Firestop plug CFS-PL - Hilti Sweden€¦ · stèm Te Installed by: ... Hilti Clean-Tec criteria...

5
Ordering description Outside diameter Package contents Sales pack quantity Item number CFS-PL 107 107 mm 1x Firestop plug CFS-PL 107 1 pc 2059530 CFS-PL 132 132 mm 1x Firestop plug CFS-PL 132 4 pc 2059531 CFS-PL 158 158 mm 1x Firestop plug CFS-PL 158 2 pc 2059532 CFS-PL 202 202 mm 1x Firestop plug CFS-PL 202 2 pc 2059533 Firestop plug CFS-PL Technical data Base materials Concrete, Masonry, Drywall Acoustics performance Test report available Tested in accordance with EN 1366-3 Repenetration Possible Reaction to fire class (EN 13501-1) E Application temperature range 5 - 40 °C Temperature resistance range -15 - 60 °C Can be painted Yes Shelf life 1) Not relevant Chemical basis PU 1) at 77 °F / 25 °C and 50% relative humidity; from date of manufacture Applications Temporary or permanent sealing around cables and cable bundles in wall and floor openings Cables and cable bundles Advantages Easy to install, no electric tools required Very easy maintenance and retrofitting of cables Economical installation as the plug is pre-cured and ready-to-use Painting of cables with firestop coating is not required Ideal for the temporary closing of empty core holes Scan this code to find out more: hilti.co.uk/ r26207 1 Firestop plug kit hilti.co.uk | Issue 08/2016

Transcript of Firestop plug CFS-PL - Hilti Sweden€¦ · stèm Te Installed by: ... Hilti Clean-Tec criteria...

Page 1: Firestop plug CFS-PL - Hilti Sweden€¦ · stèm Te Installed by: ... Hilti Clean-Tec criteria Material safety data sheet: Protection against noise: ... 8/27/2015 1:42:56 PM ...

Ordering description Outside diameter Package contents Sales pack quantity

Item number

CFS-PL 107 107 mm 1x Firestop plug CFS-PL 107 1 pc 2059530CFS-PL 132 132 mm 1x Firestop plug CFS-PL 132 4 pc 2059531CFS-PL 158 158 mm 1x Firestop plug CFS-PL 158 2 pc 2059532CFS-PL 202 202 mm 1x Firestop plug CFS-PL 202 2 pc 2059533

Firestop plug CFS-PL

Technical dataBase materials Concrete, Masonry, Drywall

Acoustics performance Test report available

Tested in accordance with EN 1366-3

Repenetration Possible

Reaction to fire class (EN 13501-1)

E

Application temperature range 5 - 40 °C

Temperature resistance range -15 - 60 °C

Can be painted Yes

Shelf life1) Not relevant

Chemical basis PU1) at 77 °F / 25 °C and 50% relative humidity; from date of manufacture

Applications■ Temporary or permanent sealing around cables and cable

bundles in wall and floor openings■ Cables and cable bundles

Advantages■ Easy to install, no electric tools required■ Very easy maintenance and retrofitting of cables■ Economical installation as the plug is pre-cured and

ready-to-use■ Painting of cables with firestop coating is not required■ Ideal for the temporary closing of empty core holes

Scan this code to findout more:

hilti.co.uk/ r26207

1

Firestop plug kit

hilti.co.uk | Issue 08/2016

Page 2: Firestop plug CFS-PL - Hilti Sweden€¦ · stèm Te Installed by: ... Hilti Clean-Tec criteria Material safety data sheet: Protection against noise: ... 8/27/2015 1:42:56 PM ...

Ordering description Package contents Sales pack quantity

Item number

CFS-FIL 1x Firestop filler mastic CFS-FIL 1 pc 2052899

Firestop filler mastic CFS-FIL

Technical dataVolume per unit 310 ml

Approx. curing time1) 4mm/3 days

Re-penetration Not possible

Application temperature range 5 - 40 °C

Temperature resistance range -20 - 60 °C

Can be painted Yes

Shelf life2) 12 months

Chemical basis Water-based acrylic dispersion

LEED VOC 9 g/l

Colour Red1) at 75 °F / 24 °C, 50% relative humidity 2) at 77 °F / 25 °C and 50% relative humidity; from date of manufacture

Applications■ For use with CFS-BL firestop block ■ For use with CFS-PL firestop plug

Advantages■ Fits the CFS-DISP dispenser ■ Easy to work with and fast cleanup■ Water-based

Ordering description Package contents Sales pack quantity

Item number

CFS-P BA 1x Firestop putty bandage CFS-B PA 5 mm 1 pc 2062876

Firestop putty bandage CFS-B PA

Applications■ For use with CFS-PL firestop plug ■ for specific cable configurations, to achieve EI 120

Advantages■ East to cut ■ Self-adhesive

Scan this code to findout more:

hilti.co.uk/ r68870

Scan this code to findout more:

hilti.co.uk/ r115931

2

Firestop plug kit

Issue 08/2016 | hilti.co.uk

Page 3: Firestop plug CFS-PL - Hilti Sweden€¦ · stèm Te Installed by: ... Hilti Clean-Tec criteria Material safety data sheet: Protection against noise: ... 8/27/2015 1:42:56 PM ...

Main approved applications

Partition Flexible wall Rigid wall Rigid floorBase material thickness (tE) ≥ 100 mm ≥ 100 mm ≥ 150 mmOpening diameter < 202 mm (largest available plug)Fixing to wall / floor Friction fit within opening. Framing of opening not requiredGap filler CFS-FILPenetration Single cable and cable bundle, metal and plastic conduits, conduit bundlesBeading Square gypsum board size 200 mm + Ø plug on each side to reach

150 mm total seal depthNone

*All sheathed cable types currently and commonly used in building practice in Europe (e.g. power, control, signal, telecommunication, data optical fibre cables)

Note: Beading required to reach 150 mm penetration depth with walls of less than 150 mm. Square plates made of gypsum or calcium silicate board size 200 mm plus plug Ø (wA = 100 mm), installed around the opening in the necessary number of layers. On both sides of the wall.

Excerpt of ETA document. Check the exact field of application for each Penetration (type, diameter) in the ETA 13/0125 document.

Penetration: Cables* Cable Ø mm Flexible wall Rigid wall Rigid floor

All sheathed cables ≤ 21 EI 120

Non-sheathed cables (wires) ≤ 24 EI 60 or E 120 EI 30 or EI 120

Tied cable bundle Ø ≤ 100 mm ≤ 21 EI 120

All sheathed cables ≤ 50 EI 90 (EI 120 with CFS-P BA) E 120

All sheathed cables ≤ 80 EI 90 or E 120

Penetration: Conduits Pipe Ø mm

Plastic conduits and tubes ≤ 16 EI 120 U/U

Steel conduits and tubes ≤ 16 EI 120 C/U

Flexible conduits PO with or without cables 16 - 40

EI 120 U/UFlexible conduits PVC with or without cables 16 - 32

Rigid conduits PO / PVC with or without cables 16 - 40

Bundles (Ø ≤ 100 mm) of rigid and flexible conduits with or without cables ≤ 20

No penetration

Blank seal - EI 120

General information

3

Firestop plug kit

hilti.co.uk | Issue 08/2016

Page 4: Firestop plug CFS-PL - Hilti Sweden€¦ · stèm Te Installed by: ... Hilti Clean-Tec criteria Material safety data sheet: Protection against noise: ... 8/27/2015 1:42:56 PM ...

General instructions for use

Cable / conduitØ (mm)

Maximum number of cables / conduits

CFS-PL 107 CFS-PL 132 CFS-PL 158 CFS-PL 202

3.0 566 861 1233 20044.0 318 484 694 11275.0 204 310 444 7318.0 80 121 173 2829.0 63 96 137 22315.0 23 34 49 8020.0 3 5 8 15 20 mm to seal edge and

to other penetrations for conduits Ø > 16 mm

30.0 1 3 5 1040.0 1 1 3 7

Fire Rated Assembly / Assemblage Homolugué

Product: Produt:

Location: Endroit:

System #: Système #: Tel:

Installed by: Installation Date: Date d’installation:

Repenetrated by: Date:

Fire Rated Assembly / Assemblage Homolugué

Product: Produt:

Location: Endroit:

System #: Système #: Tel:

Installed by: Installation Date: Date d’installation:

Repenetrated by: Date:

Fire Rated Assembly / Assemblage Homolugué

Product: Produt:

Location: Endroit:

System #: Système #: Tel:

Installed by: Installation Date: Date d’installation:

Repenetrated by: Date:

Maximum 60% visual fill

Maximum number of cables or conduits per opening

4

Firestop plug kit

Issue 08/2016 | hilti.co.uk

Page 5: Firestop plug CFS-PL - Hilti Sweden€¦ · stèm Te Installed by: ... Hilti Clean-Tec criteria Material safety data sheet: Protection against noise: ... 8/27/2015 1:42:56 PM ...

Characteristics of CFS-PL

Characteristics Assessment of characteristics Norm, standard, testHealth and the environmentDangerous substances

Clean-TecBelow any respective occupational exposurelimits as far as such limits exist (compared withthe list of dangerous substances of the European Commission).

Hilti Clean-Tec criteriaMaterial safety data sheet

Protection against noiseAirborne sound insulation

Double plug CFS-PL=Rw (C; Ctr) = 54 (-1; –7) dB EN ISO 140-3

Thermal properties Thermal conductivity λ = 0.089 W/mK andthermal resistance R = 0.563 m2K/W

EN 12667

Electrical properties Electrical volume resistivity:2.17E+9 (± 0.5) Ω cmElectrical surface resistivity:49.6E+9 (± 10 ) Ω

DIN IEC 60093 (VDE 0303 Part 30):1993-12

Durability and serviceability Category Y1 (Products intended for use at temperatures between -5 °C and +70 °C with exposureto UV but without exposure to rain).

EOTA Technical Report TR 024ETAG 026-2

Reaction to fire Class E EN 13501-1