Fualt Level Sps
-
Upload
susil-kumar-khuntia -
Category
Documents
-
view
214 -
download
0
Transcript of Fualt Level Sps
-
8/9/2019 Fualt Level Sps
1/12
FAULT LEVEL CALCULATION(PU Method)At 33 KV side of SPS Site.
Alternative-1Sr. No. Description Voltage Amps MVA Qty. Remarks
1 System Voltage220KV
2 Fault Level8.737KA
3 04 N0. of the transformer 2
5 Rating of each trans. 220/33KV 42/280A 16 MVA
69.98% cosidering 90% i.e. 8.982%
7 220/33 Kv
178.13MVA
80.56
10
0.31
11Fault Level At 33 side
12 5.63KA
erna ve-Sr. No. Description Voltage Amps MVA Qty. Remarks
1 System Voltage220KV
2 Fault Level8.737KA 3329.1 MVA
3 04 N0. of the transformer 25 Rating of each trans. 220/33KV 42/280A 50 MVA
611.82% cosidering 90% i.e. 10.638%
7 220/33 Kv470MVA
3329.1MVA
PU Rectance=BaseMVAFualt MVAXs=1003329.1PU Reactance of Considering 100MVA
% Impedance.of eachtrafo.
PU Rectance=BaseMVAFualt MVAXs=100178.13Fault rating of each
transfo.0.468/3.11KA
PU Reactance of Each Trafo.
Considering 100MVABase
PU Rectance=BaseMVAFualt MVA
Total PU Impedance( Xs+Xt)
Base(100)(Xs+St)=321.85
Total Fault Current At33KV Side
PU Rectance=BaseMVAFualt MVAXs=1003329.1PU Reactance of
System (Xs)Considering 100MVA
Base
% Impedance.of eachtrafo.
Fault rating of eachtransfo.
1.233/8.22KA
PU Rectance=BaseMVAFualt MVAXs=100470
PU Reactance of Considering 100MVA
-
8/9/2019 Fualt Level Sps
2/12
8 0.21
9 0.11
100.14
11Fault Level At 33 side
12 12.83KA
Alternative-3Sr. No. Description Voltage Amps MVA Qty. Remarks
1 System Voltage220KV
2 Fault Level8.737KA 3329.1 MVA
3 04 N0. of the transformer 25 Rating of each trans. 220/33KV 183.7/1224 70 MVA
612.52% cosidering 90% i.e. 11.268%
7 220/33 Kv621.22 MVA
8 0.17
9 0.08
100.11
11Fault Level At 33 side
1215.83KA
FAULT LEVEL CALCULATION(Simple Method)At 33 KV side of SPS Site.
Alternative-1Sr. No. Description Voltage Amps MVA Qty. Remarks
1System Voltage
220KV
2 Fault Level 8.737KA 3329.1MVA3 N0. of the transformer 24 Rating of each trans. 220/33KV 42/280A 16 MVA5 9.98% cosidering 90% i.e. 8.982%
Each Trafo.
Base
Total PU Reactanceof Trafo (Xt)
PU Rectance=BaseMVAFualt MVAXs=100(2x470)Total PU Impedance
( Xs+Xt)
Base(100)(Xs+St)=733.24 Fault Current=Base
MVATotal PUImpdance
Fault Current At 33KV Side
PU Rectance=BaseMVAFualt MVAXs=1003329.1PU Reactance of
System (Xs)Considering 100MVA
Base
% Impedance.of eachtrafo.
PU Rectance=BaseMVAFualt MVAXs=100621.22Fault rating of each
transfo.1.63/10.868KA
PU Reactance of Each Trafo.
Considering 100MVABase
PU Rectance=BaseMVAFualt MVAXs=100(2x621.22)Total PU Reactance
of Trafo (Xt)Total PU Impedance
( Xs+Xt)Base(100)(Xs+St)=
904.97 Fault Current=BaseMVATotal PU
ImpdanceFault Current At 33
KV Side
% Impedance.of each
-
8/9/2019 Fualt Level Sps
3/12
6 220/33 Kv178.13MVA
7356.26MVA
8 321.82MVA
9 5.63 KAAlternative-2
System Voltage1 220KV2 Fault Level 8.737KA 3329.1MVA3 N0. of the transformer 2
4 Rating of each trans. 220/33KV50 MVA
511.82% cosidering 90% i.e.10.638%
6 220/33 Kv 470 MVA
7940MVA
8 733.02MVA
9 12.82 KAAlternative-3
Sr. No. Description Voltage Amps MVA Qty. Remarks1
System Voltage220KV
2 Fault Level 8.737KA 3329.1MVA3 N0. of the transformer 24 Rating of each trans. 220/33KV 42/280A 70 MVA5
6 220/33 Kv621.22MVA
71242.45MVA
8904.77 MVA
9 15.83 KA
Fault Level CalculationAlternative-1
1 Voltage Level of the System 220KV
Fault rating of eachtransfo.
0.468/3.11KA
Total Fault Rating for both Trafo.
0.936/6.22KA
16x1008.982=178.13MVA
Total Impedanceduring Fault(Z)
0.844/5.63KA
Z=3329.1x356.263329.1+356.26=
321.82Total Fault Current At33 k v side
131.12/875Amps
% Impedance.of eachtrafo.
Fault rating of eachtransfo. 1.23/8.22KATotal Fault Rating for both Trafo.
2.44/16.22KA
Z=3329.1x9403329.1+940=733.02Total Impedance
during Fault(Z).896/5.98
KA
Total Fault Current At33Kv Side
% Impedance.of each 12.52% cosidering 90%Fault rating of eachtransfo.
1.63/10.86KA
70x1008.982=621.22MVA
Total Fault Rating for both Trafo.
3.26/21.75KA
Total Impedanceduring Fault
2.37/15.83KA
Z=3329.1x1242.453329.1+1242.45=
904.77Total Fault current At33KV Side
-
8/9/2019 Fualt Level Sps
4/12
2 Fault Level at220KV
332.1 MVA At Budipadar S/S
3 Fault current at 220KV
433
5
2
616MVA
7 9.98%8 8.98%9 100
10
110.56
1213 Xs+Xt= 0.3114 Fault Level at 33 KV15 fault Current at 33 kv side of System 5.63 KA
Alternative-II1 Voltage Level of the System 220KV
2 Fault Level at 220KV
3 Fault current at 220KV
433
5
2
650MVA
7 11.82%8 10.64%9 100
10 220KV Side
11 0.21
1213 Xs+Xt= 0.1414 Fault Level at 33 KV15 fault Current at 33 kv side of System 12.83 KA
KV side of System
KV side of System
8.737KA atBudipadar S/S
It is required to bedetermine the fault
KV side of thesystem.
No. of Transformer Installed in the S/S
( consideringfuture
extention)
Rating of EachTransformer 220/33 KV At
ONAF cooling
Reactance of Eachwith 10% negative
PU Reactance of thesystem UpTo
220KVSide
Xs=BaseMVA/FaultMVA=0.0300
PU Reactance of
Each Tranfo.at
100 MVA
basePU equivelentReactance Of Tranfo.
100 MVAbase
Xt=0.28069
Total PU equivelent,=
=
KV side of System
332.1 MVA AtBudipadar S/S
KV side of System
8.737 AtBudipadar S/S
It is required to bedetermine the fault
KV side of thesystem.
No. of Transformer Installed in the S/S
( consideringfuture
extention)
Rating of EachTransformer 220/33 KV At
ONAF cooling
Reactance of Eachwith 10% negative
Xs=BaseMVA/FaultPU Reactance of Each Tranfo.at
100 MVAbase
equ ve enReactance Of Tranfo. 100 MVAbase
Xt=0.10638
,=
=
-
8/9/2019 Fualt Level Sps
5/12
Alternative-III1 Voltage Level of the System 220KV
2 Fault Level at 220KV
3Fault current at
220KV
433
5
2
670MVA
7 12.52%8 11.27%9 100
10 220KV Side
11 0.16
1213 Xs+Xt= 0.1114 Fault Level at 33 KV15 fault Current at 33 kv side of System 15.83 KA
1 33KV2 Fault level At 33KV side of system 904.78MVA
3 33KV side of system 15.83KA4 6.6 KV of system
5 2 Nos.
6Rating Of Each trafo.
33KV/6.6KV 10MVA
7 8.40%
8 Assumed 7.56%
9 100MVA
10 33 KV Side 0.11
11 0.76
12 Xt=0.378
KV side of System
332.1 MVA AtBudipadar S/S
KV side of System
8.737 AtBudipadar S/S
It is required to bedetermine the fault
KV side of thesystem.
No. of Transformer Installed in the S/S
( consideringfuture
extention)
Rating of EachTransformer 220/33 KV At
ONAF cooling
Reactance of Eachwith 10% negative
Xs=BaseMVA/FaultPU Reactance of Each Tranfo.at
100 MVAbase
equ ve enReactance Of Tranfo. 100 MVAbase
Xt=0.08049
Side of System,=Base MVA/PU
Faultcurrent atIt required to bedetermine the faultlevel atNo. of Tranfo.Installed in S/S
Reactance of eachTrafo.With 10% Negativetolerance reactanceof each trafo.Let Cosider baseMVAPU Reactance of system upto
XS=Base MVA / FaultMVA
PU Reactance of each trafo at
100 MVABase
PU Equivelent 100 MVA
-
8/9/2019 Fualt Level Sps
6/12
Xs+Xt= 0.49
Fault level at
15 Fault current at 17.91 KA
reactance of trafo. Inparallel.At
base
Total PU EquivelentReactance
6.6 KV side of system=BaseMVA/PUEquivelent Reactance=
204.7MVA
6.6 KV side of system=BaseMVA/PUEquivelent Reactance=
-
8/9/2019 Fualt Level Sps
7/12
-
8/9/2019 Fualt Level Sps
8/12
-
8/9/2019 Fualt Level Sps
9/12
-
8/9/2019 Fualt Level Sps
10/12
-
8/9/2019 Fualt Level Sps
11/12
-
8/9/2019 Fualt Level Sps
12/12