REVISIONS (DO NOT USE THIS BLOCK UNTIL AFTER PERMIT IS ISSUED)
HARRIS COUNTY (IFC 2012)FIRE CODE DESIGN AND COMPLIANCE REVIEW SHEET VERSION 7.0 (MAR 2017)
BUILDING PLANNING & DESCRIPTION1 MEANS OF EGRESS3 FIRE-RESISTANCE RATE CONSTRUCTION5 STORAGE: STANDARD & HIGH PILED9CHAPTER 10 IBC 2012 CHAPTER 6, 7 AND 10 IBC 2012 CHAPTER 32 IFC 2012 (REFER TO REGULATIONS FOR REQUIREMENT FOR CONSULTANT ENGINEER SECTION
3201.5 HC AMENDMENTS)
NEW CONSTRUCTIONLEASE SPACE BUILD-OUT (LSBO)
SUBSTANTIAL IMPROVEMENT
SHELL BUILDING
CHANGE OF OCCUPANCYOTHER: __________________________
SINGLE OCCUPANCY SEPARATED USE NON-SEPARATED USE
(SECTION 508.3 OR 508.4 IBC 2012)TYPE OF CONSTRUCTION: __________________________ (CHAPTER 6 IBC 2012)HEIGHT LIMITATION: __________________ AREA LIMITATION: ________________ (TABLE 503 IBC 2012)
BUILDING VALUATIONBUILDING NUMBER: ________ OF ________
CALL CENTERPOINT ENERGY AHEAD OF TIME, AT 713-207-4460, TO OBTAIN AN ADDRESS
ADDRESS: ____________________________________________________________________________________CITY, ST: ___________________________________ ZIP CODE: _________________ SUITE: _______________
ESTIMATED COST OF CONSTRUCTION: $_________________________________________________T.D.L.R #: ________________________________ (REQUIRED FOR CONSTRUCTION OVER $50,000)TEXAS DEPARTMENT OF LICENSING AND REGULATIONS(http://www.license.state.tx.us/)TELEPHONE: (512) 463-6599 TOLL FREE (IN TEXAS): 800-803-99202FAX: (512) 475-2871 RELAY TEXAS-TDD: 800-735-2989
HCAD #. OR PROPERTY TAX #: _________________________________ (13 DIGITS) FLOODPLAIN: _______
LIST BELOW THE PURPOSE/USE OF THE BUILDING OR AREA BEING REVIEWED. INCLUDEDETAILS ON THE PRODUCTS/MATERIALS BEING STORED/FABRICATED AND NOTE HOW THEYARE BEING PACKAGED.
SHELL BUILDING PERMIT #: ___________________________ CIVIL PROJECT #: _______________________
GROSS SQUARE FOOTAGE: __________________________ #OF FLOORS: ___________ HEIGHT:__________
OCCUPANCY TYPE AND LOAD2CHAPTER 2, 3 & TABLE 1004.1.2 IBC 2012
A-1 A-2 A-3 A-4 A-5 B E
F-1 F-2 H-1 H-2 H-3 H-4 H-5
I-1 I-2 I-3 I-4 M R-1 R-2
R-3 R-4 S-1 S-2 U
OCCUPANCY CLASSIFICATION TYPES
BREAK DOWN AREAS AND OCCUPANT LOADS PER FLOOR
OCCUPANCYCLASSIFICATION SPECIFIC USE
TOTAL
SQUAREFOOTAGE
SF PEROCCUPANT
DESIGNOCCUPANTS
# OF EXITS PROVIDED# OF REQUIRED EXITSMEANS OF EGRESS SHEET #
STAIRWAYS (PER FLOOR)
EGRESS @ 1ST FL OR LSBO
(SECTION 1005.3 IBC 2012)
PANIC HARDWARE ON EXIT DOORS? YES NO (SECTION 1008.1.9 IBC 2012)STAIRWAYS (SECTION 1009 IBC 2012)MINIMUM CLEAR WIDTH SHOWN ON: ________________________________ (EACH STAIRWELL)EGRESS WIDTHS ARE SHOWN ON: __________ACCESSIBLE AREAS OF REFUGE & 2-WAY COMMUNICATIONS SHOWN ON: ________
FRONTAGE INCREASE CALCULATIONS ARE SHOWN ON SHEET: __________________________________(SECTION 1007.3 TO 1007.6 IBC 2012)
EXIT SIGNS/EGRESS ILLUMINATION (SECTION 1006 & 1011 IBC 2012)REQUIRED AND SHOWN ON: ___________________________ (HIGHLIGHT ON PLANS)
EXTERIOR EMERGENCY LIGHTING PROVIDED? YES NOEXIT TRAVEL DISTANCE (TABLE 1016.2 IBC 2012)
PROVIDE TRAVELDISTANCEMAX TRAVEL DISTANCEOCCUPANCY TYPE SHEET #
ELEVATORSELEVATOR KEYBOX LOCATED IN LOBBY?(MUST BE WITHIN 20' OF THE CALL BUTTON)
NEW EXISTING YES NO
FIRE PROTECTION SYSTEMS4CHAPTER 9 IBC & IFC 2012
ALL FIRE PROTECTION PLANS SHALL BE SUBMITTED FOR REVIEW AFTER BUILDING PERMITHAS BEEN ISSUED (I.E. UNDERGROUND FIRE LINE, SPRINKLER SYSTEM, FIRE ALARM SYSTEM,STANDPIPE, FIRE PUMP ROOM, AND FIRE PROTECTION WATER SUPPLY SYSTEMS)
AUTOMATIC FIRE SPRINKLER SYSTEM/ALTERNATIVE AUTOMATIC FIREEXTINGUISHING SYSTEMALL SPRINKLERS SHALL COMPLY WITH MONITORING(SECTION 903 HC FIRE CODE AMENDMENTS & SECTION 903.4 IFC 2012)
PROVIDED AS NOTED ON: __________ NOT REQUIRED PER SECTION 903
SYSTEM PROVIDED:NFPA 13NFPA 13RNFPA 13DOTHER: __________
STANDARDELOESFRQUICK RESPONSE
SPRINKLER HEAD PROVIDED:
FIRE DEPARTMENT ACCESS TO SPRINKLER CONTROLS:SPRINKLER RISER ROOM OR POST INDICATOR VALVE SHOWN ON: __________(SECTION 901.4.6.1 HC AMENDMENTS IFC 2012)
FDC SHOWN ON: __________ (FDC SHALL COMPLY WITH SECTION 912 IFC 2012)
SUPPRESSION SYSTEM PROVIDED (SECTION 904 IFC 2012)REQUIRED AND SHOWN ON: __________
STANDPIPE SYSTEM & HOSE CONNECTIONS (SECTION 905 IFC 2012)(I.E. IN STAIRWAYS, STAGES, MALLS)
PROVIDED AS NOTED ON: __________, TYPE OF SYSTEM PROVIDED: _________ (CLASS I, II OR III)NOT REQUIRED PER SECTION 905
PORTABLE FIRE EXTINGUISHERS (SECTION 906 IFC 2012)PROVIDED AS NOTED ON: __________, NUMBER PROVIDED: __________ (HIGHLIGHT ON PLANS)
FIRE ALARM & DETECTION SYSTEMS (SECTION 907 & HC AMENDMENTS IFC 2012)FIRE ALARM SYSTEM (DEFERRED SUBMITTAL)
EMERGENCY VOICE EVACUATION
DEDICATED FUNCTION (SPRINKLERMONITORING, ELEVATOR RECALL,PRE-ACTION, EMERGENCY ALARM,SMOKE CONTROL)
OTHER: ________________________
HVAC & AIR DISTRIBUTION SYSTEM CONTROLS (SECTION 907.2.13.1.2 IFC 2012)SMOKE DETECTORS PROVIDED TO SHUT DOWN UNITS OVER 2,000 CFM PROVIDED ON: __________
FIRE/SMOKE DAMPERS IN THE BUILDING SHOWN ON: __________NO FIRE/SMOKE DAMPERS IN THE BUILDING
SMOKE CONTROL SYSTEMS (SECTION 909 IFC 2012)(I.E. FOR HIGH RISE, ATRIUMSOR STAIRWAY PRESSURIZATION)
PROVIDED AS NOTED ON: __________
NOT REQUIRED PER SECTION 909
SMOKE & HEAT VENTILATION (SECTION 910 & TABLE 910.3 IFC 2012)CALCULATIONS PROVIDED AS NOTED ON: __________NOT REQUIRED PER SECTION 910
NOTE: WHERE AREAS OF THE BUILDING ARE EQUIPPED WITH EARLY SUPPRESSION FAST-RESPONSE(ESFR) SPRINKLERS, AUTOMATIC SMOKE AND HEAT VENTS SHALL BE INSTALLED PERMANUFACTURERS SPECIFICATIONS, MEETING LOCAL JURISDICTION REQUIREMENTS.
SHOW DETAILS OF FIRE WALLS OR FIRE BARRIERS MEETING HORIZONTAL WALLS AND ROOF DECKS(SEE SECTION 706.5, 706.6 & 707.5 IBC 2012)
FIRE-RESISTANCE RATING REQUIREMENTS (TABLES 601, 602 & 602.4 IBC 2012)
HOURSPROVIDED
HOURSREQUIREDBUILDING ELEMENTS UL OR IBC STANDARD USED &
DESIGN DETAIL SHOWN ONSTRUCTURAL FRAME
EXTERIOR BEARING WALLS
EXTERIOR NON-BEARING WALLS
INTERIOR BEARING WALLS
INTERIOR NON-BEARING WALLS
FLOOR CONSTRUCTION
ROOF CONSTRUCTION
STAIRWELLS (SECTION 1009)
CORRIDORS (SECTION 1018)
ELEVATOR SHAFTS (SECTION 713)
FIRE RATED DOORS (TABLE 716.5)
DEMISING/PARTITION WALL (SECTION 708)
FIRE BARRIER (SECTION 707)
FIRE WALL (SECTION 706)
DRAFTSTOPS: YES, SHOWN ON: __________ NO (SPRINKLED ATTIC) N/A (SECTION 718.4)
HAVE YOU CHECKED WIDTH OF OPENINGS IN FIRE RATED WALLS?(TABLE 705.8, SECTION 706.8 & 707.6 IBC 2012)
YES NO
FIRE SEPARATION DISTANCE (FEET)(SECTION 602 IBC 2012)
NORTH SOUTH EAST WEST
ROOF COVERING CLASSIFICATION PROVIDED:(TABLE 1505.1 IBC 2012)
A B C
WATER SUPPLY (FOR FIREFIGHTING)6CHAPTER 5, APPENDIX B & C IFC 2012
__________ GROSS SIZE OF BUILDING IN SQUARE FEET (INCLUDE ALL OVERHANGS UNDER ROOF)
PUBLIC WATER SUPPLY WITH FIRE HYDRANTS(FOR PROPOSED AND EXISTING FIRE HYDRANTS ONLY)NAME OF THE MUNICIPAL UTILITY DISTRICT: ________________________________________________NUMBER OF HYDRANTS WITHIN 400 FT (NON-SPRINKLED) OR 600 FT (SPRINKLED) OF BUILDING: __________,SHOWN ON: __________REQUIRED GPM: __________ DURATION: __________ (TABLE B105.1 IFC 2012)
75% REDUCTION? YES NO (MUST MAINTAIN MINIMUM OF 1,500 GPM)
WATER SOURCE FOR RURAL AREAS WITHOUT FIRE HYDRANTS(COMPLETE THE FIRE FLOW CALCULATOR)
***DRY HYDRANTABOVEGROUND STORAGE
UNDERGROUND STORAGEOTHER: _________________________
DESIGN SPECIFICATIONS AND LOCATIONS SHOULD MEET MINIMUM REQUIRED WATER SUPPLY FROM THEFIRE FLOW CALCULATOR NFPA 1142 (http://hcpid.org/permits/docs/FC_fire_flow_calculator.pdf).
***SUBMIT DRY HYDRANT DESIGN PLANS & CALCULATIONS TO FIRE PROTECTION FOR REVIEW &APPROVAL (http://hcpid.org/permits/docs/FC_dry_hydrant_worksheet.pdf)
FIRE LANE ACCESS7CHAPTER 5 & APPENDIX D IFC 2012
FIRE LANE LAYOUT PLAN, WHICH SHALL INCLUDE THE SITE PLAN, THE FIRE LANE & FIRE HYDRANTS, ISSHOWN ON: __________. (HIGHLIGHT THE FIRE HYDRANT LOCATIONS ON THE PLANS) AERIAL ACCESSLAYOUT, FOR BUILDINGS OVER 30 FT, IS SHOWN ON: __________.
FIRE LANES WILL BE APPROVED CONCEPTUALLY DURING THE CIVIL REVIEW PROCESS. HOWEVER, THEFIRE CODE PLAN REVIEWER MAY CHANGE THE FIRE LANE LAYOUT BASED ON THE BUILDINGSPECIFICATIONS.
PROVIDING A DRY STANDPIPE/WALL HYDRANT OR REMOTE FIRE HOSE CONNECTION TO COMPLY WITHFIRE LANE HOSE COVERAGE. SUBMIT PLANS TO FIRE PROTECTION FOR REVIEW (SECTION 915.1 HCAMENDMENTS)
FIRE LANE LAYOUT, GENERAL REQUIREMENTS & APPROVED SIGN(http://hcpid.org/permits/docs/FC_firelane_layout_gen_req_and_approved_sign.pdf)
INTERIOR FINISH8CHAPTER 8 & TABLE 803.9 IBC 2012
ROOMS AND ENCLOSEDSPACES
EXIT ENCLOSURES ANDEXIT PASSAGEWAYS
OCCUPANCYGROUP SHEET #CORRIDORS
PRODUCTS BEING STORED: ____________________________________________________YES NOSTORAGE PACKAGING (I.E. PALLETS, RACKS, SOLID PILED, DRUMS, CARDBOARD BOXES, WRAPPEDIN PLASTIC, ETC.): ____________________________________________________________________________
YES NO
MAXIMUM HEIGHT OF COMMODITY: ____________________________________________________YES NO***THIS BUILDING IS DESIGNED FOR THE INTENT OF HIGH PILED STORAGE. IF YES, THENPROVIDE HIGH PILED STORAGE FORM (http://hcpid.org/permits/docs/FC_high_piled_storage_form.pdf).
YES NO
FIRE DEPARTMENT ACCESS DOORSYES NOHIGH PILED STORAGE RACK LAYOUT/ELEVATIONS, CODE ANALYSIS, ETC. SHOWN ON: __________NO
HAZARDOUS MATERIALS10CHAPTER 50 IFC 2012
***THIS BUILDING IS DESIGNED FOR THE INTENT OF HAZARDOUS MATERIAL STORAGE. IF YES,THEN PROVIDE ALL HMIS SUMMARY AND MSDS REPORTS.
YES NO
EMERGENCY ALARM SYSTEM REQUIRED PER SECTION 5004.9 IFC 2012YES NO
YES
VENTILATION WITH EMERGENCY ALARM STAND BY POWER PER SECTION 5004.3 AND 5004.7 IFC 2012.NOYESSPILL CONTROL AND SECONDARY CONTAINMENT PER SECTION 5004.2 IFC 2012YES NO
SPECIAL CONDITIONS11PROPERTIES WITH FENCE AND GATES SHALL PROVIDE A 911 KEY BOX AT ENTRY GATE
ATRIUM(S) PER 404 IBC 2012?YES NO PAINT SPRAY BOOTHS, COATINGS,DIPPING OR INDUSTRIAL OVENS USEDPER 2404, 2405, 2406 AND CHAPTER 30 IFC2012?
YES NOYES NO HIGH RISE BLDG PER 403 IBC 2012?YES NO ANY FUEL STORAGE TANKS PER
5704 IFC 2012?YES NO SEPTIC SYSTEM? SUBMIT PLANS
TO WASTEWATER FOR REVIEW.YES NOYES NO
YES NO HEALTH DEPARTMENT APPROVAL?REQUIRED FOR ALL ESTABLISHMENTSTHAT SERVE/PREPARE FOOD ANDBEVERAGES FOR THE PUBLIC OR HAVEREFRIGERATED FOOD STORAGE.
YES NO MEDICAL GAS PER 5306 IFC 2012?YES NO
PUBLIC UTILITIES?
CERTIFICATION
PERMIT OFFICE
REVIEWER'S SIGNATURE BLOCK
THE PROJECT KNOWN AS(MUST BE THE NAME OF BUSINESS/DBA IF BUILDING IS FOR A SPECIFIC COMPANY)
PROJECT NUMBER: IFC 2012
COMMENTS & NOTES
A COPY OF THESE APPROVED CONSTRUCTION PLANS MUST BE KEPT AT PROJECT SITE FORTHE FINAL INSPECTION OF THE BUILDING
(http://www.hcad.org)
(http://www.eng.hctx.net/permits/Fire/Fire-Code/Fire-Code-Review)
SHEET NO.(S)DATE DESCRIPTION REVIEWER COUNTY P.E. FIRE CODEREVIEW
SHEET NUMBER
________ OF ________
WAS ACCEPTED BY HARRIS COUNTY FOR THE PURPOSES LISTED BELOW:
REVIEWER'S STAMP
CRITICAL FACILITIES (HARRIS COUNTYREGULATIONS AND AMENDMENTS)FIRE PUMP EMERGENCY STANDBYPOWER PER 913.8 HC AMENDMENTS?
MIXED OCCUPANCY
NO HVAC UNITS OVER 2,000 CFM
YES NO OTHER: __________________________
RESIDENTIAL BOARD AND CARE OCCUPANCIES (REFER TO THE HARRIS COUNTY CODEWORD OF THESAME NAME AND ALSO COMPLETE THE RESIDENTIAL BOARD AND CARE CERTIFICATION FORM
RBC-8A RBC-8B RBC-16A RBC-16B
NOT REQUIRED PER SECTION 907
NOT REQUIRED
I-45 NORTH
TO HOUSTON
F
.M
. 2
9
2
0
S
P
R
IN
G
S
T
U
E
B
N
E
R
W
E
S
T
G
R
A
N
D
P
A
R
K
W
A
Y
SPRING
STUEBNER EAST
RILEY FUZZELL
SPRING
CYPRESS
ALD
IN
E W
ES
TF
IE
LD
LOUETTA
CYPRESSWOOD
OH
E
OHEOHE
OHEOHE OHE
//
//
//
//
//
OHE OHE OHE OHE OHE OHE
OH
EO
HE
OH
EO
HE
OH
EO
HE
OH
EO
HE
THE UTILITY COMPANIES AND TO VERIFY THE EXISTING
PRIVATE AND PUBLIC UTILITIES FROM DAMAGE.
CONSTRUCTION. THE CONTRACTOR SHALL PROTECT ALL
LOCATION AND DEPTH OF THE UTILITIES PRIOR TO ANY
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO NOTIFY
LOCAL CODES, STANDARD SPECIFICATIONS, AND DRAWING
ALL WORK TO BE COMPLETED IN ACCORDANCE WITH ALL
OR REPLACE THE DAMAGED WORK TO ITS ORIGINAL
CONDITION-AT THE CONTRACTORS EXPENSE.
WHICH IS TO REMAIN - THEN THE CONTRACTOR SHALL REPAIR
THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE
AGENTS SHOULD DAMAGE OR DESTROY ANY EXISTING WORK
DURING THE COURSE OF WORK - IF THE CONTRACTOR OR ITS
KEEP SITE CLEAN AND SECURE AT ALL TIMES.
REMOVE ALL DEBRIS FROM SITE AND DISPOSE CORRECTLY.
PROJECT DATES
REQUIREMENTS.
OWNER PRIOR TO COMMENCING THE WORK.
5.
4.
3.
VICINITY MAP
GENERAL NOTES
2.
1.
BUILDING CODE AND DATA
INDEX OF DRAWINGS:
SITE PLAN
ENGINEER'S LICENSE SEAL, SIGNATURE & DATE.
COVER SHEETCS1
PROJECT SCOPE
12345
A1.10
ARCHITECTURAL
(NOT TO SCALE)
01-01-20 ISSUED FOR PERMIT REVIEW
SYMBOLS AND ABBREVIATIONSCS2
ACCESSIBILITY STANDARDSCS3
FLOOR PLAN & DETAILS
COVER SHEET
CS1
SCALE = AS NOTED 1COVER SHEET
JOB LOCATION
NEW CONSTRUCTION SHELL BUILDING
SHEET TITLE
DRAWN BY: MJM
PROJECT NO: 080717
CHECKED BY : SB
PROJECT TITLE
01-01-20 PERMIT DRAWINGS
SHEET NUMBER
1
MALONEY SERVICES L.L.C. 2020. THIS OFFICE ASSUMES NO
LIABILITY FOR ERRORS OR OMISSIONS ON THESE PLANS. ALL
INFORMATION MUST BE CONFIRMED PRIOR TO
COMMENCEMENT OF CONSTRUCTION. IT IS THE OWNERS AND
BUILDERS RESPONSIBILITY FOR FOLLOWING MATERIAL AND
MANUFACTURERS INSTRUCTIONS, AND USING RECOGNIZED
STANDARDS FOR EACH TRADE, AS WELL AS COMPLIANCE IN
FULL WITH ALL GOVERNING CODE REQUIREMENTS FOR THE
GEOGRAPHIC AREA IN WHICH THIS PROJECT IS TO BE
CONSTRUCTED.
PROJECT DESCRIPTION:
NEW CONSTRUCTION OF METAL BUILDING / OFFICE WAREHOUSE - TENANT
UNSPECIFIED
BUILDING CODES TO BE FOLLOWED
ALL DRAWINGS & CONSTRUCTION SHALL COMPLY
WITH THE INTERNATIONAL BUILDING
CODE 2012 ED.
2012 INTERNATIONAL FIRE CODE
OCCUPANCY USE: SHELL ONLY - 7,200 S.F. TOTAL
OCCUPANCY LOAD: SEE FIRE CODE REVIEW SHEET
CONSTRUCTION TYPE:
TYPE IIB
SPRINKLED:
NO
SQUARE FOOTAGE:
7,200
C-4.0 SITE PLAN
A1.20 BUILDING ELEVATIONS
BLDG "A" BLDG "B" BLDG "C"
BLDG "D"BLDG "E"
BLDG "F"
ALD
IN
E W
ES
TF
IE
LD
PROVIDE FIRE BLOCKING WHERE WALLS INTERSECT FURR DOWNS AND
COMBUSTIBLE FRAMING. SPACE NO FARTHER THAN 10'-0" APART AND
AND LOCATE 2X FIRE BLOCKING AT ALL CONCEALED SPACES WITH
PROVIDE AS REQUIRED BY GOVERNING AUTHORITIES HAVING JURISDICTION
CONTRACTOR SHALL PROVIDE PROOF TO OWNER THAT ADEQUATE
CONTRACTOR WILL BE HELD RESPONSIBLE FOR STUDYING DRAWINGS,
TO HAVE VISITED THE SITE, AND TO HAVE SATISFIED HIMSELF
REGARDING ALL EXISTING CONDITIONS UNDER WHICH HE WILL BE
CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING
AND NEW WORK. ANY WORK DAMAGE FOR ANY REASON SHALL BE
SUBSTITUTIONS, REVISIONS OR CHANGES MAY BE ALLOWED ONLY IF
SUCH ITEMS ARE SUBMITTED TO THE OWNER IN A TIMELY MANNER IN
WRITING AND SUBSEQUENTLY APPROVED BY THE ARCHITECT IN DESIGN
AND PERFORMANCE. THE CONTRACTOR IS LIABLE FOR REPLACEMENT,
REPAIR AND DELAYS CAUSED BY ANY UNAUTHORIZED SUBSTITUTION,
AND COMPLETE SPECIFICATIONS AND DRAWINGS AS REQUIRED
COMPARING ITEMS. THE OWNER RESERVES THE RIGHT TO REJECT
UNLESS NOTED OTHERWISE, REFER TD THE EQUIPMENT DRAWINGS AND
SPECIFICATIONS FOR ALL KITCHEN EQUIPMENT WORK. KITCHEN
WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS.
CONTRACTOR SHALL INSTALL ROUGH BLOCKING OR WOOD NAILERS
DURING THE ROUGH FRAMING STAGE OF CONSTRUCTION AS REQUIRED
FOR PROPERLY SECURING WALL CABINETS, SHELVING, LIGHTING AND
ELECTRICAL FIXTURES, WALL MOUNTED EQUIPMENT, MILLWORK,
APPLIED DECORATIVE TREATMENTS, AND HANDRAIL BRACKETS.
WHERE DISCREPANCIES EXIST IN DRAWINGS THE CONTRACTOR SHALL
NOTIFY THE OWNER IMMEDIATELY AND IF HE FAILS TO DO SO IT
WILL BE HIS RESPONSIBILITY TO CORRECT THE SITUATION REASONABLY
AS PER THE OWNER DIRECTION ENLARGED SCALE DRAWINGS
/DETAILS SHALL GOVERN OVER SMALLER SCALED DRAWINGS AND
AXX.XX
AXX.XX
CONTRACTOR SHALL SUPERVISE THE WORK AND COORDINATE ALL 7.
ALL MATERIALS AND EQUIPMENT INCORPORATED IN THE WORK SHALL
BE NEW UNLESS OTHERWISE SPECIFIED AND ALL WORK SHALL BE OF
GOOD QUALITY, FREE FROM FAULTS AND IN CONFORMANCE WITH THE
WOOD SHALL BE NEW UNLESS SPECIFIED AS "USED" OR "BARNWOOD.
CONTRACTOR SHALL KEEP THE PREMISES FREE FROM ACCUMULATION
OF WASTE MATERIALS OR RUBBISH CAUSED BY HIS OPERATIONS. AT
THE COMPLETION OF THE WORK HE SHALL PERFORM A FINAL CLEAN-UP
INSIDE, CLEAN ALL GLASS SURFACES AND LEAVE THE WORK ROOM
CONTRACTOR SHALL GUARANTEE FOR (1) ONE YEAR THAT ALL OF THE
WORK UNDER THE CONTRACT IS FREE FROM FAULTY MATERIALS,
WATER-TIGHT, AND LEAK PROOF IN EVERY PARTICULAR AND FREE FROM
AXX.XX
AXX.XX
AXX.XX
USED WOOD SHALL BE SUPPLIED BY OWNER.
IMPROPER WORKMANSHIP.
CLEAN.
11.
PORTIONS THEREOF.
PLANS.
10.
9.
8.
CEILINGS, AND WHERE INDICATED ON THE DRAWINGS
DRAFT STOPS & FIRE BLOCKING:
SPECIFICATIONS SHALL GOVERN ALL.
19A.
19.
17.
18.
UTILITY TAP FEES. G.C. SHALL PAY FOR REMAINING PERMITS & FEES.
ALL WORK PERFORMED SHALL BE IN STRICT ACCORDANCE WITH ALL
BEFORE PERFORMING ANY WORK OR ORDERING ANY MATERIALS, THE
CONTRACTOR SHALL VERIFY ALL DIMENSIONS OF ANY EXISTING OR
NEW WORK AND SHALL BE RESPONSIBLE FOR THEIR ACCURACY, ANY
DIFFERENCES FOUND SHALL BE SUBMITTED TO THE ARCHITECT FOR
OWNER SHALL PAY FOR GENERAL BUILDING PERMIT, IMPACT FEES &
CONTRACTOR SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
FIXTURES, AND SERVICE NECESSARY FOR THE PROPER EXECUTION OF
CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACTS AND OMISSIONS
APPLICABLE CODES, REGULATIONS AND ORDINANCES HAVING
CONSIDERATION BEFORE PROCEEDING WITH THE WORK. THE
CONTRACTOR SHALL ALSO VERIFY THE LOCATION OF EXISTING
UTILITIES PRIOR TO BEGINNING WORK.
UTILITIES SHALL BE PROVIDED BY CONTRACTOR.
OF ALL HIS EMPLOYEES AND SUBCONTRACTORS.
THE PLANS.
6.
4.
5.
3.
JURISDICTION.
2.
1.
DRAWINGS GOVERN FOR ALL CRITICAL DIMENSIONS.
LIABILITY INSURANCE HAS BEEN OBTAINED.
OBLIGED TO OPERATE.
REPLACED AT NO COST TO THE OWNER.
FOR ANY REASON.
16.
15.
14.
13.
12.
NOT USED
PROVIDE VAPOR RETARDER WITH A MAX. PERF OF ONE
PROVIDE GALVANIZED STRAP MASONRY TIES AT 16" O.C. EACH WAY.
CERTIFIED TEST & BALANCE REPORT IS REQUIRED BY LOCAL AUTHORITY.)
ALL GYPSUM BOARD TO BE 5/8' TYPE 'X' UNLESS NOTED OTHERWISE. IN
DAMP AREAS GREEN GYPSUM SHALL BE USED IN LIEU OF GYP. BOARD.
IN WET AREAS DUR-ROCK OR CONC./MESH BD. SHALL BE USED.
ALL WORK ON THIS PROJECT SHALL BE IN CONFORMANCE WITH THE
1.STATE AND LOCAL BUILDING CODE LATEST EDITION
2.NATIONAL FIRE CODES: BY NFPA
3.NATIONAL ELECTRICAL CODE (LATEST EDITION)
5.NATIONAL SANITATION FOUNDATIONS (N.S.F.)
6.OCCUPATIONAL SAFETY AND HEALTH STANDARDS - 1910, CHAPTER
XVII OF TITLE 20, CODE OF FEDERAL REGULATIONS.
7.REGULATIONS BY UTILITY COMPANIES SUPPLYING UTILITIES TO THE
PROJECT, BOTH TEMPORARILY AND PERMANENTLY.
8.COMPRESSED GAS ASSOCIATION (C.G.A.)
9.FIRE RESISTANCE RATINGS: BY AMERICAN INSURANCE ASSOCIATION.
CONTRACTOR TO BALANCE SYSTEM FOR ADEQUATE AIR DISTRIBUTION
WITHIN ALL CONDITIONED AREAS TO THE OWNER'S SATISFACTION. (UNLESS
CONTRACTOR SHALL SUBMIT ALL WOOD STAIN AND SPECIALTY FINISHES
SAMPLES TO THE ARCHITECT AND OWNER FOR APPROVAL PRIOR TO
FINAL FINISHING. IF FAILURE TO SUBMIT SAMPLES FOR APPROVAL THE
CONTRACTOR WILL BE RESPONSIBLE FOR REFINISHING TO THE
ARCHITECT AND OWNER'S SATISFACTION.
CONTRACTOR SHALL REPAIR WALLS AND EQUIPMENT DAMAGED DURING
CONTRACTOR SHALL COMPLY WITH ALL THE REQUIREMENTS AS STATED
IN THE AIA A201 GENERAL CONDITIONS OF THE CONTRACT FOR
CONSTRUCTION, 1987 EDITION, UNLESS WRITTEN AUTHORIZATION IS
1. ART CONSULTING
CONTRACTOR SHALL COORDINATE ALL DELIVERIES AND ACCESSIBILITY
TO BUILDING FOR ALL ITEMS SUCH AS, BUT NOT LIMITED TO THE
FOLLOWING' FURNITURE, FIXTURES, EQUIPMENT, ACCESSORIES.
PRIOR TO STARTING CONSTRUCTION THE GENERAL CONTRACTOR SHALL
BE RESPONSIBLE TO VERIFY THAT ALL REQUIRED PERMITS AND
APPROVALS HAVE BEEN OBTAINED. NO CONSTRUCTION OR FABRICATION
OF ANY ITEM SHALL BEGIN UNTIL THE CONTRACTOR HAS RECEIVED ALL
PLANS AND ANY OTHER APPROVALS FROM GOVERNMENTAL AGENCIES
OR OTHER REGULATORY AUTHORITIES HAVING JURISDICTION OVER THE
PROJECT. FAILURE OF THE CONTRACTOR TO FOLLOW THIS PROCEDURE
SHALL CAUSE THE CONTRACTOR TO ASSUME FULL RESPONSIBILITY FOR
ANY SUBSEQUENT MODIFICATION OF THE WORK MANDATED BY ANY
2. SPECIALTY LIGHTING
3. KITCHEN EQUIPMENT
REGULATORY AUTHORITY.
26.
25.
35.
34.
33.
32.
31.
AT THE WARM SIDE OF INSULATION.
CONSTRUCTION AS REQUIRED.
OBTAINED BY THE ARCHITECT.
SHOP DRAWINGS SHALL BE SUBMITTED TO THE OWNER FOR APPROVAL
PRIOR TO FABRICATION OF ANY ITEM. FAILURE TO ADHERE TO THIS
PROCEDURE SHALL PLACE FULL RESPONSIBILITY FOR ANY ERRORS
UNLESS OTHERWISE NOTED, ALL DIMENSIONS ARE TO STUD
THE SUBMISSION OF A BID OR PROPOSAL WILL BE CONSTRUED AS
EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED HIMSELF WITH
THE PLANS AND EXISTING CONDITIONS OF THE BUILDING SITE. CLAIMS
MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR
BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF
THEY COULD HAVE BEEN FORESEEN HAD PROPER EXAMINATION BEEN
ALL WOOD PLATFORMS ARE TO HAVE FIRE BLOCK SEPARATION
CONTRACTOR TO COORDINATE ALL WORK WITH OWNER'S
CONSULTANTS AND OWNER'S CONTRACTORS OF EACH SPECIALTY AREA.
SUCH SPECIALTY AREAS SHALL INCLUDE BUT NOT LIMITED TO THE
DIRECTLY UPON THE CONTRACTOR.
FRAMING.
WALLS FOR EVERY 100 SQUARE FEET.
FOLLOWING:
24.
23.
MADE.
22.
21.
20.
30.
29.
28.
27.
4.NATIONAL PLUMBING CODE
FOLLOWING
ANY ROOM THAT IS USED FOR AN ASSEMBLY PURPOSE WHERE FIXED 36.
SEATS ARE NOT INSTALLED SHALL HAVE THE CAPACITY OF THE ROOM POSTED
IN A CONSPICUOUS PLACE ON AN APPROVED SIGN NEAR THE MAIN EXIT OR
EXIT-ACCESS DOORWAY FROM THE ROOM. SUCH SIGNS SHALL INDICATE THE
NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM USE.
SYMBOLS &
ABBREVIATIONS
CS2
SHEET TITLE
DRAWN BY: MJM
PROJECT NO: 080717
CHECKED BY : SB
PROJECT TITLE
01-01-20 PERMIT DRAWINGS
SHEET NUMBER
1
MALONEY SERVICES L.L.C. 2020. THIS OFFICE ASSUMES NO
LIABILITY FOR ERRORS OR OMISSIONS ON THESE PLANS. ALL
INFORMATION MUST BE CONFIRMED PRIOR TO
COMMENCEMENT OF CONSTRUCTION. IT IS THE OWNERS AND
BUILDERS RESPONSIBILITY FOR FOLLOWING MATERIAL AND
MANUFACTURERS INSTRUCTIONS, AND USING RECOGNIZED
STANDARDS FOR EACH TRADE, AS WELL AS COMPLIANCE IN
FULL WITH ALL GOVERNING CODE REQUIREMENTS FOR THE
GEOGRAPHIC AREA IN WHICH THIS PROJECT IS TO BE
CONSTRUCTED.
ACCESSIBILITY CRITERIA NOT SHOWN HERE.
THE INFORMATION ON THIS SHEET IS NOT "ALL-INCLUSIVE" OF THE ACCESSIBILITY STANDARD
REQUIREMENTS INDICATED. THE CONTRACTOR SHALL REFER TO SAID STANDARDS FOR
ACCESSIBLE STANDARDS:
DOOR CLEARANCES
GENERAL NOTES DRINKING FOUNTAINS
MIN. CLEAR FLOOR SPACESCURB RAMPS AND PARKING -
SITE DRAWINGS
REFER TO
STANDARD CABINET SECTION RAMPS
ACCESSIBLE SYMBOL-
BATHROOM FIXTURES, LAVATORY AND SINK CLEARANCES
ACCESSIBLE PARKING SIGNREACH RANGES
PARKING STALL
ACCESIBILITY
STANDARDS
CS3
SCALE = AS NOTED 1
SHEET TITLE
DRAWN BY: MJM
PROJECT NO: 080717
CHECKED BY : SB
PROJECT TITLE
01-01-20 PERMIT DRAWINGS
SHEET NUMBER
1
MALONEY SERVICES L.L.C. 2020. THIS OFFICE ASSUMES NO
LIABILITY FOR ERRORS OR OMISSIONS ON THESE PLANS. ALL
INFORMATION MUST BE CONFIRMED PRIOR TO
COMMENCEMENT OF CONSTRUCTION. IT IS THE OWNERS AND
BUILDERS RESPONSIBILITY FOR FOLLOWING MATERIAL AND
MANUFACTURERS INSTRUCTIONS, AND USING RECOGNIZED
STANDARDS FOR EACH TRADE, AS WELL AS COMPLIANCE IN
FULL WITH ALL GOVERNING CODE REQUIREMENTS FOR THE
GEOGRAPHIC AREA IN WHICH THIS PROJECT IS TO BE
CONSTRUCTED.
160'-0"
45
'-0
"
PARKING AREA
12'X12' OVERHEAD
DOOR
12'X12' OVERHEAD
DOOR
12'X12' OVERHEAD
DOOR
12'X12' OVERHEAD
DOOR
EXIT SIGN W/ LIGHTS AND
BATTERY BACK-UP POWER
EMERGENCY EXIT LIGHTS WITH
BATTERY BACK-UP POWER
EXTERIOR RATED
WALL MOUNTED FIRE
EXTINGUISHER
FLOOR PLAN &
DETAILS
A1.10
SCALE: 1/8"=1'-0" 1FLOOR PLANDOOR DETAILS SCALE: NTS 3
LEGEND AND WALL DETAILS
SHEET TITLE
DRAWN BY: MJM
PROJECT NO: 080717
CHECKED BY : SB
PROJECT TITLE
01-01-20 PERMIT DRAWINGS
SHEET NUMBER
1
MALONEY SERVICES L.L.C. 2020. THIS OFFICE ASSUMES NO
LIABILITY FOR ERRORS OR OMISSIONS ON THESE PLANS. ALL
INFORMATION MUST BE CONFIRMED PRIOR TO
COMMENCEMENT OF CONSTRUCTION. IT IS THE OWNERS AND
BUILDERS RESPONSIBILITY FOR FOLLOWING MATERIAL AND
MANUFACTURERS INSTRUCTIONS, AND USING RECOGNIZED
STANDARDS FOR EACH TRADE, AS WELL AS COMPLIANCE IN
FULL WITH ALL GOVERNING CODE REQUIREMENTS FOR THE
GEOGRAPHIC AREA IN WHICH THIS PROJECT IS TO BE
CONSTRUCTED.
SCALE: NTS 2
1 HR. FIRE RATED WALL
1 HR. FIRE RATED WALL
160'-0"
16'-0"
21
'-5
"
2/12 COMMON PITCH METAL ROOF TYP.
45'-0"
16
'-0
"
120'-0"
16'-0"
21'-5"
2/12 COMMON PITCH METAL ROOF TYP.
45'-0"
16
'-0
"
BUILDING
ELEVATIONS
A1.20
SCALE: 1/8"=1'-0" 1SOUTH ELEVATION
SHEET TITLE
DRAWN BY: MJM
PROJECT NO: 080717
CHECKED BY : SB
PROJECT TITLE
01-01-20 PERMIT DRAWINGS
SHEET NUMBER
1
MALONEY SERVICES L.L.C. 2020. THIS OFFICE ASSUMES NO
LIABILITY FOR ERRORS OR OMISSIONS ON THESE PLANS. ALL
INFORMATION MUST BE CONFIRMED PRIOR TO
COMMENCEMENT OF CONSTRUCTION. IT IS THE OWNERS AND
BUILDERS RESPONSIBILITY FOR FOLLOWING MATERIAL AND
MANUFACTURERS INSTRUCTIONS, AND USING RECOGNIZED
STANDARDS FOR EACH TRADE, AS WELL AS COMPLIANCE IN
FULL WITH ALL GOVERNING CODE REQUIREMENTS FOR THE
GEOGRAPHIC AREA IN WHICH THIS PROJECT IS TO BE
CONSTRUCTED.
SCALE: 1/8"=1'-0" 2
EAST ELEVATION
SCALE: 1/8"=1'-0" 3
WEST ELEVATION SCALE: 1/8"=1'-0" 4
NORTH ELEVATION
1 HR. FIRE RATED WALL
1 HR. FIRE RATED WALL
SITE PLAN
SP1.10
SCALE: 1"=25'-0" 1SITE PLAN
SHEET TITLE
DRAWN BY: MJM
PROJECT NO: 080717
CHECKED BY : SB
PROJECT TITLE
01-01-20 PERMIT DRAWINGS
SHEET NUMBER
1
MALONEY SERVICES L.L.C. 2020. THIS OFFICE ASSUMES NO
LIABILITY FOR ERRORS OR OMISSIONS ON THESE PLANS. ALL
INFORMATION MUST BE CONFIRMED PRIOR TO
COMMENCEMENT OF CONSTRUCTION. IT IS THE OWNERS AND
BUILDERS RESPONSIBILITY FOR FOLLOWING MATERIAL AND
MANUFACTURERS INSTRUCTIONS, AND USING RECOGNIZED
STANDARDS FOR EACH TRADE, AS WELL AS COMPLIANCE IN
FULL WITH ALL GOVERNING CODE REQUIREMENTS FOR THE
GEOGRAPHIC AREA IN WHICH THIS PROJECT IS TO BE
CONSTRUCTED.
*
EXISTING FIRE HYDRANT
*
EXISTING FIRE HYDRANT 132' FROM PROPERTY LINE
*
EXISTING FIRE HYDRANT 125' FROM PROPERTY LINE
*
NEW FIRE HYDRANT
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM
1 HR FIRE RATED
WALL SYSTEM