Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit...

45
Stephen Hamstra, PE, CGD Greensleeves LLC [email protected] Eye-opening GSHP System Performance: Reality versus Design for the life of a Project Session C: Technical

Transcript of Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit...

Page 1: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

StephenHamstra,PE,CGDGreensleevesLLC

[email protected]

Eye-opening GSHP System Performance: Reality versus Design for the life of a Project

Session C: Technical

Page 2: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Learning Objectives• Our industry needs real performance feedback to grow:

How do we get it?

• Design Phase In-situ testing versus “Effective” GHX properties, do we see a difference?

• What about the building loads changing?

• When there is a difference from design to reality, what can be done to optimize system performance?

• How do we close the performance feedback loop?2

Page 3: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Acknowledgements• Shane Mason, P.E. – Greensleeves LLC

• Abe Glas, P.E. – Greensleeves LLC

• Zhicheng Zhang – Greensleeves LLC

• Ross Ulberg – Greensleeves LLC

• Bob Braam –Greensleeves LLC

3

Page 4: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Outline/Agenda

4

1. Design,construct,operateandoptimize;Whatcanhappentomakethingsdifferent?

2. CaseStudies

A. OverheatedFloridaHighSchool

B. Hot/coldborefieldsinNorthCarolinaVAFacilities

C. TheMichiganhighschoolthat“grewtoomuch”

D. TheMichiganhighschoolthatissavingtheOwnerbig$$$inconstruction

E. AnIowajailthat’sthe“hot”placetobe

F. Ilikecows,youshouldtoo

3. Conclusions&A Challenge

Page 5: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Design Process

5

Energymodeling In-situFormationTesting IterativeprocessofGHXsimulations

Page 6: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Design Process

6

Page 7: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Construction Process

7

Page 8: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

The construction is finally done…

8

Page 9: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

9

©HBOBoardwalkEmpire

Page 10: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

10

Page 11: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

11

Butfirst,anexplanation.

Page 12: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Solar Thermal Systems

Heat Exchangers to Sewer or Irrigation systems

Ground-Source Heat Exchanger(s)

Manyconfigurationoptions!

Energy Plant(s)

HEAT TRANSFER

Thermal Energy Storage

HEAT TRANSFER

CHP & Emergency Power Systems

Closed-CircuitCooling Towers

Bodies ofWater

Air-Source Heat Pump

HEA

T TR

ANSF

ER

Data & Control

Building Automation

System

Ground-Source Heat Exchanger

Site-based Energy Heat Pump Systems

12

Page 13: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

HEAT TRANSFEREnergy Plant(s)Closed-CircuitCoolingTowerCCCT

Data & Control

Building Automation

System

Reactive v. Predictive Control

Reactive(Real-time)or“ASHRAEHybrid”Mode:

• WhenGHXleavingwatertemperaturesexceedasetpoint, theCCCTisenabled

• Typicallythisiswhen:o Outsideairtemperatureishottesto Outsideairhumidity ishighesto Electricityisthemostexpensive

• TypicallyusesMOREENERGYthanfullsize GHX

Predictive(Pre-Conditioning)Mode:

• Intelligentcontrols“look”toafuturehorizonandpredictGHXLWT’s

• IntelligentlydecidewhentooperatetheCCCT:o Cooleranddryerweathero Lessexpensiveenergyo Lesswaterusage

• Self-adaptingalgorithmsadjustautomaticallyCanuseLESSENERGYthanfullsize GHX!

13

GHX

Page 14: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Time shifting Heat Rejection?

14

RunHo

urs

WetBulbTemp°F

Page 15: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Or explained in another way…

15

• RunningaCCCTcreatesan“artificial”heatingload

o Especiallywhenruninthewintermonthsduring

coolweather– makesPhysicsworkforus!

• Inrealitywearesimplybalancing theannualcoolingand

heatingloads

o Weknowthatbalanced borefieldsworkbetter!

• Wearealsoresettinganypotentialtemperaturecreep

fromyeartoyear

UncontrolledFullsize GHX

ControlledFullsize GHX

Page 16: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

HEAT TRANSFEREnergy Plant(s)Closed-CircuitCoolingTowerCCCT

Data & Control

Building Automation

System

Reactive v. Predictive Conclusion…

Reactive(Real-time)or“ASHRAEHybrid”Mode: Predictive(Pre-Conditioning)Mode:

16

GHX

Notreally…

©StarWars©BacktotheFuture

Page 17: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Overheated Florida High School

17

• Builtin2000

• Nominal1,000tonpeakcooling load

• Issueswithborefield installation– varyingdepthsand32coiledloops

• Installedapproximately179borefeetperpeaktonofcooling

• Temperaturesstartedtocreepreachingwellover100°+Frange

• Compressor failuresstartedin2006– notethesearenon-extendedrangeGSHP’s

• 2014– diagnosticsoftwarewasinstalledtotracktheloadsandtheGHXresponse

Page 18: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Overheated Florida High School

18

Actualloadsv.DesignLoads

Page 19: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Overheated Florida High School

19

Seven(7)yearsimulation results;addinganominal375toncooling tower:

Every dollar spent on the CCCT returns nearly $8!!!

(-76%) (-100%)

Page 20: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

North Carolina VA Housing

20

• Two(2)housingunits– onemountain,onevalley

• Singlepipeheatpumpconfiguration

• Sixseparateborefields (GHX’s)perbuilding

• ProblemswithoverheatingGHXaswellas

overcooling (noantifreeze)

Page 21: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

21

North Carolina VA Housing

Page 22: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

22

North Carolina VA Housing

“Effective”GHXThermalConductivity

Red=ActualBlue=Predicted

Page 23: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

North Carolina VA Housing #1

23Whenboth heatingandcoolingoccur,wecandoalong-termin-situtestonthe“effective”GHXThermalConductivity

1.63

0.74

1.5

1.68 1.72

1.11

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

GHX1 GHX2 GHX3 GHX4 GHX5 GHX6

DesignTC "Effective"TC

AVG 1.40(– 11%)

Design 1.57

Page 24: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

North Carolina VA Housing #2

24Whenboth heatingandcoolingoccur,wecandoalong-termin-situtestonthe“effective”GHXThermalConductivity

1

0.78

1.14

0.51

1.14

1.36

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

GHX1 GHX2 GHX3 GHX4 GHX5 GHX6

DesignTC "Effective"TC

AVG 0.99(– 30%)

Design 1.41

Page 25: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

North Carolina VA Housing

25

• SignificantvarianceinGHXeffectiveperformanceversusdesign

• SomevarianceofactualHVACloadstodesign– someduetotemperaturesetpoint changes

o Residentspreferwarmertemperaturesallyear– addedheatingload,diminished cooling load

• Singlepipedesignexacerbatedtheimpactof“outofrange”enteringwatertemperaturescausingfrequentGSHP

trips

• Butmostinterestingisthattheloaddiversitywasgreatenoughsuchthatifallsix(6)

GHX’s(eachbuilding)werecombined,theEWT’scouldstaywithintheneededrange

CurrentlytheyarecombiningtheGHX’s

Results:

Page 26: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

26

Growing High School

• Builtin2001,Natatoriumaddedin2005

• Severalmajoradditions totheGHSPSystem,butnotGHX

• SummerGSHPEWTclimbsto120°F+!

• Numerousnuisancetripsandunhappy occupants

• Applied loadmonitoring softwaretosortitout…

Page 27: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

27

Growing High School

• Majorirrigationsystemforathleticfields

• Runsnightlyinsummerfor6to8hours

• Citywatertemperaturesinthe60’s°Frange

• IrrigationpipepassesthroughGHXmechanicalroom

• Serendipity!

• Let’susetheirrigationasaclosed-circuitcoolingtower!

Observations:

Page 28: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

28

Growing High School• IsolatedtheGHXflowfromthebuilding

• Added theirrigationHX

• Irrigationheatrejectioncanhit100+tons!

• Loadmonitoring softwarealsousedtoidentifyGHXcapacity– coulditsupport1MMBTUsnowmelt?Yes!

Page 29: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Growing High School

Page 30: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Growing High SchoolEnterin

gWaterTe

mp’s

Notewhenirrigation turnedoff!125°F!!!

80°F!!!

Page 31: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

The “BIG” Borefield

31

• Builtin2003

• OriginaldesignofGHX:48°FMinto85°FMax

• Actualoperation: 55°Fto75°F,extracapacityavailable!

• Loadmonitoring softwareinstalled

• Newschoolbuilding proposed tobeconstructedadjacent

with$900,000GHX…

• Butbyknowing theavailablecapacityandhaving theproper

controls, theSchoolDistrictcantiethenewbuilding intothe

oldGHXandredirectconstructiondollars!

Page 32: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

One “Hot” County Jail

32

• Builtin2009

• 58tonpeakload

• 9.9:1coolingdominant

• GHXleavingwatertemperaturescreptto115°F

Page 33: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

One “Hot” County Jail

• Apply38tonCCCT

• Operatereal-timein“ASHRAEHybrid”mode

Option#1:Real-timeCCCTApproach

Page 34: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

One “Hot” County Jail

34

• Apply38tonCCCT

• Operateinpre-conditioning mode

Option#2:PredictiveCCCTApproach– looktothefuture!

Page 35: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

One “Hot” County Jail

35

Real-time Predictive

LowerEWT=LowerCoolingEnergy!

Page 36: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

One “Hot” County Jail

36

Simulation results;addinganominal38toncoolingtower:

ExistingGHX Real-timeMode Pre-conditioningMode

MinGHXTemperature 70°F 68°F 63°F

MaxGHX Temperature 115+°F 96°F 90°F

LoadAdjusted GHXTemperature

Notsureyet! 81°F 73°F8°Fcooler!

CCCTkWH NA 13,751 11,34317.5%less

CCCTWaterkGal NA 159 8149%less

Page 37: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

One “Hot” County Jail

37

Dropping from81°Fto73°FLoad-adjustedEWT:

Approx.11%less

Page 38: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Dairy Application????

38

• 2500dairycattle

• Eachcowproduces75poundsofmilkperday

• Mustbechilledfrom98°Fto38°F

o Thisisabout10,500BTU’spercow

• Milkinggoeson24/7– noofftime

• Alsoneedaround5.5gallonsofhotwaterpercow

perdayforcleaningandflushing

• ThisisCalifornia– majorwaterissues

Does “time shifting” heat rejection make sense???

Page 39: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Dairy Application????

39

SystemConcept:

• HeatRecoveryCentralHeatPump(nominal40tons)

• Makechilledfluidforchillingmilk

• Makehotwaterforcleaningpurposes

• SmallverticalclosedloopGHX (1.4borefeet percow)

• Smallclosed-circuitcoolingtower(15or36tons)

Page 40: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Did it “work”????

40

Versusconventionalwater-cooledrefrigeration,noheatrecoveryandnoGHX:

• Reductioninwaterusageperyear:

o 15tonCCCT: 79%less!!!

o 36tonCCCT: 87%less!!!

• Energycostreduction?

o Naturalgas(cheap)istough,maybe2-3%lessorroughlyequal.

o Propaneisnobrainer,like25%less!

Bottomline:TimeshiftingheatrejectioncanmakesenseinMANYapplications!

Bessieishappy!

Page 41: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Conclusions

41

1. Wecan’tfixwhatwecan’tmeasure,norcanweoptimizeit.

2. ConsiderincludingperformancetrackinganalyticsonEVERYPROJECT(neworold):

A. Measurerealbuildingloads(GHXflowrate)andcomparetodesignand/or

historicalloads

B. MeasurerealGHXresponse(GHXentering/leavingtemperaturesandoutsideair

temperature)

Page 42: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Conclusions

42

3. Forecastwhenthingsaregoingsouth,BEFOREtheissuehits!

4. Knowhowtoaddressachangeinloads…forreal,notjustguessing

5. Knowwhatistheavailablecapacityforfutureadditions

Page 43: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

43

Let’s have projects that better and smarter over time!

A Challenge

Then we will too!

Page 44: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

44

CominginNovember:FreeOnlineGSHPScopingTool!

• 16standardcommercialbuilding types(NREL)• 16ASHRAEClimateZones• ConventionalHVACv.GSHPFullsize GHX&Preconditioned GHX – FirstCostandEnergyCost

Page 45: Eye-opening GSHP System Performance · Eye-opening GSHP System Performance: ... Closed-Circuit Cooling Tower CCCT ... , diminished cooling load • Single pipe design exacerbated

Questions?

45

StephenHamstra,PE,[email protected]