1. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL ELECTRICAL DRAWINGS.
2. ALL WORK IS NEW UNLESS OTHERWISE NOTED.
3. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK. FOLLOWDRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OF OTHER TRADES TO VERIFY SPACE CONDITIONS.MAINTAIN HEADROOM AND SPACE CONDITIONS.
4. SECURE ALL SUPPORTS TO BUILDING STRUCTURE UTILIZING TOGGLE BOLTS (HOLLOW MASONRY), EXPANSIONSHIELDS OR INSERTS (CONCRETE AND BRICK), MACHINE SCREWS (METAL), BEAM CLAMPS (FRAMEWORK), WOODSCREWS (WOOD) OR PAN THRU STRAPS (METAL DECK). NAILS, RAWL PLUGS AND WOOD PLUGS ARE NOTPERMITTED. WHERE REQUIRED BY STRUCTURE, PROVIDE THRU BOLTS AND FISH PLATES. SUPPORT HORIZONTALRUNS OF METALLIC RACEWAYS NOT MORE THAN 10 FT APART. SUPPORT RACEWAY RISERS AT EACH FLOORLEVEL. RUN EXPOSED RACEWAYS PARALLEL WITH OR AT RIGHT ANGLES TO WALLS.
5. PASS RACEWAYS OVER WATER, STEAM OR OTHER PIPING WHEN PULL BOXES ARE NOT REQUIRED. NORACEWAY WITHIN 3 INCHES OF STEAM OR HOT WATER PIPES OR APPLIANCES (EXCEPT PIPE CROSSINGS WHERERACEWAY SHALL BE AT LEAST 1 INCH FROM PIPE COVERS).
6. CUT CONDUIT ENDS SQUARE. REAM SMOOTH. PAINT MALE THREAD OF FIELD THREADED RACEWAYS WITHGRAPHITE BASE PIPE COMPOUND. DRAW UP TIGHT WITH RACEWAY COUPLING.
7. HORIZONTAL OR CROSS RUNS IN PARTITIONS AND WALLS ARE NOT PERMITTED. DO NOT RUN CONDUIT IN PRECASTROOF SLABS, IN 2 INCH SLABS OR IN TERRAZZO FLOOR FINISH.
8. LEAVE WIRES WITH SUFFICIENT SLACK TO PERMIT MAKING FINAL CONNECTIONS. RACEWAYS OVER 10 FT LONG INWHICH WIRING IS NOT INSTALLED: FURNISH FISH WIRE.
9. SET BOXES SQUARE AND TRUE WITH BUILDING FINISH. ERECT WALL AND SWITCH OUTLETS IN ADVANCE OFFURRINGAND FIREPROOFING. SECURE TO BUILDING STRUCTURE BY ADJUSTABLE STRAP IRONS.
10. VERIFY LOCATIONS OF OUTLETS AND SWITCHES IN FINISHED ROOMS WITH ARCHITECTURAL DRAWINGS OFINTERIORDETAILS AND FINISH. IN CENTERING OUTLETS AND LOCATING BOXES AND OUTLETS, ALLOW FOROVERHEAD PIPES,DUCTS AND MECHANICAL EQUIPMENT, VARIATIONS IN FIREPROOFING AND PLASTERING, WINDOW AND DOORTRIM, PANELING, HUNG CEILINGS AND THE LIKE. CORRECT ANY INACCURACY RESULTING FROM FAILURE TODO SO WITHOUT EXPENSE TO OWNER.
11. LOCATIONS INDICATED FOR LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS AT OR NEAR DOORS.COORDINATE WITH ARCHITECT AND INSTALL SWITCH ON SIDE OPPOSITE HINGE. VERIFY FINAL HINGELOCATIONS INFIELD PRIOR TO SWITCH OUTLET INSTALLATION.
12. COVERS OF JUNCTION AND PULLBOXES SHALL BE READILY ACCESSIBLE.
13. PROVIDE PULLBOXES WHERE REQUIRED BY CODE AND WHEREVER NECESSARY TO FACILITATE PULLING OF WIRE.COORDINATE PULLBOX LOCATIONS WITH OTHER TRADES.
14. EMPTY RACEWAY RUNS: PROVIDE PULLBOXES EVERY 100 FT AND AS INDICATED. COORDINATE LOCATIONS WITHOTHER TRADES.
15. JUNCTION AND PULLBOXES: LOCATE GENERALLY NOT EXPOSED IN FINISHED SPACES. WHERE NECESSARY,REROUTE RACEWAYS OR MAKE OTHER ARRANGEMENTS FOR CONCEALMENT.
16. SUPPORT PANEL, JUNCTION AND PULLBOXES INDEPENDENTLY TO BUILDING STRUCTURE WITH NO WEIGHT BEARINGON RACEWAYS.
17. ALL ACCESS DOOR LOCATIONS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR. ELECTRICAL CONTRACTORSHALL NOTIFY GENERAL CONTRACTOR OF ANY LOCATIONS THAT REQUIRE AN ACCESS PANEL.
18. CONNECT CONDUIT TO MOTOR CONDUIT TERMINAL BOXES WITH FLEXIBLE CONDUIT (MINIMUM 18 IN. LENGTHAND 50%SLACK). DO NOT TERMINATE IN OR FASTEN RACEWAYS TO MOTOR FOUNDATION.
19. PROVIDE 2#14 INDICATING PILOT LIGHT WIRES FROM PILOT LIGHT IN CONTROLLER TO LOAD SIDE OF DISCONNECTSWITCH. RUN WIRES IN BRANCH CIRCUIT CONDUIT AND INCREASE CONDUIT SIZE AS REQUIRED.
20. PULL NO THERMOPLASTIC WIRES AT TEMPERATURES LOWER THAN 32°F (0C). PROVIDE CABLE SUPPORTS FORWIRE IN RISER CONDUITS AS REQUIRED BY CODE.
21. PROVIDE SEPARATE RACEWAYS FOR CONDUCTORS OF NORMAL AND EMERGENCY CIRCUITS. COMMON BOXES:PROVIDE BARRIERS BETWEEN EMERGENCY AND NORMAL WIRING.
22. HEIGHTS OF OUTLETS FROM FINISHED FLOOR TO CENTERLINE OF OUTLET:
RECEPTACLES AND TELEPHONES:GENERALLY 1'-6"OVER WORK BENCHES 3'-6"WALL SWITCHES 4'-0"WALL FIXTURES 7'-0"MOTOR CONTROLLERS 5'-0"GONGS AND HORNS 7'-6"FIRE ALARM STATIONS 4'-0"CLOCKS 7'-6"STROBE LIGHTS 6'-8" TO BOTTOM
EXCEPTIONS: AT JUNCTION OF DIFFERENT WALL FINISH MATERIALS, ON MOLDING OR BREAK IN WALL SURFACE, INVIOLATION OF CODE REQUIREMENTS, AS NOTED OR DIRECTED.
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND CONFIRMING ALL MOUNTING HEIGHTS WITHARCHITECT AND ARCHITECTURAL DRAWINGS.
23. WIRE COLOR CODING: AS PER CODE. WHERE COLOR-CODED CABLE IS NOT AVAILABLE, CERTIFY IN WRITINGANDREQUEST PERMISSION FOR OVERLAP COLOR TAPING OF CONDUCTORS (MINIMUM LENGTH 6") IN ACCESSIBLELOCATIONS. COLOR CODING, ONCE SELECTED, MUST BE USED CONSISTENTLY FOR THE ENTIREPROJECT.
24. INSTALL NEW WORK AND CONNECT TO EXISTING WORK WITH MINIMUM. INTERFERENCE TO EXISTING FACILITIES.TEMPORARY SHUTDOWNS: ONLY WITH WRITTEN CONSENT OF OWNER. MAINTAIN CONTINUOUS OPERATION OFEXISTING FACILITIES. ALARM AND EMERGENCY SYSTEMS ARE NOT TO BE INTERRUPTED.
25. FIRESTOPPING SHALL BE INSTALLED WHENEVER WIRING OR RACEWAYS CROSS FIRE RATED CONSTRUCTION.
26. REPAIR AND PATCH ANY PENETRATIONS CREATED AS PART OF THIS SCOPE OF WORK. MATCH NEW FINISHESWITH ARCHITECTURAL PLANS.
27. COORDINATE INSTALLATION OF CONDUIT, CABLES, WIRES, AND FIXTURES WITH ALL OTHER TRADES.
28. ANY REQUIRED EXCAVATION AND BACKFILL REQUIRED FOR THIS PROJECT SHALL BE BY THE CONTRACTOR OFEACH TRADES WORK. COORDINATE WITH EACH OTHER TRADE.
ELECTRICAL GENERAL NOTES
XX
XX
AIM
R
RTS
HC
CD
CCD
XX
CONTROL UNITS (PANELS) SYMBOLS
SIGNAL INITIATING DEVICES & ACTIVATIONSWITCHES SYMBOLS
NOTIFICATION APPLIANCES SYMBOLS
FIRE ALARM CONTROL PANEL
FIRE ALARM DATA GATHERING PANEL
FIRE ALARM ANNUNCIATOR
UNINTERRUPTIBLE POWER SUPPLY
ELEVATOR STATUS/RECAL
NOTIFICATION APPLIANCE SUBSCRIPTS ('XX')WP = WEATHERPROOFWG = WIRE GUARDH = HIGH AUDIBLE SETTINGL = LOW AUDIBLE SETTINGC = CEILING MOUNTnW = WATTAGE SETTING (n = SPEAKER TAP)P = PENDENTSL = SIGNAL LIGHTRI = REMOTE INDICATOR
HORN ONLYC = CEILING MOUNT
SPEAKER ONLYC = CEILING MOUNT
BELL - SINGLE STROKE
BELL - TROUBLE
GONG
VISIBLE ONLY (STROBE) - WALL MOUNTCD = CANDELA RATING/SETTING
VISIBLE ONLY (STROBE) - CEILING MOUNTCD = CANDELA RATING/SETTING
COMBINATION HORN/VISIBLECD = CANDELA RATING/SETTINGC = CEILING MOUNT
COMBINATION SPEAKER/VISIBLECD = CANDELA RATING/SETTINGC = CEILING MOUNT
REMOTE INDICATOR - WALL MOUNT
REMOTE ALARM INDICATING AND TEST SWITCH
REMOTE INDICATOR - CEILING MOUNT
FACP
DGP
FAA
UPS
ESR
MANUAL STATION - PULL STATION/FIRE ALARM BOX,'XX' DENOTES TYPE:
CO2 = CARBON DIOXIDEDC = DRY CHEMICALHL = HALONF = FIRE ALARMFO = FOAMWC = WET CHEMICALCA = CLEAN AGENTWM = WATER MISTDL = DELUGE FIRE SPRINKLERPRE = PREACTION
HEAT DETECTOR/SENSOR (THERMAL DETECTION) ORIENTATIONNOT TO BE CHANGED
HEAT DETECTOR/SENSOR, 'XX' DENOTES TYPE:R/F = COMBINATION RATE OF RISE/FIXED TEMPERATURER/C = RATE COMPENSATIONF = FIXED TEMPERATURER = RATE OF RISE ONLY
SMOKE DETECTOR/SENSOR, 'XX' DENOTES TYPE:AS = AIR SAMPLINGP = PHOTOELECTRICI = IONIZATIONR = RELAY BASESS = SINGLE STATIONSB = SOUNDER BASEID = IN DUCT
SMOKE/HEAT DETECTOR/SENSOR COMBINATION
SMOKE DETECTION/SENSOR FOR DUCT
FLOW DETECTOR/SWITCH
TAMPER DETECTOR/SWITCH
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
ADDRESSABLE INPUT/OUTPUT MODULE# DENOTES NUMBER OF INPUTS AND OUTPUTS
NON-ADDRESSABLE OUTPUT RELAY
XX
XX
FS
TS
AOM
AIO#
RELATED EQUIPMENTDOOR HOLDER
DOOR CLOSER
END OF LINE RESISTOR
ISOLATOR MODULE(STYLE 6 OR 7 FAULT PROTECTION)
JUNCTION BOX
DH
J
DCL
ISO
SC
SS
T
G
CD
CCD
RI
RI
ELECTRICAL SYMBOLS LISTLIGHTING SYMBOLS
POWER SYMBOLS
SINGLE LINE DIAGRAM SYMBOLS
VOICE/DATA/P.A. SYMBOLS
m
CB
S
S
'A'a
'A'
NSNS 'A'a
'A'
'A'a
'A'a
a a
a'A'NS
'A'a
EM
a'A'
a'A'
'A'a
'X'
'X1'
'A'
'A'
'A'
3a
450
A
100/90/3
13,5,
1
30/3
100/3
100/60/3
90/3
A
1HA
WALL MOUNTED PUBLIC ADDRESS SPEAKERD = DUAL HORN
CEILING MOUNTED PUBLIC ADDRESS SPEAKERD = DUAL HORN
VOICE & DATA OUTLET LOCATION WITH 3/4" CONDUITTERMINATED IN A 90 DEG. BEND 6" INTO NEAREST ACCESSIBLECEILING
#/# = # OF VOICE JACKS / # OF DATA JACKS
VOICE OUTLET LOCATION WITH 3/4" CONDUIT TERMINATED IN A90 DEG. BEND 6" INTO NEAREST ACCESSIBLE CEILING
P = PUBLICF = FAXW = WALL MOUNTED 48"AFF# = NUMBER OF JACKS
DATA OUTLET LOCATION WITH 3/4" CONDUIT TERMINATED IN A90 DEG. BEND 6" INTO NEAREST ACCESSIBLE CEILING
# = NUMBER OF JACKS
TELEVISION OUTLET LOCATION WITH 3/4" CONDUIT TERMINATEDIN A 90 DEG. BEND 6" INTO NEAREST ACCESSIBLE CEILING
2'x4'/2'x2' RECESSED FLUORESCENT CEILING MOUNTEDFIXTURE
'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'NS = NOT SWITCHEDNL = NIGHT LIGHT
SIMILAR TO ABOVE WITH EMERGENCY BACKUP'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'
RECESSED FLUORESCENT LIGHT FIXTURE ON EMERGENCYLIFE SAFETY CIRCUIT
'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'
WALL MOUNTED FLUORESCENT LIGHT FIXTURE'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'NS = NOT SWITCHEDNL = NIGHT LIGHT
FLUORESCENT STRIP FIXTURE - TYPE AS NOTED'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'EM = EMERGENCY BACKUP
UNDERCABINET LIGHT FIXTURE'A' = FIXTURE TYPE
RECESSED CEILING MOUNTED FIXTURE'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'EM = EMERGENCY BACKUP
WALL MOUNTED LIGHT FIXTURE'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'EM = EMERGENCY BACKUP
ACCENT LIGHT OR WALL WASHER'A' = FIXTURE TYPE'a' = CONTROLLED BY SWITCH 'a'EM = EMERGENCY BACKUP
CEILING MOUNTED EXIT LIGHT; TYPE 'X' - DIRECTIONALARROWS WHERE INDICATED - SHADED AREAS INDICATEILLUMINATED FACE/FACES
WALL MOUNTED EXIT LIGHT; TYPE 'X' - DIRECTIONALARROWS WHERE INDICATED - SHADED AREAS INDICATEILLUMINATED FACE/FACES
EMERGENCY BATTERY LIGHT UNIT'A' = FIXTURE TYPE
REMOTE LIGHT HEADS FOR EMERGENCY BATTERY LIGHTUNIT TYPE AS NOTED
SINGLE POLE SWITCHa = CONTROLLING OUTLET 'a'2 = DOUBLE POLE3 = THREE-WAY4 = FOUR-WAYD = DOORK = KEY OPERATEDMO = MOMENTARY CONTACTT = TIME SWITCHP = PILOT LIGHT
DISCONNECT SWITCH - TOGGLE TYPE WITH THERMALOVERLOAD
DISCONNECT SWITCH - TOGGLE TYPE MOTOR RATED, 20A,1P, U.O.N.
WALL DIMMER - TYPE 'A' NUMBER INDICATES WATTAGERATING
OCCUPANCY SENSOR, CEILING MOUNTED
OCCUPANCY SENSOR, WALL MOUNTED
PHOTO CONTROL SWITCH
SPEAKER BACKBOX
20A, 125V DUPLEX RECEPTACLE - FLUSH WALL MOUNTEDCONTROLLED FROM WALL SWITCH 'a'
20A, 125V QUADRUPLEX RECEPTACLE - ABOVE COUNTER -REFER TO ARCH FOR MOUNTING HEIGHT
20A, 125V QUADRUPLEX RECEPTACLE - FLUSH WALLMOUNTED
20A, 125V DUPLEX RECEPTACLE FLUSH WALL MOUNTED.GFI TYPE.
20A, 125V WEATHER RATED DUPLEX RECEPTACLEFLUSH WALL MOUNTED WITH EXTERIOR COVER
SINGLE RECEPTACLE - FLUSH WALL MOUNTEDFM = FLOOR MACHINEWC = WATER COOLERXR = X-RAY
20A, 125V DUPLEX RECEPTACLE SURFACE MOUNTED
20A, 125V SURGE SUPPRESSION DUPLEX RECEPTACLE.FLUSH WALL MOUNTED
FLUSH FLOOR MOUNTED JUNCTION BOX OR POKE-THRUFOR ELECTRIFIED FURNITURE POWER FEED
C = VOICE/DATA FEED
20A, 125V DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED
20A, 125V QUADRUPLEX RECEPTACLE FLUSH FLOORMOUNTED
SPECIAL PURPOSE RECEPTACLE - FLUSH WALL MOUNTEDA = TYPE
SPECIAL PURPOSE RECEPTACLE - FLUSH FLOOR MOUNTEDA = INDICATES TYPE
PLUG-IN SURFACE METAL RACEWAY - LETTER INDICATESTYPE - WITH SPECIAL PURPOSE RECEPTACLES WHEREINDICATED
HOMERUN-NUMERAL WHERE USED INDICATES CIRCUITNUMBER FOR REFERENCE ONLY.
2#12+1#12G-3/4"C FOR ONE CKT. HOMERUN, U.O.N.3#12+1#12G-3/4"C FOR TWO CKT. HOMERUN, U.O.N.4#12+1#12G-3/4"C FOR THREE CKT. HOMERUN, U.O.N.
HOMERUN - NUMERAL WHERE USED INDICATES CIRCUITNUMBER FOR REFERENCE ONLY
DIMMER ZONE HOMERUN
MOTOR CONTROLLER
COMBINATION MOTOR CONTROLLER AND DISCONNECTSWITCH SWITCH AMPS/# OF POLES, VOLTAGE RATING ASREQUIRED
UNFUSED DISCONNECT SWITCHSWITCH AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED
FUSED DISCONNECT SWITCH; SWITCH AMPS/FUSE AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED
ENCLOSED CIRCUIT BREAKERTRIP AMPS/# OF POLES, VOLTAGE RATING AS REQUIRED
NA = NON-AUTOMATIC
SURFACE MOUNTED LIGHTING PANELBOARD
FLUSH MOUNTED LIGHTING PANELBOARD
SURFACE MOUNTED POWER PANELBOARD
FLUSH MOUNTED POWER PANELBOARD
SURFACE MOUNTED POWER DISTRIBUTION PANELBOARD
CEILING MOUNTED JUNCTION BOX WITH FINAL EQUIPMENTCONNECTION
FLUSH WALL MOUNTED JUNCTION BOX WITH FINALEQUIPMENT CONNECTION
FLUSH FLOOR MOUNTED JUNCTION BOX
a
FM
C
A
A
B
D A
OS
PC
S
OS
J
J
J
POWER TRANSFORMERVOLTAGES, WINDINGS AND SIZE AS INDICATED
AUTOMATIC TRANSFER SWITCHATS = AUTOMATIC TRANSFERMTS = MANUAL TRANSFER POLES
AND RATING AS NOTED
MOTOR
GENERATOR
GROUND CONNECTION
FUSED SWITCH100 AMP SWITCH / 90 AMP/ 3 POLE
UNFUSED SWITCH100 AMP SWITCH / 3 POLE
CIRCUIT BREAKER - DRAW OUT TYPE100 AMP FRAME / 90 AMP TRIP
CIRCUIT BREAKER - MOLDED CASE TYPE90 AMP TRIP / # OF POLES
LT = LONG TIME SETTINGST = SHORT TIME SETTINGI = INSTANTANEOUS SETTING
NETWORK PROTECTOR2000 AMP FRAME / 1600 AMP TRIP
DIGITAL MULTIMETER
MEDIUM VOLTAGE CIRCUIT BREAKER200A CAPACITY
MEDIUM VOLTAGE CIRCUIT BREAKERDRAW OUT TYPE - 200A CAPACITY
CURRENT TRANSFORMERNUMBER AND RATIO AS INDICATED
FUSED SWITCH100 AMP SWITCH / 90 AMP
HOOKSWITCH FUSE - 125A EXPULSION FUSE
CURRENT LIMITER
LIGHTNING ARRESTOR WITH GROUND CONNECTION
CAPACITOR
REACTOR
COMBINATION MOTOR CONTROLLER AND FUSEDDISCONNECT SWITCH; SWITCH AMPS / FUSE AMPS / # OFPOLES. VOLTAGE RATING & STARTER SIZE AS REQUIRED
COMBINATION MOTOR CONTROLLER AND CIRCUITBREAKER TRIP AMPS / # OF POLES, VOLTAGE RATING &STARTER SIZE AS REQUIRED
460V500kVA120/208V
NEL
ATS-1200A4P
M
G
100/3
100/90
90/3
2000/1600
M
52 200A
52200A
3400/5
100/90
125A
100/90/3
90/3
DS
TV
S D
##
#
#
K
EM EM
NLNL
EM
EM
EM
PULLBOX
EXISTING CONDUIT TO BE REMOVED
EXISTING CONDUIT/EQUIPMENT TO REMAIN
NEW CONCEALED CONDUIT
NEW EXPOSED CONDUIT
NEW UNDERGROUND/IN SLAB CONDUIT
NEW EMERGENCY CONDUIT
CONDUIT TURNING UP
CONDUIT TURNING DOWN
CONDUIT STUB-UP WITH FLEXIBLE EQUIPMENTCONNECTION
FLEXIBLE EQUIPMENT CONNECTION
CAPPED CONDUIT
PUSH BUTTONK = KEY OPERATEDH = HOLD UPP = PANIC
SECTION A-A
FEEDER DESIGNATIONH = 480VL = 208VA = SWITCHBOARD 'A'1 = FEEDER NUMBER ONE
WP
+
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
E-000G150004-000
ELECTRICAL COVER SHEET
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
ELECTRICAL ABBREVIATIONSKVA KILOVOLT AMPEREKW KILOWATTKWH KILOWATT HOUR
LCP LOCAL CONTROL PANELLIM LINE ISOLATION MONITORLTG LIGHTING
MAP MECHANICAL ALARM PANELMAX MAXIMUMMCA MINIMUM CIRCUIT AMPERESMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMDP MAIN DISTRIBUTION PANELMECH MECHANICALMER MECHANICAL EQUIPMENT ROOMMFS MAIN FUSED SWITCHMH MANHOLEMIC MICROPHONEMIN MINIMUMMLO MAIN LUG ONLYMOPD,MOCP MAXIMUM OVERCURRENT PROTECTIONMTD MOUNTEDMTG MOUNTINGMTS MANUAL TRANSFER SWITCHMUFS MAIN UNFUSED SWITCH
N NEUTRALNIC NOT IN CONTRACTNO NORMALLY CLOSEDNO NORMALLY OPENNP NETWORK PROTECTORNTS NOT TO SCALE
OC ON CENTEROCB OIL CIRCUIT BREAKEROD OUTSIDE DIAMETER
P POLEPA PUBLIC ADDRESSPAP PLUMBING ALARM PANELPB PULL BOXPBS PUSH BUTTON SWITCHPHC PIPE HEATING CABLEPNL PANELPR PRINTERPS PRESSURE SWITCHPT POTENTIAL TRANSFORMERPWR POWERø PHASE
(RE) RELOCATED EXISTING(RRO) EXISTING TO BE REMOVED AND RETURN TO OWNERRCS REMOTE CONTROL SWITCHRDCP REMOTE DATA COLLECTION PANELRECEPT,REC RECEPTACLEREF REFRIGERATORREQ REQUIREDRFL RAISED FLOORRG ROOM GROUND POINTRM ROOMRO RACEWAY ONLYRP REFERENCE GROUND POINT
SAP SPRINKLER ALARM PANELSBST SUBSTATIONSCHED,SCH SCHEDULESD SMOKE DETECTORSDP SMOKE DETECTION PANELSE SINGLE ENDED SUBSTATIONSECT SECTIONSIG SIGNALSN SOLID NEUTRALSP SINGLE POLESPEC SPECIFICATIONSPKLR SPRINKLERSPKR SPEAKERSV SOLENOID VALVESW SWITCHSWBD SWITCHBOARDSWGR SWITCHGEARSYM SYMMETRICALSYS SYSTEMS
TB TROUBLE BELLTBD TO BE DETERMINEDTEL TELEPHONETEMP TEMPERATURETHERM THERMOSTATTLBD TERMINAL BOARDTP TAMPER PROOFTRANSF,XFMR TRANSFORMERTS TAMPER SWITCHTV TELEVISIONTVSS TRANSIENT VOLTAGE SURGE SUPPRESSIONTYP TYPICAL
UFD UNDERFLOOR DUCTUH UNIT HEATERUNF UNFUSEDUON UNLESS OTHERWISE NOTED
V VOLT OR VOLTAGEVA VOLT AMPEREVP VAPORPROOFWFD VARIABLE FREQUENCY DRIVEWM VOLTMETER
W WATTWFS WATERFLOW SWITCHWHM WATT HOUR METERWP WEATHERPROOFWT WATERTIGHT
XP EXPLOSION PROOF
+ SPECIAL MOUNTING HEIGHT. COORDINATE LOCATION WITHARCHITECTURAL ELEVATIONS
1P SINGLE POLE2P TWO POLE3P THREE POLE
A AMPEREAC ABOVE COUNTERACB AIR CIRCUIT BREAKERAFF ABOVE FINISHED FLOORAIC AMPERE INTERRUPTING CAPACITYAL ALUMINUMALM ALARMAMM AMMETERAQST AQUASTATARF ABOVE RAISED FLOORASYM ASYMMETRICALATS AUTOMATIC TRANSFER SWITCHAUTO AUTOMATICAV AUDIO VISUALAWG AMERICAN WIRE GAUGE
BG BREAK GLASS SWITCHBIL BASIC IMPULSE LEVELBLDG BUILDING
C CONDUITCAB CABINETCAT CATALOGCB CIRCUIT BREAKERCCTV CLOSED CIRCUIT TELEVISIONCKT CIRCUITCL CENTER LINECLG CEILINGCLOS CLOSETCO CONDUIT ONLYCOMM COMMUNICATIONCONN CONNECTEDCONT CONTINUATIONCT CURRENT TRANSFORMERCTL CONTROLCU COPPERCUH CABINET UNIT HEATER
DB DECIBELDE DOUBLE ENDED SUBSTATIONDEG DEGREEDF DRINKING FOUNTAINDIA DIAMETERDISC DISCONNECTDIV DIVISIONDN DOWNDP DISTRIBUTION PANEL BOARDDT DUST TIGHTDWG DRAWING°C DEGREE CELSIUS°F DEGREE FAHRENHEIT
(E) EXISTING TO REMAIN(ER) EXISTING TO BE REMOVED(ERR) EXISTING TO BE REMOVED AND RELOCATEDE.C. EMPTY CONDUITEA EACHEC ELECTRICAL CONTRACTOREL ELEVATIONELEC ELECTRICALELEV ELEVATOREMER,EM EMERGENCYEQUIP EQUIPMENTERC ELECTRIC REHEAT COILEWC ELECTRIC WATER COOLEREXIST,EX EXISTINGEXT EXTERIOR
FA FIRE ALARMFACP FIRE ALARM CONTROL PANELFAP FIRE ALARM ANNUNCIATOR PANELFBO FURNISHED BY OTHER DIVISION OF WORKFCU FAN COIL UNITFDR FEEDERFDS FUSED DISCONNECT SWITCHFIXT FIXTUREFL FLFLA FULL LOAD AMPERESFLEX FLEXIBLEFLUOR FLUORESCENTFM FLOOR MACHINEFRZ FREEZERFSP FAN SHUTDOWN PANE;FT FEET OR FOOT
G GROUNDGEN GENERATORGFI GROUND FAULT INTERRUPTER
HC HUNG CEILINGHH HAND HOLEHID HIGH INTENSITY DISCHARGEHN HALF NEUTRALHP HORSE POWERHV HIGH VOLTAGEHZ HERTZ
IC INTERRUPTING CAPACITYID INSIDE DIAMETERIG ISOLATED GROUNDINCAND INCANDESCENTINST INSTRUMENTIPC ISOLATED POWER CENTERIPX ISOLATED POWER CENTER X-RAY
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILSKV KILOVOLT
NO. ISSUE DATE: DESCRIPTION
CO
CO
GC
MC
EC
PC/FPC
WV
MH
MH
MH
MH
WV
WV
WV
MH
WV
WV
MH
WV
MH
WV
MH
MH
WV
MH
WV
WV
BENCHMARK
MAG NAIL SET IN
SIDEWALK SEAM
ELEVATION=317.62
EX. BUILDING
GORDINIER HALL
EX. BUILDING
EX. BUILDING
STUDENT MEMORIAL
CENTER
EX.
BUILDING
EX.
BUILDING
EX.
BUILDING
FFE=320.17
FFE=320.21
FFE=320.22
FFE=304.93
C.O.
C.O.
C.O.
C.O.
C.O.
JAMES STREET
( MILLERSVILLE UNIVERSITY)
LOMBARDO WELCOMECENTER
WVWV
UT UT
UT
UT
INSTALL (N)15KV CABLE IN(E)ELECTRICAL DUCTBANK
INTERCEPT (E)ELECTRICALDUCTBANK AT THIS LOCATION
DEDUCT ALTERNATE -TRANSFORMER LOCATION
Z1
TYPICAL MU STANDARDPEDESTRIAN FIXTURE. FIXTUREAND POLE BY OWNER.
(N)DUCTBANK E-1 - REFER TO DETAIL 1/E-002
TO GORDINIER
TO GORDINIER(N) TELECOM DUCTBANKT-1 - SEE DET. 3/E-002
IT ROOM #123 - SEE FLOOR PLAN
(N)GROUNDINGCOUNTERPOISE -REFER TO DET. 8/E-002
(N)DUCTBANK - REFERTO DETAIL 2/E-002
(ER)ABANDONEDDUCTBANK
2
3
12A
2A
4
2A
(N)PAD MOUNTEDTRANSFORMER AND HVL SWITCH -REFER TO DETAIL 5/E-002. PROVIDEHOUSEKEEPING PAD.
PV TRACKER (NOT INCLUDEDIN BASE BID #3). CONNECT TOINVERTER "G1".
Z1
Z1Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1Z1Z1
Z1 Z1Z1
Z1
Z1
L2
L2
L2
L2
5
5
5
5
INVERTER "G1" MOUNTEDTO TRACKER SUPPORTG1-1
G1-3
G1-4
G1-2
(E)LOOP FEED SWITCH #7
(E)COMM MANHOLE
(E)COMMMANHOLE MH-10
(E)COMM DUCTBANK
(E)COMM DUCTBANK
(E)COMM DUCTBANK
02
'4
'6
'0
8'
16
'2
4'
06
"9
"3
"0
1'
6"
1-6
"0
1/
2'
1'
2'
01
'2
'3
'0
1'
2'
4'
02
'4
'8
'4
'0
8'
16
'0
8'
16
'3
2'
SHEET NUMBER
SFA PROJECT NUMBER
FULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SC
ALE
: 1/
16
" =
1'-0
"S
CA
LE: 1
/8
" =
1'-0
"S
CA
LE: 1
/4
" =
1'-0
"S
CA
LE: 1
/2
" =
1'-0
"S
CA
LE: 3
/4
" =
1'-0
"S
CA
LE: 1
" =
1'-0
"S
CA
LE: 1
1/
2"
= 1
'-0"
SC
ALE
: 3"
= 1
'-0"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SC
ALE
: 3/
32
" =
1'-0
"S
CA
LE: 3
/8
" =
1'-0
"
PROJECT No: MI-1105
C:\
Revi
t Lo
cal F
iles\
G1
50
00
4-0
00
- M
ille
rsvi
lle -
MEP
15
_C
entr
al_
jbut
z.rv
t
E-001G150004-000
ELECTRICAL SITE PLAN
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1" = 30'-0"1
SITE PLAN
DRAWING NOTES:1. REFER TO E-300 FOR THE SINGLE LINE DIAGRAM. 2. ALL EXCAVTION AND BACKFILL NEEDED FOR ELECTRICAL WORK SHALL BE PERFORMED
BY THE ELECTRICAL CONTRACTOR. REFER TO SITE SPECIFICATION FOR MOREINFORMATION ON EXCAVATION AND BACKFILL REQUIREMENTS.
3. ALL TEMPORARY POWER SHALL BE FED FROM LOOP SWITCH FOR PHASE 2 DORMS.ELECTRICAL CONTRACTOR SHALL CONNECT TO THIS LOOP SWITCH AND PROVIDE POWERFOR A TEMPORARY TRANSFORMER AND TEMPORARY SERVICE FOR THE PROJECT SITEAND ALL TRADES.
4. ALL MAIN ELECTRICAL SERVICE EQUIPMENT SHALL BE PURCHASED BY ELECTRICALCONTRACTOR.
5. ALL EXTERIOR POLE MOUNTED LIGHTING AND BOLLARDS SHALL BE CIRCUITED BACK TO480/277V LIGHTING PANEL AT GORDINIER LOCATED ON FIRST FLOOR.
6. ELECTRICAL CONTRACTOR SHALL INTERCEPT AND REROUTE EXISTING DUCT BANK.CONTRACTOR SHALL PULL 15KV PRIMARY WIRES FROM LOOP FEED SWITCH#7.
7. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL TRADES TO ENSURE THERE IS12 INCH CLEARANCE BETWEEN OTHER TRADES PIPING, ETC...
8. PROVIDE AN ADD ALTERNATE SCOPE ITEM FOR A COMPLETE UL MASTER LABELLIGHTNING PROETECTION SYSTEM LOCATED ON ROOF. REFER TO THE ELECTRICALCONSTRUCTION BID FORM.
9. COORDINATE DUCTBANK DETAILS WITH SINGLE LINE DIAGRAMS FOR CONDUIT ANDFEEDER SIZES. ALL CONDUITS SHALL BE ENCASED IN MIN. 5" CONCRETE ENVELOPEWHERE SHOWN.
10. DUCTBANK/CONDUIT DEPTHS SHALL BE 24" MINIMUM TO 30" MAXIMUM FROM TOP OFDUCTBANK/CONDUIT TO GRADE, UNLESS OTHERWISE INDICATED ON DRAWINGS ORREQUIRED TO PASS OTHER UTILITIES. UNLESS OTHERWISE NOTED, THE MINIMUMDUCTBANK CLEARANCES FROM OTHER UNDERGROUND FACILITIES SHALL BE ASFOLLOWS:
18. BEFORE EXCAVATING, THE ELECTRICAL CONTRACTOR SHALL TAKE ALL POSSIBLEPRECAUTIONS TO LOCATE AND COORDINATE ALL EXISTING UNDERGROUND FACILITIES.
19. LOCATION OF UNDERGROUND CONDUIT RUNS IS DIAGRAMMATIC ONLY. NEW PIPINGSHALL BE INSTALLED AS NECESSARY TO AVOID INTERFERENCE WITH EXISTINGFACILITIES. COORDINATE INSTALLATION OF ALL UNDERGROUND DUCTBANKS, CONDUITSAND MANHOLES WITH CIVIL ENGINEERING DRAWINGS. CIVIL ENGINEERING DRAWINGSSHALL TAKE PRECEDENCE FOR DUCTBANK LOCATIONS.
20. ALL EXISTING WORK, DAMAGED BY ELECTRICAL CONSTRUCTION OPERATIONS, SHALL BEREPAIRED AND RESTORED TO ORIGINAL CONDITION.
21. COORDINATE WITH OWNER ALL EXISTING LANDSCAPE FEATURES (TREES, SHRUBS, ETC.)NOT WISHED TO BE DISTURBED. TAKE PRECAUTIONS TO AVOID DAMAGES.
22. THE CONTRACTOR MUST COORDINATE ALL ELECTRICAL SITEWORK WITH THE SITEWORKCONSULTANT. REFER TO SITE IMPROVEMENT CIVIL ENGINEERING DRAWINGS FORACTUAL DUCTBANK AND CONDUIT LOCATIONS. COORDINATE ALL UNDERGROUND WORKWITH UTILITY COMPANIES.
23. ELECTRICAL CONTRACTOR SHALL PROVIDE HOUSE KEEPING PAD FOR EXTERIORTRANSFORMER. HOUSE KEEPING PAD SHALL BE IN ADDITION TO CONCRETE FLOOR OFGENERAL CONTRACTOR PROVIDED EXCAVATED TRANSFORMER AREA.
24. ELECTRICAL CONTRACTOR SHALL MAINTAIN AND ENSURE ALL EXISTING LIGHTING ISFUNCTIONAL IN PROJECT BOUNDARY DURING THE CONSTRUCTION PROCESS.
25. REFER TO DRAWING E-202 FOR NOTES REGARDING THE PV ARRAY. ALL PV SYSTEMNOTES ON E-202 APPLY TO THE DUAL AXIS TRACKER SHOWN ON THIS PLAN. REFER TO E-002FOR THE DUAL AXIS TRACKER FOUNDATION DETAIL.
A. A DUCTBANK PARALLELING OTHER UNDERGROUND FACILITIES - 24 INCHES.B. A DUCTBANK CROSSES OVER OR UNDER THE TELEPHONE - 3 INCHES OF CONCRETE OR
12 INCHES OF EARTH.C. A DUCTBANK CROSSES OVER OR UNDER GAS AND WATER MAINS OR SEWERS - 12
INCHES OF EARTH.D. THE MULTIPLE CONDUIT RACKS MUST HAVE BASE AND INTERMEDIATE SPACERS
PLACED APPROXIMATELY EVERY 5 FEET.E. ALL 90 DEGREES BENDS MUST BE RIGID GALVANIZED STEEL CONDUIT.F. ALL RIGID STEEL CONDUITS INSTALLED IN DUCTBANK SHALL HAVE BOTH INSIDE AND
OUTSIDE SURFACES PROTECTED AGAINST CORROSION BY A COATING OF ZINC ORENAMEL.
11. WHERE POSSIBLE, CONDUITS SHALL SLOPE 1/8" PER FOOT FROM EXTERIOR EQUIPMENTTO MANHOLE, OR FROM MANHOLE TO MANHOLE AS DETERMINED BY LANDSCAPEFEATURES.
12. ALL CONDUIT AND CABLES ENTERING INTO AND/OR PASSING THROUGH MANHOLESSHALL BE LABELED WITH THEIR CONDUIT NUMBER, SOURCE AND DESTINATION.
13. PROVIDE A PULLWIRE IN ALL SPARE CONDUITS.14. CONDUIT DUCTBANKS EXTERIOR TO THE BUILDING SHALL BE CONCRETE ENCASED
WITH REBAR AS REQUIRED IN DETAILS.15. CONDUIT DUCTBANKS IN THE INTERIOR OF THE BUILDING BELOW THE FLOOR SLAB
SHALL BE DIRECT BURIAL.16. ALL EXISTING DIMENSIONS AND CONDITIONS MUST BE VERIFIED BY CONTRACTOR AT
THE SITE.17. WHERE EQUIPMENT AND CONDUIT ARE TO BE INSTALLED WITHIN LIMITING CONDITIONS,
IT SHALL BE THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO MODIFY DETAILSOR PROVIDE SPECIAL FITTINGS TO SUIT.
KEY NOTES:
TERMINATE TELECOM DUCTBANK INTO EXISTING COMM MANHOLE MH-10. VERIFYEXISTING MANHOLE LOCATION AND ORIENTATION IN FIELD. PENETRATE MANHOLEUSING EXISTING DUCTBANK WINDOW. COORDINATE ALL WORK IN FIELD WITH OWNER.
STUB-UP TELECOM CONDUITS MINIMUM OF 2" ABOVE FINISHED FLOOR SLAB ANDTERMINATE WITH GROUNDING BUSHING. CAP SPARE CONDUIT.
PROVIDE AN ADD ALTERNATE SCOPE ITEM FOR LIGHTNING PROTECTION SYSTEM ONNEW BUILDING THAT IS INSTALLED IN A CONCEALED FASHION.
DISCONNECT AND REMOVE EXISTING ABANDONED COMMUNICATIONS DUCTBANKBACK TO COMM MANHOLE MH-10. COORDINATE EXACT LOCATION IN FIELD WITHEXISTING CONDITIONS AND OWNER. MAINTAIN MANHOLE OPENING FOR NEWDUCTBANK ENTRANCE.
ELECTRICAL CONTRACTOR TO PROVIDE CONCRETE POLE BASE AND INSTALL THEOWNER SUPPLIED LIGHTS.
1
2
3
4
5
NO. ISSUE DATE: DESCRIPTION
PV STRING HOMERUN LEGEND
G1-3
INVERTER NAME
STRING NUMBER
SCALE: SCALE: SCALE: SCALE: SCALE:
SCALE: SCALE: SCALE: SCALE:
SCALE:
SCALE:
CONDUIT SPACERSSEE SPECIFICATIONS
TOP 1" SHALL BESPRINKLED ANDTHROUGHLYMIXED WITH REDDYE.
7-1/2"MIN.
22"
5"
5" 15-1
/2"
DEPTH ASSPECIFIED
4000PSI CONCRETE
(2) 4" SCH. 40PVC TYPICAL
UNDISTURBED EARTHSEE SPECIFICATIONS
CONDUIT SCHEDULE1- ACTIVE - PRIMARY FEEDER2- SPARE - PULLWIRE ONLY
1 2
5"
5"
FINISHED GRADE
YELLOW LINE MARKER AS SPECIFIED18" BELOW GRADE, ENTIRE WIDTH,OF DUCT BANK - SEE DET. 4/E-002
1
3 4
2
5"M
IN.
7-1/
2"
22"
5"
5"22"
MIN.7-1/2"
5"UNDISTURBED EARTHSEE SPECIFICATIONS
4000PSI CONCRETE
DEPTHASSPECIFIED
FINISHED GRADE
YELLOW LINE MARKER AS SPECIFIED18" BELOW GRADE, ENTIRE WIDTH,OF DUCT BANK - SEE DET. 4/E-002
TOP 1" SHALL BE SPRINKLED ANDTHROUGHLY MIXED WITH RED DYE
CONDUIT SPACERSSEE SPECIFICATIONS
(4) 4" SCH. 40PVC TYPICAL
CONDUIT SCHEDULE1- SPARE, PULLWIRE ONLY2- SPARE, PULLWIRE ONLY
3- ACTIVE - SECONDARY FEEDER4- ACTIVE - SECONDARY FEEDER
CONDUIT SPACERSSEE SPECIFICATIONS
TOP 1" SHALL BESPRINKLED ANDTHROUGHLYMIXED WITH REDDYE.
7-1/2"MIN.
22"
5"
5" 15-1
/2"
DEPTH ASSPECIFIED
4000PSI CONCRETE
(2) 4" SCH. 40PVC TYPICAL
UNDISTURBED EARTHSEE SPECIFICATIONS
CONDUIT SCHEDULE1- ACTIVE - OSP OPTICAL FIBER2- SPARE - PULLWIRE ONLY3- 1"C. - ACTIVE - #6 AWG. INSULATED COPPER FOR DETECTION
1 2
5"
5"
FINISHED GRADE
YELLOW LINE MARKER AS SPECIFIED18" BELOW GRADE, ENTIRE WIDTH,OF DUCT BANK - SEE DET. 4/E-002
3
ZIG-
ZAG
5'-0"
MAX
.
SEE DUCTBANK DETAIL FORACTUAL DEPTH AND WIDTH
ZIG-ZAG YELLOW WARNINGTAPE OVER CONDUITDUCTBANK FOR IT'S ENTIRELENGTHREFER TO SITE PLAN
SIDES OF TRENCH
1. PROVIDE A MINIMUM OF 36" OF CRUSHED GRAVEL AROUND ENTIRE PAD AT 8" IN DEPTH. REFER TO MANUFACTURER FOR OIL CAPACITY TO DETERMINE VOLUME OF GRAVEL BED.
2. DEPTH WILL VARY FOR CONDUIT PENETRATION. MINIMUM DEPTH SHALL BE 36". INCREASE DEPTH FOR CONDUIT PENETRATIONS.
3. REFER TO DETAILS 6 AND 7 ON THIS SHEET.
NOTES:
LOWEST CONDUIT
CRUSHEDGRAVEL
#4 AT 12 EA. WAYEA. FACE
#4 AT 12 TOP & BOT.EA. WAY
4000 P.S.I. CONCRETE
ANCHOR BOLTS PER MANUFACTURER'SREQUIREMENTS.
EDGE OF TRANSFORMER
6"M
IN.
2"10"
CLR3"
10"
GRADE6"M
IN
EXTENDBELOW FROSTLINE OR 36"MIN.
4"
6" X 6" - #8/#8 W.W.F.
A
C
6" WIDE CURBWITH 1" DIAMETER PVC WEEPS
OPENING TOSTRUCTURAL PAD
SECONDARYCONDUITS/DUCTBANKFRONT ELEVATION
PLAN
1#4 CONT. IN CURB
WEEPS (TYP.)
SECTION
SEE NOTE 8
WEEPS (TYP.)PRIMARYCONDUITS/DUCTBANK
STRUCTURAL PADSEE DETAIL X/E6.X
NOTE 2
MIN
.6" 1"
CLR
9 NOTE 1
3
REINFORCING BARS3" CLEAR
NOTES:
SIDE ELEVATIONB
5
6
4
7
5 USE 4000 PSI MINIMUM CONCRETE STRENGTH.
3 SECONDARY CONDUITS SHALL TERMINATE NO LESS THAN 1" ABOVE HOUSEKEEPING PAD.
2. SIZE OF HOUSEKEEPING DRAINAGE PAD TO BE PER MANUFACTURER'S RECOMMENDATIONS.
1. SEE EXTERIOR OIL FILLED TRANSFORMER PAD DETAIL. OTHERWISE USE 6" MIN. (TYP.)
8 PROVIDE 4" LONG, 2 X 2 MIN. ZEE SHAPE OF #10 GAUGE GALVANIZED SHEET STEEL FOR EACH WEEP AND FASTEN TO STRUCTURAL PAD WITH 1/2" STAINLESS STEEL HILTI QUICK BOLTS.
7 FASTEN TRANSFORMER TO PAD PER MANUFACTURER'S RECOMMENDATIONS.
6 STRUCTURAL PAD SHALL BE CONSTRUCTED
WITH NO OPENINGS, EXCEPT F0R CDTS,
GROUND ROD ACCESSWELL (TYP. FOR 3) SEEDETAIL X
3/4" X 10'-0" LONG COPPERGROUND ROD. (TYP. FOR 3)
#2/0 BARE, STRANDEDCOPPER CABLE
10'- 0" ALL SIDES
LL
L
(4) 1/2" x 15" HOT DIP GALVANIZEDSTEEL ANCHOR BOLTS ON A Ø8.91"BOLT CIRCLE AT 90°
N.T.S.1 PRIMARY ELECTRICAL DUCTBANK E-1N.T.S.2 SECONDARY ELECTRICAL DUCTBANK E-2
N.T.S.3 TELECOM DUCTBANK T-1N.T.S.5 EXTERIOR OIL FILLED TRANSFORMER PAD
N.T.S.6 PADMOUNT DRAINAGE PADN.T.S.7 PADMOUNT DRAINAGE PAD
N.T.S.8 EXTERIOR GROUND ROD CONFIGURATIONN.T.S.9 CONDUIT SERVICE ENTRANCE
N.T.S.11 BOLT DIAGRAM FOR Z1 FIXTURE
N.T.S.12 HANOVER LANTERN POLE BASE
N.T.S.10 PV TRACKER FOUNDATION
4 UNDERGROUND DUCTBANK MARKERNTS
4" [RIGID STEEL][SCHEDULE 80PVC] CONDUIT. 48"RADIUS MINIMUM.
REFER TO MFR. SHOPDRAWINGS FOREXACT LOCATION.
CONDUIT COUPLING ORTRANSITION FITTING AS REQUIRED
CRUSHED STONE
FINISHEDFLOOR SLAB
CONCRETEPAD SEEDETAIL
FINISHED INSTALLATIONOF CONDUIT STUB UPINCLUDING BUSHINGSHALL NOT EXCEED 3"ABOVE FINISHEDCONCRETE
[SWITCHGEAR][SUBSTATION] ENCLOSURE, SEE FLOOR PLANS AND DETAILS
4 PROVIDE EPOXY BONDING COMPOUND WHERE HOUSEKEEPING PAD BEARS ON STRUCTURAL PAD.
HOUSEKEEPINGDRAINAGE PADSEE PLAN C
FRONT OFFIXTURE
BOLT CIRCLE � 8.91"
.8"
2.50" OPENFOR CONDUIT
PLATE 11"
15"
2" EXPOSEDTHREAD
APROX. 3/4" GAP:FILL WITH GROUT
LEVELINGWASHERSAND NUTS
CONDUIT(BY OTHERS)
MOUNTING DETAIL
HANOVER LANTERN POLEBY OWNER
ANCHOR BOLTS, NO. AND SIZEAS REQUIRED BY POLE MANUF.
16" X 16" SQUARE FIELDFORMED CONCRETE BASETO 6" BELOW GRADE.REMAINDER OF BASE TOBE 18" DIAMETER
PROVIDE ANCHORBOLTS AS REQUIRED BYPOLE MANUFACTURER
FINISHED GRADE OR PAVING
#4 HOOP @ 12"O.C. SPACING
SCH. 40 PVC CONDUIT WITHCIRCUIT WIRING (SIZE ANDQUANTITY PER PLAN). TRANSITIONTO RIGID GALVANIZED STEELCONDUIT 5'-0" BEFORE POLEAND FOR STUB UP INTO POLE
3000# CONCRETE
3" MIN. CLEARALL SIDES
3'0"
24"M
IN.
1" X 45°CHAMFERALL SIDES
6"
ANCHOR POLE TOCONCRETE BASE ASREQUIRED BY POLEMANUFACTURER
6 #5 VERTICALREINFORCINGBARS
SCALE:
9 PRIMARY CONDUITS SHALL TERMINATE NO MORE THAN 1" ABOVE STRUCTURAL PAD.
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
E-002G150004-000
ELECTRICAL SITE DETAILS
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION
ST
B115
B1INV#2
B1INV#5
B115
B115
B115
B115
B1INV#2
B115
B1INV#5
B115
B115
B115
B1INV#5
B115
B115
W4INV#3
X1
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
B115
B115
B115
EMNL
EMNL
EM
EM
EM
B115
EM
ECU INV#5 ECU INV#3
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
E-100G150004-000
ELECTRICAL LOWER LEVELPLAN - LIGHTING
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN
DRAWING NOTES:
1. REFER TO E-400 FOR THE LIGHTING FIXTURE SCHEDULE AND LIGHTING CONTROLS SCHEDULE.2. ALL LIGHTS SHALL BE CIRCUITED TO PANEL LP UNLESS OTHERWISE NOTED.3. ALL SWITCHES SHALL BE GRAY WITH STAINLESS STEEL FACE PLATES UNLESS OTHERWISE
NOTED.4. ALL EMERGENCY FIXTURES SHALL BE CONNECTED TO CENTRAL BATTERY INVERTER.5. PROVIDE EMERGENCY CONTROL UNITS SUCH AS WATTSTOPPER ELCU-200 OR BODINE BLCD-20B
ON ALL FIXTURES ON EMERGENCY POWER. THESE FIXUTRES SHALL BE WIRED SO THAT THEYARE CONTROLLED WITH ADJACENT FIXTURES WITHOUT SWITCHING TO THE INVERTER. UPONLOSS OF POWER ALL EMERENCY LIGHT FIXTURES SHALL COME TO FULL ON REGARDLESS OFLIGHTING CONTROL SWITCH POSITION.
6. ALL EXIT SIGNS AND NIGHT LIGHTS SHALL BE CIRCUITED AS UNSWITCHED.
NO. ISSUE DATE: DESCRIPTION
SD
ST ST ST
VS VS VS
VS
VSVS
VS VS
VS
VS
VS
VS
VS VS
OS
OS
S OS
S OS
OSOS
OS
OS
OS
OS OS OS OS
OS
OS
OS OS OS OS OS OS
OS
OS OS OS OS OS OS
OS
OS
SDSD
SDSD
SD
SD SDSDSD
SD SD SD
SD
SD
STST
S T
SD
SD
SDaSDb
SDa SDb
OS
OSOS
OS OS
OS
OS
OS
OS
SOR
SD
SD
SOR
SDS
KP
SDa
SDa SDb
SDb
OS
OS
VSPC PC PC
PC
PC PCPC
PCPC
PC PCPC PC
PC
PC
PC
PC
VS PC
OSVS
SKP
SDc
SDc
S D
VS
S DSD
DRAWING NOTES:
1. REFER TO E-400 FOR THE LIGHTING FIXTURE SCHEDULE AND LIGHTING CONTROLS SCHEDULE.2. ALL SWITCHES SHALL BE GRAY WITH STAINLESS STEEL FACE PLATES UNLESS OTHERWISE NOTED.3. ALL CONDUIT RUNS IN EXPOSED CEILING AREAS SHALL BE MINIMAL AND SHALL RUN IN CLEAN LINES
AND WILL BE OF HIGH WORKMANSHIP QUALITY. CONCEAL CONDUIT RUNS WHERE POSSIBLE.CONDUIT ALONG THE WALLS/CEILING WHERE APPROPRIATE. FINISH OF SURFACE MOUNTEDCONDUIT SHALL MATCH WALL OR CEILING COLOR OF SPACE.
4. ALL LIGHTS SHALL BE CIRCUITED TO PANEL LP UNLESS OTHERWISE NOTED.5. ALL WIRING DONE IN LOBBY AREA SHALL BE CONCEALED BEHIND CURTAIN WALL FRAMING.6. ALL LOBBY PENDANTS, P1, SHALL BE MOUNTED AT 15'-0'' AFF.7. ALL EMERGENCY FIXTURES SHALL BE CONNECTED TO CENTRAL BATTERY INVERTER8. PROVIDE EMERGENCY CONTROL UNITS SUCH AS WATTSTOPPER ELCU-200 OR BODINE BLCD -20B ON
ALL FIXTURES ON EMERGENCY POWER. THESE FIXUTRES SHALL BE WIRED SO THAT THEY ARECONTROLLED WITH ADJACENT FIXTURES WITHOUT SWITCHING TO THE INVERTER. UPON LOSS OFPOWER ALL EMERENCY LIGHT FIXTURES SHALL COME TO FULL ON REGARDLESS OF LIGHTINGCONTROL SWITCH POSITION.
9. ALL EXIT SIGNS AND NIGHT LIGHTS SHALL BE CIRCUITED AS UNSWITCHED.
KEY NOTES:
PROVIDE AND INSTALL ROOM CONTROLLERS LMRC-211 AND LMBC-300 ABOVE CEILINGS.REFER TO WIRING DIAGRAM ON E-400 FOR MORE INFORMATION.
PROVIDE AND INSTALL ROOM CONTROLLERS LMRC-211, LMRC-213, AND LMBC-300 ABOVECEILIGNS. REFER TO WIRING DIAGRAM ON E-400 FOR MORE INFORMATION.
PROVIDE AND INSTALL ROOM CONTROLLERS LMRC-212 AND LMBC-300 ABOVE CEILINGS. REFERTO WIRING DIAGRAM ON E-400 FOR MORE INFORMATION.
PROVIDE 2 GANG BOX FOR SWICHES AT THIS LOCATION.
PROVIDE 3 GANG BOX FOR SWITCHES AT THIS LOCATION. ALIGN SWITCHES UNDERNEATHOCCUPANCY SENSOR.
FIXTURE SHALL CONTINUE THE WHOLE LENGTH OF THE MULLION AND MOUNTED AT 16'-0'' AFF.
LOCATE ALL P1 REMOTE DRIVERS ABOVE EPIC DECK CEILING.
MOUNT EXIT SIGNS ABOVE GLASS TRANSOM AT 10'-0'' ON WALL.
MOUNT EXIT SIGN ABOVE DOOR, 11'-0'' AFF.
MOUNT EXIT SIGNS ABOVE GLASS TRANSOM AT 9'-0'' ON WALL.
MOUNT EXIT SIGN BETWEEN WOOD SLOT CEILING AT 9'-0''. COORDINATION WITH WOOD SLOTCEILING SHALL BE DONE IN FIELD.
OVERRIDE SWITCHES SHALL CONTROL CORRIDOR LIGHTING ONLY.
PROVIDE 4 FOOT EMERGENCY SECTION IN LIGHTING FIXTURE.
PROVIDE AND INSTALL ROOM CONTROLLERS LRMC-213 AND LMBC-300, ABOVE CEILING, FORALL CORRIDOR LIGHTING CIRCUITS. REFER TO WIRING DIAGRAM ON E-400 FOR MORE
INFORMATION.
PROVIDE AND INSTALL ROOM CONTROLLERS LMRC-212 AND LMBC-300FOR ALL EXTERIORLIGHTING CIRCUITS. REFER TO WIRING DIAGRAM ON E-400 FOR MORE INFORMATION.
PROVIDE AND INSTALL A WATTSTOPPER SEGMENT MANAGER LMSM-3E LOCATED INENCLOSURE LMSM-ENC1. PROVIDE AND INSTALL LMSM-CONNECT ON SEGMENT MANAGER.
PROVIDE AND INSTALL TWO (2) ROOM CONTROLLERS LMRC-213 AND LMBC-300, ABOVE EPICDECK, FOR ALL LOBBY LIGHTING CIRCUITS . REFER TO WIRING DIAGRAM ON E-400 FOR MOREINFORMATION.
BOXED IN AREA SHALL BE CONTROLLED BY PHOTOCELLS, OCCUPANCY SENSORS, ANDDIMMING SWITCHES LOCATED IN AREA.
A1INV#5
B1INV#5
B1INV#5
B111
A14
A14 A1
4
A16
A16
A16
A16
A16
A11
A11
A13
A13
A11
A13
A13
A13
A13
A13
A11
A1A5
A1A5
A1A2
A1A2
A1A2
A1A2
A1A2
A1A2
A18
A1INV#2
A18
D1INV#2
D1INV#2
D18
D1INV#5
D1INV#2
D1INV#2D1
INV#2
D16
D16
D16
A16A1
11
A111
P112
P112
P112
A1A5
D1INV#5
D1INV#2
D113
A211
A211
A2INV#5
X1
X1B
X1B
X1A
X1
X1
D113
D113
A14
A14
A1A5
A17
A1A2
A1INV#1
A1A2
A16
A1A5
A1A5
A18
A1A5
A1INV#1
A1A5
A18D1
8D1INV#1
D18
D1INV#2
D1INV#1
D18
D18
D1INV#1
D18
D1INV#2
A17
A17
W116
W119
W114
W114
A17
A17
D12
D110
P110
P1INV#2
P117
P117
P117
P117
P117
P117
P117
P1INV#2
P2INV#7
P212P2
INV#7
P2INV#7
P212P2
INV#7
D113
A16
A1INV#1
A1INV#1
A16
EM NL
EM NL EM NL
EM NL
EM NL
EM NL
EM NL
EM NL
a
a
a b
aa
a
aa
a
bc
c A18
A18
A16
A18
A16
A18
1
1
1
1
11
111
1 11 1
11 1
1 1
1
1
3
A16
A16
NL
EMNL
NL
INV#6EM
EM NL
EM NL
18
18 18
2
5
5
4
4
W3INV#3
A311
A311
W119
W119
6
6
LV
LV
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
VEST.V-1
ALCOVEL101-5
WOMEN'S143
PASSAGE104
MEN'S142
ALCOVEL101-6JANITOR
141
MECHANICAL141.1
FAMILYTOILET
144
STORAGE140.1
PASSAGEL101-7
VEST.V-2
CLASSROOM/PRESENTATIONROOM
140
V.P. OFFICE112A
SMALL CONF.105
STORAGE103.1
OFFICE112
PASSAGEL101-1
OFFICE118
OFFICE114
OFFICE116
OFFICE110
OFFICE108
OFFICE104
CORRIDORC 1-1
CORRIDORC 1-2
BREAK ROOM107
STORAGE119
ELEC. RM.121
COFFEESTATIONL101-3
STORAGE103.2
ADMISSIONSOPEN OFFICE
106
HOUSINGOPEN OFFICE
130
OFFICE128
OFFICE126
OFFICE124
OFFICE122
MARKETINGOPEN OFFICE
120
SMALL CONF.115
CONFERENCE117
I.T. ROOM123
CALL CENTER109
CORRIDORC 1-3
OFFICE102
WORK ROOM111
RESOURCEROOM
103
RECEPT.L101-2
STUDENTWORK SPACE
113
LOBBYL101
8
8
9
X1A9
10
11
11
6
6
W2INV#3
W2INV#4
W116
12
12
A111
LP
LCP
aP212
P212a
EM
EM
EM
EM EM EM
EMEMEMEM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
INV#7EM
EM
17
17
17INV#6EM13
13
INV#7EM
INV#7EM
13
14
15
15
ECU INV#4
ECU INV#7
ECU INV#5
ECU INV#1
ECU INV#7
1
1
P2A8
P2A8
P2A8
P2A8
P2A8
1
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
E-101G150004-000
ELECTRICAL GROUNDFLOOR PLAN - LIGHTING
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
NO. ISSUE DATE: DESCRIPTION
18
WP
J
W
WP
TS
TS
TS
TS
TS
TS
FS
F
MDP
RP2#4
PVP
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
HP2#2,4
HP2#10,12HP2#6,8
HP2#1,3
GYLOCL SKID
HP2#5
MDP
MDP
HP2#20,22
ACCU-1
EF-1HP2#7
HP2#17EF-2
400APV UTILITYDISCONNECT
TVSS FOR PVP
PV NET METER
P-1
P-2
1
1
1
RP2#23
RP2#23
RP2#23 RP2#23
RP2#4
UTILITY METER
MEP SHAFT
PROVIDE J-BOXFOR FLOODCONTROLVALVE HP2#21
HP2#23HP2#28
BAS CONTROL PANELS
HP2#30,32
P-4HP2#9
P-3HP2#16
GROUND BUS BAR
HP-19
HP-20 HP-21
HP-22 HP-23
HP-23MDP
HP2
2 - 2 INCH CONDUITSTO ELECTRICALROOM
2 - 2 INCH CONDUITSTO ELECTRICALROOM
FEEDER METERS
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
E-200G150004-000
ELECTRICAL LOWER LEVELPLAN - POWER
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN
DRAWING NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OFRECEPTACLES, DISPLAYS, AND FIRE ALARM DEVICES IN ALL SPECIALITY AREAS.
2. REFER TO E-000 FOR COMPLETE SYMBOLS LIST AND GENERAL NOTES.3. REFER TO E-300 FOR SINGLE LINE DIAGRAM.4. REFER TO E-401 FOR ELECTRICAL PANEL SCHEDULES.5. ALL RECEPTACLES SHALL BE GRAY WITH STAINLESS STEEL FACE PLATES UNLESS OTHERWISE
NOTED.6. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER CONNECTIONS TO ALL
MECHANICAL EQUIPMENT. REFER TO MECHANICAL DRAWINGS FOR ADDITONAL MECHANICALEQUIPMENT INFORMATION.
7. PROVIDE COMPLETE FIRE ALARM SYSTEM WITH BATTERY BACKUP FOR EMERGENCY POWER.
1
KEY NOTES:
PROVIDE DISCONNECT IN WATERPROOF ENCLOSURE.
NO. ISSUE DATE: DESCRIPTION
15cd
15cd
15cd
30cd 30cd 30cd 30cd
15cd
15cd
60cd60cd30cd
15cd30cd
60cd
60cd
15cd
30cd
15cd
135cd
F
J J
J
J
JJ
J
J
F
15cd
30cd
30cd30cd 15cd
WP
WP
WP
J
J
J
J
J
J
S
SS
S
S
S
S
S
S
S
S
S
S
S
S SS
SS
J
J
J
J
15cd
15cd
30cd
F
J
J
J
J
J
J
J
J
J
W
W
J
J
15cd
15cd
15cd
15cd
J
J
JJ
JJJ
J
J
J
J
J
J
J
J
J
J
15cd
HH
H
H
H
H
HHHH
15cd
15cd
HH
DRAWING NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OFRECEPTACLES, DISPLAYS, AND FIRE ALARM DEVICES IN ALL SPECIALITY AREAS.
2. REFER TO E-000 FOR COMPLETE SYMBOLS LIST AND GENERAL NOTES.3. REFER TO E-300 FOR SINGLE LINE DIAGRAM.4. REFER TO E-401 FOR ELECTRICAL PANEL SCHEDULES.5. ALL RECEPTACLES SHALL BE GRAY WITH STAINLESS STEEL FACE PLATES UNLESS OTHERWISE
NOTED.6. ALL CONDUIT RUNS IN EXPOSED CEILING AREAS SHALL BE MINIMAL AND SHALL RUN IN CLEAN LINES
AND WILL BE OF HIGH WORKMANSHIP QUALITY. CONCEAL CONDUIT RUNS WHERE POSSIBLE.CONDUIT ALONG THE WALLS/CEILING WHERE APPROPRIATE. FINISH OF SURFACE MOUNTEDCONDUIT SHALL MATCH WALL OR CEILING COLOR OF SPACE.
7. ALL CABLING SHALL SHALL BE DONE IN CORRDIOR ON J-HOOKS ALONG THE INTERIOR WALL OFTHE OPEN OFFICE AREA, ABOVE THE CEILING.
8. ALL WIRING DONE IN LOBBY AREA SHALL BE CONCEALED BEHIND CURTAIN WALL FRAMING.9. PROVIDE BRANCH CIRCUIT METERING FOR ALL BRANCH CIRCUITS IN PANELS MDP, RP1, RP2, LP,
HP1, AND HP2. PROVIDE NETWORK CONNECTION FROM BRANCH CIRCUIT METERS TO CAMPUSMETERING COMPUTER FOR REMOTE MONITORING OF LOADS. ALL METERING SHALL BEMILLERSVILLE CAMPUS STANDARD SMART METERING FROM E-MON D-MON.
10. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER CONNECTIONS TO ALLMECHANICAL EQUIPMENT. REFER TO MECHANICAL DRAWINGS FOR ADDITONAL MECHANICALEQUIPMENT INFORMATION.
11. PROVIDE COMPLETE FIRE ALARM SYSTEM WITH BATTERY BACKUP FOR EMERGENCY POWER.12. PROVIDE DEDICATED 1" CONDUIT BETWEEN FIRE ALARM SYSTEM CONTROL PANEL AND THE IDF
ROOM FOR NETWORK CONNECTIVITY TO THE CAMPUS FIRE ALARM SYSTEM.13. ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT TO ANY SPEAKERS INDICATED ON THE
DRAWINGS AND TERMINATE AT STORAGE ROOM 140.1. CONFIRM WITH OWNER FINAL TERMINATIONOF CONDUIT AND SPECIFIC POWER REQUIREMENTS.
14. ELECTRICAL CONTRACTOR SHALL PROVIDE POWER TO ALL PROJECTORS AND BACKBOXES FORANY IT/AV NEEDED.
15. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER AND CONTROL WIRINGASSOCIATED WITH MECHANICAL SHADES.
16. ALL CONDUIT ABOVE WOOD SLAT CEILING SHALL BE PAINTED WHITE. COORDINATE FINAL PAINTINGDETAILS WITH ARCHITECT.
17. ELECTRICAL CONTRACTOR SHALL PURCHASE TV MOUNT BACK BOX, PAC525, AND INSTALL ALLNECESSARY POWER CONNECTIONS TO TELEVISION.
18. POWER AND DATA DEVICES SHOWN ON OFFICE FURNITURE ARE DIAGRAMMATIC. FINAL LOCATIONSAND REQUIREMENTS SHALL BE PROVIDED BY FURNITURE VENDOR. COORDINATE WITH FURNITUREVENDOR EXACT DATA AND POWER REQUIREMENTS REQUIRED FOR OFFICE FURNITURE.ELECTRICAL CONTRACTOR SHALL CONNECT TO FURNITURE WHIP TO OWNER PROVIDED PRE-WIRED FURNITURE.
19. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL BACK BOXES, FLOOR BOXES, AND CONDUITSTO DATA DEVICES. CABLING WILL BE PROVIDED BY OTHERS.
20. ALL DISCONNECTS FOR HEATPUMPS AND VAV UNITS SHALL BE MOUNETED ON OR ADJACENT TOUNITS AND SHALL BE CONCEALED ABOVE CEILING.
KEY NOTES:
WIREWAY SHALL BE SIMILAR TO LEGRAND AL2400. WIREWAY SHALL BE INSTALLED AT BASEOF CURTAIN WALL. SEE ARCHITECTURAL DRAWINGS FOR MOUNTING DETAILS. CONFIRMFINISH OR WIREWAY WITH ARCHITECT.
UNDERSLAB CONDUIT PATHWAY TO OPEN OFFICE FURNITURE. PROVIDE THREE (3) 3/4 INCHCONUDITS.
PROVIDE CAT 6 PATH FROM DEVICE BACK TO MDF ROOM. PROVIDE PULL WIRES IN ALL OFTHESE CONDUITS.
LOCATE DEVICES WITHIN RECEPTION DESK. REFER TO ARCHITECTURAL DRAWINGS FOREXACT LOCATION.
PROVIDE HAND DRYER XLERATOR FROM EXCEL, MODEL NUMBER XL-*-ECO. CONFIRM COLOROF HAND DRYER WITH ARCHITECT.
RP1
LPHP1
+
+
+
+
+
FOR TV
FOR TVLCP
FLOOR BOX FOR FURNITURE WHIP
FLOOR BOXFOR FURNITURE WHIP
FOR FURNITURE WHIP
FACP
FAP
FOR FURNITUREWHIP
FLOOR BOX -POWER ANDDATA
FLOOR BOX -POWER ANDDATA
RP2
RP1#28
RP1#28RP1#28
RP1#17
RP1#17
RP1#17
RP1#33
RP1#33
RP1#33
RP1#16
RP1#16
RP1#31
RP1#36
RP1#36
RP1#36
RP1#36
RP1#19 RP1#19 RP1#38 RP1#38
RP1#39
RP1#8
RP1#8
RP1#8
RP1#15
RP1#15RP1#15
RP2#13
RP2#18
RP1#23
RP1#40 RP1#39
RP2#31
RP2#31
RP1#27
RP1#27
RP1#27
RP1#1
RP1#1
RP1#1
RP1#5
RP1#5
RP1#5
RP1#24
RP1#24 RP1#24
RP1#14 RP1#14RP1#14
RP1#26RP1#25
RP1#31
RP1#16
RP1#22
RP1#22
RP1#6
RP1#6
RP1#11
RP2#18
RP2#22
RP2#18
RP2#18
RP2#15
RP1#14
RP2#8
RP1#35
RP1#35
RP1#27
RP1#34
RP1#30
RP1#18
RP1#7
RP1#7RP1#9
RP1#10 RP1#10
RP1#12 RP1#13RP1#10RP1#9
RP1#12
RP1#12 RP1#13RP1#7
RP1#21 RP1#21
RP1#9
RP2#25
RP2#7
RP2#7
RP2#13
RP2#18
RP2#20
RP2#20
RP2#20
RP1#35
RP1#18
RP1#18
RP1#38
RP1#25
RP1#27
RP1#26
RP1#24
RP1#40
RP1#23
RP1#21
RP1#28RP1#3
RP1#2
RP1#11RP1#4
RP1#32
RP2#28
RP2#34
RP2#21
RP1#29
RP1#20
RP2#1
RP2#2
RP2#3
FOR REF.
FOR DISHWASHER
FOR REF.
BOTTLEFILLER
+
EWH-1-2
EWH-1-1
RP2#15RP1#16
+
RP1#31
RP1#31
RP1#31
RP1#31
RP1#37
RP1#37
RP1#37
RP1#37
RP1#37
RP1#37
RP2#36
RP1#39 RP1#22
RP1#40RP1#23
RP2#6
RP2#10
RP2#10
RP2#12+
+
HP-5
HP-4
HP-3
HP-2
HP-1
HP-8
HP-7HP-6
HP-10
HP-11
HP-9
HP-12
HP-14
HP-13
HP-15
HP-16
HP-17
HP-18
RP1#19
HP1#30,32
HP1#37,39
HP1#38,40
HP1#34,36
HP1#33,35
HP1#17,19
HP1#10,12
HP1#9,11HP1#6,8
HP1#5,7
HP1#13,15
HP1#2,4HP1#1,3
HP1#14,16
HP1#21,23
HP1#22,24
HP1#25,27
HP1#18,20
HP1#26
HP1#28
RP2#22
HP2#14 HP2#14
HP2#14
HP2#14
HP2#14
HP2#14
HP2#14
HP1#29
HP1#29
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
VEST.V-1
ALCOVEL101-5
WOMEN'S143
PASSAGE104
MEN'S142
ALCOVEL101-6JANITOR
141
MECHANICAL141.1
FAMILYTOILET144
STORAGE140.1
PASSAGEL101-7
VEST.V-2
CLASSROOM/PRESENTATIONROOM140
V.P. OFFICE112A
SMALL CONF.105
STORAGE103.1
OFFICE112
PASSAGEL101-1
OFFICE118
OFFICE114
OFFICE116
OFFICE110
OFFICE108
OFFICE104
CORRIDORC 1-1
CORRIDORC 1-2
BREAK ROOM107
STORAGE119
ELEC. RM.121
COFFEESTATIONL101-3
STORAGE103.2
ADMISSIONSOPEN OFFICE
106
HOUSINGOPEN OFFICE
130
OFFICE128
OFFICE126
OFFICE124
OFFICE122
MARKETINGOPEN OFFICE
120
SMALL CONF.115
CONFERENCE117
I.T. ROOM123
CALL CENTER109
CORRIDORC 1-3
OFFICE102
WORK ROOM111
RESOURCEROOM103
RECEPT.L101-2
STUDENTWORK SPACE
113
LOBBYL101
RP2#22
RP2#10
RP2#10
1
1
STACKDEVICESON WALL
ADA DOOROPERATOR
ADA DOOROPERATOR
VAVB-7
VAVB-8
VAVB-9
VAVB-10
VAVB-11
VAVB-6
VAVB-5
VAVB-3
VAVB-2VAVB-1
POWER FORADA DOOROPERATOR
POWER FORADA DOOROPERATOR
POWER FOR OWNER PROVIDEDSIGN. TERMINATE CIRCUIT ATFOUNDATION WALL. REFER TODETAIL 2/A1.02 FORTERMINATION DETAIL.
LP#18
RP2#16
RP2#11
HAND DRYERS
HANDDRYER
RP2#12+
+
FORDASHBOARD
VAVB-4
HP1#29HP1#29
TF-1
HP1#31
HP2#15BR-1
HP2#15BR-1
HP2#18BR-1
HP2#18BR-1
AC-1
HP2#11,13
CEILINGMOUNTEDPROJECTOR
CEILING MOUNTPROJECTOR
RP2#20
FLOOR BOX -POWER ANDDATA
RP2#24
RP2#24
FORMOTORIZEDSHADES
FORMOTORIZEDSHADES HP2#19
HP2#26
MOTORIZEDSHADESCONTROLLER
2 2
RP2#22
RP2#22
RP2#24
RP2#24
VAV-1
HP1#29
RP2#27
RP2#26
RP2#29
+
+FORMONITOR
RP2#30
3
3
3
INV
+
FORMICROWAVE
+RP2#19
+
RP2#32RP2#14
RP2#9
HP2#25,27
BACK BOX FORCARD READER
BACK BOX FORCARD READER
BACK BOX FORCARD READER
BACK BOX FORCARD READER
BACK BOX FORCARD READER
AC-2
BACK BOXFOR CARDREADER
HAND DRYERS
RP1#35
RP2#33
KNOX BOXFIRE ALARMCONNECTION.
+
+
RP2#12
RP2#12
+
+
BACK BOX FORCARD READER
BACK BOX FORCARD READER
FLOOR BOXFOR FURNITURE WHIP
FLOOR BOXFOR FURNITURE WHIP
FLOOR BOXFOR FURNITURE WHIP
FLOOR BOXFOR FURNITURE WHIP
POWER FORFAUCETS
POWER FORFAUCETS
RP2#17
POWER FORFAUCETS
RP2#25
TV
4
5
5
DOOR POWER
DOOR POWER
DOOR POWER
DOOR POWER
HP2#29
HP2#29
HP2#31
HP2#31
HP2#29
HP2#29
HP2#29
HP2#31
HP2#31
DOOR POWER
DOOR POWER
DOOR POWER
TV
+
+RP1#22
INCOMING 4"CONDUIT
02'
4'
6'
08'
16'
24'
06"
9"
3"
01'
6"
1-6"
01/2'
1'
2'
01'
2'
3'
01'
2'
4'
02'
4'
8'
4'
08'
16'
08'
16'
32'
SHEET NUMBER
SFA PROJECT NUMBER
FULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCALE: 1/16" = 1'-0"
SCALE: 1/8" = 1'-0"
SCALE: 1/4" = 1'-0"
SCALE: 1/2" = 1'-0"
SCALE: 3/4" = 1'-0"
SCALE: 1" = 1'-0"
SCALE: 1 1/2" = 1'-0"
SCALE: 3" = 1'-0"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCALE: 3/32" = 1'-0"
SCALE: 3/8" = 1'-0"
PROJECT No: MI-1105
C:\Revit Local Files\G150004-000 - M
illersville -
MEP15_Central_skaplan.rvt
E-201G150004-000
ELECTRICAL GROUNDFLOOR PLAN - POWER
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1
GROUND FLOOR PLAN
1
2
3
NO. ISSUE DATE: DESCRIPTION
4
5
ALL PV PANELS ON THIS ROOF SHALL BE BASIS OF DESIGN TYPE SPR-E20-327 SUNPOWER CORP. PANELS MOUNTED ON BASIS OF DESIGNRACKING SYSTEM TYPE HELIX DT - EAST/WEST 10 DEGREE TILT BYSUNPOWER COPR. PANELS SHALL BE STRUNG AS INDICATED BYCIRCUITING AND HOME RUNS.
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
INV.E7
E4-6E7-1
E5-2E1-2
ALL PV PANELS ON THIS ROOF SHALL BE BASIS OF DESIGN TYPESPR-E20-327 SUNPOWER CORP. PANELS MOUNTED ON BASIS OFDESIGN RACKING SYSTEM TYPE HELIX DT - EAST/WEST 10 DEGREETILT BY SUNPOWER COPR. PANELS SHALL BE STRUNG ASINDICATED BY CIRCUITING AND HOME RUNS.
ALL PV PANELS ON THE ROOF SHALL BE BASIS OF DESIGN TYPESPR-X21-345 SUNPOWER CORP. PANELS MOUNTED ON BASIS OFDESIGN STANDING METAL SEAM ROOF CLAMP SYSTEM. PANELSSHALL BE STRUNG AS INDICATED BY CIRCUITING AND HOME RUNS.
FACADE MOUNTED BIPV: GLASS PANELS AT TOP AND BOTTOM OFCUTRAIN WALL SHALL HAVE GLASS INTEGRATED SOLAR CELLS. BASISOF DESIGN SYSTEM BY ONYX GLASS. MOUNTING SHALL BE ASINDICATED ON ARCHITECTURAL PLANS. PANELS SHALL BE STRUNG ASINDICATED BY CIRCUITING AND HOME RUNS. PANELS SHALL CONNECTTO DESIGNATED COMBINER BOX OR OTHER SIMILAR FUSED DC POWERCOMINATION METHOD. REFER TO 3/E202 FOR ELEVATION. (NOTINCLUDED IN BASE BID #3)
FACADE MOUNTED BIPV: GLASS PANELS AT TOP AND BOTTOM OFCUTRAIN WALL SHALL HAVE GLASS INTEGRATED SOLAR CELLS. BASISOF DESIGN SYSTEM BY ONYX GLASS. MOUNTING SHALL BE ASINDICATED ON ARCHITECTURAL PLANS. PANELS SHALL BE STRUNG ASINDICATED BY CIRCUITING AND HOME RUNS. PANELS SHALL CONNECTTO DESIGNATED COMBINER BOX OR OTHER SIMILAR FUSED DC POWERCOMINATION METHOD. REFER TO 3/E202 FOR ELEVATION. (NOTINCLUDED IN BASE BID #3)
E7-2 E4-5
E7-4 E4-2
INV.E3
INV.E4
E8-1
E3-6 E8-2
E3-1
ACCB1
E3-5
E3-2
INV.C3
INV.C1
ACCB2
INV.W1
INV.W2
ACCB4
W2-3
W2-1
W1-5
W2-2
W2-6
W1-1W1-2
W1-3
W2-4
W1-4
ACCB3
INV.E6
INV.E5
INV.E1
C4-2
C4-4 C4-5C4-3
C2-3
C1-6
MAINTAIN A MINIMUM OF 3'-6"BETWEEN THE PANELS AND THEROOF EDGE.
EW
INV.E2
INV.F2
1
1
1
1
1
INV.C2
W2-5
MAINTAIN A MINIMUM OF 2'-6"BETWEEN THE PANELS AND THEROOF EDGE.
MAINTAIN A MINIMUM OF 2'-6"BETWEEN THE PANELS AND THEROOF EDGE.
PROVIDE A MINIMUM 1'-6" WIDEMAINTENCE ACCESS AISLE.
MAINTAIN A MINIMUM OF 3'-6"BETWEEN THE PANELS AND THEROOF EDGE.
MAINTAIN A MINIMUM OF 2'-6"BETWEEN THE PANELS AND THEROOF EDGE.
PROVIDE A MINIMUM 1'-0" WIDEMAINTENCE ACCESS AISLE.
MAINTAIN A MINIMUM OF 2'-6"BETWEEN THE PANELS AND THEROOF EDGE.
C3-1 C3-2C4-1
C3-4 C3-3C2-5
C3-5 C3-6C2-4
C2-6
C2-2
C2-1
INV.C4
C1-5
C1-1C1-2
C1-4
C1-3
INV.F1
INV.E8
E4-3
E7-3
E7-5
E8-3
E8-4
E8-5
E5-1E1-1
E5-3E1-3
E5-4E1-4
E5-5E1-5
E5-6E1-6
E6-2E2-2
E6-1E2-1
E4-4
E4-1
E3-4E3-3
E7-6
E6-3E2-3
E6-4E2-4
E6-5
E6-6
E2-5
E2-6
L PNM Q RJH
9
12
6
14
4
15U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8L PNM Q RJHE FGLJL PNM Q RJHE FG
BUILDING INTEGRATED PV GLASS TO BE INSTALLED BYGC IN THESE LOCATIONS. EC SHALL WIRE BIPV TOINVERTER F1. (SCOPE OF WORK NOT INCLUDED INBASE BID #3)
INV F2 INV F1
BUILDING INTEGRATED PV GLASS TO BE INSTALLEDBY GC IN THESE LOCATIONS. EC SHALL WIRE BIPV TOINVERTER F2. (SCOPE OF WORK NOT INCLUDED INBASE BID #3)
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
E-202G150004-000
ELECTRICAL ROOF PLAN -POWER
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 ROOF BASE PHOTOVOLTAIC SYSTEM LAYOUT
DRAWING NOTES:
1. REFER TO E-300 FOR THE SINGLE LINE DIAGRAM AND INVERTER SCHEDULE.2. REFER TO SPECIFICATION SECTION 263100 FOR ADDITIONAL SYSTEM INFORMATION INCLUDING RACKING
SYSTEM TYPES AND PV PANEL MANUFACTURER INFORMATION.3. FINAL LAYOUT OF THE PV ARRAY SHALL BE DOCUMENTED BY THE PV CONTRACTOR. CONTRACTOR SHALL
PROVIDE COMPLETE DOCUMENTATION INCLUDING LAYOUT, STRINGING, EQUIPMENT, AND PREDICTEDENERGY GENERATION CALCULATIONS.
4. THIS PROJECT IS PURSUING NET ZERO ENERGY. THE FINAL INSTALLED SYSTEM SHALL PROVIDE ACALCULATED MINIMUM OF 201,000 KWH ANNUALLY THAT INCLUDES A DERATING FACTOR FOR POTENTIALSNOW LOAD.
5. NOT ALL PV ARRAYS INDICATED ARE INCLUDED IN BASE BID #3. IF ROOF TOP ARRAY CAN NOT GENERATETHE CALCULATED MINIMUM ENERGY FOR NET ZERO ENERGY THEN THIS SHOULD BE NOTED INDOCUMENTATION FOR BASE BID #3. THE FINAL SYSTEM MUST CALCULATE OUT TO PROVIDE THE MINIMUMENERGY NEEDED FOR NET ZERO ENERGY.
6. CONTRACTOR SHALL PROVIDE A COMPLETE PV SYSTEM, INCLUDING PANELS, RACKING, WIRING,DISCONNECTS, INVERTERS, ETC. THE CONTRACTOR SHALL PROVIDE DC COMBINER BOXES IF THEY AREREQUIRED FOR THE CONTRACTOR SELECTED INVERTER. THE CONTRACTOR SHALL ALSO PROVIDE ALLDATA CABLE WIRING REQUIRED TO NETWORK CONNECT THE INVERTERS TO THE BUILDING MANAGEMENTSYSTEM AND FOR ANY ENERGY DATA REQUIRED FOR THE BUILDING DASHBOARD SYSTEM.
7. REFER TO E-001 FOR THE LOCATION OF THE DUAL AXIS TRACKER PV SUB-ARRAY.
SCALE: 1/16" = 1'-0"2 ROOF ALTERNATE PV PANEL LAYOUT FOR OTHER APR. MANUFACTURER
SCALE: 1/16" = 1'-0"3 SOUTH FACADE
STRING HOMERUN LEGEND
E1-3
INVERTER NAME
STRING NUMBER
NO. ISSUE DATE: DESCRIPTION
KEY NOTES:
WIRING FROM CENTER HIGH ROOF PV SHALL BE RUN CONCEALED DOWN TO LOWER ROOF. RUNALL WIRING DOWN THE FACADE CONCEALED IN ENLARGED MULLIONS INDICATED.
1
Y
(AWG/KCMIL)WIRE SIZE
CONDUCTOR PHASEAND NEUTRAL GROUND 1PH, 2W+G
A
No. OF WIRES AND CONDUIT SIZE
B3PH, 3W+G 3PH, 4W+G
C
(IN INCHES)TAGSAMPS
HP-WOAU-1 M M
100A/3P 175A/3P 175A/3P 40A/2P225A/3P
700A/3P
40A/2P 30A/2P
LP30 POLE 208/120V
100A MCB
RP1 42 POLE 208/120V
125A MCB
HP142 POLE 208/120V
125AMCB
HP242 POLE 208/120V
125AMCB
RP2 42 POLE 208/120V
100A MCB
M M
MMMM
HVL SWITCH
30A/3P
M M M MM M M
WIRE & CONDUIT SIZING SCHEDULE
= = =
= == == = == = == ===
800A/3P
'MDP' 208/120V, 3 , 4W, 1200A, 65,000 AIC
12.48KV PRIMARY
GF
1 2
700A/3P
100A/3P
24C
225A/3P
3
10C
208/120V SECONDARY
125A/3P
11C
24B
4
100A/3P
5 6
225KVA
LIGHTINGPANELPANEL
MECH
15C
7 8 129 11
100A/3SPACE
100/3SPACE
UTILITY METER LOCATED AT BUILDING
125A/3P
PANELMECH
11C
TO INCOMINGMILLERSVILLE CAMPUSLOOP FEED SWITCH #7
10
700ADISCONNECT
60A/3P 40A/3P 60A/3P40A/3P
6B
6B
4B
4B
4B
4B
6B
6B
10C
NET METER FOR PV SYSTEM - LOCATED IN BUILDING
EASTERN ROOF PV ARRAYCENTER ROOF PV ARRAY
PVPANEL
PVPANEL
PVPANEL
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
PVPANEL
PVPANEL
STR4
STR5
PVPANEL
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR5
STR4
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
WESTERN ROOF PV ARRAY
10B 13B 13B 15B
PVP 208V, 3P, 800A
AC CB2 AC CB1 AC CB3
AC CB4
12KW
P-1 P-2
Voc MAX DCCOLDEST
MAX DCCURRENT
MINIMUM WIRE & CONDUIT SIZEFOR PV STRING
PV INVERTER INFORMATION
C18 AWG CONDUCTORS &
GROUND PV WIRE IN WEATHERTIGHT INSULATION
12KW 480V3 INVERTER
FRONIUS SYMO20.1" x 28.5" x 8.9"
NUMBER OFMPPT
2
2
2
C2
C3
E1
E2
E3
E4
E5
E6
12KW 480V3 INVERTER
3 INVERTER
8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER
TIGHT INSULATION8 AWG CONDUCTORS &
GROUND PV WIRE IN WEATHERTIGHT INSULATION
8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER
TIGHT INSULATION8 AWG CONDUCTORS &
GROUND PV WIRE IN WEATHERTIGHT INSULATION
8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER
TIGHT INSULATION8 AWG CONDUCTORS &
GROUND PV WIRE IN WEATHERTIGHT INSULATION
8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER
TIGHT INSULATION8 AWG CONDUCTORS &
GROUND PV WIRE IN WEATHERTIGHT INSULATION
INVERTERLETTER
MODELNUMBER
DIMENSIONSWxDxH
NOTE:1. THE ABOVE SCHEDULE IS BASED ON 600 VOLT WIRE TYPE THWN/XHHW AND EMT/RGS CONDUIT
700
800
600
500
200
450
400
300
250
275
225
175
125
150
70
100
90
80
30
50
60
40
20
15
24
25
23
22
14
21
20
19
18
16
17
15
13
11
12
10
9
7
8
3
5
6
4
1
2
3/0
500
350
250
300
.
4/0
1/0
2/0
1
1
2
4
3
10
6
4
8
12
14
6
3
3
4
4
4
4
.
6
6
6
8
8
8
8
10
10
10
10
14
12
350 500
(2)500
(2)500
(2)350
(2)250
(2)4/0
(2)1/0
(2)1/0
(2)1
(2)2
(2)2
(2)4 (2)4
NUMBER INDICATES FEEDER SIZE IN AMPS AND WIRELETTER INDICATES CONDUIT SIZE AND NUMBER OF WIRES2B
2
1 1/4
1 1/4
1
1
3/4
3/4
1
3/4
3/4
3/4
1 1/4
1 1/4
2
1 1/4
3/4
1
1 1/4
3/4
3/4
3/4
2 1/2
3
11/4
1 1/4
1 1/4
3/4
3/4
3/4
3/4
1
1 1/4 1 1/2
1 1/2
1 1/2 2
2
221 1/2
1 1/2 2 2 1/2
2 1/22
2
2 1/2
3
2 1/2
4 4
3
3 3
32 1/2
2 1/2
3 4 4
(2)4 (2)4
(2)2 1/2(2)2 1/2
(2)2 1/2
(2)3
(2)3
(2)4
SPACE
F1
AC
INV G1
1 1 1 1
26.2"x25.6"x10.4"8 AWG CONDUCTORS &
GROUND PV WIRE IN WEATHERTIGHT INSULATION
7.5KW 208V1 INVERTER 600V 30A 1
NOT INCLUDEDIN BASE BID #3
TO BIPV GLASS PANELS
SPACE
MAX ACCURRENT
32A
4A
20.1" x 28.5" x 8.9"
20.1" x 28.5" x 8.9"12KW 208V
41.5A 33.3A
FRONIUS SYMO
FRONIUS SYMO
FRONIUS IG PLUS ADV.
DCDC
INV F1
AC
NOT INCLUDEDIN BASE BID #3
DCDC
TO BIPV GLASS PANELS
INV F2
AC
NOT INCLUDEDIN BASE BID #3
DCDC
AC
INV W1
DC
DCMPPT1 MPPT2
15KW
AC
INV W2
DC
DC
PVPANEL
STR6
PVPANEL
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR5
STR4
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
INV C3
PVPANEL
STR6
PVPANEL
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR5
STR4
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
AC
INV C2
DC
DC
PVPANEL
STR6
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR4
STR3
STR2
STR1
TO ADDITIONAL SOLARTRACKER PV PANELS.
PVPANEL
PVPANEL
PVPANEL
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
AC
INV C4
DC
DC
12KW
MPPT1 MPPT2
12KW 12KW
MPPT1 MPPT2
PVPANEL
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR5
STR4
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
INV C1
PVPANEL
STR6
12KW
AC
DC
DCMPPT1 MPPT2
AC
DC
DCMPPT1 MPPT2
PVPANEL
PVPANEL
STR4
STR5
PVPANEL
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR5
STR4
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
INV E7
PVPANEL
STR6
TO ADDITIONAL PV PANELS.
AC
INV E4
DC
DC
TO ADDITIONAL PV PANELS.
INV E812KW
MPPT1 MPPT2
12KW 12KW
PVPANEL
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR5
STR4
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
INV E3
PVPANEL
STR6
12KW
AC
DC
DCMPPT1 MPPT2
AC
DC
DCMPPT1 MPPT2
PVPANEL
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR5
STR4
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
INV E5
PVPANEL
STR6
PVPANEL
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR5
STR4
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
INV E2
DC
PVPANEL
STR6
AC
INV E6
DC
DC
15KW 15KW 15KW
PVPANEL
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR5
STR4
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
INV E1
PVPANEL
STR6
15KW
AC
DC DC
W1
W2
12KW 208V3 INVERTER
15KW 208V3 INVERTER
600V 41.5A 2
1
8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER
TIGHT INSULATION8 AWG CONDUCTORS &
GROUND PV WIRE IN WEATHERTIGHT INSULATION
F2
G1
26.2"x25.6"x10.4"8 AWG CONDUCTORS &
GROUND PV WIRE IN WEATHERTIGHT INSULATION
7.5KW 208V1 INVERTER 21.1" x 28.5" x 7.8" 600V 35.1A 1
8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER
TIGHT INSULATION
3.8KW 208V1 INVERTER
FRONIUS IG PLUS ADV.600V 17.8A 1
33.3A
41.6A
32A
18.3A
20.1" x 28.5" x 8.9"
20.1" x 28.5" x 8.9"
FRONIUS SYMO
FRONIUS SYMO50A
FRONIUS IG PLUS ADV.
E7
E8
8 AWG CONDUCTORS &GROUND PV WIRE IN WEATHER
TIGHT INSULATION8 AWG CONDUCTORS &
GROUND PV WIRE IN WEATHERTIGHT INSULATION
2C4 3 INVERTER8 AWG CONDUCTORS &
GROUND PV WIRE IN WEATHERTIGHT INSULATION
20.1" x 28.5" x 8.9"12KW 208V
41.5A 33.3AFRONIUS SYMO
41.5A 33.3A
41.5A 33.3A
SPACE SPACE
4A 2A
AC
DC
DCMPPT1 MPPT2
PVPANEL
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR5
STR4
STR3
STR2
STR1
TO ADDITIONAL PV PANELS.
PVPANEL
STR6
AC
DC
AC
DC
AC
DC
15KW 208V3 INVERTER 141.6A20.1" x 28.5" x 8.9"
FRONIUS SYMO50A
15KW 208V3 INVERTER 141.6A20.1" x 28.5" x 8.9"
FRONIUS SYMO50A
15KW 208V3 INVERTER 141.6A20.1" x 28.5" x 8.9"
FRONIUS SYMO50A
15KW 208V3 INVERTER 141.6A20.1" x 28.5" x 8.9"
FRONIUS SYMO50A
23 INVERTER 20.1" x 28.5" x 8.9"12KW 208V
41.5A 33.3AFRONIUS SYMO
23 INVERTER 20.1" x 28.5" x 8.9"12KW 208V
41.5A 33.3AFRONIUS SYMO
23 INVERTER 20.1" x 28.5" x 8.9"12KW 208V
41.5A 33.3AFRONIUS SYMO
23 INVERTER 20.1" x 28.5" x 8.9"12KW 208V
41.5A 33.3AFRONIUS SYMO
1000V
1000V
1000V
1000V
1000V
600V
600V
600V
600V
600V
600V
600V
600V
PVPANEL
PVPANEL
PVPANEL
STR3
STR2
STR1
PVPANEL
PVPANEL
STR4
STR5
PVPANEL
PVPANEL
PVPANEL
PVPANEL
PVPANEL
STR5
STR4
STR3
STR2
STR1
PVPANEL
STR6
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
E-300G150004-000
ELECTRICAL SINGLE LINEDIAGRAM
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
DRAWING NOTES:
1. PROVIDE BRANCH CIRCUIT METERING FOR ALL BRANCH CIRCUITS IN PANELS RP1, RP2, LP, HP1, AND HP2. PROVIDE NETWORK CONNECTION FROMBRANCH CIRCUIT METERS TO CAMPUS METERING COMPUTER FOR REMOTE MONITORING OF LOADS. ALL METERING SHALL BE MILLERSVILLE CAMPUSSTANDARD TYPE CLASS 5000 SMART METERING FROM E-MON D-MON.
KEY NOTES:
METERS SHALL BE LOCATED IN BASEMENT. REFER TO E-200 FOR LOCATION.1
NO. ISSUE DATE: DESCRIPTION
RJ45(Typical)
NTSSCALE:
DIGITAL LIGHTING MANAGEMENT NETWORK DIAGRAM - TYPICAL ROOM CONTROLLERNONESCALE:
FIXTURE W1 - TYPICAL MULLION MOUNTING DETAILNONESCALE:
SCALE:LMSM-3E - TYPICAL WIRING DETAIL
NONE
D
MM
T W PS
MM MM
D
LIGHTING FIXTURE SCHEDULE LIGHTING CONTROL DEVICE SCHEDULE
RECESSED 6" WIDE LINEAR LED WITH SATIN LENS WITH 0-10V DIMMABLEDRIVER AND COMPATIBLE WITH TECH ZONE CEILINGS. CONFIRM LENGTHS
OF FIXTURES WITH DRAWINGS.
MOUNTINGVOLTSTYPENO.CATALOG NUMBERMANUFACTURERDESCRIPTIONTYPE
LAMPS
REMARKS
LED 5.1W/FT UNV
A1
A1A -
FIXTUREWATTS
PENDANT
LED 7.5W/FT UNVGAMMALUXPINNACLE RECESSED-GB56RC2-1SOLED35-UNV-DVR-*N-REC/
*-ASLMD-*-*
GB66B2-1/1CPOLED35-UNV-DIM-*-C*-APL/ASLMD-*
6" WIDE LINEAR LED INDIRECT/DIRECT PENDANT WITH SATINLENS WITH 0-10V DIMMABLE DRIVER. CONFIRM LENGTHS OF
FIXTURES WITH DRAWINGS.
LED 7.2W/FT UNVA2 - RECESSEDRECESSED PERIMETER LED WITH 6" OPENING AND ASYMMETRIC AMBIENTILLUMINATION.
LED UNVA3 - RECESSED
LED 18W UNVD1 - RECESSEDRECESSED 6" DIAMETER LED DOWNLIGHT WITH 1500 LUMEN PACKAGE AND0-10V DIMMABLE DRIVER.
B1 LED 38W UNVLIGHT EMITTING DES.HE WILLIAMS - PENDANTINDUSTRIAL STYLE LED PENDANT
7.4W/FTMULLION MOUNTED LINEAR LED, WET LOCATION RATED WITH REMOTE
DRIVERS,100 DEGREE OPTICS, AND 0-10V DIMMABLE DRIVER. PROVIDE ALLCOMPONENTS FOR A COMPLETE INSTALLATION. CONFIRM LENGTHS OF
FIXTURES WITH DRAWINGS.
C6L15NUVBZ10V-C6L1520DL35KMCCL
SML150-40ND-TBH
PHILIPSHE WILLIAMS
INSIGHT
4WWALL MOUNT EDGE LIT LED EXIT SIGN WITH GREEN LETTERS. SIGNTEXHE WILLIAMS
*CONFIRM MOUNTINGDETAILS AND FINISHES
WITH ARCHITECT
*CONFIRM MOUNTINGDETAILS AND FINISHES
WITH ARCHITECT. CPO =30% OF HIGH OUTPUT
DRIVER.
MXI-6-35K-100-U-CES-*RPS/96/PWR/WET-DIM-*
*CONFIRM NUMBER OFFACES AND CHEVRON
DIRECTION WITH DRAWING.CONFIRM FINISH WITH
ARCHITECT.
LED 6.3W/FT 120P1 - PENDANTSQUARE PROFILE 1.14" X 1.14" LED DIRECT PENDANT WITH REMOTE 0-10VDIMMABLE DRIVER AND DIFFUSE LENS. CONFIRM LENGHTS OF FIXTURES
WITH DRAWINGS.VODE 107-BX 01 * * CC * 2R AE 1 0 Z SO 35 1 0 * 0
*CONFIRM MOUNTINGDETAILS AND FINISHES
WITH ARCHITECT
LIGHTING FIXTURE SCHEDULE NOTES:
1. CATALOG NUMBER IS BASED ON FIRST MANUFACTURER LISTED.
2. ELECTRICAL CONTRACTOR TO VERIFY MOUNTING TYPE AND VOLTAGE (IF MVOLT IS NOT AVAILABLE) PRIOR TO ORDERING FIXTURES.
3. ELECTRICAL CONTRACTOR TO COORDINATE DIMMING BALLAST TYPE WITH THE SPECIFIED LIGHTING CONTROL SYSTEM. DIMMERS SHALL BE COMPATIBLE WITH THE DRIVERS IN THELIGHTING FIXTURE.
4. ELECTRICAL CONTRACTOR TO COORDINATE ALL PRODUCTS SUCH THAT ALL NECESSARY PARTS, ACCESSORIES, ETC ARE INSTALLED FOR A COMPLETE FUNCTIONING SYSTEM AS PERDESIGN INTENT.
VOLTS MOUNTING REMARKSMANUFACTURERTYPE DESCRIPTION CATALOG NUMBER
OS LOW VOLT WALL MOUNTEDPASSIVE INFRARED LOW VOLTAGE WALL SENSOR THAT CONTROLSLIGHTS ON AND OFF WITH OCCUPANCY WITH HIGH DENSITY LENS. LMPX-100
ST WALL SWITCHLINE VOLTAGE DIGITAL TIMER SWITCH TS-400-W-U 120V
LOW VOLT CEILINGVSPASSIVE INFRARED LOW VOLTAGE CEILING SENSOR THAT CONTROLSOFF WITH OCCUPANCY BUT REQUIRES A MANUAL WALL SWITCH TO
TURN LIGHTS ON.LMPC-100
LIGHTING CONTROL DEVICE SCHEDULE NOTES:
1. CATALOG NUMBER IS BASED ON FIRST MANUFACTURER LISTED.
2. TIME CLOCK CONTROL IS BY AREA. REFER TO REFLECTED CEILING PLANS AND SEQUENCE OF OPERATION FOR MORE INFORMATION.
LIGHTING CONTROL SEQUENCE OF OPERATION:
1. ALL EMERGENCY LIGHTING SHALL BE CONTROLLED BY EMERGENCY BATTERY BACKUP IN THE EVENT OF A POWER LOSS. NIGHT LIGHTING AND EXIT SIGNS SHALL ALWAYS BE ON.
2. THE LOBBY, OPEN OFFICE CORRIDOR, AND EXTERIOR LIGHTING SHALL BE CONTROLLED BY TIME CLOCK. THE LOBBY LIGHTS SHALL TURN ON 30 MINUTES BEFORE OPENING AND TURN OFF AT 10:00 PM. AT OFF HOURS LIGHTS IN LOBBY SHALL BECONTROLLED BY OVERRIDE SWITCHES AND OCCUPANCY SENSORS ONLY. THE CORRIDOR LIGHTS SHALL TURN ON 30 MINUTES BEFORE OPENING AND TURN OFF 30 MINUTES AFTER CLOSING. AT OFF HOURS LIGHTS IN THE CORRIDOR SHALL BECONTROLLED BY OVERRIDE SWITCHES AND OCCUPANCY SENSORS. ALL OTHER SPACES SHALL BE CONTROLLED BY LOCAL CONTROLS (SWITCHES, VACANCY SENSORS, AND OCCUPANCY SENSORS AS INDICATED). CONFIRM SCHEDULE WITH OWNERBEFORE PROGRAMMING OF TIME CLOCK. ALL PROGRAMMING SHALL BE DONE BY USING WATTSTOPPER DLM SYSTEM.
3. LOCAL CONTROLS AND OCCUPANCY/VACNACY SENSORS SHALL BE USED IN AREAS NOT CONTROLLED BY TIME CLOCK. ANY OCCUPANCY SENSORS SHALL AUTOMATICALLY TURN ON LIGHTS AFTER ACTIVATION OF SENSOR. THE VACANCY SENSOR SHALLONLY TURN THE LIGHTS OFF AND THE LIGHTS SHALL ONLY TURN ON WITH ACTIVATION OF THE WALL SWITCH.
OS LOW VOLT CEILINGDUAL TECHNOLOGY LOW VOLTAGE CEILING SENSOR THAT CONTROLSLIGHTS ON AND OFF WITH OCCUPANCY. LMDC-100
WATTSTOPPER
WATTSTOPPER
WATTSTOPPER
WATTSTOPPER
SD
SOR
ONE BUTTON DIMMING WALL SWITCH WITH LED DIMMING INDICATOR LMDM-101
OVERRIDE WALL SWITCH
LOW VOLTWATTSTOPPER
LOW VOLTWATTSTOPPER
LOW VOLTWATTSTOPPER
LMSW-100
SOR ONE BUTTON DIMMING WALL SWITCH LOW VOLTWATTSTOPPER
120VWATTSTOPPER
LMSW-100
SKP5 BUTTON SCENE SWITCH WITH RAISE/LOWER AND 4 SCENE PRESETS
AND CUSTOM ENGRAVED BUTTONS. LMSW-105
PC LOW VOLT CEILINGWATTSTOPPER
SOS ONE BUTTON PASSIVE INFRARED WALL SWITCH OCCUPANCY SENSOR DSW-100
0-10V Dimming Wiring DiagramLMRC-211 Single Relay
DEVICES ARE PRESET FOR PLUG n' GO ™ OPERATION,ADJUSTMENT IS OPTIONAL. Sequence of Operation: In this configuration theLMRC-211 defaults to manual-on/automatic-off operation. Enhanced roomcontrollers support up to 64 loads and 48 devices per DLM localnetwork. At system startup, default dimming parameters are established including:levels for presets 1-4; fade times; and fade and ramp rates. Dimming and systemparameters may be customized. For full operational details, adjustmentsand more features of the product, see the DLM SystemInstallation Guide at www.wattstopper.com
Red
Neutral Wht
LightingLoad
LMRC-211Single Relay
On/Off/0-10V DimmingRoom Controller
Vio
Gry
VioGry
LMRJ Series Pre-TerminatedCables or CAT5e. Free Topology& Splitter Acceptable
Class 2 0-10 VoltControl Wiring
0-10VDC DimmingBallast required.
(As Needed)LMDM-101 Digital
Dimming Wall Switch
UnswitchedHot Blk120/277
*DLM OccupancySensor
*NOTE:Corner mount Sensorshown with pigtail &supplied coupler. Ceilingmount Sensor has twoRJ45 ports.
LMRJ-C8Coupler
EarthGround
Grn
LMBC-300Digital Network
Bridge
FromPrevious
DeviceTo NextDevice
SegmentNetwork MS/TP
R - +
(+) White
(R) Green/White (-) Black
Twist & WrapShield TogetherWrap Shield with
Tape for strain relief
FromPreviousDevice
To NextDevice
DLM Terminalblock for MS/TP
SegmentNetwork MS/TP
R - +
SegmentNetwork MS/TP
LMLS-400Photosensor
LMLS-400SINGLE-ZONE ON/OFF AND DIMMING CLOSED LOOP PHOTOSENSOR
*NOTE:TYPICAL WIRING DIAGRAMSHOWN. REFER TO E-101FOR CONTROLS, SWITCHES,AND ROOM CONTROLLERSTHAT ARE NEEDED FORAREA.
WALL SWITCH
WALL SWITCH
WALL SWITCH
WALL SWITCH
WALL SWITCH
LED 18W UNVP2 - PENDANT7" DIAMETER LED CYLINDER WITH 1500 LUMEN WITH WIDE OPTICSPACKAGE WITH 0-10V DIMMABLE DRIVER.
PHILIPSPRESCOLITE C4L10C*35KCCLUVB-C4CC*X5
*CONFIRM MOUNTINGDETAILS AND FINISHES
WITH ARCHITECT
10WWALL MOUNTED MULLION MOUNT EXTERIOR LED FIXTURE.
*CONFIRM MOUNTINGDETAILS AND FINISHES
WITH ARCHITECT
*CONFIRM MOUNTINGDETAILS AND FINISHES
WITH ARCHITECT
10WWALL MOUNTED EXTERIOR LED FIXTURE. SIGNTEX MAEAC10*W*CONFIRM MOUNTINGDETAILS AND FINISHES
WITH ARCHITECT
LED UNV-
LED UNV-
LED UNV-
UNV
SURFACE
WALL
WALL
W1
W2
W3
X1 LED- WALL
GPCAR6N-1SOLED35T-UNV-DVR-*N-RECW*-**CONFIRM MOUNTINGDETAILS AND FINISHES
WITH ARCHITECT
*CONFIRM MOUNTINGDETAILS AND FINISHES
WITH ARCHITECT7.2W/FTRECESSED PERIMETER LED WITH 6" OPENING. GPRG6B-1SOLED35T-UNV-DVR-*-
OS 120V CEILINGDUAL TECHNOLOGY LINE VOLTAGE CEILING SENSOR THAT CONTROLSLIGHTS ON AND OFF WITH OCCUPANCY. DT-355WATTSTOPPER
LV PROVIDE POWER PACKS AS NEEDED.
4WMULLION MOUNT EDGE LIT LED EXIT SIGN WITH GREEN LETTERS. CRS-BB-*G**-*-MMSIGNTEXHE WILLIAMS
*CONFIRM NUMBER OFFACES AND CHEVRON
DIRECTION WITH DRAWING.CONFIRM FINISH WITH
ARCHITECT.
UNVX1A LED- SURFACE
4WPENDANT MOUNT EDGE LIT LED EXIT SIGN WITH GREEN LETTERS. CRS-BB-*G**-*-TWSIGNTEXHE WILLIAMS
*CONFIRM NUMBER OFFACES AND CHEVRON
DIRECTION WITH DRAWING.CONFIRM FINISH WITH
ARCHITECT.
UNVX1B LED- PENDANT
W4
CRS-BB-*G**-*-WM
SIGNTEX
SIGNTEX
MUEAC10*W
MOEAC10*WALL MOUNTED EXTERIOR LED FIXTURE. 10WLED UNV- WALL*CONFIRM MOUNTINGDETAILS AND FINISHES
WITH ARCHITECT
REFER TO E-101 FOR ROOMCONTROLLERS NEEDED
120V CIRCUIT
FIRE ALARMANNUNCIATOR
PANEL(FAP)(W/GRAPHIC DISPLAY)
LOCATED INLOBBY
FIRE ALARMCONTROL PANEL
(FACP)LOCATED IN
ELECTRIC ROOM-121
F
TO OTHER INITIATINGDEVICES
TO OTHER INITIATINGDEVICES
TO OTHER SIGNALINGDEVICES
F
TO OTHER INITIATINGDEVICES
TO OTHER INITIATINGDEVICES
TO OTHER SIGNALINGDEVICES
FIRE ALARM RISER NOTES:
1. SEE ELECTRICAL FLOOR PLANS FOR QUANTITY OF DEVICES.2. INSTALLER SHALL COORDINATE WITH OWNER TO ESTABLISH A FACILITY FIRE
ALARM ADDRESS SCHEDULE FOR ZONING OF AREA DETECTION DEVICES.INSTALLER SHALL INCLUDE WITHIN HIS BID AN ADEQUATE NUMBER OFADDRESSABLE LOOPS & NOTIFICATION APPLIANCE DEVICE OUTPUT CIRCUITSTO ACCOMMODATE THE ESTABLISHED FACILITY ZONING NEEDS, INCLUDINGTWENTY PERCENT SPARE CAPACITY, FOR FUTURE DEVICES, ON ADDRESSZONE AND NOTIFICATION APPLIANCE DEVICE LOOPS.
3. ALL WIRING SHALL BE METAL-CLAD FIRE ALARM/CONTROL CABLE TYPE FPL ASMANUFACTURED BY "AFC" WITH RED FLEXIBLE OUTER METAL JACKET.
4. PROVIDE CONTROL AND MONITOR MODULES AS REQUIRED.5. REFER TO MECHANICAL AND FIRE PROTECTION DRAWINGS FOR QUANTITIES
AND LOCATIONS OF ALL FIRE ALARM DEVICES ASSOCIATED WITH MECHANICALSYSTEMS.
6. PROVIDE POWER SUPPLY(S) AS REQUIRED FOR DOOR CLOSURES, SMOKEDAMPER CONTROL AND VISUAL ANNUCIATORS (STROBES).
7. NO SUBSTITUTIONS. SIEMENS AS BASIS OF DESIGN.8. FIRE ALARM VENDOR SHALL PROVIDE ALL GRAPHICS AND SIGNAGE REQUIRED.9. FIBER CONNECTION TO IT ROOM 123 FOR CONNECTION TO CAMPUS
MONITORING SYSTEM.
KEY NOTES:
PROVIDE (2)UNIVERSAL DIGITAL ALARM - PROTECTED FIBER CONNECTION TO ITROOM 123. CONNECT FIRE ALARM SYSTEM FROM MDF ROOM TO GORDINIERAND THE CAMPUS COMMAND CENTER AT STUDENT MEMORIAL CENTER.PROVIDE BUILDING GRAPHICS FOR DISPLAY AT THE CAMPUS COMMANDCENTER.
GAMMALUXPINNACLE
GAMMALUXPINNACLE
GAMMALUXPINNACLE
RJ45ETHERNET
LAN
LM-MSTPDATALINE
THE LMBC-300'S ARE CONNECTED TOGETHER USINGLM-MSTP DATALINE. THE DATALINE MUST BE RUN IN ALINEAR FASHION.
Segment #1LMBC-300
AS PER PLANSLMBC-300
11LMSM-3E
120 VAC
LMSM-ENC1
BOTTOM OF FIXTURE SHALLBE MOUNTED AT 9'-0'' AFF.
Z1 15WLED EXTERIOR BOLLARD. FLINDT/15W LED/4000K/120-277VPOULSEN UNVLED- IN GRADE
LED 15W UNVP2A - PENDANT4" DIAMETER LED CYLINDER WITH 1000 LUMEN WITH MEDIUM OPTICSPACKAGE WITH 0-10V DIMMABLE DRIVER.
PHILIPSPRESCOLITE C7L20C*35KWCCLUVB-C7CC*X5
*CONFIRM MOUNTINGDETAILS AND FINISHES
WITH ARCHITECT
1
1
4 FIRE ALARM RISER
3
1
2
GROUND FLOOR
LOMBARDO WELCOME CENTERLOWER LEVEL
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
E-400G150004-000
ELECTRICAL LIGHTINGSCHEDULE & FA RISER
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
E-401G150004-000
ELECTRICAL PANELSCHEDULES
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NOTES:PROVIDE BRANCH CIRCUITING METERING FOR PANEL HP1
TOTAL EST. DEMAND: 127TOTAL CONN.: 127
TOTAL EST. DEMAND: 45734 VAPower 39234 VA 100.00% 39234 VA TOTAL CONN. LOAD: 45734 VAHeating 6500 VA 100.00% 6500 VALOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 148 A 144 A 101 ATOTAL LOAD: 17086 VA 16539 VA 12109 VA
41 SPARE 20 1 0 0 1 20 SPARE 4239 2683 1061 4037
HP-5 50 22683 1061
2 20 HP-438
35 2132 1061 3633
HP-2 40 22132 1061
2 20 HP-334
31 TF-1 20 1 1500 1154 3229 VAVB 20 1 1500 1154
2 20 HP-130
27 1498 1500 1 20 EWH-1-1 2825
HP-18 30 21498 2000 1 30 EWH-1-2 26
23 385 385 2421
HP-16 20 2385 385
2 20 HP-1722
19 1154 730 2017
HP-14 20 21154 730
2 20 HP-1518
15 1154 1498 1613
HP-12 20 21154 1498
2 30 HP-1314
11 1154 914 129
HP-10 20 21154 914
2 20 HP-1110
7 1154 385 85
HP-8 20 21154 385
2 20 HP-96
3 385 730 41
HP-6 20 2385 730
2 20 HP-72
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
ENCLOSURE: Type 1 MOUNTING: SURFACE MCB RATING / POLES: 225A / 3P FEED (TOP/ BOTTOM):FEEDER SIZE: WIRES: 4 MAINS RATING: 225 A GROUND BUS: Yes
FED FROM:: PHASES: 3 MAINS TYPE: MAIN CIRCUIT BREAKER BUSSING (CU/AL): CULOCATION: ELEC. RM. 121 VOLTS (V): 120/208 Wye A.I.C. RATING: 22,000 NEUTRAL: 100%
BRANCH PANEL: HP1
NOTES:PROVIDE BRANCH CIRCUITING METERING FOR PANEL HP2
Power 11678 VA 100.00% 11678 VA TOTAL EST. DEMAND: 60Other 4000 VA 100.00% 4000 VA TOTAL CONN.: 60Motor 120 VA 125.00% 150 VA TOTAL EST. DEMAND: 21643 VAHeating 5780 VA 100.00% 5780 VA TOTAL CONN. LOAD: 21613 VAHVAC 35 VA 100.00% 35 VALOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 63 A 41 A 82 ATOTAL LOAD: 7234 VA 4940 VA 9439 VA
41 SPACE -- -- 0 0 -- -- SPACE 4239 SPACE -- -- 0 0 -- -- SPACE 4037 SPACE -- -- 0 0 -- -- SPACE 3835 SPARE 20 1 0 0 -- -- SPACE 3633 SPARE 20 1 0 0 1 20 SPARE 3431 POWER 20 1 2000 2080 3229 POWER 20 1 2500 2080
2 30 ACCU-130
27 104 0 1 20 BAS CONTROL PANEL 2825
POWER ELEC. RM. 121 20 2104 500 1 20 POWER 26
23 BAS CONTROL PANEL 20 1 0 120 1 20 P-3 2421 FLOOD CONTROL VALVE 20 1 250 385 2219 MOTORIZED SHADES 20 1 500 385
2 20 HP-2320
17 EF-2 20 1 35 2640 1 30 BR-1 1815 BR-1 30 1 2640 0 1 20 P-3 1613 104 0 1 20 VAVB 1411
AC-1 20 2104 730 12
9 P-4 20 1 0 7302 20 HP-20
107 EF-1 20 1 0 730 85 GYLOCL SKID 20 1 500 730
2 20 HP-216
3 385 447 41
HP-22 20 2385 447
2 20 HP-192
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
ENCLOSURE: Type 1 MOUNTING: SURFACE MCB RATING / POLES: 125A / 3P FEED (TOP/ BOTTOM):FEEDER SIZE: WIRES: 4 MAINS RATING: 225 A GROUND BUS: Yes
FED FROM:: PHASES: 3 MAINS TYPE: MAIN CIRCUIT BREAKER BUSSING (CU/AL): CULOCATION: MECHANICAL 002 VOLTS (V): 120/208 Wye A.I.C. RATING: 22,000 NEUTRAL: 100%
BRANCH PANEL: HP2
NOTES:PROVIDE BRANCH CIRCUITING METERING FOR PANEL LP
TOTAL EST. DEMAND: 34TOTAL CONN.: 27
TOTAL EST. DEMAND: 12210 VAOther 0 VA 0.00% 0 VA TOTAL CONN. LOAD: 9768 VALighting 9768 VA 125.00% 12210 VALOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 26 A 23 A 31 ATOTAL LOAD: 3058 VA 2743 VA 3669 VA
29 SPACE -- -- 0 0 -- -- SPACE 3027 SPACE -- -- 0 0 -- -- SPACE 2825 SPARE 20 1 0 0 -- -- SPACE 2623 SPARE 20 1 0 0 1 20 SPARE 2421 SPARE 20 1 0 0 1 20 SPARE 2219 LIGHTING 20 1 848 0 1 20 SPARE 2017 LIGHTING 20 1 882 0 1 20 MAIN LIGHTING SIGN 1815 LIGHTING 20 1 570 864 1 20 LIGHTING 1613 LIGHTING 20 1 72 350 1 20 LIGHTING 1411 LIGHTING 20 1 521 762 1 20 LIGHTING 129 INVERTER 30 1 461 127 1 20 LIGHTING 107 LIGHTING 20 1 150 383 1 20 LIGHTING 85 LIGHTING 20 1 513 918 1 20 LIGHTING 63 LIGHTING 20 1 420 300 1 20 LIGHTING 41 LIGHTING 20 1 240 736 1 20 LIGHTING 2
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
ENCLOSURE: Type 1 MOUNTING: SURFACE MCB RATING / POLES: 100A / 3P FEED (TOP/ BOTTOM):FEEDER SIZE: WIRES: 4 MAINS RATING: 100 A GROUND BUS: Yes
FED FROM:: PHASES: 3 MAINS TYPE: MAIN CIRCUIT BREAKER BUSSING (CU/AL): CULOCATION: ELEC. RM. 121 VOLTS (V): 120/208 Wye A.I.C. RATING: 22,000 NEUTRAL: 100%
BRANCH PANEL: LP
NOTES:PROVIDE BRANCH CIRCUITING METERING FOR PANEL RP1
TOTAL EST. DEMAND: 42TOTAL CONN.: 56
TOTAL EST. DEMAND: 15170 VATOTAL CONN. LOAD: 20340 VA
Receptacle 20340 VA 74.58% 15170 VALOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 62 A 63 A 48 ATOTAL LOAD: 7200 VA 7380 VA 5760 VA
41 SPARE 20 1 0 0 1 20 SPARE 4239 RECEPTACLE OFFICE 124 20 1 540 540 1 20 RECEPTACLE OFFICE 128 4037 RECEPTACLE STUDENT WORK SPACE... 20 1 1080 540 1 20 RECEPTACLE OFFICE 118 3835 RECEPTACLE RESOURCE ROOM 120 20 1 540 720 1 20 RECEPTACLE CONFERENCE 133 3633 RECEPTACLE OFFICE 112 20 1 540 180 1 20 RECEPTACLE RESOURCE ROOM 120 3431 RECEPTACLE STUDENT WORK SPACE... 20 1 1080 180 1 20 IT RACK REC. 3229 RECEPTACLE WORK ROOM 129 20 1 180 180 1 20 RECEPTACLE V.P. OFFICE 112A 3027 RECEPTACLE ROOM 121, 122, 123 20 1 900 720 1 20 RECEPTACLE ROOM 131, 132 2825 RECEPTACLE HOUSING OPEN OFFICE... 20 1 360 360 1 20 RECEPTACLE HOUSING OPEN OFFICE... 2623 RECEPTACLE ROOM 116, 117 20 1 540 720 1 20 RECEPTACLE ROOM 119, 128 2421 RECEPTACLE MARKETING OPEN... 20 1 540 720 1 20 RECEPTACLE ROOM 115, 114 2219 RECEPTACLE MARKETING OPEN... 20 1 540 180 1 20 RECEPTACLE WORK ROOM 129 2017 RECEPTACLE ROOM 110, 109 20 1 540 540 1 20 RECEPTACLE OFFICE 111 1815 RECEPTACLE ROOM 107, 106 20 1 540 720 1 20 RECEPTACLE OFFICE (V.P. O... 1613 RECEPTACLE ADMISSIONS OPEN... 20 1 360 720 1 20 RECEPTACLE ROOM 104, 105 1411 RECEPTACLE ROOM 127, 126 20 1 360 540 1 20 RECEPTACLE ADMISSIONS OPEN... 129 RECEPTACLE ADMISSIONS OPEN... 20 1 540 540 1 20 RECEPTACLE ADMISSIONS OPEN... 107 RECEPTACLE ADMISSIONS OPEN... 20 1 540 540 1 20 RECEPTACLE OFFICE 110 85 RECEPTACLE ROOM 103, 102 20 1 540 360 1 20 RECEPTACLE ADMISSIONS OPEN... 63 IT RACK REC. 20 1 180 180 1 20 IT RACK REC. 41 RECEPTACLE OFFICE 104 20 1 540 180 1 20 IT RACK REC. 2
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
ENCLOSURE: Type 1 MOUNTING: SURFACE MCB RATING / POLES: 125A / 3P FEED (TOP/ BOTTOM):FEEDER SIZE: WIRES: 4 MAINS RATING: 225 A GROUND BUS: Yes
FED FROM:: PHASES: 3 MAINS TYPE: MAIN CIRCUIT BREAKER BUSSING (CU/AL): CULOCATION: ELEC. RM. 121 VOLTS (V): 120/208 Wye A.I.C. RATING: 22,000 NEUTRAL: 100%
BRANCH PANEL: RP1
NOTES:PROVIDE BRANCH CIRCUITING METERING FOR PANEL RP2
TOTAL EST. DEMAND: 44TOTAL CONN.: 47
Receptacle 12260 VA 90.78% 11130 VA TOTAL EST. DEMAND: 15950 VAPower 4820 VA 100.00% 4820 VA TOTAL CONN. LOAD: 17080 VAOther 0 VA 0.00% 0 VALOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 37 A 37 A 69 ATOTAL LOAD: 4420 VA 4420 VA 8240 VA
41 SPARE 20 1 0 0 1 20 SPARE 4239 SPARE 20 1 0 0 1 20 SPARE 4037 SPARE 20 1 0 0 1 20 SPARE 3835 SPARE 20 1 0 180 1 20 RECEPTACLE 3633 SPARE 20 1 0 180 1 20 RECEPTACLE 3431 RECEPTACLE BREAK ROOM 124 20 1 360 180 1 20 RECEPTACLE 3229 OTHER RESOURCE ROOM 103 20 1 0 180 1 20 RECEPTACLE RECEPT. L101-2 3027 OTHER CLASSROOM/PRESENTATION... 20 1 0 180 1 20 RECEPTACLE 2825 LAV FAUCETS 20 1 720 0 1 20 OTHER CLASSROOM/PRESENTATION... 2623 RECEPTACLE 20 1 720 4820 1 30 HAND DRYERS 2421 RECEPTACLE 20 1 180 1260 1 20 RECEPTACLE ROOM 137, 136, 135 2219 RECEPTACLE 20 1 180 720 1 20 RECEPTACLE PRESENTATION ROOM... 2017 LAV FAUCETS 20 1 540 900 1 20 RECEPTACLE ROOM 142, 143, 141, 135 1815 RECEPTACLE PRESENTATION ROOM... 20 1 360 0 1 20 DOOR OPERATOR 1613 RECEPTACLE ROOM 145, 146, 144 20 1 360 1000 1 20 COPIER 1411 DOOR OPERATOR 20 1 0 720 1 20 RECEPTACLE 129 COPIER 20 1 1000 720 1 20 RECEPTACLE 107 RECEPTACLE LOBBY 135 20 1 360 180 1 20 RECEPTACLE ALCOVE 147 85 FACP 20 1 0 180 1 20 RECEPTACLE COFFEE STATION L101-3 63 RECEPTACLE 20 1 180 360 1 20 RECEPTACLE 41 RECEPTACLE 20 1 180 180 1 20 RECEPTACLE 2
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
ENCLOSURE: Type 1 MOUNTING: SURFACE MCB RATING / POLES: 100A / 3P FEED (TOP/ BOTTOM):FEEDER SIZE: WIRES: 4 MAINS RATING: 100 A GROUND BUS: Yes
FED FROM:: PHASES: 3 MAINS TYPE: MAIN CIRCUIT BREAKER BUSSING (CU/AL): CULOCATION: ELEC. RM. 121 VOLTS (V): 120/208 Wye A.I.C. RATING: 22,000 NEUTRAL: 100%
BRANCH PANEL: RP2
NO. ISSUE DATE: DESCRIPTION
T
FIRE PROTECTION SYMBOL LISTBASIC
FIRE STANDPIPE PIPING (STANDALONE)
SPRINKLER PIPING
DRY SPRINKLER PIPING
PRE-ACTION SPRINKLER PIPING
DRAIN PIPING
PIPING BELOW SLAB
EXISTING PIPING
EXISTING WORK TO BE REMOVED
HEAT TRACE / FREEZE PROTECTION CABLE & INSULATION
SLOPED CHANGE IN PIPE ELEVATION
BOTTOM PIPE CONNECTION
TOP PIPE CONNECTION
SIDE CONNECTION
PIPE DOWN/DROP
PIPE RISE/UP
PIPE SLOPE
VALVE IN VERTICAL
UNION
REDUCER
WATER PROOF SLEEVE
SLEEVE
FIRE EXTINGUISHERA - WATERB - DRY CHEMICALC - GASEOUS (CO2 OR HALON 1211 - SEE SPEC.)
FIRE EXTINGUISHER IN CABINET
FIRE HOSE VALVE
FIRE HOSE VALVE IN CABINET
FIRE HOSE VALVE w/HOSE IN CABINET
FIRE HOSE VALVE w/FIRE EXTINGUISHER
ROOF MANIFOLD (3-WAY)
SPRINKLER CONTROL VALVE ASSEMBLY
VALVE ASSEMBLYAC - ALARM CHECKDR - DRY PIPEPA - PRE ACTION
CONNECT TO EXISTING
DISCONNECT FROM EXISTING
FIRE DEPARTMENT SIAMESE CONNECTION (WALL MOUNTED)
EXISTING FIRE HYDRANT
NEW FIRE HYDRANT
TEMPERATURE AND PRESSURE RELIEF VALVE
PLUG VALVE
MIXING VALVE
RELIEF VALVE
BALL VALVE
GATE VALVE
GLOBE VALVE
OUTSIDE SCREW & YOKE (OS & Y) VALVE
CHECK VALVE
PRESSURE REDUCING VALVE (PRV)
SOLENOID VALVE
FLOAT VALVE
Y STRAINER w/BLOW-OFF VALVE
REDUCED PRESSURE DETECTOR ASSEMBLY
DOUBLE CHECK DETECTOR ASSEMBLY
HYDRAULIC REF. POINTS # = ELEMENT, # = NODE
TAMPER SWITCH
WATERFLOW SWITCH
PRESSURE GAUGE w/GAUGE COCK
RISER DESIGNATION:X = RISER SERVICE; # = RISER NUMBER
EXTEND EXISTING SPRINKLER PIPING TO NEW SPRINKLER HEAD
DSP
RPDA
DCDA
X#
#
F
PA
DR
S
S
#
FE-X
FE-X
X
FE-X
FP-2-3
XXX-XX-XX
SECOND FLOOR
(REFER TO SPECIFIC TRADE LIST)
EQUIPMENT TAG NUMBERFLOOR DESIGNATIONEQUIPMENT DESIGNATION
FIRE PUMP(REFER TO LIST)
UNIT NUMBER 3
FP EQUIPMENT DESIGNATIONS
1. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL FIRE PROTECTION DRAWINGS.
2. ALL WORK IS NEW UNLESS OTHERWISE NOTED.
3. ALL FIRE PROTECTION WORK SHALL BE IN ACCORDANCE WITH THE CURRENT FIRE PROTECTION CODEAND ALL APPLICABLE LOCAL CODES AND DRAWINGS.
4. PROVIDE WET-PIPE SPRINKLERS IN ALL AREAS.
5. SECURE WATER FLOW TEST DATA TAKEN FROM FIRE HYDRANTS NEAREST SITE. IF RECENT FLOW TESTDATA IS NOT AVAILABLE FROM CITY RECORDS, MAKE NECESSARY TESTS AS REQUIRED BY NFPASTANDARDS TO DETERMINE CHARACTER OF WATER SUPPLY. MINIMUM OF 20 PSI DROP IN PRESSUREBETWEEN STATIC AND RESIDUAL PRESSURE SHALL BE REQUIRED IN ORDER TO OBTAIN ACCURATEDATA.
6. SPRINKLER SYSTEM SHALL BE HYDRAULICALLY CALCULATED.
7. ADD 10% CONTINGENCY FACTOR TO HYDRAULIC CALCULATIONS.
8. EXACT LOCATION OF SPRINKLER HEADS IN FINISHED AREAS WITH SUSPENDED CEILING SHALL BE ASINDICATED ON REFLECTED CEILING PLANS.
9. MINIMUM PRESSURE AT END SPRINKLER HEAD 7 PSI.
10. EQUIVALENT FITTING LENGTHS USED IN HYDRAULIC CALCULATIONS SHALL BE IN ACCORDANCE WITHNFPA STANDARD NO. 13 AND FACTORY MUTUAL 0.5 2-8N.
11. MAXIMUM FLOW VELOCITY SHALL NOT EXCEED 20 F.P.S.
12. ALL AUTOMATIC SPRINKLER HEADS, PIPE FITTINGS, PIPE HANGERS, AUTOMATIC CONTROL VALVES ANDMANUAL CONTROL VALVES SHALL BE UL LISTED AND BEAR FACTORY MUTUAL APPROVAL AND SHALL BEAPPROVED BY THE ENGINEER PRIOR TO INSTALLATION.
13. ALL EXPOSED PIPE, FITTINGS, HANGERS AND SUPPLEMENTARY STEEL SHALL BE PAINTED.
14. ENDS OF ALL CROSS MAINS SHALL BE PROVIDED WITH THREADED FLUSHING CONNECTION NO MORETHAN 2 INCHES IN DIAMETER.
15. PROVIDE AUXILIARY DRAINS FOR ALL PIPING BELOW DUCT SPRINKLERS AND OPEN TRAPPED SECTIONS.PIPING TO ONE SINGLE SPRINKLER IS EXCLUDED.
16. PROVIDE FLUSHING CONNECTIONS WHERE REQUIRED BY NFPA AND F.M.
17. COORDINATE WITH OWNER FOR ALL SHUTDOWNS.
18. PROVIDE TEST CONNECTIONS AT HIGHEST POINT OF MAIN PORTION OF EACH SPRINKLER SYSTEM, WITH1" PIPE AND VALVE. TEST PIPE SHALL BE CONNECTED TO SPRINKLER PIPE AT LEAST 1-1/4" IN SIZE ANDSHALL DISCHARGE OUTSIDE BUILDING OR THROUGH 1/2" SMOOTH BORE BRASS OUTLET, WHERE IT CANBE EASILY SEEN.
19. PROVIDE ADDITIONAL HEADS UNDER DUCTWORK LARGER THAN 48" WIDE.
20. THE REUSE OF EXISTING SPRINKLER HEADS SHALL BE PROHIBITED.
21. NEW SPRINKLER HEAD TYPE AND TEMPERATURE RATING SHALL BE IN ACCORDANCE WITH SCHEDULEUNLESS NOTED OTHERWISE AND/OR REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
22. COORDINATE ALL PIPE PENETRATIONS AND CORING WITH STRUCTURAL ENGINEER AND INACCORDANCE WITH DIVISION 01.
23. REFER TO ARCHITECTURAL DRAWINGS FOR ALL CEILING RELATED WORK.
24. COORDINATE ALL NEW FIRE PROTECTION WORK WITH ALL NEW DUCTWORK, PIPING AND UTILITIES OFANY SYSTEMS. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE INTENT OF THE DESIGN. REROUTE ANYPIPING AROUND EXISTING AND/OR NEW SYSTEMS INCLUDING ALL REQUIRED FITTINGS AND SUPPORTSTO MAKE THE INSTALLATION OF THE PIPING AND SPRINKLER HEADS POSSIBLE. RESEAL ANY FIREAND/OR SMOKE RATED PENETRATIONS THAT HAVE BEEN AFFECTED AS A RESULT OF THEMODIFICATION.
25. ALL COMPONENTS USED IN FIRE PROTECTION SYSTEMS SHALL BE IN ACCORDANCE WITH THE OWNER'SGUIDELINES, STANDARDS AND SPECIFICATIONS.
26. WATER SUPPLY INFORMATION TO BE VERIFIED BY FLOW TEST.
27. REPAIR AND PATCH ANY PENETRATIONS CREATED AS PART OF THIS SCOPE OF WORK. MATCH NEWFINISHES WITH ARCHITECTURAL PLANS.
28. COORDINATE INSTALLATION OF PIPING AND SPRINKLER HEADS WITH ALL OTHER TRADES.
29. ALL EXCAVATION AND BACKFILL REQUIRED FOR FIRE PROTECTION WORK SHALL BE BY THE FIREPROTECTION CONTRACTOR. REFER TO SITE SPECIFICATIONS FOR MORE INFORMATION ONEXCAVATION AND BACKFILL REQUIREMENTS.
30. PAINTING OF ALL ARCHITECTURALLY EXPOSED PIPING WORK SHALL BE BY THE GENERAL CONTRACTOR.PAINTING OF ANY NON-ARCHITECTURALLY EXPOSED PIPING SHALL BE BY THIS TRADES CONTRACTOR.REFER TO DIVISION 9 PAINTING.
31. FIRESTOPPING FOR THE WORK INCLUDED IN THESE DOCUMENTS, SHALL BE FURNISHED AND INSTALLEDBY THE FIRE PROTECTION CONTRACTOR. REFER TO DIVISION 7 FIRESTOPPING.
32. SLEEVES THAT ARE REQUIRED FOR THIS PROJECTS SHALL BE FURNISHED BY THE FIRE PROTECTIONCONTRACTOR AND INSTALLED BY THE GENERAL CONTRACTOR. COORDINATE THE LOCATION OF THESLEEVES WITH THE GENERAL CONTRACTOR.
FIRE PROTECTION GENERAL NOTES SPRINKLER HEAD SCHEDULE
MODEL NUMBER
MANUFACTURER
STAR
TYPE
EXIST
SPRI
NKLE
RHD
FLUS
HPE
NDEN
T
REMO
VED/
RELO
CATE
DEX
ISTSP
RHO
TOBE
EXTE
NDED
COVE
RAGE
QUIC
KRES
PONS
E
INTE
RMED
IATES
HIEL
D
(CHR
OMEF
INISH
)SID
EWAL
L
FLUS
HCO
NCEA
LED
PLAT
ESPK
R.
DESIG
NATIO
N
SEMI
-REC
ESSE
D
UPRI
GHT
PEND
ENT
DRY
CENT
RAL
RELIA
BLE
GRIN
NELL
VIKIN
G
REMARKS
A
NOTES:
2. PROVIDE ESCUTCHEONS WHEN PENETRATING EXPOSED WALL.
1. EXPOSED UPRIGHT HEADS IN OCCUPIED SPACES SHALL BE CHROME FINISH.
3. PROVIDE SPRINKLER GUARDS AT ALL HEADS 7'-0" AND LOWER.
4. COORDINATE COLOR SELECTION WITH ARCHITECT.A. SPRINKLER AND ESCUTCHEON TO BE WHITEB. SPRINKLER HEAD TO BE WHITEC. COVER PLATE TO BE WHITED. SPRINKLER AND SHIELD IN EXPOSED IN COORIDORS TO BE WHITEE. SPRINKLER AND SHIELD IN WOOD SLOT CEILING TO BE BLACK
F1FR56 INTERMEDIATE LEVELW/ SHIELD
F1FR56
F1FR56
G4A
DH56 DRY
K=5.6, 1/2" ORIFICE
K=5.6, 1/2" ORIFICE
K=5.6, 1/2" ORIFICE165°F RATING
155°F RATING
155°F RATING
K=5.6, 1/2" ORIFICE155°F RATING
F1FR56 K=5.6, 1/2" ORIFICE155°F RATING
K=5.6, 1/2" ORIFICE155°F RATING
SEE NOTE 4C.
SEE NOTE 4B.
SEE NOTE 4D AND 4E
SEE NOTE 4A.
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
F-000G150004-000
FIRE PROTECTION COVERSHEET
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
FIRE PROTECTION ABBREVIATIONSABD AUTOMATIC BALL DRIPAD AREA DRAINAFF ABOVE FINISHED FLOORATS AUTOMATIC TRANSFER SWITCH
BOP BOTTOM OF PIPE
CFM CUBIC FEET PER MINUTECV CHECK VALVE
DIA DIAMETERDN DOWN (PENETRATES FLOOR SLAB)DR DRAIN
(E) EXISTING(ER) EXISTING TO BE REMOVED(ERR) EXISTING TO BE REMOVED & RELOCATED
FD FLOOR DRAINFHC FIRE HOSE CABINETFHR FIRE HOSE RACKFHV FIRE HOSE VALVEFHVC FIRE HOSE VALVE CABINETFL FLOORFP FIRE PUMPFSP FIRE STANDPIPEFT FEET
GAL GALLONSGC GENERAL CONTRACTORGPM GALLONS PER MINUTEGV GATE VALVE
HD HEAT DETECTOR
ID INSIDE DIAMETERIN INCH
JP JOCKEY PUMP
MAX MAXIMUMMIN MINIMUM
NC NORMALLY CLOSENIC NOT IN THIS CONTRACTNO NORMALLY OPENNTS NOT TO SCALE
OD OUTSIDE DIAMETEROS&Y OUTSIDE SCREW & YOKE GATE VALVE
PRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCH (GAUGE)PSIA POUNDS PER SQUARE INCH (ABSOLUTE)
(RE) RELOCATED EXISTING(RRO) EXISTING TO REMOVED AND RETURN TO OWNER
SD SMOKE DETECTORSPKR SPRINKLER
TOP TOP OF PIPETS TAMPER SWITCH
UON UNLESS OTHERWISE NOTEDUP UP (PENETRATES FLOOR SLAB)
WFS WATER FLOW SWITCH
Z ZONE
NO. ISSUE DATE: DESCRIPTION
4"SP
DCDA
ALARM CHECKVALVE ASSEMBLY
6" TRANSITION TO 4" SPRINKLER SERVICE.REFER TO PLUMBING DRAWINGS FORCONTINUATION.
F14" RISER UP
4" TO 5" STORZ FDCREFER TO SITE CIVILPLANS FOR CONTINUATION
CHECK VALVE
CAP FOR FUTURE
RISER VALVE
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
3"SP 3"SP
4"SP
4"SP
1"SP
1"SP
1"SP
1"SP
1"SP
1"SP
11/4"
SP
11/4"
SP
4"SP
1"SP
1"SP
1"SP
1"SP
11/4"
SP
1
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
F-100G150004-000
FIRE PROTECTION LOWERLEVEL PLAN
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN
DRAWING KEY NOTES:
COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.1
NO. ISSUE DATE: DESCRIPTION
F1 4" RISER DN
(2) 2 1/2"FDC
4"DN
4"SP 4"SP 4"SP4"SPRUN SPRINKLER PIPE HIGHAND TIGHT TO STEEL BEAM
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
VEST.V-1
ALCOVEL101-5
WOMEN'S143
PASSAGE104
MEN'S142
ALCOVEL101-6JANITOR
141
MECHANICAL141.1
FAMILYTOILET
144
STORAGE140.1
PASSAGEL101-7
VEST.V-2
CLASSROOM/PRESENTATIONROOM
140
V.P. OFFICE112A
SMALL CONF.105
STORAGE103.1
OFFICE112
PASSAGEL101-1
OFFICE118
OFFICE114
OFFICE116
OFFICE110
OFFICE108
OFFICE104
CORRIDORC 1-1
CORRIDORC 1-2
BREAK ROOM107
STORAGE119
ELEC. RM.121
COFFEESTATIONL101-3
STORAGE103.2
ADMISSIONSOPEN OFFICE
106
HOUSINGOPEN OFFICE
130
OFFICE128
OFFICE126
OFFICE124
OFFICE122
MARKETINGOPEN OFFICE
120
SMALL CONF.115
CONFERENCE117
I.T. ROOM123
CALL CENTER109
CORRIDORC 1-3
OFFICE102
WORK ROOM111
RESOURCEROOM
103
RECEPT.L101-2
STUDENTWORK SPACE
113
LOBBYL101
11/4"
SP
11/4"
SP1"S
P
1"SP
1"SP
1"SP
1"SP
1"SP
1"SP
11/4"
SP
11/4"
SP1"S
P1"SP
1"SP
1"SP
11/2"
SP
11/2"
SP3"SP
3"SP
3"SP 3"SP 3"SP
1 1/2"SP1 1/4"SP
1"SP 1 1/4"SP
1 1/4"SP
1 1/4"SP
1"SP1"SP
1"SP1"SP
1 1/2"SP
1 1/2"SP
1"SP
1 1/2"SP
1 1/2"SP
1 1/2"SP
1 1/2"SP
1 1/2"SP
1 1/4"SP1"SP
1"SP
1"SP
11/2"
SP2"S
P11
/2"SP
1"SP1"SP1"SP
11/2"
SP
1"SP
1"SP
1"SP 1"SP
11/4"
SP2"S
P2"S
P 1"SP
1"SP
1 1/4"SP
1"SP 1"SP
11/2"
SP2"S
P
1"SP1"SP
1"SP 1"SP
2"SP
11/4"
SP11
/2"SP
1"SP
1"SP
1"SP
1"SP
1"SP 1 1/4"SP
11/4"
SP11
/4"SP
1"SP1"SP 1"SP 1"SP
1"SP 11/2"
SP11
/4"SP
1"SP
1"SP
11/4"
SP11
/2"SP
11/4"
SP1"S
P
1"SP
2"SP
1 1/2"SP
11/2"
SP
1"SP
1"SP
1"SP
2"SP
1"SP 1"SPA A
AA
A A
AA
A A
AA
A A A
1
1
11
11
11
1
1
1
INPECTORS TEST DRAIN
2
3 4
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
F-101G150004-000
FIRE PROTECTION GROUNDFLOOR PLAN
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN
DRAWING KEY NOTES:
PROVIDE SPRINKLER COVERAGE ABOVE AND BELOW COMBUSTIBLE WOOD CEILING.REFER TO DETAIL ON DRAWING F-200.
COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.
BASE: PROVIDE CONCEALED SPRINKLER PIPING AND SPRINKLER HEADS IN EPIC DECK CEILING STRUCTURE.COORDINATE WITH ARCHITECTURAL CEILING DETAILS AND DRAWINGS IN THIS AREA.
1
2
3
NO. ISSUE DATE: DESCRIPTION
DCDA
WITHOUT INSULATIONPIPE PENETRATION
PIPE TO BE CENTERED IN SLEEVE - DONOT SUPPORT PIPE FROM SLEEVE
TERMINAL SLEEVE FLUSH WITHFINISHED WALL SURFACES
SEALANT (SEE SPEC.)
PIPE SLEEVE
ESCUTCHEON PLATE FLUSH AGAINSTWALL AND OF SIZE TO COMPLETELYCOVER OPENING (TYPICAL BOTHSIDES OF WALL)
FINISHED WALL SURFACE
PIPE SLEEVE THRU FLOOR SLAB
SEALENT
FLOOR SLAB
RISER CLAP
PLAN VIEW
UPRIGHT SPRINKLERHEAD CONNECTION
UPRIGHT SPRINKLER HEAD
BRANCH LINE
1%%188" BRANCH TEE
1%%188" NIPPLE
1"x 1/2" REDUCER
SLAB ABOVE
SPRINKLER HEAD CONNECTION
& DWG FOR TYPE)(SEE SPECIFICATIONSPRINKLER HEAD
SUSPENDED CEILING
(IF REQUIRED)1" x 1/2" COUPLING
1" DROP NIPPLE
BRANCH PIPE
WET SYSTEMINSPECTOR'S TEST CONNECTION
WALLEXTERIOR
SPRINKLERFLOW EQUIVALENT TO ONERESISTANT OUTLET GIVINGSMOOTH BORE CORROSION
ABOVE FLOORNOT OVER 7 FT.1 IN. GLOBE VALVE
1 IN.
1 IN. BRANCH LINE 1 IN. PLUG
PITCH
SLEEVE ANDSEALANT
INSTALLATION SCHEMATICTYPICAL ALARM CHECK VALVE
PS
PG
PG
TS
TO SYSTEM
TO WMG
ORIFICE DRAIN
PROVIDE FUNNEL ANDEXTEND PIPE TO DRAIN
EXTEND PIPE TO DRAINBY-PASS WITHCHECK VALVE
FROM SUPPLY
FIRE ALARM TEST PIPEWITH VALVE (N.C.)
ALARM CHECK VALVE
TO ALARM PANEL(BY OTHERS)
TO ALARM PANEL(BY OTHERS)
SCALE:
FOR SPACES WITH CONCEALED COMBUSTILE CONSTRUCTIONTYPICAL SPRINKLER HEAD (W/ COVER PLATE) INSTALLATIONS
BRANCH TEE
ESCUTCHEON
1"x
NIPPLE
BRANCH LINE
CONSTRUCTIONTO PROTECT COMBUSTIBLEUPRIGHT SPRINKLER HEAD
HUNG CEILING
1/2" REDUCER
SPRINKLER HEAD(COLOR AS PER SCHEDULE)
T
T T T
T
T
1 SPRINKLER RISER DIAGRAMNONE
TYPICAL SPRINKLER HEAD IN EPIC DECK DETAIL
AC
ROOF
GROUND FLOOR
LOWER LEVEL
ROOF
GROUND FLOOR
LOWER LEVEL
(2) 2 1/2" FDC
6" COMBINED DOMESTIC AND SPRINKLERWATER SERVICE. 5'-0" FROM BUILDING.FOR CONTINUATION REFER TO SITE/CIVILDRAWINGS.
4"CHECK VALVE
4"
ALARM CHECK VALVE
4"
4"
3" TO SPRINKLERS
2 1/2" DOMESTIC WATER SERVICE.FOR CONTINUATION REFER TOPLUMBING DRAWINGS.
BY FC BY PC
4"
2 1/2"
6"
F1
RISER VALVE
4"TO SPRINKLERS
4"
EPIC DECKSPRINKLER HEAD(COLOR TO BEWHITE)
SPRINKLER PIPEW/EPIC DECK FASTNER ROOF DECK
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
F-200G150004-000
FIRE PROTECTION RISERDIAGRAMS & DETAILS
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION
SECURITY SYMBOL LISTSECURITY SYMBOLS
SECURITY CAMERA FIXEDX = FLOORY = TYPEXX = NUMBER
SECURITY CAMERA PTZX = FLOORY = TYPEXX = NUMBER
CARD READERB = BIOMETRICC = PROXIMITY/KEYPADM = MAGNETICP = PROXIMITY
DOOR CONTACT
WINDOW CONTACT
DURESS ALARM
INTERCOMM = MASTER STATIONS = SUB STATION
VIDEO INTERCOMM = MASTER STATIONS = SUB STATION
GUEST LOCKS = STAND ALONEIR = INFRA REDRF = RADIO FREQUENCY
REQUEST TO EXITM = MOTIONPB = PUSH BUTTON
DELAYED EGRESS
DOOR RELEASE
LCD SECURITY MONITOR
DIGITAL VIDEO RECORDER
NETWORK VIDEO RECORDER
GLASS BREAK SENSOR
LOCAL ALARM SOUNDER
ELECTRIC DOOR STRIKE
ELECTRIC LOCKSET WITH REX SWITCHFL = FAIL SECURE (DEFAULT)FS = FAIL SAFE
TRANSFER HINGE (POWER & RX)
ELECTROMAGNETIC LOCKS = SINGLED = DOUBLE
PANIC BUTTON
MOTION DETECTOR
FIRE RELAY (CLASS "E" FIRE ALARM)
FIBER OPTIC TRANSMITTER
FIBER OPTIC RECEIVER
IP CONVERTER
JUNCTION BOX - 4"Lx4"Wx4"D
JUNCTION BOX - 6"Lx6"Wx4"D
POWER SUPPLY
ANNUNCIATOR
EMERGENCY TELEPHONE
ACCESS CONTROL SERVER
PATCH PANEL
CLOSED CIRCUIT TELEVISION POWER SUPPLY
UNINTERUPTIBLE POWER SUPPLY
POWER SYMBOLSTRANSFORMER
20A, 125V DUPLEX RECEPTACLE - FLUSH WALL MOUNTED
20A, 125V QUADRUPLEX RECEPTACLE - FLUSH WALLMOUNTED
20A, 125V ISOLATED GROUND, DUPLEX RECEPTACLE, FLUSHFLOOR MOUNTED.
20A, 125V DUPLEX RECEPTACLE FLUSH WALL MOUNTED.GFI TYPE.
20A, 125V EMERGENCY DUPLEX RECEPTACLE.FLUSH WALL MOUNTED
20A, 125V DUPLEX RECEPTACLE SURFACE MOUNTED
20A, 125V SURGE SUPPRESSION DUPLEX RECEPTACLE.FLUSH WALL MOUNTED
FLUSH FLOOR MOUNTED JUNCTION BOX OR POKE-THRUFOR ELECTRIFIED FURNITURE POWER FEED
C = VOICE/DATA FEED
20A, 125V DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED
20A, 125V QUADRUPLEX RECEPTACLE FLUSH FLOORMOUNTED
SPECIAL PURPOSE RECEPTACLE - FLUSH WALL MOUNTEDA = TYPE
SPECIAL PURPOSE RECEPTACLE - FLUSH FLOOR MOUNTEDA = INDICATES TYPE
FLUSH FLOOR MOUNTED 20A, 125V DUPLEX RECEPTACLE
FLUSH FLOOR MOUNTED 20A, 125V QUADRUPLEXRECEPTACLE
FLUSH FLOOR MOUNTED JUNCTION BOX OR POKE-THRUFOR ELECTRIFIED FURNITURE POWER FEED.
PEDESTAL MOUNTED SPECIAL PURPOSE RECEPTACLELETTER INDICATES TYPE
PEDESTAL MOUNTED COMBINATION VOICE/DATA & POWEROUTLET
CEILING MOUNTED JUNCTION BOX WITH FINAL EQUIPMENTCONNECTION
FLUSH WALL MOUNTED JUNCTION BOX WITH FINALEQUIPMENT CONNECTION
FLUSH FLOOR MOUNTED JUNCTION BOX
PULLBOX
POWER POLE
EXISTING CONDUIT TO BE REMOVED
EXISTING CONDUIT/EQUIPMENT TO REMAIN
NEW CONCEALED CONDUIT
NEW EXPOSED CONDUIT
NEW UNDERGROUND/IN SLAB CONDUIT
NEW EMERGENCY CONDUIT
CONDUIT TURNING UP
CONDUIT TURNING DOWN
CONDUIT STUB-UP WITH FLEXIBLE EQUIPMENTCONNECTION
FLEXIBLE EQUIPMENT CONNECTION
CAPPED CONDUIT
HOMERUN - NUMERAL WHERE USED INDICATES CIRCUITNUMBER FOR REFERENCE ONLY.
HOMERUN - NUMERAL WHERE USED INDICATES CIRCUITNUMBER FOR REFERENCE ONLY
UNDERFLOOR DUCT WITH COMPARTMENT JUNCTION BOXT = TELEPHONEP = POWERS = SIGNAL
CABLE TRAY
SECTION A# = DRAWING NUMBER
a
C
A
A
T
13,5,
1
A
J
J
J
P
S
TP
FIX
PTZ
CR
DC
WC
DA
IC
VI
GL
RX
DE
DR
MON
DVR
NVR
GB
LA
DS
EL
TH
ML
PB
MD
K
FOT
FOR
IPC
J1
PS
AN
ET
ACS
CCTVPS
PP
UPSPS
J2
X-Y-XX
X-Y-XX
X
X
X
X
X
X
X
A
#
SECURITY DEVICE DESIGNATIONS
X = FLOOR NUMBERY = DEVICE TYPE:
A = ACCESSC = CAMERAL = LOCKM = MONITORING
## = SEQUENTIAL NUMBER
X-Y-##
1. ALL WORK SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, NFPA,UL, ADA AND ALL OTHER GOVERNING AGENCIES HAVING JURISDICTION.
2. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK. FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OF OTHER TRADES TO VERIFY SPACECONDITIONS.MAINTAIN HEADROOM AND SPACE CONDITIONS.
3. VERIFY LOCATIONS OF VIDEO CAMERAS IN FINISHED SPACES WITH ARCHITECTURAL DRAWINGS OF INTERIORDETAILS AND FINISH. PROVIDE BACK BOXES AND CONDUIT RUNS TO THE NEAREST ACCESSIBLE
CEILING ON THE SIDE OF THE BUILDING WITH THE IDF ROOM FOR ALL CAMERAS. CAMERAS ANDASSOCIATED WIRING SHALL BE INSTALLED BY A SEPERATE CONTRACTOR.
4. FIRESTOPPING SHALL BE INSTALLED WHENEVER WIRING OR RACEWAYS CROSS FIRE RATED CONSTRUCTION.
5. ANY DAMAGE TO PARTITIONS, FLOORS, CEILINGS OR ANY PART OF THE BUILDING OR EQUIPMENTCAUSED BY THE WORK OF THE CONTRACTOR SHALL BE MADE GOOD AT NO ADDITIONAL EXPENSE TO THEOWNER.
6. ALL CUTTING AND PATHING SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR.
7. CONTRACTOR, BEFORE INSTALLING ANY OF THE WORK, SHALL SEE THAT IT DOES NOT INTERFERE WITHCLEARANCES REQUIRED FOR FINISHED COLUMNS, HUNG CEILINGS, PLASTER, PARTITIONS, WALLS, ETC., ASSHOWN IN THE ARCHITECTURAL DRAWINGS AND DETAILS. IF ANY WORK IS SO INSTALLED AND IT LATERDEVELOPS THAT SUCH DETAILS OR DESIGN CANNOT BE FOLLOWED, CONTRACTOR AT HIS OWN EXPENSESHALL MAKE SUCH CHANGES IN THE WORK AS DIRECTED BY THE ARCHITECT, AS WELL AS TO PERMIT THEINSTALLATION OF THE ARCHITECTURAL WORK AS SHOWN ON THE PLANS AND DETAILS.
8. FINAL ACCEPTANCE IS TO BE MADE AFTER THE CONTRACTOR HAS DEMONSTRATED THAT THE WORKFULLFILLS THE REQUIREMENTS OF THE PLANS AND SPECIFICATIONS.
9. CONTRACTOR SHALL PROVIDE COMPLETE AS-BUILT DOCUMENTATION AND ACAD DRAWINGS.
10. MECHANICAL DOOR LOCK HARDWARE BY OTHERS. COORDINATE WITH ARCHITECT AND GENERAL CONTRACTOR.
11. COORDINATE MOUNTING OF CARD READERS WITH GENERAL CONTRACTOR AT LOCATIONS WHERE THECARD READERS ARE LOCATED ON MULLIONS.
12. COORDINATE EXACT LOCATIONS AND FINISHES OF DEVICES WITH ARCHITECT.
SECURITY GENERAL NOTES0
2'
4'
6'
08
'1
6'
24
'0
6"
9"
3"
01
'6
"1
-6"
01
/2
'1
'2
'0
1'
2'
3'
01
'2
'4
'0
2'
4'
8'
4'
08
'1
6'
08
'1
6'
32
'
SHEET NUMBER
SFA PROJECT NUMBER
FULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SC
ALE
: 1/
16
" =
1'-0
"S
CA
LE: 1
/8
" =
1'-0
"S
CA
LE: 1
/4
" =
1'-0
"S
CA
LE: 1
/2
" =
1'-0
"S
CA
LE: 3
/4
" =
1'-0
"S
CA
LE: 1
" =
1'-0
"S
CA
LE: 1
1/
2"
= 1
'-0"
SC
ALE
: 3"
= 1
'-0"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SC
ALE
: 3/
32
" =
1'-0
"S
CA
LE: 3
/8
" =
1'-0
"
PROJECT No: MI-1105
C:\
Revi
t Lo
cal F
iles\
G1
50
00
4-0
00
- M
ille
rsvi
lle -
MEP
15
_C
entr
al_
ska
pla
n.rv
t
SC-000G150004-000
SECURITY COVER SHEET
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SECURITY ABBREVIATIONS
N NEUTRAL
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NP NETWORK PROTECTOR
NTS NOT TO SCALE
OC ON CENTER
OCB OIL CIRCUIT BREAKER
OD OUTSIDE DIAMETER
P POLE
PA PUBLIC ADDRESS
PAP PLUMBING ALARM PANEL
PB PULL BOX
PBS PUSH BUTTON SWITCH
PHC PIPE HEATING CABLE
PNL PANEL
PR PRINTER
PS PRESSURE SWITCH
PT POTENTIAL TRANSFORMER
PWR POWER
ø PHASE
(RE) RELOCATED EXISTING
(RRO) EXISTING TO BE REMOVED AND RETURN TO OWNER
RCS REMOTE CONTROL SWITCH
RDCP REMOTE DATA COLLECTION PANEL
RECEPT, REC RECEPTACLE
REF REFRIGERATOR
REQ REQUIRED
RFL RAISED FLOOR
RG ROOM GROUND POINT
RM ROOM
RO RACEWAY ONLY
RP REFERENCE GROUND POINT
SAP SPRINKLER ALARM PANEL
SBST SUBSTATION
SCH SCHEDULE
SD SMOKE DETECTOR
SDP SMOKE DETECTION PANEL
SE SINGLE ENDED SUBSTATION
SECT SECTION
SIG SIGNAL
SN SOLID NEUTRAL
SP SINGLE POLE
SPEC SPECIFICATION
SPKLR SPRINKLER
SPKR SPEAKER
SV SOLENOID VALVE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
SYS SYSTEMS
TB TROUBLE BELL
TBD TO BE DETERMINED
TEL TELEPHONE
TEMP TEMPERATURE
THERM THERMOSTAT
TLBD TERMINAL BOARD
TP TAMPER PROOF
TRANSF, XFMR TRANSFORMER
TS TAMPER SWITCH
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UH UNIT HEATER
UNF UNFUSED
UON UNLESS OTHERWISE NOTED
V VOLT OR VOLTAGE
VA VOLT AMPERE
VFD VARIABLE FREQUENCY DRIVE
VM VOLTMETER
VP VAPORPROOF
W WATT
WFS WATER FLOW SWITCH
WHM WATT HOUR METER
WP WEATHERPROOF
WT WATERTIGHT
XP EXPLOSION PROOF
+ SPECIAL MOUNTING HEIGHT. COORDINATE LOCATION WITH ARCHITECTURALELEVATIONS
1P SINGLE POLE
2P TWO POLE
3P THREE POLE
A AMPERE
AC ABOVE COUNTER
ACB AIR CIRCUIT BREAKER
AFF ABOVE FINSIHED FLOOR
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALM ALARM
AMM AMMETER
AQST AQUASTAT
ARF ABOVE RAISED FLOOR
ASYM ASYMMETRICAL
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BG BREAK GLASS SWITCH
BIL BASIC IMPULSE LEVEL
BLDG BUILDING
C CONDUIT
CAB CABINET
CAT CATALOG
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CLOS CLOSET
CNTL CONTROL
CO CONDUIT ONLY
COMM COMMUNICATION
CONN CONNECTED
CONT CONTINUATION
CT CURRENT TRANSFORMER
CU COPPER
CUH CABINET UNIT HEATER
DB DECIBEL
DE DOUBLE ENDED SUBSTATION
DEG DEGREE
DF DRINKING FOUNTAIN
DIA DIAMETER
DISC DISCONNECT
DIV DIVISION
DN DOWN
DP DISTRIBUTION PANEL BOARD
DT DUST TIGHT
DWG DRAWING
°C DEGREE CELSIUS
°F DEGREE FAHRENHEIT
(E) EXISTING TO REMAIN
(ER) EXISTING TO BE REMOVED
(ERR) EXISTING TO BE REMOVED & RELOCATED
EA EACH
EC ELECTRICAL CONTRACTOR
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMER, EM EMERGENCY
EQUIP EQUIPMENT
ERC ELECTRIC REHEAT COIL
EWC ELECTRIC WATER COOLER
EXIST, EX EXISTING
EXT EXTERIOR
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAP FIRE ALARM ANNUNCIATOR PANEL
FBO FURNISHED BY OTHER DIVISION OF WORK
FCU FAN COIL UNIT
FDR FEEDER
FDS FUSED DISCONNECT SWITCH
FIXT FIXTURE
FL FLOOR
FLA FULL LOAD AMPERES
FLEX FLEXIBLE
FLUOR FLUORESCENT
FM FLOOR MACHINE
FRZ FREEZER
FSP FAN SHUTDOWN PANEL
FT FEET OR FOOT
G GROUND
GEN GENERATOR
GFI GROUND FAULT INTERRUPTER
HC HUNG CEILING
HH HAND HOLE
HID HIGH INTENSITY DISCHARGE
HN HALF NEUTRAL
HP HORSE POWER
HV HIGH VOLTAGE
HZ HERTZ
IC INTERRUPTING CAPACITY
ID INSIDE DIAMETER
INCAND INCANDESCENT
INST INSTRUMENT
IPC ISOLATED POWER CENTER
IPX ISOLATED POWER CENTER-X-RAY
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILS
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATT
KWH KILOWATT HOUR
LCP LOCAL CONTROL PANEL
LIM LINE ISOLATION MONITOR
LTG LIGHTING
MAP MECHANICAL ALARM PANEL
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPERES
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MER MECHANICAL EQUIPMENT ROOM
MFS MAIN FUSED SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MLO MAIN LUG ONLY
MOPD,MOCP MAXIMUM OVERCURRENT PROTECTION
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MUFS MAIN UNFUSED SWITCH
NO. ISSUE DATE: DESCRIPTION
CR
CR
CRCR
CR
CR
LA
LA
LACR
LA
LA
LA
CR
CR
PB
PB
PB
HW#1
4/SC-300
HW#1
4/SC-300
HW#7
8/SC-300
HW#16
10/SC-300
HW#7
8/SC-300
HW#2
5/SC-300
SEE TELECOM
DRAWINGS FOR
MORE
INFORMATION
ACCESS CONTROL PANEL
AND POWER SUPPLY -SEE
ELEV. DETAIL 1/SC-300 1
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
VEST.
V-1
ALCOVE
L101-5
WOMEN'S
143
PASSAGE
104
MEN'S
142
ALCOVE
L101-6JANITOR
141
MECHANICAL
141.1
FAMILY
TOILET
144
STORAGE
140.1
PASSAGE
L101-7
VEST.
V-2
CLASSROOM/PRESENTATION
ROOM
140
V.P. OFFICE
112A
SMALL CONF.
105
STORAGE
103.1
OFFICE
112
PASSAGE
L101-1
OFFICE
118
OFFICE
114
OFFICE
116
OFFICE
110
OFFICE
108
OFFICE
104
CORRIDOR
C 1-1
CORRIDOR
C 1-2BREAK ROOM
107
STORAGE
119
ELEC. RM.
121
COFFEE
STATION
L101-3
STORAGE
103.2
ADMISSIONS
OPEN OFFICE
106
HOUSING
OPEN OFFICE
130
OFFICE
128
OFFICE
126
OFFICE
124
OFFICE
122
MARKETING
OPEN OFFICE
120
SMALL CONF.
115
CONFERENCE
117
I.T. ROOM
123
CALL CENTER
109
CORRIDOR
C 1-3
OFFICE
102
WORK ROOM
111
RESOURCE
ROOM
103
RECEPT.
L101-2
STUDENT
WORK SPACE
113
LOBBY
L101
HW#13
9/SC-300
HW#5
6/SC-300
HW#6
7/SC-300
5
HW#3
4/SC-300
3
ARCHITECTURAL BOLLARD
BY OTHERS
2
4
TO DOOR JUNCTION BOX -
SEE DOOR DETAIL 4/SC-300
4
5
HW#3
4/SC-300
TO DOOR JUNCTION BOX -
SEE DOOR DETAIL 4/SC-300
3
ARCHITECTURAL BOLLARD
BY OTHERS
2
02'
4'
6'
08'
16'
24'
06"
9"
3"
01'
6"
1-6"
01/2'
1'
2'
01'
2'
3'
01'
2'
4'
02'
4'
8'
4'
08'
16'
08'
16'
32'
SHEET NUMBER
SFA PROJECT NUMBER
FULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCALE: 1/16" = 1'-0"
SCALE: 1/8" = 1'-0"
SCALE: 1/4" = 1'-0"
SCALE: 1/2" = 1'-0"
SCALE: 3/4" = 1'-0"
SCALE: 1" = 1'-0"
SCALE: 1 1/2" = 1'-0"
SCALE: 3" = 1'-0"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCALE: 3/32" = 1'-0"
SCALE: 3/8" = 1'-0"
PROJECT No: MI-1105
C:\Revit Local Files\G150004-000 - M
illersville -
MEP15_Central_skaplan.rvt
SC-100G150004-000
SECURITY GROUND FLOORPLAN
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1
GROUND FLOOR PLAN
DRAWING NOTES:
1. FOR SECURITY SYMBOLS, ABBREVIATIONS, AND OVERALL GENERAL NOTES, REFER TO
DRAWING SC-000.
2. REFER TO POWER PLANS FOR LOCATION AND QUANTITIES OF POWER DEVICES.
3. ALL CCTV CAMERAS AND ASSOCIATED WIRING SHALL BE PROVIDED BY AND INSTALLED BY A
SEPERATE CONTRACTOR.
5. LOCATIONS OF CONDUIT SYSTEM ROUTING IS DIAGRAMMATIC ONLY. CONDUIT SHALL BE
INSTALLED AS NECESSARY TO AVOID OTHER FACILITIES. COORDINATE INSTALLATION WITH ALL
TRADES TO PROVIDE A COORDINATED LAYOUT.
6. REFER TO SECURE DOOR ELEVATIONS, LOCATED ON DETAIL DRAWINGS.
7. COORDINATE MOUNTING HEIGHTS AND DEVICE LOCATIONS WITH ARCHITECTURAL DRAWINGS.
PROVIDE BACK BOX FLUSH WITH CEILING FOR CCTV CAMERA TO BE INSTALLED BY OTHERS.
COORDINATE EXACT LOCATION IN FIELD WITH OWNER. REFER TO DETAIL 2/SC-300.
SURFACE MOUNT CARD READER TO ARCHITECTURAL BOLLARD. COORDINATE EXACT MOUNTING
REQUIREMENTS IN FIELD WITH OWNER AND ARCHITECTURAL DETAILS.
DIRECT-BURIED 1" CONDUIT, PROVIDED BY ELECTRICAL CONTRACTOR, FOR SECURITY AND DOOR
CONTROL WIRING TERMINATED TO JUNCTION BOX SERVING SECURE DOOR. COORDINATE ALL
WORK WITH ELECTRICAL CONTRACTOR.
COORDINATE LOCATION OF PUSH BUTTON WITH ARCHITECTURAL DETAILS, OWNER, AND GENERAL
CONTRACTOR.
PROVIDE SURFACE MOUNT BACK BOX ON FACE OF STRUCTURAL BEAM FOR CCTV CAMERA TO BE
INSTALLED BY OTHERS. PROVIDE CONCEALED CONDUIT TO ACCESSABLE CEILING ON THE IDF
ROOM SIDE OF THE BUILDING FOR CAMERA INSTALLED TO RUN WIRE. COORDINATE LOCATION IN
FIELD WITH OWNER AND ARCHITECTURAL DETAILS. REFER TO DETAIL 3/SC-300.
1
KEY NOTES:
NO. ISSUE DATE: DESCRIPTION
2
3
4
5
CR
TH
DA
DR
SCALE:
CR DCCR TH CR CR DCCR TH
DC
ML RX RX CR ML RX RX CR ML RX CR ML RX ML RX CR ML RX ML RX
ML
PB PB PB PB PB PB PB
1ACCESS CONTROL RISER DIAGRAM
NTS
EL
TS
J1
J2
J1
EL
J1 J1 J1 J1
LA
J1
EL
LALAJ1 J1 J1 J1 J1
LA
LA
2WPWP
M M 2WP M M 2 M M M M M 2
ACCESS CONTROL KEY NOTES:
PROVIDE TAMPER SWITCH WITHIN DATA GATHERING
PANEL ENCLOSURE TO ALARM WHEN CABINET IS OPENED.
ACCESS CONTROL PANEL SHALL HAVE CAPACITY TO
SERVE QUANTITY OF CARD READERS INDICATED PLUS
10% SPARE FOR FUTURE GROWTH.
1
2
ACCESS CONTROL SYSTEM NOTES:
1. ACCESS CONTROL SYSTEM COMPONENTS INCLUDING BUT
NOT LIMITED TO CARD READERS, REQUEST TO EXIT
DEVICES, DOOR CONTACTS, DOOR CONTROLLERS, DATA
GATHERING PANELS AND SIMILAR ACTIVE DEVICES SHALL
BE PROVIDED BY DIVISION 26 SECURITY CONTRACTOR.
2. ACCESS CONTROL SYSTEM CABLING SHALL BE
FURNISHED AND INSTALLED BY DIVISION 26 SECURITY
CONTRACTOR AND TERMINATED ONTO ACCESS CONTROL
DEVICES.
3. UNSHIELDED TWISTED PAIR (UTP) FOR ETHERNET AND
FIBER-OPTIC CABLING SHALL BE FURNISHED AND
INSTALLED BY DIVISION 27 TELECOMMUNICATIONS
CONTRACTOR.
4. COORDINATE ALL CABLE TYPES, AND QUANTITIES WITH
EQUIPMENT MANUFACTURER.
5. COORDINATE ALL DEVICE LOCATIONS, OUTLET BOX
DIMENSIONS, CONDUIT SIZES AND SIMILAR
INFRASTRUCTURE REQUIREMENTS IN FIELD WITH OWNER
AND EQUIPMENT VENDOR PRIOR TO COMMENCEMENT OF
ANY WORK.
ACCESS CONTROL DRAWING NOTES:
1. FOR SYMBOLS AND ABBREVIATIONS REFER TO DRAWING
SC-000.
2. FOR IT CLOSET ROOM DETAILS REFER TO
TELECOMMUNICATION DRAWINGS.
3. THIS RISER DIAGRAM INDICATES POSSIBLE TYPICAL
ARRANGEMENTS ONLY; FOR EXACT LOCATIONS AND NUMBER
OF DEVICES REFER TO FLOOR PLANS, DOOR ELEVATION
DETAILS AND DOOR HARDWARE SPECIFICATIONS.
4. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR
EQUIPMENT PANEL, CONDUIT, WIRE SIZES, WIRE TYPES AND
ACTUAL ROUTING OF RACEWAYS.
5. COORDINATE ALL WORK WITH OWNER STANDARDS AND
SPECIFICATIONS.
6. REFER TO DOOR ELEVATION DETAILS ON DRAWING
SC-300 FOR SPECIFIC DOOR CABLING REQUIREMENTS.
ACCESS CONTROL WIRING SCHEDULE:
A PROVIDE 6#18 AWG COPPER CONDUCTORS SHIELDED IN
PLENUM RATED SHEATHING FOR CARD READER
CONNECTION TO DATA GATHERING PANEL (DGP). REFER
TO SECURE DOOR ELEVATION FOR ADDITIONAL CABLING
REQUIREMENTS.
B PROVIDE 2#18 AWG COPPER CONDUCTORS
NON-SHIELDED IN PLENUM RATED SHEATHING FOR LOCAL
AUDIBLE ALARM CONNECTION TO DATA GATHERING
PANEL (DGP).
C PROVIDE 2#22 AWG COPPER CONDUCTORS
NON-SHIELDED IN PLENUM RATED SHEATHING FOR
DURESS ALARM, DOOR CONTACT, DOOR RELEASE AND
PUSH BUTTON CONNECTION TO DATA GATHERING PANEL
(DGP).
E UNSHIELDED TWISTED PAIR (UTP) CATEGORY 6A CABLE
PROVIDED BY DIVISION 27 COMMUNICATIONS
CONTRACTOR; PROVIDE JUMPER (PATCH CABLE) FROM
LAN OUTLET TO EQUIPMENT.
DIAGRAM SYMBOLS:
CARD READER
WP - WEATHERPROOF
MAGNETIC LOCK
TRANSFER HINGE
ELECTRIC LATCH
JUNCTION BOXES
DURESS ALARM
DOOR RELEASE
TAMPER SWITCH
/
ACCESSIBLE CEILINGSYSTEM (TYP.)
CABLE TRAY (TYP.)
A
VESTIBULE V1-1A HOUSINGCORRIDOR #103
A
RESOURCE ROOM#103
A
PASSAGE#L101-1
A
MARKETING OPENOFFICE #120
A
ACCESSCONTROL PANEL
21
LOCAL AUDIBLE ALARM
A
RESOURCE ROOM#103A
DOOR CONTACT
REQUEST TO EXIT - MOTION TYPEM
C
VESTIBULE V1-1
A
VESTIBULE V1-2A
C
VESTIBULE V1-2
A
PRESENTATIONL101-7
A
PRESENTATIONL101-4
LOBBYL101
ITROOM #123
MECHROOM #002
UNEXCAVATED
LOWERLEVEL
GROUNDLEVEL
ROOF
LOMBARDO WELCOME CENTER
02
'4
'6
'0
8'
16
'2
4'
06
"9
"3
"0
1'
6"
1-6
"0
1/
2'
1'
2'
01
'2
'3
'0
1'
2'
4'
02
'4
'8
'4
'0
8'
16
'0
8'
16
'3
2'
SHEET NUMBER
SFA PROJECT NUMBER
FULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SC
ALE
: 1/
16
" =
1'-0
"S
CA
LE: 1
/8
" =
1'-0
"S
CA
LE: 1
/4
" =
1'-0
"S
CA
LE: 1
/2
" =
1'-0
"S
CA
LE: 3
/4
" =
1'-0
"S
CA
LE: 1
" =
1'-0
"S
CA
LE: 1
1/
2"
= 1
'-0"
SC
ALE
: 3"
= 1
'-0"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SC
ALE
: 3/
32
" =
1'-0
"S
CA
LE: 3
/8
" =
1'-0
"
PROJECT No: MI-1105
C:\
Revi
t Lo
cal F
iles\
G1
50
00
4-0
00
- M
ille
rsvi
lle -
MEP
15
_C
entr
al_
ska
pla
n.rv
t
SC-200G150004-000
SECURITY SINGLE LINEDIAGRAM
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION
SCALE:
SCALE: SCALE:
SCALE: SCALE: SCALE: SCALE:
SCALE:
SCALE: SCALE:
S
TS
FA
4SECURE DOOR ELEVATION HARDWARE SETS #1 AND #3
NONE
5SECURE DOOR ELEVATION HARDWARE SET #2
NONE 6SECURE DOOR ELEVATION HARDWARE SET #5
NONE
7SECURE DOOR ELEVATION HARDWARE SET #6
NONE 8SECURE DOOR ELEVATION HARDWARE SET #7
NONE 9SECURE DOOR ELEVATION HARDWARE SET #13
NONE 10SECURE DOOR ELEVATION HARDWARE SET #16
NONE
1DATA GATEHRING PANEL ELEVATION DETAIL
NONE
2CCTV MINI-DOME IP CAMERA INTERIOR CEILING MOUNT
NONE3
CEILING SURFACE MOUNTED MOUNTED CCTV MINI-DOME CAMERANONE
J1 TO CONTROL PANEL
3
2
RECESSED DOOR OPERATOR IN SLAB
STUB 3/4" CONDUIT WITH DRAG LINE
PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH
COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.
KEY NOTES:
2
3
1
1
CEILING SLAB
FINISHED FLOOR
FINISHED CEILING
4 CARD READER (UNPROTECTED SIDE)
6 6
5 5
7
3' 6"
4
5 EXIT DEVICE BAR
6 MAGNETIC LOCK
7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)
J1
DOOR OPERATION:
-DOOR NORMALLY CLOSED AND LOCKED
-ENTRY BY VALID CARD READ; EITHER POWER OPERATED
OR MANUAL PULL
-FREE EGRESS AT ALL TIMES VIA PANIC DEVICE; REQUEST
TO EXIT MOTION SENSOR WILL SIGNAL VALID EGRESS
-LOCK IS FAIL-SECURE UPON POWER LOSS
-ACTIVATION OF INTERIOR VESTIBULE DOOR
PUSHBUTTON WILL OPEN DOOR UNDER TIME DELAY
-DOOR WILL FAIL-SAFE UNDER FIRE ALARM CONDITION
ARCHITECTURAL BOLLARD
PS
8
8 POWER SUPPLY
TO 120 VAC
J1 TO CONTROL PANEL
3
2
RECESSED DOOR OPERATOR IN SLAB
STUB 3/4" CONDUIT WITH DRAG LINE
PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH
COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.
KEY NOTES:
2
3
1
1
CEILING SLAB
FINISHED FLOOR
FINISHED CEILING
4 PUSH BUTTON (UNPROTECTED SIDE)
5 5
7
3' 6"
4
5 EXIT DEVICE BAR
6 (NOT USED)
7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)
J1
PS
8
8 POWER SUPPLY
TO 120 VAC
DOOR OPERATION:
-DOOR NORMALLY CLOSED AND UNLOCKED
-ENTRY BY VALID CARD READ WILL ACTIVE POWER
OPERATOR OR MANUAL PULL ALWAYS AVAILABLE
-FREE EGRESS AT ALL TIMES VIA PANIC DEVICE; REQUEST
TO EXIT MOTION SENSOR WILL SIGNAL VALID EGRESS
-ACTIVATION OF INTERIOR VESTIBULE DOOR
PUSHBUTTON WILL OPEN DOOR
J1 TO CONTROL PANEL
3
RECESSED DOOR OPERATOR IN SLAB
STUB 3/4" CONDUIT WITH DRAG LINE
PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH
COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.
KEY NOTES:
2
3
1
1
CEILING SLAB
FINISHED FLOOR
FINISHED CEILING
4 CARD READER (UNPROTECTED SIDE)
6
5
7
3' 6"
4
5 EXIT DEVICE BAR
6 MAGNETIC LOCK
7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)
J1
DOOR OPERATION:
-DOOR NORMALLY CLOSED AND LOCKED
-ENTRY BY VALID CARD READ; EITHER POWER OPERATED
OR MANUAL PULL
-FREE EGRESS AT ALL TIMES VIA PANIC DEVICE; REQUEST
TO EXIT MOTION SENSOR WILL SIGNAL VALID EGRESS
-LOCK IS FAIL-SECURE UPON POWER LOSS
-AUDIBLE CHIME WILL RING EACH TIME DOOR IS OPENED
PS
8
8 POWER SUPPLY
TO 120 VAC
3' 6"
9
2
10
9 PUSH BUTTON (UNPROTECTED SIDE)
10 LOCAL AUDIBLE CHIME
J1 TO CONTROL PANEL
3
2
PUSH BUTTON (UNPROTECTED SIDE)
STUB 3/4" CONDUIT WITH DRAG LINE
PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH
COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.
KEY NOTES:
2
3
1
CEILING SLAB
FINISHED FLOOR
FINISHED CEILING
4 CARD READER (UNPROTECTED SIDE)
6 6
5 5
7
5 EXIT DEVICE BAR
6 MAGNETIC LOCK
7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)
J1
DOOR OPERATION:
-DOOR NORMALLY CLOSED AND LOCKED
-ENTRY BY VALID CARD READ
-PUSH BUTTON WILL RELEASE MAGNETIC LOC FOR
EGRESS; REQUEST TO EXIT MOTION SENSOR WILL
SIGNAL VALID EGRESS
-LOCK IS FAIL-SECURE UPON POWER LOSS
-DOOR WILL FAIL-SAFE UNDER FIRE ALARM CONDITION
PS
8
8 POWER SUPPLY
TO 120 VAC
3' 6"
4
3' 6"
1
J1 TO CONTROL PANEL
3
2
PUSH BUTTON (UNPROTECTED SIDE)
STUB 3/4" CONDUIT WITH DRAG LINE
PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH
COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.
KEY NOTES:
2
3
1
CEILING SLAB
FINISHED FLOOR
FINISHED CEILING
4 CARD READER (UNPROTECTED SIDE)
6
5
7
5 EXIT DEVICE BAR
6 MAGNETIC LOCK
7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)
J1
DOOR OPERATION:
-DOOR NORMALLY CLOSED AND LOCKED
-ENTRY BY VALID CARD READ
-PUSH BUTTON WILL RELEASE MAGNETIC LOCK FOR
EGRESS; REQUEST TO EXIT MOTION SENSOR WILL
SIGNAL VALID EGRESS
-LOCK IS FAIL-SECURE UPON POWER LOSS
-DOOR WILL FAIL-SAFE UNDER FIRE ALARM CONDITION
PS
8
8 POWER SUPPLY
TO 120 VAC
3' 6"
4
3' 6"
1
J1 TO CONTROL PANEL
3
2
PUSH BUTTON (UNPROTECTED SIDE)
STUB 3/4" CONDUIT WITH DRAG LINE
PROVIDE 4"x4"x2" DEEP JUNCTION BOX WITH
COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.
KEY NOTES:
2
3
1
CEILING SLAB
FINISHED FLOOR
FINISHED CEILING
4 CARD READER (UNPROTECTED SIDE)
6
5
7
5 EXIT DEVICE BAR
6 MAGNETIC LOCK
7 REQUEST TO EXIT (MOTION) - (PROTECTED SIDE)
J1
DOOR OPERATION:
-DOOR NORMALLY CLOSED AND LOCKED
-ENTRY BY VALID CARD READ
-PUSH BUTTON WILL RELEASE MAGNETIC LOCK FOR
EGRESS; REQUEST TO EXIT MOTION SENSOR WILL
SIGNAL VALID EGRESS
-LOCK IS FAIL-SECURE UPON POWER LOSS
-AUDIBLE CHIME WILL RING EACH TIME DOOR IS OPENED
-DOOR WILL FAIL-SAFE UNDER FIRE ALARM CONDITION
PS
8
8 POWER SUPPLY
TO 120 VAC
3' 6"
4
3' 6"
1
9
9 LOCAL AUDIBLE CHIME
FINISHED FLOOR
CEILING SLAB
FINISHED CEILING
J1
STUB 3/4" CONDUIT WITH DRAG LINE (TYPICAL)
PROVIDE 4" x 4" x 2" DEEP JUNCTION BOX WITH
COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.
CARD READER (BOTH SIDES)
LOCKING DEVICE: ELECTRIFIED MORTISE WITH INTEGRAL RX SWITCH
POWER TRANSFER HINGE AND MORTAR JUNCTION BOX
STUB 3/4" CONDUIT DOWN DOOR FRAME ONTHE HINGE SIDE OF THE DOOR BACK BOX, TO JUNCTION BOXLOCATED ABOVE ACCESSIBLE CEILING
NOTES:
TO CONTROL PANEL
J1
J1
TH
EL
CR
6
5
4
2
3
1
56
1
4
2
3
WIRE HARNESS BY HARDWARE INSTALLER7
3' 6"
7
DOOR OPERATION:
-DOOR NORMALLY CLOSED AND LOCKED; DOOR SWITCH
RELAYS POSITION
-ENTRY BY VALID CARD READ BOTH DIRECTIONS
-FREE EGRESS AT ALL TIMES VIA HANDLE; INTEGRAL RX
SWITCH WILL SIGNAL VALID EGRESS
-LOCK IS FAIL-SECURE UPON POWER LOSS - CORRIDOR
INTO ROOM
-DOOR WILL FAIL-SAFE UNDER FIRE CONDITION
-AUDIBLE CHIME WILL RING WITH EACH DOOR OPEN
4
9 8
DOOR CONTACT8 DC
LOCAL AUDIBLE CHIME9 LA
PS
10
POWER SUPPLY10 PS
TO 120 VAC
FINISHED FLOOR
CEILING SLAB
FINISHED CEILING
J1
STUB 3/4" CONDUIT WITH DRAG LINE (TYPICAL)
PROVIDE 4" x 4" x 2" DEEP JUNCTION BOX WITH
COVER MOUNTED ABOVE DOOR, ABOVE ACCESSIBLE CEILING.
CARD READER (BOTH SIDES)
LOCKING DEVICE: ELECTRIFIED MORTISE WITH INTEGRAL RX SWITCH
POWER TRANSFER HINGE AND MORTAR JUNCTION BOX
STUB 3/4" CONDUIT DOWN DOOR FRAME ONTHE HINGE SIDE OF THE DOOR BACK BOX, TO JUNCTION BOXLOCATED ABOVE ACCESSIBLE CEILING
NOTES:
TO CONTROL PANEL
J1
J1
TH
EL
CR
6
5
4
2
3
1
56
1
4
2
3
WIRE HARNESS BY HARDWARE INSTALLER7
3' 6"
7
9 8
PS
10
TO 120 VAC
DOOR OPERATION:
-DOOR NORMALLY CLOSED AND LOCKED; SWITCH RELAYS
DOOR POSITION
-ENTRY BY VALID CARD READ
-FREE EGRESS AT ALL TIMES VIA HANDLE; INTEGRAL RX
SWITCH WILL SIGNAL VALID EGRESS
-LOCK IS FAIL-SECURE UPON POWER LOSS - CORRIDOR
INTO ROOM
-DOOR WILL FAIL-SAFE UNDER FIRE CONDITION
-AUDIBLE CHIME WILL RING WITH EACH DOOR OPEN
DOOR CONTACT8 DC
LOCAL AUDIBLE CHIME9 LA
POWER SUPPLY10 PS
CAT-6A CABLE AND OUTLET JACK BY
CONTRACTOR, TO DATA CLOSETTO FIRE ALARM CONTROL PANEL. SEE
FIRE PROTECTION DRAWING
FIRE ALARM INTERFACE RELAY.
COORDINATE WITH FIRE ALARM SYSTEM
INSTALLATION
3/4" FIRE SAFE PLYWOOD MOUTNING
BACKBOARD WITHIN ENCLOSURE
120V, 20 AMP DEDICATED DUPLEX RECEPTACLE TO
ELECTRICAL PANEL -
REFER TO ELECTRICAL DRAWING(TYP)
NETWORK
CONNECTOR -
REFER TO TELECOM
DRAWINGS
ACCESS
CONTROL
PANEL
LOCKPOWER
LOCK
POWER
FAIL
SAFE
LOCK
POWER
AUX
POWER
CABLE TROUGH
6'-6" CA
BLE
TR
OU
GH 4
5
1
(TYP.)
2
(TYP.)
(TYP.)
KEY NOTES:
1
2
3
4
5
I-STAR
7
8
6
TWO (2) SPST LOCAL TOGGLE TYPE
DISCONNECT SWITCHES
PROVIDE QUANTITY OF CARD READER MODULES, INPUT RELAYS AND OUTPUT RELAYS WITHIN ACCESS CONTROL PANEL ENCLOSURE AS REQUIRED TO SUPPORT THE QUANTITY AND TYPES
OF DEVICES SHOWN ON THE RISER DIAGRAM AND DOOR ELEVATION DETAILS.
PROVIDE QUANTITY OF POWER SUPPLY MODULES AS REQUIRED TO PROVIDE POWER TO ALL DEVICES AND MODULES REQUIRED TO SUPPORT THE DEVICES SHOWN ON THE RISER DIAGRAMS
AND DOOR ELEVATION DETAILS.
PROVIDE 60"H X 60"W X 10"D STEEL NEMA 1 ENCLOSURE WITH HINGED, LOCKING FRONT DOOR, VENTILATED BOTTOM, AND VENTILATION FAN FOR MOUNTING OF ACCESS CONTROL
EQUIPMENT. PANELS SHALL BE MANUFACTURED BY HOFFMAN OR APPROVED EQUAL.
COORDINATE FIRE ALARM INTERFACE CONNECTIONS WITH ELECTRICAL DRAWINGS AND CONTRACTOR.
PROVIDE VERTICAL AND HORIZONTAL CABLE TROUGHS IN LOCATIONS AS SHOWN WITH MINIMUM CROSS-SECTION DIMENSIONS OF 8" X 8" IN LENGTHS AS REQUIRED.
BOTTOM VENTALATION LOUVER WITH FILTER MATERIAL SIZE AS RECOMENDED BY ENCLOSURE VENDOR.
VENTILATION FAN WITH CORD/ENDPLUG RATED FOR 120VAC SIZED AS RECOMMENDED BY ENCLOSURE VENDOR.
TAMPER SWITCH MOUNTED WITHIN ENCLOSURE TO ALARM WHEN DOOR IS OPENED.
6
7
8
MINI-DOME CAMERA BY OTHER CONTRACTOR
CEILING - REFER TO
PROVIDE MINIMUM 3/4" CONDUIT RUN CONCEALED
TO ABOVE ACCESSIBLE CEILING
PROVIDE BACKBOX - 4" X 4" X 2 1/8"D
NOTES:
1. DETAIL REPRESENTS TYPICAL SECURITY REQUIREMENTS. SEE THE FLOOR PLANS FOR
DEVICE LOCATIONS.
ARCHITECTURAL PLANSPROVIDE BACK-BOX
MINI-DOME CAMERA BY
CEILING DECK
NOTES:
4"x4"x1.5" (D)
OTHER CONTRACTOR
PROVIDE MINIMUM 3/4" CONDUIT
RUN CONCEALED TO ABOVEACCESSIBLE CEILING
1. DETAIL REPRESENTS TYPICAL SECURITY REQUIREMENTS. SEE THE FLOOR PLANS FOR
DEVICE LOCATIONS.
02
'4
'6
'0
8'
16
'2
4'
06
"9
"3
"0
1'
6"
1-6
"0
1/
2'
1'
2'
01
'2
'3
'0
1'
2'
4'
02
'4
'8
'4
'0
8'
16
'0
8'
16
'3
2'
SHEET NUMBER
SFA PROJECT NUMBER
FULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SC
ALE
: 1/
16
" =
1'-0
"S
CA
LE: 1
/8
" =
1'-0
"S
CA
LE: 1
/4
" =
1'-0
"S
CA
LE: 1
/2
" =
1'-0
"S
CA
LE: 3
/4
" =
1'-0
"S
CA
LE: 1
" =
1'-0
"S
CA
LE: 1
1/
2"
= 1
'-0"
SC
ALE
: 3"
= 1
'-0"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SC
ALE
: 3/
32
" =
1'-0
"S
CA
LE: 3
/8
" =
1'-0
"
PROJECT No: MI-1105
C:\
Revi
t Lo
cal F
iles\
G1
50
00
4-0
00
- M
ille
rsvi
lle -
MEP
15
_C
entr
al_
ska
pla
n.rv
t
SC-300G150004-000
SECURITY DETAILS
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION
T
FIRE PROTECTION SYMBOL LISTBASIC
FIRE STANDPIPE PIPING (STANDALONE)
SPRINKLER PIPING
DRY SPRINKLER PIPING
PRE-ACTION SPRINKLER PIPING
DRAIN PIPING
PIPING BELOW SLAB
EXISTING PIPING
EXISTING WORK TO BE REMOVED
HEAT TRACE / FREEZE PROTECTION CABLE & INSULATION
SLOPED CHANGE IN PIPE ELEVATION
BOTTOM PIPE CONNECTION
TOP PIPE CONNECTION
SIDE CONNECTION
PIPE DOWN/DROP
PIPE RISE/UP
PIPE SLOPE
VALVE IN VERTICAL
UNION
REDUCER
WATER PROOF SLEEVE
SLEEVE
FIRE EXTINGUISHERA - WATERB - DRY CHEMICALC - GASEOUS (CO2 OR HALON 1211 - SEE SPEC.)
FIRE EXTINGUISHER IN CABINET
FIRE HOSE VALVE
FIRE HOSE VALVE IN CABINET
FIRE HOSE VALVE w/HOSE IN CABINET
FIRE HOSE VALVE w/FIRE EXTINGUISHER
ROOF MANIFOLD (3-WAY)
SPRINKLER CONTROL VALVE ASSEMBLY
VALVE ASSEMBLYAC - ALARM CHECKDR - DRY PIPEPA - PRE ACTION
CONNECT TO EXISTING
DISCONNECT FROM EXISTING
FIRE DEPARTMENT SIAMESE CONNECTION (WALL MOUNTED)
EXISTING FIRE HYDRANT
NEW FIRE HYDRANT
TEMPERATURE AND PRESSURE RELIEF VALVE
PLUG VALVE
MIXING VALVE
RELIEF VALVE
BALL VALVE
GATE VALVE
GLOBE VALVE
OUTSIDE SCREW & YOKE (OS & Y) VALVE
CHECK VALVE
PRESSURE REDUCING VALVE (PRV)
SOLENOID VALVE
FLOAT VALVE
Y STRAINER w/BLOW-OFF VALVE
REDUCED PRESSURE DETECTOR ASSEMBLY
DOUBLE CHECK DETECTOR ASSEMBLY
HYDRAULIC REF. POINTS # = ELEMENT, # = NODE
TAMPER SWITCH
WATERFLOW SWITCH
PRESSURE GAUGE w/GAUGE COCK
RISER DESIGNATION:X = RISER SERVICE; # = RISER NUMBER
EXTEND EXISTING SPRINKLER PIPING TO NEW SPRINKLER HEAD
DSP
RPDA
DCDA
X#
#
F
PA
DR
S
S
#
FE-X
FE-X
X
FE-X
FP-2-3
XXX-XX-XX
SECOND FLOOR
(REFER TO SPECIFIC TRADE LIST)
EQUIPMENT TAG NUMBERFLOOR DESIGNATIONEQUIPMENT DESIGNATION
FIRE PUMP(REFER TO LIST)
UNIT NUMBER 3
FP EQUIPMENT DESIGNATIONS
1. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL FIRE PROTECTION DRAWINGS.
2. ALL WORK IS NEW UNLESS OTHERWISE NOTED.
3. ALL FIRE PROTECTION WORK SHALL BE IN ACCORDANCE WITH THE CURRENT FIRE PROTECTION CODEAND ALL APPLICABLE LOCAL CODES AND DRAWINGS.
4. PROVIDE WET-PIPE SPRINKLERS IN ALL AREAS.
5. SECURE WATER FLOW TEST DATA TAKEN FROM FIRE HYDRANTS NEAREST SITE. IF RECENT FLOW TESTDATA IS NOT AVAILABLE FROM CITY RECORDS, MAKE NECESSARY TESTS AS REQUIRED BY NFPASTANDARDS TO DETERMINE CHARACTER OF WATER SUPPLY. MINIMUM OF 20 PSI DROP IN PRESSUREBETWEEN STATIC AND RESIDUAL PRESSURE SHALL BE REQUIRED IN ORDER TO OBTAIN ACCURATEDATA.
6. SPRINKLER SYSTEM SHALL BE HYDRAULICALLY CALCULATED.
7. ADD 10% CONTINGENCY FACTOR TO HYDRAULIC CALCULATIONS.
8. EXACT LOCATION OF SPRINKLER HEADS IN FINISHED AREAS WITH SUSPENDED CEILING SHALL BE ASINDICATED ON REFLECTED CEILING PLANS.
9. MINIMUM PRESSURE AT END SPRINKLER HEAD 7 PSI.
10. EQUIVALENT FITTING LENGTHS USED IN HYDRAULIC CALCULATIONS SHALL BE IN ACCORDANCE WITHNFPA STANDARD NO. 13 AND FACTORY MUTUAL 0.5 2-8N.
11. MAXIMUM FLOW VELOCITY SHALL NOT EXCEED 20 F.P.S.
12. ALL AUTOMATIC SPRINKLER HEADS, PIPE FITTINGS, PIPE HANGERS, AUTOMATIC CONTROL VALVES ANDMANUAL CONTROL VALVES SHALL BE UL LISTED AND BEAR FACTORY MUTUAL APPROVAL AND SHALL BEAPPROVED BY THE ENGINEER PRIOR TO INSTALLATION.
13. ALL EXPOSED PIPE, FITTINGS, HANGERS AND SUPPLEMENTARY STEEL SHALL BE PAINTED.
14. ENDS OF ALL CROSS MAINS SHALL BE PROVIDED WITH THREADED FLUSHING CONNECTION NO MORETHAN 2 INCHES IN DIAMETER.
15. PROVIDE AUXILIARY DRAINS FOR ALL PIPING BELOW DUCT SPRINKLERS AND OPEN TRAPPED SECTIONS.PIPING TO ONE SINGLE SPRINKLER IS EXCLUDED.
16. PROVIDE FLUSHING CONNECTIONS WHERE REQUIRED BY NFPA AND F.M.
17. COORDINATE WITH OWNER FOR ALL SHUTDOWNS.
18. PROVIDE TEST CONNECTIONS AT HIGHEST POINT OF MAIN PORTION OF EACH SPRINKLER SYSTEM, WITH1" PIPE AND VALVE. TEST PIPE SHALL BE CONNECTED TO SPRINKLER PIPE AT LEAST 1-1/4" IN SIZE ANDSHALL DISCHARGE OUTSIDE BUILDING OR THROUGH 1/2" SMOOTH BORE BRASS OUTLET, WHERE IT CANBE EASILY SEEN.
19. PROVIDE ADDITIONAL HEADS UNDER DUCTWORK LARGER THAN 48" WIDE.
20. THE REUSE OF EXISTING SPRINKLER HEADS SHALL BE PROHIBITED.
21. NEW SPRINKLER HEAD TYPE AND TEMPERATURE RATING SHALL BE IN ACCORDANCE WITH SCHEDULEUNLESS NOTED OTHERWISE AND/OR REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
22. COORDINATE ALL PIPE PENETRATIONS AND CORING WITH STRUCTURAL ENGINEER AND INACCORDANCE WITH DIVISION 01.
23. REFER TO ARCHITECTURAL DRAWINGS FOR ALL CEILING RELATED WORK.
24. COORDINATE ALL NEW FIRE PROTECTION WORK WITH ALL NEW DUCTWORK, PIPING AND UTILITIES OFANY SYSTEMS. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE INTENT OF THE DESIGN. REROUTE ANYPIPING AROUND EXISTING AND/OR NEW SYSTEMS INCLUDING ALL REQUIRED FITTINGS AND SUPPORTSTO MAKE THE INSTALLATION OF THE PIPING AND SPRINKLER HEADS POSSIBLE. RESEAL ANY FIREAND/OR SMOKE RATED PENETRATIONS THAT HAVE BEEN AFFECTED AS A RESULT OF THEMODIFICATION.
25. ALL COMPONENTS USED IN FIRE PROTECTION SYSTEMS SHALL BE IN ACCORDANCE WITH THE OWNER'SGUIDELINES, STANDARDS AND SPECIFICATIONS.
26. WATER SUPPLY INFORMATION TO BE VERIFIED BY FLOW TEST.
27. REPAIR AND PATCH ANY PENETRATIONS CREATED AS PART OF THIS SCOPE OF WORK. MATCH NEWFINISHES WITH ARCHITECTURAL PLANS.
28. COORDINATE INSTALLATION OF PIPING AND SPRINKLER HEADS WITH ALL OTHER TRADES.
29. ALL EXCAVATION AND BACKFILL REQUIRED FOR FIRE PROTECTION WORK SHALL BE BY THE FIREPROTECTION CONTRACTOR. REFER TO SITE SPECIFICATIONS FOR MORE INFORMATION ONEXCAVATION AND BACKFILL REQUIREMENTS.
30. PAINTING OF ALL ARCHITECTURALLY EXPOSED PIPING WORK SHALL BE BY THE GENERAL CONTRACTOR.PAINTING OF ANY NON-ARCHITECTURALLY EXPOSED PIPING SHALL BE BY THIS TRADES CONTRACTOR.REFER TO DIVISION 9 PAINTING.
31. FIRESTOPPING FOR THE WORK INCLUDED IN THESE DOCUMENTS, SHALL BE FURNISHED AND INSTALLEDBY THE FIRE PROTECTION CONTRACTOR. REFER TO DIVISION 7 FIRESTOPPING.
32. SLEEVES THAT ARE REQUIRED FOR THIS PROJECTS SHALL BE FURNISHED BY THE FIRE PROTECTIONCONTRACTOR AND INSTALLED BY THE GENERAL CONTRACTOR. COORDINATE THE LOCATION OF THESLEEVES WITH THE GENERAL CONTRACTOR.
FIRE PROTECTION GENERAL NOTES SPRINKLER HEAD SCHEDULE
MODEL NUMBER
MANUFACTURER
STAR
TYPE
EXIST
SPRI
NKLE
RHD
FLUS
HPE
NDEN
T
REMO
VED/
RELO
CATE
DEX
ISTSP
RHO
TOBE
EXTE
NDED
COVE
RAGE
QUIC
KRES
PONS
E
INTE
RMED
IATES
HIEL
D
(CHR
OMEF
INISH
)SID
EWAL
L
FLUS
HCO
NCEA
LED
PLAT
ESPK
R.
DESIG
NATIO
N
SEMI
-REC
ESSE
D
UPRI
GHT
PEND
ENT
DRY
CENT
RAL
RELIA
BLE
GRIN
NELL
VIKIN
G
REMARKS
A
NOTES:
2. PROVIDE ESCUTCHEONS WHEN PENETRATING EXPOSED WALL.
1. EXPOSED UPRIGHT HEADS IN OCCUPIED SPACES SHALL BE CHROME FINISH.
3. PROVIDE SPRINKLER GUARDS AT ALL HEADS 7'-0" AND LOWER.
4. COORDINATE COLOR SELECTION WITH ARCHITECT.A. SPRINKLER AND ESCUTCHEON TO BE WHITEB. SPRINKLER HEAD TO BE WHITEC. COVER PLATE TO BE WHITED. SPRINKLER AND SHIELD IN EXPOSED IN COORIDORS TO BE WHITEE. SPRINKLER AND SHIELD IN WOOD SLOT CEILING TO BE BLACK
F1FR56 INTERMEDIATE LEVELW/ SHIELD
F1FR56
F1FR56
G4A
DH56 DRY
K=5.6, 1/2" ORIFICE
K=5.6, 1/2" ORIFICE
K=5.6, 1/2" ORIFICE165°F RATING
155°F RATING
155°F RATING
K=5.6, 1/2" ORIFICE155°F RATING
F1FR56 K=5.6, 1/2" ORIFICE155°F RATING
K=5.6, 1/2" ORIFICE155°F RATING
SEE NOTE 4C.
SEE NOTE 4B.
SEE NOTE 4D AND 4E
SEE NOTE 4A.
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
F-000G150004-000
FIRE PROTECTION COVERSHEET
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
FIRE PROTECTION ABBREVIATIONSABD AUTOMATIC BALL DRIPAD AREA DRAINAFF ABOVE FINISHED FLOORATS AUTOMATIC TRANSFER SWITCH
BOP BOTTOM OF PIPE
CFM CUBIC FEET PER MINUTECV CHECK VALVE
DIA DIAMETERDN DOWN (PENETRATES FLOOR SLAB)DR DRAIN
(E) EXISTING(ER) EXISTING TO BE REMOVED(ERR) EXISTING TO BE REMOVED & RELOCATED
FD FLOOR DRAINFHC FIRE HOSE CABINETFHR FIRE HOSE RACKFHV FIRE HOSE VALVEFHVC FIRE HOSE VALVE CABINETFL FLOORFP FIRE PUMPFSP FIRE STANDPIPEFT FEET
GAL GALLONSGC GENERAL CONTRACTORGPM GALLONS PER MINUTEGV GATE VALVE
HD HEAT DETECTOR
ID INSIDE DIAMETERIN INCH
JP JOCKEY PUMP
MAX MAXIMUMMIN MINIMUM
NC NORMALLY CLOSENIC NOT IN THIS CONTRACTNO NORMALLY OPENNTS NOT TO SCALE
OD OUTSIDE DIAMETEROS&Y OUTSIDE SCREW & YOKE GATE VALVE
PRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCH (GAUGE)PSIA POUNDS PER SQUARE INCH (ABSOLUTE)
(RE) RELOCATED EXISTING(RRO) EXISTING TO REMOVED AND RETURN TO OWNER
SD SMOKE DETECTORSPKR SPRINKLER
TOP TOP OF PIPETS TAMPER SWITCH
UON UNLESS OTHERWISE NOTEDUP UP (PENETRATES FLOOR SLAB)
WFS WATER FLOW SWITCH
Z ZONE
NO. ISSUE DATE: DESCRIPTION
4"SP
DCDA
ALARM CHECKVALVE ASSEMBLY
6" TRANSITION TO 4" SPRINKLER SERVICE.REFER TO PLUMBING DRAWINGS FORCONTINUATION.
F14" RISER UP
4" TO 5" STORZ FDCREFER TO SITE CIVILPLANS FOR CONTINUATION
CHECK VALVE
CAP FOR FUTURE
RISER VALVE
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
3"SP 3"SP
4"SP
4"SP
1"SP
1"SP
1"SP
1"SP
1"SP
1"SP
11/4"
SP
11/4"
SP
4"SP
1"SP
1"SP
1"SP
1"SP
11/4"
SP
1
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
F-100G150004-000
FIRE PROTECTION LOWERLEVEL PLAN
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN
DRAWING KEY NOTES:
COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.1
NO. ISSUE DATE: DESCRIPTION
F1 4" RISER DN
(2) 2 1/2"FDC
4"DN
4"SP 4"SP 4"SP4"SPRUN SPRINKLER PIPE HIGHAND TIGHT TO STEEL BEAM
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
VEST.V-1
ALCOVEL101-5
WOMEN'S143
PASSAGE104
MEN'S142
ALCOVEL101-6JANITOR
141
MECHANICAL141.1
FAMILYTOILET
144
STORAGE140.1
PASSAGEL101-7
VEST.V-2
CLASSROOM/PRESENTATIONROOM
140
V.P. OFFICE112A
SMALL CONF.105
STORAGE103.1
OFFICE112
PASSAGEL101-1
OFFICE118
OFFICE114
OFFICE116
OFFICE110
OFFICE108
OFFICE104
CORRIDORC 1-1
CORRIDORC 1-2
BREAK ROOM107
STORAGE119
ELEC. RM.121
COFFEESTATIONL101-3
STORAGE103.2
ADMISSIONSOPEN OFFICE
106
HOUSINGOPEN OFFICE
130
OFFICE128
OFFICE126
OFFICE124
OFFICE122
MARKETINGOPEN OFFICE
120
SMALL CONF.115
CONFERENCE117
I.T. ROOM123
CALL CENTER109
CORRIDORC 1-3
OFFICE102
WORK ROOM111
RESOURCEROOM
103
RECEPT.L101-2
STUDENTWORK SPACE
113
LOBBYL101
11/4"
SP
11/4"
SP1"S
P
1"SP
1"SP
1"SP
1"SP
1"SP
1"SP
11/4"
SP
11/4"
SP1"S
P1"SP
1"SP
1"SP
11/2"
SP
11/2"
SP3"SP
3"SP
3"SP 3"SP 3"SP
1 1/2"SP1 1/4"SP
1"SP 1 1/4"SP
1 1/4"SP
1 1/4"SP
1"SP1"SP
1"SP1"SP
1 1/2"SP
1 1/2"SP
1"SP
1 1/2"SP
1 1/2"SP
1 1/2"SP
1 1/2"SP
1 1/2"SP
1 1/4"SP1"SP
1"SP
1"SP
11/2"
SP2"S
P11
/2"SP
1"SP1"SP1"SP
11/2"
SP
1"SP
1"SP
1"SP 1"SP
11/4"
SP2"S
P2"S
P 1"SP
1"SP
1 1/4"SP
1"SP 1"SP
11/2"
SP2"S
P
1"SP1"SP
1"SP 1"SP
2"SP
11/4"
SP11
/2"SP
1"SP
1"SP
1"SP
1"SP
1"SP 1 1/4"SP
11/4"
SP11
/4"SP
1"SP1"SP 1"SP 1"SP
1"SP 11/2"
SP11
/4"SP
1"SP
1"SP
11/4"
SP11
/2"SP
11/4"
SP1"S
P
1"SP
2"SP
1 1/2"SP
11/2"
SP
1"SP
1"SP
1"SP
2"SP
1"SP 1"SPA A
AA
A A
AA
A A
AA
A A A
1
1
11
11
11
1
1
1
INPECTORS TEST DRAIN
2
3 4
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
F-101G150004-000
FIRE PROTECTION GROUNDFLOOR PLAN
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN
DRAWING KEY NOTES:
PROVIDE SPRINKLER COVERAGE ABOVE AND BELOW COMBUSTIBLE WOOD CEILING.REFER TO DETAIL ON DRAWING F-200.
COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.
BASE: PROVIDE CONCEALED SPRINKLER PIPING AND SPRINKLER HEADS IN EPIC DECK CEILING STRUCTURE.COORDINATE WITH ARCHITECTURAL CEILING DETAILS AND DRAWINGS IN THIS AREA.
1
2
3
NO. ISSUE DATE: DESCRIPTION
DCDA
WITHOUT INSULATIONPIPE PENETRATION
PIPE TO BE CENTERED IN SLEEVE - DONOT SUPPORT PIPE FROM SLEEVE
TERMINAL SLEEVE FLUSH WITHFINISHED WALL SURFACES
SEALANT (SEE SPEC.)
PIPE SLEEVE
ESCUTCHEON PLATE FLUSH AGAINSTWALL AND OF SIZE TO COMPLETELYCOVER OPENING (TYPICAL BOTHSIDES OF WALL)
FINISHED WALL SURFACE
PIPE SLEEVE THRU FLOOR SLAB
SEALENT
FLOOR SLAB
RISER CLAP
PLAN VIEW
UPRIGHT SPRINKLERHEAD CONNECTION
UPRIGHT SPRINKLER HEAD
BRANCH LINE
1%%188" BRANCH TEE
1%%188" NIPPLE
1"x 1/2" REDUCER
SLAB ABOVE
SPRINKLER HEAD CONNECTION
& DWG FOR TYPE)(SEE SPECIFICATIONSPRINKLER HEAD
SUSPENDED CEILING
(IF REQUIRED)1" x 1/2" COUPLING
1" DROP NIPPLE
BRANCH PIPE
WET SYSTEMINSPECTOR'S TEST CONNECTION
WALLEXTERIOR
SPRINKLERFLOW EQUIVALENT TO ONERESISTANT OUTLET GIVINGSMOOTH BORE CORROSION
ABOVE FLOORNOT OVER 7 FT.1 IN. GLOBE VALVE
1 IN.
1 IN. BRANCH LINE 1 IN. PLUG
PITCH
SLEEVE ANDSEALANT
INSTALLATION SCHEMATICTYPICAL ALARM CHECK VALVE
PS
PG
PG
TS
TO SYSTEM
TO WMG
ORIFICE DRAIN
PROVIDE FUNNEL ANDEXTEND PIPE TO DRAIN
EXTEND PIPE TO DRAINBY-PASS WITHCHECK VALVE
FROM SUPPLY
FIRE ALARM TEST PIPEWITH VALVE (N.C.)
ALARM CHECK VALVE
TO ALARM PANEL(BY OTHERS)
TO ALARM PANEL(BY OTHERS)
SCALE:
FOR SPACES WITH CONCEALED COMBUSTILE CONSTRUCTIONTYPICAL SPRINKLER HEAD (W/ COVER PLATE) INSTALLATIONS
BRANCH TEE
ESCUTCHEON
1"x
NIPPLE
BRANCH LINE
CONSTRUCTIONTO PROTECT COMBUSTIBLEUPRIGHT SPRINKLER HEAD
HUNG CEILING
1/2" REDUCER
SPRINKLER HEAD(COLOR AS PER SCHEDULE)
SINGLE ARM BRACE
ANGLE CLIP
UNISTRUT TO CLIPBOLTS CONNECTINGTWO 3/8" DIAMETER
BRACESINGLE ARM
PIPE
CLEVISPIPE
CLEVIS
SUPPORT ROD
45
PIPE
PLAN VIEW OF BRACE
HUNG PIPESINGLE ARM BRACE FOR CLEVIS
PLAN VIEW OF BRACE
PIPECLEVISPIPE
TRANSVERSE CABLE BRACECLEVIS
CABLE CONNECTION
CABLESEISMIC
SUPPORT ROD
45°
PIPE
LONGITUDINAL CABLE BRACE
BRACE FOR CLEVIS HUNG PIPETRAVERSE AND LONGITUDINAL CABLE
T
T T T
T
T
1 SPRINKLER RISER DIAGRAMNONE
TYPICAL SPRINKLER HEAD IN EPIC DECK DETAIL
AC
ROOF
GROUND FLOOR
LOWER LEVEL
ROOF
GROUND FLOOR
LOWER LEVEL
(2) 2 1/2" FDC
6" COMBINED DOMESTIC AND SPRINKLERWATER SERVICE. 5'-0" FROM BUILDING.FOR CONTINUATION REFER TO SITE/CIVILDRAWINGS.
4"CHECK VALVE
4"
ALARM CHECK VALVE
4"
4"
3" TO SPRINKLERS
2 1/2" DOMESTIC WATER SERVICE.FOR CONTINUATION REFER TOPLUMBING DRAWINGS.
BY FC BY PC
4"
2 1/2"
6"
F1
RISER VALVE
4"TO SPRINKLERS
4"
EPIC DECKSPRINKLER HEAD(COLOR TO BEWHITE)
SPRINKLER PIPEW/EPIC DECK FASTNER ROOF DECK
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
blim
.rvt
F-200G150004-000
FIRE PROTECTION RISERDIAGRAMS & DETAILS
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION
1. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL HVAC/MECHANICAL DRAWINGS.2. ALL WORK IS NEW UNLESS OTHERWISE NOTED.3. DRAWINGS ARE DIAGRAMMATIC. DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD.4. COORDINATE THIS WORK WITH THAT OF OTHER TRADES.5. DIMENSIONS SHOWN ON PLAN ARE HORIZONTAL. DIMENSIONS SHOWN IN ELEVATION ARE VERTICAL.6. NEITHER ACCURACY NOR COMPLETION OF SERVICES AND UTILITY LOCATIONS SHOWN ON DRAWINGS IS
GUARANTEED. DETERMINE EXACT LOCATIONS OF EXISTING SERVICES AND UTILITIES IN FIELD, WHETHER OR NOTSHOWN ON DRAWINGS. EXERCISE CAUTION AND IDENTIFY LOCATIONS OF UNMARKED UTILITY LINES ASNECESSARY TO PERFORM WORK OF THIS SECTION.
7. MANUFACTURERS MODEL NUMBERS ARE SPECIFIED AS BASIS OF DESIGN. REFER TO SPECIFICATIONS FOROTHER APPROVED MANUFACTURERS.
8. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURERS RECOMMENDATIONS.9. ALL ACCESS PANELS SHALL BE PROVIDED BY AND INSTALLED BY GC. CONTRACTOR SHALL BE RESPONSIBLE FOR
NOTIFYING GC WHERE ACCESS PANELS ARE REQUIRED.10. PROVIDE HANGERS, INSERTS, ANCHORS, SUPPLEMENTAL STEEL & SUPPORTS AS REQUIRED TO SUPPORT
DUCTWORK, PIPING AND EQUIPMENT FROM STRUCTURE.11. RUN DUCTS AND PIPING CONCEALED, UNLESS OTHERWISE SPECIFIED AND CLEAR OF CEILING INSERTS.12. INSTALL THERMOSTATS AT ADA COMPLIANT HEIGHTS OR AS DIRECTED OTHERWISE BY ARCHITECT.13. STRUCTURAL WELDING SHALL BE CONTINUOUS 1/4" FILLET UNLESS REQUIRED OTHERWISE.14. ALL SLEEVES AND PENETRATIONS THROUGH CONCRETE FLOORS AND ALL CORE DRILLING OR CUTTING OF
CONCRETE FLOORS AND WALLS SHALL BE BY THIS CONTRACTOR.15. ALL PAINTING SHALL BE DONE ACCORDING TO THE SPECIFICATIONS. MECHANICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGE TO FINISHED SURFACES CAUSED BY HIS WORK.16. REQUIRED EXCAVATION AND BACKFILL REQUIRED FOR THIS PROJECT SHALL BE BY THIS CONTRACTOR UNLESS
OTHERWISE INDICATED. COORDINATE WITH OTHER TRADES.
AIR SYSTEMS
1. AIR SYSTEMS: REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF AIR DEVICES.2. INTERNAL AIRFLOW DIMENSIONS ARE SHOWN FOR DUCTS. INCREASE DUCT SIZE AS NECESSARY TO MAINTAIN
FREE FLOW AREA INDICATED.3. NO INTERNAL DUCT SOUND LINING OR INSULATION TO BE EXPOSED TO AIR STREAM.4. WHERE REQUIRED, ALL INTERNAL SOUND LINING SHALL BE CONTAINED WITHIN INTERSTITIAL SPACE OF DOUBLE
WALL DUCTWORK.5. ALL VISUALLY EXPOSED DUCTWORK IN FINISHED SPACES REQUIRES INSULATION TO BE DOUBLE WALL WITH
INTERSTITIAL INSULATION.6. USE FLAT TRANSVERSE SEAM FOR DUCTWORK WHERE SPACE AVAILABLE DICTATES.7. DIFFUSER SIZES SHOWN ARE NECK SIZES. REGISTERS AND GRILLE SIZES ARE NOMINAL.8. PROVIDE VOLUME DAMPERS OR OTHER APPROVED BALANCING DEVICES AT DUCT BRANCHES AND RUN OUTS,
AND AT REGISTER GRILLE AND DIFFUSER NECKS IN SUPPLY, RETURN AND EXHAUST DUCTWORK WHETHERSHOWN OR NOT.
9. DUCTWORK DOWNSTREAM OF ALL VAV BOXES SHALL BE DOUBLE WALL WITH INTERSTITIAL INSULATION FOR AMINIMUM OF 15 FEET.
10. PROVIDE 36" CLEARANCE IN FRONT OF ALL ELECTRIC CONTROL PANELS PER N.E.C. AND MFG. REQUIREMENTS.11. PROVIDE DUCT TRANSITIONS FROM VAV BOX INLET/OUTLET DUCT WORK AT SIZES INDICATED TO VAV BOX
INLET/OUTLET UNIT CONNECTIONS.12. VAV DUCT INLET SIZE SHALL BE AS SCHEDULED OR AS INDICATED ON THE FLOOR PLANS. PROVIDE TRANSITION
FROM DUCT SIZE INDICATED ON THE FLOOR PLANS TO SCHEDULED SIZE MINIMUM 2'-0" FROM VAV BOX INLETS.
PIPING SYSTEMS
1. PITCH PIPING 1" IN 20' IN DIRECTION OF FLOW.2. PROVIDE TRAPS IN CONDENSATE LINES THAT EXTEND OVER 2".3. COORDINATE HANGING METHODS WITH STRUCTURAL ENGINEER.
MECHANICAL GENERAL NOTES
SINGLE LINE DUCTWORK OR EQUIPMENT - EXISTING
EXISTING DUCTWORK TO BE REMOVED
DUCTWORK WITH ACOUSTIC LINING
VOLUME DAMPER
FIRE DAMPER AND ACCESS DOOR
BACKDRAFT DAMPER
AUTOMATIC DAMPER
HVAC DUCTWORKSINGLE LINE DUCTWORK OR EQUIPMENT - NEW
DUCTWORK POSITIVE PRESSURE(SUPPLY AIR OR FAN DISCHARGE)
DUCTWORK NEGATIVE PRESSURE(RETURN, EXHAUST OR OUTSIDE AIR)
VD
FD
BDD
M
COMBINATION SMOKE AND FIRE DAMPERWITH ACCESS DOOR
RISE IN DUCTWORK (IN DIRECTION OF AIR FLOW)R
DROP IN DUCTWORK (IN DIRECTION OF AIR FLOW)D
CENTERLINE
CUBIC FEET PER MINUTEOR CFM
DIAMETERØ
SQUARE FEET
OVAL DUCTWORK
TYPE A CEILING DIFFUSER400 CFM SUPPLY AIR
RECTANGULAR CEILING DIFFUSER WITH 12"x12" NECK400 CFM SUPPLY AIR
12x12 CD400
10" BY 8" CEILING REGISTER (CEILING GRILLE)300 CFM RETURN AIR
10x8 CR(CG)300
RECTANGULAR DIFFUSER WITH BLANKING PLATE
10" BY 6" TOP REGISTER, 150 CFM SUPPLY AIR10x8 TR150
10x8 TR(TG)150
10" BY 6" TOP REGISTER (TOP GRILLE)150 CFM RETURN AIR
10x8 BR(BG)150
10" BY 6" BOTTOM REGISTER (BOTTOM GRILLE)150 CFM RETURN AIR
VANED ELBOW (SEE DETAIL)
VANED ELBOW (SEE DETAIL) OR RADIUS ELBOW
FLEXIBLE DUCT
SLOTTED LINEAR DIFFUSER WITH PLENUM
DUCT FLEXIBLE CONNECTION
VERTICAL DUCT DROP(IN DIRECTION OF AIR FLOW)
VERTICAL DUCT RISE(IN DIRECTION OF AIR FLOW)
VARIABLE AIR VOLUME BOXTYPE AVARIABLE AIR VOLUME BOX, TYPE A,WITH REHEAT COILVARIABLE AIR VOLUME BOX, TYPE A, WITHSOUND ATTENUATOR AND REHEAT COIL
THERMOSTAT
H HUMIDISTAT
SMOKE DETECTORSD
HUMIDIFIERH
NEW PIPE WITH DIRECTION OF FLOW
PIPE DROP
PIPE RISE
HVAC PIPING
EXISTING PIPING
EXISTING PIPING TO BE REMOVED
EXISTING PIPING TO BE ABANDONED
PITCH UP IN DIRECTION OF FLOW
PITCH DOWN IN DIRECTION OF FLOW
UNION
CONCENTRIC REDUCER
ECCENTRIC REDUCER - FLAT BOTTOM
ECCENTRIC REDUCER - FLAT TOP
FLANGED CONNECTION
U
D
FLANGED END - BLIND FLANGE
EXPANSION LOOP
PIPE EXPANSION JOINT
PIPE ALIGNMENT GUIDE
PIPE ANCHOR
GATE VALVE
ANGLE GATE VALVE
GLOBE VALVE
ANGLE GLOBE VALVE
NEEDLE VALVE COCK
DRAIN VALVE
LOCK SHIELD VALVE
CHECK VALVE, SWING OR LIFT
SILENT CHECK (NON-SLAM) VALVE
FLEXIBLE CONNECTOR
BUTTERFLY VALVE
SQUARE HEAD COCK
BALANCING VALVE
PLUG VALVE (TYPE AS NOTED)
AUTOMATIC CONTROL VALVE
THREE-WAY AUTOMATIC CONTROL VALVE
BALL VALVE
"Y" TYPE STRAINER WITH BLOWOFF VALVE AND CAP
THERMOMETER AND WELL
PRESSURE GAUGE WITH SYPHON
PUMP
MECHANICAL SYMBOL LIST
AUTOMATIC SMOKE DAMPER
RISE IN DUCTWORK (IN DIRECTION OF AIR FLOW)UC
CONDENSER WATER SUPPLY
CHILLED WATER RETURN
CONDENSER WATER RETURN
CHILLED WATER SUPPLY
DOMESTIC WATER
DRAIN
HOT WATER RETURN
HOT WATER SUPPLY
CWR
CWS
CHWR
CHWS
DW
D
HWR
HWS
HVAC GENERALPOINT OF CONNECTION
POINT OF DISCONNECTION
NEW STEEL CUT
EXISTING STEEL CUT
DIRECT DIGITAL CONTROL PANEL
SECTION DESIGNATION
SHEET No. WHERE SECTION IS SHOWN
EQUIPMENT TAG NUMBERXXX-XX-XX
FLOOR DESIGNATIONEQUIPMENT DESIGNATION
UNIT NUMBER 3
ACU-2-3
SECOND FLOORAIR CONDITIONING UNIT
DDCP
HVAC EQUIPMENT DESIGNATIONS
SD M
FSD M
T
S
BALL JOINT
VAV-A
VAV-A
VAV-A
SECTION DESIGNATION
SHEET No. WHERE SECTION IS SHOWN
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-000G150004-000
MECHANICAL COVER SHEET
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
MECHANICAL ABBREVIATIONSHR HOURHRC HEAT RECOVERY COILHT HEIGHTHTWP HIGH TEMPERATURE WATER PUMPHV HEATING AND VENTILATINGHWP HOT WATER PUMPHX HEAT EXCHANGERHZ FREQUENCE
IN INCH OR INCHESIPS IRON PIPE SIZE
KW KILOWATTKX KITCHEN RANGE HOOD EXHAUST
L LENGTHLAT LEAVING AIRE TEMPERATURELBS POUNDSLCP LOCAL CONTROL PANELLD LINEAR DIFFUSERLDB LEAVING DRY BULB TEMPERATURELF, LIN.FT. LINEAR FEETLR LINEAR RETURNLRA LOCKED ROTOR AMPSLV LOW VELOCITYLWB LEAVING WET BULB TEMPERATURELWT LEAVING WATER TEMPERATURE
MAV MANUAL AIR VENTMAX MAXIMUMMBH THOUSAND BTU PER HOURMCC MOTOR CONTROL CENTERMD MOTORIZED DAMPERMER MECHANICAL EQUIPMENT ROOMMHP MOTOR HORSEPOWERMIN MINIMUMMM MILLIMETERMOT MOTORMOV MOTOR OPERATED VALVEMX MECHANICAL ROOM EXHAUST
N.O. NORMALLY OPENNC NORMALLY CLOSEDNIC NOT IN CONTRACTNO. NUMBERNPSH NET POSITIVE SUCTION HEADNTS NOT TO SCALE
OA OUTSIDE AIROAI OUTSIDE AIR INTAKEOD OUTSIDE DIAMETEROED OPEN END DUCTOV OUTLET VELOCITY
P PUMPPCC PRE-COOLING COILPD PRESSURE DROPPF PRE-FILTERPHC PREHEAT COILPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCHPSIA PSI ABSOLUTEPSIG PSI GAUGE
(RE) RELOCATED EXISTING(RRO) EXISTING TO REMOVED AND RETURN TO OWNERR RISERA RETURN AIRRAD RADIATIONRCC RECOOLING COILREFR REFRIGERANTRF RETURN FANRH RELATIVE HUMIDITYRHC REHEAT COILRHWP REHEAT WATER PUMPRLA RUNNING LOAD AMPSRM ROOMROT ROTATIONRPM REVOLUTIONS PER MINUTE
SA SUPPLY AIRSAU SOUND ATTENUATION UNITSCHWP SECONDARY CHILLED WATER PUMPSD SMOKE DETECTORSF SUPPLY FANSHWP SECONDARY HOT WATER PUMPSLD STRIPLINE DIFFUSERSMK.CTL. SMOKE CONTROL OPERATIONSP STATIC PRESSURESPEC SPECIFICATIONSQ.FT. SQUARE FEETSS STAINLESS STEELSX SMOKE EXHAUST
T THROATTAD TOP ANGULAR DISCHARGETDH TOTAL DYNAMIC HEADTEMP TEMPERATURETF TERMINAL FILTERTG TOP GRILLETHD TOP HORIZONTAL DISCHARGETR TOP REGISTERTRD TRANSFER DUCTTRF TRANSFER FANTRG TRANSFER GRILLETS TIP SPEEDTT TOP THROATTV TURNING VANESTX TOILET EXHAUSTTYP TYPICAL
UBD UPBLAST DISCHARGEUH UNIT HEATERUON UNLESS OTHERWISE NOTED
V VOLTSVA VENTILATION AIRVAC VACUUMVAV VARIABLE AIR VOLUME UNITVF VENTILATION FANVFD VARIABLE FREQUENCY DRIVEVIV VARIABLE INLET VANESVP VACUUM PUMP
W WIDTHW/ WITHW/O WITHOUTWB WET BULBWC WATER COLUMNWG WATER GAUGEWMS WIRE MESH SCREENWP WORKING PRESSUREWSP WORKING STEAM PRESSURE
A AMPERESAAV AUTOMATIC AIR VENTAC AIR CONDITIONINGACCU AIR COOLED CONDENSING UNITACS AUTOMATIC CONTROL SYSTEMACU AIR CONDITIONING UNITAD ACCESS DOORAF AFTER FILTERAFDW AIR FOIL DOUBLE WIDTHAFF ABOVE FINISHED FLOORAFMS AIR FLOW MONITORING STATIONAFSW AIR FOIL SINGLE WIDTHAHU AIR HANDLING UNITAL ALUMINUMAMCS AUTOMATED MONITORING AND CONTROL SYSTEMAP ACCESS PANEL
BAD BOTTOM ANGULAR DISCHARGEBD BLOW DOWNBF BOOSTER FANBFP BOTTOM GRILLEBG BOILER FEED PUMPBHD BOTTOM HORIZONTAL DISCHARGEBHP BRAKE HORSEPOWERBIDW BACKWARD INCLINE DOUBLE WIDTHBISW BACKWARD INCLUDE SINGLE WIDTHBMS BUILDING MANAGEMENT SYSTEMBR BOTTOM REGISTERBT BOTTOM THROATBTU BRITISH THERMAL UNITBTUH BTU PER HOUR
C CONVERTORCAR CONSTANT AIRFLOW REGULATORCC COOLING COILCCP CENTRAL CONTROL PANELCCW COUNTER CLOCKWISECD CEILING DIFFUSERCFFC CAP FOR FUTURE CONNECTIONCFM CUBIC FEET PER MINUTECFP CHEMICAL FEED PUMPCG CEILING GRILLECH CHILLERCHWP CHILLED WATER PUMPCLG CEILINGCOD CLEAN-OUT DOORCOMPR COMPRESSORCOND CONDENSATECOV CHAIR OPERATED VALVECP CONDENSATE PUMPCPA CONTROL POINT ADJUSTMENTCPU CONDENSATE PUMP UNITCR CEILING REGISTERCT COOLING TOWERCU FT CUBIC FEETCU IN CUBIC INCHESCUH CABINET UNIT HEATERCV CONSTANT VOLUMECW CLOCKWISECWP CONDENSER WATER PUMP°C DEGREES CENTIGRADE (CELSIUS)
D DROPDB DRY BULBDBD DOWN BLAST DISCHARGEDF DUCT FURNACE UNITDFWP DEARATOR FEED WATER PUMPDG DIESEL GENERATORDHW DOMESTIC HOTER WATERDMPR DAMPERDN DOWNDOP DIESEL OIL PUMPDWG DRAWINGDX DIRECT EXPANSIONø,DIAM DIAMETER
(E) EXISTING TO REMAIN(ER) EXISTING TO BE REMOVED(ERR) EXISTING TO BE REMOVED & RELOCATEDEA EACHEAT ENTERING AIR TEMPERATUREEDB ENTERING DRY BULB TEMPERATUREEDH ELECTRIC DUCT HEATEREDR EQUIVALENT DIRECT RADIATIONEF EXHAUST FANEL ELEVATIONELEC ELECTRICELEV ELEVATOREQ EQUALET EXPANSION TANKEUH ELECTRIC UNIT HEATEREWB ENTERING WET BULBEWT ENTERING WATER TEMPERATUREEXH EXHAUSTEXIST EXISTINGEXP EXPANSION
F FILTERF&T FLOAT AND THERMOSTATICFA FREE AREA (SQ.FT.)FC FLEXIBLE CONNECTIONFCDW FORWARD CURVED DOUBLE WIDTHFCSW FORWARD CURVED SINGLE WIDTHFCU FAN COIL UNITFD FIRE DAMPERFF FINAL FILTERFG FINISHED GRADEFIN FL FINISHED FLOORFLA FULL LOAD AMPERESFOP FUEL OIL PUMPFOT FUEL COIL TANKFPI FINS PER INCHFPM FEET PER MINUTEFPS FEET PER SECONDFR FLOOR REGISTERFT FEETFTR FINNED TUBE RADIATIONFV FACE VELOCITYFX FUME HOOD EXHAUST°F DEGREES FAHRENHEIT
G GAUGEGAL GALLONGPH GALLONS PER HOURGPM GALLONS PER MINUTEGX GENERAL EXHUAST
H HUMIDIFIERHALX HALON EXHAUSTHC HEATING COILHD HEAD
NO. ISSUE DATE: DESCRIPTION
CO
CO
GC
MC
EC
PC/FPC
WV
MH
MH
MH
MH
WV
WV
WV
MH
WV
WV
MH
WV
MH
WV
MH
MH
WV
MH
WV
WV
BENCHMARK
MAG NAIL SET IN
SIDEWALK SEAM
ELEVATION=317.62
EX. BUILDING
GORDINIER HALLEX. BUILDING
EX. BUILDING
STUDENT MEMORIAL
CENTER
EX.
BUILDING
EX.
BUILDING
EX.
BUILDING
FFE=320.17
FFE=320.21
FFE=320.22
FFE=304.93
C.O.
C.O.
C.O.
C.O.
C.O.
JAMES STREET
( MILLERSVILLE UNIVERSITY)
LOMBARDO WELCOMECENTER
WVWV
A
B
C
D
E
CLOSED LOOP VERTICAL BOREFIELDGEOTHERMAL HEAT EXCHANGERS.DEPRESS HEAD HEIGHT ANDHORIZONTALPIPING AS REQUIRED TO COORDINATEWITH OTHER UTILITIES. COORDINATEWITH CIVIL SITE PLAN FOR EXACT BORELOCATIONS AND PIPE ROUTING.
WHERE DESIGNATED BORES ARE NOT ABLETO BE DRILLED TO 400 FT, PROVIDEADDITIONAL BORES AND EXTEND PIPING LOOPTO MAKE UP LOST DEPTH AT GHOSTEDLOCATIONS INDICATED. INFORM ENGINEERIMMEDIATELY.
GEOTHERMAL BRANCHESTO BE 18" APART
(5) SETS OF 2" GEO SUPPLY/RETURN LINES(TO/FROM FIELD). SEE M-200 FORCONTINUATION. SEE STRUCTURALFOR COORDINATION.
PUMP ROOM. SEE M-200 FORCONTINUATION.
ACCU-1
BASE BID #2- ACCU-1 LOCATION.
CIRCUIT AS INDICATED. PROVIDE REVERSE RETURN TOEACH SET OF WELLS.
PIPE SIZES SHALL BE AS FOLLOWS:1 BORE: 1.5" (6.25 GPM)2 BORES: 1.5" (12.5 GPM)3 BORES: 2" (18.75 GPM)4 BORES: 2" (25.0 GPM)
REVERSE RETURN PIPING DIAGRAM (NTS)
GLYCOL SUPPLY/RETURN
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-001G150004-000
MECHANICAL SITE PLAN
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1" = 30'-0"1 LOWER LEVEL PLAN
DRAWING NOTES
GROUND LOOP INSTALLATION NOTES:
GENERAL: INSTALLATION SHALL BE IN ACCORDANCE WITH PROJECT SPECIFICATION SECTION 235743 AND CLOSED-LOOP/GEOTHERMAL HEATPUMP SYSTEMS DESIGN AND INSTALLATION STANDARDS 2014 EDITION PUBLISHED BY IGSHPA.
1. THE GROUND LOOP DESIGN FOR THIS PROJECT IS BASED UPON THE FOLLOWING PROPERTIES AS DRAWN FROM THE IN SITU THERMALCONDUCTIVITY TEST PREPARED BY GRTI / ALLIED WELL DRILLING, DATED OCTOBER 13, 2015.A. FORMATION THERMAL CONDUCTIVITY: 1.72 BTU/HR-FT-DEG FB. SOIL VOL. HEAT CAPACITY: 35.8 BTU/DEG F-FT^3C. GROUND TEMPERATURE: 55.7 DEG F
2. THE GROUND LOOP DESIGN FOR THIS PROJECT IS BASED UPON THE FOLLOWING PROPERTIES AS DETERMINED BY THE PROJECTSPECIFICATION:A. BOREHOLE SPACING: 20' O.C. MINIMUMB. GROUT THERMAL CONDUCTIVITY 1.1 BTU/HR-FT-DEG F, MINIMUMC. VERTICAL PIPE CHARACTERISTICS: PE4710, SDR 9, 1.5" NOMINAL DIAMETERD. BOREHOLE CONFIGURATION: SINGLE U-BEND (2-PIPES PER BORE)E. FLUID: 20% PROPYLENE GLYCOL
3. THE BOREFIELD IS BASED ON THE FOLLOWING NOMINAL LENGTHS:A. BOREFIELD TOTAL ACTIVE LENGTH: 7,900 FT VERTICAL BOREHOLE LENGTHB. NOMINAL BOREHOLE QUANTITY: 20C. BOREHOLE DEPTH EACH: 400 FT BELOW GRADED. BOREHOLE ACTIVE DEPTH EACH: 395 FT
4. COORDINATION AND WARRANTYA. THE EXTENT AND SCHEDULE OF DRILLING AND EXCAVATION FOR GEOTHERMAL PIPING SHALL BE COORDINATED BY THIS CONTRACTOR WITH
SCOPES OF WORK SHOWN ON CIVIL AND STRUCTURAL DESIGN DOCUMENTS.B. ALL TRENCHING FOR GROUND LOOP AND HEADERING SHALL BE A MINIMUM OF 24" WIDE.C. COORDINATE TRENCHING AND EXCAVATION REQUIREMENTS WITH ALL OTHER SITE WORK, ALL RELEVANT STANDARDS AND LOCAL
REGULATIONS.D. STANDARDS FOR BACKFILL, COMPACTION AND ALL OTHER RELEVANT SITE WORK SHALL BE COORDINATED WITH ALL OTHER SITE WORK TO
ENSURE ALL PERFORMANCE REQUIREMENTS FOR WORK SPECIFIED ELSEWHERE ARE MET. ALL CIVIL AND STRUCTURAL DESIGNDOCUMENTS ARE HEREBY INCORPORATED INTO THIS CONTRACT BY REFERENCE AND ARE BINDING ON THIS CONTRACTOR.
E. LOOP CONTRACTOR SHALL BE EXPERIENCED IN LOOP DESIGN AND INSTALLATION AND SHALL BE CERTIFIED BY IGSHPA. LOOP CONTRACTORSHALL BE RESPONSIBLE FOR ALL PERMITS AND INSPECTION OF THE LOOP FIELD.
F. AS-BUILT DRAWINGS OF THE LOOP FIELD SHALL BE PROVIDED BY THE LOOP CONTRACTOR.G. THE GROUND LOOP SHALL BE WARRANTED AGAINST LEAKS FOR 10 YEARS BY THE PIPING MANUFACTURER AND THE INSTALLING
CONTRACTOR, INCLUDING ALL PARTS, MATERIALS, LABOR, AND SERVICES.
5. BOREHOLE DRILLINGA. VERTICAL BOREHOLES SHALL BE DRILLED IN ACCORDANCE WITH APPLICABLE LOCAL CODES AND REGULATIONS. DRILLER SHALL BE
LICENSED IN ACCORDANCE WITH CODE AND BE EXPERIENCED IN GROUND LOOP DRILLING AND GROUTING PROCEDURES.B. HEADERING AND ALL OTHER GROUND LOOP PIPE CONNECTIONS SHALL BE COMPLETED BY AN IGSHPA CERTIFIED CONTRACTOR
EXPERIENCED IN THE CONSTRUCTION OF GROUND LOOPS.C. CONTAIN, MANAGE, AND DISPOSE OF DRILL CUTTINGS IN ACCORDANCE WITH LOCAL REGULATIONS.D. AFTER THE LOOP INSTALLATION, BOREHOLES ARE TO BE IMMEDIATELY BACKFILLED WITH THERMALLY ENHANCED BENTONITE GROUT IN
ACCORDANCE WITH THE SPECIFICATION.E. DRILLING CONTRACTOR SHALL PROVIDE WRITTEN GUARANTEE THAT THE BOREHOLES ARE COMPLETELY BACKFILLED.F. PROVIDE DRILL LOG INDICATING ACCURATE GPS POSITION OF EACH VERTICAL BOREHEAD, USING LATITUDE AND LONGITUDE WITH
SUFFICIENT PRECISION TO LOCATE THE BOREHEADS.
6. GROUND LOOP (HEAT EXCHANGER AND HEADER) MATERIALSA. PIPING MATERIAL SHALL BE HIGH DENSITY POLYETHYLENE (HDPE) PE 4710B. VERTICAL PIPE SHALL BE MANUFACTURED IN ACCORDANCE WITH ASTM D-3035 WITH A STANDARD DIMENSION RATIO (DR) OF 9.C. HORIZONTAL PIPE SHALL BE MANUFACTURED IN ACCORDANCE WITH ASTM D-3035 WITH A STANDARD DIMENSION RATIO (DR) OF 11.
7. PIPE FUSION AND CONFIGURATIONA. ALL BURIED PIPE SHALL BE HEAT FUSED BY BUTT, SOCKET, OR ELECTROFUSION IN ACCORDANCE WITH THE PIPE MANUFACTURER'S
PROCEDURES. ALL JOINING TO BE PERFORMED BY FACTORY-TRAINED INSTALLERS WITH CURRENT IGSHPA CERTIFICATION DOCUMENTS.B. VERTICAL PIPES SHALL BE FUSED TO THE LATERAL PIPING FIVE (5) FEET BELOW FINISHED GRADE.C. SUPPLY AND RETURN PIPING FROM THE LOOP FIELD TO THE MECHANICAL ROOM SHALL BE AT LEAST THREE (3) FEET BELOW FINISHED
GRADE.D. WHERE REQUIRED, PIPING OUTSIDE OF A BUILDING OR IN AN EXTERIOR WALL SHALL BE PROTECTED FROM FREEZING, AND SLEEVES SHALL
BE INSTALLED WHERE PIPING PASSES THROUGH MASONRY, CONCRETE, OR ANY FIRE SEPARATION PER IBC 2009 SECTION 713.E. SHUT-OFF VALVES, BALANCING VALVES AND FUSED CONNECTING FLANGES SHALL BE PROVIDED AT THE SUPPLY AND RETURN LINE
TERMINATION POINTS IN THE MECHANICAL ROOM BY THIS CONTRACTOR.
8. HORIZONTAL PIPING INSTALLATIONA. LOCATE HORIZONTAL PIPING 5'-0" BELOW GRADE ON CENTER, UNLESS OTHERWISE NOTED. PROVIDE ELBOWS AS REQUIRED TO
ACCOMMODATE CHANGES IN SITE ELEVATION.B. INSTALL EACH PIPE IN THE CENTER OF AN 18" DEEP SAND BED CONSTRUCTED OF WELL-GRADED SAND, HAND LAID ABOVE PIPE. COMPACT
SAND; BACKFILL TRENCH WITH APPROVED FILL AND PROVIDE COMPACTION.C. PROVIDE TRACER WIRE FOR EACH CIRCUIT FROM ACCESSIBLE LOCATION ADJACENT TO MECHANICAL ROOM. WRAP TRACER WIRE AROUND
PIPE FOR TRACER WIRE ON TOP OF 3" OF SAND ON TOP OF ENTIRE HORIZONTAL RUN OF LOOP.D. PROVIDE LOCATOR DISKS SIMILAR TO GEOTHERMAL SUPPLY COMPANY GDM4 OR GDM10 AT EACH TEE AND AT EACH WELLHEAD FOR
FUTURE WAY-FINDING. FURNISH DISK LOCATOR DEVICE SIMILAR TO GEOTHERMAL SUPPLY COMPANY GDM-L TO OWNER FOR FUTURELOCATION OF DISKS.
E. PROVIDE HORIZONTAL METALLIC CAUTION TAPE ON TOP OF SAND BACKFILL OVER ENTIRE HORIZONTAL RUN (LOOPS AND MAINS BACK TOBUILDING).
F. PROVIDE HORIZONTAL PLASTIC YELLOW WARNING TAPE 1 FT BELOW GRADE ABOVE ENTIRE HORIZONTAL RUN (LOOPS AND MAINS BACK TOBUILDING).
NO. ISSUE DATE: DESCRIPTION
48x36X56EXHAUST AIRPLENUM
48x36x56OUTDOOR AIRINTAKE PLENUM. PROVIDE 3/4" CAPPEDDRAIN OUTLET.
22X20 OUTDOOR AIRSUPPLY DUCTWORKUP. PROVIDE FIREDAMPER THROUGHPENETRATION AT BASEOF SHAFT.
10X20 HEAT PUMP RETURN AIRDUCTWORK UP. PROVIDE FIREDAMPER THROUGHPENETRATION AT BASE OFSHAFT.
10X12 EXHAUST AIR DUCTWORKUP. PROVIDE FIRE DAMPERTHROUGH PENETRATION AT BASEOF SHAFT.
PROVIDE AND INSTALL 48x36 EXHAUST AIRLOUVER MIN. 50% FREE AREA. LOUVER SHALL BECS MODEL A2097 OR GREENHECK EDD-401.BOTTOM OF LOUVER MINIMUM OF 4'-0" ABOVEGRADE; COORDINATE FINAL ELEVATION WITHARCHITECTURAL DRAWINGS.
PROVIDE AND INSTALL 48x36 OUTDOOR AIRLOUVER MIN. LOUVER SHALL BE CS MODELA2097 OR GREENHECK EDD-401. 50% FREEAREA. BOTTOM OF LOUVER MINIMUM OF 4'-0"ABOVE GRADE; COORDINATE FINAL ELEVATIONWITH ARCHITECTURAL DRAWINGS.
OUTDOOR AIRDUCT INTRENCH
EXHAUST AIRDUCT INTRENCH
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
INSTALL DUCT IN TRENCH.
10X20 OUTDOOR RELIEF AIRDUCTWORK UP. PROVIDE FIREDAMPER THROUGH PENETRATIONAT BASE OF SHAFT.
HEAT PUMP SUPPLY AIRDUCTWORK UP (TYPICAL OF 4).PROVIDE FIRE DAMPERTHROUGH PENETRATION ATBASE OF SHAFT.
EF-1
EF-2
8x8
8x8
8x10
8x8
22x20
10x12
10x20
20x1
0
12ø16ø
48x36
48x36
10x20
22x2
0
42x20
16x1
6
12x12
36x22
16x1
6
12X24RETURN AIRTO OAU-1
28X20OUTSIDE AIRSUPPLYFROM OAU-1
36X22 EXHAUST AIR FROM OAU-1TO EXIT UNIT BELOW SUPPLYOUTLET.
P-2P-1
HP-19 HP-20 HP-21 HP-22 HP-23 HP-W
ACCU-1
P-3
TRANSITION TO PRE-FABRICATEDUNDERGROUND DUCTPRIOR TO DROPPINGBELOW ELEVATION OFSLAB.
TRANSITION FROM PRE-FABRICATEDUNDERGROUND DUCTAFTER RISING ABOVEELEVATION OF SLAB.
MOTORIZED DAMPER.
MOTORIZEDDAMPER.
PROVIDE 4" HIGHHOUSEKEEPING PADFOR OAU-1. PAD TOEXTEND A MINIMUM OF6" BEYOND UNIT IN ALLDIRECTIONS.
(2) BMS CONTROLPANELS.
2M-300
1
ROUTE CONDENSATE FROM HEATPUMPS TO NEAREST FLOOR DRAIN.SEE PLUMBING FLOOR PLANS FORDRAIN LOCATIONS. (TYPICAL)
12X10EXHAUST OPEN ENDEDDUCT WITH WIRE-MESHSCREEN.
P-4
OAU-1
5M-501
TRENCH BY OTHERS.
BASE BID #2 - ALTERNATEACCU-1 LOCATION. PROVIDE 4"HIGH HOUSEKEEPING PAD FORALTERNATE LOCATION. PAD TOEXTEND A MINIMUM OF 6"BEYOND UNIT IN ALLDIRECTIONS.
PROVIDE 4" HIGHHOUSEKEEPING PAD FORACCU-1. PAD TO EXTEND AMINIMUM OF 6" BEYOND UNITIN ALL DIRECTIONS.
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-100G150004-000
MECHANICAL LOWER LEVELPLAN - DUCTWORK
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN
DRAWING NOTES
1. COORDINATE DUCT AND HANGING EQUIPMENT ELEVATIONS WITH STRUCTURAL DRAWINGS AND ARCHITECTURAL REFLECTED CEILING PLANS.
KEY NOTES
COORDINATE SHAFT ROUTING WITH ALL OTHER TRADES.1
NO. ISSUE DATE: DESCRIPTION
HP-1
HP-2
HP-3
HP-4
HP-5
HP-6 HP-7
HP-8
HP-9 HP-10 HP-11
HP-12
HP-13
HP-14
HP-15
HP-16
HP-17
HP-18
VAVB-2VAVB-1
VAVB-8
VAVB-7
VAVB-9
VAVB-10
VAVB-11
VAVB-5VAVB-6VAVB-3
BR-1
CAR TO BE SIMILAR TO ALDES LOW-PRESSURE CONSTANT AIRFLOWREGULATOR. CAR AND MD TYPICAL ONALL OA DUCT BRANCHES, SIZED TOMATCH DUCT.
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
VEST.V-1
ALCOVEL101-5
WOMEN'S143
PASSAGE104
MEN'S142
ALCOVEL101-6JANITOR
141
MECHANICAL141.1
FAMILYTOILET
144
STORAGE140.1
PASSAGEL101-7
VEST.V-2
CLASSROOM/PRESENTATIONROOM
140
V.P. OFFICE112A
SMALL CONF.105
STORAGE103.1
OFFICE112
PASSAGEL101-1
OFFICE118
OFFICE114
OFFICE116
OFFICE110
OFFICE108
OFFICE104
CORRIDORC 1-1
CORRIDORC 1-2
BREAK ROOM107
STORAGE119
ELEC. RM.121
COFFEESTATIONL101-3
STORAGE103.2
ADMISSIONSOPEN OFFICE
106
HOUSINGOPEN OFFICE
130
OFFICE128
OFFICE126
OFFICE124
OFFICE122
MARKETINGOPEN OFFICE
120
SMALL CONF.115
CONFERENCE117
I.T. ROOM123
CALL CENTER109
CORRIDORC 1-3
OFFICE102
WORK ROOM111
RESOURCEROOM
103
RECEPT.L101-2
STUDENTWORK SPACE
113
LOBBYL101
18x1
210x8
8ø
6x6
6x6
8x8
10x812x12
8ø
10x8
8x8
10ø
10ø
8x8
8ø
6ø6x6
6x6
4ø
4ø
6ø8ø
8ø
8ø
8x8
8x8
10ø
6x6
8x10
4ø
4ø
4ø
4ø6ø
8ø
8x8
8ø
4ø22x12
14x8
6ø
6ø
6ø
4ø10ø
20x1018x10
16ø
12x1210x8
4ø
10x8
12x1
2
4ø
4ø
10x8
10ø
10ø
4ø
10x108x8
6ø
8ø
8ø
8x12
10ø
6ø
10ø
CAR
MD
6x6
8x6
6x6
6ø6ø
4ø10x8
6x10
10x1
2
10ø10
ø
10x8
12ø
14ø
1 2x141 2x14
18x16
LD-C340
SA: 325/OA: 15
(2)CD-B25EA.
LR-B
6ø
4ø
LR-B
LD-C375
SA: 375/OA: 15
LD-C340
SA: 325/OA: 15
LR-BLR-B
LD-A105
LD-B205
SA:105/OA: 100
LD-A105
LD-A105
LD-B190
SA: 175/OA:15
LR-A
LD-B115
SA: 100/OA: 15LR-A
LD-B115
SA: 100/OA: 15
LR-A
LD-B140
SA: 120/OA: 20
LR-A
LD-C245
SA: 225/OA: 20LR-B
LD-B115
SA: 100/0A: 15
LR-A
LD-B115
SA: 100/OA: 15
LR-ALD-A120
(10)LD-A120EA.
LD-B125
SA: 125/OA: 55
LD-A125
LD-B95
SA: 80/OA: 15
LR-A
LD-B95
SA: 80/OA: 15
LR-A
(6)LD-A120EA.
(2)LD-A175
(TYP. OF 2)
LR-A
LD-A150 LR-B
LD-C235
SA: 150/OA: 85LR-A
LD-B130
SA: 100/OA: 30
LD-C305
SA: 250/OA: 55
LR-B
LD-B165
SA: 150/OA: 45
LR-A
LD-B80
SA: 55/OA: 25
LD-C350
SA: 275/OA: 75
LR-BLR-A
LD-B125
SA: 95/OA: 30
LR-A
LD-A175
LD-A175
CD-B25
LD-C340
SA: 325/OA: 15
SR-A50
SR-A50
CD-B10
CD-B10
LD-A120
LD-A120
LD-A200LD-A
120
4ø4ø
(3)SR-B100EA.
(3)SR-B100EA.
LD-D150
LD-D200
LD-D150
LD-D200
LD-D150
LD-D200
CD-A75
CD-B15
LD-D450
ER-A150
ER-A75
CD-A75
12ø
12ø
12ø
6ø12ø
20x14
12ø
12ø
16ø
10ø 14x14
8 ø
1 0ø8 ø
8 x8
8x6
6x6
BR-1BR-1
BR-1
LD-E400
8x10
6ø
6ø6ø
6ø
VAV-110ø
6ø
TF-1
8x8
22x10
AC-1
CD-B10
10x8
LD-A115
8ø 8ø
4ø
4ø4ø
8ø8ø
6 ø
4 ø
8 x8
10x10
ER-B75
8ø
12x1212x10
8ø 8ø 6ø 8ø
6ø8ø
8ø6ø8ø
8x8
8x8
8x8
8x8
8x88x8TG-1
8x8TG-1
8x8TG-1
8x8TG-1
8x8TG-1
6ø
14x1
4
6x6
VAVB-4
ER-A150
(3)SR-A150EA.
(3)SR-A150EA.
14ø
10ø
6ø
6ø
6ø 8ø
6ø
1 0ø
6ø 8ø
6ø
1M-300
1 1
212" ROUND EXHAUSTDOWN
16" ROUND OUTDOORAIR DOWN
LD-A120
3M-300
2M-300
3
4M-300
4
6x6
6x6
6x6TG-1
10x10TG-1
14x14TG-1 10x10
TG-114x18TG-1
12x12TG-1
6x6TG-1
6x6TG-1
14x12TG-1
24x18TG-1
14x14TG-1
14x14TG-1
12x12TG-1
8x8TG-1
14x14TG-1
8ø 8ø
8ø 8ø 8ø 8ø 8ø
8ø 8ø
8ø
8ø
8ø
6x6
6x6
6x6
10x8TG-1
10x8TG-1
10x8 10
x8
6x6
CR-A
CR-A
10x8TG-1
LR-A
LR-A
10x8TG-1
4ø
10x8
10x8
6x6
LR-A
LR-A
LR-A
LR-A
LD-D450
LD-D450
LR-C
LR-C
LD-D450
LD-D450
LD-D450
LR-C
LR-C
LD-D450
LD-D450
30x10TG-1
30x10TG-1
16x10TG-1
1 4x12
12ø
12ø6ø
8x6
AC-2
55
5
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-101G150004-000
MECHANICAL GROUNDFLOOR PLAN - DUCTWORK
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN
DRAWING NOTES
1. CONSTANT AIRFLOW REGULATOR (CAR) TO BE SIMILAR TO ALDES LOW-PRESSURE CONSTANT AIRFLOW REGULATOR. CAR AND MOTORIZEDDAMPER (MD) TYPICAL ON ALL OA DUCT BRANCHES, SIZED TO MATCH DUCT.
2. COORDINATE DUCT AND HANGING EQUIPMENT ELEVATIONS WITH STRUCTURAL DRAWINGS AND ARCHITECTURAL REFLECTED CEILING PLANS.3. ALL TRANSFER DUCTS TO BE OPEN ENDED WITH WIRE MESH SCREENS UNLESS OTHERWISE INDICATED.
1
KEY NOTES
TRANSITION TO PRE-FABRICATED UNDERGROUND DUCT SIMILAR TO BLUE DUCT PRIOR TO DUCT DROPPING BELOW ELEVATION OF SLAB.
PROVIDE WIRE MESH SCREEN ON RETURN AND RELIEF DUCT OPENINGS.
COORDINATE SHAFT ROUTING WITH ALL TRADES. PROVIDE FIRE DAMPER IN DUCTS AT EACH SHAFT PENETRATION. SEE DETAIL ON M-501.
OUTDOOR AIR TO LARGE CONFERENCE TO BE CONTROLLED WITH MOTORIZED DAMPER (MD) AND PRESSURE INDEPENDENT MODULE (PIM).
PERIMETER SLOT DIFFUSER CEILING TRIM BY GC. HVAC CONTRACTOR SHALL MAKE FINAL PLENUM CONNECTION TO CEILING TRIM.
2
3
4
5
NO. ISSUE DATE: DESCRIPTION
SEE GLYCOL CHARGING DETAIL ONM-500. CONTAINS GMU-1. PROVIDE 4"HIGH HOUSEKEEPING PADS THATEXTEND A MINIMUM OF 6" IN ALLDIRECTIONS BEYOND EQUIPMENT INDETAILS. GLYCOL TANKS TO BELABELED WITH PERCENTAGE ANDTYPE OF GLYCOL AND THEMANUFACTURER OF THE SOLUTION.
GEOEXCHANGE FIELD HEADERSTHRU WALL. MINIMUM OF 5' BELOWGRADE. SEE DETAIL ON M-501 FORSPACING.
4" GLYCOL SUPPLY& RETURN UP. SEEM-201 FORCONTINUATION.
HP-19
HP-20
HP-21
HP-22
HP-23
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
HP-W
P-2
P-1
ACCU-1
EF-2
GLYCOL SUPPLY ANDRETURN IN TRENCH.
NEMA 3R RATED ENCLOSURE.TERMINATE ALL TRACERWIRE AND TAG WITH LOOPIDENTIFIER PER PLANS.
REFRIGERANT PIPING TOCHANGE ELEVATION WITHININTERIOR OF BASEMENT ANDPENETRATE EXTERIOR WALLNEAR GRADE. COORDINATEELEVATION OF EXTERIORPENETRATION WITH ARCHITECT.
P-3
3" GLYCOL SUPPLY ANDRETURN UP. SEE M-201 FORCONTINUATION.
1" HW SUPPLY &RETURN UP. SEEM-201 FORCONTINUATION.
MAKE-UP WATER CONNECTION.SEE PLUMBING DRAWINGS FORCONTINUATION.
REFRIGERANTLINES UP. SEEM-201 FORCONTINUATION.
CONDENSATE DRAIN UP.ROUTE TO NEAREST FLOORDRAIN. SEE PLUMBING FLOORPLANS FOR DRAIN LOCATIONS. 1
ROUTE CONDENSATE FROM HEATPUMPS TO NEAREST FLOOR DRAIN.SEE PLUMBING FLOOR PLANS FORDRAIN LOCATIONS. (TYPICAL)
ROUTE CONDENSATE FROM OAU-1AND GLYCOL CHARGING SKID TONEAREST FLOOR DRAIN. SEEPLUMBING FLOOR PLANS FOR DRAINLOCATIONS. (TYPICAL)
3"
3"
4"4"
2"
2"
2"
2"
3/4"
3/4"
3/4"
3/4"
3/4"
11/2"
1 1/2"
11/4"
4"
11/4"
4"
P-4
ET-2
(2) BMS CONTROLPANELS.
PROVIDE 4" HIGHHOUSEKEEPING PADFOR OAU-1. PAD TOEXTEND A MINIMUM OF6" BEYOND UNIT IN ALLDIRECTIONS.
REFRIGERANT PIPINGSHALL BE SIZED PERMANUFACTURER'SRECOMMENDATIONS.
TRENCH BY OTHERS.
BASE BID #2 - ACCU-1 LOCATION.PROVIDE 4" HIGH HOUSEKEEPING PADFOR ALTERNATE LOCATION. PAD TOEXTEND A MINIMUM OF 6" BEYONDUNIT IN ALL DIRECTIONS. ROUTEREFRIGERANT PIPING TO ALTERNATELOCATION.
PROVIDE 4" HIGHHOUSEKEEPING PAD FORALTERNATE LOCATION. PAD TOEXTEND A MINIMUM OF 6"BEYOND UNIT IN ALLDIRECTIONS
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-200G150004-000
MECHANICAL LOWER LEVELPLAN - PIPING
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN
KEY NOTES
COORDINATE SHAFT ROUTING WITH ALL OTHER TRADES.1
DRAWING NOTES
1. SEE FLOW DIAGRAM AND DETAILS FOR PIPING SPECIALTIES.
NO. ISSUE DATE: DESCRIPTION
HP-3
HP-4
HP-1
HP-2
HP-5
HP-10
HP-13
HP-16
HP-18HP-14HP-12HP-8
HP-11
HP-9
HP-17
HP-7HP-6HP-15
VAVB-2VAVB-1
VAVB-8
VAVB-7
VAVB-9
VAVB-10
VAVB-11
VAVB-5 VAVB-6VAVB-3
RADIANT HEAT FLOORING. SEE DETAILS.
MANIFOLD FOR RADIANT HEAT FLOORING.COORDINATE LOCATION WITH ARCHITECT.
RADIANT HEAT FLOORING. SEE DETAILS.
MANIFOLD FOR RADIANT HEAT FLOORING.COORDINATE LOCATION WITH ARCHITECT.
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
VEST.V-1
ALCOVEL101-5
WOMEN'S143
PASSAGE104
MEN'S142
ALCOVEL101-6JANITOR
141
MECHANICAL141.1
FAMILYTOILET
144
STORAGE140.1
PASSAGEL101-7
VEST.V-2
CLASSROOM/PRESENTATIONROOM
140
V.P. OFFICE112A
SMALL CONF.105
STORAGE103.1
OFFICE112
PASSAGEL101-1
OFFICE118
OFFICE114
OFFICE116
OFFICE110
OFFICE108
OFFICE104
CORRIDORC 1-1
CORRIDORC 1-2
BREAK ROOM107
STORAGE119
ELEC. RM.121
COFFEESTATIONL101-3
STORAGE103.2
ADMISSIONSOPEN OFFICE
106
HOUSINGOPEN OFFICE
130
OFFICE128
OFFICE126
OFFICE124
OFFICE122
MARKETINGOPEN OFFICE
120
SMALL CONF.115
CONFERENCE117
I.T. ROOM123
CALL CENTER109
CORRIDORC 1-3
OFFICE102
WORK ROOM111
RESOURCEROOM
103
RECEPT.L101-2
STUDENTWORK SPACE
113
LOBBYL101
AC-1
VAV-1TF-1
BR-1BR-1
BR-1BR-1
VAVB-4
T
HP-1
HP-3
T
HP-4
T
HP-5
T
HP-2
T
VAVB-1 VAVB-2
T
HP-7
T
T
HP-8
HP-9
TT
HP-10
T
HP-11
VAVB-4
T
VAVB-3
T
VAVB-5
T
VAVB-6
T
HP-13
T
HP-15
T
VAVB-7
T
VAVB-8
T
VAVB-9
T
HP-19
T
VAVB-10
T
VAVB-11
T
HP-22
T
HP-17
T
HP-21
T
4" GLYCOL SUPPLY ANDRETURN DOWN. SEEM-200 FORCONTINUATION.
1" HW SUPPLY ANDRETURN DOWN. SEE M-200FOR CONTINUATION.
3" GLYCOL SUPPY ANDRETURN DOWN TOTRENCH.
THERMOSTAT TOALIGN WITH SWITCHES.
THERMOSTAT TOALIGN WITH SWITCHES.
HP-18
T
CO2
CO2T
CO21
CONDENSATE MAINTO ROUTE THROUGHBUILDING CORE TOSHAFT AND DOWNTO BASEMENT.
CONDENSATE FROMHP-1 TO 5 TO ROUTETO MOP RECEPTOR INJANITOR CLOSET.(TYPICAL)
INSTALL AUTO-FLOW BALANCING VALVE IN BYPASS.
INSTALL SELF-CONTAINED PRESSURE REGULATING VALVE.
INSTALL SELF-CONTAINED PRESSURE REGULATING VALVE.
3"
3"
3/4"
3/4"
3/4"
3/4"
1"1"1"3/4"
3"
3/4"
3/4"
1" 1"
1"
11/2"
3"3"
1"11/2"
1"
4"
21/2"
1"
1 1/2"
4"
3"
11/4"
1 1/4"
1 1/4"
1 1/4" AC-2
REFRIGERANT PIPINGSHALL BE SIZED PERMANUFACTURER'SRECOMMENDATIONS.
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-201G150004-000
MECHANICAL GROUNDFLOOR PLAN - PIPING
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN
DRAWING NOTES
1. PROVIDE CONDENSATE DRAIN PIPING FOR ALL HEAT PUMP AND AC UNITS.2. CONDENSATE DRAIN PIPING TO SLOPE 1/4" PER FOOT. AVOID OPEN OR VISIBILE CEILING SPACES WHERE POSSIBLE AND ROUTE CONDENSATE
MAIN WITHIN FULL HEIGHT WALLS IN CORE SPACE. CONDENSATE MAY NOT CROSS OVER ELECTRIC OR IT ROOMS.3. SEE FLOW DIAGRAM AND DETAILS FOR PIPING SPECIALTIES.4. SIZE REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS.
KEY NOTES
COORDINATE SHAFT ROUTING WITH ALL OTHER TRADES.1
NO. ISSUE DATE: DESCRIPTION
12 14 15
10ø8x1012x12
HP-12
VAVB-4
JHE F G
TRANSITION TO PRE-FABRICATEDUNDERGROUND DUCTPRIOR TO DROPPINGBELOW ELEVATION OFSLAB.
DUCT AND GLYCOLSUPPLY/RETURN IN TRENCH.TRENCH TO BE PROVIDED BYOTHERS.
16" DIA. OUTDOORAIR DUCT INTRENCH
12' DIA. EXHAUSTAIR DUCT INTRENCH
YY
10ø
6ø6ø
14ø
10ø
6ø 6ø
14ø
10ø
14ø8ø
6øHP-1
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-300G150004-000
MECHANICAL SECTIONS
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/2" = 1'-0"1 M_SECTION-1SCALE: 1/4" = 1'-0"2 M_SECTION-2
SCALE: 3/8" = 1'-0"4 M_SECTION-4SCALE: 1/2" = 1'-0"3 M_SECTION-3
NO. ISSUE DATE: DESCRIPTION
SCALE: NTS
P-1
P-2
DP
DP
VSD
VSD
WATER-FLOW DIAGRAM
OAU-1
HP-19
HP-20
HP-21
HP-22
HP-W
HP-17
HP-18
HP-16
HP-15
HP-13
HP-14
HP-11
HP-10
HP-12
HP-9
HP-7
HP-8
HP-6 HP-1
HP-2
HP-3
HP-5
HP-4
INSIDE BUILDING
OUTSIDE
BY INTERIORCONTRACTOR
BY LOOPCONTRACTOR
Z-1 Z-2
Z-1Z-2
Z-3 Z-4
Z-3Z-4
AUTOFLOWBALANCINGVALVE
SELF-CONTAINEDPRESSURE REGULATINGVALVE. SHALL BE SIMILAR TODANFOSS AVDO.
CALIBRATED BALANCING VALVE (TYP.)
ET-1
AUTOMATIC AIRVENT 1" SPILL TO FD
RELIEF VALVE SPILLTO NEAREST FLOOR DRAIN
TANGENTIAL AIRSEPARATORFILL/PURGE VALVE WITHFLANGED CONN. TO 1"HOSE OUTLET
432
5
1
6
AIR ELIMINATOR SIMILAR TOSPIROVENT MODEL VJR125
ET-2
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-301G150004-000
MECHANICALGEOTHERMAL FLOW
DIAGRAM
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
DRAWING NOTES
1. SEE DETAILS ON DRAWINGS M-500 AND M-501 FOR ADDITIONAL INFORMATION.2. PROVIDE AUTOMATIC AIR VENTS AT ALL PIPING HIGH POINTS IN MECHANICAL ROOM.3. PROVIDE MANUAL AIR VENTS AT ALL PIPING HIGH POINTS IN FINISHED SPACES.
KEY NOTES
INSTALL TWO DRAIN VALVES AT LOW POINT IN SYSTEM. LOW POINT TO BE FIELD VERIFIED.
TO/FROM GEOTHERMAL WELLFIELD. SEE PLAN FOR QUANTITY AND PIPING ARRANGEMENT.
PROVIDE HDPE PIPING FOR GROUND-LOOP EXCHANGER PER SPECIFICATION.
SEAL WALL AND FLOOR PENETRATION WATER-TIGHT. SEE DETAIL ON M-501.
SEE FLOOR PLANS FOR PIPE SIZES.
BUFFER TANK - SIMILAR TO TACO MODEL BT, 50 GALLONS WITH 2" THICK FIBERGLASS INSULATION AND ALUMINUM JACKET.
1
2
3
4
5
6
NO. ISSUE DATE: DESCRIPTION
c
c
c
c
c
c
c
c
c
SCALE:
c c cc
NTSAIRFLOW DIAGRAM
GROUND LEVEL
LOWER LEVEL
EF-1
OAU-1
HP-19 HP-20 HP-21 HP-22
EF-2
450
MAX: 1500
1720
1070
230
100
1950
1950
MAX: 600
(MAX)
(MAX)
320 350 190225
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-302G150004-000
MECHANICAL AIR FLOWDIAGRAM
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION
FAN SCHEDULE
SPLIT SYSTEM AC SCHEDULE
CONDENSING UNIT SCHEDULE
OUTDOOR AIR UNIT SCHEDULESUPPLY FAN DATA EXHAUST FAN DATA COIL - COOLING DATA
BASIS OF DESIGNTAG SERVICE LOCATION AIRFLOW SP (IN.WG.) MOTOR DATA EXHAUST SP (IN.WG.) MOTOR DATA CAPACITY (MBH)EAT (°F) LAT (°F)
(CFM) EXT. TOTAL MAX BHP RPM CFM EXT. TOT. MAX BHP RPM SENSIBLE TOTAL MCA
NOTES:1. PROVIDE VFD ON SUPPLY FAN & ON EXHAUST FAN2.3.4.
FANS ARE TO BE INTERNALLY VIBRATION ISOLATED.
5.
SEE AIR FILTER SECTION SCHEDULE.PROVIDE DUCT FLANGES FOR SUPPLY, RETURN, OUTDOOR AIR AND RELIEF DUCTS.SEE DIAGRAM BELOW FOR ADDITIONAL ACCESSORY AND ARRANGEMENT INFORMATION.
PUMP SCHEDULETOTAL IMPELLER OPER. SIZE IN.
SYMBOL TYPE LOCATION SERVICE GPM HEAD DIAMETER TEMP. EFF. RPM HP BHP VFD FOUND. BASIS OF DESIGNFT.WG IN. F° SUCT. DISCH. % TYPE
P-1 IN-LINE BASEMENT GROUND LOOP 123.7 75.3 4.625 80 2 2 76 3450 5 YES BELL & GOSSETT - E-90 2AAC
NOTES:1. PUMPS TO BE NON-OVERLOADING AT EVERY POINT ON PUMP CURVE.
OAU-1 VENTILATION BASEMENT 1950 2.0 3.16 2214 1600 1.0 1.76 1703 40.41.41 TRANE HORIZON WSHP D0720.67
3.97
AIR FILTER SCHEDULESUPPLY AIR SEGMENT EXHAUST AIR SEGMENT
UNIT TYPE SERVICE CFM APD / IN. WG MERV-A APD / IN. WG MERV-A REMARKS BASIS OF DESIGNLOC. INITIAL FINAL RATING TYPE INITIAL FINAL RATING TYPE
OAU-1 1950 PF MERV-8 PLEATED MERV-8 PLEATED SEE NOTES 1 & 2 CAMFIL-FARR 30/30
NOTES:1. SUPPLY AIR SEGMENT IS LOCATED UPSTREAM OF WHEEL ON OUTDOOR AIR SIDE. EXHAUST AIR SEGMENT IS LOCATED UPSTREAM OF WHEEL ON RETURN SIDE.2. ALL PERFORMANCE DATA SHALL BE IN ACCORDANCE WITH ASHRAE 52.2-2012 AND AHRI STANDARD 850-2013.
VOLTAGE PHASEHZ
208 60 3
ELECTRICAL DATA
VOLT PHASE FLAHZ
UNIT ELECTRICAL DATA
208 60 34.683
HOT GAS REHEAT COIL
80.52 / 64.5356.2 / 55.6
AIRFLOW (CFM)SUMMER PERFORMANCE
SUPPLY EXHAUSTEAT (°F) LAT (°F)
DB WB DB WB
1950 1600 95.0 75.0 82.7 67.855.7
GLYCOL MAKEUP UNITTANK FILL TOTAL OPER.
SYMBOL LOCATION SERVICE CAPACITY PRESS. GPM HEAD TEMP. HP REMARKS BASIS OF DESIGNGAL. PSIG FT.WG F°
GMU-1 BASEMENT GROUND LOOP 55 60 5 138 100 3/4 FACTORY ASSEMBLED SKID BELL & GOSSETT - GMU-60P
2015-09-24 12:11
NOTES:1. FACTORY ASSEMBLED SKID CONSISTING OF PUMP, STORAGE TANK, LOW WATER CUT OFF SWITCH, PRESSURE SWITCH/STARTER,
Y-STRAINER, TRIPLE DUTY VALVE, PRESSURE GAUGE, ELECTRONIC CONTROLLER, AND NEMA 4 CONTROL PANEL. PROVIDE TIE-IN FOR BAS ALARM.
EXPANSION TANK SCHEDULEFILL
SYMBOL TYPE LOCATION SERVICE ACCEPTABLE DIA. HEIGHT PRESS. REMARKS BASIS OF DESIGN(GALLONS) IN. IN. PSIG
ET-1 BLADDER
2015-09-24 12:12
WATERFLOW DATA
FLOWRATE(GPM)
ENT. TEMP. (°F)MIN.
11.0
MAX. DB / WB DB / WB
COIL - HEATING DATA
CAPACITY(MBH)
EAT (°F) LAT (°F)
62.4
DB DBEAT (°F) LAT (°F)DB / WB DB / WB
WINTER PERFORMANCEEAT (°F) LAT (°F)
DB WB DB WB
10.0 9.0 49.0 44.3
ENERGY RECOVERY WHEEL
N/A
TF-1 CALL CENTER ELECTRIC ROOM IN-LINE CENTRIFUGAL
UNIT No.
EF-1
SERVICE
BSMT
LOCATION
TOILET EXHAUST
FANTYPE
0.0143 0.15 1050
BHP
0.18
TOTAL SP(IN. W.G.)
PERFORMANCE DATA
CFM
450 0.625
RPM
1/140 - 115 1 60
MOTOR DATA
3/4
MHP
-
TYPESTARTER ELECTRICAL DATA
VOLTS PHASE HZ
GREENHECK SQ-60-E
MODEL #MANUF.
REMARKS
SEE NOTE 1
-
-
(FPM)MAX. OV
TYPE
DIRECT
DRIVE
EF-2 BSMT BSMT 0.05600 0.18 1550 1/10 --
1628
DIRECT
DIRECT
115 1 60
115 1 60
GREENHECK SE1-12-426-D
GREENHECK SQ-98-VGIN-LINE CENTRIFUGAL
SIDEWALL SEE NOTE 1
SEE NOTE 1
NOTES:
1. PROVIDE SOLID STATE SPEED FOR BALANCING. MOUNT CONTROLLER NEXT TO FAN.
CFM MCA VOLTS PHASE HZELECTRICAL DATA
MBH WBDBDBEAT LATTOTAL
FAN MOTOR DATA
FLA
DX COOLING COIL
LOCATIONO/ACFM
ESP(IN.) MANUF. MODEL NO.
CONDENSORUNIT NO.
BASIS OF DESIGN
REMARKSWBEVAPORATOR
REMARKSNo.UNIT
CONDENSING
(MBH)
TOTALCOOLING COMPRESSOR
QUANTITY MOTOR FLATYPE TYPEFAN
CFMEXT. SP
(IN. W.G.) VOLTS PHASE HZELECTRICAL DATA
MCA
CONDENSING UNIT
(IN)WIDTH
UNIT DIMENSIONS
(LBS) (IN)
COND.WEIGHT LENGTH
(IN)HEIGHT
MODEL #MANUF.
No.UNIT
EVAPORATOR
AC-1 IT ROOM 399 - - 1.0 208 1 60 0.76 12 80 67 55 55 MITSUBISHI MSZ-GE12NA ACCU-1 -
208 1 60 22.1 MITSUBISHI MXZ-3C24NA37-13/321331-11/32SCROLL1 1.922.0ACCU-1 135-ECM -
90 40 82.7 / 67.8 56.2 / 55.6 73.5 49.0 76.9
OUTDOOR AIR
AC-2 ELEC. ROOM 399 - - 1.0 208 1 60 0.76 6 80 67 55 55 MITSUBISHI MSZ-GE06NA ACCU-1 -
NOTES:
1. PROVIDE 4" HOUSE KEEPING PAD.
NOTES:
1. PROVIDE INTERNAL CONDENSATE PUMPS AND ROUTE CONDENSATE TO NEAREST MAIN.
P-4 IN-LINE BASEMENT RADIANT LOOP 7.5 40.6 2.8 115 1.5 1.5 41 3600 5 NO BELL & GOSSETT ECOCIRC XL55-450.68 208 60 3 N/A
P-3 IN-LINE BASEMENT RADIANT LOOP 7.5 40.6 2.8 115 1.5 1.5 41 3600 5 NO BELL & GOSSETT ECOCIRC XL55-450.68 208 60 3 N/A
P-2 IN-LINE BASEMENT GROUND LOOP 123.7 75.3 4.625 80 2 2 76 3450 5 YES BELL & GOSSETT - E-90 2AAC3.97 208 60 3 N/A
0.1 1.0 0.1 1.0
BASEMENT GROUND LOOP
TOTAL VOLUME(GALLONS)
39.0 29.8 16 48.5 15 - WESSEL NALP-150
ET-2 BLADDER BASEMENT RADIANT LOOP 2.0 1.0 8 13 15 PROVIDE MOD #700-C AIR VENT AMTROL EX-15
PLEATED
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-400G150004-000
MECHANICAL SCHEDULES
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION
TERMINAL BOX WITH BYPASS SCHEDULE
TERMINAL BOX SCHEDULE
ELECTRIC BASEBOARD SCHEDULE
LINEAR DIFFUSER SCHEDULE
DIFFUSER, REGISTER, AND GRILLE SCHEDULE
WATER TO WATER HEAT PUMP SCHEDULE (HEATING ONLY)
VENTILATION SCHEDULE
WATER TO AIR HEAT PUMP SCHEDULEFAN COOLING HEATING MAX.
SYMBOL SERVICE ESP/ TOTAL SENS. INPUT HEAT INPUT HEAT GPM PD/ NOM. UNIT BASIS OF DESIGNCFM IN. WG HP MBH MBH KW EER REJECT. MBH MBH KW COP ABSORB. MBH FT. WG TONS VOLTAGE TRANE
HP-01 800 5.20 2.0 208/60/1 VSH024
HP-02
HP-03
HP-04
HP-05
HP-06
HP-07
HP-08
HP-09
HP-10
HP-11
HP-12
HP-13
HP-14
HP-15
HP-16
HP-17
HP-18
HP-19
HP-20
NOTES:1. FANS SHALL BE ECM TYPE.2. PROVIDE UNIT W/ PROGRAMMABLE WALL MOUNTED AUTO CHANGE-OVER THERMOSTAT; UNIT
MOUNTED MICROPROCESSOR CONTROLS, SINGLE POINT POWER ENTRY, 2" DISPOSABLE FILTERS.3. ALL RATINGS ARE BASED ON 20% PROPYLENE GLYCOL SOLUTION.4. DISCONNECT TO BE PROVIDED BY ELECTRICAL CONTRACTOR5. AHRI EER AND COP SHALL BE EVALUATED PER AHRI/ISO 13256-1 PER GROUND LOOP STANDARDS AT
FULL LOAD.6. PROVIDE WITH CONDENSATE PUMPS WHERE REQUIRED.7. PROVIDE WITH VIBRATION ISOLATION (SEE SPEC.)8. PROVIDE HP-03 WITH A HOT GAS REHEAT FOR HUMIDITY CONTROL
HP-21
HP-22
EXHF018
EXHF018
VSH024
VSH024
VSH050
VSH024
VSH024
VSH060
EXHF006
EXHF006
EXHF006
EXHF006
EXHF009
EXHF006
EXHF012
EXHF015
EXHF012
EXHF012
EXHF015
VSH042
VSH042
PRESENTATION - NORTH
LOBBY, STORAGE, BATHROOMS
PRESENTATION - CORE
PRESENTATION - SOUTH
LOBBY
OFFICES
RESOURCE ROOM
HOUSING OPEN OFFICE
SMALL CONFERENCE, STORAGE
ADMISSIONS OPEN OFFICE
BREAK ROOM, CALL CENTER
OFFICES
ADMISSIONS OPEN OFFICE
OFFICES
WORK ROOM, STUDENT WORK SPACE
OFFICES
SMALL CONFERENCE, STORAGE
MARKETING OPEN OFFICE
VP OF ENROLLMENT
OFFICES
OFFICE
LARGE CONFERENCE
VAVB-1
DESIGNATION
AIRFLOW
MODEL #
ZQCV -
REMARKS(INLET SIZE)
5 X 5
MIN.
0
MAX.
RANGE (CFM)BOXTYPE
BYPASS
BOX SIZESTATIC
(IN W.G.)
0.10
PRESSURE PS
MINIMUMSOUND LEVELAT MAX. CFM &
PS=2" (NC)
55
DISCHARGESOUND LEVEL
PS=2" (NC)
39
RADIATED
AT MAX. CFM &CONTROLS
TYPE OF
ANALOG ELECTRONIC
TITUS
VAVB-2 -80
VAVB-3 -0.47 52 40
VAVB-4 -
VAVB-5 -325
VAVB-6 -375 0.25
VAVB-7 -
VAVB-8 -
VAVB-9 -
VAVB-10 -
VAVB-11 -
VAV-1
DESIGNATION
AIRFLOW
MODEL #
DESV -
REMARKS(INLET SIZE)
5
MIN.
120
MAX.
200
RANGE (CFM)BOXTYPE
SINGLE DUCT
BOX SIZESTATIC
(IN W.G.)
0.02
PRESSURE PS
MINIMUMSOUND LEVELAT MAX. CFM &
PS=2" (NC)
35
DISCHARGESOUND LEVEL
PS=2" (NC)
25
RADIATED
AT MAX. CFM &CONTROLS
TYPE OF
DDC
HP-23
18.3 28.701.5517.4823.40 20.95 1.49 6.44 15.87 2.850.50.50
5 X 5
6 X 6
6 X 6
6 X 6
8 X 6
5 X 5
5 X 5
5 X 5
5 X 5
5 X 5
325
325
80
100
100
120
100
100
0
0
0
0
0
0
0
0
0
0
0.10
0.10
0.10
0.10
0.10
0.10
0.47
0.47
51 40
ANALOG ELECTRONIC
ANALOG ELECTRONIC
ANALOG ELECTRONIC
ANALOG ELECTRONIC
ANALOG ELECTRONIC
ANALOG ELECTRONIC
ANALOG ELECTRONIC
ANALOG ELECTRONIC
ANALOG ELECTRONIC
ANALOG ELECTRONIC
BYPASS
BYPASS
BYPASS
BYPASS
BYPASS
BYPASS
BYPASS
BYPASS
BYPASS
BYPASS
EXHF009MECHANICAL BASEMENT
TITUS
LOCATION
BR-1
UNIT No. REMARKSMODEL #
RUNTAL - EB3-108D -
MANUF.
ELECTRICAL DATA
1.32
KW PHASEVOLTS
208 1 60
HZSERVICE
ELECTRIC
TYPE (MBH)
4.5
CAPACITYHEATING
-
FLA
VESTIBULE VESTIBULE
(IN.)DESIGNATION
LD-B
LD-A 1
INLETS
3/4 1,3,4,5,6,7
REMARKS
LINEAR
TYPE
LINEAR 2
SLOTSNo. OF
SUPPLY
SERVICE
SUPPLY/OA
NO. OFSIZESLOT
(IN.)WIDTH MANUF.
MODEL #
TITUS ML-TZ
PLENUM SIZES
48 6
LENGTH(IN.)
WIDTH(IN.)
FINISHES SHALL BE SPECIFIED BY ARCHITECT. ARCHITECT TO PROVIDE COLOR SAMPLE FOR FACTORY PAINTING OF BAKED ENAMEL.
NOTES:
1.
SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2.
PROVIDE LINEAR DIFFUSERS WITH PLENUM AND CORD OPERATED OPPOSED BLADE VOLUME DAMPER.
4.ALL DIFFUSERS SHALL BE SUITABLE FOR THE TYPE OF CEILING CONSTRUCTION THAT ARE BEING INSTALLED IN. COORDINATE WITH ARCHITECT.
3.
COORDINATE DIFFUSER WIDTH WITH ARCHITECTURAL DRAWINGS, SECTIONS, AND REFLECTED CEILING PLAN.
5.
DESIGNATION
SR-A
REMARKSSERVICE
SUPPLY
NECK SIZE (IN.)/SIZE& NO. OF SLOTS
-
NOMINAL OVERALL
10 x 3
DIMENSION WxL (IN.)RANGE
50
MAX NC
30
CFM
DUCT MOUNTED
TYPE
-
MODEL
TITUS - S3OOFS
MANUF.
2 3/42 TITUS ML-TZ48 6
LD-C LINEARSUPPLY/OA 2 14 TITUS ML-TZ48 6
LD-D LINEARSUPPLY 1 - 1,2,3,4,5,6,7- TITUS CT-54148 6
LD-E LINEAROA 1 - 1,2,3,4,5,6,7- TITUS CT-54148 3
LR-A LINEARRETURN - 3/42 TITUS MLR-TZ- -
TG-1 RETURN/EXHAUST - SEE DWG- - WALL MOUNTED -TITUS - S35OFS
ER-A EXHAUST 6" x 6" 24 x 2475-150 - LAY-IN -TITUS - PAR
ER-B EXHAUST - 8 x 675 - DUCT MOUNTED -TITUS - 350RL
CD-A SUPPLY 6" 24 x 2475 30 LAY-IN -TITUS - OMNI
CD-B SUPPLY/OA 4" 12 x 1210-25 30 LAY-IN -TITUS - OMNI
AIR AIREDB EWB EWT
90.064.076.9
UNITFLA
10.17
AIREDB EWT
70.10 40.00
800 5.20 2.0 208/60/118.3 28.701.5517.4823.40 20.95 1.49 6.44 15.87 2.850.50.50 90.064.076.9 10.1770.10 40.00
800 5.20 2.0 208/60/118.3 28.701.5517.4823.40 20.95 1.49 6.44 15.87 2.850.50.50 90.064.076.9 10.1770.10 40.00
800 5.20 2.0 208/60/118.3 28.701.5517.4823.40 20.95 1.49 6.44 15.87 2.851/20.50 90.064.076.9 10.1770.10 40.00
800 5.20 2.0 208/60/118.3 28.701.5517.4823.40 20.95 1.49 6.44 15.87 2.851/20.50 90.064.076.9 10.1770.10 40.00
1800 11.70 4.2 208/60/116.5 59.633.4437.1247.87 45.88 3.16 5.80 35.09 3.901.00.50 90.064.076.9 20.4970.10 40.00
2000 13.00 5.0 208/60/114.8 73.464.5542.8357.93 57.70 4.34 5.30 42.89 4.611.00.50 90.064.076.9 25.8370.10 40.00
215 1.30 0.5 208/60/115.0 9.410.645.507.23 6.67 0.56 4.90 4.75 2.480.06 kW0.50 90.064.076.9 3.7070.10 40.00
215 1.30 0.5 208/60/115.0 9.410.645.507.23 6.67 0.56 4.90 4.75 2.480.06 kW0.50 90.064.076.9 3.7070.10 40.00
215 1.30 0.5 208/60/115.0 9.410.645.507.23 6.67 0.56 4.90 4.75 2.480.06 kW0.50 90.064.076.9 3.7070.10 40.00
215 1.30 0.5 208/60/115.0 9.410.645.507.23 6.67 0.56 4.90 4.75 2.480.06 kW0.50 90.064.076.9 3.7070.10 40.00
215 1.30 0.5 208/60/115.0 9.410.645.507.23 6.67 0.56 4.90 4.75 2.480.06 kW0.50 90.064.076.9 3.7070.10 40.00
380 2.60 1.0 208/60/115.5 14.080.928.6710.95 10.32 0.87 5.20 7.36 3.550.09 kW0.50 90.064.076.9 7.0270.10 40.00
380 2.60 1.0 208/60/115.5 14.080.928.6710.95 10.32 0.87 5.20 7.36 3.550.09 kW0.50 90.064.076.9 7.0270.10 40.00
380 2.60 1.0 208/60/115.5 14.080.928.6710.95 10.32 0.87 5.20 7.36 3.550.09 kW0.50 90.064.076.9 7.0270.10 40.00
570 3.90 1.5 208/60/116.7 21.881.3113.6617.42 16.23 1.31 5.10 11.77 3.930.13 kW0.50 90.064.076.9 11.1070.10 40.00
570 3.90 1.5 208/60/116.7 21.881.3113.6617.42 16.23 1.31 5.10 11.77 3.930.13 kW0.50 90.064.076.9 11.1070.10 40.00
475 3.30 1.25 208/60/115.3 17.401.1410.5013.50 13.01 1.10 4.80 9.25 5.110.11 kW0.50 90.064.076.9 8.7970.10 40.00
475 3.30 1.25 208/60/115.3 17.401.1410.5013.50 13.01 1.10 4.80 9.25 5.110.11 kW0.50 90.064.076.9 8.7970.10 40.00
1250 9.00 3.5 208/60/118.6 47.762.5828.7238.95 35.62 2.60 6.70 26.75 2.551.00.50 90.064.076.9 15.1370.10 40.00
1250 9.00 3.5 208/60/118.6 47.762.5828.7238.95 35.62 2.60 6.70 26.75 2.551.00.50 90.064.076.9 15.1370.10 40.00
285 2.00 0.75 208/60/114.9 10.850.736.678.37 7.87 0.64 5.40 5.69 3.611.00.50 90.064.076.9 4.3070.10 40.00
285 2.00 0.75 208/60/114.9 10.850.736.678.37 7.87 0.64 5.40 5.69 3.611.00.50 90.064.076.9 4.3070.10 40.00
48
ACTIVE
(IN.)LENGTH
48
48
48
48
48
PLENUM
6
6
6
6
3
6
LR-B LINEARRETURN - 14 TITUS MLR-TZ- -48 6
LR-C LINEARRETURN - - 2,3,4,5,6,7- TITUS CT-541- -48 6
PLENUM TO BE SIMILAR TO TITUS MP-TZ.TITUS CT (OR SIMILAR) TO BE PROVIDED WITH 1/4" BARS, 1/2" SPACING.
6.7.
1,3,4,5,6,7
1,3,4,5,6,7
3,4,5,6,7
3,4,5,6,7
LOCATION
HP-W
TAG REMARKSMODEL #
TRANE EXWE0601 -
MANUF.
ELECTRICAL DATA
27.60
RLAPHASEVOLTS
208 1 60
HZSERVICE
10.0
(GPM) MAX PD (IN. W.G.)
5.74 27.60
FLA
BASEMENT RADIANT HEAT
WATER FLOW DATA
SOURCE
HEATING DATA
LWTEWT
40.0 32.76 101.7
EWT
110.3
LWTLOAD (°F)SOURCE (°F)
102
ROOM No.
1
PEOPLE
12
AIR
OFFICE
DESCRIPTIONNo. OF
122
(SQ.FT.)AREAROOM
-
EXHAUST
REQUIRED (CFM)
15 -
DESIGNED (CFM)
55 39
55 39
55 39
55 39
55 39
55 39
52 40
52 40
ZQCV
ZQCV
ZQCV
ZQCV
ZQCV
ZQCV
ZQCV
ZQCV
ZQCV
ZQCV
104
106
108
112A
112
114
116
118
120
122
110
124
126
128
130
OFFICE
OPEN OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OPEN OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OPEN OFFICE
1
16
1
1
1
1
1
1
1
8
1
1
1
1
5
120
1985
120
150
248
175
118
124
124
963
154
132
132
132
483
OUTDOORAIR EXHAUST
OUTDOOR
12 - 15 -
199 - 200 -
12 - 15 -
14 - 15 -
20 - 20 -
16 - 20 -
12 - 15 -
12 - 15 -
12 - 15 -
98 - 100 -
14 - 15 -
13 - 15 -
13 - 15 -
13 - 15 -
54 - 55 -
103 RESOURCE ROOM 10 590 85 - 85 -
105 SMALL CONFERENCE 4 104 30 - 26 -
103.1 STORAGE 0 52 6 - 10 -
103.2 STORAGE 0 52 6 - 10 -
107 BREAK ROOM 8 213 53 - 55 -
109 CALL CENTER 6 205 42 - 45 -
111 WORK ROOM 2 200 22 - 25 -
113 STUDENT WORK 12 253 75 - 75 -
115 SMALL CONFERENCE 4 104 26 - 30 -
119 STORAGE 0 83 10 - 10 -
117 CONFERENCE 12 348 111 - 115 -
101 LOBBY 50 2358 391 - 400 -
140 PRESENTATION 50 1166 445 - 450 -
141 JANITOR 0 61 - 61 - 75
140.1 STORAGE 0 125 12 - 15 -
144 FAMILY TOILET 0 84 - 50 - 75
142 MENS BATHROOM 0 170 - 150 - 150
143 WOMENS BATHROOM 0 212 - 150 - 150
7.5
(GPM)
3.08
LOAD
WATER FLOW DATA
MAX PD (IN. W.G.)
4.30
AHRI COP
AHRI AHRI
PERIMETER SLOT DIFFUSER CEILING TRIM BY GC. HVAC CONTRACTOR SHALL MAKE FINAL PLENUM CONNECTION TO CEILING TRIM.8.
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-401G150004-000
MECHANICAL SCHEDULES
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION
SINGLE-THICKNESS TURNINGVANES FOR SQUARE ELBOW
VANED ELBOW
11/2"(TYP)
1 1/2"(TYP)
FRAME
FLOW
RUNNER
CHANNEL SEENOTE #4
CRIMP (TYP)
3/4" FLATTRAILING
EDGE (TYP)
FLOW
TURNING VANES
NOTES:
1. MAXIMUM UNSUPPORTED VANE LENGTH 36".
2. VANES AND FRAMES-24 GAUGE.
3. DUCT INLET AND OUTLET DIMENSIONS TO BE EQUAL.
4. FOR HIGH VELOCITY APPLICATIONS PROVIDE 18 GAUGE CHANNELAND TACK WELD VANE EDGES TO CHANNEL TYPICAL BOTH ENDS.
5. FRAMES AND CHANNELS-BOLTED OR TACK WELDED TO ELBOW.
45° 45°R=2"
WITH VOLUME DAMPERRECTANGULAR DUCT ANGULAR TAP
NOT TO BE USED AS A SUBSTITUTE FOR AN ELBOW.
FOR LOW PRESSURE BRANCHES WITH LESS THAN 700 CFM AND MEDIUM PRESSUREFURNISH THIS TYPE CONNECTION WHEN SINGLE LINE DUCTWORK IS INDICATED AS THIS .
45°
SUPPLY
BRANCHES WITH LESS THAN 1,000 CFM.
W1
RETURN/EXHAUSTAIRFLOW
AIRFLOW
W2
3/8" SQUARE ROD
MAIN DUCT
BRANCH DUCT
END BEARING
0.25 X W2, 4" MINIMUM
CLEAR INSULATIONQUADRANT AND SADDLE TOLOCKING TYPE INDICATOR.VOLUME DAMPER WITH
CLINCH COLLAR
1.
NOTES:
2.
TO SINGLE OUTLETCIRCULAR BRANCH CONNECTION
AIRFL
OW
MAIN DUCT
1.5D
D
SHEET METAL ASREQUIRED
OR DIFFUSERTO TROFFERFLEXIBLE DUCT
FLAT SEAM DUCTWORKTRANSVERSE JOINT FOR FLUSH
OUTSIDE OF DUCT
INSIDE OF DUCT
TAPPING SCREWSOVAL HEAD SELFCOUNTER SUNK OR
WELDED 6" ON CENTERSPOP RIVETED OR SPOT
MAXIMUM 3/8"
INTERNAL BRACINGOR 2"x3/8"FLAT BAR
1/8" THICK
DIFFUSER CONNECTION DETAIL
6" MINIMUM
R=D
D
DIFFUSERFOR RECTANGULAR
D
SIZE
THERMAL INSULATION
ACOUSTIC LINING
2-3/4 IN. MINIMUM
DIFFUSER
ROUND DUCT CONNECTOR
SIDE CONNECTION
ROUND DUCT ADAPTOR
D MINIMUM
DIFFUSER
CEILING
DIFFUSER NECK
FULLY EXTENDEDFLEXIBLE DUCTMAXMIUM 6 FT. LENGTH
MAXMIUM 6 FT. LENGTHFLEXIBLE DUCTFULLY EXTENDED
TOP CONNECTION
CEILING
PS
PS
PS
1
AAV
WATER COOLED CEILING HUNG HEAT PUMP PIPING DETAIL
VERTICAL DIAPHRAGM TYPE EXPANSIONTANK GLYCOL CHARGING DETAIL
W/ MANUAL PREMIX MAKE-UP
DUCT SUPPORT DETAIL
STEEL ANGLES BACK TO BACK WELDED TOBEAM FLANGE
PROVIDE SOLENOID (ELECTRICAL) VALVESHARD WIRED TO LIQUID DETECTOR TO SHUTDOWN IN EVENT OF A LEAK (TYP)
SHUT-OFF VALVE (TYP)
CONDENSER WATER SUPPLY
CHECK VALVE (TYP)
CONDENSER WATER RETURN
RUNOUTS SHALL BE SAME SIZE AS COILCONNECTIONS (TYP)
PROVIDE FILTER ACCESS SECTION
RETURN AIR
FLEXIBLE CONNECTION (TYP)FILTER
TRAP
LEAK DETECTOR WIRED TO SHUTDOWN HP UNIT
STRAINER W/ BLOW-DOWN VALVE
DIFFERENTIAL PRESSURE SWITCH WIREDTO SHUTOFF HP UNIT UPON LOSS OF FLOW
FLANGECONNECTION (TYP)
STEEL CONNECTION PLATE WELDEDTO ANGLES (TYP) AT 4 LOCATIONSEACH SPAN
THREADED ROD
SPRING VIBRATIONS ISOLATOR
CONTROL VALVE 2-WAY OR 3-WAYAS INDICATED ON FLOW DIAGRAM
BALANCING VALVE(SEE NOTE 2)
SUPPLY AIR
DRAIN PAN INDEPENDENTLYSUPPORTED FROM HP UNIT
CONDENSATE PUMPIF REQUIRED
NOTES:
1. SUPPORT DESIGN NEEDS TO BE APPROVED BY A REGISTERED STRUCTURAL ENGINEER.
2. PROVIDE AUTOMATIC BALANCING VALVE FOR HEAT PUMPS
3. INTER-CONNECT SUPPLY AND RETURN PIPING AT FLANGE CONNECTIONS WITH FLEXIBLE HOUSE TOFLUSH PIPING BEFORE CONNECTING TO HEAT PUMP
PETE'S PLUG (TYP)
DOMESTIC COLDWATER SUPPLY
RPZ TYPE BACKFLOW PREVENTERASSEMBLY FURNISHED ANDINSTALLED BY PLUMBINGCONTRACTOR
CONNECT TO DOMESTIC WATERSYSTEM
SHUT-OFF VALVE, REFER TOSPECIFICATIONS (TYP)BYPASS FOR SYSTEM FILL
HIGH CAPACITYAUTOMATIC AIR VENT
SHUT-OFF VALVERUN TO SPILL OVERFLOOR DRAIN ORFUNNEL DRAIN
SYSTEM MAIN TO SUCTIONSIDE OF PUMP
RUN TO SPILL OVERFLOOR DRAIN OR FUNNELDRAIN
PRESSURE REDUCINGVALVE
EXPANSION LINE
DIAPHRAGM TYPEEXPANSION TANK
TO ADDITIONAL TANK ASREQUIRED
R
RELIEF VALVE
MAKE-UP SIZE (d)
TOTAL SYSTEMPUMP FLOW (GPM)
d(IN)
PRV MINFLOW (GPM)
UP TO 200201-500501-1,2001,201-3,0003,001-5,0005,001-12,000
0.50.751.01.251.52.0
3510203060
EXPANSIONLINE SIZE
1.251.52.02.02.52.5
(d)
LOCK SHIELD VALVE
12"
AFF
NOTES:
1. REFER TO EXPANSION TANK SCHEDULE FOR CAPACITY AND SIZE.
2. REFER TO PLANS FOR LOCATION OF TANK.
3. SET RELIEF VALVE SETTING 10% ABOVE WORKING PRESSURE.
4. PROVIDE ANTI-THERMOSYPHON LOOP AS SHOWN TO PREVENT GRAVITYHEATING OF TANK.
AIR SEPARATOR
INSTALL FOR RADIANTSYSTEM. OMIT FORGLYCOL SYSTEM.
GLYCOL MAKE-UP FROMDRUM, POWER PUMP, ORHAND PUMP (MANUALOPERATION)
FLOOR
SYSTEM MAINPUMP SUCTION
AAV (LARGE CAPACITY)
AIR SEPARATOR
DRAIN OUT VALVE WITHHOSE BIBB
LOW PRESSURE SWITCH, WIRE ALARMTO BLDG FACILITIES OR SECURITYOFFICE
GLYCOL & WATERPREMIX DRUM (55GALLON MINIMUM)
LOW - LEVEL ALARM,ANNUNCIATE TO BLDGFACILITIES OR SECURITYOFFICE
HOUSEKEEPING PAD
BY OTHERS
RELIEF VALVE DISCHARGEPIPED BACK TO GLYCOL &WATER PREMIX DRUM
HAND PUMP
GLYCOL DRUM
BACK- FLOWPREVENTERBY OTHERS
COLD WATER MAKE-UP(MANUAL OPERATION)BY OTHERS
NOTES:
1. COORDINATE POWER REQUIREMENTS FOR MAKE-UP PUMP AND CONTROLSWITH ELECTRICAL CONTRACTOR.
2. ALL PIPING & EQUIPMENT DOWNSTREAM OF MAKE-UP PUMP SHALL BERATED FOR INSTALLED OPERATING PRESSURE.
3. IN "AUTO" POSITION PUMP RUNS AUTOMATICALLY WHEN SYSTEMPRESSURE FALLS BELOW CHARGE PRESSURE. WHEN IN "HAND" THE PUMPRUNS CONTINUOUSLY. WHEN IN "OFF", THE SYSTEM IS OFF.
12"
EXPANSION TANK
LOCKSHIELDVALVE
HB
LAG BOLT 1 1/2"x11/2"x 1/8" TOJOIST
JOIST JOIST
BEND STRAP OVER ANGLE &BOLT TOP & SIDE
UNDERSIDE OFSLAB OR BEAM
SEE NOTE 3
DUCT HANGERS NOTLESS THAN 1"x1/8"
APPROVED INSERT &ANCHOR
BEAMCLAMP
STRUCTURAL ANGLECHANNEL AS REQUIRED
HANGER ROD
PARALLELCONNECTION
TRANSVERSECONNECTION
WOOD JOISTATTACHMENTS
HANGER ROD
EXPANSIONBOLT
HANGER ROD
EXPANSIONSHIELD
BEAM
BEAMCLAMP
HANGER ROD
BEAMATTACHMENT
DUCT
BEAMCLAMP
CONCRETEATTACHMENT
NOTES:
1. ALL DUCTWORK TO BE HUNG FROM BUILDINGCONSTRUCTION. DO NOT SUPPORT FROMHUNG CEILING.
2. WHEN DUCT AREA EXCEEDS 8 SQ FT ANGLESTIFFENERS ARE REQUIRED AROUNDCIRCUMFERENCE EVERY 4'-0".
3. FOR DUCTS UP TO 60" WIDE, HANGERS SHALLTURN UNDER DUCT AT LEAST 2" AND SHALL BEFASTENED TO THE BOTTOM AS WELL AS TOTHE SIDES OF THE DUCT. FOR DUCTS OVER 60" WIDE, USE TRAPEZE HANGER.
4. REFER TO SPECIFICATIONS FOR HANGERSPACING.
5. NOT ALL CONSTRUCTION TYPES ARE APPLICABLETO THIS PROJECT.
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-500G150004-000
MECHANICAL DETAILS
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION
SS
SUSPENDED INSTALLATIONVERTICAL IN-LINE PUMP
PROVIDE FLANGE FOR PUMPS WITH FLANGECONNECTIONS, FURNISH UNION AT INLET ANDDISCHARGE FOR PUMPS WITH SCREWEDCONNECTIONS
LOCATION OF UNION IF REQUIRED(TYP)
Y-PATTERN STRAINER WITH3/4" BALL VALVE AND HOSEBIBB END ADAPTER WITHCAP
ECCENTRIC REDUCER (TOPFLAT) (TYP)
SILENT CHECK VALVE
SHUT-OFF VALVE (TYP)
HANGER (TYP)
VIBRATION ISOLATION (TYP)SEE SPECIFICATIONS
THREADED HANGER ROD ATTACHED TOBUILDING STRUCTURE OR MISCELLANEOUSSTEEL WITH WELDED BEAM ATTACHMENT (TYP)
MOTORPRESSURE GAUGE
BALANCING VALVE
1/4" SS PIPE
EXTERIOR WALL PIPE PENETRATION SEAL ASSEMBLY
WATER STOP/LEAK PLATE ANDWELDED ANCHOR COLLAR
STAINLESS STEEL BOLTS(NOT STUDS)
STUFF OPENING WITHASBESTOS FREE ROPE
CATHODIC TYPE (NON CONDUCTIVE)PRESSURE PLATES
PIPE SLEEVE TO BE INSTALLEDDURING WALL CONSTRUCTION
NEOPRENE SEALING ELEMENTS
CONTINUOUS WELDBOTH SIDES(TYP)
INSULATION AS PERSPECIFICATIONS
PIPE TO SLIDETHROUGH SEAL
PIPE OR CONDUITCENTERED IN SLEEVE
INTERIOR FACEOF BUILDING
NOTES:
1. WHEN SEALING FLOOR PENETRATIONS, EXTEND SLEEVE 3"ABOVE FINISHED FLOOR.
2. WHEN CORE DRILL IS USED THE PIPE SLEEVE AND WATERSTOP/LEAK PLATE ARE NOT REQUIRED.
SECTION A-A
A
A
TYPICAL DETAIL OF PIPETHRU RATED WALL
EXTEND SLEEVEBEYOND FINISHED WALLSURFACE
SEAL OR CAULK SLEEVESTHRU FIRE WALLS IN A SMOKETIGHT MANNER REFER TOSPECIFICATION
STANDARD WEIGHT STEEL PIPESLEEVE OF SIZE TO PASS PIPE
FINISHED ESCUTCHEON PLATEFLUSH AGAINST WALL AND OF SIZETO COMPLETELY COVER OPENING(TYP FOR EACH SIDE)
FINISHED WALL SURFACEFILL VOID WITHFIRESTOPPING PERSPECIFICATIONS
1/2" CLEAR MAX
PIPE INSULATION TO BECONTINUOUS THROUGHTHE WALL
DIELECTRIC FLANGE KIT DETAIL
TEFLON BOLT SLEEVEISOLATING INSERT
STANDARD BOLT RATED ANDSIZED FOR FLANGE
FLANGE - BRAZED ORSOLDERED TO PIPE
COPPER PIPESTEEL PIPE
FLANGE - BRAZED ORSOLDERED TO PIPE
NOTES:
1. TEFLON NON-CONDUCTIVE ISOLATINGINSERTS ARE TYPICAL FOR ALL BOLTHOLES/BOLTS.
TEFLON WASHER
STANDARD NUT RATED ANDSIZED FOR FLANGE
STANDARD STEEL FLANGE -WELDED OR THREADED RATEDFOR PRESSURE CLASS OF PIPE
TEFLON GASKET
PLAN VIEW
(CAV OR VAV)TERMINAL UNIT INSTALLATION
INDICATED ABOVE CANNOT BE MAINTAINED, PROVIDE ORIFICE PLATE, STRAIGHTENING
ACOUSTICAL DUCT LINING MINIMUM10 FEET DOWNSTREAM OR SOUND
AND PLANS FOR FURTHER REQUIREMENTS.ATTENUATOR AS REQUIRED. SEE SPECS
ADEQUATE SERVICE ACCESSMOUNT CONTROL PANEL WITH
FASTEN AND SEAL CONNECTION
FASTEN AND SEAL CONNECTION
THE OPERATION OF VARIABLE VOLUME TERMINAL UNITS ARE AFFECTED BYEXCESSIVE TURBULENCE ON THE ENTERING SIDE OF EACH TERMINAL UNITTHEREFORE, TERMINAL UNITS MUST NOT BE INSTALLED TOO CLOSE TOMAIN DUCTS, ELBOWS AND FITTINGS.
WHEN MINIMUM UPSTREAM STRAIGHT DUCT CONNECTION TO TERMINALS AS
VANES OR OTHER DEVICE AS RECOMMENDED BY TERMINAL UNIT MANUFACTURERAND SUBMIT TO ENGINEER FOR REVIEW PRIOR TO INSTALLATION.
MANUFACTURER OF TERMINAL UNIT SHALL PROVIDE CONTROLS ON LEFT ORRIGHT SIDE AS REQUIRED BY FIELD CONDITIONS.
ARRANGE ACCESS TO PERMIT EASY FIELD BALANCE AND MAINTENANCE OFTERMINAL UNIT.
1.
2.
3.
4.
NOTES:
RIGID CONNECTION
TERMINAL UNIT
CONICAL CONNECTION
MAIN DUCT
STRAIGHT ROUND DUCT
(MINIMUM 3'-0")LENGTH 2 DIAMETERS
RECTANGULAR TOROUND TRANSITION
AIR FLOW
SAME SIZE AS INLET.
SLOT DIFFUSER WITH VOLUME DAMPERDETAIL
FLEX MAX LENGTH 4"
CABLE OPERATED OPPOSEDBLADE VOLUME DAMPER
PERIMETER SLOT DIFFUSERPLENUM W/SOUND LINING
HUNG CEILING
CONTINUOUS PERIMETER SLOT(SEE EQUIPMENT SCHEDULEFOR REQUIRED NUMBER OF SLOTS)
CABLE WITH HEX-NUTADJUSTMENT
GWB SOFFIT(BY OTHERS)
SUPPLY AIRTHRU SLOT
BRANCH OR MAIN DUCT WITH TYPE "B" FIRE DAMPER-DETAILPROPELLER FAN DETAIL
FIRE RATED WALL PARTITION
PROVIDE CLEARANCE FOR DAMPEREXPANSION ON BOTH SIDES ANDTOP AS REQUIRED
ANGLE IRON FRAME AND OVERLAPALL FOUR SIDES FASTENED TODUCT SLEEVE SEE NOTES
MANUFACTURERFURNISHED SLEEVE
SEAL ALL S-JOINTS ATBREAKAWAY CONNECTIONS
FUSIBLE LINK RATED FOR50°F ABOVE MAXIMUMTEMPERATURE OF SYSTEM
FIRE DAMPER FRAMEFACTORY MOUNTED IN SLEEVE
BREAKAWAY CONNECTION(TYP)
6"
FASTEN FIRE DAMPER FRAMETO SLEEVE. SEE NOTES
2" ACCESS DOOR
DUCT3"MIN
3"MIN
MINIMUM 1" OVERLAP
LINTEL
MAXIMUM 6". IF ACCESSDOOR IN SLEEVE,
MAXIMUM 16 INCHES
FASTEN TO SLEEVE(TYP)
GENERAL NOTES:
1. DAMPER TO BE UL LABELED NFPA 90A, BSA AND MEA APPROVED.
2. NFPA APPROVED INSTALLATION DETAILS TO BE PART OF SUBMISSIONOF FIRE DAMPER FOR APPROVAL, WICH SHALL MEET NFPA STANDRAD90A AND SHALL BE BSA APPROVED.
3. DETAILS SHOWN ARE FOR FIRE DAMPERS IN HORIZONTAL DUCTWORK,FOR DAMPERS IN VERTICAL DUCTWORK, DETAILS SIMILAR EXCEPTDAMPERS ARE TO BE SPRING LOADED.
4. ACCESS DOOR IS SHOWN IN SIDE OF DUCT; IF FUSIBLE LINK ISMORE ACCESSIBLE FROM BOTTOM OF DUCT RELOCATE ACCESS DOOR.
1. UL APPROVED BREAKWAY SLIP JOINT CONNECTIONSHALL BE USED.
2. THIS DETAIL IS A GUIDE ONLY. INSTALL FIRE DAMPER INACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONSAND UL LISTING.
3. RETAINING ANGLES MUST OVERLAP THE FIRE WALL 1"MINAND COVER CORNERS OF OPENINGS.
WALL
FIXED LOUVER
12"x12" ACCESS DOOR
16"MIN
ANGLE IRON SIDES
18 GAUGE SHEET METALPLENUM TO EXTEND
FAN AND MOTOR MOUNTEDON VIBRATION ISOLATORS
AIRFLOW
WIRE MESH INLET GUARD
FLEXIBLE CONNECTION
DAMPER (MOTORIZED ORSELF ACTING-SEESPECIFICATIONS)
(10) 2" DIAMETER GEOTHERMALSUPPLY/RETURN PIPES. MINIMUM OF 5'-0"BELOW GRADE IN ALL DIRECTIONS. SEEEXTERIOR WALL PIPE PENETRATION ASSEMBLYDETAIL. HORIZONTAL PIPE SPACING OF 1'-4"CENTER TO CENTER, VERTICAL PIPE SPACINGOF 1'-9" CENTER TO CENTER.
Q
1' - 4"
1'-9
"
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-501G150004-000
MECHANICAL DETAILS
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 3/8" = 1'-0"5 GEOTHERMAL PIPE DETAIL - ENTRY THROUGH BASEMENT WALL, SUB-GRADE
NO. ISSUE DATE: DESCRIPTION
T
T
T
T
ZONE 1
ZONE 2
ZONE 4
ZONE 3
185'
165'
140'
195'
220'
220'
225'
110'
JH
9
12
6
14
4
15
U
16
13
B
11
10
7
5
3
C
E F
LL
G
YY
XX
ZZ
8
RADIANT HEAT FLOORING. SEE DETAILS.
MANIFOLD FOR RADIANT HEAT FLOORING
RADIANT HEAT FLOORING.SEE DETAILS.
MANIFOLD FOR RADIANTHEAT FLOORING
VEST.V-1
ALCOVEL101-5
WOMEN'S143
MEN'S142
ALCOVEL101-6
PASSAGEL101-7
VEST.V-2
PASSAGEL101-1
COFFEESTATIONL101-3
HOUSINGOPEN OFFICE
130
OFFICE102
RESOURCEROOM
103
RECEPT.L101-2
LOBBYL101
Stainless-steelManifoldSupply/ReturnBall Valve, Set of 2
TemperatureGauge
Uponor hePEX Tubing
ProPEX FittingAssemblies
Stainless-steelManifold Flow Meter
MountingBracket
Fill Valve
Coin Air Vent
Stainless-steel ManifoldIsolation Valve Body
Stainless-steelManifold
Spacer Ring for Actuator
Thermal Actuator,four-wire
Concrete Slab
Wire Tie
Base Material
Slab InsulationWire Mesh, Rebar or Staple to
Rigid Foam
Edge Insulation
Uponor Tubing
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
M-502G150004-000
MECHANICAL DETAILS
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NOTES: CONCRETE SLAB WILL NOT BE RE-INFORCED; CONTRACTOR SHALL FURNISH ALL SUPPORTS AND SPACERS REQUIRED FOR INSTALLATION OF RADIANT PIPING.
SCALE: 1/4" = 1'-0"1 GROUND FLOOR PLAN
SCALE: NTS2 STAINLESS STEEL MANIFOLDSCALE: NTS3 SLAB ON OR BELOW GRADE
NO. ISSUE DATE: DESCRIPTION
1. GENERAL NOTES, SYMBOL LIST AND DETAILS ARE APPLICABLE TO ALL PLUMBING DRAWINGS.
2. ALL WORK IS NEW UNLESS OTHERWISE NOTED.
3. DRAWINGS ARE DIAGRAMMATIC: DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD.
4. NEITHER ACCURACY NOR COMPLETION OF UTILITY LOCATIONS SHOWN ON DRAWINGS IS GUARANTEED.DETERMINE EXACT LOCATIONS OF EXISTING UTILITY IN FIELD, WHETHER OR NOT SHOWN ON DRAWINGS.EXERCISECAUTION AND IDENTIFY LOCATIONS OF UNMARKED UTILITY LINES AS NECESSARY TO PERFORM WORK OF THISSECTION.
5. ALL PLUMBING WORK SHALL BE IN ACCORDANCE WITH THE CURRENT PLUMBING CODE AND ALLAPPLICABLE LOCALCODES AND DRAWINGS.
6. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE HIS WORK WITH THAT OF ALLOTHERTRADES, INCLUDING (BUT NOT LIMITED TO), ELECTRICAL, HVAC PROCESS PIPING, SPRINKLER, PLUMBINGSTRUCTURAL AND GENERAL ARCHITECTURE.
7. ANY INTERFERENCE SHALL BE BROUGHT TO THE ATTENTION OF THE PROFESSIONAL IN WRITING, AND SHALL BERESOLVED PRIOR TO THE INSTALLATION OF THE WORK INVOLVED.
8. NO WORK SHALL BE INSTALLED IN VIOLATION OF ANY GOVERNING CODES. ANY WORK SHOWN ON THE DRAWINGSWHICH IS IN VIOLATION OF SUCH CODES SHALL BE BROUGHT TO THE ATTENTION OF THE CONSTRUCTION MANAGERAND THE OWNER'S REPRESENTATIVE AND SHALL BE RESOLVED PRIOR TO THE INSTALLATION OF THE WORKINVOLVED.
9. ALL PIPING PENETRATING CEILING AND WALLS SHALL BE INSTALLED WITH ESCUTCHEONS AT THE PENETRATION.(COLOR SHALL BE BY ARCH). ALL PIPING PENETRATING EXTERIOR WALLS AND ROOFS SHALL BE FLASHED IN ANAPPROVED MANNER AND SHALL BE SEALED WEATHER TIGHT. PIPING PENETRATING RATED PARTITIONS SHALL BEPROTECTED AS REQUIRED BY LOCAL CODE AUTHORITY.
10. MANUFACTURER'S MODEL NUMBERS ARE BASIS OF DESIGN, REFER TO SPECIFICATIONS FOR APPROVEDEQUALS..
11. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURERS' RECOMMENDATIONS.
12. ACCESS PANELS SHALL BE FURNISHED AND INSTALLED BY THE G.C. COORDINATE WITH THE G.C THEEQUIPMENT LOCATIONS THAT REQUIRES PERIODIC SERVICE.
13. TOPS OF ALL FLOOR DRAINS SHALL BE SET FLUSH WITH FINISHED FLOOR. ALL PIPING ABOVE GRADE SHALL BEPROPERLY SUPPORTED BY THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING TILES OR CEILINGSTRUCTURE.
14. CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL PLUMBINGEQUIPMENT WITH THE ELECTRICAL DRAWINGS AND SHALL FURNISH EQUIPMENT WIRED FOR THE VOLTAGES SHOWNHEREIN.
15. PROVIDE SHUTOFF VALVES ON ALL BRANCH PIPING AND ON ALL SUPPLIES TO INDIVIDUAL FIXTURES ANDEQUIPMENT. PROVIDE BALL VALVES ON ALL WATER MAIN BRANCHES IN CORRIDORS AND WHERE INDICATED ONDRAWINGS. ALL VALVES SHALL BE ACCESSIBLE.
16. ALL SLEEVES THROUGH CONCRETE FLOORS AND ALL CORE DRILLING OF CONCRETE FLOORS AND WALLSSHALL BEBY THIS CONTRACTOR.
17. CONCRETE PADS AND PLATFORMS FOR WORK OF THIS SECTION WILL BE PROVIDED BY THIS TRADESCONTRACTOR. PROVIDE ALL HARDWARE AS NECESSARY TO COMPLETE THE WORK.
18. SCHEDULE WORK OF THIS SECTION TO AVOID INTERFERENCES WITH FIRE-PROOFING WORK.
19. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER TRADES AND WITH FLASHING REQUIREMENTS.
20. RUN PIPING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS.
21. STRUCTURAL WELDING SHALL BE 1/4-INCH FILLET UNLESS REQUIRED OTHERWISE.
22. PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ONPIPING.
23. PROVIDE BALANCING VALVES AT SYSTEM LOOP RETURNS AND AT RETURN RISERS. PROVIDE SHUT-OFF VALVES ATSYSTEM LOOP SUPPLIES AND SUPPLY RISERS.
24. PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT LOW POINTS.
25. PROVIDE GAUGE FITTINGS AND THERMOMETER WELLS AT HOT WATER SUPPLY AND RETURN BRANCHES AND ATPUMP INLETS AND OUTLETS.
26. VERIFY EXACT SIZES, LOCATIONS, INVERTS AND ELEVATIONS PRIOR TO RUNNING ANY PIPING. REFER TOARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS OF ALL FIXTURES AND EQUIPMENT.
27. WATER HEATERS SHALL BE INSTALLED WITH DRAIN PANS UNDER HEATERS. ROUTE PAN DRAINS TONEARESTFLOOR DRAIN OR SAFE DRAIN.
28. PIPING SHALL NOT RUN OVER ELECTRICAL PANELS AND SHALL BE COORDINATED WITH WORK OF OTHER TRADES.
29. REPAIR AND PATCH ANY PENETRATIONS CREATED AS PART OF THIS SCOPE OF WORK. MATCH NEWFINISHES WITHARCHITECTURAL PLANS.
30. COORDINATE INSTALLATION OF PIPING AND FIXTURES WITH ALL OTHER TRADES.
31. ALL EXCAVATION AND BACKFILL REQUIRED FOR PLUMBING WORK SHALL BE BY THE PLUMBING CONTRACTOR.REFER TO SITE SPECIFICATIONS FOR MORE INFORMATION ON EXCAVATION AND BACKFILL REQUIREMENTS.
32. PAINTING OF ALL ARCHITECTURALLY EXPOSED PIPING WORK SHALL BE BY THE GENERAL CONTRACTOR. PAINTINGOF ANY NON-ARCHITECTURALLY EXPOSED PIPING SHALL BE BY THIS TRADES CONTRACTOR. REFER TO DIVISION 9PAINTING.
33. FIRESTOPPING FOR THE WORK INCLUDED IN THESE DOCUMENTS, SHALL BE FURNISHED AND INSTALLED BY THEPLUMBING CONTRACTOR. REFER TO DIVISION 7 FIRESTOPPING.
34. SLEEVES THAT ARE REQUIRED FOR THIS PROJECTS SHALL BE FURNISHED BY THE PLUMBING CONTRACTOR ANDINSTALLED BY THE GENERAL CONTRACTOR. COORDINATE THE LOCATION OFTHE SLEEVES WITH THE GENERALCONTRACTOR.
PLUMBING GENERAL NOTES
T
M
BPA
PLUMBING SYMBOL LISTBASIC
PS
LS
S
S
EXISTING PIPING
EXISTING PIPING TO BE REMOVED
PIPING TO BE ABANDONED
NEW SOIL, WASTE OR SANITARY PIPING
VENT PIPING (SANITARY)
PIPING BELOW SLAB
DOMESTIC COLD WATER PIPING
DOMESTIC HOT WATER PIPING (120°)
DOMESTIC HOT WATER CIRCULATION PIPING
PIPING w/FREEZE PROTECTION CABLE & INSULATION
ARROW INDICATES DIRECTION OF FLOW
COMPRESSED AIR PIPING
GAS PIPING
EJECTOR DISCHARGE PIPING
INDIRECT WASTE PIPING
PUMP DISCHARGE PIPING
SUMP PUMP DISCHARGE PIPING
STORM WATER DRAINAGE PIPING
TEMPERED WATER PIPING
DISCONNECT FROM EXISTING
CONNECT TO EXISTING
SHOCK/WATER HAMMER ARRESTOR
FLEXIBLE CONNECTION
EXPANSION LOOP SIZE
HOSE BIBB
WALL HYDRANT
FRESH AIR INLET
CLEAN OUT/PLUGGED OUTLET
CAPPED OUTLET
CLEAN-OUT DECK PLATE
P-TRAP
VACUUM BREAKER
BOTTOM PIPE CONNECTION
TOP PIPE CONNECTION
SIDE CONNECTION
PIPE DOWN/DROP
PIPE RISE/UP
PIPE SLOPE
VALVE IN VERTICAL
UNION
REDUCER
WATER PROOF SLEEVE
SLEEVE
PRESSURE GAUGE w/GAUGE COCK
TEMPERATURE GAUGE
FLOOR DRAIN
ROOF DRAIN
PUMP
WATER METER
AUTOMATIC BALL DRIP
VENT THRU ROOF
TRAP
TAMPER SWITCH
PRESSURE SWITCH w/GAUGE COCK
WATERFLOW SWITCH
TEMPERATURE AND PRESSURE RELIEF VALVE
BACKWATER VALVE
PLUG VALVE
MIXING VALVE
RELIEF VALVE
BALL VALVE
BALL VALVE w/LOCK SHIELD
GATE VALVE
GLOBE VALVE
OUTSIDE SCREW & YOKE (OS & Y) VALVE
CHECK VALVE
PRESSURE REDUCING VALVE (PRV)
SOLENOID VALVE
FLOAT VALVE
BALANCING VALVE
Y STRAINER w/BLOW-OFF VALVE
BACKFLOW PREVENTER ASSEMBLY
REDUCED PRESSURE ZONE BACKFLOW PREVENTER ASSEMBLY
REDUCED PRESSURE DETECTOR ASSEMBLY
DOUBLE CHECK VALVE ASSEMBLY
DOUBLE CHECK DETECTOR ASSEMBLY
BALANCING VALVE ASSEMBLY
RISER DESIGNATION:X = RISER SERVICE; # = RISER NUMBER
ST
G
EJ
IW
PD
SD
T
AB
(H) (L)X
ABD
ISOLATION VALVE W/BOX TO GRADE
MANHOLE IN SANITARY SEWER
EXISTING MANHOLE
FIRE HYDRANT
WELL
SITE WATER (COMBINED DOMESTIC & FIRE
WELL WATER
CA
RPZ
RPDA
DCV
DCDA
BVA
X#
WATER SERVICE
WW
W
WH-2-3
XXX-XX-XX
SECOND FLOOR
(REFER TO SPECIFIC TRADE LIST)
EQUIPMENT TAG NUMBERFLOOR DESIGNATIONEQUIPMENT DESIGNATION
WATER HEATER(REFER TO LIST)
UNIT NUMBER 3
PLUMBING EQUIPMENT DESIGNATIONS
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
P-000G150004-000
PLUMBING COVER SHEET
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
PLUMBING ABBREVIATIONSAD AREA DRAINAFF ABOVE FINISHED FLOOR
BLDG BUILDINGBOP BOTTOM OF PIPE
CLG CEILINGCM COFFEE MAKERCO CLEANOUTCODP CLEANOUT DECK PLATECONN CONNECTCONT CONTINUATIONCV CHECK VALVECVO CAPPED AND VALVED OUTLETCW COLD WATER
DIA DIAMETERDN DOWN (PENETRATES FLOOR SLAB)DR DRAINDWG DRAWINGEJ DIS EJECTOR DISCHARGEEQC ELECTRIC WATER COOLER
(E) EXISTING(ER) EXISTING TO BE REMOVED(ERR) EXISTING TO BE REMOVED & RELOCATEDEL ELEVATION
FAI FRESH AIR INLETFD FLOOR DRAINFL FLOORFL H FLOOR HYDRANTFT FEETFU FIXTURE UNIT
GAL GALLONSGC GENERAL CONTRACTORGPM GALLONS PER MINUTE
HB HOSE BIBBHCLG HUNG CEILINGHW HOT WATERHWR HOT WATER RETURN
ID INSDIE DIAMETERIN INCHIW INDIRECT WASTE
JS JANITOR'S SINK
LAV LAVATORY
MAX MAXIMUMMIN MINIMUMMR MOP RECEPTOR
NC NORMALLY CLOSEDNFGH NON FREEZE GROUND HYDRANTNFWH NON FREEZE WALL HYDRANTNIC NOT IN THIS CONTRACTNO NORMALLY OPENNTS NOT TO SCALE
OD OUTSIDE DIAMETEROS&Y OUTSIDE SCREW & YOKE GATE VALVE
PD PLUMBING CONTRACTORPD PUMP DISCHARGEPO PLUGGED OUTLETPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCH (GAUGE)
(RE) RELOCATED EXISTING(RRO) EXISTING TO BE REMOVED AND RETURN TO OWNERRD ROOF DRAIN
SA SHOCK ABSORBERSAN SANITARYSD SUMP PUMP DISCHARGESH SHOWERSK SINKSQ FT SQUARE FOOTST STORM
TYP TYPICAL
UON UNLESS OTHERWISE NOTEDUP UP (PENETRATES FLOOR SLAB)UR URINAL
V VENTVB VACUUM BREAKERVTR VENT THROUGH ROOF
W WASTEWC WATER CLOSETWCO WALL CLEANOUTWH WALL HYDRANT
NO. ISSUE DATE: DESCRIPTION
CO
CO
WV
MH
MH
MH
MH
WV
WV
WV
MH
WV
WV
MH
WV
MH
WV
MH
MH
WV
MH
WV
WV
BENCHMARK
MAG NAIL SET IN
SIDEWALK SEAM
ELEVATION=317.62
EX. BUILDING
GORDINIER HALLEX. BUILDING
EX. BUILDING
STUDENT MEMORIAL
CENTER
EX.
BUILDING
EX.
BUILDING
EX.
BUILDING
FFE=320.17
FFE=320.21
FFE=320.22
FFE=304.93
C.O.
C.O.
C.O.
C.O.
C.O.
JAMES STREET
( MILLERSVILLE UNIVERSITY)
LOMBARDO WELCOMECENTER
WVWV
6"SAN SERVICE5'-0" FROM FROM BLDG.(CONTINUED BY SITE/CIVIL)
2 1/2"DOMESTIC WATER SERVICE5'-0" FROM FROM BLDG.(CONTINUED BY SITE/CIVIL)
6"FIRE WATER SERVICE5'-0" FROM FROM BLDG.(CONTINUED BY SITE/CIVIL)
4" SPRINKLER PIPE TO5" STORZ FDC5'-0" FROM FROM BLDG.(CONTINUED BY SITE/CIVIL)
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
P-001G150004-000
PLUMBING SITE PLAN
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1" = 30'-0"1 LOWER LEVEL PLAN
DRAWING NOTES:
1. REFER TO SITE CIVIL PLAN FOR TEMPORARY WATER SERVICE CONNECTION.
NO. ISSUE DATE: DESCRIPTION
21/2"
CW
2 1/2" DOMESTIC WATER SERVICE .5'-0" FROM BUILDING. REFER TO SITE/CIVILDRAWINGS FOR CONTINUATION. 6" SPRINKLER SERVICE. REFER TO
FIRE PROTECTION DRAWINGS FORCONTINUATION.
RPZ
4"S 4"S 4"S
FD-B
FD-B
FD-B
4" SANITARY MAIN. 5'-0" FROM BUILDING.REFER TO SITE/CIVIL DRAWINGS FORCONTINUATION.
P12 1/2"CW UP
4"S
299.00' INV.
310.00' INV.
4"SAN DN4"V UP
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
2"S
2"S
4"S4"S4"S
4"S
2"S2"S
2"S
V1
2 1/2" DOMESTICWATER SERVICE.
2"SAN UPTO F-6
2"SAN UPTO F-6
2"SAN UPTO F-4
3"SAN UPTO FD-B 2"SAN UP
TO FD-A2"W UPTO F-3
2"S UPTO F-2
2"W UPTO F-3
2"SAN UPTO FD-A
4"SAN UPTO F-1A
4"SAN UPS2
3"V
4"S3"S
3"S
3"V
3"S
1"CW
3/4"CW
HB
3/4"CW UPTO NFGH
1"PRV WITHBY-PASS BFP
3/4"CW UP
1
HB
FD-B
3"S
3"S
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
P-100G150004-000
PLUMBING LOWER LEVELPLAN
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 LOWER LEVEL PLAN
DRAWING KEY NOTES:
COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.
PROVIDE DEEP SEAL TRAPS ON MECHANICAL FLOOR DRAINS.
1
2
NO. ISSUE DATE: DESCRIPTION
EWH-1-2
EWH-1-1
NFGH
NFWH
NFWH
F-4
F-1A
F-3
F-3AF-5
F-1
F-1A
F-1A
F-1
F-2A
F-3DW
F-6
F-6
FD-A
FD-A
3/4"CW
3/4"CW
3/4"HW
3/4"C
W
3/4"CW3/4"HW 3/4"CW
3/4"HW
1/2"CW/HW2" SAN/VTO F-6(TYP.)
1/2"CW/HW2" SAN/VTO F-3(TYP.)
1 1/4"CW4" SAN/VTO F-1/F-1A(TYP.)
3/4"CW2" SAN/VTO F-2/F-2A(TYP.)
3/4"CW2" SAN/VTO F-5(TYP.)
3/4"CW/HW2" SAN/VTO F-4(TYP.)
3/4"CWW/ VACUUM BREAKERTO NFWH(TYP.)
3/4"CW W/ VACUUMBREAKER TONFGH(TYP.)
P1 2 1/2"CW DN
3/4"CW
3/4"C
W
3/4"CW
2 1/2"CW
21/2"
CW
2 1/2"CW
RUN PIPING HIGH AND TIGHT TO BEAM
F-5A
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
VEST.V-1
ALCOVEL101-5
WOMEN'S143
PASSAGE104
MEN'S142
ALCOVEL101-6JANITOR
141
MECHANICAL141.1
FAMILYTOILET
144
STORAGE140.1
PASSAGEL101-7
VEST.V-2
CLASSROOM/PRESENTATIONROOM
140
V.P. OFFICE112A
SMALL CONF.105
STORAGE103.1
OFFICE112
PASSAGEL101-1
OFFICE118
OFFICE114
OFFICE116
OFFICE110
OFFICE108
OFFICE104
CORRIDORC 1-1
CORRIDORC 1-2
BREAK ROOM107
STORAGE119
ELEC. RM.121
COFFEESTATIONL101-3
STORAGE103.2
ADMISSIONSOPEN OFFICE
106
HOUSINGOPEN OFFICE
130
OFFICE128
OFFICE126
OFFICE124
OFFICE122
MARKETINGOPEN OFFICE
120
SMALL CONF.115
CONFERENCE117
I.T. ROOM123
CALL CENTER109
CORRIDORC 1-3
OFFICE102
WORK ROOM111
RESOURCEROOM
103
RECEPT.L101-2
STUDENTWORK SPACE
113
LOBBYL101
3
4"ST
4"ST
4"ST
4"ST
6"ST
6"ST 4"ST
4"ST
4"ST
4"ST
4"ST
4"ST
3/4"CW
3/4"CW
4"ST
2"V
2"V
2"V
4"V
2"V
2"V4"V
4"V
4"OF SPILL TOSLASH BLOCK
4"OF SPILL TOSLASH BLOCK
4"OF SPILL TOSLASH BLOCK
V1
V1
4"V UP
4"VTR 4"OF SPILL TOSLASH BLOCK
4"ST SPILL TORAIN GARDEN
4"ST UP TO RD-A(2400 SQFT.)
4"OF UP TO RD-B(2400 SQFT.)
4"ST UP TO RD-A(2045 SQFT.)
4"OF UP TO RD-B(2045 SQFT.)
4"ST UP TO RD-A(2075 SQFT.)
4"OF UP TO RD-B(2075 SQFT.)
4"ST UP TO RD-A(2105 SQFT.)
4"OF UP TO RD-B(2105 SQFT.)
4"ST UP TO RD-A(2150 SQFT.)
4"OF UP TO RD-B(2150 SQFT.)
4"ST
CODP
CODP
CODP
V2
4"VTR
1
4
5
4
F-1RD-C
6"ST
6"ST
6"ST SPILL TORAIN GARDEN
6"ST SPILL TORAIN GARDEN
ST2
6"ST DN(4255 SQFT.)
ST1
6"ST DN(4120 SQFT.)
4"OF SPILL TOSLASH BLOCK
ST3
4"ST DN(2400 SQFT.)
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
P-101G150004-000
PLUMBING GROUNDFLOOR PLAN
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 1/8" = 1'-0"1 GROUND FLOOR PLAN
DRAWING KEY NOTES:
COORDINATE PIPE RISERS IN SHAFT WITH PIPES, DUCTS AND CONDUITS FROM ALL OTHER TRADES.
PROVIDE DEEP SEAL TRAPS ON MECHANICAL FLOOR DRAINS.
3/4"CW BELOW GRADE TO NON-FREEZE GROUND HYDRANT (NFGH). WRAP IN CELLULAR FOAM COREINSULATION. SIMILAR TO ARMAFLEX. NFGH TO BE INSTALLED IN CONCRETE CURB WITH 24" GRAVEL BEDBELOW FOR DRAINAGE.
FOR NEW COFFEE MAKERS, AND REFRIGERATORS (FURNISHED AND INSTALLED BY OTHERS). EXTEND COLD WATERSERVICE AND PROVIDE BACKFLOW PREVENTER (BFP), WATER FILTER, AND ALL ASSOCIATED APPURTENANCESINSTALLED BENEATH COUNTER. PROVIDE 5'0" OF COPPER COIL FOR EACH PIECE OF EQUIPMENT. (REFER TO DETAIL)
PROVIDE WASTE AND HOT WATER CONNECTION TO DISHWASHER AS PER MANUFACTURER REQUIREMENTS(REFER TO DETAIL)
1
2
3
4
5
DRAWING NOTES:
1. NON FREEZE WALL HYDRANTS SHALL BE INSTALLED IN THE CONCRETE FOUNDATION WALL, AND NOTIN THE TERRACOTTA PANELS.
NO. ISSUE DATE: DESCRIPTION
RD-ARD-B
RD-ARD-B
RD-ARD-B
RD-ARD-B
RD-A RD-B
L PNM
Q RJH
9
12
6
14
4
15
U
16
17
13
B
11
10
7
5
3
2
C
E F
LL
G
YY
XX
ZZ
RR
1
8
V1 4"VTR
V2
2400 SQFT.
2150 SQFT.
2045 SQFT.
2105 SQFT.
2075 SQFT.
4"VTR
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
P-102G150004-000
PLUMBING ROOF PLAN
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION
M
SCALE:
SCALE:
RPZ M
BFP
1 DOMESTIC WATER RISER DIAGRAMNONE
2 SANITARY RISER DIAGRAMNONE
DRAIN SCHEDULE
PLUMBING FIXTURE SCHEDULE
ELECTRIC WATER HEATER SCHEDULE
PLUMBING EQUIPMENT SCHEDULE
STRAINER
BACK
WATE
RVA
LVE
SERI
ESNO
.
REQU
IRED
ZURN
WADE
JOSA
M
SMITH
SECO
NDAR
YCL
AMP
CLAM
PING
DEVIC
E
CAST
IRON
2005-A
2110
GALV
ANIZE
D
ALLB
RONZ
E
DECK
CLAM
P
TRAC
TOR
GRAT
E
FLAS
HING
COLL
AR
SUMP
RECI
EVER
NICK
ELBR
ONZE
(ADJ
USTA
BLE)
CHRO
MEPL
ATED
SEDI
MENT
BUCK
ET
SECO
NDAR
YSTR
AINER
POLIS
HED
FINISH
CAST
IRON
GALV
ANIZE
D
ALLB
RONZ
E
SATIN
FINISH
DESIG
NATIO
N
FD-B
FD-A
ALL FLOOR DRAINS IN MECHANICAL EQUIPMENT, BOILER ROOMS,FAN ROOMS ETC., SHALL BE LOCATED IN COORDINATION WITHTHE MECHANICAL CONTRACTOR. PROVIDE DEEP SEAL TRAPS.
THE CONTRACTOR SHALL VERIFY THE COMPATIBILITY OF THE DRAINSWITH THE APPROVED ROOFING AND/OR WATER PROOFING SYSTEMSPRIOR TO SUBMITTING SHOP DRAWINGS.
THE TOP OF CURVE OF ALL FLOOR DRAINS SHALL BE FLUSH WITHTHE ADJACENT FINISHED FLOOR.
1.
2.
3.
4.
SHALL BE LOCATED AS PER THE ARCHITECTURAL DRAWINGS.ALL FLOOR DRAINS IN FINISHED AREAS AND ALL ROOF DRAINS
NOTES:
BODY
BRON
ZEME
SHSC
REEN
POLY
ETHY
LENE
SOLID
HING
EDCO
VER
EXTE
NSIO
N
FLAT
TOP
FUNN
ELTO
P
RAISE
DLIP
DOME
IRON
GRAT
E
BRON
ZETO
P
LESS
GRAT
E
TOILET ROOMS
MER
LOCATION
REMARKS
1080
1010
RD-B
RD-A FLAT ROOF
OVER FLOW W/ 2"DAM
SERVICE CONNECTIONFIXTURES FIXTURE #
WSF-1DF-1C
4"
4"
2"
2"
F-1 F-1A
F-2 F-2A
HANDICAPPED
FLUSH VALVE
URINALS
WATER CLOSET
F-3 F-3A
HANDICAPPED
WASH-OUT
LAV SYSTEM
LAVATORIES
F-2B
F-1B
F-3B
F-4AF-4
RECEPTOR
SLOP SINKS
F-5AF-5E.W.C. F-5B
F-4B
V
2"
2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"1 1/2"
3"
1 1/2" 1 1/2"
MODEL NO. REMARKS
MOUNT AT HANDICAPPED HEIGHT
MOUNT AT HANDICAPPED HEIGHT
HW
SAME AS F-1
SAME AS F-2
3/4"
CW
1 1/4"
1 1/4"
1"
1"
3/4"
3/4" 3/4"
1/2"
MANUFACTURER AND EQUIPMENT
ELKAY
PROVIDE ZURN EZCARRY FIXTURE CARRIERSAS REQUIRED
PROVIDE ZURN FIXTURE CARRIERS AS REQUIRED
PROVIDE OFFSET TRAP, VALVE STOPS, RISERS,FAUCET MIXING VALVE AND INSULATION KIT.0.35 GPC ; 10 SEC CYCLESPROVIDE WITH SOAP DISPENSER (6334)
2257.001TET1LN32-CP95
AMERICAN STANDARD AFWALL EL 1.28TOTO FLUSH VALVEOLSONITE OPEN FRONT SEAT LESS COVER
AMERICAN STANDARD WASHBROOK 0.125TOTO FLUSH VALVE
BRADLEY VERGE LVL SERIESTRIM: BRADLEY FAUCETTRUEBRO ADA KIT
6590.125TEU1UN-CP
LVLD3IR-DCG102W WITH 105W
MSB-3624E-77-AA,889-CC, 832-AA8344.212#G1781 W/ #G3600 MIXING VALVE
FIAT 24"x 24" x 10" MOLDED STONEFIAT BUMPERGUARD, MOP HANGERHOSE AND HOSE BRACKET.TRIM: AMERICAN STANDARDEYE WASH STATION (EWS) - GUARDIAN
SETTINGSYMBOLDEG RISEGALS
STORAGE RECOVERY
GPH ELEMENTSNUMBER
KW
ELECTRICAL
V PH HZREMARKSMANUFACTURER
& MODELTEMP
ET
SA
RPZ
ITEM NO.
ARRESTORSHOCK
TANKEXPANSION
PREVENTERBACKFLOW
EQUIPMENTIW
SERVICE CONNECTION
SERIES 5000J.R. SMITH
MANUFACTURER AND EQUIPMENT
WATTS REDUCED PRESSUREZONE DETECTOR ASSEMBLY
DOMESTIC WATER SERVICEFLOOD PROTECTION VALVE
REMARKS
W/F113-6RFPLF 957RPDA-OSY-AG
MODEL NO.
LOCATE AS SHOWN ON PLAN
W V CW HW
2 1/2"
PIPE SIZE
EWH-1-1
EWH-1-2
TP LOCATE AS SHOWN ON PLAN1/2"TRAP PRIMER P-1-500PPP-INC.
DOMESTIC METERSENSUS OMNI C2
WITH MODBUS CAPABILITIES TIE INTOBMS SYSTEM
SEE DWGS
NON-FREEZE WALLHYDRANT NFWH 3/4" ZURN Z1300
WITH IN-LINE VACUUM BREAKERASSE-1011. LOCATE AS SHOWN ON PLAN
LZSTL8WSLK PROVIDE CARRIER SUPPORT AND INLINEFILTER.
1.28 GPF; ECO POWER BATTERY
1.28 GPF; ECO POWER BATTERY
MV LOCATE AS SHOWN ON PLAN1/2"MIXINGVALVE ZW3870XLTZURN
15 8 180 1.5 120 1 11060 BRADFORD WHITE - LE115U3-1
PROVIDE WITH RELIEF SENSORS AND PAN. EXTEND RELIEF DRAIN TO PAN.EXTEND DRAW FROM PAN TO NEAREST INDIRECT WASTE RECEPTOR.
20 10 80 BRADFORD WHITE - LE120U3-12.0 1201 1 60 110
MOUNT ON WALL. PROVIDE WITH RELIEF SENSORS AND PAN. DRAIN PANTO MOP RECEPTOR.
ROOF
GROUND FLOOR
LOWER LEVEL
ROOF
GROUND FLOOR
LOWER LEVEL
6" COMBINED DOMESTIC AND SPRINKLERWATER SERVICE. 5'-0" FROM BUILDING.FOR CONTINUATION REFER TO SITE/CIVILDRAWINGS.
4" FIRE WATER SERVICE. FORCONTINUATION REFER TO FIREPROTECTION DRAWINGS.
BY FC BY PC
4"
2 1/2"
6"
ROOF
GROUND FLOOR
LOWER LEVEL
ROOF
GROUND FLOOR
LOWER LEVEL
WALL MOUNTED 1 1/2"1 1/2" 3/4" 3/4"BRADLEY VERGE LVL SERIESTRIM: BRADLEY FAUCETTRUEBRO ADA KIT
LVLD1IR-DCG102W WITH 105W
2 1/2"
NFGH
1/2"F-6F-6
3/4"
EWH-1-1
2 1/2"
2 1/2"
NFWH
3/4"3/4"
2 1/2"
F-5F-3AF-1A
3/4"
F-3
1/2"
F-3
3/4"
F-1F-1F-1A
2"
1 1/4" 1 1/4"
F-1F-2A
3/4"
F-1A
NFWH
F-4
3/4"3/4"3/4"
EWH-1-2
2 1/2"1 1/4"
3/4" 3/4"
3" FD-B3" FD-B3" FD-B
4" 4" SANITARY TO MAIN. 5'-0" FROM BLDG.REFER TO SITE CIVIL PLAN FOR CONTINUATION.PROVIDE BUILDING TRAP AND FAI.
3"4"
4"
3"
3"
4"
V1
2"2"
F-6F-6
2"
4"VTR
2"2"
CODP
4"4"
4"
F-3A
2"
2"
F-1A
F-1 F-1 F-1AF-2AF-1F-1A
V2
4"VTR
2"2"2"2"2"
4"
4"
4"2"2"
4"4"
2"
4"
F-3F-3
3" FD-A3" FD-A
3"2"
3"
CODP
4"3"2"
3" FD-AF-4
4"
2"
2"
1/2" 1/2" 1/2"
3/4"3/4"
1/2" 1/2" 1/2" 1/2" 1/2"
1 1/4"1 1/4"
1 1/4"
3/4"
3/4"3/4"3/4"
F-6 F-6A F-6BSINKS
PANTRY 1 1/2"2" 3/4"3/4"SK: ELKAYTRIM: CHICAGO FAUCET
LR-2219201-GN8A-E3-317
1 1/2" 1 1/2" 1/2" ELKAY LZWSGRNM8K 1.1 GPM FILLING. PROVIDE CARRIERSUPPORT AND INLINE FILTER.
BOTTLE FILLINGSTATION
TWO-LEVEL -ADA
NON-FREEZE GROUNDHYDRANT NFGH 3/4" ZURN Z1360
WITH IN-LINE VACUUM BREAKERASSE-1011. LOCATE AS SHOWN ON PLAN
SA
SASA
SA
SA
SASA
EWS
SA
F-5A
WRAP BURIED COPPER PIPE INCELLULAR FOAM CORE INSULATION,SIMILAR TO ARMAFLEX OR EQUAL.
3" FD
1"
1/2"
TP
1 1/4"
3/4" SA
3" FD
1/2"
TP
BFPPREVENTERBACKFLOW WATTS REDUCED PRESSURE
ZONE ASSEMBLYFOR MECHANICAL EQUIPMENT
W/ AIR GAP & DRAIN TO INDIRECT WASTEW/909AGLF 9093/4"
1"3/4"
3/4"CW MAKE UP TOMECHANICAL EQUIPMENT.CONNECTION BY MC.
HB
3/4"
PRV4"
NOTES:
1. PROVIDE WATER BUG SENSORS SIMILAR TO WINLAND WB-200 ON EACH WATER HEATER FORAUTOMATIC LEAK DETECTION. PROVIDE POWER AND LOW VOLTAGE WIRING. TIE INTO NEW ALARM/BAS SYSTEM.
NOTES:
1. FIXTURE CARRIERS SHALL BE OF STEEL CONSTRUCTION.
PROVIDE OFFSET TRAP, VALVE STOPS, RISERS,FAUCET MIXING VALVE AND INSULATION KIT.0.35 GPC ; 10 SEC CYCLESPROVIDE WITH SOAP DISPENSER (6334)
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
P-200G150004-000
PLUMBING RISERDIAGRAMS & SCHEDULES
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
SCALE: 12" = 1'-0"1 PLUMBING RISER DIAGRAM
NO. ISSUE DATE: DESCRIPTION
PIPE SLEEVE THRU INTERIOR WALL
PIPE SLEEVE
COMPLETELY COVER OPENINGAGAINST WALL AND OF SIZE TOFINISHED ESCUTCHEON PLATE FLUSH
FINISHED WALL SURFACE
FINISHED WALL SURFACESTERMINATE SLEEVE FLUSH WITH
SEALANT
FROM SLEEVEIN SLEEVE - DO NOT SUPPORT PIPEPIPE AND INSULATION TO BE CENTERED
FLASHING SLEEVE
VENT THRU ROOF
VENT STACK OUTLET TO BE 10 FT.(MIN)
WATERTIGHT MANNERMOP IN ROOFING IN AFILL IN ABOVE SLEEVE AND
ANCHORED IN PLACEFLASHING SLEEVEMANUFACTURED STACK
SLEEVECLAMPED INTO FLASHINGSHEET LEAD FLASHING
VENT STACK EXTENSION
VENT STACK
COLLAROPTIONAL CLAMPING
ROOFING
ROOF CONSTRUCTION
MIN. 12"
MIN. 12"
3 FT.ABOVE STRUCTURE FROM ANY WALL OR STRUCTURE ORNOTE:
NO-HUB COUPLING
FOUNDATION WALL PENETRATION DETAIL
SMOOTH CORE DRILL (10" )
LINK-SEAL TYPE LS-400-CWALL PENETRATION SEAL
(VERIFY THICKNESS IN FIELD)FOUNDATION WALL
TYPICAL HANGER DETAIL
ROD (SIZE AS REQUIRED)
THE MANUFACTURER'S RECOMMENDATION.INSTALLATION SHALL BE IN ACCORDANCE WITHSERIES HDI, OR APPROVED EQUAL.CONCRETE ANCHOR HILTI-KWICK BOLT,
EXISTING WF STEEL MEMBER
GENERAL PURPOSE HANGERS MAY BE USED ON PIPING 1" OR SMALLER.
PIPE
CLEVIS HANGERS REQUIRED ON PIPING LARGER 1".*
*CLEVIS HANGER
STEEL RETAINING STRAP
COUPLER
METAL DECK
"C" CLAMP
CONCRETE WITH INSULATION SLOPED)DETAIL OF ROOF DRAIN (POURED
MEMBRANEBUILT-UP
GRAVEL STOPFLASHING RING AND
INSULATION
GRAVEL
EXTENSION
SLAB
FLASHING
PIPE OUTLET
OAKUM
LEAD
GRADE
OVERFLOW DRAINAGE SYSTEMDISCHARGE AT GRADE
PLACARD 8"x6" "CONTACT FACILITYMAINTENANCE STAFF AT XXXX IF WATERDISCHARGES HERE"
ESCUTCHEONPLATE
DOWNSPOUT NOZZLEJR SMITH 1770
24" MIN
SPLASH BLOCK
SLEEVE ANDSEALANT
FLOOR DRAIN WITH ADJUSTABLE TOP
ADJUSTABLE TOP
COLLAR CAN BEUSED AS FLASHINGCLAMP
TO BE FLUSH WITHFINAL FINISH FLOOR
MAT FINISH
FLOOR DRAIN FOR INDIRECT WASTETYPICAL MECHANICAL ROOM
INDIRECT WASTE SPILLOVER MECHANICALROOM FLOOR DRAIN
MAXIMUM DIAMETERBOTTOM BAR STRAINER ONSHORT LEGS
S
SCALE:
S PLUMBING EQUIPMENT SCHEDULE
NTS
WATER HEATER ABOVE HUNG CEILING WALL MOUNTED WATER HEATER DETAIL
TYPICAL DISHWASHER CONNECTION
FOR STRUCTURAL STABILITYREINFORCE AS NECESSARY24"X24"X1-1/2" LIPDRIP PAN (WATERTIGHT)
STEEL RETAINING STRAP
3/4"
RELIEF VALVE
PAN DRAIN
"C" CLAMP
SUPPORTCHANNEL IRON
CONCRETE FLOOR SLAB
HUNG CEILINGBOTTOM OF
HW SUPPLY
CW SUPPLY
VACUUM BREAKER
110°F 110°F
TP
TO TRAPEXP.TANK
ELECTRICWATERHEATER
COPPER TUBING (TYP)5'-0" OF COILED
1/2"
1/2"CW W/ESCUTCHEON
WATTS SD2 BFP(TYPICAL)
(TYP)WHA
ILF-1
COFFEE MACHINEBY OTHERS
REFBY OTHERS
BFP-1
ITEM No.
PREVENTERBACKFLOW
EQUIPMENTIW W
SERVICE CONNECTION
V CWMANUFACTURER AND EQUIPMENT
WATTS BACKFLOW PREVENTER
HW
1/2"
REMARKS
SD2
MODEL No.
IN-LINEFILTER ILF-1 1/2" AP200
5005HYDROTROLJ.R. SMITH1/2"WHAARRESTER
WATER HAMMER
FILTERED WATERREFRIG/COFFEE MAKER
REFRIG/COFFEE MAKERFILTERED WATER
REFRIG/COFFEE MAKERFILTERED WATER
AQUAPURE
ICE MAKERBY OTHERS
SPILL INDIRECTLYTO HUB DRAIN
NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR ROOFING DETAILS
RELIEF VALVE
HW SUPPLY
CW SUPPLY
VACUUM BREAKER
110°F 110°F
ELECTRICWATERHEATER
SPILL INDIRECTLYTO MOP RECEPTOR
MOP RECEPTOR
WALL MOUNTING BRACKETAND STRUCTURAL SUPPORT
CHECK VALVE
DISHWASHER(BY OTHERS)
SINK
3/4"FLEX
2"WASTE
2"VENT
1/2"HW
TYPICAL WATER & FILTER CONNECTION DETAIL
02'
4'6'
08'
16'
24'
06"
9"3"
01'
6"1-
6"0
1/2'
1'2'
01'
2'3'
01'
2'4'
02'
4'8'
4'0
8'16
'0
8'16
'32
'
SHEET NUMBER
SFA PROJECT NUMBERFULL SHEET SIZE: 30" x 42"
REGISTRATION
CURRENT ISSUE
DRAWING HISTORY
SCAL
E:1/
16"=
1'-0
"SC
ALE:
1/8"
=1'
-0"
SCAL
E:1/
4"=
1'-0
"SC
ALE:
1/2"
=1'
-0"
SCAL
E:3/
4"=
1'-0
"SC
ALE:
1"=
1'-0
"SC
ALE:
11/
2"=
1'-0
"SC
ALE:
3"=
1'-0
"
1
A
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL / ELECTRICAL / PLUMBING
FIRE PROTECTION ENGINEER
LANDSCAPE ARCHITECT
ACOUSTICAL ENGINEER
NOTES: DO NOT SCALE DRAWINGS. CONTRACTORSSHALL VERIFY ALL DIMENSIONS BEFORE INSTALLATION
COPYRIGHT 2016 SFA
AUDIO VISUAL ENGINEER
2 3 4 5 6 7 8 9 10 11 12
B
C
D
E
F
G
H
I
J
SECURITY ENGINEER
SCAL
E:3/
32"=
1'-0
"SC
ALE:
3/8"
=1'
-0"
PROJECT No: MI-1105
C:\R
evit
Loca
lFile
s\G
1500
04-0
00-M
illers
ville
-M
EP15
_Cen
tral_
tbla
ncha
.rvt
P-300G150004-000
PLUMBING DETAILS
Millersville University
LOMBARDO WELCOMECENTER
P.O. Box 1002Millersville, PA 17551-0302
P.O. Box 1002Millersville, PA 17551-0302
09/28/2016
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
Providence Engineering Corporation10 Eisenhower Blvd.
Lancaster, PA 17603717-509-7000
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
InPosse1500 Walnut Street, Suite 1414
Philadelphia, PA 19102215-282-6800
Derck & Edson33 South Broad Street
Lititz, PA 17543717-626-2054
N/A
N/A
N/A
NO. ISSUE DATE: DESCRIPTION