ECP 11-0512i Schneider RN6c with MICOM P116...
Transcript of ECP 11-0512i Schneider RN6c with MICOM P116...
![Page 1: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/1.jpg)
THIS
IS A
N U
NC
ON
TRO
LLED
DO
CU
MEN
T, T
HE
REA
DER
MU
ST C
ON
FIR
M IT
S VA
LID
ITY
BEF
OR
E U
SE
Document Number: ECP 11-0512i
Version: 1.0
Date: 20/03/2017
SCHNEIDER RN6C WITH MICOM P116 RELAY TEST FORM
Substation Name
Substation Number
Voltage
Switchgear
Installed Mode Free-standing () Transformer-mounted ()
Switchboard Number Manufacturer Schneider
Serial Number Type RN6c
Protection CTs
CT Ratio (400/1 or 800/1)
Relay
Serial Number Setting Range (x2 or x4)
Shunt Trip Coil (if fitted)
20-48V DC () 110-240V AC/DC ()
Protection Settings (specified by planner/designer)
Overcurrent Settings Earth Fault Settings
Setting Current Setting Current
Curve Curve
Time Multiplier Time Multiplier
Highset Setting Current Highset (or SEF) Setting Current
Highset Time Highset (or SEF) Time
Preliminary Checks ()
Disconnect the umbilical cable from the RTU (if fitted)
Visual inspection satisfactory (no visible signs of damage etc)
Earthing satisfactory
SF6 gas pressure satisfactory
Functional/Interlock Checks ()
Open and close switches
Earth switches cannot be operated when service selected
Switch/circuit-breaker cannot be operated when earth selected
Open and close earth switches
Test access cannot be opened when switch/circuit-breaker in On and Off position
Test access can be opened when earth switch closed
Switch/circuit-breaker cannot be operated when test access open
![Page 2: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/2.jpg)
THIS
IS A
N U
NC
ON
TRO
LLED
DO
CU
MEN
T, T
HE
REA
DER
MU
ST C
ON
FIR
M IT
S VA
LID
ITY
BEF
OR
E U
SE
Document Number: ECP 11-0512i
Version: 1.0
Date: 20/03/2017
Functional/Interlock Checks ()
Transformer Winding Insulation Resistance using Test Voltage from ECS 11-0006 (transformer-mounted units only)
HV windings to earth (LV windings connected together and to earth) M
LV windings to earth (HV windings connected together and to earth) M
Switchgear Continuity Test
RSW1 RSW2 CB Terminals Under Test Continuity
TM* FS* TM* FS*
RSW1 to RSW2 RSW1 to RSW2 to CB
Closed Closed Open Closed L1 - L1 L1 - L1 - L1
Closed Closed Open Closed L2 - L2 L2 - L2 - L2
Closed Closed Open Closed L3 - L3 L3 - L3 - L3
Closed Open Closed L1 - L2 (RSW1)
Closed Open Closed L2 - L3 (RSW1)
RSW1 RSW2 CB Terminals Under Test Continuity
Earthed Open Open RSW1 L1 - E
L2 - E
L3 - E
Open Earthed Open RSW2 L1 - E
L2 - E
L3 - E
HV Insulation Tests using Test Voltage from ECS 11-0006
RSW1 RSW2 CB Terminal Voltage (kV)
Duration (min)
IR (M)
Under Test
Earthed
TM* FS* RSW1 RSW2 CB(FS* only)
Closed Closed Open Closed L1 L2, L3
Closed Closed Open Closed L2 L1, L3
Closed Closed Open Closed L3 L1, L2
Open Closed Open Closed L1, L2, L3
L1, L2, L3
L1, L2, L3
Closed Open Open Open L1, L2, L3
L1, L2, L3
* TM - transformer-mounted and FS - free-standing.
![Page 3: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/3.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
FPI CTs Insulation Resistance using 1kV Test Voltage (test from rail C terminal block – Figure 1 and Figure 2)
Disconnect FPI or RTU (if fitted) ()
Switch Phase Wire
RSW1
Remove CT earth link D190L – D170L ()
L1 D111L - Earth M
L2 D131L - Earth M
L3 D151L - Earth M
Replace CT earth link D190L – D170L ()
RSW2
Remove CT earth link D190R – D170R ()
L1 D111R - Earth M
L2 D131R - Earth M
L3 D151R - Earth M
Replace CT earth link D190R – D170R ()
FPI CTs Loop Continuity (test from rail C terminal block – Figure 1 and Figure 2)
Switch Phase Wire
RSW1
L1 D111L – D170L
L2 D131L – D170L
L3 D151L – D170L
RSW2
L1 D111R – D170R
L2 D131R – D170R
L3 D151R – D170R
Ensure all physical shorting links are open/removed (D111, D131, D151, D171) ()
Reconnect FPI or RTU (if fitted) ()
© UK Power Networks 2017 All rights reserved 3 of 12
![Page 4: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/4.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
Figure 1 – RSW1 FPI CTs Figure 2 – RSW2 FPI CTs
© UK Power Networks 2017 All rights reserved 4 of 12
![Page 5: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/5.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
Protection CTs Insulation Resistance using 1kV Test Voltage(test from rail C terminal block – Figure 3)
Remove CT wiring links C12, C32, C52, C71
()
Remove CT wiring earth link C70, C90 ()
Ensure yellow physical shorting link is open ()
Measure the insulation resistance C70 - Earth M
Replace CT wiring earth link C70 - C90 ()
Protection CTs Loop Continuity(test from rail C terminal block – Figure 3)
Measure L1 CT continuity C11 - C70
Measure L3 CT continuity C31 - C70
Measure L3 CT continuity C51 - C70
Replace CT wiring links C12, C32, C52, C71 ()
Figure 3 – Protection CTs
© UK Power Networks 2017 All rights reserved 5 of 12
![Page 6: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/6.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
Dual Ratio Protection CTs
For switchgear with dual ratio protection CTs select the appropriate ratio to give the required protection settings and record CT ratio on the front of the form
()
CT Ratio Terminal Block Connections
400/1C210 - 5C230 - 6C250 - 7
()
800/1C110 - 1C130 - 2C150 - 3
()
Using The Protection Relay as an FPI Function.
When the RMU T-Off is used to supply another RMU as part of an interconnected network, the protection relay can be configured to be used as an FPI (Fault Path Indicator).
Follow the procedure below to remove the trip output function from the relay to the circuit breaker on the RMU.
Starting at the home screen on the protection relay, follow the steps below to disable the tripping output to the circuit breaker. The Schneider Electric RMU protection relay will come from the Schneider Electric factory with the protection relay already enabled for CB tripping and protection alarm operated.
Figure 4: P116 Relay Home Screen
© UK Power Networks 2017 All rights reserved 6 of 12
![Page 7: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/7.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
From main menu:
Setting Group 1 I>?OK Setting Mode OK Change setting to 2: Alarm (using up/down buttons)
Phase O/C G1 E/GND Fault G1 IN_1 stageOK Setting Mode OK Change setting to 2: IN> Alarm (using up/down buttons)
Press C button four times to return to go back to main screen
© UK Power Networks 2017 All rights reserved 7 of 12
![Page 8: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/8.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
Test Protection Settings
Apply the following temporary settings to the relay (refer to Appendix A for guidance) ()
Overcurrent Settings Earth Fault Settings
I> 80A400/1 0.2 In
Ie> 60A400/1 0.15 Ien
800/1 0.1 In 800/1 0.075 Ien
Delay Type DMT Delay Type DMT
IDMT IEC SI IDMT IEC SI
TMS 1.5 TMS 1.5
I>> 4.0 x In Ie>> 2.0 x Ien
I>>> No Ie>>> No
Relay Operation - Primary Injection Test
Increase current until the LED starts to flash and record the current value. Reset the relay and, if necessary, close the circuit breaker before each test
Overcurrent Pickup Test
RSW1 RSW2 CB Conductors Under Test
Short Conductors
I> Setting
Calculated Pickup Current (Is + 20%)
Actual Pickup Current
RSW1 CB
Closed Open Closed L1 - L2 L1, L2, L3 80A 96A A
Closed Open Closed L2 - L3 L1, L2, L3 80A 96A A
Earth Fault Pickup Test
RSW1 RSW2 CB Conductors Under Test Ie>
Setting
Calculated Pickup Current (Ios + 20%)
Actual Pickup Current
RSW1 CB
Closed Open Closed L1 L1 60A 72A A
Closed Open Closed L2 L2 60A 72A A
Closed Open Closed L3 L3 60A 72A A
© UK Power Networks 2017 All rights reserved 8 of 12
![Page 9: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/9.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
In-service Protection Settings
Apply the in-service protection settings as specified by the planner/designer to the relay and record them below (refer to Appendix A for guidance) ()
Overcurrent Settings Earth Fault Settings
Is Ios
I> curve Io> curve
DT only DT only
t> Select from table on relay
to> Select from table on relayx10 / x1 x10 / x1
I>> (Highset Current ÷Is) Io>> (Highset Current ÷Is)
t>> to>>
Table A - Calculate Injection Currents Overcurrent Setting Earth Fault Setting
CT Ratio
Primary Setting Current (Is) (Ios)
Secondary Setting Current (Primary Setting Current ÷ CT Ratio)
2 x Secondary Setting Current
5 x Secondary Setting Current
I>> or Io>> x Secondary Setting Current (highset)*
DT x Secondary Setting Current (SEF)*
Table B - Calculate Operating Times Overcurrent Setting Earth Fault Setting
Curve (I>) (Io>)
Time Setting on relay
(if x10 is selected multiply t> or to> setting by 10)
(t>) (to>)
(t>>) (to>>)
Tripping time at 2 x secondary current
Curve SI (t> or to> x 3.38) +0.09s s s
Curve VI (t> or to> x 9) + 0.09s s s
Curve EI (t> or to> x 33) + 0.09s s s
Tripping time at 5 x secondary current
Curve SI (t> or to> x 1.44) + 0.09s s s
Curve VI (t> or to> x 2.25) + 0.09s s s
Curve EI (t> or to> x 4.1) + 0.09s s s
Tripping time at I>> or Io>> or DT x Secondary Setting Current
Highset/Instantaneous t>> or to>> + 0.09s s s
SEF* to> + 0.09s s
* Only calculate highset, instantaneous or SEF settings if used.
© UK Power Networks 2017 All rights reserved 9 of 12
![Page 10: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/10.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
Relay Operation - Secondary Injection Test
Connect timer circuit to auxiliary contacts 124 and 125 on rail A in marshalling box ()
Overcurrent Test
SettingCalculated Injection Current(from table A)
Calculated Operating Time (from table B)
Actual Operating Times
C11 - C31 C31 - C51 C51 - C11
2x A s s s s
5x A s s s s
Instantaneous A s s s s
Earth Fault Test
SettingCalculated Injection Current(from table A)
Calculated Operating Time (from table B)
Actual Operating Times
C11 - C70 C31 - C70 C51 - C70
2x A s s s s
5x A s s s s
Instantaneous A s s s s
SEF* A s s s s
Figure 5: Relay Timing Test Terminals
© UK Power Networks 2017 All rights reserved 10 of 12
![Page 11: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/11.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
Shunt Trip and Emergency Trip (if fitted)
Check correct shunt trip coil voltage is selected ()
Test Coil Terminals Test Voltage CB Trips
Apply 70% (dc) or 85% (ac) of coil rated voltage
20-48V DC 17 – 20 V ()
110-240V AC/DC 17 – 18 V ()
Apply 110% Voltage of coil rated voltage
20-48V DC 17 – 20 V ()
110-240V AC/DC 17 – 18 V ()
Check emergency trip button operates circuit-breaker ()
Final Checks ()
Check correct CT and interposing CT ratios selected
Check correct ratio labels have been fitted
Check correct protection settings applied
Check relay reset
Ensure FPI CT shorting-link(s) are replaced if CTs are not used or not connected to FPI or RTU
Reconnect umbilical cable to RTU (if fitted)
Asset data form completed
Test Equipment
Make/Type Serial Number Calibration Date
Certification ()
All tests have been completed satisfactorily
Comments
© UK Power Networks 2017 All rights reserved 11 of 12
![Page 12: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/12.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
Commissioning Engineer Signature Date
The completed test form shall be left on-site in a plastic wallet and in secure location. A copy of the completed test shall be sent to the relevant ART mailbox.
© UK Power Networks 2017 All rights reserved 12 of 12
![Page 13: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/13.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
Appendix A – MICOM P116
A.1 Introduction
The MiCOM P116 is a three-phase overcurrent and earth fault relay which has been designed to control, protect and monitor industrial and distribution installations. The relay can be self-powered powered from the CTs or an auxiliary voltage supply. The relay includes a built-in USB port which provides access to disturbance records, fault records, events and relay settings. Settings for the protection elements can be entered using the front panel keyboard and local display or using the MiCOM S1 or S1 Studio setting software.
A.2 Front Panel
1 – Green ‘Healthy’ LED – Watchdog
2 – Red ‘Trip’ LED - Protection Trip
3 – Yellow ‘Alarm’ LED
4 – Five red programmable LEDs
5 – 16 character by 2-lin3 alphanumeric LCD
6 – Clear key
7 – Read key (jump to RECORDS column)
8 – Arrow keys and enter key
9 – Electromechanical flag indicators
10 – Circuit-breaker Close
11 – Circuit-breaker Open
12 – USB port for local connection
A.3 Relay Front Panel Navigation
An overview of the relay front panel is shown in Section A.2. The arrow buttons can be used to move left, right, up, down respectively to navigate from one menu to the another in turn to access information such as protection settings, fault records, etc. The OK button is used as an enter key.
The main menu structures are shown Section A.5 and should be self-explanatory when used in conjunction with the arrow buttons. When the P116 relay is energised the screen display will show the three-phase and neutral current values on the LCD display screen, which is the starting point for navigating to the various sub menus within the relay.
© UK Power Networks 2017 All rights reserved 1
![Page 14: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/14.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
A.4 Programming
The keypad has seven keys divided into two groups:
The and keys situated immediately under the screen are dedicated to reading and acknowledging alarms.
The other five keys situated below these are used for programming the relay and navigating the menu system (a map of the menu system is shown in section A.5). The
directional keys either move through the various levels of the menu or are
used to change settings. The key validates a choice or applied value. The general
menu navigation is left and right to scroll through the main menu headings. Pressing down will enter the menu selected and allow you to scroll through the various options.
For example, applying the following typical settings to a MiCOM P116 relay used with 400/1 CTs:
Test Protection SettingsApply the following temporary settings to the relay (refer to Appendix A for guidance)
()
Overcurrent Settings Earth Fault Settings
I> 80A400/1 0.2
In Ie> 60A400/1 0.15 Ien
800/1 0.1 In 800/1 0.075
IenDelay Type DMT Delay Type DMTIDMT IEC SI IDMT IEC SITMS 1.5 TMS 1.5I>> 4.0 x In Ie>> 2.0 x IenI>>> No Ie>>> No
Note: Various settings, such as the selection of the various thresholds, time delays, trip settings etc are password protected and when accessing these menus a password entry is required. By default this is set to OOOO and will already be entered when the password
prompt appears on the LCD. To proceed past this screen press the key.
First enter the CT ratio (400/1A) into the relay:
Global Settings LOC CT Ratio Line CT primaryOK Setting Mode OK Change setting to 400A (using up/down & left/right buttons) OK OK
Moves to ‘E/Gnd CT Primary’ change setting to 400AChange setting to 400A (using up/down & left/right buttons)
© UK Power Networks 2017 All rights reserved 2
![Page 15: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/15.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
Next apply the relay settings:
Overcurrent: Global Settings Setting Group 1
Protection G1Phase O/C G1 [50/51]
I>OK Change setting to 1: Trip OK
Use up or down arrows to change settingI> Threshold
OK Change setting to 0.2In OK
Use left or right buttons to move to required positionUse up or down buttons to change settingDelay Type I>
OK OK Change setting to 1: IEC SI (using up or down buttons) I> TMSOK OK Change setting to 1.5 (using up/down & left/right buttons) I>>OK OK Change setting to 1: Trip (using up/down buttons) I>> ThresholdOK OK Change setting to 4.0In (using up/down & left/right buttons) Delay Type I>>OK OK Change setting to 0: DMT (using up/down buttons) tI>>OK OKOK OK
Change setting to 3s (using up/down & left/right buttons)I>>> set to 0:disabled (using up/down buttons)set to 0:disabled (using up/down buttons)
Earth Fault:Return to Phase O/C G1 [50/51] (press 13 times) E/GND FAULT G1 [50N/51N/67N] IN_1 stageOK OK Change setting to 1: IN> Trip (using up/down buttons) IN_1 ThresholdOK OK Change setting to 0.15 Ien (using up/down & left/right
buttons) Delay Type IN_1OK OK Change setting to 1: IEC SI (using up/down buttons) IN_1 TMSOK OK Change setting to 1.5 (using up/down & left/right buttons) IN_2 stageOK OK Change setting to 1: IN>> Trip (using up/down buttons) IN_2 ThresholdOK OK Change setting to 2.0 Ien (using up/down & left/right
buttons) tIN_2OK OK Change setting to 3s (using up/down & left/right buttons)
Output Relays:Return to PROTECTION G1(press 10 times) OUTPUT RELAYS configuration G1 Protect TF654321
© UK Power Networks 2017 All rights reserved 3
![Page 16: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/16.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
OK Change setting to configure output relays required for tripping
TF65432110000011 (using up/down & left/right buttons) to change
each digit position to a 1 or 0, press once complete.
Press button three times to go back to main screen.
If further earth fault settings are required they should be implemented using the IN_3 menu. If not required, ensure this is not enabled by setting them to 0:Disabled. From main screen press right button () 3 times, down button () 2 times, right button () 2
times, press down button () 10 times, press use up/down buttons to change to
0:Disabled, press once complete. Press button four times to go back to main screen.
Main Screen
© UK Power Networks 2017 All rights reserved 4
![Page 17: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/17.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
A.5 P116 Menu Structure Diagrams
For ease of reference the following menu structures go from the main LCD display through to the setting group 1 menu where the protection settings are stored. All other menu structures are detailed in the P116 relay manual (available from Alfresco > Reference Library > Schneider).
© UK Power Networks 2017 All rights reserved 5
Start here
![Page 18: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/18.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
© UK Power Networks 2017 All rights reserved 6
![Page 19: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/19.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 10/04/2017
This page is left intentionally blank.
© UK Power Networks 2017 All rights reserved 7
![Page 20: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/20.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 20/03/2017
Appendix B – Schematic Diagrams
© UK Power Networks 2017 All rights reserved 1
![Page 21: ECP 11-0512i Schneider RN6c with MICOM P116 …library.ukpowernetworks.co.uk/library/asset/a2800354-f62... · Web viewSchneider RN6c with MICOM P116 Relay Test Form Document Number:](https://reader030.fdocuments.in/reader030/viewer/2022040210/5e512cc4638b9433775b9ee1/html5/thumbnails/21.jpg)
Schneider RN6c with MICOM P116 Relay Test Form Document Number: ECP 11-0512i
Version: 1.0
Date: 20/03/2017
© UK Power Networks 2017 All rights reserved 2