FAQ-BU Wall Mounted Unit technical data Split Sky Air air conditioning systems

Transcript of FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches...

Page 1: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

FAQ-BU

Wall Mounted Unit

technical data

SplitSky Air

air co

nd

ition

ing

system

s

Page 2: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

Split - Sky Air

EE

DE0

5-1

/3 •

05/2

005

Prepar

ed in

Belg

ium

by

Goeki

nt

Gra

phic

s

B - 8400 Ostend Belgium

Specifications are subject to change without prior notice.

ISO14001 assures an effective environmental management system in order to help protecthuman health and the environment from the potentialimpact of our activities, products and services and toassist in maintaining and improving the quality ofthe environment

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Daikin units comply with the European regulations that guarantee the safety of the product.

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.

www.daikineurope.com

Zandvoordestraat 300

Page 3: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

TABLE OF CONTENTSFAQ-BU

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Nominal capacity, capacity steps and nominal input

Technical specifications

3 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

6 Sound level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Sound level data

Sound pressure spectrum

7 Air flow patterns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

8 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Standard accessories

Optional accessories

9 Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

10 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

11 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

For capacity tables, please refer to part II: outdoor units

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

1• Split - Sky Air • Indoor Units

Page 4: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

1 Features

+ Ideal for shops, restaurants or offices requiring maximum floorspace for furniture and fittings

+ The 71 class has a modern casing: it is very compact (290mmheight - 1050mm width) and very lightweight (only 13 kg).

+ Fits neatly on a wall+ Automatic air flow director ensures uniform air flow and

temperature distribution+ The flap of the unit is closed when not operating.+ The front panel of the new casing is easy removable and

washable.+ Extremely quiet in operation both indoors and outdoors+ For equal distribution in larger rooms, up to 3 indoor units can

be connected to 1 outdoor. They are operated from 1 remotecontrol

+ These indoor units can also be connected to the Sky Air superinverter RZQ-B.

+ Daikin remote controls give you easy control at your fingertips.+ The wired remote control provides you with a schedule timer,

enabling to program the air conditioning daily or weekly.+ The optional remote ON/OFF enables you to start/stop the air

conditioning from a mobile phone via a telephone remotecontrol (field supply).

+ The optional forced OFF enables you to switch off the unitautomatically. E.g. when a window is opened, the unit switchesoff.

+ The ’home leave’ operation button prevents large temperaturedifferences by continuously operating at a minimum (heatingmode) or maximum (cooling mode) preset level while you’reout or sleeping. It also allows the indoor temperature to returnquickly to your favourite comfort level.

2 1 3 0 8 q x6 ) ( 6Optional Optional Heat pump

2 steps

Optional

Twin / Triple

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

11

2 • Split - Sky Air • Indoor Units

Page 5: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

2 Specifications

NOMINAL CAPACITY and NOMINAL INPUTFor indoor units only:INDOOR UNITS FAQ71BUV1B FAQ100BUV1BNOMINAL INPUT Cooling kW 0.068 0.101

Heating kW 0.068 0.101

For combination indoor + outdoor units (air cooled):INDOOR UNITS FAQ71B7V3B FAQ100B7V3BOUTDOOR UNITS RR71B7V3B/RR71B7W1B RR100B7V3B/RR100B7W1BNOMINAL CAPACITY (3) Cooling (1) nominal kW 7.10 10.00NOMINAL INPUT Cooling nominal kW 2.65/2.53 3.56/3.52EER 2.68/2.81 2.81/2.84ENERGY LABEL Cooling D/C C/CANNUAL ENERGYCONSUMPTION

Cooling kWh 1,325 1,780

For combination indoor + outdoor units (air cooled):INDOOR UNITS FAQ71B7V3B FAQ100B7V3BOUTDOOR UNITS RQ71B7V3B/RQ71B7W1B RQ100B7V3B/RQ100B7W1BNOMINAL CAPACITY (3) Cooling (1) nominal kW 7.10 10.10

Heating (2) nominal kW 8.00 11.20NOMINAL INPUT Cooling nominal kW 2.65/2.53 3.56/3.52

Heating nominal kW 2.58/2.49 3.96/3.82EER 2.68/2.81 2.81/2.84COP 3.10/3.21 2.83/2.93ENERGY LABEL Cooling D/C C/C

Heating D/C D/DANNUAL ENERGYCONSUMPTION

Cooling kWh 1,325 1,780

For combination indoor + outdoor units (air cooled):INDOOR UNITS FAQ71BUV1B FAQ100BUV1BOUTDOOR UNITS RZQ71B8V3B RZQ100B8V3B/B7W1BNOMINAL CAPACITY (3) Cooling (1) nominal kW 7.10 10.00

Heating (2) nominal kW 8.00 11.20NOMINAL INPUT Cooling nominal kW 2.36 2.78

Heating nominal kW 2.42 3.39EER 3.01 3.6COP 3.31 3.30ENERGY LABEL Cooling B A

Heating C CANNUAL ENERGYCONSUMPTION

Cooling kWh 1,180 1,390

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

12

3• Split - Sky Air • Indoor Units

Page 6: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

TECHNICAL SPECIFICATIONSINDOOR UNITS FAQ71BUV1B FAQ100BUV1BDIMENSIONS Unit H mm 290 360

W mm 1,050 1,570D mm 230 200

WEIGHT Unit kg 13 26MATERIAL Unit ResinCOLOUR Unit WhiteSOUND LEVEL Sound pressure (cooling/heating) (4) high dB(A) 43/43 45/45

low dB(A) 37/37 41/41Sound power (cooling/heating) (5) high dB(A) 59/59 61/61

low dB(A) 53/53 57/57FAN Air flow rate high m3/min 19/19 23/23

low m3/min 15/15 19/19Speed steps 2 stepsType Cross flow fanQty x motor output W 1 x 43 1 x 49

HEAT EXCHANGER Type Cross fin coil (Multi louver fins and Hi-XA tubes)Rows x stages x fin pitch mm 2 x 16 x 1.4 2 x 12 x 1.4Face area m2 0.289 0.332

PIPING CONNECTIONS liquid mm φ9.5 (flare)gas mm φ15.9 (flare)drain I.D. mm φ13 (VP13) φ20 (VP20)drain O.D. mm φ18 (VP13) φ26 (VP20)

INSULATION MATERIAL Heat insulation Foamed polystyrene/foamed polyethylene

For outdoor units Pair / Twin / Triple application See chapter RR-B / RQ-B / RZQ-B

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

2 Specifications

12

4 • Split - Sky Air • Indoor Units

Page 7: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

ELECTRICAL SPECIFICATIONSFor indoor units only: FAQ71BUV1B FAQ100BUV1BCURRENT Nominal running current cooling A

See chapter RR-B7, RQ-B7, RZQ-Bheating A

Max. running current cooling Aheating A

For combination indoor + outdoor units (air cooled): FAQ71B7V3B FAQ100B7V3BRR71B7V3B/RR71B7W1B RR100B7V3B/RR100B7W1B

CURRENT Nominal running current cooling ASee chapter RR-B7Maximum running current cooling A

Starting current cooling A

For combination indoor + outdoor units (air cooled): FAQ71BUV1B FAQ100BUV1BRQ71B7V3B/RQ71B7W1B RQ100B7V3B/RQ100B7W1B

CURRENT Nominal running current cooling ASee chapter RQ-B7Maximum running current cooling A

Starting current cooling A

For combination indoor units + outdoor units: FAQ71BUV1B FAQ100BUV1BRZQ71B8V3B RZQ100B8V3B/B7W1B

CURRENT Nominal running current cooling ASee chapter RZQ-BMaximum running current cooling A

Starting current cooling A

For indoor units only: FAQ71BUV1B FAQ100BUV1BPOWER SUPPLY V1 V1NOMINAL DISTRIBUTIONSYSTEM VOLTAGE

Phase 1∼ 1∼Frequency Hz 50 50Voltage V 220-240 220-240

4D043953

NOTES1 Nominal cooling capacities are based on: indoor temperature 27°CDB/19.5°CWB * outdoor temperature 35°CDB * equivalent refrigerant piping

length: 7.5m * level difference: 0m.

2 Nominal heating capacities are based on: indoor temperature: 20°CDB * outdoor temperature: 7°CDB/6°CWB * refrigerant piping length: 7.5m *level difference 0m.

3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

4 The sound pressure level is measured via a microphone at 1m distance from the unit. It is a relative value, depending on the distance andacoustic environment. For measuring conditions: please refer to item 6 of this chapter.

5 The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.

6 Energy label: scale from A (most efficient) to G (less efficient).

7 Annual energy consumption: based on average use of 500 running hours per year at full load (= nominal conditions).

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

2 Specifications

12

5• Split - Sky Air • Indoor Units

Page 8: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

3 Dimensional drawings

unit (mm)

50or

mor

e30

orm

ore

(Req

uire

dsp

ace)

J80 hole

approx. 345

approx. 475

FAQ71BUV1B

approx. 400

Mounting location

approx. 390

Piping direction

(Required space)

50 or more

Dimensions forfull open frontpanel

Outside line

J80 hole

(piping and wiringintake)

2500 or moreFor installation in high

spaces

(Req

uire

dsp

ace)

120 or less

1 Front panel2 Front grille3 Air outlet4 Gas pipe (J15.9 Flare connection)5 Liquid pipe (J9.5 Flare connection)6 Drain hose VP13 (External dia J18)7 Grounding terminal (M4)8 Right side piping connection hole9 Left side drain piping connection hole

3D038540B

Notes:1 Location of general rated name plate

Right side plate outside surface2 In case of using infrared remote control,

this position will be a signal receiver.Refer to the drawing of infrared remotecontrol in detail.

Name plate

50 or more

Piping directionNote) 2

Piping direction

(Required space)

unit (mm)

50or

mor

e

250 or more

(Req

uire

dsp

ace)

J80 hole

approx. 450

approx. 600

FAQ100BUV1B

8-5x20 Oval hole (for wood screw)

Mounting locationDetailjA (Mounting hole for installation plate)

approx. 580

Piping direction

(Required space)

50 or more50 or more

(Required space)

5-6x20 Oval hole (for wood screw)

13-J5 Hole (for wood screw)

2-J12 Hole (for bolt)(piping and wiringintake)

Note 2. (service space for air filter)

Direction for air filter draw out

1 Front grille2 Air filter3 Discharge outlet4 Gas piping connection (J15.9 flare)5 Gas piping connection (J9.5 flare)6 Drain pipe connection (VP20 O.D. J26)7 Earth terminal(M4) (inside cover)8 Slit hole for right side piping connection9 Slit hole for left side piping connection

3D044897

Notes:1 Location of general rated name plate

Right side plate outside surface2 In case of using infrared remote control, this

position will be a signal receiver. Refer to thedrawing of infrared remote control in detail.

Brand name plate

Ceiling surface

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

13

6 • Split - Sky Air • Indoor Units

Page 9: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

4 Piping diagrams

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

Indoor heat exchanger

Field piping J9.5 C1220T-0

4D037995A

FAQ71-100BUV1B

Field piping J15.9 C1220T-0

Refrigerant pipe connection port diameters

Model A BFAQ71, 100BUV1B J 9.5 J 15.9

To outdoor unit

Indoor unit

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

14

7• Split - Sky Air • Indoor Units

Page 10: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

5 Wiring diagrams

3D043881

FAQ71BUV1B

A1P Printed circuit boardHAP Light emitting diode (service monitor green)M1S Motor (swing flap)M1F Motor (indoor fan)R1T Thermistor (air)R2T Thermistor (coil)SS1 Selector switch (emergency)X1M Terminal blockX2M Terminal block

Power supply? Signal receiver circuit. Signal transmission circuit

Infrared remote controlReceiver / display unitA2P Printed circuit boardA3P Printed circuit boardBS1 Push button (on/off)H1P Light emitting diode (on-red)H2P Light emitting diode (timer-green)H3P Light emitting diode (filter sign-red)H4P Light emitting diode (defrost-orange)SS1 Selector switch (main/sub)SS2 Selector switch (wireless address set)

Connector for optional partsX15A Connector (float switch)X35A Connector (group control adapter)Wired remote controlR1T Thermistor (air)SS1 Selector switch (main/sub)

To outdoorunit

Note) 4

In case of simultaneousoperation system.

Toou

tdoo

runi

t

Notes

1. D : Terminal, F : Connector, : Field wiring2. In case using central remote control, connect it to the

unit in accordance with the attached instructionmanual.

3. Remote control model varies according to thecombination system, confirm technical materials andcatalogs, etc. before connecting.

4. X24A is connected when the infrared remote controlkit is being used.

5. Shows short circuit connector6. Symbols show as follows Red:red, Blk:black, Ylw:yellow,

Org:orange, Gry:gray, Prp:purple, Blu:blue7. Confirm the method of setting the selector switch (SS1,

SS2) by installation manual and engeneering materials,etc.

Receiver / display unit (attached to infrared remote control)

Note) 4

Indoor unit(master)

Indoor unit(slave)

Remote control

Norm. Emerg.

Note) 2

Transmission wiringconnection/central remotecontrol

Wired remote control

Control box

SIDE FRONT

ON/OFF input from outside

3D044228

FAQ100BUV1B

A1P Printed circuit boardA2P Printed circuit board

(Transformer) 230V/16V)C1R Capacitor (M1F)HAP Light emitting diode (service monitor green)KAR Magnetic relay (M1S)KPR Magnetic relay (M1P)M1F Motor (indoor fan)M1S Motor (swing flap)Q1M Thermo switch (M1F embedded)R1T Thermistor (air)R2T Thermistor (coil)

S1Q Limit switch (swing flap)SS1 Selector switch (emergency)V1TR Phase control circuitX1M Terminal blockX2M Terminal block? Signal receiver circuit. Signal transmission circuitWired remote controlR1T Thermistor (air)SS1 Selector switch (main/sub)

Infrared remote controlReceiver / display unitA3P Printed circuit boardA4P Printed circuit boardBS1 Push button (on/off)H1P Light emitting diode (on-red)H2P Light emitting diode (timer-green)H3P Light emitting diode (filter sign-red)H4P Light emitting diode (defrost-orange)SS1 Selector switch (main/sub)SS2 Selector switch (wireless address set)

Connector for optional partsX15A Connector (float switch)X25A Connector (drain pump)X35A Connector (group control adapter)X16AX61A

Connector (interface adapter for sky air series)

To outdoorunit

Note) 4

Wired remotecontrol

Control box

In case of simultaneousoperation system.

Toou

tdoo

runi

t

Notes

1. D : Terminal F, : Connector2. : Field wiring3. In case using central remote control, connect it to

the unit in accordance with the attachedinstruction manual.

4. X24A is connected when the infrared remotecontrol kit is being used.

5. Remote control model varies according to thecombination system, confirm technical materialsand catalogs, etc. before connecting.

6. Symbols show as follows Red:red, Blk:black,Ylw:yellow, Org:orange, Gry:gray, Prp:purple,Blu:blue

7. Confirm the method of setting the selectorswitch (SS1, SS2) by installation manual andengeneering materials, etc.

8. x15A, x25A are connected when the drain up kitis being used. Connect it to the kit in accordancewith the attached installation manual.

Receiver / display unit

Note) 4

Indoor unit(master)

Indoor unit(slave)

Infrared remotecontrol

Emerg.Norm.

Note) 8

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

15

8 • Split - Sky Air • Indoor Units

Page 11: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

4D044475

V1, ModelPower supply1∼50Hz220V-240V

Main switch

Fuse Fuse

NOTES1 Line voltage wiring

Control circuit wiring2 All wiring, components and materials to be produced on the site must comply with the applicable local and national codes.3 Use copper conductors only.4 See wiring diagrams for details.5 Install fuse and mainswitch for safety.6 All field wiring and components must be provided by a licensed electrician.7 The unit shall be grounded in compilance with the applicable local and national codes.8 Wiring shown are general points-of-connection guides only and are not intended for or to include all details for a specific

installation.9 Never share a common power supply with other equipment.

V3, ModelPower supply1∼50Hz230V

Main switch

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

5 Wiring diagrams

15

9• Split - Sky Air • Indoor Units

Page 12: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

6 Sound levels6-1 Sound level data

Oct

ave

band

soun

dpr

essu

rele

vel

Model

Sound pressure level

Sound power level230V

Measuring location50Hz

CoolingH/L

HeatingH/L

CoolingH/L

HeatingH/L

FAQ71BUV1B 43/37 43/37 45/41 45/41

FAQ100BUV1B 59/53 59/53 61/57 61/57

Octave band center frequency (Hz)

FAQ71BUV1B (Cooling/Heating)

4D038512B

6-2 Sound pressure spectrum

approximatethreshold hearingfor continuousnoise

FAQ100BUV1B (Cooling) FAQ100BUV1B (Heating)

Oct

ave

band

soun

dpr

essu

rele

vel

Oct

ave

band

soun

dpr

essu

rele

vel

4D027787A 4D027790AOctave band center frequency (Hz) Octave band center frequency (Hz)

approximatethreshold hearingfor continuousnoise

approximatethreshold hearingfor continuousnoise

Microphone

H (230V)

L (230V)

H (230V)

L (230V)

H (230V)

L (230V)

Note:1. Sound pressure levels are measured in an anechoic room.2. Data are valid at nominal operation conditions.3. Operation sound level differs with operation and ambient conditions.

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

16

6-1

10 • Split - Sky Air • Indoor Units

Page 13: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

7 Air flow patterns

FAQ71BUV1B

Cooling - air velocity distribution

Air flow direction: 10° (downward)

FAQ71BUV1B

Cooling - air temperature distribution

Air flow direction: 10° (downward)

4D039573A

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

17

11• Split - Sky Air • Indoor Units

Page 14: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

FAQ71BUV1B

Heating - air velocity distribution

Air flow direction: 65°C (downward)

FAQ71BUV1B

Heating - air temperature distribution

Air flow direction: 65°C (downward)

4D039574A

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

7 Air flow patterns

17

12 • Split - Sky Air • Indoor Units

Page 15: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

FAQ100BUV1B

Cooling - air velocity distribution

Air flow direction: 10° (downward)

FAQ100BUV1B

Cooling - air temperature distribution

Air flow direction: 10° (downward)

4D028547A

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

7 Air flow patterns

17

13• Split - Sky Air • Indoor Units

Page 16: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

FAQ100BUV1B

Heating - air velocity distribution

Air flow direction: 65°C (downward)

FAQ100BUV1B

Heating - air temperature distribution

Air flow direction: 65°C (downward)

4D028548A

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

7 Air flow patterns

17

14 • Split - Sky Air • Indoor Units

Page 17: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

8 Accessories8-1 Standard accessories

Name 1. Installation panel Insulation for fitting(for refrigerant pipe) 4. Insulation tape 5. Paper pattern for installation

(Other)

+ Installation manual

+Operation manual

Quantity 1 pc. 1 of each 2 pcs. 1 pc.

Shape

6. Screw x 12

2. For liquid pipe

3. For gas pipe

8-2 Optional accessories

Optional accessories FAQ71BUV1B FAQ100BUV1B

Remote control Wired BRC1D527

Infrared type Heat pump BRC7E618 BRC7C510W

Cooling only BRC7E619 BRC7C511W

Wiring adapter for electrical appendices (2)* *KRP4A51

Installation box for adapter PCB KRP4A93 -

Central remote control DCS302C51

Electrical box with earth terminal (3 blocks) KJB311A

Unified ON/OFF control DCS301B51

Electrical box with earth terminal (2 blocks) KJB212A

Noise filter (for electromagnetic interface use only) KEK26-1 -

Schedule timer DST301B51

Interface adapter for Sky Air series - DTA112B51

Remote sensor KRCS01-1 -

Drain up kit K-KDU572CVE -

Connector for forced on, forced off - EKRORO

3D044482Note:1. Installation box (KRP4A93) is necessary for each adapter marked*

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

18

8-1

15• Split - Sky Air • Indoor Units

Page 18: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

9 Control systems9-1 Wired remote control

6.5 x 9 (Round end slit)

Cover open

Cover closed

5 x 7 (Round end slit) HoleJ5

5 x 10 (Round end slit)

3TW23651-2

BRC1D527

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

19

9-1

16 • Split - Sky Air • Indoor Units

Page 19: FAQ-BU Wall Mounted UnitFAA... · 2019. 5. 9. · E.g. when a window is opened, the unit switches off. +The ’home leave’ operation button prevents large temperature differences

10 Safety device settings

FAQ71-100BUV1B

Model Safety devices FAQ71BUV1B FAQ100BUV1B

FAQ∼BUV1B

Fuse − −Fan motor thermal fuse (°C) − −

Fan motor thermal protector (°C) − OFF: 130±5ON: 83±20

DU423-9101K

11 InstallationNames and functions of partsja Indoor unitjb Outdoor unitjc Infrared remote controljd Inlet airje Discharged airjf Air outletjg Air flow flap (at air outlet)jh Refrigerant piping, connection electric wireji Drain pipejj Air inlet

The built-in air filter removes dust and dirt.jk Ground wire

Wire to ground from the outdoor unit to prevent electrical shocks.

• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B

110

17• Split - Sky Air • Indoor Units