Extron OCS 100 specifications · Extron OCS 100 Occupancy Sensors • Specifications 1...

4
1 Extron OCS 100 Occupancy Sensors • Specifications Specifications OCS 100 Occupancy Sensors OCS 100C Square feet coverage area ������������� 2000 square feet 32' (10 m) 23' (7 m) 64' (20 m) 45' (14 m) 12' (4 m) 22' (7 m) U.S. Patents: 6151529, 5946209, 5699243, 5640143, 6415205, 6078253, D404326, 6222191, 5986357, 6759954 3 (max Disabled) Threshold Not Used OCS 100C 68-3155-52 Rev. A www.extron.com Sensor Coverage US Minor Motion US Major Motion IR Minor Motion IR Major Motion NOTE: These coverage dimensions are achieved when the OCS 100C is installed 10 ft (3�04 m) above the coverage area� OCS 100W Square feet coverage area ������������� 1600 square feet 32' (10 m) 23' (7 m) 32' (10 m) 23' (7 m) 40' (12 m) 20' (6 m) 40' (12 m) Major Motion Coverage 20' (6 m) Minor Motion Coverage 10' (3 m) Mounting Height Sensor Coverage US Minor Motion US Major Motion IR Minor Motion IR Major Motion

Transcript of Extron OCS 100 specifications · Extron OCS 100 Occupancy Sensors • Specifications 1...

Page 1: Extron OCS 100 specifications · Extron OCS 100 Occupancy Sensors • Specifications 1 Specifications OCS 100 Occupancy Sensors OCS 100C Square feet coverage area ...

1Extron OCS 100 Occupancy Sensors • Specifications

SpecificationsOCS 100 Occupancy Sensors

OCS 100CSquare feet coverage area ������������� 2000 square feet

32'(10 m)

23'(7 m)

64'(20 m)

45'(14 m)

12'(4 m)

22'(7 m)

U.S. Patents: 6151529, 5946209, 5699243, 5640143, 6415205,

6078253, D404326, 6222191, 5986357, 6759954

67E4

Appliance C

ontrol

3(m

ax Disabled)

Threshold

Not U

sed

OCS 100C

68-3155-52 Rev. A

Extro

n Head

quarters

+1.800.633.9876 (Insid

e US

A/C

anada O

nly)E

xtron U

SA

- West

+1.714.491.1500

+1.714.491.1517 FA

X

ww

w.extro

n.com

Center ofSensor Coverage

Sensor CoverageUS Minor Motion

US Major Motion

IR Minor Motion

IR Major Motion

NOTE: These coverage dimensions are achieved when the OCS 100C is installed 10 ft (3�04 m) above the coverage area�

OCS 100WSquare feet coverage area ������������� 1600 square feet

32'(10 m)

23'(7 m)

32'(10 m)

23'(7 m)

40'(12 m)

20'(6 m)

40' (12 m) MajorMotion Coverage

20' (6 m) MinorMotion Coverage

10' (3 m) MountingHeight

Sensor CoverageUS Minor Motion

US Major Motion

IR Minor Motion

IR Major Motion

Page 2: Extron OCS 100 specifications · Extron OCS 100 Occupancy Sensors • Specifications 1 Specifications OCS 100 Occupancy Sensors OCS 100C Square feet coverage area ...

2

Specification • OCS 100 Occupancy Sensors (Continued)

Extron OCS 100 Occupancy Sensors • Specifications

SensorInteliDAPT® technology ����������������� Auto reset from test setting

Self-adjusting timer Self-adjusting passive infrared thresholds Automatic false-on and false-off correction

LED lamp ��������������������������������������� Red - infrared motion Green - ultrasonic detection

Timer timeoutOCS 100C ������������������������������ Automatic mode: 8 to 42 minutes (self-adjusts based on occupancy)

Manual mode: 8 to 42 minutes Test mode: 8 seconds

OCS 100W ������������������������������ Automatic mode: 4 to 30 minutes (self-adjusts based on occupancy) Manual mode: 4, 8, 15 and 30 minutes Test mode: 8 seconds

Ultrasonic (US)OCS 100C ������������������������������ 4 sensors - 32 kHz outputOCS 100W ������������������������������ 2 sensors - 32 kHz output

Passive infrared (PIR)OCS 100C ������������������������������ Dual-element pyrometer and 12-element cylindrical segmented Fresnel lens,

integral filter excludes excess PIR energy from sunlightOCS 100W ������������������������������ Dual-element pyrometer and 12-element cylindrical rugged lens

RelayRelay ��������������������������������������������� 1 Normally Open and Closed contact, single pole, double throw 500 mA rated at

24 VDC, three-wire isolated relay

PhotocellPhotocell ���������������������������������������� Adjustable natural-light override ranges from 1 to 100 foot-candles (10 to 1000

Lux)

Adaptive functionsLearning ����������������������������������������� 4 weeks for response error conditions, air current adaption and timer optimizationPost-learning occupancy periods ��� 24-hour circadian occupancy periods learnedAdjustments in post-learning period �������������������������������������������� Generally occupied periods

Generally unoccupied periods

Digital outputQuantity/type ��������������������������������� 2 digital outputsConnectors ������������������������������������ Blue wire = Occupancy only

Gray wire = Occupancy + PhotocellOutput voltage range ��������������������� 0 - 24 VDC

Active high logic control signal with short-circuit protection, open collector when unoccupied

GeneralSensor power input requirements��� 20-24 VDC, 33 mA nominal

NOTE: If power is supplied by an optional 12 VDC power supply, then use the included PC 1224 to convert 12 VDC to 24VDC�

PC 1224 power requirements �������� Input: 12 VDC, 1�5 A max Output: 12 VDC, 1�25 A max               24 VDC, 75 mA max

Wiring �������������������������������������������� Color coded, pre-stripped leads - 6" (15 am) in total lengthTemperature/humidity �������������������� Operation: +32 to +104 °F (0 to +40 °C) / 0% to 95 %, noncondensing

For indoor use onlyCooling ������������������������������������������ Convection, no vents

Page 3: Extron OCS 100 specifications · Extron OCS 100 Occupancy Sensors • Specifications 1 Specifications OCS 100 Occupancy Sensors OCS 100C Square feet coverage area ...

3

Specification • OCS 100 Occupancy Sensors (Continued)

Extron OCS 100 Occupancy Sensors • Specifications

Mounting ��������������������������������������� Mounting base provided Recommended mounting height: 8 feet with a max mounting height of 12 feet

Enclosure type ������������������������������� PlasticEnclosure dimensions

OCS 100C ������������������������������ 4�5" W x 1�4" D (114 mm W x 38 mm D)

1.4"(36 mm)

4.5"(114 mm)

OCS 100W ������������������������������ 2�8" W x 5�5" L  x 2�1" D (71 mm W x 140 mm x 53 mm D)

5.5"(140 mm)

3.7"(94 mm)

3.9"(99 mm)

2.8"(71 mm)

2.1"(53 mm)

PC 1224 ���������������������������������� 1�0" W x 1�0" L x 0�5" D (25�4 mm W x 25�4 mm L x 12�7 mm D)

Product weight ������������������������������ 0�1 lb (<0�1 kg)Color ���������������������������������������������� Off-whiteVibration ���������������������������������������� ISTA 1A in carton (International Safe Transit Association)Regulatory compliance

Safety �������������������������������������� CE, c-UL, ULEMI/EMC ��������������������������������� CE, FCC Class AEnvironmental �������������������������� Complies with the appropriate requirements of RoHS, WEEE, and California Title

24Warranty ���������������������������������������� 3 years parts and labor

Page 4: Extron OCS 100 specifications · Extron OCS 100 Occupancy Sensors • Specifications 1 Specifications OCS 100 Occupancy Sensors OCS 100C Square feet coverage area ...

4

Specification • OCS 100 Occupancy Sensors (Continued)

Extron Headquarters+800.633.9876 Inside USA/Canada Only

Extron USA - West Extron USA - East+1.714.491.1500 +1.919.850.1000

+1.714.491.1517 FAX +1.919.850.1001 FAX

Extron Europe+800.3987.6673

Inside Europe Only

+31.33.453.4040

+31.33.453.4050 FAX

Extron Asia+65.6383.4400

+65.6383.4664 FAX

Extron Japan+81.3.3511.7655

+81.3.3511.7656 FAX

Extron China+86.21.3760.1568

+86.21.3760.1566 FAX

Extron Middle East+971.4.299.1800

+971.4.299.1880 FAX

Extron Australia+61.8.8113.6800+61.8.8351.2511 FAX

Extron India1800.3070.3777

(Inside India Only)

+91.80.3055.3777

+91.80.3055.3737 FAX

© 2017 Extron Electronics All rights reserved. All trademarks mentioned are the property of their respective owners. www.extron.com

NOTE: Specifications are subject to change without notice�

NOTE: Shipping weights and dimensions are available at www.extron.com�

4153-D4