Electrical Power Generation Notes 4

download Electrical Power Generation Notes 4

of 48

Transcript of Electrical Power Generation Notes 4

  • 7/25/2019 Electrical Power Generation Notes 4

    1/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Unit.5

    ECONOMICS ASPECTS

    Introduction. Terms commonly used in system operation. Diversity factor, load factor, plant

    capacity factor, plant use factor, plant utilization factor and loss factor, load duration curve.

    All the electrical energy generated in a power station must be consumed

    immediately as it cannot be stored. So the electrical energy generated in a power

    station must be regulated according to the demand. The demand of electrical

    energy or load will also vary with the time and a power station must be capable of

    meeting the maximum load at any time.

    TERMS COMMONLY USED IN SYSTEM OPERATION

    Firm power: Firm power is the power intended always to be available even

    under emergency conditions.

    Cold reserve: Cold reserve is the reserve generating capacity that is available

    for service but not in operation.

    Hot reserve: Hot reverse is the reserve generating capacity that is in

    operation but not in service.

    Spinning reserve: Spinning reserve is the reserve generating capacity that is

    connected to the bus and ready to take load.

  • 7/25/2019 Electrical Power Generation Notes 4

    2/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    1.

    Connected load: The sum of continues ratings of all the equipments which are

    connected to the supply system is called connected load.

    It is the sum of the continuous ratings of the load consuming

    apparatus connected to the system.

    Ex: Theconnected loads in the premises of a consumer are shown in Figure below

    The total connected load in the consumer's premises

    = 60 +500 + 40 + 60 + 500 +100 + 60 + 60 = 1380 watts.

    2. Maximum demand : Maximum demand is the greatest of all demands which

    have occurred during a given period of time.

    3. Demand factor: Demand factor is the ratio of maximum demand to the

    connected load of a consumer.

    Ex: The lighting installation has 10 bulbs each of rated 100 w and at no time of the day

    more than 7 lights are switched on. Fine demand factor for this lighting installation.

    Connected load = 10 x 100 =1000W

    Maximum demand = 7 x 100 =700W

    Demand factor = 700 /1000 = 0.70 =70%

  • 7/25/2019 Electrical Power Generation Notes 4

    3/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    4.

    Average demand or Average load: It is defined as the average of the loads

    occurring on the power station in a given period. The period may be day or

    month or year.

    5.

    Load factor:It is defined as the ratio of average load to the maximum demand

    during a given period.It is always less than 1 because average demand is less than maximum

    demand

    If the plant operates for T hours, then

    That is

  • 7/25/2019 Electrical Power Generation Notes 4

    4/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    6. Units generated in year:

    Units generated in year is given as follows

    7. Units generated in day:

    8. Diversity factor: The diversity factor is thus defined as the ratio of sum of

    individual maximum demands to the maximum demand on power station.

    Mathematically it is defined as

    The diversity factor is always greater than unity because,

    Sum of individual maximum demands > maximum demand on power station

    Units generated / annum = Average demand X hours in year

    Units generated / annum = Average demand X 8760

    Units generated / annum = Max.demand X Load factor X 8760

    Units generated / Day = Max.demand X Load factor X 24

  • 7/25/2019 Electrical Power Generation Notes 4

    5/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    9. Plant Capacity factor: This is the ratio of actual energy produced to the

    maximum possible energy that could have been produced during a given

    period.

    If the considered period as year, then

  • 7/25/2019 Electrical Power Generation Notes 4

    6/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    10.

    Utilization factor: It is defined as the ratio of maximum demand on power

    station to the installed capacity (or plant capacity) of the plant.

    For reducing the cost utilization factor must be very close to unity.

    11.

    Plant use factor: It is the ratio of energy (kWh or units) Produced to the

    product of plant capacity the number of hours for which the plant was in

    operation.

    Example: A plant having installed capacity (or plant rated capacity) of 20MW

    produces output of 7 X 106kWh and remains in operation for 2080 hours inn

    year then

    Plant use factor = = 0 .168 = 16.8%

    12.

    Loss factor: It is defined as average power loss to the peak load power loss

    during a specified period of time.

    7 X 106

    20000 X 2080

  • 7/25/2019 Electrical Power Generation Notes 4

    7/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Note:

    1.

    Where

    E ------> Energy produced

    C --------> Plant capacity

    t ---------> hours in that period that is it should be 24 or (30X24) or (8760)

    2.

    Where

    E ------> Energy produced

    C --------> Plant capacity

    t ---------> hours of operation here is not 24 or (30X24) or (8760)

  • 7/25/2019 Electrical Power Generation Notes 4

    8/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A generating station has a connected load of 40MW and a

    maximum demand of 20MW; the units generated being 60 x 106

    calculate i) demand factor ii) load factor

    Solution:

    Connected load = 40 MW

    Maximum demand = 20 MW

    Units generated = 60 x 106

    60 x 106

    8760

    6849.31 kW

    849.31kW 6849310

    20 MW 20000000

    Demand factor =0.5 =50%

    Load factor= 0.3424 = 34.24 %

    0.3424

  • 7/25/2019 Electrical Power Generation Notes 4

    9/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    The maximum demand on a thermal power station is 480 MW. If

    the annual load factor is 40%. Calculate the total energy

    generated annually.

    Solution:

    Given data: Maximum Demand = 480 MW = 480 x 103kW

    Load factor = 40% = 0.4

    Energy generated per year = Max.Demand x Load factor x 8760

    = (480 x 103

    ) x 0.4 x 8760

    = 1681920 x 103kWh

    = 1681920 MWh

    The maximum demand on a power station is 100 MW. If the

    annual load factor is 40%. Calculate the total energy generated

    per year.

    Solution:

    Given data: Maximum Demand = 100 MW = 100 x 103kW

    Load factor = 40% = 0.4

    Energy generated per year = Max. Demand x Load factor x 8760

    = (100 x 103) x 0.4 x 8760

    = 350400 x 103kWh

  • 7/25/2019 Electrical Power Generation Notes 4

    10/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A 100 MW power station deliver 100 MW for 2 hours, 50 MW for

    8 hours and it is shut down for the rest of the day. It is also shut

    down for maintenance for 60 days each year. Calculate its

    annual load factor

    Solution:

    Energy supplied for each working day = (100 x 2) + (50 x 8)

    = 600 MWh

    Max.Demand = 100 MW

    Station operation days = 36560 = 305 days

    Annual energy supplied = 600 x 305 = 183000 MWh

    Annual Average demand =

    =

    = 20.89 MW

    =

    = 0.2089

    = 20.89%

  • 7/25/2019 Electrical Power Generation Notes 4

    11/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A generating station supplies the following loads: 15000 kW,

    12000 kW, 8500 kW, 6000 kW and 450 kW. The station has a

    max demand of 22,000 kW. Calculate:

    i)Demand factor

    ii)Diversity factor

    iii)No of units supplied annually, if the load factor is 48%

    Solution:

    Load factor = 48% = 0.48

    Connected load = 15000 + 12000 + 8500 + 6000 + 450 = 41,950 kW

    Max. Demand = 22,000 kW

    22000

    41950

    15000 + 12000 + 8500 + 6000 + 450

    22000

    41950

    22000

    1.906

    No of units supplied annually = Max. Demand x load factor x 8760

    = 22000 x 0.48 x 8760

    = 92505600 kWh = 925.056 x 105kWh

    JUNE 10, 12M

    0.5244 52.44%

  • 7/25/2019 Electrical Power Generation Notes 4

    12/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A generating station supplies the following loads to various

    consumers :

    Industrial consumers = 750 MW

    Commercial establishment = 350 MW

    Domestic power =10 MW

    Domestic light = 50 MW

    If the maximum demand on station is 1000 MW and the number

    of units generated per year is 50 X 105kWh

    Determine i) diversity factor ii) annual load factor

    5 X105

    8760

    570.78MW

    = 0.57078 = 57.078%

  • 7/25/2019 Electrical Power Generation Notes 4

    13/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Power station is to supply four regions of load whose peak loads

    are 10MW, 5MW, 8MW and 7MW. The delivery factor of the

    load at the station is 1.5 and average annual (yearly) load factor

    is 0.6. Calculate maximum demand on station and annual energy

    supplied from station.

    OR

    Power station is to supply four regions of load whose peak loads

    are 10000kW, 5000kW, 8000kW and 7000kW. The diversity

    factor of the load at the station is 1.5 and average annual load

    factor is 60%. Calculate maximum demand on station and

    annual energy supplied from station.

    Solution:

    Given data: Diversity factor = 1.5

    Load factor = 60% = 0.6

    Max. demand = ?

    Annual energy supplied = ?

    Sum of individual max. demands = 10000 + 5000 + 8000 + 7000

    = 30,000 kW

    JAN 09, 05M

  • 7/25/2019 Electrical Power Generation Notes 4

    14/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    = 20,000 KW

    Annual energy supplied = max. Demand x LF x 8760

    = 20000 x 0.6 x 8760

    = 105120000 kWh

    = 105.12 x106kWh

    Maximum demand on station = 20000 kW

    Annual energy supplied = 105.12 x106kWh

    Maximum demand on

    power station

  • 7/25/2019 Electrical Power Generation Notes 4

    15/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A base load station having a capacity of 400 MW and stand by

    station having capacity of 50 MW share a common load. Find

    the annual load factor and capacity factor of two power stations

    from the following details

    i) Annual stand by station output = 87.35 x 106kWhr

    ii) Annual base load station output = 101.0 x 106kWhr

    iii) Peak load on the stand by station = 120 MW

    iv) Hours of use by stand by station/ year = 3000 hrs

    Solution:

    Stand by station:

    Given data: Annual stand by station output = 87.35 x 106kWhr

    Plant capacity = 50 MW = 50,000 kW

    Peak load= max load= 120MW = 120,000 kW

    Hours of use = 3000 hrs

    87.35 x 106

    3000

    29116.66 kW

    = 0.2426 = 24.26%

    JUNE 11, 10 M

  • 7/25/2019 Electrical Power Generation Notes 4

    16/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    0.1994 = 19.94%

    Base load station:

    Given data: Annual base load station output = 101.0 x 106kWhr

    Plant capacity = 400 MW = 400,000 kW

    Peak load= max load= 400MW = 400,000 kW

    Hours of use = 8760 hrs

    Because in base load station maximum demand equal to plant capacity

    (400MW) and it operates throughout year i.e8760 hours

    101.0 x 106

    8760

    11529.68 kW

    = 0.0288 = 2.88%

    87.35 x 106

    50000 x 8760

  • 7/25/2019 Electrical Power Generation Notes 4

    17/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    0.0288 = 2.88%

    Note :

    Use this formula to find load factor directly

    101.0 x 106

    400000 x 8760

  • 7/25/2019 Electrical Power Generation Notes 4

    18/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A generating station has a maximum demand of 400 MW. An

    annual load factor is 60% and capacity factor is 45%. Find the

    reserve capacity of the plant.

    Solution:

    Given data:. Max. Demand = 400 MW

    Load factor = 60% = 0.6

    Capacity factor = 45% = 0.45

    Units generated per year = Max.demand x LF x 8760

    = 400 x 0.6 x 8760

    = 2.10 x 106MWh

    2.10 x 106MWh

    0.45 X 8760

    533.33MW

    Reserve capacity Plant Capacity Max.Demand

    533.33400

    133.33 MW

  • 7/25/2019 Electrical Power Generation Notes 4

    19/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Alternate method:

    Max. Demand = 400 MW

    Load factor = 60% = 0.6

    Capacity factor = 45% = 0.45

    Average demand = max. Demand X Load factor

    = 400 X 0.6

    = 240 MW

    Reserve capacity Plant Capacity Max.Demand

    533.33400

    133.33 MW

  • 7/25/2019 Electrical Power Generation Notes 4

    20/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A generating station has a maximum demand of 500 MW. An

    annual load factor is 50% and capacity factor is 40%. Find the

    reserve capacity of the plant

    Solution:

    Given data:. Max. Demand = 400 MW

    Load factor = 60% = 0.6

    Capacity factor = 45% = 0.45

    Units generated per year = max.demand x LF x 8760

    = 500 x 0.5 x 8760

    = 2.19 x 106MWh

    2.19 x 106MWh

    0.4 X 8760

    625 MW

    Reserve capacity Plant Capacity Max.Demand

    625500

    125 MW

  • 7/25/2019 Electrical Power Generation Notes 4

    21/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A power plant has the following annual factors.

    Load factor = 70% Capacity factor = 50%

    Use factor = 60% Maximum demand = 20MW

    Find

    i)Annual energy production.

    ii)Reserve capacity over and above peak load.

    iii)Hours during which the plant is not in service per year

    Solution:

    Given data: Max. Demand = 20 MW

    Load factor = 70% = 0.7

    Capacity factor = 50% = 0.5

    Use factor = 60% = 0.6

    Units generated per year = Max.demand x LF x 8760= 20 x 0.7 x 8760

    = 122640 MWh

    = 122.64 X 106kWh

    122640MWh

    0.5 X 8760

    28 MW

    DEC 11, 8 M

  • 7/25/2019 Electrical Power Generation Notes 4

    22/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Reserve capacity Plant Capacity Max.Demand

    2820

    8 MW

    Hours during which the plant is not in service per year = 87607300

    = 1430 hours

  • 7/25/2019 Electrical Power Generation Notes 4

    23/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A generating station has a maximum demand of 20 MW, a load

    factor of 60%, a plant capacity factor 48%, and plant use factor

    0f 80% find

    i)Daily energy produced

    ii)Reserve capacity of the plant

    iii)The maximum energy that could have been produced daily

    if the plant were running all the time

    iv)The maximum energy that could have been produced if the

    plant (when running according to operating schedule) were

    fully loaded.

    Solution:

    Given data:. Max. Demand = 20 MW

    Load factor = 60% = 0.6

    Plant Capacity factor = 48% = 0.48

    Plant use factor = 80% = 0.8

    Daily energy produced = Max.demand x LF x 24

    = 20 x 0.6 x 24

    = 288 MWh

    Average demand = max. Demand X Load factor

    = 20 X 0.6

    = 12 MW

    JUNE 08, 12, 10 M

  • 7/25/2019 Electrical Power Generation Notes 4

    24/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Reserve capacity Plant Capacity Max.Demand

    2520

    5 MW

    The maximum energy that could have been produced daily if the plant

    were running all the time is given by

    = installed capacity X hours in day

    = 25 X 24

    = 600 MWh

    The maximum energy that could have been produced if the plant whenrunning according to operating schedule is given by

  • 7/25/2019 Electrical Power Generation Notes 4

    25/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A power supply is having the following loads

    Type of load Maximum demand

    (kW)

    Diversity factor of

    group

    Demand

    factor

    1) Residential 15,000 1.25 0.7

    2) Commercial 25,000 1.2 0.9

    3)Industrial 50,000 1.3 0.98

    If the overall system diversity factor is 1.5, determine

    i)

    Maximum demand

    ii) Connected load of each type

    Solution:

    Given data: Diversity factor= 1.5

    i)

  • 7/25/2019 Electrical Power Generation Notes 4

    26/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    ii)

    Note :

    1.To find the connected load on power station if demand factor and diversity

    factors both are given then

    2.To find the maximum demand(load) on power station if demand factor and

    diversity factors both are given then

  • 7/25/2019 Electrical Power Generation Notes 4

    27/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    At the end of the power distribution system a certain feeder

    supplies three distribution transformers. Each one supplying a

    group of customers whose connected load as shown below

    If diversity factor among the transformer is 1.3 find max demand

    on the feeder

    Solution:

    Transformer Load Demand factor Diversity factor

    Tfr 1 10 0.65 1.5

    Tfr 2 12 0.6 3.5

    Tfr 3 15 0.7 1.5

  • 7/25/2019 Electrical Power Generation Notes 4

    28/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Diversity factor among the three transformer is 1.3

    A feeder supplies three distribution transformer which feed the

    following connected loads:

    Transformer 1:

    Motor loads = 300 kW; Demand factor = 0.6

    Commercial loads = 10 kW; Demand factor = 0.5Transformer 2:

    Residential loads = 50 kW; Demand factor = 0.4

    Transformer 3:

    Residential loads = 50 kW; Demand factor = 0.5

    The diversity factors for the loads on three transformers

    may be taken as 1.8, 2.5 and 3. The diversity factors between the

    transformers may be taken as 1.1 find:

    i)Peak load on each transformer

    ii)Peak load on feederDEC 11, 8 M

  • 7/25/2019 Electrical Power Generation Notes 4

    29/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Solution:

    i)

    ii)

    Given : Diversity factor = 1.1

    Sum of individual max demands of transformer = 102.77 + 8+ 8.33

    =119.1 kW

  • 7/25/2019 Electrical Power Generation Notes 4

    30/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Find the i) Maximum demand ii) Daily load consumption

    iii) Load factor of power supply system having following loads.

    Type of load Maximum demand

    (kW)

    Load factor Diversity factor of group

    1) Residential 1000 20 1.2

    2) Commercial 2000 25 1.1

    3)Industrial 10,000 80 1.25

    What are the connected loads under each category if the

    Demand factors for residential, commercial and industrial loads

    are 80, 90 and 100% respectively?

    Solution:

    JUNE 09, 12 M

  • 7/25/2019 Electrical Power Generation Notes 4

    31/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

  • 7/25/2019 Electrical Power Generation Notes 4

    32/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

  • 7/25/2019 Electrical Power Generation Notes 4

    33/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    1.

    LOAD CURVE

    A load curve (or load graph) is a graphical representation of variation of load

    with respect to time in chronological order.

    It is a graphical record showing the power demands for every instant during

    a certain time interval.

    If the load curve plotted for 24 hours in a day it is called daily load curve.

    If the load curve plotted for hours in a month it is called monthly load curve

    If the load curve plotted for hours in a year (8760 hrs) it is called yearly load

    curve.

  • 7/25/2019 Electrical Power Generation Notes 4

    34/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Importance of load curve:

    It shows variation of load on the power station.

    Area under the load curve represents the number of units (energy)

    generated in the period considered.

    The area under the curve divided by the total number of hours gives the

    average load on the power station.

    The peak (highest point) of the load curve indicates the maximum demand

    of the power station.

    The ratio of area under load curve to the total area of rectangle in which it is

    contained gives the load factor.

    Load curves give full information about the incoming and help to decide the

    installed capacity of the power station and to decide the economical sizes of

    various generating units.

    2.

    LOAD DURATION CURVE

    Load duration curve is a rearrangement of all the load elements of the load

    curve in descending order with greatest load on left hand side and lesser load

    on right hand side.

    Load duration curve is obtained from the same data as load curve but

    ordinates are arranged in descending order.

  • 7/25/2019 Electrical Power Generation Notes 4

    35/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Importance of load curve:

    The area under the load duration curve is equal to area under the load curve

    which gives the total number of units generated in a given period.

    Load duration curve gives a clear analysis of generating power economically.

    Proper selection of base load power plants and peak load power plants

    becomes easier.

    3.

    ENERGY CURVE( INTEGRATED LOAD CURVE)

    It is a graphical representation between load in kW with respect to energy

    kWh (or units) is known as energy load curve.

    kW is taken in y- axis and kWh in x-axis.

    It gives the total number of units generated for a given max. demand or upto

    a given demand.

    If the energy (kWh) and demand are plotted as percentage quantity the load

    curve is called peak percentage load curve.

    Importance of energy load curve:

    It helps for estimating base load/peak load on a station

    This curve helps for variation between rate of water in flow in hydro power

    station & that of electrical load.

  • 7/25/2019 Electrical Power Generation Notes 4

    36/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A residential consumer has 12 lamps of 60 watts connected at

    his premises. His demand as follows

    From 12 midnight to 5 A.M - 60 watts

    5 A.M to 6 P.M - no load

    6 P.M to 7 P.M - 240 watts

    7 P.M to 9 P.M - 360 watts

    9 A.M to Midnight - 180 watts

    Plot the load curve and hence determine the maximum load,

    load factor, average load and electrical energy consumption

    during the day

    Solution:

    From the above graph

    i) Maximum demand = 360 watts

    DEC 11, 7 M

  • 7/25/2019 Electrical Power Generation Notes 4

    37/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    ii) No of units generated = (60 X 5) + (0 X13) + (240 X 1) + ( 360 X2) + (180 X 3)

    = 1800 watt-hr

    iii) Average demand

    iv) Load factor

  • 7/25/2019 Electrical Power Generation Notes 4

    38/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    The daily demands of three consumers are given below:

    Time Consumer 1 Consumer 2 Consumer 3

    12 mid night to 8 A.M No load 200 W No load

    8 A.M to 2P.M 600 W No load 200 W

    2 P.M to 4P.M 200 W 1000 W 1200 W

    4 P.M to 10P.M 800 W No load No load

    10 P.M to Mid night No load 200W 200 W

    Plot the load curve and find:

    i) Maximum demand of individual consumer

    ii)Load factor of individual consumer

    iii)Diversity factor

    iv)Load factor of the station.

    Solution:

    DEC 10, 8M

  • 7/25/2019 Electrical Power Generation Notes 4

    39/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

  • 7/25/2019 Electrical Power Generation Notes 4

    40/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A power station has to meet the following load demand:

    LOAD A 50kW Between 10 AM and 6 PM

    LOAD B 30kW Between 6 PM and 10 PM

    LOAD C 20kW Between 4 PM and 10 AM

    Plot the daily load curve and determine:

    i) Diversity factor

    ii) Units generated per day

    iii) Load factor

    Solution:

    JUNE 10, 8M

  • 7/25/2019 Electrical Power Generation Notes 4

    41/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Sum of individual max.Demand = 50 + 30 + 20

    Maximum load on power station = 70

    Units generated per day = (20 x 10) +(50 x 6) +(70 x2) +(50 x 4) +(20 x 2)

    = 880 kWh

    Diversity factor = 1.43

    Units generated per day = 880 kWh

    Load factor = 52.38%

  • 7/25/2019 Electrical Power Generation Notes 4

    42/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A power station has the following daily load cycle

    Time in hours 6 8 8 12 12- 16 16- 20 20 -24 24 -6

    Load in MW 20 40 60 20 50 20

    Plot the load curve & load duration curve, also calculate energy

    generated per day.

    Solution: Load curve

    Energy generated per day = (20 X 8) + (40 X 4) + (60 X 4) + (20 X 4) +(50 X 4)

    = 840 MWh

    = 840 X 103kWh

  • 7/25/2019 Electrical Power Generation Notes 4

    43/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Load duration curve

    Energy generated per day = (60 X 4) + (50 X 4) + (40 X 4) + (20 X 12)

    = 840 MWh

    = 840 X 103kWh

    This is same for both the curves

  • 7/25/2019 Electrical Power Generation Notes 4

    44/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    The maximum demand of a power station is 96000 kW and daily

    load curve is described as follows:

    Time (hours) 0 - 6 6 - 8 8 - 12 1214 14 - 18 18- 22 2224

    Load (MW) 48 60 52 40 84 96 48

    i) Draw load curve and load duration curve

    ii) Determine the load factor and demand factor, energy

    supplied per year

    Solution:

    Load curve

    Load duration curve

    JUNE 11, 10 M

  • 7/25/2019 Electrical Power Generation Notes 4

    45/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    Maximum demand= 96000 kW= 96 MW

    Connected load = 48+ 60+ 52+ 40+ 84+ 96+ 48 = 428 MW

    i)

    ii) From load duration curve energy supplied per day=

    (96X4) + (84X4) + (60X2) + (52X4) + (48X8)+(40X2)= 1512 MWh

    iii) Units generated per year= (units generated per day)X 365

    = 1512 X 365

    =551880 MWh

  • 7/25/2019 Electrical Power Generation Notes 4

    46/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    The yearly load duration curve can be considered as a straight

    line from 300MW to 80 MW for a certain power plant. Power is

    supplied with one generating unit of 200 MW capacity and two

    units of 100 MW capacity each. Determine:

    iv) Installed capacity ii) Load factor iii) plant factor

    iv) Maximum demand v) Utilization factor

    Solution:

    JAN 09, 10 M

  • 7/25/2019 Electrical Power Generation Notes 4

    47/48

    Vinayaka.B.G, Asst.Professor, Dept of E& E, BIET, Davanagere

    ECONOMIC ASPECTS

    A 200 MW thermal power plant is to supply power to a system

    having maximum and minimum demand of 140 MW and 40

    MW respectively during the year, assuming load duration curve

    to be straight line, determine i) installed capacity ii) load

    factor iii) capacity factor iv) utilisation factor

  • 7/25/2019 Electrical Power Generation Notes 4

    48/48

    ECONOMIC ASPECTS

    The load on the power plant on a typical day as under

    Time 12 - 5 am 5- 9 am 9 6 pm 6pm- 10pm 10pm 12 pm

    Load(MW) 20 40 80 100 20

    Draw energy load curve.

    Solution:

    First draw Load duration curve

    To draw energy load curve

    DEC 08, 8 M