PART I. GENERAL PROVISIONS DIVISION 16 - ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS LEGEND ELECTRICAL SYMBOLS DATA OUTLET, HEIGHT AS NOTED ON PLANS WITH 3/4 " EMPTY CONDUIT TO ABOVE CEILING. PROVIDE PULL WIRE. 1. SCOPE: PROVIDE ALL LABOR, MATERIAL, AND EQUIPMENT IN ACCORDANCE WITH THESE SPECIFICATIONS, AND THE ACCOMPANYING DRAWINGS TO PROVIDE A COMPLETE AND PROPERLY OPERATING ELECTRICAL SYSTEM FOR THE BUILDING. A. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL OF THE FOLLOWING MATERIAL AND EQUIPMENT UNDER THIS DIVISION OF THE SPECIFICATIONS, UNLESS NOTED OTHERWISE: PANELBOARDS; LIGHTING FIXTURES; LAMPS; RACEWAYS; 600 VOLT WIRE AND CABLE; WIRING DEVICES; DEVICE PLATES; DEVICE, PULL, AND JUNCTION BOXES; SAFETY SWITCHES; MOTOR STARTERS; LIGHTING CONTROLS; CIRCUIT BREAKERS; FUSES; TIME CLOCKS; EQUIPMENT IDENTIFICATION (NAMEPLATES AND DIRECTORIES); WIRE AND CABLE TERMINATIONS; CONNECTIONS TO INDIVIDUAL UNITS OF EQUIPMENT FOR THE WALK-IN FREEZERS AND COOLERS; AND TEMPORARY POWER. B. THE FOLLOWING MATERIAL AND EQUIPMENT WILL BE FURNISHED AND/OR INSTALLED BY OTHERS, OR UNDER OTHER DIVISIONS OF THE SPECIFICATIONS, UNLESS NOTED OTHERWISE: LOW VOLTAGE (24 VOLT) WIRE AND CABLE, COMMUNICATION DEVICES, SECURITY EQUIPMENT, POINT OF SALE (POS) EQUIPMENT, SIGNAGE, CONCRETE BASES FOR SITE LIGHTING POLES. C. THE FOLLOWING MATERIAL AND EQUIPMENT WILL BE FURNISHED BY OTHERS, OR UNDER OTHER DIVISIONS OF THE SPECIFICATIONS, AND INSTALLED BY THE CONTRACTOR, UNLESS NOTED OTHERWISE: SITE LIGHTING FIXTURES AND POLES. 2. GENERAL REQUIREMENTS: ALL WORK SHALL BE PERFORMED BY SKILLED LICENSED ELECTRICIANS IN ACCORDANCE WITH THE BEST PRACTICES OF THE TRADE, MEETING THE REQUIREMENTS OF THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, APPLICABLE FEDERAL, STATE AND LOCAL CODES, AND THE REQUIREMENTS OF THE ELECTRICAL UTILITY COMPANY FURNISHING THE SERVICES. ALL NECESSARY CONSTRUCTION PERMITS AND CERTIFICATES OF INSPECTION SHALL BE PURCHASED AND OBTAINED UNDER THIS CONTRACT. A. COORDINATION: ALL OUTLETS MUST BE ACCURATELY LOCATED, PARTICULARLY APPLIANCE OUTLETS WHICH SHALL BE LOCATED FROM THE DIMENSIONS GIVEN ON THE DRAWING AND FIELD VERIFIED. REVIEW THE ARCHITECTURAL, PLUMBING AND HEATING AND VENTILATING PLANS IN ORDER TO COORDINATE THIS WORK WITH OTHER TRADES, AND COOPERATE WITH THEM IN THE ENTIRE INSTALLATION. 3. SERVICE VOLTAGE: THESE DRAWINGS ARE FOR A METERED, UNDERGROUND BUILDING SERVICE OF 120/208 VOLT, THREE PHASE, FOUR WIRE, 60 HERTZ. ALL KITCHEN AND AIR CONDITIONING EQUIPMENT HAS BEEN DESIGNED AND PURCHASED FOR USE ON THIS ELECTRICAL SYSTEM. THE CONTRACTOR SHALL CONTACT THE ELECTRICAL UTILITY AND VERIFY ALL OF THE ABOVE SERVICE CHARACTERISTICS, AND THE AVAILABLE FAULT CURRENT. 4. SERVICE EQUIPMENT: THE SERVICE SHALL BE LOCATED AS SHOWN ON THE SITE PLAN, OR AS INDICATED IN THE INSTRUCTIONS TO BIDDERS. UTILITY POLES, PADS FOR UTILITY TRANSFORMERS, CURRENT TRANSFORMER ENCLOSURES, METERING EQUIPMENT, SERVICE MASTS, AND OTHER RELATED MATERIALS AND EQUIPMENT SHALL BE APPROVED, FURNISHED, AND INSTALLED AS REQUIRED. INCLUDE THE COST OF ALL THE ABOVE ITEMS, SERVICE CONNECTIONS, AND METER CHARGES IN THE BASE BID. MAIN SERVICE SWITCHES AND CURRENT TRANSFORMER CABINETS SHALL BE INCLUDED IN THE BASE BID. UNLESS NOTED OTHERWISE, A MAIN SERVICE SWITCH WITH CURRENT LIMITING FUSES MAY BE USED WHEN THE AVAILABLE FAULT CURRENT (AFC) IS EXCESSIVE, IN ORDER TO USE STOCK PANELBOARDS, WITH 10K OR 22K AIC RATINGS. PART II. MATERIALS 1. MATERIALS: ALL MATERIALS SHALL BE NEW AND OF THE QUALITY INDICATED BY THE SPECIFIED BRAND NAMES. SUBSTITUTIONS OF MATERIAL OF EQUAL QUALITY BY OTHER MAJOR MANUFACTURERS OF COMMERCIAL EQUIPMENT MAY BE ACCEPTABLE PROVIDED A LIST OF SUCH SUBSTITUTIONS IS APPROVED IN WRITING BY POPEYE'S ARCHITECTURE AND ENGINEERING DEPARTMENT. THE CONTRACTOR SHALL SUBMIT A SUBSTITUTION LIST IN TRIPLICATE AT LEAST FIVE DAYS PRIOR TO THE BID OPENING. SINGLE FACE EXIT LIGHT W/EMERGENCY BATTERY PACK AND TWO (2) EMERGENCY LIGHT HEADS. SEE FIXTURE SCHEDULE BRACKET OR WALL MOUNTED LIGHT FIXTURE. LETTER DENOTES MARK, SEE FIXTURE SCHEDULE. FLUORESCENT LIGHT FIXTURE. LETTER DENOTES MARK. SEE FIXTURE SCHEDULE. FLUORESCENT LIGHT FIXTURE ON NIGHT LIGHT CIRCUIT. FLUORESCENT LIGHT FIXTURE. LETTER DENOTES MARK. SEE FIXTURE SCHEDULE. PENDANT LIGHT FIXTURE. LETTER DENOTES MARK. SEE FIXTURE SCHEDULE. RECESSED DOWN LIGHT FIXTURE. LETTER DENOTES MARK. SEE FIXTURE SCHEDULE. 8" VERTICAL FLUORESCENT RECESSED LIGHT FIXTURE. LETTER DENOTES MARK. SEE FIXTURE SCHEDULE. TOGGLE SWITCH - SINGLE POLE - HUBBEL #HBL1221-I. DUPLEX RECEPTACLE; NUMBER SUBSCRIPT INDICATES MOUNTING HEIGHT ABV FINISHED FLOOR IF DIFFERENT THAN SPECIFIED. HUBBEL #5362-I DUPLEX RECEPTACLE - IN WEATHER PROOF ENCLOSURE OR COVER, GROUND FAULT INTERUPTER. RECEPTACLE FLUSH MOUNTED IN CEILING. VERIFY EXACT LOCATION AND NEMA CONFIGURATION. DUPLEX RECEPTACLE - ISOLATED GROUND SURGE PROTECTED - HUBBELL #IG-5362-OSP FOR POS EQUIP. & PRINTERS DUPLEX RECEPTACLE - ISOLATED GROUND SURGE PROTECTED; MOUNTED IN CEILING. HUBBELL #IG-5362-OSP FOR MONITORS SPECIAL PURPOSE RECEPTACLE 208/120 PANELBOARD. DISCONNECT SWITCH SIZE AS NOTED. DOOR SWITCH MOUNTED IN DOOR FRAME (F.B.C.) SEE ELECTRICAL NOTES. ABOVE FINISHED FLOOR. ABOVE FINISHED CEILING. GROUND FAULT INTERUPTING FURNISHED BY CONTRACTOR. WEATHERPROOF UNLESS NOTED OTHERWISE. CONDUIT RUN CONCEALED IN WALLS OR CL. SPACES. ARROWS INDICATE HOMERUNS. SUBSCRIPT INDICATES PANEL AND CIRCUIT NUMBERS. SLASH MARKS INDICATE NUMBER OF CONDUCTORS. EQUIPMENT GROUNDING CONDUCTOR REQUIRED IN ALL CONDUITS NOT INDICATED WITH WITH HASHMARK. SAME AS ABOVE NOTE EXCEPT RUN CONDUIT BELOW FLOOR EXHAUST FAN. SUPPLY FAN. FLY FAN JUNCTION OR OUTLET BOX. JUNCTION OBOXFOR SIGN-MOUNT SWITCH NEAR SIGN. MAKE ALL CONNECTIONS REQ'D. VERIFY ALL ASPECTS WITH SIGNAGE VENDOR. SEE ARCHITECTURAL ELEVATIONS FOR HEIGHT AND LOCATION AS SHOWN. JUNCTION BOX FOR SMOKE DETECTOR (F.B.C.) 120v WIRING BY THIS CONTRACTOR. COMBINATION DUAL DATA OUTLET AND TELEPHONE OUTLET HEIGHT AS NOTED ON PLANS WITH 3/4 " EMPTY CONDUIT TO ABOVE CEILING. PROVIDE PULL WIRE. TELEPHONE OUTLET, WALL TYPE, 24" AFF U.N.O ON PLANS WITH 3/4 " EMPTY CONDUIT TO ABOVE CEILING. PROVIDE PULL WIRE. PROVIDE 'ON/OFF' SELECTOR SWITCH AND PILOT LIGHT IN NEMA 4 STAINLESS STEEL ENCLOSURE MOUNTED ON THE FACE OF THE HOOD. PROVIDED BY HOOD MANUFACTURER. SPEAKER; CEILING MOUNTED SPEAKER OUTLET IN WALL STUB 3/4" CONDUIT TO SPACE ABOVE ACCESSIBLE CEILING. PROVIDE PULL WIRE. TRANSFORMER MOUNTED ACCESSIBLE ELECTRIC DOOR PUSHBUTTON: EDWARDS #590 48" MOUNTING HEIGHT ELECTRIC DOOR BUZZER: 8" BELOW CEILING PHOTOCELL A. PANELBOARDS: PANELBOARDS SHALL BE BOLT-IN CIRCUIT BREAKER TYPE, AS SHOWN ON THE PLANS. PANELS SHALL BE OF PANELBOARD CONSTRUCTION, 20 INCHES WIDE (MINIMUM), 5-3/4" TO 6-1/2" DEEP, UL LISTED, AND MEET UL 67, UL 50, AND FEDERAL SPECIFICATION W-P-115B AS TYPE 1, CLASS 1, WITH BOLT-ON CIRCUIT BREAKERS, COPPER BUS BARS, NEUTRAL BUS, GROUND BUS, AND A HINGED LOCKABLE DOOR. CABINETS SHALL BE CODE GAUGE, GALVANIZED STEEL, MOUNTED AS SHOWN. PROVIDE TYPEWRITTEN CIRCUIT DIRECTORIES WITH CLEAR PLASTIC PROTECTORS IN ALL PANELS. ALL WIRES SHALL BE TAGGED WITH PANEL AND CIRCUIT NUMBERS. PANEL "MP" SHALL BE UL LISTED AND LABELED AS SUITABLE FOR USE AS SERVICE ENTRANCE EQUIPMENT. APPROVED MANUFACTURERS OF PANELS ARE SQUARE D/TELEMECHANIQUE, CUTLER-HAMMER, GENERAL ELECTRIC, WESTINGHOUSE, AND SIEMENS (I-T-E). B. LIGHTING FIXTURES: ALL LIGHTING FIXTURES SHALL BE UL LISTED, COMMERCIAL QUALITY. REFER TO NATIONAL ACCOUNT SCHEDULE. REVIEW AT: WWW.POPEYESDEVELOPMENT.COM; PASSWORD: lagniappe C. LAMPS: ALL NEW FLUORESCENT LAMPS (F40T8) SHALL BE COOL WHITE, OR COLOR IMPROVED COOL WHITE, WITH A 4100 DEGREE K COLOR TEMPERATURE, 2950 MIN INITIAL LUMENS, 20,000 HOURS RATED LIFE, AND 62 MIN CRI, UNLESS NOTED OTHERWISE. D. WIRING DEVICES: ALL WIRING DEVICES SHALL BE UL LISTED, COMMERCIAL SPECIFICATION GRADE. SWITCHES SHALL BE RATED 20 AMPS AT 120/277 VOLTS, AC. STANDARD RECEPTACLES SHALL BE 20 AMP, DUPLEX, GROUNDING TYPE, IN NEMA CONFIGURATIONS, UNLESS NOTED OTHERWISE. SWITCHES IN THE SAME LOCATION SHALL BE GANGED BEHIND A SINGLE PLATE. DEVICE PLATES IN THE KITCHEN AREA SHALL BE METAL, ALUMINUM OR STAINLESS STEEL. DEVICE PLATES IN THE DINING AREA SHALL BE THERMOPLASTIC PLASTIC (NYLON) OR METAL, COLOR AS APPROVED BY THE ARCHITECT OR OWNER. APPROVED MANUFACTURERS OF SWITCHES AND RECEPTACLES ARE HUBBELL, ARROW HART, BRYANT, LEVITON, PASS & SEYMOUR, GENERAL ELECTRIC, SLATER, OR EQUAL. 1. SWITCHES: a. SINGLE POLE: HUBBELL HBL1221-I, OR EQUAL. b. THREE WAY: HUBBELL HBL1223-I, OR EQUAL. 2. RECEPTACLES: a. NEMA 5-20R: HUBBELL 5362I, OR EQUAL. b. NEMA 5-20R-IG: HUBBELL IG-5362, OR EQUAL. c. NEMA 5-20R-IG/SS: HUBBELL IG-5362-OS, OREQUAL. d. NEMA 5-20R-GFCI: HUBBELL GF5362-I, OR EQUAL. e. NEMA 6-20R: HUBBELL 5462-I, OR EQUAL. f. OTHERS: COMMERCIAL OR INDUSTRIAL GRADE, UL LISTED, FEDERAL SPECIFICATION WC596F. 3. WP PLATES: WEATHERPROOF COVERS ARE PERMITTED UNDER NEC ARTICLE 406.8(B)(I). 4. NATIONAL ACCOUNT: REFER TO THE NATIONAL ACCOUNT DIRECTORY. THE FOLLOWING EQUIPMENT MAY BE AVAILABLE: MAIN SERVICE PANELBOARD WITH BREAKERS INSTALLED, LIGHTING AND DISTRIBUTION PANELBOARDS WITH BREAKERS INSTALLED, ROOF-TOP DISCONNECTS FOR HVAC UNITS AND KITCHEN HOOD FANS, LIGHTING CONTACTOR PANEL, AND SHUNT TRIP SYSTEMS (IF REQUIRED PER LOCAL CODE). 5. EXCAVATIONS: PERFORM ALL NECESSARY EXCAVATING AND BACK-FILLING REQUIRED FOR THIS INSTALLATION. ALL EXCAVATIONS BELOW THE BOTTOM OF FOOTINGS SHALL BE BACKFILLED WITH 3000 PSI CONCRETE. WHERE DITCHES ARE CUT FOR OUTSIDE RUNS OF CONDUIT, REPLACE AND TAMP THE EARTH IN 12" LAYERS AND LEAVE THE GROUND LEVEL AND EQUAL TO ITS ORIGINAL CONDITION. 6. CONDUIT AND FITTINGS: CONDUIT PERMITTED: (A) RIGID GALVANIZED STEEL (RGS), (B) EMT, (C) PVC, AND (D) ENT. TYPES UTILIZED SHALL BE RUN ONLY AS PERMITTED PER CODE. ALL WIRING SHALL BE RUN IN CONDUIT. CONDUIT PLACED IN CONCRETE OR RUN UNDERGROUND SHALL BE RIGID GALVANIZED CONDUIT OR PVC. IF PVC IS USED, ALL ELBOWS, SWEEPS AND STUB-UPS SHALL BE RGS. CONDUIT EXPOSED OR RUN IN MASONRY WALLS ABOVE GRADE MAY BE PVC OR EMT WHERE ALLOWED BY LOCAL CODES. IF EMT IS NOT PERMITTED, RIGID SCREWED GALVANIZED PIPE CONDUIT AND FITTINGS SHALL BE USED. IF SHIELDED CABLE IS REQUIRED FOR CONTROL CIRCUITRY, IT SHALL BE TAN, GREY OR ANY NEUTRAL COLOR OTHER THAN THAT AS SPECIFIED FOR POWER DISTRIBUTION. NO CONDUIT SMALLER THAN 3/4" SHALL BE INSTALLED EXCEPT FOR TWO-WIRE SWITCH LEGS. ALL CONDUIT BENDS SHALL BE FREE FROM DENTS AND KINKS. ALL CONDUITS SHALL BE ELECTRICALLY CONTINUOUS FROM THE SERVICE EQUIPMENT TO ALL OUTLETS, AND SHALL BE SECURED TO ALL METAL BOXES WITH ONE LOCK NUT OUTSIDE, AND ONE INSIDE THE BOX WITH A REINFORCED BAKELITE BUSHING. IF PVC, OR ENT, IS USED, THEN APPROPRIATE SIZED, ELECTRICALLY CONTINUOUS, BOND WIRES SHALL BE RUN FROM THE SERVICE EQUIPMENT TO ALL OUTLETS, AND SHALL BE SECURED TO EACH WIRING DEVICE PER THE NATIONAL ELECTRICAL CODE. WHERE CONNECTIONS ARE TO BE MADE BETWEEN CONDUIT TERMINATIONS AND MOTORS, EQUIPMENT, OR APPARATUS NECESSITATING FLEXIBLE CONNECTIONS, APPROVED FLEXIBLE CONDUIT SHALL BE USED. OUTDOOR CONNECTIONS TO FANS, HVAC UNITS, OR ROTATING EQUIPMENT SHALL B MADE WITH HELICAL WOUND, LIQUIDTIGHT, FLEXIBLE STEEL CONDUIT. EXPOSED CONDUIT SHALL BE SUITABLY SUPPORTED AT INTERVALS NOT TO EXCEED FIVE (5) FEET. DURING CONSTRUCTION, CONDUIT SHALL BE KEPT FREE OF ALL FOREIGN MATTER BY USE OF CAPPED BUSHINGS ON ALL TURNED UP ENDS. PAPER OR WOOD PLUGS ARE NOT ACCEPTABLE FOR THIS PURPOSE. 7. WIRE AND CABLES: ALL WIRE AND CABLES SHALL BE UNDERWRITERS LABORATORIES' LISTED, AND LABELED, AND CONFORM WITH APPLICABLE STANDARDS OF UL (44, AND 83), NEMA (WC-5, AND WC-7), IPCEA (S-61-402, AND S-66-524), FEDERAL SPECIFICATIONS (J-C-30A(1), AND HH-I-595C), ANSI, AND OTHER APPLICABLE INDUSTRY STANDARDS. CONNECTORS AND LUGS SHALL MEET UL PUBLICATION 486. ALL BRANCH CIRCUIT WIRING SHALL BE 600 VOLT, COPPER, 75 DEGREE C (MIN), TYPE THHN/THWN WITH A MINIMUM SIZE OF #12 AWG, UNLESS NOTED OTHERWISE. WIRE SIZES OF #8 AWG AND LARGER SHALL BE STRANDED. SERVICE AND FEEDER CABLES SHALL BE 600 VOLT, STRANDED COPPER, 75 DEGREE C (MIN), TYPE XHHW. ALL CIRCUITS SHALL HAVE A SEPARATE GROUND CONDUCTOR. PROVIDE GREEN-INSULATED GROUND WIRE IN ALL RACEWAYS, CABLE ASSEMBLIES, AND WHERE NOTED. SIZE EQUIPMENT GROUNDS PER TABLE 250-122 OF THE NATIONAL ELECTRICAL CODE. INSULATION COLOR CODES SHALL BE BLACK, RED, AND BLUE (PHASE), WHITE (NEUTRAL), AND GREEN (GROUND). A. ALL WIRING SHALL BE INSTALLED IN CONDUIT, EXCEPT WHERE SPECIFICALLY SHOWN ON THE DRAWINGS. NON-METALLIC SHEATHED (TYPE NM) CABLE IS NOT PERMITTED. B. ALL BRANCH CIRCUIT, COMMUNICATION, SIGNALING, AND CONTROL WIRING TO KITCHEN, FIRE PROTECTION, AND OTHER EQUIPMENT SHALL BE ROUTED ABOVE THE CEILING. VERIFY WHETHER OR NOT THE SPACE ABOVE THE CEILING IS USED AS A SPACE FOR RETURN AIR FOR THE ENVIRONMENTAL AIR SYSTEM. IF IT IS USED FOR RETURN AIR, PROVIDE APPROVED RACEWAYS FOR ALL OVERHEAD WIRING PER NEC ARTICLE 300-22(B). IF IT IS NOT "OTHER SPACE USED FOR ENVIRONMENTAL AIR", APPROVED LOW VOLTAGE CABLES MEETING THE REQUIREMENTS OF NEC ARTICLES 725 AND 760 MAY BE RUN WITHOUT RACEWAYS, UNO. ALL SAFETY CONTROL WIRING FOR FIRE PROTECTION SYSTEMS, SHUNT TRIPS, ETC. SHALL BE RUN IN A RACEWAY IN ACCORDANCE WITH NEC ARTICLES 725.25 AND 725.28. 8. SITE LIGHTING: THE G.C. WILL FURNISH THE SITE LIGHTING PACKAGE, AS REQUIRED FOR THE SPECIFIC LOCATION. UNDER THIS SPECIFICATION SECTION, PROVIDE 1" RIGID GALVANIZED STEEL ELECTRICAL CONDUIT, AND THE REQUIRED WIRING FROM THE PANEL TO THE POLE. SET FIXTURES AND POLES ON CONCRETE BASES, AS PROVIDED UNDER SPECIFICATION SECTION 3A: CONCRETE. GROUND/BOND ALL SITE LIGHTING FIXTURES/POLES PER THE NEC. THE BRANCH CIRCUIT CONDUCTORS SHALL BE INCREASED FROM #10 AWG TO #8 AWG IF THE HORIZONTAL DISTANCE FROM THE PANEL TO THE POLE IS GREATER THAN EIGHTY (80) FEET. ALL SITE LIGHTING SHALL BE CONTROLLED THROUGH THE LIGHTING CONTROL SYSTEM SHOWN ON THE DRAWINGS. REFER TO THE SITE PLAN FOR QUANTITY AND LOCATION OF ALL SITE LIGHTING. SET FIXTURES AS SPECIFIED, AND AIM AFTER DARK FOR UNIFORM LIGHT DISTRIBUTION. 9. SIGNAGE LIGHTING: PROVIDE A 1" RIGID GALVANIZED STEEL ELECTRICAL CONDUIT, AND WIRING, FROM THE PANEL TO ALL ILLUMINATED SIGNS AS SHOWN ON THE LIGHTING AND SITE PLANS. GROUND/BOND EACH SIGN. SIGNS WILL BE FURNISHED AND INSTALLED BY THE OWNER, OR UNDER A SEPARATE CONTRACT, UNO. POWER AND WIRING SHALL BE FURNISHED AND INSTALLED UNDER THIS SECTION OF THE SPECIFICATIONS. OTHER WIRING: A. FURNISH AND INSTALL ALL POWER WIRING AND CONDUIT AS INDICATED ON THE DRAWINGS FOR ROOF-TOP HVAC EQUIPMENT, KITCHEN HOOD FANS, AND WALK-IN FREEZER AND COOLER EQUIPMENT. DISCONNECT SWITCHES, AVAILABLE FROM THE NATIONAL ACCOUNT, SHALL BE FURNISHED AND INSTALLED FOR EACH UNIT OF HVAC EQUIPMENT, AND FOR KITCHEN EQUIPMENT WITHOUT A CORD AND PLUG. BEFORE ENERGIZING ANY EQUIPMENT, VERIFY THAT THE CORRECT POWER SUPPLY VOLTAGE, AMPACITY, AND PHASING HAS BEEN PROVIDED AT THE LOAD SIDE OF THE DISCONNECT. B. FURNISH AND INSTALL THE LIGHTING CONTACTOR PANEL, AND ALL ASSOCIATED POWER WIRING, AS INDICATED. THE LIGHTING CONTACTOR PANEL IS CUSTOM BUILT, AND AVAILABLE FROM THE NATIONAL ACCOUNT. 10. EMPTY CONDUIT: LEAVE A #12 AWG PULL WIRE IN ALL EMPTY CONDUITS. 11. BOXES AND WIREWAYS: ALL JUNCTION BOXES, PULL BOXES, WIREWAYS, ETC, SHALL BE SIZED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. 12. EQUIPMENT IDENTIFICATION: PROVIDE NAMEPLATES FOR ALL PANELBOARDS, CONTROLS, AND OTHER ELECTRICAL EQUIPMENT. EQUIPMENT VISIBLE TO THE PUBLIC SHALL BE IDENTIFIED WITH ENGRAVED LAMINATED NAMEPLATES ATTACHED WITH STAINLESS STEEL FASTENERS. ELECTRICAL EQUIPMENT NOT VISIBLE TO THE PUBLIC MAY BE NEATLY IDENTIFIED WITH BLACK PERMANENT MARKERS. PART III. EXECUTION 1. TESTS: MAKE ALL TESTS NECESSARY TO ENSURE THAT THE ENTIRE INSTALLATION IS FREE FROM IMPROPER GROUNDS, AND FROM SHORTED AND/OR OPEN CONDUCTORS. VOLTAGE, CURRENT, AND ROTATION TESTS SHALL BE MADE BEFORE ANY MOTORS ARE PLACED IN OPERATION. ALL LOADS SHALL BE BALANCED ACROSS PHASES. CHECK TO SEE THAT ALL LIGHTS WORK, AND ARE CONTROLLED BY SWITCHES INDICATED ON DRAWINGS, OR CIRCUIT BREAKERS SO INDICATED ON PANEL SCHEDULE. 2. GUARANTEE: FURNISH A GUARANTEE IN WRITING TO THE OWNER THAT ALL WORK EXECUTED UNDER THIS SECTION IS FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL ACCEPTANCE. IN ADDITION, DURING THE TERM OF THIS GUARANTEE, THE REPAIR AND/OR REPLACEMENT OF ANY DEFECTIVE WORK, AND ALL RESULTING DAMAGES SHALL BE MADE AT NO ADDITIONAL EXPENSE TO THE OWNER. 3. TEMPORARY POWER: AT THE PROJECT SITE, PROVIDE A 100 AMP, 120/240 VOLT, SINGLE PHASE, SERVICE WITH POWER OUTLETS ADEQUATE FOR TEMPORARY CONSTRUCTION POWER. TEMPORARY LIGHTING SHALL BE MAINTAINED IN ALL AREAS OF THE BUILDING UNTIL PERMANENT POWER SOURCES HAVE BEEN ENERGIZED. TEMPORARY SERVICE SHALL BE PROVIDED UNDER SECTION 1A OF THESE SPECIFICATIONS. 4. CLEAN-UP: LEAVE THE ELECTRICAL PORTION OF THE WORK IN A CLEAN AND FINISHED CONDITION. 5. SHOP DRAWINGS: PROVIDE SHOP DRAWINGS FOR THE FOLLOWING ITEMS: PANELBOARDS, LIGHTING FIXTURES. 6. AS-BUILT DRAWINGS: MAINTAIN AS-BUILT DRAWINGS, UPDATED DAILY DURING CONSTRUCTION, AND PRESENT THE OWNER WITH ONE SET UPON COMPLETION. PROVIDE THE OWNER'S PERSONNEL WITH ON-SITE INSTRUCTION IN THE OPERATION AND MAINTENANCE OF THE COMPLETED ELECTRICAL SYSTEM. BALCONY UPLIGHT FIXTURE CHECKED: DATE: POPEYES LK 1260-DL-PLUS PROTOTYPE E.I.F.S. / SIMULATED STONE LOUISIANA KITCHEN LK-PLUS DESIGN STANDARDS 60 SEATS / DUAL-LINE PRODUCTION ELECTRICAL DATA SHEET and SPECIFICATIONS E0 04/17/15 KR REVISIONS:

Transcript of E0€¦ ·  · 2017-04-10verify exact location and nema configuration. duplex receptacle -...

PART I. GENERAL PROVISIONS

DIVISION 16 - ELECTRICAL SPECIFICATIONS

ELECTRICAL SPECIFICATIONS LEGEND

ELECTRICAL SYMBOLS

DATA OUTLET, HEIGHT AS NOTED ON PLANS WITH 3/4 " EMPTY

CONDUIT TO ABOVE CEILING. PROVIDE PULL WIRE.

1. SCOPE: PROVIDE ALL LABOR, MATERIAL, AND EQUIPMENT IN

ACCORDANCE WITH THESE SPECIFICATIONS, AND THE

ACCOMPANYING DRAWINGS TO PROVIDE A COMPLETE AND

PROPERLY OPERATING ELECTRICAL SYSTEM FOR THE

BUILDING.

A. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL OF THE

FOLLOWING MATERIAL AND EQUIPMENT UNDER THIS

DIVISION OF THE SPECIFICATIONS, UNLESS NOTED OTHERWISE:

PANELBOARDS; LIGHTING FIXTURES; LAMPS; RACEWAYS; 600 VOLT

WIRE AND CABLE; WIRING DEVICES; DEVICE PLATES; DEVICE, PULL,

AND JUNCTION BOXES; SAFETY SWITCHES; MOTOR STARTERS;

LIGHTING CONTROLS; CIRCUIT BREAKERS; FUSES; TIME

CLOCKS; EQUIPMENT IDENTIFICATION (NAMEPLATES AND

DIRECTORIES); WIRE AND CABLE TERMINATIONS; CONNECTIONS TO

INDIVIDUAL UNITS OF EQUIPMENT FOR THE WALK-IN FREEZERS

AND COOLERS; AND TEMPORARY POWER.

B. THE FOLLOWING MATERIAL AND EQUIPMENT WILL BE FURNISHED

AND/OR INSTALLED BY OTHERS, OR UNDER OTHER

DIVISIONS OF THE SPECIFICATIONS, UNLESS NOTED OTHERWISE:

LOW VOLTAGE (24 VOLT) WIRE AND CABLE, COMMUNICATION

DEVICES, SECURITY EQUIPMENT, POINT OF SALE (POS) EQUIPMENT,

SIGNAGE, CONCRETE BASES FOR SITE LIGHTING POLES.

C. THE FOLLOWING MATERIAL AND EQUIPMENT WILL BE FURNISHED BY

OTHERS, OR UNDER OTHER DIVISIONS OF THE SPECIFICATIONS,

AND INSTALLED BY THE CONTRACTOR, UNLESS NOTED

OTHERWISE: SITE LIGHTING FIXTURES AND POLES.

2. GENERAL REQUIREMENTS: ALL WORK SHALL BE PERFORMED BY

SKILLED LICENSED ELECTRICIANS IN ACCORDANCE WITH THE

BEST PRACTICES OF THE TRADE, MEETING THE REQUIREMENTS OF

THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE,

APPLICABLE FEDERAL, STATE AND LOCAL CODES, AND THE

REQUIREMENTS OF THE ELECTRICAL UTILITY COMPANY

FURNISHING THE SERVICES. ALL NECESSARY CONSTRUCTION

PERMITS AND CERTIFICATES OF INSPECTION SHALL BE

PURCHASED AND OBTAINED UNDER THIS CONTRACT.

A. COORDINATION: ALL OUTLETS MUST BE ACCURATELY LOCATED,

PARTICULARLY APPLIANCE OUTLETS WHICH SHALL BE LOCATED

FROM THE DIMENSIONS GIVEN ON THE DRAWING AND FIELD

VERIFIED. REVIEW THE ARCHITECTURAL, PLUMBING AND HEATING

AND VENTILATING PLANS IN ORDER TO COORDINATE THIS WORK

WITH OTHER TRADES, AND COOPERATE WITH THEM IN THE ENTIRE

INSTALLATION.

3. SERVICE VOLTAGE: THESE DRAWINGS ARE FOR A METERED,

UNDERGROUND BUILDING SERVICE OF 120/208 VOLT, THREE

PHASE, FOUR WIRE, 60 HERTZ. ALL KITCHEN AND AIR

CONDITIONING EQUIPMENT HAS BEEN DESIGNED AND PURCHASED

FOR USE ON THIS ELECTRICAL SYSTEM. THE CONTRACTOR SHALL

CONTACT THE ELECTRICAL UTILITY AND VERIFY ALL OF THE ABOVE

SERVICE CHARACTERISTICS, AND THE AVAILABLE FAULT CURRENT.

4. SERVICE EQUIPMENT: THE SERVICE SHALL BE LOCATED AS SHOWN

ON THE SITE PLAN, OR AS INDICATED IN THE INSTRUCTIONS

TO BIDDERS. UTILITY POLES, PADS FOR UTILITY TRANSFORMERS,

CURRENT TRANSFORMER ENCLOSURES, METERING EQUIPMENT,

SERVICE MASTS, AND OTHER RELATED MATERIALS AND

EQUIPMENT SHALL BE APPROVED, FURNISHED, AND INSTALLED AS

REQUIRED. INCLUDE THE COST OF ALL THE ABOVE ITEMS, SERVICE

CONNECTIONS, AND METER CHARGES IN THE BASE BID. MAIN

SERVICE SWITCHES AND CURRENT TRANSFORMER CABINETS

SHALL BE INCLUDED IN THE BASE BID. UNLESS NOTED OTHERWISE,

A MAIN SERVICE SWITCH WITH CURRENT LIMITING FUSES MAY BE

USED WHEN THE AVAILABLE FAULT CURRENT (AFC) IS EXCESSIVE,

IN ORDER TO USE STOCK PANELBOARDS, WITH 10K OR 22K AIC

RATINGS.

PART II. MATERIALS

1. MATERIALS: ALL MATERIALS SHALL BE NEW AND OF THE QUALITY

INDICATED BY THE SPECIFIED BRAND NAMES. SUBSTITUTIONS OF

MATERIAL OF EQUAL QUALITY BY OTHER MAJOR MANUFACTURERS

OF COMMERCIAL EQUIPMENT MAY BE ACCEPTABLE PROVIDED A

LIST OF SUCH SUBSTITUTIONS IS APPROVED IN WRITING BY

POPEYE'S ARCHITECTURE AND ENGINEERING DEPARTMENT. THE

CONTRACTOR SHALL SUBMIT A SUBSTITUTION LIST IN TRIPLICATE

AT LEAST FIVE DAYS PRIOR TO THE BID OPENING.

SINGLE FACE EXIT LIGHT W/EMERGENCY BATTERY

PACK AND TWO (2) EMERGENCY LIGHT HEADS. SEE

FIXTURE SCHEDULE

BRACKET OR WALL MOUNTED LIGHT FIXTURE. LETTER

DENOTES MARK, SEE FIXTURE SCHEDULE.

FLUORESCENT LIGHT FIXTURE. LETTER

DENOTES MARK. SEE FIXTURE SCHEDULE.

FLUORESCENT LIGHT FIXTURE ON NIGHT LIGHT CIRCUIT.

FLUORESCENT LIGHT FIXTURE. LETTER

DENOTES MARK. SEE FIXTURE SCHEDULE.

PENDANT LIGHT FIXTURE. LETTER

DENOTES MARK. SEE FIXTURE

SCHEDULE.

RECESSED DOWN LIGHT FIXTURE. LETTER

DENOTES MARK. SEE FIXTURE SCHEDULE.

8" VERTICAL FLUORESCENT RECESSED LIGHT

FIXTURE. LETTER DENOTES MARK. SEE

FIXTURE SCHEDULE.

TOGGLE SWITCH - SINGLE POLE - HUBBEL #HBL1221-I.

DUPLEX RECEPTACLE; NUMBER SUBSCRIPT INDICATES

MOUNTING HEIGHT ABV FINISHED FLOOR IF DIFFERENT THAN

SPECIFIED. HUBBEL #5362-I

DUPLEX RECEPTACLE - IN WEATHER PROOF ENCLOSURE

OR COVER, GROUND FAULT INTERUPTER.

RECEPTACLE FLUSH MOUNTED IN CEILING.

VERIFY EXACT LOCATION AND NEMA

CONFIGURATION.

DUPLEX RECEPTACLE - ISOLATED GROUND SURGE

PROTECTED - HUBBELL #IG-5362-OSP FOR POS EQUIP.

& PRINTERS

DUPLEX RECEPTACLE - ISOLATED GROUND SURGE

PROTECTED; MOUNTED IN CEILING. HUBBELL #IG-5362-OSP

FOR MONITORS

SPECIAL PURPOSE

RECEPTACLE

208/120 PANELBOARD.

DISCONNECT SWITCH SIZE AS NOTED.

DOOR SWITCH MOUNTED IN DOOR FRAME (F.B.C.)

SEE ELECTRICAL NOTES.

ABOVE FINISHED FLOOR.

ABOVE FINISHED CEILING.

GROUND FAULT INTERUPTING

FURNISHED BY CONTRACTOR.

WEATHERPROOF

UNLESS NOTED OTHERWISE.

CONDUIT RUN CONCEALED IN WALLS OR CL. SPACES. ARROWS

INDICATE HOMERUNS. SUBSCRIPT INDICATES PANEL AND

CIRCUIT NUMBERS. SLASH MARKS INDICATE NUMBER OF

CONDUCTORS. EQUIPMENT GROUNDING CONDUCTOR

REQUIRED IN ALL CONDUITS NOT INDICATED WITH WITH

HASHMARK.

SAME AS ABOVE NOTE EXCEPT RUN CONDUIT

BELOW FLOOR

EXHAUST FAN.

SUPPLY FAN.

FLY FAN

JUNCTION OR OUTLET BOX.

JUNCTION OBOXFOR SIGN-MOUNT SWITCH NEAR SIGN. MAKE ALL

CONNECTIONS REQ'D. VERIFY ALL ASPECTS WITH SIGNAGE

VENDOR. SEE ARCHITECTURAL ELEVATIONS FOR HEIGHT AND

LOCATION AS SHOWN.

JUNCTION BOX FOR SMOKE DETECTOR (F.B.C.) 120v

WIRING BY THIS CONTRACTOR.

COMBINATION DUAL DATA OUTLET AND TELEPHONE OUTLET

HEIGHT AS NOTED ON PLANS WITH 3/4 " EMPTY CONDUIT TO

ABOVE CEILING. PROVIDE PULL WIRE.

TELEPHONE OUTLET, WALL TYPE, 24" AFF U.N.O ON PLANS WITH

3/4 " EMPTY CONDUIT TO ABOVE CEILING. PROVIDE PULL WIRE.

PROVIDE 'ON/OFF' SELECTOR SWITCH AND PILOT LIGHT IN NEMA

4 STAINLESS STEEL ENCLOSURE MOUNTED ON THE FACE OF

THE HOOD. PROVIDED BY HOOD MANUFACTURER.

SPEAKER; CEILING MOUNTED

SPEAKER OUTLET IN WALL STUB 3/4" CONDUIT TO

SPACE ABOVE ACCESSIBLE CEILING. PROVIDE PULL

WIRE.

TRANSFORMER MOUNTED ACCESSIBLE

ELECTRIC DOOR PUSHBUTTON:

EDWARDS #590 48" MOUNTING HEIGHT

ELECTRIC DOOR BUZZER: 8" BELOW

CEILING

PHOTOCELL

A. PANELBOARDS: PANELBOARDS SHALL BE BOLT-IN CIRCUIT

BREAKER TYPE, AS SHOWN ON THE PLANS. PANELS SHALL

BE OF PANELBOARD CONSTRUCTION, 20 INCHES WIDE

(MINIMUM), 5-3/4" TO 6-1/2" DEEP, UL LISTED, AND MEET UL

67, UL 50, AND FEDERAL SPECIFICATION W-P-115B AS TYPE 1,

CLASS 1, WITH BOLT-ON CIRCUIT BREAKERS, COPPER BUS BARS,

NEUTRAL BUS, GROUND BUS, AND A HINGED LOCKABLE DOOR.

CABINETS SHALL BE CODE GAUGE, GALVANIZED STEEL, MOUNTED

AS SHOWN. PROVIDE TYPEWRITTEN CIRCUIT DIRECTORIES WITH

CLEAR PLASTIC PROTECTORS IN ALL PANELS. ALL WIRES SHALL

BE TAGGED WITH PANEL AND CIRCUIT NUMBERS. PANEL "MP"

SHALL BE UL LISTED AND LABELED AS SUITABLE FOR USE AS

SERVICE ENTRANCE EQUIPMENT. APPROVED MANUFACTURERS

OF PANELS ARE SQUARE D/TELEMECHANIQUE, CUTLER-HAMMER,

GENERAL ELECTRIC, WESTINGHOUSE, AND SIEMENS (I-T-E).

B. LIGHTING FIXTURES: ALL LIGHTING FIXTURES SHALL BE UL LISTED,

COMMERCIAL QUALITY. REFER TO NATIONAL ACCOUNT

SCHEDULE. REVIEW AT: WWW.POPEYESDEVELOPMENT.COM;

PASSWORD: lagniappe

C. LAMPS: ALL NEW FLUORESCENT LAMPS (F40T8) SHALL BE COOL

WHITE, OR COLOR IMPROVED COOL WHITE, WITH A 4100 DEGREE K

COLOR TEMPERATURE, 2950 MIN INITIAL LUMENS, 20,000 HOURS

RATED LIFE, AND 62 MIN CRI, UNLESS NOTED OTHERWISE.

D. WIRING DEVICES: ALL WIRING DEVICES SHALL BE UL LISTED,

COMMERCIAL SPECIFICATION GRADE. SWITCHES SHALL BE RATED

20 AMPS AT 120/277 VOLTS, AC. STANDARD RECEPTACLES SHALL

BE 20 AMP, DUPLEX, GROUNDING TYPE, IN NEMA

CONFIGURATIONS, UNLESS NOTED OTHERWISE. SWITCHES IN THE

SAME LOCATION SHALL BE GANGED BEHIND A SINGLE PLATE.

DEVICE PLATES IN THE KITCHEN AREA SHALL BE METAL,

ALUMINUM OR STAINLESS STEEL. DEVICE PLATES IN THE DINING

AREA SHALL BE THERMOPLASTIC PLASTIC (NYLON) OR METAL,

COLOR AS APPROVED BY THE ARCHITECT OR OWNER. APPROVED

MANUFACTURERS OF SWITCHES AND RECEPTACLES ARE

HUBBELL, ARROW HART, BRYANT, LEVITON, PASS & SEYMOUR,

GENERAL ELECTRIC, SLATER, OR EQUAL.

1. SWITCHES:

a. SINGLE POLE: HUBBELL HBL1221-I, OR EQUAL.

b. THREE WAY: HUBBELL HBL1223-I, OR EQUAL.

2. RECEPTACLES:

a. NEMA 5-20R: HUBBELL 5362I, OR EQUAL.

b. NEMA 5-20R-IG: HUBBELL IG-5362, OR EQUAL.

c. NEMA 5-20R-IG/SS: HUBBELL IG-5362-OS, OREQUAL.

d. NEMA 5-20R-GFCI: HUBBELL GF5362-I, OR EQUAL.

e. NEMA 6-20R: HUBBELL 5462-I, OR EQUAL.

f. OTHERS: COMMERCIAL OR INDUSTRIAL GRADE, UL LISTED,

FEDERAL SPECIFICATION WC596F.

3. WP PLATES: WEATHERPROOF COVERS ARE PERMITTED UNDER

NEC ARTICLE 406.8(B)(I).

4. NATIONAL ACCOUNT: REFER TO THE NATIONAL ACCOUNT

DIRECTORY. THE FOLLOWING EQUIPMENT MAY BE AVAILABLE:

MAIN SERVICE PANELBOARD WITH BREAKERS INSTALLED,

LIGHTING AND DISTRIBUTION PANELBOARDS WITH BREAKERS

INSTALLED, ROOF-TOP DISCONNECTS FOR HVAC UNITS AND

KITCHEN HOOD FANS, LIGHTING CONTACTOR PANEL, AND SHUNT

TRIP SYSTEMS (IF REQUIRED PER LOCAL CODE).

5. EXCAVATIONS: PERFORM ALL NECESSARY EXCAVATING AND

BACK-FILLING REQUIRED FOR THIS INSTALLATION. ALL

EXCAVATIONS BELOW THE BOTTOM OF FOOTINGS SHALL BE

BACKFILLED WITH 3000 PSI CONCRETE. WHERE DITCHES ARE CUT

FOR OUTSIDE RUNS OF CONDUIT, REPLACE AND TAMP THE EARTH

IN 12" LAYERS AND LEAVE THE GROUND LEVEL AND EQUAL TO ITS

ORIGINAL CONDITION.

6. CONDUIT AND FITTINGS: CONDUIT PERMITTED: (A) RIGID

GALVANIZED STEEL (RGS), (B) EMT, (C) PVC, AND (D) ENT. TYPES

UTILIZED SHALL BE RUN ONLY AS PERMITTED PER CODE. ALL

WIRING SHALL BE RUN IN CONDUIT. CONDUIT PLACED IN

CONCRETE OR RUN UNDERGROUND SHALL BE RIGID GALVANIZED

CONDUIT OR PVC. IF PVC IS USED, ALL ELBOWS, SWEEPS AND

STUB-UPS SHALL BE RGS. CONDUIT EXPOSED OR RUN IN

MASONRY WALLS ABOVE GRADE MAY BE PVC OR EMT WHERE

ALLOWED BY LOCAL CODES. IF EMT IS NOT PERMITTED, RIGID

SCREWED GALVANIZED PIPE CONDUIT AND FITTINGS SHALL BE

USED. IF SHIELDED CABLE IS REQUIRED FOR CONTROL

CIRCUITRY, IT SHALL BE TAN, GREY OR ANY NEUTRAL COLOR

OTHER THAN THAT AS SPECIFIED FOR POWER DISTRIBUTION. NO

CONDUIT SMALLER THAN 3/4" SHALL BE INSTALLED EXCEPT FOR

TWO-WIRE SWITCH LEGS. ALL CONDUIT BENDS SHALL BE FREE

FROM DENTS AND KINKS. ALL CONDUITS SHALL BE ELECTRICALLY

CONTINUOUS FROM THE SERVICE EQUIPMENT TO ALL OUTLETS,

AND SHALL BE SECURED TO ALL METAL BOXES WITH ONE LOCK

NUT OUTSIDE, AND ONE INSIDE THE BOX WITH A REINFORCED

BAKELITE BUSHING. IF PVC, OR ENT, IS USED, THEN APPROPRIATE

SIZED, ELECTRICALLY CONTINUOUS, BOND WIRES SHALL BE RUN

FROM THE SERVICE EQUIPMENT TO ALL OUTLETS, AND SHALL BE

SECURED TO EACH WIRING DEVICE PER THE NATIONAL

ELECTRICAL CODE. WHERE CONNECTIONS ARE TO BE MADE

BETWEEN CONDUIT TERMINATIONS AND MOTORS, EQUIPMENT, OR

APPARATUS NECESSITATING FLEXIBLE CONNECTIONS, APPROVED

FLEXIBLE CONDUIT SHALL BE USED. OUTDOOR CONNECTIONS TO

FANS, HVAC UNITS, OR ROTATING EQUIPMENT SHALL B MADE WITH

HELICAL WOUND, LIQUIDTIGHT, FLEXIBLE STEEL CONDUIT.

EXPOSED CONDUIT SHALL BE SUITABLY SUPPORTED AT

INTERVALS NOT TO EXCEED FIVE (5) FEET. DURING

CONSTRUCTION, CONDUIT SHALL BE KEPT FREE OF ALL FOREIGN

MATTER BY USE OF CAPPED BUSHINGS ON ALL TURNED UP ENDS.

PAPER OR WOOD PLUGS ARE NOT ACCEPTABLE FOR THIS

PURPOSE.

7. WIRE AND CABLES: ALL WIRE AND CABLES SHALL BE

UNDERWRITERS LABORATORIES' LISTED, AND LABELED, AND

CONFORM WITH APPLICABLE STANDARDS OF UL (44, AND 83),

NEMA (WC-5, AND WC-7), IPCEA (S-61-402, AND S-66-524), FEDERAL

SPECIFICATIONS (J-C-30A(1), AND HH-I-595C), ANSI, AND OTHER

APPLICABLE INDUSTRY STANDARDS. CONNECTORS AND LUGS

SHALL MEET UL PUBLICATION 486. ALL BRANCH CIRCUIT WIRING

SHALL BE 600 VOLT, COPPER, 75 DEGREE C (MIN), TYPE

THHN/THWN WITH A MINIMUM SIZE OF #12 AWG, UNLESS NOTED

OTHERWISE. WIRE SIZES OF #8 AWG AND LARGER SHALL BE

STRANDED. SERVICE AND FEEDER CABLES SHALL BE 600 VOLT,

STRANDED COPPER, 75 DEGREE C (MIN), TYPE XHHW. ALL

CIRCUITS SHALL HAVE A SEPARATE GROUND CONDUCTOR.

PROVIDE GREEN-INSULATED GROUND WIRE IN ALL RACEWAYS,

CABLE ASSEMBLIES, AND WHERE NOTED. SIZE EQUIPMENT

GROUNDS PER TABLE 250-122 OF THE NATIONAL ELECTRICAL

CODE. INSULATION COLOR CODES SHALL BE BLACK, RED, AND

BLUE (PHASE), WHITE (NEUTRAL), AND GREEN (GROUND).

A. ALL WIRING SHALL BE INSTALLED IN CONDUIT, EXCEPT WHERE

SPECIFICALLY SHOWN ON THE DRAWINGS. NON-METALLIC

SHEATHED (TYPE NM) CABLE IS NOT PERMITTED.

B. ALL BRANCH CIRCUIT, COMMUNICATION, SIGNALING, AND

CONTROL WIRING TO KITCHEN, FIRE PROTECTION, AND OTHER

EQUIPMENT SHALL BE ROUTED ABOVE THE CEILING. VERIFY

WHETHER OR NOT THE SPACE ABOVE THE CEILING IS USED AS A

SPACE FOR RETURN AIR FOR THE ENVIRONMENTAL AIR SYSTEM.

IF IT IS USED FOR RETURN AIR, PROVIDE APPROVED RACEWAYS

FOR ALL OVERHEAD WIRING PER NEC ARTICLE 300-22(B). IF IT IS

NOT "OTHER SPACE USED FOR ENVIRONMENTAL AIR", APPROVED

LOW VOLTAGE CABLES MEETING THE REQUIREMENTS OF NEC

ARTICLES 725 AND 760 MAY BE RUN WITHOUT RACEWAYS, UNO.

ALL SAFETY CONTROL WIRING FOR FIRE PROTECTION SYSTEMS,

SHUNT TRIPS, ETC. SHALL BE RUN IN A RACEWAY IN ACCORDANCE

WITH NEC ARTICLES 725.25 AND 725.28.

8. SITE LIGHTING: THE G.C. WILL FURNISH THE SITE LIGHTING

PACKAGE, AS REQUIRED FOR THE SPECIFIC LOCATION. UNDER

THIS SPECIFICATION SECTION, PROVIDE 1" RIGID GALVANIZED

STEEL ELECTRICAL CONDUIT, AND THE REQUIRED WIRING FROM

THE PANEL TO THE POLE. SET FIXTURES AND POLES ON

CONCRETE BASES, AS PROVIDED UNDER SPECIFICATION SECTION

3A: CONCRETE. GROUND/BOND ALL SITE LIGHTING

FIXTURES/POLES PER THE NEC. THE BRANCH CIRCUIT

CONDUCTORS SHALL BE INCREASED FROM #10 AWG TO #8 AWG IF

THE HORIZONTAL DISTANCE FROM THE PANEL TO THE POLE IS

GREATER THAN EIGHTY (80) FEET. ALL SITE LIGHTING SHALL BE

CONTROLLED THROUGH THE LIGHTING CONTROL SYSTEM SHOWN

ON THE DRAWINGS. REFER TO THE SITE PLAN FOR

QUANTITY AND LOCATION OF ALL SITE LIGHTING. SET FIXTURES

AS SPECIFIED, AND AIM AFTER DARK FOR UNIFORM LIGHT

DISTRIBUTION.

9. SIGNAGE LIGHTING: PROVIDE A 1" RIGID GALVANIZED STEEL

ELECTRICAL CONDUIT, AND WIRING, FROM THE PANEL TO

ALL ILLUMINATED SIGNS AS SHOWN ON THE LIGHTING AND

SITE PLANS. GROUND/BOND EACH SIGN. SIGNS WILL BE

FURNISHED AND INSTALLED BY THE OWNER, OR UNDER A

SEPARATE CONTRACT, UNO. POWER AND WIRING SHALL BE

FURNISHED AND INSTALLED UNDER THIS SECTION OF THE

SPECIFICATIONS.

OTHER WIRING:

A. FURNISH AND INSTALL ALL POWER WIRING AND CONDUIT AS

INDICATED ON THE DRAWINGS FOR ROOF-TOP HVAC EQUIPMENT,

KITCHEN HOOD FANS, AND WALK-IN FREEZER AND COOLER

EQUIPMENT. DISCONNECT SWITCHES, AVAILABLE FROM THE

NATIONAL ACCOUNT, SHALL BE FURNISHED AND INSTALLED FOR

EACH UNIT OF HVAC EQUIPMENT, AND FOR KITCHEN EQUIPMENT

WITHOUT A CORD AND PLUG. BEFORE ENERGIZING ANY

EQUIPMENT, VERIFY THAT THE CORRECT POWER SUPPLY

VOLTAGE, AMPACITY, AND PHASING HAS BEEN PROVIDED AT THE

LOAD SIDE OF THE DISCONNECT.

B. FURNISH AND INSTALL THE LIGHTING CONTACTOR PANEL, AND ALL

ASSOCIATED POWER WIRING, AS INDICATED. THE LIGHTING

CONTACTOR PANEL IS CUSTOM BUILT, AND AVAILABLE FROM THE

NATIONAL ACCOUNT.

10. EMPTY CONDUIT: LEAVE A #12 AWG PULL WIRE IN ALL EMPTY

CONDUITS.

11. BOXES AND WIREWAYS: ALL JUNCTION BOXES, PULL BOXES,

WIREWAYS, ETC, SHALL BE SIZED IN ACCORDANCE WITH THE

NATIONAL ELECTRICAL CODE.

12. EQUIPMENT IDENTIFICATION: PROVIDE NAMEPLATES FOR ALL

PANELBOARDS, CONTROLS, AND OTHER ELECTRICAL EQUIPMENT.

EQUIPMENT VISIBLE TO THE PUBLIC SHALL BE IDENTIFIED WITH

ENGRAVED LAMINATED NAMEPLATES ATTACHED WITH STAINLESS

STEEL FASTENERS. ELECTRICAL EQUIPMENT NOT VISIBLE TO THE

PUBLIC MAY BE NEATLY IDENTIFIED WITH BLACK PERMANENT

MARKERS.

PART III. EXECUTION

1. TESTS: MAKE ALL TESTS NECESSARY TO ENSURE THAT THE

ENTIRE INSTALLATION IS FREE FROM IMPROPER GROUNDS, AND

FROM SHORTED AND/OR OPEN CONDUCTORS. VOLTAGE,

CURRENT, AND ROTATION TESTS SHALL BE MADE BEFORE ANY

MOTORS ARE PLACED IN OPERATION. ALL LOADS SHALL BE

BALANCED ACROSS PHASES. CHECK TO SEE THAT ALL LIGHTS

WORK, AND ARE CONTROLLED BY SWITCHES INDICATED ON

DRAWINGS, OR CIRCUIT BREAKERS SO INDICATED ON PANEL

SCHEDULE.

2. GUARANTEE: FURNISH A GUARANTEE IN WRITING TO THE

OWNER THAT ALL WORK EXECUTED UNDER THIS SECTION

IS FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP

FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL

ACCEPTANCE. IN ADDITION, DURING THE TERM OF THIS

GUARANTEE, THE REPAIR AND/OR REPLACEMENT OF ANY

DEFECTIVE WORK, AND ALL RESULTING DAMAGES SHALL BE

MADE AT NO ADDITIONAL EXPENSE TO THE OWNER.

3. TEMPORARY POWER: AT THE PROJECT SITE, PROVIDE A 100

AMP, 120/240 VOLT, SINGLE PHASE, SERVICE WITH POWER

OUTLETS ADEQUATE FOR TEMPORARY CONSTRUCTION

POWER. TEMPORARY LIGHTING SHALL BE MAINTAINED IN

ALL AREAS OF THE BUILDING UNTIL PERMANENT POWER

SOURCES HAVE BEEN ENERGIZED. TEMPORARY SERVICE SHALL

BE PROVIDED UNDER SECTION 1A OF THESE

SPECIFICATIONS.

4. CLEAN-UP: LEAVE THE ELECTRICAL PORTION OF THE WORK IN A

CLEAN AND FINISHED CONDITION.

5. SHOP DRAWINGS: PROVIDE SHOP DRAWINGS FOR THE

FOLLOWING ITEMS: PANELBOARDS, LIGHTING FIXTURES.

6. AS-BUILT DRAWINGS: MAINTAIN AS-BUILT DRAWINGS, UPDATED

DAILY DURING CONSTRUCTION, AND PRESENT THE OWNER

WITH ONE SET UPON COMPLETION. PROVIDE THE OWNER'S

PERSONNEL WITH ON-SITE INSTRUCTION IN THE

OPERATION AND MAINTENANCE OF THE COMPLETED

ELECTRICAL SYSTEM.

BALCONY UPLIGHT FIXTURE

CHECKED:

DATE:

PO

PE

YE

S

LK

1

26

0-D

L-P

LU

S P

RO

TO

TY

PE

E.I.F

.S

. / S

IM

UL

AT

ED

S

TO

NE

LO

UIS

IA

NA

K

IT

CH

EN

L

K-P

LU

S D

ES

IG

N S

TA

ND

AR

DS

60 S

EA

TS

/ D

UA

L-L

IN

E P

RO

DU

CT

IO

N

ELECTRICAL DATA

SHEET

and SPECIFICATIONS

E0

04/17/15

KR

REVISIONS:

FREEZER

WALK-IN

MENWOMEN

ELECTRICAL PANELS

COOLER

WALK-IN

SET FOR 30 MIN TIME DELAY WHEN TURNED OFF.

AND ADJUSTIBLE TIMER & BLOCK

PROVIDE DPDT RELAY

SQUARE D #8501-KP12V20

& #8501 NR51 BASE

B-16DIR SIGNS

N

ROOR FACING NORTH

(TYPICAL)

B-20

PE

OFF

ON

AUTO

PROVIDE PUSHBUTTON

SQUARE D #9001 KR1 RH13

& #9001KN202 "OFF"

LEGEND

MOUNT ON ROOF

(TYPICAL)

OPTIONAL

FACING NORTH

A-32

NO

R1

NC

OFF

PARKING

B-15

B-18

B-21

B-19

SPARE

8" W x 13" H x 6" D

NOMINAL ENCL. DIMENSIONS-

SD D #8903-LG80VO2

AT 20 AMP EACH (TYPICAL)

LIGHTING CONTACTOR W/ 8 POLES

B-38

SPARE

LC1

NOMINAL ENCL. DIMENSIONS-

LIGHTING CONTACTOR W/ 8 POLES

AT 30 AMP EACH (TYPICAL)

PYLON SIGN

MENU BOARD

PYLON SIGN

SIGN BLDG FRT

A-34

A-36

A-40

A-38

A-42

WALL ART

SPARE

SPARE

8" W x 13" H x 6" D

SD D #8903-LG80VO2

PARKING

PARKING

PARKING

PARKING

PARKING

LC2

EX

ON ROOF

CONTROL MOUNTED

REMOTE PE

120V

N

B-7

H

PE

WP

FIXTURE

LIGHT

H

38

REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, EXTERIOR ELEVATIONS AND

WALL SECTIONS FOR DIMENSIONED LOCATIONS OF LIGHTING FIXTURES.

NOTE:

VIA LC-3

B-28,30

CONTACTOR DIAGRAM NOTES:

LIGHTING CONTACTOR W/ 6 POLES

B-28

B-30

B-32

SD D #8903-LG80VO2

8" W x 13" H x 6" D

AT 20 AMP EACH (TYPICAL)

NOMINAL ENCL. DIMENSIONS-

CANOPY LIGHTS

CANOPY LIGHTS

CANOPY LIGHTS

SPARE

SPARE

SPARE

LC3

SHEET NOTES:

A-32,34,36,38,40,42 VIA LC2

# 8'S

WP

B-19:21 VIA LC1

WP

POPEYES RADIO SYSTEM

LABOR INCLUDES INSTALLATION OF 150' OF 12 GAUGE SPEAKER WIRE.

NUMBER OF SPEAKERS MAY VARY DUE TO DESIGN CONSIDERATIONS

CHANNEL MASTER

ECOHO STAR

PASO

QUAM

QUAM

VARIOUS

1.0 ANTENNA

3000

VARIOUS

QC-10

1

1

1

3

701

MODEL #16, BLACK

OWI

SSB-2

ERD-8

MU 3130 BGM

MAKE

BOSE

MODEL

4

2

2

1

QUANTITY

4

3. PROVIDE REMOTE MOUNTED (ON ROOF) PE CELL FOR ALL EXTERIOR FIXTURE, TYPE 'WP' NOT ON THE LIGHTING CONTACTOR.

2. ALL OUTLETS FOR LIGHTS SHALL BE SUPPORTED INDEPENDENTLY OF CEILING

4 LAMP ELECTRONIC BALLAST > 20% THD ELECTRONIC

SYSTEM USING 1/4 " ALL THREAD ROD.

1. SEE ARCHITECTURAL DETAILS FOR MOUNTING LOCATIONS.

CW20

FIXTURE NOTES:

PE

M

NOMENCLATURE

1/4 GEB

A12

COLD WEATHER BALLAST

FACTORY INSTALLED PHOTOCELL

METAL HALIDE SOURCE

PATTER #12 ACRYLIC PRISMATIC LENS

DEFINITIONS

5" x 7 GAUGE x 25' SQUARE STEEL POLE

(VERFIFY COUNTS AND TYPE WITH SITE PLAN)

VERIFY WIND LOAD TO ENSURE POLE SIZE IS SUFFICIENT.NOTE:

5

LL1

SITE LIGHTING

LL2

10

16

8

1000 WATT MH FLOODLIGHT

SECURITY

SECURITY

HERMITAGE

GOOSENECKS 100WMH - OUTDOOR

EX6

11 H

LED EXIT EMERGENCY COMBO

CL

MARK

3

A15

QTY.

COOLER/FREEZER

2 x 4 LAY-IN ELECTRONIC BALLAST

EXITRONIX

HILITE

COLUMBIA

MANUFACTURER

SSSP25-5-7-DBZ

BRONZE

EDJ31111

ASBF000MH-DM-MT

PF346315721216

BRONZE

MH1000/U/BT56

EVERGREEN

VEXUBPWHEL-90R

H811/C/GU/602-100MH

BY COOLER MANUFACTURER

JT824-332G-FSA12-3EU

LIGHT FIXTURE

WHITE

COLOR

INCLUDED

(3) F0735

BULBS

LIGHT FIXTURE SCHEDULE

MUZAK MBS 8-ST3, BLACK 2

QUAM

SEE THE NATIONAL ACCOUNT VENDOR LIST FOR EQUIPMENT SUPPLIER.

LABOR WARRANTY FOR TWO YEARS IS PROVIDED ON ALL PARKING LOT LIGHTING THRU HERMITAGE LIGHTING NATIONAL ACCOUNTS.

NO SUBSTITUTION ALLOWED FOR SPECIFIED LIGHT FIXTURES.

N/A

(1) MH100/U/MED

42 LL4 6" RECESSED DOWNLIGHT JUNO PL642EU-28B-WH

(7) 15W (GU-24)

ALL "EX" EMERGENCY & EXIT LIGHTING FIXTURES SHALL BE

CONNECTED AHEAD OF ROOM/AREA SWITCHES PER

NATIONAL ELECTRICAL CODE (NEC) ARTICLE 700-12(f).

ELECTRICAL CONTRACTOR SHALL VERIFY EXACT SIGN(S) WIRING

REQUIREMENTS WITH THE SIGN SUPPLIER PRIOR TO SUBMITTING

A BID FOR THE ELECTRICAL.

PROVIDE 2P/30A NEMA 3R, FUSED DISCONNECT SWITCH W/

LIQUID-TIGHT FLEXIBLE CONNECTION TO PYLON SIGN. FUSE

SIZE PER SIGN MFR'S RECOMMENDATION.

PROVIDE RACEWAYS, WIRING, AND LAMPS (F40T8) FOR ALL LIGHT

FIXTURES FURNISHED W/ THE FREEZER/COOLER/STORAGE UNIT.

LIGHT FIXTURES SHALL BE INSTALLED BY ELECTRICAL

CONTRACTOR. COORDINATE THE INSTALLATION OF SWITCHES AND

PLATES WITH THE EQUIP. SUPPLIER.

G.C. TO VERIFY EXACT ELECTRICAL REQUIREMENTS FOR ILLUMINATED

SITE/MONUMENT SIGN STRUCTURE W/ SIGN SUPPLIER PRIOR TO

INSTALLATION. G.C. TO PROVIDE FINAL ELECRICAL HOOK-UP.

TO SITE LIGHTING -

TYPICAL. SEE SITE

PLAN TO VERIFY

LOCATION AND

QUANTITY. SEE NOTE 7

LP

LP

1. THE LIGHTING CONTACTORS

SHALL BE HELD MAGNETICALLY IN A

NEMA 1 ENCLOSURE. THE SIGN &

CANOPY LIGHTING SHALL BE SET TO

COME ON FIRST, EVEN ON

RAINY/CLOUDY DAYS AND THE

PARKING LOT LIGHTING SHALL BE

SET TO COME ON LATER. THE

CONTROLS SHALL BE WIRED SO

THAT EACH GROUP OF LIGHTING

(SIGNAGE/CANOPY ADN PARKING

LOT) IS INDEPENDENT, AND MAY BE

MANUALLY SWITCHED OFF AT

CLOSING WITH ITS SELECTOR

SWITCH VIA TIME DELAY RELAY -

SEE CONTACTOR DIAGRAM DETAIL

THIS SHEET.

SET FOR DUSK

OR RAINY/CLOUDY

DAYS; MOUNT ON

SET FOR DARK,

R1

LOCATE SEL. SWITCH

CONTROLS FOR LC-1, LC3

LIGHTING CONTACTORS, AND

PUSHBUTTON CONTROL FOR

LC-2 LIGHTING CONTACTOR

AT THIS LOCATION

VERIFY LOCATION

ON SITE PLAN

PREVIEW BOARD ON

CLEARANCE SIGN

DRIVE-THRU

MENU BOARD

TO DIRECTION SIGNS. VERIFY LOCATIONS AND

QUANTITY OF SIGN ON SITE PLAN.

2

3 D1

D

BALCONY RECESSED SOFFIT LIGHT

SECURITY

SECURITY

851-DL-100MH-FP-WH-120

MIC100MHEV/RL6009 EVERGREEN

(1) MH100/U/MED

(1) MH100/U/MED

VERIFY THE EXACT LOCATION OF SIGNS, AND FASCIA

BOXES BEFORE INSTALLATION OF JUNCTION BOXES.

HOMERUNS MAY BE COMBINED AS ALLOWED BY THE NATIONAL

ELECT. CODE ALL CONDUIT SHALL BE SIZED PER THE 2002 NEC.

ELECTRICAL CONTRACTOR SHALL VERIFY THE LOCATION OF

THE PYLON SIGN ON THE SITE PLAN.

THE BUILDING SIGNAGE, PYLON SIGN, FASCIA LIGHTING,

BUILDING SIGN LIGHTING, DRIVE-THRU MENUBOARD(S), AND SITE

LIGHTING SHALL BE WIRED THRU THE LIGHTING CONTACTORS

FOR AUTOMATIC & MANUAL CONTROL.

J-BOX ON HOOD FOR PRE-WIRED HOOD LIGHTS.

NOT USED.

ROUTE CIRCUIT VIA EXTERIOR/SIGN LIGHTING CONTACTOR

(SEE CONTROL SCHEMATIC DIAGRAM SHEET E1.

FIXTURE TYPE "B1" EQUIPPED WITH EMERGENCY LIGHTING BATTERY

PACK, THE BATTERY PACK SHALL BE WIRED AHEAD OF ANY SWITCHES.

36"x8"x8" SHEET METAL GUTTER FOR BALLAST AND CAPACITORS FOR

FIXTURES "H". MOUNT GUTTER ABOVE CEILING TO INTERIOR STUDS.

LOCATE LIGHTING AND

FAN ON/OFF CONTROL

SWITCHES "a, b, c, d & e"

AT THIS LOCATION

H

38

LTG CONT. LC-1, 2 &

3 CONTACTORS, SEE

DIAGRAM THIS

SHEET & POWER

RISER SHEET E3.

(1) 15W

(3) 15W

WHITE

WHITE

J-BOX FOR SPEAKER AT

10'-4" A.F.F.,

CENTERLINE

SHUTTER UPLIGHT / CUSTOM COLOR

CAST ROUND BOX COVER FOR FIXTURE

B-15

SIGN ACCENT

VIA LC1

J-BOX FOR SPEAKER

AT 14'-6" A.F.F.,

CENTERLINE

J-BOX FOR SPEAKER AT

14'-6" A.F.F.,

CENTERLINE

B-32

VIA

LC-3

PYLON SIGN -

REFER TO SITE

PLAN FOR SEE

NOTES 5 & 7

RECESSED SPEAKERS* (DINING)

RECESSED SPEAKERS* (KITCHEN)

OUTDOOR BOX SPEAKERS*

AMPLIFIER

SPEAKER SUPPORT

SPEAKER BACKCAN

CABLE, CONNECTORS, HARDWARE AND

SHELF

AREA VOLUME CONTROL

RECEIVER

DISH

7 LL3 PENDENT HERMITAGE FLAVORIETY

ER

ER3

EM4 EMERGENCY LIGHTING UNIT

REMOTE EMERGENCY LIGHTING UNIT

(2) BLUE

(3) AMBER

(2) RED

26W TRT

WALL PACK w/ PHOTO CELL (REAR DOOR)WP1 SWP-100MH-DB-MT BRONZE (1) MH100/U/MEDSECURITY

PENDENT

PENDENT HERMITAGE

WP

C9

26W TRIPLE TUBE

6" RECESSED WALLWASHER WHITE

ALL LIGHT FIXTURES LISTED IN THE ABOVE SCHEDULE SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR,

EXCEPT AS NOTED IN PARAGRAPH, PART 1.1.C OF ELECTRICAL SPECIFICATIONS.

PLEASE CONTACT HERMITAGE LIGHTING FOR INFORMATION ON LIGHTING PACKAGE, TEL. (800) 264-3383

(BY SIGN SUPPLIER/BALCONY)

4. BALLAST LOCATION FOR GOOSE NECKS INSTALLED PER N.E.C.

WHITE

JUNO PL642EU-261B-WH

RED

LL90

LL50H-N4EXITRONIX

EXITRONIX WHITE

WHITE (1) 5W

(2) 5W

LL2

66" AFF

LL1

66" AFF

LL1

66" AFF

LL1

66" AFF

LL1

66" AFF

LL1

66" AFF

LL1

66" AFF

LL1

66" AFF

LL1

66" AFF

LL1

66" AFF

LL1

66" AFF

LL1

66" AFF

LL2

84" AFF

LL2

84" AFF

LL2

84" AFF

LL2

84" AFF

LL1

66" AFF

LL1

66" AFF

LL1

66" AFF

E12 MANSARD WALL MOUNT UNIT PNK126Q-120N-JCTERON CLEAR (1) 26W

LL2

66" AFF

CRABPOT LIGHTS AT "P" COUNTER TO BE MOUNTED 84" ABOVE FINISH FLOOR.

NOTE:

PENDANT and CRABPOT LIGHTS AT TABLES TO BE MOUNTED 66" ABOVE FINISH FLOOR.

LL1

84" AFF

LL1

84" AFF

CHECKED:

DATE:

PO

PE

YE

S

LK

1

26

0-D

L-P

LU

S P

RO

TO

TY

PE

E.I.F

.S

. / S

IM

UL

AT

ED

S

TO

NE

LO

UIS

IA

NA

K

IT

CH

EN

L

K-P

LU

S D

ES

IG

N S

TA

ND

AR

DS

60 S

EA

TS

/ D

UA

L-L

IN

E P

RO

DU

CT

IO

N

E1

1

LIGHTING PLAN

1/4"=1'-0"

E1

2

DETAIL(PE CONTROL FOR FIXTURE 'WP')

1/4"=1'-0"

E1

3

LIGHTING CONTACTOR DIAGRAM

1/4"=1'-0"

LIGHTING PLAN

E1

04/17/15

KR

REVISIONS:

24"x

60"

5-TI

ER

21"x

54"

4-TI

ER

24"x

54"

4-TI

ER

TRASH

PLAN (SD2) FOR

REFR TO SITE

EXACT LOCATION

FINISHED FLOOR

CEILING GRID

AT 6" ABOVE FINISHED CEILING.

CONDUIT BUSHING WITH TERMINATION

CABLE/S

@ 24"A

,F

,F

,

SINGLE

U.O

.N

.

TEL

DUAL/DOUBLE

TEL

DATA

PULL STRING AS NOTED.

1" OR 3/4" CONDUIT WITH

RECESSED SINGLE GANG

ELECTRICAL BOX.

C

PARTIAL EQUIPMENT SCHEDULE

CO Convenience Outlet 115 1 X

2'-6"

(MIN.)

2'-0"

IN CONC. DRIVE WITHIN 24"

OF PREFAB LOOP

OMIT WIRE REINFORCING MESH

EXTERIOR MENUBOARD

SEE SITE PLAN FOR

ORIENTATION

NOTE: REFER TO MFR. LITERATURE

INSTRUCTIONS FOR PREFAB LOOP

LITERATURE FOR SPECIFIC INSTALLATION

PRE-FAB DETECTOR LOOP

SUPPLIED & INSTALLED BY G.C.

W/ 3/4" BUSHING

WIRELESS DRIVE-THRU

CENTER MODULE

(WALL MOUNTED)

CIRCUIT B-22

120 VOLT DUPLEX

FIN. FLOOR

LOOP DETECTOR

SPEAKER POST.

3/4" CONDUIT TO

VERIFY LOCATION

ON SITE PLAN.

4"x4" J-BOX

COUNTER TOP

HOLE FOR SIGNAL

OUTLET BOX"

"PROVIDE STAINLESS

STEEL COVER PLATE

CEILING GRID

COORDINATE WITH SHEET K2.

SIGNAL 4"x4" J-BOX

Front Service Counter

NOTES:

1. FOR DIRECT CONNECTION EQUIPMENT A LOCAL

DISCONNECTING MEANS SHALL BE PROVIDED IN

ACCORDANCE WITH NEC & LOCAL CODE REQUIREMENTS.

backsplash w/ u/s

POWER PLAN KEY NOTES

REFER TO FOOD SERVICE DRAWING K1 FOR

TAG LOCATIONS NOT SHOWN THIS SHEET.

REFER TO HVAC DRG. M1 FOR EXACT LOCATIONS

FOR MECHANICAL HVAC EQUIPMENT.

3P30A NEMA 3R FUSED DISC. ON WALK-IN COND.

UNIT LOCATED ON ROOF. FUSE PER EQUIPMENT

NAMEPLATE. LIQUID TIGHT FLEX CONNECTION.

MAKE FINAL POWER CONNECTION TO WALK-IN

COOLER EVAPORATOR, PROVIDE MOTOR

SWITCH IN CAST BOX.

MAKE FINAL POWER CONNECTION TO WALK-IN

FREEZER FREEZER EVAP., DEFROSTER, HEAT

TAPE & DOOR HEATER.

PROVIDE LOCAL 3P60A NEMA 3R NON-FUSED

DISC SW. ON A/C RTU'S LOCATED ON ROOF

EQUIP. NAMEPLATE. PROVIDE LIQUID TIGHT

FLEX CONN. TO UNIT.

PROVIDE GFCI PROTECTED 5-20R DUPLEX

RECEPT. INSTALLED IN WP BOX W/ WP

COVER AT RTU. (TYP).

PROVIDE 120V WIRING TO DUCT MOUNTED

SMOKE DETECTORS AND REMOTE

TEST/INDICATORS. FOR EXACT LOCATIONS

OF DUCT DETECTORS, REMOTE INDICATORS

& TEST SW'S. (SEE HVAC PLANS).

E.C. SHALL INSTALL AND WIRE RELAY CONTROL

PANEL PACKAGE FOR HOOD EXHAUST FANS EF-1

AND EF-2. PROVIDE POWER AND INTERLOCK

CONTROL WIRING FOR HP1-F CONTROL PANEL

AND HOOD FIRE SUPPRESSION SYSTEM. SEE

HOOD FAN CONTROL INTERLOCK WIRING DIAGRAM.

SHEET M2. MOUNT STARTERS AND CONTROLS ON

WALL.

"ON/OFF" SELECTOR SWITCH AND PILOT LIGHT

IN NEMA 4X STAINLESS STEEL ENCLOSURE

MOUNTED ON THE FACE OF THE HOOD.

PROVIDED BY HOOD MFR.

PROVIDE 2P30A NEMA 3R FUSED DISC

SWITCH & L.T. FLEX CONNECTION TO ROOF

MTD ICE MAKER COND UNIT, FUSE SIZE PER

MFG'S NAMEPLATE DATA.

PROVIDE CEILING OUTLET W/ISOLATED

GROUND RECEPTACLES SUPPORTED FROM

BLDG. STRUCTURE FOR VIDEO

MONITOR/PRINTER & OR HEADSET. VERIFY

EXACT REQUIREMENTS & LOCATION.

PROVIDE 3/4" x 18" H x 24" W PLYWOOD TELEPHONE

BOARD PAINTED WITH 2 COATS OF "LISTED" FIRE

RETARDANT LIGHT GRAY COLOR PAINT. AT 96" A.F.F.

PROVIDE QUAD RECEPTACLE ADJACENT TO BOARD.

PROVIDE # 6 CU, GROUND TO SERVICE ENTRANCE

GROUND, SEE DETAIL ARCHITECTURAL ELEVATIONS.

PROVIDE CEILING DROPS FOR PRODUCTION

COUNTER BRANCH CIRCUITS TO CEILING

MOUNTED J-BOXES TO SERVE ALL ELECTRICAL

IN CTR.

PRODUCTION COUNTER ELECTRICAL POWER

CIRCUITS: REFER TO PANEL SCHEDULE "C" FOR

CIRCUIT NO'S. REFER TO EQUIPMENT SUPPLIER

SHOP DRAWINGS FOR EXACT LOCATIONS AND

TYPE OF CONNECTIONS FOR EQUIPMENT AND

HEAT LIGHTS IN/OR ON PRODUCTION

COUNTER.

BRANCH CIRCUIT(S) CONTINUED TO

ADDITIONAL OUTLETS, HOMERUN SHOWN

FOR CLARITY ONLY.

OUTLET AND CONNECTION FOR SECURITY

CAMERA. VERIFY EXACT LOCATIONS AND

TYPE CONNECTIONS FOR INDOOR AND

OUTDOOR CAMERAS WITH G.C..

ROUTE ALL CONDUIT ROOF PENETRATIONS

THRU (WITH-IN) ROOF CURBS FOR THE

EQUIPMENT. REFR TO MECH. PLANS FOR

CURB DETAILS. (TYPICAL)

PROVIDE 1" CONDUIT TO 6" ABOVE

CEILING.

HOOD ANSUL FIRE SUPPRESION

SYSTEM.

MAKE FINAL CONNECTION TO

EQUIPMENT

OFFICE EXHAUST FAN SHALL BE INTERCONNECTED TO

OPERATE WITH AREA LIGHTING. INTERLOCK EXHAUST

FAN WITH LIGHTS.

P.O.S. NOTES:

1. ALL P.O.S. (POINT OF SALE) CIRCUITS SHALL HAVE

AN ISOLATED GROUND WIRE BACK TO THE PANEL.

ALL P.O.S. EQUIP. SHALL BE WIRED

INDEPENDENTLY OF ANY NON-P.O.S. EQUIPMENT.

2. ALL RECEPTACLES FOR P.O.S. EQUIPMENT SHALL

BE ISOLATED GROUND WITH SURGE SUPPRESSOR

TYPE. ALL RECEPTACLES FOR P.O.S. EQUIPMENT

SHALL BE SINGLE UNIT, UNLESS A DUPLEX

RECEPTACLE CAN BE USED TO SUPPLY TWO P.O.S.

UNITS. DUPLEX RECEPTACLES MAY BE USED IN

THE MANAGER'S OFFICE FOR NON-P.O.S.

EQUIPMENT (COMPUTER, MUSIC, FIRE ALARM,

SECURITY, ETC.)

3. ALL CIRCUITS FOR P.O.S. EQUIPMENT SHALL BE

CONNECTED TO THE SAME PHASE OF POWER IN

THE PANEL. ALL BRANCH CIRCUIT BREAKERS

SUPPLYING P.O.S. EQUIPMENT SHALL HAVE

LOCKING HANDLES DEVICES.

4. EACH RECEPTACLE TYPE (LOCKING OR STRAIGHT

BLADE) SHALL MATCH THAT OF THE EQUIPMENT

FURNISHED. WHERE P.O.S. EQUIPMENT IS

FURNISHED WITHOUT A PLUG THE RECEPTACLE

SHALL BE LOCKING TYPE. COORDINATE

RECEPTACLE TYPES WITH THE P.O.S. EQUIPMENT

SUPPLIER.

GENERAL NOTES:

A. VERIFY MOUNTING HEIGHTS OF ALL

RECEPTACLES WITH EQUIPMENT SUPPLIED PRIOR

TO INSTALLATION.

B. ALL EQUIPMENT ELECTRICAL OUTLETS ARE

DIMENSIONED TO CENTERLINE OF BOX FROM

ABOVE FINISHED FLOOR.

C. ELECTRICAL CONTRACTOR TO PROVIDE CORD &

PLUG CONNECTIONS FOR EQUIPMENT AS

REQUIRED.

1" CONDUIT

INTERLOCK W/ RTU-2

FOR DRIVE-THRU

AUDIO SYSTEM

SEE DETAIL 4

WP

SP

SPEAKER

POST

FLOOR TO CENTERLINE

48" DENOTES MOUNTING

HEIGHT ABOVE FINISHED

(TYPICAL-INTERIOR OF BLDG.)

OF OUTLET BOX.

E.C. SHALL WIRE &

CONNECT G.C.

PROVIDED REMOTE

ANSUL PULL STATION

E.C. SHALL PROVIDE

3/4" C. STUBBED

ABOVE CEILING FOR

ANSUL SYSTEM

FOR HEAT TRACE AT

GREASE RECOVERY

UNIT. (VERIFY EXACT

LOCATION)

FOR IRRIGATION

CONTROLLER,

(VERIFYEXACTLOCATION)

WP

THIS SHEET

RUN 2 - 2" CONDUITS FROM

TELEPHONE EQUIPMENT BOARD

TO A LOCATION COORDINATED

WITH LOCAL TELEPHONE

COMPANY, OWNER REQUIREMENT

SERVICE CONDUITS SHALL BE

SIZED FOR 25 PAIR (MINIMUM).

TELEPHONE SERVICE CABLE,

CONDUITS SHALL BE INSTALLED

WITH PULLWIRE. CONDUITS RISE

FROM U.G. INSIDE EXTERIOR WALL

AND TURN-OUT WITH 90 DEG ELLS

INSIDE BLDG. AT TERM. BD. SEE

ARCHITECTURAL ELEVATIONS.

OWNER REQUIRED SEPERATE

TELEPHONE SERVICE LINES TO

BUILDING:

(1) LINE FOR VOICE

(1) LINE FOR SECURITY

(1) LINE FOR CREDIT CARD

(1) LINE FOR CASH REGISTER

(1) LINE FOR COMPUTER LINES

E.C. SHALL CONNECT

G.C. PROVIDED DOOR

FLY FAN

E.C. SHALL INSTALL

AND WIRE-G.C.

PROVIDED MICRO

SWITCH IN IN DOOR

FRAME FOR ON/OFF

CONTROL OF DOOR

FLY FAN

TO CENTERLINE OF OUTLET

BOX. 102" DENOTES MOUNTING

HEIGHT ABOVE FINISHED

GRADE/WALKWAY/PAVEMENT

(TYPICAL-EXTERIOR OF BLDG.)

REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT

DIMENSIONED LOCATIONS FOR ALL WALL OUTLETS

POWER CO

METER & MAIN -

SEE RISER

DIAGRAM SHT E3

FOR HEAT TRACING

IN THE COOLER.

NOTE: REFER TO OFFICE ELEVATION

ON SHEETS A12 & A16.

SERVICE SIGN &

PUSH BUTTON

WP J-BOX & DISC SW

4 WIRE TO GREASE

CONTAINER

FOR HEAT TRACING

IN THE FREEZER.

120V / 1ph - To recp't

mounted under sink

120V / 1ph - To recp't

mounted under sink

CHECKED:

DATE:

PO

PE

YE

S

LK

1

26

0-D

L-P

LU

S P

RO

TO

TY

PE

E.I.F

.S

. / S

IM

UL

AT

ED

S

TO

NE

LO

UIS

IA

NA

K

IT

CH

EN

L

K-P

LU

S D

ES

IG

N S

TA

ND

AR

DS

60 S

EA

TS

/ D

UA

L-L

IN

E P

RO

DU

CT

IO

N

E2

1

ELECTRICAL POWER PLAN & DETAILS

1/4"=1'-0"

E2

2

TYP COMM. STUB UP DETAIL

NTS

E2

3

DRIVE-THRU LOOP DETECTOR

NTS

E2

4

DRIVE-THRU AUDIO / TIMERS

NTS

POWER PLAN

E2

04/17/15

KR

REVISIONS:

Current sensors are factory wired but must be

field adjusted for proper operation. With the hood exhaust

fans running, spin the potentiometer dials counterclockwise

until the status "OFF" green LED lights and cooking

equipment contactors de-energize. Then turn dials back

clockwise one full turn. If the current sensors are improperly

adjusted, cooking equipment may not shut off should a

hoods exhaust fan fail. If the cooking equipment fails to

operate while the hood switches are on and the exhaust

fans are running, spin the appropriate setpoint dial

clockwise until the status "ON" red LED lights.

DRW: S. BROADBEAR

REV 2.0

C 2012

PH: (727) 544-6679FX: (727) 544-6670

R

Y1

W1

COOLING

HEATING

24V POWER

R-3,4

R-5,6

R-1,2

RED

GRN

ROOFTOP UNIT

TERMINALS

S.E.C.

FIRE INTERLOCK

TERMINALS

LOW VOLTAGE A/C CONTROL

FIELD WIRING DETAIL

BURGER KING LOW VOLTAGE WIRING CONNECTIONS

DATE: 7 / 19 / 2012

R

G

R

CK1

CKGND

Y1

Y2

W1

W2

C

W2

C

HEATING ST. 2

COMMON

G FAN CONTROL

Y2 COOLING ST. 2

W2

G

Y1

W1

FAN CONTROL

COOLING

HEATING

HEATING ST. 2

CK

CK1 CK 1

CK GND

THERMOSTAT VENSTAR T-2700

R 24V POWER

MISC COOLING ST. 2

C 24V COMMON

UNIT

STAT

1

YEL

BLU

WHT

BLK

BRN

GND

RS+5

RS1

RS GND

RS+5

RS1

RS GND

REMOTE TEMP.

SENSOR ACC0400

(OPTIONAL)

REMOTE SENSOR

REMOTE SENSOR

REMOTE SENSOR

4 P

OL

E C

ON

TA

CT

OR

12

0V

C

OIL

3

0 A

MP

R

ES

.

ON W/PHOTOCELL IN AUTO,ON/OFF WITH O/R SWITCH,TIMED DELAY TO OFF WITHSECURITY DEPARTURESWITCH

C - 1

C - 2

C - 3

BUILDING/SIGN LTS.

LOT POLE LTS.

LOT POLE LTS.

C - 4

BUILDING/SIGN LTS.

C - 5

BUILDING/SIGN LTS.

ON/OFF W/ PHOTOCELL INAUTO,

ON/OFF WITH O/R SWITCH

C - 7

UNDER HOODFRYER

COOKING EQUIP.

C - 6

UNDER HOODBROILER

COOKING EQUIP.

ON/OFF WITH BROILEREXHAUST FAN SW.

(15MIN. DELAY TO OFF)(ON UPON

INTERRUPTION OF FIRESUPPRESSION LOOP )

MS-1

BROILER HOODEXAUST FAN-1

MS-2

FRYER HOODEXAUST FAN-2

ON/OFF WITH FRYEREXHAUST FAN SW.

(ON UPONINTERRUPTION OF FIRE

SUPPRESSION LOOP)

ON/OFF WITH BROILEREXHAUST FAN SW.

(OFF UPONINTERRUPTION OF FIRE

SUPPRESSION LOOP)

C - 8

REFRIGERATOR/FREEZER/GAS

VALVE

ALWAYS ON EXCEPTUPON INTERRUPTION

OF FIRE SUPPRESSIONLOOP

4 P

OL

E C

ON

TA

CT

OR

12

0V

C

OIL

3

0 A

MP

R

ES

.

4 P

OL

E C

ON

TA

CT

OR

12

0V

C

OIL

3

0 A

MP

R

ES

.

4 P

OL

E C

ON

TA

CT

OR

12

0V

C

OIL

3

0 A

MP

R

ES

.

4 P

OL

E C

ON

TA

CT

OR

12

0V

C

OIL

3

0 A

MP

R

ES

.

4 P

OL

E C

ON

TA

CT

OR

12

0V

C

OIL

3

0 A

MP

R

ES

.

4 P

OL

E C

ON

TA

CT

OR

12

0V

C

OIL

3

0 A

MP

R

ES

.

4 P

OL

E C

ON

TA

CT

OR

12

0V

C

OIL

3

0 A

MP

R

ES

.

4 P

OL

E C

ON

TA

CT

OR

12

0V

C

OIL

3

0 A

MP

R

ES

.

4 P

OL

E C

ON

TA

CT

OR

12

0V

C

OIL

3

0 A

MP

R

ES

.

CO

IL

A

2

N.C

.

N.O

.

R-7FIRE INT.

CO

IL

A

1

12

11

10

9

43

21

87

54

CO

IL

A

2

N.C

.

N.O

.

R-8EF-1

INTERLOCK

CO

IL

A

1

12

11

10

9

43

21

87

54

CIRCUIT - -

CIRCUIT - ___ - ___ LOT POLE LIGHTSCIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___

5678

34

21

CIRCUIT - -

CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___

9101112CIRCUIT - -

CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___

13141516CIRCUIT - -

CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___

17181920CIRCUIT - -

CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___

21222324CIRCUIT - -

CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___

25262728CIRCUIT - -

CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___

29303132CIRCUIT - -

CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___

33343536CIRCUIT - -

CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___

37383940CIRCUIT - -

CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___

LOT POLE LIGHTS

BLDG./SIGN LTS.

BLDG./SIGN LTS.

BLDG./SIGN LTS.

UNDER HOOD EQUIP.

FRYER

REFRIGERATORFREEZER

GAS VALVE

FRYER FAN EF-1FRYER FAN EF-1

FRYER FAN EF-2FRYER FAN EF-2

5678

34

21

910111213141516171819202122232425262728293031323334353637383940

AIROTRONICS

TH3P103HAS1

120V AC 1AMP

1 2 3

4

5

5678

34

21

910

NEUTRAL

BUILDING LIGHTS (AUTO)

FIRE INT. 120V LOOP

120VAC CONTROLLOT LIGHTS (AUTO)

LOT LIGHTS (ON)

BUILDING LIGHTS (ON)EX. FANS / COOK EQUIP.

A/C 120V INTERLOCK

L1NNEUTRAL

120VAC CONTROL POWER

P5P6

P3P4

P2P1 PHOTOCELL NEUTRAL

PHOTOCELL LINEPHOTOCELL LOADPHOTOCELL NEUTRALPHOTOCELL LINEPHOTOCELL LOAD

LOT LIGHTS PHOTOCELL

BLDG. LIGHTS PHOTOCELL

INCOMING CONTROL POWER

ROUTE TO TB 6 IN ON/OFF CONTROL PANEL

A1A2

FIRE INTERLOCK (COM.)FIRE INTERLOCK (N.C.)

ROUTE TO HOODS MICROSWITCHES

LOAD SIDE

GROUND

ON/OFF WITH FRYEREXHAUST FAN SW.

(OFF UPONINTERRUPTION OF FIRE

SUPPRESSION LOOP)

F1F2

NEUTRALOPT. ELECT FRY CONT.

ROUTE TO OPTIONAL ELECT. FRY PANEL

LINE SIDE

MOMENTARY

SWITCH FOR O/R

TDR#2

ORG

ORG

BLU

YEL

PUR

BRN ORG

RED

GRY

BLK

BLK

BLK

BLK GRY

PUR

BLU

TB-4

OPTIONAL ELECTRIC FRYER PANEL NEUTRAL

OPTIONAL ELECTRIC FRYER PANEL POWER

C 2012

PH: (727) 544-6679FX: (727) 544-6670

PANEL WIRING

FIELD WIRING

NO CONNECTION

CONNECTION

BRN

BRN

BRN

BRN

ORG

YEL

RED

BLK

WHT

WHT

WHT

WHT

WHT

WHT

WHT

WHT

WHT

WHT

WHT

WHT

BRN

ORG

YEL

RED

WHT

WHT

INTERMATIC

MOD# K4221C

UNOCCUPIED OCCUPIED AUTO OFF ON AUTO OFF ON

LOT LTS.BLDG LTS.KITCHEN A/C

SECURITY DEPARTURE SWITCH

BUILDING CONTROL

OFF ON

UNOCCUPIED OCCUPIED

DINING A/C

EXHAUST FANS

AIROTRONICS

TH3P103HAS1

120V AC 1AMP

TDR#1

TIME DELAY RELAY

1 2 3

7

6

15 P

IN

C

AB

LE

CONT

ROL

CIRC

UIT

BREA

KER

(2A)

KITCHEN A/C UNIT #____

(R) FROM A/C UNIT

G FAN CONTROL

Y-1 COOLING -1

Y-2 COOLING -2

W-1 HEATING -1

W-2 HEATING -2

C- 24V COMMON

(CK1) THERMOSTAT

RU

(R) TO THERMOSTATRT

G

Y1

Y2

W1

W2

C

CK1

(CKGND) THERMOSTAT

CK-

GND

KITCHEN A/C UNIT #____

DINING A/C UNIT #____

DINING A/C UNIT #____

DINING A/C UNIT #____

NEUT

RAL

BUIL

DING

LIG

HTS

(AUT

O)

FIRE

INT.

120V

LOO

P

5 6 7 83 421 9 10

GROU

ND

120V

AC C

ONTR

OLLO

T LI

GHTS

(AUT

O)LO

T LI

GHTS

(ON)

BUIL

DING

LIG

HTS

(ON)

EX. F

ANS

/ COO

K EQ

UIP.

A/C

120V

INTE

RLOC

K

RO

UT

E F

RO

M T

B#2 IN

M

AS

TE

R R

EL

AY

P

AN

EL

(R) FROM A/C UNIT

G FAN CONTROL

Y-1 COOLING -1

Y-2 COOLING -2

W-1 HEATING -1

W-2 HEATING -2

C- 24V COMMON

(CK1) THERMOSTAT

RU

(R) TO THERMOSTATRT

G

Y1

Y2

W1

W2

C

CK1

(CKGND) THERMOSTAT

CK-

GND

(R) FROM A/C UNIT

G FAN CONTROL

Y-1 COOLING -1

Y-2 COOLING -2

W-1 HEATING -1

W-2 HEATING -2

C- 24V COMMON

(CK1) THERMOSTAT

RU

(R) TO THERMOSTATRT

G

Y1

Y2

W1

W2

C

CK1

(CKGND) THERMOSTAT

CK-

GND

(R) FROM A/C UNIT

G FAN CONTROL

Y-1 COOLING -1

Y-2 COOLING -2

W-1 HEATING -1

W-2 HEATING -2

C- 24V COMMON

(CK1) THERMOSTAT

RU

(R) TO THERMOSTATRT

G

Y1

Y2

W1

W2

C

CK1

(CKGND) THERMOSTAT

CK-

GND

(R) FROM A/C UNIT

G FAN CONTROL

Y-1 COOLING -1

Y-2 COOLING -2

W-1 HEATING -1

W-2 HEATING -2

C- 24V COMMON

(CK1) THERMOSTAT

RU

(R) TO THERMOSTATRT

G

Y1

Y2

W1

W2

C

CK1

(CKGND) THERMOSTAT

CK-

GND

COIL A2

N.C.

N.O.

COIL A1

12 11 10 9

4 3 2 1

8 7 5 4

R-1

KITCHEN

SETBACK

COIL A2

N.C.

N.O.

COIL A1

12 11 10 9

4 3 2 1

8 7 5 4

COIL A2

N.C.

N.O.

COIL A1

12 11 10 9

4 3 2 1

8 7 5 4

COIL A2

N.C.

N.O.

COIL A1

12 11 10 9

4 3 2 1

8 7 5 4

COIL A2

N.C.

N.O.

COIL A1

12 11 10 9

4 3 2 1

8 7 5 4

COIL A2

N.C.

N.O.

COIL A1

12 11 10 9

4 3 2 1

8 7 5 4

R-2

DINING

SETBACK

R-3

KITCHEN

A/C FAN

R-4

DINING

A/C FAN

R-5

A/C

FIRE INT.

R-6

A/C

FIRE INT.

HVAC INTERLOCK PANELNFPA-96 COMPLIANT

N C A

CHECKED:

DATE:

PO

PE

YE

S

LK

1

26

0-D

L-P

LU

S P

RO

TO

TY

PE

E.I.F

.S

. / S

IM

UL

AT

ED

S

TO

NE

LO

UIS

IA

NA

K

IT

CH

EN

L

K-P

LU

S D

ES

IG

N S

TA

ND

AR

DS

60 S

EA

TS

/ D

UA

L-L

IN

E P

RO

DU

CT

IO

N

POWER PLAN

E2a

04/17/15

KR

REVISIONS:

1.

GENERAL NOTES:

GND

12

12

12

12

12

12

12

12

12

12

12

SERIES/INTEGRATED RATING

-

12

12

WIRE SIZE

SERIES/INTEGRATED RATING

225 AMP MAIN LUGS ONLY

1P-20

121212TOASTER (C20)

PROVIDE SCREW-ON BREAKER LOCK DEVICE.

PROVIDE SEPARATE GROUND CONDUCTOR IN ALL CONDUITS

TOTALS

NOTES:

(2)

(1)

SPARE

SPACE

FREEZER EVAP (E10)

FREEZER (A54)

HOLD CABT. (D90)

REFRIG. BATTER (A47.4)

SANDWICH (A53.27)

---

PRODUCT ASSEM. (C40)

SPARE

SPARE

SPACE

---

MICROWAVE (D20)

(2)

(2)

(2)

-

10

-

-

-

-

-

- -

-

-

-

10

41

37

39

1P-20

1P-20

1P-20

-

-

-

-

-

-

-

-

31

33

35

27

29

10

12

-

12

12

12

12

1P-20

10

-

10

12

-

12

-

12

1P-25

2P-20

23

25

1P-20

21

19

12

12

12

12

12 12

13

1P-20

1P-20

17

15

1P-20 11

9

12,60811,3329,348

504

-1180

-

1180

2000

1180

-

624

1180

624

376

300

900

- 600

1440

1500

684

100

1212

1P-15

20001180

-

1180

1000

2P-30

42

38

40

8

2P-30

1P-2O

2P-30

32

34

36

28

30

8

8

12 12

2110 100

1600

780

540

600

1P-20

1P-20

1P-20

1P-20

24

26

22

20

12

12

12

12

12

12

12

12

1P-20

1P-20

1P-20

1P-20

1P-20

14

18

16

12

10

12

12

12

12

12

12

12

12

12

12

121P-20360 12390

15

1P-20FRONT SIGN

PROVIDE SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN ALL CONDUITS

PROVIDE SCREW-ON BREAKER LOCK DEVICE.

LIGHTING BRANCH CIRCUIT BREAKERS SHALL BE LISTED FOR SWITCHING DUTY

120/208 VOLTS - 3 PHASE - 4 WIRE - SOLID NEUTRAL

MARINATOR (A31)

CARBONATORS (K42)

FRYER HOOD (EF-2)

LOAD DESCRIPTION

FRYER HOOD (EF-1)

FLUSH MOUNTED - EQUIPMENT GROUND BAR & ISOLATED EQUIPMENT GROUND BAR

CIRCUIT SCHEDULE

WIRE SIZE

PH

12

12

12

12

NOBKRGNDN

12

12

12

12

12

12

12

12

1P-20

1P-20

7

5

1P-20

1P-20

1

3

CKT CKT

VIDEO MONITORS

PYLON SIGN

PYLON SIGN

FLY FAN

SPARE

SPACE

SPACE

SODA DISP'S (K32F)

RECS-G.P.(FRONT CNTR)

POS SYSTEM

SPARE

SECURITY SYS

(2)

(1)

NOTES:

(2)SAFE (M30)

TOTALS

1P-20

1P-20

12

10

10

12

12

12

12

12

-

1212

-

12 12

-

12

12 12

12

1P-20

1P-20

1P-20

1P-20

1P-20

10

12

10

12

10

12 12

10

1P-20

1P-20

1P-20

1P-20

CONN. LOAD (VA)

1728

1320

100

600

PH A

1320 300

PH B

PANEL "A"

10,000 A.I.C.

600 1150

PH C

NPHNO BKR

1P-20

1P-15

1P-20

1P-20

8

6

2

4

12

12

12

12

12

12

12

12

CKT CKT

SQUARE D "NQOD"

11,040

1000

39

41

35

37

780

7,280

--

360

600

29

31

33

25

27

1125

1200

21

23

19

17

100

790

1200 1200

9,754

-

-

42

40

36

38

12

1P-20

1P-20

1P-2012

720

30

790

32

34

26

28

1420

720

600

22

24

500

20

18

-

1P-20

1P-20

1P-20

1P-20

1P-20

-

12

12

12

12

1P-20

1P-20

1P-20

1P-20

12

12

12

12

120/208 VOLTS - 3 PHASE - 4 WIRE - SOLID NEUTRAL

LIGHTING BRANCH CIRCUIT BREAKERS SHALL BE LISTED FOR SWITCHING DUTY

LOAD DESCRIPTION

CIRCUIT SCHEDULE

FLUSH MOUNTED - EQUIPMENT GROUND BAR & ISOLATED EQUIPMENT GROUND BAR

DIGITAL MENUBOARD (Q11)

SODA DISP'S (K31)

KITCHEN & R.R'S. LTG

DINING - PAD FANS

KITCHEN & SALES LTG

TEA BREWER (K74)

RTU RECS & DUCT DET'S

(2)

CKTWIRE SIZE

PH

12

12

12

12

12

12

12

12

1212

12

12

12

12

12

12

12

12

1P-20

1P-20

1P-20

1P-20

GND

12

12

12

12

12

N

12

1P-20

1P-20

BKR

1P-20

PH A

CKT

PH B

600

1380

11

13

7

9

360

360

3

5

NO

1 1384

600500

1000 700

CONN. LOAD (VA)

PANEL "B"

CKTCKTPH C WIRE SIZE

1920

12

500

14

16

8

10

1264 360

4

6

NO

2

12

12

12

12

1P-20

1P-20

1P-20

1P-20

12

12

12

12

PH

12

12

12

1P-20

1P-20

BKR

1P-20

12

12

12

N

SQUARE D "NQOD"

10,000 A.I.C.

225 AMP MAIN LUGS ONLY

PROVIDE SEPARATE GROUND CONDUCTOR IN ALL CONDUITS

PROVIDE BREAKER LOCK DEVICE FOR CIRC'S. #8 & 14.

MAIN BREAKER SHALL BE LISTED FOR AVAILABLE FAULT CURRENT

(ESTIMATED 42,000 A.I.C.) AND FEEDER BREAKERS SHALL BE SERIES LISTED

TO ALLOW USE OF 10,000 A.I.C. DOWNSTREAM BRANCH OR FEEDER BREAKERS

TO MAINTAIN AVAILABLE FAULT CURRENT RATING.

(2)

(1)

(3)

----

SPARE

----

---

---

---

---

PANEL "A"

---

---

---

PANEL "C"

PANEL "B"

SPACE

SPACE

---

SPACE

(2)

12COOLER EVAP. (E10)

HEAT TRACE FRZ (E10)

SITE LIGHTS

---

10

---

SITE LIGHTS

SITE LIGHTS

10

10

12 (2)

SERVICE DOORBELL

SECURITY CAMERA'S

RECEPTS-DINING RM

CLR/FRZR LIGHTS

RECEPTS-DINING RM

WATER HEATER12

12

12

12

IRRIG CONTROLS

REFRIGERATOR (B60)

ANSUL SYSTEM

12

12

12

12

12

(2)

(2)

(2)

(2)

27

NOTES:

TOTALS

41

37

39

3P-225

33

35

31

29

4/04/0

-

-

-

3P-225

3P-225

23

25

21

19

3P-50

--

-

-

-

-

13

17

15

11

9

5366

6740

68,088

- 624

31627

71,135

- 624

28360

10040

9348

5366

4445

- 624

11332

4445

-

2880

624

652

28

67,692

- 624

21231

9690

5366

42

38

40

34

36

32

30

12068

4445

-

2880

624

652

3P-60

3P-60

24

26

22

20

6

6

3P-3014

18

16

12

10

10

---

WALK-IN COOLER (2)

---

---

RTU-2

RTU-1

---

10

10

---

COMPRESSOR (E10)

---

C0MPRESSOR (E10)

10

WIRE SIZE

SERIES/INTEGRATED RATING

600 AMP MAIN LUGS ONLY

SQUARE D "I-LINE" TYPE HCN

DRV THRU DIR. SIGNS

CKT

120/208 VOLTS - 3 PHASE - 4 WIRE - SOLID NEUTRAL

----

LOAD DESCRIPTION

CONV. OVEN (B10)

----

CONV. OVEN (B10)

LOAD DESCRIPTION

GND

OFFICE CAB. FAN

RECEPTS

HOOD CONTROLS

12

12

12

12

EF-3

(2)

(2)

WIRE SIZE

PH

10

-

-

10

NOBKRN GND

3P-30

3P-30

1010

- -

10

-

10

-

7

5

1

3

CKT

FLUSH MOUNTED - EQUIPMENT GROUND BAR

CIRCUIT SCHEDULE

WALL ART LIGHTS

SPACE

POS SYSTEM/PRINTER

DRIVE THRU MENU BD

SPARE

EXT SOFFIT LIGHTS

EXT SOFFIT LIGHTS

EXT SOFFIT LIGHTS

DIGITAL M/B SYSTEM

DRIVE THRU AUDIO

LIGHTING CONTROLS

POS SYS. /PRINTER

(3)

(2)

CABINET = 26" W x 6-1/2" D

PANEL "DP"

CONN. LOAD (VA)

2880

2880

652

-

PH A

2880 4750

PH B

2880 4750

PH C

NBKR PHNO

3P-30

2P-60

8

6

2

4

10

6

CKT CKT

MINIMUM 42,000 A.I.C.

LOAD DESCRIPTION

RECEPTS-TEL EQ BD

RECEPTS - OFFICE

MUSIC SOUND/G.P.

COMPUTER/PRINTER

D/T WINDOW

DINING PENDANT LIGHTS

DINING LIGHTS

(2)

(2)

LOAD DESCRIPTION

WALK-IN FREEZER (2)

GND

SPACE

----

CHUB WARMER (D81)

10

10

10

10

178.2 KVA

@ 1.00 D.F. = 48.1 KVA

@ 0.65 D.F. = 92.5 KVA

@ 1.00 D.F. = 12.4 KVA

@ 1.25 D.F. = 25.3 KVA

KITCHEN EQUIP.

RECEPT & MISC.

TOTAL DEMAND LOAD

HVAC

LIGHTING/SIGNS

12390.0 VA

48028.0 VA

142310.0 VA

20270.0 VA

= 495.0 AMPS

TOTAL AMPS

TOTAL KVA205.0

569.0

KITCHEN EQUIP.

RECEPT & MISC.

TOTAL DEMAND LOAD

HVAC

LIGHTING/SIGNS

= 110.6 AMPS

@ 1.00 D.F. = 3.2 KVA

@ 0.65 D.F. = 13.3 KVA

@ 1.00 D.F. = 3.9 KVA

@ 1.25 D.F. = 9.2 KVA

3240.0 VA

20518.0 VA

3850.0 VA

7380.0 VA

29.6 KVA

TOTAL KVA

TOTAL AMPS

32.8

91.0

2P-30

-

-

8

8

8

TOTAL DEMAND LOAD

RECEPT & MISC.

KITCHEN EQUIP.

HVAC

LIGHTING/SIGNS

= 78.3 AMPS

@ 1.00 D.F. = 2.0 KVA2020.0 VA

28.2 KVA

@ 1.25 D.F. = 16.1 KVA

@ 1.00 D.F. = 8.5 KVA

@ 0.65 D.F. = 1.6 KVA2520.0 VA

8540.0 VA

12890.0 VA

TOTAL AMPS

TOTAL KVA

73.6

26.5

POS SYSTEM, COMPUTER, PRINTERS, MONITORS, CREDIT CARDS AND MODEM(3)

TO BE ON ISOLATED GROUND

(2)

(3)

1800

12 12 12

121212

12 12 12

4

4/0 4/04

4

4/04/0

(4)

(4)

(4)

(4)

PROVIDE HACR TYPE CIRCUIT BREAKER.(4)

(2)

(2)

960

(3)

12 12 12

(3)

- - -

12 12 12

DIGITAL PRE-SELL M/B

3P-60

6

---

RTU-3

---

10

(4)

4445

4445

4445

COOLER EVAP (E10)

12 12 12(2)

3P-3010

WALK-IN COOLER (2)

---

C0MPRESSOR (E10)

1010

(3) 540

WIRE SIZE

SERIES/INTEGRATED RATING

225 AMP MAIN LUGS ONLY

1P-20

16120015

PROVIDE SEPARATE GROUND CONDUCTOR IN ALL CONDUITS

PROVIDE BREAKER WITH SHUNT TRIP INTERLOCKED WIRED

PROVIDE BREAKER WITH GROUND-FAULT CIRCUIT INTERRUPTER.

(3)

UC REFRIG (J40)

SPARE

----

MICROWAVE (D20)

HOLDING BIN (D92)

---

HAND DRYER

SHUNT TRIP SPACE

FRYER/TIMERS (A10.U3)

HOT WTR DISP (D70)

(2)

(1)

(2)

NOTES:

12

10

TOTALS

2P-20

2P-30

12

10

41

39

35

35

12

12

12

1P-20

1P-20

1P-25

1212

1212

29

31

33

25

27

2P-30

2P-20

12

21

23

17

19

25032

2000

21557

437

1238

-

1920

2000

12502850

2040

-

1250

1238

2000

1238

24889

437

2000

1920

1250

42

40

36

38

588 2000

2000

1250

1238

2850

26

2P-20

2P-3030

32

34

28

10

2P-40

2P-20

22

24

18

20

CKT

LIGHTING BRANCH CIRCUIT BREAKERS SHALL BE LISTED FOR SWITCHING DUTY

120/208 VOLTS - 3 PHASE - 4 WIRE - SOLID NEUTRAL

LOAD DESCRIPTION

(H10.4PD)

HEAT LAMPS

---

HOLDING UNIT (F15.1)

PRODUCTION COUNTER

CKTWIRE SIZE

PH

2P-30

13

11

7

9

BKR

2P-30

2P-20

GNDN

1

5

3

NO

FLUSH MOUNTED - EQUIPMENT GROUND BAR

CIRCUIT SCHEDULE

PH BPH A

2578

540

3000

14564250

2578

1456

CONN. LOAD (VA)

PANEL "C"

CKTCKT

PH C

2578

2578 3000

1P-20

1P-20

1P-20

14

12

10

8

2P-40

2P-502

6

4

NO BKR PH N

10,000 A.I.C.

SQUARE D "NQOD"

(3)

HEAT TRACE BOSS (A92)

---

HAND DRYER

SPACE

SPACE

HOT WTR DISP (D70)

ICE CUBER W/REM. (K10)

---

HOLDING BIN (D92)

10

HOLDING CABINET (D94)

---

LOAD DESCRIPTION

LIGHTING (H10.4PD)

BISCUIT HOLD (B65)

GREASE COL SYS (A92)

IMMERS. HEATER (H10.4PD)

GND

= 146.6 AMPS

@ 1.00 D.F. = 0.0 KVA

@ 0.65 D.F. = 52.8 KVA

@ 1.00 D.F. = 0.0 KVA

@ 1.25 D.F. = 0.0 KVA

TOTAL KVA

TOTAL AMPS

0.0 VA

81218.0 VA

0.0 VA

0.0 VA

52.8 KVA

81.2

198.4

KITCHEN EQUIP.

RECEPT & MISC.

TOTAL DEMAND LOAD

HVAC

LIGHTING/SIGNS

TO HOOD FIRE PROTECTION SYSTEM.

10 10

2P-30

10 10

10 10

10

10 10

---

4250

1200

1950

1950

8 8

12 12 12

12 12 12

12 12

12 12

---

---

ICE CUBER W/REM. (K10)

12 12 12

12 12

10 10

---

1920

----

HOLDING BIN (D93)8 8

2P-20 12 12

1P-20 12 12 12

8 8

(H10.4PD)

HEAT LAMPS

(H10.4PD)

HEAT LAMPS

(H10.4PD)

SECTION 250-50 (N.E.C.)

ROD. GROUNDING TO CONFORM TO

DIA. x 10'-0" LENGTH GROUNDING

RUN #2/0 CONDUCTOR TO 5/8 "

ENCL.

IDENTIFICATION

IN 2 1/2" CONDUIT

PANEL

LC3

H-O-A SELECTOR

NEAR OFFICE AREA.

SWITCHES - CONTROLS

LOCATED AT SW STATION

FOR LTG CONTACTORS

LC2

LC1

4 - #4/0, THWN, CU

IN 2 1/2" CONDUIT

# 4 CU GND

PANEL

"C"

"A"

PANEL

"B"

IN (2) 3 1/2" CONDUITS.

(2) RUNS EACH:

# 1/0 CU GND

4 - #350 KCMIL, THWN, CU

"DP"

600A M.C.B

I-LINE

PANEL

FOUNDATION

METAL WATER PIPE

WHERE AVAILBLE

STEEL REBARS IN

PLAQUE

AVAILABLE

FAULT CURRENT

LISTED FOR

CT

WP

# 4 CU GND

4 - #4/0, THWN, CU

REMOTE ROOF MOUNTED

DIAGRAM SHT. E1.

PHOTO-ELEC-CONTROL

FOR (2) SEE WIRING

SWITCH (TYP.)

LTG. CIRCUITS

PARK'G LOT

TO EXTERIOR

LTG. CIRCUITS

TO EXTERIOR

LC3

LC2

LC1

PE

SIGN CIRCUITS

TO EXTERIOR

ENGRAVED SIGN

"MAIN DISCONNECT"

TERMINATE ON POLE

ROUTE TWO RUNS : (4) 350 KCMIL, THWN, CU,

TO POWER CO SERVICE POINT AND TERMINATE

REFER TO CIVIL SITE DWGS FOR LOCATION .

AT SERVICE LOC. PER POWER CO REQMT'S.

PROVIDE & INSTALL

CT CABINET AND

POWER CO REQUIREMENTS

IN (2) 3 1/2" CONDUITS VIA CT CABINET

METER IN ACCORD WITH

METER

OR WHERE REQUIRED

REQUIREMENTS.

PER POWER CO

WEATHER HEADS

POLE - SEE SITE

POWER CO SERVICE

SERVICE

(TYPICAL)

CIVIL PLAN FOR

LOCATION

= 451.1 AMPS

ELECTRICAL SERVICE CONNECTED LOAD

KITCHEN EQUIP. KVA

RECEPT & MISC. KVA

HVAC KVA

TOTAL KVA

LIGHTING/SIGNS

@ 0.65 D.F. = 92.5 KVA

@ 1.00 D.F. = 12.4 KVA

@ 1.25 D.F. = 25.3 KVA

32153.0 VA

142310.0 VA

205000.0 VA

12390.0 VA

20270.0 VA

162.4 KVA

@ 1.00 D.F. = 32.2 KVA

SPACE

- - - -

(2)

12 12 12

12 12 12

(3)

CHECKED:

DATE:

PO

PE

YE

S

LK

1

26

0-D

L-P

LU

S P

RO

TO

TY

PE

E.I.F

.S

. / S

IM

UL

AT

ED

S

TO

NE

LO

UIS

IA

NA

K

IT

CH

EN

L

K-P

LU

S D

ES

IG

N S

TA

ND

AR

DS

60 S

EA

TS

/ D

UA

L-L

IN

E P

RO

DU

CT

IO

N

E3

1

ELECTRICAL POWER RISER DIAGRAM

1/4"=1'-0"

ELECTRICAL PANEL

SCHEDULES and

RISER DIAGRAMS

E3

04/17/15

KR

REVISIONS:

LEGEND

BRACKET COVER

BY P.O.S. VENDOR

A.F.F.

EL. 9'-4"

S.S. STEEL

BRACKET

MONITOR

MONITOR

ASSEMBLY

2.

1.

6'-8

"

(NOT SHOWN)

CONCEAL

SLEEVE TO

POWER CORDS

CHANNELS &

WHT. PLASTIC

ATTACH

BOLTS

W/ (2) 1/4"

BRACKET

MONITOR

CHANNEL

OUTER STEEL

CEILING TILE

PLATE

FLASHING

INNER STEEL

CHANNEL

(2) 1/2"

U-BOLTS

OR JOISTS TOG.C.

TO ROOF TRUSSES

"U" HANGERS

@ EA. END TO

RAFTER PLATE

W/ SIMPSON

DBL. 2X4

BLOCKING

NOTES:

MONITOR BRACKETS TO BE SUPPLIED AND

INSTALLED BY P.O.S. VENDOR.

G.C. TO SUPPLY 2x4 BLOCKING AND

TO SECURE BLOCKING AT LOCATION

PER P.O.S. VENDOR DIRECTION. VERIFY

W/ P.O.S. VENDOR BEFORE INSTALLATION

REGISTER CONNECTIONS

1. CABLES SHALL BE COAX.

2. BUMP BARS SHALL BE MOUNTED TO DELIVERY SYSTEM AT

AREAS MARKED "BB".

3. BUMP BAR CABLES SHALL BE RUN THROUGH DELIVERY

SYSTEM FROM MOUNT UP THROUGH WALLS TO ABOVE THE

CEILING AND BACK TO THE MANAGER STATION.

4. CRT MONITORS SHALL BE MOUNTED ON CEILING BRACKETS

PROVIDED BY REGISTER SYSTEM.

5. WHERE CABLING IS INSTALLED IN WALLS, IT SHALL BE

ROUTED IN A 1" CONDUIT THROUGH WALL TO ABOVE

ACCESSIBLE CEILING.

BUMP BAR WIRING

VIDEO MONITOR AND POS

WIRING

SECURITY WIRING

BB - BUMP BARS

V1 = VIDEO 1

V2 = VIDEO 2

V3 = VIDEO 3

POS- POINT OF SALE

TERMINAL

CRT

FREEZER

WALK-IN

MENWOMEN

ELECTRICAL PANELS

COOLER

WALK-IN

REFERENCE ONLY

COORDINATE WITH

P.O.S. SUPPLIER

CONNECTION

2 POS COUNTER

- SINGLE ORDER

1 COUNTER #1

2 COUNTER #2

3 ORDER TAKER #1

4 DT CASHIER

COORDINATE CAT 6

3 POS COUNTER

- SINGLE ORDER

1 COUNTER #1

2 COUNTER #2

3 COUNTER #3

4 ORDER TAKER #1

5 DT CASHIER

2 POS COUNTER

- DUAL ORDER

1 COUNTER #1

2 COUNTER #2

3 ORDER TAKER #1

4 ORDER TAKER #2

5 DT CASHIER

3 POS COUNTER

- DUAL ORDER

1 COUNTER #1

2 COUNTER #2

3 COUNTER #3

4 ORDER TAKER #1

5 ORDER TAKER #2

6 DT CASHIER

VERIFY ACTUAL CONFIGURATION WITH SITE PLAN

V4 = VIDEO 4

V5 = VIDEO 5

CHECKED:

DATE:

PO

PE

YE

S

LK

1

26

0-D

L-P

LU

S P

RO

TO

TY

PE

E.I.F

.S

. / S

IM

UL

AT

ED

S

TO

NE

LO

UIS

IA

NA

K

IT

CH

EN

L

K-P

LU

S D

ES

IG

N S

TA

ND

AR

DS

60 S

EA

TS

/ D

UA

L-L

IN

E P

RO

DU

CT

IO

N

E4

1

E4

2

P.O.S. WIRING

DIAGRAMS

E4

04/17/15

KR

REVISIONS:

HOLD UP BUTTON

6 + 1

STROBE LIGHT

Dome

IEI KEYPAD

14" Monitor

EXTERIOR DOME CAMERA

GLASS BREAK

DOOR CONTACT

CONTROL PANEL

HORN/SOUNDER

MOTION DETECTOR

(Ceiling Mount)

KEY PAD

DEVICE

2

1

1

1

5

1

DIGITAL VIDEO RECORDER

SYMBOL LEGEND

SYMBOL QTY.SYMBOLDEVICE

1

1

5 + 1

1

1

10

QTY.

PIEZO 1

POPEYES INSTALLATION NOTES

NOTE: PROGRAMMING SEQUENCE SET-UP AT THE NCCC

FOR LOCATIONS WITH OUTDOOR CAMERAS

OUTDOOR POLE MOUNT 15' ABOVE FINISHED PAVEMENT

GROUND ISOLATION TRANSFORMERS

SECURITY CO. TO RUN FLEX CONDUIT INSIDE LIGHT POLES- EC TO RUN CONDUIT

FFROM RESTAURANT TO BASE OF LIGHT POLE & MOUNT JUNCTION BOX 15' ABOVE

FINISHED PAVEMENT ON POLE VIEW DRIVE-UP AND SIDE DOOR

A -1: VIEW MAIN ENTRANCE AND SIDE OF BUILDING

A-2 : VIEW SIDE DOOR AREA OPPOSITE SIDE OF BUILDING FROM DRIVE-THRU

A-3 : VIEW BACK DOOR, DRIVE-THRU MENUBOARD & REAR AREA

A-4 : VIEW SECOND DRIVE-THRU MENUBOARD W/ DUAL ORDER DESIGN

INDOOR CAMERAS

INDOOR CEILING MOUNT IN TINTED DOME

FASTEN SCREW IN CEILING FOR DOMES SO NOT EASILY DROPPED OUT OF TILE

B-1 : VIEW DINING, SALES COUNTER & BEVERAGE COUNTER

B-2 : VIEW DINING, FRONT DOORS, RESTROOM AREA & SALES COUNTER

B-3 : VIEW DINING AREA

B-4 : VIEW SALES COUNTER & SAFE AREA

B-5 : VIEW DRIVE-THRU REGISTER & WINDOW AREA

B-6 : VIEW MANAGER DESK & PREP AREA

B-7 : VIEW FRYERS & PREP AREA

B-8 : VIEW COOLER/FREEZER DOORS

B-9 : VIEW BACK DOOR AND MOP SINK AREA

B-10 : VIEW DRY STORAGE & SINK AREAE

OFFICE AREA

BAC- BURGLAR ALARM CONTROL-VISTA 20SEUL

D-VCR

E-VCR :

F-MONITOR :

QUICK REFERENCE SHEETS

ALARM INSTRUCTION SHEET TO BE MOUNTED ON WALL IN EMPLOYEE ONLY AREA

CLOSEST TO KEYPAD OR IN OFFICE AREA PER CUSTOMER INSTRUCTION

FOR LOCATIONS WITH 6 OR MORE CAMERAS: ADD MULTIPLEXER

LTC 2641/60-PLACE ON SECURITY LOCK FOR NO TAMPER

FOR LOCATIONS WITH 4 CAMERAS OR LESS:

ADD VIDQUAD 4 CHANNEL LTC 2272/60

HUB: HOLD UP BUTTON 441494 SERIES LATCHING HUB

MANAGER AREA-36" AFF OUT OF SITE FROM FRONT COUNTER

DRIVE-THRU WINDOW-18" AFF & OUT OF SITE FROM OUTSIDE

FRYER/PREP AREA

SL: STROBE LIGHT - AS SL-401B-BLUE STROBE MOUNT BEHIND MENU BOARD, IT WILL

FLASH CONTINUOUSLY WHILE BACK DOOR IS OPEN

S: SOUNDER-AS-PAL328N-LOW TONE SOUNDER MOUNT WITH STROBE BEHIND MENU

BOARD, IT WILL SOUND WHEN BACK DOOR IS OPENED, MANAGER WILL SILENCE ST

SOUNDER AT KEYPAD AFTER 1 TONE

MD: MOTION DETECTOR-AP 669 PIR-360 MOTION MOUNT IN STOVE AREA TO GET

AREA FROM DRIVE-UP WINDOW AND GENERAL REAR AREA

LOBBY/PERIMETER AREA/BACK OF HOUSE

KP: KEY PAD-MOUNT 40" AFF WALL ENTERING KITCHEN AREA

FROM LOBBY

GB: FG 1025 GLASS BREAK-LOBBY GLASS ONE EACH SIDE OF

BUILDING SEE DRAWING FOR DEVICE PLACEMENT

C: B4039 CONTACT-ALL EXTERIOR DOORS

BACK DOOR CONTACT TO ACT AS ALARM POINT FOR BACK

DOOR ALARM-24 HOUR LOCATION POINT-SOUNDER & BLUE

STROBE TO ACTIVATE WHEN BACK DOOR IS OPEN

HUB: 3050CT SERIES LATCHING HUB IN

COOLER/FREEZER-MOUNT 18" AFF ON HINGE SIDE OF DOOR,

STUB UP CONDUIT TO PROTECT WIRING FROM

CONDENSATION/DAMAGE NO DRIP LOOP AT HUB

POC : POINT OF CONNECTION TO NKL SAFE-PIGTAIL PROVIDED

BY NKL SAFE

POPEYES ADD ON MODIFICATION NAMES AND

PHONE NUMBERS

1. INSTALLER PLEASE CONTACT YOUR ADT NCCC PROJECT

COORDINATOR FOR ANY ADD-ONS OR MODIFICATIONS TO

YOUR JOB. THEY WILL CONTACT THE NATIONAL

ACCOUNT MANAGER FOR APPROVALS/PAPERWORK.

2. CONTACT THE NATIONAL ACCOUNT MANAGER.

POPEYES PROBLEM RESOLUTION NAMES & PHONE NUMBERS

ACKERMAN / LOCKNET:

NCCC PROJECT COORDINATOR:

NAME:

PHONE NUMBER:

NATIONAL ACCOUNT MANAGER:

AFC/POPEYES:

NEW INSTALLS/NEW CONSTRUCTION MANAGER

EXISTING SITES/RENOVATION PROJECTS/FACILITIES MANAGER

LOSS PREVENTION DIRECTOR:

POPEYES INSTALLATION ACCEPTANCE FORM/CHECKLIST

FOR INSTALL SITE MODIFICATIONS IE/DEVICE PLACEMENT CHANGES FROM

BLUEPRINT, HAVE CUSTOMER INITIAL MODIFY PER SITE OPTION TO SHOW

APPROVAL

CAMERAS

A-CAMERA : FOR LOCATIONS WITH OUTDOOR CAMERAS

OUTDOOR POLE MOUNT 15' ABOVE FINISHED PAVEMENT

YES_____________ N/A______________ MODIFY PER SITE__________

GROUND ISOLATION TRANSFORMERS

YES_____________ N/A______________ MODIFY PER SITE__________

ADT TO RUN CONDUIT INSIDE LIGHT POLES-EC TO RUN CONDUIT FROM

RESTAURANT TO BASE OF LIGHT POLE & MOUNT JUNCTION BOX 15' ABOVE

FINISHED PAVEMENT ON POLE

YES_____________ N/A______________ MODIFY PER SITE__________

A-1; VIEW DRIVE-UP AND SIDE DOOR

YES_____________ N/A______________ MODIFY PER SITE__________

A-2: VIEW BACK DOOR, MENU BOARD & REAR AREA

YES_____________ N/A______________ MODIFY PER SITE__________

A-3: VIEW SIDE DOOR AREA OPPOSITE SIDE OF BUILDING FROM DRIVE-THRU

YES_____________ N/A______________ MODIFY PER SITE__________

B-CAMERA: FOR LOCATIONS WITH INDOOR CAMERAS INDOOR CEILING MOUNT IN

TINTED DOME

YES_____________ N/A______________ MODIFY PER SITE__________

FASTEN SCREW IN CEILING FOR DOMES SO NOT EASILY DROPPED OUT OF TILE

YES_____________ N/A______________ MODIFY PER SITE__________

B-1: VIEW FRONT DOORS, RESTROOM AREA & SALES COUNTER

YES_____________ N/A______________ MODIFY PER SITE__________

B-2: VIEW DRIVE-THRU REGISTER & WINDOW AREA

YES_____________ N/A______________ MODIFY PER SITE__________

B-3: VIEW SALES COUNTER & SAFE AREA

YES_____________ N/A______________ MODIFY PER SITE__________

B-4: VIEW BACK DOOR & COOLER/FREEZER AREA

YES_____________ N/A______________ MODIFY PER SITE__________

B-5: 360 VIEW

YES_____________ N/A______________ MODIFY PER SITE__________

OFFICE AREA

D-VCR LOCK BOX: TC3922 SERIES

YES_____________ N/A______________ MODIFY PER SITE__________

E-VCR: LTC 3924 SERIES PLACE ON SECURITY LOCK FOR NO TAMPER

YES_____________ N/A______________ MODIFY PER SITE__________

QUICK REFERENCE SHEETS

ALARM INSTRUCTION SHEET TO BE MOUNTED ON WALL IN EMPLOYEE ONLY

AREA CLOSEST TO KEYPAD OR IN OFFICE AREA PER CUSTOMER INSTRUCTION

YES_____________ N/A______________ MODIFY PER SITE__________

VCR INSTRUCTION SHEET( 2) 1-REVIEW & 1-RECORD-TO BE MOUNTED ON WALL

CLOSEST TO VCR

YES_____________ N/A______________ MODIFY PER SITE__________

FOR LOCATIONS WITH 6 OR MORE CAMERAS: ADD MULTIPLEXER

LTC 2641/60-PLACE ON SECURITY LOCK FOR NO TAMPER

YES_____________ N/A______________ MODIFY PER SITE__________

FOR LOCATIONS WITH 4 CAMERAS OR LESS:

ADD VIDQUAD 4 CHANNEL LTC 2272/60

YES_____________ N/A______________ MODIFY PER SITE__________

HUB: HOLD UP BUTTON 441494 SERIES LATCHING HUB

MANAGER AREA-36" AFF OUT OF SITE FROM FRONT COUNTER

YES_____________ N/A______________ MODIFY PER SITE__________

DRIVE-THRU WINDOW-18" AFF & OUT OF SITE FROM OUTSIDE

YES_____________ N/A______________ MODIFY PER SITE__________

LOBBY/PERIMETER AREA/BACK OF HOUSE

KP: KEYPAD-MOUNT 40" AFF WALL ENTERING KITCHEN AREA FROM LOBBY

YES_____________ N/A______________ MODIFY PER SITE__________

GB: FG 1025 GLASS BREAK- LOBBY GLASS ONE EACH SIDE OF BUILDING SEE

DRAWING FOR DEVICE PLACEMENT

YES_____________ N/A______________ MODIFY PER SITE__________

C: B4039 CONTACT-ALL EXTERIOR DOORS

YES_____________ N/A______________ MODIFY PER SITE__________

BACK DOOR CONTACT TO ACT AS ALARM POINT FOR BACK DOOR ALARM-24

HOUR LOCATION POINT-SOUNDER & BLUE STROBE TO ACTIVATE WHEN BACK

DOOR IS OPEN

YES_____________ N/A______________ MODIFY PER SITE__________

YES_____________ N/A______________ MODIFY PER SITE__________

POC: POINT OF CONNECTION TO NKL SAFE-PIGTAIL PROVIDED BY NKL SAFE

YES_____________ N/A______________ MODIFY PER SITE__________

FRYER/PREP AREA

SL: STROBE LIGHT-AS SL-401B-BLUE STROBE MOUNT BEHIND MENU BOARD,

IT WILL FLASH CONTINUOUSLY WHILE BACK DOOR IS OPEN

YES_____________ N/A______________ MODIFY PER SITE__________

S: SOUNDER-AS-PAL328N-LOW TONE SOUNDER MOUNT WITH STROBE BEHIND

MENU BOARD, IT WILL SOUND WHEN BACK DOOR IS OPENED, MANAGER WILL

TONE SILENCE SOUNDER AT KEYPAD AFTER 1

YES_____________ N/A______________ MODIFY PER SITE__________

MD: MOTION DETECTOR-AP 669 PIR - 360 MOTION MOUNT IN STOVE AREA TO

GET ARE FROM DRIVE-UP WINDOW AND GENERAL REAR AREA

YES_____________ N/A______________ MODIFY PER SITE__________

POPEYES MATERIAL LIST

CAMERAS

A-CAMERA:

5 OR 6 LOCATIONS ( LOCATIONS W/OUTDOOR CAMERAS )

2 OR 3 GIT100-GROUND ISOLATION TRANSFORMERS

LTC 0430/20-38 SERIES CAMERA W/ 3.5-8MM VARIFOCAL AUTOIRIS LENS

TC 9340A SERIES OUTDOOR HOUSING

TC9211PM POLE MOUNT ADAPTER

BNC CONNECTORS FOR PLENUM CABLE

FLEX CONDUIT FOR OUTDOOR CAMERAS RUN INSIDE POLE FOR CABLING

INDOOR CEILING MOUNT IN TINTED DOME

NOTE: FASTEN SCREW IN CEILING FOR DOMES SO NOT EASILY DROPPED

OUT OF TILE LTC 0430/20-38 SERIES CAMERA W/ 3.5MM-8MM VARIFOCAL

AUTOIRIS LENS

TC 9345MT7 INDOOR TINTED DOME

BNC CONNECTORS FOR PLENUM CABLE

OFFICE AREA

BAC-BURGLAR ALARM CONTROL: VISTA 20SEUL

D-VCR LOCK BOX : TC3922 SERIES

E-VCR: LTC 3924 SERIES PLACE ON SECURITY LOCK FOR NO TAMPER

F-MONITOR: LTC 2813/60 SERIES

ALTV248: 8 POSITION POWER SUPPLY

QUICK REFERENCE SHEETS

ALARM INSTRUCTION SHEET TO BE MOUNTED ON WALL IN EMPLOYEE ONLY

AREA CLOSEST TO KEYPAD OR IN OFFICE AREA PER CUSTOMER

INSTRUCTION

VCR INSTRUCTION SHEETS (2) 1-REVIEW & 1-RECORD-TO BE MOUNTED ON

WALL CLOSEST TO VCR

FOR LOCATIONS WITH 6 OR MORE CAMERAS : ADD MULTIPLEXER LTC

2641/60-PLACE ON SECURITY LOCK FOR NO TAMPER

FOR LOCATIONS WITH 4 CAMERAS OR LESS : ADD VIDQUAD 4 CHANNEL LTC

2272/60

2-HUB: HOLD UP BUTTON 441494 SERIES LATCHING HUB

STOVE/PREP AREA

SL: STROBE LIGHT-AS SL-401B-BLUE STROBE MOUNT BEHIND MENU BOARD,

IT WILL FLASH CONTINUOUSLY WHILE BACK DOOR IS OPEN

S: SOUNDER-AS-PAL328N-LOW TONE SOUNDER MOUNT WITH STROBE

BEHIND MENU BOARD, IT WILL SOUND WHEN BACK DOOR IS OPENED,

MANAGER WILL SILENCE ST SOUNDER AT KEYPAD AFTER 1ST TONE

MD; MOTION DETECTOR-AP 669 PIR-360 MOTION MOUNT IN STOVE AREA TO

GET AREA FROM DRIVE-UP WINDOW AND GENERAL REAR AREA

LOBBY/PERIMETER AREA/BACK OF HOUSE

KP: KEYPAD-MOUNT 40" AFF WALL ENTERING KITCHEN AREA FROM LOBBY

2-GB: FG 1025 GLASS BREAK-LOBBY GLASS ONE EACH SIDE OF BUILDING

SEE DRAWING FOR DEVICE PLACEMENT

3 OR 4-C: B4039 CONTACT-ALL EXTERIOR DOORS BACK DOOR CONTACT TO

ACT AS ALARM POINT FOR BACK DOOR ALARM-24 HOUR LOCAL

POINT-SOUNDER & BLUE STROBE TO ACTIVATE WHEN BACK DOOR IS OPEN

1 OR 2-HUB: 3050CT SERIES LATCHING HUB IN COOLER/FREEZER-MOUNT 18"

AFF ON HINGE SIDE OF DOOR SUB UP IN CONDUIT

1-POC: POINT OF CONNECTION TO NKL SAFE-PIGTAIL PROVIDED BY NKL

SAFE

RELAYS FOR BACK DOOR/POC/ZONE EXPANSION

TELCO JACK

WATTS LINE

ELECTRICAL REQUIREMENTS

ELECTRICAL SUPPLY ALL 120 VAC FOR CAMERA SYSTEM AND BURGLAR

ALARM SYSTEM

SUPPLY 120 VAC FOR ALL CCTV HEAD END EQUIPMENT.

SUPPLY 120 VAC FOR BURGLAR ALARM PANEL.

FOR OUTDOOR CAMERAS ALL TRENCHING, CONDUIT AND PULL STRINGS,

AS WELL

AS A BACK BOX MOUNTED ON THE POLE FOR ELECTRICAL AND COAX

CONNECTIONS.

SECURITY CO. SUPPLY AND INSTALL ALL SECURITY EQUIPMENT RUN ALL

LOW VOLTAGE CABLE FOR THE SECURITY SYSTEM. SET UP, TEST AND

TRAIN ON CCTV AND BURGLAR ALARM SYSTEMS. SPECIFY ALL

LOCATIONS OF DEVICES.

FREEZER

WALK-IN

MENWOMEN

ELECTRICAL PANELS

COOLER

WALK-IN

REFERENCE ONLY

VERIFY LOW VOLTAGE

PERMIT REQUIREMENTS

(Additional camera for dual drive-thru order design)

(Additional button for 2nd drive-thru window design)

2'-9

"

2'-6"

5"

M-11 S/S MANAGER'S

DESK

HOLD-UP BUTTON

CHECKED:

DATE:

PO

PE

YE

S

LK

1

26

0-D

L-P

LU

S P

RO

TO

TY

PE

E.I.F

.S

. / S

IM

UL

AT

ED

S

TO

NE

LO

UIS

IA

NA

K

IT

CH

EN

L

K-P

LU

S D

ES

IG

N S

TA

ND

AR

DS

60 S

EA

TS

/ D

UA

L-L

IN

E P

RO

DU

CT

IO

N

E5

1

SECURITY SYSTEM

PLAN and

SPECIFICATIONS

E5

04/17/15

KR

REVISIONS: