Reliable Foam Proportioning Bladder Tanks EX26925
FOAM BLADDER TANKS
PR
OD
UC
T O
F
Bladder TankFoam Proportioning Unit
Features
Application
Description
SpecificationSpecificattiiooooooonnnn
Horizontal Mounting
Vertical MountingR.N RI TI N M T RI
1 FOAM VESSEL CARBON STEEL
2 FOAM BLADDER NYLON REINFORCED NITRILE RUBBER (BUNA-N)
3 FOAM PROPORTIONER CARBON STEEL WITH STAINLESS STEEL INTLS.
I STAINLESS STEEL
4 SPOOL PIECE CARBON STEEL
5 FOAM PIPING STAINLESS STEEL
6 WATER PIPING CARBON STEEL
7 FOAM SUPPLY VALVE STAINLESS STEEL
B WATER CHARGING VALVE STAINLESS STEEL
9 BLADDER VENT I BLADDER DRAIN STAINLESS STEEL
10 VESSEL VENT I VESSEL DRAIN STAINLESS STEEL
11 THERMAL EXPANSION RELIEF VALVE COPPER ALLOY I STAINLESS STEEL
1. ITEM CODE – VBT- # (# - INDICATES CAPACITY OF FOAM VESSEL IN LITERS)
2. CAPACITY - 200 LITERS TO 15000 LITERS
3. DESIGN CODE - ASME SEC.VIll DIV.I LATEST EDITION (OPTIONAL - ASME U STAMPED)
4. MAXIMUM WORKING PRESSURE -12.06 BAR (175 PSI)
5. HYDROSTATIC TEST PRESSURE - 18.09 BAR (263 PSI)
6. PAINTING
a) INTERNAL - COAL TAR EPOXY
b) EXTERNAL - PAINTED EPOXY FIRE-RED TO SHADE NO. RAL 3000
M T RIRI TI NR.N
RN . RI TI N M T RI1 M V RB N T
2 M B R NY N R IN R NITRI R BB R
M R RTI N R RB N T ITH T IN T INT .
4 I RB N T
5 M I IN T IN T
6 T R I IN RB N T
7 M Y V V T IN T
8 T R H R IN V V T IN T
9 B R V NT I B R R IN T IN T
10 V V NT I V R IN T IN T
11 TH RM X N I N R I V V R Y I T IN T
1. MODEL - HBT- # ( # - INDICATES CAPACITY OF FOAM VESSEL IN LITERS)
2. CAPCITY - 400 LITERS TO 15.000 LITERS
3. DESIGN CODE - ASME SEC.VIII DIV.I LATEST EDITION (OPTIONAL- ASME U STAMP)
4. MAXIMUM WORKING PRESSURE -12.06 BAR (175 PSI)
5. HYDROSTATIC TEST PRESSURE -18.09 BAR (263 PSI)
6. FINISH
a] INTERNAL - COAL TAR EPOXY
b] EXTERNAL - PAINTED EPOXY FIRE-RED TO SHADE NO. RAL3000
RN . RI TI N M T RI
Bladder TankFoam Proportioning Unit
Vertical
Bladder TankCapacities
50N B 80N B 100N B 150N B 200 N B
200 53
300 79
400 106
500 132
600 159
700 185
800 211
900 238
1,000 264
1,250 330
1,500 396
1,750 462
2,000 528
2,500 661
3,000 793
3,500 925
4,000 1,057
4,500 1,189
5,000 1,321
5,500 1,453
6,000 1,585
6,500 1,717
7,000 1,849
7,500 1,982
8,000 2,114
8,500 2,246
9,000 2,378
9,500 2,510
10,000 2,642
11,000 2,906
12,000 3,170
13,000 3,435
14,000 3,699
15,000 3,963
C A P A C IT Y IN LIT ER
C A P A C IT Y IN GA LLON S
F o am R at io C o ntro ller Size
Horizontal
Bladder Tank Capacities
50N B 80N B 100N B 150N B 200 N B
400 106
500 132
600 159
700 185
800 211
900 238
1,000 264
1,250 330
1,500 396
1,750 462
2,000 528
2,500 661
3,000 793
3,500 925
4,000 1,057
4,500 1,189
5,000 1,321
5,500 1,453
6,000 1,585
6,500 1,717
7,000 1,849
7,500 1,982
8,000 2,114
8,500 2,246
9,000 2,378
9,500 2,510
10,000 2,642
11,000 2,906
12,000 3,170
13,000 3,435
14,000 3,699
15,000 3,963
C A P A C IT Y IN LIT ER
C A P A C IT Y IN GA LLON S
F o am R at io C o ntro ller Size
Bladder TankFoam Ratio Controller
RN . RI TI N M T RI1 Body RB N T / T IN T
2 N T IN T
N T IN T
4 V v T IN T
1. MODEL - BTFP
2. APPROVAL – UL LISTED WITH AFFF3% AR-AFFF 2X3% (UL FILE NO.EX15733)
3. MAXIMUM WORKING PRESSURE :-12.06 BAR (175PSI)
4. FOAM PROPORTIONING RATIO – 3% WITH AFF & AR-AFFF FOAM CONCENTRATE
5. HYDRAULIC TEST PRESSURE – 18.09 BAR ( 263 PSI)
6. FLANGE DRILLING- AS PER ANSI B16.5, 150#, RF
7. FINISH – INTERNAL – COAL TAR EPOXY
8. EXTERNAL – EPOXY FIRE-RED TO SHADE RAL 3000
M – IZ(NB)
N MINR N IN M
R . R TIIN %
( NB ) B ( NB )
BT 50 70 - 1000 % 50 25 1000
BT 80 200 - 3200 % 80 40 1000
BT 100 400 6200 % 100 40 1000
BT 150 1000 11500 % 150 50 1000
BT 200 000 20000 % 200 65 1000
Note: 1) All dimension are in mm, unless otherwise specified2) *-Flow range mentioned above is nominal flow range, for flow range with specific foam concentrate contact SFFECO.
PR
OD
UC
T O
F
100