NOMINAL LENGTHS:A. BOREFIELD TOTAL ACTIVE LENGTH: 7,900 FT VERTICAL BOREHOLE LENGTHB. NOMINAL BOREHOLE QUANTITY: 20C. BOREHOLE DEPTH EACH: 400 FT BELOW GRADED. BOREHOLE ACTIVE DEPTH EACH: 395 FT

4. COORDINATION AND WARRANTYA. THE EXTENT AND SCHEDULE OF DRILLING AND EXCAVATION FOR GEOTHERMAL PIPING SHALL BE COORDINATED BY THIS CONTRACTOR WITH

SCOPES OF WORK SHOWN ON CIVIL AND STRUCTURAL DESIGN DOCUMENTS.B. ALL TRENCHING FOR GROUND LOOP AND HEADERING SHALL BE A MINIMUM OF 24" WIDE.C. COORDINATE TRENCHING AND EXCAVATION REQUIREMENTS WITH ALL OTHER SITE WORK, ALL RELEVANT STANDARDS AND LOCAL

REGULATIONS.D. STANDARDS FOR BACKFILL, COMPACTION AND ALL OTHER RELEVANT SITE WORK SHALL BE COORDINATED WITH ALL OTHER SITE WORK TO

ENSURE ALL PERFORMANCE REQUIREMENTS FOR WORK SPECIFIED ELSEWHERE ARE MET. ALL CIVIL AND STRUCTURAL DESIGNDOCUMENTS ARE HEREBY INCORPORATED INTO THIS CONTRACT BY REFERENCE AND ARE BINDING ON THIS CONTRACTOR.

E. LOOP CONTRACTOR SHALL BE EXPERIENCED IN LOOP DESIGN AND INSTALLATION AND SHALL BE CERTIFIED BY IGSHPA. LOOP CONTRACTORSHALL BE RESPONSIBLE FOR ALL PERMITS AND INSPECTION OF THE LOOP FIELD.

F. AS-BUILT DRAWINGS OF THE LOOP FIELD SHALL BE PROVIDED BY THE LOOP CONTRACTOR.G. THE GROUND LOOP SHALL BE WARRANTED AGAINST LEAKS FOR 10 YEARS BY THE PIPING MANUFACTURER AND THE INSTALLING

CONTRACTOR, INCLUDING ALL PARTS, MATERIALS, LABOR, AND SERVICES.

5. BOREHOLE DRILLINGA. VERTICAL BOREHOLES SHALL BE DRILLED IN ACCORDANCE WITH APPLICABLE LOCAL CODES AND REGULATIONS. DRILLER SHALL BE

LICENSED IN ACCORDANCE WITH CODE AND BE EXPERIENCED IN GROUND LOOP DRILLING AND GROUTING PROCEDURES.B. HEADERING AND ALL OTHER GROUND LOOP PIPE CONNECTIONS SHALL BE COMPLETED BY AN IGSHPA CERTIFIED CONTRACTOR

EXPERIENCED IN THE CONSTRUCTION OF GROUND LOOPS.C. CONTAIN, MANAGE, AND DISPOSE OF DRILL CUTTINGS IN ACCORDANCE WITH LOCAL REGULATIONS.D. AFTER THE LOOP INSTALLATION, BOREHOLES ARE TO BE IMMEDIATELY BACKFILLED WITH THERMALLY ENHANCED BENTONITE GROUT IN

ACCORDANCE WITH THE SPECIFICATION.E. DRILLING CONTRACTOR SHALL PROVIDE WRITTEN GUARANTEE THAT THE BOREHOLES ARE COMPLETELY BACKFILLED.F. PROVIDE DRILL LOG INDICATING ACCURATE GPS POSITION OF EACH VERTICAL BOREHEAD, USING LATITUDE AND LONGITUDE WITH

SUFFICIENT PRECISION TO LOCATE THE BOREHEADS.

6. GROUND LOOP (HEAT EXCHANGER AND HEADER) MATERIALSA. PIPING MATERIAL SHALL BE HIGH DENSITY POLYETHYLENE (HDPE) PE 4710B. VERTICAL PIPE SHALL BE MANUFACTURED IN ACCORDANCE WITH ASTM D-3035 WITH A STANDARD DIMENSION RATIO (DR) OF 9.C. HORIZONTAL PIPE SHALL BE MANUFACTURED IN ACCORDANCE WITH ASTM D-3035 WITH A STANDARD DIMENSION RATIO (DR) OF 11.

7. PIPE FUSION AND CONFIGURATIONA. ALL BURIED PIPE SHALL BE HEAT FUSED BY BUTT, SOCKET, OR ELECTROFUSION IN ACCORDANCE WITH THE PIPE MANUFACTURER'S

PROCEDURES. ALL JOINING TO BE PERFORMED BY FACTORY-TRAINED INSTALLERS WITH CURRENT IGSHPA CERTIFICATION DOCUMENTS.B. VERTICAL PIPES SHALL BE FUSED TO THE LATERAL PIPING FIVE (5) FEET BELOW FINISHED GRADE.C. SUPPLY AND RETURN PIPING FROM THE LOOP FIELD TO THE MECHANICAL ROOM SHALL BE AT LEAST THREE (3) FEET BELOW FINISHED

GRADE.D. WHERE REQUIRED, PIPING OUTSIDE OF A BUILDING OR IN AN EXTERIOR WALL SHALL BE PROTECTED FROM FREEZING, AND SLEEVES SHALL

BE INSTALLED WHERE PIPING PASSES THROUGH MASONRY, CONCRETE, OR ANY FIRE SEPARATION PER IBC 2009 SECTION 713.E. SHUT-OFF VALVES, BALANCING VALVES AND FUSED CONNECTING FLANGES SHALL BE PROVIDED AT THE SUPPLY AND RETURN LINE

TERMINATION POINTS IN THE MECHANICAL ROOM BY THIS CONTRACTOR.

8. HORIZONTAL PIPING INSTALLATIONA. LOCATE HORIZONTAL PIPING 5'-0" BELOW GRADE ON CENTER, UNLESS OTHERWISE NOTED. PROVIDE ELBOWS AS REQUIRED TO

ACCOMMODATE CHANGES IN SITE ELEVATION.B. INSTALL EACH PIPE IN THE CENTER OF AN 18" DEEP SAND BED CONSTRUCTED OF WELL-GRADED SAND, HAND LAID ABOVE PIPE. COMPACT

SAND; BACKFILL TRENCH WITH APPROVED FILL AND PROVIDE COMPACTION.C. PROVIDE TRACER WIRE FOR EACH CIRCUIT FROM ACCESSIBLE LOCATION ADJACENT TO MECHANICAL ROOM. WRAP TRACER WIRE AROUND

PIPE FOR TRACER WIRE ON TOP OF 3" OF SAND ON TOP OF ENTIRE HORIZONTAL RUN OF LOOP.D. PROVIDE LOCATOR DISKS SIMILAR TO GEOTHERMAL SUPPLY COMPANY GDM4 OR GDM10 AT EACH TEE AND AT EACH WELLHEAD FOR

FUTURE WAY-FINDING. FURNISH DISK LOCATOR DEVICE SIMILAR TO GEOTHERMAL SUPPLY COMPANY GDM-L TO OWNER FOR FUTURELOCATION OF DISKS.

E. PROVIDE HORIZONTAL METALLIC CAUTION TAPE ON TOP OF SAND BACKFILL OVER ENTIRE HORIZONTAL RUN (LOOPS AND MAINS BACK TOBUILDING).

F. PROVIDE HORIZONTAL PLASTIC YELLOW WARNING TAPE 1 FT BELOW GRADE ABOVE ENTIRE HORIZONTAL RUN (LOOPS AND MAINS BACK TOBUILDING).

NO. ISSUE DATE: DESCRIPTION

Page 26: G150004-000 F L R C P E M E-000

48x36X56EXHAUST AIRPLENUM

48x36x56OUTDOOR AIRINTAKE PLENUM. PROVIDE 3/4" CAPPEDDRAIN OUTLET.

22X20 OUTDOOR AIRSUPPLY DUCTWORKUP. PROVIDE FIREDAMPER THROUGHPENETRATION AT BASEOF SHAFT.

10X20 HEAT PUMP RETURN AIRDUCTWORK UP. PROVIDE FIREDAMPER THROUGHPENETRATION AT BASE OFSHAFT.

10X12 EXHAUST AIR DUCTWORKUP. PROVIDE FIRE DAMPERTHROUGH PENETRATION AT BASEOF SHAFT.

PROVIDE AND INSTALL 48x36 EXHAUST AIRLOUVER MIN. 50% FREE AREA. LOUVER SHALL BECS MODEL A2097 OR GREENHECK EDD-401.BOTTOM OF LOUVER MINIMUM OF 4'-0" ABOVEGRADE; COORDINATE FINAL ELEVATION WITHARCHITECTURAL DRAWINGS.

PROVIDE AND INSTALL 48x36 OUTDOOR AIRLOUVER MIN. LOUVER SHALL BE CS MODELA2097 OR GREENHECK EDD-401. 50% FREEAREA. BOTTOM OF LOUVER MINIMUM OF 4'-0"ABOVE GRADE; COORDINATE FINAL ELEVATIONWITH ARCHITECTURAL DRAWINGS.

OUTDOOR AIRDUCT INTRENCH

EXHAUST AIRDUCT INTRENCH

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

INSTALL DUCT IN TRENCH.

10X20 OUTDOOR RELIEF AIRDUCTWORK UP. PROVIDE FIREDAMPER THROUGH PENETRATIONAT BASE OF SHAFT.

HEAT PUMP SUPPLY AIRDUCTWORK UP (TYPICAL OF 4).PROVIDE FIRE DAMPERTHROUGH PENETRATION ATBASE OF SHAFT.

EF-1

EF-2

8x8

8x8

8x10

8x8

22x20

10x12

10x20

20x1

0

12ø16ø

48x36

48x36

10x20

22x2

0

42x20

16x1

6

12x12

36x22

16x1

6

12X24RETURN AIRTO OAU-1

28X20OUTSIDE AIRSUPPLYFROM OAU-1

36X22 EXHAUST AIR FROM OAU-1TO EXIT UNIT BELOW SUPPLYOUTLET.

P-2P-1

HP-19 HP-20 HP-21 HP-22 HP-23 HP-W

ACCU-1

P-3

TRANSITION TO PRE-FABRICATEDUNDERGROUND DUCTPRIOR TO DROPPINGBELOW ELEVATION OFSLAB.

TRANSITION FROM PRE-FABRICATEDUNDERGROUND DUCTAFTER RISING ABOVEELEVATION OF SLAB.

MOTORIZED DAMPER.

MOTORIZEDDAMPER.

PROVIDE 4" HIGHHOUSEKEEPING PADFOR OAU-1. PAD TOEXTEND A MINIMUM OF6" BEYOND UNIT IN ALLDIRECTIONS.

(2) BMS CONTROLPANELS.

2M-300

1

ROUTE CONDENSATE FROM HEATPUMPS TO NEAREST FLOOR DRAIN.SEE PLUMBING FLOOR PLANS FORDRAIN LOCATIONS. (TYPICAL)

12X10EXHAUST OPEN ENDEDDUCT WITH WIRE-MESHSCREEN.

P-4

OAU-1

5M-501

TRENCH BY OTHERS.

BASE BID #2 - ALTERNATEACCU-1 LOCATION. PROVIDE 4"HIGH HOUSEKEEPING PAD FORALTERNATE LOCATION. PAD TOEXTEND A MINIMUM OF 6"BEYOND UNIT IN ALLDIRECTIONS.

PROVIDE 4" HIGHHOUSEKEEPING PAD FORACCU-1. PAD TO EXTEND AMINIMUM OF 6" BEYOND UNITIN ALL DIRECTIONS.

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-100G150004-000

MECHANICAL LOWER LEVELPLAN - DUCTWORK

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN

DRAWING NOTES

1. COORDINATE DUCT AND HANGING EQUIPMENT ELEVATIONS WITH STRUCTURAL DRAWINGS AND ARCHITECTURAL REFLECTED CEILING PLANS.

KEY NOTES

COORDINATE SHAFT ROUTING WITH ALL OTHER TRADES.1

NO. ISSUE DATE: DESCRIPTION

Page 27: G150004-000 F L R C P E M E-000

HP-1

HP-2

HP-3

HP-4

HP-5

HP-6 HP-7

HP-8

HP-9 HP-10 HP-11

HP-12

HP-13

HP-14

HP-15

HP-16

HP-17

HP-18

VAVB-2VAVB-1

VAVB-8

VAVB-7

VAVB-9

VAVB-10

VAVB-11

VAVB-5VAVB-6VAVB-3

BR-1

CAR TO BE SIMILAR TO ALDES LOW-PRESSURE CONSTANT AIRFLOWREGULATOR. CAR AND MD TYPICAL ONALL OA DUCT BRANCHES, SIZED TOMATCH DUCT.

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

VEST.V-1

ALCOVEL101-5

WOMEN'S143

PASSAGE104

MEN'S142

ALCOVEL101-6JANITOR

141

MECHANICAL141.1

FAMILYTOILET

144

STORAGE140.1

PASSAGEL101-7

VEST.V-2

CLASSROOM/PRESENTATIONROOM

140

V.P. OFFICE112A

SMALL CONF.105

STORAGE103.1

OFFICE112

PASSAGEL101-1

OFFICE118

OFFICE114

OFFICE116

OFFICE110

OFFICE108

OFFICE104

CORRIDORC 1-1

CORRIDORC 1-2

BREAK ROOM107

STORAGE119

ELEC. RM.121

COFFEESTATIONL101-3

STORAGE103.2

ADMISSIONSOPEN OFFICE

106

HOUSINGOPEN OFFICE

130

OFFICE128

OFFICE126

OFFICE124

OFFICE122

MARKETINGOPEN OFFICE

120

SMALL CONF.115

CONFERENCE117

I.T. ROOM123

CALL CENTER109

CORRIDORC 1-3

OFFICE102

WORK ROOM111

RESOURCEROOM

103

RECEPT.L101-2

STUDENTWORK SPACE

113

LOBBYL101

18x1

210x8

6x6

6x6

8x8

10x812x12

10x8

8x8

10ø

10ø

8x8

6ø6x6

6x6

6ø8ø

8x8

8x8

10ø

6x6

8x10

4ø6ø

8x8

4ø22x12

14x8

4ø10ø

20x1018x10

16ø

12x1210x8

10x8

12x1

2

10x8

10ø

10ø

10x108x8

8x12

10ø

10ø

CAR

MD

6x6

8x6

6x6

6ø6ø

4ø10x8

6x10

10x1

2

10ø10

ø

10x8

12ø

14ø

1 2x141 2x14

18x16

LD-C340

SA: 325/OA: 15

(2)CD-B25EA.

LR-B

LR-B

LD-C375

SA: 375/OA: 15

LD-C340

SA: 325/OA: 15

LR-BLR-B

LD-A105

LD-B205

SA:105/OA: 100

LD-A105

LD-A105

LD-B190

SA: 175/OA:15

LR-A

LD-B115

SA: 100/OA: 15LR-A

LD-B115

SA: 100/OA: 15

LR-A

LD-B140

SA: 120/OA: 20

LR-A

LD-C245

SA: 225/OA: 20LR-B

LD-B115

SA: 100/0A: 15

LR-A

LD-B115

SA: 100/OA: 15

LR-ALD-A120

(10)LD-A120EA.

LD-B125

SA: 125/OA: 55

LD-A125

LD-B95

SA: 80/OA: 15

LR-A

LD-B95

SA: 80/OA: 15

LR-A

(6)LD-A120EA.

(2)LD-A175

(TYP. OF 2)

LR-A

LD-A150 LR-B

LD-C235

SA: 150/OA: 85LR-A

LD-B130

SA: 100/OA: 30

LD-C305

SA: 250/OA: 55

LR-B

LD-B165

SA: 150/OA: 45

LR-A

LD-B80

SA: 55/OA: 25

LD-C350

SA: 275/OA: 75

LR-BLR-A

LD-B125

SA: 95/OA: 30

LR-A

LD-A175

LD-A175

CD-B25

LD-C340

SA: 325/OA: 15

SR-A50

SR-A50

CD-B10

CD-B10

LD-A120

LD-A120

LD-A200LD-A

120

4ø4ø

(3)SR-B100EA.

(3)SR-B100EA.

LD-D150

LD-D200

LD-D150

LD-D200

LD-D150

LD-D200

CD-A75

CD-B15

LD-D450

ER-A150

ER-A75

CD-A75

12ø

12ø

12ø

6ø12ø

20x14

12ø

12ø

16ø

10ø 14x14

8 ø

1 0ø8 ø

8 x8

8x6

6x6

BR-1BR-1

BR-1

LD-E400

8x10

6ø6ø

VAV-110ø

TF-1

8x8

22x10

AC-1

CD-B10

10x8

LD-A115

8ø 8ø

4ø4ø

8ø8ø

6 ø

4 ø

8 x8

10x10

ER-B75

12x1212x10

8ø 8ø 6ø 8ø

6ø8ø

8ø6ø8ø

8x8

8x8

8x8

8x8

8x88x8TG-1

8x8TG-1

8x8TG-1

8x8TG-1

8x8TG-1

14x1

4

6x6

VAVB-4

ER-A150

(3)SR-A150EA.

(3)SR-A150EA.

14ø

10ø

6ø 8ø

1 0ø

6ø 8ø

1M-300

1 1

212" ROUND EXHAUSTDOWN

16" ROUND OUTDOORAIR DOWN

LD-A120

3M-300

2M-300

3

4M-300

4

6x6

6x6

6x6TG-1

10x10TG-1

14x14TG-1 10x10

TG-114x18TG-1

12x12TG-1

6x6TG-1

6x6TG-1

14x12TG-1

24x18TG-1

14x14TG-1

14x14TG-1

12x12TG-1

8x8TG-1

14x14TG-1

8ø 8ø

8ø 8ø 8ø 8ø 8ø

8ø 8ø

6x6

6x6

6x6

10x8TG-1

10x8TG-1

10x8 10

x8

6x6

CR-A

CR-A

10x8TG-1

LR-A

LR-A

10x8TG-1

10x8

10x8

6x6

LR-A

LR-A

LR-A

LR-A

LD-D450

LD-D450

LR-C

LR-C

LD-D450

LD-D450

LD-D450

LR-C

LR-C

LD-D450

LD-D450

30x10TG-1

30x10TG-1

16x10TG-1

1 4x12

12ø

12ø6ø

8x6

AC-2

55

5

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-101G150004-000

MECHANICAL GROUNDFLOOR PLAN - DUCTWORK

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN

DRAWING NOTES

1. CONSTANT AIRFLOW REGULATOR (CAR) TO BE SIMILAR TO ALDES LOW-PRESSURE CONSTANT AIRFLOW REGULATOR. CAR AND MOTORIZEDDAMPER (MD) TYPICAL ON ALL OA DUCT BRANCHES, SIZED TO MATCH DUCT.

2. COORDINATE DUCT AND HANGING EQUIPMENT ELEVATIONS WITH STRUCTURAL DRAWINGS AND ARCHITECTURAL REFLECTED CEILING PLANS.3. ALL TRANSFER DUCTS TO BE OPEN ENDED WITH WIRE MESH SCREENS UNLESS OTHERWISE INDICATED.

1

KEY NOTES

TRANSITION TO PRE-FABRICATED UNDERGROUND DUCT SIMILAR TO BLUE DUCT PRIOR TO DUCT DROPPING BELOW ELEVATION OF SLAB.

PROVIDE WIRE MESH SCREEN ON RETURN AND RELIEF DUCT OPENINGS.

COORDINATE SHAFT ROUTING WITH ALL TRADES. PROVIDE FIRE DAMPER IN DUCTS AT EACH SHAFT PENETRATION. SEE DETAIL ON M-501.

OUTDOOR AIR TO LARGE CONFERENCE TO BE CONTROLLED WITH MOTORIZED DAMPER (MD) AND PRESSURE INDEPENDENT MODULE (PIM).

PERIMETER SLOT DIFFUSER CEILING TRIM BY GC. HVAC CONTRACTOR SHALL MAKE FINAL PLENUM CONNECTION TO CEILING TRIM.

2

3

4

5

NO. ISSUE DATE: DESCRIPTION

Page 28: G150004-000 F L R C P E M E-000

SEE GLYCOL CHARGING DETAIL ONM-500. CONTAINS GMU-1. PROVIDE 4"HIGH HOUSEKEEPING PADS THATEXTEND A MINIMUM OF 6" IN ALLDIRECTIONS BEYOND EQUIPMENT INDETAILS. GLYCOL TANKS TO BELABELED WITH PERCENTAGE ANDTYPE OF GLYCOL AND THEMANUFACTURER OF THE SOLUTION.

GEOEXCHANGE FIELD HEADERSTHRU WALL. MINIMUM OF 5' BELOWGRADE. SEE DETAIL ON M-501 FORSPACING.

4" GLYCOL SUPPLY& RETURN UP. SEEM-201 FORCONTINUATION.

HP-19

HP-20

HP-21

HP-22

HP-23

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

HP-W

P-2

P-1

ACCU-1

EF-2

GLYCOL SUPPLY ANDRETURN IN TRENCH.

NEMA 3R RATED ENCLOSURE.TERMINATE ALL TRACERWIRE AND TAG WITH LOOPIDENTIFIER PER PLANS.

REFRIGERANT PIPING TOCHANGE ELEVATION WITHININTERIOR OF BASEMENT ANDPENETRATE EXTERIOR WALLNEAR GRADE. COORDINATEELEVATION OF EXTERIORPENETRATION WITH ARCHITECT.

P-3

3" GLYCOL SUPPLY ANDRETURN UP. SEE M-201 FORCONTINUATION.

1" HW SUPPLY &RETURN UP. SEEM-201 FORCONTINUATION.

MAKE-UP WATER CONNECTION.SEE PLUMBING DRAWINGS FORCONTINUATION.

REFRIGERANTLINES UP. SEEM-201 FORCONTINUATION.

CONDENSATE DRAIN UP.ROUTE TO NEAREST FLOORDRAIN. SEE PLUMBING FLOORPLANS FOR DRAIN LOCATIONS. 1

ROUTE CONDENSATE FROM HEATPUMPS TO NEAREST FLOOR DRAIN.SEE PLUMBING FLOOR PLANS FORDRAIN LOCATIONS. (TYPICAL)

ROUTE CONDENSATE FROM OAU-1AND GLYCOL CHARGING SKID TONEAREST FLOOR DRAIN. SEEPLUMBING FLOOR PLANS FOR DRAINLOCATIONS. (TYPICAL)

3"

3"

4"4"

2"

2"

2"

2"

3/4"

3/4"

3/4"

3/4"

3/4"

11/2"

1 1/2"

11/4"

4"

11/4"

4"

P-4

ET-2

(2) BMS CONTROLPANELS.

PROVIDE 4" HIGHHOUSEKEEPING PADFOR OAU-1. PAD TOEXTEND A MINIMUM OF6" BEYOND UNIT IN ALLDIRECTIONS.

REFRIGERANT PIPINGSHALL BE SIZED PERMANUFACTURER'SRECOMMENDATIONS.

TRENCH BY OTHERS.

BASE BID #2 - ACCU-1 LOCATION.PROVIDE 4" HIGH HOUSEKEEPING PADFOR ALTERNATE LOCATION. PAD TOEXTEND A MINIMUM OF 6" BEYONDUNIT IN ALL DIRECTIONS. ROUTEREFRIGERANT PIPING TO ALTERNATELOCATION.

PROVIDE 4" HIGHHOUSEKEEPING PAD FORALTERNATE LOCATION. PAD TOEXTEND A MINIMUM OF 6"BEYOND UNIT IN ALLDIRECTIONS

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-200G150004-000

MECHANICAL LOWER LEVELPLAN - PIPING

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN

KEY NOTES

COORDINATE SHAFT ROUTING WITH ALL OTHER TRADES.1

DRAWING NOTES

1. SEE FLOW DIAGRAM AND DETAILS FOR PIPING SPECIALTIES.

NO. ISSUE DATE: DESCRIPTION

Page 29: G150004-000 F L R C P E M E-000

HP-3

HP-4

HP-1

HP-2

HP-5

HP-10

HP-13

HP-16

HP-18HP-14HP-12HP-8

HP-11

HP-9

HP-17

HP-7HP-6HP-15

VAVB-2VAVB-1

VAVB-8

VAVB-7

VAVB-9

VAVB-10

VAVB-11

VAVB-5 VAVB-6VAVB-3

RADIANT HEAT FLOORING. SEE DETAILS.

MANIFOLD FOR RADIANT HEAT FLOORING.COORDINATE LOCATION WITH ARCHITECT.

RADIANT HEAT FLOORING. SEE DETAILS.

MANIFOLD FOR RADIANT HEAT FLOORING.COORDINATE LOCATION WITH ARCHITECT.

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

VEST.V-1

ALCOVEL101-5

WOMEN'S143

PASSAGE104

MEN'S142

ALCOVEL101-6JANITOR

141

MECHANICAL141.1

FAMILYTOILET

144

STORAGE140.1

PASSAGEL101-7

VEST.V-2

CLASSROOM/PRESENTATIONROOM

140

V.P. OFFICE112A

SMALL CONF.105

STORAGE103.1

OFFICE112

PASSAGEL101-1

OFFICE118

OFFICE114

OFFICE116

OFFICE110

OFFICE108

OFFICE104

CORRIDORC 1-1

CORRIDORC 1-2

BREAK ROOM107

STORAGE119

ELEC. RM.121

COFFEESTATIONL101-3

STORAGE103.2

ADMISSIONSOPEN OFFICE

106

HOUSINGOPEN OFFICE

130

OFFICE128

OFFICE126

OFFICE124

OFFICE122

MARKETINGOPEN OFFICE

120

SMALL CONF.115

CONFERENCE117

I.T. ROOM123

CALL CENTER109

CORRIDORC 1-3

OFFICE102

WORK ROOM111

RESOURCEROOM

103

RECEPT.L101-2

STUDENTWORK SPACE

113

LOBBYL101

AC-1

VAV-1TF-1

BR-1BR-1

BR-1BR-1

VAVB-4

T

HP-1

HP-3

T

HP-4

T

HP-5

T

HP-2

T

VAVB-1 VAVB-2

T

HP-7

T

T

HP-8

HP-9

TT

HP-10

T

HP-11

VAVB-4

T

VAVB-3

T

VAVB-5

T

VAVB-6

T

HP-13

T

HP-15

T

VAVB-7

T

VAVB-8

T

VAVB-9

T

HP-19

T

VAVB-10

T

VAVB-11

T

HP-22

T

HP-17

T

HP-21

T

4" GLYCOL SUPPLY ANDRETURN DOWN. SEEM-200 FORCONTINUATION.

1" HW SUPPLY ANDRETURN DOWN. SEE M-200FOR CONTINUATION.

3" GLYCOL SUPPY ANDRETURN DOWN TOTRENCH.

THERMOSTAT TOALIGN WITH SWITCHES.

THERMOSTAT TOALIGN WITH SWITCHES.

HP-18

T

CO2

CO2T

CO21

CONDENSATE MAINTO ROUTE THROUGHBUILDING CORE TOSHAFT AND DOWNTO BASEMENT.

CONDENSATE FROMHP-1 TO 5 TO ROUTETO MOP RECEPTOR INJANITOR CLOSET.(TYPICAL)

INSTALL AUTO-FLOW BALANCING VALVE IN BYPASS.

INSTALL SELF-CONTAINED PRESSURE REGULATING VALVE.

INSTALL SELF-CONTAINED PRESSURE REGULATING VALVE.

3"

3"

3/4"

3/4"

3/4"

3/4"

1"1"1"3/4"

3"

3/4"

3/4"

1" 1"

1"

11/2"

3"3"

1"11/2"

1"

4"

21/2"

1"

1 1/2"

4"

3"

11/4"

1 1/4"

1 1/4"

1 1/4" AC-2

REFRIGERANT PIPINGSHALL BE SIZED PERMANUFACTURER'SRECOMMENDATIONS.

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-201G150004-000

MECHANICAL GROUNDFLOOR PLAN - PIPING

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN

DRAWING NOTES

1. PROVIDE CONDENSATE DRAIN PIPING FOR ALL HEAT PUMP AND AC UNITS.2. CONDENSATE DRAIN PIPING TO SLOPE 1/4" PER FOOT. AVOID OPEN OR VISIBILE CEILING SPACES WHERE POSSIBLE AND ROUTE CONDENSATE

MAIN WITHIN FULL HEIGHT WALLS IN CORE SPACE. CONDENSATE MAY NOT CROSS OVER ELECTRIC OR IT ROOMS.3. SEE FLOW DIAGRAM AND DETAILS FOR PIPING SPECIALTIES.4. SIZE REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS.

KEY NOTES

COORDINATE SHAFT ROUTING WITH ALL OTHER TRADES.1

NO. ISSUE DATE: DESCRIPTION

Page 30: G150004-000 F L R C P E M E-000

12 14 15

10ø8x1012x12

HP-12

VAVB-4

JHE F G

TRANSITION TO PRE-FABRICATEDUNDERGROUND DUCTPRIOR TO DROPPINGBELOW ELEVATION OFSLAB.

DUCT AND GLYCOLSUPPLY/RETURN IN TRENCH.TRENCH TO BE PROVIDED BYOTHERS.

16" DIA. OUTDOORAIR DUCT INTRENCH

12' DIA. EXHAUSTAIR DUCT INTRENCH

YY

10ø

6ø6ø

14ø

10ø

6ø 6ø

14ø

10ø

14ø8ø

6øHP-1

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-300G150004-000

MECHANICAL SECTIONS

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/2" = 1'-0"1 M_SECTION-1SCALE: 1/4" = 1'-0"2 M_SECTION-2

SCALE: 3/8" = 1'-0"4 M_SECTION-4SCALE: 1/2" = 1'-0"3 M_SECTION-3

NO. ISSUE DATE: DESCRIPTION

Page 31: G150004-000 F L R C P E M E-000

SCALE: NTS

P-1

P-2

DP

DP

VSD

VSD

WATER-FLOW DIAGRAM

OAU-1

HP-19

HP-20

HP-21

HP-22

HP-W

HP-17

HP-18

HP-16

HP-15

HP-13

HP-14

HP-11

HP-10

HP-12

HP-9

HP-7

HP-8

HP-6 HP-1

HP-2

HP-3

HP-5

HP-4

INSIDE BUILDING

OUTSIDE

BY INTERIORCONTRACTOR

BY LOOPCONTRACTOR

Z-1 Z-2

Z-1Z-2

Z-3 Z-4

Z-3Z-4

AUTOFLOWBALANCINGVALVE

SELF-CONTAINEDPRESSURE REGULATINGVALVE. SHALL BE SIMILAR TODANFOSS AVDO.

CALIBRATED BALANCING VALVE (TYP.)

ET-1

AUTOMATIC AIRVENT 1" SPILL TO FD

RELIEF VALVE SPILLTO NEAREST FLOOR DRAIN

TANGENTIAL AIRSEPARATORFILL/PURGE VALVE WITHFLANGED CONN. TO 1"HOSE OUTLET

432

5

1

6

AIR ELIMINATOR SIMILAR TOSPIROVENT MODEL VJR125

ET-2

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-301G150004-000

MECHANICALGEOTHERMAL FLOW

DIAGRAM

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

DRAWING NOTES

1. SEE DETAILS ON DRAWINGS M-500 AND M-501 FOR ADDITIONAL INFORMATION.2. PROVIDE AUTOMATIC AIR VENTS AT ALL PIPING HIGH POINTS IN MECHANICAL ROOM.3. PROVIDE MANUAL AIR VENTS AT ALL PIPING HIGH POINTS IN FINISHED SPACES.

KEY NOTES

INSTALL TWO DRAIN VALVES AT LOW POINT IN SYSTEM. LOW POINT TO BE FIELD VERIFIED.

TO/FROM GEOTHERMAL WELLFIELD. SEE PLAN FOR QUANTITY AND PIPING ARRANGEMENT.

PROVIDE HDPE PIPING FOR GROUND-LOOP EXCHANGER PER SPECIFICATION.

SEAL WALL AND FLOOR PENETRATION WATER-TIGHT. SEE DETAIL ON M-501.

SEE FLOOR PLANS FOR PIPE SIZES.

BUFFER TANK - SIMILAR TO TACO MODEL BT, 50 GALLONS WITH 2" THICK FIBERGLASS INSULATION AND ALUMINUM JACKET.

1

2

3

4

5

6

NO. ISSUE DATE: DESCRIPTION

Page 32: G150004-000 F L R C P E M E-000

c

c

c

c

c

c

c

c

c

SCALE:

c c cc

NTSAIRFLOW DIAGRAM

GROUND LEVEL

LOWER LEVEL

EF-1

OAU-1

HP-19 HP-20 HP-21 HP-22

EF-2

450

MAX: 1500

1720

1070

230

100

1950

1950

MAX: 600

(MAX)

(MAX)

320 350 190225

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-302G150004-000

MECHANICAL AIR FLOWDIAGRAM

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION

Page 33: G150004-000 F L R C P E M E-000

FAN SCHEDULE

SPLIT SYSTEM AC SCHEDULE

CONDENSING UNIT SCHEDULE

OUTDOOR AIR UNIT SCHEDULESUPPLY FAN DATA EXHAUST FAN DATA COIL - COOLING DATA

BASIS OF DESIGNTAG SERVICE LOCATION AIRFLOW SP (IN.WG.) MOTOR DATA EXHAUST SP (IN.WG.) MOTOR DATA CAPACITY (MBH)EAT (°F) LAT (°F)

(CFM) EXT. TOTAL MAX BHP RPM CFM EXT. TOT. MAX BHP RPM SENSIBLE TOTAL MCA

NOTES:1. PROVIDE VFD ON SUPPLY FAN & ON EXHAUST FAN2.3.4.

FANS ARE TO BE INTERNALLY VIBRATION ISOLATED.

5.

SEE AIR FILTER SECTION SCHEDULE.PROVIDE DUCT FLANGES FOR SUPPLY, RETURN, OUTDOOR AIR AND RELIEF DUCTS.SEE DIAGRAM BELOW FOR ADDITIONAL ACCESSORY AND ARRANGEMENT INFORMATION.

PUMP SCHEDULETOTAL IMPELLER OPER. SIZE IN.

SYMBOL TYPE LOCATION SERVICE GPM HEAD DIAMETER TEMP. EFF. RPM HP BHP VFD FOUND. BASIS OF DESIGNFT.WG IN. F° SUCT. DISCH. % TYPE

P-1 IN-LINE BASEMENT GROUND LOOP 123.7 75.3 4.625 80 2 2 76 3450 5 YES BELL & GOSSETT - E-90 2AAC

NOTES:1. PUMPS TO BE NON-OVERLOADING AT EVERY POINT ON PUMP CURVE.

OAU-1 VENTILATION BASEMENT 1950 2.0 3.16 2214 1600 1.0 1.76 1703 40.41.41 TRANE HORIZON WSHP D0720.67

3.97

AIR FILTER SCHEDULESUPPLY AIR SEGMENT EXHAUST AIR SEGMENT

UNIT TYPE SERVICE CFM APD / IN. WG MERV-A APD / IN. WG MERV-A REMARKS BASIS OF DESIGNLOC. INITIAL FINAL RATING TYPE INITIAL FINAL RATING TYPE

OAU-1 1950 PF MERV-8 PLEATED MERV-8 PLEATED SEE NOTES 1 & 2 CAMFIL-FARR 30/30

NOTES:1. SUPPLY AIR SEGMENT IS LOCATED UPSTREAM OF WHEEL ON OUTDOOR AIR SIDE. EXHAUST AIR SEGMENT IS LOCATED UPSTREAM OF WHEEL ON RETURN SIDE.2. ALL PERFORMANCE DATA SHALL BE IN ACCORDANCE WITH ASHRAE 52.2-2012 AND AHRI STANDARD 850-2013.

VOLTAGE PHASEHZ

208 60 3

ELECTRICAL DATA

VOLT PHASE FLAHZ

UNIT ELECTRICAL DATA

208 60 34.683

HOT GAS REHEAT COIL

80.52 / 64.5356.2 / 55.6

AIRFLOW (CFM)SUMMER PERFORMANCE

SUPPLY EXHAUSTEAT (°F) LAT (°F)

DB WB DB WB

1950 1600 95.0 75.0 82.7 67.855.7

GLYCOL MAKEUP UNITTANK FILL TOTAL OPER.

SYMBOL LOCATION SERVICE CAPACITY PRESS. GPM HEAD TEMP. HP REMARKS BASIS OF DESIGNGAL. PSIG FT.WG F°

GMU-1 BASEMENT GROUND LOOP 55 60 5 138 100 3/4 FACTORY ASSEMBLED SKID BELL & GOSSETT - GMU-60P

2015-09-24 12:11

NOTES:1. FACTORY ASSEMBLED SKID CONSISTING OF PUMP, STORAGE TANK, LOW WATER CUT OFF SWITCH, PRESSURE SWITCH/STARTER,

Y-STRAINER, TRIPLE DUTY VALVE, PRESSURE GAUGE, ELECTRONIC CONTROLLER, AND NEMA 4 CONTROL PANEL. PROVIDE TIE-IN FOR BAS ALARM.

EXPANSION TANK SCHEDULEFILL

SYMBOL TYPE LOCATION SERVICE ACCEPTABLE DIA. HEIGHT PRESS. REMARKS BASIS OF DESIGN(GALLONS) IN. IN. PSIG

ET-1 BLADDER

2015-09-24 12:12

WATERFLOW DATA

FLOWRATE(GPM)

ENT. TEMP. (°F)MIN.

11.0

MAX. DB / WB DB / WB

COIL - HEATING DATA

CAPACITY(MBH)

EAT (°F) LAT (°F)

62.4

DB DBEAT (°F) LAT (°F)DB / WB DB / WB

WINTER PERFORMANCEEAT (°F) LAT (°F)

DB WB DB WB

10.0 9.0 49.0 44.3

ENERGY RECOVERY WHEEL

N/A

TF-1 CALL CENTER ELECTRIC ROOM IN-LINE CENTRIFUGAL

UNIT No.

EF-1

SERVICE

BSMT

LOCATION

TOILET EXHAUST

FANTYPE

0.0143 0.15 1050

BHP

0.18

TOTAL SP(IN. W.G.)

PERFORMANCE DATA

CFM

450 0.625

RPM

1/140 - 115 1 60

MOTOR DATA

3/4

MHP

-

TYPESTARTER ELECTRICAL DATA

VOLTS PHASE HZ

GREENHECK SQ-60-E

MODEL #MANUF.

REMARKS

SEE NOTE 1

-

-

(FPM)MAX. OV

TYPE

DIRECT

DRIVE

EF-2 BSMT BSMT 0.05600 0.18 1550 1/10 --

1628

DIRECT

DIRECT

115 1 60

115 1 60

GREENHECK SE1-12-426-D

GREENHECK SQ-98-VGIN-LINE CENTRIFUGAL

SIDEWALL SEE NOTE 1

SEE NOTE 1

NOTES:

1. PROVIDE SOLID STATE SPEED FOR BALANCING. MOUNT CONTROLLER NEXT TO FAN.

CFM MCA VOLTS PHASE HZELECTRICAL DATA

MBH WBDBDBEAT LATTOTAL

FAN MOTOR DATA

FLA

DX COOLING COIL

LOCATIONO/ACFM

ESP(IN.) MANUF. MODEL NO.

CONDENSORUNIT NO.

BASIS OF DESIGN

REMARKSWBEVAPORATOR

REMARKSNo.UNIT

CONDENSING

(MBH)

TOTALCOOLING COMPRESSOR

QUANTITY MOTOR FLATYPE TYPEFAN

CFMEXT. SP

(IN. W.G.) VOLTS PHASE HZELECTRICAL DATA

MCA

CONDENSING UNIT

(IN)WIDTH

UNIT DIMENSIONS

(LBS) (IN)

COND.WEIGHT LENGTH

(IN)HEIGHT

MODEL #MANUF.

No.UNIT

EVAPORATOR

AC-1 IT ROOM 399 - - 1.0 208 1 60 0.76 12 80 67 55 55 MITSUBISHI MSZ-GE12NA ACCU-1 -

208 1 60 22.1 MITSUBISHI MXZ-3C24NA37-13/321331-11/32SCROLL1 1.922.0ACCU-1 135-ECM -

90 40 82.7 / 67.8 56.2 / 55.6 73.5 49.0 76.9

OUTDOOR AIR

AC-2 ELEC. ROOM 399 - - 1.0 208 1 60 0.76 6 80 67 55 55 MITSUBISHI MSZ-GE06NA ACCU-1 -

NOTES:

1. PROVIDE 4" HOUSE KEEPING PAD.

NOTES:

1. PROVIDE INTERNAL CONDENSATE PUMPS AND ROUTE CONDENSATE TO NEAREST MAIN.

P-4 IN-LINE BASEMENT RADIANT LOOP 7.5 40.6 2.8 115 1.5 1.5 41 3600 5 NO BELL & GOSSETT ECOCIRC XL55-450.68 208 60 3 N/A

P-3 IN-LINE BASEMENT RADIANT LOOP 7.5 40.6 2.8 115 1.5 1.5 41 3600 5 NO BELL & GOSSETT ECOCIRC XL55-450.68 208 60 3 N/A

P-2 IN-LINE BASEMENT GROUND LOOP 123.7 75.3 4.625 80 2 2 76 3450 5 YES BELL & GOSSETT - E-90 2AAC3.97 208 60 3 N/A

0.1 1.0 0.1 1.0

BASEMENT GROUND LOOP

TOTAL VOLUME(GALLONS)

39.0 29.8 16 48.5 15 - WESSEL NALP-150

ET-2 BLADDER BASEMENT RADIANT LOOP 2.0 1.0 8 13 15 PROVIDE MOD #700-C AIR VENT AMTROL EX-15

PLEATED

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-400G150004-000

MECHANICAL SCHEDULES

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION

Page 34: G150004-000 F L R C P E M E-000

TERMINAL BOX WITH BYPASS SCHEDULE

TERMINAL BOX SCHEDULE

ELECTRIC BASEBOARD SCHEDULE

LINEAR DIFFUSER SCHEDULE

DIFFUSER, REGISTER, AND GRILLE SCHEDULE

WATER TO WATER HEAT PUMP SCHEDULE (HEATING ONLY)

VENTILATION SCHEDULE

WATER TO AIR HEAT PUMP SCHEDULEFAN COOLING HEATING MAX.

SYMBOL SERVICE ESP/ TOTAL SENS. INPUT HEAT INPUT HEAT GPM PD/ NOM. UNIT BASIS OF DESIGNCFM IN. WG HP MBH MBH KW EER REJECT. MBH MBH KW COP ABSORB. MBH FT. WG TONS VOLTAGE TRANE

HP-01 800 5.20 2.0 208/60/1 VSH024

HP-02

HP-03

HP-04

HP-05

HP-06

HP-07

HP-08

HP-09

HP-10

HP-11

HP-12

HP-13

HP-14

HP-15

HP-16

HP-17

HP-18

HP-19

HP-20

NOTES:1. FANS SHALL BE ECM TYPE.2. PROVIDE UNIT W/ PROGRAMMABLE WALL MOUNTED AUTO CHANGE-OVER THERMOSTAT; UNIT

MOUNTED MICROPROCESSOR CONTROLS, SINGLE POINT POWER ENTRY, 2" DISPOSABLE FILTERS.3. ALL RATINGS ARE BASED ON 20% PROPYLENE GLYCOL SOLUTION.4. DISCONNECT TO BE PROVIDED BY ELECTRICAL CONTRACTOR5. AHRI EER AND COP SHALL BE EVALUATED PER AHRI/ISO 13256-1 PER GROUND LOOP STANDARDS AT

FULL LOAD.6. PROVIDE WITH CONDENSATE PUMPS WHERE REQUIRED.7. PROVIDE WITH VIBRATION ISOLATION (SEE SPEC.)8. PROVIDE HP-03 WITH A HOT GAS REHEAT FOR HUMIDITY CONTROL

HP-21

HP-22

EXHF018

EXHF018

VSH024

VSH024

VSH050

VSH024

VSH024

VSH060

EXHF006

EXHF006

EXHF006

EXHF006

EXHF009

EXHF006

EXHF012

EXHF015

EXHF012

EXHF012

EXHF015

VSH042

VSH042

PRESENTATION - NORTH

LOBBY, STORAGE, BATHROOMS

PRESENTATION - CORE

PRESENTATION - SOUTH

LOBBY

OFFICES

RESOURCE ROOM

HOUSING OPEN OFFICE

SMALL CONFERENCE, STORAGE

ADMISSIONS OPEN OFFICE

BREAK ROOM, CALL CENTER

OFFICES

ADMISSIONS OPEN OFFICE

OFFICES

WORK ROOM, STUDENT WORK SPACE

OFFICES

SMALL CONFERENCE, STORAGE

MARKETING OPEN OFFICE

VP OF ENROLLMENT

OFFICES

OFFICE

LARGE CONFERENCE

VAVB-1

DESIGNATION

AIRFLOW

MODEL #

ZQCV -

REMARKS(INLET SIZE)

5 X 5

MIN.

0

MAX.

RANGE (CFM)BOXTYPE

BYPASS

BOX SIZESTATIC

(IN W.G.)

0.10

PRESSURE PS

MINIMUMSOUND LEVELAT MAX. CFM &

PS=2" (NC)

55

DISCHARGESOUND LEVEL

PS=2" (NC)

39

RADIATED

AT MAX. CFM &CONTROLS

TYPE OF

ANALOG ELECTRONIC

TITUS

VAVB-2 -80

VAVB-3 -0.47 52 40

VAVB-4 -

VAVB-5 -325

VAVB-6 -375 0.25

VAVB-7 -

VAVB-8 -

VAVB-9 -

VAVB-10 -

VAVB-11 -

VAV-1

DESIGNATION

AIRFLOW

MODEL #

DESV -

REMARKS(INLET SIZE)

5

MIN.

120

MAX.

200

RANGE (CFM)BOXTYPE

SINGLE DUCT

BOX SIZESTATIC

(IN W.G.)

0.02

PRESSURE PS

MINIMUMSOUND LEVELAT MAX. CFM &

PS=2" (NC)

35

DISCHARGESOUND LEVEL

PS=2" (NC)

25

RADIATED

AT MAX. CFM &CONTROLS

TYPE OF

DDC

HP-23

18.3 28.701.5517.4823.40 20.95 1.49 6.44 15.87 2.850.50.50

5 X 5

6 X 6

6 X 6

6 X 6

8 X 6

5 X 5

5 X 5

5 X 5

5 X 5

5 X 5

325

325

80

100

100

120

100

100

0

0

0

0

0

0

0

0

0

0

0.10

0.10

0.10

0.10

0.10

0.10

0.47

0.47

51 40

ANALOG ELECTRONIC

ANALOG ELECTRONIC

ANALOG ELECTRONIC

ANALOG ELECTRONIC

ANALOG ELECTRONIC

ANALOG ELECTRONIC

ANALOG ELECTRONIC

ANALOG ELECTRONIC

ANALOG ELECTRONIC

ANALOG ELECTRONIC

BYPASS

BYPASS

BYPASS

BYPASS

BYPASS

BYPASS

BYPASS

BYPASS

BYPASS

BYPASS

EXHF009MECHANICAL BASEMENT

TITUS

LOCATION

BR-1

UNIT No. REMARKSMODEL #

RUNTAL - EB3-108D -

MANUF.

ELECTRICAL DATA

1.32

KW PHASEVOLTS

208 1 60

HZSERVICE

ELECTRIC

TYPE (MBH)

4.5

CAPACITYHEATING

-

FLA

VESTIBULE VESTIBULE

(IN.)DESIGNATION

LD-B

LD-A 1

INLETS

3/4 1,3,4,5,6,7

REMARKS

LINEAR

TYPE

LINEAR 2

SLOTSNo. OF

SUPPLY

SERVICE

SUPPLY/OA

NO. OFSIZESLOT

(IN.)WIDTH MANUF.

MODEL #

TITUS ML-TZ

PLENUM SIZES

48 6

LENGTH(IN.)

WIDTH(IN.)

FINISHES SHALL BE SPECIFIED BY ARCHITECT. ARCHITECT TO PROVIDE COLOR SAMPLE FOR FACTORY PAINTING OF BAKED ENAMEL.

NOTES:

1.

SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2.

PROVIDE LINEAR DIFFUSERS WITH PLENUM AND CORD OPERATED OPPOSED BLADE VOLUME DAMPER.

4.ALL DIFFUSERS SHALL BE SUITABLE FOR THE TYPE OF CEILING CONSTRUCTION THAT ARE BEING INSTALLED IN. COORDINATE WITH ARCHITECT.

3.

COORDINATE DIFFUSER WIDTH WITH ARCHITECTURAL DRAWINGS, SECTIONS, AND REFLECTED CEILING PLAN.

5.

DESIGNATION

SR-A

REMARKSSERVICE

SUPPLY

NECK SIZE (IN.)/SIZE& NO. OF SLOTS

-

NOMINAL OVERALL

10 x 3

DIMENSION WxL (IN.)RANGE

50

MAX NC

30

CFM

DUCT MOUNTED

TYPE

-

MODEL

TITUS - S3OOFS

MANUF.

2 3/42 TITUS ML-TZ48 6

LD-C LINEARSUPPLY/OA 2 14 TITUS ML-TZ48 6

LD-D LINEARSUPPLY 1 - 1,2,3,4,5,6,7- TITUS CT-54148 6

LD-E LINEAROA 1 - 1,2,3,4,5,6,7- TITUS CT-54148 3

LR-A LINEARRETURN - 3/42 TITUS MLR-TZ- -

TG-1 RETURN/EXHAUST - SEE DWG- - WALL MOUNTED -TITUS - S35OFS

ER-A EXHAUST 6" x 6" 24 x 2475-150 - LAY-IN -TITUS - PAR

ER-B EXHAUST - 8 x 675 - DUCT MOUNTED -TITUS - 350RL

CD-A SUPPLY 6" 24 x 2475 30 LAY-IN -TITUS - OMNI

CD-B SUPPLY/OA 4" 12 x 1210-25 30 LAY-IN -TITUS - OMNI

AIR AIREDB EWB EWT

90.064.076.9

UNITFLA

10.17

AIREDB EWT

70.10 40.00

800 5.20 2.0 208/60/118.3 28.701.5517.4823.40 20.95 1.49 6.44 15.87 2.850.50.50 90.064.076.9 10.1770.10 40.00

800 5.20 2.0 208/60/118.3 28.701.5517.4823.40 20.95 1.49 6.44 15.87 2.850.50.50 90.064.076.9 10.1770.10 40.00

800 5.20 2.0 208/60/118.3 28.701.5517.4823.40 20.95 1.49 6.44 15.87 2.851/20.50 90.064.076.9 10.1770.10 40.00

800 5.20 2.0 208/60/118.3 28.701.5517.4823.40 20.95 1.49 6.44 15.87 2.851/20.50 90.064.076.9 10.1770.10 40.00

1800 11.70 4.2 208/60/116.5 59.633.4437.1247.87 45.88 3.16 5.80 35.09 3.901.00.50 90.064.076.9 20.4970.10 40.00

2000 13.00 5.0 208/60/114.8 73.464.5542.8357.93 57.70 4.34 5.30 42.89 4.611.00.50 90.064.076.9 25.8370.10 40.00

215 1.30 0.5 208/60/115.0 9.410.645.507.23 6.67 0.56 4.90 4.75 2.480.06 kW0.50 90.064.076.9 3.7070.10 40.00

215 1.30 0.5 208/60/115.0 9.410.645.507.23 6.67 0.56 4.90 4.75 2.480.06 kW0.50 90.064.076.9 3.7070.10 40.00

215 1.30 0.5 208/60/115.0 9.410.645.507.23 6.67 0.56 4.90 4.75 2.480.06 kW0.50 90.064.076.9 3.7070.10 40.00

215 1.30 0.5 208/60/115.0 9.410.645.507.23 6.67 0.56 4.90 4.75 2.480.06 kW0.50 90.064.076.9 3.7070.10 40.00

215 1.30 0.5 208/60/115.0 9.410.645.507.23 6.67 0.56 4.90 4.75 2.480.06 kW0.50 90.064.076.9 3.7070.10 40.00

380 2.60 1.0 208/60/115.5 14.080.928.6710.95 10.32 0.87 5.20 7.36 3.550.09 kW0.50 90.064.076.9 7.0270.10 40.00

380 2.60 1.0 208/60/115.5 14.080.928.6710.95 10.32 0.87 5.20 7.36 3.550.09 kW0.50 90.064.076.9 7.0270.10 40.00

380 2.60 1.0 208/60/115.5 14.080.928.6710.95 10.32 0.87 5.20 7.36 3.550.09 kW0.50 90.064.076.9 7.0270.10 40.00

570 3.90 1.5 208/60/116.7 21.881.3113.6617.42 16.23 1.31 5.10 11.77 3.930.13 kW0.50 90.064.076.9 11.1070.10 40.00

570 3.90 1.5 208/60/116.7 21.881.3113.6617.42 16.23 1.31 5.10 11.77 3.930.13 kW0.50 90.064.076.9 11.1070.10 40.00

475 3.30 1.25 208/60/115.3 17.401.1410.5013.50 13.01 1.10 4.80 9.25 5.110.11 kW0.50 90.064.076.9 8.7970.10 40.00

475 3.30 1.25 208/60/115.3 17.401.1410.5013.50 13.01 1.10 4.80 9.25 5.110.11 kW0.50 90.064.076.9 8.7970.10 40.00

1250 9.00 3.5 208/60/118.6 47.762.5828.7238.95 35.62 2.60 6.70 26.75 2.551.00.50 90.064.076.9 15.1370.10 40.00

1250 9.00 3.5 208/60/118.6 47.762.5828.7238.95 35.62 2.60 6.70 26.75 2.551.00.50 90.064.076.9 15.1370.10 40.00

285 2.00 0.75 208/60/114.9 10.850.736.678.37 7.87 0.64 5.40 5.69 3.611.00.50 90.064.076.9 4.3070.10 40.00

285 2.00 0.75 208/60/114.9 10.850.736.678.37 7.87 0.64 5.40 5.69 3.611.00.50 90.064.076.9 4.3070.10 40.00

48

ACTIVE

(IN.)LENGTH

48

48

48

48

48

PLENUM

6

6

6

6

3

6

LR-B LINEARRETURN - 14 TITUS MLR-TZ- -48 6

LR-C LINEARRETURN - - 2,3,4,5,6,7- TITUS CT-541- -48 6

PLENUM TO BE SIMILAR TO TITUS MP-TZ.TITUS CT (OR SIMILAR) TO BE PROVIDED WITH 1/4" BARS, 1/2" SPACING.

6.7.

1,3,4,5,6,7

1,3,4,5,6,7

3,4,5,6,7

3,4,5,6,7

LOCATION

HP-W

TAG REMARKSMODEL #

TRANE EXWE0601 -

MANUF.

ELECTRICAL DATA

27.60

RLAPHASEVOLTS

208 1 60

HZSERVICE

10.0

(GPM) MAX PD (IN. W.G.)

5.74 27.60

FLA

BASEMENT RADIANT HEAT

WATER FLOW DATA

SOURCE

HEATING DATA

LWTEWT

40.0 32.76 101.7

EWT

110.3

LWTLOAD (°F)SOURCE (°F)

102

ROOM No.

1

PEOPLE

12

AIR

OFFICE

DESCRIPTIONNo. OF

122

(SQ.FT.)AREAROOM

-

EXHAUST

REQUIRED (CFM)

15 -

DESIGNED (CFM)

55 39

55 39

55 39

55 39

55 39

55 39

52 40

52 40

ZQCV

ZQCV

ZQCV

ZQCV

ZQCV

ZQCV

ZQCV

ZQCV

ZQCV

ZQCV

104

106

108

112A

112

114

116

118

120

122

110

124

126

128

130

OFFICE

OPEN OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OPEN OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OPEN OFFICE

1

16

1

1

1

1

1

1

1

8

1

1

1

1

5

120

1985

120

150

248

175

118

124

124

963

154

132

132

132

483

OUTDOORAIR EXHAUST

OUTDOOR

12 - 15 -

199 - 200 -

12 - 15 -

14 - 15 -

20 - 20 -

16 - 20 -

12 - 15 -

12 - 15 -

12 - 15 -

98 - 100 -

14 - 15 -

13 - 15 -

13 - 15 -

13 - 15 -

54 - 55 -

103 RESOURCE ROOM 10 590 85 - 85 -

105 SMALL CONFERENCE 4 104 30 - 26 -

103.1 STORAGE 0 52 6 - 10 -

103.2 STORAGE 0 52 6 - 10 -

107 BREAK ROOM 8 213 53 - 55 -

109 CALL CENTER 6 205 42 - 45 -

111 WORK ROOM 2 200 22 - 25 -

113 STUDENT WORK 12 253 75 - 75 -

115 SMALL CONFERENCE 4 104 26 - 30 -

119 STORAGE 0 83 10 - 10 -

117 CONFERENCE 12 348 111 - 115 -

101 LOBBY 50 2358 391 - 400 -

140 PRESENTATION 50 1166 445 - 450 -

141 JANITOR 0 61 - 61 - 75

140.1 STORAGE 0 125 12 - 15 -

144 FAMILY TOILET 0 84 - 50 - 75

142 MENS BATHROOM 0 170 - 150 - 150

143 WOMENS BATHROOM 0 212 - 150 - 150

7.5

(GPM)

3.08

LOAD

WATER FLOW DATA

MAX PD (IN. W.G.)

4.30

AHRI COP

AHRI AHRI

PERIMETER SLOT DIFFUSER CEILING TRIM BY GC. HVAC CONTRACTOR SHALL MAKE FINAL PLENUM CONNECTION TO CEILING TRIM.8.

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-401G150004-000

MECHANICAL SCHEDULES

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION

Page 35: G150004-000 F L R C P E M E-000

SINGLE-THICKNESS TURNINGVANES FOR SQUARE ELBOW

VANED ELBOW

11/2"(TYP)

1 1/2"(TYP)

FRAME

FLOW

RUNNER

CHANNEL SEENOTE #4

CRIMP (TYP)

3/4" FLATTRAILING

EDGE (TYP)

FLOW

TURNING VANES

NOTES:

1. MAXIMUM UNSUPPORTED VANE LENGTH 36".

2. VANES AND FRAMES-24 GAUGE.

3. DUCT INLET AND OUTLET DIMENSIONS TO BE EQUAL.

4. FOR HIGH VELOCITY APPLICATIONS PROVIDE 18 GAUGE CHANNELAND TACK WELD VANE EDGES TO CHANNEL TYPICAL BOTH ENDS.

5. FRAMES AND CHANNELS-BOLTED OR TACK WELDED TO ELBOW.

45° 45°R=2"

WITH VOLUME DAMPERRECTANGULAR DUCT ANGULAR TAP

NOT TO BE USED AS A SUBSTITUTE FOR AN ELBOW.

FOR LOW PRESSURE BRANCHES WITH LESS THAN 700 CFM AND MEDIUM PRESSUREFURNISH THIS TYPE CONNECTION WHEN SINGLE LINE DUCTWORK IS INDICATED AS THIS .

45°

SUPPLY

BRANCHES WITH LESS THAN 1,000 CFM.

W1

RETURN/EXHAUSTAIRFLOW

AIRFLOW

W2

3/8" SQUARE ROD

MAIN DUCT

BRANCH DUCT

END BEARING

0.25 X W2, 4" MINIMUM

CLEAR INSULATIONQUADRANT AND SADDLE TOLOCKING TYPE INDICATOR.VOLUME DAMPER WITH

CLINCH COLLAR

1.

NOTES:

2.

TO SINGLE OUTLETCIRCULAR BRANCH CONNECTION

AIRFL

OW

MAIN DUCT

1.5D

D

SHEET METAL ASREQUIRED

OR DIFFUSERTO TROFFERFLEXIBLE DUCT

FLAT SEAM DUCTWORKTRANSVERSE JOINT FOR FLUSH

OUTSIDE OF DUCT

INSIDE OF DUCT

TAPPING SCREWSOVAL HEAD SELFCOUNTER SUNK OR

WELDED 6" ON CENTERSPOP RIVETED OR SPOT

MAXIMUM 3/8"

INTERNAL BRACINGOR 2"x3/8"FLAT BAR

1/8" THICK

DIFFUSER CONNECTION DETAIL

6" MINIMUM

R=D

D

DIFFUSERFOR RECTANGULAR

D

SIZE

THERMAL INSULATION

ACOUSTIC LINING

2-3/4 IN. MINIMUM

DIFFUSER

ROUND DUCT CONNECTOR

SIDE CONNECTION

ROUND DUCT ADAPTOR

D MINIMUM

DIFFUSER

CEILING

DIFFUSER NECK

FULLY EXTENDEDFLEXIBLE DUCTMAXMIUM 6 FT. LENGTH

MAXMIUM 6 FT. LENGTHFLEXIBLE DUCTFULLY EXTENDED

TOP CONNECTION

CEILING

PS

PS

PS

1

AAV

WATER COOLED CEILING HUNG HEAT PUMP PIPING DETAIL

VERTICAL DIAPHRAGM TYPE EXPANSIONTANK GLYCOL CHARGING DETAIL

W/ MANUAL PREMIX MAKE-UP

DUCT SUPPORT DETAIL

STEEL ANGLES BACK TO BACK WELDED TOBEAM FLANGE

PROVIDE SOLENOID (ELECTRICAL) VALVESHARD WIRED TO LIQUID DETECTOR TO SHUTDOWN IN EVENT OF A LEAK (TYP)

SHUT-OFF VALVE (TYP)

CONDENSER WATER SUPPLY

CHECK VALVE (TYP)

CONDENSER WATER RETURN

RUNOUTS SHALL BE SAME SIZE AS COILCONNECTIONS (TYP)

PROVIDE FILTER ACCESS SECTION

RETURN AIR

FLEXIBLE CONNECTION (TYP)FILTER

TRAP

LEAK DETECTOR WIRED TO SHUTDOWN HP UNIT

STRAINER W/ BLOW-DOWN VALVE

DIFFERENTIAL PRESSURE SWITCH WIREDTO SHUTOFF HP UNIT UPON LOSS OF FLOW

FLANGECONNECTION (TYP)

STEEL CONNECTION PLATE WELDEDTO ANGLES (TYP) AT 4 LOCATIONSEACH SPAN

THREADED ROD

SPRING VIBRATIONS ISOLATOR

CONTROL VALVE 2-WAY OR 3-WAYAS INDICATED ON FLOW DIAGRAM

BALANCING VALVE(SEE NOTE 2)

SUPPLY AIR

DRAIN PAN INDEPENDENTLYSUPPORTED FROM HP UNIT

CONDENSATE PUMPIF REQUIRED

NOTES:

1. SUPPORT DESIGN NEEDS TO BE APPROVED BY A REGISTERED STRUCTURAL ENGINEER.

2. PROVIDE AUTOMATIC BALANCING VALVE FOR HEAT PUMPS

3. INTER-CONNECT SUPPLY AND RETURN PIPING AT FLANGE CONNECTIONS WITH FLEXIBLE HOUSE TOFLUSH PIPING BEFORE CONNECTING TO HEAT PUMP

PETE'S PLUG (TYP)

DOMESTIC COLDWATER SUPPLY

RPZ TYPE BACKFLOW PREVENTERASSEMBLY FURNISHED ANDINSTALLED BY PLUMBINGCONTRACTOR

CONNECT TO DOMESTIC WATERSYSTEM

SHUT-OFF VALVE, REFER TOSPECIFICATIONS (TYP)BYPASS FOR SYSTEM FILL

HIGH CAPACITYAUTOMATIC AIR VENT

SHUT-OFF VALVERUN TO SPILL OVERFLOOR DRAIN ORFUNNEL DRAIN

SYSTEM MAIN TO SUCTIONSIDE OF PUMP

RUN TO SPILL OVERFLOOR DRAIN OR FUNNELDRAIN

PRESSURE REDUCINGVALVE

EXPANSION LINE

DIAPHRAGM TYPEEXPANSION TANK

TO ADDITIONAL TANK ASREQUIRED

R

RELIEF VALVE

MAKE-UP SIZE (d)

TOTAL SYSTEMPUMP FLOW (GPM)

d(IN)

PRV MINFLOW (GPM)

UP TO 200201-500501-1,2001,201-3,0003,001-5,0005,001-12,000

0.50.751.01.251.52.0

3510203060

EXPANSIONLINE SIZE

1.251.52.02.02.52.5

(d)

LOCK SHIELD VALVE

12"

AFF

NOTES:

1. REFER TO EXPANSION TANK SCHEDULE FOR CAPACITY AND SIZE.

2. REFER TO PLANS FOR LOCATION OF TANK.

3. SET RELIEF VALVE SETTING 10% ABOVE WORKING PRESSURE.

4. PROVIDE ANTI-THERMOSYPHON LOOP AS SHOWN TO PREVENT GRAVITYHEATING OF TANK.

AIR SEPARATOR

INSTALL FOR RADIANTSYSTEM. OMIT FORGLYCOL SYSTEM.

GLYCOL MAKE-UP FROMDRUM, POWER PUMP, ORHAND PUMP (MANUALOPERATION)

FLOOR

SYSTEM MAINPUMP SUCTION

AAV (LARGE CAPACITY)

AIR SEPARATOR

DRAIN OUT VALVE WITHHOSE BIBB

LOW PRESSURE SWITCH, WIRE ALARMTO BLDG FACILITIES OR SECURITYOFFICE

GLYCOL & WATERPREMIX DRUM (55GALLON MINIMUM)

LOW - LEVEL ALARM,ANNUNCIATE TO BLDGFACILITIES OR SECURITYOFFICE

HOUSEKEEPING PAD

BY OTHERS

RELIEF VALVE DISCHARGEPIPED BACK TO GLYCOL &WATER PREMIX DRUM

HAND PUMP

GLYCOL DRUM

BACK- FLOWPREVENTERBY OTHERS

COLD WATER MAKE-UP(MANUAL OPERATION)BY OTHERS

NOTES:

1. COORDINATE POWER REQUIREMENTS FOR MAKE-UP PUMP AND CONTROLSWITH ELECTRICAL CONTRACTOR.

2. ALL PIPING & EQUIPMENT DOWNSTREAM OF MAKE-UP PUMP SHALL BERATED FOR INSTALLED OPERATING PRESSURE.

3. IN "AUTO" POSITION PUMP RUNS AUTOMATICALLY WHEN SYSTEMPRESSURE FALLS BELOW CHARGE PRESSURE. WHEN IN "HAND" THE PUMPRUNS CONTINUOUSLY. WHEN IN "OFF", THE SYSTEM IS OFF.

12"

EXPANSION TANK

LOCKSHIELDVALVE

HB

LAG BOLT 1 1/2"x11/2"x 1/8" TOJOIST

JOIST JOIST

BEND STRAP OVER ANGLE &BOLT TOP & SIDE

UNDERSIDE OFSLAB OR BEAM

SEE NOTE 3

DUCT HANGERS NOTLESS THAN 1"x1/8"

APPROVED INSERT &ANCHOR

BEAMCLAMP

STRUCTURAL ANGLECHANNEL AS REQUIRED

HANGER ROD

PARALLELCONNECTION

TRANSVERSECONNECTION

WOOD JOISTATTACHMENTS

HANGER ROD

EXPANSIONBOLT

HANGER ROD

EXPANSIONSHIELD

BEAM

BEAMCLAMP

HANGER ROD

BEAMATTACHMENT

DUCT

BEAMCLAMP

CONCRETEATTACHMENT

NOTES:

1. ALL DUCTWORK TO BE HUNG FROM BUILDINGCONSTRUCTION. DO NOT SUPPORT FROMHUNG CEILING.

2. WHEN DUCT AREA EXCEEDS 8 SQ FT ANGLESTIFFENERS ARE REQUIRED AROUNDCIRCUMFERENCE EVERY 4'-0".

3. FOR DUCTS UP TO 60" WIDE, HANGERS SHALLTURN UNDER DUCT AT LEAST 2" AND SHALL BEFASTENED TO THE BOTTOM AS WELL AS TOTHE SIDES OF THE DUCT. FOR DUCTS OVER 60" WIDE, USE TRAPEZE HANGER.

4. REFER TO SPECIFICATIONS FOR HANGERSPACING.

5. NOT ALL CONSTRUCTION TYPES ARE APPLICABLETO THIS PROJECT.

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-500G150004-000

MECHANICAL DETAILS

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION

Page 36: G150004-000 F L R C P E M E-000

SS

SUSPENDED INSTALLATIONVERTICAL IN-LINE PUMP

PROVIDE FLANGE FOR PUMPS WITH FLANGECONNECTIONS, FURNISH UNION AT INLET ANDDISCHARGE FOR PUMPS WITH SCREWEDCONNECTIONS

LOCATION OF UNION IF REQUIRED(TYP)

Y-PATTERN STRAINER WITH3/4" BALL VALVE AND HOSEBIBB END ADAPTER WITHCAP

ECCENTRIC REDUCER (TOPFLAT) (TYP)

SILENT CHECK VALVE

SHUT-OFF VALVE (TYP)

HANGER (TYP)

VIBRATION ISOLATION (TYP)SEE SPECIFICATIONS

THREADED HANGER ROD ATTACHED TOBUILDING STRUCTURE OR MISCELLANEOUSSTEEL WITH WELDED BEAM ATTACHMENT (TYP)

MOTORPRESSURE GAUGE

BALANCING VALVE

1/4" SS PIPE

EXTERIOR WALL PIPE PENETRATION SEAL ASSEMBLY

WATER STOP/LEAK PLATE ANDWELDED ANCHOR COLLAR

STAINLESS STEEL BOLTS(NOT STUDS)

STUFF OPENING WITHASBESTOS FREE ROPE

CATHODIC TYPE (NON CONDUCTIVE)PRESSURE PLATES

PIPE SLEEVE TO BE INSTALLEDDURING WALL CONSTRUCTION

NEOPRENE SEALING ELEMENTS

CONTINUOUS WELDBOTH SIDES(TYP)

INSULATION AS PERSPECIFICATIONS

PIPE TO SLIDETHROUGH SEAL

PIPE OR CONDUITCENTERED IN SLEEVE

INTERIOR FACEOF BUILDING

NOTES:

1. WHEN SEALING FLOOR PENETRATIONS, EXTEND SLEEVE 3"ABOVE FINISHED FLOOR.

2. WHEN CORE DRILL IS USED THE PIPE SLEEVE AND WATERSTOP/LEAK PLATE ARE NOT REQUIRED.

SECTION A-A

A

A

TYPICAL DETAIL OF PIPETHRU RATED WALL

EXTEND SLEEVEBEYOND FINISHED WALLSURFACE

SEAL OR CAULK SLEEVESTHRU FIRE WALLS IN A SMOKETIGHT MANNER REFER TOSPECIFICATION

STANDARD WEIGHT STEEL PIPESLEEVE OF SIZE TO PASS PIPE

FINISHED ESCUTCHEON PLATEFLUSH AGAINST WALL AND OF SIZETO COMPLETELY COVER OPENING(TYP FOR EACH SIDE)

FINISHED WALL SURFACEFILL VOID WITHFIRESTOPPING PERSPECIFICATIONS

1/2" CLEAR MAX

PIPE INSULATION TO BECONTINUOUS THROUGHTHE WALL

DIELECTRIC FLANGE KIT DETAIL

TEFLON BOLT SLEEVEISOLATING INSERT

STANDARD BOLT RATED ANDSIZED FOR FLANGE

FLANGE - BRAZED ORSOLDERED TO PIPE

COPPER PIPESTEEL PIPE

FLANGE - BRAZED ORSOLDERED TO PIPE

NOTES:

1. TEFLON NON-CONDUCTIVE ISOLATINGINSERTS ARE TYPICAL FOR ALL BOLTHOLES/BOLTS.

TEFLON WASHER

STANDARD NUT RATED ANDSIZED FOR FLANGE

STANDARD STEEL FLANGE -WELDED OR THREADED RATEDFOR PRESSURE CLASS OF PIPE

TEFLON GASKET

PLAN VIEW

(CAV OR VAV)TERMINAL UNIT INSTALLATION

INDICATED ABOVE CANNOT BE MAINTAINED, PROVIDE ORIFICE PLATE, STRAIGHTENING

ACOUSTICAL DUCT LINING MINIMUM10 FEET DOWNSTREAM OR SOUND

AND PLANS FOR FURTHER REQUIREMENTS.ATTENUATOR AS REQUIRED. SEE SPECS

ADEQUATE SERVICE ACCESSMOUNT CONTROL PANEL WITH

FASTEN AND SEAL CONNECTION

FASTEN AND SEAL CONNECTION

THE OPERATION OF VARIABLE VOLUME TERMINAL UNITS ARE AFFECTED BYEXCESSIVE TURBULENCE ON THE ENTERING SIDE OF EACH TERMINAL UNITTHEREFORE, TERMINAL UNITS MUST NOT BE INSTALLED TOO CLOSE TOMAIN DUCTS, ELBOWS AND FITTINGS.

WHEN MINIMUM UPSTREAM STRAIGHT DUCT CONNECTION TO TERMINALS AS

VANES OR OTHER DEVICE AS RECOMMENDED BY TERMINAL UNIT MANUFACTURERAND SUBMIT TO ENGINEER FOR REVIEW PRIOR TO INSTALLATION.

MANUFACTURER OF TERMINAL UNIT SHALL PROVIDE CONTROLS ON LEFT ORRIGHT SIDE AS REQUIRED BY FIELD CONDITIONS.

ARRANGE ACCESS TO PERMIT EASY FIELD BALANCE AND MAINTENANCE OFTERMINAL UNIT.

1.

2.

3.

4.

NOTES:

RIGID CONNECTION

TERMINAL UNIT

CONICAL CONNECTION

MAIN DUCT

STRAIGHT ROUND DUCT

(MINIMUM 3'-0")LENGTH 2 DIAMETERS

RECTANGULAR TOROUND TRANSITION

AIR FLOW

SAME SIZE AS INLET.

SLOT DIFFUSER WITH VOLUME DAMPERDETAIL

FLEX MAX LENGTH 4"

CABLE OPERATED OPPOSEDBLADE VOLUME DAMPER

PERIMETER SLOT DIFFUSERPLENUM W/SOUND LINING

HUNG CEILING

CONTINUOUS PERIMETER SLOT(SEE EQUIPMENT SCHEDULEFOR REQUIRED NUMBER OF SLOTS)

CABLE WITH HEX-NUTADJUSTMENT

GWB SOFFIT(BY OTHERS)

SUPPLY AIRTHRU SLOT

BRANCH OR MAIN DUCT WITH TYPE "B" FIRE DAMPER-DETAILPROPELLER FAN DETAIL

FIRE RATED WALL PARTITION

PROVIDE CLEARANCE FOR DAMPEREXPANSION ON BOTH SIDES ANDTOP AS REQUIRED

ANGLE IRON FRAME AND OVERLAPALL FOUR SIDES FASTENED TODUCT SLEEVE SEE NOTES

MANUFACTURERFURNISHED SLEEVE

SEAL ALL S-JOINTS ATBREAKAWAY CONNECTIONS

FUSIBLE LINK RATED FOR50°F ABOVE MAXIMUMTEMPERATURE OF SYSTEM

FIRE DAMPER FRAMEFACTORY MOUNTED IN SLEEVE

BREAKAWAY CONNECTION(TYP)

6"

FASTEN FIRE DAMPER FRAMETO SLEEVE. SEE NOTES

2" ACCESS DOOR

DUCT3"MIN

3"MIN

MINIMUM 1" OVERLAP

LINTEL

MAXIMUM 6". IF ACCESSDOOR IN SLEEVE,

MAXIMUM 16 INCHES

FASTEN TO SLEEVE(TYP)

GENERAL NOTES:

1. DAMPER TO BE UL LABELED NFPA 90A, BSA AND MEA APPROVED.

2. NFPA APPROVED INSTALLATION DETAILS TO BE PART OF SUBMISSIONOF FIRE DAMPER FOR APPROVAL, WICH SHALL MEET NFPA STANDRAD90A AND SHALL BE BSA APPROVED.

3. DETAILS SHOWN ARE FOR FIRE DAMPERS IN HORIZONTAL DUCTWORK,FOR DAMPERS IN VERTICAL DUCTWORK, DETAILS SIMILAR EXCEPTDAMPERS ARE TO BE SPRING LOADED.

4. ACCESS DOOR IS SHOWN IN SIDE OF DUCT; IF FUSIBLE LINK ISMORE ACCESSIBLE FROM BOTTOM OF DUCT RELOCATE ACCESS DOOR.

1. UL APPROVED BREAKWAY SLIP JOINT CONNECTIONSHALL BE USED.

2. THIS DETAIL IS A GUIDE ONLY. INSTALL FIRE DAMPER INACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONSAND UL LISTING.

3. RETAINING ANGLES MUST OVERLAP THE FIRE WALL 1"MINAND COVER CORNERS OF OPENINGS.

WALL

FIXED LOUVER

12"x12" ACCESS DOOR

16"MIN

ANGLE IRON SIDES

18 GAUGE SHEET METALPLENUM TO EXTEND

FAN AND MOTOR MOUNTEDON VIBRATION ISOLATORS

AIRFLOW

WIRE MESH INLET GUARD

FLEXIBLE CONNECTION

DAMPER (MOTORIZED ORSELF ACTING-SEESPECIFICATIONS)

(10) 2" DIAMETER GEOTHERMALSUPPLY/RETURN PIPES. MINIMUM OF 5'-0"BELOW GRADE IN ALL DIRECTIONS. SEEEXTERIOR WALL PIPE PENETRATION ASSEMBLYDETAIL. HORIZONTAL PIPE SPACING OF 1'-4"CENTER TO CENTER, VERTICAL PIPE SPACINGOF 1'-9" CENTER TO CENTER.

Q

1' - 4"

1'-9

"

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-501G150004-000

MECHANICAL DETAILS

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 3/8" = 1'-0"5 GEOTHERMAL PIPE DETAIL - ENTRY THROUGH BASEMENT WALL, SUB-GRADE

NO. ISSUE DATE: DESCRIPTION

Page 37: G150004-000 F L R C P E M E-000

T

T

T

T

ZONE 1

ZONE 2

ZONE 4

ZONE 3

185'

165'

140'

195'

220'

220'

225'

110'

JH

9

12

6

14

4

15

U

16

13

B

11

10

7

5

3

C

E F

LL

G

YY

XX

ZZ

8

RADIANT HEAT FLOORING. SEE DETAILS.

MANIFOLD FOR RADIANT HEAT FLOORING

RADIANT HEAT FLOORING.SEE DETAILS.

MANIFOLD FOR RADIANTHEAT FLOORING

VEST.V-1

ALCOVEL101-5

WOMEN'S143

MEN'S142

ALCOVEL101-6

PASSAGEL101-7

VEST.V-2

PASSAGEL101-1

COFFEESTATIONL101-3

HOUSINGOPEN OFFICE

130

OFFICE102

RESOURCEROOM

103

RECEPT.L101-2

LOBBYL101

Stainless-steelManifoldSupply/ReturnBall Valve, Set of 2

TemperatureGauge

Uponor hePEX Tubing

ProPEX FittingAssemblies

Stainless-steelManifold Flow Meter

MountingBracket

Fill Valve

Coin Air Vent

Stainless-steel ManifoldIsolation Valve Body

Stainless-steelManifold

Spacer Ring for Actuator

Thermal Actuator,four-wire

Concrete Slab

Wire Tie

Base Material

Slab InsulationWire Mesh, Rebar or Staple to

Rigid Foam

Edge Insulation

Uponor Tubing

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

M-502G150004-000

MECHANICAL DETAILS

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NOTES: CONCRETE SLAB WILL NOT BE RE-INFORCED; CONTRACTOR SHALL FURNISH ALL SUPPORTS AND SPACERS REQUIRED FOR INSTALLATION OF RADIANT PIPING.

SCALE: 1/4" = 1'-0"1 GROUND FLOOR PLAN

SCALE: NTS2 STAINLESS STEEL MANIFOLDSCALE: NTS3 SLAB ON OR BELOW GRADE

NO. ISSUE DATE: DESCRIPTION

Page 38: G150004-000 F L R C P E M E-000

1. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL PLUMBING DRAWINGS.

2. ALL WORK IS NEW UNLESS OTHERWISE NOTED.

3. DRAWINGS ARE DIAGRAMMATIC: DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD.

4. NEITHER ACCURACY NOR COMPLETION OF UTILITY LOCATIONS SHOWN ON DRAWINGS IS GUARANTEED.DETERMINE EXACT LOCATIONS OF EXISTING UTILITY IN FIELD, WHETHER OR NOT SHOWN ON DRAWINGS.EXERCISECAUTION AND IDENTIFY LOCATIONS OF UNMARKED UTILITY LINES AS NECESSARY TO PERFORM WORK OF THISSECTION.

5. ALL PLUMBING WORK SHALL BE IN ACCORDANCE WITH THE CURRENT PLUMBING CODE AND ALLAPPLICABLE LOCALCODES AND DRAWINGS.

6. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE HIS WORK WITH THAT OF ALLOTHERTRADES, INCLUDING (BUT NOT LIMITED TO), ELECTRICAL, HVAC PROCESS PIPING, SPRINKLER, PLUMBINGSTRUCTURAL AND GENERAL ARCHITECTURE.

7. ANY INTERFERENCE SHALL BE BROUGHT TO THE ATTENTION OF THE PROFESSIONAL IN WRITING, AND SHALL BERESOLVED PRIOR TO THE INSTALLATION OF THE WORK INVOLVED.

8. NO WORK SHALL BE INSTALLED IN VIOLATION OF ANY GOVERNING CODES. ANY WORK SHOWN ON THE DRAWINGSWHICH IS IN VIOLATION OF SUCH CODES SHALL BE BROUGHT TO THE ATTENTION OF THE CONSTRUCTION MANAGERAND THE OWNER'S REPRESENTATIVE AND SHALL BE RESOLVED PRIOR TO THE INSTALLATION OF THE WORKINVOLVED.

9. ALL PIPING PENETRATING CEILING AND WALLS SHALL BE INSTALLED WITH ESCUTCHEONS AT THE PENETRATION.(COLOR SHALL BE BY ARCH). ALL PIPING PENETRATING EXTERIOR WALLS AND ROOFS SHALL BE FLASHED IN ANAPPROVED MANNER AND SHALL BE SEALED WEATHER TIGHT. PIPING PENETRATING RATED PARTITIONS SHALL BEPROTECTED AS REQUIRED BY LOCAL CODE AUTHORITY.

10. MANUFACTURER'S MODEL NUMBERS ARE BASIS OF DESIGN, REFER TO SPECIFICATIONS FOR APPROVEDEQUALS..

11. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURERS' RECOMMENDATIONS.

12. ACCESS PANELS SHALL BE FURNISHED AND INSTALLED BY THE G.C. COORDINATE WITH THE G.C THEEQUIPMENT LOCATIONS THAT REQUIRES PERIODIC SERVICE.

13. TOPS OF ALL FLOOR DRAINS SHALL BE SET FLUSH WITH FINISHED FLOOR. ALL PIPING ABOVE GRADE SHALL BEPROPERLY SUPPORTED BY THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING TILES OR CEILINGSTRUCTURE.

14. CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL PLUMBINGEQUIPMENT WITH THE ELECTRICAL DRAWINGS AND SHALL FURNISH EQUIPMENT WIRED FOR THE VOLTAGES SHOWNHEREIN.

15. PROVIDE SHUTOFF VALVES ON ALL BRANCH PIPING AND ON ALL SUPPLIES TO INDIVIDUAL FIXTURES ANDEQUIPMENT. PROVIDE BALL VALVES ON ALL WATER MAIN BRANCHES IN CORRIDORS AND WHERE INDICATED ONDRAWINGS. ALL VALVES SHALL BE ACCESSIBLE.

16. ALL SLEEVES THROUGH CONCRETE FLOORS AND ALL CORE DRILLING OF CONCRETE FLOORS AND WALLSSHALL BEBY THIS CONTRACTOR.

17. CONCRETE PADS AND PLATFORMS FOR WORK OF THIS SECTION WILL BE PROVIDED BY THIS TRADESCONTRACTOR. PROVIDE ALL HARDWARE AS NECESSARY TO COMPLETE THE WORK.

18. SCHEDULE WORK OF THIS SECTION TO AVOID INTERFERENCES WITH FIRE-PROOFING WORK.

19. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER TRADES AND WITH FLASHING REQUIREMENTS.

20. RUN PIPING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS.

21. STRUCTURAL WELDING SHALL BE 1/4-INCH FILLET UNLESS REQUIRED OTHERWISE.

22. PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ONPIPING.

23. PROVIDE BALANCING VALVES AT SYSTEM LOOP RETURNS AND AT RETURN RISERS. PROVIDE SHUT-OFF VALVES ATSYSTEM LOOP SUPPLIES AND SUPPLY RISERS.

24. PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT LOW POINTS.

25. PROVIDE GAUGE FITTINGS AND THERMOMETER WELLS AT HOT WATER SUPPLY AND RETURN BRANCHES AND ATPUMP INLETS AND OUTLETS.

26. VERIFY EXACT SIZES, LOCATIONS, INVERTS AND ELEVATIONS PRIOR TO RUNNING ANY PIPING. REFER TOARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS OF ALL FIXTURES AND EQUIPMENT.

27. WATER HEATERS SHALL BE INSTALLED WITH DRAIN PANS UNDER HEATERS. ROUTE PAN DRAINS TONEARESTFLOOR DRAIN OR SAFE DRAIN.

28. PIPING SHALL NOT RUN OVER ELECTRICAL PANELS AND SHALL BE COORDINATED WITH WORK OF OTHER TRADES.

29. REPAIR AND PATCH ANY PENETRATIONS CREATED AS PART OF THIS SCOPE OF WORK. MATCH NEWFINISHES WITHARCHITECTURAL PLANS.

30. COORDINATE INSTALLATION OF PIPING AND FIXTURES WITH ALL OTHER TRADES.

31. ALL EXCAVATION AND BACKFILL REQUIRED FOR PLUMBING WORK SHALL BE BY THE PLUMBING CONTRACTOR.REFER TO SITE SPECIFICATIONS FOR MORE INFORMATION ON EXCAVATION AND BACKFILL REQUIREMENTS.

32. PAINTING OF ALL ARCHITECTURALLY EXPOSED PIPING WORK SHALL BE BY THE GENERAL CONTRACTOR. PAINTINGOF ANY NON-ARCHITECTURALLY EXPOSED PIPING SHALL BE BY THIS TRADES CONTRACTOR. REFER TO DIVISION 9PAINTING.

33. FIRESTOPPING FOR THE WORK INCLUDED IN THESE DOCUMENTS, SHALL BE FURNISHED AND INSTALLED BY THEPLUMBING CONTRACTOR. REFER TO DIVISION 7 FIRESTOPPING.

34. SLEEVES THAT ARE REQUIRED FOR THIS PROJECTS SHALL BE FURNISHED BY THE PLUMBING CONTRACTOR ANDINSTALLED BY THE GENERAL CONTRACTOR. COORDINATE THE LOCATION OFTHE SLEEVES WITH THE GENERALCONTRACTOR.

PLUMBING GENERAL NOTES

T

M

BPA

PLUMBING SYMBOL LISTBASIC

PS

LS

S

S

EXISTING PIPING

EXISTING PIPING TO BE REMOVED

PIPING TO BE ABANDONED

NEW SOIL, WASTE OR SANITARY PIPING

VENT PIPING (SANITARY)

PIPING BELOW SLAB

DOMESTIC COLD WATER PIPING

DOMESTIC HOT WATER PIPING (120°)

DOMESTIC HOT WATER CIRCULATION PIPING

PIPING w/FREEZE PROTECTION CABLE & INSULATION

ARROW INDICATES DIRECTION OF FLOW

COMPRESSED AIR PIPING

GAS PIPING

EJECTOR DISCHARGE PIPING

INDIRECT WASTE PIPING

PUMP DISCHARGE PIPING

SUMP PUMP DISCHARGE PIPING

STORM WATER DRAINAGE PIPING

TEMPERED WATER PIPING

DISCONNECT FROM EXISTING

CONNECT TO EXISTING

SHOCK/WATER HAMMER ARRESTOR

FLEXIBLE CONNECTION

EXPANSION LOOP SIZE

HOSE BIBB

WALL HYDRANT

FRESH AIR INLET

CLEAN OUT/PLUGGED OUTLET

CAPPED OUTLET

CLEAN-OUT DECK PLATE

P-TRAP

VACUUM BREAKER

BOTTOM PIPE CONNECTION

TOP PIPE CONNECTION

SIDE CONNECTION

PIPE DOWN/DROP

PIPE RISE/UP

PIPE SLOPE

VALVE IN VERTICAL

UNION

REDUCER

WATER PROOF SLEEVE

SLEEVE

PRESSURE GAUGE w/GAUGE COCK

TEMPERATURE GAUGE

FLOOR DRAIN

ROOF DRAIN

PUMP

WATER METER

AUTOMATIC BALL DRIP

VENT THRU ROOF

TRAP

TAMPER SWITCH

PRESSURE SWITCH w/GAUGE COCK

WATERFLOW SWITCH

TEMPERATURE AND PRESSURE RELIEF VALVE

BACKWATER VALVE

PLUG VALVE

MIXING VALVE

RELIEF VALVE

BALL VALVE

BALL VALVE w/LOCK SHIELD

GATE VALVE

GLOBE VALVE

OUTSIDE SCREW & YOKE (OS & Y) VALVE

CHECK VALVE

PRESSURE REDUCING VALVE (PRV)

SOLENOID VALVE

FLOAT VALVE

BALANCING VALVE

Y STRAINER w/BLOW-OFF VALVE

BACKFLOW PREVENTER ASSEMBLY

REDUCED PRESSURE ZONE BACKFLOW PREVENTER ASSEMBLY

REDUCED PRESSURE DETECTOR ASSEMBLY

DOUBLE CHECK VALVE ASSEMBLY

DOUBLE CHECK DETECTOR ASSEMBLY

BALANCING VALVE ASSEMBLY

RISER DESIGNATION:X = RISER SERVICE; # = RISER NUMBER

ST

G

EJ

IW

PD

SD

T

AB

(H) (L)X

ABD

ISOLATION VALVE W/BOX TO GRADE

MANHOLE IN SANITARY SEWER

EXISTING MANHOLE

FIRE HYDRANT

WELL

SITE WATER (COMBINED DOMESTIC & FIRE

WELL WATER

CA

RPZ

RPDA

DCV

DCDA

BVA

X#

WATER SERVICE

WW

W

WH-2-3

XXX-XX-XX

SECOND FLOOR

(REFER TO SPECIFIC TRADE LIST)

EQUIPMENT TAG NUMBERFLOOR DESIGNATIONEQUIPMENT DESIGNATION

WATER HEATER(REFER TO LIST)

UNIT NUMBER 3

PLUMBING EQUIPMENT DESIGNATIONS

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

P-000G150004-000

PLUMBING COVER SHEET

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

PLUMBING ABBREVIATIONSAD AREA DRAINAFF ABOVE FINISHED FLOOR

BLDG BUILDINGBOP BOTTOM OF PIPE

CLG CEILINGCM COFFEE MAKERCO CLEANOUTCODP CLEANOUT DECK PLATECONN CONNECTCONT CONTINUATIONCV CHECK VALVECVO CAPPED AND VALVED OUTLETCW COLD WATER

DIA DIAMETERDN DOWN (PENETRATES FLOOR SLAB)DR DRAINDWG DRAWINGEJ DIS EJECTOR DISCHARGEEQC ELECTRIC WATER COOLER

(E) EXISTING(ER) EXISTING TO BE REMOVED(ERR) EXISTING TO BE REMOVED & RELOCATEDEL ELEVATION

FAI FRESH AIR INLETFD FLOOR DRAINFL FLOORFL H FLOOR HYDRANTFT FEETFU FIXTURE UNIT

GAL GALLONSGC GENERAL CONTRACTORGPM GALLONS PER MINUTE

HB HOSE BIBBHCLG HUNG CEILINGHW HOT WATERHWR HOT WATER RETURN

ID INSDIE DIAMETERIN INCHIW INDIRECT WASTE

JS JANITOR'S SINK

LAV LAVATORY

MAX MAXIMUMMIN MINIMUMMR MOP RECEPTOR

NC NORMALLY CLOSEDNFGH NON FREEZE GROUND HYDRANTNFWH NON FREEZE WALL HYDRANTNIC NOT IN THIS CONTRACTNO NORMALLY OPENNTS NOT TO SCALE

OD OUTSIDE DIAMETEROS&Y OUTSIDE SCREW & YOKE GATE VALVE

PD PLUMBING CONTRACTORPD PUMP DISCHARGEPO PLUGGED OUTLETPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCH (GAUGE)

(RE) RELOCATED EXISTING(RRO) EXISTING TO BE REMOVED AND RETURN TO OWNERRD ROOF DRAIN

SA SHOCK ABSORBERSAN SANITARYSD SUMP PUMP DISCHARGESH SHOWERSK SINKSQ FT SQUARE FOOTST STORM

TYP TYPICAL

UON UNLESS OTHERWISE NOTEDUP UP (PENETRATES FLOOR SLAB)UR URINAL

V VENTVB VACUUM BREAKERVTR VENT THROUGH ROOF

W WASTEWC WATER CLOSETWCO WALL CLEANOUTWH WALL HYDRANT

NO. ISSUE DATE: DESCRIPTION

Page 39: G150004-000 F L R C P E M E-000

CO

CO

WV

MH

MH

MH

MH

WV

WV

WV

MH

WV

WV

MH

WV

MH

WV

MH

MH

WV

MH

WV

WV

BENCHMARK

MAG NAIL SET IN

SIDEWALK SEAM

ELEVATION=317.62

EX. BUILDING

GORDINIER HALLEX. BUILDING

EX. BUILDING

STUDENT MEMORIAL

CENTER

EX.

BUILDING

EX.

BUILDING

EX.

BUILDING

FFE=320.17

FFE=320.21

FFE=320.22

FFE=304.93

C.O.

C.O.

C.O.

C.O.

C.O.

JAMES STREET

( MILLERSVILLE UNIVERSITY)

LOMBARDO WELCOMECENTER

WVWV

6"SAN SERVICE5'-0" FROM FROM BLDG.(CONTINUED BY SITE/CIVIL)

2 1/2"DOMESTIC WATER SERVICE5'-0" FROM FROM BLDG.(CONTINUED BY SITE/CIVIL)

6"FIRE WATER SERVICE5'-0" FROM FROM BLDG.(CONTINUED BY SITE/CIVIL)

4" SPRINKLER PIPE TO5" STORZ FDC5'-0" FROM FROM BLDG.(CONTINUED BY SITE/CIVIL)

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

P-001G150004-000

PLUMBING SITE PLAN

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1" = 30'-0"1 LOWER LEVEL PLAN

DRAWING NOTES:

1. REFER TO SITE CIVIL PLAN FOR TEMPORARY WATER SERVICE CONNECTION.

NO. ISSUE DATE: DESCRIPTION

Page 40: G150004-000 F L R C P E M E-000

21/2"

CW

2 1/2" DOMESTIC WATER SERVICE .5'-0" FROM BUILDING. REFER TO SITE/CIVILDRAWINGS FOR CONTINUATION. 6" SPRINKLER SERVICE. REFER TO

FIRE PROTECTION DRAWINGS FORCONTINUATION.

RPZ

4"S 4"S 4"S

FD-B

FD-B

FD-B

4" SANITARY MAIN. 5'-0" FROM BUILDING.REFER TO SITE/CIVIL DRAWINGS FORCONTINUATION.

P12 1/2"CW UP

4"S

299.00' INV.

310.00' INV.

4"SAN DN4"V UP

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

2"S

2"S

4"S4"S4"S

4"S

2"S2"S

2"S

V1

2 1/2" DOMESTICWATER SERVICE.

2"SAN UPTO F-6

2"SAN UPTO F-6

2"SAN UPTO F-4

3"SAN UPTO FD-B 2"SAN UP

TO FD-A2"W UPTO F-3

2"S UPTO F-2

2"W UPTO F-3

2"SAN UPTO FD-A

4"SAN UPTO F-1A

4"SAN UPS2

3"V

4"S3"S

3"S

3"V

3"S

1"CW

3/4"CW

HB

3/4"CW UPTO NFGH

1"PRV WITHBY-PASS BFP

3/4"CW UP

1

HB

FD-B

3"S

3"S

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

P-100G150004-000

PLUMBING LOWER LEVELPLAN

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN

DRAWING KEY NOTES:

COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.

PROVIDE DEEP SEAL TRAPS ON MECHANICAL FLOOR DRAINS.

1

2

NO. ISSUE DATE: DESCRIPTION

Page 41: G150004-000 F L R C P E M E-000

EWH-1-2

EWH-1-1

NFGH

NFWH

NFWH

F-4

F-1A

F-3

F-3AF-5

F-1

F-1A

F-1A

F-1

F-2A

F-3DW

F-6

F-6

FD-A

FD-A

3/4"CW

3/4"CW

3/4"HW

3/4"C

W

3/4"CW3/4"HW 3/4"CW

3/4"HW

1/2"CW/HW2" SAN/VTO F-6(TYP.)

1/2"CW/HW2" SAN/VTO F-3(TYP.)

1 1/4"CW4" SAN/VTO F-1/F-1A(TYP.)

3/4"CW2" SAN/VTO F-2/F-2A(TYP.)

3/4"CW2" SAN/VTO F-5(TYP.)

3/4"CW/HW2" SAN/VTO F-4(TYP.)

3/4"CWW/ VACUUM BREAKERTO NFWH(TYP.)

3/4"CW W/ VACUUMBREAKER TONFGH(TYP.)

P1 2 1/2"CW DN

3/4"CW

3/4"C

W

3/4"CW

2 1/2"CW

21/2"

CW

2 1/2"CW

RUN PIPING HIGH AND TIGHT TO BEAM

F-5A

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

VEST.V-1

ALCOVEL101-5

WOMEN'S143

PASSAGE104

MEN'S142

ALCOVEL101-6JANITOR

141

MECHANICAL141.1

FAMILYTOILET

144

STORAGE140.1

PASSAGEL101-7

VEST.V-2

CLASSROOM/PRESENTATIONROOM

140

V.P. OFFICE112A

SMALL CONF.105

STORAGE103.1

OFFICE112

PASSAGEL101-1

OFFICE118

OFFICE114

OFFICE116

OFFICE110

OFFICE108

OFFICE104

CORRIDORC 1-1

CORRIDORC 1-2

BREAK ROOM107

STORAGE119

ELEC. RM.121

COFFEESTATIONL101-3

STORAGE103.2

ADMISSIONSOPEN OFFICE

106

HOUSINGOPEN OFFICE

130

OFFICE128

OFFICE126

OFFICE124

OFFICE122

MARKETINGOPEN OFFICE

120

SMALL CONF.115

CONFERENCE117

I.T. ROOM123

CALL CENTER109

CORRIDORC 1-3

OFFICE102

WORK ROOM111

RESOURCEROOM

103

RECEPT.L101-2

STUDENTWORK SPACE

113

LOBBYL101

3

4"ST

4"ST

4"ST

4"ST

6"ST

6"ST 4"ST

4"ST

4"ST

4"ST

4"ST

4"ST

3/4"CW

3/4"CW

4"ST

2"V

2"V

2"V

4"V

2"V

2"V4"V

4"V

4"OF SPILL TOSLASH BLOCK

4"OF SPILL TOSLASH BLOCK

4"OF SPILL TOSLASH BLOCK

V1

V1

4"V UP

4"VTR 4"OF SPILL TOSLASH BLOCK

4"ST SPILL TORAIN GARDEN

4"ST UP TO RD-A(2400 SQFT.)

4"OF UP TO RD-B(2400 SQFT.)

4"ST UP TO RD-A(2045 SQFT.)

4"OF UP TO RD-B(2045 SQFT.)

4"ST UP TO RD-A(2075 SQFT.)

4"OF UP TO RD-B(2075 SQFT.)

4"ST UP TO RD-A(2105 SQFT.)

4"OF UP TO RD-B(2105 SQFT.)

4"ST UP TO RD-A(2150 SQFT.)

4"OF UP TO RD-B(2150 SQFT.)

4"ST

CODP

CODP

CODP

V2

4"VTR

1

4

5

4

F-1RD-C

6"ST

6"ST

6"ST SPILL TORAIN GARDEN

6"ST SPILL TORAIN GARDEN

ST2

6"ST DN(4255 SQFT.)

ST1

6"ST DN(4120 SQFT.)

4"OF SPILL TOSLASH BLOCK

ST3

4"ST DN(2400 SQFT.)

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

P-101G150004-000

PLUMBING GROUNDFLOOR PLAN

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN

DRAWING KEY NOTES:

COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.

PROVIDE DEEP SEAL TRAPS ON MECHANICAL FLOOR DRAINS.

3/4"CW BELOW GRADE TO NON-FREEZE GROUND HYDRANT (NFGH). WRAP IN CELLULAR FOAM COREINSULATION. SIMILAR TO ARMAFLEX. NFGH TO BE INSTALLED IN CONCRETE CURB WITH 24" GRAVEL BEDBELOW FOR DRAINAGE.

FOR NEW COFFEE MAKERS, AND REFRIGERATORS (FURNISHED AND INSTALLED BY OTHERS). EXTEND COLD WATERSERVICE AND PROVIDE BACKFLOW PREVENTER (BFP), WATER FILTER, AND ALL ASSOCIATED APPURTENANCESINSTALLED BENEATH COUNTER. PROVIDE 5'0" OF COPPER COIL FOR EACH PIECE OF EQUIPMENT. (REFER TO DETAIL)

PROVIDE WASTE AND HOT WATER CONNECTION TO DISHWASHER AS PER MANUFACTURER REQUIREMENTS(REFER TO DETAIL)

1

2

3

4

5

DRAWING NOTES:

1. NON FREEZE WALL HYDRANTS SHALL BE INSTALLED IN THE CONCRETE FOUNDATION WALL, AND NOTIN THE TERRACOTTA PANELS.

NO. ISSUE DATE: DESCRIPTION

Page 42: G150004-000 F L R C P E M E-000

RD-ARD-B

RD-ARD-B

RD-ARD-B

RD-ARD-B

RD-A RD-B

L PNM

Q RJH

9

12

6

14

4

15

U

16

17

13

B

11

10

7

5

3

2

C

E F

LL

G

YY

XX

ZZ

RR

1

8

V1 4"VTR

V2

2400 SQFT.

2150 SQFT.

2045 SQFT.

2105 SQFT.

2075 SQFT.

4"VTR

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

P-102G150004-000

PLUMBING ROOF PLAN

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION

Page 43: G150004-000 F L R C P E M E-000

M

SCALE:

SCALE:

RPZ M

BFP

1 DOMESTIC WATER RISER DIAGRAMNONE

2 SANITARY RISER DIAGRAMNONE

DRAIN SCHEDULE

PLUMBING FIXTURE SCHEDULE

ELECTRIC WATER HEATER SCHEDULE

PLUMBING EQUIPMENT SCHEDULE

STRAINER

BACK

WATE

RVA

LVE

SERI

ESNO

.

REQU

IRED

ZURN

WADE

JOSA

M

SMITH

SECO

NDAR

YCL

AMP

CLAM

PING

DEVIC

E

CAST

IRON

2005-A

2110

GALV

ANIZE

D

ALLB

RONZ

E

DECK

CLAM

P

TRAC

TOR

GRAT

E

FLAS

HING

COLL

AR

SUMP

RECI

EVER

NICK

ELBR

ONZE

(ADJ

USTA

BLE)

CHRO

MEPL

ATED

SEDI

MENT

BUCK

ET

SECO

NDAR

YSTR

AINER

POLIS

HED

FINISH

CAST

IRON

GALV

ANIZE

D

ALLB

RONZ

E

SATIN

FINISH

DESIG

NATIO

N

FD-B

FD-A

ALL FLOOR DRAINS IN MECHANICAL EQUIPMENT, BOILER ROOMS,FAN ROOMS ETC., SHALL BE LOCATED IN COORDINATION WITHTHE MECHANICAL CONTRACTOR. PROVIDE DEEP SEAL TRAPS.

THE CONTRACTOR SHALL VERIFY THE COMPATIBILITY OF THE DRAINSWITH THE APPROVED ROOFING AND/OR WATER PROOFING SYSTEMSPRIOR TO SUBMITTING SHOP DRAWINGS.

THE TOP OF CURVE OF ALL FLOOR DRAINS SHALL BE FLUSH WITHTHE ADJACENT FINISHED FLOOR.

1.

2.

3.

4.

SHALL BE LOCATED AS PER THE ARCHITECTURAL DRAWINGS.ALL FLOOR DRAINS IN FINISHED AREAS AND ALL ROOF DRAINS

NOTES:

BODY

BRON

ZEME

SHSC

REEN

POLY

ETHY

LENE

SOLID

HING

EDCO

VER

EXTE

NSIO

N

FLAT

TOP

FUNN

ELTO

P

RAISE

DLIP

DOME

IRON

GRAT

E

BRON

ZETO

P

LESS

GRAT

E

TOILET ROOMS

MER

LOCATION

REMARKS

1080

1010

RD-B

RD-A FLAT ROOF

OVER FLOW W/ 2"DAM

SERVICE CONNECTIONFIXTURES FIXTURE #

WSF-1DF-1C

4"

4"

2"

2"

F-1 F-1A

F-2 F-2A

HANDICAPPED

FLUSH VALVE

URINALS

WATER CLOSET

F-3 F-3A

HANDICAPPED

WASH-OUT

LAV SYSTEM

LAVATORIES

F-2B

F-1B

F-3B

F-4AF-4

RECEPTOR

SLOP SINKS

F-5AF-5E.W.C. F-5B

F-4B

V

2"

2"

1 1/2"

1 1/2"

1 1/2"

1 1/2"1 1/2"

3"

1 1/2" 1 1/2"

MODEL NO. REMARKS

MOUNT AT HANDICAPPED HEIGHT

MOUNT AT HANDICAPPED HEIGHT

HW

SAME AS F-1

SAME AS F-2

3/4"

CW

1 1/4"

1 1/4"

1"

1"

3/4"

3/4" 3/4"

1/2"

MANUFACTURER AND EQUIPMENT

ELKAY

PROVIDE ZURN EZCARRY FIXTURE CARRIERSAS REQUIRED

PROVIDE ZURN FIXTURE CARRIERS AS REQUIRED

PROVIDE OFFSET TRAP, VALVE STOPS, RISERS,FAUCET MIXING VALVE AND INSULATION KIT.0.35 GPC ; 10 SEC CYCLESPROVIDE WITH SOAP DISPENSER (6334)

2257.001TET1LN32-CP95

AMERICAN STANDARD AFWALL EL 1.28TOTO FLUSH VALVEOLSONITE OPEN FRONT SEAT LESS COVER

AMERICAN STANDARD WASHBROOK 0.125TOTO FLUSH VALVE

BRADLEY VERGE LVL SERIESTRIM: BRADLEY FAUCETTRUEBRO ADA KIT

6590.125TEU1UN-CP

LVLD3IR-DCG102W WITH 105W

MSB-3624E-77-AA,889-CC, 832-AA8344.212#G1781 W/ #G3600 MIXING VALVE

FIAT 24"x 24" x 10" MOLDED STONEFIAT BUMPERGUARD, MOP HANGERHOSE AND HOSE BRACKET.TRIM: AMERICAN STANDARDEYE WASH STATION (EWS) - GUARDIAN

SETTINGSYMBOLDEG RISEGALS

STORAGE RECOVERY

GPH ELEMENTSNUMBER

KW

ELECTRICAL

V PH HZREMARKSMANUFACTURER

& MODELTEMP

ET

SA

RPZ

ITEM NO.

ARRESTORSHOCK

TANKEXPANSION

PREVENTERBACKFLOW

EQUIPMENTIW

SERVICE CONNECTION

SERIES 5000J.R. SMITH

MANUFACTURER AND EQUIPMENT

WATTS REDUCED PRESSUREZONE DETECTOR ASSEMBLY

DOMESTIC WATER SERVICEFLOOD PROTECTION VALVE

REMARKS

W/F113-6RFPLF 957RPDA-OSY-AG

MODEL NO.

LOCATE AS SHOWN ON PLAN

W V CW HW

2 1/2"

PIPE SIZE

EWH-1-1

EWH-1-2

TP LOCATE AS SHOWN ON PLAN1/2"TRAP PRIMER P-1-500PPP-INC.

DOMESTIC METERSENSUS OMNI C2

WITH MODBUS CAPABILITIES TIE INTOBMS SYSTEM

SEE DWGS

NON-FREEZE WALLHYDRANT NFWH 3/4" ZURN Z1300

WITH IN-LINE VACUUM BREAKERASSE-1011. LOCATE AS SHOWN ON PLAN

LZSTL8WSLK PROVIDE CARRIER SUPPORT AND INLINEFILTER.

1.28 GPF; ECO POWER BATTERY

1.28 GPF; ECO POWER BATTERY

MV LOCATE AS SHOWN ON PLAN1/2"MIXINGVALVE ZW3870XLTZURN

15 8 180 1.5 120 1 11060 BRADFORD WHITE - LE115U3-1

PROVIDE WITH RELIEF SENSORS AND PAN. EXTEND RELIEF DRAIN TO PAN.EXTEND DRAW FROM PAN TO NEAREST INDIRECT WASTE RECEPTOR.

20 10 80 BRADFORD WHITE - LE120U3-12.0 1201 1 60 110

MOUNT ON WALL. PROVIDE WITH RELIEF SENSORS AND PAN. DRAIN PANTO MOP RECEPTOR.

ROOF

GROUND FLOOR

LOWER LEVEL

ROOF

GROUND FLOOR

LOWER LEVEL

6" COMBINED DOMESTIC AND SPRINKLERWATER SERVICE. 5'-0" FROM BUILDING.FOR CONTINUATION REFER TO SITE/CIVILDRAWINGS.

4" FIRE WATER SERVICE. FORCONTINUATION REFER TO FIREPROTECTION DRAWINGS.

BY FC BY PC

4"

2 1/2"

6"

ROOF

GROUND FLOOR

LOWER LEVEL

ROOF

GROUND FLOOR

LOWER LEVEL

WALL MOUNTED 1 1/2"1 1/2" 3/4" 3/4"BRADLEY VERGE LVL SERIESTRIM: BRADLEY FAUCETTRUEBRO ADA KIT

LVLD1IR-DCG102W WITH 105W

2 1/2"

NFGH

1/2"F-6F-6

3/4"

EWH-1-1

2 1/2"

2 1/2"

NFWH

3/4"3/4"

2 1/2"

F-5F-3AF-1A

3/4"

F-3

1/2"

F-3

3/4"

F-1F-1F-1A

2"

1 1/4" 1 1/4"

F-1F-2A

3/4"

F-1A

NFWH

F-4

3/4"3/4"3/4"

EWH-1-2

2 1/2"1 1/4"

3/4" 3/4"

3" FD-B3" FD-B3" FD-B

4" 4" SANITARY TO MAIN. 5'-0" FROM BLDG.REFER TO SITE CIVIL PLAN FOR CONTINUATION.PROVIDE BUILDING TRAP AND FAI.

3"4"

4"

3"

3"

4"

V1

2"2"

F-6F-6

2"

4"VTR

2"2"

CODP

4"4"

4"

F-3A

2"

2"

F-1A

F-1 F-1 F-1AF-2AF-1F-1A

V2

4"VTR

2"2"2"2"2"

4"

4"

4"2"2"

4"4"

2"

4"

F-3F-3

3" FD-A3" FD-A

3"2"

3"

CODP

4"3"2"

3" FD-AF-4

4"

2"

2"

1/2" 1/2" 1/2"

3/4"3/4"

1/2" 1/2" 1/2" 1/2" 1/2"

1 1/4"1 1/4"

1 1/4"

3/4"

3/4"3/4"3/4"

F-6 F-6A F-6BSINKS

PANTRY 1 1/2"2" 3/4"3/4"SK: ELKAYTRIM: CHICAGO FAUCET

LR-2219201-GN8A-E3-317

1 1/2" 1 1/2" 1/2" ELKAY LZWSGRNM8K 1.1 GPM FILLING. PROVIDE CARRIERSUPPORT AND INLINE FILTER.

BOTTLE FILLINGSTATION

TWO-LEVEL -ADA

NON-FREEZE GROUNDHYDRANT NFGH 3/4" ZURN Z1360

WITH IN-LINE VACUUM BREAKERASSE-1011. LOCATE AS SHOWN ON PLAN

SA

SASA

SA

SA

SASA

EWS

SA

F-5A

WRAP BURIED COPPER PIPE INCELLULAR FOAM CORE INSULATION,SIMILAR TO ARMAFLEX OR EQUAL.

3" FD

1"

1/2"

TP

1 1/4"

3/4" SA

3" FD

1/2"

TP

BFPPREVENTERBACKFLOW WATTS REDUCED PRESSURE

ZONE ASSEMBLYFOR MECHANICAL EQUIPMENT

W/ AIR GAP & DRAIN TO INDIRECT WASTEW/909AGLF 9093/4"

1"3/4"

3/4"CW MAKE UP TOMECHANICAL EQUIPMENT.CONNECTION BY MC.

HB

3/4"

PRV4"

NOTES:

1. PROVIDE WATER BUG SENSORS SIMILAR TO WINLAND WB-200 ON EACH WATER HEATER FORAUTOMATIC LEAK DETECTION. PROVIDE POWER AND LOW VOLTAGE WIRING. TIE INTO NEW ALARM/BAS SYSTEM.

NOTES:

1. FIXTURE CARRIERS SHALL BE OF STEEL CONSTRUCTION.

PROVIDE OFFSET TRAP, VALVE STOPS, RISERS,FAUCET MIXING VALVE AND INSULATION KIT.0.35 GPC ; 10 SEC CYCLESPROVIDE WITH SOAP DISPENSER (6334)

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

P-200G150004-000

PLUMBING RISERDIAGRAMS & SCHEDULES

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

SCALE: 12" = 1'-0"1 PLUMBING RISER DIAGRAM

NO. ISSUE DATE: DESCRIPTION

Page 44: G150004-000 F L R C P E M E-000

PIPE SLEEVE THRU INTERIOR WALL

PIPE SLEEVE

COMPLETELY COVER OPENINGAGAINST WALL AND OF SIZE TOFINISHED ESCUTCHEON PLATE FLUSH

FINISHED WALL SURFACE

FINISHED WALL SURFACESTERMINATE SLEEVE FLUSH WITH

SEALANT

FROM SLEEVEIN SLEEVE - DO NOT SUPPORT PIPEPIPE AND INSULATION TO BE CENTERED

FLASHING SLEEVE

VENT THRU ROOF

VENT STACK OUTLET TO BE 10 FT.(MIN)

WATERTIGHT MANNERMOP IN ROOFING IN AFILL IN ABOVE SLEEVE AND

ANCHORED IN PLACEFLASHING SLEEVEMANUFACTURED STACK

SLEEVECLAMPED INTO FLASHINGSHEET LEAD FLASHING

VENT STACK EXTENSION

VENT STACK

COLLAROPTIONAL CLAMPING

ROOFING

ROOF CONSTRUCTION

MIN. 12"

MIN. 12"

3 FT.ABOVE STRUCTURE FROM ANY WALL OR STRUCTURE ORNOTE:

NO-HUB COUPLING

FOUNDATION WALL PENETRATION DETAIL

SMOOTH CORE DRILL (10" )

LINK-SEAL TYPE LS-400-CWALL PENETRATION SEAL

(VERIFY THICKNESS IN FIELD)FOUNDATION WALL

TYPICAL HANGER DETAIL

ROD (SIZE AS REQUIRED)

THE MANUFACTURER'S RECOMMENDATION.INSTALLATION SHALL BE IN ACCORDANCE WITHSERIES HDI, OR APPROVED EQUAL.CONCRETE ANCHOR HILTI-KWICK BOLT,

EXISTING WF STEEL MEMBER

GENERAL PURPOSE HANGERS MAY BE USED ON PIPING 1" OR SMALLER.

PIPE

CLEVIS HANGERS REQUIRED ON PIPING LARGER 1".*

*CLEVIS HANGER

STEEL RETAINING STRAP

COUPLER

METAL DECK

"C" CLAMP

CONCRETE WITH INSULATION SLOPED)DETAIL OF ROOF DRAIN (POURED

MEMBRANEBUILT-UP

GRAVEL STOPFLASHING RING AND

INSULATION

GRAVEL

EXTENSION

SLAB

FLASHING

PIPE OUTLET

OAKUM

LEAD

GRADE

OVERFLOW DRAINAGE SYSTEMDISCHARGE AT GRADE

PLACARD 8"x6" "CONTACT FACILITYMAINTENANCE STAFF AT XXXX IF WATERDISCHARGES HERE"

ESCUTCHEONPLATE

DOWNSPOUT NOZZLEJR SMITH 1770

24" MIN

SPLASH BLOCK

SLEEVE ANDSEALANT

FLOOR DRAIN WITH ADJUSTABLE TOP

ADJUSTABLE TOP

COLLAR CAN BEUSED AS FLASHINGCLAMP

TO BE FLUSH WITHFINAL FINISH FLOOR

MAT FINISH

FLOOR DRAIN FOR INDIRECT WASTETYPICAL MECHANICAL ROOM

INDIRECT WASTE SPILLOVER MECHANICALROOM FLOOR DRAIN

MAXIMUM DIAMETERBOTTOM BAR STRAINER ONSHORT LEGS

S

SCALE:

S PLUMBING EQUIPMENT SCHEDULE

NTS

WATER HEATER ABOVE HUNG CEILING WALL MOUNTED WATER HEATER DETAIL

TYPICAL DISHWASHER CONNECTION

FOR STRUCTURAL STABILITYREINFORCE AS NECESSARY24"X24"X1-1/2" LIPDRIP PAN (WATERTIGHT)

STEEL RETAINING STRAP

3/4"

RELIEF VALVE

PAN DRAIN

"C" CLAMP

SUPPORTCHANNEL IRON

CONCRETE FLOOR SLAB

HUNG CEILINGBOTTOM OF

HW SUPPLY

CW SUPPLY

VACUUM BREAKER

110°F 110°F

TP

TO TRAPEXP.TANK

ELECTRICWATERHEATER

COPPER TUBING (TYP)5'-0" OF COILED

1/2"

1/2"CW W/ESCUTCHEON

WATTS SD2 BFP(TYPICAL)

(TYP)WHA

ILF-1

COFFEE MACHINEBY OTHERS

REFBY OTHERS

BFP-1

ITEM No.

PREVENTERBACKFLOW

EQUIPMENTIW W

SERVICE CONNECTION

V CWMANUFACTURER AND EQUIPMENT

WATTS BACKFLOW PREVENTER

HW

1/2"

REMARKS

SD2

MODEL No.

IN-LINEFILTER ILF-1 1/2" AP200

5005HYDROTROLJ.R. SMITH1/2"WHAARRESTER

WATER HAMMER

FILTERED WATERREFRIG/COFFEE MAKER

REFRIG/COFFEE MAKERFILTERED WATER

REFRIG/COFFEE MAKERFILTERED WATER

AQUAPURE

ICE MAKERBY OTHERS

SPILL INDIRECTLYTO HUB DRAIN

NOTES:

1. REFER TO ARCHITECTURAL DRAWINGS FOR ROOFING DETAILS

RELIEF VALVE

HW SUPPLY

CW SUPPLY

VACUUM BREAKER

110°F 110°F

ELECTRICWATERHEATER

SPILL INDIRECTLYTO MOP RECEPTOR

MOP RECEPTOR

WALL MOUNTING BRACKETAND STRUCTURAL SUPPORT

CHECK VALVE

DISHWASHER(BY OTHERS)

SINK

3/4"FLEX

2"WASTE

2"VENT

1/2"HW

TYPICAL WATER & FILTER CONNECTION DETAIL

02'

4'6'

08'

16'

24'

06"

9"3"

01'

6"1-

6"0

1/2'

1'2'

01'

2'3'

01'

2'4'

02'

4'8'

4'0

8'16

'0

8'16

'32

'

SHEET NUMBER

SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"

REGISTRATION

CURRENT ISSUE

DRAWING HISTORY

SCAL

E:1/

16"=

1'-0

"SC

ALE:

1/8"

=1'

-0"

SCAL

E:1/

4"=

1'-0

"SC

ALE:

1/2"

=1'

-0"

SCAL

E:3/

4"=

1'-0

"SC

ALE:

1"=

1'-0

"SC

ALE:

11/

2"=

1'-0

"SC

ALE:

3"=

1'-0

"

1

A

CIVIL ENGINEER

STRUCTURAL ENGINEER

MECHANICAL / ELECTRICAL / PLUMBING

FIRE PROTECTION ENGINEER

LANDSCAPE ARCHITECT

ACOUSTICAL ENGINEER

NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION

COPYRIGHT 2016 SFA

AUDIO VISUAL ENGINEER

2 3 4 5 6 7 8 9 10 11 12

B

C

D

E

F

G

H

I

J

SECURITY ENGINEER

SCAL

E:3/

32"=

1'-0

"SC

ALE:

3/8"

=1'

-0"

PROJECT No: MI-1105

C:\R

evit

Loca

lFile

s\G

1500

04-0

00-M

illers

ville

-M

EP15

_Cen

tral_

tbla

ncha

.rvt

P-300G150004-000

PLUMBING DETAILS

Millersville University

LOMBARDO WELCOMECENTER

P.O. Box 1002Millersville, PA 17551-0302

P.O. Box 1002Millersville, PA 17551-0302

09/28/2016

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

Providence Engineering Corporation10 Eisenhower Blvd.

Lancaster, PA 17603717-509-7000

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

InPosse1500 Walnut Street, Suite 1414

Philadelphia, PA 19102215-282-6800

Derck & Edson33 South Broad Street

Lititz, PA 17543717-626-2054

N/A

N/A

N/A

NO. ISSUE DATE: DESCRIPTION