EXISTING CONDENSATE ABV CEILING

3
1 CU-2 CU-3 CU-2 CU-3 F-5 F-4 CU-4 CU-5 RL & RS LINES (TYPICAL) F-4 F-5 3 4 " 3 4 " 3 4 " 3 4 " EXISTING CONDENSATE ABV CEILING 2'-0" CU-2 CU-3 CU-2 CU-3 $'' 1(: (/%2: /289(5 ADD NEW FM-200 SYSTEM. SEE SPECIFICATION 15301 NEW 6x6 SA L-1 '2:1 :,7+ 23(1 (1'(' '8&7 RG-1 8x8 MOTORIZED FIRE DAMPER INTERLOCK WITH SMOKE DETECTORS INTERLOCK WITH FM 200 SYSTEM TYPICAL OF 3 SEQUENCE UPON A DETECTION OF SMOKE THE MOTORIZED FIRE DAMPERS SHALL CLOSE THE FM 200 SYSTEM SHALL BE ACTIVATED & EF-1 SHALL BE ENERGIZED. EF-1 Design 3 Architecture, PC All Rights Reserved c Copyright 2015 1 HVAC FLOOR PLANS H1 2

Transcript of EXISTING CONDENSATE ABV CEILING

Page 1: EXISTING CONDENSATE ABV CEILING

CU-1

CU-2

CU-3

CU-2

CU-3

F-5

F-4

CU-4CU-5

RL & RS LINES (TYPICAL)

F-4

F-5

3

4

"

3

4

"

3

4

"

3

4

"

EXISTING CONDENSATE ABV CEILING

2'-0"

CU-2

CU-3

CU-2

CU-3

ADD NEW 90° ELBOW & LOUVER

ADD NEW FM-200 SYSTEM. SEE SPECIFICATION 15301

NEW 6x6 SA

L-1

90° DOWN WITH OPEN ENDED DUCT

RG-1

8x8

MOTORIZED FIRE DAMPER

INTERLOCK WITH SMOKE DETECTORS

INTERLOCK WITH FM 200 SYSTEM

TYPICAL OF 3

SEQUENCE

UPON A DETECTION OF SMOKE THE MOTORIZED FIRE DAMPERS

SHALL CLOSE

THE FM 200 SYSTEM SHALL BE ACTIVATED &

EF-1 SHALL BE ENERGIZED.

EF-1

Design 3 Architecture, PC All Rights Reserved

c

Copyright2015

1

HVAC FLOOR PLANS

H12

Page 2: EXISTING CONDENSATE ABV CEILING

Design 3 Architecture, PC All Rights Reserved

c

Copyright2015

HVAC SCHEDULES & DIAGRAMS

H2

Page 3: EXISTING CONDENSATE ABV CEILING

Design 3 Architecture, PC All Rights Reserved

c

Copyright2015

HVAC DETAILS

H3

NTS

NTS

SEE ARCH. DWG FOR

OPENING DETAIL

MOTORIZED LOUVER/DAMPER

WALL SLEEVE. SEAL WEATHER TIGHT

WALL (SEE ARCHITECTURAL DRAWINGS FOR WALL TYPE)

SEE ARCH. DWG FOR

OPENING DETAIL

MOTORIZED DAMPER

REAR GUARD

WALL SLEEVE

CHANNEL SUPPORTS

WALL

MARK

MANUFACTURER

SERVICE

MODEL #

E.S.P.

IN. W.G.

TYPE C.F.M.

VOLT/HZ/PHREMARKS

EF-1120/60/1.15

225

GREENHECK SP-A110

WATTS/

(HP)

(1/25)

PROVIDE MOTOR SIDE GUARD, WEATHER

HOOD, SLEEVE, DISCHARGE LOUVER

CALL CENTER

WALL

FAN

S1-8-440-D

AND INFORMATION.

OPPOSED BLADE DAMPEROBD

TYPICALTYP.

WET BULB

WATER GAUGE

WEIGHT

WB

W.G.

WT

W/ WITH

OPERATING

OUTSIDE AIR

RETURN AIR

RETURN GRILLE

SUPPLY AIR

SUPPLY REGISTER

SENSIBLE

PRESS DROP

SMOKE DETECTOR

PLUMBING CONTRACTOR

R/A

S/A

RG

SD

SR

SENS

OPER

OSA

P.C.

PH

P.D.

PHASE

T

THERMOSTAT WITH

FLOW DIRECTION

ZONE LOCATION

FIRE DAMPER

1

SUPPLY AIR DUCT

EXHAUST AIR DUCT

RETURN AIR DUCT

OR REGISTER

DRY BULBDB

FLEXIBLEFLEX

1000 BRITISH THERMAL UNITS

HORSEPOWER

LOUVER

POUNDS

MAXIMUM

HEATING CONTRACTOR

GENERAL CONTRACTOR

MANUAL VOLUME DAMPER

LEAVING AIR TEMPERATURE

L

MAX

LAT

LBS

MVD

MBH

HP

H.C.

G.C.

IN.

HZ

INCHES

HERTZ

ENTERING AIR TEMPERATURE

DIAMETER

EXHAUST FAN

EXISTING

FIRE DAMPER

FURNACE

EXTERNAL STATIC PRESSURE

ELECTRIC WALL HEATER

ELECTRICAL CONTR.

EF

EWH

ESP

EXIST

FD

F

E.C.

DIA

DN.

EA

EAT

DOWN

EACH

MAINTAIN PROPER CLEARANCES AS RECOMMENDED BY THE

EQUIPMENT MANUFACTURER & ALL INDUSTRY STANDARDS.

18.

CUBIC FEET PER MINUTE

CONDENSING UNIT

ABOVE FINISHED FLOOR

CEILING DIFFUSER

BOTTOM OF DUCT

BACKDRAFT DAMPER

ABOVE

AFF

ABV

CU

CFM

BDD

B.O.D.

CD

THE CONTRACTOR SHALL EXECUTE THE WORK IN STRICT ACCORDANCE

THE DRAWING AND NOT SPECIFIED OR SPECIFIED AND NOT SHOWN ON

WITH THE SPECIFICATION AND DRAWINGS. WHERE WORK IS SHOWN ON

FLEXIBLE

MANUFACTURER.

ELBOW, TURNED

RS

RL

RETURN AIR GRILLE

CEILING DIFFUSER

MVD

MANUAL VOLUME

DAMPER

REFRIGERATE

SUCTION

REFRIGERATE

UP

LIQUID

TURNING VANES

ELBOW, TURNED

DOWN

CONNECTION

LOUVER COLOR TO BE AS SPECIFIED BY THE ARCHITECT.11.

DRAWINGS, THE MORE STRINGENT CONDITION SHALL APPLY.

SEE SPECIFICATION SECTION 15500 FOR ADDITIONAL REQUIREMENTS

THE HEATING CONTRACTOR SHALL FURNISH ALL MOTOR STARTERS

LENGTH OF FLEXIBLE DUCT = 5'-0". FLEX SIZE = CD NECK SIZE.

IN THE EVENT OF A CONFLICT BETWEEN THE SPECIFICATIONS AND

DRAWING, THE CONTRACTOR SHALL PROVIDE ALL SUCH WORK.

THE HEATING CONTRACTOR SHALL FURNISH AND INSTALL ALL

CONCRETE BASES AND MISCELLANEOUS SUPPORTING STEEL FOR

WITH MANUAL DAMPERS WITH LOCKING QUADRANTS. MAXIMUM

EACH ITEM OF MECHANICAL EQUIPMENT.

ALL DUCT RUNOUTS TO DIFFUSERS TO BE INSTALLED

17.

16.

15.

AS REQUIRED.

13.

14.

12.

ALL DUCTWORK DIMENSIONS INDICATED ON DRAWINGS

DRAWINGS ARE DIAGRAMMATIC, CONTRACTOR TO FIELD

ARE FREE INSIDE DIMENSIONS.

HVAC LOUVERS PROVIDED BY HEATING CONTRACTOR,

VERIFY ALL DUCT ROUTING. ADDITIONAL OFFSETS

HEATING CONTRACTOR TO VERIFY ALL POWER

REQUIREMENTS WITH THE ELECTRICAL CONTRACTOR.

ALL POWER WIRING BY ELECTRICAL CONTRACTOR.

ALL CONTROL WIRING BY HEATING CONTRACTOR.

9.

10.

8.

TO BE EXPECTED.

6.

7.

4.

5.

12/20

FIGURE IS SIZE

SHOWN)

DUCT SIZE (FIRST

DUCTWORK AND PIPING WITH UTILITIES AND OTHER TRADES.

GRILLES WITH LIGHTING PLAN.

VERIFY ALL REFRIGERANT PIPE SIZES WITH EQUIPMENT

FIELD VERIFY FOR CLEARANCE BEFORE INSTALLATION.

COORDINATE FINAL LOCATION OF DIFFUSERS AND

SPACE ABOVE CEILING WILL BE CRITICAL TO COORDINATE

3.

2.

1.

FRAME

TYPE

MARK DESCRIPTION

MODEL #

MANUFACTURER

FRAME

SIZE

REMARKSOBD

NO COMBUSTIBLE MATERIALS ALLOWED WITHIN THE RETURN AIR PLENUM

INCLUDING PVC PIPING.

19.

ALL DUCT & PIPING THROUGH RATED WALLS & FLOORS TO HAVE SLEEVES,

FIRE DAMPERS AND FIRE SAFED.

SD

SMOKE DETECTOR

CEILING EXHAUST FAN

DUCT

TRANSITION

NECKNK

POINT OF CONNECTION

TO EXISTING

FLEXIBLE DUCT

& DAMPER. SAME SIZE

AS CD NK

ROOFTOP UNITRTU

L-1

WALL

MASONRY

EXISTING DUCT

EXISTING DUCT

TO BE DEMOLISHED

LOUVERRUSKIN

ELF375X

SEE DRAWING FOR NECK SIZE. PROVIDE INSECT SCREEN

SLEEVE, BDD & SECURITY BARS WELDED ON 6" CENTERS.

MECHANICAL CONTRACTORM.C.

WEATHER HOOD

SURFACERG-1 SEE DRAWING FOR NECK SIZE

NO

RETURN

GRILLE

PRICE

630