Field Evaluation of Dampers

download Field Evaluation of Dampers

of 17

Transcript of Field Evaluation of Dampers

  • 7/30/2019 Field Evaluation of Dampers

    1/17

    256

    CHAPTER 7

    Field Evaluation of Dampers

    In order to evaluate the effectiveness of fluid dampers for stay-cable vibration

    mitigation and to facilitate the design of even more effective and economical systems, it

    is important to perform quantitative assessments of damper performance under various

    types of excitation. Toward this end, this chapter seeks to evaluate the effectiveness of

    passive linear dampers installed on two stays on the Fred Hartman Bridge in Houston,

    Texas, by comparing response statistics before and after the damper installation and by

    investigating in detail the damper performance in a few selected records corresponding to

    different types of excitation.

    Fluid dampers, specified to have a linear force-velocity relationship, have been

    installed for evaluation on two stays on the Fred Hartman Bridge, and at the time of

    writing, data have been collected for more than two years after the damper installation to

    evaluate the damper performance. The two stays on which the evaluation dampers have

    been installed are indicated on the schematic drawing of the bridge in Figure 7.1 (AS16

    and AS23); this figure also indicates the coordinate system used for reporting wind speed

    and wind direction. Properties of the two stays on which evaluation dampers have been

    installed are given in Table 7.1 along with the damper locations and the specified damper

    coefficients.

  • 7/30/2019 Field Evaluation of Dampers

    2/17

  • 7/30/2019 Field Evaluation of Dampers

    3/17

    258

    previously, the error in the predictions of the universal curve is most significant near the

    optimal portion of the curve, and it is evident here that the asymptotic approximate value

    differs most significantly from the exact value in mode 1, for which the damper is nearly

    optimal. The error near the optimal portion of the curve becomes more significant in the

    higher modes, but because the damper is far from optimal in the higher modes for these

    stays, the universal curve gives quite good predictions of the damping ratios in the higher

    modes. The Sc > 10 criterion discussed previously requires modal damping ratios of

    0.53% for Stay AS16 and 0.64% for Stay AS23. It is evident from Figure 7.2 that,

    according to the analytical predictions, this criterion is satisfied in the first nine modes for

    Stay AS16 and in the first five modes for Stay AS23. Damping values for the stays have

    not yet been directly estimated from measurements for comparison with the analytical

    predictions, but work is currently in progress and results will be reported in future

    publications (Delong Zuo, personal communication).

    0.0%

    0.5%

    1.0%

    1.5%

    2.0%

    2.5%

    1 2 3 4 5 6 7 8 9 10

    Mode Number,i

    AS16: numericalAS16: asymptotic

    AS23: numerical

    AS23: asymptotic

    i

    Figure 7.2: Predicted Damping vs. Mode Number for Hartman Stays AS16 and AS23

  • 7/30/2019 Field Evaluation of Dampers

    4/17

    259

    In order to assess the presence of the damping-induced frequency shifts predicted

    by the analytical formulation, the natural frequencies of Stay AS23 before and after the

    damper installation were estimated from the peak values of averaged acceleration power

    spectra. Five 5-minute records of ambient vibration under low wind speeds were selected

    both before and after the damper installation, and each set of five spectra was averaged to

    obtain averaged undamped and damped spectra. The damping-induced frequency shift in

    each of the identified modes was computed by taking the difference of the damped and

    undamped frequencies. These measured frequency shifts were then normalized by the

    fundamental frequency of the stay to obtain dimensionless frequency shifts, which are

    plotted in Figure 7.3 for the first 12 modes. Also plotted with the measured values are

    the dimensionless frequency shifts predicted by numerical solution of the eigenvalue

    equation (3.6) (labeled Analytical), and the frequency shift i which would be

    induced if the cable were fixed at the damper location (labeled Clamped). It is evident

    that the measured values agree quite well with the analytical predictions, and the

    frequency shifts are quite significant, especially in the higher modes.

    0

    0.1

    0.2

    0.3

    0.4

    0.5

    1 2 3 4 5 6 7 8 9 10 11 12

    Mode Number, i

    Measured

    Analytical

    Clamped: i

    1o

    oii

    f

    ff

    Figure 7.3: Frequency Shift vs. Mode Number: Estimated and Measured Data

  • 7/30/2019 Field Evaluation of Dampers

    5/17

    260

    As was mentioned above, when the dimensionless frequency difference i in a

    given mode reaches 0.5, new regimes of behavior are observed. In the case of Stay

    AS23, the value of i associated with mode 13 is slightly greater than 0.5, and the

    analytical formulation for the taut string with linear damper in Chapter 3 indicates that

    the damping in this mode is supercritical, so that no oscillatory solution exists for this

    mode, but a non-oscillatory decaying solution emerges instead; this behavior is observed

    because the damper is located sufficiently near the antinode of mode 13 for Stay AS23.

    In modes 14 and higher, the damper is located past the first antinode, and solution of the

    eigenvalue equation indicates that the frequency of damped oscillation is less than the

    undamped frequency in these modes. Although not presented herein, the frequency shifts

    measured in the higher modes agree reasonably well with the analytical predictions.

    The clamping ratio ci associated with each mode can be computed by normalizing

    the dimensionless frequency shifts plotted in Figure 7.3 by the dimensionless frequency

    difference i. The value of the nondimensional damper parameter associated with

    each mode can be readily computed from the definition in (3.32) using the stay and

    damper properties in Table 7.1. Figure 7.4 shows the resulting plot of versus ci; a

    distinct data point is plotted here for each of the first 12 modes, larger values of

    corresponding to higher mode numbers. Also plotted with the measured values are the

    analytical values determined from numerical solution of (3.6) and the curve

    corresponding to the asymptotic approximation in (3.31). The measured values agree

    reasonably well with the analytical predictions, and a clear trend of increasing clamping

    ratio with mode number is evident. The measured frequency shifts thus confirm that this

  • 7/30/2019 Field Evaluation of Dampers

    6/17

    261

    damper, which was optimized for mode 1, is effectively more rigid in the higher modes

    and is tending to lock the cable at the damper location in these modes.

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1

    Measured

    Analytical

    Asymptotic

    ci

    Figure 7.4: Non-Dimensional Damping Parameter vs. Clamping Ratio

    7.2 Global Damper Performance

    In order to evaluate the effectiveness of the trial dampers installed on the two

    stays, response statistics are compared from data collected before and after the damper

    installation. The data presented herein are obtained from queries issued to the database

    described earlier. In order to minimize the inclusion of records with noise-corrupted or

    saturated data, all queries include a filter that retains only records with skewness with a

    magnitude less than 2.0 and kurtosis less than 5.0 (recall that a normal distribution has a

    skewness of zero and a kurtosis of 3.0). (A slightly more aggressive skewness filter of

    magnitude less than 1.5 was used for the load cell data). While this scheme obviously

    might exclude some data records that are of interest, experience has shown this approach

  • 7/30/2019 Field Evaluation of Dampers

    7/17

    262

    to be a reasonable method of eliminating problematic data while retaining the majority of

    features being sought.

    In the figures included herein, representative values of mean wind speed were

    computed using the same scheme described previously in Chapter 2. Wind direction is

    measured in degrees clockwise from the bridge axis, with zero degrees corresponding to

    wind approximately from the North, directly along the bridge axis, as indicated in Figure

    7.1. Acceleration data are reported from transducers installed on the stays usually about

    6 m vertically above deck level, and for the purposes of this investigation and for the data

    reported herein, the accelerations are reported at the transducer location.

    The global performance of the dampers installed on stays AS16 and AS23 is

    summarized in Figure 7.5 and Figure 7.6, respectively, which illustrate the following

    Characterization of oscillations (in-plane) occurring before installation of the

    damper as a function of wind speed and direction.

    Characterization of oscillations (in-plane) occurring after the installation of the

    damper as a function of wind speed and direction.

    Measurement of damper force as a function of wind speed and direction.

  • 7/30/2019 Field Evaluation of Dampers

    8/17

    263

    Figure 7.5: Stay Vibration and Damper Force Characteristics: Stay AS16

  • 7/30/2019 Field Evaluation of Dampers

    9/17

    264

    Figure 7.6: Stay Vibration and Damper Force Characteristics: Stay AS23

    Before the damper is installed, both stays show similar characteristics, and

    patterns that are consistent with the field observations that were described earlier. A high

    density of points is seen near the abscissa, which generally corresponds to vortex-induced

    vibration in a variety of modes and low-level buffeting response of the stay under random

  • 7/30/2019 Field Evaluation of Dampers

    10/17

    265

    excitations. Both figures clearly indicate the characteristic signature of wind-rain

    oscillation as the multiple points over a wide range of wind speeds that are of high

    amplitude i.e., root-mean-square (RMS) accelerations greater than 0.5g. One-minute

    mean wind speeds at deck level reached 15 m/s before the dampers were installed, and

    almost 18 m/s in the period after installation. This latter value corresponds to a one-

    minute average wind speed of 27 m/s (60 mi/h) at the top of the tower, recorded during a

    thunderstorm. The dependence on wind direction is also clear, with AS16 showing its

    peak responses between 90 and 160 degrees, and AS23 over a narrower range between 90

    and 135 degrees. The primary goal of a mitigation system is to reduce significantly or

    eliminate these large-amplitude events, while respecting the fact that the stays and bridge

    form dynamic systems and will always exhibit some level of dynamic response.

    The corresponding figures after the installation of the dampers suggest the

    following:

    Amplitudes are significantly reduced across all recorded wind speeds (up to 18

    m/s at deck level) with maximum RMS acceleration amplitudes of around 0.5g.

    The dependence on wind direction has been altered significantly, with the

    previously preferred range now largely unapparent, and the largest of the

    responses now nearer to a 90-degree angle of incidence. The characteristics of

    selected records corresponding to these locations will be discussed in more detail

    later.

    The third pair of figures shows the RMS damper force for the two installed

    devices as a function again of wind speed and direction. For stay AS16, the

    pattern of forces resembles closely the pre-damper acceleration figures (both in

  • 7/30/2019 Field Evaluation of Dampers

    11/17

    266

    terms of wind speed and direction), suggesting that the dampers are being

    engaged by the stays to suppress proclivity towards wind-rain vibration.

    Relatively high-magnitude forces are also seen in the complementary range of

    225 to 270 degrees, which represent wind directions also corresponding to the

    declining direction of the stay (but now from the southwest rather than southeast.)

    For stay AS23, the behavior is similar, though perhaps not as clear as in the

    previous case. Much of the high force data for this stay is now clustered around

    an incident angle of 90 degrees, although some up to 110 degrees are evident. An

    interesting and unusual cluster of points labeled Record C will be discussed

    subsequently. Note that in all the records, the highest amplitude RMS force

    recorded is approximately 5.6 kN (1125 lb) a relatively modest level of load.

    7.3 Analysis of Individual Records

    While comprehensive investigation of all individual data records is challenging

    due to the quantity of data, it is instructive and interesting to study some of these specific

    records in some detail in order to better understand what the dampers are doing, or trying

    to do. After some review of these datasets, three such representative records have been

    selected and presented herein. These records are labeled A, B, and C in Figure 7.5 and

    Figure 7.6; Records A and B are selected from stay AS16, and record C from stay AS23.

    The reasons for the selection, as well as an interpretation of each record is provided

    below. Each figure includes a ten-second time history of acceleration and damper force,

    as well as a PSD of each over a 10-Hertz range.

    Record A (Figure 7.7) represented one of the highest amplitude RMS acceleration

    events after the installation of the damper on stay AS16. It corresponded to a wind speed

  • 7/30/2019 Field Evaluation of Dampers

    12/17

    267

    of about 3.4 m/s and a wind direction of 60 degrees. The RMS force is moderate: about 2

    kN RMS. This record is interpreted as traditional vortex-induced vibration of the stay,

    with both acceleration and force presenting strongly single-mode responses at a

    frequency of about 6.5 Hz. (This corresponds to the fifth mode of vibration of this

    dampedstay. As noted above, the damper has a stiffening effect on the stay system that

    is mode dependent; the frequency of the fifth mode of the undamped stay is

    approximately 6.2 Hz.) An analysis of the Strouhal relationship for this wind speed and

    frequency suggests a Strouhal number consistent with 0.2: the value commonly assumed

    for a circular cylinder. Due to the relatively high frequency of the mode, displacement

    amplitudes associated with this motion are small even with the peak acceleration of 1g

    (about 6 mm at the transducer location.)

  • 7/30/2019 Field Evaluation of Dampers

    13/17

    268

    Stay AS16 Acceleration Time History (Record A)

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    0 2 4 6 8 10

    Time (s)

    Acceleration(g)

    Stay AS16 Acceleration PSD (Record A)

    1.0E-07

    1.0E-06

    1.0E-05

    1.0E-04

    1.0E-03

    1.0E-02

    1.0E-01

    1.0E+00

    1.0E+01

    1.0E+02

    0 2 4 6 8 10

    Frequency (Hz)

    PSDof

    Acceleration

    Stay AS16 Damper Force Time History (Record A)

    -10

    -8

    -6

    -4

    -20

    2

    4

    6

    8

    10

    0 2 4 6 8 10

    Time (s)

    Force

    (kN)

    Stay AS16 Damper Force PSD (Record A)

    1.0E-06

    1.0E-05

    1.0E-04

    1.0E-03

    1.0E-021.0E-01

    1.0E+00

    1.0E+01

    1.0E+02

    1.0E+03

    1.0E+04

    0 2 4 6 8 10

    Frequency (Hz)

    PSDofDam

    perForce

    Figure 7.7: Time History and PSD of Stay Acceleration and Damper Force

    (Record A AS16)

    Record B (Figure 7.8) represented another of the highest amplitude RMS

    acceleration events after the installation of the damper on stay AS16, but corresponded to

    a wind speed of about 8.5 m/s and a wind direction of 90 degrees. The RMS force is one

    of the largest recorded for this stay: about 4.8 kN RMS. The acceleration and force plots

    both clearly contain two main frequency components, one at about 2.6 Hz and the other

    at 5.3 Hz, corresponding to the second and fourth modes of the damped stay,

    respectively. The force data are dominated by the second-mode contribution. A number

    of other modes are evident in both spectra, but note that the log scale tends to exaggerate

    their relative contributions. The characteristics of this record suggest that it is a case of

    wind-rain vibration that is being suppressed by the damper, and analysis of the rain

  • 7/30/2019 Field Evaluation of Dampers

    14/17

    269

    bucket data confirms the presence of moderate rainfall at the time of this record (a

    rainfall rate of approximately 25 mm/hr was estimated). Note also the strong asymmetric

    appearance of the acceleration record (and to a lesser extent the force record.) Indeed

    this acceleration record has a mean of zero and is in fact not asymmetric; the addition of

    the appropriately phased second and fourth modes gives this appearance. It should be

    noted, however, that the two components conspire to produce peak accelerations of about

    1g and a peak load in the damper of a little over 9 kN (2000 lb). These values are

    certainly higher than what one would estimate assuming mono-frequency response.

    Consideration of the peaks as well as RMS values should generally be undertaken for this

    reason. The damper is certainly able to effectively control/reduce the large-amplitude

    behavior observed before the installation, and again through the provision of modest

    levels of force.

  • 7/30/2019 Field Evaluation of Dampers

    15/17

    270

    Stay AS16 Acceleration Time History (Record B)

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    0 2 4 6 8 10

    Time (s)

    Acceleration(g)

    Stay AS16 Acceleration PSD (Record B)

    1.0E-07

    1.0E-06

    1.0E-05

    1.0E-04

    1.0E-03

    1.0E-02

    1.0E-01

    1.0E+00

    1.0E+01

    1.0E+02

    0 2 4 6 8 10

    Frequency (Hz)

    PSDof

    Acceleration

    Stay AS16 Damper Force Time History (Record B)

    -10

    -8

    -6

    -4

    -20

    2

    4

    6

    8

    10

    0 2 4 6 8 10

    Time (s)

    Force

    (kN)

    Stay AS16 Damper Force PSD (Record B)

    1.0E-06

    1.0E-05

    1.0E-04

    1.0E-03

    1.0E-021.0E-01

    1.0E+00

    1.0E+01

    1.0E+02

    1.0E+03

    1.0E+04

    0 2 4 6 8 10

    Frequency (Hz)

    PSDofDam

    perForce

    Figure 7.8: Time History and PSD of Stay Acceleration and Damper Force

    (Record B AS16)

    Record C (Figure 7.9) represented the highest amplitude RMS force recorded to

    date on stay AS23, even though the acceleration measured on the stay was small. This

    corresponded to a wind speed of about 10 m/s and a wind direction of 60 degrees. The

    RMS force is the largest recorded for this stay: about 5.7 kN RMS. This record is very

    unusual and interesting for a number of reasons. Note that the acceleration amplitude is

    relatively small about 0.25g and clearly contains a broad range of frequency

    components. The peak force magnitude, however, is close to 8 kN (1800 lb) and is

    dominated (strongly) by the fundamental mode of the stay at 0.66 Hz. Again, the multi-

    frequency contributions plotted at log scale exaggerate the higher mode contributions; the

    most significant higher mode contribution is more than two orders of magnitude lower

  • 7/30/2019 Field Evaluation of Dampers

    16/17

    271

    than that of the fundamental mode. This is believed to be an example of deck-stay

    interaction that the damper is responding to suppress. First, it is unusual to see such a

    strong component of force at the fundamental mode of the stay, as preceding data have

    suggested. Ozkan et al. (2001) discuss a situation where oscillation of a stay was clearly

    preceded and presumably precipitated by oscillation of the deck of the structure in the

    fifth vertical mode of vibration. As discussed therein, the analysis suggested that in

    that case stay AS24 had a fundamental frequency very close to the third symmetric

    vertical mode of the deck, which evidently drove the stay in its fundamental mode. A

    vertical deck frequency was also identified at 0.67 Hz, which in this case is quite

    likely driving (or attempting to drive) stay AS23 in its fundamental mode. Unfortunately,

    the deck accelerometers were non-functional at the time this record was made, so this

    hypothesis cannot be confirmed in this case by reference to deck data. Again, the damper

    seemed to perform well under these circumstances.

  • 7/30/2019 Field Evaluation of Dampers

    17/17

    272

    Stay AS23 Acceleration Time History (Record C)

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    0 2 4 6 8 10

    Time (s)

    Acceleration(g)

    Stay AS23 Acceleration PSD (Record C)

    1.0E-07

    1.0E-06

    1.0E-05

    1.0E-04

    1.0E-03

    1.0E-02

    1.0E-01

    1.0E+00

    1.0E+01

    1.0E+02

    0 2 4 6 8 10

    Frequency (Hz)

    PSDof

    Acceleration

    Stay AS23 Damper Force Time History (Record C)

    -10

    -8

    -6

    -4

    -20

    2

    4

    6

    8

    10

    0 2 4 6 8 10

    Time (s)

    Force

    (kN)

    Stay AS23 -- Record C

    1.0E-05

    1.0E-04

    1.0E-03

    1.0E-02

    1.0E-01

    1.0E+00

    1.0E+01

    1.0E+02

    1.0E+03

    1.0E+04

    0 2 4 6 8 10

    Frequency (Hz)

    PSDofDam

    perForce

    Figure 7.9: Time History and PSD of Stay Acceleration and Damper Force

    (Record C AS23)

    7.4 General Remarks

    The preceding section demonstrates that under a wide range of field parameters

    that the damper solution appears to provide a reasonable and acceptable solution to the

    stay cable vibration phenomenon. Despite these promising results, a few comments and

    cautions are in order.

    The ranges of wind speeds evaluated, even over a three-year period, are limited.

    It has been suggested that high-wind-speed phenomena such as galloping might

    occur in inclined stay cables, and that a damper solution would be incapable of

    providing sufficient capacity to suppress such phenomena. While we have not