Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation...

34
NASA Technical Memorandum 110275 Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) to Clean and Verify Liquid Oxygen Systems MicheUe L. Morris Langley Research Center, Hampton, Virginia September 1996 National Aeronautics and Space Administration Langley Research Center Hampton, Virginia 23681-0001 https://ntrs.nasa.gov/search.jsp?R=19960050103 2020-04-17T14:02:12+00:00Z

Transcript of Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation...

Page 1: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

NASA Technical Memorandum 110275

Evaluation of Alternatives for

Trichlorotrifluoroethane (CFC-113) to

Clean and Verify Liquid Oxygen Systems

MicheUe L. Morris

Langley Research Center, Hampton, Virginia

September 1996

National Aeronautics and

Space AdministrationLangley Research CenterHampton, Virginia 23681-0001

https://ntrs.nasa.gov/search.jsp?R=19960050103 2020-04-17T14:02:12+00:00Z

Page 2: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid
Page 3: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Researchers at NASA Langley Research Center (LaRC) investigated several

alternatives to the use of trichlorotrifluoroethane (CFC 113) in oxygen

cleaning and verification. Options included several replacement solvents,

Non-Destructive Evaluation (NDE) and Total Organic Carbon (TOC) analysis.

Among the solvents, 1,1-dichloro-l-fluoroethane (HCFC 141b) and

dichloropentafluoropropane (HCFC 225) are the most suitable alternatives for

cleaning and verification. However, use of HCFC 141b is restricted, HCFC 225

introduces toxicity hazards, and the NDE and TOC methods of verification are

not suitable for processes at LaRC. Therefore, the interim recommendation is

to sparingly use CFC 113 for the very difficult cleaning tasks where safety is

critical and to move to an aqueous-based cleaning system for components.

Meanwhile, evaluation must continue on new solvents and procedures to find

one suited to LaRC's oxygen cleaning needs.

Keywords: trichlorotrifluoroethane, CFC 113, solvents, oxygen cleaning,verification.

Page 4: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid
Page 5: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Table of Contents

Section

1.0 Introduction

2.0 Objective

3.0 Background

4.0 NDE Methods of Investigation

5.0 TOC Method of Investigation

6.0 Solvent Efficiency Test6.1 Test Solvents6.2 Test Contaminants

6.3 Contamination and Testing Procedure

7.0 Material Compatibility7.1 Test Materials7.2 Test Solvents7.3 Test Procedure

8.0 Results

8.1 Solvent Efficiency Test8.2 Material Compatibility Test8.3 Material Compatibility Test: NVR

9.0 Health and Environmental Effects9.1 Health Effects9.2 Environmental Effects

10.0 Financial Considerations

11.0 Conclusions11.1 Future Plans11.2 Recommendations

ea_e

4

6678

8899

991120

21

2121

22

232324

iii

Page 6: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Table

List of Tables

Page

1. Level 300A Particle Limits

2. Test Solvents

3. Solvent Properties

4. Test Contaminants

5. Test Articles

6. Solvent Efficiency Test

7. Copper Compatibility Tests

8. 15-5 Stainless Steel Compatibility Tests

9. Mild Carbon Steel Compatibility Tests

10. Brass Compatibility Tests

11. Teflon Compatibility Tests

12. Viton Compatibility Tests

13. Fluorogreen Compatibility Tests

14. Buna-N Compatibility Tests

15. Vespel Compatibility Tests

16. Kel-F Compatibility Tests

17. Metals NVR Results

18. Elastomers NVR Results

19. Environmental Effects of Test Solvents

20. Cost of Alternative Solvents

3

6

7

8

8

10

11

12

13

14

15

16

17

18

19

19

20

21

22

22

iv

Page 7: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Evaluation of Alternatives for Trichlorotrifluoroethane

(CFC 113) to Clean and Verify Liquid Oxygen Systems

1.0 INTRODUCTION

The Montreal Protocol and the Clean Air Act specified that production ofchlorofluorocarbons (CFCs) will cease December 31, 1995. CFC 113 is used for

precision cleaning of sensitive aerospace equipment, electronics and liquid oxygen(LOX) systems. It is also used to verify the cleanliness level of equipment after it hasbeen cleaned.

The 8-Foot High Temperature Tunnel (8'HTT) at NASA Langley Research Center(LaRC) is a core aerothermal facility where new high-speed engine concepts are tested.It uses many high-pressure gases to simulate Mach 7 conditions, among them methane,air, silane and liquid oxygen. The cleaning process relies heavily ontrichlorotrifluoroethane (CFC 113) for the LOX injection ring and its accompanying

components and to verify the cleanliness of those parts. Therefore, it is imperative that areplacement method of cleaning and verifying the LOX system be found.

NASA LaRC has investigated several alternatives including non-destructive evaluation

(NDE) methods, total organic carbon (TOC) analysis and many alternate solvents.Methods were evaluated on their ability to remove contaminants, ability to detectremaining contaminants, material compatibility, health and environmental effects andcost.

The use of trademarks or names of manufacturers in this report is for accurate reportingand does not constitute an official endorsement, either expressed or implied, of such

products or manufacturers by the National Aeronautics and Space Administration.

2.0 OBJECtiVE

The purpose of this investigation is to find a suitable replacement for CFC 113 to be usedin the LOX cleaning and verification processes and thereby eliminate the Center's needfor CFC 113.

3.0 BACKGROUND

NASA LaRC's mission is to conduct research in aeronautics and aircraft structures and

transfer that knowledge to industry. The 8'HI'T is an aerothermal test facility where

hypersonic flight conditions can be simulated. The facility stores air, methane, hydrogen,silane and LOX, all at high pressure, to be used during a run. Many of these gases areflammable and present dangerous conditions, but the one of primary concern is LOX.

LOX is injected into high pressure air, mixes upstream and flows toward the nozzle pastthe methane spray bar (Figure 1). Methane is injected into the oxygen-enriched air and is

Page 8: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

!

t_

00

it_

0

-

J

-r_t.

2

Page 9: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

ignited a few inches from the spray bar. By the time the gas mixture reaches the testsection, the oxygen content is back to 21 percent, simulating flight conditions.

Explosion hazards are a constant concern at the facility, and cleaning the 8'HTr oxygensystem is a very important part of its operation and safety. Cleaning eliminates strayhydrocarbon greases that might combust and particles that might cause an impactexplosion. The LOX injection ring is cleaned to Level 300A after every 10 run starts.The (A) designation stipulates that the non-volatile residue (NVR) shall be less than 10

ppm. Level 300 particle limits are defined in Table 1.

Table 1: Level 300A Particle Limits

< 100 I Unlimited100 - 250 I 93

>250- 300 I 3

>300 I None

The current cleaning process is divided into two areas: components and the LOX

injection ring.

For components, the parts are precleaned with brushes and hot water, then placed inultrasonics with an aqueous alkaline solution of ten percent Brulin 815GD followed by ahot water rinse, and in some cases an acid dip. After cleaning, the parts must be undergo

a verification process to certify their cleanliness. Currently, this verification is still

performed with CFC 113 because of its previous history of reliable results.

The LOX injection ring is cleaned by clamping a gasket over the injection ring ports andfilling the ring and four sections of LOX piping with CFC 113. The solvent is drainedfrom the pipes and ring and purged with dry, oil-free GN2 and repeated twice more. On

the third fill and drain cycle, a sample of solvent is collected and analy_d for nonvolatileresidue (NVR) and particulates. If the sample passes the tests (<1 mg/ft and class 300particles), the LOX injection ring is considered clean and ready to run. The LOX pipes

are capped with polyethylene to prevent recontamination [1].

In spite of the GN2 purge, the pipe geometry is such that solvent collects in the low

points and cannot be completely removed without excessive time and purging. It isestimated that one to four gallons of solvent remain in the low points after cleaning and

during the beginning of a run. Since the ends of the pipes are covered, evaporation willnot remove the solvent. There are no low point drains due to concerns about introducinganother contamination path into the LOX system. Therefore, any solvent chosen to

replace CFC 113 for cleaning the LOX injection ring and pipes must be LOX compatibleand non-flammable.

4.0 NDE METHODS OF VERIFICATION

A new verification method of NDE, Optical Scanning for Electron Emissions (OSEE),

was investigated. Researchers developed this method to test flight hardware. The OSEEprobe emits a beam of ultraviolet light at either 185 or 254 nanometers and collects theelectrons emitted from the surface as the light strikes it. The results are dependent bothon the substrate and on the contaminant. Both must be known and the results compared

to previously generated curves to get an accurate answer. The developers alsorecommend using OSEE in an argon atmosphere for best results.

At the 8'HTr the contaminants that might be present on the surface of the pipes are not

completely known, so this method would be of minimal use. Also, it is a new technology

3

Page 10: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

and is still in the prototype stage. A compact instrument is needed, one that can be fed

into the LOX pipes, which have a 3 liT' inner diameter and complex geometry. For thismethod to work, a great deal of time and money must be spent to develop a smallprototype detector and to generate the needed curves. Therefore OSEE is not a viablecandidate for verification at the 8'HTT.

Another method of verification is carbon coulometry. In this method, the metal surfaceto be measured is placed inside a high temperature furnace where the carbon in thesurface contamination is converted to carbon dioxide and measured with an infrared (IR)detector. The main drawback to this method is the size of the test specimen, which mustbe less than 0.75 inches wide and four inches long. This method could be used withwitness plates but was deemed unsuitable for the 8'H'IT due to the size restrictions.

5.0 TOC METHOD OF VERIFICATION

Total Organic Carbon Analysis (TOC) measures thetotalcarbon concentrationin a water

sample. Itvaporizesa small (200 microliter)sample of water,convertingany carbon intocarbon dioxideand measuring itwith an IR detector.Experiments were conducted to

finda relationshipbetween partsper million(ppm) carbon from TOC and mg/ft2 of non-

volatileresidue(NVR) obtainedby the gravimetricmethods. Experimental procedureswere derivedfrom Kennedy Space Center'saqueous TOC testing[2].Three

contaminants were tested:Oster Oil and Cool Tool, both hydrocarbon oils,and SiliconDielectric,a silicongrease.

The testarticleswere stainlesssteelcoupons, two inchessquare. The TOC analyzerwasa Roscmount DC-190 from Dohrmann. A 27 kHz ultrasonictankfilledwith warm

deionizcd(DI)water was the finalcleaningstep.

The coupons were initially cleaned in CFC 113. A test solution was made from 100 mgof contaminant and 100 ml of CFC 113. The solution was shaken vigorously beforebeing applied to the coupons. The solution was applied to the coupons with a 500microliter pipette. Testing amounts were 0.5, 1.5, 2.5 and 5.0 ml of solution (or 1.5, 4.5,7.5 and 15 mg of contaminant). The coupons were dried for four hours in an oven at

80°C. They were placed in a clean pan filled with 500 _ters of warm DI water and

subjected to ultrasonication for five minutes. A sample was drawn from the pan, injectedinto the TOC and tested for the amount of carbon.

Figure 2 shows the results of a 10 ppm aqueous carbon standard tested at three different

temperatures and ultrasonicated for three different lengths of time. As the time increased,

so did the TOC reading, until it measured more carbon in the tank than was actuallythere. The TOC reading also increased as a function of temperature. Therefore, bothultrasonication time and temperature affect the measurement. Based on these results thetest water temperature was set to 50°C.

A solidcorrelationbetween TOC measurements of ppm carbon and the mg/ft2 of

contamination was sought. Ifa linearcorrelationwas found,the slope could bc used to

convertppm intothe standardtestmeasure ofmg/ft2.

4

Page 11: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

14

13

12

pp_carbon

11

10

9

Figur • 2:

I (

TOC vs TI me

I I

J

/

/ ;a

/J

(4 6 8 10

ull _n_cat ion t irne (rnin)

12

Two assumptions were made for this analysis:

•The total amount of carbon in a hydrocarbon or silicon contaminant averages 60

percent.•If the total surface area of articles to be tested is less than one squre foot, it is

assumed to be equivalent to 1 ft 2.

Initial testing showed the relation between TOC measurement and the contaminated testcoupons to be mostly linear, but the slope varied from 2.0 to 4.5.

The cut-off point for f_iling a part is 1 mg/ft 2, equivalent to three to four ppm carbon onthe TOC. The TOC lower detection limit is approximately one ppm, and the DI waterused for testing typically contains one ppm of carbon. Therefore the decision range forpass/fail verification is only 1-2 ppm above the noise level. Only 500 milliliters of waterwere used, just enough to cover the coupons. To completely cover large fittings, filters,and flex hoses more water must be added, which will decrease the overall concentrationof carbon in the ultrasonic tank. That will decrease the TOC measurement, possiblydown into the noise level and make accurate measurements impossible.

The TOC method has several problems that make it unacceptable as a verification tool:

• It is operator dependent.•It is unreliable.

•The level of contamination being measured is so low (1 mg/ft 2) that readings are

barely above the noise level of the TOC.•Less than 50 percent of the components that come in for cleaning can be verifiedwith the TOC due to restrictions on component size from the ultrasonic pan sizeand water volume.

Page 12: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

*k can take four or more hours for the TOC to reach a steady state after being shutoff for a weekend. It can take a week to reach steady state after being shut off fora month. Since LaRe's workload is infrequent, the TOC will not see continuous

operation. Therefore, a large percentage of time will be spent getting the TOCready for operation.

*It cannot be used for measuring cleanliness of the LOX injection ring due to thelarge amount of water that would be needed to flush the ring.

6.0 SOLVENT EFFICIENCY TEST

The objective of this test was to determine the cleaning power of the solvent without

major mechanical agitation. The majority of testing is to find a replacement for CFC 113used to cleaning the LOX injection ring. As such, the solvent must be a good cleaner forseveral contaminants (silicon, hydrocarbon, fluorocarbon), and it must do so withoutneeding mechanical agitation such as scrubbing or ultrasonics.

6.1 Test Solvents

Several solvents were tested for their ability to clean common contaminants found in the

8'HTr. The test solvents are listed in Table 2. They include hydrochlorofluorocarbons(HCFC) both neat and azeotroped, a hydrofluorocarbon (HFC), a perfluorocarbon (PFC),a halogenated hydrocarbon and water. Their properties are listed in Table 3.

Table 2: Test Solvents

HCFC 141b, neat

HCFC 141b, w/4% IPA

HCFC 225, neat b

HCFC 225, w/4% EtOH bHFC 43-10meePFC

Borothene

Deionized Water, 100 °C

Deionized Water, 25 °C

Genesolv 2000 aG-enesolv 2004AK 225

AK 225AE, S

Vertrel XFPF 5080

Borothene

DI Water

DI Water

a - Genesolv 2000 from Allied

1,1 dichloro- 1-fluoroethane

1,1 dichloro- 1-fluoroethane

Dichloropentafluoropropane

Dichloropentafluoropropane

DihydroperfluoropentaneC8F18

Halogenated hydrocarbon cH20

HzOSignal was the brand tested, but many companies sell

HCFC 14 lb under different trade names.

b - A mixture of 45 percent 3,3-dichloro-1,1,1,2,2-pentafluoropropane (HCFC 225ca) and55 percent 1,3-dichloro-1,1,2,2,3-pentafluoropropane (HCFC 225cb); the mixture isreferred to as HCF(2 225

c - Manufacturer's Proprietary Information

Page 13: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Table3: SolventProperties

ili' ii' iiiii',iiiiiiiM!iiii' iiiiiiCFC 113 48 I None 17.3Genesolv 2000 32 I None 19.3

Genesolv 2004 29 I None 18.5AK225 54 INone 16.2

AK225AES 52 INone 16.8

Vertrel XF 55 I None 14.1

PF5080 101 INone 15

Borothene 76 I None NDDI Water 100 I None 163.7

|

ND - Not Determined

NA - Not Applicable

.....................10oo11.5 500

10.2 400

ND 25 d

ND 25 d

4.4 2000.85 ND

ND 500.967 NA

_ _:i:;:_:__:"_:_!_::i_i

2 Yes

60 e Yes

0.55 Yes10 Yes

19.5 Yes

ND Yes

ND ND f

57.5 NDND Yes

a - Permissible Exposure Limitb - Non-Volatile Residue; baseline measurement of the solvent

c - LOX compatibilityd - Interim value; final value not established. Limit stated is for -ca isomere - Manufacturer believes our sample was contaminated. Normally <10 ppmf - Manufacturer states PF 5080 is LOX compatible, but test results have not been established

AK 225 is made up of 45% HCFC 225-ca isomer and 55% HCFC 225-cb isomer. The -ca isomerhas a PEL of 25 ppm, while the -cb isomer has a PEL of approximately 400 ppm. Since the twoisomers have different boiling points, the -ca isomer can be distilled away leaving the lesshazardous -cb isomer. However, that would effectively double the cost of the AK products. The

NVR test showed a high result for AK 225AES. The manufacturer, Asahi Glass of Japan,responded that their products should have an NVR limit of 10 ppm maximum. Borothene also hasa very high NVR that does not meet LaRC's unused solvent specifications. Borothene should

respond well to purification by distillation, but no testing has been done.

6.2 Test Contaminants

Twelve contaminants were chosen for the solvent efficiency test (Table 4). They

represent contaminants commonly found at 8'HTT and include hydrocarbon oils andgreases, a silicon grease and LOX compatible fluorinated greases. Even though the LOXcompatible greases do not have to be completely removed from the tunnel, they act astraps for hydrocarbons and particulates if they remain. Frequently, these fluorinatedgreases are the most difficult to remove and detect.

7

Page 14: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Table4: Test Contaminants

,_...-_._..-,-------_._w_.._._: ,:_.._.:_.:_,::. :_:_#...:_.:?.:___'.>.i:_Silicone Dielectric SiliconCimcoolOst_r Oil

MolydeeBlazer

Cool ToolTribolube 16

LubriplatcExtreme Pressure Lube

KrytoxFluorolubeTribol

Hydrocarbon

Hydrocarbon

Hydrocarbon

Hydrocarbon

HydrocarbonFluorocarbon

Hydrocarbon

HydrocarbonFluorocarbon

Fluorocarbon

Fluorocarbon

6.3 Contamination and Testing Procedure

The test articles were flat, stainless steel washers, 7/8" diameter. They were cleaned with

CFC 113 and oven dried at 80°F prior to testing. A cleanroom sponge applicator wasused to apply a thin layer of contaminant over 3/4 of the surface area. The washers were

dried, weighed, placed in a small aluminum weighing pan and covered with 5-10milliliters of solvent. The pan was gently agitated to simulate the conditions seen in thefill and drain cycle of the LOX injection ring. The washers were removed from the

solvent and again oven dried. They were re-weighed and the difference in weightconverted into percent contaminant removed.

7.0 MATERIAL COMPATIBILITY

Tests were conducted to determine what effects alternate solvents might have upon thematerials present in the 8'HIT. These tests include measuring changes in dimensions,changes in hardness, visual inspections and NVR of the test solvent.

7.1 Test Materials

Ten materials present in the 8'HTr were tested: four metals and six softgoods. Thematerials are listed in Table 5. One common material in the 8'HT/' that was not tested isMonel, both the K500 and the K400 series.

Table 5: Test Articles

Copper15-5 PH Stainless SteelMild Carbon SteelBrassTeflonViton

FluorogreenBuna-N

VespelKel-F

.__ii:.-........................................_"":ii_i_i...........MetalMetalMetalMetalElastomerElastomerElastomerElastomerElastomerElastomer

0.375" D x 2" L0.5"D x 2" L0.5" x 0.5 "x 2"0.5" x 0.5 "x 2"1" x .02" x 2.5"0.375" D x 2.5" L1.8" x 0.1" x 0.65"

0.375" D x 2.5"1" x 1" x 2.5"1.25" D

Page 15: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

7.2 Test Solvents

Four solvents were used in this test. They were chosen based on the results of the solvent

efficiency test. The solvents are HCFC 141b azeotroped with four percent methanol(Genesolv 2004), HCFC 225 neat and azeotroped with four percent ethanol (AK 225 andAK 225AES) and Borothene.

7.3 Test Procedure

Prior to testing, each material was stamped with an ID code, measured for dimensions,tested for hardness and visually inspected for any signs of abnormalities. Hardness tests

for metals were performed with the Wilson Rockwell Hardness Tester, bit B, except forthe 15-5 stainless steel, which was tested with bit C. Hardness tests for the softgoods

were performed with the Shore Durometer Hardness Type "A-2" and Type "D"instruments. Metal coupons were sandblasted to assure that all oxidized material wasremoved. The coupons were cleaned with CFC 113, dried and weighed.

Four series of tests were made, one per solvent. In each series, the coupons were placedin individual 60 milliliter bottles. Each bottle was filled with the series solvent until the

coupon was half submerged in the liquid. The Kel-F coupon was completely submergedin solvent due to its small size. The bottle was tightly capped and kept at room

temperature for 21 days.

The decision was made to run the tests at room temperature to avoid any problems

associated with storing solvent above its boiling point in a sealed container. Since thesolvent is normally in contact with the 8'HTr materials for a few hours at a time, and onrare occasions up to two days, 21 days was considered an adequate test period.

After 21 days, the coupons were removed from the solvent and allowed to dry at roomtemperature. Testing was conducted within three hours of removal from the solvent. Thecoupons were stored in a clean room for 24 hours, after which the tests were repeated tosee if any changes had occurred.

After the coupons were removed from the bottles, an NVR test was performed on thesolvent. The solvent was poured into a clean, dry aluminum weighing pan and boiled todryness. The residue left in the pan was weighed and recorded.

8.0 RESULTS

8.1 Solvent Efficiency Test

The results of the solvent efficiency test are listed in Table 6. This is a preliminary test

designed to point out three or four solvents suitable for further testing. Selection criteriawas simply to find the solvent with the most consistently high removal efficiency forseveral contaminants.

Of all the solvents, CFC 113 had the highest overall efficiency at 95 percent. AK 225and AK 225AES were nearly as good. Next were the G-enesolv 2000 and 2004 products

(HCFC 141b) with a respectable 80 percent average and Borothene at 78 percent. Thesesolvents, which all contain chlorine, did very well removing the hydrocarbon oils and

greases.

Page 16: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

J

!

_m

m

lO

me

el

Ih¢,wii

5

)

! ,.,11

o

i

_5._,4.

{:i a

Page 17: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

The purely fluorinated solvents, PF 5080 and Verlrel XF did poody on all contaminantsexcept the fluorinated greases (Krytox and Fluorolube). This is a good example of like

dissolving like.

As expected, water performed very poorly with hot water being marginally more

effective than room temperature water.

8.2 Material Compatibility Tests: Metals

None of the metals were significantly affected by any of the solvents except for the mildcarbon steel. It rusted heavily while immersed in Borothene. Other solvents caused

some staining, but no rusting.

Copper:

Table 7 shows the results from the copper tests. There were no significant negativeimpacts from any of the solvents tested. Genesolv 2004 did produce some slight stainingand discoloration on the coupons, but no rust was apparent.

Table 7" Co er Corn atibility Tests

iiiiiiiii',iiiiilUiiiiliiii!iiiiiiiiWiiiifilliiii!ili!iliiiiiiiiiiiliiiliiiiili_____iii!i!iii_iiiiii'i__ililiii_ili____iii_iiii_Genesolv 2004 I

Test 1 a

Test 2 b

Test 3 c

AK 225Test 1Test 2Test 3

AK 225AESTest 1Test 2Test 3

BorotheneTest 1Test 2Test 3

58.45947

NC d,e

NC e

59.06163NCNC

59.63432NCNC

58.93778NCNC

No

Yes f

Yes f

No

NoNo

No

NoNo

No

NoNo

42

45

46

44.546.546

464545

45.54546

iiiiiiiiii!iiiiiiiiiiiii_ii_ii_iiii!iiiiiiili!_iiiii_ii!ii_iiiiiii!i!i

<1

<1

<1<1

<1<1

<1<1

NC - No Change.a - Original test series.b - Test series repeated after 21 day immersion.c - Test series repeated 24 hours after removal from solvent.d - Changes less than 1 mg are not reported.e - Numbers for Test 2 and Test 3 represent the delta from the original value in Test 1.

f- Staining and discoloration were seen on the half immersed in the solvent, but nocorrosion.

g - Tested using the Rockwell B hardness bit.

11

Page 18: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

15-5 Stainless Steel:

Table 8 fists the results of the compatibility tests for 15-5 Stainless Steel. No adverseeffects appeared in any of the tests.

Table 8:15-5 Stainless Steel Compa'

....::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::Genesolv 2004

AK 225

Test 1Test 2

Test 3

Test 1Test 2Test 3

AK 225AESTest 1Test 2Test 3

BorotheneTest 1Test 2Test 3

NC - No Change.

52.47202

Nca, bNC

53.14119NC

NC

52.83139NCNC

51.83476NCNC

bilit Testsi_.::': ..... : : ...... :._%__'.". .-._.°_,:_E;:i

NoNo

No

No

NoNo

No

NoNo

No

NoNo

':' _ "._'.:_'.:

_:_:_::i:::::+....... _:i.._:_:._.'..'_:

3231

33

323233

30.53132

313233

<1

<1

<1<1

<1<1

<1<1

a - Changes less than 1 mg are not reported.b - Numbers for Test 2 and Test 3 represent the delta from the original value in Test 1.c - Tested using the Rockwell C hardness bit.

12

Page 19: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Mild Carbon Steel:

Table 9 lists the compatibility results for mild carbon steel.

caused by Borothene. It caused the steel to rust heavily.

Table 9: Mild Carbon Steel Compati

Genesolv 2004Test 1Test 2

Test 3

AK 225Test 1Test 2Test 3

AK 225AESTest 1Test 2Test 3

BorotheneTest 1Test 2

Test 3

38.18680

NC a,b

NC

37.82920NCNC

37.90452NCNC

37.905510.006

0.005

_ili_ Tests

ii !iiiiii!iii@!li! iii

NoNo

No

No

NoNo

No

No

No

No

Yes d

Yes d

The only adverse effect was

8290

93

808990

86

8992

82.590

92

iiii!i i!iiiiiiiiiiiiiiiiiiiiiiiii!iii!i!iiiii!iii!iii!iiiiiililililili

<1

<1

<1<1

<1<1

<1

<1

NC - No Change.a - Changes less than 1 mg are not reported.b - Numbers for Test 2 and Test 3 represent the delta from the original value in Test 1.

c - Tested using the Rockwell B hardness bit.d - Heavy rust was present on the submerged half. Rust spots were visible on the top half

of the coupon, which was exposed to the vapors.

13

Page 20: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Brass:

Brass, like the other metals, showed little sign of negative impacts. Bomthene causedsome staining on the coupon, but no rust. The results are listed in Table 10.

Table 10: Brass

: _._:_: :_:?q:: _:_ >.':_: ?:_ :_ _: .):_:::: :_: :.'_?...y:.::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::

Genesolv 2004Test 1Test 2

Test 3

AK 225

Test 1Test 2Test 3

AK 225AESTest 1Test 2Test 3

BorotheneTest 1Test 2

Test 3

Compatibility Tests

71.75291

Nca, b

NC

71.29208NCNC

71.21857NCNC

.. : _:_._::_:_:_

NoNo

No

No

NoNo

No

No

No

8290

93

8O899O

868992

6.).'.-: :-_ :. ..?_. _ :?_::':?..__g_ :@_ _:........ _{_}_.:.:.:.: :._.......................

<1

<1

<1<1

<1<1

71.73793 No 82.5

NC Yes d 90 < 1

NC Yes d 92 < 1i

NC - No Change.a - Changes less than 1 mg are not reported.b - Numbers for Test 2 and Test 3 represent the delta from the original value in Test 1.c - Tested using the Rockwell B hardness bit.

d - Slight staining was present, but no corrosion.

14

Page 21: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

8.3 Material Compatibility Test: Elastomers

Many of the elastomers absorbed the solvents during the 21 day immersion test causingweight gain and swelling. However, most of the elastomers released the solvents duringthe 24 hour drying period after removal from the solvent. Viton and Buna-N showedextreme incompatibility to all four solvents tested.

Teflon:

The Teflon experienced some slight weight gain, especially from the AK 225 products.However, after 24 hours of drying the weight of the coupons was decreasing back to the

original value. Test results are shown in Table 11.

Table 11: Teflon

iiiiiiii } i i iiiiiiii } ! i iiiii!iii ii iiiii i iiii!i iiiii iiiiiiiiii

Test 1Test 2

Test 3

AK 225Test 1Test 2Test 3

[AK 225AESTest 1Test 2Test 3

BorotheneTest 1Test 2

Test 3

Compatibili_ Tests

1.81413

0.003 a0.001

1.801630.0270.022

1.819380.0230.019

1.79079

NC b-0.003

No

No

No

No

NoNo

No

NoNo

No

No

No

iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!iiiiiiiiiiiiiiiiiiii

9390

91

949093

929193

9390

94

!iiiiiiiiii}iiiiiiiii}ii}ii}}}}i}}ilililil}iii!}}i!!ii',i

<1

<1

<1<1

<1<1

<1

<1

NC - No Change.a - Numbers for Test 2 and Test 3 represent the delta from the original value in Test 1.

b - Changes less than 1 mg are not reported.c - Tested using the Shore Durometer Hardness Type "A-2" and Type "D."

15

Page 22: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Viton:

Viton experienced severe compatibility problems with all four solvents. Each coupongained a large amount of weight, 10 to 45 percent of the original weight. The weight wasdecreasing even 24 hours after removal from the solvent. They also had a considerableamount of swelling. However, little change in the hardness of the coupons was seen. Ifcontact between Viton components and the alternate solvent can be limited and the

component dried thoroughly afterwards, many of these problems can be avoided. Testresults are listed in Table 12.

Table 12: Viton Com_atibili_ Tests_'.:.".'l_'_'_i!_;.'_!_i_'_;J_:_'_:,_ _."_': " _ : _" ." ._.': _ i_'>;iiiiliiiitlil!i!iiiiiiiii l i!t}il

Test 1Test 2

Test 3

AK 225Test 1Test 2

Test 3

AK 225AESTest 1Test 2

Test 3

BorotheneTest 1Test 2Test 3

4.64764

1.991 a, b

1.001 a

4.71314

2.087 a

1.368 a

4.65443

2.25 a

1.557 a

4.661730.3700.776

:__t__i_t_ .................................: ................._;1_....:_i:.... _!r..!:_!{_i:..5"_,_:,,'_:,_

NoNo

No

No

No

No

No

No

No

No

NoNo

7875

75

7575

75

77

75

79

777980

13.4

7.9

10.2

6.2

14.9

11.6

1.91.6

a - Weight of the coupon was decreasing while being weighed.b Numbers for Test 2 and Test 3 represent the delta from the original value in Test 1.c - Tested using the Shore Durometer Hardness Type "A-2" and Type "D."

16

Page 23: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Fluorogreen:

Huorogreen did well in the compatibility tests. It did gain some weight during theimmersion tests, with the coupons in the AK 225 products gaining the most weight.However, the weights decreased after drying at room temperature for 24 hours. Thelinear swelling was slight and no changes in hardness were detected. Results are listed inTable 13.

Table 13: Huoro reenCom Tests

i!iii!iiilllliii!!i!iiiiiiiiiiiiiiiii!!!!!!i iiiiiiliiiiiiiiiiGenesolv 2004

Test 1Test 2

Test 3

AK 225Test 1Test 2Test 3

AK 225AESTest 1Test 2Test 3

BorotheneTest 1Test 2Test 3

3.3739

0.057 a0.0316

3.48714

0.1220.067

3.394280.1120.064

3.557230.0160.004

a - Numbers for Test 2 and Test 3 re

No

No

No

No

NoNo

No

No

No

No

NoNo

iiii!iiiliiiiiiiiiiii!!!i!iT!iiii

9593

94

95

9393

959393

949594

iiii!iii!i itiiiiii!iii!i!ii!!iii!iii!ii

0.8

0.6

0.50.5

1.41.3

<1<1

_resent the delta from the original value in Test 1.

b - Tested using the Shore Durometer Hardness Type "A-2" and Type "D."

17

Page 24: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

B_-N:

The Buna-N components exhibited a severe incompatibility with all solvents. There was

a significant weight gain in all coupons; in many cases, the amount gained exceeded theoriginal weight. All of the coupons had lost weight by the following day, but whetherthey would return to their original weight is unknown. However, the linear swelling thatoccurred was significant and after 24 hours still had not approached the original value.All of the samples experienced a loss of hardness, probably as a result of absorbing largeamounts of solvent and partially dissolving, as indicated by the NVR tests. Table 14 liststhe test results.

Table 14: Buna-N Compatibili_ Tests

iiiiiiiiii'i ' illi!jik.-.. i:li. lil..............IL.].? .....................•.....-.:......_z.......:_._..:c.:-..:-....:.:...:.,-_,..×_...._:-....:...:.:.,._,_-k:.:.:.:.:.i.:._:.;.ff_.:.;.:_.:.:.:.:.:.:-:_,':_._:._;._:.:::_._:::::::::::::::::::::::::

Genesolv 2004Test 1Test 2

Test 3

AK 225Test 1Test 2

Test 3

AK 225AESTest 1Test 2

Test 3

Borothene

Test I

Test 2

Test 3

5.85041

6.65 a, b

1.883 a

5.85278

7.1 a

3.941 a

5.90026

8.1 a

3.936 a

5.84914

7.2 a

1.633 a

No

No

No

No

No

No

No

No

No

No

No

No

',:';';';';';':.f':.i:i_i::':':::_i:_:.:_I._:;..:;":':.:_::.i.i£i

7672

71

7973

71

7774

71

80

70

73

il!Iill!i!ii !I!!li .,#iii!ll

16.3

7.2

19.7

12.3

21.9

11.7

15.7

11.9

a - Weight of the coupon was decreasing while being weighed.b - Numbers for Test 2 and Test 3 represent the delta from the original value in Test 1.

c - Tested using the Shore Durometer Hardness Type "A-2" and Type "D."

18

Page 25: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Vespel:

Vespel is stable with respect to these solvents. The coupons experienced a slight weightgain, especially with Borothene. Unlike previous materials, the weight gain with Vespel

appears to be permanent. No other adverse effects were noted. Results are listed inTable 15.

Table 15": Vesp.el

Genesolv 2004Test 1Test 2

Test 3

AK 225Test 1Test 2Test 3

AK 225AESTest 1Test 2Test 3

BorotheneTest 1Test 2Test 3

Compatibili_ Tests .........................................i .....................

iiiiiiiiiii@ ii!iiiiii!i{ ,!i!!iiiiiiii' ii },i!!!!ii!i!{i!i

54.44768

0.028 a0.026

53.044030.0020.004

52.424090.0010.003

51.529130.4560.376

No

No

No

No

NoNo

No

No

No

No

NoNo

ii!!iiiiiiii_i_i{}iiiiiiiiiiiiiiiiiii!iiii}iiiii}!

8282

82

858584

848484

818181

ii iiiiiii{i{iiiiili!i{iiiiiiiiiiiiiiiiiiii!{ii{ii!i{

<1

<1

<1<1

<1<1

<1<1

a - Numbers for Test 2 and Test 3 represent the delta from the original value in Test 1.

b - Tested using the Shore Durometer Hardness Type "A-2" and Type "D."

KebF:

Due to a shortage of available material to test, Kel-F was only tested with two solvents.Some linear swelling and weight gain was noticed. After 24 hours, the material had not

recovered as quickly as other elastomers.

Table 16: Kel-F Compatibility Tests

_:iiiiiiiii!iiiiiiiiiiiiiiiiiiiiiii!i!iiil iii i _ ii iiii iGenesolv 2004

Test 1Test 2

Test 3

AK 225Test 1Test 2Test 3

1.17672

0.067 a0.058

1.146330._0._7

NoNo

No

No

No

No

9695

95

959595

2.4

2.2

2.02.0

a - Numbers for Test 2 and Test 3 represent the delta from the original value in Test 1.

b - Tested using the Shore Durometer Hardness Type "A-2" and Type "D."

19

Page 26: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

8.3 Material Compatibility Test: NVR

Table 17 compares the metal NVR results from the 21 day immersion test to the NVR

results of clean, unused solvent. The reference line defines the cleanliness of the originalsolvent. I_aRC specifications call for new solvent to have an NVR less than 10 ppm. TheGenesolv 2004 product is extremely clean. The AK products are marginally acceptable,and the Borothene product is too contaminated to use out of the drum without extensivepurification first.

The test determines the effect of solvents on the test materials. If they are incompatible,the solvent will react adversely to the materials and increase the NVR, either throughmetal removal in the form of rust or solubilizing the polymeric materials. The solventwas not filtered before being boiled off, so the weight of any particulates is included.

The Genesolv had a mild effect upon the metals, producing 2-13 ppm NVR. TheBorothene had similar results, adding 4-5 ppm to the baseline. The AK 225 and AK

225AES had results that were less than the baseline readings. One possible explanationis that the contaminant in the original solvent settles out on the metal coupons, thuscausing them to become more contaminated than before cleaning.

Table 17: Metals NVR Results

_:_...:.:::::_:?.@.._:::_:_:._:_i:_:?::._:_..:._:._.;':_._:_6.'._:_.:.':.:_: :.:_:.:_ v:: :::,¢_:_v..¥_'_ _:._ f_.:_:_.v:_.,x_.::-_..: .._:_.:_.:

;::_:_:_:._::::::::::::::_:.._.+¢.:_._x_.'2._'._.'.::_:._:..._:`_::f+._.._.4:.:!:_:;:;:_:;:":::;:!_:!?:;_!_;_:_$':_?_!_'%_;:'._:;'_::_:::_::_ _:?'.':!:_.::_:i

Reference a

Copper15.5 Stainless SteelBrassCarbon Steel

a - Baseline NVR.

::_iI_i:..........v""+"" "'" • " i.-'_:_

_...'v.:-:i::!:,.:'2v.:_._'6:_:!:!:..'_:_:::::

0.55

2.56.913.626

__i'-Y_:_.... "i:.......... ._:_.'_._

10.0

5.47.58.08.4

___": ._' " _ 4' ':: .. _.:::::::::I..:.. . _.:.::.: ._'. :$ _: _::.::_

19.5

9.44.916.625.3

57.5 ...........

61.661.862.6110.9

Table 18 lists the NVR measurements of the elastomers after the 21 day immersion test.Again, all elastomer results are compared to the solvents' baseline NVR. The results heredo not indicate undesirable solvents as much as they indicate undesirable materials. BothViton and Buna-N show extremely large NVRs after the 21 day immersion test. Thisdata, coupled with their large weight gains, swelling, and softening for the Buna-N,indicate a severe negative impact by all solvents upon these materials.

In theory the solvents are absorbed by the elastomer and slowly dissolve it. The Viton orBuna-N materials in the 8'HTT can trap the replacement solvent and over the course of

many days, slowly release vapors back into the tunnel and LOX injection ring. Eventhough all four solvents are non-flammable, this is a problem to avoid if possible.

For components, the Viton would be removed before cleaning. For the LOX injectionring, where softgoods such as gaskets and o-rings cannot be removed, the Viton wouldhave to be replaced with a more resistant elastomer.

20

Page 27: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Table 18:

iiiiiiiiiiiiii!liiiiiiiiiliiiiiiReference aTeflonViton

FluorogreenBuna-N

Vespel

Elastomers NVR Results

i! iii!ii!iilii !!ii!iiiiiiii!0.55

1.9790.806515.52.5

10.0

3.9372.55.03853.316.8

19.5

18.8497.57.74865.320

a - Baseline NVR.

57.5

76177.239.62790.859.6

9.0 HEALTH AND ENVIRONMENTAL EFFECTS

9.1 Health Effects

Many of the solvents have much lower Permissible Exposure Limits (PELs) than CFC113 (Table 3). This could cause problems with personnel working with the solventswhile cleaning the LOX injection ring.

A great deal of care is taken that vapors from the cleaning solvent are contained. Thesolvent is pumped from a clean barrel into the pipes and drained into a waste barrel at theother end. The only vapors come from the open bung of the barrels.

However, since some of the solvent stays in the low points of the pipes, it is possible for

vapors to be present in the working environment around the LOX injection ring. Thepipe ends are covered with polyethylene, but the fit is not always perfect. Some of thesolvents, such as HCFC 225ca and Borothene have PELs low enough to force personnelto wear supplied air respirators while working closely with the solvent. In addition, theycould release vapors that could adversely affect personnel nearby.

One possible solution is improving the facility by adding filtered ventilation systems tomove more air through the work area.

None of the solvents pose a severe health hazard regarding skin contact. Personnelshould use appropriate protective measures while working with the solvent, such as

goggles, suitable gloves, and protective coats or aprons.

9.2 Environmental Effects

Any solvent chosen to replace CFC 113 must be acceptable to the EnvironmentalProtection Agency (EPA). They define the regulations and restrictions governing the useof solvents commonly used in precision cleaning. CFC 113 is considered a Class ISubstance under the Clean Air Act. HCFC 141b and HCFC 225 are considered Class IISubstances. As such they are scheduled to be phased out of production by 2030, howeverHCFC 141b has an accelerated phase out schedule. It is due for phase out in 2003.

HCFC 141b has been defined by the EPA as "unacceptable" as a replacement for CFC

113 in cleaning applications with the following exceptions. The EPA has granted awaiver of continued use for one year (until 1997) to help industry move to an acceptablesolvent. However, this only applies to companies who have been using HCFC 141b priorto this.

In addition, HCFC 141b is still an Ozone Depleting Substance (ODS). It has an ozone

depleting potential (ODP) of 0.1 compared to CFC 113's ODP of 0.8 (Table 13).

21

Page 28: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

Another environmental hazard associated with these solvents is the Global WarmingPotential (GWP). This is caused by solvent vapors trapping heat in the earth's

atmosphere and creating a global greenhouse effect. PF 5080 is a strong greenhouse gas(Table 19).

Table 19: Environmental Effects of Test Solvents

HCFC 141bHCFC 225HFC 43-10meePF 5080Borothene

E:__i::_._:.:

Ik.p. _..I

0.110.0300ND

1.350.14

ND0.258.0ND

ND - Not Determined

a - Ozone Depleting Potentialb - Global Warming Potential

Finally, water has some environmental hazards associated with using it as a cleaner andverification agent. The restrictions on releasing wastewater into the nation's sewersystems are growing fighter. New regulations might force LaRC to pre-treat anywastewater before sending it to the wastewater treatment plant.

10.0 FINANCIAL CONSIDERATIONS

The cost of CFC 113 is $22 per pound or $286 per gallon (August 1995). As time goesby, the decreasing supply of CFC 113 and the increasing government taxes on it will

drive the price higher. The actual production cost of CFC 113 is less than $2 per pound.

The loss of one to four gallons of solvent every time the LOX injection ring is cleanedpresents another problem for the 8'HTr. That is the amount of solvent estimated to be

trapped in the low points after cleaning and purging the pipes. When the tunnel startsrunning, the trapped solvent is evaporated into the oxygen and exhausted into theatmosphere. That amount of solvent is lost forever and cannot be replaced, yet anotherreason to find an alternate solvent to replace CFC 113.

Many of the alternatives are as costly as CFC 113, but they will be available for manyyears. The costs of these alternatives are listed in Table 20.

Table 20:

CFC 113

HCFC 141bHCFC 225PF 5080HFC 43-10meeBorotheneDI Water

a - Cost as of Au_

Cost of Alternative Solvents a

:!:!:_._. _..:::_;,.'"."":':...... :"¢'_;":"? _?,_..:: "";:i'i_::_:_:_:_:__t_!_!i:il_'"":_:' """"..... :"'""";'":':':':':':';_q'".......:" " ""*...........":":::::

.............22:® o........ I14.00 183 I13.25 185 [

1 oo I2.50

0.12 1.00 |tst 1995.

In addition, the supply of CFC 113 available to the 8'I-r IT is finite. If all the optionshave not been investigated and a safe and suitable alternative chosen, the change will bemade in ignorance. That opens a Pandora's box of problems relating to safety, cleaningability, material compatibility, health issues, cost and more.

22

Page 29: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

A final cost consideration is any facility modifications that will have to be made as aresult of changing to an alternate solvent. Such modifications might include installing anew, filtered ventilation system to increase the air circulation or safety precautions such

as eye wash stations and safety showers.

11.0 CONCLUSIONS

The need to find a suitable alternate for CFC 113 is pressing. Alternatives exist, but

many of them are unsuited to the extreme conditions of the 8'H'IT. No NDE methodshave been found that would work in the 8'HTI" verification processes. The TOC methodhas been investigated, but it is too troublesome and ineffective to solve the problem. The

last approach has been to search for an alternative solvent, which would require only afew modifications to the cleaning process and minor equipment changes. This seems thebest choice for 8'HTT cleaning operations.

Regarding the cleaning ability of the solvents, HCFC 141b and HCFC 225 were the mosteffective. They functioned nearly as well as CFC 113. However, HCFC 225 has a lowPEL that would pose significant health problems for workers.

HCFC 225 shows the best overall material compatibility followed by HCFC 141b.Borothene is unacceptable due to the high corrosion effects it has on carbon steel. Vitonand Buna-N were adversely affected by all the solvents tested, indicating a need to keepthese materials out of contact with the selected solvent or replace these tunnel

components with a more resistant material. All the solvents tested have some type ofnegative impact on one or more of the materials. Further investigation must beconducted on material compatibility if an alternate solvent is chosen.

HCFC 141b is the best choice concerning health effects on personnel since it has a very

high PEL. However, it is in disfavor with the EPA due to its ODP and Class II Substancedesignation. Even ff used as a stopgap measure, research into alternatives must continueand a switch must be made as soon as a suitable one is found.

11.1 Future Plans

The issue is far from resolved. New products continue to come onto the market. DuPontand Allied Signal have formed a partnership to develop a new product: ahydrofluoroether (HFE), available for testing and commercial applications sometime in1996. It is expected to have a cost similar to CFC 113. Much remains unknown aboutthe product, including its cleaning ability, health effects and LOX and materialcompatibility, but many industry experts have expressed high hopes concerning its use inLOX applications.

Another product available for testing is Navy Oxygen Cleaner (NOC). It is currentlybeing tested by the NAVSEA and NAVAIR departments of the Navy [3]. It is a semi-aqueous cleaner that works by mechanically removing contamination from the surfacerather than dissolving it like solvents. Navy testing indicates very favorable _sults forcomponent cleaning and line flushing. They are in the process of converting meirNAVAIR cleaning operations to NOC procedures.

Much of the work discussed in this paper is based on the current cleaning procedures at

8'H'IT. Those procedures were established many years ago when CFC 113 wasinexpensive and plentiful, and ensuring a safe operation was the most important item.Now that costs of cleaning solvents are much higher than before, the cleaning proceduresneed to be re-evaluated. The question of "how clean is clean" should be asked. The fill

23

Page 30: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

and drain cycle for cleaning the LOX injection ring has been used successfully for manyyears, but perhaps a more effective method exists. These new methods might require alonger downtime or more work for personnel, but they might make a less effective

cleaner work as well as CFC 113. Several industry experts are reporting that the cleaning"process" is just as important as the solvent used and that even aqueous cleaning can besuitable if the correct process be determined for the task.

11.2 Recommendations

There was no one clear choice for replacing CFC 113 in the LOX injection ring cleaningand verification work. The best choice, HCFC 141b, is disallowed by the EPA. Thesecond best cleaner, HCFC 225, is too toxic to use safely without major modifications tothe facility and to the cleaning operations.

The 8'HTr has a reserve of CFC 113 that will last for years ff used only to clean theLOX injection ring. That is the one area where cleaning requirements are the moststringent and safety is extremely important due to the trapped solvent in the tunnel. An

alternate solvent cannot be recommend for the LOX injection ring at this time. If a futuresolvent proves to be acceptable, umuel operations can immediately move to use it. In themeantime, research must continue into new solvents, and more importantly, into newcleaning procedures and facility modifications should a toxic solvent be chosen.

Component cleaning requirements for LOX compatibility and non-flammability can berelaxed slightly because the components can be thoroughly dried prior to use in the8'HTr. Investigation into alternate cleaning products and processes is ongoing. Some

new cleaners, such as NOC, provide their own verification process. For reasons relatingto performance and safety, LaRC will concentrate on aqueous-based component cleaning.For component verification, CFC 113 will be used sparingly until an alternate verificationsolvent or method is approved by the Center.

24

Page 31: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

ACKNOWLEDGMENTS

Theauthorwouldlike to acknowledge the contributions of the following

individuals:

Barbara Pfitchard for her work with the TOC research.

Meg Moore for her work with the solvent efficiency tests.Edward Martincz for his work with the material compatibility research.

25

Page 32: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

REFERENCES

1. Procedures for Cleaning of Systems and Equipment for Oxygen Service. NASA LHB1740.5, March 1994.

2. Allen, Gale J. and Fishell, Kenneth A.: Aqueous Cleaning and Verification Processes

for Precision Cleaning of Small Parts. Aerospace Environmental TechnologyConference, August 10-11, 1994, pp. 411-419.

3. Antin, Neil. NAVSEA Report on: Aqueous Oxygen Cleaning Products andProcesses. Naval Sea Systems Command, March 1994.

26

Page 33: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid
Page 34: Evaluation of Alternatives for Trichlorotrifluoroethane (CFC-113) … · 2013-08-30 · Evaluation of Alternatives for Trichlorotrifluoroethane (CFC 113) to Clean and Verify Liquid

REPORT DOCUMENTATION PAGE I Form ApprovedOMB No. 0704.0188

Pub. li¢ _ .b_'_m. for INe _ d i_'omm_ _ ulimetod to average 1 hour I_W..rp?pcwum., im_ding the time for _ m, mrohing mm_mg data soumel,

ga_w_ngan9 maw_nn 9tip ._t= naed=4, andOOml_ .up¢lmvimdngthe ooll_tlonol inf_mlwix_.Seedc=mmemlregs_ng th= burdenedrrmo o¢_y ofhor upact d this.e_lectlo_ Of informatmn, mcluomg iluggelmono for reduol_i Ihie burden, to Wlwll/_ Heed_ Slmtlcee, _omta for Inf_ Opemtlorm snd Reports, 1215 Jefferlon Devil

H_hwuy, Suite 1204, Arlington, VA 22202-4302, and !o the (]lice of Man_lement lind Budget, Ptpen, eork Reduction Pro_ (0704-0188), Washington, DC 2050_.

1. AGENCY USE ONLY (Leave bMnk) 12. REPORT DATE 3. REPORT TYPE AND DATES COVEREDI

I September 1996 Technical Memorandum4. TITLE AND ,SUBTITLE 5. FUNDING NUMBERS

EvaluaUon of Altematives for Tdchlomrtrifluoroethane 505-90-82-01

(CFC-113) to Clean and Verify liquid Oxygen Systems

6. AUTHOR(S)

Michelle L Morris

7. PERFORMINGORGANIZATIONNAME(S)ANDADORESS(ES)

NASA Langley Research CenterHampton, VA 23681

9. SPONSORING I MONITORING AGENCY NAME(S) AND ADDRESS(ES)

National Aeronautics and Space AdministrationWashington, D.C. 20546-0001

8. PERFORMING ORGANIZATIONREPORT NUMBER

10. 8PONSOFIING I MONITORINGAGENCY REPORT NUMBER

NASA TM-110275

11. SUPPLEMENTARY NOTES

12s. DISTRIBUTION I AVAILABILITY STATEMENT

Unclassified - Unlimited

Subject Category 23

12b. DISTRIBUTION CODE

13. ABSTRACT (Maxkmm_ 200 words)

NASA Langley Research Canter (LaRC) investigated saveral alternatives to the use of tnchlorotrifluoroethane

(CFC,-113) in oxygen cleaning and verification. Alternatives invesUgated include several replacement solvents,Non-Destructive Evaluation (NDE) and Total Organic Carbon (TOC) analysis. Among the solvents, 1,1-dichloro-l-fluoroethane (HCFC 141b) and dichloropentafluoropropane (HCFC 225) are the most suitablealternatives for cleaning and verification. However, usa of HCFC 141b is restricted, HCFC 225 introducestoxicity hazards, and the NDE and TOC methods of verification are not suitable for processes at LaRC.Therefore, the interim recommendation is to sparingly use CFC-113 for the very difficult cleaning tasks where

safety is cdUcal and to use HCFC 225 to dean components in a controlled laboratory environment. Meanwhile,evaluation must continue on new solvents and procedures to find one suited to LaRC's oxygen cleaning needs.

14. SUBJECT TERMS

Tdchlorotrifluoroethane, CFC-113Solvents, Oxygen Cleaning, Verification

17. SECURITY CLASSIFICATIONOF REPORT

Unclassified

18. SECURITY CLASSIFICATIONOF THIS PAGE

Unclassified

NSN 7540-01-280-5500

lg. SECURITY CLASSIFICATIONOF ABSTRACT

Unclassified

18. NUMBER OF PAGES

31

16. PRICE CODE

A03

20, UMITATION OF ABSTRACT

Unlimited

81anchu-d Fown 2N (Rev. 2-89)Pm_rbed byANSIStd. Z3_18298-102