FAQ-BU
Wall Mounted Unit
technical data
SplitSky Air
air conditioning systems
Split - Sky Air
EED
E04-
1/2
• 01
/200
4Pr
epar
ed in
Bel
gium
by
Goe
kint
Gra
phic
s
Zandvoordestraat 300
B - 8400 Ostend Belgium
Internet: http://www.daikineurope.com
Specifications are subject to change without prior notice.
ISO14001 assures an effective environmental management system in order to help protecthuman health and the environment from the potentialimpact of our activities, products and services and toassist in maintaining and improving the quality ofthe environment
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Daikin units comply with the European regulations that guarantee the safety of the product.
Daikin Europe N.V. is participating in the EUROVENT Certification Programme.Products are as listed in the EUROVENT Directory of Certified Products.
TABLE OF CONTENTSFAQ-BU
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nominal capacity, capacity steps and nominal input
Technical specifications
3 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Sound level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sound level data
Sound pressure spectrum
7 Air flow patterns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
8 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Standard accessories
Optional accessories
9 Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
11 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
For capacity tables, please refer to part II: outdoor units
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
1• Split - Sky Air • Indoor Units
1 Features
+ Ideal for shops, restaurants or offices requiring maximum floorspace for furniture and fittings
+ The 71 class has a modern casing: it is very compact (290mmheight - 1050mm width) and very lightweight (only 13 kg).
+ Fits neatly on a wall+ Automatic air flow director ensures uniform air flow and
temperature distribution+ The flap of the unit is closed when not operating.+ The front panel of the new casing is easy removable and
washable.+ Extremely quiet in operation both indoors and outdoors+ For equal distribution in larger rooms, up to 3 indoor units can
be connected to 1 outdoor. They are operated from 1 remotecontrol
+ These indoor units can also be connected to the Sky Air superinverter RZQ-B.
+ The wired remote control has following features:- A real time clock- A schedule timer:Á Possibility to program a weekly schedule timer.Á Possibility to program 5 actions for each day of the week.
- Limit operation (min./max.): room temperature is controlledwithin adjustable upper and lower limits. This can beactivated manually or by schedule timer.
- Home leave (frost protection): during absence, the indoortemperature can be maintained at a certain level. Thisfunction can also switch the unit ON/OFF.
2 1 3 0 8 q x6 ( 6Optional Optional Heat pump
2 steps
Optional
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
11
2 • Split - Sky Air • Indoor Units
2 Specifications
Preliminary info
NOMINAL CAPACITY and NOMINAL INPUTFor indoor units only:INDOOR UNITS FAQ71BUV1B FAQ100BUV1BNOMINAL INPUT Cooling kW 0.068 0.101
Heating kW 0.068 0.101
For combination indoor + outdoor units (air cooled):INDOOR UNITS FAQ71BUV1B FAQ100BUV1BOUTDOOR UNITS RZQ71B7V3B RZQ100B7V3BNOMINAL CAPACITY (3) Cooling (1) min.∼nom.∼max. kW
Heating (2) min.∼nom.∼max. kWNOMINAL INPUT Cooling min.∼nom.∼max. kW
Heating min.∼nom.∼max. kWEER 3.23 3.59COP 3.60 3.50ENERGY LABEL Cooling A A
Heating B BANNUAL ENERGYCONSUMPTION
Cooling kWh
TECHNICAL SPECIFICATIONSINDOOR UNITS FAQ71BUV1B FAQ100BUV1BDIMENSIONS Unit H mm 290 360
W mm 1,050 1,570D mm 230 200
WEIGHT Unit kg 13 26MATERIAL Unit ResinCOLOUR Unit WhiteSOUND LEVEL Sound pressure (cooling/heating) (4) high dB(A) 43/43 45/45
low dB(A) 37/37 41/41Sound power (cooling/heating) (5) high dB(A) 59/59 61/61
low dB(A) 53/53 57/57FAN Air flow rate high m3/min 19/19 23/23
low m3/min 15/15 19/19Speed steps 2 stepsType Cross flow fanQty x motor output W 1 x 43 1 x 49
HEAT EXCHANGER Type Cross fin coil (Multi louver fins and Hi-XA tubes)Rows x stages x fin pitch mm 2 x 16 x 1.4 2 x 12 x 1.4Face area m2 0.289 0.332
PIPING CONNECTIONS liquid mm φ9.5 (flare)gas mm φ15.9 (flare)liquid I.D. mm φ13 (VP13) φ20 (VP20)liquid O.D. mm φ18 (VP13) φ26 (VP20)
INSULATION MATERIAL Heat insulation Foamed polystyrene/foamed polyethylene
For outdoor units Pair application See chapter RZQ-B
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
12
3• Split - Sky Air • Indoor Units
ELECTRICAL SPECIFICATIONSFor indoor units only: FAQ71BUV1B FAQ100BUV1BCURRENT Nominal running current cooling A
See chapter RZQ-Bheating A
Max. running current cooling Aheating A
For combination indoor units + outdoor units: FAQ71BUV1B FAQ100BUV1BRZQ71B7V3B RZQ100B7V3B
CURRENT Nominal running current cooling ASee chapter RZQ-BMaximum running current cooling A
Starting current cooling A
For indoor units only: FAQ71BUV1B FAQ100BUV1BPOWER SUPPLY V1 V1NOMINAL DISTRIBUTIONSYSTEM VOLTAGE
Phase 1∼ 1∼Frequency Hz 50 50Voltage V 220-240 220-240
4D043953
NOTES1 Nominal cooling capacities are based on: indoor temperature 27°CDB/19.5°CWB * outdoor temperature 35°CDB * equivalent refrigerant piping
length: 7.5m * level difference: 0m.
2 Nominal heating capacities are based on: indoor temperature: 20°CDB * outdoor temperature: 7°CDB/6°CWB * refrigerant piping length: 7.5m *level difference 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 The sound pressure level is measured via a microphone at 1m distance from the unit. It is a relative value, depending on the distance andacoustic environment. For measuring conditions: please refer to item 6 of this chapter.
5 The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.
6 Energy label: scale from A (most efficient) to G (less efficient).
7 The Energy Label Directive 2002/31/EC will enter into force once the relevant measurement standard will be published in the European officialStandard.
8 Annual energy consumption: based on average use of 500 running hours per year at full load (= nominal conditions).
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
2 Specifications
12
4 • Split - Sky Air • Indoor Units
3 Dimensional drawings
unit (mm)
50or
mor
e30
orm
ore
(Req
uire
dsp
ace)
J80 hole
approx. 345
approx. 475
FAQ71BUV1B
approx. 400
Mounting location
approx. 390
Piping direction
(Required space)
50 or more
Dimensions forfull open frontpanel
Outside line
J80 hole
(piping and wiringintake)
2500 or moreFor installation in high
spaces
(Req
uire
dsp
ace)
120 or less
1 Front panel2 Front grille3 Air outlet4 Gas pipe (J15.9 Flare connection)5 Liquid pipe (J9.5 Flare connection)6 Drain hose VP13 (External dia J18)7 Grounding terminal (M4)8 Right side piping connection hole9 Left side drain piping connection hole
3D038540B
Notes:1 Location of general rated name plate
Right side plate outside surface2 In case of using infrared remote control,
this position will be a signal receiver.Refer to the drawing of infrared remotecontrol in detail.
Name plate
50 or more
Piping directionNote) 2
Piping direction
(Required space)
unit (mm)
50or
mor
e
250 or more
(Req
uire
dsp
ace)
J80 hole
approx. 450
approx. 600
FAQ100BUV1B
8-5x20 Oval hole (for wood screw)
Mounting locationDetailjA (Mounting hole for installation plate)
approx. 580
Piping direction
(Required space)
50 or more50 or more
(Required space)
5-6x20 Oval hole (for wood screw)
13-J5 Hole (for wood screw)
2-J12 Hole (for bolt)(piping and wiringintake)
Note 2. (service space for air filter)
Direction for air filter draw out
1 Front grille2 Air filter3 Discharge outlet4 Gas piping connection (J15.9 flare)5 Gas piping connection (J9.5 flare)6 Drain pipe connection (VP20 O.D. J26)7 Earth terminal(M4) (inside cover)8 Slit hole for right side piping connection9 Slit hole for left side piping connection
3D044897
Notes:1 Location of general rated name plate
Right side plate outside surface2 In case of using infrared remote control, this
position will be a signal receiver. Refer to thedrawing of infrared remote control in detail.
Brand name plate
Ceiling surface
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
13
5• Split - Sky Air • Indoor Units
4 Piping diagrams
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
Indoor heat exchanger
Field piping J9. 5C1220T-0
4D037995A
FAQ71-100BUV1B
Field piping J15.9C1220T-0
Refrigerant pipe connection port diameters
Model A BFAQ71, 100BUV1B J 9.5 J 15.9
To outdoor unit
Indoor unit
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
14
6 • Split - Sky Air • Indoor Units
5 Wiring diagrams
3D043881
FAQ71BUV1B
A1P Printed circuit boardF1U Fuse (jB , 3A, 250V)HAP Light emitting diode (service monitor green)HBP Light emitting diode (service monitor green)M1S Motor (swing flap)M1F Motor (indoor fan)R1T Thermistor (air)R2T Thermistor (coil)SS1 Selector switch (main/sub)X1M Terminal blockX2M Terminal block? Signal receiver circuit. Signal transmission circuit= Power circuit
Infrared remote controlReceiver / display unitA2P Printed circuit boardA3P Printed circuit boardBS1 Push button (on/off)H1P Light emitting diode (service monitor red)H2P Light emitting diode (service monitor green)H3P Light emitting diode (service monitor red)H4P Light emitting diode (service monitor orange)SS1 Selector switch (main/sub)SS2 Selector switch (wireless address set)
Connector for optional partsX15A Connector (float switch)X35A Connector (group control adapter)
To outdoorunit
Note) 4
In case of simultaneousoperation system.
Toou
tdoo
runi
t
Notes
1. D : Terminal F, H : Connector
b : Protective earth (screw)
2. B : Field wiring3. In case using central remote control, connect it to
the unit in accordance with the attached instructionmanual.
4. X24A is connected when the infrared remotecontrol kit is being used.
5. Remote control model varies according to thecombination system, confirm technical materials andcatalogs, etc. before connecting.
6. Symbols show as follows Red:red, Blk:black,Ylw:yellow, Org:orange, Gry:gray, Prp:purple, Blu:blue
7. Confirm the method of setting the selector switch(SS1, SS2) by installation manual and engeneeringmaterials, etc.
Receiver / display unit (attached to infrared remote control)
Note) 4
Indoor unit(master)
Indoor unit(slave)
Remote control
Emerg. Norm.
Note) 2
Transmission wiringconnection
Wired remote control
Control boxIndoor
SIDE FRONT
ON/OFF input from outside
3D044228
FAQ100BUV1B
1-RED, 2-WHITE, 3-BLACK33A Limit switch (swing flap)A1P Printed circuit boardA2P Printed circuit board
(Transformer) 230V/16V)C1R Capacitor (M1F)HAP Light emitting diode (service monitor green)HBP Light emitting diode (service monitor green)M1A Motor (swing flap)M1F Motor (indoor fan)Q1F Thermo switch (M1F embedded)R1T Thermistor (air)R2T Thermistor (coil)
RyA Magnetic relay (M1A)SS1 Selector switch (emergency)X1M Terminal stripX2M Terminal strip? Signal receiver circuit. Signal transmission circuit= Phase control circuitWired remote controlR1T Thermistor (air)SS1 Selector switch (main/sub)
Infrared remote controlReceiver / display unitA3P Printed circuit boardA4P Printed circuit boardBS Push button (on/off)H1P Light emitting diode (service monitor red)H2P Light emitting diode (service monitor green)H3P Light emitting diode (service monitor red)H4P Light emitting diode (service monitor orange)SS1 Selector switch (main/sub)SS2 Selector switch (wireless address set)
Connector for optional partsX30A Connector (interface adapter for sky air series)X35A Connector (group control adapter)X40A Connector
ON/OFF input from outside
To outdoorunit
Note) 4
Wired remotecontrol
Control boxIn case of simultaneousoperation system.
Toou
tdoo
runi
t
Notes
1. D : Terminal F, H : Connector
b : Protective earth (screw)
2. B : Field wiring3. In case using central remote control, connect it to
the unit in accordance with the attachedinstruction manual.
4. X24A is connected when the infrared remotecontrol kit is being used.
5. Remote control model varies according to thecombination system, confirm technical materialsand catalogs, etc. before connecting.
6. Symbols show as follows Red:red, Blk:black,Ylw:yellow, Org:orange, Gry:gray, Prp:purple,Blu:blue
7. Confirm the method of setting the selectorswitch (SS1, SS2) by installation manual andengeneering materials, etc.
Receiver / display unit
Note) 4
Indoor unit(master)
Indoor unit(slave)
Infrared remotecontrol
Emerg.Norm.
Note) 8
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
15
7• Split - Sky Air • Indoor Units
4D044475
V1, ModelPower supply1∼50Hz220V-240V
Main switch
Fuse Fuse
NOTES1 Line voltage wiring
Control circuit wiring2 All wiring, components and materials to be produced on the site must comply with the applicable local and national codes.3 Use copper conductors only.4 See wiring diagrams for details.5 Install fuse and mainswitch for safety.6 All field wiring and components must be provided by a licensed electrician.7 The unit shall be grounded in compilance with the applicable local and national codes.8 Wiring shown are general points-of-connection guides only and are not intended for or to include all details for a specific
installation.9 Never share a common power supply with other equipment.
V3, ModelPower supply1∼50Hz230V
Main switch
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
5 Wiring diagrams
15
8 • Split - Sky Air • Indoor Units
6 Sound levels6-1 Sound level data
Oct
ave
band
soun
dpr
essu
rele
vel
Model
Sound pressure level
Sound power level230V
Measuring location50Hz
CoolingH/L
HeatingH/L
CoolingH/L
HeatingH/L
FAQ71BUV1B 43/37 43/37 45/41 45/41
FAQ100BUV1B 59/53 59/53 61/57 61/57
Octave band center frequency (Hz)
FAQ71BUV1B (Cooling/Heating)
4D038512B
6-2 Sound pressure spectrum
approximatethreshold hearingfor continuousnoise
FAQ100BUV1B (Cooling) FAQ100BUV1B (Heating)
Oct
ave
band
soun
dpr
essu
rele
vel
Oct
ave
band
soun
dpr
essu
rele
vel
4D027787A 4D027790AOctave band center frequency (Hz) Octave band center frequency (Hz)
approximatethreshold hearingfor continuousnoise
approximatethreshold hearingfor continuousnoise
Microphone
H (230V)
L (230V)
H (230V)
L (230V)
H (230V)
L (230V)
Note:1. Sound pressure levels are measured in an anechoic room.2. Data are valid at nominal operation conditions.3. Operation sound level differs with operation and ambient conditions.
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
16
6-1
9• Split - Sky Air • Indoor Units
7 Air flow patterns
FAQ71BUV1B
Cooling - air velocity distribution
Air flow direction: 10° (downward)
FAQ71BUV1B
Cooling - air temperature distribution
Air flow direction: 10° (downward)
4D039573A
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
17
10 • Split - Sky Air • Indoor Units
FAQ71BUV1B
Heating - air velocity distribution
Air flow direction: 65°C (downward)
FAQ71BUV1B
Heating - air temperature distribution
Air flow direction: 65°C (downward)
4D039574A
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
7 Air flow patterns
17
11• Split - Sky Air • Indoor Units
FAQ100BUV1B
Cooling - air velocity distribution
Air flow direction: 10° (downward)
FAQ100BUV1B
Cooling - air temperature distribution
Air flow direction: 10° (downward)
4D028547A
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
7 Air flow patterns
17
12 • Split - Sky Air • Indoor Units
FAQ100BUV1B
Heating - air velocity distribution
Air flow direction: 65°C (downward)
FAQ100BUV1B
Heating - air temperature distribution
Air flow direction: 65°C (downward)
4D028548A
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
7 Air flow patterns
17
13• Split - Sky Air • Indoor Units
8 Accessories8-1 Standard accessories
Name 1. Installation panel Insulation for fitting(for refrigerant pipe) 4. Insulation tape 5. Paper pattern for installation
(Other)
+ Installation manual
+Operation manual
Quantity 1 pc. 1 of each 2 pcs. 1 pc.
Shape
6. Screw x 12
2. For liquid pipe
3. For gas pipe
8-2 Optional accessories
Optional accessories FAQ71BUV1B FAQ100BUV1B
Remote control Wired BRC1D527
Infrared type Heat pump BRC7E618 BRC7C510W
Cooling only BRC7E619 BRC7C511W
Wiring adapter for electrical appendices (2)* *KRP4A51
Installation box for adapter PCB KRP4A93 -
Central remote control DCS302B51
Electrical box with earth terminal (3 blocks) KJB311A
Unified ON/OFF control DCS301B51
Electrical box with earth terminal (2 blocks) KJB212A
Noise filter (for electromagnetic interface use only) KEK26-1 -
Schedule timer DST301B51
Interface adapter for Sky Air series - DTA112B51
Remote sensor KRCS01-1 -
Drain up kit K-KDU572CVE -
Connector for forced on, forced off - EKRORO
3D044482Note:1. Installation box (KRP4A93) is necessary for each adapter marked*
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
18
8-1
14 • Split - Sky Air • Indoor Units
9 Control systems9-1 Wired remote control
6.5 x 9 (Round end slit)
Cover open
Cover closed
5 x 7 (Round end slit) HoleJ5
5 x 10 (Round end slit)
3TW23651-2
BRC1D527
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
19
9-1
15• Split - Sky Air • Indoor Units
10 Safety device settings
FAQ71-100BUV1B
Model Safety devices FAQ71BUV1B FAQ100BUV1B
FAQ∼BUV1B
Fuse − −Fan motor thermal fuse (°C) − −
Fan motor thermal protector (°C) − OFF: 130±5ON: 83±20
DU423-9101K
11 InstallationNames and functions of partsja Indoor unitjb Outdoor unitjc Infrared remote controljd Inlet airje Discharged airjf Air outletjg Air flow flap (at air outlet)jh Refrigerant piping, connection electric wireji Drain pipejj Air inlet
The built-in air filter removes dust and dirt.jk Ground wire
Wire to ground from the outdoor unit to prevent electrical shocks.
• Wall Mounted, Inverter Controlled Unit • R-410A • FAQ71-100BUV1B
110
16 • Split - Sky Air • Indoor Units