FIRE WATER DEMAND CALCULATION PTTGC Doc. No.: 81000-VG-001 Rev. B Page 1 / 8 SECL Doc. No. : SC6002-EH1C-HYD-81000-001 PTT Global Chemical Public Company Limited Olefins Reconfiguration Project Project No. CP-1031-16001 FIRE WATER DEMAND CALCULATION B 30-MAY-2018 IFR (For Review) G.H.Lee K.T.Jeong K.Y.Lee A 24-APR-2018 IFR (For Review) G.H.Lee K.T.Jeong K.Y.Lee REV. DATE (DD-MMM-YYYY) ISSUE STATUS WRITTEN BY (name & signature) CHECKED BY (name & signature) APPROVED BY (name & signature) This document has been prepared on behalf of and for the exclusive use of PTT Global Chemical Public Company Limited (PTTGC), and is subject to and issued in accordance with the agreement between PTTGC and the consortium of the consortium of Samsung Engineering (Thailand) Company Limited (“SET”), and Samsung Engineering Company Limited (“SECL”) or SETT. PTTGC/SETT accepts no liability or responsibility whatsoever for it in respect of any use of or reliance upon this document by any third party. Copying this document to 3rd parties without the permission of PTTGC and SETT is not permitted.

Transcript of FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation...

Page 1: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

FIRE WATER DEMAND CALCULATION

PTTGC Doc. No.:

81000-VG-001

Rev. B Page 1 / 8

SECL Doc. No. : SC6002-EH1C-HYD-81000-001

PTT Global Chemical Public Company Limited Olefins Reconfiguration Project Project No. CP-1031-16001

FIRE WATER DEMAND CALCULATION

B 30-MAY-2018 IFR (For Review) G.H.Lee K.T.Jeong K.Y.Lee A 24-APR-2018 IFR (For Review) G.H.Lee K.T.Jeong K.Y.Lee

REV. DATE

(DD-MMM-YYYY) ISSUE STATUS

WRITTEN BY (name & signature)

CHECKED BY (name & signature)

APPROVED BY (name & signature)

This document has been prepared on behalf of and for the exclusive use of PTT Global Chemical Public Company Limited (PTTGC), and is subject to and issued in accordance with the agreement between PTTGC and the consortium of the consortium of Samsung Engineering (Thailand) Company Limited (“SET”), and Samsung Engineering Company Limited (“SECL”) or SETT. PTTGC/SETT accepts no liability or responsibility whatsoever for it in respect of any use of or reliance upon this document by any third party. Copying this document to 3rd parties without the permission of PTTGC and SETT is not permitted.

User
GH Lee
User
KT JEONG
User
KY LEE
Page 2: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

FIRE WATER DEMAND CALCULATION

PTTGC Doc. No.:

81000-VG-001

Rev. B Page 2 / 8

SECL Doc. No. : SC6002-EH1C-HYD-81000-001

REVISION SUMMARY

REV. REVISED DATE (DD-MMM-YYYY)

REVISED SECTION

REVISED DESCRIPTION

A 24-APR-2018 - Initial Issue

B 30-MAY-2018 5.1 / 6.2 / 6.3 To reflect PTTGC’s Comments

.

Page 3: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

FIRE WATER DEMAND CALCULATION

PTTGC Doc. No.:

81000-VG-001

Rev. B Page 3 / 8

SECL Doc. No. : SC6002-EH1C-HYD-81000-001

TABLE OF CONTENTS

Chapter Title Page

1 INTRODUCTION .......................................................................................... 4

2 DEFINITION ................................................................................................. 4

3 REFERENCES ............................................................................................. 4

4 UNITS ........................................................................................................... 4

5 CALCULATION BASIS ................................................................................. 5

6 MAXIMUM FIRE WATER DEMAND ............................................................ 6

7 ATTACHMENT ............................................................................................. 8

Page 4: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

FIRE WATER DEMAND CALCULATION

PTTGC Doc. No.:

81000-VG-001

Rev. B Page 4 / 8

SECL Doc. No. : SC6002-EH1C-HYD-81000-001

1 INTRODUCTION

This calculation report covers the firewater demand estimating for firefighting system to protect equipments and facilities installed in OLEFINS RECONFIGURATION PROJECT (ORP) Project in Map-Ta-Put, Rayong Province, Thailand.

2 DEFINITION

Definitions used in this calculation as follows:

- OWNER : PTT Global Chemical Public Company Limited

- PID : Piping and Instrumentation Diagram

- CONSORTIUM : A Consortium of Samsung Engineering Co. Ltd. and Samsung Engineering (Thailand) Co., Ltd

3 REFERENCES

3.1 Project Document

80000-SP-SE-002_F1 Supplemental Specification for Fire Protection & Fire Fighting System

80000-SP-FF-001 Design Philosophy For Fire Fighting System

81000-VD-201 Fire Water Demand Zone Drawing

3.2 International Code and Standard

NFPA 11 - Standard for Low-, Medium-, and High-Expansion Foam Systems

NFPA 14 - Standard for the Installation of Standpipe and Hose Systems

NFPA 15 - Standard for Water Spray Fixed Systems for Fire Protection

NFPA 16 - Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems

NFPA 24 - Standard for the Installation of Private Fire Service Mains and Their Appurtenances

4 UNITS

Unless otherwise specified, metric, Celsius, kilogram and kg/cm2g units will be applied as the measurement system However, nominalsizes of piping components will be in accordance with inch system.

Page 5: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

FIRE WATER DEMAND CALCULATION

PTTGC Doc. No.:

81000-VG-001

Rev. B Page 5 / 8

SECL Doc. No. : SC6002-EH1C-HYD-81000-001

5 CALULATION BASIS

5.1 Application Rete for Water Spray System / Fixed Foam System

According to 80000-SP-FF-001_Design Philosophy for Fire Fighting System, application rate shall be applied as following.

System Equipment Type Application R t

Remarks

Water Spray System Pump, Compressor 20.4 lpm/m²

Horzontal / Vertical Vessel & Exchanger

10.2 lpm/m²

Transformer 6.5 lpm/m²

Fixed Foam System (Foam Water Spray)

Lube Oil Unit (For Compressor)

6.5 lpm/m²

Water Curtain System Cracking Heater 37.0 lpm/m

5.2 Minimum Discharge Pressure

Nozzle Type Discharge Pressure Remarks

Water Spray Nozzle 2.1 barg

Foam Water Spray Nozzle 2.1 barg

Water Curtain Nozzle 2.1 barg

5.3 Water Velocity

Water velocity in the water spray pipe including deluge valve manifold pipe taken from firewater main shall not exceed 6 m/sec although 3.5 m/sec (block case 4.5 m/sec) for firewater main network pipe.

5.4 Water Spray System Equipment

Water Spray Protected Equipment is selected as per Section 6.4 of 80000-SP-FF-001_Design Philosophy For Fire Fighting System. Water Spray Protected Equipment is shown on PID No. 81000-PI-201~81000-PI-219.

B

Page 6: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

FIRE WATER DEMAND CALCULATION

PTTGC Doc. No.:

81000-VG-001

Rev. B Page 6 / 8

SECL Doc. No. : SC6002-EH1C-HYD-81000-001

5.5 Foam Water Spray System (Fixed Foam System) Equipment

Foam Water Spray Protected Equipment is selected as per Section 6.5 of 80000-SP-FF-001_Design Philosophy For Fire Fighting System. Foam Water Spray Protected Equipment is shown on PID No. 81000-PI-301~81000-PI-305.

5.6 Water Curtain System Equipment

Water Curtain Protected Equipment is selected as per Section 6.6 of 80000-SP-FF-001_Design Philosophy For Fire Fighting System. Water Curain Protected Equipment is shown on PID No. 81000-PI-401.

6 MAXIMUM FIRE WATER DEMAND

6.1 Firewater Demand

The largest firewater demand of one of the fire risk areas will be the maximum firewater demand based on a single major fire breaking out in one fire risk area in any one time.

For estimating total fire water demand, a minimum supplementary of 1,900 Lpm from 2 hose stream hydrant and maximum 4,000Lpm from Two(2) fire monitor will be added to the water demand from fixed fire protection system the maximum 5,900Lpm should be added to the fire water demand depend on fire risk area and installed fire monitor quantity

When estimating fire water demand for water hydrant, the following shall be used:

- Flow rate for One(1) Hose Stream of Hydrant : 950 Lpm

- Flow rate for One(1) Fire Monitor Flow : 2000 Lpm

-

Page 7: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

FIRE WATER DEMAND CALCULATION

PTTGC Doc. No.:

81000-VG-001

Rev. B Page 7 / 8

SECL Doc. No. : SC6002-EH1C-HYD-81000-001

6.2 Summary Table for Fire Water Demand

Following is summary table for fire water demand for ISBL. Refer to Attachment#1 for detail manual calculaiton of water spray / water curtain/ foam water spray system.

Fire Water Demand Zone

Fire Water Demand

Remark

Deluge Valve No.

Water Spray

System (lpm)

Fixed Foam System (lpm)

Water Curtain System (lpm)

Fire Monitor (lpm)

Hose Stream (lpm)

Total Fire Water

Demand (lpm)

FZ-001 DV-301 - 259 - 4,000 1,900 11,425

DV-302 950 - -

DV-304 4,316 - -

FZ-002 - - - - 4,000 1,900 5,900

FZ-003 DV-305 2,039 - - 4,000 1,900 7,939

FZ-004 DV-303 1,770 - - 4,000 1,900 14,327

DV-306 6,657 - -

FZ-005 DV-103 - 777 - 4,000 1,900 15,893 Maxium Case

DV-421 - 9,216

FZ-006 DV-101 1,122 - - 4,000 1,900 7,022

FZ-007 DV-201 - 346 - 4,000 1,900 6,246

FZ-008 DV-203 1,440 - - 4,000 1,900 7,340

FZ-009 DV-204 6,889 - - 4,000 1,900 12,789

FZ-010 DV-202 5,139 - - 4,000 1,900 14,876

DV-208 3,837 - -

FZ-011 DV-211 4,289 - - 4,000 1,900 10,189

FZ-012 DV-205 3,976 - - 4,000 1,900 14,745

DV-206 2,911 - -

DV-207 1,957 - -

FZ-013 DV-104 - 259 - 4,000 1,900 6,159

FZ-014 DV-106 - 1,382 - 4,000 1,900 7,282

FZ-015 - - - - 4,000 1,900 5,900

FZ-016 DV-107 - 259 - 4,000 1,900 6,159

B

B

Page 8: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

FIRE WATER DEMAND CALCULATION

PTTGC Doc. No.:

81000-VG-001

Rev. B Page 8 / 8

SECL Doc. No. : SC6002-EH1C-HYD-81000-001

Fire Water Demand

Zone

Fire Water Demand

Remark

Deluge Valve No.

Water Spray

System (lpm)

Fixed Foam System (lpm)

Water Curtain System (lpm)

Fire Monitor (lpm)

Hose Stream (lpm)

Total Fire Water

Demand (lpm)

FZ-017 DV-209 2,544 - - 4,000 1,900 8,444

FZ-018 - - - - 4,000 1,900 5,900

FZ-019 DV-210 1,084 - - 4,000 1,900 6,984

FZ-020 - - - - 4,000 1,900 5,900

FZ-021 DV-403 - 1382 - 4,000 1,900 7,282

FZ-022-1 DV-401 1,875 - - 1,900 3,775

FZ-022-2 DV-402 1,875 - - 1,900 3,775

FZ-022-3 DV-404 1,875 - - - 1,900 3,775

FZ-022-4 DV-405 1,875 - - - 1,900 3,775

6.3 Calculation Result

Fire Water Demand Zone No. FZ-005 is maximum fire water demand case.

This manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report (81000-VG-002). “PIPENET” programmed by SUNRISE SYSTEM LTD. (U.K) shall be used for flow analysis in pipe network in Hydraulic Calculation Report.

7 ATTACHMENT

Attachment#1_PTTGC ORP Firewater System Manual Calculation

Attachment#2_81000-VD-201_Fire Water Demand Zone Drawing

B

B

Page 9: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

ATTACHMENT #1

PTTGC ORP Firewater System Manual Calculation

Page 10: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

Project : ORP PROJECTOwner : PTTGCJob No. : SC-6002

MANUAL CALCULATED FIREWATER DEMANDFOR FIREWATER SYSTEM

Page : 1 of 5Date : 2018-05-30

Revision : B

MINIMUM MINIMUM HYDRAULIC SYSTEM

DELUGE APPLICAT SYSTEM K- DIS- FLOW TOATL BALANCE DESIGN

ZONE VALVE RECEIVED TAG NO. DESCRIPTION DIAMETER WIDTH LENGTH SURFACE RATE WATER SPRAY FACTOR CHARGE PER RING Seal TOTAL RATE FLOW 15% FLOW VELO- INSIDE NOMINAL

No. No. GA AREA DEMAND ANGLE PRE- RING Nozzle RATE RATE CITY

or V/P TOTAL APPLIED SSURE

Y or N m m m m m m2

lpm/m2 lpm ° lpm/barg

1/2 bar ea ea ea ea lpm lpm lpm lpm m/s inch inch

N P-81802A DPG FIRST STAGE REACTORS RECYCLE PUMPS 1 2.000 3.200 6.40 20.4 131 95 25.9 2.10 2 2 4 37.5 150 23 173 6.0 0.97 1.5

N P-81802R DPG FIRST STAGE REACTORS RECYCLE PUMPS 1 2.000 3.200 6.40 20.4 131 95 25.9 2.10 2 2 4 37.5 150 23 173 6.0 0.97 1.5

N P-81809A H2S STRIPPER REFLUX PUMPS 1 1.100 1.600 1.76 20.4 36 95 25.9 2.10 2 1 2 37.5 75 11 86 6.0 0.69 1.0

N P-81809R H2S STRIPPER REFLUX PUMPS 1 1.100 1.600 1.76 20.4 36 95 25.9 2.10 2 1 2 37.5 75 11 86 6.0 0.69 1.0

Y V-81807 DPG SECOND STAGE HP FLASH DRUM 3 1.400 4.100 4.100 20.16 10.2 206 125 25.9 2.10 4 2 2 10 37.5 375 56 432 6.0 1.54 2.0

Q'TY

HEIGHT

REV

REMARK

NOZZLE DATA

FZ-001 DV-302

PIPE SIZE

WATER SPRAY SYSTEM

RISK EQUIPMENT

TY

PE

Deluge Valve 539 826 124 950 6.0 2.3 3.0 DV 3"

Y C-81404 PROPYLENE FRACTIONATOR NO.2 3 5.500 76.800 2.500 76.03 10.2 776 125 59.0 2.10 10 1 10 85.5 855 128 983 6.0 2.32 3.0

Y C-81403 PROPYLENE FRACTIONATOR NO.1 3 4.500 46.000 2.500 57.32 10.2 585 125 59.0 2.10 8 1 8 85.5 684 103 787 6.0 2.08 3.0

Deluge Valve 1,360 1,539 231 1,770 6.0 3.1 4.0 DV 4"

MANIFOLD 1,360 1,539 231 1,770 3.5 4.1 6.0

Y R-81801A DPG FIRST STAGE REACTOR 3 2.100 14.700 7.900 56.91 10.2 581 125 25.9 2.10 6 3 18 37.5 676 101 777 6.0 2.06 3.0

Y R-81801R DPG FIRST STAGE REACTOR 3 2.100 14.700 7.900 56.91 10.2 581 125 25.9 2.10 6 3 18 37.5 676 101 777 6.0 2.06 3.0

Y V-81801 DPG FIRST STAGE FEED SURGE DRUM 3 1.900 5.600 5.600 37.35 10.2 381 125 25.9 2.10 6 2 4 16 37.5 601 90 691 6.0 1.95 3.0

Y V-81802 DPG FIRST STAGE HP FLASH DRUM 3 1.500 4.400 4.400 23.18 10.2 237 125 25.9 2.10 4 2 2 10 37.5 375 56 432 6.0 1.54 2.0

Y V-81803 DPG LP FLASH DRUM 3 1.500 4.400 4.400 23.18 10.2 237 125 25.9 2.10 4 2 2 10 37.5 375 56 432 6.0 1.54 2.0

Y E-81801A DPG FIRST STAGE RECYCLE COOLER 2 1 080 9 110 33 44 10 2 341 125 25 9 2 10 5 2 4 14 37 5 525 79 604 6 0 1 82 2 0

FZ-004 DV-303

FZ-001 DV-304

Y E-81801A DPG FIRST STAGE RECYCLE COOLER 2 1.080 9.110 33.44 10.2 341 125 25.9 2.10 5 2 4 14 37.5 525 79 604 6.0 1.82 2.0

Y E-81801R DPG FIRST STAGE RECYCLE COOLER 2 1.080 9.110 33.44 10.2 341 125 25.9 2.10 5 2 4 14 37.5 525 79 604 6.0 1.82 2.0

Deluge Valve 2,697 3,753 563 4,316 6.0 4.9 6.0 DV 6"

Y P-81406 PROPYLENE FRACTIONATOR NO.1 REFLUX PUMP 1 2.000 3.000 6.00 20.4 122 95 25.9 2.10 2 2 4 37.5 150 23 173 6.0 0.97 1.5

Y P-81408A PROPYLENE PRODUCT PUMP 1 1.600 2.800 4.48 20.4 91 95 33.1 2.10 2 1 2 48.0 96 14 110 6.0 0.78 1.0

Y P-81408R PROPYLENE PRODUCT PUMP 1 1.600 2.800 4.48 20.4 91 95 33.1 2.10 2 1 2 48.0 96 14 110 6.0 0.78 1.0

Y P-81411A DEBUTANIZER BOTTOMS PUMP 1 1.700 2.300 3.91 20.4 80 95 33.1 2.10 2 1 2 48.0 96 14 110 6.0 0.78 1.0

Y P-81411R DEBUTANIZER BOTTOMS PUMP 1 1.700 2.300 3.91 20.4 80 95 33.1 2.10 2 1 2 48.0 96 14 110 6.0 0.78 1.0

Y C-81405 DEBUTANIZER 3 2.100 25.350 8.300 59.55 10.2 607 125 25.9 2.10 6 3 18 37.5 676 101 777 6.0 2.06 3.0

Y V-81404 DEBUTANIZER REFLUX DRUM 2 1.500 4.500 26.09 10.2 266 125 25.9 2.10 3 3 6 15 37.5 563 84 647 6.0 1.88 2.0

Deluge Valve 1,338 1,772 266 2,038 6.0 3.3 4.0 DV 4"

DV-305FZ-003

N P-81407A PROPYLENE FRACTIONATOR NO.2 REFLUX PUMP 1 2.400 4.600 11.04 20.4 225 95 33.1 2.10 3 2 6 48.0 288 43 331 6.0 1.35 1.5

N P-81407R PROPYLENE FRACTIONATOR NO.2 REFLUX PUMP 1 2.400 4.600 11.04 20.4 225 95 33.1 2.10 3 2 6 48.0 288 43 331 6.0 1.35 1.5

Y E-81410A PROPYLENE FRACTIONATOR CONDENSER 2 2.020 9.482 69.03 10.2 704 125 25.9 2.10 6 3 6 24 37.5 901 135 1,036 6.0 2.38 3.0

Y E-81410B PROPYLENE FRACTIONATOR CONDENSER 2 2.020 9.482 69.03 10.2 704 125 25.9 2.10 6 3 6 24 37.5 901 135 1,036 6.0 2.38 3.0

Y E-81410C PROPYLENE FRACTIONATOR CONDENSER 2 2.020 9.482 69.03 10.2 704 125 25.9 2.10 6 3 6 24 37.5 901 135 1,036 6.0 2.38 3.0

Y E-81410D PROPYLENE FRACTIONATOR CONDENSER 2 2.020 9.482 69.03 10.2 704 125 25.9 2.10 6 3 6 24 37.5 901 135 1,036 6.0 2.38 3.0

N P-81409 PROPANE PRODUCT PUMP 1 1.300 1.900 2.47 20.4 50 95 25.9 2.10 2 1 2 37.5 75 11 86 6.0 0.69 1.0

Y V-81402 PROPYLENE FRACTIONATOR REFLUX DRUM 2 3.550 10.650 146.14 10.2 1,491 125 33.1 2.10 6 4 8 32 48.0 1,535 230 1,765 6.0 3.11 4.0

DV-306FZ-004

SAMSUNG ENGINEERING CO., LTD

Page 11: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

Project : ORP PROJECTOwner : PTTGCJob No. : SC-6002

MANUAL CALCULATED FIREWATER DEMANDFOR FIREWATER SYSTEM

Page : 2 of 5Date : 2018-05-30

Revision : B

MINIMUM MINIMUM HYDRAULIC SYSTEM

DELUGE APPLICAT SYSTEM K- DIS- FLOW TOATL BALANCE DESIGN

ZONE VALVE RECEIVED TAG NO. DESCRIPTION DIAMETER WIDTH LENGTH SURFACE RATE WATER SPRAY FACTOR CHARGE PER RING Seal TOTAL RATE FLOW 15% FLOW VELO- INSIDE NOMINAL

No. No. GA AREA DEMAND ANGLE PRE- RING Nozzle RATE RATE CITY

or V/P TOTAL APPLIED SSURE

Y or N m m m m m m2

lpm/m2 lpm ° lpm/barg

1/2 bar ea ea ea ea lpm lpm lpm lpm m/s inch inch

Q'TY

HEIGHT

REV

REMARK

NOZZLE DATAPIPE SIZE

RISK EQUIPMENT

TY

PE

Deluge Valve 4,808 5,789 868 6,657 6.0 6.0 6.0 DV 8"

MANIFOLD 4,808 5,789 868 6,657 3.5 7.9 8.0 -> 10"

Y V-81116 DMDS DRUM 3 1.600 4.300 4.300 24.39 10.2 249 125 25.9 2.10 4 2 2 10 37.5 375 56 432 6.0 1.54 2.0

Y V-81001 LPG FEED VAPORIZER DRUM 3 2.200 6.550 6.550 50.52 10.2 515 125 25.9 2.10 6 2 4 16 37.5 601 90 691 6.0 1.95 3.0

Deluge Valve 764 976 146 1,122 6.0 2.5 3.0 DV 3"

MANIFOLD 764 976 146 1,122 3.5 3.2 4.0

DV-101FZ-006

Y V-81509 MEDIUM EBR DRUM 3 3.900 11.200 9.000 126.78 10.2 1,293 125 43.2 2.10 8 3 24 62.6 1,502 225 1,728 6.0 3.08 4.0

Y V-81507 LIGHT EBR ACCUMULATOR 3 3.200 9.400 9.400 105.61 10.2 1,077 125 33.1 2.10 8 3 4 28 48.0 1,343 201 1,545 6.0 2.91 3.0

Y V-81303 DEMETHANIZER FEED SEPARATOR NO.1 3 2.150 9.500 9.500 69.18 10.2 706 125 25.9 2.10 6 3 4 22 37.5 826 124 950 6.0 2.28 3.0

Y V-81304 DEMETHANIZER FEED SEPARATOR NO.2 3 1.400 6.500 6.500 30.72 10.2 313 125 25.9 2.10 4 2 2 10 37.5 375 56 432 6.0 1.54 2.0

Y V-81305 DEMETHANIZER FEED SEPARATOR NO.3 3 1.300 3.800 3.800 17.35 10.2 177 125 25.9 2.10 4 2 2 10 37.5 375 56 432 6.0 1.54 2.0

N P-81303A DEMETHANIZER BOTTOMS PUMP 1 2.300 5.200 11.96 20.4 244 95 33.1 2.10 3 2 6 48.0 288 43 331 6.0 1.35 1.5

N P-81303R DEMETHANIZER BOTTOMS PUMP 1 2.300 5.200 11.96 20.4 244 95 33.1 2.10 3 2 6 48.0 288 43 331 6.0 1.35 1.5

DEMETHANIZER (LOWER) 3 3.300 5.500 5.600 69.88 10.2 713 125 33.1 2.10 8 2 16 48.0 767 115 883 6.0 2.20 3.0

DEMETHANIZER (UPPER) 3 2.200 31.750 1.000 12.17 10.2 124 125 25.9 2.10 6 1 6 37.5 225 34 259 6.0 1.19 1.5

Deluge Valve 4,892 5,990 899 6,889 6.0 6.1 8.0 DV 8"

Y V-81302 LP DEPROPANIZER REFLUX DRUM 2 1 350 4 150 21 56 10 2 220 125 25 9 2 10 3 2 5 11 37 5 413 62 475 6 0 1 61 2 0

Y

DV-204FZ-009

C-81303

Y V-81302 LP DEPROPANIZER REFLUX DRUM 2 1.350 4.150 21.56 10.2 220 125 25.9 2.10 3 2 5 11 37.5 413 62 475 6.0 1.61 2.0

Y V-81401 ETHYLENE FRACTIONATOR REFLUX DRUM 2 2.800 8.700 93.55 10.2 954 125 33.1 2.10 5 3 7 22 48.0 1,055 158 1,214 6.0 2.58 3.0

Y E-81404 ETHYLENE FRACTIONATOR CONDENSER 4 6.200 3.800 5.000 5.000 123.56 10.2 1,260 125 25.9 2.10 14 2 8 36 37.5 1,351 203 1,554 6.0 2.92 3.0

Y V-81504 EBR ACCUMULATOR FOR E-81405 3 1.400 4.200 4.200 20.60 10.2 210 125 25.9 2.10 4 2 4 12 37.5 450 68 518 6.0 1.69 2.0

Y E-81308 LP DEPROPANIZER CONDENSER 4 0.760 0.650 2.080 2.080 6.36 10.2 65 125 25.9 2.10 4 1 1 5 37.5 188 28 216 6.0 1.09 1.5

Deluge Valve 2,710 3,457 519 3,976 6.0 4.7 6.0 DV 6"

MANIFOLD 4,892 5,990 899 6,889 3.5 8.0 10.0

Y V-81503 EBR COMPRESSOR 3RD STAGE SUCTION DRUM 3 5.400 10.900 8.000 167.37 10.2 1,707 125 43.2 2.10 10 3 30 62.6 1,878 282 2,160 6.0 3.44 4.0

Y V-81502 EBR COMPRESSOR 2ND STAGE SUCTION DRUM 3 3.000 6.350 6.350 69.62 10.2 710 125 33.1 2.10 6 2 4 16 48.0 767 115 883 6.0 2.20 3.0

Y V-81501 EBR COMPRESSOR 1ST STAGE SUCTION DRUM 3 5.100 7.700 7.700 151.60 10.2 1,546 125 33.1 2.10 10 3 8 38 48.0 1,823 273 2,096 6.0 3.39 4.0

Deluge Valve 3,964 4,468 670 5,139 6.0 5.3 6.0 DV 6"

FZ-012 DV-205

FZ-010 DV-202

Y V-81505 HEAVY EBR ACCUMULATOR 3 5.200 15.250 4.000 94.70 10.2 966 125 43.2 2.10 10 2 20 62.6 1,252 188 1,440 6.0 2.81 3.0

Deluge Valve 966 1,252 188 1,440 6.0 2.8 3.0 DV 3"

MANIFOLD 3,964 4,468 670 5,139 3.5 6.9 8.0

Y C-81402 ETHYLENE FRACTIONATOR 3 3.800 69.600 8.000 111.18 10.2 1,134 125 33.1 2.10 10 3 30 48.0 1,439 216 1,655 6.0 3.01 3.0

N P-81401A DEETHANIZER BOTTOMS PUMP 1 1.700 2.400 4.08 20.4 83 95 33.1 2.10 2 1 2 48.0 96 14 110 6.0 0.78 1.0

N P-81401R DEETHANIZER BOTTOMS PUMP 1 1.700 2.400 4.08 20.4 83 95 33.1 2.10 2 1 2 48.0 96 14 110 6.0 0.78 1.0

Y C-81401 DEETHANIZER 3 2.900 36.800 8.500 86.57 10.2 883 125 25.9 2.10 8 3 24 37.5 901 135 1,036 6.0 2.38 3.0

Deluge Valve 2,184 2,532 380 2,911 6.0 4.0 4.0 DV 6"

DV-206

FZ-008 DV-203

FZ-012

SAMSUNG ENGINEERING CO., LTD

Page 12: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

Project : ORP PROJECTOwner : PTTGCJob No. : SC-6002

MANUAL CALCULATED FIREWATER DEMANDFOR FIREWATER SYSTEM

Page : 3 of 5Date : 2018-05-30

Revision : B

MINIMUM MINIMUM HYDRAULIC SYSTEM

DELUGE APPLICAT SYSTEM K- DIS- FLOW TOATL BALANCE DESIGN

ZONE VALVE RECEIVED TAG NO. DESCRIPTION DIAMETER WIDTH LENGTH SURFACE RATE WATER SPRAY FACTOR CHARGE PER RING Seal TOTAL RATE FLOW 15% FLOW VELO- INSIDE NOMINAL

No. No. GA AREA DEMAND ANGLE PRE- RING Nozzle RATE RATE CITY

or V/P TOTAL APPLIED SSURE

Y or N m m m m m m2

lpm/m2 lpm ° lpm/barg

1/2 bar ea ea ea ea lpm lpm lpm lpm m/s inch inch

Q'TY

HEIGHT

REV

REMARK

NOZZLE DATAPIPE SIZE

RISK EQUIPMENT

TY

PE

N P-81302A LP DEPROPANIZER REFLUX PUPM 1 2.200 4.200 9.24 20.4 189 95 25.9 2.10 3 2 6 37.5 225 34 259 6.0 1.19 1.5

N P-81302R LP DEPROPANIZER REFLUX PUPM 1 2.200 4.200 9.24 20.4 189 95 25.9 2.10 3 2 6 37.5 225 34 259 6.0 1.19 1.5

Y C-81302 LP DEPROPANIZER 3 2.200 29.550 7.800 59.16 10.2 604 125 25.9 2.10 6 3 18 37.5 676 101 777 6.0 2.06 3.0

HP DEPROPANIZER (LOWER) 3 1.700 12.700 8.300 47.47 10.2 484 125 33.1 2.10 4 3 12 48.0 576 86 662 6.0 1.91 2.0

HP DEPROPANIZER (UPPER) 3 3.200 12.800 11.12 10.2 113 0 0.0 0 0 0 6.0 0.00 1.0

Deluge Valve 1,578 1,702 255 1,957 6.0 3.3 4.0 DV 4"

Y

FZ-012 DV-207

C-81301

MANIFOLD 2,184 4,233 635 4,868 3.5 6.8 8.0

N P-81204ACHARGE GAS COMPRESSOR 3RD STAGE SUCTION DRUMPUMP

1 1.500 3.200 4.80 20.4 98 95 43.2 2.10 2 1 2 62.6 125 19 144 6.0 0.89 1.0

N P-81204RCHARGE GAS COMPRESSOR 3RD STAGE SUCTION DRUMPUMP

1 1.500 3.200 4.80 20.4 98 95 43.2 2.10 2 1 2 62.6 125 19 144 6.0 0.89 1.0

Y V-81203CHARGE GAS COMPRESSOR 2ND STAGE DISCHARGEDRUM

3 2.900 4.550 4.550 50.58 10.2 516 125 33.1 2.10 6 2 12 48.0 576 86 662 6.0 1.91 2.0

Y V-81205 CHARGE GAS COMPRESSOR 3RD STAGE SUCTION DRUM 3 2.900 5.750 0.550 14.14 10.2 144 125 25.9 2.10 6 1 6 37.5 225 34 259 6.0 1.19 1.5

N P-81205ACHARGE GAS COMPRESSOR 3RD STAGE DISCHARGEDRUM PUMP

1 1.700 2.100 3.57 20.4 73 95 25.9 2.10 2 1 2 37.5 75 11 86 6.0 0.69 1.0

N P-81205RCHARGE GAS COMPRESSOR 3RD STAGE DISCHARGEDRUM PUMP

1 1.700 2.100 3.57 20.4 73 95 25.9 2.10 2 1 2 37.5 75 11 86 6.0 0.69 1.0

Y V-81206CHARGE GAS COMPRESSOR 3RD STAGE DISCHARGEDRUM

3 2.300 5.650 5.650 46.57 10.2 475 125 25.9 2.10 6 2 4 16 37.5 601 90 691 6.0 1.95 3.0

Y S-81202A LIQUID CONDENSATE DRYER 3 1.800 11.800 11.500 68.55 10.2 699 125 33.1 2.10 4 4 16 48.0 767 115 883 6.0 2.20 3.0

Y S-81202R LIQUID CONDENSATE DRYER 3 1.800 11.800 11.500 68.55 10.2 699 125 33.1 2.10 4 4 16 48.0 767 115 883 6.0 2.20 3.0

Deluge Valve 2 876 3 337 501 3 837 6 0 4 6 6 0 DV 6"

FZ-010

DV-208

Deluge Valve 2,876 3,337 501 3,837 6.0 4.6 6.0 DV 6

Y V-81201 CHARGE GAS COMPRESSOR 1ST STAGE SUCTION DRUM 3 4.200 5.950 5.950 97.66 10.2 996 125 43.2 2.10 8 2 4 20 62.6 1,252 188 1,440 6.0 2.81 3.0

Y V-81202 CHARGE GAS COMPRESSOR 2ND STAGE SUCTION DRUM 3 3.500 7.300 7.300 93.57 10.2 954 125 33.1 2.10 8 2 4 20 48.0 959 144 1,103 6.0 2.46 3.0

Deluge Valve 1,951 2,211 332 2,543 6.0 3.7 4.0 DV 4"

N P-81301A HP DEPROPANIZER REFLUX PUMP 1 1.700 2.400 4.08 20.4 83 95 33.1 2.10 2 1 2 48.0 96 14 110 6.0 0.78 1.0

N P-81301R HP DEPROPANIZER REFLUX PUMP 1 1.700 2.400 4.08 20.4 83 95 33.1 2.10 2 1 2 48.0 96 14 110 6.0 0.78 1.0

Y V-81301 HP DEPROPANIZER REFLUX DRUM 3 3.000 3.900 3.900 46.53 10.2 475 125 25.9 2.10 6 2 8 20 37.5 751 113 863 6.0 2.18 3.0

Deluge Valve 641 943 141 1,084 6.0 2.4 3.0 DV 3"

N P-81404A HP ETHYLENE PRODUCT PUMP 1 2.200 5.500 12.10 20.4 247 95 25.9 2.10 4 2 8 37.5 300 45 345 6.0 1.38 1.5

N P-81404R HP ETHYLENE PRODUCT PUMP 1 2.200 5.500 12.10 20.4 247 95 25.9 2.10 4 2 8 37.5 300 45 345 6.0 1.38 1.5

N P-81403A ETHYLENE FRACTIONATOR REFLUX PUMP 1 2.400 3.000 7.20 20.4 147 95 25.9 2.10 2 2 4 37.5 150 23 173 6.0 0.97 1.5

FZ-017 DV-209

FZ-019 DV-210

N P-81403R ETHYLENE FRACTIONATOR REFLUX PUMP 1 2.400 3.000 7.20 20.4 147 95 25.9 2.10 2 2 4 37.5 150 23 173 6.0 0.97 1.5

N P-81402A DEETHANIZER REFLUX PUMP 1 1.700 2.100 3.57 20.4 73 95 25.9 2.10 2 1 2 37.5 75 11 86 6.0 0.69 1.0

N P-81402R DEETHANIZER REFLUX PUMP 1 1.700 2.100 3.57 20.4 73 95 25.9 2.10 2 1 2 37.5 75 11 86 6.0 0.69 1.0

MAPD CONVERTER (LOWER) 3 2.500 6.650 6.500 57.84 10.2 590 125 43.2 2.10 6 2 12 62.6 751 113 864 6.0 2.18 3.0

MAPD CONVERTER (UPPER) 3 1.600 4.350 3.500 20.37 10.2 208 125 43.2 2.10 4 1 4 62.6 250 38 288 6.0 1.26 1.5

MAPD CONVERTER (LOWER) 3 2.500 6.650 6.500 57.84 10.2 590 125 43.2 2.10 6 2 12 62.6 751 113 864 6.0 2.18 3.0

MAPD CONVERTER (UPPER) 3 1.600 4.350 3.500 20.37 10.2 208 125 43.2 2.10 4 1 4 62.6 250 38 288 6.0 1.26 1.5

N P-81405A MAPD CONVERTER RECYCLE PUMP 1 1.900 2.345 4.46 20.4 91 95 25.9 2.10 2 2 4 37.5 150 23 173 6.0 0.97 1.5

DV-211FZ-011

Y

Y R-81401A

R-81401R

SAMSUNG ENGINEERING CO., LTD

Page 13: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

Project : ORP PROJECTOwner : PTTGCJob No. : SC-6002

MANUAL CALCULATED FIREWATER DEMANDFOR FIREWATER SYSTEM

Page : 4 of 5Date : 2018-05-30

Revision : B

MINIMUM MINIMUM HYDRAULIC SYSTEM

DELUGE APPLICAT SYSTEM K- DIS- FLOW TOATL BALANCE DESIGN

ZONE VALVE RECEIVED TAG NO. DESCRIPTION DIAMETER WIDTH LENGTH SURFACE RATE WATER SPRAY FACTOR CHARGE PER RING Seal TOTAL RATE FLOW 15% FLOW VELO- INSIDE NOMINAL

No. No. GA AREA DEMAND ANGLE PRE- RING Nozzle RATE RATE CITY

or V/P TOTAL APPLIED SSURE

Y or N m m m m m m2

lpm/m2 lpm ° lpm/barg

1/2 bar ea ea ea ea lpm lpm lpm lpm m/s inch inch

Q'TY

HEIGHT

REV

REMARK

NOZZLE DATAPIPE SIZE

RISK EQUIPMENT

TY

PE

N P-81405R MAPD CONVERTER RECYCLE PUMP 1 1.900 2.345 4.46 20.4 91 95 25.9 2.10 2 2 4 37.5 150 23 173 6.0 0.97 1.5

Y V-81403 MAPD EFFLUENT FLASH DRUM 3 1.500 5.700 5.700 29.30 10.2 299 125 25.9 2.10 4 2 2 10 37.5 375 56 432 6.0 1.54 2.0

Deluge Valve 3,010 3,730 559 4,289 6.0 4.8 6.0 DV 6"

MANIFOLD 3,010 3,730 501 4,289 3.5 6.3 8.0

FZ-022-01 DV-401 N - TRANSFORMER 4 4.900 6.600 5.950 5.950 169.19 6.5 1,100 125 33.1 2.10 14 2 6 34 48.0 1,631 245 1,875 6.0 3.21 4.0

Deluge Valve 1,100 1,631 245 1,875 6.0 3.2 4.0 DV 4"

FZ-022-02 DV-402 N - TRANSFORMER 4 4.900 6.600 5.950 5.950 169.19 6.5 1,100 125 33.1 2.10 14 2 6 34 48.0 1,631 245 1,875 6.0 3.21 4.0

Deluge Valve 1,100 1,631 245 1,875 6.0 3.2 4.0 DV 4"

MANIFOLD 2,200 3,262 489 3,751 3.5 5.9 6.0 -> 8"

FZ-022-03 DV-404 N - TRANSFORMER 4 4.900 6.600 5.950 5.950 169.19 6.5 1,100 125 33.1 2.10 14 2 6 34 48.0 1,631 245 1,875 6.0 3.21 4.0

Deluge Valve 1,100 1,631 245 1,875 6.0 3.2 4.0 DV 4"

FZ-022-04 DV-405 N - TRANSFORMER 4 4.900 6.600 5.950 5.950 169.19 6.5 1,100 125 33.1 2.10 14 2 6 34 48.0 1,631 245 1,875 6.0 3.21 4.0

Deluge Valve 1,100 1,631 245 1,875 6.0 3.2 4.0 DV 4"

MANIFOLD 2,200 3,262 489 3,751 3.5 5.9 6.0 -> 8"

FZ-005 DV-421 N/A H-81101~81105 SRT-VI LIQUID CRACKING HEATER 1ST & 2ND LINE - 95.000 95.00 37.0 3,515 125 79.0 2.10 35 2 70 114.5 8,014 1,202 9,216 6.0 7.11 8.0

Deluge Valve 3 515 8 014 1 202 9 216 6 0 7 1 8 0 DV 8"

WATER CURTAIN SYSTEM

Deluge Valve 3,515 8,014 1,202 9,216 6.0 7.1 8.0 DV 8

MANIFOLD 3,515 8,014 1,202 9,216 3.5 9.3 10.0

FZ-001 DV-301 Y B-81801 LUBE OIL CONSOLE - 3.400 4.000 13.60 6.5 88 95 25.9 2.10 6 1 6 37.5 225 34 259 6.0 1.19 1.5

Deluge Valve 88 225 34 259 6.0 1.2 1.5 DV 3"

MANIFOLD 88 225 34 259 3.5 1.6 4.0

FZ-005 DV-103 N B-81701A LUBE OIL CONSOLE - 2.000 3.500 7.00 6.5 46 95 25.9 2.10 6 1 6 37.5 225 34 259 6.0 1.19 1.5

N B-81701B LUBE OIL CONSOLE - 2.000 3.500 7.00 6.5 46 95 25.9 2.10 6 1 6 37.5 225 34 259 6.0 1.19 1.5

N B-81701R LUBE OIL CONSOLE - 2.000 3.500 7.00 6.5 46 95 25.9 2.10 6 1 6 37.5 225 34 259 6.0 1.19 1.5

Deluge Valve 137 676 34 777 6.0 2.1 3.0 DV 3"

FZ-013 DV-104 N B-81101A LUBE OIL CONSOLE - 2.000 3.500 7.00 6.5 46 95 25.9 2.10 6 1 6 37.5 225 34 259 6.0 1.19 1.5

FIXED FOAM WATER SPRAY SYSTEM

Deluge Valve 46 225 34 259 6.0 1.2 1.5 DV 3"

MANIFOLD 137 676 34 777 3.5 2.7 4.0

FZ-014 DV-106 NB-81501,

BN-81501, B-81201LUBE OIL CONSOLE - 6.000 13.000 78.00 6.5 507 95 25.9 2.10 32 1 32 37.5 1,201 180 1,381 6.0 2.75 3.0

Deluge Valve 507 1,201 180 1,381 6.0 2.8 3.0 DV 3"

FZ-016 DV-107 N P-81106A LUBE OIL CONSOLE - 2.000 3.500 7.00 6.5 46 95 25.9 2.10 6 1 6 37.5 225 34 259 6.0 1.19 1.5

Deluge Valve 46 225 34 259 6.0 1.2 1.5 DV 3"

MANIFOLD 507 1,201 180 1,381 3.5 3.6 4.0

FZ-007 DV-201 N B-81301 LUBE OIL CONSOLE - 3.400 6.400 21.76 6.5 142 95 25.9 2.10 8 1 8 37.5 300 45 345 6.0 1.38 1.5

SAMSUNG ENGINEERING CO., LTD

Page 14: FIRE WATER DEMAND CALCULATIONeia.onep.go.th/images/monitor/1548905621.pdfThis manual calculation result and its required fire main size will be verfitied by Hydraulic Calculation Report

Project : ORP PROJECTOwner : PTTGCJob No. : SC-6002

MANUAL CALCULATED FIREWATER DEMANDFOR FIREWATER SYSTEM

Page : 5 of 5Date : 2018-05-30

Revision : B

MINIMUM MINIMUM HYDRAULIC SYSTEM

DELUGE APPLICAT SYSTEM K- DIS- FLOW TOATL BALANCE DESIGN

ZONE VALVE RECEIVED TAG NO. DESCRIPTION DIAMETER WIDTH LENGTH SURFACE RATE WATER SPRAY FACTOR CHARGE PER RING Seal TOTAL RATE FLOW 15% FLOW VELO- INSIDE NOMINAL

No. No. GA AREA DEMAND ANGLE PRE- RING Nozzle RATE RATE CITY

or V/P TOTAL APPLIED SSURE

Y or N m m m m m m2

lpm/m2 lpm ° lpm/barg

1/2 bar ea ea ea ea lpm lpm lpm lpm m/s inch inch

Q'TY

HEIGHT

REV

REMARK

NOZZLE DATAPIPE SIZE

RISK EQUIPMENT

TY

PE

Deluge Valve 142 300 45 345 6.0 1.4 1.5 DV 3"

MANIFOLD 142 300 45 345 3.5 1.8 4.0

FZ-021 DV-403 Y B-81108 LUBE OIL CONSOLE - 7.000 13.000 91.00 6.5 592 95 25.9 2.10 32 1 32 37.5 1,201 180 1,381 6.0 2.75 3.0

Deluge Valve 592 1,201 180 1,381 6.0 2.8 3.0 DV 3"

MANIFOLD 592 1,201 180 1,381 3.5 3.6 4.0

SAMSUNG ENGINEERING CO., LTD