Electrical Thumb Rules You MUST Follow (Part 4)PostedNOV 15 2013byJIGUPARMARinENERGY AND POWERwith2 COMMENTS
Electrical Thumb Rules You MUST Follow - part 4 (on photo: distribution substation bus on a clear night in February by Eli Nelson) at Flickr
Continued from:Electrical Thumb Rules You MUST Follow (Part 3)
Eight rules to follow:1. Substation Capacity and Short Circuit Current Capacity (As per GERC)2. Substation Capacity and Short Circuit Current Capacity (As per Central Electricity Authority)3. Minimum Ground Clearance and Fault Clearing Time4. Busbar Ampere Rating5. Busbar Spacing6. Sound Level of Diesel Generator (ANSI 89.2 and NEMA 51.20)7. IR Value of Transformer8. Standard Size of MCB, MCCB, ELCB, RCCB, SFU and Fuse1. Substation Capacity and Short Circuit Current CapacityAs per GERC
VoltageSub Station CapacityShort Circuit Current
400 KVUp to 1000 MVA40 KA (1 to 3 Sec)
220 KVUp to 320 MVA40 KA (1 to 3 Sec)
132 KVUp to 150 MVA32 KA (1 to 3 Sec)
66 KVUp to 80 MVA25 KA (1 to 3 Sec)
33 KV1.5 MVA to 5 MVA35 KA (Urban) (1 to 3 Sec)
11 KV150 KVA to 1.5 MVA25 KA (Rural) (1 to 3 Sec)
415 V6 KVA to 150 KVA10 KA (1 to 3 Sec)
220 VUp to 6 KVA6 KA (1 to 3 Sec)
Go back to Rules
2. Substation Capacity andShort Circuit Current CapacityAs per Central Electricity Authority
VoltageSub Station CapacityShort Circuit Current
765 KV4500 MVA31.5 KA for 1 Sec
400 KV1500 MVA31.5 KA for 1 Sec
220 KV500 MVA40 KA for 1 Sec
110/132 KV150 MVA40 KA or 50 KA for 1 Sec
66 KV75 MVA40 KA or 50 KA for 1 Sec
3. Minimum Ground Clearance and Fault Clearing TimeVoltageMin. Ground ClearanceFault Clear Time
400 KV8.8 Meter100 mille second
220 KV8.0 Meter120 mille second
132 KV6.1 Meter160 mille second
66 KV5.1 Meter300 mille second
33 KV3.7 Meter-
11 KV2.7 Meter-
4.Busbar Ampere Rating
For Phase BusbarAluminium 130 Amp / Sq.cm or 800Amp / Sq.inch.
For Phase BusbarCopper 160 Amp / Sq.cm or 1000Amp / Sq.inch
For Neutral BusbarSame as Phase Busbar up to 200 Amp than Size of Neutral Busbar is at least half of Phase Busbar.
5. Busbar SpacingBetween Phase and Earth26mm (Min)
Between Phase and Phase32mm (Min)
Busbar Support between Two Insulator250mm.
6. Sound Level of Diesel Generator (ANSI 89.2 and NEMA 51.20)KVAMax. Sound Level
66KV600M300M150M
22KV to 33KV500M250M125M
6.6KV to 11KV400M200M100M