Blower Coil Air Handler Models BCHD, BCVD, and BCCD Air Terminal Device 400-3000 CFM June 2018 BCX-PRC001E-EN Product Catalog

Transcript of Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You...

Page 1: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Blower Coil Air Handler

Models BCHD, BCVD, and BCCD

Air Terminal Device400-3000 CFM

June 2018 BCX-PRC001E-EN

Product Catalog

Page 2: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Introduction

Trane Blower Coils—Factory Packaged How You Need It...

When You Need It

Figure 1. Horizontal blower coil (BCHD model)

Unit sizes 12, 18, 24,36, 54, 72, 90 MBh

Knockouts in all fourcorners for hanger rods

1/2 - 3 HP ECM motor (standard)

Direct-drive up to2.5 inches total static

eliminates the difficultieswith belts

Control box optionsinclude UC400-B controllerfor single zone VAV; CSTI,

ZN010, ZN510 or ZN520Main coil with coppertubes and enhances aluminum fins in 2-, 4-, or 6-row hydronicor 4- and 6-row DX

Throwaway MERV 8 or MERV 13 filters

Internal filter frame accommodates 1-inchor 2-inch filters

Main and auxiliary drain connections on same side of unit

©2018 Ingersoll Rand BCX-PRC001E-EN

Page 3: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Introduction

Figure 2. Compact vertical blower coil (BCCD model)

Unit sizes 24, 36, 48, 60 MBh

1/2 - 1 HP ECM motor (standard)

Direct-drive up to2.5 inches total static

eliminates the difficultieswith belts

Control box optionsinclude UC400-B controllerfor single zone VAV; CSTI,ZN010, ZN510 or ZN520

Main coil with coppertubes and enhances aluminum fins in 4- or 6-row hydronicor 3-, 4-, and 6-row DX

Throwaway MERV 8 or MERV 13 filters

Internal filter frame accommodates 1-inchor 2-inch filters

Main drain connectionon same side of unit

Auxillary heating coilwith 1- or 2-row hydronic

BCX-PRC001E-EN 3

Page 4: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Introduction

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

• Valve change updates

• General data updates

• Performance data updates to include piping package additions

• Dimensional data updates

• Mechanical specification updates

4 BCX-PRC001E-EN

Page 5: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Table of Contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Trane Blower Coils—Factory Packaged How You Need It...When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Single Source Responsibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Piping Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11CSTI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Tracer® Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11End Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Flexibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Coil Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Filter Placement Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Motor Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Indoor Air Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Filtration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Easy to Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Durability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Optional Accessory Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Mixing Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Angle Filter or Angle Filter/Mixing Box Combination . . . . . . . . . . . . . . . 14Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Steam Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Single-Zone, Constant Volume Applications . . . . . . . . . . . . . . . . . . . . . . . . 16Two-Pipe Hydronic Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Two-Pipe Hydronic Units With Electric Heat . . . . . . . . . . . . . . . . . . . . . . . 16Four-Pipe Hydronic Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

DX Cooling Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Four-Pipe Unit with Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Chilled-Water Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Location and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Acoustics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

BCX-PRC001E-EN 5

Page 6: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Table of Contents

Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Typical Blower Coil Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Selecting a Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Cooling Selection Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Heating Selection Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Valve Package Waterflow Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Coil Circuiting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Air Pressure Drop Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Water Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Fan arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Fan Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Chilled Water Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

High-Capacity Chilled Water Cooling Capacities . . . . . . . . . . . . . . . . . . . . . 61

R-410A, DX Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Hot Water Heating Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81Distributor Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

Why Trane Controls? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

VelociTach™ Motor Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88Manual Fan Speed Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88Customer Supplied Terminal Interface (CSTI) . . . . . . . . . . . . . . . . . . . . . 88

Tracer® Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89Tracer® ZN520 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89Tracer® UC400-B Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

Tracer® Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90Features Available on All Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90Additional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

Tracer® Controls Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 94Fan Speed Switch (units with 3-speed fan only) . . . . . . . . . . . . . . . . . . . 94Tracer® ZN010 and ZN510 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94Tracer® ZN520 and UC400-B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

Air-Fi Wireless Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94Air-Fi Wireless Communications Interface (WCI) . . . . . . . . . . . . . . . . . . . 95Air-Fi Wireless Communications Sensor (WCS) . . . . . . . . . . . . . . . . . . . . 95Wireless Zone Sensor (WZS) Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

Zone Sensor Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

6 BCX-PRC001E-EN

Page 7: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Table of Contents

End Device Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97Low Temperature Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97Condensate Overflow Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97Outside Air Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98Two-Position Mixing Box Damper Actuator . . . . . . . . . . . . . . . . . . . . . . . 98Discharge Air Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98Economizer Damper Actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98CO2 Sensor for Demand-Controlled Ventilation . . . . . . . . . . . . . . . . . . . . 98Humidity Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98Control Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99How to Choose the Correct Control Valve . . . . . . . . . . . . . . . . . . . . . . . . . 99

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

Horizontal Blower Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

Vertical Blower Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

Compact Vertical Blower Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107

Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109Angle Filter and Mixing Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109Bottom or Top Access Filter Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

Coil Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116

Piping Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117Basic Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118Deluxe Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121Casings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122EC Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122Drain Pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123Mixing Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123Electric Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123Seismic Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124Piping Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124End Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125

BCX-PRC001E-EN 7

Page 8: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Model Number Description

Following is a complete description of the blower coil model number. Each digit in the model number has a corresponding code that identifies specific unit options.

Digits 1, 2, 3, 4 — Unit ModelBCHD = Horizontal Blower CoilBCVD = Vertical Blower CoilBCCD = Compact Vertical Unit

Digits 5, 6, 7 — Unit Size012 = Unit size 12 - 1 Ton018 = Unit size 18 - 1 1/2 Ton024 = Unit size 24 - 2 Ton036 = Unit size 36 - 3 Ton048 = Unit size 48 - 4 Ton054 = Unit size 54 - 4 1/2 Ton060 = Unit size 60 - 5 Ton072 = Unit size 72 - 6 Ton090 = Unit size 90 - 7 1/2 Ton

Digit 8 — Unit Voltage A = 115 V/60 Hz/1 PhB = 208 V/60 Hz/1 PhC = 230 V/60 Hz/1 PhD = 277 V/60 Hz/1 PhE = 208 V/60 Hz/3 PhF = 230 V/60 Hz/3 PhG = 460 V/60 Hz/3 PhJ = 220 V/50 Hz/1 PhK = 240 V/50 Hz/1 PhL = 380 V/50 Hz/3 PhM = 415 V/50 Hz/3 Ph

Digit 9 —Insulation1 = Matt Face Insulation 1-in.2 = Foil Face Insulation 1-in.

Digits 10, 11 — Design Sequence *** = Factory Assigned

Digit 12 — Motor and Control Box LocationA = Same side as coil connections

horizontal or vertical counterswirl only

B = Opposite side of coil connections, horizontal or vertical counterswirl only

C = Same side as coil connections, vertical preswirl only

D = Opposite side of coil connections vertical preswirl only

E = Front return (BCCD only)F = Front return with grill (BCCD

only)G = Bottom return (BCCD only)

Digit 13 — Coil Connection Side 0 = None1 = PVC drain pan right hand coil2 = PVC drain pan left hand coil3 = SS drain pan right hand coil4 = SS drain pan left hand coil5 = PVC drain pan front connection6 = SS drain pan front connection

Digit 14 — Coil #1 First Coil in Air Stream0 = No Coil #1A = 1-row Hydronic PreheatF = 4-row HydronicG = 6-row HydronicJ = 4-row Hydronic with auto change

overK = 6-row Hydronic with auto change

overL = 2-row High Capacity Hydronic

Pre-heatM = 4-row High Capacity HydronicN = 6-row High Capacity HydronicR = 4-row High Capacity Hydronic

with auto change overT = 6-row High Capacity Hydronic

with auto change over1 = 3-row DX 3/16-in. (0.032) Dist2 = 4-row DX 3/16-in. (0.032) Dist3 = 6-row DX 3/16-in. (0.032) Dist4 = 3-row DX 3/16-in. (0.049) Dist5 = 4-row DX 3/16-in. (0.049) Dist6 = 6-row DX 3/16-in. (0.049) Dist7 = 4-row DX 3/16-in. (0.049) Dist,

Heat Pump 8 = 6-row DX 3/16-in. (0.049) Dist,

Heat Pump

Digit 15 — Coil #2 Second Coil in Air Stream0 = No Coil #2A = 1-row Hydronic ReheatF = 4-row HydronicG = 6-row HydronicJ = 4-row Hydronic with Auto

change overK = 6-row Hydronic with Auto

change overL = 2-row High Cap Hydronic ReheatM = 4-row High Cap HydronicN = 6-row High Cap HydronicR = 4-row High Cap Hydronic with

auto change overT = 6-row High Cap Hydronic with

auto change over1 = 3-row DX 3/16-in. (0.032) Dist2 = 4-row DX 3/16-in. (0.032) Dist3 = 6-row DX 3/16-in. (0.032) Dist4 = 3-row DX 3/16-in. (0.049) Dist5 = 4-row DX 3/16-in. (0.049) Dist6 = 6-row DX 3/16-in. (0.049) Dist7 = 4-row DX 3/16-in. (0.049) Dist,

Heat Pump 8 = 6-row DX 3/16-in. (0.049) Dist,

Heat Pump

Digit 16 — Motor Horsepower2 = 1/2 Horsepower4 = 1 Horsepower5 = 1.5 Horsepower7 = 3 Horsepower

Digit 17 — Motor SpeedA = 500 rpmB = 600 rpmC = 700 rpmD = 800 rpmE = 900 rpmF = 1000 rpm

G = 1100 rpmH = 1200 rpmJ = 1300 rpmK = 1400 rpmL = 1500 rpmM = 1600 rpmN = 1700 rpmP = 1800 rpmR = 1900 rpmT = 2000 rpmU = 2100 rpmV = 2200 rpmW = 2300 rpmZ = TOPSS base performance

Digit 18 — Electric Heat Stages0 = None1 = 1-stage2 = 2-stage

Digits 19, 20, 21 — Electric Heat kW010 = 1.0 kW015 = 1.5 kW020 = 2.0 kW025 = 2.5 kW030 = 3.0 kW035 = 3.5 kW040 = 4.0 kW045 = 4.5 kW050 = 5.0 kW055 = 5.5 kW060 = 6.0 kW065 = 6.5 kW070 = 7.0 kW075 = 7.5 kW080 = 8.0 kW090 = 9.0 kW100 = 10.0 kW110 = 11.0 kW000= None120 = 12.0 kW130 = 13.0 kW140 = 14.0 kW150 = 15.0 kW160 = 16.0 kW170 = 17.0 kW180 = 18.0 kW190 = 19.0 kW200 = 20.0 kW210 = 21.0 kW220 = 22.0 kW240 = 24.0 kW260 = 26.0 kW280 = 28.0 kW300 = 30.0 kW

Digit 22 — Electric Heat Controls0 = NoneA = 24 volt magnetic contactors

Digit 23 — Electric Heat OptionsA = Heater FuseB = Interlocking Disconnect SwitchC = Interlock Disc and Heater Fuse0 = None

Digit 24 — FiltersA = 1-in. ThrowawayB = 2-in. MERV 8 Pleated Throwaway

8 BCX-PRC001E-EN

Page 9: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Model Number Description

C = 2-in. MERV 13 Pleated Throwaway

0 = None

Digit 25 — Accessory SectionA = Mixing Box OnlyB = Angle Filter BoxC = Angle Filter /Mix BoxD = Top Access Filter ModE = Bot Access Filter ModF = Top Access Filter and Mix BoxG = BTM Access Filter and Mix BoxH = Steam Coil ModuleJ = Steam Coil Mod and Mix BoxK = Steam Coil Mod and Angle Filter

BoxL = Steam Coil Mod and Angle Filter /

Mix BoxM = Steam Coil Mod and Top Access

Filter ModN = Steam Coil Mod and BTM Access

Filter ModP = Steam Coil Mod and Top Access

Filter Mod and Mix BoxR = Steam Coil Mod and BTM Access

Filter Mod and Mix Box0 = None

Digit 26 — Control TypeN = CSTI Fan Status1 = CSTI2 = Tracer® ZN0103 = Tracer® ZN5104 = Tracer® ZN5206 = No Controls (FSS)8 = Tracer® UC 400-B9 = Tracer® UC 400-B and WCI

Digit 27 — Coil #1 Control Valve Type0 = NoneA = 2-Way, 2 Position N.C.B = 2-Way, 2 Position N.O.C = 3-Way, 2 Position N.C.D = 3-Way, 2 Position N.O.E = 2-Way, ModulatingF = 3-Way, ModulatingG = Field Supplied, 2 Position N.C.H = Field Supplied, 2 Position N.O.J = Field Supplied, ModulatingK = Field Supplied, Analog (2-10 VDC)

Digit 28 — Coil #1 Control Valve Cv0 = NoneV = 2-Way 2.3 Cv 3/4-in. Valve and

PipeW = 2-Way 3.3 Cv 3/4-in. Valve and

PipeY = 2-Way 4.6 Cv 3/4-in. Valve and

PipeZ = 2-Way and 3-Way 7.4 Cv 1-in. and

pipe1 = 2-Way and 3-Way 10.0 Cv 1-in.

Valve, 1 1/4-in. pipe 2 = 3-Way 1.0 Cv 1/2-in. Valve, 3/4-in.

pipe

BCX-PRC001E-EN

3 = 3-Way 2.7 Cv 1/2-in. Valve, 3/4-in. pipe

4 = 3-Way 4.6 Cv 3/4-in. Valve and Pipe

Digit 29 — Coil #1 Piping Package0 = None1 = Basic piping package2 = Deluxe piping package

Digit 30 — Coil #2 Control Valve A = 2-Way, 2 Position N.C.B = 2-Way, 2 Position N.O.C = 3-Way, 2 Position N.C.D = 3-Way, 2 Position N.O.E = 2-Way, ModulatingF = 3-Way, ModulatingG = Field Supplied, 2 Position N.C.H = Field Supplied, 2 Position N.O.J = Field Supplied, ModulatingK = Field Supplied, Analog (2-10 VDC)

Digit 31— Coil #2 Control Valve Cv0 = NoneV = 2-Way 2.3 Cv 3/4-in. Valve and

PipeW = 2-Way 3.3 Cv 3/4-in. Valve and

PipeY = 2-Way 4.6 Cv 3/4-in. Valve and

PipeZ = 2-Way and 3-Way 7.4 Cv 1-in. and

pipe1 = 2-Way and 3-Way 10.0 Cv 1-in.

Valve, 1 1/4-in. pipe 2 = 3-Way 1.0 Cv 1/2-in.Valve, 3/4-in.

pipe 3 = 3-Way 2.7 Cv 1/2-in. Valve, 3/4-in.

pipe 4 = 3-Way 4.6 Cv 3/4-in. Valve and

Pipe

Digit 32 — Coil #2 Piping Package0 = None1 = Basic piping package2 = Deluxe piping package

Digit 33 — Remote Heat Options0 = No remote heat1 = Remote staged electric heat2 = Remote 2-position hot water, N.C.

Digit 34 — Mixing Box Damper Actuator1 = 2 Position, N.O., ship loose2 = Modulating, N.C.3 = Modulating, N.O.4 = Modulating, ship loose5 = Field Supplied, 2 Pos. N.O.6 = Field Supplied, 2 Pos. N.C.7 = Field Supplied modulating0 = none

Digit 35 — Factory Mounted Control OptionsC = Condensate Overflow

D = Low LimitK = Condensate Overflow and Low

Limit0 = None

Digit 36 — Control Options 2A = Outside Air Sensor, Field

MountedB = Discharge Air SensorC = Outside Air and Discharge Air

Sensor0 = None

Digit 37 — Control Options 3A = Dehumidification with

communicated valueB = Dehumidification with Local

SensorC = CO2 SensorD = Air-Fi® Dehumidification and CO2E = Air-Fi® DehumidificationF = Air-Fi® CO20 = None

Digit 38 — Zone Sensors1 = Wall-mounted temperature

sensor (SP, OA, OCC/UNOCC, COMM)

3 = Wall-mounted temperature sensor (SP, OCC/UNOCC, COMM)

4 = Wall-mounted temperature sensor (OCC/UNOCC, COMM)

C = Wireless temperature sensor, UNIT MTD RECEIVER

E = Wall-mounted temperature sensor (SP, OALMH, OCC/UNOCC, COMM)

F = Wall-mounted display sensor (SP, OALHH, COMM)

G = Wireless display sensor, Unit-mounted receiver (SP, OALMH)

H = Wall-mounted FSS0 = None

Digit 39 — Seismic Certification0 = NoneA = IBC Seismic CertificationB = OSHPD Seismic CertificationC = LEED Wrap D = LEED Wrap IBC Seismic CertE = LEED Wrap OSHPD Seismic Cert

Digit 40 — Extra Filter0 = None1 = Extra 1-in. Throwaway ship

loose2 = Extra 2-in. MERV 8 PLTD T/A

ship loose3 = Extra 2-in. MERV 13 PLTD T/A

ship loose

9

Page 10: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Features and Benefits

Factory Packaged – What You Need – When You Need It

The Trane blower coil air handler, models BCHD, BCVD, and BCCD, accommodate a variety of applications while providing a low-cost method of air conditioning and/or heating buildings. These compact, low-profile units can fit in small spaces and are floor or ceiling mounted. With a minimum of effort, they can be relocated within the building as needs change.

Blower coils are light-duty air handlers, ranging from 1.0 to 7.5 tons nominal capacity. They are typically used in schools, hospitals, offices, stores, and similar applications. Trane blower coils are UL listed to U.S. and Canadian safety standards for all:

• 115, 208, 230, 277, and 460 volt 60 hertz motors

• 220, 240, 380, and 415 volt 50 hertz motors

Single Source Responsibility

Trane is the single source of responsibility because we ship blower coils from the factory as a total package. Included in the package are factory-mounted coils, filters, controls, direct-drive motors, and duct collars. Also, factory-provided piping packages are an available option. Because we provide the total package, this helps reduce job site labor and installation time.

Figure 3. Horizontal blower coil

10 BCX-PRC001E-EN

Page 11: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Features and Benefits

Piping Packages

All blower coil air handlers are available with factory-built piping package options for field installation using field-supplied interconnecting piping. Basic or deluxe piping package options are available with a variety of control valve options:

• Two- or three-way

• 1/2-in, 3/4-in, 1-in, or 1 1/4-in

• Two-position or modulating

The basic piping package consists of two shut-off ball valves. The deluxe piping package has one shut-off ball valve, a strainer, and a circuit setter balancing valve. Basic or deluxe piping packages with a three-way control valve also include a balancing fitting on the bypass line.

Energy Efficiency

Trane’s commitment to providing premium quality products has led to the exclusive use of Electronically Commutated Motors (ECM) in all blower coil models. These brushless DC motors incorporate the latest technology for optimized energy efficiency, acoustical abatement, maintenance free and extended motor life. Each motor comes with a VelociTach™ motor control board that allows for programmability, soft ramp-up, better airflow control, and serial communication. Trane units equipped with ECMs are significantly more efficient than permanent split capacitor (PSC) motors or belt-drive motors and enable single-zone VAV control.

Single-zone VAV control varies the fan speed as the zone cooling or heating load changes, and can result in lower operating costs and improved occupant comfort compared to constant-speed units.

Controls

Trane offers a broad array of control options, from a simple control interface (CSTI) to the Tracer® controllers.

CSTI

The control interface is intended to be used with a field-supplied, low-voltage thermostat or controller. The control box contains a disconnect switch (optional for units with electric heat). All end devices are wired to a low-voltage terminal block and are run-tested, so only a power connection and thermostat connection is needed to commission the unit. Changeover sensors and controls are provided whenever a change-over coil is selected.

Tracer® Controllers

The Tracer® family of controllers, ZN010, ZN510, ZN520, and UC400-B offers the combined advantages of simple and dependable operation with the latest Trane-designed controller. Standard control features include options normally available on more elaborate control systems. All control options are available factory-configured or can be field-configured using Rover service software for the ZN controllers, the UC400-B is serviced via Tracer® TU.

This is the industry’s first solution that is factory-mounted, wired, and programmed for infinite modulation of fan speed based on space loads, using the Tracer® UC400-B.

End Devices

Optional factory-mounted end devices such as a condensate float switch, freezestat, control valves, and actuators are available. Factory-installed and -wired electric heat features single-point power connection.

BCX-PRC001E-EN 11

Page 12: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Features and Benefits

Flexibility

The Trane blower coil is available in either horizontal (model BCHD), vertical (model BCVD), or compact vertical (model BCCD) configurations. Horizontal units are typically ceiling suspended via threaded rods. Knockouts are provided in all four corners to pass the rods through the unit. Horizontal units can also be floor mounted. Vertical units are typically floor mounted. They have a side inlet for easy duct connection, and do not require a field-fabricated inlet plenum. Vertical units ship in two pieces and can be set up in either a pre-swirl or counter-swirl configuration. Compact vertical units are floor mounted and ship in one piece.

In addition, blower coils have acoustical benefits because they are typically located outside the occupied space, either in the ceiling or in a closet. This limits the amount of sound transmission (radiated) directly from the unit to the occupant. These units are applied with discharge ductwork, which is frequently lined to help reduce the sound transmission (discharge) through the ductwork into the occupied space. Blower coils utilize a direct-drive motor solution for all units which eliminates the single phase motor hum which is evident in capacitor split motors in belt-drive applications.

Coil Options

Trane blower coils feature a wide variety of coil options that include:

• Two-, four-, or six-row hydronic cooling or heating

• Three-, four-, or six-row DX coils

• High capacity hydronic coils for cooling or heating

• One- or two-row heating coil in either the preheat or reheat position

• One-row steam preheat

Filter Placement Options

All hydronic units have an internal flat filter frame for 1- or 2-inch filters. Other filter placement options include:

• Angle filter box for 2-inch filters

• Combination angle filter/mixing box

• Bottom or top access filter box that accommodates 2-inch filters. This option allows easy filter access through a hinged door, from the bottom of the unit on horizontal units, and from the top on vertical units.

Motor Options

Direct-drive motors range from 1/2 to 3 horsepower in a wide range of voltages. All motors have internal current overload protection, permanently sealed ball bearings, and rubber grommets on the mounting brackets to reduce noise and vibration transmission.

Motors come factory programmed for specific job requirements or can be programed based on standardized motor speeds. Motors speeds have the ability to be adjusted on the job site with out the requirement of specialized tools. This enables the unit to be balanced for changes to design static pressures fast and easy.

12 BCX-PRC001E-EN

Page 13: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Features and Benefits

Indoor Air Quality

Indoor air quality is becoming a greater concern every day. That’s why Trane provides the most complete indoor air quality options of any manufacturer.

Drain Pans

Filtration

All units have an internal flat filter frame that can accommodate 1- or 2-inch filters. An optional bottom (horizontal units) or top (vertical units) filter access box is also available to improve accessibility.

An optional angle filter box (2-inch only), or combination angle filter/mixing box, provides extra filter face area, which results in extremely low face velocities and low pressure drop. With increased face area, the angle filters have substantially more dust-holding capacity than conventional flat filters. MERV 8 and MERV 13 pleated angle or flat filters options are available.

Ventilation

The optional mixing box delivers ventilation air directly to each unit. When the unit is equipped with a Tracer® ZN520 or UC400-B controller, the mixing box functions as a zero to 100 percent economizer to improve energy efficiency. For units configured to automatically switch between high and low fan speeds, the Tracer® ZN520 or UC400-B controller automatically adjusts the mixing box damper to provide the correct amount of fresh air to the space at all fan speeds.

Blower coil units are draw-thru configurations that use direct-drive fan motors with higher horsepower than fan coils. This makes them an excellent choice for use in an air supply ductwork system with diffusers—rather than a direct discharge system—because it enhances the space air mixing and ventilation effectiveness.

Dehumidification

For direct control of space humidity, a blower coil can be configured with a hydronic heating coil in the reheat position and equipped with a Tracer® ZN520 or UC400-B controller. These controllers can independently modulate the cooling and heating coils to directly control both temperature and humidity in the space.

Figure 4. Drain pan

The Trane blower coil uses a polymer or optional stainless steel drain pan, sloped in both directions to drain properly. The drain pans are easily removable and cleanable. Also, the main and auxiliary connections are on the same side. Compact vertical units include an internal trap.

Accessibility and Cleanability

Trane blower coils have 1-inch dual density insulation that meets NFPA90A and UL181, which is designed to withstand high velocities. Trane optionally offers 1-inch foil faced insulation that meets NFPA90A, UL181, and bacteriological standard ASTM C 665.

Coils mount above—not in—the drain pan and are not a structural part of the unit. The coils are easily removable and slide in and out on rails for cleaning. The drain pan is also easily removable for cleaning.

BCX-PRC001E-EN 13

Page 14: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Features and Benefits

Easy to Service

The coils and motor are easily replaced within minutes, even when the unit is suspended. Coils slide in and out by removing the coil access panel and a few screws at the rear of the unit. With the bottom filter access option, filters are easily accessed from the bottom of the unit. If the motor requires servicing, only the motor side requires access.

Durability

Trane blower coils use durable materials, including heavy gage, galvanized steel for the casing.

Optional Accessory Sections

These accessory sections make the BCHD/BCVD product more flexible:

• Mixing box

• Angle filter box

• Angle filter and mixing box section

• Bottom or top hinged access filter box

• Electric heat box

• Steam coil box

Mixing Box

Angle Filter or Angle Filter/Mixing Box Combination

Figure 5. Mixing box

The mixing box option ships separately and has internal low-leak aluminum dampers and access panels on both sides. The mixing box is insulated in the same as the main unit: matte or foil, as ordered. The mixing box is easily located in field to allow “back/bottom” dampers.

Figure 6. Angle filter/mixing box combo

Filter box options include an angle filter box and a bottom/top access filter box that are factory-installed. The angle filter can be combined with the mixing box as one accessory module. The flat filter frame can accommodate 1- or 2-inch filters. The angle filter frame accommodates only 2-inch filters.

14 BCX-PRC001E-EN

Page 15: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Features and Benefits

Electric Heat

A factory installed open-wire electric heater is available in a wide variety of voltages and kW’s. All units have a single point power connection. Optional heater fuses, magnetic contactors, and a heater door interlocking disconnect switch are available.

Steam Coils

Figure 7. Steam coil

A steam coil box with one-row coil is available in the preheat position. Module includes a filter rack for 1-inch flat filters.

BCX-PRC001E-EN 15

Page 16: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Application Considerations

Single-Zone, Constant Volume Applications

The Trane blower coil air handler offers a wide range of application flexibility between the fan coil unit and Climate Changer™ air handlers. Units are available in seven nominal capacities ranging from 1.0 to 7.5 tons cooling and 400 to 3000 cfm airflow. The basic unit is available in horizontal (model BCHD), vertical (model BCVD), and compact vertical (model BCCD) configurations.

The single-zone, constant volume applications discussed in this section are:

• Two-pipe hydronic units

• Two-pipe hydronic units with electric heat

• Four-pipe hydronic units

• Economizer

Other applications are:

• DX cooling

• Two-pipe hydronic units with steam heating

• Single-zone VAV

Two-Pipe Hydronic Units

The standard blower coil is equipped with a hydronic coil. The unit can perform cooling only, heating and cooling (changeover system), or heating only. In a changeover system, the unit cools during the spring, summer, and fall seasons (summer mode) and heats during the winter season (winter mode).

Use the Trane Official Product Selection System (TOPSS™) program for specific design criteria such as flow rate, temperature rise/drop, pressure drop, glycol mixtures, and capacity.

When selecting two-pipe changeover units, note that TOPSS will only provide output that meets both the cooling and heating capacity requirements. Because cooling and heating capacity requirements for a given unit may differ significantly, a given coil may be optimally sized for one load and over/under sized for the other load.

Two-Pipe Hydronic Units With Electric Heat

With the addition of electric heat, the two-pipe system can heat or cool. In the non-changeover system, the main coil is always used for cooling and the electric heater is always used for heating. In the changeover system, during the summer mode (spring, summer and fall), the main coil is used for cooling and electric heater is used for heating. During the winter mode, the main coil is used for heating and the electric heater is disabled.

Two-pipe systems with electric heat are an economical solution to intermediate season (spring and fall) comfort problems associated with straight two-pipe systems. In moderate climates or where electric rates are low, non-changeover systems are typically used. In climates with significant heating loads and/or high electric rates, a changeover system—to allow hydronic heating—is typically used.

All units with factory mounted electric heat are UL listed and interlocked with the fan motor switch. A call for Electric heat operation will turn the fan on. Motors controls are synchronized with fan/valve operation to ensure safe operation and that two modes of heat are not operating simultaneously. A transformer is supplied on any voltage unit, eliminating the need for field installation of a step-down transformer. Units come with either contactors or relays on the electric heat. A high temperature cutout with automatic reset is provided as an integral part of the elements to de-energize the electric heat in the event of a malfunction.

16 BCX-PRC001E-EN

Page 17: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Application Considerations

Changeover in Two-Pipe Systems

Changing between cooling and heating modes in a two-pipe system requires energy to heat or cool the mass of water in the piping system at switchover. ASHRAE Standard 90.1–2001 defines specific requirements for minimizing the energy impact of this switchover:

• The system must allow a deadband between changeover from one mode to the other of at least 15°F outdoor-air temperature.

• The system must include controls that allow the system to operate in one mode for at least four hours before changing to the other mode.

• Reset controls must be provided to allow heating and cooling supply-water temperatures, at the changeover point, to be no more than 30°F apart.

Four-Pipe Hydronic Units

The addition of a one-row or two-row heating coil to the basic blower coil makes it compatible for a four-pipe cooling and heating system. The heating coil is available factory installed in either the preheat or reheat position.

Four-pipe systems solve the intermediate season (spring and fall) comfort problems associated with straight two-pipe systems because they only either cool or heat year-round. However, they do require chiller and boiler operation to be available to operate year-round.

When making the choice between a two or four-pipe system, also consider:

• Cooling/heating loads in perimeter zones of the building

• Importance of temperature and humidity control for the zone

• First cost

TOPSS allows independent selection of the cooling and heating coils for flexibility in flow rates, pressure drops, temperature rise/drop, and fluid type.

Economizer

Adding a mixing box with a damper actuator allows economizer or free cooling applications. When using blower coils for these applications, Trane highly recommends using a freeze protection device to protect the coil(s). If the unit has a Tracer® ZN520 or UC400-B controller, you must have an outside air temperature signal from either a hard wired outside air sensor or from the building automation system, such as Tracer® Summit.

DX Cooling Units

Blower coils with a DX cooling coil will often be connected to an air-cooled condensing unit. Some condensing units have two, independent refrigeration circuits; DX coils in units sizes 12 to 60 are single-circuited. Six-row DX coils in units sizes 72 and 90 are always dual-circuited. 6-row DX coils in unit sizes 72 and 90 are always dual-circuited.

Note: Do not manifold two independent refrigeration circuits into a single-circuited DX (evaporator) coil.

Dehumidification

There are two methods for improving the dehumidification performance of the constant-volume unit with a blower coil:

• Four-pipe unit with reheat

• Chilled water reset

BCX-PRC001E-EN 17

Page 18: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Application Considerations

Four-Pipe Unit with Reheat

Blower coils equipped with a Tracer® ZN520 or UC400-B controller and a hydronic heating coil in the reheat position will provide direct control of space humidity. If the space humidity level does not exceed the desired upper limit, the unit responds to reduced cooling load by modulating the control valve and, if in AUTO mode, switching between fan speeds. However, if the space humidity level rises above the upper limit, the capacity of the cooling coil is increased, overcooling the air to maintain the space humidity below the upper limit. Then, the capacity of the heating coil modulates, adding a small amount of heat to temper the air and avoid overcooling the space.

The Tracer® ZN520 or UC400-B controller responds to a signal from a humidity sensor installed in the space or a signal from a building automation system, and independently modulates the cooling and heating coils to directly control both temperature and humidity in the space. While this configuration can directly control indoor humidity levels, it does require the boiler (or other source of heat) to be available year-round.

Chilled-Water Reset

In many constant-flow pumping systems, the leaving chilled-water temperature setpoint is reset based on either outdoor dry-bulb temperature or some indication of cooling load. Use caution when implementing a chilled-water reset strategy because space humidity control can be compromised if the water gets too warm.

Blower coils equipped with a Tracer® ZN520 or UC400-B can accept an input signal from a humidity sensor in the space. A building automation system will continually poll the humidity level in all spaces, or in a single representative space, to limit the amount of chilled-water reset and maintain space humidity levels.

Location and Installation

Avoid locating the unit directly above spaces where sound levels may be critical, such as areas near the occupied space. Install horizontal units over false ceilings in service areas such as corridors or storage rooms. Install vertical units in closets or mechanical rooms.

Horizontal units are installed by suspending the corners of the unit with threaded rods. Use suitable vibration isolators and take the following precautions to comply with generally accepted installation practices.

• Use flexible duct connectors or supply and return sides (if ducted).

• Use acoustic lining on the inside of main supply duct for noise control.

• Do not attach ceiling suspension wires to unit or through ducts.

• Locate return air grilles as far as possible from the unit to avoid noise transmission.

• Design and install ductwork as per ASHRAE guides, SMACNA, and local code requirements.

Acoustics

Controlling outdoor and equipment noise within the occupied space is increasingly important to system designers and building occupants/owners. Therefore, give proper consideration to this subject in the application of the blower coil.

Selecting fan and coil combinations is inherently flexible for sound-sensitive applications. In such instances, a fan running at low speed with a high capacity coil normally yields satisfactory results. It also may be desirable to select a larger nominal capacity unit and operate it at less than nominal airflow for further acoustic benefit.

BCHD/BCVD sound power, Lw, data for ducted discharge, inlet + casing, and casing radiated components is available in Trane Official Product Selection Software (TOPSS). This sound power data is useful in estimating the sound levels in the occupied space for a given application.

18 BCX-PRC001E-EN

Page 19: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Application Considerations

Operating Limitations

Reference the General Data section for minimum and maximum operating limits. Units must not operate above maximum fan rpm or unit airflow. Unit operation above the maximum fan rpm will drastically reduce bearing life and may result in catastrophic failure. Operating the unit above the maximum airflow in the cooling mode may result in unsatisfactory operation due to water carryover from the coil. In addition, it is often uneconomical to operate a unit at its maximum rpm due to greater motor power requirements.

The unit may not perform at an optimal acoustical performance level if it operates in the fan’s traditional stall region.

Do not operate units with electric heat below the minimum airflow limit to prevent excessive leaving air temperatures and electric heat limit trips.

Do not operate hydronic and electric heat simultaneously to prevent excessive leaving air temperatures and limit trips. Electric heat units have a lockout switch to disable the electric heater if the temperature off the hydronic coil is greater than 95°F.

Do not operate units with a leaving air temperature above 104°F for units with a single-phase motor. Do not operate units with a leaving air temperature above 130° F for units with a three-phase motor.

Do not operate coils above the water flow limits to prevent erosion and noise. A minimum or “self-venting” water flow rate is also listed in the General Data Section. If the coil is set to operate below this flow rate, vent it periodically by flushing at a higher flow rate.

Do not operate piping packages and water valves above the water flow limit to prevent erosion and noise. Water valves supplied with blower coils as accessories are intended for use in “treated” closed loop chilled or hot water systems.

Note: Do not use valves with open or potable water systems. Untreated water may cause scaling and particulate collection interference with the valve function, and reduce the life and effectiveness of the valve.

Typical Blower Coil Applications

Figure 8. Typical 4-pipe (preheat) application

Return grille

Returnductwork Filter

Auxiliary coil1 or 2-row

Main coil

2, 4, or 6-row

Blower coil unitDiffuser

Supply ductwork

2-way control valvesmain and auxiliary coils

R S R S

BCX-PRC001E-EN 19

Page 20: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Application Considerations

Figure 9. Typical 2-pipe application with electric heat and mixing box

Return grille

Returnductwork Filter

Main coil

2, 4, or 6-row

Blower coil unit

Diffuser

Supply ductw

ork

2-way control valve

Outside air grille

Mixing box

Electric heat

Modulating springreturn actuator

R S

Figure 10. Typical 2-pipe changeover application

Return grille

Returnductwork Filter

Main

coil2, 4

, or 6-row

Blower coil unitDiffuser

Supply du

ctwork

R S

Outside air grille

2-position outside air damperwith spring return actuator

Auto-changeover sensor

Bypass line

3-way mixing control valve

20 BCX-PRC001E-EN

Page 21: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Application Considerations

Figure 11. Typical 4-pipe vertical with changeover application

R S SR

Filter

Main coil

2, 4, or 6-row

Vertical blower coilunit

Diffuser

2-way control valve

Open return

Auxiliary coil1 or 2-row

Auto-changeover sensor

2-way control valve

Figure 12. Typical DX with hot water preheat application

R S

Return grille

Returnductwork Filter

Blower coil unit

Diffuser

Supply ductw

ork

Hot w

ater auxiliary coil1 or 2-row

DX m

ain coil4 or 6-row

Discharge

Suction

BCX-PRC001E-EN 21

Page 22: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Application Considerations

Figure 13. Typical BCCD bottom return

Diffuser

Electric heat

Compactvertical

blower coil BCCD model

Supply

4-6 row coil mainFilter

Field-suppliedplenum

Return

22 BCX-PRC001E-EN

Page 23: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Selection Procedure

Selecting a Unit

These selection procedures are for manual computations using the general data and capacity tables in this catalog. For particular design conditions not in this catalog, use the Trane Official Product Selection System (TOPSS) or contact your local Trane office.

1. Determine unit capacity. Refer unit capacities on p. 59 - p. 81 to determine unit size needed for cooling and/or heating. Interpolate between given values when necessary.

2. Verify air and water flow operating limits. If design airflow equals the unit rated airflow with the chosen coil, use the waterflow rate shown in the appropriate performance table. If using interpolation to determine capacity, determine waterflow using the formula: gpm = total capacity (MBh) / [(0.5) x (water temperature rise)].

Note: Airflow and water flow must fall within the unit operating limits in general data Table 1, p. 26 and Table 2, p. 27 or you must reselect the unit.

3. Heating coils only: If entering air and water conditions are different than 60/180°F or 60/120°F respectively, refer to the associated correction factors in Table 28, p. 85. Divide the required capacity by the correction factor and then refer to the table to locate the corrected capacity.

4. Calculate the water pressure drop (hydronic coils only). Determine water pressure drop using the appropriate figure on p. 16 - p. 22.

5. Check fan performance requirements. Reference fan performance data by unit size and configuration on p. 43 - p. 59. These curves include pressure drops from the casing only. Reference air pressure drop for coils, filters, and accessories using Table 8, p. 30, Table 9, p. 31, Table 10, p. 32, and Table 11, p. 33.

6. Calculate total static pressure requirements. Add the external static pressure (ESP) of the coil, filter, and accessories to the system esp to obtain the total fan static pressure requirement. Then determine BHP and fan RPM requirements using the fan performance curves. Then determine which motor to use.

7. Determine motor size. Check motor HP and fan RPM requirements to determine the correct motor and size.

8. The fan curves use the motor hp. Check CFM and SP to determine which motor and RPM will meet the application. Select TOPSS base performance in order to use the TOPSS calculated RPM.

BCX-PRC001E-EN 23

Page 24: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Selection Procedure

Cooling Selection Example

Job example:

• Horizontal blower coil

• 2-inch pleated media filters

• Mixing box with dampers

• Total capacity required: 53.0 MBh

• Sensible capacity required: 42.9 MBh

• Airflow: 2000 cfm, 0.25” ESP

• Entering air conditions: 80°F DB/67°F WB

• Entering water: 45°F

• Water temperature rise: 10°F

1. Determine unit capacity. Using Table 13, p. 60, the capacity of a BCHD 54 with a six-row coil, 10°F ΔT at 1800 cfm, is 74.51 MBh total and 52.3 MBh sensible. At 2250 cfm, it is 88.7 MBh total and 63.4 MBh sensible. Interpolate between these values for 2000 cfm to obtain 80.9 MBh total and 56.7 sensible.

2. Verify CFM and GPM limits. Using Table 13, p. 60, the water flow rate = 16.1 gpm. Reference Table 1, p. 26 and Table 10, p. 32 for airflow and water limits. Both the water flow rate (16.1 gpm) and airflow (2000 cfm) fall within the range specified for a BCHD054 with a six-row cooling coil.

3. Calculate WPD. From Table 13, p. 60, the water pressure drop for a size 54 unit, six-row coil at 16.1 gpm = 4.8 feet of water.

4. Check fan performance requirements. Calculate the air pressure drop for all components using Table 8, p. 30 and Table 10, p. 32, air pressure drop adjustment. Interpolate for 2000 cfm as follows:

5. Calculate TSP. Unit apd 1.135 inch wg + 0.25 inch wg ESP= 1.385 inch wg total static pressure.

6. Determine motor and drive size. Using Figure 41, p. 45 (fan performance), use the graph for 2000 cfm at 1.385 inches wg total static pressure to obtain 955 rpm and 1.0 HP 115/208-230V or 277V motor. Select TOPSS Base Performance to operate at 955 rpm.

6-row coil 0.934 inch wg2-inch pleated filter 0.175 inch wgmix. box/dampers 0.026 inch wg

1.135 inch wg

24 BCX-PRC001E-EN

Page 25: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Selection Procedure

Heating Selection Example

Select a heating coil for the BCHD054, selected in the cooling selection example. Operating conditions are:

• 2000 cfm

• EWT = 170°F

• EAT = 60°F

• LAT = 120°F

1. Determine unit capacity. Required capacity = CFM x 1.085 x (LAT - EAT) = 2000 x 1.085 x (120 - 60) = 130,200 Btu (130.2 MBh)

The capacity correction factor for a two-row coil is 0.917 for EAT = 60°F and EWT = 170°F. Corrected capacity required = 130.2/0.917 = 142.0 MBh

2. Verify water flow and airflow limits. Reference Table 1, p. 26 for water flow limits and Table 3, p. 28 for cfm limits. Both the water flow rate (10.9 gpm) and airflow (2000 cfm) fall within the range specified for a BCHD 054 with a 2-row heating coil.

3. Calculate water pressure drop (WPD). From Figure 27, p. 39, the water pressure drop for a size 54 unit is 20 feet of water. The wpd correction factor for the average water temperature through the coil from Table 28, p. 85 is 1.01. Corrected water pressure drop = 2.0 x 1.01 = 2.02 feet of water.

4. Calculate total static pressure and determine motor size. From Table 8, p. 30, air pressure drop for a BCHD size 54 two-row coil is 0.222 inches wg. Adding this pressure drop to the total static pressure (calculated in the cooling example) gives a total static pressure of 1.356 inches wg. From Figure 39, p. 106, use the graph for 2000 cfm and 1.446 inches wg, we obtain 975 rpm and 1.0 115/208-230V or 277V motor. Select TOPSS Base Performance to operate at 975 rpm.

10°F ΔT 15°F ΔT@1800 cfm 136.4 MBh 131.3 MBh

4.9 gpm 13.1 gpm@2250 cfm 156.9 MBh 150.7 MBh

6.4 gpm 15.1 gpm@2000 cfm 145.5 MBh 139.9 MBh

5.6 gpm 14.0 gpm

BCX-PRC001E-EN 25

Page 26: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

General Data

Table 1. BCHD/BCVD coil general data

Unit Size 12 18 24 36 54 72 90Nominal cfm 400 600 800 1200 1800 2400 3000Hydronic and DX coil dataArea - ft2 0.89 1.11 1.67 2.67 4.00 5.00 6.67Width - in. (a), (b) 8.00 8.00 12.00 12.00 18.00 18.00 24.00Length - in. (d) 16.00 20.00 20.00 32.00 32.00 40.00 40.00Velocity - ft/min. 450 540 480 450 450 480 450Hydronic coil data - high capacityArea - ft2 0.89 1.11 1.67 2.67 3.89 4.86 6.25Width - in. (a), (c) 8.00 8.00 12.00 12.00 17.50 17.50 22.50Length - in. (d) 16.00 20.00 20.00 32.00 32.00 40.00 40.00Velocity - ft/min. 450 540 480 450 463 494 4801-row coilMinimum gpm (e) 1.00 1.00 1.00 1.00 6.10 6.10 7.90Maximum gpm (f) 5.20 5.20 5.20 5.20 32.60 32.60 42.00Dry coil weight - lb 4.40 5.20 6.60 9.30 17.60 20.40 25.80Wet coil weight - lb 5.10 6.00 7.80 11.00 22.40 26.00 32.90Internal volume - in3 19.40 22.20 33.20 47.10 132.90 155.10 196.602-row coil - high capacityMinimum gpm (e) 1.00 1.00 2.00 2.00 6.10 6.10 7.90Maximum gpm (f) 5.20 5.20 10.40 10.40 32.60 32.60 42.00Dry coil weight - lb 5.90 7.00 9.90 14.10 27.20 32.10 39.40Wet coil weight - lb (kg) 7.20 8.40 12.30 17.60 36.10 42.50 52.60Internal volume - in3 36.00 38.80 66.50 96.90 246.50 288.00 365.504-row coil - standard capacityMinimum gpm (e) n/a n/a n/a n/a 8.80 8.80 11.70Maximum gpm (f) n/a n/a n/a n/a 47.00 47.00 62.60Dry coil weight - lb (g) n/a n/a n/a n/a 37.20 44.50 58.50Wet coil weight - lb (g) n/a n/a n/a n/a 48.30 57.70 77.00Internal volume - in3 (g) n/a n/a n/a n/a 307.40 365.50 512.304-row coil - high capacityMinimum gpm (e) 2.00 2.00 2.90 2.90 6.10 6.10 7.90Maximum gpm (f) 10.40 10.40 15.70 15.70 32.60 32.60 42.00Dry coil weight - lb 10.50 12.40 17.70 25.50 47.00 56.30 73.10Wet coil weight - lb 13.10 15.50 22.50 32.50 62.70 74.90 97.90Internal volume - in3 72.00 85.80 132.90 193.80 433.00 516.70 688.306-row coil - standard capacityMinimum gpm (e) n/a n/a n/a n/a 8.80 8.80 11.70Maximum gpm (f) n/a n/a n/a n/a 47.00 47.00 62.60Dry coil weight - lb (g) n/a n/a n/a n/a 52.40 63.10 82.70Wet coil weight - lb (g) n/a n/a n/a n/a 68.10 82.00 108.70Internal volume - in3 (g) n/a n/a n/a n/a 434.80 523.40 720.006-row coil - high capacityMinimum gpm (e) 2.0 2.00 2.90 2.90 6.10 6.10 7.90Maximum gpm (f) 10.4 10.40 15.70 15.70 32.60 32.60 42.00Dry coil weight - lb 14.6 17.40 24.70 36.10 65.40 78.60 101.50Wet coil weight - lb 18.2 21.80 31.50 46.10 87.80 105.60 137.00Internal volume - in3 99.7 121.80 188.30 276.90 620.40 745.90 983.10Steam coil dataArea - ft2 0.71 0.88 1.75 2.75 4.13 5.13 6.83Width - in. (a) 6.00 6.00 12.00 12.00 18.00 18.00 24.00Length - in. (d) 17.00 21.00 21.00 33.00 33.00 41.00 41.00Velocity - ft/min. 26.00 25.00 18.00 17.00 17.00 16.00 16.001-row coilMinimum steam press - psig 2.00 2.00 2.00 2.00 2.00 2.00 2.00Maximum steam press - psig 15.00 15.00 15.00 15.00 15.00 15.00 15.00Dry coil weight - lb 16.70 18.70 32.50 41.10 57.40 64.80 84.90Wet coil weight - lb 18.20 20.40 36.00 45.80 64.50 73.20 96.10Internal volume - in3 41.70 47.70 95.30 130.80 196.10 231.60 308.70

(a) Coil width = Length in the direction of a coil header, typically vertical.(b) “Hydronic and DX coil data” width dimensions apply only to DX coils (all unit sizes), 1-row standard capacity hydronic coils (unit sizes 012 through

036), and 4-row and 6-row standard capacity hydronic coils (054 through 090).(c) “High-capacity hydronic coil data” width dimensions apply only to 1-row standard capacity hydronic coils (unit sizes 054 through 090) and 2-row,

4-row, and 6-row high capacity hydronic coils (all unit sizes).(d) Coil length = Length of coil in direction of the coil tubes, typically horizontal and perpendicular to airflow.

26 BCX-PRC001E-EN

Page 27: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

General Data

(e) The minimum waterflow at 1.5 fps tubeside velocity is to ensure the coil self-vents properly. There is no minimum waterflow limit for coils that do not require self venting.

(f) Maximum gpm limits are to prevent erosion and noise problems.(g) DX coil height and width dimensions are same as comparable hydronic coils. Four- and six-row DX coil dry weight dimensions are same as comparable

4-row and 6-row hydronic coils. A 3-row DX coil dry weight is 25% less than a comparable 4-row hydronic coil. Internal volumes are approximately 6% less than comparable hydronic coils.

Table 2. BCCD coil general data

Unit size 24 36 48 60

Nominal cfm 800 1200 1600 2000

Hydronic coil and DX coil dataArea - ft2 1.67 2.50 3.47 4.17

Width - in. (a) 12.00 18.00 20.00 24.00

Length - in. (b) 20.00 20.00 25.00 25.00

Velocity - ft/min 480 480 461 480

1 - row coil

Minimum gpm (c) 1.40 1.40 2.30 2.70

Maximum gpm (d) 7.10 7.10 11.80 14.10

Dry coil weight - lb 4.80 6.30 8.30 9.60

Wet coil weight - lb 6.20 8.30 10.90 12.70

Internal volume - in3 38.80 55.40 72.00 85.90

2 - row coil

Minimum gpm (c) 2.70 4.10 4.50 5.40

Maximum gpm (d) 14.10 21.20 23.60 28.30

Dry coil weight - lb 7.60 10.50 13.80 16.20

Wet coil weight - lb 10.00 14.10 18.60 21.90

Internal volume - in3 66.50 99.70 133.00 157.90

4 - row coil

Minimum gpm (c) 2.70 4.10 4.50 5.40

Maximum gpm (d) 14.10 21.20 23.60 28.30

Dry coil weight - lb 14.60 20.00 27.00 31.50

Wet coil weight - lb 19.40 27.20 36.90 43.30

Internal volume - in3 133.00 199.50 274.30 326.90

6 - row coil

Minimum gpm (c) 2.70 4.10 4.50 5.40

Maximum gpm (d) 14.10 21.20 23.60 28.30

Dry coil weight - lb 19.70 27.70 37.50 44.10

Wet coil weight - lb 26.70 38.10 51.80 61.10

Internal volume - in3 193.90 288.10 396.20 471.00

BCX-PRC001E-EN 27

Page 28: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

General Data

Valve Package Waterflow Limits

Table 3. BCHD/BCVD fan, filter, and mixing box general data

Unit Size 12 18 24 36 54 72 90Nominal cfm 400 600 800 1200 1800 2400 3000AirflowMinimum cfm 250 375 500 750 1125 1500 1875Maximum cfm 500 675 1000 1600 2400 3000 4000Fan dataFan wheel, in. (dia. x width) 9.50 x 4.50 9.50x 4.50 9.50 x 6.00 9.50 x 6.00 12.60 x 9.50 12.60 x 9.50 12.60 x 9.50RPM range 900-2300 900-2300 800-2000 800-2000 600-1500 600-1500 600-1500Motor hp 0.50–1.00 0.50–1.00 0.50–1.00 0.50–1.00 0.50–3.00 0.50–3.00 0.50–3.00Unit flat filter

(Qty.) Size (1) 12 x 24 (1) 12 x 24 (1) 16 x 25 (2) 16 x 20 (2) 20 x 20 (1) 20 x 20(1) 20 x 25 (3) 16 x 25

Area, sq. ft 2.00 2.00 2.78 4.44 5.56 6.25 8.33Velocity, ft/min. 200 300 288 270 324 384 360Angle filter(Qty.) Size (2) 12 x 24 (2) 12 x 24 (2) 12 x 24 (2) 20 x 20 (4) 16 x 20 (6) 16 x 16 (6) 16 x 20Area, sq. ft 4.00 4.00 4.00 5.56 8.89 8.89 11.11Velocity, ft/min. 100 150 200 216 203 270 270Bottom/top access filter box

(Qty.) Size (1) 12 x 20 (1) 12 x 24 (1) 16 x 25 (1) 16 x 20(1) 16 x 16

(1) 16 x 20(1) 20 x 20

(1) 20 x 25(1) 20 x 20

(1) 16 x 25(2) 14 x 25

Area, sq. ft 1.70 2.00 2.80 4.00 5.00 6.30 8.00Velocity, ft/min. 240 300 288 300 360 384 375Mixing boxDamper opening width, in. 15.50 19.50 19.50 31.50 31.50 31.50 31.50Damper opening height, in. 7.00 7.00 7.00 7.00 12.75 12.75 12.75Area, sq. ft 0.75 0.958 0.958 1.53 2.79 2.79 2.79Velocity, ft/min. 531 633 844 784 645 861 1076Note: Minimum air flow limits apply to units with hot water or electric heat only. There is no minimum airflow limit on cooling only units. Maximum airflow

limits are to help prevent moisture carryover.

Table 4. BCCD fan and filter general data

Unit Size 24 36 48 60Nominal cfm 800 1200 1600 2000AirflowMinimum cfm 500 750 1000 1250Maximum cfm 1000 1500 2000 2500Fan dataFan wheel, in. (dia. x width) 9.50 x 6.00 9.50x 6.00 12.60 x 8.00 12.60 x 8.00RPM range 800-2000 800-2000 600-1400 600-1400Motor hp 0.50–1.00 0.50–1.00 0.50–1.00 0.50–1.00Unit flat filter

(Qty.) Size (1) 12 x 24 (1) 18 x 24(1) 18 x 20(1) 12 x 20

(1) 18 x 24(1) 12 x 24

Area, sq. ft 2.00 3.00 4.20 5.00Velocity, ft/min. 400 400 380 400Note: Minimum air flow limits apply to units with hot water or electric heat only. There is no minimum airflow limit on cooling

only units. Maximum airflow limits are to help prevent moisture carryover.

Table 5. Valve package waterflow limits

Tube Size (in.) GPM3/4 19.501 33.50

1-1/4 51.00

28 BCX-PRC001E-EN

Page 29: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

General Data

Coil Circuiting

Figure 14. Single refrigerant coil Figure 15. Horizontal face split DX coil

Table 6. BCHD/BCVD - number of circuits per coil

No. of Rows

Application Type1 Coil Type

Unit Size12 18 24 36 54 72 90

1 Heating Standard capacity 2 2 2 2 7 7 92 Heating High-capacity 2 2 4 4 7 7 93 Refrigerant DX 2 2 3 6 9 9 12

4Hydronic Standard capacity n/a n/a n/a n/a 18 18 18Hydronic High-capacity 4 4 6 6 7 7 9

Refrigerant DX 2 2 3 6 9 9 12

6Hydronic Standard capacity n/a n/a n/a n/a 18 18 18Hydronic High-capacity 2 2 4 4 7 7 9

Refrigerant DX 4 4 6 6 9 9/92 12/122

Note: 1Hydronic and refrigerant coils can be applied as heating or cooling. 2All refrigerant coils are single-circuit coils, except for sizes 72 and 90 with a 6-row coil, where there are two circuits that are face split.

Table 7. BCCD - number of circuits per coil

No. ofRows

ApplicationType1 Coil Type

Unit size

24 36 48 601 Heating High capacity 3 3 5 6

2 Heating High capacity 6 9 10 12

3 Refrigerant DX 6 9 10 12

4Hydronic High capacity

6 9 10 12Refrigerant DX

6Hydronic High capacity

6 9 10 12Refrigerant DX

Note: 1Hydronic and refrigerant coils can be applied as heating or cooling.

BCX-PRC001E-EN 29

Page 30: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Air Pressure Drop Adjustments

Table 8. BCHD/BCVD coil air pressure drop adjustments (in. wg)

Unit Size CFM

Coil Face

Velocity

2-Row 4-Row 6-Row DX CoolingHydronic

Heating CoilSteam

Coil Electric HeatHighCap

Std Cap

HighCap

StdCap

HighCap 3-Row 4-Row 6-Row 1-Row 2-Row 1-Row

Disch Velocity Delta P

12

250 300 0.13 – 0.26 – 0.39 0.19 0.26 0.39 0.05 0.08 0.09 490 0.03300 360 0.18 – 0.36 – 0.54 0.27 0.36 0.54 0.07 0.11 0.13 588 0.04350 420 0.24 – 0.47 – 0.71 0.35 0.47 0.71 0.09 0.14 0.16 686 0.04400 480 0.30 – 0.59 – 0.89 0.44 0.59 0.89 0.11 0.18 0.21 784 0.42450 540 0.36 – 0.72 – 1.08 0.54 0.72 1.08 0.14 0.21 0.25 882 0.05500 600 0.42 – 0.85 – 1.27 0.63 0.85 1.27 0.16 0.26 0.31 980 0.06

18

375 360 0.18 – 0.36 – 0.54 0.27 0.36 0.54 0.07 0.11 0.13 735 0.04450 432 0.25 – 0.49 – 0.74 0.37 0.49 0.74 0.09 0.15 0.18 882 0.05525 504 0.32 – 0.64 – 0.96 0.48 0.64 0.96 0.12 0.19 0.23 1029 0.06600 576 0.40 – 0.79 – 1.19 0.60 0.79 1.19 0.15 0.24 0.29 1176 0.07675 648 0.47 – 0.95 – 1.42 0.71 0.95 1.42 0.19 0.29 0.36 1324 0.08

24

500 288 0.12 – 0.24 – 0.36 0.18 0.24 0.36 0.05 0.08 0.06 571 0.03600 346 0.17 – 0.33 – 0.50 0.25 0.33 0.50 0.06 0.10 0.09 686 0.04700 403 0.22 – 0.44 – 0.66 0.33 0.44 0.66 0.08 0.13 0.11 800 0.05800 461 0.28 – 0.55 – 0.83 0.41 0.55 0.83 0.10 0.16 0.14 914 0.05900 518 0.34 – 0.67 – 1.01 0.50 0.67 1.01 0.13 0.20 0.18 1029 0.061000 576 0.40 – 0.79 – 1.19 0.60 0.79 1.19 0.15 0.24 0.21 1143 0.07

36

750 270 0.11 – 0.21 – 0.32 0.16 0.21 0.32 0.04 0.07 0.06 857 0.05900 324 0.15 – 0.30 – 0.44 0.22 0.30 0.44 0.06 0.09 0.08 1029 0.061050 378 0.20 – 0.39 – 0.59 0.29 0.39 0.59 0.07 0.12 0.11 1200 0.071200 432 0.25 – 0.49 – 0.74 0.37 0.49 0.74 0.09 0.15 0.13 1371 0.081350 486 0.30 – 0.60 – 0.91 0.45 0.60 0.91 0.11 0.18 0.16 1543 0.091500 540 0.36 – 0.72 – 1.08 0.54 0.72 1.08 0.14 0.21 0.20 1714 0.12

54

1125 289 0.12 0.24 0.25 0.36 0.37 0.18 0.24 0.36 0.05 0.09 0.06 960 0.061350 347 0.17 0.34 0.34 0.50 0.50 0.25 0.34 0.50 0.07 0.12 0.08 1152 0.071575 405 0.22 0.44 0.43 0.66 0.65 0.33 0.44 0.66 0.10 0.15 0.11 1344 0.081800 463 0.27 0.56 0.53 0.83 0.80 0.42 0.56 0.83 0.12 0.19 0.13 1536 0.092025 521 0.32 0.68 0.63 1.01 0.95 0.51 0.68 1.01 0.15 0.23 0.16 1728 0.122250 579 0.37 0.80 0.74 1.20 1.11 0.60 0.80 1.20 0.18 0.27 0.20 1920 0.16

72

1500 309 0.14 0.27 0.28 0.41 0.42 0.20 0.27 0.41 0.06 0.10 0.07 1280 0.071800 370 0.19 0.38 0.37 0.57 0.56 0.28 0.38 0.57 0.08 0.13 0.09 1536 0.092100 432 0.24 0.49 0.48 0.74 0.71 0.37 0.49 0.74 0.11 0.17 0.12 1792 0.132400 494 0.29 0.62 0.59 0.93 0.88 0.47 0.62 0.93 0.14 0.21 0.15 2048 0.182700 555 0.35 0.75 0.70 1.13 1.05 0.56 0.75 1.13 0.17 0.25 0.18 2304 0.243000 617 0.41 0.88 0.81 1.32 1.22 0.66 0.88 1.32 0.20 0.30 0.22 2560 0.31

90

1875 300 0.13 0.26 0.26 0.39 0.40 0.19 0.26 0.39 0.06 0.10 0.06 1600 0.102250 360 0.18 0.36 0.36 0.54 0.53 0.27 0.36 0.54 0.08 0.13 0.08 1920 0.162625 420 0.23 0.47 0.46 0.71 0.68 0.35 0.47 0.71 0.10 0.16 0.11 2240 0.233000 480 0.28 0.59 0.56 0.89 0.84 0.44 0.59 0.89 0.13 0.20 0.13 2560 0.313375 540 0.34 0.72 0.67 1.08 1.01 0.54 0.72 1.08 0.16 0.24 0.16 2880 0.413750 600 0.39 0.85 0.78 1.27 1.17 0.63 0.85 1.27 0.19 0.29 0.20 3200 0.53

Notes:

• Cooling coil APD is for a 100 percent fully wetted fin.• Heating coil APD is for dry fin surface.

30 BCX-PRC001E-EN

Page 31: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 9. BCCD coil air pressure drop adjustments (in. wg)

Unit Size CFM

Coil Face Velocity

Hydronic Coil DX CoolingHydronic Heating

Coil Electric Heat

4-Row 6-Row 3-Row 4-Row 6-Row 1-Row 2-RowDisch

Velocity Delta P

24

500 300 0.25 0.39 0.21 0.29 0.43 0.05 0.08 780.00 0.04

600 360 0.34 0.54 0.30 0.40 0.60 0.07 0.11 937.00 0.05

700 420 0.45 0.71 0.39 0.53 0.79 0.09 0.14 1093.00 0.06

800 480 0.56 0.89 0.50 0.66 0.99 0.11 0.17 1249.00 0.07

900 540 0.68 1.07 0.60 0.80 1.20 0.13 0.21 1405.00 0.08

1000 600 0.80 1.26 0.71 0.95 1.42 0.16 0.25 1561.00 0.09

36

750 300 0.25 0.39 0.21 0.29 0.43 0.05 0.08 1171.00 0.07

900 360 0.34 0.54 0.30 0.40 0.60 0.07 0.11 1405.00 0.08

1050 420 0.45 0.71 0.39 0.53 0.79 0.09 0.14 1639.00 0.11

1200 480 0.56 0.89 0.50 0.66 0.99 0.11 0.17 1873.00 0.15

1350 540 0.68 1.07 0.60 0.80 1.20 0.13 0.21 2107.00 0.19

1500 600 0.80 1.26 0.71 0.95 1.42 0.16 0.25 2341.00 0.25

48

1000 288 0.24 0.37 0.20 0.27 0.40 0.05 0.08 945.00 0.05

1200 346 0.33 0.51 0.28 0.37 0.56 0.06 0.10 1134.00 0.06

1400 403 0.43 0.67 0.37 0.49 0.73 0.08 0.13 1323.00 0.08

1600 461 0.54 0.84 0.46 0.62 0.92 0.10 0.16 1512.00 0.09

1800 518 0.65 1.02 0.56 0.75 1.13 0.13 0.20 1701.00 0.12

2000 576 0.77 1.20 0.67 0.89 1.33 0.15 0.24 1890.00 0.15

60

1250 300 0.26 0.39 0.21 0.29 0.43 0.05 0.08 1181.00 0.07

1500 360 0.35 0.55 0.30 0.40 0.60 0.07 0.11 1418.00 0.08

1750 420 0.46 0.72 0.39 0.53 0.79 0.09 0.14 1654.00 0.11

2000 480 0.58 0.90 0.50 0.66 0.99 0.11 0.17 1890.00 0.15

2250 540 0.70 1.09 0.60 0.80 1.20 0.13 0.21 2126.00 0.20

2500 600 0.82 1.28 0.71 0.95 1.42 0.16 0.25 2363.00 0.26

Note: Cooling coil APD is for a 100 percent fully wetted fin. Heating coil APD is for dry fin surface

BCX-PRC001E-EN 31

Page 32: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 10. BCHD/BCVD filter and mixing box air pressure drop adjustments (in. wg)

Unit Size CFM

Flat Filters Angle Filters Mixing Box

Velocity1-inch

Throwaway2-inch

MERV 82-inch

MERV 13 Velocity2-inch

MERV 82-inch

MERV 13 VelocityPressure

Drop

12

250 125 0.03 0.03 0.06 63 0.01 0.03 332 0.01300 150 0.04 0.04 0.08 75 0.01 0.03 398 0.01350 175 0.05 0.05 0.09 88 0.02 0.04 465 0.01400 200 0.06 0.07 0.11 100 0.02 0.05 531 0.02450 225 0.07 0.08 0.13 113 0.03 0.05 598 0.02500 250 0.08 0.10 0.14 125 0.03 0.06 664 0.02

18

375 188 0.05 0.06 0.10 94 0.02 0.04 396 0.01450 225 0.07 0.08 0.13 113 0.03 0.05 475 0.01525 263 0.08 0.10 0.15 131 0.03 0.06 554 0.02600 300 0.10 0.13 0.18 150 0.04 0.08 633 0.02675 338 0.12 0.16 0.2 169 0.05 0.09 712 0.03

24

500 180 0.05 0.06 0.10 125 0.03 0.06 527 0.01600 216 0.06 0.08 0.12 150 0.04 0.08 633 0.02700 252 0.08 0.10 0.15 175 0.05 0.09 738 0.03800 288 0.10 0.12 0.17 200 0.07 0.11 844 0.04900 324 0.11 0.15 0.20 225 0.08 0.13 949 0.051000 360 0.13 0.18 0.23 250 0.10 0.14 1055 0.06

36

750 169 0.05 0.05 0.09 135 0.04 0.07 490 0.01900 203 0.06 0.07 0.11 162 0.05 0.08 588 0.021050 236 0.07 0.09 0.13 189 0.06 0.10 686 0.021200 270 0.09 0.11 0.16 216 0.08 0.12 784 0.031350 304 0.10 0.13 0.18 243 0.09 0.14 882 0.041500 338 0.12 0.16 0.21 270 0.11 0.16 980 0.05

54

1125 202 0.06 0.07 0.11 127 0.03 0.06 403 0.011350 243 0.08 0.09 0.14 152 0.04 0.08 484 0.011575 283 0.09 0.12 0.17 177 0.06 0.09 565 0.021800 324 0.11 0.15 0.20 202 0.07 0.11 645 0.022025 364 0.13 0.18 0.23 228 0.08 0.13 726 0.032250 405 0.15 0.21 0.26 253 0.10 0.15 807 0.03

72

1500 240 0.07 0.09 0.14 169 0.05 0.09 538 0.021800 288 0.10 0.12 0.17 202 0.07 0.11 645 0.022100 336 0.12 0.16 0.21 236 0.09 0.13 753 0.032400 384 0.14 0.20 0.25 270 0.11 0.16 861 0.042700 432 0.16 0.24 0.28 304 0.13 0.18 768 0.053000 480 0.19 0.28 0.32 337 0.16 0.21 1076 0.06

90

1875 225 0.07 0.08 0.13 169 0.05 0.09 672 0.022250 270 0.09 0.11 0.16 203 0.07 0.11 807 0.032625 315 0.11 0.14 0.19 236 0.09 0.13 941 0.043000 360 0.13 0.18 0.23 270 0.11 0.16 1076 0.063750 450 0.15 0.21 0.26 304 0.13 0.18 1210 0.073375 405 0.17 0.25 0.30 338 0.16 0.21 1345 0.09

Note: Data based on clean filters.

32 BCX-PRC001E-EN

Page 33: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 11. BCCD filter air pressure drop adjustments (in. wg)

Unit Size CFM

Flat Filters

Velocity1-inch

Throwaway2-inch

MERV 82-inch

MERV 13

24

500 250 0.08 0.10 0.14600 300 0.10 0.13 0.18700 350 0.12 0.17 0.22800 400 0.15 0.21 0.26900 450 0.17 0.25 0.311000 500 0.20 0.30 0.35

36

750 250 0.08 0.10 0.14900 300 0.10 0.13 0.181050 350 0.12 0.17 0.221200 400 0.15 0.21 0.261350 450 0.17 0.25 0.311500 500 0.20 0.30 0.35

48

1000 240 0.07 0.09 0.131200 288 0.09 0.12 0.171400 336 0.12 0.16 0.211600 384 0.14 0.19 0.251800 432 0.16 0.24 0.292000 480 0.19 0.28 0.33

60

1250 250 0.08 0.10 0.141500 300 0.10 0.13 0.181750 350 0.12 0.17 0.222000 400 0.15 0.21 0.262250 450 0.17 0.25 0.312500 500 0.20 0.30 0.35

Note: Data based on clean filters.

BCX-PRC001E-EN 33

Page 34: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Water Pressure Drop

Figure 16. Two-way basic piping package water pressure drop

Figure 17. Two-way deluxe piping package water pressure drop

0.00

0.01

0.10

1.00

10.00

100.00

1000.00

0.1 1 10 100Volumetric flow rate (gpm)

Wat

er p

ress

ure

drop

(ft

of H

2O)

3/4" 2-way basic 2.3 Cv

3/4" 2-way basic 3.3 Cv

3/4" 2-way basic 4.6 Cv

1" 2-way basic 7.4 Cv1.25" 2-way basic 10.0 Cv

0.00

0.01

0.10

1.00

10.00

100.00

1000.00

0.1 1 10 100Volumetric flow rate (gpm)

Wat

er p

ress

ure

drop

(ft

of H

2O)

3/4" 2-way deluxe 2.3 Cv

3/4" 2-way deluxe 3.3 Cv

3/4" 2-way deluxe 4.6 Cv

1" 2-way deluxe 7.4 Cv

1.25" 2-way deluxe 10.0 Cv

34 BCX-PRC001E-EN

Page 35: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 18. Three-way basic piping package water pressure drop

Figure 19. Three-way deluxe piping package water pressure drop

0.00

0.01

0.10

1.00

10.00

100.00

1000.00

0.1 1 10 100Volumetric flow rate (gpm)

3/4" 3-way basic 1.0 Cv

3/4" 3-way basic 2.7 Cv

3/4" 3-way basic 4.6 Cv

1" 3-way basic 7.4 Cv

1.25" 3-way basic 10.0 Cv

Wat

er p

ress

ure

drop

(ft

of H

2O)

0.00

0.01

0.10

1.00

10.00

100.00

1000.00

10000.00

0.1 1 10 100Volumetric flow rate (gpm)

3/4" 3-way deluxe 1.0 Cv

3/4" 3-way deluxe 2.7 Cv

3/4" 3-way deluxe 4.6 Cv

1" 3-way deluxe 7.4 Cv

1.25" 3-way deluxe 10.0 Cv

Wat

er p

ress

ure

drop

(ft

of H

2O)

BCX-PRC001E-EN 35

Page 36: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 20. Four-row standard cooling coil water pressure drop

Figure 21. Six-row standard cooling coil water pressure drop

Size 54Size 72Size 90

Wat

er p

ress

ure

drop

(ft

of H

2O)

Volumetric flow rate (gpm)

100.0

10.0

1.0

0.1 1 10 100

Size 54Size 72Size 90

Wat

er p

ress

ure

drop

(ft

of H

2O)

Volumetric flow rate (gpm)

100.0

10.0

1.0

1 10 1000.10

36 BCX-PRC001E-EN

Page 37: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 22. Four-row high-capacity cooling coil water pressure drop

Figure 23. Six-row high-capacity cooling coil water pressure drop

Size 12Size 18Size 24Size 36Size 54Size 72Size 90

Wat

er p

ress

ure

drop

(ft

of H

2O)

Volumetric flow rate (gpm)

100.0

10.0

1.0

0.10.1 1 10 100

0.10

Size 12Size 18Size 24Size 36Size 54Size 72Size 90

Wat

er p

ress

ure

drop

(ft

of H

2O)

Volumetric flow rate (gpm)

100.0

10.0

1.0

0.1 0.1 1 10 100

BCX-PRC001E-EN 37

Page 38: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 24. One-row standard heating coil water pressure drop

Figure 25. Four-row standard heating coil water pressure drop

Size 12Size 18Size 24Size 36Size 54Size 72Size 90

Wat

er p

ress

ure

drop

(ft

of H

2O)

Volumetric flow rate (gpm)

100.0

10.0

1.0

0.10.1 1 10 100

0.10

Size 54Size 72Size 90

Wat

er p

ress

ure

drop

(ft

of H

2O)

Volumetric flow rate (gpm)

100.0

10.0

1.0

0.011 10 100

0.10

38 BCX-PRC001E-EN

Page 39: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 26. Six-row standard heating coil water pressure drop

Figure 27. Two-row high-capacity heating coil water pressure drop

Size 54Size 72Size 90

Wat

er p

ress

ure

drop

(ft

of H

2O)

Volumetric flow rate (gpm)

100.0

10.0

1.0

1 10 1000.10

Size 12Size 18Size 24Size 36Size 54Size 72Size 90

Wat

er p

ress

ure

drop

(ft

of H

2O)

Volumetric flow rate (gpm)

100.0

10.0

1.0

0.11 10 100

BCX-PRC001E-EN 39

Page 40: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 28. Four-row high-capacity heating coil water pressure drop

Figure 29. Six-row high-capacity heating coil water pressure drop

Size 12Size 18Size 24Size 36Size 54Size 72Size 90

Wat

er p

ress

ure

drop

(ft

of H

2O)

Volumetric flow rate (gpm)

100.0

10.0

1.0

0.1 0.1 1 10 100

Size 12Size 18Size 24Size 36Size 54Size 72Size 90

Wat

er p

ress

ure

drop

(ft

of H

2O)

Volumetric flow rate (gpm)

100.0

10.0

1.0

0.1 0.1 1 10 100

40 BCX-PRC001E-EN

Page 41: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 30. BCCD 6-row cooling coil water pressure drop

Figure 31. BCCD 4-row cooling coil water pressure drop

0.10

1.00

10.00

100.00

0.1 1 10 100

Wat

er p

ress

ure

drop

(ft

H20

)

Volumetric flow rate (gpm)

Size 60

Size 48

Size 36

Size 24

0.05

0.50

5.00

50.00

0.1 1 10 100

Wat

er p

ress

ure

drop

(ft

H20

)

Volumetric flow rate (gpm)

Size 60

Size 48

Size 36

Size 24

BCX-PRC001E-EN 41

Page 42: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 32. BCCD 1-row heating coil water pressure drop

Figure 33. BCCD 2-row heating coil water pressure drop

0.10

1.00

10.00

100.00

1 10

Wat

er p

ress

ure

drop

(ft

H20

)

Volumetric flow rate (gpm)

Size 60

Size 48

Size 36

Size 24

0.10

1.00

10.00

100.00

1 10 100

Wat

er p

ress

ure

drop

(ft

H20

)

Volumetric flow rate (gpm)

Size 60

Size 48

Size 36

Size 24

42 BCX-PRC001E-EN

Page 43: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Fan arrangements

Figure 34. BCHD horizontal draw-thru arrangement

Figure 35. BCVD vertical preswirl arrangement Figure 36. BCVD vertical counterswirl arrangement

Vertical preswirlVertical

counterswirl

BCX-PRC001E-EN 43

Page 44: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Fan Curves

Figure 37. BCCD bottom return arrangement Figure 38. BCCD front return arrangement

Figure 39. Fan performance - BCHD horizontal draw-thru units size 12-18

2.0

1.0

0.01000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

3.0

4.0

5.0

200 400 600 800 1200 1400 15000

44 BCX-PRC001E-EN

Page 45: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 40. Fan performance for BCHD horizontal draw-thru units size 24-36

Figure 41. Fan performance for BCHD horizontal draw-thru units size 54-72

2.5

2.0

1.5

1.0

0.5

0.00 500 1000 1500 2000 2500 3000 3500

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

3.0

3.5

4.0

2.5

2.0

1.5

1.0

0.5

0.00 500 1000 1500 2000 2500 3000 3500 4000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

3.0

3.5

BCX-PRC001E-EN 45

Page 46: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 42. Fan performance for BCHD horizontal draw-thru units size 90

Figure 43. Fan performance for BCVD vertical draw-thru preswirl units size 24-36

2.5

2.0

1.5

1.0

0.5

0.00 500 1000 1500 2000 2500 3000 3500 4000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

4500

2.5

2.0

1.5

1.0

0.5

0.00 500 1000 1500 2000 2500 3000 3500

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

3.0

3.5

4.0

46 BCX-PRC001E-EN

Page 47: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 44. Fan performance for BCVD vertical draw-thru preswirl units size 54-72

Figure 45. Fan performance for BCVD vertical draw-thru preswirl units size 90

2.5

2.0

1.5

1.0

0.5

0.00 500 1000 1500 2000 2500 3000 3500 4000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)3.0

2.5

2.0

1.5

1.0

0.5

0.00 500 1000 1500 2000 2500 3000 3500 4000 4500

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

BCX-PRC001E-EN 47

Page 48: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 46. Fan performance for BCVD vertical draw-thru counterswirl units size 24-36

Figure 47. Fan performance for BCVD vertical draw-thru counterswirl units size 54-72

2.5

2.0

1.5

1.0

0.5

0.00 500 1000 1500 2000 2500 3000 3500

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

) 3.0

3.5

2.5

2.0

1.5

1.0

0.5

0.00 500 1000 1500 2000 2500 3000 3500 4000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

3.0

48 BCX-PRC001E-EN

Page 49: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 48. Fan performance for BCVD vertical draw-thru counterswirl units size 90

Figure 49. Fan performance for BCHD 3-phase horizontal draw-thru units size 12-18

2.5

2.0

1.5

1.0

0.5

0.00 500 1000 1500 2000 2500 3000 3500 4000 4500

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

2.5

2.0

1.5

1.0

0.5

0.00 200 600 800 1000 1200 1400

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

3.0

3.5

400

4.0

4.5

1600

BCX-PRC001E-EN 49

Page 50: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 50. Fan performance for BCHD 3-phase horizontal draw-thru units size 24-36

Figure 51. Fan performance for BCHD 3-phase horizontal draw-thru units size 54-72

2.5

2.0

1.5

1.0

0.5

0.00 1000 3000 4000 5000 6000 7000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

) 3.0

3.5

2000

4.0

50 BCX-PRC001E-EN

Page 51: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 52. Fan performance for BCHD 3-phase horizontal draw-thru units size 90

Figure 53. Fan performance for BCVD 3-phase vertical draw-thru preswirl units size 24-36

2.5

2.0

1.5

1.0

0.5

0.00 2000 3000 4000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

3.0

3.5

1000 5000 6000 7000 8000 9000

BCX-PRC001E-EN 51

Page 52: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 54. Fan performance for BCVD 3-phase vertical draw-thru preswirl units size 54-72

Figure 55. Fan performance for BCVD 3-phase vertical draw-thru preswirl units size 90

2.5

2.0

1.5

1.0

0.5

0.00 1000 2000 3000 4000 5000 6000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

) 3.0

3.5

2.5

2.0

1.5

1.0

0.5

0.00 1000 2000 3000 4000 5000 6000 7000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

) 3.0

3.5

8000

52 BCX-PRC001E-EN

Page 53: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 56. Fan performance for BCVD 3-phase vertical draw-thru counterswirl units size 24-36

Figure 57. Fan performance for BCVD 3-phase vertical draw-thru counterswirl units size 54-72

2.5

2.0

1.5

1.0

0.5

0.00 1000 2000 3000 4000 5000 6000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

) 3.0

3.5

BCX-PRC001E-EN 53

Page 54: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 58. Fan performance for BCVD 3-phase vertical draw-thru counterswirl units size 90

Figure 59. Fan performance - BCHD 3-phase horz draw-thru unit size 54-72 with 1.5-3 HP motor

2.5

2.0

1.5

1.0

0.5

0.00 1000 2000 3000 4000 5000 6000 7000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

) 3.0

3.5

8000 9000

2.5

2.0

1.5

1.0

0.5

0.0

Tota

l sta

tic p

ress

ure

(in

H20

) 3.0

3.5

4.0

0 1000 3000 4000 5000 6000 7000Airflow (cfm)

2000

54 BCX-PRC001E-EN

Page 55: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 60. Fan performance - BCHD 3-phase horz draw-thru unit size 90 with 1.5-3 HP motor

Figure 61. Fan perform-BCVD 3-ph horz draw-thru preswirl unit size 54-72 with 1.5-3 HP motor

2.5

2.0

1.5

1.0

0.5

0.00 2000 3000 4000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

3.0

3.5

1000

4.0

5000 6000 7000 8000 9000

2.5

2.0

1.5

1.0

0.5

0.00 1000 2000 3000 4000 5000 6000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

) 3.0

3.5

BCX-PRC001E-EN 55

Page 56: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 62. Fan perform-BCVD 3-phase horz draw-thru preswirl unit size 90 with 1.5-3 HP motor

Figure 63. Fan perform-BCVD 3-ph horz draw-thru counterswirl unit size 54-72 w/1.5-3 HP

motor

2.5

2.0

1.5

1.0

0.5

0.00 1000 2000 3000 4000 5000 6000 7000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

3.0

3.5

8000

2.5

2.0

1.5

1.0

0.5

0.00 1000 2000 3000 4000 5000 6000 7000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

)

3.0

3.5

56 BCX-PRC001E-EN

Page 57: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 64. Fan perform-BCVD 3-ph horz draw-thru counterswirl unit size 90 w/1.5-3 HP motor

Figure 65. Fan performance - BCCD 1-phase compact vertical unit size 24-36

2.5

2.0

1.5

1.0

0.5

0.00 1000 2000 3000 4000 5000 6000 7000

Airflow (cfm)

Tota

l sta

tic p

ress

ure

(in

H20

) 3.0

3.5

8000 9000

4.0

BCX-PRC001E-EN 57

Page 58: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Figure 66. Fan performance - BCCD 3-phase compact vertical unit size 24-36

Figure 67. Fan performance - BCCD 1-phase compact vertical unit size 48-60

58 BCX-PRC001E-EN

Page 59: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Chilled Water Cooling Capacities

Figure 68. Fan performance - BCCD 3-phase compact vertical unit size 48-60

Table 12. BCHD/BCVD chilled water cooling capacities, EAT = 80° F DB / 67° F WB and EWT = 40° F EWT

Unit Size

Coil Rows

Air Flow

Water Temperature Rise - °F10°F 12°F

TC SC LDB LWB GPM WPD TC SC LDB LWB GPM WPD

54

41350 53.80 38.00 54.50 54.00 10.70 1.80 35.50 30.80 59.30 58.80 5.90 0.601800 68.90 49.00 55.30 54.60 13.70 2.80 32.10 31.40 63.80 61.60 5.30 0.702250 81.40 58.80 56.30 55.40 16.20 3.80 41.20 40.30 63.40 61.40 6.90 1.00

61350 75.50 47.90 47.80 47.70 15.00 4.30 67.60 44.30 50.20 50.10 11.20 2.501800 96.10 61.70 48.90 48.80 19.10 6.60 87.10 57.70 50.90 50.80 14.50 4.002250 114.20 74.20 50.10 49.90 22.70 9.10 104.00 69.80 51.90 51.60 17.30 5.50

72

41800 81.30 54.50 52.50 52.10 16.20 4.20 69.00 49.40 55.10 54.60 11.50 2.202400 100.80 69.00 53.90 53.30 20.10 6.20 87.90 63.60 56.00 55.20 14.60 3.403000 117.20 81.70 55.30 54.40 23.30 8.30 103.30 76.10 57.00 56.00 17.20 4.60

61800 104.90 65.80 46.90 46.80 20.90 8.70 97.60 62.40 48.60 48.50 16.20 5.402400 132.20 84.00 48.20 48.10 26.30 13.20 123.30 80.00 49.80 49.60 20.50 8.303000 156.10 100.60 49.60 49.30 31.10 18.00 145.80 96.00 51.00 50.70 24.20 11.30

90

42250 102.90 68.80 52.30 51.80 20.50 3.70 86.60 62.00 55.00 54.60 14.40 1.903000 128.40 87.40 53.60 53.00 25.60 5.50 111.40 80.30 55.70 55.10 18.50 3.003750 149.80 103.90 54.90 54.00 29.80 7.30 131.70 96.40 56.70 55.80 21.90 4.10

62250 132.40 82.80 46.60 46.50 26.40 7.60 123.00 78.50 48.40 48.30 20.40 4.703000 167.60 106.20 47.90 47.80 33.40 11.70 156.30 101.00 49.40 49.30 25.90 7.303750 198.60 127.50 49.20 49.00 39.60 15.90 185.40 121.60 50.60 50.40 30.80 10.00

Notes:

• Light shading = GPM is below the minimum (<1.5 fps self-venting velocity) or WPD is above the maximum (>10 ft wg) recommended for most applications.• Dark shading = GPM is below the AHRI limits (1.0 fps tube side velocity).• Some of the volumetric flow rates are less than those required for self-venting. For more information, refer to the BCHD/BCVD coil general data table.• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

BCX-PRC001E-EN 59

Page 60: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 13. BCHD/BCVD chilled water cooling capacities, EAT = 80° F DB / 67° F WB and EWT = 45° F

Unit Size

Coil Rows

Air Flow

Water Temperature Rise - °F10°F 12°F

TC SC LDB LWB GPM WPD TC SC LDB LWB GPM WPD

54

41350 36.10 31.00 59.20 58.70 7.20 0.80 28.30 28.20 61.10 60.60 4.70 0.401800 49.10 41.30 59.20 58.50 9.80 1.50 32.10 31.40 63.80 61.60 5.30 0.702250 59.40 50.30 59.70 58.80 11.80 2.10 41.20 40.30 63.40 61.40 6.90 1.00

61350 58.20 40.30 52.90 52.80 11.60 2.60 48.60 36.40 55.50 55.40 8.10 1.401800 74.50 52.30 53.60 53.50 14.90 4.10 64.40 48.20 55.70 55.50 10.70 2.302250 88.70 63.40 54.50 54.20 17.70 5.70 77.80 59.00 56.20 56.00 12.90 3.20

72

41800 60.50 46.00 56.80 56.30 12.10 2.40 46.00 40.50 59.60 59.10 7.60 1.002400 76.10 58.90 57.70 57.00 15.20 3.70 62.40 53.70 59.70 58.90 10.40 1.803000 89.00 70.50 58.70 57.70 17.70 4.90 75.20 65.20 60.30 59.20 12.50 2.60

61800 83.00 56.00 51.80 51.70 16.50 5.60 74.40 52.40 53.60 53.50 12.40 3.302400 104.50 71.80 52.80 52.70 20.80 8.50 94.70 67.80 54.40 54.20 15.70 5.103000 123.20 86.40 53.90 53.60 24.60 11.50 112.20 81.90 55.20 55.00 18.60 6.90

90

42250 76.20 57.80 56.70 56.20 15.20 2.10 56.00 50.10 59.80 59.30 9.30 0.803000 96.60 74.40 57.50 56.80 19.30 3.20 78.30 67.40 59.60 58.90 13.00 1.603750 113.60 89.30 58.40 57.50 22.60 4.30 95.20 82.30 60.10 59.10 15.80 2.20

62250 104.70 70.40 51.60 51.50 20.90 4.90 93.70 65.70 53.50 53.40 15.60 2.903000 132.50 90.70 52.60 52.40 26.40 7.50 119.90 85.40 54.20 54.00 19.90 4.503750 156.80 109.30 53.60 53.30 31.30 10.20 142.60 103.50 55.00 54.70 23.70 6.10

Notes:

• Light shading = GPM is below the minimum (<1.5 fps self-venting velocity) or WPD is above the maximum (>10 ft wg) recommended for most applications.• Dark shading = GPM is below the AHRI limits (1.0 fps tube side velocity).• Some of the volumetric flow rates are less than those required for self-venting, For more information, refer to the BCHD/BCVD coil general data table.• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

60 BCX-PRC001E-EN

Page 61: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

High-Capacity Chilled Water Cooling Capacities

Table 14. BCHD/BCVD chilled water high-capacity cooling capacities, EAT = 80° F DB / 67° F WB and EWT = 40° F

Unit Size

Coil Rows

Air Flow

Water Temperature Rise - °F10°F 12°F

TC SC LDB LWB GPM WPD TC SC LDB LWB GPM WPD

12

4300 12.60 8.70 53.70 53.20 2.50 2.20 10.30 7.80 56.60 56.10 1.70 1.10400 15.70 11.10 54.90 54.20 3.10 3.20 13.20 10.00 57.20 56.50 2.20 1.70500 18.40 13.20 56.10 55.20 3.70 4.30 15.60 12.10 58.10 57.10 2.60 2.30

6300 16.90 10.70 47.60 47.50 3.40 4.90 15.50 10.10 49.60 49.50 2.60 3.00400 21.40 13.70 48.80 48.70 4.30 7.50 19.70 12.90 50.60 50.50 3.30 4.60500 25.40 16.50 50.00 49.80 5.10 10.30 23.30 15.60 51.70 51.50 3.90 6.30

18

4450 20.00 13.40 52.90 52.40 4.00 5.40 17.60 12.50 54.90 54.30 2.90 3.10600 24.40 16.80 54.60 53.80 4.90 7.80 21.70 15.70 56.30 55.40 3.60 4.50750 28.10 19.80 56.00 55.00 5.60 10.10 25.10 18.60 57.50 56.40 4.20 5.90

6450 25.70 16.20 47.30 47.20 5.10 11.50 24.10 15.40 48.90 48.80 4.00 7.30600 32.10 20.60 48.90 48.70 6.40 17.20 30.00 19.60 50.30 50.10 5.00 10.90750 37.70 24.50 50.30 50.00 7.50 23.10 35.20 23.40 51.70 51.40 5.80 14.60

24

4600 27.40 18.30 52.30 51.90 5.50 4.10 24.10 16.90 54.40 54.00 4.00 2.30800 33.80 23.10 53.90 53.20 6.70 6.00 29.90 21.50 55.70 55.00 5.00 3.401000 39.10 27.30 55.30 54.30 7.80 7.80 34.90 25.50 56.80 55.90 5.80 4.50

6600 35.00 22.00 46.80 46.70 7.00 8.80 32.80 20.90 48.40 48.30 5.40 5.60800 44.10 28.00 48.20 48.10 8.80 13.30 41.20 26.70 49.70 49.50 6.80 8.501000 52.00 33.60 49.60 49.30 10.40 18.00 48.60 32.00 50.90 50.70 8.10 11.40

36

4900 46.80 30.00 49.70 49.40 9.30 13.70 43.50 28.60 51.20 50.80 7.20 8.601200 57.50 37.60 51.60 51.00 11.50 19.90 53.50 35.90 52.90 52.30 8.90 12.501500 66.70 44.40 53.10 52.30 13.30 26.00 61.90 42.40 54.40 53.50 10.30 16.30

6900 56.10 34.60 45.10 45.00 11.20 26.50 53.70 33.50 46.20 46.10 8.90 17.701200 70.90 44.30 46.50 46.40 14.10 40.40 67.70 42.80 47.70 47.50 11.20 26.601500 84.30 53.20 47.80 47.60 16.80 55.00 80.00 51.30 49.00 48.80 13.30 36.00

54

41350 62.70 41.80 51.90 51.60 12.50 4.50 56.70 39.20 53.60 53.20 9.40 2.701800 76.50 52.40 53.60 53.10 15.30 6.50 69.60 49.50 55.10 54.50 11.60 3.802250 88.10 62.00 55.00 54.30 17.60 8.30 80.20 58.70 56.30 55.60 13.30 5.00

61350 78.90 49.50 46.80 46.70 15.80 9.40 74.60 47.50 48.10 48.00 12.40 6.101800 98.90 63.10 48.20 48.10 19.80 14.10 93.30 60.50 49.50 49.40 15.50 9.002250 116.60 75.50 49.60 49.40 23.30 19.00 109.50 72.30 50.90 50.70 18.20 12.00

72

41800 86.20 56.80 51.40 51.00 17.20 9.10 79.80 54.00 52.80 52.40 13.30 5.602400 104.80 71.00 53.20 52.60 21.00 12.90 96.80 67.60 54.50 53.90 16.10 7.903000 120.40 83.60 54.70 54.00 24.10 16.60 111.00 79.70 55.90 55.10 18.40 10.20

61800 106.60 66.70 46.40 46.30 21.30 18.50 101.60 64.30 47.60 47.50 16.90 12.102400 133.50 84.80 48.00 47.90 26.70 27.80 126.60 81.60 49.20 49.00 21.00 17.903000 157.10 101.40 49.40 49.20 31.40 37.20 148.50 97.40 50.50 50.40 24.60 23.80

90

42250 111.80 72.80 50.70 50.30 22.40 9.00 103.90 69.30 52.10 51.70 17.20 5.603000 136.60 91.20 52.50 51.90 27.30 12.90 126.60 86.80 53.80 53.20 21.00 8.003750 157.60 107.60 54.00 53.30 31.50 16.70 145.60 102.50 55.20 54.40 24.20 10.30

62250 136.50 84.90 45.80 45.70 27.30 18.10 130.50 81.90 47.00 46.90 21.70 11.803000 171.80 108.30 47.30 47.20 34.40 27.30 163.40 104.40 48.40 48.30 27.10 17.703750 203.00 129.70 48.60 48.50 40.60 36.80 192.30 124.80 49.80 49.60 31.90 23.70

Notes:

• Light shading = GPM is below the minimum (<1.5 fps self-venting velocity) or WPD is above the maximum (>10 ft wg) recommended for most applications.• Dark shading = GPM is below the AHRI limits (1.0 fps tube side velocity).• Some of the volumetric flow rates are less than those required for self-venting. For more information, refer to the BCHD/BCVD coil general data table.• Capacities calculated with 0.00000 tube-side fouling factor.• High-capacity coils applicable where higher water pressure differentials are acceptable and are also recommended for EarthwiseTM applications.• EarthwiseTM is a trademark of Trane to identify equipment designed for applications requiring greater water temperature rises, lower entering water

temperatures (EWT) and lower air supply temperatures (LDB).• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

BCX-PRC001E-EN 61

Page 62: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 14. BCHD/BCVD chilled water high-capacity cooling capacities, EAT = 80° F DB / 67° F WB and EWT = 40° F

Unit Size

Coil Rows

Air Flow

Water Temperature Rise - ° F16° F 20° F

TC SC LDB LWB GPM WPD TC SC LDB LWB GPM WPD

12

4300 7.90 6.80 59.30 58.80 1.00 0.40 6.90 6.50 60.40 59.90 0.70 0.20400 8.90 8.40 60.90 60.10 1.10 0.50 8.20 8.20 61.50 60.70 0.90 0.30500 10.00 10.00 61.80 60.90 1.30 0.70 8.50 8.30 64.60 61.90 0.90 0.50

6300 11.60 8.40 54.60 54.50 1.40 1.10 9.70 7.60 56.90 56.80 1.00 0.50400 15.20 11.10 54.90 54.70 1.90 1.70 11.10 9.50 58.50 58.30 1.10 0.70500 18.40 13.50 55.40 55.20 2.30 2.40 12.30 11.20 59.60 59.40 1.20 0.80

18

4450 11.30 10.00 59.90 59.20 1.40 0.80 9.40 9.30 61.30 60.60 0.93 0.40600 15.20 13.20 60.10 59.20 1.90 1.40 10.50 10.00 64.60 61.70 1.05 0.50750 18.30 16.00 60.60 59.50 2.30 2.00 11.50 11.20 66.20 62.40 1.14 0.70

6450 19.90 13.60 52.50 52.40 2.50 3.10 14.20 11.30 57.10 57.00 1.40 1.10600 25.10 17.50 53.50 53.30 3.10 4.70 19.00 15.10 57.20 57.00 1.90 1.90750 29.60 21.00 54.50 54.20 3.70 6.30 23.00 18.50 57.70 57.30 2.30 2.70

24

4600 15.20 13.40 59.70 59.10 1.90 0.60 13.30 12.80 60.70 60.20 1.30 0.30800 20.40 17.70 59.90 59.10 2.50 1.00 14.70 14.70 63.40 61.40 1.40 0.401000 25.00 21.70 60.30 59.30 3.10 1.50 16.40 15.60 65.60 62.00 1.60 0.50

6600 27.00 18.40 52.20 52.10 3.40 2.40 18.70 15.10 57.20 57.10 1.90 0.80800 34.40 23.70 53.10 52.90 4.30 3.70 25.50 20.20 57.10 56.90 2.60 1.401000 40.70 28.70 54.00 53.70 5.10 4.90 31.30 24.90 57.40 57.10 3.10 2.10

36

4900 35.90 25.30 54.50 54.00 4.50 3.60 25.40 21.20 58.70 58.20 2.50 1.301200 44.70 32.20 55.70 55.00 5.60 5.40 33.90 27.90 58.90 58.20 3.40 2.201500 52.00 38.30 56.80 55.90 6.50 7.00 40.70 33.90 59.50 58.60 4.10 3.00

6900 48.20 30.90 48.80 48.70 6.00 8.70 40.80 27.70 52.10 52.00 4.10 4.301200 60.50 39.50 50.10 50.00 7.50 13.00 51.70 35.70 53.00 52.80 5.20 6.601500 71.20 47.30 51.40 51.20 8.90 17.30 61.10 43.10 54.00 53.70 6.10 8.80

54

41350 41.20 33.00 57.80 57.40 5.20 0.90 25.90 25.90 62.60 61.20 2.60 0.301800 52.90 42.90 58.40 57.80 6.60 1.40 29.60 29.60 65.10 62.00 3.00 0.302250 60.90 50.70 60.00 59.10 7.60 1.80 39.50 39.50 64.10 61.70 4.00 0.60

61350 63.70 42.60 51.40 51.30 8.00 2.80 49.40 36.70 55.30 55.20 4.90 1.201800 79.90 54.70 52.50 52.30 10.00 4.10 64.00 48.20 55.80 55.60 6.40 1.902250 93.90 65.70 53.50 53.40 11.70 5.50 76.30 58.60 56.40 56.20 7.60 2.50

72

41800 64.60 47.80 55.90 55.50 8.10 2.30 45.10 40.30 59.70 59.20 4.50 0.802400 79.60 60.60 57.10 56.50 9.90 3.30 59.70 53.10 60.00 59.30 6.00 1.303000 91.80 72.20 58.20 57.40 11.50 4.30 71.20 64.40 60.60 59.70 7.10 1.80

61800 89.80 59.00 50.30 50.20 11.20 5.80 75.10 52.70 53.40 53.30 7.50 2.802400 111.40 74.90 51.70 51.60 13.90 8.60 94.20 67.80 54.40 54.30 9.40 4.203000 12.00 89.40 53.00 52.80 16.20 11.30 110.40 81.50 55.40 55.20 11.00 5.60

90

42250 84.70 61.30 55.30 54.90 10.60 2.30 60.20 51.80 59.10 58.70 6.00 0.903000 104.60 77.90 56.50 55.90 13.10 3.40 79.30 68.10 59.40 58.80 7.90 1.403750 121.00 92.70 57.60 56.80 15.10 4.40 94.40 82.50 60.00 59.20 9.40 1.90

62250 115.90 75.40 49.60 49.50 14.50 5.80 97.60 67.40 52.80 52.70 9.80 2.903000 144.40 95.90 51.00 50.90 18.10 8.50 122.70 86.70 53.80 53.70 12.30 4.303750 168.90 114.60 52.30 52.10 21.10 11.30 144.20 104.40 54.80 54.60 14.40 5.70

Notes:

• Light shading = GPM is below the minimum (<1.5 fps self-venting velocity) or WPD is above the maximum (>10 ft wg) recommended for most applications.• Dark shading = GPM is below the AHRI limits (1.0 fps tube side velocity).• Some of the volumetric flow rates are less than those required for self-venting.For more information, refer to the BCHD/BCVD coil general data table.• Capacities calculated with 0.00000 tube-side fouling factor.• High-capacity coils applicable where higher water pressure differentials are acceptable and are also recommended for EarthwiseTM applications.• EarthwiseTM is a trademark of Trane to identify equipment designed for applications requiring greater water temperature rises, lower entering water

temperatures (EWT) and lower air supply temperatures (LDB).• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

62 BCX-PRC001E-EN

Page 63: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 15. BCCD chilled water cooling capacities, EAT = 80° F DB/67° F WB and EWT = 40° F

Unit Size

Coil Rows

Air Flow

Water Temperature Rise - °F10° F 12° F

TC SC LDB LWB GPM WPD TC SC LDB LWB GPM WPD

24

4

600 26.90 18.10 52.64 52.18 5.35 3.46 23.45 16.65 54.83 54.34 3.89 1.96

800 33.10 22.76 54.19 53.49 6.58 5.01 29.18 21.15 56.02 55.29 4.84 2.88

1000 38.31 26.93 55.57 54.63 7.62 6.50 33.98 25.17 57.16 56.18 5.63 3.77

6

600 34.65 21.80 47.05 46.97 6.89 7.71 32.35 20.73 48.65 48.57 5.36 4.93

800 43.54 27.77 48.51 48.36 8.66 11.55 40.64 26.46 50.00 49.84 6.74 7.37

1000 51.32 33.22 49.86 49.63 10.21 15.48 47.86 31.69 51.25 51.00 7.94 9.85

36

4

900 40.36 27.14 52.64 52.18 8.03 3.73 35.18 24.97 54.83 54.34 5.83 2.10

1200 49.65 34.14 54.19 53.49 9.88 5.41 43.78 31.72 56.02 55.29 7.26 3.10

1500 57.46 40.39 55.57 54.63 11.43 7.04 50.97 37.76 57.16 56.18 8.45 4.07

6

900 51.98 32.69 47.05 46.97 10.34 8.16 48.53 31.10 48.65 48.57 8.05 5.20

1200 65.31 41.65 48.51 48.36 12.99 12.26 60.95 39.69 50.00 49.84 10.11 7.80

1500 76.99 49.83 49.86 49.63 15.31 16.45 71.79 47.53 51.25 51.00 11.90 10.44

48

4

1200 58.14 38.11 51.19 50.77 11.57 6.17 52.72 35.76 52.97 52.52 8.74 3.74

1600 71.41 47.81 52.89 52.26 14.21 8.90 65.03 45.10 54.43 53.76 10.78 5.43

2000 82.59 56.45 54.40 53.52 16.43 11.54 75.36 53.44 55.76 54.86 12.49 7.05

6

1200 72.06 44.91 46.05 45.98 14.34 12.90 68.30 43.13 47.40 47.32 11.32 8.47

1600 90.68 57.23 47.55 47.42 18.04 19.38 85.79 54.97 48.83 48.69 14.22 12.67

2000 107.18 68.53 48.92 48.70 21.32 26.08 101.09 65.78 50.16 49.94 16.76 16.93

60

4

1500 71.93 47.27 51.41 50.97 14.31 6.72 65.27 44.39 53.15 52.68 10.82 4.07

2000 88.08 59.17 53.16 52.49 17.52 9.65 80.25 55.86 54.66 53.96 13.30 5.87

2500 101.64 69.77 54.68 53.76 20.22 12.47 92.78 66.09 56.02 55.06 15.38 7.61

6

1500 89.44 55.82 46.24 46.17 17.79 14.00 84.75 53.61 47.58 47.50 14.05 9.17

2000 112.28 71.01 47.79 47.65 22.34 20.97 106.17 68.21 49.06 48.91 17.60 13.68

2500 132.47 84.93 49.18 48.95 26.35 28.16 124.86 81.51 50.42 50.18 20.70 18.24

Unit Size

Coil Rows

Air Flow

Water Temperature Rise - °F16°F 20°F

TC SC LDB LWB GPM WPD TC SC LDB LWB GPM WPD

24

4

600 14.93 13.34 59.84 59.29 1.86 0.53 13.08 12.66 60.85 60.30 1.30 0.28

800 19.59 17.44 60.22 59.43 2.44 0.84 14.96 14.54 62.12 61.30 1.49 0.35

1000 24.13 21.39 60.60 59.55 3.00 1.22 16.35 15.85 63.12 62.04 1.63 0.41

6

600 26.40 18.13 52.59 52.50 3.28 2.06 18.44 14.94 57.42 57.31 1.84 0.74

800 33.63 23.44 53.42 53.24 4.18 3.16 24.84 20.02 57.30 57.20 2.48 1.24

1000 39.87 28.31 54.32 54.05 4.96 4.26 30.26 24.50 57.77 57.47 3.01 1.76

BCX-PRC001E-EN 63

Page 64: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

36

4

900 22.40 20.00 59.84 59.29 2.79 0.56 19.63 18.99 60.85 60.30 1.95 0.30

1200 29.39 26.16 60.22 59.43 3.66 0.90 22.43 21.80 62.12 61.30 2.24 0.37

1500 36.20 32.08 60.60 59.55 4.51 1.30 24.53 23.77 63.12 62.04 2.44 0.44

6

900 39.60 27.19 52.59 52.50 4.93 2.17 27.67 22.40 57.42 57.31 2.75 0.77

1200 50.45 35.16 53.42 53.24 6.27 3.32 37.26 30.03 57.30 57.20 3.71 1.29

1500 59.80 42.46 54.32 54.05 7.44 4.49 45.39 36.76 57.77 57.47 4.52 1.84

48

4

1200 38.61 30.02 57.31 56.81 4.80 1.29 27.08 25.69 60.58 60.05 2.70 0.46

1600 49.84 38.99 57.90 57.17 6.20 2.02 30.67 29.85 61.92 61.15 3.06 0.57

2000 59.02 46.95 58.71 57.74 7.34 2.72 38.66 37.62 62.12 61.10 3.85 0.86

6

1200 58.82 38.84 50.63 50.55 7.31 3.89 45.79 33.37 54.77 54.68 4.56 1.69

1600 74.19 49.84 51.74 51.59 9.23 5.85 59.69 43.81 55.16 54.99 5.94 2.68

2000 87.51 59.89 52.84 52.59 10.88 7.83 71.49 53.32 55.81 55.55 7.11 3.68

60

4

1500 48.21 37.46 57.35 56.82 6.00 1.42 33.09 31.80 60.77 60.22 3.30 0.49

2000 61.78 48.44 58.03 57.26 7.68 2.20 37.42 36.39 62.11 61.30 3.73 0.60

2500 72.91 58.22 58.87 57.86 9.07 2.94 47.26 45.96 62.31 61.24 4.70 0.92

6

1500 73.05 48.34 50.77 50.67 9.08 4.21 57.22 41.69 54.78 54.68 5.69 1.84

2000 91.84 61.88 51.93 51.76 11.42 6.31 74.13 54.54 55.26 55.07 7.38 2.90

2500 108.10 74.26 53.05 52.79 13.44 8.41 88.51 66.26 55.96 55.67 8.81 3.96

Notes:

• Light shading = GPM is below the minimum (<1.5 fps self-venting velocity) or WPD is above the maximum (>10 ft wg) recommended for most applications.• Dark shading = GPM is below the AHRI limits (1.0 fps tube side velocity).• Some of the volumetric flow rates are less than those required for self-venting. For more information, refer to the BCCD coil general data table.• Capacities calculated with 0.00000 tube-side fouling factor.• High-capacity coils applicable where higher water pressure differentials are acceptable and are also recommended for EarthwiseTM applications.• EarthwiseTM is a trademark of Trane to identify equipment designed for applications requiring greater water temperature rises, lower entering water

temperatures (EWT) and lower air supply temperatures (LDB).• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

Table 15. BCCD chilled water cooling capacities, EAT = 80° F DB/67° F WB and EWT = 40° F (continued)

64 BCX-PRC001E-EN

Page 65: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 16. BCHD/BCVD chilled water high-capacity cooling capacities, EAT = 80° F DB / 67° F WB and EWT = 45° F

Unit Size

Coil Rows

Air Flow

Water Temperature Rise - °F10° F 12° F

TC SC LDB LWB GPM WPD TC SC LDB LWB GPM WPD

12

4300 9.20 7.30 57.80 57.40 1.80 1.20 7.10 6.60 60.10 59.60 1.20 0.50400 11.60 9.40 58.60 57.90 2.30 1.80 9.20 8.50 60.70 59.90 1.50 0.90500 13.70 11.40 59.40 58.40 2.70 2.50 11.20 10.40 61.10 60.10 1.90 1.20

6300 13.20 9.10 52.60 52.50 2.60 3.10 11.60 8.40 54.60 54.50 1.90 1.80400 16.70 11.70 53.50 53.30 3.30 4.80 14.80 10.90 55.20 55.10 2.50 2.70500 19.80 14.10 54.40 54.10 4.00 6.50 17.70 13.30 56.00 55.70 2.90 3.80

18

4450 15.10 11.50 56.90 56.30 3.00 3.20 12.80 10.50 58.70 58.10 2.10 1.70600 18.60 14.50 58.10 57.20 3.70 4.70 16.00 13.50 59.60 58.70 2.70 2.60750 21.50 17.20 59.20 58.00 4.30 6.10 18.70 16.20 60.50 59.30 3.10 3.40

6450 20.40 13.80 52.10 52.00 4.10 7.50 18.60 13.10 53.70 53.50 3.10 4.50600 25.40 17.60 53.40 53.10 5.10 11.10 23.20 16.70 54.70 54.50 3.90 6.80750 29.70 21.10 54.50 54.10 5.90 14.80 27.20 20.10 55.70 55.40 4.50 9.00

24

4600 20.70 15.60 56.50 56.00 4.10 2.50 17.30 14.20 58.50 58.00 2.90 1.30800 25.70 19.80 57.60 56.80 5.10 3.60 21.90 18.30 59.20 58.50 3.60 1.901000 29.90 23.60 58.60 57.60 6.00 4.70 25.80 22.00 60.00 59.00 4.30 2.60

6600 27.80 18.70 51.70 51.60 5.50 5.80 25.30 17.70 53.30 53.20 4.20 3.50800 34.90 24.00 52.80 52.60 7.00 8.60 31.80 22.70 54.30 54.10 5.30 5.301000 41.10 28.80 53.90 53.60 8.20 11.60 37.50 27.40 55.20 54.90 6.20 7.10

36

4900 36.80 25.70 54.10 53.70 7.30 8.70 33.40 24.30 55.50 55.10 5.60 5.301200 45.10 32.30 55.60 54.90 9.00 12.60 41.20 30.80 56.70 56.10 6.80 7.701500 52.10 38.40 56.80 55.90 10.40 16.40 47.70 36.60 57.90 57.00 7.90 10.00

6900 45.40 29.70 50.10 50.00 9.10 17.90 42.80 28.50 51.20 51.10 7.10 11.601200 57.00 38.00 51.30 51.10 11.40 26.90 53.60 36.50 52.40 52.20 8.90 17.301500 67.40 45.70 52.40 52.10 13.40 36.20 63.10 43.90 53.50 53.20 10.50 23.20

54

41350 48.10 35.70 56.00 55.60 9.60 2.80 42.10 33.40 57.60 57.20 7.00 1.501800 58.90 45.30 57.20 56.60 11.80 4.00 52.30 42.70 58.50 57.90 8.70 2.302250 67.90 53.90 58.30 57.50 13.60 5.10 60.70 51.10 59.40 58.60 10.10 3.00

61350 62.90 42.30 51.60 51.50 12.60 6.20 58.20 40.30 52.90 52.80 9.70 3.801800 78.50 54.10 52.80 52.70 15.70 9.20 72.70 51.60 54.00 53.90 12.10 5.702250 92.10 64.90 53.80 53.70 18.40 12.20 85.10 62.10 55.00 54.80 14.10 7.60

72

41800 67.20 48.80 55.40 55.00 13.40 5.70 60.90 46.30 56.70 56.20 10.10 3.402400 81.50 61.40 56.80 56.20 16.30 8.10 74.20 58.50 57.90 57.30 12.30 4.903000 93.50 72.80 58.00 57.20 18.70 10.40 85.20 69.60 59.00 58.10 14.20 6.20

61800 85.50 57.10 51.20 51.10 17.10 12.30 80.20 54.80 52.40 52.30 13.30 7.802400 106.50 72.80 52.50 52.40 21.30 18.20 99.40 69.80 53.6 53.50 16.50 11.503000 124.70 87.30 53.60 53.40 25.00 24.20 116.20 83.70 54.7 54.50 19.30 15.10

90

42250 87.40 62.40 54.90 54.40 17.50 5.70 79.40 59.20 56.1 55.70 13.20 3.403000 106.50 78.60 56.30 55.60 21.30 8.10 97.20 74.90 57.4 56.70 16.10 4.903750 122.60 93.30 57.40 56.60 24.50 10.50 111.90 89.10 58.5 57.60 18.60 6.30

62250 109.90 72.70 50.70 50.60 22.00 12.10 103.30 69.80 51.9 51.80 17.20 7.703000 137.40 92.90 51.90 51.80 27.50 18.00 128.70 89.10 53.1 52.90 21.40 11.403750 161.60 111.60 53.00 52.80 32.30 24.10 150.90 107.00 54.1 53.90 25.10 15.10

Unit Size

Coil Rows

Air Flow

Water Temperature Rise - °F16°F 20°F

TC SC LDB LWB GPM WPD TC SC LDB LWB GPM WPD

12

4300 6.30 6.20 61.10 60.60 0.80 0.30 5.40 5.40 64.20 61.60 0.50 0.10400 7.10 7.10 63.90 61.60 0.90 0.30 6.20 6.20 66.00 62.40 0.60 0.20500 7.90 7.90 65.70 62.30 1.00 0.40 6.80 6.80 67.70 62.90 0.70 0.20

6300 8.50 7.20 58.20 58.10 1.10 0.60 7.40 6.80 59.40 59.30 0.70 0.30400 10.30 9.20 59.20 59.00 1.30 0.90 8.70 8.60 60.50 60.40 0.90 0.40500 7.90 7.90 65.70 62.30 1.00 0.40 9.80 9.80 62.30 61.00 1.00 0.60

18

4450 8.40 8.20 63.10 61.30 1.10 0.70 7.40 7.40 65.20 62.10 0.70 0.30600 9.70 9.70 65.40 62.10 1.20 1.20 8.40 8.40 67.40 62.80 0.80 0.30750 10.80 10.80 66.90 62.70 1.30 0.70 9.10 9.10 69.00 63.40 0.90 0.40

6450 14.20 11.30 57.20 57.00 1.80 1.70 10.30 9.90 60.10 60.00 1.00 0.60600 18.20 14.80 57.70 57.40 2.30 2.60 12.90 12.80 60.60 60.40 1.30 1.00750 21.70 18.00 58.30 57.90 2.70 3.60 15.90 15.80 60.90 60.50 1.60 1.40

BCX-PRC001E-EN 65

Page 66: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

24

4600 12.00 12.00 61.80 60.90 1.60 0.40 10.40 10.40 64.70 61.70 1.00 0.30800 13.90 13.90 64.30 61.70 1.80 0.50 11.90 11.90 66.50 62.50 1.20 0.301000 16.40 16.40 65.10 62.00 2.10 1.10 13.10 13.10 68.20 63.10 1.30 0.30

6600 19.00 15.10 57.10 57.00 2.40 1.30 14.50 13.50 59.70 59.50 1.40 0.50800 24.80 19.90 57.40 57.20 3.10 2.00 16.60 16.60 61.30 60.70 1.70 0.701000 29.70 24.30 57.90 57.70 3.70 2.80 21.20 21.20 60.80 60.50 2.10 1.10

36

4900 25.50 21.20 58.60 58.10 3.20 1.90 16.10 16.10 63.80 61.60 1.60 0.601200 32.50 27.40 59.30 58.60 4.10 3.00 21.20 21.20 64.00 61.60 2.10 0.901500 38.30 33.00 60.00 59.10 4.80 4.00 26.90 26.90 63.80 61.60 2.70 1.40

6900 36.50 25.90 53.90 53.80 4.50 5.20 28.60 22.80 57.00 56.90 2.90 2.301200 45.90 33.30 54.80 54.60 5.70 7.80 37.10 29.90 57.40 57.20 3.70 3.601500 54.20 40.20 55.70 55.40 6.80 10.50 44.40 36.50 58.00 57.70 4.40 4.90

54

41350 25.53 25.50 62.90 61.20 3.19 0.40 20.70 20.70 66.10 62.40 2.10 0.201800 35.01 35.00 62.40 61.10 4.40 0.70 23.50 23.50 68.20 63.10 2.40 0.202250 49.54 47.60 61.10 60.20 6.20 1.20 25.50 25.50 69.70 63.60 2.55 0.30

61350 46.32 35.50 56.20 56.10 5.80 1.50 36.20 33.70 58.70 58.60 3.60 0.701800 63.10 45.90 55.90 55.80 7.90 2.70 43.50 40.50 59.60 59.50 4.40 0.902250 69.86 56.30 57.30 57.20 8.70 3.20 53.40 50.20 59.80 59.70 5.30 1.30

72

41800 52.63 34.20 58.00 57.50 6.60 0.80 26.60 26.60 66.60 62.60 2.70 0.302400 64.20 50.40 59.20 58.50 8.00 1.50 38.20 38.20 65.60 62.20 3.80 0.603000 73.79 72.70 60.30 59.40 9.20 2.60 43.90 55.10 66.80 63.10 4.40 0.60

61800 67.40 49.60 55.00 54.90 8.40 3.50 54.20 44.70 57.40 57.30 5.40 1.802400 84.13 63.80 55.90 55.80 10.50 5.10 67.60 57.50 58.30 58.20 6.80 2.303000 98.27 76.50 57.00 56.80 12.30 6.80 80.40 69.90 58.90 58.70 8.00 3.20

90

42250 60.23 51.80 59.10 58.70 7.50 1.30 40.30 39.50 63.90 61.40 4.00 1.803000 76.23 67.00 59.80 59.10 9.50 1.90 51.00 51.00 64.60 61.90 5.10 0.603750 89.48 80.70 60.50 59.60 11.20 2.50 63.90 63.90 64.60 61.80 6.40 0.90

62250 87.29 63.20 54.50 54.40 10.90 3.40 68.50 55.80 57.50 57.40 6.90 1.503000 109.30 81.40 55.40 55.30 13.70 5.10 88.20 73.20 57.90 57.80 8.80 2.303750 128.13 97.80 56.50 56.30 16.00 6.80 105.00 89.60 58.30 58.20 10.50 3.20

Notes:

• Light shading = GPM is below the minimum (<1.5 fps self-venting velocity) or WPD is above the maximum (>10 ft wg) recommended for most applications.• Dark shading = GPM is below the AHRI limits (1.0 fps tube side velocity).• Some of the volumetric flow rates are less than those required for self-venting. For more information, refer to the BCCD coil general data table.• Capacities calculated with 0.00000 tube-side fouling factor.• High-capacity coils applicable where higher water pressure differentials are acceptable and are also recommended for EarthwiseTM applications.• EarthwiseTM is a trademark of Trane to identify equipment designed for applications requiring greater water temperature rises, lower entering water

temperatures (EWT) and lower air supply temperatures (LDB).• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

Table 16. BCHD/BCVD chilled water high-capacity cooling capacities, EAT = 80° F DB / 67° F WB and EWT = 45° F

66 BCX-PRC001E-EN

Page 67: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 17. BCCD chilled water cooling capacities, EAT = 80° F DB/67° F WB and EWT = 45° F

Unit Size

Coil Rows

Air Flow

Water Temperature Rise - °F10°F 12°F

TC SC LDB LWB GPM WPD TC SC LDB LWB GPM WPD

24

4

600 20.30 15.38 56.75 56.23 4.04 2.06 16.74 14.01 58.82 58.28 2.78 1.06

800 25.13 19.54 57.84 57.08 5.00 3.02 21.31 18.08 59.49 58.71 3.54 1.62

1000 29.21 23.30 58.86 57.84 5.81 3.94 25.14 21.77 60.25 59.21 4.17 2.17

6

600 27.46 18.57 51.92 51.82 5.47 5.02 24.88 17.49 53.56 53.45 4.13 3.05

800 34.40 23.76 53.05 52.88 6.85 7.48 31.30 22.48 54.50 54.32 5.19 4.57

1000 40.45 28.55 54.10 53.83 8.05 9.97 36.89 27.10 55.42 55.14 6.12 6.11

36

4

900 30.44 23.07 56.75 56.23 6.06 2.22 25.12 21.02 58.82 58.28 4.17 1.13

1200 37.70 29.31 57.84 57.08 7.50 3.25 31.97 27.12 59.49 58.71 5.31 1.74

1500 43.81 34.95 58.86 57.84 8.72 4.26 37.71 32.65 60.25 59.21 6.26 2.34

6

900 41.19 27.86 51.92 51.82 8.20 5.30 37.32 26.24 53.56 53.45 6.19 3.21

1200 51.60 35.65 53.05 52.88 10.27 7.92 46.95 33.73 54.50 54.32 7.79 4.82

1500 60.68 42.82 54.10 53.83 12.08 10.58 55.34 40.65 55.42 55.14 9.18 6.46

48

4

1200 44.91 32.51 55.42 54.94 8.94 3.84 39.23 30.26 57.12 56.63 6.51 2.18

1600 55.24 41.11 56.69 55.99 11.00 5.55 48.88 38.61 58.11 57.38 8.11 3.22

2000 63.94 48.85 57.84 56.89 12.73 7.19 57.00 46.17 59.06 58.08 9.46 4.22

6

1200 57.78 38.39 50.98 50.89 11.50 8.58 53.52 36.57 52.36 52.27 8.88 5.42

1600 72.39 49.07 52.18 52.02 14.41 12.78 67.12 46.85 53.44 53.27 11.14 8.07

2000 85.18 58.91 53.28 53.03 16.96 17.06 78.97 56.34 54.45 54.19 13.10 10.75

60

4

1500 55.58 40.37 55.58 55.08 11.06 4.17 48.66 37.63 57.24 56.72 8.07 2.37

2000 68.15 50.94 56.90 56.15 13.57 6.00 60.39 47.91 58.27 57.50 10.02 3.48

2500 78.71 60.46 58.06 57.06 15.67 7.77 70.26 57.20 59.24 58.22 11.66 4.56

6

1500 71.67 47.74 51.13 51.04 14.27 9.29 66.41 45.48 52.49 52.39 11.02 5.86

2000 89.56 60.91 52.37 52.20 17.83 13.80 83.05 58.18 53.61 53.43 13.78 8.70

2500 105.20 73.05 53.49 53.22 20.94 18.38 97.51 69.88 54.64 54.37 16.18 11.57

Unit Size

Coil Rows

Air Flow

Water Temperature Rise - °F16°F 20°F

TC SC LDB LWB GPM WPD TC SC LDB LWB GPM WPD

24

4

600 11.85 11.54 61.52 60.96 1.47 0.35 10.29 9.99 62.35 61.79 1.03 0.18

800 13.53 13.12 62.68 61.87 1.68 0.44 11.85 11.85 66.59 62.55 1.18 0.23

1000 16.02 15.52 63.23 62.15 2.00 0.58 13.00 13.00 68.22 63.11 1.30 0.27

6

600 18.43 14.93 57.42 57.31 2.29 1.08 14.29 13.39 59.76 59.64 1.42 0.47

800 24.14 19.67 57.70 57.50 3.01 1.73 16.54 16.12 60.87 60.66 1.65 0.60

1000 29.04 24.04 58.19 57.89 3.61 2.40 20.03 19.51 61.81 60.88 2.00 0.84

BCX-PRC001E-EN 67

Page 68: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

36

4

900 17.77 17.30 61.52 60.96 2.21 0.37 15.43 14.98 62.35 61.79 1.54 0.19

1200 20.29 19.68 62.68 61.87 2.53 0.46 17.76 17.76 66.60 62.55 1.77 0.24

1500 24.03 23.27 63.23 62.15 2.99 0.62 19.47 19.47 68.24 63.12 1.94 0.29

6

900 27.65 22.40 57.42 57.31 3.44 1.13 21.43 20.08 59.76 59.64 2.13 0.49

1200 36.21 29.50 57.70 57.50 4.51 1.82 24.81 24.18 60.87 60.66 2.47 0.63

1500 43.56 36.06 58.19 57.89 5.42 2.52 29.55 28.77 61.29 60.98 2.94 0.85

48

4

1200 24.75 24.12 61.21 60.68 3.08 0.58 21.02 20.42 62.20 61.67 2.09 0.29

1600 34.42 33.23 61.16 60.40 4.29 1.03 24.24 23.44 63.29 62.41 2.42 0.37

2000 41.73 40.51 61.62 60.61 5.19 1.45 26.60 26.60 67.95 63.02 2.65 0.44

6

1200 43.03 32.27 55.61 55.51 5.36 2.21 29.12 26.99 59.60 59.49 2.90 0.75

1600 54.97 41.94 56.22 56.04 6.84 3.40 40.46 36.44 59.34 59.16 4.03 1.33

2000 65.30 50.89 56.92 56.64 8.13 4.60 49.94 45.09 59.55 59.26 4.97 1.93

60

4

1500 31.44 31.20 61.13 60.57 3.92 0.65 25.72 24.97 62.35 61.79 2.56 0.31

2000 42.98 41.42 61.21 60.41 5.36 1.13 29.61 29.61 66.59 62.55 2.95 0.39

2500 51.80 50.38 61.72 60.66 6.45 1.58 32.07 32.07 68.38 63.17 3.20 0.46

6

1500 53.56 40.23 55.67 55.56 6.67 2.40 37.08 33.97 59.46 59.34 3.70 0.84

2000 68.14 52.17 56.34 56.14 8.48 3.67 50.58 45.51 59.36 59.15 5.04 1.46

2500 80.76 63.22 57.06 56.77 10.05 4.94 62.10 56.19 59.61 59.30 6.19 2.09

Notes:

• Light shading = GPM is below the minimum (<1.5 fps self-venting velocity) or WPD is above the maximum (>10 ft wg) recommended for most applications.• Dark shading = GPM is below the AHRI limits (1.0 fps tube side velocity).• Some of the volumetric flow rates are less than those required for self-venting. For more information, refer to the BCCD coil general data table.• Capacities calculated with 0.00000 tube-side fouling factor.• High-capacity coils applicable where higher water pressure differentials are acceptable and are also recommended for EarthwiseTM applications.• EarthwiseTM is a trademark of Trane to identify equipment designed for applications requiring greater water temperature rises, lower entering water

temperatures (EWT) and lower air supply temperatures (LDB).• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

Table 17. BCCD chilled water cooling capacities, EAT = 80° F DB/67° F WB and EWT = 45° F (continued)

68 BCX-PRC001E-EN

Page 69: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

R-410A, DX Cooling Capacities

Table 18. BCHD/BCVD R-410A, 3-row DX cooling capacities

Unit Size

Air Flow

Suct. Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

12

300

40 11.80 8.30 49.80 49.00 14.90 9.50 51.20 50.30 18.20 10.60 52.70 51.8045 9.00 7.00 53.70 52.70 12.10 8.30 54.80 53.90 15.40 9.50 56.20 55.3050 6.10 5.90 57.20 56.10 9.00 7.10 58.60 57.60 12.40 8.30 59.90 58.8055 4.70 4.60 60.80 57.90 6.40 6.00 61.60 60.50 9.00 7.10 63.60 62.40

400

40 14.30 10.20 51.60 50.40 17.90 11.70 53.40 52.20 21.80 13.00 55.30 54.1045 10.90 8.80 55.00 53.70 14.60 10.30 56.60 55.30 18.60 11.70 58.40 57.1050 7.60 7.50 58.00 56.70 10.90 8.80 59.90 58.50 14.90 10.30 61.60 60.1055 5.80 5.80 61.80 58.20 7.50 7.50 62.90 61.30 10.90 8.90 64.90 63.30

500

40 16.30 12.00 53.20 51.70 20.40 13.60 55.30 53.70 24.80 15.10 57.50 56.0045 12.50 10.30 56.20 54.60 16.60 12.00 58.10 56.50 21.00 13.60 60.30 58.5050 8.90 8.90 58.90 57.10 12.50 10.40 61.10 59.30 16.90 12.10 63.10 61.2055 6.50 6.50 63.10 58.70 8.80 8.80 64.00 61.60 12.40 10.50 66.00 64.00

18

450

40 16.90 11.90 50.80 49.80 20.90 13.50 52.60 51.50 25.30 15.00 54.60 53.5045 13.10 10.30 54.20 53.00 17.30 12.00 55.80 54.60 21.70 13.60 57.60 56.4050 9.30 8.70 57.30 56.10 13.20 10.30 59.10 57.80 17.70 12.00 60.70 59.4055 6.70 6.70 61.50 58.10 9.20 8.90 62.10 60.80 13.20 10.40 64.00 62.60

600

40 20.00 14.50 52.90 51.40 24.70 16.40 55.10 53.60 29.70 18.10 57.50 56.0045 15.50 12.70 55.80 54.20 20.40 14.60 57.80 56.20 25.60 16.50 60.00 58.3050 11.20 10.90 58.40 56.80 15.60 12.80 60.60 58.90 20.90 14.70 62.70 60.9055 8.30 8.30 62.40 58.50 11.10 11.10 63.20 61.40 15.70 12.90 65.50 63.60

750

40 22.40 16.80 54.50 52.70 27.60 18.90 57.10 55.20 33.50 20.80 59.60 57.6045 17.50 14.80 57.00 55.10 22.90 17.00 59.40 57.40 28.60 19.00 62.00 59.9050 12.90 12.90 59.40 57.30 17.60 15.00 61.90 59.80 23.40 17.10 64.30 62.1055 9.80 9.80 63.20 58.80 12.90 12.80 64.50 61.80 17.60 15.10 66.70 64.40

24

600

40 23.40 16.40 50.00 49.10 29.20 18.70 51.60 50.70 35.30 20.80 53.40 52.5045 18.20 14.10 53.60 52.50 24.10 16.50 55.00 54.00 30.30 18.70 56.60 55.6050 12.80 11.90 56.90 55.90 18.30 14.20 58.50 57.40 24.70 16.50 60.00 58.8055 9.50 9.40 60.70 57.80 12.60 12.10 61.70 60.50 18.40 14.30 63.50 62.20

800

40 28.00 20.10 52.00 50.70 34.70 22.80 54.00 52.70 41.80 25.20 56.30 55.0045 21.80 17.50 55.10 53.70 28.70 20.30 56.90 55.50 36.00 22.90 59.00 57.5050 15.60 15.00 58.00 56.50 21.90 17.60 60.00 58.50 29.40 20.40 61.90 60.3055 11.50 11.50 62.00 58.30 15.50 15.20 62.70 61.10 22.00 17.80 64.90 63.20

1000

40 31.70 23.40 53.70 52.00 39.10 26.30 56.00 54.30 47.50 29.10 58.40 56.7045 24.70 20.50 56.40 54.60 32.40 23.60 58.60 56.80 40.50 26.50 60.90 59.1050 18.00 17.80 58.80 57.00 24.80 20.70 61.20 59.30 33.10 23.70 63.50 61.5055 13.50 13.50 62.80 58.60 17.90 17.90 63.80 61.60 24.90 20.90 66.10 64.00

36

900

40 36.60 25.30 49.30 48.50 45.80 28.90 50.60 49.80 55.80 32.40 52.10 51.3045 28.10 21.60 53.10 52.20 37.50 25.30 54.30 53.40 47.50 28.90 55.70 54.8050 19.50 18.00 56.70 55.70 28.30 21.60 58.10 57.10 38.40 25.40 59.40 58.3055 14.40 14.30 60.40 57.70 19.20 18.30 61.60 60.40 28.30 21.70 63.10 62.00

1200

40 44.30 31.30 51.10 50.00 55.30 35.70 52.90 51.70 67.20 39.80 54.80 53.6045 34.00 26.90 54.60 53.30 45.30 31.40 56.20 54.80 57.20 35.70 57.90 56.6050 24.00 22.80 57.70 56.30 34.20 27.00 59.50 58.10 46.20 31.50 61.20 59.7055 18.00 17.80 61.40 58.10 23.70 23.20 62.50 61.00 34.20 27.20 64.50 62.90

1500

40 50.60 36.60 52.70 51.20 63.10 41.50 54.80 53.20 76.50 46.10 57.00 55.4045 39.00 31.60 55.80 54.20 51.70 36.70 57.70 56.00 65.10 41.60 59.80 58.1050 27.80 27.20 58.50 56.80 39.00 31.80 60.70 58.90 52.50 36.80 62.70 60.9055 20.60 20.60 62.50 58.50 27.60 27.50 63.40 61.40 39.00 32.10 65.60 63.70

BCX-PRC001E-EN 69

Page 70: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

54

1350

40 54.90 38.00 49.30 48.50 68.70 43.40 50.60 49.80 83.70 48.70 52.10 51.3045 42.20 32.40 53.10 52.20 56.30 38.00 54.30 53.40 71.30 43.40 55.70 54.8050 29.20 27.10 56.70 55.70 42.50 32.40 58.10 57.10 57.60 38.00 59.40 58.3055 21.70 21.50 60.40 57.70 28.90 27.40 61.60 60.40 42.50 32.60 63.10 62.00

1800

40 66.40 47.00 51.10 50.00 83.00 53.50 52.90 51.70 100.80 59.70 54.80 53.645 51.10 40.40 54.60 53.30 67.90 47.10 56.20 54.80 85.80 53.50 57.90 56.6050 36.00 34.20 57.70 56.30 51.30 40.50 59.50 58.10 69.30 47.20 61.20 59.7055 26.90 26.70 61.40 58.10 35.60 34.80 62.50 61.00 51.30 40.80 64.50 62.90

2250

40 75.90 54.90 52.70 51.20 94.70 62.20 54.80 53.20 114.70 69.20 57.00 55.4045 58.40 47.40 55.80 54.20 77.50 55.10 57.70 56.00 97.70 62.30 59.80 58.1050 41.70 40.70 58.50 56.80 58.50 47.80 60.70 58.90 78.80 55.30 62.70 60.9055 30.90 30.90 62.50 58.50 41.40 41.30 63.40 61.40 58.40 48.10 65.60 63.70

72

1800

40 72.10 50.10 49.60 48.70 89.60 56.90 51.10 50.30 108.30 63.40 52.90 52.0045 56.30 43.10 53.20 52.20 74.10 50.20 54.60 53.60 93.10 57.00 56.20 55.2050 39.80 36.30 56.60 55.60 56.80 43.20 58.20 57.00 76.10 50.30 59.60 58.5055 28.40 28.40 60.70 57.80 39.40 36.70 61.50 60.30 57.20 43.40 63.10 61.90

2400

40 86.40 61.50 51.60 50.30 107.00 69.50 53.60 52.30 128.80 77.10 55.70 54.5045 67.60 53.40 54.70 53.40 88.60 61.80 56.60 55.10 110.90 69.70 58.60 57.1050 48.40 45.60 57.70 56.30 68.00 53.70 59.70 58.10 90.70 62.00 61.50 60.0055 35.50 35.50 35.50 61.60 48.00 46.30 62.50 60.90 68.20 54.10 64.60 62.90

3000

40 97.90 71.50 53.30 51.70 120.90 80.40 55.60 53.90 143.80 87.00 58.50 56.5045 76.70 62.40 56.00 54.30 100.30 71.90 58.20 56.40 125.10 80.80 60.50 58.7050 55.70 54.00 58.60 56.80 77.10 62.90 60.90 59.00 102.30 72.30 63.10 61.1055 41.70 41.70 41.70 62.40 55.30 55.00 63.40 61.40 77.20 63.50 65.80 63.70

90

2250

40 92.00 63.60 49.20 48.30 114.40 72.30 50.60 49.80 138.40 80.70 52.30 51.5045 71.90 54.60 52.90 51.90 94.70 63.70 54.20 53.20 118.90 72.40 55.70 54.7050 50.70 45.90 56.40 55.40 72.60 54.80 57.80 56.80 97.20 63.90 59.20 58.1055 46.80 44.40 57.10 56.00 68.00 53.00 58.60 57.50 92.60 62.10 59.90 58.80

3000

40 110.80 78.40 51.10 50.00 137.30 88.70 53.00 51.80 165.60 98.50 55.10 53.9045 86.70 67.90 54.40 53.10 113.70 78.70 56.10 54.80 142.40 89.00 58.00 56.7050 61.90 57.80 57.50 56.10 87.30 68.30 59.30 57.90 116.50 79.00 61.10 59.6055 57.50 56.10 58.00 56.60 81.80 66.20 59.90 58.50 110.90 77.00 61.70 60.20

3750

40 126.10 91.30 52.80 51.30 155.80 102.90 55.00 53.40 192.10 115.20 56.90 55.3045 98.70 79.60 55.70 54.00 129.20 91.80 57.70 56.00 161.20 103.30 60.00 58.2050 71.40 68.60 58.30 56.70 99.20 80.20 60.60 58.80 132.00 92.30 62.70 60.8055 53.20 53.20 62.10 58.40 70.80 69.80 63.10 61.20 99.40 80.90 65.50 63.50

Notes: To select the correct distributor size at conditions exactly matching those shown on this table, use the shading legend below:• No shade = 3/16 in. x 0.049 wall distributor tubes• Light shading = 3/16 in. x 0.032 wall distributor tubes.• Dark shading = Distributor load (MBh) per circuit is under the minimum for 3/16 in. x 0.049 distributor or over the maximum for 3/16 in. x 0.032 distributor.

Use only for interpolation• Values shown in this table are based on a liquid condensing temperature of 105°F. Capacities at liquid condensing temperatures between 90°F and 120°F

will generally be within ±5 percent of capacities shown in this table• Distributor selection is based on TC capacities divided by number of circuits. For more information, refer to the BCHD/BCVD - number of circuits per coil

general data table.• To select the correct distributor size at conditions other than exactly shown in this table interpolate to calculate the TC MBh, divide it by the number of

circuits For more information, refer to the BCHD/BCVD - number of circuits per coil general data and plot the result within the Performance Data section on the figure displaying the R-410A Blower coil distributor selection.

• TC and SC values do not include heat generated by the fan and motor.• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

Table 18. BCHD/BCVD R-410A, 3-row DX cooling capacities (continued)

Unit Size

Air Flow

Suct. Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

70 BCX-PRC001E-EN

Page 71: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 19. BCCD R-410A, 3-row DX cooling capacities

UnitSize

Air Flow

Suct. Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

24

600

40.00 20.11 14.42 53.06 51.31 25.84 16.70 54.61 52.86 32.26 19.00 56.13 54.42

45.00 15.63 12.49 56.03 54.14 20.47 14.43 58.10 56.15 26.92 16.79 59.54 57.58

50.00 10.17 10.15 59.60 57.39 15.11 12.34 61.31 59.21 21.10 14.56 62.97 60.80

55.00 7.15 7.15 64.18 59.13 10.14 10.13 64.69 61.88 14.73 12.32 66.41 64.09

800

40.00 24.21 17.71 54.79 52.57 31.01 20.41 56.75 54.48 38.65 23.14 58.67 56.39

45.00 18.00 15.08 57.83 55.44 24.56 17.74 59.82 57.34 32.20 20.53 61.68 59.15

50.00 12.59 12.57 60.71 57.82 18.22 15.29 62.63 60.01 25.23 17.91 64.70 61.96

55.00 9.09 9.09 64.68 59.31 12.62 12.60 65.71 62.24 17.75 15.30 67.68 64.80

1000

40.00 27.57 20.57 56.24 53.59 35.23 23.60 58.50 55.76 43.87 26.68 60.73 57.94

45.00 20.21 17.48 59.08 56.26 27.90 20.61 61.25 58.30 36.50 23.75 63.43 60.38

50.00 14.70 14.68 61.64 58.17 20.76 17.88 63.76 60.66 28.58 20.82 66.12 62.88

55.00 10.75 10.75 65.24 59.52 14.79 14.76 66.61 62.55 20.23 17.94 68.77 65.38

36

900

40.00 30.17 21.63 53.06 51.31 38.77 25.04 54.61 52.86 48.53 28.56 56.07 54.37

45.00 42.70 22.44 52.14 46.42 30.70 21.64 58.10 56.15 40.55 25.25 59.48 57.52

50.00 15.26 15.23 59.60 57.39 22.67 18.51 61.31 59.21 31.83 21.91 62.90 60.74

55.00 10.72 10.72 64.18 59.13 15.22 15.19 64.69 61.88 22.29 18.54 66.34 64.03

1200

40.00 36.31 26.57 54.79 52.57 46.51 30.61 56.75 54.48 58.12 34.77 58.62 56.35

45.00 26.50 22.42 57.98 55.59 36.84 26.60 59.82 57.34 48.48 30.86 61.62 59.10

50.00 18.88 18.85 60.71 57.82 27.33 22.94 62.63 60.01 38.05 26.93 64.64 61.91

55.00 13.63 13.63 64.68 59.31 18.93 18.90 65.71 62.24 26.84 23.03 67.63 64.75

1500

40.00 41.36 30.85 56.24 53.59 52.84 35.40 58.50 55.76 65.97 40.09 60.69 57.90

45.00 30.32 26.22 59.08 56.26 41.85 30.91 61.25 58.30 54.95 35.70 63.38 60.34

50.00 22.06 22.02 61.64 58.17 30.07 26.44 64.00 60.89 43.10 31.31 66.07 62.84

55.00 16.12 16.12 65.24 59.52 22.19 22.15 66.61 62.55 30.57 26.99 68.72 65.33

48

1200

40.00 42.36 29.86 52.27 50.61 53.76 34.37 53.86 52.21 66.67 38.99 55.37 53.76

45.00 31.61 25.19 55.86 54.04 43.24 29.87 57.33 55.46 56.15 34.57 58.78 56.92

50.00 21.93 21.28 58.86 56.93 32.45 25.60 60.60 58.59 44.70 30.13 62.20 60.13

55.00 15.62 15.62 63.17 58.75 21.67 21.63 63.65 61.52 32.07 25.61 65.67 63.44

1600

40.00 50.95 36.66 54.08 51.96 64.52 42.01 56.06 53.90 79.95 47.50 57.96 55.80

45.00 38.15 31.17 57.25 54.95 51.87 36.71 59.12 56.74 67.23 42.29 60.97 58.56

50.00 26.95 26.68 59.83 57.43 39.29 31.79 61.94 59.42 53.45 37.04 63.99 61.37

55.00 19.65 19.65 63.84 59.00 26.69 26.65 64.89 61.96 38.50 31.77 67.02 64.24

2000

40.00 58.03 42.54 55.59 53.04 73.33 48.58 57.87 55.24 90.74 54.77 60.08 57.41

45.00 43.50 36.37 58.43 55.71 58.93 42.63 60.61 57.77 76.26 48.93 62.77 59.85

50.00 31.25 31.19 60.81 57.86 43.25 36.59 63.38 60.38 60.58 43.06 65.47 62.35

55.00 23.14 23.14 64.49 59.24 31.09 31.04 65.92 62.32 43.74 37.18 68.17 64.90

BCX-PRC001E-EN 71

Page 72: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

UnitSize

Air Flow

Suct. Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

60

1500

40.00 52.25 36.93 52.51 50.80 66.28 42.48 54.16 52.44 82.20 48.17 55.72 54.05

45.00 39.01 31.19 56.05 54.16 53.32 36.95 57.56 55.63 69.21 42.74 59.08 57.14

50.00 27.13 26.40 58.99 57.00 40.02 31.70 60.79 58.71 55.09 37.27 62.44 60.30

55.00 19.40 19.40 63.25 58.78 26.81 26.77 63.81 61.57 39.55 31.72 65.84 63.55

2000

40.00 62.67 45.24 54.35 52.16 79.33 51.80 56.38 54.14 98.22 58.54 58.35 56.10

45.00 46.94 38.50 57.46 55.09 63.77 45.29 59.39 56.93 82.63 52.15 61.29 58.79

50.00 33.25 33.02 59.98 57.51 46.71 38.67 62.43 59.82 65.69 45.72 64.26 61.55

55.00 24.32 24.32 63.95 59.04 32.95 32.90 65.08 62.02 47.33 39.25 67.23 64.36

2500

40.00 72.49 52.97 55.67 53.05 91.34 60.39 57.99 55.29 111.32 67.40 60.47 57.70

45.00 54.73 45.41 58.45 55.66 73.62 53.06 60.69 57.78 93.54 60.26 63.10 60.09

50.00 38.49 38.43 61.01 57.93 59.10 59.10 9.06 4.66 74.30 53.07 65.75 62.53

55.00 28.57 28.57 64.62 59.29 38.34 38.27 66.11 62.38 53.67 45.89 68.39 65.02

Notes: To select the correct distributor size at conditions exactly matching those shown on this table, use the shading legend below:• No shade = 3/16 in. x 0.049 wall distributor tubes• Light shading = 3/16 in. x 0.032 wall distributor tubes.• Dark shading = Distributor load (MBh) per circuit is under the minimum for 3/16 in. x 0.049 distributor or over the maximum for 3/16 in. x 0.032 distributor.

Use only for interpolation• Values shown in this table are based on a liquid condensing temperature of 105°F. Capacities at liquid condensing temperatures between 90°F and 120°F

will generally be within ±5 percent of capacities shown in this table• Distributor selection is based on TC capacities divided by number of circuits. For more information, refer to the BCCD - number of circuits per coil general

data table.• To select the correct distributor size at conditions other than exactly shown in this table interpolate to calculate the TC MBh, divide it by the number of

circuits. For more information, refer to the BCCD - number of circuits per coil general data and plot the result within the Performance Data section on the figure displaying the R-410A Blower coil distributor selection.

• TC and SC values do not include heat generated by the fan and motor.• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

Table 19. BCCD R-410A, 3-row DX cooling capacities (continued)

72 BCX-PRC001E-EN

Page 73: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 20. BCHD/BCVD R-410A, 4-row DX cooling capacities

Unit Size

Air Flow

Suct Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

12

300

40 13.40 9.10 47.20 46.80 16.70 10.40 48.20 47.90 20.20 11.70 49.50 49.2045 10.40 7.80 51.30 50.90 13.80 9.20 52.10 51.70 17.40 10.50 53.20 52.8050 7.30 6.50 55.30 54.80 10.50 7.80 56.20 55.80 14.20 9.20 57.20 56.7055 5.30 5.30 59.00 57.20 7.20 6.60 60.10 59.60 10.60 7.90 61.20 60.70

400

40 16.40 11.40 48.90 48.30 20.30 13.00 50.40 49.90 24.50 14.40 52.10 51.6045 12.80 9.90 52.50 51.90 16.80 11.50 53.80 53.20 21.10 13.00 55.40 54.7050 9.10 8.30 56.00 55.40 12.90 9.90 57.50 56.80 17.30 11.50 58.80 58.1055 6.40 6.40 60.40 57.70 9.00 8.40 60.80 60.10 13.00 10.00 62.40 61.60

500

40 18.80 13.40 50.40 49.70 23.30 15.20 52.30 51.50 28.00 16.80 54.40 53.6045 14.70 11.70 53.70 52.90 19.40 13.50 55.30 54.50 24.20 15.30 57.20 56.3050 10.60 10.00 56.80 55.90 14.90 11.80 58.60 57.60 19.90 13.60 60.30 59.3055 7.70 7.70 61.00 57.90 10.50 10.20 61.50 60.60 15.00 11.90 63.50 62.40

18

450

40 18.80 13.10 48.40 48.00 23.10 14.80 50.10 49.60 27.70 16.30 51.90 51.5045 15.00 11.40 51.90 51.40 19.50 13.20 53.30 52.80 24.20 14.90 54.90 54.4050 10.80 9.70 55.40 54.90 15.20 11.50 56.80 56.20 20.10 13.30 58.20 57.6055 7.70 7.70 59.50 57.40 10.70 9.80 60.30 59.60 15.40 11.50 61.70 61.10

600

40 22.40 16.10 50.50 49.80 27.40 18.00 52.60 51.80 32.80 19.80 54.90 54.1045 18.00 14.20 53.50 52.70 23.20 16.30 55.30 54.50 28.70 18.20 57.40 56.6050 13.20 12.20 56.50 55.60 18.30 14.30 58.30 57.40 23.90 16.40 60.20 59.3055 9.60 9.60 60.40 57.70 13.10 12.40 61.20 60.30 18.40 14.50 63.20 62.20

750

40 25.30 18.70 52.20 51.20 30.90 20.80 54.60 53.60 36.70 22.80 57.20 56.2045 20.40 16.60 54.80 53.70 26.10 19.00 57.00 55.90 32.20 21.10 59.40 58.3050 15.20 14.60 57.30 56.20 20.70 16.90 59.60 58.40 26.90 19.20 61.80 60.6055 11.40 11.40 61.20 58.00 15.20 14.90 62.00 60.80 20.90 17.10 64.40 63.10

24

600

40 26.10 17.90 47.60 47.30 32.10 20.30 49.10 48.70 38.60 22.50 50.80 50.4045 20.70 15.50 51.40 50.90 27.00 18.10 52.60 52.10 33.60 20.40 54.00 53.6050 14.90 13.10 55.10 54.60 21.10 15.60 56.30 55.80 27.90 18.20 57.50 57.0055 10.40 10.40 59.30 57.30 14.80 13.30 59.90 59.40 21.40 15.70 61.20 60.70

800

40 31.40 22.20 49.60 49.00 38.50 25.00 51.50 50.90 46.00 27.50 53.70 53.0045 25.10 19.50 52.80 52.20 32.50 22.40 54.50 53.80 40.30 25.20 56.40 55.7050 18.30 16.70 56.00 55.30 25.50 19.60 57.70 56.90 33.50 22.60 59.30 58.6055 13.20 13.20 60.00 57.60 18.20 16.90 60.80 60.00 25.80 19.80 62.60 61.70

1000

40 35.70 25.90 51.30 50.50 43.50 29.00 53.60 52.70 51.90 31.70 56.00 55.1045 28.60 22.90 54.10 53.20 36.90 26.20 56.10 55.20 45.50 29.30 58.30 57.4050 21.20 19.90 56.90 55.90 29.10 23.20 58.90 57.90 38.00 26.50 60.90 59.9055 15.70 15.70 60.80 57.80 21.10 20.30 61.60 60.50 29.40 23.50 63.70 62.60

36

900

40 41.30 27.90 46.60 46.30 51.30 31.90 47.60 47.30 62.10 35.60 48.80 48.5045 32.30 23.90 50.80 50.30 42.60 28.00 51.60 51.20 53.50 31.90 52.70 52.3050 22.80 19.90 54.80 54.40 32.80 24.00 55.80 55.30 43.90 28.00 56.70 56.2055 16.20 16.10 58.60 57.00 22.60 20.10 59.70 59.20 33.20 24.00 60.80 60.20

1200

40 50.60 35.00 48.30 47.80 62.70 39.70 49.80 49.20 75.60 44.20 51.40 50.9045 39.80 30.20 52.10 51.50 52.20 35.10 53.30 52.70 65.30 39.80 54.80 54.2050 28.40 25.50 55.70 55.00 40.30 30.30 57.00 56.30 53.60 35.20 58.30 57.6055 20.10 20.10 59.80 57.50 28.10 25.80 60.50 59.80 40.60 30.50 62.00 61.20

1500

40 58.40 41.20 49.90 49.10 72.20 46.60 51.70 50.90 86.80 51.60 53.60 52.9045 46.00 35.80 53.20 52.40 60.10 41.40 54.80 54.00 75.00 46.80 56.60 55.8050 33.10 30.60 56.50 55.60 46.40 36.00 58.20 57.20 61.70 41.60 59.80 58.9055 24.00 24.00 60.50 57.70 32.80 31.00 61.20 60.30 46.70 36.30 63.10 62.10

BCX-PRC001E-EN 73

Page 74: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

54

1350

40 61.90 41.90 46.60 46.30 77.00 47.80 47.60 47.30 93.10 53.40 48.80 48.5045 48.50 35.90 50.80 50.30 63.90 42.00 51.60 51.20 80.30 47.90 52.70 52.3050 34.30 29.90 54.80 54.40 49.20 36.00 55.80 55.30 65.90 42.10 56.70 56.2055 24.60 24.20 58.60 57.00 33.90 30.20 59.70 59.20 49.80 36.10 60.80 60.20

1800

40 76.00 52.50 48.30 47.80 94.10 59.60 49.80 49.20 113.50 66.20 51.40 50.9045 59.60 45.30 52.10 51.50 78.20 52.70 53.30 52.70 98.00 59.70 54.80 54.2050 42.60 38.20 55.70 55.00 60.40 45.50 57.00 56.30 80.40 52.80 58.30 57.6055 30.10 30.10 59.80 57.50 42.20 38.60 60.50 59.80 60.80 45.70 62.00 61.20

2250

40 87.70 61.90 49.90 49.10 108.30 69.90 51.70 50.90 130.20 77.40 53.60 52.9045 69.00 53.70 53.20 52.40 90.10 62.10 54.80 54.00 112.50 70.10 56.60 55.8050 49.70 45.80 56.50 55.60 69.70 54.00 58.20 57.20 92.50 62.40 59.80 58.9055 36.00 36.00 60.50 57.70 49.20 46.50 61.20 60.30 70.10 54.40 63.10 62.10

72

1800

40 80.40 54.80 47.10 46.80 99.00 62.00 48.50 48.10 118.80 68.80 50.10 49.7045 64.00 47.50 50.90 50.50 83.20 55.10 52.10 51.60 103.50 62.30 53.40 53.0050 46.20 40.00 54.80 54.30 65.10 47.70 55.90 55.40 86.00 55.30 57.00 56.6055 32.00 32.00 58.80 57.10 45.80 40.40 59.60 59.10 66.10 47.90 60.80 60.30

2400

40 97.20 68.00 49.10 48.50 119.20 76.50 50.90 50.30 140.70 83.10 53.30 52.6045 77.70 59.40 52.40 51.70 100.50 68.50 54.00 53.30 124.50 77.00 55.80 55.1050 56.70 50.80 55.70 55.00 78.90 59.90 57.30 56.60 103.70 68.90 58.90 58.1055 40.60 40.60 59.60 57.40 56.40 51.40 60.60 59.80 80.00 60.30 62.20 61.40

3000

40 110.90 79.60 50.80 49.90 135.40 89.00 52.90 52.10 159.60 96.20 55.70 54.6045 88.90 70.10 53.70 52.80 114.50 80.30 55.60 54.70 141.30 89.80 57.80 56.8050 65.70 60.60 56.60 55.70 90.30 70.80 58.50 57.50 118.00 81.00 60.50 59.4055 48.30 48.30 60.40 57.70 65.30 61.60 61.40 60.30 91.20 71.50 63.40 62.30

90

2250

40 102.50 69.50 46.70 46.40 126.20 78.70 48.00 47.70 151.50 87.50 49.50 49.2045 81.50 60.00 50.60 50.20 106.00 69.80 51.70 51.30 132.00 79.00 53.00 52.6050 58.70 50.50 54.60 54.10 82.90 60.30 55.60 55.20 109.60 70.00 56.70 56.2055 54.10 48.60 55.30 54.90 78.00 58.40 56.40 55.90 104.80 68.20 57.40 57.00

3000

40 124.50 86.50 48.60 48.10 152.80 97.40 50.30 49.80 182.70 107.70 52.30 51.7045 99.40 75.40 52.10 51.40 128.70 87.10 53.50 52.90 159.60 98.00 55.20 54.6050 72.40 64.20 55.50 54.80 101.00 75.90 57.00 56.30 132.90 87.60 58.50 57.8055 67.10 62.20 56.10 55.50 95.20 73.70 57.70 57.00 127.10 85.40 59.10 58.40

3750

40 142.50 101.50 50.30 49.50 174.30 113.70 52.30 51.60 216.20 128.20 53.70 53.0045 114.20 89.20 53.30 52.50 147.20 102.40 55.10 54.30 181.90 114.60 57.20 56.3050 84.10 76.80 56.30 55.50 115.90 90.00 58.20 57.30 151.80 103.20 60.00 59.1055 61.30 61.30 60.20 57.60 83.60 78.00 61.10 60.20 117.20 90.80 63.10 62.00

Notes: To select the correct distributor size at conditions exactly matching those shown on this table, use the shading legend below:• No shade = 3/16 in. x 0.049 wall distributor tubes• Light shading = 3/16 in. x 0.032 wall distributor tubes.• Dark shading = Distributor load (MBh) per circuit is under the minimum for 3/16 in. x 0.049 distributor or over the maximum for 3/16 in. x 0.032 distributor.

Use only for interpolation• Values shown in this table are based on a liquid condensing temperature of 105°F. Capacities at liquid condensing temperatures between 90°F and 120°F

will generally be within ±5 percent of capacities shown in this table• Distributor selection is based on TC capacities divided by number of circuits. For more information, refer to the BCHD/BCVD - number of circuits per coil

general data table. • To select the correct distributor size at conditions other than exactly shown in this table interpolate to calculate the TC MBh, divide it by the number of

circuits. For more information, refer to the BCHD/BCVD - number of circuits per coil general data and plot the result within the Performance Data section on the figure displaying the R-410A Blower coil distributor selection.

• TC and SC values do not include heat generated by the fan and motor.• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

Table 20. BCHD/BCVD R-410A, 4-row DX cooling capacities (continued)

Unit Size

Air Flow

Suct Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

74 BCX-PRC001E-EN

Page 75: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 21. BCCD R-410A, 4-row DX cooling capacities

Unit Size

Air Flow

Suct. Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

24

600

40 23.96 16.64 49.65 48.74 30.45 19.21 50.75 49.87 37.86 21.89 51.69 50.87

45 18.47 14.22 53.38 52.36 24.53 16.65 54.71 53.68 31.98 19.37 55.58 54.58

50 12.45 11.76 57.15 56.06 18.54 14.25 58.40 57.26 25.54 16.83 59.50 58.36

55 8.68 8.68 61.86 58.26 12.27 11.93 61.95 60.74 18.41 14.25 63.47 62.21

800

40 29.29 20.72 51.34 50.08 37.12 23.81 52.83 51.59 46.13 27.04 54.17 52.97

45 21.94 17.54 55.01 53.63 29.90 20.74 56.38 54.97 38.91 24.02 57.67 56.27

50 15.51 14.94 58.00 56.54 21.96 17.62 60.00 58.45 31.03 20.98 61.19 59.62

55 11.10 11.10 62.39 58.46 15.33 15.19 62.77 61.16 22.45 17.91 64.72 63.03

1000

40 33.75 24.31 52.80 51.22 42.68 27.82 54.62 53.01 52.37 31.24 56.54 54.93

45 25.34 20.70 56.13 54.40 34.37 24.35 57.83 56.05 44.67 28.10 59.45 57.65

50 18.16 17.83 58.78 56.97 25.31 20.82 61.08 59.16 35.59 24.64 62.63 60.67

55 13.24 13.24 62.98 58.68 17.98 17.95 63.71 61.54 25.81 21.19 65.81 63.71

36

900

40 35.93 24.97 49.65 48.74 45.67 28.82 50.75 49.87 56.79 32.84 51.69 50.87

45 26.84 20.97 53.75 52.73 36.80 24.97 54.71 53.68 47.98 29.06 55.58 54.58

50 18.67 17.65 57.15 56.06 27.81 21.38 58.40 57.26 38.31 25.25 59.50 58.36

55 13.02 13.02 61.86 58.26 18.41 17.90 61.95 60.74 27.62 21.38 63.47 62.21

1200

40 43.94 31.09 51.33 50.08 56.63 36.14 52.51 51.27 69.20 40.57 54.17 52.97

45 32.91 26.30 55.01 53.63 44.85 31.11 56.38 54.97 58.36 36.03 57.67 56.27

50 23.27 22.41 58.00 56.54 32.93 26.43 59.98 58.45 46.55 31.46 61.19 59.62

55 16.66 16.66 62.39 58.46 22.99 22.79 62.77 61.16 33.67 26.87 64.72 63.03

1500

40 50.62 36.46 52.80 51.22 64.02 41.74 54.62 53.01 79.55 47.28 56.28 54.69

45 38.01 31.05 56.13 54.41 51.56 36.52 57.83 56.05 67.01 42.14 59.44 57.65

50 27.23 26.74 58.78 56.97 37.96 31.24 61.08 59.16 53.39 36.96 62.63 60.67

55 19.86 19.86 62.98 58.68 26.98 26.93 63.71 61.54 38.71 31.79 65.81 63.71

48

1200

40 49.74 34.17 48.96 48.11 62.58 39.24 50.13 49.30 77.29 44.53 51.12 50.35

45 37.99 28.94 52.99 52.03 51.08 34.19 54.02 53.05 65.76 39.54 54.97 54.03

50 26.63 24.27 56.59 55.54 38.22 29.00 58.01 56.93 53.11 34.49 58.87 57.78

55 18.54 18.54 60.97 57.92 26.24 24.54 61.44 60.29 39.07 29.35 62.82 61.63

1600

40 60.76 42.52 50.72 49.54 76.24 48.59 52.27 51.10 92.86 54.42 53.98 52.83

45 46.49 36.26 54.33 53.03 62.23 42.58 55.75 54.42 79.18 48.69 57.30 55.96

50 32.14 30.42 57.69 56.29 46.79 36.42 59.30 57.84 64.58 42.99 60.59 59.10

55 23.57 23.57 61.62 58.16 32.55 31.17 62.32 60.78 47.55 36.85 64.12 62.52

2000

40 69.95 49.83 52.24 50.74 87.60 56.75 54.11 52.59 106.25 63.25 56.19 54.65

45 53.58 42.75 55.51 53.87 71.49 49.95 57.25 55.56 90.65 56.84 59.15 57.42

50 37.53 36.26 58.50 56.76 54.92 43.42 60.26 58.44 73.32 50.22 62.20 60.32

55 28.01 28.01 62.28 58.41 37.14 36.90 63.26 61.35 54.61 43.57 65.27 63.26

BCX-PRC001E-EN 75

Page 76: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Unit Size

Air Flow

Suct. Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

60

1500

40 61.48 42.34 49.19 48.30 77.33 48.58 50.41 49.54 94.48 54.66 51.73 50.91

45 46.97 35.90 53.17 52.16 63.11 42.37 54.25 53.23 81.25 48.97 55.25 54.27

50 32.98 30.15 56.70 55.61 47.25 35.97 58.18 57.05 65.61 42.75 59.09 57.96

55 23.05 23.05 61.04 57.95 32.51 30.49 61.55 60.35 48.27 36.41 62.99 61.74

2000

40 74.88 52.56 50.99 49.75 93.93 60.03 52.60 51.36 114.26 67.16 54.38 53.17

45 57.30 44.87 54.54 53.27 76.66 52.64 56.02 54.62 97.48 60.14 57.63 56.23

50 39.70 37.72 57.83 56.38 58.83 45.54 59.29 57.77 79.54 53.17 60.85 59.30

55 29.22 29.22 61.73 58.21 39.22 38.30 62.62 61.02 58.58 45.63 64.33 62.65

2500

40 87.62 62.22 52.27 50.71 109.56 70.81 54.16 52.58 133.09 79.01 56.20 54.62

45 67.41 53.45 55.51 53.80 89.51 62.33 57.29 55.54 113.00 70.76 59.25 57.47

50 47.40 45.35 58.49 56.69 67.52 53.67 60.49 58.59 91.05 62.36 62.35 60.40

55 34.66 34.66 62.41 58.46 46.87 46.08 63.28 61.30 67.13 53.87 65.48 63.40

Notes: To select the correct distributor size at conditions exactly matching those shown on this table, use the shading legend below:• No shade = 3/16 in. x 0.049 wall distributor tubes• Light shading = 3/16 in. x 0.032 wall distributor tubes.• Dark shading = Distributor load (MBh) per circuit is under the minimum for 3/16 in. x 0.049 distributor or over the maximum for 3/16 in. x 0.032 distributor.

Use only for interpolation• Values shown in this table are based on a liquid condensing temperature of 105°F. Capacities at liquid condensing temperatures between 90°F and 120°F

will generally be within ±5 percent of capacities shown in this table• Distributor selection is based on TC capacities divided by number of circuits. For more information, refer to the BCCD - number of circuits per coil general

data table. • To select the correct distributor size at conditions other than exactly shown in this table interpolate to calculate the TC MBh, divide it by the number of

circuits. For more information, refer to the BCCD - number of circuits per coil general data and plot the result within the Performance Data section on the figure displaying the R-410A Blower coil distributor selection.

• TC and SC values do not include heat generated by the fan and motor.• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

Table 21. BCCD R-410A, 4-row DX cooling capacities (continued)

76 BCX-PRC001E-EN

Page 77: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 22. BCHD/BCVD R-410A, 6-row DX cooling capacities

Unit Size

Air Flow

Suct. Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

12

300

40 15.00 10.00 44.50 44.40 18.90 11.60 44.80 44.70 23.10 13.10 45.10 45.0045 11.50 8.40 49.50 49.40 15.50 10.00 49.60 49.50 19.80 11.50 49.80 49.7050 8.50 7.10 53.40 53.30 12.10 8.50 54.00 53.90 16.00 10.00 54.70 54.6055 5.80 5.70 57.50 56.60 8.40 7.10 58.40 58.30 12.20 8.50 59.10 59.00

400

40 19.10 12.90 45.60 45.50 24.00 14.80 46.10 46.00 29.30 16.70 46.80 46.7045 14.60 10.80 50.20 50.10 19.60 12.90 50.70 50.50 25.00 14.80 51.20 51.1050 10.60 9.10 54.10 54.00 14.80 10.90 55.30 55.10 20.20 12.90 55.80 55.6055 7.40 7.40 58.20 56.80 10.50 9.20 59.00 58.80 14.90 10.90 60.30 60.10

500

40 22.70 15.50 46.70 46.50 28.50 17.80 47.50 47.30 34.70 20.00 48.50 48.3045 17.40 13.20 51.00 50.80 23.30 15.50 51.70 51.50 29.60 17.80 52.60 52.3050 12.00 10.90 55.10 54.90 17.60 13.20 56.00 55.80 23.90 15.50 56.80 56.5055 8.90 8.90 58.80 57.10 12.50 11.20 59.60 59.30 17.70 13.20 61.00 60.70

18

450

40 22.20 14.90 44.80 44.70 27.80 17.00 45.40 45.30 33.70 19.10 46.10 46.0045 17.40 12.60 49.40 49.30 23.00 14.90 49.80 49.70 29.00 17.00 50.40 50.3050 12.10 10.40 53.90 53.80 17.60 12.60 54.40 54.30 23.80 14.90 54.90 54.8055 8.60 8.60 57.60 56.60 12.50 10.60 58.50 58.30 17.90 12.70 59.40 59.30

600

40 27.80 18.90 46.20 46.00 34.60 21.50 47.20 47.00 41.90 24.10 48.30 48.2045 21.80 16.20 50.40 50.20 28.70 18.90 51.20 51.00 36.10 21.60 52.20 52.0050 15.40 13.50 54.50 54.30 22.10 16.20 55.40 55.20 29.50 18.90 56.30 56.0055 11.00 11.00 58.30 56.90 15.20 13.60 59.40 59.10 22.30 16.30 60.40 60.20

750

40 32.60 22.50 47.50 47.30 40.50 25.60 48.80 48.60 48.80 28.50 50.30 50.1045 25.60 19.40 51.40 51.10 33.60 22.60 52.50 52.20 42.10 25.70 53.80 53.5050 18.20 16.40 55.10 54.80 25.90 19.50 56.30 56.00 34.50 22.70 57.50 57.2055 12.90 12.90 59.40 57.30 18.00 16.60 59.90 59.60 26.10 19.60 61.30 60.90

24

600

40 30.30 20.10 44.30 44.20 37.80 23.10 44.80 44.70 45.90 26.00 45.40 45.3045 23.60 17.00 49.10 49.00 31.30 20.10 49.40 49.30 39.60 23.10 49.80 49.7050 17.20 14.30 53.20 53.10 24.00 17.10 54.10 54.00 32.40 20.10 54.40 54.3055 11.70 11.60 57.30 56.50 17.10 14.30 58.20 58.10 24.40 17.10 59.10 59.00

800

40 38.20 25.70 45.60 45.40 47.50 29.40 46.40 46.30 57.60 32.90 47.40 47.2045 29.80 21.90 50.00 49.80 39.40 25.80 50.60 50.50 49.60 29.40 51.40 51.3050 20.90 18.20 54.30 54.10 30.30 22.00 55.00 54.80 40.60 25.80 55.70 55.5055 15.00 14.90 58.00 56.80 20.70 18.40 59.10 59.00 30.60 22.00 60.00 59.80

1000

40 45.00 30.80 46.80 46.60 56.00 35.10 47.90 47.70 67.60 39.10 49.20 49.0045 35.30 26.50 50.90 50.60 46.40 30.90 51.80 51.60 58.30 35.20 52.90 52.7050 25.00 22.20 54.80 54.50 35.70 26.50 55.80 55.60 47.80 31.00 56.80 56.6055 18.10 17.90 58.60 57.00 24.70 22.40 59.60 59.30 36.10 26.70 60.80 60.50

36

900

40 45.60 30.20 44.20 44.10 56.00 34.30 45.20 45.10 67.00 38.10 46.30 46.2045 36.70 26.10 48.50 48.40 47.50 30.40 49.20 49.10 58.90 34.50 50.00 49.9050 26.70 21.90 52.90 52.80 37.60 26.20 53.40 53.30 49.40 30.50 54.10 54.0055 18.10 18.00 56.80 56.30 26.60 22.00 57.80 57.70 38.50 26.40 58.40 58.30

1200

40 56.60 38.30 45.80 45.70 69.20 43.10 47.10 47.00 82.60 47.70 48.70 48.6045 45.80 33.40 49.60 49.50 58.90 38.60 50.60 50.50 72.80 43.50 52.00 51.8050 33.70 28.30 53.50 53.40 46.90 33.60 54.50 54.30 61.30 38.80 55.50 55.4055 23.00 23.00 57.60 56.60 33.60 28.50 58.40 58.30 47.90 33.80 59.40 59.20

1500

40 65.90 45.50 47.30 47.10 80.20 51.00 48.90 48.80 95.30 55.90 50.90 50.7045 53.60 40.00 50.70 50.40 68.60 45.90 52.10 51.80 84.30 51.50 53.70 53.5050 39.70 34.20 54.20 54.00 54.80 40.40 55.50 55.30 71.20 46.30 56.90 56.7055 27.90 27.90 58.10 56.80 39.60 34.60 59.00 58.80 55.90 40.70 60.40 60.10

BCX-PRC001E-EN 77

Page 78: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

54

1350

40 68.40 45.30 44.20 44.10 83.90 51.40 45.20 45.10 100.50 57.10 46.30 46.2045 55.10 39.20 48.50 48.40 71.20 45.60 49.20 49.10 88.30 51.70 50.00 49.9050 40.10 32.80 52.90 52.80 56.40 39.40 53.40 53.30 74.10 45.80 54.10 54.0055 27.10 26.90 56.80 56.30 39.90 33.00 57.80 57.70 57.70 39.50 58.40 58.30

1800

40 84.90 57.50 45.80 45.70 103.80 64.70 47.10 47.00 123.90 71.50 48.70 48.6045 68.70 50.10 49.60 49.50 88.40 57.90 50.60 50.50 109.20 65.20 52.00 51.8050 50.50 42.40 53.50 53.40 70.40 50.40 54.50 54.30 91.90 58.20 55.50 55.4055 34.50 34.50 57.60 56.60 50.30 42.70 58.40 58.30 71.90 50.70 59.40 59.20

2250

40 98.80 68.20 47.30 47.10 120.40 76.50 48.90 48.80 142.90 83.90 50.90 50.7045 80.30 60.00 50.70 50.40 102.80 68.90 52.10 51.80 126.50 77.20 53.70 53.5050 59.60 51.40 54.20 54.00 82.30 60.50 55.50 55.30 106.80 69.50 56.90 56.7055 41.80 41.80 58.10 56.80 59.40 51.90 59.00 58.80 83.90 61.00 60.40 60.10

72

1800

40 92.60 61.20 43.90 43.80 115.30 70.10 44.30 44.20 139.70 78.80 44.90 44.8045 72.90 52.00 48.60 48.50 95.90 61.20 48.90 48.80 120.70 70.20 49.40 49.3050 52.30 43.00 53.10 53.00 74.20 52.10 53.60 53.50 99.30 61.30 54.00 53.9055 35.60 35.40 57.00 56.40 52.30 43.20 58.10 57.90 75.40 52.10 58.70 58.60

2400

40 117.00 78.40 45.10 45.00 145.40 89.50 45.90 45.80 175.90 100.30 46.80 46.7045 92.10 66.90 49.50 49.40 120.90 78.40 50.20 50.00 151.80 89.50 51.00 50.8050 65.30 55.70 53.90 53.70 93.50 67.00 54.60 54.40 124.70 78.50 55.20 55.1055 45.50 45.10 57.80 56.70 64.70 56.00 58.80 58.60 94.70 67.20 59.60 59.40

3000

40 138.30 94.00 46.30 46.10 171.60 106.90 47.40 47.20 207.20 119.30 48.60 48.5045 109.00 80.70 50.40 50.20 142.60 94.10 51.40 51.10 178.80 107.10 52.50 52.2050 77.80 67.70 54.40 54.20 110.40 80.90 55.40 55.20 146.90 94.20 56.40 56.1055 54.40 54.00 58.50 57.00 77.00 68.30 59.30 59.00 111.60 81.20 60.40 60.10

90

2250

40 116.90 77.00 43.70 43.60 145.60 88.40 44.00 43.90 176.50 99.40 44.50 44.4045 92.00 65.40 48.40 48.30 121.10 77.10 48.70 48.60 152.40 88.40 49.10 49.0050 67.90 54.90 52.70 52.60 93.70 65.40 53.50 53.40 125.40 77.10 53.80 53.7055 63.00 52.80 53.50 53.40 87.90 63.10 54.40 54.30 119.60 74.80 54.70 54.60

3000

40 148.30 99.00 44.80 44.70 184.30 113.20 45.50 45.40 223.10 126.80 46.30 46.2045 116.70 84.40 49.30 49.20 153.20 99.00 49.90 49.70 192.50 113.20 50.60 50.4050 82.60 70.00 53.70 53.60 118.60 84.50 54.30 54.20 158.30 99.10 54.90 54.8055 76.00 67.30 54.60 54.40 111.30 81.60 55.20 55.10 150.90 96.20 55.80 55.70

3750

40 175.90 119.00 46.00 45.80 218.40 135.60 46.90 46.80 263.80 151.40 48.10 47.9045 138.50 102.00 50.20 50.00 181.50 119.10 51.00 50.80 227.70 135.70 52.00 51.8050 98.70 85.30 54.30 54.00 140.50 102.20 55.20 54.90 187.00 119.30 56.10 55.8055 70.30 69.80 58.00 56.80 97.70 86.00 59.20 58.90 142.00 102.50 60.20 59.90

Notes: To select the correct distributor size at conditions exactly matching those shown on this table, use the shading legend below:• No shade = 3/16 in. x 0.049 wall distributor tubes• Light shading = 3/16 in. x 0.032 wall distributor tubes.• Dark shading = Distributor load (MBh) per circuit is under the minimum for 3/16 in. x 0.049 distributor or over the maximum for 3/16 in. x 0.032 distributor.

Use only for interpolation• Values shown in this table are based on a liquid condensing temperature of 105°F. Capacities at liquid condensing temperatures between 90°F and 120°F

will generally be within ±5 percent of capacities shown in this table• Distributor selection is based on TC capacities divided by number of circuits. For more information, refer to the BCHD/BCVD - number of circuits per coil

general data table.• To select the correct distributor size at conditions other than exactly shown in this table interpolate to calculate the TC MBh, divide it by the number of

circuits. For more information, refer to the BCHD/BCVD - number of circuits per coil general data and plot the result within the Performance Data section on the figure displaying the R-410A Blower coil distributor selection.

• TC and SC values do not include heat generated by the fan and motor.• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

Table 22. BCHD/BCVD R-410A, 6-row DX cooling capacities (continued)

Unit Size

Air Flow

Suct. Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

78 BCX-PRC001E-EN

Page 79: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 23. BCCD R-410A, 6-row DX cooling capacities

Unit Size

Air Flow

Suct. Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

24

600

40 28.61 19.21 45.71 45.46 35.87 22.08 46.33 46.10 44.28 25.15 46.66 46.47

45 22.10 16.24 50.29 49.99 29.54 19.22 50.75 50.46 37.98 22.32 51.05 50.78

50 15.69 13.55 54.43 54.10 22.40 16.27 55.31 54.98 30.98 19.43 55.51 55.19

55 10.53 10.53 59.06 57.18 15.49 13.64 59.35 58.98 23.14 16.49 60.06 59.69

800

40 35.73 24.35 47.16 46.76 44.68 27.86 48.16 47.77 54.11 31.17 49.40 49.05

45 27.66 20.73 51.35 50.89 36.81 24.39 52.19 51.73 46.56 27.90 53.20 52.76

50 19.83 17.48 55.10 54.60 27.98 20.79 56.35 55.83 38.05 24.49 57.15 56.63

55 13.66 13.66 59.49 57.35 19.59 17.63 59.99 59.43 28.48 20.96 61.23 60.65

1000

40 41.86 28.98 48.51 47.94 52.22 33.02 49.83 49.27 62.98 36.75 51.46 50.91

45 33.30 25.17 52.03 51.39 43.05 29.05 53.51 52.86 54.23 33.05 54.89 54.29

50 22.78 20.84 56.03 55.33 32.77 24.92 57.33 56.61 44.34 29.17 58.48 57.75

55 16.51 16.51 60.00 57.55 22.52 21.10 60.85 60.07 33.26 25.14 62.21 61.40

36

900

40 42.91 28.81 45.71 45.46 53.80 33.12 46.33 46.10 66.42 37.72 46.66 46.47

45 33.15 24.36 50.29 49.99 44.31 28.83 50.75 50.46 56.97 33.48 51.05 50.78

50 23.53 20.32 54.43 54.10 33.60 24.40 55.31 54.98 46.47 29.15 55.51 55.19

55 15.80 15.80 59.06 57.18 23.23 20.47 59.35 58.98 34.70 24.73 60.06 59.69

1200

40 53.60 36.53 47.16 46.76 67.02 41.80 48.16 47.77 81.16 46.75 49.40 49.05

45 41.49 31.09 51.35 50.89 55.22 36.58 52.19 51.73 69.84 41.85 53.20 52.76

50 28.81 25.84 55.39 54.88 41.96 31.18 56.35 55.83 57.07 36.73 57.15 56.63

55 20.48 20.48 59.49 57.35 29.38 26.45 59.99 59.43 42.73 31.44 61.23 60.65

1500

40 64.20 44.11 48.11 47.55 80.00 50.29 49.36 48.81 97.06 56.26 50.75 50.23

45 49.95 37.76 52.03 51.39 66.01 44.17 53.14 52.50 83.12 50.31 54.44 53.80

50 35.21 31.67 55.77 55.08 50.44 37.87 57.02 56.30 67.67 44.19 58.21 57.49

55 24.77 24.77 60.00 57.55 34.79 32.02 60.62 59.85 50.60 37.96 62.05 61.25

48

1200

40 58.20 38.90 45.33 45.09 72.36 44.47 46.09 45.88 87.14 49.65 47.17 46.98

45 45.74 33.18 49.75 49.47 60.27 38.99 50.33 50.07 75.60 44.50 51.15 50.90

50 32.13 27.43 54.17 53.86 46.58 33.26 54.75 54.44 62.50 39.11 55.33 55.02

55 21.98 21.98 58.36 56.91 32.61 27.91 58.87 58.52 47.55 33.46 59.68 59.33

1600

40 72.46 49.21 46.86 46.49 89.79 55.97 48.02 47.66 107.48 62.05 49.57 49.23

45 57.08 42.26 50.88 50.45 74.90 49.37 51.84 51.41 93.42 55.97 53.10 52.69

50 40.48 35.33 54.88 54.41 57.94 42.41 55.87 55.38 77.34 49.51 56.85 56.36

55 28.41 28.41 58.87 57.11 40.08 35.65 59.77 59.24 58.97 42.69 60.79 60.24

2000

40 84.60 58.42 48.29 47.75 104.54 66.16 49.78 49.25 129.37 75.06 50.73 50.24

45 68.37 51.18 51.64 51.04 87.34 58.69 53.24 52.63 111.79 67.55 54.22 53.62

50 47.78 42.64 55.58 54.93 69.28 51.37 56.62 55.95 92.02 59.69 57.86 57.18

55 33.69 33.67 59.70 57.43 47.33 43.12 60.43 59.70 69.86 51.55 61.62 60.87

BCX-PRC001E-EN 79

Page 80: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Unit Size

Air Flow

Suct. Temp

Entering Dry Bulb / Wet Bulb (°F)75/63 80/67 85/71

TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB

60

1500

40 72.14 48.31 45.52 45.27 89.65 55.19 46.34 46.11 107.88 61.56 47.48 47.27

45 56.72 41.24 49.89 49.60 74.69 48.42 50.53 50.24 93.61 55.22 51.40 51.13

50 39.89 34.14 54.26 53.93 57.67 41.33 54.90 54.57 77.40 48.57 55.52 55.20

55 27.39 27.39 58.41 56.93 39.47 34.38 59.18 58.81 58.91 41.60 59.82 59.45

2000

40 89.54 60.98 47.11 46.71 110.90 69.30 48.33 47.94 132.60 76.73 49.96 49.59

45 70.56 52.43 51.07 50.61 92.54 61.18 52.09 51.63 115.32 69.29 53.41 52.96

50 50.12 43.90 55.00 54.50 71.60 52.62 56.05 55.53 95.49 61.36 57.09 56.57

55 35.31 35.31 58.96 57.15 49.62 44.31 59.88 59.31 72.83 52.98 60.97 60.39

2500

40 106.80 73.43 48.14 47.58 132.00 83.21 49.59 49.03 159.48 92.76 51.13 50.59

45 84.35 63.40 51.85 51.21 110.14 73.67 53.12 52.48 137.81 83.55 54.55 53.91

50 60.46 53.49 55.51 54.82 85.45 63.66 56.83 56.11 113.45 73.90 58.12 57.39

55 42.55 42.55 59.54 57.37 59.87 54.04 60.37 59.60 86.14 63.90 61.82 61.02

Notes: To select the correct distributor size at conditions exactly matching those shown on this table, use the shading legend below:• No shade = 3/16 in. x 0.049 wall distributor tubes• Light shading = 3/16 in. x 0.032 wall distributor tubes.• Dark shading = Distributor load (MBh) per circuit is under the minimum for 3/16 in. x 0.049 distributor or over the maximum for 3/16 in. x 0.032 distributor.

Use only for interpolation• Values shown in this table are based on a liquid condensing temperature of 105°F. Capacities at liquid condensing temperatures between 90°F and 120°F

will generally be within ±5 percent of capacities shown in this table• Distributor selection is based on TC capacities divided by number of circuits. For more information, refer to the BCCD - number of circuits per coil general

data table.• To select the correct distributor size at conditions other than exactly shown in this table interpolate to calculate the TC MBh, divide it by the number of

circuits. For more information, refer to the BCCD - number of circuits per coil general data and plot the result within the Performance Data section on the figure displaying the R-410A Blower coil distributor selection.

• TC and SC values do not include heat generated by the fan and motor.• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB =

leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

Table 23. BCCD R-410A, 6-row DX cooling capacities (continued)

80 BCX-PRC001E-EN

Page 81: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Hot Water Heating Capacities

Table 24. BCHD/BCVD one-row hot water heating capacities, EAT = 60° F and EWT = 180° F

Unit Size

Air Flow

Water Temperature Drop - °F10°F 15°F 20°F

TC LAT GPM WPD TC LAT GPM WPD TC LAT GPM WPD

12300 16.30 110.20 3.30 6.00 15.50 107.60 2.10 2.50 14.60 105.00 1.50 1.30400 18.80 103.40 3.80 7.90 17.80 101.10 2.40 3.30 16.80 98.80 1.70 1.70500 20.90 98.50 4.20 9.60 19.80 96.40 2.60 4.00 18.70 94.40 1.90 2.10

18450 22.60 106.40 4.50 11.90 21.60 104.20 2.90 5.00 20.50 102.00 2.00 2.70600 25.90 99.90 5.20 15.40 24.70 98.00 3.30 6.50 23.50 96.10 2.30 3.40750 28.70 95.20 5.70 18.60 27.30 93.50 3.60 7.80 25.90 91.80 2.60 4.10

24600 32.50 110.00 6.50 29.30 31.30 108.00 4.20 12.70 30.00 106.10 3.00 6.90800 37.50 103.20 7.50 38.20 36.00 101.40 4.80 16.50 34.50 99.70 3.40 8.901000 41.50 98.30 8.30 46.40 39.80 96.70 5.30 20.00 38.20 95.20 3.80 10.80

36900 51.00 112.30 10.20 82.10 49.30 110.50 6.60 36.10 47.60 108.70 4.80 19.801200 58.90 105.30 11.80 107.50 56.90 103.70 7.60 47.20 54.90 102.20 5.50 25.901500 65.40 100.20 13.10 131.00 63.10 98.80 8.40 57.40 60.90 97.40 6.10 31.40

541350 75.50 111.50 15.10 3.30 70.70 108.30 9.40 1.30 66.00 105.10 6.60 0.701800 87.10 104.60 17.40 4.40 81.50 101.70 10.90 1.70 76.00 98.90 7.60 0.902250 96.80 99.70 19.30 5.40 90.50 97.10 12.00 2.10 84.20 94.50 8.40 1.10

721800 99.00 110.70 19.80 5.90 93.50 107.90 12.50 2.40 88.10 105.10 8.80 1.202400 114.20 103.90 22.80 7.70 107.70 101.40 14.30 3.20 101.30 98.90 10.10 1.603000 126.80 99.00 25.30 9.50 119.40 96.70 15.90 3.90 112.20 94.50 11.20 2.00

902250 125.50 111.40 25.10 7.10 118.50 108.60 15.80 2.90 111.60 105.70 11.20 1.503000 144.80 104.50 28.90 9.40 136.60 102.00 18.20 3.80 128.50 99.50 12.80 1.903750 160.90 99.60 32.10 11.60 151.60 97.30 20.20 4.70 142.50 95.00 14.20 2.40

Unit Size

Air Flow

25°F 30°F 40°FTC LAT GPM WPD TC LAT GPM WPD TC LAT GPM WPD

12300 13.80 102.40 1.10 0.80 12.90 99.80 0.90 0.50 11.20 94.30 0.60 0.20400 15.90 96.50 1.30 1.00 14.90 94.30 1.00 0.60 12.90 89.70 0.60 0.30500 17.50 92.40 1.40 1.20 16.40 90.30 1.10 0.80 14.30 86.40 0.70 0.40

18450 19.40 99.80 1.60 1.60 18.40 97.70 1.20 1.00 16.30 93.40 0.80 0.50600 22.20 94.20 1.80 2.00 21.00 92.30 1.40 1.30 18.70 88.70 0.90 0.60750 24.50 90.10 2.00 2.50 23.20 88.50 1.50 1.60 20.60 85.30 1.00 0.70

24600 28.70 104.10 2.30 4.20 27.40 102.10 1.80 2.80 24.80 98.20 1.20 1.40800 33.00 98.00 2.60 5.40 31.50 96.30 2.10 3.60 28.60 93.00 1.40 1.801000 36.50 93.60 2.90 6.60 34.80 92.10 2.30 4.30 31.70 89.20 1.60 2.10

36900 45.80 107.00 3.70 12.30 44.10 105.20 2.90 8.20 40.50 101.50 2.00 4.101200 52.80 100.60 4.20 16.00 50.80 99.00 3.40 10.60 46.90 96.00 2.30 5.401500 58.60 96.00 4.70 19.40 56.30 94.60 3.80 12.90 52.10 92.00 2.60 6.60

541350 61.30 101.90 4.90 0.40 56.60 98.70 3.80 0.20 45.50 91.10 2.30 0.101800 70.50 96.10 5.60 0.50 65.00 93.30 4.30 0.30 53.10 87.20 2.70 0.102250 78.10 92.00 6.20 0.60 71.90 89.50 4.80 0.40 59.30 84.30 3.00 0.10

721800 82.60 102.30 6.60 0.70 77.20 99.50 5.10 0.40 66.20 93.90 3.30 0.202400 94.90 96.50 7.60 0.90 88.50 94.00 5.90 0.60 76.30 89.30 3.80 0.203000 105.10 92.30 8.40 1.10 97.90 90.10 6.50 0.70 84.50 86.00 4.20 0.30

902250 104.80 102.90 8.40 0.80 97.90 100.10 6.50 0.50 83.90 94.40 4.20 0.203000 120.40 97.00 9.60 1.10 112.30 94.50 7.50 0.70 96.80 89.80 4.80 0.303750 133.40 92.80 10.70 1.40 124.30 90.60 8.30 0.80 107.20 86.40 5.40 0.40

Light shading = GPM is below the minimum (<1.5 fps self-venting velocity) or WPD is above the maximum (>10 ft wg) recommended for most applications.Dark shading = LAT must be less than 104°F to avoid overheating the motor on single phase.Notes:

• Capacities calculated with 0.00025 fouling factor.• Fluid flow in GPM; fluid PD in feet of water• Useful formulas:

LAT = EAT + (TC x 922.1)/CFMLWT = EWT - (TC x 2.0)/GPM

• High-capacity coils applicable where higher water pressure differentials are acceptable and are also recommended for EarthwiseTM applications (see Performance data correction factors).

• EarthwiseTM is a trademark of Trane to identify equipment designed for applications requiring greater water temperature rises, lower entering water temperatures (EWT) and lower air supply temperatures (LDB).

• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB = leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

BCX-PRC001E-EN 81

Page 82: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 25. BCCD one-row hot water heating capacities, EAT = 60° F and EWT = 180° F

Unit Size

Air Flow

Water Temperature Drop - °F10°F 15°F 20°F

TC LAT GPM WPD TC LAT GPM WPD TC LAT GPM WPD

24

600 34.13 112.45 6.82 8.36 32.52 109.97 4.33 3.60 30.92 107.52 3.09 1.93

800 39.71 105.77 7.94 11.10 36.67 102.27 4.88 4.62 34.84 100.16 3.48 2.47

1000 44.40 100.94 8.87 13.68 40.80 97.63 5.43 5.64 38.75 95.73 3.87 3.01

36

900 52.03 113.31 10.40 25.04 49.95 111.18 6.66 10.98 47.90 109.07 4.79 6.00

1200 60.57 106.55 12.11 33.25 56.39 103.33 7.51 14.09 54.03 101.52 5.40 7.68

1500 67.76 101.65 13.54 41.00 64.98 99.94 8.66 17.89 62.23 98.25 6.22 9.73

48

1200 70.21 113.95 14.03 17.69 67.21 111.64 8.96 7.59 62.65 108.14 6.26 3.98

1600 81.82 107.15 16.35 23.67 78.26 105.10 10.43 10.12 72.57 101.82 7.25 5.25

2000 91.59 102.23 18.31 29.34 87.55 100.37 11.67 12.51 80.83 97.26 8.07 6.43

60

1500 86.15 112.96 17.22 20.85 82.46 110.69 10.99 8.89 78.80 108.44 7.88 4.74

2000 100.27 106.23 20.04 27.88 95.90 104.21 12.78 11.84 88.85 100.96 8.87 6.10

2500 112.13 101.36 22.41 34.54 107.18 99.53 14.29 14.64 102.30 97.73 10.23 7.77

Unit Size

Air Flow

25 °F 30 °F 40 °F

TC LAT GPM WPD TC LAT GPM WPD TC LAT GPM WPD

24

600 28.58 103.92 2.28 1.14 27.02 101.53 1.80 0.74 23.93 96.77 1.20 0.35

800 33.01 98.05 2.64 1.49 31.18 95.94 2.08 0.96 27.70 91.92 1.38 0.46

1000 36.70 93.84 2.93 1.81 34.64 91.94 2.31 1.17 30.77 88.37 1.54 0.56

36

900 45.84 106.97 3.67 3.68 42.66 103.71 2.84 2.38 38.60 99.55 1.93 1.18

1200 51.68 99.71 4.13 4.71 49.31 97.89 3.28 3.10 44.76 94.40 2.24 1.55

1500 57.49 95.34 4.59 5.73 54.83 93.71 3.65 3.77 49.84 90.64 2.49 1.88

48

1200 59.75 105.91 4.77 2.40 56.83 103.67 3.79 1.56 50.99 99.18 2.55 0.75

1600 69.16 99.85 5.53 3.16 65.73 97.88 4.38 2.05 59.15 94.09 2.96 0.99

2000 76.98 95.49 6.15 3.86 73.13 93.72 4.87 2.50 65.87 90.37 3.29 1.21

60

1500 75.16 106.20 6.01 2.85 69.66 102.82 4.64 1.80 62.53 98.44 3.13 0.86

2000 84.66 99.03 6.77 3.66 80.46 97.10 5.36 2.36 72.43 93.39 3.62 1.14

2500 97.43 95.94 7.80 4.66 92.56 94.14 6.17 3.00 83.40 90.76 4.17 1.44

Light shading = GPM is below the minimum (<1.5 fps self-venting velocity) or WPD is above the maximum (>10 ft wg) recommended for most applications.Dark shading = LAT must be less than 130°F to avoid overheating the motor on three-phase. LAT on single phase motors must be less than 104° F.Notes:

• Capacities calculated with 0.00025 fouling factor. • Fluid flow in GPM; fluid PD in feet of water• Useful formulas:

LAT = EAT + (TC x 922.1)/CFMLWT = EWT - (TC x 2.0)/GPM

• High-capacity coils applicable where higher water pressure differentials are acceptable and are also recommended for EarthwiseTM applications (see Performance data correction factors).

• EarthwiseTM is a trademark of Trane to identify equipment designed for applications requiring greater water temperature rises, lower entering water temperatures (EWT) and lower air supply temperatures (LDB).

• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB = leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

82 BCX-PRC001E-EN

Page 83: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 26. BCHD/BCVD two-row high-capacity hot water heating capacities, EAT = 60° F and EWT = 180° F

Unit Size

Air Flow

Water Temperature Drop - °F15°F 20°F 25°F

TC LAT GPM WPD TC LAT GPM WPD TC LAT GPM WPD

12300 25.30 137.80 3.40 9.50 24.60 135.50 2.50 5.30 23.80 133.10 1.90 3.30400 30.70 130.70 4.10 13.60 29.70 128.40 3.00 7.50 28.70 126.10 2.30 4.70500 35.20 124.90 4.70 17.50 34.00 122.70 3.40 9.60 32.80 120.50 2.60 6.00

18450 36.10 134.10 4.80 20.00 35.10 131.90 3.50 11.10 34.00 129.80 2.70 7.00600 43.30 126.50 5.80 28.00 42.00 124.50 4.20 15.50 40.60 122.40 3.20 9.70750 49.40 120.70 6.60 35.80 47.80 118.80 4.80 19.80 46.20 116.80 3.70 12.30

24600 49.50 136.10 6.60 9.50 48.00 133.70 4.80 5.20 46.40 131.20 3.70 3.20800 59.70 128.80 8.00 13.50 57.70 126.50 5.80 7.40 55.70 124.20 4.40 4.501000 68.30 123.00 9.10 17.40 65.90 120.80 6.60 9.50 63.50 118.50 5.10 5.80

36900 77.00 138.90 10.30 25.80 75.10 136.90 7.50 14.40 73.00 134.80 5.80 9.001200 93.40 131.80 12.40 37.10 90.80 129.80 9.10 20.60 88.20 127.80 7.10 12.901500 107.20 125.90 14.30 48.10 104.10 124.00 10.40 26.50 100.90 122.10 8.10 16.50

541350 112.10 136.50 14.90 3.40 108.00 133.80 10.80 1.80 103.90 131.00 8.30 1.101800 136.40 129.90 18.20 4.90 131.30 127.20 13.10 2.70 126.00 124.50 10.10 1.602250 156.90 124.30 20.90 6.40 150.70 121.70 15.10 3.40 144.40 119.20 11.50 2.10

721800 148.30 136.00 19.70 6.30 143.50 133.50 14.30 3.40 138.60 131.00 11.10 2.102400 179.90 129.10 24.00 9.00 173.70 126.80 17.40 4.90 167.40 124.30 13.40 3.003000 206.20 123.40 27.50 11.70 198.90 121.10 19.90 6.40 191.40 118.80 15.30 3.90

902250 186.90 136.60 24.90 7.60 180.90 134.10 18.10 4.10 174.70 131.60 14.00 2.503000 227.20 129.80 30.30 11.00 219.40 127.40 21.90 6.00 211.50 125.00 16.90 3.603750 260.80 124.10 34.70 14.30 251.50 121.80 25.10 7.70 242.10 119.50 19.40 4.70

Unit Size

Air Flow

30°F 40°FTC LAT GPM WPD TC LAT GPM WPD

12300 23.00 130.60 1.50 2.20 21.30 125.30 1.10 1.10400 27.60 123.70 1.80 3.10 25.50 118.80 1.30 1.60500 31.60 118.20 2.10 4.00 29.00 113.50 1.50 2.00

18450 33.00 127.50 2.20 4.70 30.70 122.80 1.50 2.50600 39.30 120.30 2.60 6.50 36.40 116.00 1.80 3.40750 44.60 114.80 3.00 8.20 41.20 110.70 2.10 4.20

24600 44.70 128.70 3.00 2.10 41.20 123.40 2.10 1.10800 53.60 121.70 3.60 3.00 49.20 116.70 2.50 1.501000 61.00 116.20 4.10 3.80 55.90 111.50 2.80 1.90

36900 70.90 132.70 4.70 6.10 66.50 128.20 3.30 3.201200 85.50 125.70 5.70 8.70 79.90 121.40 4.00 4.501500 97.70 120.10 6.50 11.10 91.10 116.00 4.60 5.70

541350 99.70 128.10 6.60 0.70 90.90 122.10 4.50 0.401800 120.60 121.80 8.00 1.10 109.40 116.00 5.50 0.502250 138.00 116.50 9.20 1.40 124.70 111.10 6.20 0.70

721800 133.50 128.40 8.90 1.40 122.90 123.00 6.10 0.702400 161.00 121.90 10.70 2.00 147.60 116.70 7.40 1.003000 183.70 116.50 12.20 2.60 168.00 111.60 8.40 1.30

902250 168.40 129.00 11.20 1.70 155.10 123.60 7.80 0.803000 203.40 122.50 13.60 2.40 186.60 117.40 9.30 1.203750 232.50 117.20 15.50 3.10 212.60 112.30 10.60 1.50

Light shading = GPM is below the minimum (<1.5 fps self-venting velocity) or WPD is above the maximum (>10 ft wg) recommended for most applications.Dark shading = LAT must be less than 130°F to avoid overheating the motor on three-phase. LAT on single phase motors must be less than 104° F.Notes:

• Capacities calculated with 0.00025 fouling factor. • Fluid flow in GPM; fluid PD in feet of water• Useful formulas:

LAT = EAT + (TC x 922.1)/CFMLWT = EWT - (TC x 2.0)/GPM

• High-capacity coils applicable where higher water pressure differentials are acceptable and are also recommended for EarthwiseTM applications (see Performance data correction factors).

• EarthwiseTM is a trademark of Trane to identify equipment designed for applications requiring greater water temperature rises, lower entering water temperatures (EWT) and lower air supply temperatures (LDB).

• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB = leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

BCX-PRC001E-EN 83

Page 84: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Table 27. BCCD two-row hot water heating capacities, EAT = 60° F and EWT = 180° F

Unit Size

Air Flow

Water Temperature Drop - °F

15 °F 20 °F 25 °F

TC LAT GPM WPD TC LAT GPM WPD TC LAT GPM WPD

24

600 50.76 138.02 6.77 3.31 48.81 135.02 4.88 1.78 46.82 131.95 3.75 1.09

800 61.87 131.32 8.25 4.82 59.35 128.41 5.93 2.58 56.79 125.45 4.54 1.56

1000 71.42 125.85 9.52 6.33 68.38 123.05 6.84 3.38 65.31 120.22 5.23 2.03

36

900 76.15 138.02 10.15 4.12 73.22 135.02 7.32 2.21 70.23 131.95 5.62 1.34

1200 92.81 131.32 12.37 6.03 89.03 128.41 8.90 3.21 85.18 125.45 6.82 1.93

1500 107.12 125.85 14.28 7.94 102.57 123.05 10.26 4.21 97.96 120.22 7.84 2.52

48

1200 103.98 139.90 13.86 6.76 100.48 137.21 10.05 3.66 96.89 134.45 7.75 2.23

1600 127.16 133.28 16.95 9.95 119.81 129.05 11.97 5.26 115.21 126.40 9.21 3.19

2000 147.04 127.79 19.60 13.15 137.73 123.50 13.75 6.86 132.23 120.96 10.57 4.15

60

1500 128.54 139.02 17.13 7.69 124.17 136.33 12.42 4.15 119.70 133.58 9.58 2.53

2000 156.79 132.29 20.90 11.28 147.57 128.04 14.74 5.93 141.87 125.41 11.34 3.59

2500 181.07 126.79 24.14 14.89 174.24 124.26 17.42 7.95 167.30 121.71 13.39 4.80

Unit Size

Air Flow

30 °F 40 °F

TC LAT GPM WPD TC LAT GPM WPD

24

600 44.77 128.80 2.99 0.71 40.28 121.90 2.02 0.34

800 54.17 122.43 3.61 1.02 48.68 116.11 2.44 0.49

1000 62.18 117.34 4.15 1.32 55.73 111.39 2.79 0.63

36

900 67.15 128.80 4.48 0.87 60.41 121.90 3.02 0.41

1200 81.25 122.43 5.42 1.25 73.02 116.11 3.65 0.59

1500 93.27 117.34 6.22 1.62 83.60 111.39 4.18 0.77

48

1200 93.19 131.61 6.22 1.47 83.62 124.25 4.18 0.72

1600 110.50 123.68 7.36 2.08 100.67 118.02 5.03 1.02

2000 126.62 118.38 8.43 2.70 114.97 113.01 5.75 1.31

60

1500 112.83 129.36 7.52 1.64 103.16 123.41 5.16 0.80

2000 136.02 122.71 9.06 2.34 123.85 117.10 6.19 1.14

2500 160.24 119.10 10.69 3.12 145.64 113.72 7.29 1.51

Light shading = GPM is below the minimum (<1.5 fps self-venting velocity) or WPD is above the maximum (>10 ft wg) recommended for most applications.Dark shading = LAT must be less than 130°F to avoid overheating the motor on three-phase. LAT on single phase motors must be less than 104° F.Notes:

• Capacities calculated with 0.00025 fouling factor. • Fluid flow in GPM; fluid PD in feet of water• Useful formulas:

LAT = EAT + (TC x 922.1)/CFMLWT = EWT - (TC x 2.0)/GPM

• High-capacity coils applicable where higher water pressure differentials are acceptable and are also recommended for EarthwiseTM applications (see Performance data correction factors).

• EarthwiseTM is a trademark of Trane to identify equipment designed for applications requiring greater water temperature rises, lower entering water temperatures (EWT) and lower air supply temperatures (LDB).

• TC = total capacity (MBh); SC = sensible capacity (MBh); GPM = water flow rate-gallons per minute; LDB = leaving dry-bulb temperature (°F); LWB = leaving wet-bulb temperature (°F); WPD = water pressure drop at average water density (ft H20).

84 BCX-PRC001E-EN

Page 85: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Performance Data

Distributor Selection

Select distributor size using MBh/Cir based on system analysis with matching condensing unit operating.

Table 28. Performance data correction factors

Capacity correction factors: use the correction factors listed below for different entering air conditions.EAT - EWT (°F) = 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20Correction factor = 1.50 1.42 1.33 1.25 1.167 1.08 1.00 0.92 0.83 0.75 0.67 0.58 0.50 0.42 0.33 0.25 0.17Water pressure drop (WPD) correction factors: use the correction factors listed below for entering water temperatures different than 180°F.Average water temp. °F = 190 180 170 160 150 140 130 120 110 100 90 80Correction factor = 1.00 1.00 1.01 1.01 1.02 1.03 1.04 1.06 1.07 1.09 1.11 1.14

Figure 69. R-410A Blower coil distributor selection

Hea

t lo

ad (

MBh/

Cir)

Saturated suction temperature (°F)

Max. MBh/Cir3/16 in. x 0.032 wall

Max. MBh/Cir3/16 in. x 0.032 wall

Max. MBh/Cir3/16 in. x 0.049 wall

Max. MBh/Cir3/16 in. x 0.049 wall

20

15

10

5

035 40 45 50 55 60

BCX-PRC001E-EN 85

Page 86: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

Why Trane Controls?

Trane offers a broad range of control packages from a field convertible end-device package, to a complete building automation system solution with BACnet® or LonTalk® controls.

The good news is Trane controls are factory-mounted, wired, tested and configured or programmed with Trane application expertise to provide comfort, efficiency, and reliability, as well as single-source warranty and service.WithTrane integrated controls, the installed costs are lower because the equipment has turn-key factory controls and every component of the system is optimized to fit with the controller.Trane installs not only the controller, but also the hardware that works intimately with the controller to allow the system to function properly (i.e., piping package, valves, dampers, actuators, etc.). When a product with Trane controls arrives on the jobsite, it is completely ready for quick installation.

Table 29. Tracer® controller input/output summary

Binary outputs ZN010 ZN510 ZN520 UC400-BSingle zone VAV •3-speed fan • • •2-position hydronic valve • • • •2-position mixing box damper • • •1-stage electric heat • • • •Modulating mixed air damper • •Modulating hydronic valve • •2-stage electric heat • •Reheat (hydronic) • •Generic • • • •Binary inputsCondensate overflow detection • • • •Low temperature detection • • • •Occupancy • • • •Generic input • • • •Analog inputsZone temperature • • • •Setpoint • • • •Fan mode: auto, high, medium, low • • • •Entering water • • • •Discharge air • • • •Outside air • •Generic •Note: The generic input and output are for use with a Tracer® Summit systems only.

Table 30. Tracer® controller function summary

Control functions ZN010 ZN510 ZN520 UC400-BEntering water temp. sampling (purge) • • • •Timed override • • • •Auto changeover • • • •Fan cycling • • •Continuous fan • •Warm-up • • • •Pre-cool • • • •Data sharing (master/slave) • •Random start • • • •Dehumidification • •Staged capacity (2-stage electric supplementary) • •DX cooling • •Two-stage DX cooling •Other FunctionsManual test • • • •Filter maintenance timer • • • •Setpoint limits • • • •

86 BCX-PRC001E-EN

Page 87: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

VelociTach™ Motor Control Board

The VelociTach motor control board controls and reports the performance of up to two Trane brushless DC (BLDC) motors.

Status Display

Figure 70. VelociTach motor control board

The motor control board also:

• Coordinates the operation of the fan in response to electric heat behavior and electric behavior in response to hydronic heat behavior.

• Incorporates a user interface that allows adjustment of certain unit parameters and provides constant feedback on motor operation.

• Integrates service and troubleshooting tools.

• Integrates a versatile configurable auxiliary temperature sensor.

• Incorporates various safety and lockout features, such as maintaining proper fan speeds if electric heat is called for.

Figure 71. Status display

The motor control board contains a four-digit, seven-segment display that is used to present information in a format close to real-world language, while having a small-form factor. Most characters are immediately recognizable; however, refer the screen representation of alphabetical characters and numeric characters shown in the following tables.

Table 31. Screen representation of alphabetical characters

A B C D E F G H I J K L M N O P Q R S T U V W X Y ZA B C D E F G H I J K L M N O P Q R S T U V W X Y Z

Table 32. Screen representation of numeric characters

1 2 3 4 5 6 7 8 9 01 2 3 4 5 6 7 8 9 0

BCX-PRC001E-EN 87

Page 88: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

Control Options

Available control options are:

• Manual fan speed switch (FSS)

• Customer-supplied terminal interface (CSTI)

• Tracer® ZN010 controller

• Tracer® ZN510 controller

• Tracer® ZN520 controller

• Tracer® UC400-B controller with optional Air-Fi® Wireless Communications Interface (WCI)

Manual Fan Speed Switch

Customer Supplied Terminal Interface (CSTI)

The CSTI is intended to be used with a field-supplied, low-voltage thermostat or controller. The control box contains a relay board which includes a line voltage to 24-volt transformer and disconnect switch (for non-electric heat units). All end devices are wired to a low-voltage terminal block and are run-tested, so the only a power connection and thermostat connection is needed to commission the unit. Changeover sensors and controls are provided whenever a change-over coil is selected. When N.O. valves are selected, inverting relays are provided for use with standard thermostats.

Figure 72. Fan speed switch

The manual fan mode switch is available for units that do not have Trane factory-mounted control packages. This four-position switch (off, high, medium, low) allows manual fan mode selection. This wall-mounted option is low-voltage and has three 24 volt relays using a factory-wired transformer and relays to control the fan motor.

Figure 73. CSTI adapter board and field connections

1. VSP 10V

2. VSP 0–10V

3. VSP DC COM

1. 24 Vac B (hot)

2. 24 Vac Y (gnd)

3. High

4. Medium

5. Low

6. V1Op/Cooling

7. V1Cl (not std)

8. Not used

9. Not used

10. V2Op/EH1St/Heating

11. V2Cl/EH2St (not std)

12. Damper Open

13. Dmp Cl (not std)

88 BCX-PRC001E-EN

Page 89: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

The CSTI adapter board provides all the hookups as the standard adapter board, but in addition, provides hookups for valve control (main and auxiliary coils), electric heat control, and damper control. Screw terminal blocks provide convenient access to fan controls and to end device control. In addition, a courtesy 10-Vdc supply is provided for use with an external potentiometer or rheostat. The 10-Vdc supply supports up to 10 mA draw.

Tracer® Controllers

Tracer® ZN010 controller is a stand-alone microprocessor controller. Tracer® ZN510 controller can be used as either a stand-alone or communicating microprocessor controller.

Tracer® ZN520 Controller

The Tracer® ZN520 controller is a factory-installed, -tested and -commissioned LonTalk® control designed to provide control of Trane products. Features include:

• Automatic fan-speed reset

• Automatic ventilation reset

• Active dehumidification

• Manual output test

• Filter maintenance

• Master slave

• Water valve override

• Freeze avoidance

• Interoperability

• Three generic I/O ports

The Tracer® ZN520 controller is designed to be used in the following applications:

• As part of a Tracer® SC or Tracer® Summit building automation system (BAS), the Tracer® ZN520 becomes an important part of the Tracer control system.

• The Tracer® ZN520 can function as a completely stand-alone controller in situations where a BAS is not present.

• For situations when a non-Trane BAS is present, the Tracer® ZN520 can be used as an inter-operable unit controller.

Through building management of the HVAC system, optimizing energy consumption becomes possible at the room level. Each unit is capable of functioning independently of one another during occupied and unoccupied hours of the day. This allows the temperature setpoint and ventilation setting to be changed automatically based on usage.

Two Systems in One

In a Tracer® system environment, the Tracer® ZN520 is pre-designed to install quickly and easily into the system. Since the controller and the unit are factory tested and commissioned, the start-up time for the entire system is minimized. Trane becomes the single source of responsibility for the equipment, unit controls, and building automation system.

As a standalone controller, the Tracer® ZN520 is ideally suited for fix-on-fail replacement of units with old pneumatic controllers, or in situations where a BAS will be added at a later date. Once power is applied to the controller, it will automatically start up and run based upon the setpoint on the local zone sensor. An individual time clock can be added to the unit for local scheduling.

The Tracer® ZN520 is certified to the interoperable LONMARK® Space Comfort Controller profile. This allows the controller to be used with another vendor’s BAS and thereby still provide the high quality of factory installation and testing. In addition, the Tracer® ZN520 provides one of the most extensive interoperable data lists of any controller of its type in the industry.

BCX-PRC001E-EN 89

Page 90: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

Tracer® UC400-B Controller

The Tracer® UC400-B single-zone VAV controller can be used in a stand-alone application or as part of a Tracer® control system.

In the stand-alone configuration, Tracer® UC400-B receives operation commands from the zone sensor and/or the auto changeover sensor (on auto changeover units).The entering water temperature is read from the auto changeover sensor and determines if the unit is capable of cooling or heating. The zone sensor module is capable of transmitting the following information to the controller:

• Timed override on/cancel request

• Zone setpoint

• Current zone temperature

• Fan mode selection (off-auto-high-med-low)

For optimal system performance, units can operate as part of a Tracer® SC building automation system. The controller is linked directly to the Tracer® SC via a twisted pair communication wire, requiring no additional interface device (i.e., a command unit). The Tracer® control system can monitor or override Tracer® UC400-B control points.This includes such points as temperature and output positions.

Tracer® Controller Features

The Tracer® family of controllers, ZN010, ZN510, ZN520, and UC400-B offer the combined advantages of simple and dependable operation with the latest Trane-designed controller. Standard control features include options normally available on more elaborate control systems. All control options are available factory-configured or can be field-configured using Rover or Tracer® TU service software. For more detailed information, refer to Trane installation manuals CNT-IOP-1 (for Tracer® ZN010 or ZN510), CNT-SVX04*-EN (for Tracer® ZN520), or BAS-SVX48-EN (for Tracer® UC400-B).

Features Available on All Controllers

The following control functions are standard features on units with Tracer® ZN010, ZN510, ZN520, or Tracer® UC400-B.

Entering Water Temperature Sampling Function

A system that uses a two-way control valve option might not sense the correct entering water temperature during long periods when the control valve is closed. If the demand for heating or cooling does not exist for a long period, the entering water will eventually approach ambient temperature.

Using the entering water temperature sampling function, the controller provides accurate two-pipe system changeover-without sacrificing the benefits of two-way control valves. Also, it eliminates inefficient bleed or bypass lines that can allow unnecessary waterflow through the system.

This function periodically samples the entering water temperature by opening the hydronic valve. The valve opens for 20 seconds to allow the water temperature to stabilize.Then the controller reads the entering water temperature for up to three minutes to see if the correct water temperature is available for the selected operating mode.

The entering water temperature must be five degrees or more above the space temperature to allow hydronic heating and five degrees or more below the space temperature to allow hydronic cooling. If the correct water temperature for the operating mode is available, the unit begins normal heating or cooling operation. If the correct water temperature is not available, the controller closes the control valve and waits 60 minutes before attempting to sample the entering water temperature again.

90 BCX-PRC001E-EN

Page 91: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

A factory-mounted thermistor senses the entering water temperature on changeover cooling/ heating coil units. If the fan coil has a factory-mounted piping package, the sensor is strapped to the entering water pipe. If the fan coil does not have a piping package, the sensor is coiled in the end pocket for mounting on customer-supplied piping.This sensor must detect accurate water temperature for proper changeover.

Automatic Heat/Cool Mode Determination

The controller automatically determines whether heating or cooling is needed-based on space and system conditions. Using a proportional/integral (PI) control algorithm to maintain the space temperature at the active heating or cooling setpoint.The controller measures the space temperature and active setpoint temperature to determine the unit's heating or cooling capacity (zero to 100 percent).

Occupied/Unoccupied Operation

The occupancy input uses a binary switch (i.e., motion sensor, time clock, etc.) that allows the zone sensor to use its unoccupied internal setpoints.

Random Start

This feature randomly staggers multiple unit start-up to reduce electrical demand spikes.

Warm-up

The two-position fresh air damper option closes during the occupied mode when the space temperature is three degrees or more below the heating setpoint temperature.The damper remains closed during warm-up until the space temperature is within two degrees of the heating setpoint temperature.

Cool-down

The two-position fresh air damper option closes during the occupied mode when the space temperature is three degrees or more above the cooling setpoint temperature.The damper remains closed during cool-down until the space temperature is within two degrees of the cooling setpoint temperature.

Manual Output Test

This function may be initiated from the blue test push button on the controller or through the Rover or Tracer® TU service tool.This feature is used to manually exercise the outputs in a defined sequence.

The purpose of this test sequence is to verify output and end device operation.The manual output test function may also be used in the following situations:

• Reset latching diagnostics

• Verify output wiring and operation

• Force the water valve(s) open to balance the hydronic system during installation set-up or service.

BCX-PRC001E-EN 91

Page 92: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

Peer-to-Peer Communication (Tracer® ZN510, ZN520, and UC400-B)

Peer-to-peer communication allows multiple units in one space to share the same zone sensor and provide simultaneous heating and cooling.The Tracer® ZN510 or ZN520 controller can share information between units on the same communication link using a twisted pair wire in the field. Unit configuration must be modified with Rover service tool.On the Tracer® UC400-B, zone sensor data sharing can be accomplished by use of the BAS system controller.

A thermistor to sense fresh air is factory-mounted at the unit's fresh air opening for use in economizer applications or as a read-only point for Tracer® SC or Tracer® Summit. If the fresh air temperature is a read-only value, it will not impact the control algorithm. In an economizer application, a fresh air temperature signal must be provided either by this thermistor, Tracer® SC, or Tracer® Summit.

Additional Features

When the zone temperature drops to heating setpoint, the fan continues to operate at minimum speed and the DAT setpoint is reset further upward. Heating capacity is modulated or staged to maintain this DAT setpoint. If the zone heating load increases to the point where DAT reaches the maximum limit, fan speed is again increased, while heating capacity is modulated or staged to maintain DAT at this maximum limit.

Economizing Control (Tracer® ZN520)

With the controller configured for economizing control, it will calculate the required cooling capacity every ten seconds and modulate the damper option open to the calculated position. If the setpoint is not satisfied, the damper will continue to open until the setpoint condition has been met or the damper is 100 percent open. If this still does not satisfy the setpoint, the cooling valve option will begin to open and try to satisfy the load requirements. Once capacity exceeds the load requirements, the valve will begin to close until the setpoint has been reached or the damper reaches its minimum position, which is field-adjustable.This option uses a three-wire, floating point damper actuator.

A thermistor to sense discharge air is factory mounted near the discharge surface of the last coil for use in economizing and cascade temperature control.Tracer® SC or Tracer® Summit can also use this temperature value as a read-only point. Cascade temperature control uses both the zone and discharge air temperatures to more accurately calculate the required unit capacity.

Figure 74. Single-zone VAV control

Single-zone VAV control. Single-zone VAV control aries the speed of the EC fan motor as the zone cooling or heating load changes. When the zone is at design cooling load, the unit operates the fan at maximum speed and cooling capacity is modulated or cycled to deliver the air at the design discharge air temperature (DAT) setpoint for cooling. As the zone cooling load decreases, fan speed is reduced to maintain zone temperature at cooling setpoint, while cooling capacity (and/or economizer) is modulated or cycled to maintain DAT at the same design setpoint. When the fan has reached minimum speed, and the zone cooling load continues to decrease, the fan continues to operate at minimum speed while the DAT setpoint begins to reset upward to maintain zone temperature at cooling setpoint. Cooling capacity (and/or economizer) is modulated or cycled to maintain this DAT setpoint.

Design heating load

Zone load Designcooling load

Minimumfan speed

Maximumfan speed

Fan speed

Discharge DATfor cooling

Maximun DATfor heating

Dis

char

ge a

ir t

empe

ratu

re s

etpo

int

92 BCX-PRC001E-EN

Page 93: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

Automatic Fan and Ventilation Reset

A two-speed fan control for the unit delivers the airflow output customized to support the cfm space needs.When less cfm is necessary to meet the load of the classroom (typically 75 to 80 percent of the time), the equipment operates on low speed. However, if the room temperature rises, the controller will switch to high speed, and the outside air damper will adjust to satisfy the space needs.This helps maintain the proper amount of ventilation air to the occupants independent of the fan speed. As part of the ventilation strategy, the controller will reposition the outside air damper to confirm the minimum outside air cfm is met at both operating conditions.

Filter Maintenance

Filter status for the controller is based on the cumulative run hours of the unit fan. The controller compares the amount of fan run time against an adjustable fan run hour (stored in the controller) to determine when maintenance is recommended for the unit. The run-hours value may be user edited as required (through Rover or Tracer® TU). The valid range for the fan run hours limit is 0 to 5000 hours with a default of 600 hours. Once the run hours limit has been exceeded, the controller generates a maintenance required diagnostic (unit will not shut-down). The user will be notified of this diagnostic through the building automation system or when a Trane service tool is communicating with the controller.

Active Dehumidification

On units with reheat coils, the controller can provide active dehumidification. This means that the relative humidity in the space can be kept below an adjustable setpoint independent of outdoor weather conditions. Indoor humidity levels are recommended by ASHRAE to be kept below 60 percent in order to minimize microbial growth and the life span of airborne illness causing germs.

Master Slave (Data Sharing)

The controller can send or receive data (setpoint, heat/cool mode, fan request, space temperature, etc.) to and from other controllers on the communication link with or without the existence of a building automation system.This applies to applications where multiple units might share one zone sensor for both stand-alone (with communication wiring between units) and a building automation system.

Water Valve Override

The controller can be commanded via the Rover service tool or Tracer® TU to open all hydronic valves 100 percent.This allows for the faster water balancing of each unit and the entire system when the command is sent globally to all controllers. A properly balanced system is essential for proper and efficient operation.

Hydronic Coil Freeze Protection (Freeze Avoidance)

Systems in cold climates need to take precautions to avoid hydronic coil freeze-up.The controller does this from three different aspects. Any of these methods of protections will result in the unit fan being disabled, the outside air damper being shut, and the hydronic valves being opened 100 percent.

The three methods of freeze avoidance include:

1. A binary freeze protection thermostat is mounted on the coil and will cause a latching diagnostic if the coil temperature falls below 35°F.

2. An analog discharge air sensor monitors the temperature of the air coming off of the coil and if the temperature falls below 40°F the outside air damper is closed, the fan is turned off and the valves are fully opened.

3. When in the unoccupied mode, the controller has an adjustable freeze avoidance setpoint. If the outside air temperature is below the setpoint, the unit will open the valves to allow water to flow through the coils.

BCX-PRC001E-EN 93

Page 94: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

Interoperability

Inter-operability allows the owner freedom to select multiple vendors, and multiple products.With this advantage, the owner can choose the best products, the best application, and the best service from a variety of suppliers to meet their evolving building control needs in a cost effective manner.

Generic Binary Input/Output

The three generic binary inputs/outputs are not part of the normal control, but are actually controlled through the Tracer® SC or Tracer® Summit system (when present) to issue commands to the controller to turn the generic inputs/outputs of add-on equipment (such as baseboard heating, exhaust fans, occupancy sensors, lighting, etc.) on and off.This binary port is not affected when other binary diagnostics interrupt unit operation.

Tracer® Controls Sequence of Operation

Fan Speed Switch (units with 3-speed fan only)

Off: Fan is turned off.

High, medium, or low: Fan runs continuously at the selected speed.

Tracer® ZN010 and ZN510

Off: Fan is off; control valves and the low air temperature detection option are still active.

Auto (Fan Cycling): The fan and mixing box damper cycle with control valve option to maintain setpoint temperature. If the unit has three-speeds, in cooling mode the fan cycles from off to high and in heating mode it cycles from off to low (factory default that can be field-adjusted using Rover service software). When no heating or cooling is required, the fan is off and the mixing box damper option closes. Units with three speeds can also be field-configured using Rover to run at a defined speed when the fan speed control is in the auto position.

Low, Medium, or High (Continuous Fan): The fan operates continuously while control valve option cycles to maintain setpoint temperature. The mixing damper option is open.

Tracer® ZN520 and UC400-B

Off: Fan is off; control valve options and mixing box damper options close. The low air temperature detection option is still active.

Auto: Fan speed control in the auto setting allows the modulating control valve option and single- or three-speed fan to work cooperatively to meet precise capacity requirements, while minimizing fan speed (motor/energy/acoustics) and valve position (pump energy/chilled water reset). As the capacity requirement increases at low fan speed, the water valve opens. When the low fan speed capacity switch point is reached, the fan switches to the next higher speed and the water valve repositions to maintain an equivalent capacity. The reverse sequence takes place with a decrease in required capacity.

Units with three-speed fans on low, medium, or high: The fan runs continuously at the selected speed and the valve option cycles to meet setpoint.

Air-Fi Wireless Systems

For more detailed information on Air-Fi® Wireless systems and devices, see:

• BAS-SVX40*: Air-Fi® Wireless Installation, Operation, and Maintenance

• BAS-PRD021*-EN: Air-Fi® Wireless Product Data Sheet

• BAS-SVX55*: Air-Fi® Wireless Network Design

94 BCX-PRC001E-EN

Page 95: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

Air-Fi Wireless Communications Interface (WCI)

Air-Fi Wireless Communications Sensor (WCS)

Wireless Zone Sensor (WZS) Set

A factory-installed Air-Fi® Wireless Communications Interface (WCI) provides wireless communication between the Tracer® SC and Tracer® unit controllers. The Air-Fi® WCI is the perfect alternative to a Trane BACnet® wired communication link. Eliminating the communication wire between terminal products, space sensors, and system controllers has substantial benefits:

• Reduced installation time and associated risks.

• Completion of projects with fewer disruptions.

• Easier and more cost-effective re-configurations, expansions, and upgrades

Communicates wirelessly to a Tracer® unit controller. A WCS is an alternative to a wired sensor when access and routing of communication cable are issues. A WCS allows flexible mounting and relocation.

A wireless zone sensor (WZS) set (sensor and receiver) communicates wirelessly to a Tracer® unit controller. A wireless zone sensor set is an alternative to a wired sensor when access and routing of communication cable are issues. The sensor allows flexible mounting and relocation.

Note: A wireless zone sensor set is not compatible with an Air-Fi® wireless system.

BCX-PRC001E-EN 95

Page 96: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

Zone Sensor Options

A variety of wall-mounted zone sensors are available for design flexibility. Zone sensors have an internal thermistor and operate on 24 Vac. Options with setpoint knobs are available in Fahrenheit or Celsius.

Figure 75. Wall-mounted zone sensor

with setpoint dial, OA,

occupied/unoccupied, COMM

Figure 76. Wall mounted zone sensor

with setpoint dial, occupied/

unoccupied, COMM.

Figure 77. Wall-mounted zone sensor

with occupied/unoccupied,

COMM.

Figure 78. Wireless zone sensor, unit

mounted receiver.

Figure 79. Wall-mounted zone sensor

with setpoint dial, OALMH,

occupied/unoccupied, COMM.

Figure 80. Wall-mounted wired display

sensor (WDS) with setpoint

adjustment, OALMH.

Figure 81. Wireless display sensor (WDS)

with setpoint, OALMH, and

unit-mounted receiver

Figure 82. Air-Fi Wireless

Communications Sensor

(WCS) with setpoint, OALMH

(UC400-B only)

Figure 83. Wall-mounted fan speed

switch

96 BCX-PRC001E-EN

Page 97: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

End Device Options

All end device options are factory-installed and -tested.

Low Temperature Detection

Condensate Overflow Detection

Table 33. End device option availability

Device Tracer® ZN010 Tracer® ZN510 Tracer® ZN520 Tracer® UC400-B CSTI

Condensate float switch • • • • •

Low limit • • • • •

Filter run-time diagnostic • • • •

Fan status • • •

2-position control valves • • • • •

Modulating control valves • • •

1-stage electric heat • • • • •

2-stage electric heat • • •

Frostat protection (DX coils) • • •

Notes:

• The Tracer® ZN010, Tracer® ZN510, Tracer® ZN520, and Tracer® UC400-B are factory-provided controls that control the end devices listed in the table.• CSTI provides an adapter board with screw down terminals for wiring to end devices for a field-supplied controller.• Positive proof fan status switch included with all Trane Controlled units

Figure 84. Low temperature detection device

When the low temperature detection device senses an entering air temperature of 36°F to the hydronic coil, the normally-closed switch opens a corresponding set of binary input terminals. The fan disables, control valves open, and the fresh air damper closes.

Thirty minutes after the diagnostic, Tracer® ZN010, ZN510, or ZN520 uses an automatic reset function to attempt to reset the unit. If the diagnostic occurs again within 24 hours after an automatic diagnostic reset, the unit will require a manual reset. This function attempts to resolve the infrequent nuisance alarm.

The low temperature detection device is an averaging type capillary tube and will reset when it detects an entering air temperature of at least 44°F.

Figure 85. Condensate overflow detection device

A float switch is factory-supplied for field installation in the auxiliary drain pan to detect a high condensate water level. When the float switch rises, the normally closed input opens a corresponding set of binary input terminals. With Trane controls installed, this also causes the fan to disable, and the control valve and fresh air damper options to close. Although the float switch will close when the high condensate level recedes, the controller must be manually reset before normal unit operation can occur. If using a Tracer® ZN510, ZN520 or UC400-B controller you can reset using Tracer® Summit. Use Rover service software to reset units with Tracer® ZN010, ZN510, or ZN520 and Tracer® TU for units with a UC400-B. When wired to the CSTI, the switch does not de-energize the unit when open position occurs. This is a dry contact only and sequence of operation of unit when this condition is reached is the responsibility of the field provided controller or thermostat.

BCX-PRC001E-EN 97

Page 98: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

Outside Air Sensor

The outside air sensor is field-mounted before the fan to sense the outside air temperature, primarily for use in economizer applications or as a status value when available for other applications.

Two-Position Mixing Box Damper Actuator

Note: Not available with Tracer® ZN520 controller.

This damper actuator uses a 24V signal. It allows zero to 50 percent fresh air. The damper will drive open to an adjustable mechanical stop-position whenever the fan is running during occupied mode and will spring-return closed when the fan turns off. The two-position damper ships separate for field installation.

Note: Trane highly recommends using the low temperature detection option with mixing box dampers to detect possible freeze conditions.

Discharge Air Sensor

The discharge air sensor is factory-mounted on the fan housing downstream of the coils for use as a status point or with other control algorithms. On units with optional electric heat, the sensor is field-mounted in the ductwork, downstream of the unit discharge.

Economizer Damper Actuator

Note: Available with Tracer® ZN520 and UC400-B controllers only.

This option is a modulating, spring-return damper actuator and is factory-wired and mounted to the mixing box damper assembly. When the controller enables the economizer damper and the unit is in occupied mode, the damper modulates between its minimum position (configurable) and the full open position to maintain setpoint temperature. If economizer operation stops or if the unit is in the heating mode, the damper adjusts to its minimum position.

Note: Trane highly recommends using the low temperature detection option with a mixing box damper to detect possible freeze conditions.

CO2 Sensor for Demand-Controlled Ventilation

Note: Available with Tracer® UC400-B controller only.

The unit is provided with a CO2 sensor to enable demand-controlled ventilation (DCV). This sensor provides a 4-20mA signal and ships separate for field installation (wired to Ul1). DCV can be used for modulating ECM, single-speed, two-speed, three-speed. It functions during occupied modes (Occupied, Occupied Standby, Occupied Bypass), in either heating or cooling mode, as long as the fan is operating (high, medium, low, On, or Auto). Refer to BAS-SVX48*-EN Tracer® UC400-B Programmable Controller for Blower Coil, Fan Coil, and Unit Ventilator Installation, Operation, and Programming manual for a description of DCV control and guidance in determining the appropriate CO2 and economizer damper setpoints for a given application.

Humidity Sensor

Note: Available with Tracer® ZN520 and UC400-B controllers only.

The humidity sensor is communicated value or with a local humidity sensor.

98 BCX-PRC001E-EN

Page 99: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

Control Valves

Three-way valve options allow either full waterflow through the coil or diverted waterflow through the bypass.

Two-Position Control Valves

Two-position valve options are spring-return or capacitor discharge-return types. Valves respond to a 24V signal and will either fully open or close. These valves cannot be driven or actuated to a partially open or closed position. If the valve loses power, the valve returns to its de-energized position.

Modulating Control Valves

Modulating control valves offer an alternative for more precise capacity control by modulating or varying the water flow through the coil. The valve responds to a 24V signal from the controller, which determines the valve position by a control algorithm. If the valve loses power, it remains in the position it was in when the power loss occurred.

Field-Supplied Valves

This option allows the controller to be factory-configured for the normal position of the field-supplied valve, as well as running a wiring harness from the control box to the piping side of the unit. When the field-supplied valve option is chosen, the control box is provided with low voltage components and wired back to a terminal strip (CSTI) or controller.

Note: Trane does not recommend wild coil applications.

How to Choose the Correct Control Valve

Valve flow coefficient or Cv, is defined as the volume of water flow through a control valve in the fully open position with a 1 psig differential across the valve. It is calculated using the following formula:

– Cv = Q/Square root ΔP where:

– Cv = flow coefficient

– Q = flow rate (Gpm)

– ΔP = pressure drop across the valve or coil (psig).

Branch authority or β (modulating valves only), which is represented by the following formula:

– β = pressure drop across the valve divided by the pressure drop across the branch circuit* x 100% = ΔP valve/ΔP branch circuit. * Branch circuit includes the coil and piping package (control valve, circuit setter, ball valves, fittings, and piping) between the supply and return riser.

Note: For good control, β should be between 25 and 70 percent.

Units with either the control interface or any of the Tracer® controllers (Tracer® ZN010, ZN510, ZN520, or UC400-B) are available with chilled and/or hot water control valves for each coil configuration. Control valve options are available as:

• Modulating

• Two-position, normally-open or normally-closed

• Two- or three-way configurations

• With sweat connections

See the valve availability table for a complete list of available valve options by size.

BCX-PRC001E-EN 99

Page 100: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Controls

Modulating Valve Selection Example

Assume a size 12 blower coil is selected to operate at the following conditions:

Blower Coil

Entering water temperature = 45°F

Leaving water temperature = 55°F

EAT conditions = 80/67.

The coil is selected as a four-row coil.

Select the best modulating valve size for this unit.

1. Find the ΔP across the water coil. Refer to the AHRI performance table to determine the ΔP across the water coil (or use TOPSS™ selection program). The water pressure drop is found to be 7.0’ of water at a flow rate of 3.74 gpm. This converts to a pressure drop of 3.03 psig (1.0 feet of water = 0.4328 psig.)

2. Calculate the Cv of the water coil.

Cv = Gpm/Square root ΔP

Cv = 3.74/Square root 3.03

Cv = 2.15

Therefore, the valve with the Cv of 2.3 should be selected since it has the Cv which is closest to the Cv of the water coil.

Table 34. Valve availability

Option

A B C D E F2-way,

2-position, N.C.

2-way, 2-position,

N.O.

3-way, 2-position,

N.C.

3-way, 2-position,

N.O.2-way,

modulating3-way,

modulating

V 2.3 Cv 3/4 in. Valve and Pipe X

W 3.3 Cv 3/4 in. Valve and Pipe X

Y 4.6 Cv 3/4 in. Valve and Pipe X X

Z 7.4 Cv 1 in. Valve and Pipe X X X X X X

1 10 Cv 1 in. Valve, 1-1/4 in. Pipe X X X X X X

2 1.0 Cv 1/2 in. Valve, 3/4 in. Pipe X

3 2.7 Cv 1/2 in. Valve, 3/4 in. Pipe X

4 4.6 Cv 3/4 in. Valve and Pipe X X X

100 BCX-PRC001E-EN

Page 101: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Data

Minimum Circuit Ampacity (MCA) and Maximum Fuse Size (MFS) Calculations

for non-Electric Heat Units

MCA = 1.25 x motor FLAs

MFS or HACR type circuit breaker = 2.25 x motor FLA

Minimum Circuit Ampacity (MCA) and Maximum Fuse Size (MFS) Calculations

for Units with Electric Heat

Heater amps = (heater kW x 1000) / heater voltage

Notes: Use 120 V heater voltage for 115 V units. Use 240 V heater voltage for 230 V units.Use 208 V heater voltage for 208 V units. Use 277 V heater voltage for 277 V units. Use 480 V heater voltage for 460 V units.

MCA = 1.25 x (heater amps + all motor FLAs) MFS or HACR type circuit breaker = (2.25 x motor FLA) + heater amps

HACR (Heating, Air-Conditioning, and Refrigeration) type circuit breakers are required in the branch circuit wiring for all units with electric heat.

Select a standard fuse size equal to the calculated MFS. Use the next smaller size if the calculated MFS does not equal a standard size.

Standard fuse sizes: 15, 20, 25, 30, 35, 40, 45, 50, 60 amps

Useful Formulas

kW = (cfm x ΔT) / 3145ΔT = (kW x 3145) / air flowSingle phase amps = (kW x 1000) / voltageElectric heat MBh = (Heater kW) (3.413) Three-phase amps = (kW x 1000)/(voltage x 1.73)

Table 35. Available motor horsepower

Motor Unit Voltage

Motor Horsepower

0.5 1.00 1.5 3

60 Hz

115/1 • •

208/1 • •

230/1 • •

277/1 • •

208/3 • • • •

230/3 • • • •

460/3 • • • •

50 Hz

220/1 • •

240/1 • •

380/3 • • • •

415/3 • • • •

BCX-PRC001E-EN 101

Page 102: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Data

Table 36. Available electric heat (kW)

Electrical heat (kW)

Voltage

115/60/1 208/60/1 220/50/1 230/60/1 240/50/1 277/60/1 208/60/3 230/60/3 380/50/3 460/60/3 415/50/3

1.0

1.5 Sizes 12-90

2.0, 2.5, 3.0

3.5, 4.0

4.5

5.0 Size 18-90

5.5, 6.0 Size 24-90

6.5, 7.0, 7.5, 8.0

9.0, 10.0, 11.0 Size 36-90

12.0

13.0, 14.0, 15.0, 16.0 Size 48-90

17.0, 18.0, 19.0, 20.0 Size 72-90

21.0

22.0, 24.0, 26.0, 28.0 Size 90

30.0

Notes:

• Magnetic contactors are standard. • Units with electric heat are available with or without door interlocking disconnect switch.• Units with electric heat are available with or without line fuses.• Units with electric heat must not be run below the minimum cfm listed. Refer to the General Data section for more information.• Electric heat is balanced staging: 1 stage = 100 percent, 2 stages = 50 percent/50 percent.

102 BCX-PRC001E-EN

Page 103: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Data

Table 37. Motor electrical data

Voltage Voltage range Rated HP Weight (lbs) FLA115/60/1 104-127 0.5 14 7.46

115/60/1 104-127 1.0 19 13.3

208/60/1 187-229 0.5 14 4.26

208/60/1 187-229 1.0 19 7.73

230/60/1 207-253 0.5 14 4.26

230/60/1 207-253 1.0 19 7.73

277/60/1 249-305 0.5 14 3.76

277/60/1 249-305 1.0 19 6.73

220/50/1 198-242 0.5 14 4.26

220/50/1 198-242 1.0 19 7.73

240/50/1 216-264 0.5 14 4.26

240/50/1 216-264 1.0 19 7.73

208/60/3 187-229 0.5 13 2.40

208/60/3 187-229 1.0 17 4.60

208/60/3 187-229 1.5 39 7.60

208/60/3 187-229 3.0 56 11.20

230/60/3 207-253 0.5 13 2.60

230/60/3 207-253 1.0 17 4.80

230/60/3 207-253 1.5 39 6.50

230/60/3 207-253 3.0 56 11.20

380/50/3 342-418 0.5 13 1.20

380/50/3 342-418 1.0 18 2.30

380/50/3 342-418 1.5 40 4.20

380/50/3 342-418 3.0 56 5.30

415/50/3 374-457 0.5 13 1.30

415/50/3 374-457 1.0 18 2.40

415/50/3 374-457 1.5 40 4.00

415/50/3 374-457 3.0 56 5.50

460/60/3 414-506 0.5 13 1.30

460/60/3 414-506 1.0 18 2.50

460/60/3 414-506 1.5 40 3.30

460/60/3 414-506 3.0 56 5.50

BCX-PRC001E-EN 103

Page 104: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Horizontal Blower Coil

Figure 86. BCHD Horizontal blower coil

B

Heating and Cooling Coils

Filters1.00

1.00

2.00

1.00

0.875 Power connection on opposite side

3.05

0.88 Knockout for hanger rodstop and bottom of unit

1.00T

F F

M D MRE

C

LH RH

W

Unit control box

Jbox

0.875 powerconnection

S 3.05

4.292.00

1.33 only for wirelesszone sensor receiver

Access panels All coil connectionslocated in this area

Filter access

P 5.50 0.95

AQ

K

0.95

1.00G

J2.15 1.50

L

19 nominal SCH 40 PVC mainand auxiliary drain connection

1.02

H

Table 38. BCHD Horizontal blower coil dimensions (in.) and weights (lb)

Unit Size H W L A B C D E F

G (RH)

G (LH)

J (RH)

J (LH) K M P Q R S T

Unit Weight

12 14.00 24.00 31.15 12.09 18.00 10.56 7.47 0.55 3.00 11.42 13.42 9.42 11.42 4.20 8.24 9.00 5.75 1.35 0.99 4.26 64.0018 14.00 28.00 31.15 12.09 22.00 10.56 7.47 0.55 3.00 11.42 13.42 9.42 11.42 4.20 10.24 9.00 5.75 3.42 0.99 4.19 69.0024 18.00 28.00 33.72 16.09 22.00 13.57 9.04 1.30 3.00 11.42 13.42 9.42 11.42 6.20 9.68 9.00 5.75 2.73 1.17 4.09 89.6036 18.00 40.00 33.72 16.09 34.00 13.57 9.04 1.30 3.00 11.42 13.42 9.42 11.42 6.20 15.68 9.00 5.75 8.64 1.01 4.19 104.5054 22.00 40.00 41.57 20.09 34.00 13.58 12.57 0.72 3.00 11.42 13.42 9.42 11.42 7.43 13.72 11.00 7.27 6.87 5.01 4.19 129.0072 22.00 48.00 41.57 20.09 40.00 13.58 12.57 0.72 4.00 11.42 13.42 9.42 11.42 7.43 17.72 11.00 7.27 10.87 5.01 4.19 142.0090 28.00 48.00 43.94 26.09 40.00 13.58 12.57 1.66 4.00 12.79 14.79 10.79 12.79 8.24 17.72 11.25 11.64 10.92 11.14 4.14 162.80

104 BCX-PRC001E-EN

Page 105: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Vertical Blower Coil

Notes:

• All coil connections are sweat style. • Weight of basic unit includes cabinet, fan, wiring and average filter. It does not include coil, motor or shipping package. Add to basic unit weight seven

pounds for weight of control box.• Control box factory-mounted on motor side.

Table 38. BCHD Horizontal blower coil dimensions (in.) and weights (lb) (continued)

Unit Size H W L A B C D E F

G (RH)

G (LH)

J (RH)

J (LH) K M P Q R S T

Unit Weight

Figure 87. BCVD Vertical blower coil

B F

Filters0.45

V

URHLH

T

M D MV

W

Jbox

Heating and Cooling Coils

W2.00

1.50

N2.15

1.50

R

JG

5.50

19 nominal SCH 40 PVC mainand auxiliary drain connection

All coil connectionslocated in this area

1.000.95

K

Q A

0.95

SFilter access

Access panels

1.02

7.40

H

L

2.00

1.33EN

C

Vertical preswirlconfiguration

Vertical counterswirlconfiguration

Only for wirelesszone sensor receiver

P

0.875 power connection

F

BCX-PRC001E-EN 105

Page 106: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Table 39. BCVD Vertical blower coil dimensions (in.) and weights (lb)

Unit Size H W L A B C D E F G (RH) G (LH) J (RH) J (LH)24 51.72 28.00 32.22 16.09 22.00 13.57 9.04 1.30 3.00 11.42 13.42 9.42 11.42

36 51.72 40.00 32.22 16.09 34.00 13.57 9.04 1.30 3.00 11.42 13.42 9.42 11.42

54 63.57 40.00 40.07 20.09 34.00 13.58 12.57 0.72 3.00 11.42 13.42 9.42 11.42

72 63.57 48.00 40.07 20.09 40.00 13.58 12.57 0.72 4.00 11.42 13.42 9.42 11.42

90 71.94 48.00 42.44 26.09 40.00 13.58 12.57 1.66 4.00 12.79 14.79 10.79 12.79

Unit Size K M N P Q R S T U V WBasic Unit

Weight24 6.20 9.68 18.00 9.00 5.50 28.00 10.00 1.96 4.88 3.90 4.56 141.10

36 6.20 15.68 18.00 9.00 5.50 28.00 10.00 8.63 4.88 3.23 4.56 168.80

54 4.21 13.72 22.00 11.00 7.27 30.00 8.00 6.87 8.88 3.23 4.56 197.40

72 4.18 17.72 22.00 11.00 7.27 30.00 8.00 5.83 8.88 8.27 4.56 246.40

90 4.81 17.72 28.00 11.25 11.64 30.00 2.00 7.84 14.88 6.26 4.56 258.40

Notes:

• All coil connections are sweat style.• Weight of basic unit includes cabinet, fan, wiring and average filter. Add to basic unit weight seven pounds for weight of control box. Control box factory-

mounted on motor side.• Vertical coil and filter section ships separate for field installation. Refer to installation and maintenance manual for instructions.• Vertical units provided with 4-inch to 6-inch high mounting legs. Legs are seismic rated.

106 BCX-PRC001E-EN

Page 107: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Compact Vertical Blower Coil

Figure 88. BCCD compact vertical blower coil

P

VG H J

F

13.03

EDC

B

A

4.54

4.28

3.00

1.59

T

S

N

M

1.03

1.66

7.35

K

Q

L

R

1.27.908

1.38

1.75

2.01

0.875 Powerconnection

0.875 Powerconnection

Filte

r

Heating and cooling coilsMain coilconnections

3/4-inch nominal SCH40 PVC main drainconnection

Aux coilconnections

Front openreturn only

Max 3.50

Bottom return only

BCX-PRC001E-EN 107

Page 108: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Table 40. BCCD Compact vertical blower coil dimensions (in.) and weights (lb)

Unit Size A B C D E F G H J K

24 44.50 1.00 2.00 10.25 18.00 2.10 5.51 9.01 13.48 8.00

36 48.50 1.00 2.00 10.25 21.50 3.74 5.51 9.01 13.48 8.00

48 55.50 1.00 1.25 13.25 23.00 3.74 7.03 11.51 14.46 7.88

60 57.50 1.00 1.25 13.25 26.00 3.98 7.03 11.51 14.46 7.88

Unit Size L M N P Q R S T Basic Unit Weight

24 20.56 6.19 22.43 28.00 7.05 21.50 22.00 7.00 111

36 24.70 9.63 22.43 28.00 7.05 25.64 22.00 11.20 125

48 26.19 11.48 27.43 33.00 9.53 25.96 27.00 12.48 163

60 29.04 14.60 27.43 33.00 7.65 30.67 27.00 16.22 174

Notes:• All coil connections are sweat style. • Weight of basic unit includes cabinet, fan, wiring and average filter. Does not include coil, motor, or shipping package. Add to basic unit weight seven pounds

for weight of control box.

108 BCX-PRC001E-EN

Page 109: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Options

Angle Filter and Mixing Box

Figure 89. Angle filter and mixing box dimensions

Table 41. Angle filter and mixing box dimensions (in.) and weights (lb)

Unit Size H L W A B C Weight12 14.12 22.00 24.11 7.06 15.56 4.28 36.0018 14.12 22.00 28.11 7.06 19.56 4.28 41.0024 18.12 19.50 28.11 7.06 19.56 4.28 43.0036 18.12 24.50 40.11 7.06 31.56 4.28 56.0054 22.12 23.50 40.11 12.81 31.56 4.28 72.0072 22.00 23.50 48.00 12.81 31.56 8.22 72.5090 27.90 27.56 48.00 12.85 31.56 8.22 84.10

combination angle filter

& mixing box

mixing box

angle filter box

Angle filter box

Mixing box

Combination anglefilter and mixing box

BCX-PRC001E-EN 109

Page 110: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Bottom or Top Access Filter Box

Figure 90. Bottom or top access filter box

Table 42. Bottom or top access filter box dimensions (in.) and weights (lb)

Unit Size H W A B C D Weight12 14.00 24.00 9.98 2.01 18.23 2.88 1518 14.00 28.00 9.98 2.01 21.98 3.01 1724 18.00 28.00 14.23 1.89 23.23 2.38 1836 18.00 40.00 14.23 1.89 33.73 3.13 2554 22.00 40.00 18.23 1.89 33.73 3.13 2872 22.00 48.00 18.23 1.89 42.73 2.63 3290 28.00 48.00 23.23 1.89 41.23 3.38 37

7.170.97

Airflow

Filter

Right side view

Filter access panel

A H

B

Filter

D C

W

AirflowTop view

Rotate 180° for top accessSections ship attached to the unit.

110 BCX-PRC001E-EN

Page 111: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Electric Heat

Figure 91. BCHD/BCVD Blower coils with electric heat section

Table 43. BCHD/BCVD Blower coils with electric heat section dimensions (in.) and weights (lb)

Unit Size W X Y12 28.28 37.97 n/a18 32.29 37.97 n/a24 30.54 40.75 48.5436 42.57 40.75 60.5754 44.32 48.39 66.3272 48.29 48.60 70.2990 48.29 50.96 76.29

Horizonatal Blower Coil

Vertical Blower Coil

Unit controlbox

Electric heat elements

Electric heat controls

Unit controlbox

Electric heat elements

Electric heat controls

Note 13.46 in. for units with CSTI, DX and 2-stage EH1.33 in. for units with wireless zone sensor

see Note 1W

W

Y

X

see Note 1

BCX-PRC001E-EN 111

Page 112: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Figure 92. BCCD blower coil with electric heat section

Table 44. BCCD Blower coils with electric heat section dimensions (in.)

Unit size A B26 52.00 28.0036 56.00 28.0048 63.00 33.0060 65.00 33.00

A

BUnit control box

Electric heat controls

Electric heat elements

112 BCX-PRC001E-EN

Page 113: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

• Electric heater is factory mounted on unit discharge face and wired to unit control box.

• Heater may be mounted with horizontal or vertical up airflow.

• Electric heat may need field-supplied externally-wrapped insulation if the unit is installed in an unconditioned space or if sweating is an issue.

Figure 93. Electric heat section for BCHD/BCVD

Table 45. Electric heat section for BCHD/BCVD dimensions (in.) and weights (lb)

Unit Size H W A B C D E Weight12 14.06 17.88 8.13 6.79 10.50 8.75 0.03 10.0018 14.06 19.88 10.13 8.79 10.50 8.75 0.03 10.8024 18.06 17.75 7.63 6.29 13.50 9.13 0.80 11.3036 18.06 23.75 13.63 12.29 13.50 9.13 0.80 12.8054 18.06 27.25 13.63 11.67 13.50 12.63 0.22 16.0072 18.06 27.25 13.63 11.67 13.50 12.63 0.22 17.4090 18.06 27.25 13.63 11.67 13.50 12.63 1.16 19.20

1.501.50

A

W

1.00

E

1.00

0.56

H

1.00

6.631.00

BD1.00

Duct opening

Duct opening

C

3.00

1.25

2.001.25

1.25

0.875 Power connectionon opposite side

0.875 Power connection

0.875 Power connectionon opposite side

Right hand heater shown. Left hand heater is mirror image of right hand.

Mounting flange top and bottom unit sizes 12, 18, 24, 36Top only unit sizes 54, 72, 90, 120

Control panel door

Mounting flange bottomunit sizes 54, 72, 90, 120

Airflo

w

BCX-PRC001E-EN 113

Page 114: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Figure 94. Electric heat section for BCCD size 24-36

B

M

1.00

A

P

C

D

1.00

N Q

E

G

H

F

K

1.00

L7.63

1.00

T

U

0.875 Powerconnection

0.875 Powerconnection

Control panel door

Hinges

0.875 Powerconnection onopposite side

Airflo

w

114 BCX-PRC001E-EN

Page 115: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

• Electric heater is factory mounted on unit discharge face and wired to unit control box.

• Electric heat may need field-supplied externally-wrapped insulation if the unit is installed in an unconditioned space or if sweating is an issue.

Figure 95. Electric heat section for BCCD size 48-60

B

M

1.00

A

E

P

C

G

H

D F

K

1.00

J

L

1.00

7.63

N Q

1.00

�.875 POWER CONNECTION

R

S

Control panel door

0.875 KO

Hinges

0.875 Powerconnection on opposite side

0.875 Powerconnection on opposite side

Airflo

w

Table 46. Electric heat section for BCCD dimensions (in.) and weights (lb)

Unit Size A B C D E F G H J K L M N P Q R S T U Weight24 15.06 10.13 13.48 10.99 1.12 8.67 3.88 5.12 n/a 6.74 3.66 0.56 7.09 0.63 3.95 n/a n/a 0.56 5.77 15.2036 15.06 10.13 13.46 13.54 2.03 9.46 4.25 6.41 n/a 7.77 3.72 0.56 8.13 1.00 2.64 n/a n/a 0.56 7.08 17.2048 15.25 12.17 14.68 15.59 1.83 11.92 3.90 7.80 13.66 7.34 3.75 0.75 8.64 1.00 3.04 n/a n/a n/a n/a 21.5060 15.26 12.17 16.68 18.49 0.79 16.91 3.88 9.34 12.93 7.34 3.88 0.76 9.94 1.00 2.39 3.88 3.79 n/a n/a 23.40

BCX-PRC001E-EN 115

Page 116: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Steam Coil

Coil Connections

Figure 96. Steam coil dimensions

Access panel

Hea

ting

coil

Filter access

Airflow

21.00

0.97

0.97

H A

W

B CC

Table 47. Steam coil box dimensions (in.) and weights (lb)

Unit Size H W A B C WeightCoil Connections, NPTSupply Return

12 14.00 24.00 12.06 18.04 2.98 34 1 3/418 14.00 28.00 12.06 22.04 2.98 37 1 3/424 18.00 28.00 16.06 22.04 2.98 40 1-1/2 136 18.00 40.00 16.06 34.04 2.98 48 1-1/2 154 22.00 40.00 20.06 34.04 2.98 50 2 172 22.00 48.00 20.06 42.04 2.98 56 2 190 28.00 48.00 26.06 40.04 3.98 63 2-1/2 1-1/4

Notes:

• Filter access and access panel located on both sides.• Weight includes cabinet with average filter, but does not include coil weight. See general data section for coil weights.

Table 48. BCHD/BCVD hydronic coil connection sizes, OD (in.)

Unit SizeStandard Capacity High Capacity

1-Row 4-Row 6-Row 2-Row 4-Row 6-Row12 5/8 — — 5/8 7/8 7/818 5/8 — — 5/8 7/8 7/824 5/8 — — 7/8 1-1/8 1-1/836 5/8 — — 7/8 1-1/8 1-1/854 1-1/8 1-3/8 1-3/8 1-1/8 1-1/8 1-1/872 1-1/8 1-3/8 1-3/8 1-1/8 1-1/8 1-1/890 1-1/8 1-5/8 1-5/8 1-1/8 1-1/8 1-1/8

Table 49. BCCD hydronic coil connection sizes, OD (in.)

Unit Size 1, 2-Row 4, 6-Row24 7/8 1 1/836 7/8 1 1/848 7/8 1 3/860 7/8 1 3/8

116 BCX-PRC001E-EN

Page 117: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Piping Packages

Table 50. BCHD/BCVD DX coil connection sizes, OD (in.)

Unit Size3-Row and 4-Row 6-Row

Suction Liquid Suction Liquid12 5/8 5/8 5/8 5/818 5/8 5/8 5/8 5/824 5/8 5/8 7/8 5/836 7/8 5/8 7/8 5/854 1 1/8 7/8 1 1/8 7/872 1 1/8 7/8 1 1/8 7/890 1 3/8 7/8 1 1/8 7/8

Table 51. BCCD DX coil connection sizes, OD (in.)

Unit Size3, 4, 6-Row

Suction Liquid24 7/8 5/836 7/8 5/848 1 1/8 7/860 1 1/8 7/8

Table 52. Steam coil connection sizes, female connection, NPT (in.)

Unit Size Supply Return12 1 3/418 1 3/424 1-1/2 136 1-1/2 154 2 172 2 190 2-1/2 1-1/4

Table 53. Piping package dimensions (in.)

Piping Package

Nominal Tube Size

ActualSize Valve Size A B C D E F

2-way, Basic0.750 0.875 0.750 11.31 2.62 - - - -1.000 1.125 1.000 16.06 4.40 - - - -1.250 1.375 1.000 16.04 3.70 - - - -

2-way, Deluxe0.750 0.875 0.750 11.31 - 6.87 - - -1.000 1.125 1.000 16.06 - 9.76 - - -1.250 1.375 1.000 16.04 - 9.95 - - -

3-way, Basic

0.750 0.875 0.500 14.17 0.96 - 1.86 6.07 -0.750 0.875 0.750 11.11 3.16 - 2.39 7.98 -1.000 1.125 1.000 16.05 1.35 - - 6.68 5.511.250 1.375 1.000 18.54 1.22 - - 7.57 7.02

3-way, Deluxe

0.750 0.875 0.500 15.81 3.56 - 1.86 6.07 -0.750 0.875 0.750 12.75 5.76 - 2.39 7.99 -1.000 1.125 1.000 14.91 5.17 - - 6.68 5.511.250 1.375 1.000 18.09 5.47 - - 7.57 7.02

BCX-PRC001E-EN 117

Page 118: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Basic Piping

Figure 97. 2-way basic piping package

Figure 98. 3-way basic piping package - 3/4-in piping

A B

MainReturnA B

2-way control valve

Return from coil

BALL VALVE

A B

E

D

3-way control valve

Return from coil A B

AB

Bypass flowfitting

Supply

Return tochiller

BALLVALVE

BALL VALVE

118 BCX-PRC001E-EN

Page 119: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Deluxe Piping

Figure 99. 3-way basic piping package – 1-in and 1 1/4-in piping

F

A B

E

3-waycontrolvalve

3-waycontrolvalve

Supply

Bypass flowfitting

Supply

Return tochiller

A AB

Return from coil

B

BALL VALVE

BALL VALVE

Figure 100. 2-way deluxe piping package

C

A

SupplySupply

Return from coil

A B2-way control valve

BALLVALVE

STRAINER

MANUAL CIRCUITSETTER

BCX-PRC001E-EN 119

Page 120: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions and Weights

Figure 101. 3-way deluxe piping package – 3/4-in piping

Figure 102. 3-way deluxe piping package – 1-in and 1 1/4-in piping

A B

D

E

Return tochiller

A BReturn from coil

3-way controlvalve

Bypass flowfitting

Supply

AB

Supply

Manual circuitsetter

Strainer

Ball valve

A B

E

F

Bypass flowfitting

Supply

Return tochiller

B

3-way controlvalve

Supply

Return from coil A AB

Ball valve

Strainer

Manual circuitsetter

120 BCX-PRC001E-EN

Page 121: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Mechanical Specifications

General

The product line consists of horizontal and vertical air handling units and mixing boxes. Units are tested and certified with AHRI 430 and tested in accordance with AHRI 260. The unit complies with NFPA 90A and is UL listed to U.S. and Canadian safety standards.

Air handlers consist of a hydronic and/or DX coil, drain pan, and centrifugal fan with motor mounted in a common cabinet. Coil connections are independent for the same or opposite side location.

Horizontal air handlers are provided with knockouts in all four corners for installing the unit suspended from the ceiling with threaded rods.

Unit and accessories are insulated with 1-inch, 1-1/2 lb/ft3 density fiberglass insulation. One-inch foil-faced insulation is also available.

Large motor access panels are provided on both sides of the unit and accessories for horizontal model BCHD and vertical model BCVD. Vertical models BCVD ship in two pieces.

Casings

Casings (structural components) are constructed of heavy-gauge galvanized steel, insulated with one-inch, 1-1/2 lb density fiberglass fire resistant and odorless glass fiber material to provide thermal and acoustical insulation. Fan housing sides are directly attached to the air handler top and bottom panels strengthening the entire unit assembly. Coil access panels are located on both sides of BCHD/BCVD air handlers and allow easy removal of the internal coils and drain pan. Coil access is located on the front of the BCCD model. Main access panels provide generous access to the fan and motor from both sides of the BCHD/BCVD air handler, and the front of the BCCD unit.

Coils

Hydronic Coils

Cooling coils are four- or six-row, chilled water. Heating coils are one- or two-row hot water. Heating coils are available factory-installed in the preheat or reheat position. All hydronic coils are 12 fins per inch. All hydronic coils use highly efficient aluminum fins, mechanically bonded to seamless copper tubes. All coils are specifically designed and circuited for water use. All coils are factory tested with 450 psi air under water. Maximum standard operating conditions are: 300 psig, 200°F. Sweat type connections are standard. Coil performance data is in accordance with the current edition of AHRI Standard 410.

Direct Expansion (DX) Coils

DX coils use refrigerant 410A, have 3/8” OD x 0.014” W round seamless copper tubes expanded into full fin collars for permanent fin-tube bond. Three-, four-, and six-row DX coils use highly efficient aluminum fins mechanically bonded to stainless copper tubes with 12 fins per inch fin spacing.

The coil casing is 16-gauge galvanized steel. A foam sealing strip between the casing (top and bottom) channels and fins helps eliminate air bypass and reduce potential water carryover. Coils have round, seamless, copper pipe liquid lines and suction headers with male sweat connections. Suction headers have bottom connections to aid drainage of any oil that may collect in the coil. Liquid line and suction connections are outside the unit casing (on the same side of the unit) to facilitate field piping. Connections are clearly labeled to ensure coils are piped correctly. Coils have a venturi-type distributor assembly designed with a vertical downflow feed for low pressure drops.

Coils are proof tested at 715 psig and leak tested at 650 psig air-under-water. Coils are dehydrated and sealed with a dry air charge. Maximum standard operating conditions are 650 psig at 127°F with R-410A. Coil performance data is in accordance with the current edition of AHRI Standard 410.

BCX-PRC001E-EN 121

Page 122: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Mechanical Specifications

Steam Coils (Type NS)

A one-row steam distributing coil section is available in the pre-heat position. Steam coils are non-freezing and are pitched to ensure adequate condensate drainage. Coils have 1” OD x 0.031” W round seamless copper condensing tubes expanded into full fin collars for permanent fin-tube bond. Coil headers are cast iron for permanent leak-tight joints. Coils have continuous Sigma-Flo™ aluminum fins with full fin collars for maximum fin-tube contact and accurate spacing at 6 fpi. The coil casing is 16-gauge galvanized steel. Coil headers are gray cast iron with NPT internal thread connections.

Supply, return, and vacuum breaker connections are located at the same end of the unit and clearly labeled to ensure coils are piped correctly. Distributor tubes are 11/16” OD copper. Also, they have die-formed, accurately-spaced directional kinetic orifices that discharge steam in the direction of condensate flow (toward the return connection) to ensure even steam distribution across the coil face area and push out condensate. Distributor tubes are located concentrically within condensing tubes using corrosion resistant support clips. Supply header steam deflectors prevent impingement of steam into tubes in supply connection area.

Coils are proof tested at 300 psig and leak tested at 200 psig air-under-water. Maximum standard operating conditions are 15 psig at 400°F. Coil performance data is in accordance with the current edition of AHRI Standard 410.

Fan

The fans are DWDI (double width double inlet) forward curved centrifugal blower type. The fans are direct drive mounted directly to the motor shaft. All fans are dynamically balanced. All air handlers have a single fan.

EC Motors

A 50/60 Hertz, variable speed, multiple voltage EC motor has a plus or minus 10 percent voltage utilization range. The motor is open type with permanently sealed ball bearings, internal overload protection, and uses a radial mount. The motor is factory installed, programmed, and wired to the air handler control panel.

All motors are brushless DC (BLDC)/electronically commutated motors (ECM) factory-programmed and run-tested in assembled units. The motor controller is mounted in a touch-safe control box with a built-in integrated user interface and LED tachometer. If adjustments are needed, motor parameters can be adjusted through momentary contact switches on the motor control board accessible without factory service personnel.

Motors will soft-ramp between speeds to lessen the acoustics due to sudden speed changes. Motors can be operated at single speed, three speeds or with single zone VAV control. The motor will choose the highest speed if there are simultaneous/conflicting speed requests.

All motors have integral thermal overload protection and are permanently lubricated. BCHD/BCVD single-phase motors have a maximum ambient operating temperature of 104°F and three-phase motors have a maximum ambient operating temperature of 130°F. BCCD motors have a maximum ambient operating temperature of 104° F. Motors are capable of operating at 90 percent of rated voltage on all speed settings. Motors can operate up to 10 percent over voltage.

Drain Pan

The drain pan is noncorrosive and double-sloped to allow condensate drainage. The drainpan construction is polymer or optional stainless steel. Coils mount above the drain pan—not in the drain pan—thus allowing the drain pan to be fully inspected and cleaned. The drain pan can also be removed for cleaning. The polymer drain pan connections are unthreaded 3/4-inch schedule 40 PVC for solvent bonding. The stainless steel drain pan connection is 3/4-inch NPT schedule 40 stainless steel pipe. The main drain connection is at the lowest point of the drain pan. An auxiliary drain connection is provided on the same side as the main connection for BCHD/BCVD. BCCD

122 BCX-PRC001E-EN

Page 123: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Mechanical Specifications

utilizes a rubber hose for an internal trap. A 3/4-inch schedule 40 PVC can connect to the internal trap with the provided hose clamp.

Filters

One-inch standard efficiency throwaway, two-inch MERV 8, and two-inch MERV 13 are available on all blower coil units. Units have a standard flat filter rack that is sized for less that 500 feet per minute at nominal airflow. An optional angle filter rack is available; this is sized for less than 300 feet per minute at nominal airflow. All units and filter racks use standard filter sizes.

Units equipped with MERV 8 filters have a rating based on ASHRAE Standard 52.2. The average dust spot efficiency is no less than 35 to 40 percent when tested in accordance with ASHRAE 52.1 atmospheric dust spot method.

Mixing Box

Mixing boxes are constructed of heavy-gauge galvanized steel. They are complete with two low-leak parallel blade dampers that are factory-linked together. A 1/2-inch extendible drive rod is provided that can be used for actuator connection, either internally or externally. Damper blades are extruded aluminum having interlocked PVC extruded edge seals. Damper frame seals are PVC extruded forms interlocked to the damper frame and provided with a continuous edge seal to the blades. Damper seals are stable in the temperature range of -50°F to 230°F.

Mixing boxes also include two side access panels as standard to provide access to the unit’s internal components.

Electric Heater

The heater is a UL recognized resistance open-wire heater with disc-type automatic and manual reset-type thermal safety devices. The electric heater is factory-mounted and an air handler with this heater is a UL/CUL product. One or two stages of control are available. A single-point power connection to the unit is provided. Optional heater fuses, and a heater door interlocking disconnect switch are available.

Controls

Controls options are: control interface, Tracer® ZN010, ZN510, ZN520, and UC400-B. A variety of inputs and outputs are available for the control interface and Tracer controller options. A disconnect switch (for non-electric heat units), fused transformer, contactor(s), and terminal strip are provided with the control interface and Tracer controller options.

Customer Supplied Thermostat Interface (CSTI)

The control interface is intended to be used with a field-supplied, low-voltage thermostat or controller. The control box contains a line voltage to 24-volt transformer and a disconnect switch on non-electric heat units.

Tracer ZN520

The Tracer® ZN520 discrete speed controller can be used as part of a building automation system with Lontalk communication. The Tracer® ZN520 offers the combined advantages of simple and dependable operation. Standard control features include options normally available on more elaborate control systems. All control options are available factory mounted, wired and configured and can also be field configured using a service tool.

Tracer UC400-B

The Tracer® UC400-B controller delivers single zone VAV control in a stand-alone application or as part of a building automation system with BACnet communication. The UC400-B ships with unit of measure over BACnet link in SI units. When a BAS system is unable to convert to other desired units a free software tool is available for changing to other unit of measure. The Tracer UC400-B offers the combined advantages of a factory mounted, wired and programmed controller for

BCX-PRC001E-EN 123

Page 124: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Mechanical Specifications

dependable out-of-the box operation. Standard control features include options normally available on more elaborate control systems. All control options are available factory programmed with additional configuration and programming in the field using a service tool.

Wireless Comm Interface (WCI)

The Trane Wireless Comm Interface (WCI) enables wireless communication between system controls, unit controls, and wireless sensors for the new generation of Trane control products. The WCI replaced the need for communication wire in all system applications and communicates via the ZigBee PRO protocol.

Seismic Certification

IBC Seismic Certification

Blower coil models BCHD and BCVD (all sizes) are certified to meet or exceed all seismic provisions set forth in IBC 2000, 2003, 2006, 2009, and 2012 where SDS ≤ 2.27g and z/h up to 1.0. The testing procedures and the acceptance criteria for passage of the seismic shake test are set forth in accordance with ICC-ES AC-156. All non-robust components, considered critical to the unit’s continued function, were successfully shake-tested under the witness of and analytical evaluation by an independent approval agency. This equipment is capable of structurally withstanding and remaining functionally operational after a seismic event and approved for seismic application when properly installed, used as intended, and located in the United States.

OSHPD Seismic Certification

Blower coil models BCHD and BCVD (all sizes) are certified to meet or exceed all seismic provisions set forth in IBC 2000, 2003, 2006, 2009, and 2012 where SDS ≤ 2.27 g and z/h up to 1.0. California OSHPD OSP-0123-10. The testing procedures and the acceptance criteria for passage of the seismic shake test are set forth in accordance with ICC-ES AC-156. All non-robust components, considered critical to the unit’s continued function, were successfully shake-tested under the witness of and analytical evaluation by an independent approval agency. This equipment is capable of structurally withstanding and remaining functionally operational after a seismic event and approved for seismic application when properly installed, used as intended, and located in the United States.

Piping Packages

All piping packages are proof-tested at 300 psig (air) and leak tested at 100 psig (air under water). The maximum working pressure of the interconnecting piping is 300 psig.

Control valves are mounted in all factory piping packages. All piping packages are factory installed and come in two options:

• Basic: Shut-off ball valve on the supply line. Control valve and shut-off ball valve on the return line.

• Deluxe with Manual circuit setter: Strainer and shut-off ball valve on the supply line. Control valve and manual circuit setter on the return line.

Two Position Control Valves

Two position control valves are ball valve design with zero leakage. The ball valve incorporates self-cleaning technology to provide superior clog resistance. The actuator is easily removable for service without removing the valve body.

Valves with a Cv of 2.4 to 4.8 are capacitor discharge return. Valves with a Cv of 7.4 and 10.0 are spring return.

124 BCX-PRC001E-EN

Page 125: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Mechanical Specifications

Modulating Control Valves

Modulating control valves are ball valve design with zero leakage. The ball valve incorporates self-cleaning technology to provide superior clog resistance. The actuator is easily removable for service without removing the valve body. The actuator is easily removable for service without removing the valve body. Actuators are fail in place.

End Valves

Each piping package includes a ball valve for the entering water pipe and one of the following end valves on the leaving water pipe: ball valve or manual circuit setter.

Ball Valve

Ball valves, also known as stop valves, allow the unit to be cut off for service purposes. These valves have a two-inch handle that rotates 90o to a fully closed position.

Manual Circuit Setter

A manual circuit setter acts as both a flow setting device and a stop valve. This valve allows water flow through the unit to be set quickly and accurately. The manual circuit setter includes ¼ in. Schrader ports in the valve body. These ports are used to measure the pressure drop across the

Table 54. Control Valve - 2.4-4.6 Cv

Figure 103. Control valve MaterialMedia

TemperatureWorking Pressure

Differential Pressure

Close off Pressure

Body - Forged BrassBall - Chrome Plated Brass

Stem - BrassSeats - PTFE

O-Rings - EPDM (lubricated)

36oF Min200oF Max

360 psig 40 psig 75 psig

Table 55. Control Valve - 7.4-10.0 Cv

Material Media Temperature Working Pressure Differential Pressure Close off Pressure

Body - Forged Brass Nickel Plated

Ball - Stainless SteelStem - Stainless Steel

Seats - PTFEO-Rings - EPDM (lubricated)Characterizing Disk - Tefzel®

0oF Min250oF Max

600 psig 50 psig 200 psig

Figure 104. Ball valve Material Media Temperature Working PressureBody - BrassSeat - RPTFEBall - Brass

Stem - BrassStem Packing - RPTFE

Nut - Corrosion Resistant Plated SteelRetainer - Brass

Handle - Plated Steel / Insulated PolyvinylGland - Brass

0oF min400oF max

600 psig

BCX-PRC001E-EN 125

Page 126: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Mechanical Specifications

valve. This pressure drop can be compared to factory supplied curves that relate the pressure drop to a specific flow rate. This valve also has a memory stop that helps find the correct setting quickly.

Strainer

The strainer contains a 20 mesh screen with 2.5 square inches of screen area.

Bypass Balance Valve

All three-way control valve packages include a balance fitting in the bypass line to allow flow balancing in the bypass position.

Figure 105. Manual circuit setter Material Media Temperature Working PressureBody - BronzeSeats - Teflon®

Internal Components - Brass, Teflon®, EPDMSchrader Valve Connections - Brass 1/4 in.

Indicator Plate - Stainless SteelPointer - Die Cast Zinc

250°F max 300 psig

Figure 106. Strainer Material Media Temperature Working Pressure

Body - Forged BrassScreen - 20 Mesh Stainless SteelO-Ring - TFE Coated Neoprene

-40oF min300oF max

700 psig

Figure 107. Balance fitting Material Media Temperature Working Pressure

Body - Cast BronzeStem/Gland Screw - Brass

O-Ring - EPDMPacking Washer - 11 Ga Brass

250oF max 300 psig

126 BCX-PRC001E-EN

Page 127: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 128: Blower Coil Air Handler Models BCHD, BCVD, and BCCD...Trane Blower Coils—Factory Packaged How You Need It... When You Need It . . . . . . . . . . . . . . . . . . . . . . . . . .

Ingersoll Rand has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.We are committed to using environmentally conscious print practices.

Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficientenvironments. Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® andTrane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protectfood and perishables; and increase industrial productivity and efficiency. We are a global business committed to aworld of sustainable progress and enduring results.

The AHRI Certified mark indicates Ingersoll Rand’s participation in the AHRI Certification program. For verification of individual certified products, go to www.ahridirectory.org.

ingersollrand.com

©2018 Ingersoll RandBCX-PRC001E-EN 06 Jun 2018Supersedes BCX-PRC001D-EN (Jul 2016)