Electrical transmitter

download Electrical transmitter

of 4

Transcript of Electrical transmitter

  • 7/24/2019 Electrical transmitter

    1/4

    masibus UT-94

    Document Ref No. m98A/om/101 Issue No: 06

    Masibus Automation And Instrumentation (P) Ltd.B-30,GIDC Electronics Estate,

    Gandhinagar.E Mail: [email protected]

    Page 1 of 4

    INTRODUCTION

    This is a micro-controller based Universal Transmitter whichretransmits the Universal Inputs given, into the required Voltageor current.

    This instrument provides isolation at 4 levels:

    (a) Between input and Power supply(b) Between output and Power supply.(c) Between input and output.(d) Output to Output.

    SPECIFICATIONS

    MODEL : UT-94

    TYPE : Universal Transmitter withDual

    Retransmission Output.

    DISPLAY : 4 digit, 0.3", 7- segment red LED

    DISPLAY SCALING:-1999 to 9999

    DISPLAY RANGE :RTD : -199.9 TO 850.0 CLinear : -1999 to 9999 (selectable)T/C : as per sensor

    KEYS : 3 Keys (ENT, SEL & ESC)

    NO. OF INPUT : One

    I/P TYPES : -T/C : E, J, K, T, B, R, S, NRTD : Pt100, 3-WIRE

    Linear : -10 - 20mV, 0-100mV, 0-2V, 0.4-2V,0-5V, 0-20mA, 1-5V, 4-20 mA, 0-10 VDC

    I/P ACCURACY : 0.1% of Full Scale.

    I/P RESOLUTION : As Per Input table.

    RESPONSE TIME : 75 mSec.

    LINEARIZATION : Through Software, using 9thorder Co-

    METHOD efficient.

    NO OF OUTPUTS : Two (O/P-2 is Optional).

    O/P TYPES : 4 -20mA, 0 -20mA , 1-5V, 0-5V, 0-10VDC (Either Voltage or Current from achannel at a time)

    O/P LOAD : 750 Ohms max (For Current O/Ps)4000Ohms min (For Voltage O/Ps)

    O/P ACCURACY : 0.25% of Full Scale.

    TRANSMITTED : 24VDC @ 30 mA, with

    POWER SUPPLY Short circuit Protection

    CALIBRATION : Through Front panel

    COLD JUNCTION

    COMPENSATION : By software.

    OVER RANGE O/P : 5% above F.S.(Not applicable for Voltage Inputs)

    PROTECTION : Short ckt. & Open ckt. (At output)

    CMRR : > 120 dB

    NMRR : > 50 dB

    THERMOCOUPLE : (Programmable scaling)

    BURN OUTOPERATING SUPPLY : 85-265 VAC or

    18-30 VDC (Optional).

    POWER CONSUMPTION: < 10 W

    ISOLATION : Three port isolation I.e. betweeninput/ output/ power supply.

    ISOLATION LEVEL : 1500 VAC/ 500VDC@2000 Megaohms between input, outputsand power supply

    MOUNTING : DIN Rail

    DIMENSION : 55 (W) x 75 (H) x 110 (D) mm

    OPERATING : 0 to 55 deg CTEMPERATURE

    OPERATING RH : 20% to 90 % RH non-condensing.

    Dimensions

    Front Panel

    ENTER / SCROLL KeyThis key is used to start menu,scroll through the menu and savevalues.

    SEL / SHIFT Key This key is used to select the menuoptions, for shifting the digit of theselected parameters and for

  • 7/24/2019 Electrical transmitter

    2/4

    masibus UT-94

    Document Ref No. m98A/om/101 Issue No: 06

    Masibus Automation And Instrumentation (P) Ltd.B-30,GIDC Electronics Estate,

    Gandhinagar.E Mail: [email protected]

    Page 2 of 4

    Ambient display in Run Mode forTC Input.

    ESC / INC Key This key is used to revert back tothe parent menu from the sub

    menu levels and Increment theselected digit.

    Menu Function List

    inTY

    T/C: E, J, K, T, B, R, S, N.RTD: Pt100 3-WIRE.Linear: -10 - 20mV, 0-100mV, 0-2V,0.4-2V, 0-5V, 0-20mA, 1-5V, 4-20, 0-10V.

    Zero Input Zero ValueSpan Input Span ValueDP 0 - 3

    INP

    UNIT C,F,K

    OPNO 1, 2

    OPTY 4 20mA, 0 20mA, 1-5V, 0-5V, 0-10VDC

    OPLO

    *Percentage of Output(O/P Lowlimit will be limited to thisconfigured 0-25 % of O/P Span)

    OPHI

    *Percentage of output(O/P Hilimit will be limited to thisconfigured 75-100 % of O/P Span)

    OPSC UPSC/DNSC

    OUT

    DIR DIR/REV

    FILT 0 - 60 SecFSET Give Default password for factory settingsPASS Change PasswordSQRT YES/NO

    CONF

    ADV

    TOUT 10-300 SEC

    AMB

    SPANINP

    ZERO

    OPNO 1, 2

    ZERO

    CAL

    OUT

    SPAN

    VER 1 UT1.1

    * Output will not be scaled but only limit to thisconfigured % of output.

    Parameter Description

    CONF Configuration Mode

    CALI Calibration Mode

    INP Input type Parameter Settings

    OUT Output type Parameter Settings

    ADV Advance Parameter Settings

    VER Software Version

    AMB Ambient

    inTY Input Type

    Zero Input Zero

    Span Input Span

    DP Decimal Point

    UNIT Engineering Units

    OPNO Output Channel No

    OPTY Output Type

    OPLO * Percentage of the O/P Zero range

    OPHI * Percentage of the O/P Span range

    OPSC Up/down Scale one sensor open

    DIR Forward/Reverse Output

    FILT Digital Filter

    FSET Factory Setting

    PASS Password

    SQRT Square root

    TOUT Time out From the Menu (10 to 300 Sec)

    OVER Input Signal Above SpanUNDR Input Signal Below Zero

    OPEN Sensor Burned

    WAIT Calibration In Process

    CERR Error in Calibration

    SERR Setting Error

    AERR ADC Error

    Ferr Factory setting Error

    Input Ranges

    Input Range Resolution

    E TC -200 to 1000 C # 0.1 C

    J TC -200 to 1200 C # 0.1 C

    K TC -200 to 1370 C # 0.1 C

    T TC -200 to 400 C 0.1 C

    B TC 450 to 1820 C 1 C

    R TC 0 to 1750 C 1 C

    S TC 0 to 1750 C 1 C

    N TC -200 to 1300 C # 0.1 C

    RTD Pt100 -200 TO 850 C 0.1 C

    -10 to 20 mV -1999 to 9999 Counts 1 Count

    0 to 100 mV -1999 to 9999 Counts 1 Count

    0 to 2 V -1999 to 9999 Counts 1 Count

    0.4 to 2 V -1999 to 9999 Counts 1 Count

    * 0 to 20 mA -1999 to 9999 Counts 1 Count

    * 4 to 20 mA -1999 to 9999 Counts 1 Count

    0 to 5 V -1999 to 9999 Counts 1 Count

    1 to 5 V -1999 to 9999 Counts 1 Count

    0 to 10 V -1999 to 9999 Counts 1 Count

    Note : # Resolution 1C After 999.9 C.

    * Connect 100R 0.1% Resistance at I/P.

  • 7/24/2019 Electrical transmitter

    3/4

    masibus UT-94

    Document Ref No. m98A/om/101 Issue No: 06

    Masibus Automation And Instrumentation (P) Ltd.B-30,GIDC Electronics Estate,

    Gandhinagar.E Mail: [email protected]

    Page 3 of 4

    Using Menu

    To enter into the menu mode, Press the ENT key. Display will show PASSand asking for password..

    Press SEL key to enter password. Display will show 0000.

    Now press SEL key to edit password. Now last digit will start blinking.

    Now edit password digit by INC (ESC). In this case pressing SEL(SHIFT) key will shift the blinking to the next digit.

    Press ENT key to give password.o If password is correct, then display will be steady instead of

    blinking. Press ENT key to enter in menu mode.

    o If password is wrong then unit will directly enter in RUN mode.

    Scroll through the menu options using the ENT Key Conf , Cal

    and Ver1.

    Select the option by pressing the SEL key.

    Scroll the sub menu options using ENT key.

    Select the particular option by pressing the SEL key.

    Use the ESC key to exit from the submenu, back to the parent menu levels.

    To change the displayed value, press the SEL key again.

    Now according to the option selected,o If its a text message the whole display blinks togethero Else if its a numeric value the first digit starts blink. In this case

    pressing SEL (SHIFT) key will shift the blinking to the next digit.

    Change the display settings using INC (ESC) key and SHIFT (SEL) key.

    Press the ENT key to save the setting.

    Press the ESC key and you will be in the parent menu option.

    Configuration Menu Input Selection

    Input Type Selection Input Zero Setting Input Span Setting

    Decimal Point Setting (Only for Linear Inputs) Engineering Unit Setting (C, F or K, only for TC

    and RTD inputs) Output Selection

    Output Channel Selection for doing Setting (1 or 2) Output Type Selection (0 20 mA, 4-20 mA, 0-5 V,

    1-5 V, 0 10 V)

    Output Low Setting (Minimum 0.0 25.0 %) Output High Setting (Maximum 75.0 - 100.0 %) Output Upscale / Downscale Setting for OPEN input Output direction Setting (Direct / Reverse)

    Advance Options Digital filtering (Range: 0 to 60.0 second) Factory Setting- To retrieve the factory setting. Password Setting Square Root (No / YES, for Linear inputs only) For Square Root, Output will be come as per

    PV =

    SQRT[ { (input reading config. IP Zero) / (config.IP Span Config. IP Zero) } * Config. OP Span ]+ Config. OP Zero

    Time Setting for Come back to RUN mode on no keyoperation (Range: 10 to 300 second)

    Calibration Menu Ambient Calibration(For TC only)

    Input Calibrationo Input Zero Calibration (For RTD only)o Input Span Calibration

    Output Calibrationo Output Channel Selection for calibrationo Output Zero Calibration

    o Output Span Calibration

    Software Version

    o Version Number of the Software

    Calibration Procedure

    Calibration for the unit is to be carried out by an experiencedengineer only. Reference used for the calibration should be ofhigh accuracy (0.1% better) and good stability.

    After Giving correct Password Press the Enter Key to enter intothe menu levels (Scroll along using the Enter Key itself. From itselect CAL using the SELECT Key).Here we have 3 optionsAmb, INP, and OUT. Scroll along using the Enter Key andselect the required option using the SELECT Key.

    Ambient Calibration:

    Once you enter the ambient calibration option the ambienttemperature sensed by the device is shown. Now to calibrate itpress the Select Key that blinks the digits one by one on eachpress, use the Increment Key to change the value from 0-9.Adjust the values as required and press the Enter Key to save

    the value.Exit from the menu levels using the Inc/Esc Key. Now wehave both Input and output calibration.

    Input Calibration:

    Here calibration is done only after entering span value(ForRTD Zero & Span value sequentially). For this we require asource with good stability and resolution.

    Any of the inputs can be calibrated at any point within theentered range. The Inputs are divided into Six groups.Calibrating any of the inputs of a group will calibrate all theother inputs of the same group.The groups are:

    Group0: ETC, JTC, KTC, TTC, NTC, and 0-100mV.

    Group1: BTC, RTC, STC, -10 - 20mV.

    Group2: RTD.

    Group3: 0-5V, 1-5V.

    Group4: 0-2V, 0.4-2V,0-20mA, 4-20mA.

    Group5: 0-10V.

    Now select the INP from the menu feed the Zero inputvalue for zero calibration (For RTD only) and enter the Zerocalibration option using the Select Key. Now change the valuesas required using the select and Inc Key. Save the value usingthe Enter Key and Exit one level back using the Inc/Esc Key.

    Scroll to the Span calibration using the Enter key, PressSelect Key to enter into the span calibration. Feed the spaninput for calibration and change the values as required andpress Enter to perform calibration, Here it show a WaitMessage until it completes the calibration Procedure. It

    automatically saves and applies the calibration parametersnow. Exit the menu level using the Inc/Esc Key. (There is noneed for repetition of calibration except RTD inputs)

    Output Calibration

    Here calibration is done only after entering both the zeroand span values sequentially for separate channels. For this werequire a DMM of 6 1/2 Digit or more resolution. No input isrequired while calibration.

    Here calibration has to be done in both current andvoltage of both channels separately. Here in the menu we firstselect the channel we are calibrating, monitor the output of thatcorresponding channel using the DMM(Digital Multi meter).Here both channels have separate voltage and currentterminals. Enter the zero option and correct the value you seeon the display with the value you see in the DMM. Do the same

    for the Span also. Now select channel 2 and monitor the output

  • 7/24/2019 Electrical transmitter

    4/4

    masibus UT-94

    Document Ref No. m98A/om/101 Issue No: 06

    Masibus Automation And Instrumentation (P) Ltd.B-30,GIDC Electronics Estate,

    Gandhinagar.E Mail: [email protected]

    Page 4 of 4

    of second channel and repeat what we did with the first channeloutput.

    Its recommended to calibrate 0-20mA for current

    and 0-10V for voltage output.

    WIRING DETAIL

    Note: 18-30 VDC is Optional Supply.

    TERMINAL POSITION DETAIL