PRACTICAL MANUAL Electrical Machine Lab TO PERFORM LOAD TEST ON THREE PHASE INDUCTION MOTOR AND DRAW (1) TORQUE-SPEED CHARACTERISTICS. (2) POWER-FACTOR-LINE CURRENT CHARACTERISTICS.

Transcript of Eee 551

Page 1: Eee 551

PRACTICAL MANUAL

Electrical Machine Lab

TO PERFORM LOAD TEST ON THREE PHASE INDUCTION MOTOR AND DRAW

(1) TORQUE-SPEED CHARACTERISTICS. (2) POWER-FACTOR-LINE CURRENT CHARACTERISTICS.

Page 2: Eee 551

Experiment No. – 1

Aim: -

To perform load test on a three phase induction motor and draw:(1) Torque-speed characteristics.(2) Power-factor-line current characteristics.

APPARATUS REQUIRED: - S.No Equipments Type Specification/Range/Rating Quantity

1.2.3.4.5.6.

AmmeterVoltmeterWattmeterTachometer2-phase variacStar/Delta starter

MIMIDynamometerDigitalFully variableManual Type

0-10A0-500 V 0-750W0-2000 i.e.10A,0-470V

1 No.1 No.2 No.1 No.1 No.1 No.

THEORY: -

The load test on induction motor is performed to its complete performance i.e. torque, slip, efficiency, power factor etc. During this test, the motor is operated at rated voltage and frequency and normally loaded mechanically by brake and pulley arrangement from the observed data, the performance can be calculated, following the steps given below:

TORQUE: Mechanical loading is the most common type of method employed in laboratories, the brake drum is coupled to the shaft of the motor and the load is applied by tightening the belt, provide on brake drum. The net force exerted at the brake drum in kg is obtained from the readings W1 and W2 of the spring balance i.e. Output =Torque x Speed Thus as the speed of the motor does not vary appreciably with the load torque will increase with increasing load. Net Force exerted, W= (W1-W2) kg Then Load torque, T= F x d/2 kg-m = F x d/2 x 9.8 N-mWhere d is effective diameter of brake drum in meters.

SPEED: when the induction motor is NO-LOAD speed is slightly below the synchronous speed. The current due to induced emf in the rotor winding is responsible for production of torque required at NO-LOAD. As the load is increased the rotor speed is slightly reduced. The emf induced in the rotor causes the current increases to produce higher torque, until the torque developed is equal to the torque required by the load on motor.

SLIP: The speed of the rotor, Nr drops slightly as the load on the motor is increased. The synchronous speed, Ns of the rotating magnetic field is calculated, based on the number of poles, p and the supply frequency, f i.e. Synchronous speed, Ns = 120f/p rpmThen, Slip = (Ns-Nr)/Ns x 100

Page 3: Eee 551

Normally, the range of slip at full load is from 2 to 5 %.

Output power, Po The output power in watts developed by the motor is given by,

Output power, Po = 2∏ NT/60 watts

Where, N is the speed of the motor in rpm.

Input power, Pi Input power is measured by the two watt meters, properly connected in the circuit i.e.

Input power, Pi = (P1+P2) watts

Where P1 and P2 are the readings of the two watt meters.

POWER FACTOR: Power factor of the induction motor on NO-LOAD is very low because of the high value of magnetizing current. With the increase in load the power factor increases because the power component of the current is increased. Low power factor operation is one of the disadvantages of induction motor. An induction motor draws heavy amount of magnetizing current due to presence of air gap between the stator and rotor. Thus to reduce the magnetizing current in induction motor the air-gap is kept small is possible.

Input power factor can also be calculated from the readings of two wattmeter for balanced load. If p is the power angle, then Tan Ф = √3 [P1-P2]/[P1+P2]

It may be noted clearly that the power factor of induction motor is very slow at no load, hardly 0.1 to 0.25 lagging. As such, one of the wattmeter will record a negative reading, till the power factor is less than 0.5, which may be measured by reversing the connection of either the current coil or pressure coil of the multimeter.

EFFICIENCY: % efficiency of the motor, ὴ = (output power / input power) x100%

Full load efficiency of 3 phase induction motor lies in the range of 72% (for small motors) to 82% (for very large motors).

Page 4: Eee 551

CIRCUIT DIAGRAM:

OBSERVATION- TABLE:

S.No. Line Voltage (volts)

Input current (amp)

P1

(Watt)P2

(Watt)W1

(kg)W2

(kg)Speed (rpm)

Torque (Nm)

CALCULATION: Net force exerted, W kg Then load torque, T = (W1-W2) x 9.8 N-m

RESULT:

Page 5: Eee 551

VIVA VOICE QUESTIONSQ.1 Explain the reasons for lower power factor of low speed, 3- phase induction motor as compared to that of high speed motors.Ans. Because of larger no. of poles in low speed 3-phase induction motor as compared to high speed motors, magnetizing current is more due to increase in leakages, which increases with the increase in number of poles. So the parameter of low speed induction motor is poor in comparison to that of high speed induction motor.

Q.2 Why the power factor of an induction motor is low at starting?Ans. The rotor frequency & rotor reactance are high under starting condition and therefore, rotor currents leg the rotor emf by large angle. This results in low power factor at starting.

Q.3 What are the types of induction motors? Ans. There are two types of induction motors: (a) Squirrel-cage induction motor (i) Single-cage (ii) Double cage (b) Wound-rotor induction motor

Q.4 Why do you require starters for the starting of 3 phase induction motor? Ans. The object of using starters for the starting of three phase induction motor is to limit the starting current to safe values so that voltage dip in the line voltage is not objectionable to other consumers connected to the same line.

Q.5 Name the four types of starter used for 3 phase induction motor? Ans.1 Direct online starter 2. Stator reactor starter 3. Auto transformer starter 4. Star-delta starter.

Q.6. Why the air – gap between stator core and rotor of induction is very small? Ans. The air –gap is made as small as possible so as to produce required flux with a minimum exciting current & give leakage reactance as small as possible. This results in improved power factor.

Q.7 which type of induction motor can not run at synchronous speed? Ans. Slip ring induction motor

Q.8 why an induction motor cannot run at synchronous speed? Ans. The direction of rotation of the 3- phase induction motor may be reversed by interchanging the connection to the supply of any leads of the motor.

Q.9 What is the speed of the rotor mmf of 3 phase induction motor with its stator mmf? Ans. Zero.

Q.10 How does the slip very with the load?Ans. The greater the load , the greater the slip.

Page 6: Eee 551

PRACTICAL MANUAL

Electrical Machine Lab

TO PERFORM NO LOAD AND BLOCK ROTOR TEST ON SINGLE PHASE INDUCTION MOTOR AND DETERMINE ITS EFFICIENCY

Page 7: Eee 551

Experiment No. 2

AIM: To perform no load and block rotor test on a single phase induction motor and determine its efficiency.

APPARATUS REQUIRED:

S.No. Name Type Range Quantity1 Voltmeter MI 0-300V 12 Ammeter MI 0-10 A 13 Wattmeter UPF 5/10A, 150/300/600V 14 Variac Single phase 6 A, 0-270 V 1

THEORY: Circuit diagram shows the laboratory setup of no load and block rotor test on capacitor start single phase induction motor. The motor is provided with the centrifugal switch phase on the rotor shaft and are connected in series with the starting winding. This switch is closed, when the motor at rest and thus the starting winding is in the circuit and as such the motor can be started as split phase motor. The switch gets opened and disconnect the starting winding, when the speed of the motor approaches to the approximately 75% of the rated speed. For performing NO-LOAD test, the range of voltmeter should be higher than the rated voltage of the machine i.e 300 V and the range of the ammeter should be nearly equal to the half of the full load current of the machine. For performing on Block Rotor test ,the range of voltmeter should be approximately 40% of the rated voltage of the machine i.e. 150v and the range of ammeter should be nearly equal to the full load current of the machine.

CIRCUIT DIAGRAM:

Page 8: Eee 551

PROCEDURE:1. Connect the circuit as per circuit diagram.2. Ensure that the motor is unloaded and the variac is set as zero output voltage.3. Switch on 3-phase ac mains and start the motor at reduced applied voltage. Increase the applied voltage,

till its rated value.4. Observe the direction of rotation of the motor. In case, it is reverse, change the phase sequence of the

applied voltage.5. Take the readings of all the meters and the speed under no load running.6. Increase the load on the motor gradually by turning of the hand wheels, thus tightening the belt. Record

the readings of all the meters and the speed at every setting of the load. Observation may be continued up to the full load current rating of the motor.

7. Reduce the load on the motor and finally unload it completely.8. Switch off the supply to stop the motor.9. Note down effective diameter of the brake drum.

PRECAUTION:

While loading the induction motor by brakes, check whether cooling water is circulated in the drum. Before starting the motor, loosen the strap and then tighten it gradually when the motor has picked up speed.

RESULT:

Page 9: Eee 551

VIVA VOICE QUESTIONS

Q.1 What is the effect of increasing rotor resistance in a single phase induction motor?Ans. Increase in the rotor resistance of a single phase induction motor reduces its breakdown torque, lowers the efficiency and increases the slip corresponding to the maximum torque.

Q.2 A single phase induction motor is provided with a main winding and an auxiliary winding .Which of the two winding should be more resistive?Ans. Auxiliary winding should be more resistive.

Q.3 How is the direction of rotation of a single phase induction motor reversed?Ans. The direction of rotation of a single phase induction motor is reversed by reversing the leads to the main or starting winding, but not both.

Q.4 Does the capacitor start induction motor have a high or low starting torque?Ans. The capacitor start induction motor has the high starting torque.

Q.5 In a two phase capacitor motor which capacitor is of fairly high value and to what order?Ans. In a two phase capacitor motor the starting capacitor is about 10-15 times as large as the running capacitor.

Q.6 What happens when the auxiliary winding of a capacitor motor is disconnected during running condition?Ans, The motor will continue running but will develop small torque. Once it stops , it will not start again.

Q.7 How will you resolve a single pulsating field?Ans. A single pulsating field can be resolved into two components of half it amplitude and rotating in opposite direction with equal speed.

Q.8 How is eddy current loss reduced?Ans. By making core of thin laminations.

Q.9 State the faraday’s law.Ans Faraday’s law states that an emf is induced in a coil when the magnetic flux linking the coil changes with time. It is expressed as, e = N(dФ / dt ) where e = induced emf N = No. of turns in the coil

Q.10 Why we perform no load and blocked rotor test on a single phase induction motor?Ans. In order to determine the efficiency , losses , power factor and equivalent circuit parameter.

Page 10: Eee 551

PRACTICAL MANUAL

Electrical Machine Lab

TO PERFORM THE V CURVE AND INVERTED V CURVE OF THE THREE PHASE SYNCHRONOUS MOTOR

Page 11: Eee 551

Experiment No. 3

AIM: To Perform the V curve and inverted V curve of the three phase synchronous motor.

APPARATUS REQUIRED: -

For dc generator (shunt type) for electrical loading:1 MC voltmeter 96 x 96 mm flush mounted 0-220 V2 MC ammeter 96 x 96 mm flush mounted 0-6 A3 Double pole for cut out (DPIC) 16A4 Field Rheostat 260 ohm ,1.4 A5 Lamp load of 200 Watts x106 DP switch for load lamp

For synchronous motor:1 MI voltmeter 96 x 96 mm flush mounted 0-500V2 MI ammeter 96 x 96 mm flush mounted 0-2.5A3 Power factor meter, flush mounted, 96 x 96 mm4 MCB TP5 Indicating Light6 Shunt Field Rheostat 260 ohm, 1.4 A7 DOL Starter8 Excitation Switch

For Exciter:1 MC voltmeter 96 x 96 mm flush mounted 0-200V2 MC ammeter 96 x 96mm flush mounted 0-2.5A

THEORY: -With constant mechanical load on synchronous motor, the variation of field current change the armature current drawn by motor and also its operating power factor. As such, the behavior of the synchronous motor is described below under three different modes of field excitation.

(1) NORMAL EXCITATION: The armature current is minimum at a particular value of field current, which is called the normal field excitation. The operating power factor of motor is unity at this excitation and thus the motor is equivalent to a resistive type of load.

(2) UNDER EXCITATION: When the field current is decrease gradually below the normal excitation, the armature current increase and operating power factor of motor decreases. The power factor under this condition is lagging. Thus the synchronous motor draws a lagging current, when it is under excited and equivalent to an inductive load.

(3) OVER EXCITATION: When the field current is increased gradually beyond the normal excitation, the armature current again increase and operating power factor increases. However, the power factor is leading current, when it is over excited and is equivalent to a capacitive load.

If the above variation of field current and the corresponding armature current are plotted for a constant mechanical load, a curve of shape of ‘V’ is obtained as shown in fig. such a characteristics of synchronous motor is commonly called as V curve of the motor. The characteristic curve plotted between input power

Page 12: Eee 551

factor and field current for a constant mechanical load on the motor are of shape of inverted V and are known as inverted ‘V’ curve.

For increased constant mechanical load on the motor, ‘V’ curves bodily shift upwards as shown in fig. The curve joining the minimum current points of various ‘V’ curves plotted for different mechanical loads is normally called a unity power factor compounding curve.

CIRCUIT DIAGRAM:

Page 13: Eee 551

GRAPH:

OBSERVATION TABLE:

S.NO. SYN. MOTOR EXCITATION DC GENARATOR COSФ

V(Volt) IaI (Amp) Iext (Amp) Vext (Volt) Vdc (Volt) Idc (Amp)

1

2

3

4

Page 14: Eee 551

PROCEDURE:1. Connect the MG set with starter and measuring instrument as per connection diagram.2. Switch on the ac supply to be fed to synchronous motor ac input terminal by using triple pole MCB and start the motor with DOL starter and make sure that dc generator is on NO LOAD and the dc excitation switch is off position and the rheostat in minimum position. 3. Press the green push button and the full voltage is being applied to the stator of the motor.Observe the direction of MG set to the marked position, otherwise change the phase sequence to get marked direction of rotation.4. At this point armature current Ia, line voltage VL power factor of the motor which will be lagging.5. Now switch on the dc excitation switch. Under this condition the armature current will tends to a minimum value and power factor will tends towards unity. This is the position of normal excitation. Note the readings of armature current, power factor & , excitation current.6. Now move the excitation rheostat gradually and note down the readings of the meters connected in circuits. Note carefully the value of excitation current the point at which power factor crosses from unity towards the leading power factor and now the armature current will increase with excitation current.Excitation may be increased till the rated value of current of synchronous motor till the behavior of motor is normal because at large excitation motor will try to fall out of step.7. Adjust the voltage of the dc generator coupled to the synchronous motor to rated value by varying the field current using field rheostat. 8.To stop the motor the red push button should be pressed .The excitation rheostat should be brought to minimum position, dc excitation switch in off position.9. Repeat steps no. 5 to 8 sequentially for loading the Dc generator to half load, three fourth loads and maintain it constant through out the experiment. Dc generator is loaded through lamp bank load by switching on DP switch. Thus V curves at various loading conditions can be drawn and can be verified with the theoretical V curve graph as shown in fig.10. The Load on D.C. Generator should be gradually removed.11. Step no. 9 should be repeated after the half load, and also after the three fourth loads.

PRECAUTIONS:

1. Check the power supply properly.2. Take the readings carefully.3. Don’t touch the live wire.

RESULT:

Page 15: Eee 551

VIVA VOICE QUESTIONS

Q.1 What is a synchronous condenser?Ans. A synchronous condenser is an over excited synchronous motor whose primary function is the to improve the power factor of an electrical system .It does show by delivering reactive power to the ac system. A synchronous condenser has no shaft extension, because it is not designed to deliver any mechanical load.

Q.2 Describe the operating condition at which an alternator will give negative voltage regulation?Ans. When excitation voltage EF is less than the terminal voltage VT , the alternator voltage regulation would be negative. This can happen when alternator is delivering a capacitive load.

Q3.Name any two method of starting a synchronous motor?Ans. 1. Starting of a synchronous motor by means of damper winding (Starting of a synchronous motor first as slip ring induction motor and then as synchronous motor.) 2. By use of external prime mover.

Q.4 Why will a 3 phase synchronous motor always run at synchronous speed?Ans.Stator poles and rotor poles of synchronous motor are magnetically locked. This locking is possible only if relative speed between field poles and synchronously rotating armature poles is zero.Therefore in order to maintain this magnetic locking between poles of opposite polarity, the rotor must run at synchronous speed.

Q5. What is meant by synchronizing power?Ans. Synchronizing power is the power that comes into play when rotor speed departs from synchronous speed momentarily. Depending upon whether the load angle decreases or increases suddenly to cause the rotor speed to vary from synchronous speed, synchronizing power flows in order to maintain synchronize. This power flow is transient in nature.

Q6. How the power factor of a Synchronous motor is changed keeping the Shaft load undistributed?Ans: By varying the field excitation.

Q7. Does the change in excitation affect the Synchronous motor speed and power factor?Ans: Change in excitation will affect the power factor (not the speed) of the synchronous motor.

Q8. What is meant by V-curves of Synchronous motor?Ans: The Curves drawn between armature current and field current for difference constant loads are known as V-curves.

Q9. What is meant of hunting of Synchronous motor?Ans: The oscillation of Synchronous motor rotor above its equilibrium position is called the hunting.

Q9. What is the purpose of damper winding?Ans: The purpose of damper winding is to minimize hunting and make the Synchronous motor self starting.

Page 16: Eee 551

PRACTICAL MANUAL

Electrical Machine Lab

To determine Xd and Xq of a three phase salient synchronous machine using slip test and draw the power angle curve.

Page 17: Eee 551

Experiment No.4

AIM: To determine Xd and Xq of a three phase salient synchronous machine using slip test and draw the power angle curve.

APPARATUS USED:

S.No. Name Type Range Quantity1 Ammeter MI 0-5/10A 12 Ammeter MC 0-5/10A 13 Ammeter MC 0-1/2A 14 Voltmeter MI 0-300/600V 15 Voltmeter MI 0-75/150V 16 Voltmeter MC 0-150/300V 17 3 Phase variac - 440V/8A 18 Rheostat Single tube 260 Ὠ,1.4A 2

THEORY:Direct axis synchronous reactance and quadrature axis synchronous reactance are the steady state reactances of the synchronous machine. These reactances can be measured by performing ,open circuit ,short circuit test and the slip test on a synchronous machine.

1 Direct axis synchronous reactance, Xd

The Direct axis synchronous reactances of synchronous machine in per unit is equal to the ratio of field current, I fsc at rated armature current from the short circuit test to the field current ,Ifo at rated voltage on the air gap line i.e. Direct axis synchronous reactance Xd = Ifsc /Ifo per unit Thus Direct axis synchronous reactance can be found out by performing open circuit and short circuit test on alternator. 2 Quadrature axis synchronous reactance, Xq by slip test

For the slip test the alternator should be driven at a speed, slightly less than the synchronous speed with its field circuit open .Three phase balanced reduced voltage of same frequency is applied to armature terminals of the synchronous machine .Applied voltage is to be adjusted, should at the current drawn by the stator winding is full load rated current. The wave shapes of stator current and stator voltage clearly indicated that these are changing between minimum and maximum value .When the crest of the stator mmf wave coincides with the direct axis of the rotating field, the inducted emf in the open field is zero, the voltage across the stator terminal will be maximum and the current drawn by the stator winding is minimum as shown clearly in fig. Thus approximate value of direct axis synchronous reactance, Xds is given by

Xds = Emax /Imin

When the crest of stator mmf wave coincides with the quadrature axis of the rotating field, the induced emf in the open circuit field is maximum; the voltage across the terminals will be minimum and current drawn by the stator winding in maximum as shown in fig. Hence, approximate value of quadrature axis synchronous reactance, Xqs is given by

Xqs = Emin/Imax

Page 18: Eee 551

For best result, these values are not taken as the final values .The most accurate method for determining the direct axis synchronous reactance Xd is the one, that has already been described above. The most accurate value of quadrature axis synchronous reactance Xq can now be found out using the above information i.e. Xds, Xqs and Xd .

Quadrature axis, synchronous reactance Xq =( Xqs/Xds) x Xd

= ( Emin/Imax )(Imin/ Emax) x Xd per unit

Hence the accurate value of Xq can be found out by calculating minimum and maximum values of the above quantities .Accurate result can be obtained if the oscillograms are taken during experimentation for stator current, stator voltage and injected voltage across field.It may be noted clearly that for synchronous machine Xd is greater than Xq i,e. Xd >Xq

CIRCUIT DIAGRAM:

Page 19: Eee 551

IMPORTANT PRECAUTION FOR CONDUCTING SLIP TEST:1. Slip should be extremely low during experiment. In case of high slip (more than above 5%)\ following

effects may be observed :Current induced in the damper winding of an alternator will produce an appreciable error due to induced voltage in the open circuit field may reach dangerous value.

2. It should be assure that the induced voltage in the field circuit is less than the rating of the voltmeter connected in the circuit.

OBSERVATION TABLE:

S.No. Open circuit test Short circuit test Slip testIf (A) Vo (V) Imin (A) Imax (A) Vmin (V) Vmax (V)

12345

PROCEDURE:1. Connect the circuit as per circuit diagram.2. Ensure the external resistance in the field circuit of the dc motor acting as a prime mover for alternator is

minimum and the external resistance in the field circuit of alternator is maximum’3. Switch on the dc supply to dc motor and field of the alternator \.4. Start the dc motor with the help of the starter. The starter arm should be moved slowly, till the speed of

the motor builds up and finally all the resistance steps are cut out and the starter arm is held in ON position by the magnet of no volt release.

5. Adjust the speed of the motor to rated speed of the alternator by varying the external resistance in the field circuit of the motor.

6. Record the field current and its open circuit voltage per phase.7. Increase the field current of the alternator in steps by decreasing the resistance and record the field

current and open circuit of the alternator for various values of the field current.8. Similarly perform the short circuit parameter by changing the connections of the alternator.

PRECAUTIONS:1. Check the power supply properly.2. Take the readings carefully.3. Don’t touch the live wire.

RESULT:

Page 20: Eee 551

VIVA VOICE QUESTIONS

Q.1 Name two types of alternators depending on the rotor construction?Ans. Salient pole alternator and cylindrical rotor alternator.

Q.2 What will be the number of poles of a 50 Hz alternator, if it runs at its greatest speed?Ans. Two

Q.3Why are the poles and pole shoes laminated? Ans. To reduce eddy current loss.

Q.4 What is meant by armature reaction of a synchronous machine? Ans. The effect of armature flux on main field flux is known as armature reaction. Armature reaction has

distorting effect on unity power factor, wholly demagnetizing at zero power factor lagging and wholly magnetizing at zero power factor leading

Q.5 What is the effect of armature reaction for a alternator for zero power factor lagging?Ans. Wholly demagnetizing.

Q.6.At what voltage is the field of an Alternator usually excited?Ans: 125- 250 V d.c.

Q.7. By which tests Synchronous reactance of the Synchronous machine is determined?Ans: By open circuit and short circuit test.

Q.8. Why is the short circuit characteristic of an Alternator is linear?Ans: The short circuit characteristic is normally a straight line through the origin because the net excitation is so small that there is no saturation in the magnetic circuit.

Q.9. State the use of slip test on an Alternator.Ans: The slip test is perform on an Alternator to determine Xd and Xq.

Q.10. Why an alternator with low value of SCR has lower limit stability? Ans: An Alternator with low value of SCR has high value of Xd (Xd == 1/SCR) and, therefore, has lower

stability limit because maximum power output of a machine is inversely proportional to Xd.

Page 21: Eee 551

PRACTICAL MANUAL

Electrical Machine Lab

TO STUDY SYNCHRONIZATION OF AN ALTERNATOR WITH THE INFINITE BUS BY USING:

1. DARK LAMP METHOD2. TWO BRIGHT AND ONE DARK LAMP METHOD

Page 22: Eee 551

Experiment No. 5

AIM: To study synchronization of an alternator with the infinite bus by using:

1. Dark lamp method2. Two bright and one dark lamp method

THEORY:It is an established practice these days to connect a number of synchronous generator in parallel to supply a

common load. In power station, instead of having one large capacity generator, a number of smaller units are installed and their output terminals connected in parallel. Moreover, for a number of reasons, large number stations in a country are interconnected through transmission and distribution lines. All the synchronous generator of the system, therefore, works in parallel and form a very large synchronous machine. Similarly, all the electrical loads of the consumers are connected in parallel and form a very large variable load.

A supply system with a large number of synchronous generators connected in parallel is referred to as infinite bus bar. Any additional machine, whether to work as a generator or as a motor is connected in parallel with the system. The characteristics of an infinite bus-bar system are constant terminals voltage, constant bus-bar frequency and very small synchronous impedance (since a large number of generators are in parallel). There are number of advantage of connecting alternators in parallel to such an infinite bus-bar system.

ADVANTAGE OF PARALLEL OPERATION OF SYNCHRONOUS GENERATORS:

The following are the advantage of connecting a large number of synchronous generators in parallel to supply a common load:

(a) Repair and maintenance of individual generating units can be done keeping the continuity supply by properly scheduling maintenance of generators one after the other. If only one large generator is installed, supply is to be cut off for maintenance work.

(b) For operating an alternating on maximum efficiency it is to be run near to its full load capacity. It is uneconomic to operate large alternators on low loads. If several small units are used, units can be added or put off depending upon the load requirement and thus the units can be operated at near to their capacity.

(c) Additional sets can be connected in parallel to meet the increasing demand, thereby reducing the initial capital cost of buying larger units in anticipation if increasing demands.

(d) There is physical and economics limit to the possible capacity of the alternator that can be built. The demand of the single power station may be as high as 1200 MVA. It may not be feasible to build a single alternator of such a high rating due to physical and economics considerations.

PARALLEL CONNECTION OR SYNCHRONISING OF ALTERNATOR Before a synchronous generator can be put to share the load, it should be properly connected in parallel with the common bus-bar. Interconnection of the terminals of a generator with the terminals of another or a bus-bar, to which a large number of synchronous generators are already connected, is called synchronizing.

CONDITION FOR PARALLEL CONNECTION OR SYNCHRONISATION: For satisfactory parallel connection of alternator, the following three conditions must be fulfilled:

(a) The generated voltage of the incoming alternator to be connected in parallel with a bus-bar should be equal to the bus-bar voltage.

Page 23: Eee 551

(b) Frequency of the generated voltage of the incoming alternator should be equal to the bus-bar frequency.

(c) Phase sequence of the voltage of the incoming alternator should be the same as that of the bus-bar.

Fig: ‘A’ Three lamps method of checking three phase sequence of an alternator Generated voltage of the incoming alternator can be adjusted the field excitation. Frequency of the incoming alternator can be controlled and made equal to bus-bar frequency by controlling the speed of the prime mover driving the alternator. Phase sequence of the alternator and the bus-bar can be checked by a phase sequence indicator. Alternatively, three lamps as shown in fig.A can be used for checking of phase sequence. Three lamps L1, L2 and L3 are to be connected as shown in the fig. with the synchronous generator driven at rated speed if all the lamps glow together and become dark together then the phase sequence of the incoming alternator in the same as that of the bus-bar.

Once the three conditions mentioned above are satisfied, the incoming alternator can be switched on to the bus-bar, provided the instant when the voltage of the incoming generator and the bus-bar are in expect phase is known. For this purpose the two commonly used method are described as follows.

METHOD OF SYNCHRONISATION:

Synchronisations are parallel connection of alternator can be achieved by any of the following two methods:(a) By three lamps(one dark, two bright method)(b) By using a synchroscope

SYNCHRONISING BY THREE LAMPS METHOD:In the method of synchronising an alternator, three lamps are connected as show in fig.A two lamps is

cross connected with the bus-bar. In this method the brightness of lamps will vary in sequence. Particular sequence will indicate if the incoming alternator is running two fast and two slow. Perfect synchronising will occur when lamp L1 is dark while lamps L2 and L3 are equally bright.

When the speed and voltage have been adjusted, the switch of the incoming synchronous machine can be closed only when lamp L1 is dark while lamps L2 and L3 are equally bright. if the frequency of incoming

Page 24: Eee 551

alternator is higher than the bus-bar frequency , the phasors R1-Y1-B1 representing the bus-bar voltage. At the instant when R1 is in phase with R2, lamp L1 will be dark and the other two lamps will be equally bright. After one third of the cycle, B2 will be in phase with Y2. Since the lamp L2 is connected across B2 and Y2, it will be dark. After another one third of the cycle, lamp L3 will be dark. Thus if the frequency of incoming alternator is higher, the lamps will become dark in sequence L1-L2-L3.

Similarly, if the frequency of the incoming alternator is lower, the lamps will become dark in the sequence L1-L2-L3. The speed of alternator will, therefore have to be slowly adjusted so that the lamp L1 is dark and lamps L2 and L3 are bright. At this instant, the switch can be closed. The incoming machine thus gets connected in parallel with the bus-bar.

In this three lamp method, in addition to knowing the exact instant of closing of synchronising switch, it is also known whether the incoming alternator frequency is less or more than the bus-bar frequency.

SYNCHRONISING BY USING A SYNCHOSCOPE:

A Synchronous determine the instant of synchronism more accurately than the three lamp method. A synchroscope consists of a rotor(moving coil) and a stator(fixed coil), one of which is connected to the incoming alternator and the other to the bus-bar as shown in fig. A pointer connected to the rotor will rotate if there is a difference in frequencies of the incoming alternator and bus-bar anticlockwise rotation of the rotor pointer indicate that the frequency of the incoming alternator is slower, whereas clockwise rotation of the

Page 25: Eee 551

pointer indicates that the frequency is higher than the bus-bar frequency. The speed of the prime mover driving the alternator will, therefore, have to be adjusted such that, when the frequencies are equal the pointer is stationary. The alternator can be switched on the bus-bar by closing the switch, S at this instant.

PROCEDURE: (a) Always switch ON the MCB for DC motor keeping in view that A.C. Generator is not loaded.(b) Ensure that the MCB for DC Exciter as should be in off position.(c) Ensure that the T.P.D.T. switch is in middle position.(d) Ensure that the MCBs for Synchroscope should be in OFF position.(e) Ensure that field Rheostat is connected across F.R. terminal.(f) Never leave Synchroscope and Phase Sequence Indicator permanently connected in the circuit i.e.

MCB meant for Synchroscope be should turned OFF immediately once the synchronizing procedure is over.

(g) After starting the MG set following the steps for synchronizing.1. Connection is made as per the circuit diagram shows in fig.D.2. Ensure that the synchronising switch is open, external resistance in the field circuit of the motor is

zero and external resistance in the field circuit of alternator is maximum.3. Switch on the DC supply to the DC motor -1 and DC motor-2 and start it using the starter.4. Adjust the speed of both the DC motor to rated speed of alternators, by varying the rheostat in its

field circuit of respective motors.

Switch on the DC supply to the field of alternator by switching on the MCBs and moving the Variac knob in clockwise position so that the generated voltage of both the alternators is equal. Check the phase sequence of both the alternators should be same.

Page 26: Eee 551

VIVA VOICE QUESTIONS

Q. 1 What parameter of load influences the armature reaction of an alternator?Ans. Power factor of load.

Q.2 Why are Alternator put in parallel?Ans: For high efficiency of operation, reliability, convenience and economy in maintenance and repair and possibility of addition to plant capacity with the growth in load on the power system.

Q.3. What is meant by synchronizing of an Alternator? Ans. The process of connecting an Alternator in parallel with another Alternator or with the common bus-bar is called the synchronizing. Q.4. What are the conditions for parallel operation of an Alternator?Ans: Terminal voltage, frequency and phase sequence of the incoming machine must be the same as that of the bus-bars (other alternator already operating in parallel.

Q.5.What are the two methods by which two alternators are put in parallel. Ans: Synchronizing lamp and synchroscope method.

Q.6. What is meant by infinite bus-bars?Ans: Infinite bus-bars represent a system of large capacity whose frequency and the phase and magnitude of the

voltage are not affected ever if there is a variation of excitation power of a Synchronous machine connected to it.

Q.7. At what power angle a Synchronous Generator will develop maximum power?Ans: Synchronous Generator will develop maximum power when power angle δ = internal angle, θ

Where θ= tan-1 Xs/Re

Q.8. How hunting is reduced in an Alternator?Ans: The hunting in an Alternator is reduced by employing heavy fly wheels, putting dash-pots on the engine

generator and to use squirrel-cage windings on the surface of the rotor.

Q.9. Compare the salient-pole rotor and cylindrical-pole rotor Synchronous motor on stability point of view.Ans: Salient-pole rotor machine is more stable that cylindrical-pole rotor machine.

Q.10. Name three important characteristics of a 3-phase synchronous motor not found in a 3-phase induction motor.

Ans:1. A 3-phase Synchronous motor has no inherent starting torque, whereas a 3-phase induction motor

possesses inherent starting torque.2. A 3-phase Synchronous motor always runs at constant speed, equal to synchronous speed, whereas

speed of a 3-phase induction motor varies as it is loaded.3. A 3-phase Synchronous motor can operate at lagging, unity and leading power factor, whereas a 3-phase

induction motor always operated at lagging power factor.

Page 27: Eee 551

PRACTICAL MANUAL

Electrical Machine Lab

TO DETERMINE VOLTAGE REGULATION OF 3- PHASE ALTERNATOR BY SYNCHRONOUS IMPEDANCE METHOD

Page 28: Eee 551

Experiment No. -6

AIM: To determine voltage regulation of 3- phase alternator by synchronous impedance method.

APPARATUS REQUIRED:

Sl. No. Items Type Specifications Quantity1 Voltmeter M.C. Type 0-300V ( for D.C. Motor) 12 Voltmeter M.I. Type 0-300V/500V (for A.C. Generator 13 Voltmeter M.C. Type 0-150V/300V ( for D.C. Exciter) 14 Ammeter M.C. Type 0-10A/20A ( for D.C. Motor) 15 Ammeter M.C. Type 0-1A/2A ( for D.C. Motor Field) 16 D.C. Motor Shunt Wound 5 HP,230 V, 18 A, 1500 rpm 17 Rheostat Tabular Type 260 Ω, 1.4 A 18 Potential

DividerVariable Type 1

9 Alternator Silent Pole Type 2 KVA, 415 V, 2.8 A,50 Hz, 3 phase, 1500 rpm

1

10 Tachometer Digital 0-2000 rpm 111 Connecting

WiresPVC Insulated As per

requirement

THEORY:

Short Circuit Test:

It is obtained by short circuiting the armature (stator) through a low resistance or ammeter. The excitation is adjusted to obtain 1.25 times the full load current. During this test the speed is kept constant which need not be synchronous.

Voltage Regulation: The regulation of alternator is defined as the change in output voltage from no load to full load.

% Voltage Regulation = (E0±V)/V

Where E0 is the magnitude of voltage induced at no load.

Where V is the magnitude of the voltage at full load.

Note: Use “+” sign for lagging power factor load and “-“sign for leading power factor load.

Page 29: Eee 551

PROCEDURE:

Open Circuit Test:

Make the connections as per the circuit diagram.

Set its field potential divider to zero output position.

Set the field resistance of motor to minimum value.

Switch ON the D.C. supply and start the motor with the help of the Starter.

Adjust the speed of the motor to the Synchronous speed of Alternator with the help of the field rheostat and note the meter readings.

Switch ON supply to Alternator field and increase excitation, in steps and note the corresponding meter readings. Take reading upto 10% more than the rated voltage.

Alternator

Short Circuit Test

Short the Stator

Adjust excitation to give 1.25 times the full load current

Increase the excitation to change Isc

Page 30: Eee 551

Short Circuit Test:

Make the connections as per the circuit diagram.

Switch ON the supply and start the motor with the help of the Starter. Keep its field rheostat in minimum resistance position and potential divider to zero output.

Adjust the speed of the motor to Synchronous speed with the help of field rheostat.

Switch ON the supply to Alternator field. Note the ammeter readings for different values of excitation. Take the reading upto 1.25 times of rated armature current.

Measurement of Armature Resistance:

Measure the value of Armature resistance of all the three phases separately by ammeter and voltmeter method or by ohmmeter accurately.

CIRCUIT DIAGRAM:

Page 31: Eee 551

OBSERVATION TABLE:

Synchronous speed = ______ rpm.

For open circuit test:

Sl. No. Field Current (I2) in Amp Induced voltage (V1) in volt123456

For short circuit test:

Sl. No. Field Current (I2) in Amp Armature short circuit current (I1) in amp

123456

For measurement of armature resistance:

Voltage across armature winding(V2)= _______ volt

Current through armature winding (I3)= _______ Amp

Armature resistance per phase (Ra)= = _____ = ______ ohms

GRAPH:

Plot the graph between open circuit voltage and short circuit current against field current. From this graph calculate the value of Synchronous impedance for rated value of excitation.

The nature of graph will be as shown in following figure:

Page 32: Eee 551

CALCULATIONS:

The Synchronous impedance Zs = = _____ ohms

The synchronous reactance (Xs) = = ________= ________ ohms

Calculate % Voltage regulation:

At 0.8 leading power factor:

At 0.8 lagging power factor:

At Unity power factor:

RESULT AND CONCLUSION: The regulation for the alternator is found to be:______ at 0.8 p.f leading.______ at 0.8 p.f. lagging._______ at unity p.f. load.

VIVA VOICE QUESTIONS

Page 33: Eee 551

Q.1 Name the method giving the pessimistic value of the regulation of an alternator. Ans. Synchronous impedance or emf method.

Q.2 By which tests synchronous reactance of synchronous machine is determine?Ans. By open circuit and short circuit test.

Q.3 Why is the short circuit characteristic of an alternator linear?Ans. The short circuit characteristics are normally a straight line through the origin because the net excitation is

too small that there is no saturation in the magnetic circuit.

Q.4 What is an airgap line?Ans. Tangent to OCC is called the airgap line.

Q.5 What is an exciter?Ans. An exciter is a small dc generator to supply dc power to the field magnet system or rotor of the alternator.

Q.6. What do you mean by voltage regulation?Ans: It is defined as the change in terminal voltage, expressed as a percentage (or P.u.) of the rated voltage,

when the load at a given power factor is removed, with speed & field current remaining unchanged, therefore,

Voltage Regulation= (Ef-Vt)/Vt in P.u. = (Ef-Vt)/Vt X 100 in percentage

Here, Ef is no load voltage excitation voltage and Vt is full load terminal voltage at the same speed and field excitation.

Q.7. What do you mean by the short circuit characteristics of an Alternator?Ans: The short circuit characteristics of an Alternator are a curve (usually a straight line passing through origin)

plotted between short circuit current and field current when the Alternator is being driven at its rated speed.

Q.8. What are the different methods for finding out the voltage regulation in Alternators?Ans:

1. Synchronous Impedance (or emf) method.2. Ampere- turn (or mmf) method.3. Potier- triangle (or zero power factor) method.

Q.9. What is the use of Potier-triangle?Ans: Potier-triangle is used in determination of voltage regulation of an Alternator.

Q.10. What are the losses takes place in an Alternator?Ans:

1. Electrical Losses including armature winding loss, brush contact loss and field loss.2. Core loss.3. Friction and windage loss.4. Stray power loss.

Page 34: Eee 551

PRACTICAL MANUAL

Electrical Machine Lab

TO PERFORM NO LOAD TEST AND BLOCK ROTOR TESTON A THREE PHASE INDUCTION MOTOR AND DETERMINE

PARAMETER OF EQUIVALENT CIRCUIT

Page 35: Eee 551

Experiment No. -7

AIM: To perform no load test and block rotor test on a three phase induction motor and determine parameter of equivalent circuit.

APPARATUS REQUIRED:

Sl. No. Items Type Specifications Quantity1 Ammeter MI 0-5/10 A 12 Voltmeter MI 0-300/600V 13 Wattmeter UPF 0-5/10A, 0-300/600V 24 Variac 3 phase 0-10A/ 0-400/470V 1

THEORY:

In this experiment it is intended to study the effect of variation of applied voltage on the speed, power input, power factor, stator current of an induction motor running on no-load. The effect of change of applied voltage on the above mentioned quantities are explained as follows:

Effect on Speed: Speed remains practically constant until very low voltage are reached. Unless heavily loaded, the speed of an induction motor is affected very little by fluctuations of voltage.

Effect on Stator Current: As applied voltage is increased, stator current rises gradually on account of the increase in magnetizing current required to produce the stator flux. The component of field stator current which provides field ampere-turns balancing field rotor ampere-turns will steadily diminish as the rotor current decrease with the increase in rotor speed. The increase in field magnetizing component is however, more than sufficient to balance this decrease. At normal voltage the rotor current requires only a small portion of field stator currents to balance them. The highest saturation a much stronger magnetizing current to maintain the air gap flux.

CIRCUIT DIAGRAM:

Page 36: Eee 551

EQUIVALENT CIRCUIT:

Fig:1

Fig:2

OBSERVATION TABLE:

Sl. No No Load Test Block Rotor TestV0 (Volt) I0(Amp) P0(Watt) Vsc(Volt) Isc(Amp) Psc(Watt)

1234

CALCULATIONS:

Page 37: Eee 551

PROCEDURE:

No Load Test

Connect the circuit as per the circuit diagram.

Ensure motor is unloaded and variac is set at zero.

Switch on the 3 phase a.c. supply and gradually increase the voltage through variac till its rated value. Thus the motor is running at the rated speed on the \No Load Condition.

Record the readings of all the meters connected in the circuit and tabulate observation.

Switch OFF the supply.

Block Rotor Test

Connect the circuit as per the circuit diagram.

Ensure motor is unloaded and variac is set at zero. Block the rotor either by tightening the belt or by hand.

Switch on the 3 phase a.c. supply and gradually increase the voltage through variac till its full load current value. Thus the motor is under Block Rotor Test condition.

Record the readings of all the meters connected in the circuit and tabulate observation.

Switch OFF the supply.

RESULT:

Page 38: Eee 551

VIVA VOICE QUESTIONS

Q.1. Why is the rotor rheostat starter unsuited for a cage motor? Ans. Because there is no provision for inserting resistance in the rotor circuit of a cage motor.

Q.2. What is the cheapest method of starting a 3-phase induction starter? Ans. Direct online starter.

Q.3. Why induction motors are called “a Synchronous”? Ans: Because the rotor does not turn in Synchronism with the rotating field developed by the stator currents.

Q.4. What is the condition for maximum torque at starting in a 3-phase induction motor? Ans: Torque developed in an induction motor at start will be maximum when rotor resistance equal to rotor standstill reactance i.e. R2 = X2.

Q.5. Is the maximum torque of a 3-phase induction motor depend on the rotor resistance?

Ans: No, it is independent of rotor resistance.

Q.6. Why are the iron losses in the rotor of a 3-phase induction motor normally neglected?

Ans: Because of very low frequency of emf induced in rotor.

Q.7. Why the power factor of an induction motor slow at starting? Ans: The rotor frequency and rotor reactance are high under starting condition and therefore rotor currents lag the rotor emf by a large angle. This results in low power factor at starting.

Q.8. In what ratio line current and starting torque are reduced with star-delta starting. Ans: Line current and starting torque is reduced to 1/3rd with star-delta starting.

Q.9. Give three reasons for the preference of fractional-pitch stator winding in 3-phase induction motor.

Ans:

1. To reduce the mmf harmonics produced by the stator windings.2. To reduce the amount of copper required for the stator windings.

3. To make the torque-slip characteristics a smooth curve so as to avoid the crawling.

Q.10. What is slip of an induction motor? Ans: The difference between the speed of the stator field and the actual speed of the rotor expressed as a fraction of synchronous speed is known as slip of an induction motor.

Page 39: Eee 551

PRACTICAL MANUAL

Electrical Machine Lab

To study speed control of the 3-phase induction motor By keeping V/F ratio constant.

Page 40: Eee 551

Experiment no. 8

AIM: To study speed control of the 3-phase induction motor by keeping V/F control.

APPARATUS USED:

S.No, NAME TYPE RANGE QUANTITIES1 3 -phase Induction motor Squirrel cage 5 hp/3 Phase /

415V/7.25A1

2 Autotransformer 3-ф variac 0-470 V 1

3 Voltmeter MI 0-500 V 1

4 Ammeter MI 0-10 A 1

THEORY:According to torque equation

T = 3/WS x I22 x r2 / s

Since, T α V12

SIMILARLY,

R2 = V1 / √[(r1 + r2/s)2 + (x1 + x2ʹ)2 ] I2 = I and I1 α V1

This reducing voltage has the effect of decreasing torque.There will be voltage below which the motor will not run .If the load is sufficient, the voltage cannot be reduced below a certain value of continuous running. The change in slip at no load is given by (S1

ʹ - S1)While the load is given by (S1 - S2 ) change in speed can be easily calculated .To study the same effect under load the motor has to below loaded & the loaded convenient method of loading is to have a coupled dc generator to keep the approximately constant.The dc generator voltage and current are kept constant with this constant output of a dc generator and note the speed .

CIRCUIT DIAGRAM:

Page 41: Eee 551

PROCEDURE:

1. Arrange the circuit as per circuit diagram.2. To check the 3 phase variac is in zero position. Then increases it gradually.3. Note down the reading of voltage and speed of the motor.4. Draw the graph accordingly.5. Finally switch off the power supply.

OBSERVATION TABLE:Sl.No. Voltage(Volts) Speed(rpm)

PRECAUTIONS:1. Check the power supply properly.2. Take the readings carefully.3. Don’t touch the main supply.

RESULT:

Page 42: Eee 551

VIVA VOICE QUESTIONS

Q.1. If frequency variation is used to control the speed of an induction motor , what else must be changed? Ans: The voltage applied to the stator must be varied in direct proportion to the frequency so as to maintain flux level constant?

Q.2. On what factor does the speed of an induction motor depends? Ans. The speed of an induction motor depends on supply frequency, slip and number of poles on stator.

Q.3. What measure can be taken for minimizing the effect of crawling? Ans. Effect of crawling can be minimized by chording, skewing and integral slot winding.

Q.4. Why that is the V/F ratio is kept constant while controlling the speed of a 3-phase induction motor by varying the supply frequency? Ans: In order to maintain flux level constant.

Q.5. What is the relationship of developed torque of a 3-phase induction motor with the supply voltage? Ans: Torque α s V2

Where s= slip

And V = supply voltage.

Q.6. When the applied rated voltage per phase is reduced to one-half, what will be the starting torque of a squirrel-cage induction motor in terms of its starting torque with full voltage? Ans: One-fourth of starting torque with full rated voltage.

Q.7. What are the losses in a 3-phase induction motor?Ans: Stator copper loss, Stator iron loss, Rotor copper loss, friction and windage losses and stray load loss.

Q.8. How many terminals does u expect to find on the terminal box of a squirrel cage induction motor to be started by star-delta starter?

Ans: 6

Q.9. What is the condition for producing maximum torque in a 3-phase induction motor?

Page 43: Eee 551

Ans: for producing maximum torque in an induction motor, the condition is R2=smax X2.

Q.10. While controlling induction motor speed, how super Synchronous speed is achieved?Ans: It can be achieved by injecting a slip frequency voltage in phase with emf induced in the rotor.

\

PRACTICAL MANUAL

Electrical Machine Lab

To study speed control of the 3-phase induction motor By varying supply voltage.

Page 44: Eee 551

Experiment no. 8

AIM: To study speed control of the 3-phase induction motor by varying supply voltage.

APPARATUS USED:

S.No, NAME TYPE RANGE QUANTITIES1 3 -phase Induction motor Squirrel cage 5 hp/3 Phase /

415V/7.25A1

2 Autotransformer 3-ф variac 0-470 V 1

3 Voltmeter MI 0-500 V 1

4 Ammeter MI 0-10 A 1

THEORY:According to torque equation

T = 3/WS x I22 x r2 / s

Since, T α V12

SIMILARLY,

R2 = V1 / √[(r1 + r2/s)2 + (x1 + x2ʹ)2 ] I2 = I and I1 α V1

This reducing voltage has the effect of decreasing torque.There will be voltage below which the motor will not run .If the load is sufficient, the voltage cannot be reduced below a certain value of continuous running. The change in slip at no load is given by (S1

’ - S1)While the load is given by (S1 - S2 ) change in speed can be easily calculated .To study the same effect under load the motor has to below load & the loaded convenient method of loading is to have a coupled dc generator to keep the approximately constant. The dc generator voltage and current are kept constant with this constant output of a dc generator and note the speed.

CIRCUIT DIAGRAM:

Page 45: Eee 551

PROCEDURE:1) Arrange the circuit as per circuit diagram.2) To check the 3 phase variac is in zero position. Then increases it gradually.3) Note down the reading of voltage and speed of the motor.4) Draw the graph accordingly.5) Finally switch off the power supply.

OBSERVATION TABLE:

Sl.No. Voltage(Volts) Speed(rpm)

GRAPH:

PRECAUTIONS:1. Check the power supply properly.2. Take the readings carefully.3. Don’t touch the main supply.

RESULT:

Page 46: Eee 551

VIVA VOICE QUESTIONS

Q.1. What type of protection is provided in the starter meant for 3-phase induction motor? Ans: Over load and under voltage protection.

Q.2. What is the serious objection to the practice of employing reduced voltage for the starting of a squirrel-cage induction motor? Ans. Large reduction in starting torque because the starting torque varies as the square of voltage applied to the stator.

Q.3. If frequency variation is used to control the speed of an induction motor, what else must be changed? Ans. The voltage applied to the stator must varied indirectly proportional to the frequency so as to maintain flux level constant.

Q.4. What will be the effect on the torque developed by an Induction motor when the applied voltage is reduced to half, supply frequency unchanged?

Ans: Torque developed by an Induction motor with half rated voltage, supply frequency remaining unchanged, will be reduced to 1/4th because T α V2 (i.e. square of the supply voltage).

Q.5. Why the rotor of a slip- ring Induction motor should be wound for the same number of poles as its stator? Ans: Because the slip-ring Induction motor having the same number of poles on the rotor as that of the stator will be in a position to run at slip speed.

Q.6. Why an Induction motor can not run at Synchronous speed?Ans: Because at Synchronous speed the Induction motor can not developed any torque to move the rotor from

its stationary position. Q.7. A 3-phase, 50 Hz induction motor runs at 960 rpm on NO load and 940 rpm at Full. Find Full load slip?Ans: 6%

Q.8. What is the speed of stator mmf of 3-phase Induction motor with respect to its rotor mmf?Ans: 0

Q.9. Speed of a 3-phase Induction motor is varied by varying the supply frequency while (V/F) is kept constant. How will be maximum torque vary?

Page 47: Eee 551

Ans: The magnitude of maximum torque does not change but the speed at which it occurs changes in the same ratio as the supply frequency.

Q.10. Why NO load current of an Induction motor is much higher than that of an equivalent transformer?Ans: Owing to the air-gap in an Induction motor the magnetizing current is large for the Induction motor as compare to that for a transformer. The frequency and windage losses are also present in the Induction motor. So NO load current of an Induction motor is much higher than that of an equivalent transformer.