ABV-4 ABV-5 ABV-6 Product Information Applications Information ... MODEL ABV-4 PRESSURE (inches/WG)...

6
PROUDLY MADE IN THE USA Product Information The ABV Automatic Balancing Valves maintain a constant airflow volume in HVAC applications. The engineered damper blade is calibrated to automatically adjust to varying pressures using physics not electricity giving the ABV true pressure independence. Airflow Balancing Valves have been very popular in Europe for several years, and we are proud to be the first to build this type of product in the United States and the first to design the product specifically to meet the needs of American applications. Applications Precise and automatic airflow regulation in supply or exhaust ventilation systems in any residential or commercial building. Automatic balancing of the supply grilles in forced air heating and cooling systems in homes. Any HVAC applications with a static pressure between 0.2 and 2.0 inches w.c. Controlled volume of make-up air. OEM Applications such as chilled beams, Fan Coil Units, PTAC units, centralized fan systems, fresh/make-up air systems, and HRV/ERV’s. Suitable for application in temperatures ranging from 25º to 150ºF (-4º to 65ºC). Residential, Commercial, OEM Classified by UL to UL 2043 for heat release rate and smoke optical density. ABV Sizes Available Airflow Range Nominal 4" Diameter 25 to 130 CFM Nominal 5" Diameter 25 to 130 CFM Nominal 6" Diameter 50 to 275 CFM Warranty Every ABV product comes with a product replacement warranty to be free from manufacturing defects for a period of 5 years from the date of purchase. Semiannual cleaning is suggested to ensure the precise operation of the valve. Lab Calibrated Every ABV features a unique, patent-pending set-point adjustment arm that allows for easy adjustment of the airflow rate through each valve. Each ridge of the set-point adjustment indicator has been laboratory calibrated in accordance with ANSI/AMCA 500-D-12. Each ridge is lab proven to deliver a flow rate within 10% of the set point from 0.2" up to 2.0" of water column. ABV-4 ABV-5 ABV-6 (4" and 5" model set-points shown.) R38089 Note: Airflow range determined through +/- 10% of average airflow over 0.2" to 2" W.C. www.airflowbalancing.com 1

Transcript of ABV-4 ABV-5 ABV-6 Product Information Applications Information ... MODEL ABV-4 PRESSURE (inches/WG)...

Page 1: ABV-4 ABV-5 ABV-6 Product Information Applications Information ... MODEL ABV-4 PRESSURE (inches/WG) SET POINTS CFM CFM 30 CFM 35 CFM 45 CFM 50 CFM 60 CFM 75 CFM 105 ... CFM 180 …

PROUDLYMADE IN

THE USA

Product InformationThe ABV Automatic Balancing Valves maintain a constant airflow volume in HVAC applications. The engineered damper blade is calibrated to automatically adjust to varying pressures using physics not electricity giving the ABV true pressure independence.

Airflow Balancing Valves have been very popular in Europefor several years, and we are proud to be the first to build this type of product in the United States and the first to design the product specifically to meet the needs of American applications.

Applications

• Precise and automatic airflow regulation in supply or exhaust ventilation systems in any residential or commercial building.

• Automatic balancing of the supply grilles in forced air heating and cooling systems in homes.

• Any HVAC applications with a static pressure between 0.2 and 2.0 inches w.c.

• Controlled volume of make-up air.

• OEM Applications such as chilled beams, Fan Coil Units, PTAC units, centralized fan systems, fresh/make-up air systems, and HRV/ERV’s.

• Suitable for application in temperatures ranging from 25º to 150ºF (-4º to 65ºC).

Residential, Commercial, OEM

Classified by UL to UL 2043 forheat release rate and smokeoptical density.

ABV Sizes Available • Airflow Range

Nominal 4" Diameter • 25 to 130 CFMNominal 5" Diameter • 25 to 130 CFMNominal 6" Diameter • 50 to 275 CFM

WarrantyEvery ABV product comes with a product replacement warranty to be free from manufacturing defects for a period of 5 years from the date of purchase. Semiannual cleaning is suggested to ensure the precise operation of the valve.

Lab CalibratedEvery ABV features a unique, patent-pending set-point adjustment arm that allows for easy adjustment of the airflow rate through each valve.Each ridge of the set-point adjustment indicator has been laboratory calibrated in accordance with ANSI/AMCA 500-D-12. Each ridge is lab proven to deliver a flow rate within 10% of the set point from0.2" up to 2.0" of water column.

ABV-4 ABV-5 ABV-6

(4" and 5" model set-points shown.)

R38089

Note: Airflow range determined through +/- 10% of average airflow over 0.2" to 2" W.C.

www.airflowbalancing.com1

Page 2: ABV-4 ABV-5 ABV-6 Product Information Applications Information ... MODEL ABV-4 PRESSURE (inches/WG) SET POINTS CFM CFM 30 CFM 35 CFM 45 CFM 50 CFM 60 CFM 75 CFM 105 ... CFM 180 …

Features & Benefits

1. The desired airflow is set by moving the set-point adjustment arm to the desired airflow in CFM (cubic feet per minute).

They Work Using Physics, Not Electricity

2. Then the fixed stator blade applies the exact amount of tension on the moving damper blade to hold the airflow at the targeted airflow.

3. Then the pressure differential across the moving damper blade gives the blade lift to automatically adjust to changes in static pressure & air velocity. This is what gives it “pressure independence”.

Using physics, the Airflow Balancing Valves will constrain the airflow volume toprecise factory calibrated volumes as marked on the front of the valve.

Steri-Balance™

Sealed Tight

Total Control

Anti-microbial agent toprevent mold and bacteria.

Raised gasket for insertion intoround duct or flat rubber gasket for connection to adapter plate.

20-24 Set-points that can be viewedand adjusted through the grille.

Lab CalibratedAirflow lab-tested at each set point.

AdaptabilityPatented quick connect adapter ring for easy use with field platesand boxes.

UL ClassifiedUL2043 Tested and Classified.

Bi-DirectionalBy flipping the valve it changesfrom exhaust to supply.

www.airflowbalancing.com2

Page 3: ABV-4 ABV-5 ABV-6 Product Information Applications Information ... MODEL ABV-4 PRESSURE (inches/WG) SET POINTS CFM CFM 30 CFM 35 CFM 45 CFM 50 CFM 60 CFM 75 CFM 105 ... CFM 180 …

www.airflowbalancing.com3

Performance Data

Units tested in accordance with AMCA 500-D-12, Figure 5.1.ABV-4 and ABV-5 have 20 individual manual set points. ABV-6 has 24 individual manual set points. The most common ventilation flow rates are labeled on the products. The performance data for those set points is reported here. Performance data for each individual manual set point is available upon request.

CFM

CFM 30

CFM 35

CFM 45

CFM 50

CFM 60

CFM 75

CFM 105

CFM 125

CFM 90

140.0

120.0

100.0

80.0

60.0

40.0

20.0

0.00.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00

MODEL ABV-4

PRESSURE (inches/WG)

SET POINTS

CFM

CFM 30

CFM 35

CFM 45

CFM 50

CFM 60

CFM 75

CFM 105

CFM 125

CFM 90

140.0

120.0

100.0

80.0

60.0

40.0

20.0

0.00.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00

MODEL ABV-5

PRESSURE (inches/WG)

SET POINTS

300.0

250.0

200.0

150.0

100.0

50.0

0.00.25 0.50 0.75 1.00 1.25 1.50 1.75

MODEL ABV-6

PRESSURE (inches/WG)

CFM 60

CFM 75

CFM 90

CFM 105

CFM 120

CFM 135

CFM 180

CFM 205

CFM 150

CFM 240

CFM

SET POINTS

Page 4: ABV-4 ABV-5 ABV-6 Product Information Applications Information ... MODEL ABV-4 PRESSURE (inches/WG) SET POINTS CFM CFM 30 CFM 35 CFM 45 CFM 50 CFM 60 CFM 75 CFM 105 ... CFM 180 …

www.airflowbalancing.com4

ABV Assemblies

ABV with Square/Rectangular Transition

The ABV Automatic Balancing Valve can be supplied as a part of several assemblies for numerous applications. The ABV can be flipped around in all assemblies to go from exhaust to supply applications without any modification.

Allows the ABV to be inserted into square/rectangular duct, plenum boxes or grille boxes. The transition plate is intended to go inside the square/rectangular duct or plenum box and can be used with legs turned in or out (for space gain).

(Legs Turned Out)(Legs Turned In)

4" Model with 6" x 6" transition shown.

ABV with Grille MountsThe ABV can be supplied with a grille mount box with or without a grille. The grille mount box is a flanged galvanized steel box that allows the insertion of a grille.

ABV with Fire Damper in a UL Rated AssemblyThe ABV can be supplied as a part of a UL rated assembly with a UL 555 rated Fire Damper when penetrating fire rated walls and floors. This assembly employs an ABV, square/rectangular transition, flanged sleeve, slimline fire damper (static or dynamic) and optional grille.

Unlike some competitors, the entire assembly that is provided is UL rated and approved (not just the fire damper).

R38089R8218

ABV

S/R Transition (tab or adapter plate depends on size) Flanged Sleeve

Slimline Fire Damper

Grille (optional)

Page 5: ABV-4 ABV-5 ABV-6 Product Information Applications Information ... MODEL ABV-4 PRESSURE (inches/WG) SET POINTS CFM CFM 30 CFM 35 CFM 45 CFM 50 CFM 60 CFM 75 CFM 105 ... CFM 180 …

5

Competition Comparison

AAB Model ABV Aldes Model CAR-II*

Can be provided in a UL rated assembly with UL rated fire damper Yes No

Effective Opertating Pressure Range 0.2-2.0 In. WG 0.2-0.8 In. WG

Engineered for use in Imperial Measurements Yes No

Qualifies for ARRA section 1605 and Buy america 49 U.S.C. section 50101for use in all FAA, FHWA, AMTRAK and FTA projects. Yes No

Bi-Directional to be used for Supply or Exhaust Applications Yes No

Anti-Microbial agent infused into plastic to deter mold & bacterial growth Yes - Steri-Balance™ No

Quick Connect adapter ring to be used to attach to almost any adapter plate Yes No

Total Unique Set-Points (4" and 5" model) 20 Non-Adjustable

Total Unique Set-Points (6" model) 24 Non-Adjustable

Set Point Range (CFM) (4" model) 25-130 10-60

Set Point Range (CFM) (6" model) 50-275 75-175

Airflow Accuracy range+/- 10% within0.2-2.0" WG

+/- 15% for under50 CFM and +/-10%within 0.2-0.8" WG

Hydraulic blade dampener for extremely quiet operation Yes No

5-Year Warranty Yes Yes

*Aldes model CAR-II is made by the Anjos company and private labeled for several other manufacturers.

www.airflowbalancing.com

Page 6: ABV-4 ABV-5 ABV-6 Product Information Applications Information ... MODEL ABV-4 PRESSURE (inches/WG) SET POINTS CFM CFM 30 CFM 35 CFM 45 CFM 50 CFM 60 CFM 75 CFM 105 ... CFM 180 …

Sales Sheet - Model ABV - 030118

Automatic Airflow Balancing is a brand of Metal Industries, Inc. which was founded in 1947 and has been focused on providing the highest quality products to the HVAC industry and doing so with respect for our customers, our employees and the environment.

As an American owned company built on a tradition of integrity and respect, we strive to meet the needs of the HVAC market with a relentless focus on the customer. All Metal Industries products offer best in class lead time and are backed by a tireless support team of industry professionals.

AUTOMATIC AIRFLOW BALANCING1985 Carroll Street · Clearwater, FL 33761727.441.2651 · www.airflowbalancing.com