Fan Power Final

4
FAN POWER Source of formula: http://hvacformula.blogspot.com/2008/12/fan- equations.html BHP = Q x Total Friction Loss / (6356 x Fan Ef f.) Where: BHP = Break Horsepower Total Friction loss = in H 2 O Q = Air flow rate in CFM FAN EFF = Fan efficiency usually in 65–85% range = use 75%

description

Fan power

Transcript of Fan Power Final

Page 1: Fan Power Final

FAN POWER

Source of formula: http://hvacformula.blogspot.com/2008/12/fan-equations.html

BHP = Q x Total Friction Loss / (6356 x Fan Ef f.)

Where:

BHP = Break Horsepower

Total Friction loss = in H2O

Q = Air flow rate in CFM

FAN EFF = Fan efficiency usually in 65–85% range

= use 75%

291

Page 2: Fan Power Final

Example:

BHP = Q x Total Friction Loss / (6356 x Fan Ef f.)

For AHU 1

Q = 90000 CFM

Total Friction Loss = 3.3986 in H20

Fan Eff. = 75%

BHP = 90, 000 x 3.3986/ (6356x 0.75)

= 64.16536675

Use 65 hp

292

Page 3: Fan Power Final

AHUCFM

Total Friction Loss (in H20)

Brake Power (HP) FAN (HP)

Page 4: Fan Power Final

AHU1 90000 3.3986 64.16536675 65

AHU 2 90000 3.3986 64.16536675 65

AHU 3 23100 2.8330 13.72803133 14

AHU 4 23100 2.8330 13.72803133 14

AHU 5 71500 4.1509 62.25865613 63

AHU 6 56400 4.0733 48.19304038 49

AHU 7 65550 3.9815 54.74849994 55

AHU 8 49910 4.1329 43.27074066 44

AHU 9 56250 3.9641 46.77560069 47

AHU 10 56250 3.9641 46.77560069 47

AHU 11 20600 1.9968 8.628788751 9

293