May 31st, 2017 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.
You may view more detailed information for this home and can make an offer at
http://www.faira.com/listings/11125 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team
Home Inspection Report
975 N Stephenson Dr, Montesano , WA 98563Inspection Date:
Tuesday, May 30, 2017Prepared For:Christopher EllisPrepared By:Jess Hampton
2204 Pershing St Aberdeen, WA 98520
Report Number:ELL053017-HInspector:
Jess Hampton
License/Certification #:960
Inspector Signature:
975 N Stephenson Dr Montesano , WA 98563 Page 2
Report SummaryItems Not Operating
All major items operating at the time of inspection.
Major ConcernsNegative grading - "Grounds" section. Bare ground, wood debris and standing water - "Crawlspace" section.
Potential Safety HazardsFire door not closing automatically - "Garage" section. Missing carbon monoxide alarm - "Interior" section.
Deferred Cost Items11 year old heat pump - "Exterior" section. 11 year old water heater - "Plumbing" section.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 3
Report OverviewScope of Inspection
All components designated for inspection in the Washington State Standards of Practice are inspected, except as may be noted in the "Limitations of Inspection" sections within this report. It is the goal of the inspection to put a home buyer in a better position to make a buying decision. Not all improvements will be identified during this inspection. Unexpected repairs should still be anticipated. The inspection should not be considered a guarantee or warranty of any kind.Please refer to the pre-inspection contract for a full explanation of the scope of the inspection.
This is a visual, non-invasive, non-technical inspection only.
Main Entrance FacesWest
State of OccupancyOccupied Fully furnished
Weather ConditionsCloudy Rain
Recent RainNo
Ground CoverDamp
Approximate Age11 years
Inspection Start/Finish Time9am - 12pm
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
Receipt/InvoiceJess Hampton2204 Pershing St Aberdeen, WA 98520360-591-1008
Date: Tue. May. 30, 2017 9:00
Inspected By: Jess Hampton
Property Address975 N Stephenson DrMontesano , WA 98563
Inspection Number: ELL053017-H
Payment Method: Credit Card
Client: Christopher Ellis
Inspection FeeHome Inspection $400.00
Total $400.00
975 N Stephenson Dr Montesano , WA 98563 Page 5
GroundsService WalksMaterial X ConcreteCondition X Satisfactory
Driveway/ParkingMaterial X ConcreteCondition X Satisfactory X Typical cracks
PorchCondition X Satisfactory
Deck/StepsDeck Condition X Satisfactory
Landscaping affecting foundationNegative Grade X South X Wood in contact with/improper clearance to soilVegetation X Vegetation too close to structure X Recommend 12" of clearence
X Trees too close to structure/overhanging roof X Recommend cutting trees backComments Some areas of grading on the south side were sloping towards foundation, soil is in contact with
siding at this area as well. This can affect the foundation and can cause water to enter into crawlspace area which creates a conducive condition for wood destroying pests. Recommend a lic. landscape contractor evaluate site drainage and make any necessary repairs to create positive grading/drainage away from the perimeter of foundation.
Photos
Vegetation encroaching in on home.
Tree branches starting to overhang roof.
Negative grading area, note soil in contact with siding and encroaching in on foundation vent.
Hose bibsCondition X SatisfactoryOperable X Yes
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 6
ExteriorGutters/DownspoutsGutter Condition X SatisfactoryDownspout Condition X Satisfactory
SidingMaterial X Fiber-cementCondition X Satisfactory
TrimCondition X Marginal X Rotted/DamagedComments Wood rot was noted at the bottom of the garage northwest corner trim. It is possible that the rotted area can
be trimmed off the bottom and not have to replace the full pieces of trim. Recommend further evaluation for any necessary repairs.
Photos
Wood rot at bottom of trim.
Soffit/EavesCondition X Satisfactory
FasciaCondition X Marginal X Rotted/DamagedComments Wood rot was noted at the end of the northwest corner facia.
Recommend repair/replace facia as necessary.Photos
Rotted facia.
FlashingCondition X Satisfactory
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 7
ExteriorWindows/ScreensCondition X SatisfactoryScreens X Not installedComments Window screens were not installed, it is unknown if screens area stored or missing. No comments can be
made on missing screens.
FoundationFoundation Type X Poured concreteCondition X SatisfactoryFoundation Venting X Satisfactory
Service Entry/Exterior ElectricalLocation X UndergroundCondition X SatisfactoryExterior receptacles X Yes Operable: X YesGFCI present X Yes Operable: X Yes
Building(s) Exterior Wall ConstructionType X FramedCondition X Not VisibleComments Building structure not visible due to siding, trim etc. and therefore cannot be evaluated.
Exterior DoorsMain Entrance Door condition: X SatisfactoryRear door Door condition: X Satisfactory
Exterior A/C - Heat PumpUnit #1 Brand:
NordyneApproximate Age:11 years
Condition X MarginalEnergy source X ElectricOutside Disconnect X Yes Maximum fuse/breaker rating (amps): 30 amp Fuses/Breakers installed (amps): 30 ampComments Heat pump was in normal working order at the time of inspection. The heat pump is at the end of
its normal life expectancy, although operating normally, this appliance may need replacing soon.Photos
Heat pump information.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 8
RoofGeneralVisibility X AllInspected From X RoofPhotos
General roof.
Style of RoofType X GablePitch X MediumRoof #1 Type:
Asphalt shingle Age:11 years
Ventilation SystemType X Soffit X Ridge X Gable
FlashingCondition X MissingComments Flashing or roofing has not been installed on top of the exposed facia ends. Recommend facia ends be
protected from weather as needed.Photos
Exposed tops of facia.
SkylightsCondition X Satisfactory
Roof Vents/JacksPlumbing Vent Condition X SatisfactoryVent Jack Condition X Satisfactory
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 9
RoofCondition of Roof CoveringsRoof #1 X Satisfactory X Moss buildupComments Roof was showing normal wear for age and was in overall adequate condition.
Moss is starting to build up at some areas of the roof. Recommend treating roof for moss as needed.
Photos
Moss starting to build up.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 10
GarageTypeType X Attached X 2-Car
Automatic Opener(s)Number of door openers X OneElectric eyes (safety equipment) X OperationalPressure reverse (safety equipment) X OperationalQuick release mechanism (safety equipment) X OperationalAutomatic door opener wall switch X Operational
FloorMaterial X ConcreteCondition X Satisfactory X Typical cracks
Sill PlatesType X ElevatedCondition X Satisfactory
Overhead Door(s)Material X MetalComments Some damage to the garage door was noted, this damage does not appear to affect the function of the door.
Repair/replace door as desired.Photos
Damaged garage door.
Electrical ReceptaclesX Yes Operable: X Yes
Reverse polarity X NoOpen ground X NoGFCI Present X Yes Operable: X Yes
Fire Separation Walls & CeilingCondition X SatisfactoryFire door X SatisfactorySelf closure X Safety Hazard X InoperativeComments Self closing door hardware for the fire door is not adjusted properly, door to garage does not close
automatically. Recommend adjusting hardware to fully close door.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 11
Photos
Fire door does not close automatically.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 12
KitchenCountertopsCondition X Satisfactory
CabinetsCondition X Satisfactory
PlumbingFaucet Leaks X NoPipes leak/corroded X NoSink/Faucet X ChippedFunctional drainage X SatisfactoryFunctional flow X SatisfactoryComments Some chips in sink were noted, this does not appear to affect the function of the sink. Repair/replace sink as
desired.Photos
Chips in sink.
Walls & CeilingCondition X Satisfactory
Heating/Cooling SourceX Yes Type: X Forced Air
Condition X Operational
FloorCondition X Loose/broken tile/grout X Recommend repairComments Some areas of the floor tile grout is cracked/missing. Recommend re-grouting floor as needed.Photos
Loose/cracked/missing grout.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 13
KitchenAppliancesDisposal X N/AOven Operable: X YesRange Operable: X YesDishwasher Operable: X YesExhaust fan Operable: X YesRefrigerator Operable: X YesMicrowave Operable: X YesDishwasher airgap X YesReceptacles present X Yes Operable: X YesGFCI X Yes Operable: X YesOpen ground/Reverse polarity: X NoComments All appliances were operating normally at the time of inspection.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 14
Laundry RoomLaundryHeat source present X YesRoom vented X YesElectrical Open ground/reverse polarity: X NoAppliances X Washer X DryerWasher hook-up lines/valves X SatisfactoryFloor X Satisfactory
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 15
Bathroom (1)BathLocation Off hallway Sinks Faucet leaks: X No Pipes leak: X NoTubs Faucet leaks: X NoShowers Shower head leak: X NoToilet Bowl loose: X No Operable: X YesShower/Tub area X Fiberglass Condition : X SatisfactoryDrainage X SatisfactoryWater flow X SatisfactoryMoisture stains present X NoDoors X SatisfactoryWindow X NoneReceptacles present X Yes Operable: X YesGFCI X Yes Operable: X YesOpen ground/Reverse polarity X NoHeat source present X Yes Type: X Forced Air Operational: X YesExhaust fan X Yes Operable: X YesFloor X Satisfactory
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 16
Bathroom (2)BathLocation Off Master Bedroom Sinks Faucet leaks: X No Pipes leak: X NoTubs Faucet leaks: X No Tub spout loose: X Yes X Recommend repairShowers Faucet leaks: X No Shower head leak: X NoToilet Bowl loose: X No Operable: X YesWhirlpool X NoShower/Tub area X Fiberglass Condition : X SatisfactoryDrainage X SatisfactoryWater flow X SatisfactoryMoisture stains present X NoDoors X SatisfactoryWindow X NoneReceptacles present X Yes Operable: X YesGFCI X Yes Operable: X YesOpen ground/Reverse polarity X NoHeat source present X Yes Type: X Forced Air Operational: X YesExhaust fan X Yes Operable: X YesFloor X SatisfactoryComments The tub spout and handles were loose. Recommend securing these items as needed.Photos
Loose tub spout and handles.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 17
General Living Area General Living AreaType Living/Dining Rooms, HallwaysWalls & Ceiling X SatisfactoryMoisture stains X NoFloor X SatisfactoryElectrical Switches: X Yes X Operable Receptacles: X Yes X Operable Open ground/Reverse polarity: X NoHeating source present X Yes Type: X Forced Air Operational: X YesDoors X SatisfactoryWindows X Satisfactory
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 18
Room (1)RoomLocation EastType Bedroom Walls & Ceiling X SatisfactoryMoisture stains X NoFloor X SatisfactoryElectrical Switches: X Yes X Operable Receptacles: X Yes X Operable Open ground/Reverse polarity: X NoHeating source present X Yes Type: X Forced Air Operational: X YesBedroom Egress restricted X NoDoors X SatisfactoryWindows X Satisfactory
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 19
Room (2)RoomLocation Southeast Type Bedroom (Master)Walls & Ceiling X SatisfactoryMoisture stains X NoFloor X SatisfactoryElectrical Switches: X Yes X Operable Receptacles: X Yes X Operable Open ground/Reverse polarity: X NoHeating source present X Yes Type: X Forced Air Operational: X YesBedroom Egress restricted X NoDoors X SatisfactoryWindows X Satisfactory
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 20
Room (3)RoomLocation SouthType Bedroom Walls & Ceiling X SatisfactoryMoisture stains X NoFloor X SatisfactoryElectrical Switches: X Yes X Operable Receptacles: X Yes X Operable Open ground/Reverse polarity: X NoHeating source present X Yes Type: X Forced Air Operational: X YesBedroom Egress restricted X NoDoors X SatisfactoryWindows X Satisfactory
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 21
InteriorSmoke/Carbon Monoxide detectorsSmoke Detector X Present Operable: X YesCO Detector X Not Present X Safety HazardComments Carbon monoxide alarm is missing outside sleeping areas, recommend alarm be installed as needed.Photos
Recommended carbon monoxide alarm location.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 22
AtticAttic/Structure/Framing/InsulationAccess X Scuttlehole/HatchInspected from X In the atticLocation X Bedroom ClosetFlooring X NoneInsulation X Fiberglass X Loose Depth: 13"Ventilation X Ventilation appears adequateStructural problems observed X NoRoof structure X TrussesSheathing X OSBEvidence of condensation X NoEvidence of moisture X NoEvidence of leaking X NoElectrical X No apparent defectsComments Attic area appeared in overall satisfactory condition.Photos
General attic area.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 23
CrawlspaceCrawl spaceType X Full crawlspaceComments Note: Some rat activity was noted, there were no obvious access areas evident at the time of inspection.
May want to consult a pest management professional for abatement options.
AccessLocation X Interior hatch/doorInspected from X In the crawl space
Foundation wallsCondition X Satisfactory
FloorMaterial X DirtComments Moisture barrier has been disturbed at various areas exposing bare ground, recommend moisture
barrier be redistributed to cover all bare ground. Wood debris and remaining concrete form material was noted throughout the crawlspace area, this is a conducive condition for wood destroying pests. Recommend all wood debris be removed from crawlspace area.
Photos
Remaining form material north side.
Bare ground along the north side. Wood and other debris at the west side of crawlspace.
Seismic bolts/StrapsCondition X Appear satisfactory
DrainageSump pump X NoStanding water X YesComments Standing water and evidence of high seasonal standing water was noted at the south crawlspace area.
Some of the grade beam framing members are covered in mud and water. Recommend further evaluation of this issue by a licensed contractor for site and/or foundation drainage solutions to discharge water and to keep framing member from contacting soil and water.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 24
Photos
Evidence of high standing water. Framing members buried in mud and water.
VentilationLocation X Wall vents
JoistsCondition X SatisfactoryComments Joist inspection was limited due to the installation of floor insulation, only visible members/components could
be inspected.
SubfloorX Not Visible
Comments Subfloor was not visible due to insulation, some random areas were checked around perimeter, under bathrooms and kitchen. Areas that were checked appeared satisfactory.
InsulationType X FiberglassLocation X Between floor joistsCondition X Satisfactory
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 25
PlumbingWater serviceMain shut-off location At the southwest corner of property.Water entry piping X PolyethyleneVisible water distribution piping X PEX PlasticCondition X SatisfactoryDrain/Waste/Vent pipe X ABSCondition X SatisfactoryComments Note: The plumbing inspection was limited due to floor insulation, only visible components could be
inspected.
Water heater #1General Brand Name:
RheemCapacity:65 gallon Approx. age:11 years
Type X ElectricRelief valve X Yes Extension proper: X YesCondition X MarginalComments The water heater appeared to be operating normally at the time of inspection. This appliance is at the end of
its normal life expectancy and may need replacing soon.Photos
Water heater information.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 26
Heating/Cooling SystemHeating systemUnit #1 Brand name:
NordyneApprox. age:11 years
Energy source X ElectricDistribution X Insulated flex ductFilter X Standard X SatisfactoryWhen turned on by thermostat X Fired Proper operation: X YesComments Both the heating and cooling system appeared to be operating normally at the time of inspection.
There is no service record for this system. It is recommended that a licensed HVAC technician perform a full service on the heating and cooling system.
Photos
Furnace information.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton
975 N Stephenson Dr Montesano , WA 98563 Page 27
Electrical SystemMain panelLocation Garage Condition X SatisfactoryAmperage/Voltage X 200aBreakers/Fuses X BreakersAppears grounded X YesGFCI breaker X NoAFCI breaker X YesMain wire X Copper Condition: X SatisfactoryBranch wire condition X SatisfactoryPhotos
Main panel in garage.
This confidential report is prepared exclusively for Christopher Ellis© 2017 Jess Hampton