March 25, 2019Presentation Title 2

A paradigm shift: Inverter-based resources

Conventional synchronous resources

Inverter-based resourcesCourtesy Nick Miller and Debbie Lew

Page 3: Expertise to Enable Grid Transformation Summit 20… · Courtesy Nick Miller and Debbie Lew. March 25, 2019 4 Source: Drake Bartlett, PSCO, 2018 Moderate annual averages translate

March 25, 2019 3

Source: Drake Bartlett, PSCO, 2018

Moderate annual averages translate

to high instantaneous penetrations25% Annual

energy

71% instantaneous

Courtesy Nick Miller and Debbie Lew

Page 4: Expertise to Enable Grid Transformation Summit 20… · Courtesy Nick Miller and Debbie Lew. March 25, 2019 4 Source: Drake Bartlett, PSCO, 2018 Moderate annual averages translate

March 25, 2019 4

Source: Drake Bartlett, PSCO, 2018

Moderate annual averages translate

to high instantaneous penetrations

Courtesy Nick Miller and Debbie Lew

Page 5: Expertise to Enable Grid Transformation Summit 20… · Courtesy Nick Miller and Debbie Lew. March 25, 2019 4 Source: Drake Bartlett, PSCO, 2018 Moderate annual averages translate

March 25, 2019 5

MIGRATE, 2016

Today we are on the blue line and working towards the dashed blue curve.We don’t know what the green curve looks like or how to get there.

You can’t get there from here without a paradigm shift

100% inverters0% inverters

Stab

ility

Courtesy Nick Miller and Debbie Lew

Page 6: Expertise to Enable Grid Transformation Summit 20… · Courtesy Nick Miller and Debbie Lew. March 25, 2019 4 Source: Drake Bartlett, PSCO, 2018 Moderate annual averages translate

Frequency Response

• What is Synchronous Inertial Response?

• Fast Frequency Response?

• Primary Frequency response?

• As we move to an Inverter Based world, Frequency response is one thing that must evolve

Page 7: Expertise to Enable Grid Transformation Summit 20… · Courtesy Nick Miller and Debbie Lew. March 25, 2019 4 Source: Drake Bartlett, PSCO, 2018 Moderate annual averages translate

Frequency after a Disturbance Event

Disturbance(e.g., loss of a large

generating unit)

Figure from J. Eto, LBNL,https://www.ferc.gov/industries/electric/indus-act/reliability/frequencyresponsemetrics-report.pdf

Why does the frequency fall?

Consumption is unchanged (all load is being served)

Page 8: Expertise to Enable Grid Transformation Summit 20… · Courtesy Nick Miller and Debbie Lew. March 25, 2019 4 Source: Drake Bartlett, PSCO, 2018 Moderate annual averages translate

Synchronous Generators

• Mechanical torque goes in (from the energy source - “prime mover”)

• Electrical torque is pulled out (the electrical power to the grid)• When starting up, energy is applied to bring the generator up

to speed and then it is synchronized (electro-mechanically coupled) with the electrical grid

• Thereafter, the plant controls try to maintain a “torque in = torque out” balance to generate the desired power output level

Page 9: Expertise to Enable Grid Transformation Summit 20… · Courtesy Nick Miller and Debbie Lew. March 25, 2019 4 Source: Drake Bartlett, PSCO, 2018 Moderate annual averages translate

Putting it all Together: Frequency Response to an Event

Disturbance (e.g., loss of a large

generating unit)

Fast frequency response establishes nadir

Additional power from regulation and dispatch compensates for lost

resources to bring the system frequency back to 60 Hz

Primary frequency response stabilizes

the frequency

Figure from J. Eto, LBNL,https://www.ferc.gov/industries/electric/indus-act/reliability/frequencyresponsemetrics-report.pdf

Synchronous inertial response sets initial slope