Ordering description Outside diameter Package contents Sales pack quantity
Item number
CFS-PL 107 107 mm 1x Firestop plug CFS-PL 107 1 pc 2059530CFS-PL 132 132 mm 1x Firestop plug CFS-PL 132 4 pc 2059531CFS-PL 158 158 mm 1x Firestop plug CFS-PL 158 2 pc 2059532CFS-PL 202 202 mm 1x Firestop plug CFS-PL 202 2 pc 2059533
Firestop plug CFS-PL
Technical dataBase materials Concrete, Masonry, Drywall
Acoustics performance Test report available
Tested in accordance with EN 1366-3
Repenetration Possible
Reaction to fire class (EN 13501-1)
E
Application temperature range 5 - 40 °C
Temperature resistance range -15 - 60 °C
Can be painted Yes
Shelf life1) Not relevant
Chemical basis PU1) at 77 °F / 25 °C and 50% relative humidity; from date of manufacture
Applications■ Temporary or permanent sealing around cables and cable
bundles in wall and floor openings■ Cables and cable bundles
Advantages■ Easy to install, no electric tools required■ Very easy maintenance and retrofitting of cables■ Economical installation as the plug is pre-cured and
ready-to-use■ Painting of cables with firestop coating is not required■ Ideal for the temporary closing of empty core holes
Scan this code to findout more:
hilti.co.uk/ r26207
1
Firestop plug kit
hilti.co.uk | Issue 08/2016
Ordering description Package contents Sales pack quantity
Item number
CFS-FIL 1x Firestop filler mastic CFS-FIL 1 pc 2052899
Firestop filler mastic CFS-FIL
Technical dataVolume per unit 310 ml
Approx. curing time1) 4mm/3 days
Re-penetration Not possible
Application temperature range 5 - 40 °C
Temperature resistance range -20 - 60 °C
Can be painted Yes
Shelf life2) 12 months
Chemical basis Water-based acrylic dispersion
LEED VOC 9 g/l
Colour Red1) at 75 °F / 24 °C, 50% relative humidity 2) at 77 °F / 25 °C and 50% relative humidity; from date of manufacture
Applications■ For use with CFS-BL firestop block ■ For use with CFS-PL firestop plug
Advantages■ Fits the CFS-DISP dispenser ■ Easy to work with and fast cleanup■ Water-based
Ordering description Package contents Sales pack quantity
Item number
CFS-P BA 1x Firestop putty bandage CFS-B PA 5 mm 1 pc 2062876
Firestop putty bandage CFS-B PA
Applications■ For use with CFS-PL firestop plug ■ for specific cable configurations, to achieve EI 120
Advantages■ East to cut ■ Self-adhesive
Scan this code to findout more:
hilti.co.uk/ r68870
Scan this code to findout more:
hilti.co.uk/ r115931
2
Firestop plug kit
Issue 08/2016 | hilti.co.uk
Main approved applications
Partition Flexible wall Rigid wall Rigid floorBase material thickness (tE) ≥ 100 mm ≥ 100 mm ≥ 150 mmOpening diameter < 202 mm (largest available plug)Fixing to wall / floor Friction fit within opening. Framing of opening not requiredGap filler CFS-FILPenetration Single cable and cable bundle, metal and plastic conduits, conduit bundlesBeading Square gypsum board size 200 mm + Ø plug on each side to reach
150 mm total seal depthNone
*All sheathed cable types currently and commonly used in building practice in Europe (e.g. power, control, signal, telecommunication, data optical fibre cables)
Note: Beading required to reach 150 mm penetration depth with walls of less than 150 mm. Square plates made of gypsum or calcium silicate board size 200 mm plus plug Ø (wA = 100 mm), installed around the opening in the necessary number of layers. On both sides of the wall.
Excerpt of ETA document. Check the exact field of application for each Penetration (type, diameter) in the ETA 13/0125 document.
Penetration: Cables* Cable Ø mm Flexible wall Rigid wall Rigid floor
All sheathed cables ≤ 21 EI 120
Non-sheathed cables (wires) ≤ 24 EI 60 or E 120 EI 30 or EI 120
Tied cable bundle Ø ≤ 100 mm ≤ 21 EI 120
All sheathed cables ≤ 50 EI 90 (EI 120 with CFS-P BA) E 120
All sheathed cables ≤ 80 EI 90 or E 120
Penetration: Conduits Pipe Ø mm
Plastic conduits and tubes ≤ 16 EI 120 U/U
Steel conduits and tubes ≤ 16 EI 120 C/U
Flexible conduits PO with or without cables 16 - 40
EI 120 U/UFlexible conduits PVC with or without cables 16 - 32
Rigid conduits PO / PVC with or without cables 16 - 40
Bundles (Ø ≤ 100 mm) of rigid and flexible conduits with or without cables ≤ 20
No penetration
Blank seal - EI 120
General information
3
Firestop plug kit
hilti.co.uk | Issue 08/2016
General instructions for use
Cable / conduitØ (mm)
Maximum number of cables / conduits
CFS-PL 107 CFS-PL 132 CFS-PL 158 CFS-PL 202
3.0 566 861 1233 20044.0 318 484 694 11275.0 204 310 444 7318.0 80 121 173 2829.0 63 96 137 22315.0 23 34 49 8020.0 3 5 8 15 20 mm to seal edge and
to other penetrations for conduits Ø > 16 mm
30.0 1 3 5 1040.0 1 1 3 7
Fire Rated Assembly / Assemblage Homolugué
Product: Produt:
Location: Endroit:
System #: Système #: Tel:
Installed by: Installation Date: Date d’installation:
Repenetrated by: Date:
Fire Rated Assembly / Assemblage Homolugué
Product: Produt:
Location: Endroit:
System #: Système #: Tel:
Installed by: Installation Date: Date d’installation:
Repenetrated by: Date:
Fire Rated Assembly / Assemblage Homolugué
Product: Produt:
Location: Endroit:
System #: Système #: Tel:
Installed by: Installation Date: Date d’installation:
Repenetrated by: Date:
Maximum 60% visual fill
Maximum number of cables or conduits per opening
4
Firestop plug kit
Issue 08/2016 | hilti.co.uk
Characteristics of CFS-PL
Characteristics Assessment of characteristics Norm, standard, testHealth and the environmentDangerous substances
Clean-TecBelow any respective occupational exposurelimits as far as such limits exist (compared withthe list of dangerous substances of the European Commission).
Hilti Clean-Tec criteriaMaterial safety data sheet
Protection against noiseAirborne sound insulation
Double plug CFS-PL=Rw (C; Ctr) = 54 (-1; –7) dB EN ISO 140-3
Thermal properties Thermal conductivity λ = 0.089 W/mK andthermal resistance R = 0.563 m2K/W
EN 12667
Electrical properties Electrical volume resistivity:2.17E+9 (± 0.5) Ω cmElectrical surface resistivity:49.6E+9 (± 10 ) Ω
DIN IEC 60093 (VDE 0303 Part 30):1993-12
Durability and serviceability Category Y1 (Products intended for use at temperatures between -5 °C and +70 °C with exposureto UV but without exposure to rain).
EOTA Technical Report TR 024ETAG 026-2
Reaction to fire Class E EN 13501-1
5
Firestop plug kit
hilti.co.uk | Issue 08/2016