FIREGUARD 20, 60, 90, 180 - Won-Door specs... · An electromagnetic locking clutch is added to the...

36
FIREGUARD 20, 60, 90, 180 Standard Color Optional Colors Available at Additional Cost FIREGUARD COLOR CHART #55 Platinum #63 Sandalwood #77 Almond #64 Colonial Blue #62 Nile #33 Toast #53 Rose

Transcript of FIREGUARD 20, 60, 90, 180 - Won-Door specs... · An electromagnetic locking clutch is added to the...

FIREGUARD 20, 60, 90, 180Standard Color

Optional Colors Available at Additional Cost

FIREGUARD COLOR CHART

#55 Platinum

#63 Sandalwood

#77 Almond #64 Colonial Blue

#62 Nile

#33 Toast

#53 Rose

FIRE DOOR SELECTION GUIDEThis guide will assist the specifier in selecting the most appropriate assembly and related options based on:1. Fire rating required.2. Special requirements for access control/security.FIRE RATINGS:1. Won-Door FireGuard is listed as a fire-rated door (NFPA 252) with ratings up to 3 hours.

Door Model Fire RatingWon-Door FireGuard 20 20 MinutesWon-Door FireGuard 60 1 HourWon-Door FireGuard 90 1 1/2 Hours

Won-Door FireGuard 180 3 Hours2. Won-Door FireGuard is also listed as a 450° temperature rise door (NFPA 252) with a 1 1/2 hour rating for use

in stairwell enclosure applicationsDoor Model Fire Rating

Won-Door FireGuard 90TR 1 1/2 Hour Temperature Rise3. Won-Door FireGuard is also listed as a moveable fire wall (ASTM E-119) in straight, single parting

configurations.Door Model Fire Rating

Won-Door FireGuard MFWI 1 HourWon-Door FireGuard MFWII 2 Hours

SPECIAL REQUIREMENTS (OPTIONAL):1. Exit Hardware may be specified at multiple locations along the door assembly to allow exiting from a space

where a single exit device would not be sufficient. (see details on page 35)2. Vision Panels may be specified to meet code requirements for smoke barriers. (see details on page 33)3. Access Control Options. Where required, the Won-Door FireGuard assembly can be equipped to provide two

levels of access control. (Note: Access Control is disabled when the door is in fire mode.):a. Level 1 Access Control – Disabled Exit Hardware

When the door is in the normal supervisory mode, the door’s exit hardware is programmed to be inactive (it isactive in emergency mode only). In addition, the closing system will seek the closed position. If an attempt ismade to force the door off its closed limit, it immediately re-closes and sounds an alarm. The alarm can soundlocally or remotely. When the door re-closes, the clutch engages for approximately 5 minutes to resist furtherattempts to force it open. A key switch or other access device is required to open/close the door, thereforespecifiers must determine the type and location of the device(s) and specify the required boxes, conduit andwiring in the electrical section of the specification. (See pages 28, 29)For increased security, the standard sliding jamb and “quick release” jamb stops can be replaced with a heavy-gauge steel sliding jamb and rigid Z-shaped fixed jamb stops. An additional 25 mm of pocket depth is required.

b. Level 2 Access Control – Electromagnetic Locking DeviceAn electromagnetic locking clutch is added to the closing system and provides 182 kg to 227 kg of resistance toopening. A key switch or other access device is required to open/close the door, therefore specifiers mustdetermine the type and location of the device(s) and specify the required boxes, conduit and wiring in theelectrical section of the specification. (See pages 28, 29)

USING OTHER TYPES OF ACCESS DEVICES (OPTIONAL)In the access control applications, other types of operating devices can be added including numeric keypads, pushbutton and infrared operating devices, providing they are capable of receiving a low voltage signal via stranded 18-gauge wire in conduit to the Won-Door automatic closing system control box. Additional operating device contactscan be added as required. These access devices should be defined, provided, and installed under the respectivespecification section.ADVANCED SYNCHRONIZED LOGISTICS (ASL) (OPTIONAL)The REMOTE CONTROL AND STATUS PC STATION will monitor and control up to 120 FireGuard assembliesand consists of a dedicated personal computer and customized software designed to indicate door status informationand to provide remote operation of the doors. (See page 30)

SPECIFICATIONS: PART 1 – GENERAL1.01 SUMMARY OF WORKA. Division 0 and Division 1, as indexed, apply to this section.B. Furnish and install all horizontal sliding, accordion-type fire doors shown on the drawings and

specified herein.

1.02 RELATED SECTIONSA. All headers, support structures, surrounding insulation, jambs, storage pockets, pocket doors, access

doors, blocking and trim shall be furnished and installed by other sections.B. All electrical wire, wiring, conduit and electrical boxes shall be furnished and installed by electrical

section.C. [All track, soffit, chain guide and wall mounted striker posts shall be painted by Section 09900. Color

shall be selected by the architect.]D. [(Note: The following paragraph should be included when 2.04 Option P, ASL-Advanced

Synchronized Logistics, is specified) Regarding 2.04 Option P – The Microsoft Windows based PCshall be supplied by the owner. Wiring from the computer to the doors shall be furnished and installedby the electrical section and shall consist of one (1) USOC RJ14-6POS 4 wire jack per line, up to eight(8) lines, installed near the computer. From the computer, each line shall daisy chain up to 32 doorstogether with one (1) USOC RJ14-6POS 4 wire jack installed on the back wall of the storage pocketfor each door. Wire used in the daisy chain shall be a minimum of CAT 3 twisted 2 pair cable. Eachline shall be 1219 meters or less in length.]

E. [(Note: The following paragraph should be included when 2.04 Option J, individual LCD door statusdisplay panel, is specified) Regarding 2.04 Option J– One (1) USOC RJ14-6POS 4 wire jack shall besupplied at the back of the storage pocket and shall be tied to the 4 square junction box adjacent to thedoor with CAT 3 twisted 2 pair cable. The junction box, RJ14 jack and wire shall be furnished andinstalled by the electrical section. Termination to the LCD panel shall be by punch down block andshall be by the electrical section as per the manufacturer’s instructions. If the LCD panel is suppliedwith 2.04 Option J, then the CAT 3 twisted 2 pair cable can be terminated in parallel with the ASLwiring in the same USOC RJ14-6POS 4 wire jack.]

1.03 QUALITY ASSURANCEA. Installation shall be performed by factory trained and certified installers with a minimum of three

years experience installing accordion-type fire doors.B. Fire doors shall be tested in accordance with China Test standard GB14102-2005, listed by

Underwriters Laboratories, and FM global for ratings as indicated, when tested in accordance with therequirements of UL 10B and ASTM E-2074. Fire doors shall comply with the requirements of theInternational Building Code Congress and NFPA 5000.

C. Automatic closing system shall be tested in accordance with China Test standard GB 14102-2005 andlisted by Underwriters Laboratories and FM Global in accordance with the requirements of UL 864and be intended for use with assembly in compliance with NFPA 80, Chapter 9, Section 9.4.2.1.

D. Fire doors used for smoke and draft control shall bear the “S” mark on the fire door label and shall betested in compliance with China Test standard GB14102.

E. Fire doors used at the point of access to an elevator shall bear the “S” mark on the fire door label shallbe tested in compliance with China Test standard GB14102.

Brackets [ ] indicate specifier’s optionSpecifier’sNote

Specifications FireGuard 20, 60, 90, 180SECTION 08 35 13.26 – Horizontal Sliding, Accordion-Type Fire Doors

Specifications FireGuard 20, 60, 90, 180SECTION 08 35 13.23 – Horizontal Sliding, Accordion-Type Fire Doors

1.04 SUBMITTALSA. Refer to Section 01300 - Shop Drawings and Submittals.B. Indicate required stacking depth, storage pocket width and height of header above finished floor. Show

installation details, layout, and electrical requirements.

1.05 DELIVERY, STORAGE, AND HANDLINGA. Deliver to the job site in manufacturer's original, unopened package.

1.06 COORDINATION BY GENERAL CONTRACTORA. Coordinate the efforts of the various trades affected by the work of this section. Assure accurate

installation of header, jamb, and trim. Provide field dimensions for fabrication. Supervise unloadingand handling of materials.

B. Permanent power shall be in-place and ready for final connection when fire doors are erected. Assureaccess to and proper clearance for motor operators.

C. After testing the fire alarm system, automatic-closing fire doors shall be re-set to the originalpositions.

D. Store boxes flat (not more than three high) in a dry area and protect from elements that may damagematerials. Replace damaged materials at no cost to the owner.

1.07 WARRANTYA. Materials and installation shall be warranted against defects in workmanship for a period of one (1)

year from the date of substantial completion.B. [A Manufacturers Service Agreement shall cover years 2 thru 5 and include regularly scheduled

testing and inspection of all door functions. The Service Agreement will include [select one: annual,semi-annual, quarterly or monthly] visits to inspect, test and perform all required maintenance. Allservice and maintenance functions are performed by factory-trained service technicians.]

C. [A comprehensive owner training seminar will be conducted by a factory trained service technician.The owner training shall include horizontal sliding, accordion-type fire door operation, care,maintenance, testing and trouble-shooting.]

SPECIFICATIONS: PART 2 – PRODUCTS2.01 MANUFACTURER AND MODELA. Horizontal sliding accordion-type fire doors shall be Won-Door FireGuard model WDFG[select one:

20, 60, 90, or 180] (number designates minutes of fire rating)(China classification code GFYJ-420480-FY3-Cx-S-203) as manufactured by Won-Door Corporation, Salt Lake City, Utah. (Note: Add suffix“S” for smoke and draft OR suffix “E” if door is used at the point of access to an elevator.)

B. Products of other manufacturers demonstrating complete compliance with each of the fire rating andperformance criteria of the product specified will be considered for approval. Minimum proof ofcompliance shall include UL 864 9th edition listing, UL test report and independent testing agencyreport documenting compliance with IBC Section 1008.1.3.3 and NFPA 80, Chapter 9. Writtenrequests for substitutions will be considered by the architect up to ten days prior to the bid date.

C. [No substitutions allowed.]

2.02 FIRE RATINGA. Fire Doors shall be tested in accordance with China Test standard GB 141102-2005 and listed by

Underwriters Laboratory as special purpose fire doors having a fire resistive rating up to three hours inaccordance with the requirements of UL 10B and ASTM E-2074.

Specifications FireGuard 20, 60, 90, 180SECTION 08 35 13.23 – Horizontal Sliding, Accordion-Type Fire Doors

2.03 REMOTE MONITORING AND CONTROL(Note: Remote Monitoring and Control may be specified under 2.04 Option P)A. Fire doors shall be capable of being remotely monitored and controlled by a personal computer (PC).

Information displayed on the computer shall indicate the voltage of the battery, AC line voltage anderror conditions. Status information shall indicate whether the door(s) is closed, open, closing,opening, stopped, blocked or locked. Access using the Fire Exit Hardware shall be indicated as wellas when the door(s) has received a fire signal.

2.04 MATERIALSA. Construction: shall consist of two parallel, accordion-type walls of panels independently suspended

with no floor tracks, pantographs, or interconnections except at the lead-post.B. Panels shall be formed of 24-gauge (.7 mm) enamel coated steel V-grooved for strength and resilience.

Panels shall be connected by full height 24-gauge (.7 mm) enamel coated steel hinges. Panels shall bemodular in design and capable of in-place repair-ability.

C. Suspension System: shall consist of two 14-gauge cold rolled steel (or 3 mm aluminum) tracks on 203mm centers attached to the overhead structural support. Each lead post shall be suspended by an 8-wheel ball bearing trolley. Each panel shall be suspended by a steel hanger pin and a ball bearingroller.

D. Lead-posts: shall be of 24-gauge (.7 mm) cold rolled steel and shall be connected by specially formedsteel panels. An internally mounted stabilizer bar shall keep lead-posts plumb and in proper alignmentduring operation and insure a tight fitting closure.

E. Perimeter Seals: shall consist of continuous extruded vinyl sweeps attached to the top and bottom ofthe fire door to form a smoke and draft seal.

F. Hanging weight shall be 27 kg/m2.G. Automatic Closing System shall consist of the following:

1. Microprocessor based Electronic Control box with these features:a. Ability to monitor dual power sources continually for peak performance including:

i. Detect a missing battery, bad battery, or low battery condition.ii. Detect if the charging circuit is bad.iii. Detect fuse failures.iv. Detect high or low AC conditions.

b. Ability to monitor the health of the drive train including:i. Direction errors, obstruction errors, hindrance errors, and position errors.ii. Active daily path checks, by actually closing and opening to assure a clear path and proper

operation.iii. Ability to monitor a passive input such as an infrared light beam to assure the closing path

is clear.c. Ability to monitor inputs including:

i. Sticky door block, exit hardware, patron hardware, and key switches.ii. Key switch mis-wires where key open and key close are both on simultaneously.

d. Ability to self-monitor the health of:i. Internal volatile and non-volatile memory.ii. Proper operation of firmware.

Brackets [ ] indicate specifier’s optionSpecifier’sNote

Specifications FireGuard 20, 60, 90, 180SECTION 08 35 13.23 – Horizontal Sliding, Accordion-Type Fire Doors

e. Ability to run a “watch dog” monitoring circuit which will force a software restart in the eventthe software hangs, including the ability to track the number of resets that occur for diagnosticpurposes.

f. Ability to record the number of times the door has closed, opened, lost communication withexternal microprocessors, and the number of times the controller has been reset manually.

g. Ability to monitor ambient temperature and lockout the operating devices once theenvironment at the door becomes untenable.

h. Ability to enter a security mode to help control access through the door including:i. The ability to automatically re-close and secure itself after a legitimate patron access has

occurred.ii. The ability to unlock and revert to a fire door in a fire alarm condition, including the

ability to re-lock automatically after the fire alarm condition has cleared.i. Ability to withstand voltages up to 120 volts AC on the fire alarm input circuit without

damage including the ability to indicate that the alarm circuit has not been wired as a drycontact, “no voltage” circuit when errant voltages are applied to the circuit.

j. Ability to communicate with other microprocessors on the system via an internal bus system,including but not limited to microprocessors on the motor drive, in the leading edge of thedoor, and on a wall mounted display panel adjacent to the door.

k. Ability to indicate trouble or supervised information both locally and at a remote location.2. Motor Operator Assembly including:

a. A DC gear-motor, drive sprocket, clutch, and position sensors. The motor shall drive the firedoor by means of a chain attached to a stabilizer bar trolley each time the door operatesincluding the initial closing cycle.

3. A door control momentary rocker switch shall be mounted on one side of the door near the leadpost and shall have the following functions: Pressing the upper portion of the switch shall closethe door and/or clear fault conditions. Pressing the lower portion of the switch shall open the doorand/or temporarily mute the local horn. For doors using wall mounted key switches, 2.04 OptionI, a color coordinated cover plate shall be provided to fill the hole left when the rocker switch isremoved or not used.

4. The control box shall be equipped with a service switch that performs the following functions:a. When the switch is off with AC power present, the controller shall emit an audible coded

sound indicating the system is out of service. In this mode all normal functions shall ceaseincluding motor and communications.

b. When the switch is off and AC power is not present, the controller shall enter a sleep modeduring which the system shall use the battery to monitor the AC line for power but do nothingelse.

c. When the switch is moved from the off position to the on position, the controller shall enter acalibrate mode where it emits a coded audible alert indicating that the door needs to be closedto complete the calibration sequence. As soon as the door is closed, the controller shallautomatically stop the audible alert, and resume all normal functions and monitoring.

5. Leading Edge Obstruction Detector:

Brackets [ ] indicate specifier’s optionSpecifier’sNote

Specifications FireGuard 20, 60, 90, 180SECTION 08 35 13.23 – Horizontal Sliding, Accordion-Type Fire Doors

a. Shall be pressure sensitive such that each contact with an obstruction shall cause the door tostop, reverse enough to remove pressure on the leading edge, pause, and then re-close when inan alarm condition. The leading edge obstruction detector shall be fully functional at all times,including during the initial closing cycle.

b. Constant pressure to the leading edge in the direction of opening shall, while the door isopening under motor power, continue to open under motor power until the leading edge isreleased. This is termed motor assisted opening.

c. Constant pressure to the leading edge while not under motor power shall prevent motoroperation and allow the door to be opened manually.

6. Exit Hardware shall be located on both sides of each fire door.a. In emergency mode, a slight pressure on the hardware will cause the door to open a minimum

of 813 mm, pause for 3 seconds, and then automatically close.b. The open distance shall be field programmable, up to the entire opening width, if the local

authority requires an opening larger than 813 mm.c. The pause before re-close shall be field programmable, up to 30 seconds, if the local authority

requires a longer pause time.d. The exit hardware shall have the ability when not in the emergency (fire) mode or the security

(lock) mode to be used to open the door and move it back into the storage pocket.e. The exit hardware shall be field programmable to provide access control. When programmed,

the exit hardware shall not respond when pressed until activated by signal from smokedetector or fire alarm.

7. Suffix “E” doors shall include the following extras; track seals, anti-sway brackets every five feetor less across the opening, modified lead post trolleys and foil tape between the panels and thesmoke liner.

OPTIONSH. [Vision Panel shall consist of frame and clear glass assembly with listings from Underwriters

Laboratory up to 1 1/2 hours]. (Note: required only in smoke barriers in Group I occupancies.)I. [A Key switch module shall be provided.] (Note: required for doors equipped with Access Control

devices.)J. [An individual LCD door status display panel shall be provided adjacent to the door to indicate in the

English language the status of the door, i.e. door position and trouble conditions. It shall have a portthat allows easy access to a diagnostic tool for the purposes of field programming the door tocustomized settings. When used with the ASL system, it shall be compatible and not disrupt the ASLcommunications] (Note: Electrical requirements for the LCD panel can be found in 1.02 Option E)

K. [Air Pressure Resistance. When the differential pressure on the two sides of the fire resistant andsmoke resistant shutter is 20 Pa, the amount of smoke leaked through when it is in a standard state (20deg C) shall not be greater than 0.2 m3 (m2*min).]

L. [An infrared light beam shall be provided on non-curved doors to monitor the opening path. In theevent that an object is placed in the path of the door for more than 4 minutes, the beam shall cause thedoor to sound an alarm indicating a path obstruction.]

Brackets [ ] indicate specifier’s optionSpecifier’sNote Brackets [ ] indicate specifier’s optionSpecifier’sNote

Specifications FireGuard 20, 60, 90, 180SECTION 08 35 13.23 – Horizontal Sliding, Accordion-Type Fire Doors

M. [Acoustic Insulation: Interior surfaces of both walls shall be completely covered with a continuousblanket of .454 kg density foil-backed fiberglass fastened in place with steel spring-clips]. (Note:When specifying insulated doors, contact the manufacturer for pocket depths, hanging weight and sizelimitations.)

OPTIONS - ACCESS CONTROL/MONITORING(Note: Level 1 and Level 2 Access Control options are independent systems and may not be specified inconjunction with each other)N. [Level 1 Access Control. The Exit Hardware shall not respond when pressed until activated by signal

from smoke detector or fire alarm. Upgrades to the fire door for this level of access control shallinclude a heavy-gauge steel sliding jamb and rigid jamb stops.] (Note: at least one key-switchrequired.)

O. [Level 2 Access Control. An Electromagnetic lock shall be added to the motor operator assembly toprovide 181-226 kg of resistance to manual opening until activated by a signal from fire alarm. Whenthe fire alarm is cleared, the door returns to normal access control. Upgrades to the fire door for thislevel of access control shall include a heavy-gauge steel sliding jamb, rigid jamb stops and 10-gaugesteel vertical reinforcement to the lead post.] (Note: at least one key-switch required.)

P. [Advanced Synchronized Logistics- an integrated building asset management system (ASL), asmanufactured by Won-Door Corporation, shall be furnished and installed to continuously control andmonitor the status of up to 256 doors. ASL shall consist of a Multi-port On-site Monitor box, a serialcable, a 12-volt power supply and software on CD-ROM media. Installation, jacks, a computer (PC)and wiring shall be provided by others.] (Note: Electrical requirements for the ASL system can befound in 1.02 Option D)

2.05 COLORA. Color shall be manufacturer’s standard #55 Platinum.B. [Color shall be selected from manufacturer's optional colors at additional cost.]C. [Color shall be selected by architect and field painted by others.]

SPECIFICATIONS: PART 3 – EXECUTION3.01 PREPARATION BY GENERAL CONTRACTORA. Openings shall be to the dimensions specified, plumb and level.B. Headers shall be parallel with the finished floor within ±3 mm tolerance over the entire length of the

opening.C. Manufacturer shall make available to the general contractor a DVD showing door opening preparation.

3.02 INSPECTIONA. Inspect openings prepared for fire doors and surrounding conditions. Immediately notify the architect,

in writing, of any unacceptable conditions.

3.03 INSTALLATIONA. Install fire doors in accordance with manufacturer's instructions for clearance and fastenings.B. Adjust for smooth, quiet operation. Verify that all operations are functional and meet the requirements

of applicable codes and regulations.

Specifications FireGuard 20, 60, 90, 180SECTION 08 35 13.23 – Horizontal Sliding, Accordion-Type Fire Doors

Specifications FireGuard 20, 60, 90, 180SECTION 08 35 13.23 – Horizontal Sliding, Accordion-Type Fire Doors

C. Upon completion of the installation, general contractor shall protect fire doors from damage and shallreplace or repair subsequent damage so that doors are acceptable to the architect at no additional costto the owner.

D. Installation shall be performed by factory trained and certified installers with a minimum of threeyears experience installing accordion-type fire doors.

3.04 DEMONSTRATIONA. Manufacturer’s onsite field technician shall demonstrate the operation of the doors to the General

Contractor. A DVD outlining the operation, scheduled maintenance, basic troubleshooting and care ofthe door system shall be provided to the owner by the door manufacturer.

Copyright © 2011 by Won-Door Corporation, all rights reserved.END OF SECTION

Brackets [ ] indicate specifier’s optionSpecifier’sNote

This page intentionally left blank.

STANDARD HEAD w/POCKET MOUNTED MOTORCAD FILE: FGHD1

1. 12 mm dia. threaded rod with nuts and washers by others. (457 mm O.C. in opening, 305 mm O.C. in stackarea.)

2. 1 layer 19 mm x 438 mm continuous plywood and 2 layers 19 mm x 381 mm continuous plywood. Staggerjoints, glue and screw together @ 610 mm O.C. with 2 #7 x 41 mm screws. [OR] 12 mm X 457 mm steelplate.

3. Provide rated construction on each side corresponding to rating required for opening by others. (Note: 1hour condition shown. To view additional rated conditions, visit our website @ www.wondoor.com)

4. Two layers 16 mm x 457 mm x continuous type ”X” gypsum board and three layers 12 mm x 92 mm type“X” gypsum board terminating 305 mm into the pocket. All gypsum to be furnished, installed, finished,and field painted by others.

5. Motor operator unit. (Mounted at back of pocket. (See page 14)6. Structural support or anchorage by others. Structural support is not limited to concrete deck.7. Minimum dimension required to meet U.L. compliance. The dimension may be increased to further recess

the head condition if required.8. L-shaped trim piece with pre-finished white color to match track by Won-Door. (Provides transition from

track to gypsum soffit.)

Brackets [ ] indicate specifier’s optionSpecifier’sNote

STRAIGHT DOOR – HEAD DETAIL

Brackets [ ] indicate specifier’s optionSpecifier’sNote

STANDARD HEAD w/POCKET MOUNTED MOTORCAD FILE: FGHD1METRIC

1. Provide rated construction on each side corresponding to rating required for opening by others. (Note: 1hour condition shown. To view additional rated conditions, visit our website @ www.wondoor.com)

2. Sliding jamb assembly.3. Exit Hardware.4. Blocking by others.5. Sliding jamb stops mounted 127 mm back from face of pocket.6. Non-rated pocket cover door by others. (See page 26, 27)7. Door bumper by others required when spring loaded hinge is not used by others. (See page 27)8. Maintain 229 mm clearance on each side of the centerline of the door.9. Fire rated bulkhead above, drop or flush with ceiling.10. Striker by Won-Door recessed into rated construction and caulked by others.11. Center striker pocket on door centerline.

STRAIGHT DOOR – PLAN VIEWSINGLE PARTING

SINGLE PARTINGCAD FILE: FGPL1METRIC

Brackets [ ] indicate specifier’s option*To determine pocket depth, see the Instructions on page 17 and Pocket Depth Calculation Chart on page 18.Specifier’s

Note

BI-PARTINGCAD FILE: FGPL2METRIC

1. Provide rated construction on each side corresponding to rating required for opening by others. (Note: 1hour condition shown. To view additional rated conditions, visit our website @ www.wondoor.com)

2. Sliding jamb assembly.3. Exit Hardware.4. Blocking by others.5. Sliding jamb stops mounted 127 mm back from face of pocket.6. Non-rated pocket cover door by others. (See page 26, 27)7. Door bumper by others. Bumper required when spring loaded hinge is not used. (See page 27)8. Maintain 229 mm clearance on each side of the centerline of the door.9. Fire rated bulkhead above, drop or flush with ceiling.

STRAIGHT DOOR – PLAN VIEWBI-PARTING

Brackets [ ] indicate specifier’s option*To determine pocket depth, see the Instructions on page 17 and Pocket Depth Calculation Chart on page 18.Specifier’s

Note

STANDARD POCKET MOUNTED MOTORCAD FILE: FGELEV1METRIC

1. Top of door track. (Fabrication height.)2. Ceiling line.3. Motor operator assembly.4. Folding fire door by Won‐Door.5. Storage pocket.6. Electronic control box by Won‐Door.7. [Optional keyswitch by Won‐Door. (See page 31.]8. Fire exit hardware. (Allows passage through the door when closed.)9. Two 102 mm x 102 mm junction boxes surface mounted side by side on back wall of pocket 305 mm

above finished floor for required electrical connections.

STRAIGHT DOOR – ELEVATIONSIDE VIEW

Brackets [ ] indicate specifier’s optionSpecifier’sNote

1. Fabrication height/field dimension height taken from top of track to top of finished floor.2. Finished floor. (Carpet, tile, etc.)3. Sub floor. (Concrete, etc.)

Door Profile Widths:• Stacked Width: 406 mm• Extended Width: 292 mm

STRAIGHT DOOR – ELEVATIONFRONT VIEW

STRAIGHT DOORCAD FILE: FGELEV4METRIC

1. 12 mm threaded rods, Steel Pan Header and track assembly by Won-Door.2. Provide rated construction on each side corresponding to rating required for opening by others. (Note: 1

hour condition shown. To view additional rated conditions, visit our website @ www.wondoor.com)3. Motor operator unit. (Mounted at back of pocket. (See page 14)4. Minimum dimension required to meet U.L. compliance. The dimension may be increased to further recess

the head condition if required.

STRAIGHT DOOR – HEAD DETAILSTEEL PAN HEADER

STEEL PAN HEAD w/POCKET MOUNTED MOTORCAD FILE: SPHFGHD1METRIC

The Steel Pan Header System may be specified for straight doors less than 9144 mm wide and 3048 tall.Specifier’sNote

From: To: Single Bi-Part2236 2464 940 10672465 2692 965 10922693 2921 1016 1143

Clear Opening Width Min. Pocket Depth

From: To: Single Bi-Part2236 2464 940 10672465 2692 965 10922693 2921 1016 1143

Clear Opening Width Min. Pocket Depth

Single Parting Straight DoorsThe term CLEAR OPENING WIDTH on the Pocket Depth Calculation Chart refers to the distance from the frontof the storage pocket to face of the striker.To determine the pocket depth requirement of a door:

1. Determine the door’s CLEAR OPENING WIDTH2. Find the appropriate range for that width (From-To columns)3. Refer to the “Single” (for single parting) column.4. Consult the Options Affecting Pocket Depth section below the chart to determine how optionalequipment affects stack requirements.

Example below: Pocket depth for FireGuard 60 single parting door w/ 2540 mm clear opening (in the range from2489 mm to 2692 mm). Minimum pocket depth = 965 mm.

Bi Parting Straight DoorsBi‐part doors require two storage pockets. Instead of using the total CLEAR OPENING WIDTH when referring tothe stack chart, use 1/2 of the CLEAR OPENING WIDTH (which is the distance from the front of storage pocket onone side to the center of the door opening), then follow the same instructions listed in “single parting” (above) todetermine the pocket depth requirement. For bi‐parting doors, a motor operator can be placed in each pocket toincrease the maximum door size for a standard pocket mounted motor. For unequal bi‐parting doors, consult thefactory.Example below: Pocket depth for FireGuard 60 bi‐parting door with 4775 mm clear opening width. Look up 2386mm on stack chart (1/2 of 4775). Min. pocket depth = 1067 mm for each pocket.

List of Options Affecting Pocket DepthOnce you have determined the appropriate depth requirements using the chart on the next page, consult the OptionsAffecting Pocket Depth section below the chart. Optional equipment such as the access control sliding jambs,vision panels, and multiple exit hardware will also affect pocket depth as will pocket cover doors in excess of 51mm thick.

POCKET DEPTH CHART INSTRUCTIONS

*For bi‐parting doors: Use1/2 the clear opening width.Minimum Pocket Depth isaffected by door height.The charts on this pageshow Minimum PocketDepths for doors 3048 mmin height or less.Minimum Pocket Depths fortaller doors are shown

below.For doors over 3048 mm inheight, if the MinimumPocket Depth shown on thecharts for the required widthis less than that shownabove use the appropriatevalue from above instead. Ifit is not, use the valueshown on the charts. Fordoors over 4572 mm inheight, the minimum pocketwidth of 508 mm isrequired.For doors over 6096 mm inheight, please consult thefactory. The above chart isfor straight door openingsless than 183 m2. Forstraight doors openings

greater than 183 m2, please consult the factory.

OPTIONS AFFECTING POCKET DEPTH:Access Control sliding jamb: Add 25 mm to pocket depth.Pocket Cover Door: Above charts allow for 51 mm thick cover door. Add appropriate amount if cover door andfinish materials are thicker than 51 mm. (See page 26, 27)Vision Panel: Add 152 mm to pocket depth.Additional exit hardware: Add 25 mm to pocket depth for each exit device. Maximum of 3 sets of exit hardwareper door leaf.FireGuard SE for doors used at the point of access to an elevator: Minimum stack depth is 813 mm.

STRAIGHT DOOR – POCKET DEPTH CALCULATION CHARTFireGuard 20, 60, 90, 180

Height Single Bi-Part3048 940 9913962 1118 11684877 1295 1346

From: To:0 1295 736 863

1296 1529 762 8891530 1762 812 9391763 1996 863 9651997 2230 889 10162231 2463 939 10662464 2697 965 10922698 2931 1016 11432932 3164 1041 11683165 3398 1092 12193399 3632 1117 12443633 3865 1168 12953866 4099 1193 13204100 4333 1244 13714334 4566 1295 14224567 4800 1320 14474801 5034 1371 14985035 5267 1397 15245268 5501 1447 15745502 5735 1473 16005736 5969 1524 16515970 6202 1549 16766203 6436 1600 17276437 6670 1625 17786671 6903 1676 18036904 7137 1727 18547138 7371 1752 18797372 7604 1803 19307605 7838 1828 19557839 8072 1879 20068073 8305 1905 20328306 8539 1955 20828540 8773 1981 21088774 9006 2032 21599007 9240 2082 2209

Clear Opening Width SingleParting

Bi-Parting From: To:

9241 9474 2108 22359475 9707 2184 23119708 9941 2235 23629942 10175 2260 2387

10176 10408 2311 243810409 10642 2336 246310643 10876 2387 251410877 11109 2438 254011110 11343 2463 259011344 11577 2514 264111578 11811 2540 266711812 12044 2590 271712045 12278 2616 274312279 12512 2667 279412513 12745 2692 281912746 12979 2743 287012980 13213 2768 289513214 13446 2819 294613447 13680 2870 299713681 13914 2895 302213915 14147 2946 307314148 14381 2971 309814382 14615 3022 314914616 14848 3048 317514849 15082 3098 322515083 15316 3124 325115317 15549 3175 330215550 15783 3200 335215784 16017 3251 337816018 16250 3302 342916251 16484 3327 345416485 16718 3378 350516719 16951 3403 353016952 17185 3454 358117186 17419 3479 360617420 17653 3530 365717654 17886 3556 368317887 18120 3606 373318121 18354 3657 3784

Clear Opening Width SingleParting

Bi-Parting

CURVED HEAD w/POCKET MOUNTED MOTORCAD FILE: FGHD3METRIC

1. 12 mm dia. threaded rod with nuts and washers by others. (457 mm O.C. in opening, 305 mm O.C. in stackarea.)

2. 3 layers 19 mm x 457 mm continuous plywood and 2 layers 16 mm x 140 mm continuous plywood.Stagger joints, glue and screw together @ 610 mm O.C. with 2 #7 x 41 mm screws.

3. 2 layers 16 mm x 178 mm continuous type “X” gypsum board by others.4. 2 layers 16 mm x 171 mm continuous type “X” gypsum board by others.5. Three layers 12 mm x 92 mm type “X” gypsum board terminating 305 mm into the pocket. All gypsum to

be furnished, installed finished, and field painted by others.6. Motor operator unit. (Mounted at back of pocket. See page 14.)7. Structural support or anchorage by others. (Structural support is not limited to concrete deck.)8. Provide rated construction on each side corresponding to rating required for opening by others. (Note: 1

hour condition shown. To view additional rated conditions, visit our website @ www.wondoor.com)9. Minimum dimension required to meet U.L. compliance. The dimension may be increased to further recess

the head condition if required.10. L‐shaped trim piece with pre‐finished white color to match track by Won‐Door. (Provides transition from

track to gypsum soffit.)

CURVED DOOR – HEAD DETAIL

Brackets [ ] indicate specifier’s optionSpecifier’sNote

Brackets [ ] indicate specifier’s option*To determine pocket depth, see Instructions on page 24 and Pocket Depth Calculation Chart on page 25.Minimum radius is 1524 mm. Standard radii are 1524 mm and 3048 mm. Custom curves greater than 1524mm and multiple curves are available.

Specifier’sNote

1. Provide rated construction on each side corresponding to rating required for opening by others (Note: 1 hourcondition shown. To view additional rated conditions, visit our website @ www.wondoor.com)

2. Sliding jamb assembly.3. Exit Hardware.4. Blocking by others.5. Sliding jamb stops mounted 127 mm back from face of pocket.6. Non-rated pocket cover door by others. (See page 26, 27)7. Door bumper by others. Bumper required when spring loaded hinge is not used. (See page 27)8. Maintain 229 mm clearance on each side of the centerline of the door.9. Fire rated bulkhead above, drop or flush with ceiling.10. Striker by Won-Door recessed into rated construction and caulked by others.

CURVED DOOR – PLAN VIEWSINGLE PARTING

CURVED DOORCAD FILE: FGPL1CURVEDMETRIC

Brackets [ ] indicate specifier’s option*To determine pocket depth, see Instructions on page 24 and Pocket Depth Calculation Chart on page 25.Minimum radius is 1524 mm. Standard radii are 1524 mm and 3048 mm. Custom curves greater than 1524mm and multiple curves are available.

Specifier’sNote

1. Provide rated construction on each side corresponding to rating required for opening by others. (Note: 1hour condition shown. To view additional rated conditions, visit our website @ www.wondoor.com)

2. Sliding jamb assembly.3. Exit Hardware.4. Blocking by others.5. Sliding jamb stops mounted 127 mm back from face of pocket.6. Non-rated pocket cover door by others. (See page 26, 27)7. Door bumper by others. Bumper required when spring loaded hinge is not used. (See page 27)8. Maintain 229 mm clearance on each side of the centerline of the door.9. Fire rated bulkhead above, drop or flush with ceiling.

CURVED DOOR – PLAN VIEWBI-PARTING

CURVED DOORCAD FILE: FGPL2CURVEDMETRIC

1. Centerline of header. (Radius of curved track is determined by measuring the centerline of the header.)2. Centerline of outside track.3. Centerline of inside track.

CURVED DOOR GUIDELINES

1. Standard 1524 mm and 3048 mm radius with custom curves greater than 1524 mm and multiplecurves available.

2. Templates of header radii are supplied to the field upon request.Specifier’sNote

1. Fabrication height/field dimension height taken from top of track to top of finished floor.2. Finished floor. (Carpet, tile, etc.)3. Sub floor. (Concrete, etc.)

Door Profile Widths: Stacked Width: 406 mm Extended Width: 292 mm

CURVED DOOR – ELEVATIONFRONT VIEW

CURVED DOORCAD FILE: FGELEV5

From: To: Single Bi-Part2185 2413 940 10672414 2642 991 11182643 2870 1016 1143

Clear Opening Width Min. Pocket Depth

From: To: Single Bi-Part2185 2413 940 10672414 2642 991 11182643 2870 1016 1143

Clear Opening Width Min. Pocket Depth

Single Parting Curved DoorsThe term CLEAR OPENING WIDTH on the Pocket Depth Calculation Chart refers to the distance from the frontof the storage pocket to face of the striker.To determine the pocket depth requirement of a door:

1. Determine the door’s CLEAR OPENING WIDTH2. Find the appropriate range for that width (From-To columns)3. Refer to the “Single” (for single parting) column.4. Consult the Options Affecting Pocket Depth section below the chart to determine how optionalequipment affects stack requirements.

Example below: Pocket depth for FireGuard 60 single parting door w/ 2540 mm clear opening (in the range from2489 mm to 2692 mm). Minimum pocket depth = 991 mm.

Bi Parting Curved DoorsBi‐part doors require two storage pockets. Instead of using the total CLEAR OPENING WIDTH when referring tothe stack chart, use 1/2 of the CLEAR OPENING WIDTH (which is the distance from the front of storage pocket onone side to the center of the door opening), then follow the same instructions listed in “single parting” (above) todetermine the pocket depth requirement. For bi‐parting doors, a motor operator can be placed in each pocket toincrease the maximum door size for a standard pocket mounted motor. For unequal bi‐parting doors, consult thefactory.Example below: Pocket depth for FireGuard 60 bi‐parting door with 4775 mm clear opening width. Look up 2388mm on stack chart (1/2 of 4775 mm). Min. pocket depth = 1067 mm for each pocket.

List of Options Affecting Pocket DepthOnce you have determined the appropriate depth requirements using the chart on the next page, consult the OptionsAffecting Pocket Depth section below the chart. Optional equipment such as the access control sliding jambs, visionpanels, and multiple exit hardware will also affect pocket depth as will pocket cover doors in excess of 51 mm thick.

POCKET DEPTH CHART INSTRUCTIONS

*For bi‐parting doors: Use1/2 the clear opening width.

Minimum Pocket Depth isaffected by door height.The charts on this pageshow Minimum PocketDepths for doors 3048 mmin height or less.For single parting doors3049 -3961 mm in height,the minimum pocket depthis 940 mm. For bi-partingdoors 3962-6096 mm inheight the minimum pocketdepth is 1168 mm.For doors over 3962 mm in

height, if the MinimumPocket Depth shown on thecharts for the required widthis less than that shownabove use the appropriatevalue from above instead. Ifit is not, use the valueshown on the charts.

For doors over 4572 mm inheight, the minimum pocketwidth of 508 mm isrequired.For doors over 4572 mm inheight, please consult thefactory.

The above chart is forcurved door openings lessthan 152.4 m2. For curveddoors openings greater than

152.4 m2, please consult the factory.

OPTIONS AFFECTING POCKET DEPTH:Access Control sliding jamb: Add 25 mm to pocket depth.Pocket Cover Door: Above charts allow for 51 mm thick cover door. Add appropriate amount if cover door andfinish materials are thicker than 51 mm. (See page 26, 27)Vision Panel: Add 152 mm to pocket depth.Additional exit hardware: Add 25 mm to pocket depth for each exit device. Maximum of 3 sets of exit hardwareper door leaf.FireGuard SE for doors used at the point of access to an elevator: Minimum stack is 813 mm for single partingdoors and 940 mm for bi-parting doors.

CURVED DOOR – POCKET DEPTH CALCULATION CHARTFireGuard 20, 60, 90, 180

From: To:0 1295 736 863

1296 1524 762 8891525 1752 812 9391753 1981 863 9651982 2209 889 10162210 2438 939 10662439 2667 965 10922668 2895 1016 11432896 3124 1041 11683125 3352 1092 12193353 3581 1117 12443582 3810 1168 12953811 4038 1193 13204039 4267 1244 13714268 4495 1295 14224496 4724 1320 14474725 4953 1371 14984954 5181 1397 15245182 5410 1447 15745411 5638 1473 16005639 5867 1524 16515868 6096 1549 16766097 6324 1600 17276325 6553 1625 17786554 6781 1676 18036782 7010 1727 18547011 7239 1752 18797240 7467 1803 19307468 7696 1828 19557697 7924 1879 20067925 8153 1905 20328154 8382 1955 20828383 8610 1981 21088611 8839 2032 21598840 9067 2082 22099068 9296 2108 22359297 9525 2159 2286

Bi-Parting

Clear Opening Width SingleParting From: To:

9526 9753 2184 23119754 9982 2235 23629983 10210 2260 2387

10211 10439 2311 243810440 10668 2336 246310669 10896 2387 251410897 11125 2438 254011126 11353 2463 259011354 11582 2514 264111583 11811 2540 266711812 12039 2590 271712040 12268 2616 274312269 12496 2667 279412497 12725 2692 281912726 12954 2743 287012955 13182 2768 289513183 13411 2819 294613412 13639 2870 299713640 13868 2895 302213869 14097 2946 307314098 14325 2971 309814326 14554 3022 314914555 14782 3048 317514783 15011 3098 322515012 15240 3124 325115241 15468 3175 330215469 15697 3200 335215698 15925 3251 337815926 16154 3302 342916155 16383 3327 345416384 16611 3378 350516612 16840 3403 353016841 17068 3454 358117069 17297 3479 360617298 17526 3530 365717527 17754 3556 368317755 17983 3606 3733

Clear Opening Width SingleParting

Bi-Parting

Pocket cover doors are not required, but may be used to aesthetically conceal Won‐Door Fireguard doors.When properly done, they add to the continuity of the project and provide anonymity to the installation.

Won‐Door Corporation does not manufacture or install pocket cover doors. Therefore, they should bespecified in a separate specification section. Unless specifically required by the Authority HavingJurisdiction, pocket doors need not be fire‐rated, but solid core doors are preferable for reasons ofdurability. The door thickness and covering material is at the discretion of the designer. Many coveringmaterials have been successfully used including: plastic laminates, wood veneers, vinyl, paint, bronze,stainless steel, and marble. If the aggregate thickness of the pocket cover door exceeds 51 mm, however,the additional thickness must be added to the calculation of the pocket depth (see Pocket DepthCalculation Chart on page 17,24.)

Some basic criteria for the successful design of pocket cover doors are listed below:1. Doors must be side hinge swinging and must swing at least 90°. When in the open position,

pocket doors may not encroach on the 457 mm minimum opening width required for the pocket.Designing “notches” on either side of the pocket opening to accommodate the cover doorthickness will prevent this (see Pocket Cover Door Detail on page 27.)

2. Cover doors must be operable with less than 22.68 kg of lateral force. As the Won‐DoorFireGuard door is activated, the leading edge will make contact with the cover door and push itopen. 22.68 kg is the normal operating force required for egress‐type swinging doors and only ifthe cover door is unusually heavy would special considerations need to be taken.

3. When activated, pocket doors should remain in the open position so as not to obstruct the path ofthe Won‐Door FireGuard door when it is closing.

4. Won‐Door recommends specifying either (a) a spring‐action such as the Hager #1257 (withreversed spring action)to hold the cover door open when activated or (b) a continuous hinge suchas a Stanley #314.

a. The reversed spring action in the Hager #1257 butt hinge makes the cover door self-opening rather than self‐closing. Cover doors without spring action hinges may swingback into the operating path of the Won‐Door FireGuard and cause damage or obstructemergency operation.

b. For aesthetic considerations, a continuous hinge is preferable because it does not protrudebeyond the face of the pocket cover door and therefore presents a “hinge less”appearance. When a continuous hinge is used, however, a “bumper” is required. Thebumper prevents the pocket door from swinging back in to the operating path of theWon‐Door FireGuard. Won‐door does not provide bumpers, but its design is shown onpage 27.

5. A magnetic catch not to exceed 13.608 kg can serve to keep the pocket cover doors in the closedposition when the Won‐Door Fireguard door is not in use. Positive latches such as hooks or throwbolts are not permitted because they prevent the Won‐door FireGuard door from pushing thecover door open during operation.

6. A door frame is not required although one may be used. For aesthetic considerations, however, a“frame less” design may be preferable because it leaves only two slight reveals at the door edgesand provides a less noticeable pocket door installation.

POCKET COVER DOOR GUIDELINES

1. Provide fire rated construction corresponding to rating required for opening by others.2. Blocking for sliding jamb stops centered at 127 mm from face of pocket by others.3. Spring action hinge or continuous hinge by others.4. Non-rated pocket cover door by others.5. Magnetic catch (not to exceed 13.608 kg) by others.6. Bumper (mounted on inside of pocket cover door 76 mm above finished floor) by others.

POCKET COVER DOOR DETAIL

Bumpers must be specified when non-spring action hinges are used.Specifier’sNote

POCKET MOUNTED MOTOR OPERATORELECTRICAL DIAGRAM

Note: Cable lengths referred to in this detail are actual cable lengths, not straight line distances. If cable lengthexceeds 7.62 wire meters, consult the factory.Key switch is required with access control.

Specifier’sNote

Note: Cable lengths referred to in this detail are actual cable lengths, not straight line distances. If cable lengthexceeds 7.62 wire meters, consult the factory.Specifier’s

Note

LARGE DOOR MOTOR OPERATORASSEMBLY WIRING DIAGRAM

The PC-based remote display provides central control and monitoring capabilities for up to 120 fire doors. Thedisplay screen monitors current status of each door (closed, closing, open, opening, stopped, blocked, accessusing fire exit hardware, or locked), battery voltage, and AC line voltage. The remotely located PC allows allmonitored Won-Door FireGuard doors to be opened or closed from a central control station. Doors equippedwith optional magnetic locks may also be remotely locked or unlocked. Changes in door status are displayedon the monitor when doors are in fire mode or a malfunction is detected. The Remote control and StatusDisplay Station is a dedicated PC for use with Won-Door Fireguard assemblies only.

Specifier’sNote

ASL – ADVANCED SYNCHRONIZED LOGISTICS

1. Key switch module.2. Plaster ring by others.3. 102 mm x 102 mm x 64 mm electrical box by others.

OPTIONAL KEY SWITCH

Key switches are optional except with access control options.For safety reasons, a key switch must be installed within line-of-sight of the operation of the Won-DoorFireGuard door.

Specifier’sNote

CCOM ROCKER SWITCH

CCOM rocker switch is included when a key switch is not specified. The switch is used to open and close thedoor and to reset and silence door faults.Specifier’s

Note

1. Ceiling line.2. 1 1/2-hour U.L. listed Vision Panel. Required only for smoke barrier applications in Group I occupancies.

Maximum size is 146 mm x 67 mm.3. Exit hardware.

OPTIONAL VISION PANEL

Add 152 mm to pocket depth for vision panel (except when the vision panel is required to be closer than 1219mm to the leading edge of the door or 2438 mm on a curved door. In these cases, contact the factory fordetails.)

Specifier’sNote

1. Single door display module.2. Plaster ring by others.3. 102 mm x 102 mm x 64 mm electrical box by others.

OPTIONAL SINGLE DOOR DISPLAY

The Single Door Display communicates door status & fault information to building tenants.Mounted in a standard 102 mm x 102 mm recessed “J” box.

Specifier’sNote

1. Top of track.2. Ceiling line.3. Finished floor.4. Exit hardware. (In sets, one on each side of the door, or one side only.)

OPTIONAL MULTIPLE EXIT HARDWARE DETAIL

1. Up to three (3) sets of exit hardware per leaf may be specified at any horizontal locations on the door(example above shows two sets in front of a bank of elevators). Upon activation of the exithardware, the FireGuard door will open to a field-programmable distance.

2. Add 25 mm to stack or pocket depth for each set of exit hardware.Specifier’sNote