FGM IN SR
Transcript of FGM IN SR
-
7/28/2019 FGM IN SR
1/72
Presentation on
FREE GOVERNOR MODE OPERATION
-
7/28/2019 FGM IN SR
2/72
FREE GOVERNOR OPERATION
WHYFREQ COMPARISION
MAY-02 & MAY-03
GOVERNOR
BEFORE GOVERNOR GOVERNOR RESPONSEIN NER
DEAD BAND GOVERNOR TIME LAG
BLOCKED GOVERNOR
ROLE
DROOPFREQUENCY DECAY RATEBACKLASH
TYPES OF CONTROLS
DROOP RESPONSE IN SR
ABT & GOVERNOR
ADVANTAGES
GOVERNOR TYPES
TIME DELAY
CHARACTERISTICS
PROBLEMS UCPE/NERC LIST OF GENERATORS
FREQUENCY BASED
DISPATCH
FREQUENCY BASED
DISPATCHSUPPRESSED GOVERNOR
ACTION
PID CONTROLPTI TAPE ORDERS
-
7/28/2019 FGM IN SR
3/72
ORDERS
IEGC 6.2 (e) & 6.2(f)IEGC 1.6IEGC 6.2 (g)
IEGC 6.2 (h)CERC ORDER ON
WB dt 02/01/01
KERALA LETTER
ON FGM
FREE GOVERNOR
OPERATION
-
7/28/2019 FGM IN SR
4/72
ROLE OF SYSTEM OPERATOR
LOAD GENERATION
BALANCE50
-
7/28/2019 FGM IN SR
5/72
WHY DOES FREQUENCY DROP ?
Sudden addition of load causes a drop in frequency.
An increased load is supplied through an increase in the load angle by which
the rotor lags the stator field.
It means a loss of Kinetic Energy of the rotating M/c and a slower speed
of rotation i.e. a lower frequency.
f = (P/2) X (N/60)Where f = frequency of the system
P = no of poles of the M/c.
N = rpm of the M/c.
-
7/28/2019 FGM IN SR
6/72
Load dependent on frequency Free Governor Operation
Under Frequency Operation
PRIMARY CONTROLS
-
7/28/2019 FGM IN SR
7/72
PRIMARY CONTROL (UCPE)Primary control involves the action of
turbine speed governors in generating units,which will respond where the speed(frequency) deviates from the speed(frequency) set point as a result of an
imbalance between generation and demandin the synchronously interconnectednetwork as a whole. Technical solidarity
between members will involve thesimultaneous action of primary control on allgenerating units involved in system control.
-
7/28/2019 FGM IN SR
8/72
PRIMARY CONTROL (UCPE)The various assumptions, characteristics and parametersapplied to primary control are as follows:
The maximum instantaneous deviation P betweengeneration and demand to be corrected by primary controlis 2000 MW
For the whole system, with a peak load of the order of20000 MW and an off-peak load of the order of 12000 MW,
assuming 1% self-regulation of load, the quasi-steady-state frequency deviation must not exceed 180 mHz andthe instantaneous frequency must not fall below 49.2 Hz inresponse to a shortfall in generation capacity equal to orless than 2000 MW. The overall network power frequencycharacteristic for the system is set at 1000 MW/Hz
-
7/28/2019 FGM IN SR
9/72
FREQUENCY RESPONSE (NERC)
NERC
-
7/28/2019 FGM IN SR
10/72
ABT AND GOVERNOR
POST ABT FREQUENCY WITHIN 49 TO 50.5HZ
ACHIEVED BY STAGGERING OF LOADS
FLUCTUATION IN FREQUENCY INCREASED
-
7/28/2019 FGM IN SR
11/72
FREQUENCY COMPARISON FOR
47.50
48.00
48.50
49.00
49.50
50.00
50.50
51.00
51.50
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
04-MARCH 02 & 03
2003
2002
-
7/28/2019 FGM IN SR
12/72
HUMAN GOVERNOR OPERATION
SYSTEM~TGX
GOVERNOR
-
7/28/2019 FGM IN SR
13/72
GOVERNOR
SPEED GOVERNOR IS THE CONTROLLING MECHANISM WHICH
CONTROLS THE INPUT TO THE PRIME MOVER AUTOMATICALLY WHEN
THERE IS A CHANGE IN SYSTEM SPEED (FREQUENCY)
WHEN THERE IS A CHANGE IN SYSTEM FREQUENCY GOVERNOR
RESPONSE BY CAUSING VALVES/GATES TO OPEN/CLOSE TO
INCREASE/DECREASE THE INPUT TO THE PRIME MOVER
-
7/28/2019 FGM IN SR
14/72
MISCONCEPTION
Governors attempt to restore frequency to normal.
In reality, Governors attempt to restore load generation balance, using
frequency change as a signal.
-
7/28/2019 FGM IN SR
15/72
-
7/28/2019 FGM IN SR
16/72
-
7/28/2019 FGM IN SR
17/72
CHARACTERISTICS
1. Respond promptly to a small change inspeed.
2. Adjust the throttle valve with a minimum
of overshoot.3. Have sufficient power to overcome
friction losses and unbalance forces in
the throttle valve.4. Permit very little speed fluctuation under
constant load and steam conditions.
-
7/28/2019 FGM IN SR
18/72
TYPES OF GOVERNORS
Mechanical shaft
Direct acting orifice
Oil relay
Precision oil relayElectronic governor
-
7/28/2019 FGM IN SR
19/72
DEAD BAND
DEAD BAND OF THE SPEED GOVERNORING SYSTEM IS THE TOTAL
AMOUNT OF CHANGE IN STEADY STATE SPEED WITHIN WHICH THEREIS NO ACTION BY GOVERNOR.
Turbine rated outputMW
Dead band percent ofrated speed
IN 50HZ BASE
< 5MW 0.15 0.075HZ
5 to 30mw 0.10 0.050HZ
> 30mw 0.06 0.030HZ
IEC - 45
-
7/28/2019 FGM IN SR
20/72
-
7/28/2019 FGM IN SR
21/72
DROOP CHARACTERISTICS
THE AMOUNT OF SPEED (OR FREQUENCY) CHANGE THAT IS NECESSARY
TO CAUSE THE MAIN PRIME MOVER CONTROL MECHANISM TO MOVEFROM FULLY CLOSED TO FULLY OPEN.
NORMAL RANGE - 3 TO 5%
THE MINIMUM RATE OF CHANGE OF SPEED SHOULD NOT BE LESS THAN
0.4 TIMES OF ITS DROOP.
THE MAXIMUM RATE OF CHANGE OF SPEED SHOULD NOT BE MORE
THAN 3 TIMES OF ITS DROOP.
-
7/28/2019 FGM IN SR
22/72
5% DROOP ON 200MW GENERATOR
0
40
80
120
160
200
49 49.5 50 50.5 51 51.5
FREQ IN HZ --->
GENERATIONIN
MW
--->
-
7/28/2019 FGM IN SR
23/72
PARTICIPATION OF 5% DROOP ON 200MW & 500MW GENERATORS
0
100
200
300
400
500
600
49 49.5 50 50.5 51 51.5
FREQ IN HZ --->
GENERATIONIN
MW
--->
100MW for 0.5HZ
Frequency
40MW for 0.5HZ
Frequency
-
7/28/2019 FGM IN SR
24/72
GOVERNOR DROOP 5% (500MW UNIT)
0
100
200
300
400
500
600
47 47.5 48 48.5 49 49.5 50 50.5 51 51.5 52 52.5 53
FREQ IN HZ --->
GENERATIONINM
W
---->
600
500
300
200
0
-
7/28/2019 FGM IN SR
25/72
GOVERNOR DROOP 5% (210MW UNIT)
0
50
100
150
200
250
47 47.5 48 48.5 49 49.5 50 50.5 51 51.5 52 52.5 53
FREQ IN HZ --->
GENERATIONINM
W
---->
250
210
125
85
0
-
7/28/2019 FGM IN SR
26/72
RESPONSE BY A 500 MW GENERATOR WITH DIFFRENT DROOP
0
375
125
0
200
500
400
300
100
500
250
0
50
100
150
200
250
300
350
400
450
500
48 48.5 49 49.5 50 50.5 51 51.5
HZ->
MW
->
5 % DROOP
4 % DROOP
-
7/28/2019 FGM IN SR
27/72
GOVERNOR TIME LAG
TIME TAKEN BY GOVERNOR TO JUST BEGIN CHANGING POWER OUTPUT
TO STABILISE FREQUENCY.
OR
TIME BETWEEN A CHANGE IN GENERATOR SPEED & CHANGE IN
TURBINE POWER.
TIME DELAY IN GOVERNOR OPERATION
-
7/28/2019 FGM IN SR
28/72
Dead band 0.25 sec
Valve opening 0.5 sec
Steam flow 4 seconds
During transient state Governor is of little help.
Effect is felt during steady state
TIME DELAY IN GOVERNOR OPERATION
-
7/28/2019 FGM IN SR
29/72
BLOCKED GOVERNOR
BYPASSING THE GOVERNING FEEDBACK MECHANISM TO MAINTAIN
FIXED GENERATOR OUTPUT.
DISADVANTAGES:-
SYSTEM INSTABILITY
RESTORATION OF SYSTEM FREQUENCY TO NORMAL TAKES MORETIME AFTER A DISTURBANCE.
-
7/28/2019 FGM IN SR
30/72
FREQUENCY DECAY RATE
Approximate Freq 5 X Lost Generation
Decay Rate = --------------------------------------
In Hz / sec Remaining Generation
Example:-
2200MW200MW
Generation Lost
Freq decay rate = (5 X 200) / 2000 = 0.5 Hz /second
-
7/28/2019 FGM IN SR
31/72
NEYVELI U-4 ON FGM ON 19/06/2003
160
170
180
190
200
210
220
11:00 11:15 11:30 11:45 12:00 12:15 12:30 12:45 13:00
TIME ->
MW->
49
49.2
49.4
49.6
49.8
50
50.2
50.4
HZ->
GENERATION
FREQUENCY
-
7/28/2019 FGM IN SR
32/72
DROOP CHARACTERISTICS OF NYL U4
170
175
180
185
190
195
200
205
210
49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5
FREQ CHANGE 49.7 - > 50.4 0.7Hz
GEN CHANGE 205 -> 177 35MW
CHANGE IN GEN 28 MW FOR 0.7 Hz CHANGE IN FREQ
FOR 200 MW CHANGE IN GEN FREQ CHANGE REQD =
(200*0.7)/28 = 5 Hzi.e 5*100 /50 = 10% Droop
-
7/28/2019 FGM IN SR
33/72
NLY U6 ON FGM ON 15/07/03
145
150
155
160
165
170
175
180
185
190
195
11:30 11:45 12:00 12:15 12:30
TIME-->
MW
-->
49
49.2
49.4
49.6
49.8
50
50.2
50.4
50.6
HZ-->
GENERATION
FREQUENCY
-
7/28/2019 FGM IN SR
34/72
DROOP CHARACTERISTICS OF NYL U6
160
165
170
175
180
185
190
195
49.8 49.9 50 50.1 50.2 50.3 50.4 50.5 50.6 50.7
FREQ CHANGE 49.9 - > 50.5 0.6Hz
GEN CHANGE 191 -> 168 23MW
CHANGE IN GEN 24 MW FOR 0.6 Hz CHANGE IN FREQ
FOR 200 MW CHANGE IN GEN FREQ CHANGE REQD =
(200*0.6)/24 = 5 Hzi.e 5*100 /50 = 10% Droop
-
7/28/2019 FGM IN SR
35/72
IDUKKI GENERATION ON 16/07/2003
0
50
100
150
200
250
300
350
400
0 2 4 6 8 10 12 14 16 18 20 22 0
MW
48.5
49
49.5
50
50.5
51
FREQ->
FREQUENCY
GENERATION
-
7/28/2019 FGM IN SR
36/72
DROOP CHARACTERSTICS OF IDUKKI
0
50
100
150
200
250
300
350
400
49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1
-
7/28/2019 FGM IN SR
37/72
49.849.1 49.749.649.549.449.2 49.3 49.9
POINT APOINT B
POINT C
POINT D
POINT A - GENERATION LOSS
POINT B GOVERNOR ACTION STARTED
POINT C - FREQUENCY AFTER GOVERNER ACTION
POINT D FREQUENCY AFTER OPERATOR ACTION
-
7/28/2019 FGM IN SR
38/72
The distance through which one part of connected machinery, as a
wheel, piston, or screw, can be moved without moving the connected parts.
BACKLASH
-
7/28/2019 FGM IN SR
39/72
BOILER CONTROLS
BOILER FOLLOWING SYSTEM
TURBINE FOLLOWING SYSTEM
INTEGRATED CONTROL SYSTEM
-
7/28/2019 FGM IN SR
40/72
-
7/28/2019 FGM IN SR
41/72
-
7/28/2019 FGM IN SR
42/72
50
-
7/28/2019 FGM IN SR
43/72
ADVANTAGES
1. Reduce the random change of frequency
2. Mitigate effect of load generation mismatch
3. Prevents wastage of fuel during low load condition
4. Faster restoration from grid disturbance
-
7/28/2019 FGM IN SR
44/72
PROBLEMS
1. Steam deposits on the valve stem .2. Lubrication deposits (i.e., soaps, dirt, detergents,
etc.) in the top works of the valve exposed to theelements.
3.Mechanical failures of the valve resulting from bentstems, either in the valve proper or the upperworks, damaged split couplings, etc., all withinabout a 6" area near the center of the valvemechanism.
4. Galling of the piston in the hydraulic latch cylinder.5. Jamming of the screw spindle in the larger
cylinder-type valve design due to forcing byoperations personnel
-
7/28/2019 FGM IN SR
45/72
FREE GOVERNOR OPERATION
Mother of all ControlsSelf healing mechanism
Collectively ControlMost equitable
Reduces risk of collapseMakes restoration easy
World wide mandatory practice
-
7/28/2019 FGM IN SR
46/72
-
7/28/2019 FGM IN SR
47/72
5% DROOP OF 210MW UNIT OF STATION A
VARIABLE COST = 140 Ps
140
150
160
170
180
190
200
210
49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5
FREQ IN HZ --->
GENERATIONIN
MW--->
0
60
120
180
240
300
360
420
UIPRICE-->
STEADY STATE OPERATION
AT 50 HZ GEN= 190MW
-
7/28/2019 FGM IN SR
48/72
5% DROOP OF 210MW UNIT OF STATION A
VARIABLE COST = 140 Ps
140
150
160
170
180
190
200
210
49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5
FREQ IN HZ --->
GENERATIONIN
MW--->
0
60
120
180
240
300
360
420
UIPRICE-->
OVER GENERATED BY 5%
FREQUENCY DIPPED TO 49.8 HZ
GENERATION INCREASED BY 10 MW
-
7/28/2019 FGM IN SR
49/72
5% DROOP OF 210MW UNIT OF STATION A
VARIABLE COST = 140 Ps
140
150
160
170
180
190
200
210
49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5
FREQ IN HZ --->
GENERATIONIN
MW--->
0
60
120
180
240
300
360
420
UIPRICE-->
OVER GENERATED BY 5%
-
7/28/2019 FGM IN SR
50/72
5% DROOP OF 210MW UNIT OF STATION A
VARIABLE COST = 140 Ps
140
150
160
170
180
190
200
210
49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5
FREQ IN HZ --->
GENERATIONIN
MW--->
0
60
120
180
240
300
360
420
UIPRICE-->
STEADY STATE OPERATION
AT 50 HZ GEN= 190MW
-
7/28/2019 FGM IN SR
51/72
5% DROOP OF 210MW UNIT OF STATION A
VARIABLE COST = 140 Ps
140
150
160
170
180
190
200
210
49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5
FREQ IN HZ --->
GENERATIONIN
MW--->
0
60
120
180
240
300
360
420
UIPRICE-->
UI PRICE = 84 Ps
FREQUENCY RISE UPTO 50.2 HZ
GENERATION DECREASED BY 17MW
INITIAL
-
7/28/2019 FGM IN SR
52/72
5% DROOP OF 210MW UNIT OF STATION B
VARIABLE COST = 70 Ps
140
150
160
170
180
190
200
210
49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5
FREQ IN HZ --->
GENERATIONIN
MW--->
0
60
120
180
240
300
360
420
UIPRICE-->
UI PRICE = 84 Ps
FREQUENCY RISE UPTO 50.2 HZ
GENERATION DECREASED BY 17MW
INITIAL
-
7/28/2019 FGM IN SR
53/72
5% DROOP OF 210MW UNIT OF STATION B
VARIABLE COST = 70 Ps
140
150
160
170
180
190
200
210
49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5
FREQ IN HZ --->
GENERATIONIN
MW--->
0
60
120
180
240
300
360
420
UIPRICE-->
GENERATION INCREASED BY 17MW
FINALSINCE VARIABLE COST OF
STATION B < UI PRICE
-
7/28/2019 FGM IN SR
54/72
5% DROOP OF 210MW UNIT OF STATION A
VARIABLE COST = 140 Ps
140
150
160
170
180
190
200
210
49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5
FREQ IN HZ --->
GENERATIONIN
MW--->
0
60
120
180
240
300
360
420
UIPRICE-->
FINAL
GENERATION FURTHER REDUCED BY
17MW
SINCE VARIABLE COST OF
STATION A > UI PRICE
PROPORTIONAL CONTROL
-
7/28/2019 FGM IN SR
55/72
Kc
FB
PROPORTIONAL CONTROL
A simple form of control, where the controller
response is proportional to the control error.
Provides immediate controller response to setpoint
change, but speed may not settle exactly on SP usingproportional control alone
-
7/28/2019 FGM IN SR
56/72
INTEGRAL CONTROL
-
7/28/2019 FGM IN SR
57/72
FB
fdt1/Tc
INTEGRAL CONTROL
Control action is control error integratedover time.
Integrates the error over time to overcome theoffset from Proportionalalone such that speed =
SP. However, Integral action may cause
overshoot, oscillation and/or instability problems
Kc
-
7/28/2019 FGM IN SR
58/72
PID Parameter Tuning PI
only
DIFFERENTIAL CONTROL
-
7/28/2019 FGM IN SR
59/72
FB
df/dtTd
DIFFERENTIAL CONTROL
In dif ferent ia l contro l, control action is based onthe change (derivative) of the control error.
Used to put the reigns on PI control to prevent
overshoot and oscillation and to add stability
Kc
PID CONTROL
-
7/28/2019 FGM IN SR
60/72
A form of control based on the three basic
types of control: proport ional, integraland
dif ferentialcont ro l. PID Contro l lersare
created by combining P, I and D elements toget the desired control characteristic.
PID CONTROL
-
7/28/2019 FGM IN SR
61/72
-
7/28/2019 FGM IN SR
62/72
SUPPRESSED GOVERNOR OPERATION
http://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/PIDMOD2.xls -
7/28/2019 FGM IN SR
63/72
SUPPRESSED GOVERNOR OPERATION
OPEN
-
7/28/2019 FGM IN SR
64/72
CERC ORDER ON IEGC DATED 22.02.2002QUOTE
-
7/28/2019 FGM IN SR
65/72
1.6 Free-Governor Action:
The dates from which the stipulations under sections 4.8(c), 4.8(d), 6.2(e), 6.2(f),
6.2(g) and 6.2(h) would come into effect shall be as under :
(i) All thermal generating units of installed capacity 200 MW and above and reservoir
based hydro units of installed capacity 50 MW and above :
Southern Region }
}
Eastern Region }
}
Northern Region } The date for the
} implementation of theWestern Region } Commercial mechanism
} mentioned in Section 7.1(d)
(ii) All thermal and reservoir based hydro } for the respective region.
generating units of installed capacity }
10 MW and above in North Eastern Region }
(iii) All other generating units - three months after the above dates for the respectiveregions except in the case of Nuclear Power Stations which shall be exempted till the next
review of the IEGC.
Any exemptionfrom the above may be granted only by CERC for which the
concerned constituent shall file a petition in advance.
UNQUOTE
CERC ORDER ON IEGC DATED 22.02.2002QUOTE
-
7/28/2019 FGM IN SR
66/72
6.2(e) All generating units, which are synchronised with the grid, irrespective of
their ownership, type and size, shall have their governors in normal operation at all
times. If any generating unit of over fifty (50) MW size (10 MW for North Eastern
Region) is required to be operated without its governor in normal operation, the
RLDC shall be immediately advised about the reason and duration of such
operation. All governors shall have a droop of between 3% and 6%.
6.2(f) Facilities available with/in load limiters, Automatic Turbine Run up System
(ATRS), Turbine supervisory control, coordinated control system, etc. shall not be
used to suppress the normal governor action in any manner. No dead bands and/or
time delays shall be deliberately introduced.
UNQUOTE
CERC ORDER ON IEGC DATED 22.02.2002QUOTE
-
7/28/2019 FGM IN SR
67/72
6.2(g) All Generating Units, operating at/up to 100% of their Maximum Continuous
Rating (MCR) shall normally be capable of (and shall not in any way be prevented from)
instantaneously picking up five per cent (5%) extra load for at least five (5) minutes or
within technical limits prescribed by the manufacturer when frequency falls due to a
system contingency. The generating units operating at above 100% of their MCR shall
be capable of (and shall not be prevented from) going at least up to 105% of their MCR
when frequency falls suddenly. Any generating unit of over fifty (50) MW size (10 MW for
NER) not complying with the above requirement, shall be kept in operation
(synchronised with the Regional grid) only after obtaining the permission of RLDC.
However, the constituent can make up the corresponding short fall in spinning reserve
by maintaining an extra spinning reserve on the other generating units of the constituent.
UNQUOTE
CERC ORDER ON IEGC DATED 22.02.2002QUOTE
-
7/28/2019 FGM IN SR
68/72
6.2(h) The recommended rate for changing the governor setting, i.e. supplementary
control for increasing or decreasing the output (generation level) for all generating .units,
irrespective of their type and size, would be one (1.0) per cent per minute or as per
manufacturer's limits. However, if frequency falls below 49.5 Hz, all partly loaded
generating units shall pick up additional load at a faster rate, according to their capability.
UNQUOTE
FREE GOVERNOR MODE OF
-
7/28/2019 FGM IN SR
69/72
OPERATION
Quote
6.2 (c) All generating units, which are synchronised with the
grid, irrespective of their ownership, type and size, shall have
their governors in normal operation at all times. If any
generating unit of over fifty (50) MW size (10 MW for North
Eastern Region) is required to be operated without its governor
in normal operation, the RLDC shall be immediately advised
about the reason and duration of such operation. All governors
shall have a droop of between 3% and 6%.
Unquote
CERC Order ON IEGC dated 21.12.1999
SRLDC Requested all constituents including ISGS vide letter
dated 3rd Jan 03 to take a lead in this matter.
FREE GOVERNOR MODE OF
-
7/28/2019 FGM IN SR
70/72
OPERATION The matter discussed in 368th OCC meeting
All SR constituents/ISGS agreed to convey their readiness by 21.01.2003
SRLDC again requested all constituents vide letter dt.21.01.03 to intimate unit/station wise status/ programme
Matter discussed in 109th TCC/131st SREB meeting.
ISGS/SR constituents agreed for FGM by 1st May 2003.
Discussed in 369th, 370th, 371st & 372nd OCC meetings.
KSEB & TNEB furnished unit wise/ station wise program/ constraint/ preparedness
APTRANSCO conveyed readiness for FGM of all generators except thermal units of APGENCO
Freq response characteristics calculation details covering 3 events furnished for examination & necessary
feedback by the constituents.
Constituents Actual response Shortfall(AVG) (AVG)
AP 2 % 98 %
KAR 17 % 83 %
KER 29 % 71 %
TN 13 % 87 %
Matter again discussed in 110th TCC/132nd SREB meeting.
All SR constituents/ISGS agreed for FGM by 1st August 2003.
Action by constituents to achieve the target to be discussed.
Present status to be reviewed.
NLY-II U#4LETTERS
http://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/Understand_Calculate_Frequency_Response.pdfhttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/LIST%20OF%20GENERATORS%20TO%20BE%20ON%20FREE%20GOV%20MODE.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/OCC/373RD%20OCC%20MEETING/FREQUENCY%20RESPONSE%20CHARACTERISTICS%20FOR%20JUNE%202003.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xlshttp://localhost/var/www/apps/FREE%20GOVERNOR%20OPERATION/STATUS%20OF%20GENERATORS%20ON%20FGM.xls -
7/28/2019 FGM IN SR
71/72
NEYVELI U-4 ON FGM ON 19/06/2003
160
170
180
190
200
210
220
11:00 11:15 11:30 11:45 12:00 12:15 12:30 12:45 13:00
49
49.2
49.4
49.6
49.8
50
50.2
50.4
NYL U-4 GENERATION
REDUCTION OF 21 MW IN 5 MTS
FREQUENCY
-
7/28/2019 FGM IN SR
72/72
Thank you