Final Experiment 5_1

download Final Experiment 5_1

of 25

Transcript of Final Experiment 5_1

  • 8/6/2019 Final Experiment 5_1

    1/25

    CHEMICAL ENGINEERING LABORATORY II

    1.0 TITLE OF EXPERIMENT: Temperature Process Control.

    2.0 OBJECTIVES OF EXPERIMENT

    The objective of this experiment is to demonstrate and understand the characteristic

    of proportional (P), proportional integral (PI) and proportional-integral-derivative

    (PID) controller in a temperature control loop. Besides that, the objective of this

    experiment is also to observe the different types of temperature responses to P, PI,

    and PID controller.

    3.0 INTRODUCTION

    Temperature process control is a process of where the temperature of the fluid is

    changed in order to be measured, as the heat energy in or out of the space is adjusted

    to achieve a desired average or optimum temperature. The temperature control

    system consists of a heat exchanger, a sensor, a controller and a control panel. The

    controller is used for maintaining the temperature measuring the process variable at a

    particular set. In this experiment, a circulation pump transfers water within a closed

    circuit in order to allow water to experience heat exchange between the hot and cold

    water. The water flow is controlled by an actuator, taking place automatically should

    any deviation occurs from the set point with the supply of compressed air.

    A proportionalintegralderivative controller (PID controller) is a control

    loop feedback mechanism, which is able to minimize errors of the values by

    adjusting the process control inputs. The output of a PID controller is a linear

    combination of P, I, and D modes of control. The proportional controller, or P

    controller, is a linear type of feedback control system and is more complex than an

    on-off control system, but simpler than a proportional-integral-derivative (PID)

    control system. However, the P-only controller still has some amount of offset away

    from the set point. Therefore, with the addition of an extra controlling system, the

  • 8/6/2019 Final Experiment 5_1

    2/25

    integral controller, forming the proportional-integral (PI) control. The integral action

    will attempt to avoid or minimize the offset created in the proportional control by

    bringing the output closer to the set point. PID control system is a linear combination

    of P, I and the derivative (D) which permits an increase in the proportional gain,

    offsetting the decrease error from the integral controlling. The derivative action

    reduces the period of cycling, yet producing the same speed of response as with the

    proportional action but without offsets.

    PI controller offers a balance of complexity and capability that makes them

    popular in many process control applications due to the integral action that enables

    PI controllers to eliminate offsets.

    4.0 MATERIALS AND EQUIPMENT

    Figure 4.1: Schematic Diagram of Temperature Control Unit / Trainer.

  • 8/6/2019 Final Experiment 5_1

    3/25

    5.0 RESULTS AND CALCULATIONS

    Experiment 1: Closed Loop Proportional (P) Control

    Variable= P Value

    Constant = I Value (600 s) and D Value (0 s)

    Table 5.1: Load Change (PB = 5)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 14:10:11 45.0 45.0 12.4

    23/03/2011 14:10:13 45.1 45.0 11.8

    23/03/2011 14:10:43 43.2 45.0 49.7

    23/03/2011 14:11:13 43.1 45.0 50.1

    23/03/2011 14:11:43 45.1 45.0 10.623/03/2011 14:12:13 45.1 45.0 11.4

    23/03/2011 14:12:43 45.0 45.0 13.3

    23/03/2011 14:13:13 44.9 45.0 14.4

    23/03/2011 14:13:43 45.0 45.0 12.4

    23/03/2011 14:14:13 44.9 45.0 14.3

    Figure 5.1: Load Change (PB = 5)

    Table 5.2: Set Point Change (PB = 5)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 17:12:58 44.9 45.0 28.7

    23/03/2011 17:13:00 44.9 45.0 27.9

    23/03/2011 17:13:30 47.3 50.0 79.623/03/2011 17:14:00 47.8 50.0 70.7

  • 8/6/2019 Final Experiment 5_1

    4/25

    23/03/2011 17:14:30 47.6 50.0 75.4

    23/03/2011 17:15:00 47.7 50.0 71.7

    23/03/2011 17:15:30 47.8 50.0 71.1

    23/03/2011 17:16:00 47.2 50.0 83.9

    23/03/2011 17:16:30 47.5 50.0 76.9

    23/03/2011 17:17:00 47.7 50.0 73.523/03/2011 17:17:30 47.8 50.0 72.7

    23/03/2011 17:18:00 47.9 50.0 69.5

    23/03/2011 17:18:30 47.3 50.0 82.4

    23/03/2011 17:19:00 47.4 50.0 81.6

    23/03/2011 17:19:30 47.5 50.0 78.4

    23/03/2011 17:20:00 47.7 50.0 75.4

    23/03/2011 17:20:30 47.9 50.0 71.7

    23/03/2011 17:21:00 47.2 50.0 85.8

    23/03/2011 17:21:30 47.4 50.0 80.9

    Figure 5.2: Set Point Change (PB = 5)

    Table 5.3: Load Change (PB = 20)

    Date Time TT01 (C) Set Point (C) Output (%)23/03/2011 14:02:09 45.1 45.0 13.1

    23/03/2011 14:02:39 43.6 45.0 20.5

    23/03/2011 14:03:09 41.4 45.0 31.9

    23/03/2011 14:03:39 44.0 45.0 19.1

    23/03/2011 14:04:09 45.1 45.0 13.5

    23/03/2011 14:04:39 45.2 45.0 12.9

    23/03/2011 14:05:09 45.0 45.0 14.1

    23/03/2011 14:05:39 45.0 45.0 14.0

    23/03/2011 14:06:09 45.0 45.0 13.8

    23/03/2011 14:06:39 44.9 45.0 14.2

  • 8/6/2019 Final Experiment 5_1

    5/25

    Figure 5.3: Load Change (PB = 20)

    Table 5.4: Set Point Change (PB = 20)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 16:55:30 44.7 45.0 28.1

    23/03/2011 16:55:32 44.7 45.0 28.1

    23/03/2011 16:56:02 46.4 50.0 44.5

    23/03/2011 16:56:32 46.6 50.0 43.6

    23/03/2011 16:57:02 46.4 50.0 44.7

    23/03/2011 16:57:32 46.1 50.0 46.6

    23/03/2011 16:58:02 46.4 50.0 45.1

    23/03/2011 16:58:32 46.5 50.0 44.7

    23/03/2011 16:59:02 46.6 50.0 44.4

    23/03/2011 16:59:32 46.7 50.0 43.9

    23/03/2011 17:00:02 46.0 50.0 47.1

    23/03/2011 17:00:32 46.3 50.0 46.0

    23/03/2011 17:01:02 46.4 50.0 45.5

    23/03/2011 17:01:32 46.5 50.0 45.0

    23/03/2011 17:02:02 46.7 50.0 44.4

    23/03/2011 17:02:32 46.0 50.0 47.8

    23/03/2011 17:03:02 46.3 50.0 46.523/03/2011 17:03:32 46.5 50.0 45.6

    23/03/2011 17:04:02 46.6 50.0 45.3

    23/03/2011 17:04:32 46.1 50.0 47.5

    23/03/2011 17:05:02 46.3 50.0 46.9

  • 8/6/2019 Final Experiment 5_1

    6/25

    Figure 5.4: Set Point Change (PB = 20)

    Table 5.5: Load Change (PB = 100)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 13:26:15 44.9 45.0 15.1

    23/03/2011 13:26:45 45.3 45.0 14.8

    23/03/2011 13:27:15 45.2 45.0 14.8

    23/03/2011 13:27:45 43.8 45.0 16.3

    23/03/2011 13:28:15 39.8 45.0 20.3

    23/03/2011 13:28:45 45.0 45.0 15.1

    23/03/2011 13:29:15 44.9 45.0 15.2

    23/03/2011 13:29:45 45.2 45.0 14.9

    23/03/2011 13:30:15 45.0 45.0 15.1

    23/03/2011 13:30:45 45.3 45.0 14.8

    23/03/2011 13:31:15 45.5 45.0 14.5

    23/03/2011 13:31:45 45.2 45.0 14.8

    23/03/2011 13:32:15 45.3 45.0 14.8

    23/03/2011 13:32:45 45.5 45.0 14.5

    23/03/2011 13:33:15 45.2 45.0 14.8

    Figure 5.5: Load Change (PB = 100)

  • 8/6/2019 Final Experiment 5_1

    7/25

    Table 5.6: Set Point Change (PB = 100)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 13:38:47 45.2 45.0 14.8

    23/03/2011 13:39:17 45.1 45.0 14.9

    23/03/2011 13:39:47 44.9 45.0 15.1

    23/03/2011 13:40:17 45.9 50.0 19.223/03/2011 13:40:47 45.5 50.0 19.6

    23/03/2011 13:41:17 45.7 50.0 19.4

    23/03/2011 13:41:47 45.9 50.0 19.2

    23/03/2011 13:42:17 45.6 50.0 19.5

    23/03/2011 13:42:47 45.5 50.0 19.7

    23/03/2011 13:43:17 46.2 50.0 19.0

    23/03/2011 13:43:47 46.0 50.0 19.2

    23/03/2011 13:44:17 45.7 50.0 19.5

    23/03/2011 13:44:47 46.0 50.0 19.3

    23/03/2011 13:45:17 45.9 50.0 19.323/03/2011 13:45:47 45.7 50.0 19.6

    23/03/2011 13:46:17 46.0 50.0 19.3

    23/03/2011 13:46:47 45.9 50.0 19.4

    23/03/2011 13:47:17 45.5 50.0 19.8

    23/03/2011 13:47:47 45.8 50.0 19.5

    23/03/2011 13:48:17 45.9 50.0 19.5

    23/03/2011 13:48:47 45.5 50.0 19.9

    23/03/2011 13:49:17 46.0 50.0 19.5

    23/03/2011 13:49:47 45.9 50.0 19.5

    23/03/2011 13:50:17 45.9 50.0 19.6

    23/03/2011 13:50:47 46.2 50.0 19.3

    23/03/2011 13:51:17 45.9 50.0 19.6

    23/03/2011 13:51:47 45.9 50.0 19.6

    23/03/2011 13:52:17 46.2 50.0 19.4

    23/03/2011 13:52:47 45.8 50.0 19.7

    Figure 5.6: Set Point Change (PB = 100)

  • 8/6/2019 Final Experiment 5_1

    8/25

    Table 5.7: Mean Temperatures, Settling Time for Different PB Values

    PB value

    Mean Temperature (C) Settling Time (s)

    Load ChangeSet Point

    ChangeLoad Change

    Set Point

    Change

    5 45.0 47.6 71 127

    20() 45.0 46.3 67 41100 45.2 46.0 467 1

    Experiment 2: Closed Loop Proportional-Integral (PI) Control

    Variable= I Value

    Constant = P Value (20 s) and D Value (0 s)

    Table 5.8: Load Change (I = 1)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 14:33:41 45.0 45.0 13.7

    23/03/2011 14:33:43 45.0 45.0 13.6

    23/03/2011 14:34:13 42.6 45.0 46.3

    23/03/2011 14:34:43 47.3 45.0 17.4

    23/03/2011 14:35:13 45.3 45.0 12.6

    23/03/2011 14:35:43 45.1 45.0 11.1

    23/03/2011 14:36:13 44.9 45.0 12.5

    23/03/2011 14:36:43 44.9 45.0 14.8

    23/03/2011 14:37:13 45.1 45.0 12.8

    23/03/2011 14:37:43 44.9 45.0 13.3

    23/03/2011 14:38:13 44.9 45.0 15.2

    Figure 5.7: Load Change (I = 1)

  • 8/6/2019 Final Experiment 5_1

    9/25

    Table 5.9: Set Point Change (I = 1)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 16:37:29 45.1 45.0 28.1

    23/03/2011 16:37:31 45.0 45.0 28.2

    23/03/2011 16:38:01 46.9 50.0 92.4

    23/03/2011 16:38:31 47.4 50.0 100.023/03/2011 16:39:01 47.7 50.0 100.0

    23/03/2011 16:39:31 47.7 50.0 100.0

    23/03/2011 16:40:01 48.0 50.0 100.0

    23/03/2011 16:40:31 48.1 50.0 100.0

    23/03/2011 16:41:01 47.5 50.0 100.0

    23/03/2011 16:41:31 47.4 50.0 100.0

    23/03/2011 16:42:01 47.7 50.0 100.0

    23/03/2011 16:42:31 47.8 50.0 100.0

    23/03/2011 16:43:01 47.9 50.0 100.0

    23/03/2011 16:43:31 48.0 50.0 100.023/03/2011 16:44:01 47.3 50.0 100.0

    23/03/2011 16:44:31 47.5 50.0 100.0

    23/03/2011 16:45:01 47.7 50.0 100.0

    23/03/2011 16:45:31 47.8 50.0 100.0

    23/03/2011 16:46:01 48.0 50.0 100.0

    23/03/2011 16:46:31 47.6 50.0 100.0

    23/03/2011 16:47:01 47.6 50.0 100.0

    23/03/2011 16:47:31 47.7 50.0 100.0

    23/03/2011 16:48:01 47.9 50.0 100.0

    Figure 5.8: Set Point Change (i = 1)

    Table 5.10: Load Change (I = 10)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 14:27:14 45.0 45.0 12.7

    23/03/2011 14:27:16 45.0 45.0 12.8

    23/03/2011 14:27:46 44.9 45.0 13.5

    23/03/2011 14:28:16 45.3 45.0 11.7

  • 8/6/2019 Final Experiment 5_1

    10/25

    23/03/2011 14:28:46 45.4 45.0 10.5

    23/03/2011 14:29:16 45.1 45.0 11.7

    23/03/2011 14:29:46 44.9 45.0 12.8

    23/03/2011 14:30:16 45.2 45.0 11.3

    23/03/2011 14:30:46 45.3 45.0 10.6

    23/03/2011 14:31:16 44.9 45.0 12.2

    Figure 5.9: Load Change (I = 10)

    Table 5.11: Set Point Change (I = 10)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 16:24:17 45.2 45.0 28.423/03/2011 16:24:32 45.3 45.0 28.0

    23/03/2011 16:25:02 47.0 50.0 48.6

    23/03/2011 16:25:32 46.6 50.0 55.5

    23/03/2011 16:26:02 47.1 50.0 57.8

    23/03/2011 16:26:32 47.3 50.0 61.0

    23/03/2011 16:27:02 47.6 50.0 63.4

    23/03/2011 16:27:32 47.7 50.0 66.1

    23/03/2011 16:28:02 47.1 50.0 72.9

    23/03/2011 16:28:32 47.3 50.0 76.7

    23/03/2011 16:29:02 47.5 50.0 79.5

    23/03/2011 16:29:32 47.6 50.0 82.5

    23/03/2011 16:30:02 47.8 50.0 85.1

    23/03/2011 16:30:32 48.0 50.0 87.4

    23/03/2011 16:31:02 48.0 50.0 90.1

    23/03/2011 16:31:32 47.5 50.0 96.2

    23/03/2011 16:32:02 47.3 50.0 100.0

    23/03/2011 16:32:32 47.6 50.0 100.0

    23/03/2011 16:33:02 47.7 50.0 100.0

    23/03/2011 16:33:32 48.0 50.0 100.0

    23/03/2011 16:34:02 48.0 50.0 100.0

    23/03/2011 16:34:32 48.1 50.0 100.023/03/2011 16:35:02 47.9 50.0 100.0

  • 8/6/2019 Final Experiment 5_1

    11/25

    Figure 5.10: Set Point Change (I = 10)

    Table 5.12: Load Change (I = 100)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 14:19:49 44.8 45.0 13.1

    23/03/2011 14:19:55 44.8 45.0 13.2

    23/03/2011 14:20:25 41.4 45.0 30.5

    23/03/2011 14:20:55 44.9 45.0 13.2

    23/03/2011 14:21:25 45.1 45.0 12.0

    23/03/2011 14:21:55 44.9 45.0 13.1

    23/03/2011 14:22:25 45.1 45.0 12.3

    23/03/2011 14:22:55 45.2 45.0 11.723/03/2011 14:23:25 45.1 45.0 12.3

    23/03/2011 14:23:55 44.9 45.0 13.4

    Figure 5.11: Load Change (I = 100)

  • 8/6/2019 Final Experiment 5_1

    12/25

    Table 5.13: Set Point Change (I = 100)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 16:11:12 44.8 45.0 28.0

    23/03/2011 16:11:14 44.8 45.0 28.0

    23/03/2011 16:11:44 46.8 50.0 100.0

    23/03/2011 16:12:14 47.8 50.0 100.023/03/2011 16:12:44 47.8 50.0 100.0

    23/03/2011 16:13:14 48.0 50.0 100.0

    23/03/2011 16:13:44 48.1 50.0 100.0

    23/03/2011 16:14:14 47.8 50.0 100.0

    23/03/2011 16:14:44 47.3 50.0 100.0

    23/03/2011 16:15:14 47.6 50.0 100.0

    23/03/2011 16:15:44 47.7 50.0 100.0

    23/03/2011 16:16:14 47.9 50.0 100.0

    23/03/2011 16:16:44 48.1 50.0 100.0

    23/03/2011 16:17:14 48.1 50.0 100.023/03/2011 16:17:44 47.2 50.0 100.0

    23/03/2011 16:18:14 47.5 50.0 100.0

    23/03/2011 16:18:44 47.7 50.0 100.0

    23/03/2011 16:19:14 47.8 50.0 100.0

    23/03/2011 16:19:44 48.0 50.0 100.0

    Figure 5.12: Set Point Change (I = 100)

    Table 5.14: Mean Temperatures and Settling Time for Different I Values

    I value

    Mean Temperature (C) Settling Time (s)

    Load ChangeSet Point

    ChangeLoad Change

    Set Point

    Change

    1() 45.0 47.7 36 14010 45.2 47.8 42 630

    100 45.1 47.8 73 300

  • 8/6/2019 Final Experiment 5_1

    13/25

    Experiment 3: Closed Loop Proportional-Integral-Derivative (PID) Control

    Variable= D Value

    Constant = P Value (20 s) and I Value (1 s)

    Table 5.15: Load Change (D = 1)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 14:41:26 45.4 45.0 13.4

    23/03/2011 14:41:29 45.4 45.0 13.6

    23/03/2011 14:41:59 44.3 45.0 30.1

    23/03/2011 14:42:29 43.0 45.0 20.9

    23/03/2011 14:42:59 44.2 45.0 23.7

    23/03/2011 14:43:29 44.4 45.0 23.6

    23/03/2011 14:43:59 44.5 45.0 24.8

    23/03/2011 14:44:29 44.3 45.0 26.0

    23/03/2011 14:44:59 44.5 45.0 25.923/03/2011 14:45:29 44.6 45.0 26.1

    23/03/2011 14:45:59 44.4 45.0 28.8

    23/03/2011 14:46:29 44.5 45.0 27.5

    23/03/2011 14:46:59 44.7 45.0 27.6

    Figure 5.13: Load Change (D = 1)

    Table 5.16: Set Point Change (D = 1)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 14:57:49 44.8 45.0 31.7

    23/03/2011 14:57:50 44.8 45.0 31.6

    23/03/2011 14:58:20 46.4 50.0 49.4

    23/03/2011 14:58:50 47.0 50.0 53.6

    23/03/2011 14:59:20 47.2 50.0 56.8

    23/03/2011 14:59:50 47.2 50.0 62.0

    23/03/2011 15:00:20 47.1 50.0 65.6

    23/03/2011 15:00:50 47.4 50.0 68.7

  • 8/6/2019 Final Experiment 5_1

    14/25

    23/03/2011 15:01:20 47.7 50.0 70.8

    23/03/2011 15:01:50 47.9 50.0 73.0

    23/03/2011 15:02:20 47.8 50.0 77.7

    23/03/2011 15:02:50 47.2 50.0 84.0

    23/03/2011 15:03:20 47.5 50.0 85.7

    23/03/2011 15:03:50 47.6 50.0 89.323/03/2011 15:04:20 47.8 50.0 91.6

    23/03/2011 15:04:50 48.0 50.0 93.6

    23/03/2011 15:05:20 47.7 50.0 99.7

    23/03/2011 15:05:50 47.4 50.0 100.0

    23/03/2011 15:06:20 47.7 50.0 100.0

    23/03/2011 15:06:50 47.8 50.0 100.0

    23/03/2011 15:07:20 47.9 50.0 100.0

    23/03/2011 15:07:50 48.1 50.0 100.0

    23/03/2011 15:08:20 48.0 50.0 100.0

    23/03/2011 15:08:50 47.2 50.0 100.023/03/2011 15:09:20 47.6 50.0 100.0

    23/03/2011 15:09:50 47.7 50.0 100.0

    23/03/2011 15:10:20 47.8 50.0 100.0

    Figure 5.14: Set Point Change (D = 1)

    Table 5.17: Load Change (D = 10)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 15:15:43 44.9 45.0 31.8

    23/03/2011 15:15:46 44.9 45.0 30.1

    23/03/2011 15:16:16 43.7 45.0 53.7

    23/03/2011 15:16:46 45.2 45.0 19.0

    23/03/2011 15:17:16 45.5 45.0 23.4

    23/03/2011 15:17:46 45.6 45.0 26.8

    23/03/2011 15:18:16 45.7 45.0 26.2

    23/03/2011 15:18:46 45.8 45.0 24.4

    23/03/2011 15:19:16 45.8 45.0 26.323/03/2011 15:19:46 45.6 45.0 25.8

  • 8/6/2019 Final Experiment 5_1

    15/25

    23/03/2011 15:20:16 45.8 45.0 22.7

    23/03/2011 15:20:46 45.7 45.0 23.3

    23/03/2011 15:21:16 45.6 45.0 23.0

    23/03/2011 15:21:46 45.6 45.0 20.5

    23/03/2011 15:22:16 45.6 45.0 19.0

    23/03/2011 15:22:46 45.4 45.0 22.223/03/2011 15:23:16 45.3 45.0 19.9

    Figure 5.15: Load Change (D = 10)

    Table 5.18: Set Point Change (D = 10)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 15:33:09 45.0 45.0 30.0

    23/03/2011 15:33:11 45.2 45.0 24.8

    23/03/2011 15:33:41 46.6 50.0 28.5

    23/03/2011 15:34:11 47.0 50.0 36.1

    23/03/2011 15:34:41 47.6 50.0 38.3

    23/03/2011 15:35:11 48.1 50.0 40.2

    23/03/2011 15:35:41 48.0 50.0 52.0

    23/03/2011 15:36:11 48.3 50.0 49.5

    23/03/2011 15:36:41 48.6 50.0 48.3

    23/03/2011 15:37:11 48.6 50.0 55.9

    23/03/2011 15:37:41 48.4 50.0 58.723/03/2011 15:38:11 48.7 50.0 56.4

    23/03/2011 15:38:41 49.0 50.0 56.8

    23/03/2011 15:39:11 48.7 50.0 67.8

    23/03/2011 15:39:41 48.6 50.0 63.5

    23/03/2011 15:40:11 48.9 50.0 62.9

    23/03/2011 15:40:41 49.0 50.0 64.4

    23/03/2011 15:41:11 49.0 50.0 69.9

    23/03/2011 15:41:41 48.5 50.0 79.1

    23/03/2011 15:42:11 48.9 50.0 70.1

    23/03/2011 15:42:41 49.1 50.0 70.523/03/2011 15:43:11 49.3 50.0 71.1

  • 8/6/2019 Final Experiment 5_1

    16/25

    Figure 5.16: Set Point Change (D = 10)

    Table 5.19: Load Change (D = 100)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 15:48:45 45.2 45.0 22.4

    23/03/2011 15:48:47 45.2 45.0 22.2

    23/03/2011 15:49:17 43.8 45.0 64.8

    23/03/2011 15:49:47 45.0 45.0 30.6

    23/03/2011 15:50:17 45.1 45.0 28.6

    23/03/2011 15:50:47 45.2 45.0 28.2

    23/03/2011 15:51:17 45.1 45.0 33.0

    23/03/2011 15:51:47 45.2 45.0 31.423/03/2011 15:52:17 45.3 45.0 30.4

    23/03/2011 15:52:47 45.4 45.0 28.1

    23/03/2011 15:53:17 45.3 45.0 32.6

    23/03/2011 15:53:47 45.3 45.0 32.5

    Figure 5.17: Load Change (D = 100)

  • 8/6/2019 Final Experiment 5_1

    17/25

    Table 5.20: Set Point Change (D = 100)

    Date Time TT01 (C) Set Point (C) Output (%)

    23/03/2011 15:55:25 45.3 45.0 35.4

    23/03/2011 15:55:35 45.3 45.0 35.6

    23/03/2011 15:56:05 46.2 50.0 40.4

    23/03/2011 15:56:35 46.4 50.0 43.023/03/2011 15:57:05 46.7 50.0 42.5

    23/03/2011 15:57:35 47.0 50.0 44.5

    23/03/2011 15:58:05 46.6 50.0 63.1

    23/03/2011 15:58:35 46.9 50.0 61.2

    23/03/2011 15:59:05 47.2 50.0 62.8

    23/03/2011 15:59:35 47.3 50.0 64.4

    23/03/2011 16:00:05 47.5 50.0 67.7

    23/03/2011 16:00:35 47.7 50.0 67.9

    23/03/2011 16:01:05 47.3 50.0 87.0

    23/03/2011 16:01:35 47.4 50.0 92.623/03/2011 16:02:05 47.5 50.0 93.2

    23/03/2011 16:02:35 47.7 50.0 94.8

    23/03/2011 16:03:05 47.8 50.0 97.5

    23/03/2011 16:03:35 48.0 50.0 97.0

    23/03/2011 16:04:05 48.1 50.0 98.9

    23/03/2011 16:04:35 47.4 50.0 100.0

    23/03/2011 16:05:05 47.4 50.0 100.0

    23/03/2011 16:05:35 47.5 50.0 100.0

    23/03/2011 16:06:05 47.7 50.0 100.0

    23/03/2011 16:06:35 47.8 50.0 100.0

    Figure 5.18: Set Point Change (D = 100)

  • 8/6/2019 Final Experiment 5_1

    18/25

    Table 5.21: Mean Temperatures and Settling Time for Different I Values

    D value

    Mean Temperature (C) Settling Time (s)

    Load ChangeSet Point

    ChangeLoad Change

    Set Point

    Change

    1() 44.5 47.7 65 44610 45.7 48.9 208 >750100 45.2 47.7 234 550

    Offset Calculation

    Taking P=5 in Experiment 1 as sample calculation,

    Offset = Mean Value of Operating TemperatureSet Point

    = 47.6 C45 C

    = 2.6 C

    Refer Table 6.1 for complete offset values for all conditions.

    Overshoot Calculation

    Figure 5.19: Performance characteristics of an underdamped process.

    Overshoot is only applicable when the system attempts to make the response of the

    controlled variable to a set-point change, which exhibit a prescribed amount of

    overshoot and oscillation as it settles at the new operating point.

    eh

    ts= settling time

    tp = time to first peak

  • 8/6/2019 Final Experiment 5_1

    19/25

    By using Figure 5.2 for reference for calculation,

    Overshoot summary,

    Table 5.22: Offset value for proportional change only

    P Overshoot % Remarks

    100 - No overshoot

    20 () 17.0212766 -

    5 35.71428571 -

    Table 5.23: Offset value for proportional change onlyI Overshoot % Remarks

    1 - No overshoot, drifting oscillation only

    10 - Drifting new set point

    100 - No overshoot, drifting oscillation only

    Table 5.24: Offset value for proportional change only

    D Overshoot % Remarks

    1 - Drifting new set point

    10 20 -

    100 - Drifting new set point

    6.0 DISCUSSION

    Figure 6.1: Temperature Control System Block Diagram

    P

    I

    D

    Temperature

    Controller

    Error

    Detector

    Control

    Valve

    Process

    Temperature

    Transmitter

  • 8/6/2019 Final Experiment 5_1

    20/25

    Figure 6.1 indicates the cycle of temperature control system. The temperature

    transmitter used to measure the current temperature, . The temperature transmitter

    will send an analogue signal to the error detector so that the error detector can

    compare the value between the analogue of current temperature,

    and the set point

    temperature, . The temperature controller will then receive the error from the

    Error Detector through the P,I and D. Controller will send an electrical current signal

    to the Control Valve and the control valve is used to vary the liquid flow rate. The

    liquid flow rate will be controlled by the openings of the control valve.

    Temperature control utilizes a feedback loop that begins with a system's

    measured temperature. A temperature sensor - typically a thermocouple, RTD or

    thermistor - measures a process's real-time temperature and feeds the reading back to

    a controller. The controller compares the measured temperature to the set point

    temperature and actuates devices like heaters or valves to bring the temperature to

    the desired set point. The three most common methods of control are proportional

    (P), proportional-integral (PI) and proportional-integral-derivative (PID). For this

    experiment we had two parts to be done, that are load change and set point change.

    This both, are actually the disturbance of the process. The disturbances are the

    change of the flow rate in between and also the set point change (temperature

    change). When there is disturbance, there will be some fluctuating in the current

    value of temperature. The current value of temperature supposed to be nearest to the

    set point, but due to the disturbance the value will shoot up. To come back to the set

    point value, the output (the opener of valve) will be increased automatically to have a

    current value of temperature near to the set point.

    For the load change experiment, the cold water flow rate is changed from 5

    LPM to 10 LPM and back to 5 LPM. The increased in the amount of cold water

    entering the heat exchanger will cause the reduction of water outlet temperature. This

    introduced disturbance will cause the system to respond and try to return the cold

    water outlet temperature to the set point by controlling the electro-pneumatic

    proportional valve (adjusting the opening of hot water inlet). For the set point change

    experiment, the set point is increased from 45 C to 50 C. This increase in set point

    will cause the system to try to give response so that the process value (temperature)

    matches the new set point.

  • 8/6/2019 Final Experiment 5_1

    21/25

    For proportional control, the controller output is proportional to the error

    signal. A disadvantage of proportional-only control is that a steady-state error or

    offset occurs after a set-point change or a sustained disturbance. In principle, offset

    can be eliminated by manually resetting either the set-point or bias value after an

    offset occurs. However, this approach is inconvenient because operator intervention

    is required and the new value of set point must usually be found by trial and error.

    Integral control action provides automatic reset of set point. It is widely used

    because it provides an important practical advantage, the elimination of offset. When

    integral action is used, controller output changes automatically until it attains the

    value required to make the steady state error zero. Proportional-integral controller

    provides immediate corrective action as soon as an error is detected without the

    problem of offset. One disadvantage of using integral actions is that it tends to

    produce oscillatory response of the controlled variable and reduces the stability of

    the feedback control system. A limited amount of oscillation can be tolerated

    because it is often associated with a faster response. The undesirable effects of too

    much integral action can be avoided by proper tuning of the controller or by

    including derivative action which tends to counteract the destabilizing effects.

    Derivative control action is to anticipate the future behavior of the error

    signal by considering its rate of change. While for proportional control, it reacts to a

    deviation in temperature only, making no distinction as to the time period over which

    the deviation develops. Integral control action is also ineffective for a sudden change

    in temperature because corrective action occurs when the deviation persists for a

    long period. Derivative control action also tends to improve the dynamic response of

    the controlled variable by decreasing the process settling time, the time it takes the

    process to reach steady state.

    In conclusion, when there is a step change in a disturbance variable occurs,

    proportional control speeds up the process response and reduces the offset. The

    addition of integral control action eliminates offset but tends to make the response

    more oscillatory. Adding derivative action reduced both the degree of oscillation and

    the response time.

  • 8/6/2019 Final Experiment 5_1

    22/25

    Table 6.1: Comparison between Different Values of P, I and D.

    Controller

    Mode

    Proportional Proportional-Integral Proportional-Integral-Derivative

    P=100 P=20 P=5 I=100 I=10 I=1 D=1 D=10 D=100

    Operating

    Value46 46.3 47.6 47.8 47.8 47.7 47.7 48.9 46.45

    Offsets 1 1.3 2.6 2.8 2.8 2.7 2.8 2.7 2.7

    Response

    Time

    Almost Immediate

    Response

    Behavior

    Moderate

    Oscillation

    Little

    Oscillation

    Large

    Oscillation

    Moderate

    Oscillation

    Large

    Oscillation

    Little

    Oscillation

    Little

    Oscillation

    Moderate

    Oscillation

    Large

    Oscillation

    Selection

    Table 6.2: Comparison between P, PI and PID of Controller Mode.

    Controller Mode Proportional Proportional-Integral Proportional-Integral-Derivative

    Operating Value 46.63 47.77 48.1

    Offsets 1.63 2.77 3.1

    Response Time Almost Immediate

    Response

    Behavior Little Oscillation Moderate Oscillation Large Oscillation

    Selection

  • 8/6/2019 Final Experiment 5_1

    23/25

    From the graphs and results, it can be clearly seen that the set point change

    takes longer to settle and creates more cycle (oscillation) for the system to reach

    steady state compared to load change.

    Theoretically, the sensitivity of controller will increase as Kc increases. In

    other words, when Kc increases, the controller is very sensitive and results in larger

    response and more overshoot when the controller is making correction to the

    disturbances in the system.

    where,

    PB proportional band or P-value

    Kc controller gain

    According to Equation 1, the P-value is inversely proportional to the

    controller gain, Kc. At large P-value, the controller become less sensitive as Kc is

    small. This theory applies in this experiment as the larger the P-value, the smaller the

    overshoot.

    Besides that, we also observed that the offset value decreases as the P-value

    decreases. This phenomenon can be explained with Equations 2 and 3.

    where

    KOL open loop gain

    Kv valve gain

    Kp process gain

    Km steady state gain

    ffe

    where,Mis the set point

    From Equation 2, KOL is proportional to Kc. In Equation 1, we showed that P-value is

    inversely proportional to Kc. Therefore, when P-value decreases, the Kc and KOL

    increases. When KOL increases, the offset decreases. So, when P-value decreases, the

  • 8/6/2019 Final Experiment 5_1

    24/25

    offset decreases. A large Kc is not always desirable as it will tend to cause

    oscillations.

    Integral control action is widely used because it provides an important

    practical advantage, the elimination of offset. When integral action is used, controller

    output changes automatically until it attains the value required to make the steady

    state error zero. Therefore, in this experiment, the offset value cannot be compared in

    terms of integral time value as this mode of control eliminates the problem of offset.

    Response time for all the three mode of control is almost immediate

    whenever there is a disturbance to the system as can be seen in the results and graph.

    This is because all three mode of control (P, PI and PID) include the proportional

    control, where it provides immediate corrective action as soon as an error is detected.

    While for the response behavior, we can see that the oscillation occur the

    most in PID control mode, followed by PI and lastly P control as the addition of D-

    value tends to amplify noise. This noise amplification increases as the D-value

    becomes larger. A larger D-value also causes the system to exhibit larger and longer

    oscillations.

    Underdamped systems frequently overshoot their target value initially. This

    initial surge is known as the "overshoot value". The ratio of the amount of overshoot

    to the target steady-state value of the system is known as the percent overshoot.

    Percent overshoot represents an overcompensation of the system, and can output

    dangerously large output signals that can damage a system. Percent overshoot is

    typically denoted with the term OS. No percentage overshoot is most preferable.

    Based on our calculations, the proportional integral there is no overshoot percentage.

    When proportional, the control process gives an overshoot percentage when P=20

    and P=5. The value of P=100 there is no overshoot percentage. For proportional

    integral derivate, when D=10 there is overshoot percentage. During this mode, the

    settling time for set point change is very high. So we can conclude that due the

    higher value of settling point, there will be an overshoot percentage. Another

    situation, during the proportional mode when P=100 the settling time is just 1 s.Tha he lwe eling pin we bained hee i n any eh.

  • 8/6/2019 Final Experiment 5_1

    25/25

    Overall the proportional mode gives a lower operating value. And when as

    the P values increases the operating value decreases and it requires less settling time

    for the temperature to reach its steady temperature (nearest to its set point).

    Theoretically, PID gives the best control system. However, in this

    experiment, it shows that the inclusion of D gives longer settling time and higher

    oscillation than PI control. Overall, by comparing all the response (operating value,

    offset, overshoot, settling time, response time and response behavior), we conclude

    that the best choice (a symbol of is located near all the response factors) of control

    mode is PI with the setting of P = 20 and I =1 where all the factors are within the

    acceptable range.

    One of the recommendations is that the value of D should not be so high,

    because the settling time required for the process to achieve steady state is very high.

    So it require us to stay longer, hence the results we obtain might not be so accurate.

    Apart from that, the pressure should be constant throughout the process and there

    should be an alarm to alert us when there is no pressure being supplied. This is

    because, during the experiment, the compressor may not working all of sudden, and

    we are not being notified for this incident. Due to the un-working compressor, the

    settling time for the process value to achieve a steady state is higher.

    7.0 CONCLUSIONIn conclusion, proportional mode gives a lower operating value. The operating value

    is inversely proportional with the P value. In this experiment, we found out PI

    controller is the best choice with P = 20 and I = 1, in which the mean temperatures

    f lad change and e pin change ae 45.0C and 47.7C, respectively.

    8.0 REFERENCES

    Seborg, D. E., Edgar, T. F., & Mellichamp, D. A. (2004). Process dynamics and

    control (2nd Edition). New Jersey: John Wiley & Sons.

    Julabo (2010). Temperature Control Solutions, Retrieved March 20, 2011 fromwww.julabo.de