ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …
Transcript of ENGINEERING DATAENGINEERING DATA COILS — BLOWER COIL …
CB17 SERIES — UP-FLOW
CBH17 SERIES — HORIZONTAL63 900 to 223 200 Btuh (18.7 to 65.4 kW) Cooling Capacity
75 700 To 199 500 Btuh (22.2 To 58.5 kW) Heat Pump Heating Capacity
32 100 To 153 600 Btuh (9.4 To 45.0 kW) Optional Electric Heat
185 000 To 462 000 Btuh (54.2 To 134.4 kW) Optional Hot Water Heat
CB17/CBH17
September 1994Supersedes
June 1988
Bulletin #490018
MATCHED REMOTE SYSTEMS – 50hzENGINEERING DATA COILS — BLOWER COIL UNITS – 50hzENGINEERING DATA
Typical Applications
CBH17-95VHorizontal Unit
CB17-95VUp-Flow Unit
Horizontal Store Installation WithOptional Hot Water Heat Section and
Supply Air Plenum and Grille
Suspended Horizontal Installation With Optional Electric Heat and
Economizer Dampers
Up–Flow Installation WithOptional Hot Water Heat Section and
Economizer Dampers
Vertical Store Cooler Installation WithOptional Electric Heat Section and
Supply Air Plenum and Grille
NOTE — Due to Lennox’ ongoing committent to quality,Specifications, Ratings and Dimensions subject to change without notice. 1994 Lennox Industries Inc.
FEATURES
Application — Lennox CB17 and CBH17 model blower-coil-filter units provide installation versatility and maximum effi-ciency in cooling performance, air handling and filtering incooling or heat pump applications. Units are available in twomodel styles, CB17 series with up-flo supply air discharge orCBH17 series with horizontal supply air discharge. The unitsare equipped with dual circuit evaporator coils, this makesthem suitable for application with Lennox HS17 remotecondensing units or HP17 heat pump outdoor units. Each in-door coil circuit has a separate expansion valve and distribu-tion system for two stage capacity control during coolingcycles. Blower coil units are shipped factory assembled readyto install. Blower drives are shipped separately and must beordered extra. See condensing unit bulletins (section SpiltSystem Condensing Units) or heat pump outdoor units (sec-tion Split System — Heat Pump Units) for heating-cooling ef-ficiencies and capacities.
Completely Tested — Blower coil units are thoroughly testedwith matching outdoor units in the Lennox Research Labora-tory environmental test room which meet American Societyof Heating, Refrigeration and Air-Conditioning Engineers(ASHRAE) Standard 37 requirements. The rating test condi-tions are those included in Air-Conditioning and Refrigera-tion Institute (ARI) Standard test conditions while operatingat rated voltage and air volumes. Units and components with-in are bonded for grounding to meet safety standards forservicing required by Underwriter’s Laboratories (U.L.) andthe International Electrotechnical Commission (I.E.C.). Blow-er performance data is from actual unit tests conducted in theLennox air test chamber.
Cabinet — Cabinet is constructed of heavy gauge galvanizedsteel. A five station metal wash preparation assures a perfectbonding surface for the finish coat of baked-on enamel. Cabi-net is completely lined with thick fiberglass insulation result-ing in quiet and efficient operation due to the excellent sounddeadening and insulating qualities of fiberglass. Large re-movable panels are provided for complete service access.Electrical inlets are conveniently located in the cabinet.
Drain Pan — Deep, corrosion resistant drain pan isconstructed of heavy gauge galvanized steel. Equipped withtwin drain connections on both sides of cabinet as addedprotection from overflow. Dual galvanized pipe drain outletsextend outside the cabinet for ease of connection.
Belt Drive Blowers — CB17/CBH17-95V models are equippedwith a single blower, CB17/CBH17-135V, -185V & 275V modelshave dual blowers. Centrifugal belt driven blowers deliverlarge air volumes quietly and with low power consumption.Blower wheels are heavy duty, with forward curved bladesand double inlet. Wheels are statically and dynamically bal-anced to eliminate vibration and designed to give maximumair delivery. Bearings are heavy duty, self aligning, perma-nently sealed and lubricated. All moving parts (blowerwheels, drives and motor) are mounted on a rugged frame,resiliently mounted and isolated from the rest of the cabinet.Motor mounting frame allows simple belt adjustment andmotor mounting. Adjustable motor pulley provides variablespeed adjustments. A choice of motor outputs and drives areavailable and must be ordered extra. See drive kit table.
Dual Circuit Copper Tube Coil — Extra large surface area ofLennox designed coil provides maximum cooling efficiency,excellent heat transfer and low air resistance. Coil is face splitwith separate circuits, each circuit has its separate expansionvalve. Precise circuiting gives uniform refrigerant distribu-tion. Lennox fabricated coil is constructed of precisely spacedripple-edged aluminum fins fitted to durable seamless cop-per tubes. Fins are strengthened to resist bending and areequipped with collars that grip tubing for maximum contactarea. Flared tubing connections and silver soldering providetight, leakproof joints. Long life copper tubing is corrosion-re-sistant and easy to field service. Coil is thoroughly factorytested under high pressure to insure leakproof construction.
Expansion Valve — Factory installed and piped. Dual cir-cuited coils have two expansion valves, one for each coil sec-tion. Valves are sized for best performance.
Refrigerant Piping Connections — Refrigerant line inlets areprovided on both sides of the cabinet. Refrigerant lines re-quire sweat connections and are made internal to the cabinet.
Air Filters — 1 inch (25 mm) thick throwaway fiberglass mediafilters are furnished as standard. Filter rack is adjustable to ac-commodate up to two inch (51 mm) thick throwaway or clean-able optional filters. Filter rack design permits quick and easyremoval of filters for servicing.
OPTIONAL ACCESSORIES (Must Be Ordered Extra)
EMD17M Series Economizer Damper Section (Optional) —Factory assembled and wired economizer dampers and con-trols are available for field installation. Heavy gauge steelcabinet has a baked-on enamel finish and is completely insu-lated with thick matte faced fiberglass insulation. Large re-movable panels on both sides of cabinet provide completeservice access. Mounting flanges provide ease of connectionto unit. Flanges on outdoor air opening and return air openingpermit easy duct connection. Economizer has mechanicallylinked outdoor air and recirculated air dampers. Formeddampers rotate smoothly in nylon bearings. Outdoor airdampers are reinforced and gasketed for tight seal and quietoperation. Damper linkage and shafts are plated. The posi-tioning of the dampers is accomplished by a 24 volt fully mod-ulating electronic spring return damper motor with adjust-able minimum position potentiometer and controlled by theroom thermostat, adjustable mixed air sensor and adjustableenthalpy control. The enthalpy control allows 0 to 100% out-door air to be used for ”free cooling” when outdoor tempera-ture and humidity are acceptable.
Differential Enthalpy Control (Optional For EMD17M-95 andEMD17M-135 only) — A solid-state return air enthalpy sensoris available to be used with the outdoor air enthalpy control todetermine which air has the lowest enthalpy. The air with thelowest enthalpy will be selected. Return air enthalpy sensor(54G44) field installs in the economizer damper section andmust be ordered extra.
Heat Pump Check Valve Kit (Optional) — Field installed kitcontains check valves with connecting tubing, sweat connec-tions. Kit must be ordered extra. See Specifications Table.
CBH17 Suspension Kits (Optional For CBH17-95V &CBH17-135V only) — Provides support of units in sus-pended horizontal applications. Kit consists of 2 angle ironchannels with holes at each end. CBH17-95V usesLB-50866CA (44F93), 60 inches (1.5 m) long, andCBH17-135V uses LB-50866CB (44F94), 72 inches (1.8 m)long. Kits are not available for the CBH17-185V &CBH17-275V models and must be field provided.
— 2 —
OPTIONAL ACCESSORIES (Must Be Ordered Extra)
EH17 Series Electric Heat (Optional) — Furnished in a sepa-rate add-on matching cabinet. Bolts, nuts and washers are fur-nished to secure cabinets together. Holes are pre-punched.Cabinet is constructed of heavy gauge galvanized steel with abaked-on enamel finish. Completely insulated with thick fiber-glass insulation. Removable panel permits service access.Electrical inlet provides wiring entry. Factory installed electricheaters are available in several sizes, see electric heat datatable. Helix wound nichrome heating elements are exposeddirectly in the air stream resulting in instant heat transfer, low-er coil temperatures and long service life. Elements are accu-rately located and insulated from the heavy gauge steel sup-port frame by high quality insulators. Time delays bring theelements on and off the line in sequence and equal incre-ments in response to demand with a time delay between eachelement. Elements are equipped with individual limit controlsproviding positive protection in case of excessive overheat-ing. Heaters may be two stage controlled with each stage be-ing energized only when required. Heaters must be orderedextra. Sub-fusing, contactors, control relays, 24 volt trans-former, terminal block and blower motor contactor are fur-nished as standard equipment.
HW17 Series Hot Water Heat (Optional) — Furnished in a sep-arate add-on matching cabinet. Bolts, nuts and washers arefurnished to secure cabinets together. Holes are pre-punched. Cabinet is constructed of heavy gauge galvanizedsteel with a baked-on enamel paint finish. Completely insu-lated with thick matte faced fiberglass insulation. Removablepanel permits service access. Piping inlets are furnished inboth sides of cabinet. Factory installed Lennox designed andbuilt coil has large face area, excellent heat transfer and lowair resistance. Constructed of precisely spaced ripple-edgedaluminum fins fitted to durable copper tubes. Fins areequipped with collars that grip tubing for maximum contactarea. Flared shoulder tubing connections and silver solderingprovide tight, leakproof joints. Long life copper tubing is easyto field service. Coil is thoroughly factory tested under highpressure to insure leakproof construction. Must be orderedextra. Valves and pumps must be furnished by installer.
Outdoor Thermostat (Optional) — An outdoor thermostatcan be used to lock out some of the heating elements on unitswhere two stage control is applicable. Outdoor thermostatmaintains the heating load on the low power input as long aspossible before allowing the full power load to come on theline. Thermostat LB-29740BA (56A87) and mounting boxM-1595 (31461) must be ordered extra.
SPG17 and SPGH17 Supply Air Plenum & Grille (Optional) —Constructed of heavy gauge galvanized steel with a baked-onenamel paint finish. Completely lined with thick matte facedfiberglass insulation. Equipped with anodized aluminumgrille with double deflection and four-way directional controlin vertical and horizontal planes for precise control of dis-charge air. Bolts, nuts and washers are furnished to secureplenum to cabinet. Must be ordered extra.
”00” Spacer Cabinets (Optional) — Matching ”00” emptyspacer cabinets give additional height required for plenumand grille in up-flo store cooler applications and providesspacing between unit and plenum and grille in horizontalinstallations not using an electric heat or hot water heat cabi-net. Constructed of heavy gauge galvanized steel with abaked-on enamel paint finish. Completely lined with thickmatte faced fiberglass insulation. Must be ordered extra.
RG17 Return Air Grille (Optional) — Anodized aluminumgrille field installs in return air opening of blower-coil unit.Must be ordered extra.
DRIVE KIT SELECTIONUsing Total Air Volume and System External Static Pressure needed for unit requirements,determine from blower performance table blower speed and blower motor output required.
UnitModel
Number
Drive KitModel
Number
*NominalMotorOutput
Blower SpeedRev./Min.
at 1440 Rev./Min.
ShippingWeight
Electrical Data380/420V — 50hz — 3 phase
Number Numberhp kW Motor Speed lbs. kg Full Load (A) Locked Rotor (A)
CB17-95VCBH17-95V
DKB17-95/135-1.5–5 1.5 1.1 600 — 780 42 19 2.7 17.8
CB17-135VCBH17-135V �DKB17-95/135-2–9 2 1.5 710 — 890 49 22 3.3 21.6
CB17-185VCBH17 185V
DKB17185/275-2–16 2 1.5 520 — 640 49 22 3.3 21.6CBH17-185VCB17-275V DKB17185/275-3–17 3 2.2 590 — 710 55 25 5.0 28.0CB17 275V
CBH17-275V DKB17185/275-5–18 5 3.7 700 — 850 74 34 7.8 50.0*Service Factor = 1.15�Drive Kit includes belt to be field installed in place of belt shipped in blower Coil unit.NOTE — Motors do not have internal overload protectors.NOTE — Magnetic Starters and Overload Protectors are available and must be ordered extra. See Lennox Price Book.
INSTALLATION CLEARANCES
Model NumberCB17-95V
CBH17-95VCB17-135V
CBH17-135VCB17-185V
CBH17-185VCB17-275V
CBH17-275V
Cabinet 0 inch (0 mm) 0 inch (0 mm) 0 inch (0 mm) 0 inch (0 mm)
Plenum 1 inch (25 mm) 1 inch (25 mm) 1 inch (25 mm) 1 inch (25 mm)
Duct *1 inch (*25 mm) **1 inch (**25 mm) *1 inch (*25 mm) *1 inch (*25 mm)
*Within 3 feet (90 cm) of the unit.**Within 4 feet (122 cm) of the unit.
— 3 —
SPECIFICATIONS
Model NumberCB17-95V
CBH17-95VCB17-135V
CBH17-135VCB17-185V
CBH17-185VCB17-275V
CBH17-275V
Nominal Cooling Capacity — Tons (kW) 7-1/2 (26) 10 (35) 15 (53) 20 (70)
Blower wheel nominal diameter x width — in. (mm) (1) 15 x 15 (381 x 381) (2)15 x 9 (381 x 229) (2) 15 x 11 (381 x 279) (2) 15 x 15 (381 x 381)
Blower motor output and blower drives See Drive Kit Table (shipped separately)
*Number and size of air filters
in. (2) 16 x 25 x 1(1) 20 x 25 x 1 (4) 16 x 25 x 1 (6) 16 x 20 x 1
(2) 16 x 25 x 1(6) 20 x 20 x 1(2) 20 x 25 x 1
*Number and size of air filters
mm (2) 406 x 635 x 25(1) 508 x 635 x 25 (4) 406 x 635 x 25 (6) 406 x 508 x 25
(2) 406 x 635 x 25(6) 508 x 508 x 25(2) 508 x 635 x 25
Condensate drain connection — in. (2) 1-1/4 (2) 1-1/4 (2) 1-1/4 (2) 1-1/4
female pipe thread mm (2) 31.8 (2) 31.8 (2) 31.8 (2) 31.8
Refrigerant HCFC-22
Net face area — ft.2 (m2) 7.98 (0.74) 10.07 (0.94) 17.38 (1.61) 23.16 (2.15)
Number of rows 4 4 4 4
Tube outside diameter — in. (mm) 3/8 (9.5) 3/8 (9.5) 1/2 (12.7) 1/2 (12.7)
Evapora-tor
Fins per inch (fins per m) 14 (551) 13 (512) 13 (512) 13 (512)torCoil Suction line connection — in. 1-3/8 1-3/8 (2) 1-1/8 (2) 1-3/8
outside diameter (sweat) mm 34.9 34.9 (2) 28.5 (2) 34.9
Liquid line connection — in. (2) 3/8 (2) 3/8 (2) 1/2 (4) 3/8qoutside diameter (sweat) mm (2) 9.5 (2) 9.5 (2) 12.7 (4) 9.5
**Shipping weight — lbs. (kg) Up-flow 350 (159) 418 (190) 720 (327) 815 (370)g g g(�2 packages) Horizontal 312 (142) 379 (172) 760 (345) 860 (390)
� Optional Accessories (Must Be Ordered Extra) �
Electric Heat Model Number EH17-95 EH17-135 EH17-185/275
Model Number HW17-95 (41F20) HW17-135 (41F21) HW17-185/275 (27G75)
Shipping weight — lbs. (kg) 95 (43) 104 (47) 160 (73)
��Heating capacity — Btuh (kW) 185 000 (54.2) 257 000 (75.3) 405 000 (118.7) 462 000 (135.4)
Hot Wa- Net face area — ft.2 (m2) 6.4 (0.59) 8.5 (0.79) 15.6 (1.45)
terCoil Tube outside diameter — in. (mm)
number of rows1/2 (12.7)
21/2 (12.7)
21/2 (12.7)
2
Fins per inch (fins per m) 12 (472) 12 (472) 12 (472)
Water line connections Inlet 1-3/8 (35) sweat 1-3/8 (35) sweat 1-5/8 (41) sweat
Outside diameter — in. (mm) Outlet 1-3/8 (35) sweat 1-3/8 (35) sweat 1-5/8 (41) sweat
Supply Air Plenum and GrilleUp-flow SPG17-95 (68F08)
124 lbs. (56 kg)SPG17-135 (68F09)
148 lbs. (67 kg)SPG17-185/275 (25G89)
242 lbs. (110 kg)pp y(shipping weight)
Horizontal SPGH17-95 (68F10)41 lbs. (19 kg)
SPGH17-135 (68F11)50 lbs. (23 kg)
SPGH17-185/275 (25G88)86 lbs. (39 kg)
Return Air Grille (shipping weight) RG17-95 (68F14)29 lbs. (13 kg)
RG17-135 (68F15)37 lbs. (17 kg)
RG17-185 (25G97)65 lbs. (29 kg)
RG17-275 (25G98)82 lbs. (37 kg)
Empty Spacer Cabinet (shipping weight) CB17-95-00 (50F06)55 lbs. (25 kg)
CB17-135-00 (50F07)60 lbs. (27 kg)
CB17-185/275-00 (27G76)82 lbs. (37 kg)
Economizer Dampers (shipping weight) EMD17M-95 (74G20)145 lbs. (66 kg)
EMD17M-135 (74G21)185 lbs. (84 kg)
EMD17M-185 (43G63)395 lbs. (179 kg)
EMD17M-185 (43G64)542 lbs. (264 kg)
Differential Enthalpy Control 54G44
CBH17 Horizontal Suspension Kit (shipping weight) LB-50866CA (44F93)21 lbs. (10 kg)
LB-50866CB (44F94)25 lbs. (11 kg) Not Available
Heat Pump Check Valve Kit LB-51486CA (53F21) LB-51486CA (53F21) LB-55674CA (29G19) LB-51486CB (29G20)
*Standard filters are 1 inch (25 mm) thick. 2 inch (51 mm) filters may also be used.**Weight does not include motor and drives.�Packages consist of: blower coil unit and drive kit with motor and drives.��Rated at 180�F (82�C) supply water temperature, 70�F (21�C) entering air temperature, 20�F (11�C) water temperature drop and 450 cfm air volume per ton (60 L/sair volume per kW) of cooling capacity. See Hot Water Capacity Curves for heating capacities at different conditions.
— 4 —
BLOWER DATA
CB17-95V AND CBH17-95V BLOWER PERFORMANCE
AirSTATIC PRESSURE EXTERNAL TO UNIT — Inches Water Gauge (Pa)
AirVolume
cfm0 (0) 0.2 (50) 0.4 (100) 0.6 (150) 0.8 (200) 1.0 (250) 1.25 (310) 1.5 (375)
cfm(m3/s) Rev/ hp
Min (W)Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
2000(0.95)
0.25375
(186)0.35
440(261)
0.405150
(298)0.50
590(373)
0.60650
(448)0.75
720(560)
1.05790
(783)1.30
850(970)
2500(1.20)
0.35425
(261)0.40
500(298)
0.50560
(373)0.65
630(485)
0.80700
(597)1.00
760(746)
1.30830
(970)1.40
880(1044)
3000(1.40)
0.55490
(410)0.60
560(448)
0.75625
(560)0.95
690(709)
1.15750
(858)1.30
800(970)
1.55860
(1156)1.80
925(1343)
3500(1.65)
0.85575
(634)0.95
620(709)
1.05685
(783)1.30
740(970)
1.50800
(1119)1.65
840(1231)
1.95910
(1455)2.20
970(1641)
4000(1.90)
1.30650
(970)1.40
700(1044)
1.60750
(1194)1.75
800(1306)
1.95850
(1455)2.15
900(1604)
- - - - - - - -
NOTE — All data is measured external to the unit with air filters in place.Legend — Rev/Min = Blower speed required. W (HP) = Motor output required.
CB17-135V AND CBH17-135V BLOWER PERFORMANCE
AirSTATIC PRESSURE EXTERNAL TO UNIT — Inches Water Gauge (Pa)
AirVolume
cfm0 (0) 0.2 (50) 0.4 (100) 0.6 (150) 0.8 (200) 1.0 (250) 1.25 (310) 1.5 (375)
cfm(m3/s) Rev/ hp
Min (W)Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
3000(1.40)
0.30425
(224)0.45
500(336)
0.60575
(448)0.80
650(597)
1.05725
(783)1.30
790(970)
1.55860
(1156)1.85
925(1380)
3500(1.65)
0.50475
(373)0.60
550(448)
0.80620
(597)1.05
680(793)
1.25750
(933)1.55
820(1156)
1.95900
(1455)2.10
950(1567)
4000(1.90)
0.75525
(560)0.85
595(634)
1.10665
(821)1.30
725(970)
1.55790
(1156)1.90
850(1417)
2.15920
(1604)- - - -
4500(2.10)
1.00580
(746)1.15
650(858)
1.40715
(1044)1.70
755(1268)
1.95840
(1455)2.25
890(1679)
- - - - - - - -
5000(2.35)
1.40650
(1044)1.55
710(1156)
1.80760
(1343)2.15
825(1604)
- - - - - - - - - - - - - - - -
NOTE — All data is measured external to the unit with air filters in place.Legend — Rev/Min = Blower speed required. W (HP) = Motor output required.
CB17-185V AND CBH17-185V BLOWER PERFORMANCE
AirSTATIC PRESSURE EXTERNAL TO UNIT — Inches Water Gauge (Pa)
AirVolume
cfm0.1 (25) 0.2 (50) 0.3 (75) 0.4 (100) 0.5 (125) 0.6 (150) 0.7 (175) 0.8 (200) 0.9 (225) 1.0 (250) 1.25 (310)
cfm(m3/s) Rev/ hp
Min (W)Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
5000(2.35) - - - - - - - -
1.00500
(746)1.05
530(783)
1.20560
(895)1.50
630(1119)
1.55640
(1156)1.65
660(1231)
1.75685
(1306)1.90
720(1417)
2.25800
(1679)
5500(2.60) - - - -
1.05495
(783)1.20
525(895)
1.35555
(1007)1.50
585(1119)
1.65635
(1231)1.70
650(1268)
1.85680
(1380)2.05
710(1529)
2.20740
(1641)2.55
825(1902)
6000(2.85)
1.20490
(895)1.30
520(970)
1.45550
(1082)1.60
580(1194)
1.75610
(1306)1.90
640(1417)
2.10675
(1567)2.20
705(1641)
2.35730
(1753)2.50
760(1865)
2.90840
(2163)
6500(3.05)
1.45515
(1082)1.60
550(1194)
1.75575
(1306)1.90
610(1417)
2.05635
(1529)2.25
670(1679)
2.35700
(1753)2.50
725(1865)
2.65750
(1977)2.75
780(2052)
3.30870
(2462)
7000(3.30)
1.75550
(1306)1.90
575(1417)
2.05605
(1529)2.25
635(1679)
2.35665
(1753)2.55
690(1902)
2.65720
(1977)2.85
745(2126)
3.00775
(2238)3.20
810(2387)
- - - -
7500(3.55)
2.05575
(1529)2.25
605(1679)
2.55635
(1828)2.45
660(1902)
2.75690
(2052)2.90
720(2163)
3.05740
(2275)3.25
775(2425)
3.40800
(2536)3.55
835(2648)
- - - -
8000(3.80)
2.40605
(1790)2.60
635(1940)
2.80660
(2089)2.95
690(2201)
3.15720
(2350)3.30
740(2462)
3.50775
(2611)3.65
800(2723)
3.85835
(2872)4.10
870(3059)
- - - -
NOTE — All data is measured external to the unit with air filters in place.Legend — Rev/Min = Blower speed required. W (HP) = Motor output required.
— 5 —
BLOWER DATACB17-275V AND CBH17-275V BLOWER PERFORMANCE
AirSTATIC PRESSURE EXTERNAL TO UNIT — Inches Water Gauge (Pa)
AirVolume
cfm0.1 (25) 0.2 (50) 0.3 (75) 0.4 (100) 0.5 (125) 0.6 (150) 0.7 (175) 0.8 (200) 0.9 (225) 1.0 (250) 1.25 (310)
cfm(m3/s) Rev/ hp
Min (W)Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
Rev/ hpMin (W)
6500(3.05)
1.35515
(1007)1.45
535(1082)
1.70570
(1268)1.80
585(1343)
1.90615
(1417)2.00
635(1492)
2.25670
(1679)2.30
690(1716)
2.45720
(1828)2.50
740(1865)
2.95805
(2201)7000(3.30)
1.55525
(1156)1.70
545(1268)
1.85575
(1380)2.00
600(1492)
2.15625
(1604)2.30
650(1716)
2.45680
(1828)2.55
705(1902)
2.70730
(2014)2.80
755(2089)
3.25820
(2425)
7500(3.55)
1.70530
(1268)1.85
555(1380)
2.05585
(1529)2.25
615(1679)
2.30630
(1716)2.55
665(1902)
2.65685
(1977)2.80
720(2089)
2.90740
(2163)3.15
770(2350)
3.60825
(2686)8000(3.80)
1.90540
(1417)2.15
565(1604)
2.25590
(1679)2.45
625(1828)
2.65650
(1977)2.80
675(2089)
2.95705
(2201)3.05
730(2275)
3.35760
(2499)3.40
785(2536)
3.95840
(2947)
8500(4.00)
2.15555
(1604)2.30
580(1714)
2.55610
(1902)2.70
630(2014)
2.90665
(2163)3.10
690(2313)
3.20720
(2387)3.35
745(2499)
3.60775
(2686)3.80
805(2835)
4.40855
(3282)
9000(4.25)
2.35565
(1753)2.60
595(1940)
2.85630
(2126)3.05
655(2275)
3.20680
(2387)3.40
710(2536)
3.55735
(2648)3.75
760(2798)
4.00795
(2894)4.20
820(3133)
4.70870
(3506)9500(4.50)
2.65585
(1977)2.95
620(2201)
3.15640
(2350)3.05
670(2275)
3.55700
(2648)3.75
730(2798)
3.90755
(2909)4.15
785(3096)
4.40815
(3282)4.65
840(3469)
4.90880
(3655)
10 000(4.70)
3.05610
(2275)3.30
635(2462)
3.45660
(2574)3.30
690(2462)
3.90720
(2909)4.10
750(3059)
4.35775
(3245)4.55
805(3394)
4.85835
(3618)5.15
860(3842)
- - - -
10 500(4.95)
3.35625
(2499)3.55
655(2648)
3.80685
(2835)4.05
715(3021)
4.30745
(3208)4.60
775(3432)
4.75800
(3544)5.05
830(3767)
5.40860
(4028)5.70
880(4252)
- - - -
NOTE — All data is measured external to the unit with air filters in place.Legend — Rev/Min = Blower speed required. W (HP) = Motor output required.
SUPPLY AIR PLENUM AND GRILLE AIR THROW DATA
Blower Coil and Supply Air Volume*Effective Throw — ft. (m)
Blower Coil and SupplyPlenum and Grille
M d l N b
Air Volume�10 ft. (3.0 m) Ceiling
Model Numbercfm m3/s Front of Unit 45� From Unit
�
2000 0.95 40 (12.2) 31 (9.4)�CB17-95V With
SPG17 95 or2500 1.20 46 (14.0) 36 (11.0)
SPG17-95 orCBH17-95V With 3000 1.40 53 (16.2) 41 (12.5)CBH17 95V With
SPGH17-95 3500 1.65 56 (17.1) 45 (13.7)
4000 1.90 63 (19.2) 50 (15.2)
3000 1.40 50 (15.2) 35 (10.7)
�CB17-135V With 3500 1.65 55 (16.8) 40 (12.2)�CB17 135V With
SPG17-135 or 4000 1.90 61 (18.6) 44 (13.4)CBH17-135V With
SPGH17 1354500 2.10 67 (20.4) 50 (15.2)
SPGH17-1355000 2.35 71 (21.6) 56 (17.1)
5500 2.60 74 (22.6) 61 (18.6)
5000 2.35 30 (9.1) 19 (5.8)
�
5500 2.60 31 (9.4) 19 (5.8)�CB17-185V WithSPG17 185/275 or
6000 2.85 35 (10.7) 22 (6.7)SPG17-185/275 orCBH17-185V With 6500 3.05 36 (11.0) 22 (6.7)CBH17 185V WithSPGH17-185/275 7000 3.30 36 (11.0) 22 (6.7)
7500 3.55 39 (11.9) 24 (7.3)
8000 3.80 41 (12.5) 26 (7.9)
6500 3.05 36 (11.0) 22 (6.7)
7000 3.30 36 (11.0) 22 (6.7)
�
7500 3.55 39 (11.9) 24 (7.3)�CB17-275V WithSPG17 185/275 or
8000 3.80 41 (12.5) 26 (7.9)SPG17-185/275 orCBH17-275V With 8500 4.00 43 (13.1) 27 (8.2)CBH17 275V WithSPGH17-185/275 9000 4.25 46 (14.0) 29 (8.8)
9500 4.50 49 (14.9) 30 (9.1)
10 000 4.70 53 (16.2) 33 (10.1)
10 500 1.95 55 (16.8) 34 (10.4)*Effective throw is terminated at a point where conditioned air reaches a level of 3 feet (90 cm) above the floor or where velocityhas decreased to 50 feet per minute (0.25 m/s.�Ceiling height not applicable to CB17 Up-Flow models.
— 6 —
BLOWER DATA
ACCESSORY AIR RESISTANCE — CB17-95V, CBH17-95V, CBH17-135V AND CB17-135V
M d l Air VolumeTotal Resistance — inches water gauge (Pa)
ModelNumber
Air VolumeHW17 Hot Water Coil EMD17M Economizer Dampers
Number
cfm m3/s HW17-95 HW17-135 EMD17M-95 EMD17-135
2000 0.95 0.13 (32) - - - - 0.02 (5) - - - -
CB17 95V2500 1.20 0.16 (40) - - - - 0.04 (10) - - - -
CB17-95VCBH17-95V 3000 1.40 0.18 (45) - - - - 0.07 (17) - - - -CBH17 95V
3500 1.65 0.20 (50) - - - - 0.09 (22) - - - -
4000 1.90 0.24 (60) - - - - 0.12 (30) - - - -
3000 1.40 - - - - 0.14 (350 - - - - 0.03 (70
CB17 135V3500 1.65 - - - - 0.17 (42) - - - - 0.05 (12)
CB17-135VCBH17-135V 4000 1.90 - - - - 0.18 (45) - - - - 0.07 (17)CBH17 135V
4500 2.10 - - - - 0.20 (50) - - - - 0.09 (22)
5000 2.35 - - - - 0.24 (60) - - - - 0.13 (32)NOTE — Electric heat section, plenum and grilles have no appreciable air resistance.
ACCESSORY AIR RESISTANCE — CB17-185V, CBH17-185V, CBH17-275V AND CB17-275V
M d l Air VolumeTotal Resistance — inches water gauge (Pa)
ModelNumber
Air VolumeHW17 Hot Water Coil EMD17M Economizer Dampers
Number
cfm m3/s HW17-185/275 EMD17M-185 EMD17-275
5000 2.35 0.08 (20) 0.04 (10) - - - -
5500 2.60 0.10 (25) 0.05 (12) - - - -
CB17 185V6000 2.85 0.11 (27) 0.06 (15) - - - -
CB17-185VCBH17-185V 6500 3.05 0.13 (32) 0.07 (17) - - - -CBH17 185V
7000 3.30 0.15 (37) 0.08 (20) - - - -
7500 3.55 0.17 (42) 0.09 (22) - - - -
8000 3.80 0.18 (45) 0.10 (25) - - - -
6500 3.05 0.13 (32) - - - - 0.04 (10)
7000 3.30 0.15 (37) - - - - 0.05 (12)
7500 3.55 0.17 (42) - - - - 0.06 (15)
CB17 275V8000 3.80 0.18 (45) - - - - 0.07 (17)
CB17-275VCBH17-275V 8500 4.00 0.21 (52) - - - - 0.08 (20)CBH17 275V
9000 4.25 0.23 (57) - - - - 0.08 (20)
9500 4.50 0.25 (62) - - - - 0.09 (22)
10 000 4.70 0.27 (67) - - - - 0.10 (25)
10 500 4.95 0.30 (75) - - - - 0.11 (27)NOTE — Electric heat section, plenum and grilles have no appreciable air resistance.
HOT WATER COIL PRESSURE DROP
Flow Rate Pressure Drop — feet of water (kPa)
gpm L/s HW17-95 HW17-135 HW17-185/275
15 0.95 0.93 (3.0) 1.18 (3.5) - - - -
20 1.25 1.56 (4.5) 1.99 (6.0) 0.55 (1.5)
25 1.60 2.33 (7.0) 2.97 (9.0) 0.82 (2.5)
30 1.90 3.24 (9.5) 4.13 (12.5) 1.14 (3.5)
35 2.20 4.27 (12.5) 5.44 (16.0) 1.50 (4.5)
40 2.50 5.44 (16.0) 6.92 (20.5) 1.91 (5.5)
45 2.85 6.72 (20.0) 8.56 (25.5) 2.36 (7.0)
50 3.15 - - - - - - - - 2.86 (8.5)
55 3.45 - - - - - - - - 3.39 (10.0)
60 3.80 - - - - - - - - 3.97 (12.0)
65 4.10 - - - - - - - - 4.58 (13.5)
70 4.40 - - - - - - - - 5.23 (15.5)
— 7 —
OPTIONAL ELECTRIC HEAT DATA
NOTE — Refer to local electrical codes to determine wire, fuse and disconnect requirements. Use wires suitable for at least 75�C (167�F).
ECH17 ELECTRIC HEAT FOR CB17/CBH-95V and -135V
Electric HeatNumber Number
HeatingElectric HeatModel Number
and
Numberof
Numberof
VoltsInput
gCapacity
andShipping Weight
oElements
oSteps
Input
kW Btuh
ECH17-95-15 380 9.4 32 100ECH17 95 15(63F22)
170 lb (77 k )1 2 400 10.4 35 500
170 lbs. (77 kg)1 2
420 11.2 38 200ECH17-95-30 380 18.8 64 100
(63F23)176 lb (80 k )
2 1 400 20.8 71 000176 lbs. (80 kg) 420 22.4 76 400ECH17-95-45 380 28.2 96 100
(63F24)182 lb (83 k )
3 �2 400 31.3 106 800182 lbs. (83 kg) 420 33.6 114 600ECH17-135-15 380 9.4 32 100
(63F34)193 lb (88 k )
1 1 400 10.4 38 200193 lbs. (88 kg) 420 11.2 38 200ECH17-135-30 380 18.8 64 100
(63F35)200 lb (91 k )
2 � 400 20.8 71 000200 lbs. (91 kg) 420 22.4 76 400ECH17-135-45 380 28.2 96 200
(63F36)207 lb (94 k )
3 �2 400 31.3 106 800207 lbs. (94 kg) 420 33.6 114 600
ECH17-135-60 380 37.6 128 300ECH17 135 60(63F37) 4 �2 400 41.7 142 300
214 lbs. (97 kg)�
420 45.0 153 600�May be used with two stage control.
ECH17 ELECTRIC HEAT FOR CB17/CBH-185V and -275V
Electric HeatNumber Number
HeatingElectric HeatModel Number
d
Numberof
Numberof
VoltsI t
gCapacity
andShipping Weight
oElements
oSteps
InputkW Btuh
ECH17 185/275 15380 9.4 32 100
ECH17-185/275-15(27G01)
193 lbs (88 kg)1 1 400 10.4 35 500
193 lbs. (88 kg)420 11.2 38 200
ECH17 185/275 30380 18.8 64 100
ECH17-185/275-30(27G02)
200 lbs (91 kg)2 � 400 20.8 71 000
200 lbs. (91 kg)420 22.4 76 400
ECH17 185/275 45380 28.2 96 200
ECH17-185/275-45(27G03)
207 lbs (94 kg)3 �2 400 31.3 106 800
207 lbs. (94 kg)420 33.6 114 600
ECH17 185/275 60380 37.6 128 300
ECH17-185/275-60(27G04)
214 lbs (97 kg)4 �2 400 41.7 142 300
214 lbs. (97 kg)420 45.0 153 600
�May be used with two stage control.
GUIDE SPECIFICATIONS
Prepared for the guidance of architects, consulting engineers andmechanical contractors.
General — Furnish and install a blower-coil-filter unit. The unit shallbe a standard product of a firm regularly engaged in the manufactureof heating-cooling equipment.
The installed weight shall not be more than . . . . . . . lbs. (kg) Unit shallhave a width of not more than . . . . . . . inches (mm), a depth of notmore than . . . . . . . inches (mm) and an overall height of not more than .. . . . . . inches (mm).
The equipment shall be shipped assembled ready for necessary fieldconnections. Blower motor and pulley shall be shipped separate andfield installed. CB17 models shall be capable of up-flo air distribution.CBH17 models shall have horizontal air distribution.
Cooling System — The total certified cooling capacity shall not beless than . . . . . . . . Btuh (kW) with an evaporator air volume of . . . . . . .cfm (m3/s), an entering wet bulb temperature of . . . . . . . �F ( �C) and . . . . . . . �F ( �C) coil refrigerant evaporating temperature.
The coil shall be non-ferrous construction with aluminum fins ma-chine fitted to copper tubes. The coil shall be dual circuit with each cir-cuit having an expansion valve. Coil shall be factory pressure leaktested. Coil face area shall be not less than . . . . . . . sq. ft. (m2).
Heat Pump Heating System — The total certified heating capacityshall not be less than . . . . . . . Btuh (kW) with an indoor coil air volumeof . . . . . . .. cfm (m3/s), an entering dry bulb temperature of . . . . . . . �F( �C) and a condensing temperature of . . . . . . . �F ( �C).
Air Movers — Centrifugal conditioned air blowers shall have stati-cally and dynamically balanced, forwardly curved, double inletblower wheels, permanently lubricated bearings, adjustable beltdrives and be capable of delivering . . . . . . . cfm at an external staticpressure of . . . . . . .inches water gauge (Pa), requiring not more than. . . . . . . bhp (W) and . . . . . . . rpm. CB17/CBH17-95V models shall beequipped with a single blower. CB17/CBH17-135V, 185V and 275Vmodels shall have dual blowers.
Cabinet — The unit cabinet shall be constructed of galvanized steelwith a baked-on enamel finish. Panels shall be insulated with not lessthan one inch thick fiberglass insulation. Cabinet shall be equippedwith large removable panels providing service access to interior. In-lets shall be provided for refrigerant line and power connection entry.Dual drain connections shall be accessible external to the cabinet.
Air Filters — One inch (25 mm) thick throwaway filters furnished shallhave not less than . . . . . . . sq. ft. (m2) of area. Filter rack shall be capa-ble of holding optional two inch (51 mm) thick throwaway or clean-able filters.
OPTIONAL ACCESSORIES
Additive Electric Heat — The certified total heating capacity output shallbe . . . . . . . . Btuh with . . . . . . . . kw input at . . . . . . . . volts power supply.Optional electric heaters shall be available in a separate matchingcabinet. Heating elements shall be nichrome bare wire exposed di-rectly to the air stream. Time delays shall bring the elements on andoff in sequence with a time delay between each element. Limit con-trols shall provide overload and short circuit protection. Cabinet shallbe constructed of galvanized steel with a baked-on enamel paint fin-ish and insulated with fiberglass insulation. Shall have removable ac-cess panel and electrical inlets.Additive Hot Water Heat — The certified total heating capacity outputshall be . . . . . . . . Btuh (kW) with a heating coil air volume of . . . . . . . cfm(m3/s), at water entering temperature of . . . . . . . �F ( �C) and a flow rateof . . . . . . . gpm (L/s) and an entering air temperature of . . . . . . . �F ( �C).Optional hot water coil shall be available in a separate matching cabi-net. Cabinet shall be constructed of galvanized steel with a baked-onenamel finish and insulated with fiberglass insulation. Shall have re-movable access panel and piping inlet openings. The coil shall benon-ferrous construction with aluminum fins mechanically bondedto copper tubes. Coil shall be factory pressure leak tested. Coil facearea shall be not less than . . . . . . . sq. ft (m2).Economizer Damper Section — Furnish and install complete withcontrols an optional air mixing damper assembly including outdoorair and recirculated air dampers. The assembly shall provide for theintroduction of outside air for minimum ventilation and free cooling.The assembly shall be furnished in a fully insulated heavy gauge gal-vanized steel cabinet with baked-on enamel finish. The damper mo-tor shall be 24 volt, fully modulating electronic spring return. Controlsshall include adjustable mixed air sensor, adjustable minimum posi-tion potentiometer, and adjustable enthalpy control. Optional differ-ential enthalpy control (return air sensor) shall be available forEMD17M-95 and EMD17M-135 models.Supply Air Plenum and Grille — Optional plenum and grille shall beconstructed of galvanized steel with baked-on enamel paint finishand insulated with fiberglass insulation. Shall be equipped with an-odized aluminum discharge air grille with double deflection and four-way directional control in the vertical and horizontal planes.Spacer Cabinets — Optional empty cabinets shall match cabinet sec-tions in size and provide necessary spacing between cabinet sectionsfor varying applications. Shall be constructed of galvanized steel withbaked-on enamel paint finish and insulated with fiberglass insulation.Return Air Grille — Optional anodized grille shall be available for fieldaddition to blower-coil unit.Suspension Kit — Kit shall be available for CBH17-95V andCBH17-135V models in suspended horizontal applications.
— 8 —
DIMENSIONS — inches (mm)
CB17-95V AND CB17-135V HORIZONTAL MODELS52 (1321)
27(686)
64 (1626)
27(686)
INLET END
SUPPLY END(CB17-135V)
SUPPLY END(CB17-95V)
ELECTRICAL INLET(Either Side)
LIQUID LINEINLETS (2)
(Either Side)
SUCTION (VAPOR)LINE INLETS(Either Side)
AIR FILTERS
16-3/8(416)
18-5/8(473)
12-1/4(311) SUPPLY
AIROPENING
12-7/8(327)
12-7/8(327)
9-1/2(241)
7-3/4(197)
16-3/8(416)
SUPPLY AIROPENINGS ELECTRICAL INLET
(Electric Heat)
47-7/8 (1216) — CB17-95V
59-7/8 (1521) — CB17-135V
2-1/16(52)
24-1/2(622)
1-1/2(38)
RETURNAIR
OPENING
2-1/16(52)
49(1245)
52-1/2(1308)
8 (203)
6 (152)
2 (51)
12-7/8(352)
EXTERNAL STATICPRESSURE TEST HOLE
INDOOR COIL
DRIVE END VIEW
AIR FLOW27 (686)
1 (25) 1 (25)
ELECTRICAL INLET(Electric Heat)
2-1/2(64)
AIRFLOW
BLOWER
45-1/2 (1156) — CB17-95V
57-1/2 (1461) — CB17-135V
2-1/2(64)
3/4 (19) 3/4 (19)
2-1/2(64) 4
(102)
2(51)
4(102)
CONDENSATE DRAIN (Either Side)12-1/4(311)
CB17-185V AND CB17-275V HORIZONTAL MODELS
85 (2159)
19(483)
19(483)
17-3/8(441)
9-3/8(238) 16-5/8
(422)
1 (25)
SUPPLY AIROPENINGS
ELECTRICALINLET
(Electric Heat)
SUPPLY END
AIR FLOW
DRIVE END VIEW
LIQUID LINEINLETS
(Either Side)
1-7/8(48)10-1/2
(267)
D
F
B E
C
C
F
10-5/8(207)
RETURNAIR
OPENING
81-3/4 (2076)
1-5/8(41)
1-5/8(41)
33-1/8(841)
CB17-185VONLY
7/8(22)
10(254)
42-1/8(1070)
CB17-275VONLY
7/8(22)
1 (25)
75-1/2 (1918)
4(102)
4(102)
3/4(19)
3/4(19)
44(1118)
3(76)
47(1194)
SUCTION(VAPOR)
LINE INLETS(Either Side)
INLET VIEW
AIR FLOW
ELECTRICALINLET
INDOOR COIL
AIR FILTERS
CONDENSATEDRAIN
(Either Side)
BLOWERS
A
Model NoA B C D E F
Model No.in. mm in. mm in. mm in. mm in. mm in. mm
CB17-185V 35 889 18-3/8 467 2-1/2 57 12-1/2 318 22-5/8 575 1-1/4 32
CB17-275V 44 1118 22-3/4 578 2–5/8 67 14-1/4 362 22-1/2 572 4-7/8 124
— 9 —
DIMENSIONS — inches (mm)
CBH17-95V AND CBH17-135V HORIZONTAL MODELS52
(1321)
27(686)16-3/8
(416)18-5/8(473)
12-1/4(311)
SUPPLYAIR
OPENING
64(1626)
27(686)
12-7/8(327)
12-7/8(327)
9-1/2(241)
9-1/2(241)
16-3/8(416)
2-1/4(57)
2-1/4(57) SUPPLY AIR
OPENINGSELECTRICAL
INLET(Electric Heat)
ELECTRICALINLET
(Electric Heat)
AIR
FLOW
47-7/8 (1216) — CBH17-95V
59-7/8 (1521) — CBH17-135V
2-1/16(52)
2-1/16(52)
24-1/2(622)
1-1/4(32)
1-1/4(32)
RETURNAIR
OPENING
IND
OO
R C
OIL
INLET END
SUPPLY END(CBH17-135V)
SUPPLY END(CBH17-95V)
DRIVE END VIEW
36(914)
ELECTRICAL INLET(Either Side)
LIQUID LINEINLETS (2)
(Either Side)
SUCTION (VAPOR)LINE INLET(Either Side)
AIR FILTERS
CONDENSATE DRAIN(Either Side)
2 (51)
6 (152)
6 (152)
2 (51)
12-3/8(314)
13-1/4(337)
EXTERNALSTATIC
PRESSURETEST HOLE
AIRFLOW
BLOWERS
CBH17-185V AND CBH17-275V HORIZONTAL MODELS
85 (2159)
19(483)
19(483)
17-3/8(441)
9-3/8(238)
16-5/8(422)
1 (25) SUPPLY AIROPENINGS
ELECTRICALINLET
(Electric Heat)
AIR
FLOW
82 (2083)1-1/2(38)
1-1/8(29)
7/8(22)
RETURNAIR
OPENING
INLET END
SUPPLY END
DRIVE END VIEW
44(1118)
ELECTRICAL INLET (Either Side) LIQUID LINE INLETS(Either Side)
SUCTION (VAPOR)LINE INLETS(Either Side)
AIR FILTERS
CONDENSATE DRAIN(Either Side)
7/8 (22)
10-1/2(267)
1-1/2(38)
G
A
F
E
B D
C
C
E
10-5/8(207)
AIRFLOW
BLOWERS
Model NoA B C D E F G
Model No.in. mm in. mm in. mm in. mm in. mm in. mm in. mm
CBH17-185V 35 889 18-3/8 467 2-1/4 57 22-5/8 575 1-1/4 32 13-1/8 333 33 838
CBH17-275V 44 1118 22-11/16 576 2-5/8 67 22-7/16 570 4-7/8 124 14-7/8 378 42 1067
— 10 —
OPTIONAL ACCESSORY DIMENSIONS — inches (mm)
EH17-95 AND EH17-135 ELECTRIC HEAT SECTION
A A
BC
1 (25)
24(610)
17-5/8(448)
D19-1/2(495)
1 (25)
OUTLET VIEWINLET VIEW FRONT VIEW
OUTDOORAIR
OPENING
INLETAIR
OPENING AIR
FLOW
ELECTRICINLETS
WIRING OUTLET(To Blower Motor)
19 (483) 7/8(22)
27(686)
Model NoA B C D
Model No.in. mm in. mm in. mm in. mm
EH17-95 52 1321 29-7/8 759 14-9/16 370 21-1/16 535
EH17-135 64 1626 39-7/8 1013 18-1/8 470 37-15/16 948
EH17-185/275 ELECTRIC HEAT SECTION
1 (25)
29-7/8(759)
20-1/4(514)
OUTLET VIEWINLET VIEW FRONT VIEW
INLET AIROPENING AIR
FLOW
ELECTRICINLETS
14(356)
1(25)
69-7/8(1775)OPENING
OUTDOOR AIR
35(889)
85 (2159)85 (2159)
20-1/2(521)
20-1/2(521)
14-1/2(368)
14-1
/8 (
359)
16-7/8(429)
WIRING OUTLET(To Blower Motor)
1 (25)
HW17 SERIES HOT WATER HEAT SECTION
OUTDOOR AIROPENING
B
A
C
D
F
14(356)
OUTLET VIEW
1 (25)
J
INLET AIROPENING
A
C
D
INLET VIEW
1 (25)
GH
AIR
FLOW
FRONT VIEW
HO
T W
AT
ER
CO
IL
K
L
MWATER INLET(EITHER SIDE)
WATER OUTLET(EITHER SIDE)
Model No. A B C D E F G H J K L M
HW17-95in. 52 27 41-1/2 25 50 9-1/2 1 1 1 3 2-3/8 4
HW17-95mm 1321 686 1054 635 1270 241 25 25 25 76 60 102
HW17-135in. 64 27 53-1/2 25 62 9-1/2 1 1 1 3 2-3/8 4
HW17-135mm 1626 686 1359 635 1575 241 25 25 25 76 60 102
HW17-185/275in. 85 35 69 33 70 13 13 2 3 2-1/4 2 2-3/4
HW17-185/275mm 2159 889 1753 838 1778 330 330 51 76 57 51 70
— 11 —
OPTIONAL ACCESSORY DIMENSIONS — inches (mm)
CB17-00 SERIES EMPTY SPACER CABINETS
OUTDOOR AIROPENING
B
A
C
D
F
14(356)
OUTLET VIEW
1 (25)
J
INLET AIROPENING
A
E
D
INLET VIEW
1 (25)
GH
AIR
FLOW
FRONT VIEW
Model NoA B C D E F G H J
Model No.in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm
CB17-95-00 52 1321 27 686 41-1/2 1054 25 635 50 1270 9-1/2 241 1 25 1 25 1 25
CB17-135-00 64 1626 27 686 53-1/2 1359 25 635 62 1575 9-1/2 241 1 25 1 25 1 25
CB17-185/275-00 85 2159 35 889 69 1753 33 838 70 1778 13 330 13 330 2 51 3 76
EMD17 SERIES ECONOMIZER DAMPERS
SIDE VIEW
AIR
OUTDOOR
OUTDOORAIR
DAMPERS
C
C A
RETURN AIR
B
E
F
D
B
E
F
D
1 (25) 1 (25)
1 (25)
1 (25)
DAMPERMOTOR
RECIRCULATEDAIR
DAMPERS
END VIEW
TOP VIEW
NOTE — Economizer section may be rotated180� for bottom return air connection.
SUPPLYAIR
TOUNIT
Model NoA B C D E F
Model No.in. mm in. mm in. mm in. mm in. mm in. mm
EMD17-95 48 1219 36 914 25 635 6 152 18 457 3-1/2 89
EMD17-135 60 1524 48 1219 25 635 6 152 18 457 3-1/2 89
EMD17-185 83 2108 60 1524 33 838 11-1/2 292 24 610 4-1/2 114
EMD17-275 83 2108 60 1524 42 1067 11-1/2 292 30 762 6 152
— 12 —
DIMENSIONS — inches (mm)
CB17 UP-FLOW MODELS WITH OPTIONAL ACCESSORY SECTIONS
Model NoGrille Free Area
Model No.sq. ft. m2
Supply SPG17-95 4.5 0.42SupplyAir
G illSPG17-135 5.6 0.52
Grille SG17-185/275 9.7 0.90
RG17-95 7.3 0.68Return
AirRG17-135 9.0 0.84
AirGrille RG17-185 16.5 1.53
RG17-275 21.2 1.97
Model NoA B C D E F G H
Model No.in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm
CB17-95V Basic Unit 51-1/2 1308 – – – – – – – – – – – – – – – – – – 52 1321 27 686 – – – – – – – – – – – –
CB17-135V Basic Unit 51-1/2 1308 – – – – – – – – – – – – – – – – – – 64 1626 27 686 – – – – – – – – – – – –
CB17-185V Basic Unit 47 1194 – – – – – – – – – – – – – – – – – – 85 2159 35 889 – – – – – – – – – – – –
CB17-275V Basic Unit 47 1194 – – – – – – – – – – – – – – – – – – 85 2159 44 1118 – – – – – – – – – – – –
EH17-95 Electric Heat Section – – – – – – 19 483 – – – – – – 94-1/2 2400 – – – – – – – – – – – – 27 686 52 1321
EH17-135 Electric Heat Section – – – – – – 19 483 – – – – – – 94-1/2 2400 – – – – – – – – – – – – 27 686 64 1626
EH17-185/275 Electric Heat Section – – – – – – 14 356 – – – – – – 91 2311 – – – – – – – – – – – – 35 889 85 2159
HW17-95 or CB17-95-00 – – – – – – 14 356 – – – – – – 89-1/2 2273 – – – – – – – – – – – – 27 686 52 1321
HW17-135 or CB17-135-00 – – – – – – 14 356 – – – – – – 89-1/2 2273 – – – – – – – – – – – – 27 686 64 1626
HW17-185/275 or CB17-185/275-00 – – – – – – 14 356 – – – – – – 91 2311 – – – – – – – – – – – – 35 889 85 2159
SPG17-95 Supply Air Plenum & Grille – – – – – – – – – – – – 24 610 – – – – – – – – – – – – – – – – – – 27 686 52 1321
SPG17-135 Supply Air Plenum & Grille – – – – – – – – – – – – 24 610 – – – – – – – – – – – – – – – – – – 27 686 64 1626
SPG17-185/275 Supply Air Plenum & Grille – – – – – – – – – – – – 30 762 91 2311 – – – – – – – – – – – – 35 889 85 2159
CB17 UP-FLOW MODELS WITH ECONOMIZER DAMPER SECTION
Model NoA
Model No.in. mm
EMD17-95 & 135 25 635
EMD17-185 33 838
EMD17-275 42 1067
— 13 —
SUPPLY
AIR
HW17 HOT WATER CABINET“00” EMPTY SPACER CABINETEH17 ELECTRIC HEAT CABINET
CB17 BLOWER COIL UNIT
FRONT VIEW(Without Economizer)
DRIVE SIDE VIEW(Without Economizer)
AIR
RETURN
B
C
A
D
GH
FE
RG17RETURN AIR
GRILLE(Optional)
OPTIONAL
SUPPLY AIR
SPG17SUPPLY AIR PLENUM
AND GRILLE
NOTE — Plenum may be rotated 180�for change in direction of discharge air.
SUPPLY
AIR
EMD17ECONOMIZER
DAMPERSECTION
RETURNAIR
SPG17SUPPLY AIR
PLENUM
HW17 HOT WATER CABINET“00” EMPTY SPACER CABINETEH17 ELECTRIC HEAT CABINET
CB17 BLOWER COIL UNIT
FRONT VIEW(With Economizer)
DRIVE SIDE VIEW(With Economizer)
AIR
OUTDOOR
A
A
DIMENSIONS — inches (mm)
CBH17 HORIZONTAL MODELS WITH OPTIONAL ACCESSORY SECTIONS
SUPPLY
AIR
EMD17ECONOMIZER
DAMPERSECTION
RETURNAIR
HW17 HOT WATER CABINET“00” EMPTY SPACER CABINETEH17 ELECTRIC HEAT CABINET
CB17 BLOWERCOIL UNIT
RETURN AIR VIEW(With Economizer)
AIR
OUTDOOR
G
G
SPGH17SUPPLY
AIR GRILLE
RG17RETURN AIR
GRILLE(Optional)
C B
D
F
A
A A
RETURN AIR VIEW(Without Economizer)
SUPPLY AIR VIEWOPTIONALRETURN AIR(Rotate 180�)
SPGH17SUPPLY AIR PLENUM
AND GRILLE
4 (102)
E
GRILLE AREA
Model NoGrille Free Area
Model No.sq. ft. m2
SupplySPGH17-95 4.5 0.42
SupplyAir
GrilleSPGH17-135 5.6 0.52
GrilleSPGH17-185/275 9.7 10.90
RG17-95 7.3 0.68
ReturnAir
RG17-135 9.0 0.84Air
Grille RG17-185 16.5 1.53
RG17-275 21.2 1.97
Model NoA B C D E F G
Model No.in. mm in. mm in. mm in. mm in. mm in. mm in. mm
CBH17-95V Basic Unit 52 1321 – – – – – – 36 914 – – – – – – 27 686 – – – – – – – – – – – –
CBH17-135V Basic Unit 64 1626 – – – – – – 36 914 – – – – – – 27 686 – – – – – – – – – – – –
CBH17-185V Basic Unit 85 2159 – – – – – – 44 1118 – – – – – – 35 889 – – – – – – – – – – – –
CBH17-275V Basic Unit 85 2159 – – – – – – 44 1118 – – – – – – 44 1118 – – – – – – – – – – – –
EH17-95 Electric Heat Section 52 1321 19 483 – – – – – – 59 1499 – – – – – – 27 686 – – – – – –
EH17-135 Electric Heat Section 64 1626 19 483 – – – – – – 59 1499 – – – – – – 27 686 – – – – – –
EH17-185/275 Electric Heat Section 85 2159 14 356 – – – – – – 62 1575 – – – – – – 35 889 – – – – – –
HW17-95 or CBH17-95-00 52 1321 14 356 – – – – – – 54 1375 – – – – – – 27 686 – – – – – –
HW17-135 or CBH17-135-00 64 1626 14 356 – – – – – – 54 1375 – – – – – – 27 686 – – – – – –
HW17-185/275 or CBH17-185/275-00 85 2159 14 356 – – – – – – 62 1575 – – – – – – 35 889 – – – – – –
SPGH17-95 Supply Air Plenum & Grille 52 1321 – – – – – – – – – – – – – – – – – – – – – – – – 27 686 – – – – – –
SPGH17-135 Supply Air Plenum & Grille 64 1626 – – – – – – – – – – – – – – – – – – – – – – – – 27 686 – – – – – –
SPGH17-185/275 Supply Air Plenum & Grille 85 2159 – – – – – – – – – – – – – – – – – – – – – – – – 35 889 – – – – – –
EMD17-95 or EMD17-135 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 25 635
EMD17-185 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 33 838
EMD17-275 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 42 1067
— 14 —
HOT WATER HEATING CAPACITY CURVES
Water Temp. BtuhDrop (�F) 500 x U.S. gpm
Air Temp. BtuhRise (�F) 1.08 x cfm
Water Temp. kWDrop (�C) 4.19 x L/s (water)
Air Temp. kWRise (�C) 1210 x L/s (air)
=
=
=
=
HOT WATER WITH GLYCOL SOLUTIONCAPACITY CORRECTION FACTOR CHART
Multiply rating in hot water capacity
chart by correction factor below
% Of CorrectionGlycol Factor
0 1.0010 .9720 .9430 .9140 .8750 .84
Water Temp. BtuhDrop (�F) 500 x U.S. gpm
Air Temp. BtuhRise (�F) 1.08 x cfm
Water Temp. kWDrop (�C) 4.19 x L/s (water)
Air Temp. kWRise (�C) 1210 x L/s (air)
=
=
=
=
HOT WATER WITH GLYCOL SOLUTIONCAPACITY CORRECTION FACTOR CHART
Multiply rating in hot water capacity
chart by correction factor below
% Of CorrectionGlycol Factor
0 1.0010 .9720 .9430 .9140 .8750 .84
4000
3500
3000
2500
130 140 150 160 170 180 190 200 210 220 230 240 250 260120Btuh (1000) Btuh (1000)
35 49 45 50 55 60 65 70 75kW kW
TOTAL HEATING CAPACITY1800
1600
1400
1200
1000
L/s
L/s
TO
TA
L A
IR V
OLU
ME
HW17-95 HOT WATER HEATING CAPACITY
cfm
cfm
4500
4000
3500
3000
130 140 150 160 170 180 190 200 210 220 230 240 250 260120Btuh (1000) Btuh (1000)
35 40 45 50 55 60 65 70 75kW kW
TOTAL HEATING CAPACITY
TO
TA
L A
IR V
OLU
ME
HW17-135 HOT WATER HEATING CAPACITY
2000
1800
1600
1400
L/s
L/scfm
cfm
— 15 —
HOT WATER HEATING CAPACITY CURVES
180 200 220 240 260 280 300 320 340 360 380 400 420
50 60 70kW kW80 90 100 110 120 130
TOTAL HEATING CAPACITY
Btuh (1000) Btuh (1000)
7500
7000
6500
6000
5500
3400
3200
3000
2800
2600
2400
L/s
L/scfm
cfm
TO
TA
L A
IR V
OLU
ME
HW17-185/275 HOT WATER HEATING CAPACITY with CB17/CBH17-185V
240 260 280 300 320 340 360 380 400 420 440 460 480
TOTAL HEATING CAPACITY
Btuh (1000) Btuh (1000)
9500
9000
8500
8000
7500
4400
4200
4000
3800
3600
3400
L/s
L/s
cfm
cfm
TO
TA
L A
IR V
OLU
ME
HW17-185/275 HOT WATER HEATING CAPACITY with CB17/CBH17-275V
70 80 90kW kW100 110 120 130 140 150
Water Temp. BtuhDrop (�F) 500 x U.S. gpm
Air Temp. BtuhRise (�F) 1.08 x cfm
Water Temp. kWDrop (�C) 4.19 x L/s (water)
Air Temp. kWRise (�C) 1210 x L/s (air)
=
=
=
=
HOT WATER WITH GLYCOL SOLUTIONCAPACITY CORRECTION FACTOR CHART
Multiply rating in hot water capacity
chart by correction factor below
% Of CorrectionGlycol Factor
0 1.0010 .9720 .9430 .9140 .8750 .84
Water Temp. BtuhDrop (�F) 500 x U.S. gpm
Air Temp. BtuhRise (�F) 1.08 x cfm
Water Temp. kWDrop (�C) 4.19 x L/s (water)
Air Temp. kWRise (�C) 1210 x L/s (air)
=
=
=
=
HOT WATER WITH GLYCOL SOLUTIONCAPACITY CORRECTION FACTOR CHART
Multiply rating in hot water capacity
chart by correction factor below
% Of CorrectionGlycol Factor
0 1.0010 .9720 .9430 .9140 .8750 .84
— 16 —