FGM IN SR

download FGM IN SR

of 72

Transcript of FGM IN SR

  • 7/28/2019 FGM IN SR

    1/72

    Presentation on

    FREE GOVERNOR MODE OPERATION

  • 7/28/2019 FGM IN SR

    2/72

    FREE GOVERNOR OPERATION

    WHYFREQ COMPARISION

    MAY-02 & MAY-03

    GOVERNOR

    BEFORE GOVERNOR GOVERNOR RESPONSEIN NER

    DEAD BAND GOVERNOR TIME LAG

    BLOCKED GOVERNOR

    ROLE

    DROOPFREQUENCY DECAY RATEBACKLASH

    TYPES OF CONTROLS

    DROOP RESPONSE IN SR

    ABT & GOVERNOR

    ADVANTAGES

    GOVERNOR TYPES

    TIME DELAY

    CHARACTERISTICS

    PROBLEMS UCPE/NERC LIST OF GENERATORS

    FREQUENCY BASED

    DISPATCH

    FREQUENCY BASED

    DISPATCHSUPPRESSED GOVERNOR

    ACTION

    PID CONTROLPTI TAPE ORDERS

  • 7/28/2019 FGM IN SR

    3/72

    ORDERS

    IEGC 6.2 (e) & 6.2(f)IEGC 1.6IEGC 6.2 (g)

    IEGC 6.2 (h)CERC ORDER ON

    WB dt 02/01/01

    KERALA LETTER

    ON FGM

    FREE GOVERNOR

    OPERATION

  • 7/28/2019 FGM IN SR

    4/72

    ROLE OF SYSTEM OPERATOR

    LOAD GENERATION

    BALANCE50

  • 7/28/2019 FGM IN SR

    5/72

    WHY DOES FREQUENCY DROP ?

    Sudden addition of load causes a drop in frequency.

    An increased load is supplied through an increase in the load angle by which

    the rotor lags the stator field.

    It means a loss of Kinetic Energy of the rotating M/c and a slower speed

    of rotation i.e. a lower frequency.

    f = (P/2) X (N/60)Where f = frequency of the system

    P = no of poles of the M/c.

    N = rpm of the M/c.

  • 7/28/2019 FGM IN SR

    6/72

    Load dependent on frequency Free Governor Operation

    Under Frequency Operation

    PRIMARY CONTROLS

  • 7/28/2019 FGM IN SR

    7/72

    PRIMARY CONTROL (UCPE)Primary control involves the action of

    turbine speed governors in generating units,which will respond where the speed(frequency) deviates from the speed(frequency) set point as a result of an

    imbalance between generation and demandin the synchronously interconnectednetwork as a whole. Technical solidarity

    between members will involve thesimultaneous action of primary control on allgenerating units involved in system control.

  • 7/28/2019 FGM IN SR

    8/72

    PRIMARY CONTROL (UCPE)The various assumptions, characteristics and parametersapplied to primary control are as follows:

    The maximum instantaneous deviation P betweengeneration and demand to be corrected by primary controlis 2000 MW

    For the whole system, with a peak load of the order of20000 MW and an off-peak load of the order of 12000 MW,

    assuming 1% self-regulation of load, the quasi-steady-state frequency deviation must not exceed 180 mHz andthe instantaneous frequency must not fall below 49.2 Hz inresponse to a shortfall in generation capacity equal to orless than 2000 MW. The overall network power frequencycharacteristic for the system is set at 1000 MW/Hz

  • 7/28/2019 FGM IN SR

    9/72

    FREQUENCY RESPONSE (NERC)

    NERC

  • 7/28/2019 FGM IN SR

    10/72

    ABT AND GOVERNOR

    POST ABT FREQUENCY WITHIN 49 TO 50.5HZ

    ACHIEVED BY STAGGERING OF LOADS

    FLUCTUATION IN FREQUENCY INCREASED

  • 7/28/2019 FGM IN SR

    11/72

    FREQUENCY COMPARISON FOR

    47.50

    48.00

    48.50

    49.00

    49.50

    50.00

    50.50

    51.00

    51.50

    00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23

    04-MARCH 02 & 03

    2003

    2002

  • 7/28/2019 FGM IN SR

    12/72

    HUMAN GOVERNOR OPERATION

    SYSTEM~TGX

    GOVERNOR

  • 7/28/2019 FGM IN SR

    13/72

    GOVERNOR

    SPEED GOVERNOR IS THE CONTROLLING MECHANISM WHICH

    CONTROLS THE INPUT TO THE PRIME MOVER AUTOMATICALLY WHEN

    THERE IS A CHANGE IN SYSTEM SPEED (FREQUENCY)

    WHEN THERE IS A CHANGE IN SYSTEM FREQUENCY GOVERNOR

    RESPONSE BY CAUSING VALVES/GATES TO OPEN/CLOSE TO

    INCREASE/DECREASE THE INPUT TO THE PRIME MOVER

  • 7/28/2019 FGM IN SR

    14/72

    MISCONCEPTION

    Governors attempt to restore frequency to normal.

    In reality, Governors attempt to restore load generation balance, using

    frequency change as a signal.

  • 7/28/2019 FGM IN SR

    15/72

  • 7/28/2019 FGM IN SR

    16/72

  • 7/28/2019 FGM IN SR

    17/72

    CHARACTERISTICS

    1. Respond promptly to a small change inspeed.

    2. Adjust the throttle valve with a minimum

    of overshoot.3. Have sufficient power to overcome

    friction losses and unbalance forces in

    the throttle valve.4. Permit very little speed fluctuation under

    constant load and steam conditions.

  • 7/28/2019 FGM IN SR

    18/72

    TYPES OF GOVERNORS

    Mechanical shaft

    Direct acting orifice

    Oil relay

    Precision oil relayElectronic governor

  • 7/28/2019 FGM IN SR

    19/72

    DEAD BAND

    DEAD BAND OF THE SPEED GOVERNORING SYSTEM IS THE TOTAL

    AMOUNT OF CHANGE IN STEADY STATE SPEED WITHIN WHICH THEREIS NO ACTION BY GOVERNOR.

    Turbine rated outputMW

    Dead band percent ofrated speed

    IN 50HZ BASE

    < 5MW 0.15 0.075HZ

    5 to 30mw 0.10 0.050HZ

    > 30mw 0.06 0.030HZ

    IEC - 45

  • 7/28/2019 FGM IN SR

    20/72

  • 7/28/2019 FGM IN SR

    21/72

    DROOP CHARACTERISTICS

    THE AMOUNT OF SPEED (OR FREQUENCY) CHANGE THAT IS NECESSARY

    TO CAUSE THE MAIN PRIME MOVER CONTROL MECHANISM TO MOVEFROM FULLY CLOSED TO FULLY OPEN.

    NORMAL RANGE - 3 TO 5%

    THE MINIMUM RATE OF CHANGE OF SPEED SHOULD NOT BE LESS THAN

    0.4 TIMES OF ITS DROOP.

    THE MAXIMUM RATE OF CHANGE OF SPEED SHOULD NOT BE MORE

    THAN 3 TIMES OF ITS DROOP.

  • 7/28/2019 FGM IN SR

    22/72

    5% DROOP ON 200MW GENERATOR

    0

    40

    80

    120

    160

    200

    49 49.5 50 50.5 51 51.5

    FREQ IN HZ --->

    GENERATIONIN

    MW

    --->

  • 7/28/2019 FGM IN SR

    23/72

    PARTICIPATION OF 5% DROOP ON 200MW & 500MW GENERATORS

    0

    100

    200

    300

    400

    500

    600

    49 49.5 50 50.5 51 51.5

    FREQ IN HZ --->

    GENERATIONIN

    MW

    --->

    100MW for 0.5HZ

    Frequency

    40MW for 0.5HZ

    Frequency

  • 7/28/2019 FGM IN SR

    24/72

    GOVERNOR DROOP 5% (500MW UNIT)

    0

    100

    200

    300

    400

    500

    600

    47 47.5 48 48.5 49 49.5 50 50.5 51 51.5 52 52.5 53

    FREQ IN HZ --->

    GENERATIONINM

    W

    ---->

    600

    500

    300

    200

    0

  • 7/28/2019 FGM IN SR

    25/72

    GOVERNOR DROOP 5% (210MW UNIT)

    0

    50

    100

    150

    200

    250

    47 47.5 48 48.5 49 49.5 50 50.5 51 51.5 52 52.5 53

    FREQ IN HZ --->

    GENERATIONINM

    W

    ---->

    250

    210

    125

    85

    0

  • 7/28/2019 FGM IN SR

    26/72

    RESPONSE BY A 500 MW GENERATOR WITH DIFFRENT DROOP

    0

    375

    125

    0

    200

    500

    400

    300

    100

    500

    250

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    48 48.5 49 49.5 50 50.5 51 51.5

    HZ->

    MW

    ->

    5 % DROOP

    4 % DROOP

  • 7/28/2019 FGM IN SR

    27/72

    GOVERNOR TIME LAG

    TIME TAKEN BY GOVERNOR TO JUST BEGIN CHANGING POWER OUTPUT

    TO STABILISE FREQUENCY.

    OR

    TIME BETWEEN A CHANGE IN GENERATOR SPEED & CHANGE IN

    TURBINE POWER.

    TIME DELAY IN GOVERNOR OPERATION

  • 7/28/2019 FGM IN SR

    28/72

    Dead band 0.25 sec

    Valve opening 0.5 sec

    Steam flow 4 seconds

    During transient state Governor is of little help.

    Effect is felt during steady state

    TIME DELAY IN GOVERNOR OPERATION

  • 7/28/2019 FGM IN SR

    29/72

    BLOCKED GOVERNOR

    BYPASSING THE GOVERNING FEEDBACK MECHANISM TO MAINTAIN

    FIXED GENERATOR OUTPUT.

    DISADVANTAGES:-

    SYSTEM INSTABILITY

    RESTORATION OF SYSTEM FREQUENCY TO NORMAL TAKES MORETIME AFTER A DISTURBANCE.

  • 7/28/2019 FGM IN SR

    30/72

    FREQUENCY DECAY RATE

    Approximate Freq 5 X Lost Generation

    Decay Rate = --------------------------------------

    In Hz / sec Remaining Generation

    Example:-

    2200MW200MW

    Generation Lost

    Freq decay rate = (5 X 200) / 2000 = 0.5 Hz /second

  • 7/28/2019 FGM IN SR

    31/72

    NEYVELI U-4 ON FGM ON 19/06/2003

    160

    170

    180

    190

    200

    210

    220

    11:00 11:15 11:30 11:45 12:00 12:15 12:30 12:45 13:00

    TIME ->

    MW->

    49

    49.2

    49.4

    49.6

    49.8

    50

    50.2

    50.4

    HZ->

    GENERATION

    FREQUENCY

  • 7/28/2019 FGM IN SR

    32/72

    DROOP CHARACTERISTICS OF NYL U4

    170

    175

    180

    185

    190

    195

    200

    205

    210

    49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

    FREQ CHANGE 49.7 - > 50.4 0.7Hz

    GEN CHANGE 205 -> 177 35MW

    CHANGE IN GEN 28 MW FOR 0.7 Hz CHANGE IN FREQ

    FOR 200 MW CHANGE IN GEN FREQ CHANGE REQD =

    (200*0.7)/28 = 5 Hzi.e 5*100 /50 = 10% Droop

  • 7/28/2019 FGM IN SR

    33/72

    NLY U6 ON FGM ON 15/07/03

    145

    150

    155

    160

    165

    170

    175

    180

    185

    190

    195

    11:30 11:45 12:00 12:15 12:30

    TIME-->

    MW

    -->

    49

    49.2

    49.4

    49.6

    49.8

    50

    50.2

    50.4

    50.6

    HZ-->

    GENERATION

    FREQUENCY

  • 7/28/2019 FGM IN SR

    34/72

    DROOP CHARACTERISTICS OF NYL U6

    160

    165

    170

    175

    180

    185

    190

    195

    49.8 49.9 50 50.1 50.2 50.3 50.4 50.5 50.6 50.7

    FREQ CHANGE 49.9 - > 50.5 0.6Hz

    GEN CHANGE 191 -> 168 23MW

    CHANGE IN GEN 24 MW FOR 0.6 Hz CHANGE IN FREQ

    FOR 200 MW CHANGE IN GEN FREQ CHANGE REQD =

    (200*0.6)/24 = 5 Hzi.e 5*100 /50 = 10% Droop

  • 7/28/2019 FGM IN SR

    35/72

    IDUKKI GENERATION ON 16/07/2003

    0

    50

    100

    150

    200

    250

    300

    350

    400

    0 2 4 6 8 10 12 14 16 18 20 22 0

    MW

    48.5

    49

    49.5

    50

    50.5

    51

    FREQ->

    FREQUENCY

    GENERATION

  • 7/28/2019 FGM IN SR

    36/72

    DROOP CHARACTERSTICS OF IDUKKI

    0

    50

    100

    150

    200

    250

    300

    350

    400

    49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1

  • 7/28/2019 FGM IN SR

    37/72

    49.849.1 49.749.649.549.449.2 49.3 49.9

    POINT APOINT B

    POINT C

    POINT D

    POINT A - GENERATION LOSS

    POINT B GOVERNOR ACTION STARTED

    POINT C - FREQUENCY AFTER GOVERNER ACTION

    POINT D FREQUENCY AFTER OPERATOR ACTION

  • 7/28/2019 FGM IN SR

    38/72

    The distance through which one part of connected machinery, as a

    wheel, piston, or screw, can be moved without moving the connected parts.

    BACKLASH

  • 7/28/2019 FGM IN SR

    39/72

    BOILER CONTROLS

    BOILER FOLLOWING SYSTEM

    TURBINE FOLLOWING SYSTEM

    INTEGRATED CONTROL SYSTEM

  • 7/28/2019 FGM IN SR

    40/72

  • 7/28/2019 FGM IN SR

    41/72

  • 7/28/2019 FGM IN SR

    42/72

    50

  • 7/28/2019 FGM IN SR

    43/72

    ADVANTAGES

    1. Reduce the random change of frequency

    2. Mitigate effect of load generation mismatch

    3. Prevents wastage of fuel during low load condition

    4. Faster restoration from grid disturbance

  • 7/28/2019 FGM IN SR

    44/72

    PROBLEMS

    1. Steam deposits on the valve stem .2. Lubrication deposits (i.e., soaps, dirt, detergents,

    etc.) in the top works of the valve exposed to theelements.

    3.Mechanical failures of the valve resulting from bentstems, either in the valve proper or the upperworks, damaged split couplings, etc., all withinabout a 6" area near the center of the valvemechanism.

    4. Galling of the piston in the hydraulic latch cylinder.5. Jamming of the screw spindle in the larger

    cylinder-type valve design due to forcing byoperations personnel

  • 7/28/2019 FGM IN SR

    45/72

    FREE GOVERNOR OPERATION

    Mother of all ControlsSelf healing mechanism

    Collectively ControlMost equitable

    Reduces risk of collapseMakes restoration easy

    World wide mandatory practice

  • 7/28/2019 FGM IN SR

    46/72

  • 7/28/2019 FGM IN SR

    47/72

    5% DROOP OF 210MW UNIT OF STATION A

    VARIABLE COST = 140 Ps

    140

    150

    160

    170

    180

    190

    200

    210

    49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

    FREQ IN HZ --->

    GENERATIONIN

    MW--->

    0

    60

    120

    180

    240

    300

    360

    420

    UIPRICE-->

    STEADY STATE OPERATION

    AT 50 HZ GEN= 190MW

  • 7/28/2019 FGM IN SR

    48/72

    5% DROOP OF 210MW UNIT OF STATION A

    VARIABLE COST = 140 Ps

    140

    150

    160

    170

    180

    190

    200

    210

    49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

    FREQ IN HZ --->

    GENERATIONIN

    MW--->

    0

    60

    120

    180

    240

    300

    360

    420

    UIPRICE-->

    OVER GENERATED BY 5%

    FREQUENCY DIPPED TO 49.8 HZ

    GENERATION INCREASED BY 10 MW

  • 7/28/2019 FGM IN SR

    49/72

    5% DROOP OF 210MW UNIT OF STATION A

    VARIABLE COST = 140 Ps

    140

    150

    160

    170

    180

    190

    200

    210

    49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

    FREQ IN HZ --->

    GENERATIONIN

    MW--->

    0

    60

    120

    180

    240

    300

    360

    420

    UIPRICE-->

    OVER GENERATED BY 5%

  • 7/28/2019 FGM IN SR

    50/72

    5% DROOP OF 210MW UNIT OF STATION A

    VARIABLE COST = 140 Ps

    140

    150

    160

    170

    180

    190

    200

    210

    49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

    FREQ IN HZ --->

    GENERATIONIN

    MW--->

    0

    60

    120

    180

    240

    300

    360

    420

    UIPRICE-->

    STEADY STATE OPERATION

    AT 50 HZ GEN= 190MW

  • 7/28/2019 FGM IN SR

    51/72

    5% DROOP OF 210MW UNIT OF STATION A

    VARIABLE COST = 140 Ps

    140

    150

    160

    170

    180

    190

    200

    210

    49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

    FREQ IN HZ --->

    GENERATIONIN

    MW--->

    0

    60

    120

    180

    240

    300

    360

    420

    UIPRICE-->

    UI PRICE = 84 Ps

    FREQUENCY RISE UPTO 50.2 HZ

    GENERATION DECREASED BY 17MW

    INITIAL

  • 7/28/2019 FGM IN SR

    52/72

    5% DROOP OF 210MW UNIT OF STATION B

    VARIABLE COST = 70 Ps

    140

    150

    160

    170

    180

    190

    200

    210

    49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

    FREQ IN HZ --->

    GENERATIONIN

    MW--->

    0

    60

    120

    180

    240

    300

    360

    420

    UIPRICE-->

    UI PRICE = 84 Ps

    FREQUENCY RISE UPTO 50.2 HZ

    GENERATION DECREASED BY 17MW

    INITIAL

  • 7/28/2019 FGM IN SR

    53/72

    5% DROOP OF 210MW UNIT OF STATION B

    VARIABLE COST = 70 Ps

    140

    150

    160

    170

    180

    190

    200

    210

    49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

    FREQ IN HZ --->

    GENERATIONIN

    MW--->

    0

    60

    120

    180

    240

    300

    360

    420

    UIPRICE-->

    GENERATION INCREASED BY 17MW

    FINALSINCE VARIABLE COST OF

    STATION B < UI PRICE

  • 7/28/2019 FGM IN SR

    54/72

    5% DROOP OF 210MW UNIT OF STATION A

    VARIABLE COST = 140 Ps

    140

    150

    160

    170

    180

    190

    200

    210

    49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5

    FREQ IN HZ --->

    GENERATIONIN

    MW--->

    0

    60

    120

    180

    240

    300

    360

    420

    UIPRICE-->

    FINAL

    GENERATION FURTHER REDUCED BY

    17MW

    SINCE VARIABLE COST OF

    STATION A > UI PRICE

    PROPORTIONAL CONTROL

  • 7/28/2019 FGM IN SR

    55/72

    Kc

    FB

    PROPORTIONAL CONTROL

    A simple form of control, where the controller

    response is proportional to the control error.

    Provides immediate controller response to setpoint

    change, but speed may not settle exactly on SP usingproportional control alone

  • 7/28/2019 FGM IN SR

    56/72

    INTEGRAL CONTROL

  • 7/28/2019 FGM IN SR

    57/72

    FB

    fdt1/Tc

    INTEGRAL CONTROL

    Control action is control error integratedover time.

    Integrates the error over time to overcome theoffset from Proportionalalone such that speed =

    SP. However, Integral action may cause

    overshoot, oscillation and/or instability problems

    Kc

  • 7/28/2019 FGM IN SR

    58/72

    PID Parameter Tuning PI

    only

    DIFFERENTIAL CONTROL

  • 7/28/2019 FGM IN SR

    59/72

    FB

    df/dtTd

    DIFFERENTIAL CONTROL

    In dif ferent ia l contro l, control action is based onthe change (derivative) of the control error.

    Used to put the reigns on PI control to prevent

    overshoot and oscillation and to add stability

    Kc

    PID CONTROL

  • 7/28/2019 FGM IN SR

    60/72

    A form of control based on the three basic

    types of control: proport ional, integraland

    dif ferentialcont ro l. PID Contro l lersare

    created by combining P, I and D elements toget the desired control characteristic.

    PID CONTROL

  • 7/28/2019 FGM IN SR

    61/72

  • 7/28/2019 FGM IN SR

    62/72

    SUPPRESSED GOVERNOR OPERATION

    http://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/PIDMOD2.xls
  • 7/28/2019 FGM IN SR

    63/72

    SUPPRESSED GOVERNOR OPERATION

    OPEN

  • 7/28/2019 FGM IN SR

    64/72

    CERC ORDER ON IEGC DATED 22.02.2002QUOTE

  • 7/28/2019 FGM IN SR

    65/72

    1.6 Free-Governor Action:

    The dates from which the stipulations under sections 4.8(c), 4.8(d), 6.2(e), 6.2(f),

    6.2(g) and 6.2(h) would come into effect shall be as under :

    (i) All thermal generating units of installed capacity 200 MW and above and reservoir

    based hydro units of installed capacity 50 MW and above :

    Southern Region }

    }

    Eastern Region }

    }

    Northern Region } The date for the

    } implementation of theWestern Region } Commercial mechanism

    } mentioned in Section 7.1(d)

    (ii) All thermal and reservoir based hydro } for the respective region.

    generating units of installed capacity }

    10 MW and above in North Eastern Region }

    (iii) All other generating units - three months after the above dates for the respectiveregions except in the case of Nuclear Power Stations which shall be exempted till the next

    review of the IEGC.

    Any exemptionfrom the above may be granted only by CERC for which the

    concerned constituent shall file a petition in advance.

    UNQUOTE

    CERC ORDER ON IEGC DATED 22.02.2002QUOTE

  • 7/28/2019 FGM IN SR

    66/72

    6.2(e) All generating units, which are synchronised with the grid, irrespective of

    their ownership, type and size, shall have their governors in normal operation at all

    times. If any generating unit of over fifty (50) MW size (10 MW for North Eastern

    Region) is required to be operated without its governor in normal operation, the

    RLDC shall be immediately advised about the reason and duration of such

    operation. All governors shall have a droop of between 3% and 6%.

    6.2(f) Facilities available with/in load limiters, Automatic Turbine Run up System

    (ATRS), Turbine supervisory control, coordinated control system, etc. shall not be

    used to suppress the normal governor action in any manner. No dead bands and/or

    time delays shall be deliberately introduced.

    UNQUOTE

    CERC ORDER ON IEGC DATED 22.02.2002QUOTE

  • 7/28/2019 FGM IN SR

    67/72

    6.2(g) All Generating Units, operating at/up to 100% of their Maximum Continuous

    Rating (MCR) shall normally be capable of (and shall not in any way be prevented from)

    instantaneously picking up five per cent (5%) extra load for at least five (5) minutes or

    within technical limits prescribed by the manufacturer when frequency falls due to a

    system contingency. The generating units operating at above 100% of their MCR shall

    be capable of (and shall not be prevented from) going at least up to 105% of their MCR

    when frequency falls suddenly. Any generating unit of over fifty (50) MW size (10 MW for

    NER) not complying with the above requirement, shall be kept in operation

    (synchronised with the Regional grid) only after obtaining the permission of RLDC.

    However, the constituent can make up the corresponding short fall in spinning reserve

    by maintaining an extra spinning reserve on the other generating units of the constituent.

    UNQUOTE

    CERC ORDER ON IEGC DATED 22.02.2002QUOTE

  • 7/28/2019 FGM IN SR

    68/72

    6.2(h) The recommended rate for changing the governor setting, i.e. supplementary

    control for increasing or decreasing the output (generation level) for all generating .units,

    irrespective of their type and size, would be one (1.0) per cent per minute or as per

    manufacturer's limits. However, if frequency falls below 49.5 Hz, all partly loaded

    generating units shall pick up additional load at a faster rate, according to their capability.

    UNQUOTE

    FREE GOVERNOR MODE OF

  • 7/28/2019 FGM IN SR

    69/72

    OPERATION

    Quote

    6.2 (c) All generating units, which are synchronised with the

    grid, irrespective of their ownership, type and size, shall have

    their governors in normal operation at all times. If any

    generating unit of over fifty (50) MW size (10 MW for North

    Eastern Region) is required to be operated without its governor

    in normal operation, the RLDC shall be immediately advised

    about the reason and duration of such operation. All governors

    shall have a droop of between 3% and 6%.

    Unquote

    CERC Order ON IEGC dated 21.12.1999

    SRLDC Requested all constituents including ISGS vide letter

    dated 3rd Jan 03 to take a lead in this matter.

    FREE GOVERNOR MODE OF

  • 7/28/2019 FGM IN SR

    70/72

    OPERATION The matter discussed in 368th OCC meeting

    All SR constituents/ISGS agreed to convey their readiness by 21.01.2003

    SRLDC again requested all constituents vide letter dt.21.01.03 to intimate unit/station wise status/ programme

    Matter discussed in 109th TCC/131st SREB meeting.

    ISGS/SR constituents agreed for FGM by 1st May 2003.

    Discussed in 369th, 370th, 371st & 372nd OCC meetings.

    KSEB & TNEB furnished unit wise/ station wise program/ constraint/ preparedness

    APTRANSCO conveyed readiness for FGM of all generators except thermal units of APGENCO

    Freq response characteristics calculation details covering 3 events furnished for examination & necessary

    feedback by the constituents.

    Constituents Actual response Shortfall(AVG) (AVG)

    AP 2 % 98 %

    KAR 17 % 83 %

    KER 29 % 71 %

    TN 13 % 87 %

    Matter again discussed in 110th TCC/132nd SREB meeting.

    All SR constituents/ISGS agreed for FGM by 1st August 2003.

    Action by constituents to achieve the target to be discussed.

    Present status to be reviewed.

    NLY-II U#4LETTERS

    http://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/Understand_Calculate_Frequency_Response.pdfhttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/LIST%20OF%20GENERATORS%20TO%20BE%20ON%20FREE%20GOV%20MODE.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xls
  • 7/28/2019 FGM IN SR

    71/72

    NEYVELI U-4 ON FGM ON 19/06/2003

    160

    170

    180

    190

    200

    210

    220

    11:00 11:15 11:30 11:45 12:00 12:15 12:30 12:45 13:00

    49

    49.2

    49.4

    49.6

    49.8

    50

    50.2

    50.4

    NYL U-4 GENERATION

    REDUCTION OF 21 MW IN 5 MTS

    FREQUENCY

  • 7/28/2019 FGM IN SR

    72/72

    Thank you