EXISTING CONDENSATE ABV CEILING
Transcript of EXISTING CONDENSATE ABV CEILING
CU-1
CU-2
CU-3
CU-2
CU-3
F-5
F-4
CU-4CU-5
RL & RS LINES (TYPICAL)
F-4
F-5
3
4
"
3
4
"
3
4
"
3
4
"
EXISTING CONDENSATE ABV CEILING
2'-0"
CU-2
CU-3
CU-2
CU-3
ADD NEW 90° ELBOW & LOUVER
ADD NEW FM-200 SYSTEM. SEE SPECIFICATION 15301
NEW 6x6 SA
L-1
90° DOWN WITH OPEN ENDED DUCT
RG-1
8x8
MOTORIZED FIRE DAMPER
INTERLOCK WITH SMOKE DETECTORS
INTERLOCK WITH FM 200 SYSTEM
TYPICAL OF 3
SEQUENCE
UPON A DETECTION OF SMOKE THE MOTORIZED FIRE DAMPERS
SHALL CLOSE
THE FM 200 SYSTEM SHALL BE ACTIVATED &
EF-1 SHALL BE ENERGIZED.
EF-1
Design 3 Architecture, PC All Rights Reserved
c
Copyright2015
1
HVAC FLOOR PLANS
H12
Design 3 Architecture, PC All Rights Reserved
c
Copyright2015
HVAC SCHEDULES & DIAGRAMS
H2
Design 3 Architecture, PC All Rights Reserved
c
Copyright2015
HVAC DETAILS
H3
NTS
NTS
SEE ARCH. DWG FOR
OPENING DETAIL
MOTORIZED LOUVER/DAMPER
WALL SLEEVE. SEAL WEATHER TIGHT
WALL (SEE ARCHITECTURAL DRAWINGS FOR WALL TYPE)
SEE ARCH. DWG FOR
OPENING DETAIL
MOTORIZED DAMPER
REAR GUARD
WALL SLEEVE
CHANNEL SUPPORTS
WALL
MARK
MANUFACTURER
SERVICE
MODEL #
E.S.P.
IN. W.G.
TYPE C.F.M.
VOLT/HZ/PHREMARKS
EF-1120/60/1.15
225
GREENHECK SP-A110
WATTS/
(HP)
(1/25)
PROVIDE MOTOR SIDE GUARD, WEATHER
HOOD, SLEEVE, DISCHARGE LOUVER
CALL CENTER
WALL
FAN
S1-8-440-D
AND INFORMATION.
OPPOSED BLADE DAMPEROBD
TYPICALTYP.
WET BULB
WATER GAUGE
WEIGHT
WB
W.G.
WT
W/ WITH
OPERATING
OUTSIDE AIR
RETURN AIR
RETURN GRILLE
SUPPLY AIR
SUPPLY REGISTER
SENSIBLE
PRESS DROP
SMOKE DETECTOR
PLUMBING CONTRACTOR
R/A
S/A
RG
SD
SR
SENS
OPER
OSA
P.C.
PH
P.D.
PHASE
T
THERMOSTAT WITH
FLOW DIRECTION
ZONE LOCATION
FIRE DAMPER
1
SUPPLY AIR DUCT
EXHAUST AIR DUCT
RETURN AIR DUCT
OR REGISTER
DRY BULBDB
FLEXIBLEFLEX
1000 BRITISH THERMAL UNITS
HORSEPOWER
LOUVER
POUNDS
MAXIMUM
HEATING CONTRACTOR
GENERAL CONTRACTOR
MANUAL VOLUME DAMPER
LEAVING AIR TEMPERATURE
L
MAX
LAT
LBS
MVD
MBH
HP
H.C.
G.C.
IN.
HZ
INCHES
HERTZ
ENTERING AIR TEMPERATURE
DIAMETER
EXHAUST FAN
EXISTING
FIRE DAMPER
FURNACE
EXTERNAL STATIC PRESSURE
ELECTRIC WALL HEATER
ELECTRICAL CONTR.
EF
EWH
ESP
EXIST
FD
F
E.C.
DIA
DN.
EA
EAT
DOWN
EACH
MAINTAIN PROPER CLEARANCES AS RECOMMENDED BY THE
EQUIPMENT MANUFACTURER & ALL INDUSTRY STANDARDS.
18.
CUBIC FEET PER MINUTE
CONDENSING UNIT
ABOVE FINISHED FLOOR
CEILING DIFFUSER
BOTTOM OF DUCT
BACKDRAFT DAMPER
ABOVE
AFF
ABV
CU
CFM
BDD
B.O.D.
CD
THE CONTRACTOR SHALL EXECUTE THE WORK IN STRICT ACCORDANCE
THE DRAWING AND NOT SPECIFIED OR SPECIFIED AND NOT SHOWN ON
WITH THE SPECIFICATION AND DRAWINGS. WHERE WORK IS SHOWN ON
FLEXIBLE
MANUFACTURER.
ELBOW, TURNED
RS
RL
RETURN AIR GRILLE
CEILING DIFFUSER
MVD
MANUAL VOLUME
DAMPER
REFRIGERATE
SUCTION
REFRIGERATE
UP
LIQUID
TURNING VANES
ELBOW, TURNED
DOWN
CONNECTION
LOUVER COLOR TO BE AS SPECIFIED BY THE ARCHITECT.11.
DRAWINGS, THE MORE STRINGENT CONDITION SHALL APPLY.
SEE SPECIFICATION SECTION 15500 FOR ADDITIONAL REQUIREMENTS
THE HEATING CONTRACTOR SHALL FURNISH ALL MOTOR STARTERS
LENGTH OF FLEXIBLE DUCT = 5'-0". FLEX SIZE = CD NECK SIZE.
IN THE EVENT OF A CONFLICT BETWEEN THE SPECIFICATIONS AND
DRAWING, THE CONTRACTOR SHALL PROVIDE ALL SUCH WORK.
THE HEATING CONTRACTOR SHALL FURNISH AND INSTALL ALL
CONCRETE BASES AND MISCELLANEOUS SUPPORTING STEEL FOR
WITH MANUAL DAMPERS WITH LOCKING QUADRANTS. MAXIMUM
EACH ITEM OF MECHANICAL EQUIPMENT.
ALL DUCT RUNOUTS TO DIFFUSERS TO BE INSTALLED
17.
16.
15.
AS REQUIRED.
13.
14.
12.
ALL DUCTWORK DIMENSIONS INDICATED ON DRAWINGS
DRAWINGS ARE DIAGRAMMATIC, CONTRACTOR TO FIELD
ARE FREE INSIDE DIMENSIONS.
HVAC LOUVERS PROVIDED BY HEATING CONTRACTOR,
VERIFY ALL DUCT ROUTING. ADDITIONAL OFFSETS
HEATING CONTRACTOR TO VERIFY ALL POWER
REQUIREMENTS WITH THE ELECTRICAL CONTRACTOR.
ALL POWER WIRING BY ELECTRICAL CONTRACTOR.
ALL CONTROL WIRING BY HEATING CONTRACTOR.
9.
10.
8.
TO BE EXPECTED.
6.
7.
4.
5.
12/20
FIGURE IS SIZE
SHOWN)
DUCT SIZE (FIRST
DUCTWORK AND PIPING WITH UTILITIES AND OTHER TRADES.
GRILLES WITH LIGHTING PLAN.
VERIFY ALL REFRIGERANT PIPE SIZES WITH EQUIPMENT
FIELD VERIFY FOR CLEARANCE BEFORE INSTALLATION.
COORDINATE FINAL LOCATION OF DIFFUSERS AND
SPACE ABOVE CEILING WILL BE CRITICAL TO COORDINATE
3.
2.
1.
FRAME
TYPE
MARK DESCRIPTION
MODEL #
MANUFACTURER
FRAME
SIZE
REMARKSOBD
NO COMBUSTIBLE MATERIALS ALLOWED WITHIN THE RETURN AIR PLENUM
INCLUDING PVC PIPING.
19.
ALL DUCT & PIPING THROUGH RATED WALLS & FLOORS TO HAVE SLEEVES,
FIRE DAMPERS AND FIRE SAFED.
SD
SMOKE DETECTOR
CEILING EXHAUST FAN
DUCT
TRANSITION
NECKNK
POINT OF CONNECTION
TO EXISTING
FLEXIBLE DUCT
& DAMPER. SAME SIZE
AS CD NK
ROOFTOP UNITRTU
L-1
WALL
MASONRY
EXISTING DUCT
EXISTING DUCT
TO BE DEMOLISHED
LOUVERRUSKIN
ELF375X
SEE DRAWING FOR NECK SIZE. PROVIDE INSECT SCREEN
SLEEVE, BDD & SECURITY BARS WELDED ON 6" CENTERS.
MECHANICAL CONTRACTORM.C.
WEATHER HOOD
SURFACERG-1 SEE DRAWING FOR NECK SIZE
NO
RETURN
GRILLE
PRICE
630