Technical Data 1756 ControlLogix Communication Modules Specifications Standard ControlLogix Catalog Numbers 1756-EN2F, 1756-EN2T, 1756-EN2TR, 1756-EN3TR, 1756-ENBT, 1756-EWEB, 1756-CN2, 1756-CN2R, 1756-CNB, 1756-CNBR, 1756-DNB, 1756-DHRIO, 1756-RIO, 1756-DH485, 1756-SYNCH ControlLogix-XT Catalog Numbers 1756-EN2TXT, 1756-CN2RXT, 1756-DHRIOXT Linking Device Catalog Numbers 1757-FFLD2, 1757-FFLD4, 1757-FFLDC2, 1757-FFLDC4 Separate communication-interface modules are available for different networks. Install multiple communication-interface modules into the ControlLogix backplane to configure a gateway to bridge or route control and information data between different networks. You do not need a ControlLogix controller in the chassis. Topic Page Available Communication Modules 3 EtherNet/IP Network 4 Stratix Switches 10 ControlNet Network 12 DeviceNet Network 18 DH+ and Remote I/O Networks 21 FOUNDATION Fieldbus Network 26 DH-485 Network 29 SynchLink Communication 32

Transcript of Especificacion Tecnica Tarjeta de Comunicacion

Page 1: Especificacion Tecnica Tarjeta de Comunicacion

Technical Data

1756 ControlLogix Communication Modules Specifications

Standard ControlLogix Catalog Numbers1756-EN2F, 1756-EN2T, 1756-EN2TR, 1756-EN3TR, 1756-ENBT, 1756-EWEB, 1756-CN2, 1756-CN2R, 1756-CNB, 1756-CNBR, 1756-DNB, 1756-DHRIO, 1756-RIO, 1756-DH485, 1756-SYNCH

ControlLogix-XT Catalog Numbers1756-EN2TXT, 1756-CN2RXT, 1756-DHRIOXT

Linking Device Catalog Numbers1757-FFLD2, 1757-FFLD4, 1757-FFLDC2, 1757-FFLDC4

Separate communication-interface modules are available for different networks. Install multiple communication-interface modules into the ControlLogix backplane to configure a gateway to bridge or route control and information data between different networks. You do not need a ControlLogix controller in the chassis.

Topic Page

Available Communication Modules 3

EtherNet/IP Network 4

Stratix Switches 10

ControlNet Network 12

DeviceNet Network 18

DH+ and Remote I/O Networks 21

FOUNDATION Fieldbus Network 26

DH-485 Network 29

SynchLink Communication 32

Page 2: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Important User InformationSolid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

Rockwell Automation, Rockwell Software, Allen-Bradley, Tech-Connect, ControlLogix, ControlLogix-XT, Data Highway Plus, DH+, KwikLink, Logix5000, PLC-5, PanelView Plus, SLC, Stratix 8300, Stratix 8000, Stratix 6000, Stratix 2000, RSLogix 5000, RSLinx, NetLinx, and SynchLink are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

2 Publication 1756-TD003C-EN-E - December 2010

Page 3: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Available Communication Modules

Network Catalog Number Description Page

EtherNet/IP 1756-EN2F EtherNet/IP bridge, fiber, 256 Logix connections 4

1756-EN2T EtherNet/IP bridge, copper, 256 Logix connections 4

1756-EN2TR EtherNet/IP bridge, embedded switch, copperSupports as many as 8 axis of motion

4

1756-EN3TR EtherNet/IP bridge, embedded switch, copperSupports as many as 255 axis of motion

4

1756-ENBT EtherNet/IP bridge, copper, 128 Logix connections 4

1756-EWEB Ethernet web server, 128 Logix connections 4

1756-EN2TXT ControlLogix-XT, EtherNet/IP bridge, copper, 256 Logix connections

7

ControlNet 1756-CN2/B, 1756-CN2R/B

ControlNet bridge, 128 Logix connections(1) 12

1756-CNB, 1756-CNBR

ControlNet bridge, 64 connections; recommend using only 40...48 Logix connections for I/O

12

1756-CN2RXT ControlLogix-XT, ControlNet bridge, 128 Logix connections(1) 15

DeviceNet 1756-DNB DeviceNet bridge 18

Data Highway Plus 1756-DHRIO Data Highway Plus/Remote I/O module 21

1756-DHRIOXT ControlLogix-XT, Data Highway Plus/Remote I/O module 24

Remote I/O 1756-DHRIO Data Highway Plus/Remote I/O module 21

1756-RIO/B Remote I/O module 21

1756-DHRIOXT ControlLogix-XT, Data Highway Plus/Remote I/O module 24

Foundation Fieldbus 1757FFLD2, 1757-FFLD4

Foundation Fieldbus linking device bridges from an Ethernet network to either two or four H1 ports

26

1757-FFLDC2, 1757-FFLDC4

Foundation Fieldbus linking device bridges from a ControlNet network to either two or four H1 ports

26

Serial 1756-DH485 Compatible with RS-232 serial communication, supports the DF1 protocol, send and receive messages, does not support remote programming and monitoring

29

SynchLink 1756-SYNCH SynchLink fiber-optic communication link 32

(1) 128 connections are available for standard use. An additional three connections are reserved for redundant control.

Publication 1756-TD003C-EN-E - December 2010 3

Page 4: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Communication ConnectionsA ControlLogix system uses connections to establish communication links between devices. The types of connections include the following:

Controller-to-local I/O modules or local communication modules Controller-to-remote I/O or remote communication modules Controller-to-remote I/O (rack-optimized) modules Produced and consumed tags Messages Controller access by RSLogix 5000 programming software Controller access by RSLinx software for HMI or other applications

You indirectly determine the number of connections the controller uses by configuring the controller to communicate with other devices in the system. The limit of connections may ultimately reside in the communication module you use for the connection. If a message path routes through a communication module, the connection related to the message also counts towards the connection limit of that communication module.

EtherNet/IP Network The Ethernet Industrial (EtherNet/IP) network protocol is an open industrial-networking standard that supports both real-time I/O messaging and message exchange. The EtherNet/IP network uses off-the-shelf Ethernet communication chips and physical media.

If you need to Select this interface

Control I/O modules and drives

Act as an adapter for I/O on remote EtherNet/IP links

Communicate with other EtherNet/IP devices (messages and HMI)

Bridge EtherNet/IP links to route messages to devices on other networks

1756-EN2F bridge1756-EN2T bridge1756-ENBT bridge

Support device level ring (DLR) and linear topologies 1756-EN2TR bridge1756-EN3TR bridge

Provide control in environments where temperatures range from -25...70 C (-13...158 F).

1756-EN2TXT bridge

Use an Internet browser to remotely access tags in a ControlLogix controller

Communicate with other EtherNet/IP or generic Ethernet devices (messaging only; no I/O control)

Bridge EtherNet/IP links to route messages to devices on other networks

1756-EWEB web server

4 Publication 1756-TD003C-EN-E - December 2010

Page 5: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Technical Specifications - 1756 EtherNet/IP Modules

Attribute 1756-EN2F 1756-EN2T 1756-EN2TR, 1756-EN3TR

1756-ENBT 1756-EWEB

EtherNet/IP communication rate 100 Mbps 10/100 Mbps 10/100 Mbps 10/100 Mbps 10/100 Mbps

Logix communication connections 256 128

TCP/IP communication connections 128 64

Current draw @ 5.1V DC 1.2 A 1 A 1 A 700 mA

Current draw @ 24V DC 3 mA 3 mA 3 mA 3 mA

Power dissipation 6.2 W 5.1 W 5.1 W 3.65 W

Isolation voltage No isolation between USB and system

30V (continuous), basic insulation type, Ethernet network to backplane

No isolation between USB and backplane

Type tested @ 510V AC for 60 s

30V (continuous), basic insulation type, Ethernet network to backplane

No isolation between USB and backplane

Type tested @ 853V AC for 60 s

30V (continuous), basic insulation type, Ethernet network to backplane

Type tested @ 707V DC for 60 s

Slot width 1

Module location Chassis-based, any slot

Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant 756-PA75R, 1756-PB75R, 1756-PSCA2

Ports 1 Ethernet fiber1 USB 1.1

1 Ethernet RJ45 Category 51 USB 1.1

1 Ethernet RJ45 Category 5

Ethernet cable Multimode fiber, LC connector

802.3 compliant shielded or unshielded twisted pair

USB cable Samtec cable, PN RSP-119350 —

Wire category(1) 3 - on USB ports 2 - on Ethernet ports3 - on USB ports

2 - on Ethernet ports

North American temperature code T4A

IEC temperature code T4

Enclosure type rating None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756 EtherNet/IP Modules

Attribute 1756-EN2F 1756-EN2T 1756-EN2TR, 1756-EN3TR

1756-ENBT, 1756-EWEB

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, storageIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Publication 1756-TD003C-EN-E - December 2010 5

Page 6: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged damp heat)

5…95% noncondensing

VibrationIEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

EmissionCISPR 11

Group 1, Class A

ESD immunityIEC 61000-4-2

6 kV contact discharges8 kV air discharges

Radiated RF immunityIEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunityIEC 61000-4-4

— ±2 kV at 5 kHz on Ethernet ports

±3 kV at 5 kHz on Ethernet ports

±2 kV at 5 kHz on Ethernet ports

Surge transient immunityIEC 61000-4-5

— ±2 kV line-earth (CM) on Ethernet ports

Conducted RF immunityIEC 61000-4-6

— 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Environmental Specifications - 1756 EtherNet/IP Modules

Attribute 1756-EN2F 1756-EN2T 1756-EN2TR, 1756-EN3TR

1756-ENBT, 1756-EWEB

Certifications - 1756 EtherNet/IP Modules

Certification(1) 1756-EN2F, 1756-EN2T 1756-EN2TR, 1756-EN3TR 1756-ENBT 1756-EWEB

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

— CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

6 Publication 1756-TD003C-EN-E - December 2010

Page 7: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

TÜV — TÜV Certified for Functional Safety:Capable of SIL 2

EtherNet/IP ODVA conformance tested to EtherNet/IP specifications

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Certifications - 1756 EtherNet/IP Modules

Certification(1) 1756-EN2F, 1756-EN2T 1756-EN2TR, 1756-EN3TR 1756-ENBT 1756-EWEB

Technical Specifications - 1756 EtherNet/IP-XT Module

Attribute 1756-EN2TXT

EtherNet/IP communication rate 10/100 Mbps

Logix communication connections 256

TCP/IP communication connections 128

Current draw @ 5.1V DC 1 A

Current draw @ 24V DC 3 mA

Power dissipation 5.2 W

Power consumption 17.7 BTU/hr

Isolation voltage 30V (continuous), basic insulation type, Ethernet network to backplane

No isolation between USB and backplane

Type tested @ 853V AC for 60 s

Slot width 1

Module location Chassis-based, any slot

Chassis 1756-A4LXT, 1756-A5XT, 1756-A7LXT

Power supply, standard 1756-PAXT, 1756-PBXT

Power supply, redundant None

Ports 1 Ethernet RJ45 Category 51 USB 1.1

Ethernet cable 802.3 compliant shielded or unshielded twisted pair

USB port USB 1.1

USB cable Samtec cable, PN RSP-119350

Wire category (1) 2 - on Ethernet ports3 - on USB ports

North American temperature code T4A

IEC temperature code T4

Enclosure type rating None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD003C-EN-E - December 2010 7

Page 8: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Environmental Specifications - 1756 EtherNet/IP-XT Module

Attribute 1756-EN2TXT

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-25…70 °C (-13…158 °F)

Temperature, surrounding air, max 70 °C (158 °F)

Temperature, storageIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged damp heat)

5…95% noncondensing

VibrationIEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

EmissionsCISPR 11

Group 1, Class A

ESD immunityIEC 61000-4-2

6 kV contact discharges8k V air discharges

Radiated RF immunityIEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunityIEC 61000-4-4

±2 kV at 5 kHz on Ethernet ports

Surge transient immunityIEC 61000-4-5

±2 kV line-earth (CM) on Ethernet ports

Conducted RF immunityIEC 61000-4-6

10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Certifications - 1756 EtherNet/IP-XT Module

Certification(1) 1756-EN2TXT

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

TÜV TÜV Certified for Functional Safety:Capable of SIL 2

EtherNet/IP ODVA conformance tested to EtherNet/IP specifications

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

8 Publication 1756-TD003C-EN-E - December 2010

Page 9: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Accessories - Ethernet Network

Cat. No. Description Specifications

1585J-M8PBJM-x Ethernet RJ45 patchcordx = 2 (2 m), 5 (5 m), or 10 (10 m)

8-conductor, Teal Riser PVC Cable (flex Rated cable also available)

1585J-M8CC-H RJ45 insulation displacement connector (IDC) 0.128...0.325 mm2 (26…22 AWG), Cat. 6, IDC, no tool required

1585J-M8CC-C RJ45 crimp connector with boot, qty = 50 pieces

0.128...0.205 mm2 (26…24 AWG), Cat. 5e, requires crimp tool for assembly

1585A-JCRIMP Crimp tool —

9300-RADES Remote access dial-in kit 56 Kbps modem connection to devices on an Ethernet network

Publication 1756-TD003C-EN-E - December 2010 9

Page 10: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Stratix Switches To effectively manage real-time control and information flow throughout the manufacturing and IT enterprise, Rockwell Automation offers a full portfolio of industrial Ethernet switches and media, including a line of Stratix switches integrated with Cisco technology. The Stratix line of switches includes modular managed, fixed managed, and unmanaged switches.

If your application Select

Requires Layer 3 routing

Integrates enterprise and manufacturing environments

Manages multicast traffic

Requires diagnostics data

Requires security options

Stratix 8300 modular, managed switch

Integrates enterprise and manufacturing environments

Manages multicast traffic

Requires diagnostics data

Requires security options

Stratix 8000 modular, managed switch

Integrates plant floor devices

Manages multicast traffic

Requires diagnostics data

Requires security options

Stratix 6000 fixed, managed switch

Requires easy set up and direct replacement of switches

Is a small, isolated network

Stratix 2000 unmanaged switch

10 Publication 1756-TD003C-EN-E - December 2010

Page 11: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Stratix Managed Switch Specifications

Stratix 8000 and Stratix 8300 Stratix 6000

Base Base Base Base Expansion Expansion

Feature 1783-MS06T 1783-RMS06T 1783-MS10T 1783-RMS10T 1783-MX08T 1783-MX08F 1783-EMS04T 1783-EMS08T

Ports per module 6 10 8 4 9

Layer 3 routing No Yes No Yes No No No No

Total ports, max Up to 26(1) — —

Fiber ports 0...10(1) — 1

10/100 copper ports

4...24(1) 4 8

100 base LC fiber ports

0...8(1)

SFP slots 2(2) — 1

10/100/1000 copper ports

2(2) — —

100 Mbps fiber support

Yes — Yes No No

1 G fiber support Yes — — No Yes

CompactFlash memory

Yes No No

Power requirements

24/48V DC (18…60V DC) 24V DC (12…48V DC)

(1) Maximum port counts require expansion ports.

(2) Two ports each can be used for SFP or 10/100/1000 copper.

Stratix Unmanaged Switch Specifications

Stratix 2000

Feature 1783-US03T01F 1783-US05T 1783-US06T01F 1783-US08T

Ports per module 4 5 7 8

Fiber ports 1 — 1 —

10/100 copper ports 3 5 6 8

100 base LC fiber ports 1 — 1 —

100 Mbps fiber support

Yes — Yes —

CompactFlash memory No No No No

Power requirements 20V AC (10…24V AC)24V DC (10…35V DC)

Publication 1756-TD003C-EN-E - December 2010 11

Page 12: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

ControlNet Network The ControlNet network is an open, control network for real-time, high-throughput applications. The ControlNet network uses the Common Industrial Protocol (CIP) to combine the functionality of an I/O network and a peer-to-peer network providing high-speed performance for both functions. The ControlNet network gives you deterministic, repeatable transfers of all mission-critical control data in addition to supporting transfers of non-time-critical data. I/O updates and controller-to-controller interlocking always take precedence over program uploads and downloads, and messaging.

Connect to Other Devices via a ControlNet Network

The RSLogix 5000 Enterprise Series software supports a generic ControlNet module that allows connections to ControlNet nodes for which there is no specific support currently available in the programming software. A module configured as a generic ControlNet module communicates with the controller in the form of input, output, status, and configuration tags.For example, use the generic module configuration to set up communication between a ControlLogix controller and a 1203-CN1 ControlNet communication module. Then use the CIP generic MSG instruction type to send and receive messages from the 1203-CN1 module.

If your application requires Select this interface

128 ControlNet connections per communication module

1756-CN2/B1756-CN2R/B

Control in environments where temperatures range from -25...70 C (-13...158 F)

1756-CN2RXT

40...48 ControlNet connections per communication module

1756-CNB1756-CNBR

Technical Specifications - 1756 ControlNet Modules

Attribute 1756-CN2/B 1756-CN2R/B 1756-CNB/E 1756-CNBR/E

Configuration Standard Redundant Standard Redundant

ControlNet communication rate 5 Mbps

Logix communication connections 128 40…48

Connections supported, max 131(1) 64

Number of nodes, max 99

Current draw @ 5.1V DC 1100 mA 1300 mA 970 mA

Current draw @ 24V DC 3 mA 1.7 mA

Power dissipation 5.7 W 6.7W 5.14 W

Thermal dissipation 19.5 BTU/hr 22.9 BTU/hr 17.5 BTU/hr

12 Publication 1756-TD003C-EN-E - December 2010

Page 13: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Isolation voltage Standard: 30V (continuous), basic insulation type, ControlNet network to backplane

Redundant: 30V (continuous), basic insulation type, ControlNet A/B to backplane, and ControlNet A to ControlNet B

No isolation between NAP or USB and backplane

Type tested at 500V AC for 60 s

Weight, approx. 0.26 kg (0.57 lb) 0.293 kg (0.64 lb) 0.26 kg (0.57 lb) 0.293 kg (0.64 lb)

Slot width 1

Module location Chassis-based, any slot

Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2

Ports 1 ControlNet BNC 1 USB 1.1

2 ControlNet BNC 1 USB 1.1

1 ControlNet BNC 1 NAP RJ45

2 ControlNet BNC 1 NAP RJ45

ControlNet cable 1786-RG6 quad shield RG6 coaxial cable

USB cable Samtec cable, PN RSP-119350 —

NAP cable — — 1786-CP

Wire category(2) 1 - on ControlNet ports

3 - on USB ports

1 - on ControlNet ports

3 - on NAP ports

North American temperature code T4A

IEC temperature code T4

Enclosure type rating None (open-style)

(1) 128 connections are available for standard use. An additional three connections are reserved for redundant control.

(2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Technical Specifications - 1756 ControlNet Modules

Attribute 1756-CN2/B 1756-CN2R/B 1756-CNB/E 1756-CNBR/E

Environmental Specifications - 1756 ControlNet Modules

Attribute 1756-CN2/B, 1756-CN2R/B 1756-CNB/E, 1756-CNBR/E

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, storageIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

VibrationIEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

EmissionsCISPR 11

Group 1, Class A

Publication 1756-TD003C-EN-E - December 2010 13

Page 14: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

ESD immunityIEC 61000-4-2

6 kV contact discharges8 kV air discharges

Radiated RF immunityIEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunityIEC 61000-4-4

±3 kV at 5 kHz on ControlNet ports ±2 kV at 5 kHz on ControlNet ports

Surge transient immunityIEC 61000-4-5

±2 kV line-earth (CM) on ControlNet ports

Conducted RF immunityIEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Environmental Specifications - 1756 ControlNet Modules

Attribute 1756-CN2/B, 1756-CN2R/B 1756-CNB/E, 1756-CNBR/E

Certifications - 1756 ControlNet Modules

Certification(1) 1756-CN2/B, 1756-CN2R/B, 1756-CNB/E, 1756-CNBR/E

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

TÜV TÜV Certified for Functional Safety:Capable of SIL 2

CI ControlNet International conformance tested to ControlNet specifications

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

14 Publication 1756-TD003C-EN-E - December 2010

Page 15: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Technical Specifications - 1756 ControlNet-XT Module

Attribute 1756-CN2RXT

Configuration Redundant

ControlNet communication rate 5 Mbps

Logix communication connections 128

Connections supported, max 131(1)

Number of nodes, max 99

Current draw @ 5.1V DC 1300 mA

Current draw @ 24V DC 3 mA

Power dissipation 6.7 W

Thermal dissipation 22.9 BTU/hr

Isolation voltage 30V (continuous), basic insulation type, ControlNet A/B to backplane, and ControlNet A to ControlNet B

No isolation between USB and backplane

Type tested at 500V AC for 60 s

Weight, approx. 0.293 kg (0.64 lb)

Slot width 1

Module location Chassis-based, any slot

Chassis 1756-A4LXT, 1756-A5XT, 1756-A7LXT

Power supply, standard 1756-PAXT, 1756-PBXT

Power supply, redundant None

Ports 2 ControlNet BNC 1 USB 1.1

ControlNet cable 1786-RG6 quad shield RG6 coaxial cable

USB cable Samtec cable, PN RSP-119350

Wire category(2) 2 - on ControlNet ports3 - on USB port

North American temperature code T4A

IEC temperature code T4

Enclosure type rating None (open-style)

(1) 128 connections are available for standard use. An additional three connections are reserved for redundant control.

(2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756 ControlNet-XT Module

Attribute 1756-CN2RXT

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-25…70 °C (-13…158 °F)

Temperature, surrounding air, max 70 °C (158 °F)

Temperature, storageIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Publication 1756-TD003C-EN-E - December 2010 15

Page 16: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

VibrationIEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

EmissionsCISPR 11

Group 1, Class A

ESD immunityIEC 61000-4-2

6 kV contact discharges8 kV air discharges

Radiated RF immunityIEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunityIEC 61000-4-4

±2 kV at 5 kHz on ControlNet ports

Surge transient immunityIEC 61000-4-5

±1 kV line-earth (CM) on ControlNet port

Conducted RF immunityIEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Environmental Specifications - 1756 ControlNet-XT Module

Attribute 1756-CN2RXT

Certifications - 1756 ControlNet-XT Module

Certification(1) 1756-CN2RXT

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

TÜV TÜV Certified for Functional Safety:Capable of SIL 2

CI ControlNet International conformance tested to ControlNet specifications

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

16 Publication 1756-TD003C-EN-E - December 2010

Page 17: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Accessories - ControlNet Network

For more information, see ControlNet Media System Components List, publication AG-PA002.

Cat. No. Description

Taps

1786-TCT2BD1 T-tap straight IP67 rated

1786-TPR T-tap right angle

1786-TPS T-tap straight

1786-TPYR Y-tap right angle

1786-TPYS Y-tap straight

Cables

1786-CP Programming cable to ControlNet RJ45 port

1786-RG6 ControlNet network, shield high-flex cable

1756-RG6F ControlNet network, quad-shield high-flex coax cable

Other

1786-TNCLXT4 ControlNet IP67 termination resistor

1786-XT ControlNet termination resistor

Repeaters

1786-RPA ControlNet modular repeater adapter

1786-RPCD ControlNet coaxial hub repeater

1786-RPFRL ControlNet fiber ring repeater, long distance

1786-RPFRXL ControlNet fiber ring repeater, extra long distance

1786-RPFS ControlNet fiber repeater, short distance

1786-RPFM ControlNet fiber repeater, medium distance

Publication 1756-TD003C-EN-E - December 2010 17

Page 18: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

DeviceNet Network The DeviceNet network is an open, low-level network that provides connections between simple industrial devices (such as sensors and actuators) and higher-level devices (such as controllers and computers). The DeviceNet network uses the proven Common Industrial Protocol (CIP) to provide the control, configure, and data collection capabilities for industrial devices.

Technical Specifications - 1756-DNB DeviceNet Module

Attribute 1756-DNB

DeviceNet communication rate 125 Kbps (500 m max)250 Kbps (250 m max)500 Kbps (100 m max)

Number of nodes, max 64

Current draw @ 5.1V DC 850 mA

Current draw @ 24V DC 3 mA

DeviceNet current range 11…25V DC

Power dissipation 5.8 W

Thermal dissipation 19.8 BTU/hr

Isolation voltage 30V (continuous), basic insulation type, DeviceNet network to backplane

Type tested at 500V AC for 60 s

Slot width 1

Module location Chassis-based, any slot

Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2

DeviceNet power To comply with the CE low voltage directive (LVD), the DeviceNet network must be powered from a source compliant with the safety extra low voltage (SELV) or protected extra low voltage (PELV).

To comply with UL restrictions, the DeviceNet network must be powered from a source compliant with Class 2 or limited voltage/current.

Ports 1 DeviceNet open-style 5-or 10-pin linear plug1 USB 1.1

DeviceNet connector torque 0.56…0.79 N•m (5…7 lb•in)

USB cable Samtec cable, PN RSP-119350

Wire category(1) Refer to the DeviceNet Media Design and Planning Guide, publication DNET-UM072, for information specific to your DeviceNet network

North American temperature code T4A

IEC temperature code T4

Enclosure type rating None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

18 Publication 1756-TD003C-EN-E - December 2010

Page 19: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Environmental Specifications - 1756-DNB DeviceNet Module

Attribute 1756-DNB

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, storageIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

VibrationIEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

EmissionsCISPR 11

Group 1, Class A

ESD immunityIEC 61000-4-2

6 kV contact discharges8 kV air discharges

Radiated RF immunityIEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunityIEC 61000-4-4

±3 kV at 5 kHz on DeviceNet ports

Surge transient immunityIEC 61000-4-5

±2 kV line-earth (CM) on DeviceNet ports

Conducted RF immunityIEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Publication 1756-TD003C-EN-E - December 2010 19

Page 20: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Accessories - DeviceNet Network

For more information on selecting DeviceNet media, see the NetLinx Selection Guide, publication NETS-SG001.

Certifications - 1756-DNB DeviceNet Module

Certification(1) 1756-DNB

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

ODVA ODVA conformance tested to DeviceNet specifications

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Cat. No. Description

KwikLink Lite flat media KwikLink Lite flat media is a newer, ODVA-approved solution for wiring DeviceNet networks. Drop-lines for connecting nodes are added by using the KwikLink Lite two-piece connectors. This cable system supports the intermixing of DeviceNet cable types (thin-round with flat). All of the KwikLink Lite connectors provide insulation displacement technology with reduced assembly time.

KwikLink flat media The KwikLink flat media system provides a modular cabling method with its flat four-wire cable and Insulation Displacement Connectors (IDCs). The KwikLink system allows nodes to be added to the network without severing the trunkline. Cutting or stripping of the trunkline is eliminated, as is the need for predetermined cable lengths.

Round media Round trunk cable is available in bulk spools or as pre-molded cordsets or patchcords in varying lengths. A wide variety of rugged, durable DeviceNet components is available for use in round trunk systems. Stainless steel versions of round cable system components are also available: Thick-trunk round media systems use thick cable for maximum DeviceNet trunk line length.

Round media thin-trunk systems use thin cable to reduce maximum trunk line distances with a more compact and cost-effective installation for some applications. Thin-cable outer jacket material is TPE for additional chemical resistance.

20 Publication 1756-TD003C-EN-E - December 2010

Page 21: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

DH+ and Remote I/O Networks

The Data Highway Plus network supports messaging between devices. The remote I/O link connects to remote I/O chassis and other intelligent devices.The 1756-DHRIO module supports messaging between devices on DH+ networks. The remote I/O functionality enables the module to act as a scanner for transferring digital and block-transfer data to and from remote I/O devices.The 1756-RIO module can act as a scanner or adapter on a remote I/O network. In addition to digital and block-transfer data, the 1756-RIO module transfers analog and specialty data without message instructions.

Example Configuration - DH+ Network

Example Configuration - Remote I/O Network

PanelView Plus

PLC-5 1784-U2DHPRSLogix 5000

ControlLogix1756-DHRIO

SLC 5/04

PanelView PlusPLC-5

1756-RIO as a Remote I/O Adapter

1791 I/O1794 I/O

1756-DHRIO as a Remote I/O Scanner

Publication 1756-TD003C-EN-E - December 2010 21

Page 22: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Technical Specifications - 1756 DH+ and Remote I/O Modules

Attribute 1756-DHRIO 1756-RIO/B

Communication rate 57.6 Kbps, 115.2 Kbps, 230.4 Kbps 57.6 Kbps, 115.2 Kbps, 230.4 Kbps

Remote I/O communication Remote I/O scanner only

32 logical rack connections per remote I/O channel16 block-transfer connections per remote I/O channel

Remote I/O scanner or adapter

32 physical racks (0...76), any combination of rack size and block transfers

Connections supported, max 32 10 scheduled I/O

Current draw @ 5.1V DC 850 mA 450 mA

Current draw @ 24V DC 1.7 mA 5 mA

Power dissipation 4.5 W 2.5 W

Thermal dissipation 15.4 BTU/hr 8.5 BTU/hr

Isolation voltage 30V (continuous), basic insulation type, DHRIO A/B to backplane, and DHRIO A/programming port to DHRIO B

No isolation between DHRIO A and Programming port

Type tested at 877V DC for 60 s

50V (continuous), basic insulation type, RIO communication lines to backplane

Type tested at 500V AC for 60 s

Slot width 1

Module location Chassis-based, any slot

Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2

Ports 2, individually selectable for DH+ or remote I/O 1 for remote I/O

Screw terminal torque — 0.5…0.6 N•m (5…7 lb•in.)

Wire size 0.519 mm2 (20 AWG) Belden 9463 copper twinaxial

Wire category(1) 1 - on DHRIO ports3 - on local programming port

2 - on RIO ports

North American temperature code T4A

IEC temperature code T4 —

Enclosure type rating None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756 DH+ and Remote I/O Modules

Attribute 1756-DHRIO 1756-RIO/B

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, storageIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

VibrationIEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

22 Publication 1756-TD003C-EN-E - December 2010

Page 23: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

EmissionsCISPR 11

Group 1, Class A

ESD immunityIEC 61000-4-2

6 kV contact discharges8 kV air discharges

Radiated RF immunityIEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunityIEC 61000-4-4

±4 kV at 5 kHz on DHRIO ports ±2 kV at 5 kHz on RIO ports

Surge transient immunityIEC 61000-4-5

±2 kV line-earth (CM) on DHRIO ports

Conducted RF immunityIEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Environmental Specifications - 1756 DH+ and Remote I/O Modules

Attribute 1756-DHRIO 1756-RIO/B

Certifications - 1756 DH+ and Remote I/O Modules

Certification(1) 1756-DHRIO 1756-RIO

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres,

Protection "n"

EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

TÜV TÜV Certified for Functional Safety:Capable of SIL 2

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD003C-EN-E - December 2010 23

Page 24: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Technical Specifications - 1756 DH+ and Remote I/O XT Module

Attribute 1756-DHRIOXT

Communication rate 57.6 Kbps, 115.2 Kbps, 230.4 Kbps

DH+ communication connections 32 DH+ messages per DH+ module

Remote I/O communication connections Remote I/O scanner only

32 logical rack connections per remote I/O channel16 block-transfer connections per remote I/O channel

Connections supported, max 32

Current draw @ 5.1V DC 850 mA

Current draw @ 24V DC 1.7 mA

Power dissipation 4.5 W

Thermal dissipation 15.4 BTU/hr

Isolation voltage 30V (continuous), basic insulation type, DHRIO A/B to backplane, and DHRIO A/programming port to DHRIO B

No Isolation between DHRIO A and Programming port

Type tested at 853V AC for 60 s

Slot width 1

Module location Chassis-based, any slot

Chassis 1756-A4LXT, 1756-A5XT, 1756-A7LXT

Power supply, standard 1756-PBXT

Power supply, redundant None

Ports 2, individually selectable for DH+ or remote I/O

Screw terminal torque 0.5…0.6 N•m (5…7 lb•in.)

Wire size 0.519 mm2 (20 in.) Belden 9463 copper twinaxial

Wire category 1 - on DHRIO ports3 - on local programming port(1)

North American temperature code T4A

IEC temperature code T4

Enclosure type rating None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756 DH+ and Remote I/O XT Module

Attribute 1756-DHRIOXT

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-25…70 °C (-13…158 °F)

Temperature, surrounding air, max 70 °C (158 °F)

Temperature, storageIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

24 Publication 1756-TD003C-EN-E - December 2010

Page 25: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Accessories - DH+ and Remote I/O Networks

VibrationIEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

EmissionsCISPR 11

Group 1, Class A

ESD immunityIEC 61000-4-2

6 kV contact discharges8 kV air discharges

Radiated RF immunityIEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunityIEC 61000-4-4

±4 kV at 5 kHz on DHRIO ports

Surge transient immunityIEC 61000-4-5

±2 kV line-earth (CM) on DHRIO ports

Conducted RF immunityIEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Environmental Specifications - 1756 DH+ and Remote I/O XT Module

Attribute 1756-DHRIOXT

Certifications - 1756 DH+ and Remote I/O XT Module

Certification(1) 1756-DHRIOXT

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4X

TÜV TÜV Certified for Functional Safety:Capable of SIL 2

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Cat. No. Description Specifications

1770-CD Cable to connect communication module to DH+ network Belden 9463 twinaxial

9300-RADKIT Remote access dial-in kit 56 Kbps modem connection to devices on a DH+ network, includes: Pre-configured modem

Communication module

DIN rail mounting hardware

Associated cables

Publication 1756-TD003C-EN-E - December 2010 25

Page 26: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

FOUNDATION Fieldbus Network

The FOUNDATION Fieldbus network is a communication network created by the Fieldbus Foundation. It is a protocol designed for robust, distributed control of process control applications. Devices connected by a FOUNDATION Fieldbus network can be used for sophisticated, highly-distributed process control.

If your application bridges from

Select Description

EtherNet/IP network 1757-FFLD21757-FFLD4

The 1757-FFLDx linking device bridges from an Ethernet/IP network to either two or four H1 ports. Each H1 port can support the recommended maximum 8...10 devices. Each H1 network can support a maximum of 16 publisher and 16 subscriber VCR connections.

ControlNet network 1757-FFLDC21757-FFLDC4

The 1757-FFLDCx linking device bridges from a ControlNet network to either two or four H1 ports. Each H1 port can support the recommended maximum 8...10 devices. Each H1 network can support a maximum of 64 publisher and 64 subscriber VCR connections. The 1757-FFLDCx linking device is compatible with ControlLogix redundancy and supports redundant ControlNet media.

Technical Specifications - 1757 FOUNDATION Fieldbus Modules

Attribute 1757-FFLD2 1757-FFLD4 1757-FFLDC2 1757-FFLDC4

Foundation Fieldbus communication rate 31.25 Kbps

EtherNet/IP communication rate 10/100 Mbps —

ControlNet communication rate — 5 Mbps

Number of H1 networks per linking device, max(1) 2 4 2 4

Number of Fieldbus devices per H1 network, max 16 (8…10 recommended)

Number of Fieldbus devices per linking device, max 32 64 32 64

Current draw @ 24V DC(2) (3) 300 mA 450 mA

Inrush current 1.5 A

Power dissipation — 9.6 W

Isolation voltage 50V (continuous), basic insulation typeFieldbus to system backplane and Ethernet network to system backplaneType tested @ 500V AC for 60 s

50V (continuous), basic insulation type tested at 500V AC for 60 s, Fieldbus to system backplane, ControlNet network to system backplane, and ControlNet Channel A to ControlNet Channel BType tested @ 500V AC for 60 s

Module location DIN rail or panel

Power supply User-supplied 24V DC

Ports 2 H1 FOUNDATION Fieldbus1 Ethernet RJ45

4 H1 FOUNDATION Fieldbus1 Ethernet RJ45

2 H1 FOUNDATION Fieldbus1 ControlNet BNC

4 H1 FOUNDATION Fieldbus1 ControlNet BNC

Wire category(3) 2 - on shielded Fieldbus port3 - on power port2 - on communication port

26 Publication 1756-TD003C-EN-E - December 2010

Page 27: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Wire size DC power connection: 0.2…1.5 mm2 (26…16 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (.05 in.) insulation, max

Fieldbus connections: 0.8 mm2 (18 AWG) solid or stranded shielded twisted pair copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (.05 in.) insulation, max

Ethernet connections: RJ45 connector according to IEC 6003-7, 2 or 4 pair Category 5e min cable according to TIA 568-B.1, or Category 5 cable according to ISO/IEC 24702

DC power connection: 0.2... 1.5 mm2 (26...16 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater 1.2 mm (3/64 in.) insulation max

Fieldbus connections: 0.8 mm2 (18 AWG) solid or stranded shielded twisted-pair copper wire rated at 75 °C (167 °F) or greater 1.2 mm (3/64 in.) insulation max

Screw terminal torque 0.34 Nm (3 lb•in.) on power and Fieldbus wire connections

Panel mount screw torque 1.1…1.8 N•m (10…16 lb•in)

North American temperature code T4

IEC temperature code T4

Enclosure type rating None (open-style)

(1) Each network defined as a Foundation Fieldbus 31.25 Kbps H1 network.

(2) 24V DC (± 20%).

(3) 24V DC (±10%).

Technical Specifications - 1757 FOUNDATION Fieldbus Modules

Attribute 1757-FFLD2 1757-FFLD4 1757-FFLDC2 1757-FFLDC4

Environmental Specifications - 1757 FOUNDATION Fieldbus Modules

Attribute 1757-FFLD2, 1756-FFLD4 1757-FFLDC2, 1757-FFLDC4

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, storageIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

VibrationIEC 60068-2-6 (Test Fc, Operating)

5 g @ 10…500 Hz

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

15 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

EmissionsCISPR 11

Group 1, Class A

ESD immunityIEC 61000-4-2

6 kV contact discharges8 kV air discharges

Radiated RF immunityIEC 61000-4-3

1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz

10V/m with 1 kHz sine-wave 80% AM from 80…2700 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz

Publication 1756-TD003C-EN-E - December 2010 27

Page 28: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Accessories - Foundation Fieldbus Network

EFT/B immunityIEC 61000-4-4

±2 kV at 5 kHz on power ports±2 kV at 5 kHz on shielded Fieldbus ports±2 kV at 5 kHz on Ethernet ports

±2 kV at 5 kHz on shielded Fieldbus ports±2 kV at 5 kHz on ControlNet ports

Surge transient immunityIEC 61000-4-5

±2 kV line-earth (CM) on shielded Fieldbus ports±2 kV line-earth (CM) on shielded Ethernet ports

±2 kV line-earth (CM) on shielded Fieldbus ports±2 kV line-earth (CM) on shielded ControlNet ports

Conducted RF immunityIEC 61000-4-6

10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on power ports, shielded Fieldbus ports, and Ethernet ports

10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on ControlNet and shielded Fieldbus ports

Magnetic field immunityIEC 61000-4-8

30 A/m long duration at 50 Hz

Environmental Specifications - 1757 FOUNDATION Fieldbus Modules

Attribute 1757-FFLD2, 1756-FFLD4 1757-FFLDC2, 1757-FFLDC4

Certifications - 1757 Foundation Fieldbus Modules

Certification(1) 1757-FFLD2, 1757-FFLD4 1757-FFLDC2, 1757-FFLDC4

c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements II 3 G Ex nA nL IIC

FF Foundation Fieldbus H1 CTK Registered

ODVA - EtherNet/IP ODVA conformance tested to EtherNet/IP specifications —

CI — ControlNet International conformance tested to ControlNet specifications

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Cat. No. Description

DIN rail 35 x 7.5 or 35 x 15 DIN (EN 50 022), zinc-plated yellow chromate steel

28 Publication 1756-TD003C-EN-E - December 2010

Page 29: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

DH-485 Network On the DH-485 network, the controller can send and receive messages to and from other controllers on the network. The DH-485 connection does support remote programming and monitoring via RSLogix 5000 software. Excessive traffic over a DH-485 connection can adversely affect overall performance and can lead to timeouts and loss in RSLogix 5000 configuration performance.

You need a 1761-NET-AIC converter for each controller on the DH-485 network. You can have two controllers per one 1761-NET-AIC converter, but you need a different cable for each controller. Connect one controller to port 1 (9-pin connector) and one controller to port 2 (mini-DIN connector).

IMPORTANT Use Logix5000 controllers on DH-485 networks only when you want to add controllers to an existing DH-485 network. For new applications with Logix5000 controllers, we recommend open architecture networks.

To connect to this port Use this cable

Port 1DB-9 RS-232, DTE connection

1747-CP3, 1761-CBL-AC00

Port 2mini-DIN 8 RS-232 connection

1761-CBL-AP00, 1761-CBL-PM02

Technical Specifications - 1756-DH485 Module

Attribute 1756-DH485

Communication rate 19.2 Kbps9600 Kbps

Current draw @ 5.1V DC 850 mA

Current draw @ 24V DC 1.7 mA

Power dissipation 4.5 W

Thermal dissipation 15.4 BTU/hr

Isolation voltage 50V (continuous), basic insulation type, DH485 A/B to backplane, and DH485 A to DH485 B

Type tested at 750V DC for 60 s

Slot width 1

Module location Chassis

Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2

Ports 2 DH-485 9-pin, D-shell

Wire category(1) 2 - on DH485 ports

Wire type Belden 9463 twinaxial

North American temperature code T5

Enclosure type rating None (open-style)

Publication 1756-TD003C-EN-E - December 2010 29

Page 30: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

(1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-DH485 Module

Attribute 1756-DH485

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, storageIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

VibrationIEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

EmissionsCISPR 11

Group 1, Class A

ESD immunityIEC 61000-4-2

4 kV contact discharges8 kV air discharges

Radiated RF immunityIEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz1V/m with 1 kHz sine-wave 80% AM from 2000... 2700 MHz

EFT/B immunityIEC 61000-4-4

±2 kV at 5 kHz on communication ports

Surge transient immunityIEC 61000-4-5

±1 kV line-earth (CM) on communication ports

Conducted RF immunityIEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Magnetic field immunityIEC 61000-4-8

30 A/m @ 50 Hz

Certifications - 1756-DH485 Module

Certification(1) 1756-DH485

c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

30 Publication 1756-TD003C-EN-E - December 2010

Page 31: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Accessories - DH-485 Network

Cat. No. Description Specifications

1747-CP3 9-pin D-shell, straight; 9-pin D-shell, right angle 3 m (9.8 ft)

1761-CBL-AC00 9-pin D-shell, right angle; 9-pin D-shell, right angle 45 cm (17.7 in.)

1761-CBL-AP00 9-pin D-shell, right angle; 8-pin mini-DIN 45 cm (17.7 in.)

1761-CBL-PM02 9-pin D-shell, straight; 8-pin mini-DIN 2 m (6.5 ft)

1761-NET-AIC Advanced Interface Converter (AIC+) connects each channel on the 1756-DH485 module to the DH-485 network

20.4…28.8V DC power source required

Typical 120 mA 24V DC current draw

9300-RADKIT Remote access dial-in kit 56 Kbps modem connection to devices on a DH+ network, includes the following: Pre-configured modem

Communication module

DIN rail mounting hardware

Associated cables

Publication 1756-TD003C-EN-E - December 2010 31

Page 32: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

SynchLink Communication The SynchLink module provides time synchronization and data broadcasting capabilities for distributed motion and coordinated drive control. The 1756-SYNCH SynchLink module connects a ControlLogix chassis to a SynchLink fiber-optic communication link. The module does the following:

Coordinates Coordinated System Time across multiple ControlLogix chassis

Moves a limited amount of data from one chassis to another at a high speed

Lets one controller consume motion axes data from a controller in another chassis

Technical Specifications - 1756-SYNCH Module

Attribute 1756-SYNCH

SynchLink data rate 5 Mbps

Operating wavelength 650 nm (red)

Type of communication Synchronous

Frame period 50 s

Frame parameters 3 Flags - 3 bytesControl field - 1 byteData field - 24 bytesCRC field - 2 bytes

Current draw @ 5.1V DC 1200 mA

Current draw @ 24V DC 3 mA

Power dissipation 6.19 W

Thermal dissipation 21.1 BTU/hr

Slot width 1

Module location Chassis-based, any slot

Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant 1756-PA1756-PA75R, 1756-PB75R, 1756-PSCA2

Ports 2 fiber optic

Cable fiber type 200/230 micron HCS (Hard Clad Silica)

Cable fiber termination type Versalink V-System

Cable length 1…300 m (3.28…984.2 ft)

Enclosure type rating None (open-style)

32 Publication 1756-TD003C-EN-E - December 2010

Page 33: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Environmental Specifications - 1756-SYNCH Module

Attribute 1756-SYNCH

Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, storageIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

VibrationIEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

EmissionsCISPR 11

Group 1, Class A

ESD immunityIEC 61000-4-2

6 kV contact discharges8 kV air discharges

Radiated RF immunityIEC 61000-4-3

1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz

Certifications - 1756-SYNCH Module

Certification(1) 1756-SYNCH

UL UL Listed Industrial Control Equipment. See UL file E65584

CSA CSA Certified Process Control Equipment. See CSA File LR54689C

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA file LR69960C

CE European Union 2004/108/EC EMC Directive, compliant with: EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions

C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions

TÜV TÜV Certified for Functional SafetyCapable of SIL 2

FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD003C-EN-E - December 2010 33

Page 34: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Accessories - SynchLink Network

Cat. No. Description

1403-CFxxx Fiber optic cable assembly (Rockwell Automation)

HCP-M0200T V01RK Lucent Technologies 200 m simplex cable

34 Publication 1756-TD003C-EN-E - December 2010

Page 35: Especificacion Tecnica Tarjeta de Comunicacion

1756 ControlLogix Communication Modules Specifications

Notes:

Publication 1756-TD003C-EN-E - December 2010 35

Page 36: Especificacion Tecnica Tarjeta de Comunicacion

Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.

Installation Assistance

If you experience an anomaly within the first 24 hours of installation, review the information that is contained in this manual.You can contact Customer Support for initial help in getting your product up and running.

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

Documentation Feedback

Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

United States or Canada 1.440.646.3434

Outside United States or Canada

Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.

United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.

Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Publication 1756-TD003C-EN-E - December 2010 Supersedes 1756-TD003B-EN-E - May 2010 Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.